You are on page 1of 2

Sealed Lead-Acid Battery

Absorbant Glass Mat (AGM) technology for superior performance. Valve regulated, spill proof construction allows safe operation in any position. Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. recognized under file number MH 20567.

UPG No. D5695

UB3.2-6
Maintenance-Free

Specication
Nominal Voltage Nominal Capacity 20-hr. (0.16A) 10-hr. (0.30A) 5-hr. (0.54A) 1-hr. (1.92A) Approximate Weight Internal Resistance (approx.) Shelf Life (% of normal capacity at 77 F (25 C)) 3 Months 6 Months 91% 82% Temperature Dependancy of Capacity 32 F 104 F 77 F 102% 100% 85% AGM Operational Temperature Charge Discharge AGM Storage Temperature 6 volts 77 F (25 C) 3.20 Ah 2.98 Ah 2.72 Ah 1.92 Ah 1.28 lbs (0.58 kgs) 30 m 12 Months 64% (20 hour rate) 5 F 65% 0 C to 40 C -15 C to 45 C -15 C to 40 C

Charge Method (Constant Voltage) Cycle Use (Repeating Use) Initial Current .96 A or smaller Control Voltage 7.3 - 7.4 V Float Use Control Voltage 6.8 - 6.9 V

Physical Dimensions: in (mm)


2.41 (61)

Terminals
L: 2.41in (61mm) W: 1.30in (33mm) H: 3.82in (97mm) TH: 4.03in (102mm) Tolerances are +/- 0.04 in. (+/- 1mm) and +/- 0.08 in. (+/- 2mm) for height dimensions. All data subject to change without notice.

4.03 (102) 1.30 (33)

3.82 (97)

6.35

4.45

Discharge Time vs. Discharge Current

Discharge Characteristics

Cell voltage (V/Cell)

(Minute) Discharge time

(Hour)

www.upgi.com
1720 Hayden Drive Carrollton, Texas 75006 P 469.892.1122 T 866.892.1122

All specifications are subject to change.

F 469.892.1123

sales@upgi.com
S1224-1

UPG No. D5695

UB6.2-6
Charge Characteristic
Charge Capacity Current Charge Voltage Charge

Maintenance-Free

(%) 120 100 80 60 40 20 0

(CA) (V/Cell) 2.33 2.17

Constant Charge At 0.25CA-2.30V (25oC) Charge Voltage Charge Capacity

0.25 0.20 0.15 0.10 0.05 0

100%Discharge 2.00 1.83 Charge Current 0 2 4 50%Discharge

Time(hour)

10

12

Shelf Life & Storage

Cycle Life vs Depth of Discharge

Open Circuit Voltage vs Residual Capacity

Effect of Temperature on Capacity

Charge Current & Final Discharge Voltage


Application Cycle Use Standby Charge Voltage(V/Cell) Temperature 25 (77 ) 25 (77 ) Set Point 2.45
2.28

Allowable Range 2.43~2.47 2.27~2.30

Max.Charge Current 0.30C

Final Discharge Voltage V/Cell Discharge Current(A)

1.75 0.2C>(A)

1.70 0.2C<(A)<0.5C

1.60 0.5C<(A)<1.0C

1.30 (A)>1.0C

Let UPG Power Your Life.

www.upgi.com
1720 Hayden Drive Carrollton, Texas 75006 P 469.892.1122 T 866.892.1122 F 469.892.1123 sales@upgi.com