You are on page 1of 1

Seq.

Room Number Room Area CMH CMS


Velocity of fan
m/s
Fan
Diameter
m
Fan Area
Fan Used
Number
Flow rate from
each fan
m^3/s
Total Flow
Rate
m^3/s
Required
Number of
Fan
1 1 34.56 5875 1.632 1.05 1.5 1.76625 2 1.8545625 3.709125 2
2 2 35 5950 1.653 1.05 1.5 1.76625 1 1.8545625 1.8545625 1
Room # 2
2. Fan Diameter =1.5 m
3.Velocity of Fan =1.05 m/s
4. The area of Room #2 =35 m^2
5. The Wall length of Room #2 =3 m
The Design Step : -
1. The area of Room #2 =35 m^2
2. The demand flow rate for Room #2 =34 *35*2 =5950 m^3/hr =5950/3600 =1.653 m^3/s
3. Q =A * V
A: Fan Area (m^2)
V: Fan Velocity (m/s)
Q: Flow rate from fan (m^3/s)
Q =(3.14/4) * (1.5)^2
Q =1.85 m^3/s

therefore, one number of ceiling fan is estimated to cover the required demand of flow rate for Room #2.
Ceiling Fan Calculation
The Design Criteria:-
1. 34 CMH/Person/m^2.
(054-057