Protection & Control Terminals REF 54_, REM 54_, RET 54_, REC 523

Configuration Guideline

1MRS750745-MUM
Issued: Version: 20.10.1998 M/27.10.2006

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Contents
1. About this manual .....................................................................9
1.1. 1.2. 1.3. 1.4. 1.5. 1.6. 1.7. General .........................................................................................9 Use of symbols ..............................................................................9 Document conventions ................................................................10 Abbreviations ..............................................................................10 Terminology ................................................................................11 Related documents .....................................................................11 Document revisions .....................................................................12

2. Safety information ...................................................................13 3. Relay Configuration Tool .......................................................15 4. Specification for relay configuration .....................................17 5. Editing the relay configurations ............................................19
5.1. Getting started .............................................................................19 5.1.1. Libraries ...........................................................................19 5.1.2. Program organisation unit ................................................21 5.1.3. Logical POUs ...................................................................23 5.1.4. Physical hardware ............................................................25 5.1.4.1. Configuration ......................................................26 5.1.4.2. Resource for REF 54_, REM 54_ and REC 523 ......................................................27 5.1.4.3. Resource for REF 54_ Release 2.5 or later, REC 523 revision F and RET 54_ ......................37 5.1.4.4. Tasks ..................................................................47 5.2. Declaring variables ......................................................................49 5.2.1. Global variables ...............................................................52 5.2.2. Local variables .................................................................52 5.3. Compiling project ........................................................................57 5.4. Add-on protocol ...........................................................................57 5.5. Downloading the configuration ....................................................57 5.5.1. REF 54_ Release 2.5, RET 54_ and REC 523 revision F additions ..........................................59

6. Main configuration rules ........................................................63


6.1. 6.2. 6.3. 6.4. General .......................................................................................63 Digital inputs and outputs ............................................................63 Explicit feedback path .................................................................64 Analog inputs ..............................................................................65

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

6.5. 6.6. 6.7. 6.8.

Error outputs of application function blocks ................................ 66 Warnings ..................................................................................... 67 Execution order ........................................................................... 67 F-key ........................................................................................... 68

7. Engineering tips ..................................................................... 71


7.1. Horizontal communication .......................................................... 71 7.1.1. Guideline for using LON NV-variables in PLC logic ......... 71 7.1.1.1. COMM_IN .......................................................... 71 7.1.1.2. COMM_OUT ...................................................... 72 7.1.1.3. Cyclic sending generation .................................. 73 7.1.1.4. Cyclic communication check .............................. 74 7.1.1.5. Blocking ............................................................. 74 7.1.1.6. Control of objects ............................................... 75 7.1.1.7. Bypass mode ..................................................... 76 7.2. Events from the measurement function blocks ........................... 76

8. APPENDIX A: Relay configuration procedure ..................... 77 9. APPENDIX B: Specification for REF 54_ feeder terminal configuration ........................................................... 79
9.1. General data ............................................................................... 79 9.2. Electrotechnical data .................................................................. 80 9.2.1. Analog inputs ................................................................... 80 9.2.2. System frequency ............................................................ 81 9.2.3. Digital inputs .................................................................... 81 9.2.4. Digital outputs .................................................................. 84 9.2.5. RTD module .................................................................... 88 9.2.5.1. RTD/analog inputs ............................................. 88 9.2.5.2. RTD outputs ....................................................... 89 9.3. Functionality ................................................................................ 89 9.3.1. Order number .................................................................. 89 9.3.2. Application function blocks used ..................................... 90 9.3.3. Communication ................................................................ 91 9.4. Relay MIMIC configuration ......................................................... 93 9.4.1. Illustration of the system, MIMIC diagram ....................... 93 9.4.2. Alarm LEDs ..................................................................... 94 9.5. Functionality logic ....................................................................... 95 9.6. Feeder terminal settings ............................................................. 96

10.APPENDIX C: Specification for REM 54_ machine terminal configuration ........................................................... 97


10.1.General data .............................................................................. 97 10.2.Electrotechnical data .................................................................. 98

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.1.Analog inputs ...................................................................98 10.2.1.1.Hardware versions with 5 current and 4 voltage transformers .......................................................98 10.2.1.2.Hardware versions with 6 current and 3 voltage transformers .......................................................99 10.2.1.3.Hardware versions with 7 current and 2 voltage transformers .....................................................100 10.2.1.4.Hardware versions with 8 current and 1 voltage transformer .......................................................101 10.2.1.5.Sensor inputs ...................................................102 10.2.2.System frequency ..........................................................102 10.2.3.Digital inputs ..................................................................103 10.2.4.Digital outputs ................................................................105 10.2.5.RTD module ...................................................................108 10.2.5.1.RTD/analog inputs ...........................................108 10.2.5.2.RTD outputs .....................................................109 10.3.Functionality .............................................................................109 10.3.1.Order number .................................................................109 10.3.2.Application function blocks used ................................110 10.3.3.Communication ..............................................................111 10.4.Relay MIMIC configuration .......................................................112 10.4.1.Illustration of the system, MIMIC diagram ......................112 10.4.2.Alarm LEDs ....................................................................113 10.5.Functionality logic .....................................................................114 10.6.Machine terminal settings .........................................................115

11.APPENDIX D: Specification for RET 54_ transformer terminal configuration ..........................................................117


11.1.General data .............................................................................117 11.2.Electrotechnical data ................................................................118 11.2.1.Analog inputs .................................................................118 11.2.1.1.Hardware versions with 6 current and 3 voltage transformers .....................................................118 11.2.1.2.Hardware versions with 7 current and 2 voltage transformers .....................................................119 11.2.1.3.Hardware versions with 8 current and 1 voltage transformer .......................................................120 11.2.2.System frequency ..........................................................120 11.2.3.Digital inputs ..................................................................121 11.2.4.Digital outputs ................................................................123 11.2.5.RTD module ...................................................................126 11.2.5.1.RTD/analog inputs ...........................................126 11.2.5.2.RTD outputs .....................................................127

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.3.Functionality ............................................................................. 128 11.3.1.Order number ................................................................ 128 11.3.2.Application function blocks used ................................... 128 11.3.3.Communication .............................................................. 129 11.4.Relay MIMIC configuration ....................................................... 130 11.4.1.Illustration of the system, MIMIC diagram ..................... 130 11.4.2.Alarm LEDs ................................................................... 131 11.5.Functionality logic ..................................................................... 132 11.6.Transformer terminal settings .................................................. 133

12.APPENDIX E: Specification for REC 523 Remote Monitoring and Control Unit configuration ........................ 135
12.1.General data ............................................................................ 135 12.2.Electrotechnical data ................................................................ 136 12.2.1.Analog inputs ................................................................. 136 12.2.2.System frequency .......................................................... 140 12.2.3.Digital inputs .................................................................. 141 12.2.4.Digital outputs ................................................................ 142 12.3.Functionality ............................................................................. 143 12.3.1.Order number ................................................................ 143 12.3.2.Application function blocks used ................................... 143 12.3.3.Communication .............................................................. 144 12.4.Virtual channels ........................................................................ 144 12.4.1.LED configuration .......................................................... 144 12.5.Remote monitoring and control unit settings ............................ 146

13.APPENDIX F: Power quality application guide for harmonics ............................................................................. 147


13.1.Power quality and harmonics ................................................... 147 13.2.Background for harmonics ....................................................... 147 13.3.Harmonic sources .................................................................... 149 13.3.1.Single-phase power supplies ......................................... 149 13.3.2.Three-phase power converters ...................................... 150 13.3.3.Other harmonic sources ................................................ 151 13.4.System response characteristics ............................................. 152 13.5.Effects of harmonics ................................................................. 154 13.6.Applications for harmonic measurements ................................ 155 13.6.1.Power quality and harmonics ......................................... 155 13.6.2.Harmonic monitoring with individual loads and devices 156 13.6.3.Locating sources of harmonics ...................................... 157 13.6.4.Harmonic filter performance monitoring ......................... 157

14.Index ..................................................................................... 159

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Copyrights
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under alicense and may be used, copied, or disclosed only in accordance with the terms of such license. Copyright 2006 ABB Oy All rights reserved.

Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.

Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

1.
1.1.

About this manual


General
This guideline describes in general the procedures for configuring REF 54_ feeder terminals, REM 54_ machine terminals, RET 54_ transformer terminals and REC 523 remote monitoring and control units correctly with the Relay Configuration Tool. In this document, the term device is used when referring to all the above mentioned products. Chapter 5. Editing the relay configurations describes step-by-step the engineering actions required to create a relay configuration for a single device. Chapter 6. Main configuration rules defines a set of programming rules that should be followed while creating the configuration. These rules should be carefully checked when finalizing the configuration. Chapter 7. Engineering tips provides some engineering tips for doing the configuration. For instructions on operating the tool itself, refer to the operators manual for CAP 505 (see Section 1.6. Related documents). This version of the Configuration Guideline complies with products of Release 3.01. For information about the changes and additions compared to earlier revisions, refer to the technical reference manual of the appropriate product (see Section 1.6. Related documents). For information on what RE_ 5__ products support which add-on protocols, refer to the product manuals (Section 1.6. Related documents). Note that in this manual, the examples and dialog box pictures of the Relay Configuration Tool refer to REF 54_ feeder terminals (except Fig. 5.5.-1). The corresponding cases and dialog boxes can be slightly different for REM 54_, RET 54_ and REC 523.

1.2.

Use of symbols
This publication includes warning, caution, and information icons that point out safety-related conditions or other important information. It also includes tip icons to point out useful information to the reader. The corresponding icons should be interpreted as follows: The electrical warning icon indicates the presence of a hazard which could result in electrical shock.

The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.

1. Except REC 523 of revision D or later, and REM 54_ of Release 2.5
9

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

The information icon alerts the reader to relevant facts and conditions.

The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, and caution hazards are associated with equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.

1.3.

Document conventions
The following conventions are used for the presentation of material: The words in names of screen elements (for example, the title in the title bar of a dialog box, the label for a field of a dialog box) are initially capitalized. The names of push and toggle buttons are boldfaced. For example, click OK. The names of menus and menu items are boldfaced. For example, the File menu. The following convention is used for menu operations: Menu Name > Menu Item > Cascaded Menu Item. For example: select File > Open > New Project.

1.4.

Abbreviations
ASD CPU CSI FBD HMI I/O LCD LED LON NV PLC POU PWM RCT RMS RS RTD VD Adjustable speed drive Central processing unit Current source inverter Function block diagram Human-machine interface Input/output Liquid chrystal display Light-emitting diode Locally operating network Network variable Programmable logic controller Program organisation unit Pulse width modulation Relay Configuration Tool Root mean square Rogowski sensor Resistance temperature device Voltage Divider

10

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

1.5.

Terminology
device In this document refers to REF 54_ feeder terminal, REM 54_ machine terminal, RET 54_ transformer terminal and REC 523 remote monitoring and control unit Distributed Network Protocol, a communication protocol controlled by the DNP Users Group Communication protocol standardized by International Electrotechnical Commission Communication protocol standardized by International Electrotechnical Commission Graphic configuration picture on the relays LCD Communication protocol introduced by Modicon Inc. Relay Configuration Tool project, a zipped project file Communication protocol developed by ABB

DNP 3.0 IEC 60870-5-101 IEC 60870-5-103 MIMIC Modbus RCT project file SPA

1.6.

Related documents
Document Manuals for REF 54_, REM 54_, RET 54_ and REC 523 Installation Manual RE_ 5_ _a Operators Manual RE_ Feeder Terminal REF 54_ Technical Reference Manual, Generala Technical Reference Manual REM 54_a Transformer Terminal RET 54_ Technical Reference Manual, General Remote Monitoring and Control Unit REC 523 Technical Reference Manuala REM 54_ Machine Terminal Technical Reference Manual, General Technical Descriptions of Functions (CD-ROM) REF 54_ and RET 54_ Modbus Communication Protocol Technical Description Modbus Remote Communication Protocol for REM 54_ Technical Description REM 543 Modbus Configurations (CD-ROM) Modbus Remote Communication Protocol for REC 523 Technical Description REF 54_, RET 54_ and REX 521 DNP 3.0 Communication Protocol Technical Description DNP 3.0 Remote Communication Protocol for REC 523 Technical Description IEC 60870-5-101 Remote Communication Protocol for REC 523, Technical Description Tool-specific manuals CAP 505 Installation and Commissioning Manualb CAP 505 Operators Manualb Manualb CAP 505 Protocol Mapping Tool Operators 1MRS751273-MEN 1MRS751709-MUM 1MRS755277
11

ID 1MRS750526-MUM 1MRS750500-MUM 1MRS750527-MUM 1MRS750915-MUM 1MRS755225 1MRS750881-MUM 1MRS750915-MUM 1MRS750889-MCD 1MRS755238 1MRS750781-MUM 1MRS151023-MUM 1MRS752015-MUM 1MRS755260 1MRS750958-MUM 1MRS750956-MUM

54_a

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline
Document Tool-specific manuals (cont.) CAP 501 Installation and Commissioning Manualc CAP 501 Operators Manualc Relay Configuration Tool, Quick Start Referenceb Relay Configuration Tool, Tutorialb Relay Mimic Editor, Configuration LIB, CAP and SMS, Tools for Relays and Terminals, Users Guide Manualb

1MRS750745-MUM

ID 1MRS751270-MEN 1MRS751271-MUM 1MRS751275-MEN 1MRS751272-MEN 1MRS751274-MEN 1MRS752008-MUM

a. Included on the CD-ROM Technical Descriptions of Functions, 1MRS750889-MCD b. Included on the CD-ROM Relay Product Engineering Tools c. Included on the CD-ROM Relay Setting Tools

1.7.

Document revisions
Version G H K L M Date 02.04.2004 20.01.2005 01.03.2005 08.07.2005 27.10.2006 History Manual updated RET 54_ added to manual Updates according to REC 523 revision F Updates according to REF 54_, Release 3.5 Layout updated, minor corrections.

12

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

2.

Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed. The frame of the device has to be carefully earthed.

The device contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided. Breaking the sealing tape on the rear panel of the device will result in loss of warranty and proper operation will no longer be guaranteed.

13

14

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

3.

Relay Configuration Tool


The Relay Configuration Tool is a standard programming system for RED 500 devices. It is used for configuring the protection, control, condition monitoring, measurement and logic functions of the feeder terminal. The tool is based on the IEC 61131-3 standard, which defines the programming language for relay terminals, and includes a wide range of IEC features. The programmable logic controller (PLC) logics are programmed with Boolean functions, timers, counters, comparators and flip-flops. The programming language described in this manual is a function block diagram (FBD) language.

15

16

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

4.

Specification for relay configuration


Prior to starting the configuration of a product, the specification for relay configuration is to be filled out. Separate specifications for REF 54_, REM 54_, RET 54_ and REC 523 can be found in appendices B, C, D and E in the end of this manual. The purpose of the specification is to provide the technical information required for the proper configuration of the products.

17

18

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

5.
5.1.

Editing the relay configurations


Getting started
1. Start up the CAP 505 tool by double clicking the tool icon. 2. Add a new object as an empty configuration to the CAP 505 environment. For instructions, refer to the operators manual for CAP 505 (see Section 1.6. Related documents). The program opens an empty project template (see Fig. 5.1.-1) with a toolbar at the top. 3. Build the project tree structure by inserting libraries, program organisation units (POUs) and target-specific items to the project tree. The project tree editor is a window in which the whole project is represented as a tree. The project tree is illustrated with several icons. Most of the icons represent a file of the project, and different looking icons represent different types of files. The tree always contains 4 subtrees: Libraries, Data Types, Logical POUs and Physical Hardware.

ProjectTree

Fig. 5.1.-1 Project tree and the four subtrees The project tree is the main tool for editing the project structure. Editing the project structure means inserting POUs or worksheets to the project structure, or deleting existing ones. The editors for editing the code-body data and the variable declaration can be opened by double-clicking the corresponding object icons. If you edit an old project, note that saving the changes made with the Save as command does not work as in other Windows programs. If you want to keep the old project unchanged, save the project with a new name before making any changes.

5.1.1.

Libraries
Before editing any worksheets of POUs, the whole project tree structure must be build. The function block library (protection, control, measurement, condition monitoring and standard functions) needed in the relay configuration needs to be inserted to the Libraries subtree. For instructions on announcing libraries, refer to the tutorial manual for the Relay Configuration Tool, see Section 1.6. Related documents. Before inserting a library to the project, close all open worksheets in order to avoid confusing the I/O description of the function blocks.

19

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

The programs, function blocks (for example NOC3Low, the low-set stage of nondirectional three-phase overcurrent protection) and functions of the library can be reused in the new project, which is edited. The library, for example REFLIB01 for REF 54_ (see Fig. 5.1.1.-1), includes the full set of function blocks, but only those ordered by the customer can be used in the configuration. If a configuration is transferred to a newer version of the product, the library in the project must also be updated.

ref/rem/ret/reclib01

Fig. 5.1.1.-1

Libraries for REF 54_, REM 54_, RET 54_ and REC 523

The library version to be selected depends on the software revision of the product as listed in the table below. The directory path to the libraries is <installation drive>\CAP505\Common\IECLibs\Fi.
Table 5.1.1-1
Product REF 541

Product software revisions and libraries


Software revision A B C D and E K A B and C K C and D E F G and H K A B and C K Library file name COMMU_01, CONDM_01, CONTR_01, MEASU_01, PROTE_01, STAND_01 REFLIB01 REFLIB02 REFLIB03 REFLIB04 REFLIB02 REFLIB03 REFLIB04 COMMU_01, CONDM_01, CONTR_01, MEASU_01, PROTE_01, STAND_01 REFLIB01 REFLIB02 REFLIB03 REFLIB04 REFLIB02 REFLIB03 REFLIB04

REF 541 (RTD1)

REF 543

REF 543 (RTD1)

20

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline Table 5.1.1-1
Product REF 545

REF 54_, REM 54_, RET 54_, REC 523

Product software revisions and libraries (Continued)


Software revision A B C D and E K A B C A B A B A B A A A A A A B C D E F Library file name COMMU_01, CONDM_01, CONTR_01, MEASU_01, PROTE_01, STAND_01 REFLIB01 REFLIB02 REFLIB03 REFLIB04 REMLIB01 REMLIB02 REMLIB03 REMLIB02 REMLIB03 REMLIB02 REMLIB03 REMLIB02 REMLIB03 RETLIB01 RETLIB01 RETLIB01 RETLIB01 RETLIB01 RECLIB01 RECLIB01 RECLIB02 RECLIB03 RECLIB03 RECLIB04

REM 543

REM 543 (RTD1) REM 545 REM 545 (RTD1) RET 541 RET 541 (RTD1) RET 543 RET 543(RTD1) RET 545 REC 523

5.1.2.

Program organisation unit


Each Program Organisation Unit (POU) consists of several worksheets: Description worksheet for comments Variable worksheet for variable declarations Code body worksheet for the configuration. The name of each worksheet is indicated beside the corresponding icon. The * symbol after the name of a worksheet indicates that the worksheet has not been compiled yet.

POU_unit

Fig. 5.1.2.-1

Program organisation unit with three worksheets

21

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

The description worksheet (for example ProtectT) illustrated below is for describing the POU or the configuration element. The worksheet is automatically named by adding a T to the name of the POU.

text

Fig. 5.1.2.-2

Description worksheet

The variable worksheet (for example ProtectV) is for the variable declaration. The worksheet is automatically named by adding a V to the name of the POU. The variable worksheet is not edited manually but is created by the tool.

variables

Fig. 5.1.2.-3

Variable declaration worksheet

A code body worksheet (for example Protect) is for a code body declaration in the form of an function block diagram (FBD). All configurations for the devices of the RED 500 platform are made in the graphical FBD language. A code body programmed in the FBD language is composed of functions and function blocks that are connected to each other using variables, connection lines or connectors. An output of a function block can be combined with the output of another function block for example via an OR gate (refer to Section 6.1. General). Connectors are objects that can be used instead of connection lines, for example where the distance between two objects on the worksheet is long. The connectors can only be used within one worksheet, and they are resolved by textual names.

22

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Connectors should be used with care since the tool may not warn if a match to a connector cannot be found (for example, the comparison of connectors is case sensitive). Note that visually the connectors are distinguished from variables by embedding them with larger than signs, > >.

Connectors

Fig. 5.1.2.-4

Code body declaration in FBD language

Even though the tool permits adding several code body worksheets under one POU, only one worksheet is recommended to be used per POU. If more space is needed for a configuration, the worksheet size can be increased or the functionality can be divided into several POUs. Avoid creating very large configurations per POU since the RED 500 PLC environment has an inherent limit for the number of input/output points per POU. The limit is 511 I/O points and is consumed by called function block instances only. Note that the limit is checked during the configuration downloading. If the downloading fails for this reason, the user has to divide the POU into smaller units. For example, the function block NOC3Low in Fig. 5.1.2.-4 includes 14 I/O points. The I/O points are consumed regardless of whether they are connected or not.

5.1.3.

Logical POUs
In the project tree editor and in the library editor, the Logical POUs subtree represents a directory for all the POUs related to the project. The maximum of 20 POUs can be inserted to the subtree. Fig. 5.1.3.-1 shows a Logical POUs subtree

23

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

with 4 POUs; CondMon represents a function block, Confirm represents a function, and Measure and Control are programs. The associated icon represents the POU type.

LogicalPOUs

Fig. 5.1.3.-1

Logical POUs subtree with 4 POUs

Each POU type has specific characteristics from the programming point of view. A function yields exactly one data element which is evaluated from its input parameters. In other words, a function cannot contain any internal state information. Furthermore, a function can call other functions but not function blocks. A function block (FB) can return 0,1,2.. output values and can have internal variables. Function blocks can call any other function or function block except itself. Multiple copies of function blocks are called instances and each instance is given an identifier. Programs are specialized function blocks that can only be called by tasks. Note that recursion is not allowed for any POU type. The POU category is selected when a POU is inserted to the project tree. Fig. 5.1.3.2 below shows the dialog box for inserting POUs. The programming language (FBD) for the POU and the return data type for functions are also selected here. The PLC type and Processor type selections should be left to their default values.

24

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

InsertNewPOU

Fig. 5.1.3.-2

Inserting a new program POU called Demo which is programmed by using the function block diagram language

At first, a POU framework is created, that is, empty POUs are inserted to the project according to the Specification for Relay Configuration filled out prior to starting the configuration procedure. The physical hardware must be defined before creating the actual contents for the POUs, otherwise the predefined target-specific POUs are not available for the programmer. The task execution intervals recommended for function blocks must be considered already when defining the POU framework. In general, each POU forms a functional unit for example for protection function blocks. Some function blocks, however, require a different task than most of the same category, and must therefore be assigned a separate POU. For example, the task execution interval of most protection function blocks is 10 ms but Freq1St_ requires the task of 5 ms, which is why it usually needs a separate POU. However, if all the protection function blocks used are associated with the task of 5 ms, no separate POU is required for Freq1St_.

5.1.4.

Physical hardware
In the project tree editor, the physical hardware is represented as a subtree (see Fig. 5.1.4.-1) after the hardware of the device, that is, Configuration, Resource and Tasks, has been defined.

25

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

PhysicalHardware

Fig. 5.1.4.-1

Example of a subtree for the physical hardware

The configuration elements available in the Physical Hardware subtree may differ from configuration to configuration. Each terminal of the RED 500 platform can be configured separately.

5.1.4.1.

Configuration
In the Relay Configuration Tool, the name of the configuration and the appropriate product family, programmable logic controller (PLC) type, are first defined: 1. Select a Physical Hardware tree element and select Edit > Insert. 2. Define Name and PLC type, and click OK.

configuration_b

Fig. 5.1.4.1.-1 Defining the configuration type

26

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

5.1.4.2.

Resource for REF 54_, REM 54_ and REC 523


For REF 54_ Release 2.5 and later, RET 54_, and REC 523 revision F, refer to Section 5.1.4.3. Resource for REF 54_ Release 2.5 or later, REC 523 revision F and RET 54_. The PLC type selected in the Configuration dialog box above determines which processor types are available. To select the processor type and name the resource: 1. Select an object under the Physical Hardware tree and select Edit>Insert. 2. In the opening dialog box, click the option button Resource, select the correct processor type and name the resource. For example, the processor type REF543R refers to a REF 543 feeder terminal equipped with an resistance temperature device (RTD) module.

resource

Fig. 5.1.4.2.-1 Defining the processor type

Hardware version
After selecting the processor type, click the Settings button in the dialog box (see Fig. 5.1.4.2.-1 above) to define the correct hardware version (see Fig. 5.1.4.2.-2). Do not click OK after selecting the correct hardware version (see Fig. 5.1.4.2.-2), but wait until the next dialog box opens and click the option button Analog Channels (see Fig. 5.1.4.2.-3). The hardware version number is included in the order number of the product. The order number is labelled on the marking strip on the front panel of the product. Example: Order No: REF543FC127AAAA Note that for REC 523, the selectable relay variants are given as order numbers, for example REC523C 033AAA. Refer to the technical reference manual of REC 523, see Section 1.6. Related documents)

27

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

hw_variant

Fig. 5.1.4.2.-2 Defining hardware version

select_analog_channels

Fig. 5.1.4.2.-3 Selecting the dialog box for analog settings

28

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Analog channels
In the dialog box for defining analog channels (Fig. 5.1.4.2.-4), click the option button for each channel in turn, and select the measuring device and signal type for the channels in use from the drop-down list. Select the option Not in use for other channels.

analog_channels

Fig. 5.1.4.2.-4 Defining the analog channel settings Furthermore, define the technical data and measurements for the selected channels before the configuration is used in a real application.

29

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Technical data

rated_values

Fig. 5.1.4.2.-5 Defining the rated values for the selected measuring device Measurements For information about the special measurements required for each function block, refer to the Technical Descriptions of Functions (see Section 1.6. Related documents). True RMS measurement and 2nd harmonic restraint measurements If the signal type selected for an analog channel is going to be measured by any measurement function block (MECU3A etc.), select the option True RMS mode in the Special Measurements dialog box. If the Inrush3 function block (3-phase transformer inrush and motor start-up current detector) is to be used, select the option 2nd Harmonic Restraint for the analog channels (IL1, IL2, IL3) used.

30

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

SpecMeasIL1

Fig. 5.1.4.2.-6 Selecting the required special measurement modes for phase current measurement Neutral current When the DEF2_ function block (directional earth-fault protection) is going to be used, select the option Intermittent earth-fault protection in the Special Measurements dialog box for the channel via which the current I0 is measured. The intermittent earth-fault protection can be enabled for the maximum of two physical channels at a time. Note that the intermittent earth-fault protection requires the residual voltage for directional operation. Therefore, the channel for the residual voltage U0 must be defined before the selection can be made. Unless intermittent earth-fault protection has been chosen, the following configuration error indication appears on the display of REF 54_, REM 54_ or RET 54_ ( # denotes the number of the analog channel in question): System: SUPERV Ch # error

SpecMeasIo

Fig. 5.1.4.2.-7 Selecting the required special measurement modes for neutral current measurement

31

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Frequency When, for example, the function block MEFR1 (system frequency measurement) is in use, frequency measurement must be selected for the channel via which the voltage is measured for frequency measurement. For example Channel 10 (Voltage Transformer 4, Signal type U3), click the Measurements button in the Configuration of REF543 dialog box. The power quality function blocks PQCU3H and PQVO3H require frequency measurement for the channel that is connected to the FREQ_REF input, that is, the channel for frequency reference (for more information, refer to the manuals of PQCU3H and PQVO3H on the CD-ROM Technical Descriptions of Functions, see Section 1.6. Related documents). Furthermore, frequency protection must be selected if any of the function blocks SCVCSt_ or Freq1St_ is in use.

SpecMeasUL1

Fig. 5.1.4.2.-8 Selecting the required special measurement modes for frequency measurement

32

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Virtual channels In case no measuring devices are applied for measuring residual voltage (U0) and neutral current (I0), the virtual channels 11 and 12 can be used. If only one virtual channel is used, the channel is numbered as channel 11 regardless of whether residual voltage or neutral current is calculated. If both I0 and U0 are calculated, channel 11 is used for I0S and channel 12 for U0S.

virtual_channels

Fig. 5.1.4.2.-9 Using virtual channels 11 and 12 in case no measuring devices are applied for measuring I0 and U0 In case of the virtual channels for calculating I0 and U0, phase currents and voltages must be associated with current and voltage measuring devices (see Fig. 5.1.4.2.-10 and Fig. 5.1.4.2.-11).

Summed_Ios

Fig. 5.1.4.2.-10 Associating phase currents with current measuring devices


33

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Summed_Uos

Fig. 5.1.4.2.-11 Associating phase voltages with voltage measuring devices After a compiled configuration is downloaded to a device, it checks internally whether the analog channels are correctly configured regarding the analog inputs of function blocks. If the connected channels have been configured incorretly, the ERR output signal of the specific function block activates and the analog channel configuration error event (E48) is sent. Some function blocks have special error events that are explained in the corresponding function block manuals on the CD-ROM Technical Descriptions of Functions (see Section 1.6. Related documents).

34

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Digital inputs
The filter time is set for each digital input of the device via the resource settings dialog box Binary Inputs. Inversion of the inputs can also be set. Note, however, that the inversion of an input cannot be seen from the configuration. For further information refer to the technical reference manual of REF 54_, REM 54_, RET 54_ or REC 523 (see Section 1.6. Related documents).

BIN_INPUT

Fig. 5.1.4.2.-12 Defining the digital inputs

35

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Measurements
When the MEPE7 function block (power and energy measurement) is used, the measuring mode must be selected via the resource settings dialog box Measurements. True RMS measurement must also be selected for the channels used by MEPE7. Note that the measuring modes can only be selected after the analog channels have been defined (see Fig. 5.1.4.2.-4).

MEPE7

Fig. 5.1.4.2.-13 Selecting the measuring mode for power and energy measurement

36

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Condition monitoring
Values for the circuit-breaker wear function blocks CMBWEAR 1 and 2 can be set via the resource settings dialog box Condition Monitoring.

cbwear

Fig. 5.1.4.2.-14 Setting the values for circuit-breaker wear

5.1.4.3.

Resource for REF 54_ Release 2.5 or later, REC 523 revision F and RET 54_
The PLC type selected in the Configuration dialog box determines which processor types are available. To select the processor type and name the resource: 1. Select an object under the Physical Hardware tree and select Edit > Insert. 2. In the opening dialog box, click the option button Resource, select the correct processor type and name the resource. For example, the processor type REF543R refers to a REF 543 feeder terminal equipped with an RTD module.

37

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

processtype2.5

Fig. 5.1.4.3.-1 Defining the processor type

Hardware version
After selecting the processor type, click the Settings button in the dialog box (see Fig. 5.1.4.3.-1 above) to define the correct hardware version (see Fig. 5.1.4.3.-2). Do not click OK after selecting the correct hardware version (Fig. 5.1.4.3.-2), but wait until the next dialog box opens and select the option Analog Channels (see Fig. 5.1.4.3.-3). The hardware version number is included in the order number of the product. The order number is labelled on the marking strip on the front panel of the product. Example: Order No: REF543GC127AAAA

hardware2.5

Fig. 5.1.4.3.-2 Defining the hardware version

38

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

analog_settings2.5

Fig. 5.1.4.3.-3 Selecting the dialog box for analog settings

Analog channels
In the dialog box for defining analog channels (see Fig. 5.1.4.3.-4), click the option button for each channel in turn, and select the measuring device and signal type for the channels in use from the drop-down list. Select the option Not in use for other channels. Furthermore, the technical data and measurements for the selected channels are to be completed correctly before the configuration is used in a real application.

analog_channels2.5

Fig. 5.1.4.3.-4 Defining the analog channels


39

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Technical data

rated_values2.5

Fig. 5.1.4.3.-5 Defining the rated values for the selected measuring device Measurements For information about the special measurements required for each function block, refer to the Technical Descriptions of Functions (see Section 1.6. Related documents). True RMS and 2nd harmonic restraint measurements If the signal type selected for an analog channel is going to be measured by any measurement function block (MECU3A etc.), the true RMS mode must be selected in the Special Measurements dialog box. Moreover, in case the Inrush3 function block (3-phase transformer inrush and motor start-up current detector) is to be used, the 2nd harmonic restraint must be selected for the analog channels (IL1, IL2, IL3) used.

40

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

phase_measu2.5

Fig. 5.1.4.3.-6 Selecting the required special measurement modes for phase current measurement Neutral current When the DEF2_ function block (directional earth-fault protection) is going to be used, intermittent earth-fault protection must be selected for the channel via which the current I0 is measured. The intermittent earth-fault protection can be enabled for the physical channels I0 and I0b as well as for the virtual channels I0s and I0bs at the same time. The intermittent earth-fault protection requires the residual voltage for directional operation. Therefore, the channel for the residual voltage U0 must be defined before the selection for I0 measurement channels can be made. The amount of the U0 channels used for the intermittent earth-fault protection is limited to one. The first available U0 channel should be selected from the list: U0, U0b, U0s and U0bs. Unless intermittent earth-fault protection has been chosen correctly, a configuration error indication will appear on the error list of the Relay Download Tool.

neutral_measu2.5

Fig. 5.1.4.3.-7 Selecting the required special measurement modes for neutral current measurement

41

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Frequency When, for example, the function block MEFR1 (system frequency measurement) is in use, frequency measurement must be selected for the channel via which the voltage is measured for frequency measurement. For example Channel 10 (Voltage Transformer 4, Signal type U3), click the Measurements button in the Configuration of REF543 dialog box. The power quality function blocks PQCU3H and PQVO3H require frequency measurement for the channel that is connected to the FREQ_REF input, that is, the channel for frequency reference (for more information refer to the manuals of PQCU3H and PQVO3H on the CD-ROM Technical Descriptions of Functions, see Section 1.6. Related documents). Furthermore, frequency protection must be selected if any of the function blocks SCVCSt_ or Freq1St_ is in use.

freq_measu2.5

Fig. 5.1.4.3.-8 Selecting the required special measurement modes for frequency measurement

42

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Virtual channels The virtual channels can be used if no measuring devices are applied for measuring phase-to-phase voltages, residual voltage (U0) and neutral current (I0). The virtual channels selected for use are numbered from the channel number 11. For further information about the channel numbers of the calculated virtual channels, refer to the technical reference manual of the terminal in question (see Section 1.6. Related documents). An example of when the virtual channels can be used is shown in Fig. 5.1.4.3.-9.

virtual_channels2.5

Fig. 5.1.4.3.-9 Using virtual channels if phase-to-phase voltages, residual voltage and neutral current measurement are not available The virtual channels are selectable according to the selections in the Analog Channels view. The selection of the virtual channels can be done in Virtual Channels view (see Fig. 5.1.4.3.-10).

43

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

select_virtual_channels2.5

Fig. 5.1.4.3.-10 The selectable virtual channels when the configuration of the analog channel is as in Fig. 5.1.4.3.-9 The special measurements are selectable for each used virtual channel (see Fig. 5.1.4.3.-11 and Fig. 5.1.4.3.-12). The special measurement view for the virtual channel Ios is shown in Fig. 5.1.4.3.11. The analog channels used for derivation and derivation equation are also shown. The analog channels are as in Fig. 5.1.4.3.-9.

Ios_measu2.5

Fig. 5.1.4.3.-11 Special measurement view for the virtual channel Ios Special measurement view for the virtual channel U12s is shown in the Fig. 5.1.4.3.12. The analog channels used for derivation and derivation equation are also shown. The analog channels are as in Fig. 5.1.4.3.-9.
44

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Ios_measu_2.5_2

Fig. 5.1.4.3.-12 Special measurement view for the virtual channel U12s. After a compiled configuration is downloaded to a device, the device checks internally whether the analog channels are correctly configured regarding the analog inputs of function blocks. If the connected channels have been configured incorrectly, the ERR output signal of the specific function block activates and the analog channel configuration error indication appears on the error list of the Relay Download Tool. For more information, refer to Section 5.5. Downloading the configuration.

Digital inputs
The filter time is set for each digital input of the device via the resource settings dialog box Binary Inputs field. Inversion of the inputs can be set as well. Note, however, that the inversion of an input cannot be seen from the configuration. For further information, refer to the technical reference manual of the terminal in question (see Section 1.6. Related documents).

digital_inputs2.5

Fig. 5.1.4.3.-13 Defining the digital inputs

45

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Measurements
When the MEPE7 function block (power and energy measurement) is used, the measuring mode must be selected by clicking the option button Measurements in the resource settings dialog box. True RMS measurement must also be selected for the channels used by MEPE7. The measuring modes can only be selected after the analog channels have been defined (see Fig. 5.1.4.3.-4).

power&energy_measu2.5

Fig. 5.1.4.3.-14 Selecting the measuring mode for power and energy measurement

Condition monitoring
Values for the circuit-breaker wear function blocks CMBWEAR 1 and 2 can be set via the resource settings dialog box by clicking the option button Condition Monitoring.

46

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

wear2rle

Fig. 5.1.4.3.-15 Setting the values for circuit-breaker wear

5.1.4.4.

Tasks Programs and tasks


Programs are associated with tasks via the dialog boxes Properties/Task and Properties/Program. To define task properties in the Relay Configuration Tool: 1. Select an object in the project tree. 2. Select Edit > Insert and define task name and type. One task may include several programs. Cyclic tasks are activated within a specific time interval and the program is executed periodically. As many as 10 POUs can be associated to a task. To define program properties in the Relay Configuration Tool: 1. Select a task in the project tree. 2. Select Edit > Insert and define program instance and type. The two dialog boxes below illustrate the association of a program type (Prot_Me) with a task (Task1) (see also Fig. 5.1.4.-1).

47

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

TASK1

Fig. 5.1.4.4.-1 Naming a cyclic task

PROT_ME

Fig. 5.1.4.4.-2 Associating the selected task with the desired program type

Task interval
Generally, operation accuracy is increased when task speed is increased, but at the same time, the load of the microprocessors is increased as well. Although the task speed can be freely chosen with the tool, it is necessary to define a maximum task execution interval for each function block. If not defined, the operation accuracy and operate times for protection functions cannot be guaranteed. The maximum task execution interval is based on test results and it has been used in the type testing of the function blocks. The recommended task execution interval quaranteed by the manufacturer can be found in technical data section in the technical description of each function block. Furthermore, certain function blocks, for example MEDREC16, must be tied to the task given by the manufacturer in order to enable the operation of these function blocks. For more information about the task execution intervals of function blocks, refer to the introduction chapter in the Technical Descriptions of Functions CD-ROM, see Section 1.6. Related documents. For microprocessor loads, refer to Section 5.5. Downloading the configuration. According to the standard, the Relay Configuration Tool offers a possibility to define the tasks on two different levels: 1. Each program organisation unit (POU) can be tied to a separate task. 2. Separate function block inside a POU can be tied to any task.
48

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

However, the second alternative is not supported in the RED 500 environment; if a separate function block inside a POU is given a separate task definition, it is ignored when transferred to the device. This means that when the function blocks are being placed in different POUs, not only the category of the function (protection, control, and so on) but also the maximum task execution interval should be considered, since all function blocks inside a POU run at the same speed. Define the task execution interval for each task by selecting a task and by selecting Edit > Insert; click the Settings button in the opening dialog. For example, the task execution interval for Task1 in the figure below is defined as 10 ms, which means that the program Prot_Me is run 100 times per one second. The maximum number of tasks with different intervals is 4. The tool automatically modifies the task setting if the set network frequency is other than 50 Hz (see the Network Frequency text box in Fig. 5.1.4.2.-4). For example at 60 Hz, 10 ms becomes 8.333 ms.

interval

Fig. 5.1.4.4.-3 Setting the task execution interval for a program If there is a need for several different tasks that control the same output relay, it is recommended that the output relay is controlled directly in the fastest task and other control commands are brought to that task via global variables. Example: Some protection function blocks can be run in the 5 ms task, some in the 10 ms task and some even using the 100 ms task. Still, all these function blocks use the same output relay. Another way to avoid also the software delays when communicating between the different tasks is to use a separate output relay for each protection task. Example: The trip signal from the 5 ms task is connected to High-Speed Power Output 1 and the trip signal from the 10 ms task to High-Speed-Power-Output 2. The outputs can then control the same opening coil of the circuit breaker.

5.2.

Declaring variables
The validity range of the declarations that are included in the declaration part should be local to the POU in which the declaration part is contained. However, variables that are declared to be global are only accessible to a POU via a
49

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

VAR_EXTERNAL declaration. The type of a variable declared in a VAR_EXTERNAL block should agree with the type declared in the VAR_GLOBAL block of the associated program, configuration or resource.
Program B FB2 FB_Y a y y b Program A FB2 FB_Y a b

FB1 FB_X

VAR y:BOOL; FB1:FB_X; FB2:FB_Y; END_VAR

FB1 FB_X

VAR FB1:FB_X; FB2:FB_Y; END_VAR

Configuration C Program A VAR_EXTERNAL x:BOOL; END_VAR VAR FB1:FB_X; END_VAR Program B VAR_EXTERNAL x:BOOL; END_VAR VAR FB2:FB_Y; END_VAR

FB1 FB_X a x VAR_GLOBAL x:BOOL; END_VAR x b

FB2 FB_Y

Fig. 5.2.-1 Local and global variables The figure above illustrates the how variable values can be communicated among software elements either directly or via global variables. Variable values within a program can be communicated directly by connecting the output of one program element to the input of another, or via local variables, such as the variable y illustrated in the upper-left corner of the figure above. In the same configuration, variable values can be communicated between programs via global variables, such as the variable x illustrated in Configuration C in the figure above. In such a case, make sure that the global variable is only written from one location in the project. The global variable can still be read from several locations. According to IEC 61131-3, all the variables that have no explicit initializer are initialized with a data-type dependent default value. Despite of this, it is always recommended that the initial value is given explicitly. Naturally, the value to which each variable should be initialised depends on the logical function of the program .
Table 5.2.-1
Data type ANY_REAL ANY_INT ANY_BIT TIME

Default values according to data types


Default initial value 0.0 0 0 (=FALSE) T#0s

50

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Especially the initial values of global variables are logically significant for the program. The user cannot choose the order in which tasks are initialised. This means that if a task reading a global variable is initialized before another task gives the variable its first value, it is important that an appropriate initial value has been selected for the global variable. CASE 1. Variables declaration
VARIABLE WORKSHEET of logical POU

******************************************************************
VAR TRIPPING :BOOL := FALSE; BLOCK :BOOL := TRUE; TMP1 :BOOL := FALSE; END_VAR VAR_EXTERNAL PS1_4_HSPO1 :BOOL; (* Double pole high speed power output *) (* X4.1/10,11,12,13 *) PS1_4_HSPO2 :BOOL; (* Double pole high speed power output *) (* X4.1/15,16,17,18 *) PS1_4_HSPO3 :BOOL; (* Double pole high speed power output *) (* X4.1/6,7,8,9 *) END_VAR VAR_EXTERNAL TCS1_ALARM :BOOL; END_VAR

******************************************************************

GLOBAL VARIABLE WORKSHEET

******************************************************************
VAR_GLOBAL PS1_4_HSPO1 PS1_4_HSPO2 PS1_4_HSPO3 END_VAR VAR_GLOBAL TCS1_ALARM END_VAR AT %QX 1.1.2 :BOOL := FALSE; (* Double pole high speed power output X4.1/10,11,12,13 *) AT %QX 1.2.2 :BOOL := FALSE; (* Double pole high speed power output X4.1/15,16,17,18 *) AT %QX 1.3.2 :BOOL := FALSE; (* Double pole high speed power output X4.1/6,7,8,9 *)

:BOOL

:= FALSE;

******************************************************************

51

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

5.2.1.

Global variables
The physical contacts are defined in the Global Variables worksheet (Fig. 5.2.1.-1). Declarations for the physical contacts are automatically defined when the correct hardware version of RE_ 54_ is selected. Declarations for the analog channels are created after the analog channel settings defined in the resource settings dialog box have been approved. The textual names of the inputs and outputs, for example BIO2-7_BI10IV (see the figure below), can be modified. Note, however, that the address (for example AT %IX 1.29.1 :BOOL := TRUE) following the name may not be changed.

global

Fig. 5.2.1.-1

Global Variables worksheet

5.2.2.

Local variables
At the beginning of each programmable controller POU type declaration there should be at least one declaration part that specifies the types of the variables used in the organisation unit. The declaration part should have the textual form of one of the keywords VAR_INPUT, VAR_OUTPUT, VAR and VAR_EXTERNAL followed by one or more declarations separated by semicolons and terminated by the keyword END_VAR. All the comments you write must be edited in parentheses and asterisks:. (*******************************) Variable declaration (* *) of REF 541 (* *) (*******************************)

52

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Caution is required regarding comments and variable declarations. The following code example would be compiled successfully but because of the non-closed comment, the END_VAR - VAR_EXTERNAL couple is excluded and thus the channel numbers become local variables of the POU and they get the initial value zero:

VAR (*AUTOINSERT*) NOC3Low_1 : NOC3Low; (* Erroneous nonclosed comment * END_VAR VAR_EXTERNAL (*AUTOINSERT*) U12 : SINT; (* Measuring channel 8 *) U23 : SINT; (* Measuring channel 9 *) U31 : SINT; (* Measuring channel 10 *) END_VAR

Three examples of creating the textual declaration for different kinds of graphical programs are given below. Example 1: POU type: FBD program Function block type declaration:
VAR SIGNAL1 SIGNAL2 SIGNAL3 SIGNAL4 END_VAR :BOOL :=FALSE; :BOOL :=FALSE; :BOOL :=FALSE; :BOOL :=FALSE;

and_or_gates

Fig. 5.2.2.-1

Function block image

53

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Example 2: POU type: NOC3Low, manufacturer-dependent function block Function block type declaration:
VAR_INPUT IL1 IL2 IL3 BS1 BS2 TRIGG GROUP DOUBLE BSREG RESET END_VAR VAR_OUTPUT START TRIP CBFP ERR END_VAR :SINT :SINT :SINT :BOOL :BOOL :BOOL :BOOL :BOOL :BOOL :BOOL :=0; :=0; :=0; :=FALSE; :=FALSE; :=FALSE; :=FALSE; :=FALSE; :=FALSE; :=FALSE; (* Analog channel *) (* Analog channel *) (* Analog channel *) (* Blocking signal *) (* Blocking signal *) (* Triggering *) (* Grp1/Grp2 select *) (* Doubling signal *) (* Blocking registering *) (* Reset signal *)

:BOOL :BOOL :BOOL :BOOL

:=FALSE; :=FALSE; :=FALSE; :=FALSE;

(* Start signal *) (* Trip signal *) (* CBFP signal *) (* Error signal *)

NOC3Low_b

Fig. 5.2.2.-2

Function block image of NOC3Low

54

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Example 3: POU type: Programmer-dependent FBD function block CONDIS Function block type declaration:

condisv

Fig. 5.2.2.-3

Type declaration of the programmer made function block CONDIS

55

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

condis

Fig. 5.2.2.-4

FBD worksheet contents of the CONDIS function block

condis_control

Fig. 5.2.2.-5

Use of the programmer made function block CONDIS

In the Example 3 above, part of the configuration has been separated to a programmer-made function block called CONDIS. Such function blocks may not be given names already belonging to library functions blocks or IEC standard function blocks. The function block CONDIS has been used like any other function block in the graphical program. It must also be remembered that a function block with an instance named by the programmer can only be inserted to the project once.
56

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

5.3.

Compiling project
In the Relay Configuration Tools Make menu, select the command Build Project to compile the whole project for the first time after editing. This means compiling all POUs, global variables, resources and so on. In the Make menu, use the Make command to compile the worksheets that have been edited. The changed worksheets are marked with an asterisk, *, in the project tree editor. The Make command is the standard mode for compiling and should normally be used when you have finished editing. It is recommended that the Build Project command is given once more just before downloading the configuration to the product. In the Relay Configuration Tool you can view the execution order of the different functions or function blocks in your worksheet. The execution order corresponds to the intermediate PLC code created while compiling. Note that the execution order can only be seen if you have already compiled the worksheet by using the menu command Make > Compile Worksheet.

5.4.

Add-on protocol
If an add-on protocol is used, the protocol mapping must be created by using the Protocol Mapping Tool (PMT). For more information, refer to the documents in Section 1.6. Related documents.
Table 5.4.-1
Relay version REF 54_ Release 2.5 REF 54_ Release 3.0 REF 54_ Release 3.5 REM 54_ Release 2.5 RET 54_ Release 3.0

Available add-on protocols


Modbus X X X X DNP 3.0 X X X IEC 60870-5-103 X X X X

REC 523 does not have any add-on protocols, but the device includes fixed protocols according to the devices software configuration. In REC 523 revision F, the protocol interface can be modified by using the Protocol Mapping Tool. In earlier releases, the protocol interface can be modified by using the Protocol Editing Tool. These tools are included in CAP 505. For more information on the REC 523 protocols, refer to the technical reference manual of REC 523 (see Section 1.6. Related documents).

5.5.

Downloading the configuration


After the configuration has been built and succesfully compiled in the Relay Configuration Tool and the MIMIC configuration has been designed, the project can be downloaded to the device.

57

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

The parts of the project to be downloaded are selected via a dialog box. The MIMIC configuration and the Relay Configuration Tool project can be downloaded separately. The project can also be downloaded separately as a compressed file. This enables later uploading of the project from the device. The compressed file is automatically created if the check box RCT project has been selected (see Fig. 5.5.-1). The target device has an inherent limitation over the size of a stored project file. If this is exceeded, the tool interrupts the downloading and issues a warning. It is useful to include some information of the project in the file by giving, for example, the name of the designer, the date and the version or other description of the configuration. To add project information, select File > Project Info in the Relay Configuration Tool. Add-on protocols (for example Modbus and IEC 60870-5-103) of the relay terminal are activated in the relay according to Add-On protocol selection in object properties.

Fig. 5.5.-1 Selecting RCT project (for REC 523, the mimic configuration is not available) When the configuration is downloaded, the total CPU load in percent can be checked via the parameter Config. capacity. In the Relay Setting Tools Main menu view, select the Configuration tab and the General subtab to view Config. capacity parameter (on the device, select MAIN MENU/Configuration/ General/Config. capacity). If the load exceeds 100%, the downloading fails, an indication Failed is displayed in the assisting window of the REF 54_,

58

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

REM 54_ or RET 54_ display, and a message appears in the CAP 505. The exceeded CPU load can also be read via the parameter after a failed downloading, that is, the load value can be for example 115%. Whenever downloading fails, a storing sequence cannot be started but the device must be reset before next downloading. Moreover, the device is automatically reset after a failed downloading when the download dialog box in the Relay Download Tool is closed. Note that the exceeded CPU load must be checked before resetting; after the device is restarted, the parameter Config. capacity only shows the load of the previous configuration that was downloaded succesfully and has become valid again.

5.5.1.

REF 54_ Release 2.5, RET 54_ and REC 523 revision F additions
The REF 54_ Release 2.5 and later, REC 523 revision F and RET 54_ includes the following functions supported by the Configuration Download Tool: Relay and configuration tool compatibility checking Improved configuration error reporting Easier identification of the relay configuration

Compatibility checking
The download tool verifies that the connected relay matches the type and revision set in the relay configuration. If a mismatch occurs, downloading is not allowed.

comp

Fig. 5.5.-2 Relay type mismatch when downloading the configuration The download tool also prevents downloading, if the configuration has been modified after the last compilation.

59

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Improved configuration error reporting


After downloading the configuration, the relay checks, that all the function block specific requirements regarding analog channel configuration and task cycle time are fulfilled. If errors are detected, a list containing all errors is shown. The list contains the name of the function block that reported the error and a plain text error description. The error list can be copied to the clipboard and printed by using any text editor for easy reference when correcting the configuration.

err

Fig. 5.5.-3 Example of an error list when downloading an incorrect configuration

Configuration identification
The relay contains parameters for configuration identification: Title Author Last modification date Last download date of the configuration program

A parameter is also included to identify the bay in which the configuration is used. The title and author are set from the File > Project info menu of the Relay Configuration Tool. The bay name is taken from the bay object in the project structure navigator or from the protection and control object, if no bay object is used. The last download/modification date parameters are set automatically. The Download Tool shows the identification data of the present configuration and the new configuration, and asks the user to verify, that the present configuration can be overwritten before proceeding with the download.

60

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

The configuration identification data can also be viewed from the relay (menu path Information/Configuration) and the Relay Setting Tool (open the Information tab and select the Configuration subtab). Note that the relay stores a maximum of 15 characters for each configuration identification parameter, although more characters are allowed in the Relay Configuration Tool.

trace

Fig. 5.5.-4 Relay configuration identification

61

62

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

6.
6.1.

Main configuration rules


General
Make sure that all analog signals are connected and all necessary inputs and outputs are wired. Note that the outputs of function blocks may not be connected together. There are also many other FBD programming rules to follow. One of the most typical rules is not to use the wired-OR connection. All signals that are connected to the same output signal (both output relays and horizontal communication outputs) must be connected via an OR gate (see Fig. 6.1.-1).

PS1_4_HSPO1

TRIP I> OR TRIP I>> PS1_4_HSPO1

I>
PS1_4_HSPO1

I>>

"wired-OR" structure is not allowed

an explicit Boolean "OR" block is required instead


ORgate

Fig. 6.1.-1 Use of an explicit Boolean OR gate (on the right)

6.2.

Digital inputs and outputs


Digital inputs and outputs of RED 500 devices are implemented as directly represented global variables. As such, they are special cases and their use in the configuration is limited. Directly represented variables are declared in the Global Variables sheet of the project tree. They can be recognized by the AT keyword as in the examples below.
BIO1_5_BI1 BIO2_7_PO1 AT %IX 1.8.2 AT %QX 1.13.2 :BOOL := FALSE; :BOOL := FALSE; ( *Binary input X5.1/1,2 *) ( *Single pole output X7.1/17,18 *)

Note that the parts of the line following the AT keyword may not be changed. Only the name of the signal, that is, the part before the AT keyword, may be changed if required. If the names are adapted to the logical meanings of the signals, the user is encouraged to create and to follow a naming convention. The name should indicate, apart from the logical meaning, whether the signal is an input or output signal. Examples of such names following a naming convention could be:
Q9_close_sta_IN Q9_close_cmd_OUT AT %IX 1.8.2 AT %QX 1.13.2 :BOOL := FALSE; :BOOL := FALSE; (* Binary input X5.1/1,2 *) (* Single pole output X7.1/17,18 *)

Access direction for the directly represented variables is restricted by their purpose. This means that a digital input can be read but not written, see Fig. 6.2.-1 below. Accordingly, an output can be written but not read. Note that an input can be read from several locations within a worksheet and even from any program organisation unit within the configuration, whereas an output can only be written from one location at a time.
63

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Digital3

Fig. 6.2.-1 Neither writing a digital input nor reading a digital output is allowed

6.3.

Explicit feedback path


A feedback path exists on the FBD worksheet when an output of a function block is used as an input to a function block that precedes it in the execution order. There are two types of feedback paths, an explicit and an implicit feedback loop (see Fig. 6.3.1 and Fig. 6.3.-2 below). It is strongly recommended that explicit feedback loops are changed to implicit loops by using a feedback variable. The Relay Configuration Tool can detect explicit loops during compilation. If you click the checked command Display warnings in the Make menu, the compiler gives warnings about the detected explicit feedback loops. To view the feedback loops, select the checked command Highlight feedback in the Layout menu. The execution order of functions compared to the expected behaviour may in some cases dictate where the feedback variable should be added (for instructions on how to view the execution order, refer to Section 6.7. Execution order). The initial value of the feedback variable should also be selected with care.

64

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

ExplFeedbck

Fig. 6.3.-1 Explicit feedback loop is detected and highlighted

ImplFeedbck

Fig. 6.3.-2 Implicit feedback via the local variable FEEDBACK

6.4.

Analog inputs
Analog channels defined in the resource can be connected to the analog inputs of application function blocks on a code body worksheet. Most of the function blocks with several analog inputs support unconnected inputs. For example, in Fig. 6.4.-1 below, the function block NOC3Low operates on only two inputs. The third and unused input constantly measures a zero current amplitude. This function block only requires that at least one of the three inputs is connected. On the other hand, certain function blocks require that all analog inputs are connected. An example of such a function block is OV3Low (see Fig. 6.4.-1 below). If the analog channel requirements of a function block are violated, a configuration error is generated. For more information on how analog inputs are expected to be connected, refer to the function block manuals on the CD-ROM Technical Descriptions of Functions, see Section 1.6. Related documents.

65

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Analog channels connected to application function blocks may not be changed runtime. Therefore, do not use any selectors between analog channels and function blocks.

analog_inputs3

Fig. 6.4.-1 Connecting analog inputs of application function blocks. Do not use a selector to switch between channels.

6.5.

Error outputs of application function blocks


If a configuration for a function block is not correct, its ERR output is activated immediately after configuration downloading and the function block is forced to the Not in use mode. In this case, application function blocks that have the Operation mode parameter in their actual setting menu display the Not in use operation mode, regardless of which mode has been selected for the parameter in the setting group menu. Currently, with most function blocks, this will result in an automatic resetting, without storing, of the relay. The automatic reset does not occur in REM 54_. The error signals of all application function blocks should be collected together via an OR gate and connected to, for example, an HMI alarm indication of REF 54_ or REM 54_, that is, an MMIALAR_ function block. Detecting any untreated configuration errors is fast and easy when the error signals of all application function blocks are collected together via an OR gate and connected to MMIALAR_ function block. Configuration errors typically originate from missing special measurements, the type, order or number of analog channels connected to function blocks, or task interval requirements.

66

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

6.6.

Warnings
In case of the indication Warning: Instance xx is never used in connection with compilation, remove the corresponding instances of the function block from the variables worksheet of the POU. The tool does not give a warning for unused variables, which is why they are recommended to be removed manually. When a global variable is added to a sheet as a copy-paste -function, the Global option button has to be chosen (see figure below properties can be accessed by double-clicking the right mouse button); otherwise the variable becomes a local variable of the POU, which is due to the auto-insert feature of the tool (global variable = VAR_EXTERNAL, local variable = VAR).

radio

Fig. 6.6.-1 Copying a global variable to a worksheet of a POU

6.7.

Execution order
After compilation, check the execution order in relation to the calling sequence of POUs by using the Layout Execution Order function. Note, however, that although the connection of simple variables to each other generates code, the execution order cannot be seen by means of the Layout Execution Order function. If the MOVE function is used instead of direct connection, the execution order can be utilised in concluding whether the result is desirable, for example, the reading and writing order of the variables.

MoveExpl

Fig. 6.7.-1 Direct connection of variables and a connection via the MOVE function

67

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

EXECUTIObw

Fig. 6.7.-2 The INTERLOCKING variable is updated (TMP1) during the task execution cycle (see the execution order 1,2,3) In addition, the execution order may be illogical or even incorrect considering the functionality.

EXECUTE2bw

Fig. 6.7.-3 The implicit feedback (TMP1) delays the updating of the INTERLOCKING variable by one task execution cycle

6.8.

F-key
The freely programmable F-key of REF 54_, REM 54_ and RET 54_ is declared as VAR_GLOBAL in the global variable worksheet as follows:
F001V021:BOOL:=0; (* (R, W) Free configuration point (F-key) *)

The F-key parameter can be added to the configuration logic as an external variable (VAR_EXTERNAL).

68

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

medrec6

Fig. 6.8.-1 Example of using F-key with the disturbance recorder function block MEDREC16 The variables below are internal variables of the system and are thus not recommended to be used like the F-key parameter.
F001V011:BOOL:=0; F001V012:BOOL:=0; F001V013:BOOL:=0; F001V020:BOOL:=0; F002V004:BOOL:=0; F002V005:USINT:=0; F002V006:BOOL:=0; F900V251:BOOL:=0; F900V252:BOOL:=0; F000V251:BOOL:=0; F000V252:BOOL:=0; (* (* (* (* (* (* (* (* (* (* (* (W) Resetting of operation indications (W) Resetting of operation indications & latched output signals (W) Resetting of operation indications, latched output signals & waveform memory (W) Resetting of accumulated energy measurement (R, W) Control: Interlocking bypass mode for all control objects (Enables all) (W) Control: Recent control position (W) Control: Virtual LON input poll status (W) Control: Execute all command for selected objects (inside module) (W) Control: Cancel all command for selected objects (inside module) (W) Control: Execute all command for selected objects (inside module) (W) Control: Cancel all command for selected objects (inside module) *) *) *) *) *) *) *) *) *) *) *)

69

70

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

7.
7.1.

Engineering tips
Horizontal communication
This example includes four (4) bays. The logic is basically the same in every bay. The intention of this guideline is to point out how to ensure the horizontal inter-bay communication, including correct state indication of control objects via LON communication. The logic also includes an alarm function in case of a broken fibre optic. Incorrect updating of interlocking information blocks the control of objects, but the blocking can be bypassed by setting the device to the bypass mode.

7.1.1.

Guideline for using LON NV-variables in PLC logic


Communication between terminals is executed by using the communication input and output signals (global variables COMM_IN_ and COMM_OUT_). The logic must be designed in a Relay Configuration Tool project. The LON network variable bindings can be created with the LON Network Tool. Communication inputs and outputs are bound to each other on a one-to-one basis by means of unacknowledged repeated unicast service. The signals are named so that the number at the end of COMM_OUT_ (for example COMM_OUT2) denotes the bay to which the signal is sent. Accordingly, the number at the end of COMM_IN_ denotes the bay from which the signal is received. This way, COMM_OUT2 of bay 1 is bound to COMM_IN1 of bay 2.

7.1.1.1.

COMM_IN
COMM_IN_ signals are converted into Boolean logic mode by INT2BOOL function blocks. The B0 output signal (BLOCK1) in an INT2BOOL function block is used for blocking the control of objects except for the one that is sending the signal. In other words, only one object can be controlled at a time. Furthermore, Comm-Check_ signals are used for checking the condition of fibre optics. Signals for bay interlocking are also received. See Fig. 7.1.1.1.-1.

71

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

comm_in

Fig. 7.1.1.1.-1 Example of the COMM_IN logic

7.1.1.2.

COMM_OUT
Communication signals sent from one bay to other bays include the reservation of control objects, updating of communication output signals and some indications needed in other bays. Overall, digital signals are sent via LON and converted from Boolean logic to unsigned integer (UINT, 16 bits) values.

72

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

comm_out

Fig. 7.1.1.2.-1 Example of the COMM_OUT logic

7.1.1.3.

Cyclic sending generation


The logic below shows an example of how the cyclic sending of communication output signals can be generated. The idea is to generate a boolean signal with a 5-second pulse duration and a 50-percent duty cycle.

update all

Fig. 7.1.1.3.-1 Example of generating the cyclic sending of communication output signals

73

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

7.1.1.4.

Cyclic communication check


Timers check the horizontal communication The timers activate an alarm signal as a result of failed communication (Bay__Comm_Failed) 15 seconds after the new value of a Comm-Check_ signal has been received. Comm_Check_ signals are updated every 5 seconds, which affects the TON timer functions thus preventing the activation of Q output signals. If the communication fails, all four bays are blocked.

check

Fig. 7.1.1.4.-1 Cyclic communication check

7.1.1.5.

Blocking
If horizontal communication has failed, the BLOCK2 signal is sent to every controllable function block to prevent the control of local objects. Furthermore, the HMI alarm indication 8 (in REF 54_ , REM 54_ or RET 54_) is activated. The BLOCK1 signal is used to create a mutual exclusion effect between bays. The signal is activated by horizontal communication when a control object is selected in one of the other bays.

74

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

BLOCK

Fig. 7.1.1.5.-1 Blocking the control of objects

7.1.1.6.

Control of objects
The control of an object, for example a breaker, can be executed if the BLOCK input is not active (TRUE). Accordingly, an object cannot be controlled during the reservation of other objects (in the same bay or in other bays) or the failing of horizontal communication. However, the blocking can be bypassed by setting the terminal to the bypass mode (MAIN MENU/Control/General/Interlocking Bypass). The bypass mode overrides interlockings provided the bypass signal is included in the logic (see also Section 7.1.1.7. Bypass mode).

Q1

Fig. 7.1.1.6.-1 Defining the bypass mode for the control object

75

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

7.1.1.7.

Bypass mode
The bypass mode signal can be generated in the logic via the COLOCAT function block. After activation of the bypass mode, the BYPASS signal is active and therefore prevents activation of the BLOCK input.

bypass

Fig. 7.1.1.7.-1 Generation of the bypass mode signal

7.2.

Events from the measurement function blocks SPA protocol used


Measurement values have to be polled because they are not sent with events. Thereby the delta supervision events of the measurement function blocks can be masked off. If limit supervision is set to be done by RTU, the limit event sending must be allowed in event masks. In this case, the client is informed of the activation and resetting of each limit with the corresponding event code numbers.

LON protocol used


Each measured variable is individualized by an IEC address. Measurement values and the corresponding IEC addresses are sent to a client, for example to MicroSCADA, with both delta supervision events and limit supervision events. The limit supervision events are not recommended to be masked off if limit supervision is used. When the warning and alarm limit supervision is active, the priority for limit event sending is higher than that for delta event sending if both type of events are sent concurrently. Concurrent event sending appears, for example, when a measured value changes considerably during a short period, for example when a circuit breaker is closed or opened. This causes problems if limit supervision events have been masked off since the client does not receive all measurement values even if major changes have taken place.

76

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

8.

APPENDIX A: Relay configuration procedure

1. Create a new project 2. Create a tree structure a) Libraries b) Logical POU framework (programs and function blocks) c) Physical Hardware i) configuration ii) resource - hardware version - used analog channels and measurement signal types - digital inputs - power and energy measurement - condition monitoring (circuit breaker breaker wear) iii) tasks - connection between program and task - task interval d) Logical POU contents 3. Design logics 4. Check variable declarations a) Data types and initialisers b) Instances of functions and function blocks c) Variable categories i) VAR - END_VAR ii) VAR_EXTERNAL - END_VAR iii) VAR_INPUT - END_VAR iv) VAR_OUTPUT - END_VAR v) VAR_GLOBAL - END_VAR 5. Compile a project 6. If an add-on protocol (DNP 3.0 or Modbus) is used, create protocol mapping. 7. Download it to the device

77

78

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

9.
9.1.

APPENDIX B: Specification for REF 54_ feeder terminal configuration


General data

Project name:

Date:

This specification suitable for bays:

Substation name:

Feeder terminal type:

Software revision

Order number: REF54 __ __ __ __ __ __ __ __ __ __(for

example REF543HC127AAAA)

Handled by:

Company:

Telephone number:

Fax number:

This document serves as a technical specification of substation protection and is used for the configuration of REF 54_ feeder terminals. Special requirements can be specified under Further information at the bottom of each page.

79

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.2. 9.2.1.

Electrotechnical data Analog inputs


Table 9.2.1-1
Channel 1 2...5 6 7...10

Analog input channel connections

Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider or general measurement Current transformer Voltage transfomer, Rogowski sensor, voltage divider or general measurement

Further information:

Module type MIM

Board X1.1 27 25 24 22 21 19 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

Terminal number

Connected object

Signal type

100V

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:24 X1.1:19, X1.1:21 X1.1:16, X1.1:18 X1.1:13, X1.1:14, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT4 VT3 VT2 VT1 CT5 CT4 CT3 CT2 CT1

100V

100V

100V
0,2A 1A

1A 5A

1A 5A

1A 5A

MIMX1.1.fh8

1A 5A

MIMX1.1

80

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type SIM

Board X2.1
DIFF

Terminal number Ch 10, sensor Ch 9, sensor Ch 8, sensor Ch 7, sensor Ch 5, sensor Ch 4, sensor Ch 3, sensor Ch 2, sensor Ch 1, sensor X2.1 X2.2 X2.3 X2.4 X2.5 X2.6 X2.7 X2.8 X2.9

Connected object

Signal type

X2.2
DIFF

X2.3
DIFF

X2.4
DIFF

X2.5
DIFF

X2.6
DIFF

X2.7
DIFF

X2.8
SIMX2.fh8
DIFF

X2.9
DIFF

Simx2

The measuring device can be connected exclusively to the analog channels of either MIM or SIM type modules. Ten channels are available. Further information:

9.2.2.

System frequency
50 Hz 60 Hz

9.2.3.

Digital inputs
Module type PS1 (REF541, REF543) Board X4.2 1 2 4 5 6 7 Terminal number Connected object

PS1_4_BI1 PS1_4_BI2 PS1_4_BI3

X4.2:1, X4.2:2 X4.2:4, X4.2:5 X4.2:6, X4.2:7

1) 1) 1)

PS1X4.2.fh8

1) Digital input / counter input


PS1X4.2

81

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type BIO1

Board X5.1 1 2 3 4 5 6 7 8 9

Terminal number

Connected object

BIO1_5_BI1 BIO1_5_BI2 BIO1_5_BI3 BIO1_5_BI4 BIO1_5_BI5 BIO1_5_BI6 BIO1_5_BI7 BIO1_5_BI8 BIO1_5_BI9 BIO1_5_BI10 BIO1_5_BI11

X5.1:1, X5.1:2 X5.1:2, X5.1:3 X5.1:4, X5.1:5 X5.1:5, X5.1:6 X5.1:7, X5.1:8 X5.1:8, X5.1:9 X5.1:10, X5.1:11 X5.1:11, X5.1:12 X5.1:13, X5.1:14 X5.1:15, X5.1:16 X5.1:17, X5.1:18 1) 1) 1)

10 11 12 13 14 15 16 17 18

BIO1X5.1.fh8

1) Digital input / counter input


BIO1X5.1

Module type BIO1 (REF 545)

Board X6.1 1 2 3 4 5 6 7 8 9

Terminal number

Connected object

BIO1_6_BI1 BIO1_6_BI2 BIO1_6_BI3 BIO1_6_BI4 BIO1_6_BI5 BIO1_6_BI6 BIO1_6_BI7 BIO1_6_BI8 BIO1_6_BI9 BIO1_6_BI10 BIO1_6_BI11

X6.1:1, X6.1:2 X6.1:2, X6.1:3 X6.1:4, X6.1:5 X6.1:5, X6.1:6 X6.1:7, X6.1:8 X6.1:8, X6.1:9 X6.1:10, X6.1:11 X6.1:11, X6.1:12 X6.1:13, X6.1:14 X6.1:15, X6.1:16 X6.1:17, X6.1:18 1) 1) 1)

10 11 12 13 14 15 16 17 18

1) Digital input / counter input


A060620

Further information:

82

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type BIO1

Board X5.2
BIO1X5.2.fh8

Terminal number

Connected object

1 2

BIO1_5_BI12

X5.2:1, X5.2:2

1)

1) Digital input/ counter input/ time sync


BIO1X5.2

Module type BIO2 (REF543, REF545)

Board

Terminal number

Connected object

X7.1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 BIO2_7_BI1 BIO2_7_BI2 BIO2_7_BI3 BIO2_7_BI4 BIO2_7_BI5 BIO2_7_BI6 BIO2_7_BI7 BIO2_7_BI8 BIO2_7_BI9 BIO2_7_BI10 X7.1:1, X7.1:2 X7.1:2, X7.1:3 X7.1:4, X7.1:5 X7.1:5, X7.1:6 X7.1:7, X7.1:8 X7.1:8, X7.1:9 X7.1:10, X7.1:11 X7.1:11, X7.1:12 X7.1:13, X7.1:14 X7.1:15, X7.1:16 1) 1)

BIO2X7.1.fh8

1) Digital input / counter input


BIO2X7.1

Further information:

83

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.2.4.

Digital outputs
Module type Connected object PS1 (REF541, REF543) 1) X4.1:1, X4.1:2 1) PS1_4_TempAlarm Terminal number PS1_4_ACFail Board X4.1 1 2 X4.1 3 4

+
Mains

X4.1:3, X4.1:4, X4.1:5

IRF

5 6 X4.1:6, X4.1:7, X4.1:8, X4.1:9 7 9 8 10 X4.1:10, X4.1:11, X4.1:12, X4.1:13 1) PS1_4_HSPO1 PS1_4_TCS1 TCS1 11 13 12 15 PS1_4_HSPO2 PS1_4_TCS2 TCS2 16 18 17
PS1X4.1.fh8 PS2X4.1.fh8

PS1_4_HSPO3

X4.1:15, X4.1:16, X4.1:17, X4.1:18 1)

1) Please indicate whether the trip circuit supervision inputs will be configured to use or not

PS1X4.1
Board X4.1 1 2 X4.1 3 4

Module type Connected object PS2 (REF545) 1)

Terminal number PS2_4_ACFail X4.1:1, X4.1:2 1) PS2_4_TempAlarm

+
Mains

X4.1:3, X4.1:4, X4.1:5

IRF

5 6 X4.1:6, X4.1:7, X4.1:8, X4.1:9 7 9 8 10 X4.1:10, X4.1:11, X4.1:12, X4.1:13 1) PS2_4_HSPO1 PS2_4_TCS1 TCS1 11 13 12 15 X4.1:15, X4.1:16, X4.1:17, X4.1:18 1) PS2_4_HSPO2 PS2_4_TCS2 TCS2 16 18 17

PS2_4_HSPO3

1) Please indicate whether the trip circuit supervision inputs will be configured to use or not

PS2X4.1

Further information:

84

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type Connected object PS1 (REF541, REF543)

Terminal number

Board X4.2 8

X4.2:8, X4.2:9, X4.2:10, X4.2:11

PS1_4_HSPO4

9 11 10 12 13 15 14 16 17

X4.2:12, X4.2:13, X4.2:14, X4.2:15

PS1_4_HSPO5

X4.2:16, X4.2:17, X4.2:18

PS1_4_SO1

18

PS1X4.2o
Module type Connected object PS2 (REF545) X4.2:1, X4.2:2, X4.2:3, X4.2:4 Terminal number Board X4.2 1 PS2_4_HSPO4 2 4 3 5 6 8 7 9 10 12 11 13 14 16 15 17 18

X4.2:5, X4.2:6, X4.2:7, X4.2:8

PS2_4_HSPO5

X4.2:9, X4.2:10, X4.2:11, X4.2:12

PS2_4_HSPO6

X4.2:13, X4.2:14, X4.2:15, X4.2:16

PS2_4_HSPO7

X4.2:17, X4.2:18

PS2_4_HSPO8

PS2X4.2o

Further information:

85

PS2X4.2o.fh8

PS1X4.2o.fh8

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type Connected object BIO1

Terminal number

Board X5.2 3

X5.2:3, X5.2:4

BIO1_5_SO1

4 5 6

X5.2:5, X5.2:6

BIO1_5_SO2

7 9
8 10 12

X5.2:7, X5.2:8, X5.2:9

BIO1_5_SO3

X5.2:10, X5.2:11, X5.2:12

BIO1_5_SO4

11 13 15 14
BIO1X5.2o.fh8 BIO1X6.2.fh8

X5.2:13, X5.2:14, X5.2:15

BIO1_5_SO5

16 18 17

X5.2:16, X5.2:17, X5.2:18

BIO1_5_SO6

BIO1X5.2o
Module type Connected object BIO1 (REF545) X6.2:3, X6.2:4 BIO1_6_SO1 Terminal number Board X6.2 3 4 5 6 7 9 8 10 12 11 13 15 X6.2:13, X6.2:14, X6.2:15 BIO1_6_SO5 14 16 18 17

X6.2:5, X6.2:6

BIO1_6_SO2

X6.2:7, X6.2:8, X6.2:9

BIO1_6_SO3

X6.2:10, X6.2:11, X6.2:12

BIO1_6_SO4

X6.2:16, X6.2:17, X6.2:18

BIO1_6_SO6

BIO1X6.2

Further information:

86

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type Connected object BIO2 (REF543, REF545)

Terminal number

Board X7.1
BIO2X7.1o.fh8

X7.1:17, X7.1:18

BIO2_7_PO1

17 18

BIO2X7.1o

Module type Connected object BIO2 (REF543, REF545)

Terminal number

Board X7.2

X7.2:1, X7.2:2

BIO2_7_PO2

1 2 3

X7.2:3, X7.2:4, X7.2:5, X7.2:6

BIO2_7_PO3

4 6 5 7

X7.2:7, X7.2:8, X7.2:9, X7.2:10

BIO2_7_PO4

8 10 9 11 12 14 13 15

X7.2:11, X7.2:12, X7.2:13, X7.2:14

BIO2_7_PO5

X7.2:15, X7.2:16, X7.2:17, X7.2:18

BIO2_7_PO6

16 18 17

BIO2X7.2

Further information:

87

BIO2X7.2.fh8

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.2.5. 9.2.5.1.

RTD module RTD/analog inputs


Module type RTD1 (REF541, REF543) Board X6.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Terminal number
SHUNT

Connected object

1)

+ SHUNT SHUNT

RTD1_6_AI1
DIFF

X6.1:1, X6.1:2, X6.1:3

RTD1_6_AI2
DIFF

X6.1:5, X6.1:6, X6.1:7

+ SHUNT SHUNT

RTD1_6_AI3
DIFF

X6.1:8, X6.1:9, X6.1:10

RTD1_6_AI4
DIFF

X6.1:12, X6.1:13, X6.1:14

+ -

RTD1_6_AI5
DIFF

X6.1:15, X6.1:16, X6.1:17

X6.2 1 2 3 4 5 6 7 8 9 10
SHUNT

SHUNT SHUNT

DIFF

RTD1_6_AI6 X6.2:1, X6.2:2, X6.2:3

+ +

RTD1_6_AI7 X6.2:4, X6.2:5, X6.2:6


DIFF

RTD1X6._.fh8

RTD1_6_AI8 X6.2:7, X6.2:8, X6.2:9


DIFF

1) Current transducer / voltage transducer / resistance sensor

RTD1X6._

Further information:

88

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

9.2.5.2.

RTD outputs
Module type RTD1 (REF541, REF543) X6.2:11, X6.2:12 RTD1_6_AO1 Connected object Terminal number Board X6.2

+ mA+ mA+ mA+ mA-

11 12

X6.2:13, X6.2:14

RTD1_6_AO2

13 14

X6.2:15, X6.2:16

RTD1_6_AO3

15 16 17 18

X6.2:17, X6.2:18

RTD1_6_AO4

RTD1X6.2

Further information:

9.3. 9.3.1.

Functionality Order number


REF54 __ __ __ __ __ __ __ __ __ __ (for example REF543HD127AAAA)

89

RTD1X6.2.fh8

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.3.2.

Application function blocks used


The lists below represent the full set of function blocks, but the selected functionality level (indicated by a letter in the order number, for example REF543HC127AAAA) determines the function blocks available for the configuration. Note that optional functions, that is, those selectable in addition to the functions included in a functionality level, are listed separately.

Protection AR5Func CUB3Low DEF2Low DEF2High DEF2Inst DOC6Low DOC6High DOC6Inst Freq1St1 Freq1St2 Freq1St3 Freq1St4 Freq1St5 Fusefail Inrush3 MotStart NEF1Low NEF1High NEF1Inst NOC3Low NOC3High NOC3Inst OV3Low OV3High PSV3St1 PSV3St2 ROV1Low ROV1High ROV1Inst SCVCSt1 SCVCSt2 TOL3Cab TOL3Dev UV3Low UV3High

Measurement MEAI1 MEAI2 MEAI3 MEAI4 MEAI5 MEAI6 MEAI7 MEAI8 MEAO1 MEAO2 MEAO3 MEAO4 MECU1A MECU1B MECU3A MECU3B MEDREC16 MEFR1 MEPE7 MEVO1A MEVO1B MEVO3A MEVO3B

Control COCB1 COCB2 COCBDIR CO3DC1 CO3DC2 CODC1 CODC2 CODC3 CODC4 CODC5 COIND1 COIND2 COIND3 COIND4 COIND5 COIND6 COIND7 COIND8 COLOCAT COSW1 COSW2 COSW3 COSW4 MMIALAR1 MMIALAR2 MMIALAR3 MMIALAR4 MMIALAR5 MMIALAR6 MMIALAR7 MMIALAR8 MMIDATA1 MMIDATA2 MMIDATA3 MMIDATA4 MMIDATA5

90

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Condition monitoring CMBWEAR1 CMBWEAR2 CMCU3 CMGAS1 CMGAS3 CMSCHED CMSPRC1 CMTCS1 CMTCS2 CMTIME1 CMTIME2 CMTRAV1 CMVO3

Communication EVENT230

General INDRESET MMIWAKE SWGRP1 SWGRP2 SWGRP3 SWGRP4 SWGRP5 SWGRP6 SWGRP7 SWGRP8 SWGRP9 SWGRP10 SWGRP11 SWGRP12 SWGRP13 SWGRP14 SWGRP15 SWGRP16 SWGRP17 SWGRP18 SWGRP19 SWGRP20

Optional functions COPFC CUB1Cap CUB3Cap FLOC OL3Cap PQCU3H PQVO3H PQVO3Sd

9.3.3.

Communication
Protocol used: Port X3.2 Modbus DNP 3.0 IEC 60870-5-103 SPA Port X3.3 LON SPA

91

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.3.4.

Virtual channels
Virtual meas. I0s I0bs U0s U0bs U12s U23s U31s U12bs U23bs U31bs Channel number Analog meas. 1 IL1 IL1b U1 U1b U1 U2 U1 U1b U2b U1b Channel number Analog meas. 2 IL2 IL2b U2 U2b U2 U3 U3 U2b U3b U3b Channel number Analog meas. 3 IL3 IL3b U3 U3b Channel number

Further information:

92

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

9.4. 9.4.1.

Relay MIMIC configuration Illustration of the system, MIMIC diagram

Symbol used Disconnector: (truck symbols)

closed

open

undef. 0 0

undef. 1 1

Circuit breaker:

Earth switch:

Further information:

93

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

9.4.2.

Alarm LEDs
Fill in the table below to describe the legend text used as well as the flashing sequence and colour of the LEDs.

Table 9.4.2-1
LED OFF state

Descriptions for legend texts and LEDs


ON state
Colour Flashing Text seq. (max. 16 characters) Colour Flashing seq.

Text (max. 16 characters)

off green yellow red latched, blinking latched, steady non-latched, blinking

1 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 2 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 3 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 7 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 8 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Interlocking _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Control test mode _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ X X X X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Further information:

94

off green yellow red latched, blinking latched, steady non-latched, blinking

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

9.5.

Functionality logic
Please specify the required special PLC logic functionality (see the examples below), by drawing or otherwise, on separate sheets and enclose all additional information with this document (Specification for Feeder Terminal Configuration). Example 1: Earthing sequence Earthing of the outgoing feeder can be done by a circuit breaker when an earthing sequence is activated, an earthing switch is earthed and no voltage is measured. If all conditions are fulfilled, the circuit breaker can be closed after 1 second. The figure below shows the implementation of the desired logic.

Earthing

Example 2: Usage of the F-key and a software switch

F key

95

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Example 3: Voltage measurement in the MIMIC view Phase-to-phase voltage must be shown in voltages [V] in the MIMIC view.

Voltage

9.6.

Feeder terminal settings


Responsibility: The end user defines the feeder terminal settings Feeder terminal settings according to the turn-key principle The setting of the parameters is not part of the configuration. The end user will normally be responsible for the setting parameters.

Further information:

96

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.
10.1.

APPENDIX C: Specification for REM 54_ machine terminal configuration


General data
Project name: Date:

This specification suitable for bays:

Substation name:

Machine terminal type:

Software revision

Order number: REM54 __ __ __ __ __ __ __ __ __ __ (for

example REM543BM212AAAA)

Handled by:

Company:

Telephone number:

Fax number:

This document serves as a technical specification of substation protection and is used for the configuration of REM 54_ machine terminals. Special requirements can be specified under Further information at the bottom of each page.

97

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.2. 10.2.1. 10.2.1.1.

Electrotechnical data Analog inputs Hardware versions with 5 current and 4 voltage transformers
Table 10.2.1.1-1 Analog input channel connections
Channel 1 2...5 6 7...10 Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider or general measurement Current transformer Voltage transfomer, Rogowski sensor, voltage divider or general measurement

The sensor inputs are shown in Section 10.2.1.5. Sensor inputs.


Module type Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021227 AA_/CA_ 25 24 22 21 19 18 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

100V

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:24 X1.1:19, X1.1:21 X1.1:16, X1.1:18 X1.1:13, X1.1:14, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT4 VT3 VT2 VT1 CT5 CT4 CT3 CT2 CT1

100V

100V

100V 0.2A 1A 1A 5A 1A 5A 1A 5A 1A 5A

Further information:

98

RemMim1

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.1.2.

Hardware versions with 6 current and 3 voltage transformers


Channel 1 2...4 5 6 7...9 10 Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer Current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer, Rogowski sensor, voltage divider or general measurement

The sensor inputs are shown in Section 10.2.1.5. Sensor inputs.


Module type Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021427 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 13 12 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT3 CT6 CT5 CT4 VT2 VT1 CT3 CT2 CT1

100V

100V 1A 5A 1A 5A 1A 5A

RemMim2

RemMim2

Further information:

99

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.2.1.3.

Hardware versions with 7 current and 2 voltage transformers


Channel 1 2...5 6 7...9 10 Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer Current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer, Rogowski sensor, voltage divider or general measurement

The sensor inputs are shown in Section 10.2.1.5. Sensor inputs.


Module type Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021627 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 13 12 11 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT2 CT7 CT6 CT5 VT1 CT4 CT3 CT2 CT1

100V 1A 5A 1A 5A 1A 5A 1A 5A

RemMim3

RemMim3

Further information:

100

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.1.4.

Hardware versions with 8 current and 1 voltage transformer


Channel 1 2...5 6 7...9 10 Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider or general measurement Current transformer Current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer, Rogowski sensor, voltage divider or general measurement

The sensor inputs are shown in Section 10.2.1.5. Sensor inputs.


Module type Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021827 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:14, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT1 CT8 CT7 CT6 CT5 CT4 CT3 CT2 CT1

RemMim4

RemMim4

Further information:

101

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.2.1.5.

Sensor inputs
Module type SIM Board X2.1
DIFF

Terminal number Ch 10, sensor Ch 9, sensor Ch 8, sensor Ch 7, sensor Ch 5, sensor Ch 4, sensor Ch 3, sensor Ch 2, sensor Ch 1, sensor X2.1 X2.2 X2.3 X2.4 X2.5 X2.6 X2.7 X2.8 X2.9

Connected object

Signal type

X2.2
DIFF

X2.3
DIFF

X2.4
DIFF

X2.5
DIFF

X2.6
DIFF

X2.7
DIFF

X2.8
SIMX2.fh8
DIFF

X2.9
DIFF

The measuring device can be connected exclusively to the analog channels of either MIM or SIM type modules. Ten channels are available.
Simx2

Further information:

10.2.2.

System frequency

50 Hz

60 Hz

102

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.3.

Digital inputs
Module type PS1 Board X4.2 1 2
PS1X4.2b.fh8

Terminal number

Connected object

PS1_4_BI1 PS1_4_BI2 PS1_4_BI3

X4.2:1, X4.2:2 X4.2:4, X4.2:5 X4.2:6, X4.2:7

1) 1) 1)

4 5 6 7

1) Digital input / counter input

PS1X4.2b
Module type BIO1 Board X5.1 1 2 3 4 5 6 7 8 9 Terminal number Connected object

BIO1_5_BI1 BIO1_5_BI2 BIO1_5_BI3 BIO1_5_BI4 BIO1_5_BI5 BIO1_5_BI6 BIO1_5_BI7 BIO1_5_BI8 BIO1_5_BI9 BIO1_5_BI10 BIO1_5_BI11

X5.1:1, X5.1:2 X5.1:2, X5.1:3 X5.1:4, X5.1:5 X5.1:5, X5.1:6 X5.1:7, X5.1:8 X5.1:8, X5.1:9 X5.1:10, X5.1:11 X5.1:11, X5.1:12 X5.1:13, X5.1:14 X5.1:15, X5.1:16 X5.1:17, X5.1:18 1) 1) 1)

10 11 12 13 14 15 16 17 18

BIO1X5.1.fh8

1) Digital input / counter input

BIO1X5.1

Further information:

103

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type BIO1

Board X5.2
BIO1X5.2.fh8

Terminal number

Connected object

1 2

BIO1_5_BI12

X5.2:1, X5.2:2

1)

1) Digital input/ counter input/ time sync

BIO1X5.2
Module type BIO2 (RET 543) (RET 545) Board X7.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 BIO2_7_BI1 BIO2_7_BI2 BIO2_7_BI3 BIO2_7_BI4 BIO2_7_BI5 BIO2_7_BI6 BIO2_7_BI7 BIO2_7_BI8 BIO2_7_BI9 BIO2_7_BI10 X7.1:1, X7.1:2 X7.1:2, X7.1:3 X7.1:4, X7.1:5 X7.1:5, X7.1:6 X7.1:7, X7.1:8 X7.1:8, X7.1:9 X7.1:10, X7.1:11 X7.1:11, X7.1:12 X7.1:13, X7.1:14 X7.1:15, X7.1:16 1) 1) Terminal number Connected object

BIO2X7.1b.fh8

1) Digital input / counter input

BIO2X7.1b

Further information:

104

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.4.

Digital outputs
Module type Connected object PS1 1) X4.1:1, X4.1:2 1) PS1_4_TempAlarm PS1_4_ACFail Terminal number Board X4.1 1 2 X4.1 3 4

+
Mains

X4.1:3, X4.1:4, X4.1:5

IRF

5 6 X4.1:6, X4.1:7, X4.1:8, X4.1:9 7 9 8 10 X4.1:10, X4.1:11, X4.1:12, X4.1:13 1) PS1_4_HSPO1 PS1_4_TCS1 TCS1 11 13 12 15 X4.1:15, X4.1:16, X4.1:17, X4.1:18 1) PS1_4_HSPO2 PS1_4_TCS2 TCS2 16 18 17
PS1X4.1b.fh8

PS1_4_HSPO3

1) Please indicate whether the trip circuit supervision inputs will be configured to use or not

PS1X4.1b
Module type Connected object PS1 Terminal number Board X4.2 8 X4.2:8, X4.2:9, X4.2:10, X4.2:11 9 11 10 12 13 15 14
PS1X4.2o_b.fh8

PS1_4_HSPO4

X4.2:12, X4.2:13, X4.2:14, X4.2:15

PS1_4_HSPO5

16 17 X4.2:16, X4.2:17, X4.2:18

PS1_4_SO1

18

PS1X4.2o_b

Further information:

105

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type Connected object BIO1

Terminal number

Board X5.2 3

X5.2:3, X5.2:4

BIO1_5_SO1

4 5 6

X5.2:5, X5.2:6

BIO1_5_SO2

7 9
8 10 12

X5.2:7, X5.2:8, X5.2:9

BIO1_5_SO3

X5.2:10, X5.2:11, X5.2:12

BIO1_5_SO4

11 13 15 14
BIO1X5.2o.fh8

X5.2:13, X5.2:14, X5.2:15

BIO1_5_SO5

16 18 17

X5.2:16, X5.2:17, X5.2:18

BIO1_5_SO6

BIO1X5.2o
Module type Connected object BIO2 (RET 543) (RET 545) X7.1:17, X7.1:18 BIO2_7_PO1 Terminal number Board X7.1

17 18

BIO2X7.1o_b

Further information:

106

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type Connected object BIO2 (RET 543) (RET 545)

Terminal number

Board X7.2

X7.2:1, X7.2:2

BIO2_7_PO2

1 2 3

X7.2:3, X7.2:4, X7.2:5, X7.2:6

BIO2_7_PO3

4 6 5 7

X7.2:7, X7.2:8, X7.2:9, X7.2:10

BIO2_7_PO4

8 10 9 11 12 14 13 15

X7.2:11, X7.2:12, X7.2:13, X7.2:14

BIO2_7_PO5

X7.2:15, X7.2:16, X7.2:17, X7.2:18

BIO2_7_PO6

16 18 17

BIO2X7.2b

Further information:

107

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.2.5. 10.2.5.1.

RTD module RTD/analog inputs


Module type RTD1 Board X6.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Terminal number
SHUNT

Connected object

1)

+ SHUNT SHUNT

RTD1_6_AI1
DIFF

X6.1:1, X6.1:2, X6.1:3

RTD1_6_AI2
DIFF

X6.1:5, X6.1:6, X6.1:7

+ SHUNT SHUNT

RTD1_6_AI3
DIFF

X6.1:8, X6.1:9, X6.1:10

RTD1_6_AI4
DIFF

X6.1:12, X6.1:13, X6.1:14

+ -

RTD1_6_AI5
DIFF

X6.1:15, X6.1:16, X6.1:17

X6.2 1 2 3 4 5 6 7
RTD1X6._b.fh8

SHUNT SHUNT

DIFF

RTD1_6_AI6 X6.2:1, X6.2:2, X6.2:3

+ SHUNT

RTD1_6_AI7 X6.2:4, X6.2:5, X6.2:6


DIFF

8 9 10

RTD1_6_AI8 X6.2:7, X6.2:8, X6.2:9


DIFF

1) Current transducer / voltage transducer / resistance sensor

RTD1X6._b

Further information:

108

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.2.5.2.

RTD outputs
Module type RTD1 Connected object Terminal number Board X6.2

X6.2:11, X6.2:12

RTD1_6_AO1

+ mA+ mA+ mA+ mA-

11 12

X6.2:13, X6.2:14

RTD1_6_AO2

13 14

X6.2:15, X6.2:16

RTD1_6_AO3

15 16 17 18
RTD1X6.2b.fh8

X6.2:17, X6.2:18

RTD1_6_AO4

RTD1X6.2b

Further information:

10.3. 10.3.1.

Functionality Order number


REM54 __ __ __ __ __ __ __ __ __ __ (for example REM543CM212AAAA)

109

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.3.2.

Application function blocks used


The lists below represent the full set of function blocks, but the selected functionality level (indicated by a letter in the order number, for example REM543CM212AAAA) determines the function blocks available for the configuration.
Protection DEF2Low DEF2High DEF2Inst Diff3 Diff6G DOC6Low DOC6High DOC6Inst Freq1St1 Freq1St2 Freq1St3 Freq1St4 Freq1St5 FuseFail Inrush3 MotStart NEF1Low NEF1High NEF1Inst NOC3Low NOC3High NOC3Inst NPS3Low NPS3High NUC3St1 NUC3St2 OE1Low OE1High OPOW6St1 OPOW6St2 OPOW6St3 OV3Low OV3High PREV3 PSV3St1 PSV3St2 REF1A ROV1Low ROV1High ROV1Inst SCVCSt1 SCVCSt2 TOL3Dev UE6Low UE6High UI6Low UI6High UPOW6St1 UPOW6St2 UPOW6St3 UV3Low UV3High VOC6Low VOC6High

Measurement MEAI1 MEAI2 MEAI3 MEAI4 MEAI5 MEAI6 MEAI7 MEAI8 MEAO1 MEAO2 MEAO3 MEAO4 MECU1A MECU1B MECU3A MEDREC16 MEFR1 MEPE7 MEVO1A MEVO3A

Control COCB1 COCB2 COCBDIR CO3DC1 CO3DC2 CODC1 CODC2 CODC3 CODC4 CODC5 COIND1 COIND2 COIND3 COIND4 COIND5 COIND6 COIND7 COIND8 COLOCAT COSW1 COSW2 COSW3 COSW4 MMIALAR1 MMIALAR2 MMIALAR3 MMIALAR4 MMIALAR5 MMIALAR6 MMIALAR7 MMIALAR8 MMIDATA1 MMIDATA2 MMIDATA3 MMIDATA4 MMIDATA5

110

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Condition monitoring CMBWEAR1 CMBWEAR2 CMCU3 CMGAS1 CMGAS3 CMSCHED CMSPRC1 CMTCS1 CMTCS2 CMTIME1 CMTIME2 CMTRAV1 CMVO3

Communication EVENT230

General INDRESET MMIWAKE SWGRP1 SWGRP2 SWGRP3 SWGRP4 SWGRP5 SWGRP6 SWGRP7 SWGRP8 SWGRP9 SWGRP10 SWGRP11 SWGRP12 SWGRP13 SWGRP14 SWGRP15 SWGRP16 SWGRP17 SWGRP18 SWGRP19 SWGRP20

10.3.3.

Communication

Protocol used:

LON

SPA

Modbus

111

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.4. 10.4.1.

Relay MIMIC configuration Illustration of the system, MIMIC diagram

Symbol used Disconnector: (truck symbols)

closed

open

undef. 0 0

undef. 1 1

Circuit breaker:

Earth switch:

Further information:

112

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

10.4.2.

Alarm LEDs
Please fill in the table below to describe the legend text used as well as the flashing sequence and colour of the LEDs.

Table 10.4.2-1 Descriptions for legend texts and LEDs


LED OFF state
Text (max. 16 characters) Colour

ON state
Flashing Text seq. (max. 16 characters) Colour Flashing seq.

off green yellow red latched, blinking latched, steady non-latched, blinking

1 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 2 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 3 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 7 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 8 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Interlocking _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Control test mode _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ X X X X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Further information:

off green yellow red latched, blinking latched, steady non-latched, blinking
113

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

10.5.

Functionality logic
Please specify the required special PLC logic functionality (see the examples below), by drawing or otherwise, on separate sheets and enclose all additional information with this document (Specification for Machine Terminal Configuration). Example 1: Earthing sequence Earthing of the outgoing feeder can be done by a circuit breaker when an earthing sequence is activated, an earthing switch is earthed and no voltage is measured. If all conditions are fulfilled, the circuit breaker can be closed after 1 second. The figure below shows the implementation of the desired logic.

Earthing

Example 2: Usage of the F-key and a software switch

F key

114

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Example 3: Voltage measurement in the MIMIC view Phase-to-phase voltage must be shown in voltages [V] in the MIMIC view.

Voltage

10.6.

Machine terminal settings


Responsibility: The end user defines the machine terminal settings Machine terminal settings according to the turn-key principle The setting of the parameters is not part of the configuration. The end user will normally be responsible for the setting parameters.

Further information:

115

116

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.
11.1.

APPENDIX D: Specification for RET 54_ transformer terminal configuration


General data
Project name: Date:

This specification suitable for bays:

Substation name:

Machine terminal type:

Software revision

Order number: RET54 __ __ __ __ __ __ __ __ __ __ (for

example RET543A_240AAAA)

Handled by:

Company:

Telephone number:

Fax number:

This document serves as a technical specification of substation protection and is used for the configuration of RET 54_ transformer terminals. Special requirements can be specified under Further information at the bottom of each page.

117

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.2. 11.2.1. 11.2.1.1.

Electrotechnical data Analog inputs Hardware versions with 6 current and 3 voltage transformers
Channel 2...4 5..6 7...9 10
Module type

Measuring devices that can be connected to the corresponding analog measuring channels Current transformer Voltage transformer Current transformer Voltage transformer
Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021427 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 13 12 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT3 CT6 CT5 CT4 VT2 VT1 CT3 CT2 CT1

100V

100V 1A 5A 1A 5A 1A 5A

RemMim2

RemMim2

Further information:

118

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.2.1.2.

Hardware versions with 7 current and 2 voltage transformers


Channel 2...5 6 7...9 10
Module type

Measuring devices that can be connected to the corresponding analog measuring channels Current transformer Voltage transformer Current transformer Voltage transformer
Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021627 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 13 12 11 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT2 CT7 CT6 CT5 VT1 CT4 CT3 CT2 CT1

100V 1A 5A 1A 5A 1A 5A 1A 5A

RemMim3

RemMim3

Further information:

119

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.2.1.3.

Hardware versions with 8 current and 1 voltage transformer


Channel 2...9 10
Module type

Measuring devices that can be connected to the corresponding analog measuring channels Current transformer Voltage transformer
Board Terminal number Connected object Signal type

MIM X1.1 1MRS09021827 AA_/CA_ 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

100V 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A 1A 5A

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:14, X1.1:15 X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT1 CT8 CT7 CT6 CT5 CT4 CT3 CT2 CT1

RemMim4

RemMim4

Further information:

11.2.2.

System frequency

50 Hz

60 Hz

120

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.2.3.

Digital inputs
Module type PS1 Board X4.2 1 2
PS1X4.2b.fh8

Terminal number

Connected object

PS1_4_BI1 PS1_4_BI2 PS1_4_BI3

X4.2:1, X4.2:2 X4.2:4, X4.2:5 X4.2:6, X4.2:7

1) 1) 1)

4 5 6 7

1) Digital input / counter input

PS1X4.2b
Module type BIO1 Board X5.1 1 2 3 4 5 6 7 8 9 Terminal number Connected object

BIO1_5_BI1 BIO1_5_BI2 BIO1_5_BI3 BIO1_5_BI4 BIO1_5_BI5 BIO1_5_BI6 BIO1_5_BI7 BIO1_5_BI8 BIO1_5_BI9 BIO1_5_BI10 BIO1_5_BI11

X5.1:1, X5.1:2 X5.1:2, X5.1:3 X5.1:4, X5.1:5 X5.1:5, X5.1:6 X5.1:7, X5.1:8 X5.1:8, X5.1:9 X5.1:10, X5.1:11 X5.1:11, X5.1:12 X5.1:13, X5.1:14 X5.1:15, X5.1:16 X5.1:17, X5.1:18 1) 1) 1)

10 11 12 13 14 15 16 17 18

BIO1X5.1.fh8

1) Digital input / counter input

BIO1X5.1

Further information:

121

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type BIO1

Board X5.2
BIO1X5.2.fh8

Terminal number

Connected object

1 2

BIO1_5_BI12

X5.2:1, X5.2:2

1)

1) Digital input/ counter input/ time sync

BIO1X5.2

Module type BIO2 (RET 543) (RET 545)

Board X7.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 BIO2_7_BI1 BIO2_7_BI2 BIO2_7_BI3 BIO2_7_BI4 BIO2_7_BI5 BIO2_7_BI6 BIO2_7_BI7 BIO2_7_BI8 BIO2_7_BI9 BIO2_7_BI10

Terminal number

Connected object

X7.1:1, X7.1:2 X7.1:2, X7.1:3 X7.1:4, X7.1:5 X7.1:5, X7.1:6 X7.1:7, X7.1:8 X7.1:8, X7.1:9 X7.1:10, X7.1:11 X7.1:11, X7.1:12 X7.1:13, X7.1:14 X7.1:15, X7.1:16 1) 1)

BIO2X7.1b.fh8

1) Digital input / counter input


A050028

Further information:

122

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.2.4.

Digital outputs
Module type Connected object PS1 1) X4.1:1, X4.1:2 1) PS1_4_TempAlarm PS1_4_ACFail Terminal number Board X4.1 1 2 X4.1 3 4

+
Mains

X4.1:3, X4.1:4, X4.1:5

IRF

5 6 X4.1:6, X4.1:7, X4.1:8, X4.1:9 7 9 8 10 X4.1:10, X4.1:11, X4.1:12, X4.1:13 1) PS1_4_HSPO1 PS1_4_TCS1 TCS1 11 13 12 15 X4.1:15, X4.1:16, X4.1:17, X4.1:18 1) PS1_4_HSPO2 PS1_4_TCS2 TCS2 16 18 17
PS1X4.1b.fh8

PS1_4_HSPO3

1) Please indicate whether the trip circuit supervision inputs will be configured to use or not

PS1X4.1b
Module type Connected object PS1 Terminal number Board X4.2 8 X4.2:8, X4.2:9, X4.2:10, X4.2:11 9 11 10 12 13 15 14
PS1X4.2o_b.fh8

PS1_4_HSPO4

X4.2:12, X4.2:13, X4.2:14, X4.2:15

PS1_4_HSPO5

16 17 X4.2:16, X4.2:17, X4.2:18

PS1_4_SO1

18

PS1X4.2o_b

Further information:

123

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type Connected object BIO1

Terminal number

Board X5.2 3

X5.2:3, X5.2:4

BIO1_5_SO1

4 5 6

X5.2:5, X5.2:6

BIO1_5_SO2

7 9
8 10 12

X5.2:7, X5.2:8, X5.2:9

BIO1_5_SO3

X5.2:10, X5.2:11, X5.2:12

BIO1_5_SO4

11 13 15 14
BIO1X5.2o.fh8

X5.2:13, X5.2:14, X5.2:15

BIO1_5_SO5

16 18 17

X5.2:16, X5.2:17, X5.2:18

BIO1_5_SO6

BIO1X5.2o

Module type Connected object BIO2 (RET 543) (RET 545)

Terminal number

Board X7.1

X7.1:17, X7.1:18

BIO2_7_PO1

17 18
A050225

Further information:

124

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type Connected object BIO2 (RET 543) (RET 545)

Terminal number

Board X7.2

X7.2:1, X7.2:2

BIO2_7_PO2

1 2 3

X7.2:3, X7.2:4, X7.2:5, X7.2:6

BIO2_7_PO3

4 6 5 7

X7.2:7, X7.2:8, X7.2:9, X7.2:10

BIO2_7_PO4

8 10 9 11 12 14 13 15

X7.2:11, X7.2:12, X7.2:13, X7.2:14

BIO2_7_PO5

X7.2:15, X7.2:16, X7.2:17, X7.2:18

BIO2_7_PO6

16 18 17
A050226

Further information:

125

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.2.5. 11.2.5.1.

RTD module RTD/analog inputs


Module type RTD1 Board X6.1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Terminal number
SHUNT

Connected object

1)

+ SHUNT SHUNT

RTD1_6_AI1
DIFF

X6.1:1, X6.1:2, X6.1:3

RTD1_6_AI2
DIFF

X6.1:5, X6.1:6, X6.1:7

+ SHUNT SHUNT

RTD1_6_AI3
DIFF

X6.1:8, X6.1:9, X6.1:10

RTD1_6_AI4
DIFF

X6.1:12, X6.1:13, X6.1:14

+ -

RTD1_6_AI5
DIFF

X6.1:15, X6.1:16, X6.1:17

X6.2 1 2 3 4 5 6 7
RTD1X6._b.fh8

SHUNT SHUNT

DIFF

RTD1_6_AI6 X6.2:1, X6.2:2, X6.2:3

+ SHUNT

RTD1_6_AI7 X6.2:4, X6.2:5, X6.2:6


DIFF

8 9 10

RTD1_6_AI8 X6.2:7, X6.2:8, X6.2:9


DIFF

1) Current transducer / voltage transducer / resistance sensor

RTD1X6._b

Further information:

126

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.2.5.2.

RTD outputs
Module type RTD1 Connected object Terminal number Board X6.2

X6.2:11, X6.2:12

RTD1_6_AO1

+ mA+ mA+ mA+ mA-

11 12

X6.2:13, X6.2:14

RTD1_6_AO2

13 14

X6.2:15, X6.2:16

RTD1_6_AO3

15 16 17 18
RTD1X6.2b.fh8

X6.2:17, X6.2:18

RTD1_6_AO4

RTD1X6.2b

Further information:

127

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.3. 11.3.1.

Functionality Order number


RET54 __ __ __ __ __ __ __ __ __ __ (for example RET543AC240AAAA)

11.3.2.

Application function blocks used


The lists below represent the full set of function blocks, but the selected functionality level (indicated by a letter in the order number, for example RET543AC240AAAA) determines the function blocks available for the configuration.
Protection DEF2Low DEF2High DEF2Inst Diff6T DOC6Low DOC6High DOC6Inst Freq1St1 Freq1St2 Freq1St3 Freq1St4 Freq1St5 FuseFail Inrush3 NEF1Low NEF1High NEF1Inst NOC3Low NOC3LowB NOC3High NOC3Inst NPS3Low NPS3High OE1Low OE1High OV3Low OV3High PSV3St1 PSV3St2 REF1A REF4A REF4B ROV1Low ROV1High ROV1Inst TOL3Dev UI6Low UI6High UV3Low UV3High

Measurement MEAI1 MEAI2 MEAI3 MEAI4 MEAI5 MEAI6 MEAI7 MEAI8 MEAO1 MEAO2 MEAO3 MEAO4 MECU1A MECU1B MECU3A MECU3B MEDREC16 MEFR1 MEPE7 MEVO1A MEVO1B MEVO3A MEVO3B

Control COCB1 COCB2 COCBDIR CO3DC1 CO3DC2 CODC1 CODC2 CODC3 CODC4 CODC5 COIND1 COIND2 COIND3 COIND4 COIND5 COIND6 COIND7 COIND8 COLOCAT COLTC COSW1 COSW2 COSW3 COSW4 MMIALAR1 MMIALAR2 MMIALAR3 MMIALAR4 MMIALAR5 MMIALAR6 MMIALAR7 MMIALAR8 MMIDATA1 MMIDATA2 MMIDATA3 MMIDATA4 MMIDATA5

128

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Condition monitoring CMBWEAR1 CMBWEAR2 CMCU3 CMGAS1 CMGAS3 CMSCHED CMSPRC1 CMTCS1 CMTCS2 CMTIME1 CMTIME2 CMTRAV1 CMVO3

Communication EVENT230

General INDRESET MMIWAKE SWGRP1 SWGRP2 SWGRP3 SWGRP4 SWGRP5 SWGRP6 SWGRP7 SWGRP8 SWGRP9 SWGRP10 SWGRP11 SWGRP12 SWGRP13 SWGRP14 SWGRP15 SWGRP16 SWGRP17 SWGRP18 SWGRP19 SWGRP20

11.3.3.

Communication

Protocol used:

Port X3.2 Modbus DNP 3.0 IEC 60870-5-103 SPA

Port X3.3 LON SPA

129

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.4. 11.4.1.

Relay MIMIC configuration Illustration of the system, MIMIC diagram

Q1 Q0 0.0A Q4 AVR AUT Q9 0POS PAR ON

0.0A 0 . 0 kW 0 . 0 A Io

Symbol used Disconnector: (truck symbols)

closed

open

undef. 0 0

undef. 1 1

Circuit breaker:

Earth switch:

Further information:

130

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

11.4.2.

Alarm LEDs
Please fill in the table below to describe the legend text used as well as the flashing sequence and colour of the LEDs.

Table 11.4.2-1 Descriptions for legend texts and LEDs


LED OFF state
Text (max. 16 characters) Colour

ON state
Flashing Text seq. (max. 16 characters) Colour Flashing seq.

off green yellow red latched, blinking latched, steady non-latched, blinking

1 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 2 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 3 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 4 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 7 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 8 _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Interlocking _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Control test mode _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ X X X X _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Further information:

off green yellow red latched, blinking latched, steady non-latched, blinking
131

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

11.5.

Functionality logic
Please specify the required special PLC logic functionality (see the examples below), by drawing or otherwise, on separate sheets and enclose all additional information with this document (Specification for Transformer Terminal Configuration). Example 1: Earthing sequence Earthing of the outgoing feeder can be done by a circuit breaker when an earthing sequence is activated, an earthing switch is earthed and no voltage is measured. If all conditions are fulfilled, the circuit breaker can be closed after 1 second. The figure below shows the implementation of the desired logic.

Earthing

Example 2: Usage of the F-key and a software switch

F key

132

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Example 3: Voltage measurement in the MIMIC view Phase-to-phase voltage must be shown in voltages [V] in the MIMIC view.

Voltage

11.6.

Transformer terminal settings


Responsibility: The end user defines the machine terminal settings Machine terminal settings according to the turn-key principle The setting of the parameters is not part of the configuration. The end user will normally be responsible for the setting parameters.

Further information:

133

134

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

12.
12.1.

APPENDIX E: Specification for REC 523 Remote Monitoring and Control Unit configuration
General data
Project name: Date:

This specification suitable for bays:

Substation name:

Monitoring and control unit type:

Software revision

Order number: REC523 __ __ __ __ __ __ __ (for

example REC523F 033AAA)

Handled by:

Company:

Telephone number:

Fax number:

This document serves as a technical specification of remote monitoring and control of secondary substations in medium-voltage networks and is used for the configuration of REC 523 remote monitoring and control units. Special requirements can be specified under Further information at the bottom of each page.

135

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

12.2. 12.2.1.

Electrotechnical data Analog inputs


Table 12.2.-1 Analog input channel connections
Channel 1 2...4 5, 7...9 6 10 Measuring devices that can be connected to the corresponding analog measuring channels Rogowski sensor, voltage divider or general measurement Current transformer, Rogowski sensor, voltage divider, or general measurement Voltage transfomer,current transformer, Rogowski sensor, voltage divider or general measurement Voltage transformer or general measururement Voltage transformer, Rogowski sensor, voltage divider or general measurement

Further information:

136

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type MIM (032 _AA, 037 _AA)

Board

Terminal number

Connected object

Signal type

X1.1 9 8 7 6 5 4 3 2 1
1A 5A 1A 5A 1A 5A

Ch 4 Ch 3 Ch 2

X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

CT3 CT2 CT1

RecMim1

RecMim1
Module type MIM (033 _AA, 038 _AA) Board X1.1 27 25 24 22 21 19 18 16 15 13 12 11 10 9 8 7 6 5 4 3 2 1
100V

Terminal number

Connected object

Signal type

Ch 10 Ch 9 Ch 8

X1.1:25, X1.1:27 X1.1:22, X1.1:24 X1.1:19, X1.1:21

VT3 VT2 VT1

100V

100V

1A 5A 1A 5A 1A 5A

Ch 4 Ch 3 Ch 2

X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

CT3 CT2 CT1

RecMim2

RecMim2

Further information:

137

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type MIM (034 _AA, 039 _AA)

Board X1.1 27 25 24 22 21 19 18 16 15 13 12 11 10 9 8 7 6 5 4 3 2 1
230V

Terminal number

Connected object

Signal type

Ch 10 Ch 9 Ch 8

X1.1:25, X1.1:27 X1.1:22, X1.1:24 X1.1:19, X1.1:21

VT3 VT2 VT1

230V

230V

1A 5A 1A 5A 1A 5A 1A 5A

Ch 5 Ch 4 Ch 3 Ch 2

X1.1:10, X1.1:11, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

CT4 CT3 CT2 CT1

RecMim3

RecMim3
Module type MIM (061 _AA, 066 _AA) Board X1.1 27 25 24 23 22 21 20 19 18 17 16 15 13 12 10 9 8 7 6 5 4 3 2 1
100V 1A 5A 1A 5A 1A 5A

Terminal number

Connected object

Signal type

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:23, X1.1:24 X1.1:19, X1.1:20, X1.1:21 X1.1:16, X1.1:17, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT3 CT6 CT5 CT4 VT2 VT1 CT3 CT2 CT1

100V

100V 1A 5A 1A 5A 1A 5A

RecMim4

RecMim4

Further information:

138

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Module type MIM (062 _AA, 067 _AA)

Board X1.1 27 25 24 22 21 19 18 16 15 13 12 10 9 8 7 6 5 4 3 2 1
100V

Terminal number

Connected object

Signal type

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25, X1.1:27 X1.1:22, X1.1:24 X1.1:19, X1.1:21 X1.1:16, X1.1:18 X1.1:13, X1.1:15 X1.1:10, X1.1:12 X1.1:7, X1.1:8, X1.1:9 X1.1:4, X1.1:5, X1.1:6 X1.1:1, X1.1:2, X1.1:3

VT6 VT5 VT4 VT3 VT2 VT1 CT3 CT2 CT1

100V

100V

100V

100V

100V 1A 5A 1A 5A 1A 5A

RecMim5

RecMim5

Module type MIM (054_AA, 059_AA

Board
X1.1
27
100V

Terminal number

Connected object VT4 VT3 VT2 VT1 CT5 CT4 CT3 CT2 CT1

Signal type

25 24 23 22 21 20 19 18 17 16 15 13 12 10 9 8 7 6 5 4 3 2 1

Ch 10 Ch 9 Ch 8 Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2

X1.1:25 X1.1:27 X1.1:22 X1.1:24 X1.1:19 X1.1:21 X1.1:16 X1.1:18 X1.1:13 X1.1:14 X1.1:15 X1.1:10 X1.1:12 X1.1:7 X1.1:8 X1.1:9 X1.1:4 X1.1:5 X1.1:6 X1.1:1 X1.1:2 X1.1:3

100V

100V

100V
0,2A 1A

1A 5A

1A 5A

1A 5A

1A 5A

A050027

Further information:

139

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Module type SIM

Board X2.1
DIFF

Terminal number Ch 10, sensor Ch 9, sensor Ch 8, sensor Ch 7, sensor Ch 5, sensor Ch 4, sensor Ch 3, sensor Ch 2, sensor Ch 1, sensor X2.1 X2.2 X2.3 X2.4 X2.5 X2.6 X2.7 X2.8 X2.9

Connected object

Signal type

X2.2
DIFF

X2.3
DIFF

X2.4
DIFF

X2.5
DIFF

X2.6
DIFF

X2.7
DIFF

X2.8
SIMX2.fh8
DIFF

X2.9
DIFF

Simx2

The measuring device can be connected exclusively to the analog channels of either MIM or SIM type modules.

Further information:

12.2.1.

System frequency

50 Hz

60 Hz

140

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

12.2.2.

Digital inputs
Module type PSC Board X7.3 1 2 3 4 5 6 PSC_7_BI1 PSC_7_BI2 PSC_7_BI3 X4.2:1, X4.2:2 X4.2:4, X4.2:5 X4.2:6, X4.2:7 1) 1) 1) Terminal number Connected object

PSCX7.3.fh8

1) Digital input / counter input

PSCX7.3
Module type BIO1 Board X3.1 1 2 3 4 5 6 7 8 9 Terminal number Connected object

BIO1_3_BI1 BIO1_3_BI2 BIO1_3_BI3 BIO1_3_BI4 BIO1_3_BI5 BIO1_3_BI6

X3.1:1, X3.1:2 X3.1:2, X3.1:3 X3.1:4, X3.1:5 X3.1:5, X3.1:6 X3.1:7, X3.1:8 X3.1:8, X3.1:9 X3.1:10, X3.1:11 X3.1:11, X3.1:12 X3.1:13, X3.1:14 X3.1:15, X3.1:16 X3.1:17, X3.1:18

10 11 12 13 14 15 16
BIO1X3.1.fh8

BIO1_3_BI7 BIO1_3_BI8 BIO1_3_BI9 BIO1_3_BI10 BIO1_3_BI11

17 18

BIO1X3.1
Module type BIO1
BIO1X3.2.fh8

Board X3.2 1 2 BIO1_3_BI12

Terminal number

Connected object

X3.2:1, X3.2:2

BIO1X3.2

Further information:

141

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

12.2.3.

Digital outputs
Module type Connected object PSC Terminal number Board X7.3 8 PSC_7_SO1 or Heater Output X7.3:11, X7.3:12, X7.3:13, X7.3:14 P S C _ 7 _ H S P O 1

9 11 12 14 13 15

X7.3:15, X7.3:16, X7.3:17, X7.3:18 P S C _ 7 _ H S P O 2

16 18 17

PSCX7.3o
Module type Connected object BIO1 Terminal number Board X3.2 3 X3.2:3, X3.2:4 BIO1_3_SO1 4 5 6 7 9 8 10 12 11 13 15 14
BIO1X3.2o.fh8

X3.2:5, X3.2:6

BIO1_3_SO2

X3.2:7, X3.2:8, X3.2:9

BIO1_3_SO3

X3.2:10, X3.2:11, X3.2:12

BIO1_3_SO4

X3.2:13, X3.2:14, X3.2:15

BIO1_3_SO5

16 18 17

X3.2:16, X3.2:17, X3.2:18

BIO1_3_SO6

BIO1X3.2o

Further information:

142

PSCX7.3o.fh8

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

12.3. 12.3.1.

Functionality Order number


REC523 __ __ __ __ __ __ __ (for example REC523F033AAA)

12.3.2.

Application function blocks used


Measurement MEAI1 MEAI2 MEAI3 MEAI4 MEAI5 MEAI6 MEAI7 MEAI8 MECU1A MECU1B MECU3A MECU3B MEDREC16 MEFR1 MEPE7 MEVO1A MEVO1B MEVO3A MEVO3B

Fault indication AR5Func CUB3Low DEF2Low DEF2High DOC6Low DOC6High Inrush3 NEF1Low NEF1High NOC3Low NOC3High UV3Low UV3High

Control COCB1 COCB2 CO3DC1 CO3DC2 CODC1 CODC2 CODC3 CODC4 CODC5 COIND1 COIND2 COIND3 COIND4 COIND5 COIND6 COIND7 COIND8 COLOCAT COPFC

Condition monitoring CMBWEAR1 CMBWEAR2 CMCU3 CMGAS1 CMSCHED CMSPRC1 CMTCS1 CMTCS2 CMTIME1 CMTIME2 CMTRAV1 CMVO3

Communication EVENT230

143

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

General INDRESET SWGRP1 SWGRP2 SWGRP3 SWGRP4 SWGRP5 SWGRP6 SWGRP7 SWGRP8 SWGRP9 SWGRP10 SWGRP11 SWGRP12 SWGRP13 SWGRP14 SWGRP15 SWGRP16 SWGRP17 SWGRP18 SWGRP19 SWGRP20

12.3.3.

Communication
Protocol used: LON IEC 60870-5-101 Modbus SPA DNP 3.0

12.4.

Virtual channels
Virtual meas. I0s I0bs U0s U12s U23s U31s Channel number Analog meas. 1 IL1 IL1b U1 U1 U2 U1 Channel number Analog meas. 2 IL2 IL2b U2 U2 U3 U3 Channel number Analog meas. 3 IL3 IL3b U3 Channel number

12.5.

LED configuration
The optional LED panel of REC 523 includes 21 LEDs that can be freely configured with the Relay Configuration Tool (for an example configuration, see Fig. 12.5.-1 below). Each LED has four states: on (steady), off, fast blinking (2 Hz) and slow blinking (0.5Hz). Please specify the desired LED configuration in Table 12.5.-1 below.

144

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Leds 1-8 in REC 523 Led panel BOOL2INT_1 PSC_7_LED1_8 BOOL2INT PSC_7_ACFail FALSE PSC_7_BattTest PSC_7_BattStatus BIO1_3_BI1 BIO1_3_BI2 PSC_7_HeatStat PSC_7_TempAlarm BIO1_3_BI3 FALSE PSC_7_Bl1 NOT
A050012

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15

Led 1: Led 2:

Fast blink = AC Fail occurred On = Battery Test running On = Battery Poor Off = Battery Good OFF = BI1&BI2 OFF Slow blink = BI1 OFF&BI2 ON Fast blink = BI1 ON&BI2 OFF ON = BI1&BI2 ON On = Heater on On = Temp. limit exceeded On = BI3 OFF Fast blink = BI3 ON Slow blink = BI1 OFF Fast blink = BI1 ON

Led 3: Led 4:

Led 5: Led 6:

Led 7:

Led 8:

Fig. 12.5.-1 Example of the LED configuration for REC 523


Table 12.5.-1 Specification for the LED configuration
On (steady) LED no 1 2 3 4 5 6 7 Slow blink Fast blink

Purpose

Off

145

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

Table 12.5.-1 Specification for the LED configuration (Continued)


On (steady) LED no 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Slow blink Fast blink

Purpose

12.6.

Remote monitoring and control unit settings


Responsibility: The end user defines the remote monitoring and control unit settings Remote monitoring and control unit settings according to the turn-key principle The setting of the parameters is not part of the configuration. The end user will normally be responsible for the setting parameters.

Further information:

146

Off

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

13.
13.1.

APPENDIX F: Power quality application guide for harmonics


Power quality and harmonics
Power quality is a topic that defines the limits for delivered electricity in power network. The key issue is to define acceptable variation limits to ensure that endcustomers are able to utilise the delivered power. Power quality is ultimately a customer-driven issue. Excellent power without interruptions is the ultimate target. Today this target has not been reached. There are many kind of disturbances in the network affecting power quality. Interruptions and other disturbances weaken the utilisation of delivered power in end-customer facilities. If these disturbances have noticeable effects on the utilisation of power, disturbances should be blocked out or the system should be made immune to these disturbances. Before taking action to reduce the effects of disturbances, the reason and source of the disturbance should be found. Only after that can reasonable solutions be weighted against costs and benefits. Harmonics, that is, distortion in the voltage and current waveforms, are one of the factors affecting power quality. Harmonic distortion is caused by non-linear loads that are, for example, electronic power supplies, converters, arc furnaces and arc welders. Harmonics may cause maloperation of devices, additional heating in devices and telecommunication interference. The importance of harmonics is emphasized by the fact that the amount of equipment generating harmonics constantly increases. Still, it should be noticed that the existence of harmonics is not automatically a problem.

13.2.

Background for harmonics


A periodic distorted waveform can be expressed as a sum of sinusoids. The waveform can be represented as a sum of pure sine waves in which the frequency of each sinusoid is an integer multiple of the fundamental frequency. This multiple h is called a harmonic of the fundamental. Harmonics added to the fundamental frequency can be odd harmonics (the integer multiple h is 3,5,7...) or even harmonics (where h is 2,4,6...). In Fig. 13.2.-1 odd harmonics with the amplitude 0.1 p.u. of the fundamental are added to the fundamental frequency.

147

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

1)

2)

3)

4)

Fig. 13.2.-1 Odd harmonics added to the 1.0 p.u. fundamental frequency (50Hz) waveform are illustrated in the first picture. The second picture shows the fundamental frequency with 0.1 p.u. third harmonic. The third picture represents the fundamental frequency with the 0.1 p.u. third and 0.1 p.u. fifth harmonics. In the last picture, the 0.1 p.u. seventh harmonic is added to the fundamental frequency with the third and fifth harmonics. The relationship for current and voltage harmonics is shown in Fig. 13.2.-2.
Pure Sinusoid Voltage drop Distorted voltage

Distorted load current


Voltdist.CNV

Fig. 13.2.-2 Voltage distortion in power system

148

Oddharm.CNV

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

Voltage sources, that is, generation plants do not generally generate harmonics. Harmonics are created because of power system non-linearity. Non-linear components and loads cause distorted currents because of their operational principles. Distorted currents flow through system impedance causing a voltage drop for each harmonic. This results in voltage harmonics appearing at the load bus. The created voltage distortion can be calculated if current harmonics as well as system frequency response are known. In most cases the system frequency response is very difficult to determine. Power system is a very large system that contains many non-linear components. This makes it difficult to precisely predict the effects of harmonics in different parts of the power system.

13.3.

Harmonic sources
The most important harmonic sources are basically converters and power supplies for numerous electrical equipment. This equipment is a source for harmonics, and at the same time, its operation principles may be very sensitive to harmonics, especially to voltage harmonics. Still, some devices can be designed to decrease their characteristic harmonics.

13.3.1.

Single-phase power supplies


A major harmonic concern in commercial buildings is that power supplies for single-phase electronic equipment will produce too much distortion for the wiring. Direct current power for modern electronic and microprocessor-based office equipment is commonly derived from single-phase full-wave diode bridge rectifiers. Modern technology for single-phase power supplies is based on switch-mode. A distinctive characteristic of switch-mode power supplies is the very high thirdharmonic content in the current. Other characteristic harmonics are the 5th and 7th harmonics. Switch-mode power supplies are beginning to find applications in fluorescent lighting systems. Typical current harmonics and the waveform for a switch-mode power supply are shown in Fig. 13.3.1.-1.
1.2 1 Magnitude p.u. of fundamental 0.8 0.6 0.4 0.2 0 1 2 3 4 5 6 7 8 9 10 11 12 13

Harmonic

Fig. 13.3.1.-1 Typical current harmonics and the waveform for a switch-mode power supply

149

Currharm.CNV

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

13.3.2.

Three-phase power converters


Three-phase electronic power converters differ from single-phase converters mainly because they do not generate the third harmonic or the third harmonic is quite small. There are many designs and types of converters for AC or DC drives with different power ratings. Harmonics may vary significantly between designs and operation conditions. Still, some examples are given below.

Six-pulse and twelve-pulse converters


Harmonic components of the AC current waveform with q-pulse rectifier are:

h = kq 1
and the magnitudes of the harmonic currents are:

I1 I h = --h
where h k q Ih I1 the harmonic order any positive integer the pulse number of the rectifier circuit the amplitude of the harmonic current of order h the amplitude of the fundamental current

The most significant harmonics for six-pulse converters are the 5th, 7th, 11th and 13th. For twelve-pulse converters, the 11th, 13th, 23rd and 25th harmonics are the most significant.

PWM-type ASD
Typical current harmonics and the waveform for a Pulse Width Modulation-type Adjustable Speed Drive with rated speed are shown in Fig. 13.3.2.-1 .
1.2 1 Magnitude p.u. of fundamental 0.8 0.6 0.4 0.2 0 1 2 3 4 5 6 7 8 9 10 11 12 13
HarmPWM.CNV

Harmonic

Fig. 13.3.2.-1 Current harmonics and the waveform for a PWM-type ASD

CSI-type ASD
Typical current harmonics and the waveform for a Current Source Inverter-type Adjustable Speed Drive are shown in Fig. 13.3.2.-2.

150

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

1.2 1 Magnitude p.u. of fundamental 0.8 0.6 0.4 0.2 0 1 2 3 4 5 6 7 8 9 10 11 12 13 HarmCSI.CNV

Harmonic

Fig. 13.3.2.-2 Current harmonics and the waveform for a CSI-type ASD

Cycloconverter harmonics
The expressions of cycloconverter current harmonics are complex. They vary as a function of the frequency ratio of the cycloconverter:

fh
where fh fi k, n q fo

= f i ( kq

1 ) 6nf o

the harmonic frequency imposed on the AC system the input frequency of the cycloconverter integers the pulse number of the converter the output frequency of the cycloconverter

This means that harmonics may vary significantly and interharmonics (non-integer multiple of fundamental frequency) may also appear. Characteristic harmonics for a six-pulse cycloconverter are harmonics from fundamental to 2nd, 5th to 7th, and 11th to 13th.

13.3.3.

Other harmonic sources


There are many other harmonic sources in addition to converters and power supplies. These sources are mainly arching devices like arc furnaces and welding equipment.

Arc furnaces
The harmonics produced by electric arc furnaces used for the production of steel are unpredictable. The steel scrap to be molten is a very non-linear load and thus the melting arc changes constantly. The arc current may be non-periodic and may include both harmonics and interharmonics. Still, in most applications, the loworder harmonics starting with the second and ending with the seventh predominate the non-integer harmonics. Fig. 13.3.3.-1 presents typical harmonics for an arc furnace during the initial melting period and the refining period. These harmonics have quite a low percentage magnitude compared to the fundamental component. Arc furnaces form a large load with fundamental currents of several kA, which makes arc furnaces a significant harmonic source for the power system.

151

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

0.1 Magnitude p.u. of fundamental 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 0 2 3 4 5 6 7 Magnitude p.u. of fundamental 0.09

0.1 0.09 0.08 0.07 0.06 0.05 0.04 0.03 0.02 0.01 2 3 4 5 6 7
Harmfurn.CNV

Harmonic

Harmonic

Fig. 13.3.3.-1 Typical harmonics for arc furnaces. The first picture is for the melting phase and the second for the refining phase. Other arching devices similar to arc furnaces are arc welding equipment.

Saturable devices
Equipment in this class includes transformers and other electromagnetic devices with a steel core, including motors. Harmonics are generated due to the non-linear magnetising characteristics of the steel. Harmonics are due to exciting current, which is very rich in harmonics like the 3rd, 5th, 7th and 9th. Transformers are not as much a concern as electronic power converters because exciting current is small compared to the rated full load current. However, their effect will be noticeable particularly on utility distribution systems that have hundreds of transformers. A significant increase in triplen harmonic currents is often noticed during the early morning hours when the load is low and thus the percentage of harmonics compared to the fundamental is high. Motors and synchronous generators also exhibit some distortion, although it is generally of little consequence.

13.4.

System response characteristics


The effect of one or more harmonic sources on a power system will depend primarily on the frequency response characteristics. The non-linear components described in Section 13.3. Harmonic sources can be represented generally as current sources for harmonics. Harmonic currents flow through impedance causing harmonic voltages. Some basic rules for the harmonic current flow are given in this section.

Flow of harmonic currents


Harmonic currents tend to flow from the non-linear loads (harmonic sources) towards the lowest impedance, usually the utility source. This was shown in Fig. 13.2.-2. However, other connected loads provide an alternative path for harmonic currents. The flow path to be chosen will depend on impedance ratios. This may result in a situation where a neighbouring load includes harmonics although there are no harmonic sources in this load branch. Harmonics generated by other load branches will flow to this branch. This is shown in Fig. 13.4.-1.

152

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

iharmonic Xsystem Xtrafo

RL

RL

RL

XC

Fig. 13.4.-1 Spreading of harmonic currents in the power system

Transformers
Transformers essentially isolate the load at higher harmonic frequencies. High-order harmonics are not passed through transformers. Another effect of the transformers is the isolation of triplen harmonics due to the transformer winding design. Triplen harmonics tend to stay trapped into the delta connection and do not show up in the line currents in the delta side. Some examples for the third harmonic current flow in transformers are shown in Fig. 13.4.-2.

Harmpow.CNV

Fig. 13.4.-2 Third harmonic flow in a wye-delta-connected transformer and in a wye-wye-connected transformer These rules about triplen harmonic current in transformers only apply to balanced loading conditions. When the phases are not balanced, the triplen harmonics may as well show up where they are not expected. Fig. 13.4.-2 also shows the nature of the third harmonic and neutral line. Third harmonics in line conductors tend to be in phase with each other. This means that as currents summarise in neutral connection, the third harmonic in neutral line is three times the third harmonic in the line conductor. This may result in a too high current flowing in the neutral conductor.

Capacitors
Capacitor banks used for voltage control and power factor correction are the major components that affect the system frequency response characteristics. Capacitors can chance the system response to harmonics by creating high impedance or, on the other hand, low impedance for harmonic currents at some frequencies. This means that although capacitors are not harmonic sources, they may cause severe harmonic distortion. On the other hand, capacitors can be used for creating paths with the
153

Harmtran.CNV

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

lowest impedance for harmonics and applied to filtering of harmonics. The connection of capacitors may cause resonance conditions that may magnify harmonic levels.

13.5.

Effects of harmonics
The main effects of voltage and current harmonics within the power system are: Amplification of harmonic levels resulting from series and parallel resonance Reduction of efficiency in power generation, transmission and utilisation Ageing of the insulation of electrical plant components and thus shortening of their useful life Equipment maloperation

Resonances and capacitors


The presence of capacitors may result in local resonances. Resonance conditions may lead to excessive harmonic currents and voltages which increase heating and voltage stress in capacitors. Another area where resonance effects may lead to component failure is associated with the power line signalling (ripple control) for load management. In such systems, tuned stoppers (filters) are often used to prevent the signalling frequency from being absorbed in low impedance elements, such as power factor correction capacitors. Where local resonance exists, excessive harmonic currents can flow, resulting in damage to the tuning capacitors.

Rotating machines
A major effect of harmonic voltages and currents in rotating machinery (induction and synchronous) is increased heating due to iron and copper losses. Harmonic pairs, such as the fifth and seventh harmonics, have the potential for creating mechanical oscillations in a turbine-generator or in a motor-load system. Then highstress mechanical forces may be developed. A pulsating output torque may affect the product quality where motor loads are sensitive to torque variations.

Transformers
With the exception that harmonics applied to transformers may result in increased audible noise, the effects of harmonics on these components usually arise from additional heating. Current harmonics cause an increase in copper losses and stray flux losses. Voltage harmonics cause an increase in iron losses and stress the insulation. Additional heating may result in overheating with less than rated load. Accelerated ageing of transformers is also possible.

Electronic equipment
Power electronic equipment is susceptible to misoperation caused by harmonic distortion. This equipment is often dependent upon accurate determination of voltage zero crossing or other aspects of voltage wave shape. Other types of electronic equipment may be affected by the transmission of ac supply harmonics through the equipment power supply or by the magnetic coupling of harmonics into equipment components. Computers and allied equipment, such as programmable controllers, may suffer from erratic data or malfunctions. Malfunctions may in some

154

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

cases have serious consequences, for example in medical equipment. Less dramatic interference may occasionally be observed in radio and television equipment, as well as in video recorders and audio reproduction systems.

Metering
Metering instruments initially calibrated on pure sinusoidal alternating current and subsequently used on a distorted electricity supply may be prone to error. Both positive and negative metering errors are possible because error is connected to the direction of the harmonic flow. In general, the distortion must be severe (>20%) before significant errors are detected.

Telephone interference
The presence of harmonic currents or voltages in circuitry associated with power conversion apparatus may produce magnetic and electric fields that will impair the satisfactory performance of the communication system that, by virtue of its proximity and susceptibility, may be disturbed.

13.6.

Applications for harmonic measurements


Harmonics measurement function blocks can be utilised in applications like monitoring power quality affected by harmonics, monitoring harmonics in selected points of the network and locating sources of harmonics.

13.6.1.

Power quality and harmonics


There are several standards and recommendations for acceptable levels of harmonics in power system. Recommendations for both voltage and current harmonics can be found for distributed electricity. European Standard EN 50160 and IEEE Std 1159-1995 are well known references for power quality. Harmonic measurements can be utilised in several ways in the network. Here a utility 110/20 kV substation is taken as an example. The substation is shown in Fig. 13.6.1.-1 with measurement points for currents and voltages on 20 kV side. There are three feeders connected to busbar. Feeders have different types of loads connected. Load A is generating harmonic currents and load B is a simple motor or resistive load. In addition, there is a capacitor unit connected to the busbar for reactive power compensation. This unit could also include load.

155

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

110 kV

Trafo 110/20 kV

Voltage measurement

Current measurement

20 kV

Current meas.

Current meas.

Current meas.

M 3~

Load A Harmonic source

Load B

Compensation

Fig. 13.6.1.-1 110/20 kV substation with different types of loads connected to the feeders Power quality affected by harmonics at the substation can be measured in the incoming feeder for both voltage harmonics and current harmonics. If individual feeders are monitored, it should be noticed that measuring the current harmonics from each feeder is enough. The 20 kV bus voltage is common for all of the feeders. Measuring the voltage harmonics from all the feeders results in unnecessary information. Most of the time only the most important feeders (for example harmonic sources) are monitored.

13.6.2.

Harmonic monitoring with individual loads and devices


Harmonic measurement function blocks can be applied to monitor harmonic levels on different types of loads and devices. There are several standards for acceptable harmonic levels with different devices. Recommendations are also given by equipment manufacturers. Still, it should be noticed that harmonic protection with PQVO3H and PQCU3H is not applicable. These function blocks have a long measurement delay to update values (minimum 600 ms). Another feature is that all kinds of spikes and other rapid changes in measured signals are filtered off from output values. Measurement of interharmonics is not possible. Some general recommendations for acceptable harmonic levels are the following: 1. Transformers Current distortion should not exceed 5 percent 2. Motors Heat problems begin when voltage distortion reaches approximately 8 percent (motor unit without drive, harmonics in drive input may be considerably higher as shown in Section 13.3. Harmonic sources)

156

Loads.CNV

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

3. Capacitors Voltage limit to 120 percent of peak voltage (with harmonics) -> sum of individual voltage harmonics <20% with rated fundamental In case of feeders containing many individual loads and devices, it is difficult to recommend levels according to specific devices. In such a case, the recommendations given in standards for power quality can be followed. Then the harmonics are monitored for the feeder itself, not for the load devices.

13.6.3.

Locating sources of harmonics


On radial utility distribution feeders and industrial plant power systems, the main tendency is for harmonic currents to flow from the harmonic producing load (Load A in Fig. 13.6.1.-1) to the power system source (towards 110 kV incoming). The impedance of the power system is normally the lowest impedance seen by the harmonic currents. There are factors that may alter the path for at least one harmonic. These factors were discussed in Section 13.3. Harmonic sources. Transformers may block some harmonics, power factor correction capacitors may provide paths for higher-order harmonics, and there may be harmonic filters. To locate the harmonic source (Load A), harmonic currents in all feeders, including the incoming feeder, should be measured. These results should be checked against each other. The harmonic source is the one containing the largest amount of harmonics. It may also be useful to check the harmonic flow while the power factor capasitances are not connected. In this situation, paths for harmonics should be decreased and locating the sources of harmonics should be easier.

13.6.4.

Harmonic filter performance monitoring


Harmonic filters are designed to catch harmonic currents produced by harmonic sources. There can be filters for a single harmonic component or filter banks for several harmonic components, like the 5th, 7th, 11th and 13th harmonics. The current harmonic measurement function block can be utilised to evaluate how well the harmonic components are caught into the filters. In case of a filter bank designed to catch several harmonic components, the connection of the filter bank to the system may lead to a situation where uncharacteristic (mostly even) harmonic components are created. These uncharacteristic harmonics may have unwanted effects on the system performance and the filter bank. Even though the level of uncharacteristic harmonics is low and negligible after installation, the harmonic levels may be considerably magnified due to the ageing of capacitors in the filter bank.

157

158

1MRS750745-MUM

Protection & Control Terminals


Configuration Guideline

REF 54_, REM 54_, RET 54_, REC 523

14.

Index
A Analog channels ................................................................................. 29, 39 B Blocking ................................................................................................... 74 Bypass mode ............................................................................................. 76 C Code body worksheet ......................................................................... 21, 22 Communication ........................................................................................ 71 Communication signals ................................................................ 71, 72, 73 Compiling the project ............................................................................... 57 Condition monitoring ......................................................................... 37, 46 Configuration ............................................................ 17, 26, 77, 79, 97, 117 Configuration error ............................................................................. 31, 41 Configuration specification for REC 523 ............................................... 135 Control of switchgears .............................................................................. 75 Cyclic communication check ................................................................... 74 Cyclic sending generation ........................................................................ 73 D Data types ................................................................................................. 19 Description worksheet ........................................................................ 21, 22 Digital inputs ................................................................................ 35, 45, 63 Digital outputs .......................................................................................... 63 Downloading the configuration ................................................................ 57 E Error outputs ............................................................................................. 66 Events ....................................................................................................... 76 Execution order ........................................................................................ 67 Explicit feedback ...................................................................................... 64 F F-key ......................................................................................................... 68 Frequency ................................................................................................. 32 G Global variables .................................................................................. 49, 52 H Hardware version ................................................................................ 27, 38 Harmonic restraint measurement ........................................................ 30, 40 Harmonics ............................................................................................... 147 HMI .................................................................................................... 66, 74 Horizontal communication ....................................................................... 71
159

REF 54_, REM 54_, Protection & Control Terminals RET 54_, REC 523
Configuration Guideline

1MRS750745-MUM

L Libraries ................................................................................................... 19 Logic ........................................................................................................ 71 Logical POUs ..................................................................................... 19, 23 M Manuals .................................................................................................... 11 Measurement function blocks ...................................................... 30, 40, 76 Measurements ......................................................................... 30, 36, 40, 46 MIMIC ......................................................... 57, 93, 96, 112, 115, 130, 133 N Neutral current .......................................................................................... 31 P Physical hardware .............................................................................. 19, 25 Polling ...................................................................................................... 71 Power quality ......................................................................................... 147 Program Organisation Unit (POU) ........................................................... 21 Project tree ................................................................................................ 19 R References .............................................................................................. 157 Relay configuration procedure ................................................................. 77 Relay Configuration Tool ........................................................................ 15 S Specification for REF 54_ Feeder Terminal Configuration ..................... 79 Specification for REM 54_ Machine Terminal Configuration ................ 97 Specification for RET 54_ Transformer Terminal Configuration ......... 117 T Task interval ............................................................................................. 48 Tasks ........................................................................................................ 47 Technical data .......................................................................................... 30 True RMS measurement ..................................................................... 30, 40 V Variable worksheet ....................................................................... 21, 22, 51 Virtual channels .................................................................................. 33, 43 W Warnings .................................................................................................. 67

160

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND Tel. +358 10 22 11 Fax. +358 10 224 1094 www.abb.com/substationautomation

1MRS750745-MUM EN 10.2006