505 Program Mode worksheet For 15 M.

W Turbine
TURBINE START -: SPEED SETPOINT VALUES :-
Manual Start No Overspeed Test Lmt (rpm) 6650
AutomaticStart No OverSpeed Trip (rpm) 6540
Semiautomatic Start Yes Max Governer Speed (rpm) 6360
Rate to Min (rpm/sec) 10 Min Governor Speed (rpm) 5820
Valve Lmtr Rate (%/sec) 2 Setpt Slow Rate (rpm/Sec) 5
Use Idle/rated? No Use Remote Speed Setpt ? No
Idle Setpt (rpm) Rmt Spd Setpt Max Rate (rpm)
Rated Setpt (rpm) Use Critical Speeds ? Yes
Idle/Rtd Rate (rpm/Sec) Critical Speed Rate (rpm/Sec) 30
use Auto Start Sequence Yes Critical Speed 1 Max (rpm) 3200
Cold Start = (>xx Hrs) 10 Critical Speed 1 Min (rpm) 2900
Hot Start = (<xx Hrs) 2 Use Critical Band 2 ? No
Low Idle Setpt (rpm) 600 Critical Speed 2 Max (rpm)
Low Idle Delay (Cold) 0 Critical Speed 2 Min (rpm)
Low Idle Delay (Hot) 0 OPERATING PARAMETERS :-
Rate to Hi idle (Cold) 8 Generator Application? Yes
Rate to Hi idle (Hot) 10 Use Gen Brkr Open Trip ? No
High Idle Setpt (rpm) 1600 Use Tie Brkr Open Trip ? No
High Idle Delay (Cold) 0 Use KW Droop ? Yes
High Idle Delay (Hot) 0 KW Max Load 15
Rate to Rated (Cold) 8 Droop (%) 5
Rate to Rated (Hot) 10 Rated Spd Setpt (rpm) 6000
Rated Setpt (rpm) 6000 Use Freq Arm/Disarm ? No
Auto Halt At Idle Setpts Yes Use Local/Remote No
Ext Trips in Trip Relay No DRIVER CONFIGURATION :-
Reset Clears Trip output No Act # 1 is 4-20 ma ? Yes
SPEED CONTROL -: Invert Driver Outputs ? No
Teeth Seen by MPU 60 Use Act 1 Fit Shutdown Yes
Gear Ratio 1 : 1 Act # 1 Dither (%) 0
Failed Speed Level (rpm) 250 Use Actuator # 2 ? No
Use Speed Input #2? Yes Act # 2 is 4-20 ma ?
Failed Speed Level (rpm) 250 Act # 2 Offset (%)
Off Line Prop Gain 3 Use Act 2 Fit Shutdown
Off Line Int Gain 0.2 Act # 2 Dither (%)
Off Line Deriv Ratio 5 Use Act # 2 as Readout ? No
Off Line Prop Gain 3.5 Act # 2 Readout is : (%)
Off Line Int Gain 0.25 Readout 4 ma value
Off Line Deriv Ratio 5 Readout 20 ma value
ANALOG INPUT :- CASCADE CONTROL :-
Analog Input # 1 Function Not Used Use Cascade control ? No
Input 1 4 ma Value 0 READOUT :-
Input 1 20 ma Value 100 Analog Readout 1 is Actual speed
Analog Input # 2 Function Not Used Readout 1 4ma Value 0
Input 2 4 ma Value 0 Readout 1 20 ma Value 8000
Input 2 20 ma Value 100 Analog Readout 2 is Speed SP
Analog Input # 3 Function Kw/Unit Load Input Readout 2 4ma Value 0
Input 3 4 ma Value 0 Readout 2 20 ma Value 8000
Input 3 20 ma Value 28.578 Analog Readout 3 is Not Used
Analog Input # 4 Function Not Used Readout 3 4ma Value 0
Input 4 4 ma Value 0 Readout 3 20 ma Value 100
Input 4 20 ma Value 100 Analog Readout 4 is Not Used
Analog Input # 5 Function Not Used Readout 4 4ma Value 0
Input 5 4 ma Value 0 Readout 4 20 ma Value 100
Input 5 20 ma Value 100 Analog Readout 5 is Not Used
Analog Input # 6 Function Not Used Readout 5 4ma Value 0
Input 6 4 ma Value 0 Readout 5 20 ma Value 100
Input 6 20 ma Value 100 Analog Readout 6 is Not Used
CONTACT INPUTS :- Readout 6 4ma Value 0
Contact Input 1 Function Generator Brkr Readout 6 20 ma Value 100
Contact Input 2 Function Utility Tie Brkr RELAYS :-
Contact Input 3 Function Not Used Use Relay # 1 ? Yes
Contact Input 4 Function Not Used Relay # 1 is Level Switch ? Yes
Contact Input 5 Function Not Used Relay 1 is Level Sw For Actual speed
Contact Input 6 Function Not Used Relay 1 ON Level 6180
Contact Input 7 Function Not Used Relay 1 Off Level 6130
Contact Input 8 Function Not Used Relay 1 Energizes On
Contact Input 9 Function Not Used Use Relay # 2 ? No
Contact Input 10 Function Not Used Relay # 2 is Level Switch ?
Contact Input 11 Function Not Used Relay 2 is Level Sw For
Contact Input 12 Function Not Used Relay 2 ON Level
FUNCTION KEY :- Relay 2 Off Level
F3 Key Performs Not Used Relay 2 Energizes On
Blink When not Active ? No Use Relay # 3 ? No
F4 key Performs Not Used Relay # 3 is Level Switch ?
Blink When not Active ? No Relay 3 is Level Sw For
AUXILIARY CONTROL :- Relay 3 ON Level
Use Axiliary Control ? Yes Relay 3 Off Level
Lost Aux Input Shutdown? No Relay 3 Energizes On
Use KW Input ? Yes Use Relay # 4 ? No
Invert Aux ? No Relay # 4 is Level Switch ?
Min Aux Setpt 3 Relay 4 is Level Sw For
Max Aux Setpt 16 Relay 4 ON Level
Aux Setpt Rate Unit/sec 0.5 Relay 4 Off Level
Use Aux Enable ? No Relay 4 Energizes On
Setpt Initial Value 15.5 Use Relay # 5 ? No
Aux Droop % 0 Relay # 5 is Level Switch ?
Aux PID Prop Gain % 1 Relay 5 is Level Sw For
Aux PID integral Gain (rps) 0.3 Relay 5 ON Level
Aux derivative Ratio % 100 Relay 5 Off Level
Tiebrkr Open Aux Disable No Relay 5 Energizes On
Genbrkr Open Aux Disable Yes Use Relay # 6 ? No
use Remote Aux Setting No Relay # 6 is Level Switch ?
Remote Aux Max Rate Relay 6 is Level Sw For
Aux Unit Of Measure MW Relay 6 ON Level
Relay 6 Off Level
Relay 6 Energizes On
COMUNICATION :-
Use Comunication ? No
505 Program Mode worksheet For 10 M.W Turbine
TURBINE START -: SPEED SETPOINT VALUES :-
Manual Start Yes Overspeed Test Lmt (rpm) 9800
AutomaticStart OverSpeed Trip (rpm) 9150
Semiautomatic Start Max Governer Speed (rpm) 8600
Rate to Min (rpm/sec) 225 Min Governor Speed (rpm) 7000
Valve Lmtr Rate (%/sec) 5 Setpt Slow Rate (rpm/Sec) 30.022
Use Idle/rated? Yes Use Remote Speed Setpt ? No
Idle Setpt (rpm) 3000 Rmt Spd Setpt Max Rate
Rated Setpt (rpm) 8306 Use Critical Speeds ? Yes
Idle/Rtd Rate (rpm/Sec) 2.998 Critical Speed Rate (rpm/Sec) 80
use Auto Start Sequence Yes Critical Speed 1 Max (rpm) 6200
Cold Start = (>xx Hrs) Critical Speed 1 Min (rpm) 5500
Hot Start = (<xx Hrs) Use Critical Band 2 ? No
Low Idle Setpt (rpm) Critical Speed 2 Max (rpm)
Low Idle Delay (Cold) Critical Speed 2 Min (rpm)
Low Idle Delay (Hot) OPERATING PARAMETERS :-
Rate to Hi idle (Cold) Generator Application? Yes
Rate to Hi idle (Hot) Use Gen Brkr Open Trip ? No
High Idle Setpt (rpm) Use Tie Brkr Open Trip ? No
High Idle Delay (Cold) Use KW Droop ? No
High Idle Delay (Hot) KW Max Load
Rate to Rated (Cold) Droop (%) 5
Rate to Rated (Hot) Rated Spd Setpt (rpm) 8305
Rated Setpt (rpm) Use Freq Arm/Disarm ? No
Auto Halt At Idle Setpts Use Local/Remote No
Ext Trips in Trip Relay DRIVER CONFIGURATION :-
Reset Clears Trip output Yes Act # 1 is 4-20 ma ? No
SPEED CONTROL -: Invert Driver Outputs ? No
Teeth Seen by MPU 83 Use Act 1 Fit Shutdown No
Gear Ratio 1 : 0.53 Act # 1 Dither (%) 0
Failed Speed Level (rpm) 250 Use Actuator # 2 ?
Use Speed Input #2? Yes Act # 2 is 4-20 ma ?
Failed Speed Level (rpm) 250 Act # 2 Offset (%)
Off Line Prop Gain 4.907 Use Act 2 Fit Shutdown
Off Line Int Gain 0.463 Act # 2 Dither (%)
Off Line Deriv Ratio 5 Use Act # 2 as Readout ? No
Off Line Prop Gain 5.976 Act # 2 Readout is : (%)
Off Line Int Gain 0.625 Readout 4 ma value
Off Line Deriv Ratio 5 Readout 20 ma value
ANALOG INPUT :- CASCADE CONTROL :-
Analog Input # 1 Function Not Used Use Cascade control ? No
Input 1 4 ma Value 0 READOUT :-
Input 1 20 ma Value 100 Analog Readout 1 is Actual Speed
Analog Input # 2 Function Not Used Readout 1 4ma Value 0
Input 2 4 ma Value 0 Readout 1 20 ma Value 9999
Input 2 20 ma Value 100 Analog Readout 2 is Actual Speed
Analog Input # 3 Function Not Used Readout 2 4ma Value 0
Input 3 4 ma Value 0 Readout 2 20 ma Value 9999
Input 3 20 ma Value 100 Analog Readout 3 is Actual Speed
Analog Input # 4 Function Not Used Readout 3 4ma Value 0
Input 4 4 ma Value 0 Readout 3 20 ma Value 9999
Input 4 20 ma Value 100 Analog Readout 4 is Actual Demand
Analog Input # 5 Function Not Used Readout 4 4ma Value 0
Input 5 4 ma Value 0 Readout 4 20 ma Value 100
Input 5 20 ma Value 100 Analog Readout 5 is Not Used
Analog Input # 6 Function Not Used Readout 5 4ma Value 0
Input 6 4 ma Value 0 Readout 5 20 ma Value 100
Input 6 20 ma Value 100 Analog Readout 6 is Not Used
CONTACT INPUTS :- Readout 6 4ma Value 0
Contact Input 1 Function Generator Brkr Readout 6 20 ma Value 100
Contact Input 2 Function Utility Brkr RELAYS :-
Contact Input 3 Function Not Used Use Relay # 1 ? Yes
Contact Input 4 Function Not Used Relay # 1 is Level Switch ? Yes
Contact Input 5 Function Not Used Relay 1 is Level Sw For Actual Speed
Contact Input 6 Function Not Used Relay 1 ON Level 600
Contact Input 7 Function Not Used Relay 1 Off Level 450
Contact Input 8 Function Not Used Relay 1 Energizes On
Contact Input 9 Function Not Used Use Relay # 2 ? Yes
Contact Input 10 Function Not Used Relay # 2 is Level Switch ? Yes
Contact Input 11 Function Not Used Relay 2 is Level Sw For Actual Speed
Contact Input 12 Function Not Used Relay 2 ON Level 7500
FUNCTION KEY :- Relay 2 Off Level 7400
F3 Key Performs Idle/Rated Relay 2 Energizes On
Blink When not Active ? No Use Relay # 3 ? Yes
F4 key Performs Not Used Relay # 3 is Level Switch ? No
Blink When not Active ? No Relay 3 is Level Sw For
AUXILIARY CONTROL :- Relay 3 ON Level
Use Axiliary Control No Relay 3 Off Level
Lost Aux Input Shutdown? Relay 3 Energizes On Overspeed Trip
Use KW Input ? Use Relay # 4 ? Yes
Invert Aux ? Relay # 4 is Level Switch ? Yes
Min Aux Setpt Relay 4 is Level Sw For Actual Speed
Max Aux Setpt Relay 4 ON Level 8800
Aux Setpt Rate Unit/sec Relay 4 Off Level 8700
Use Aux Enable Relay 4 Energizes On
Setpt Initial Value Use Relay # 5 ? No
Aux Droop % Relay # 5 is Level Switch ?
Aux PID Prop Gain % Relay 5 is Level Sw For
Aux PID integral Gain (rps) Relay 5 ON Level
Aux derivative Ratio % Relay 5 Off Level
Tiebrkr Open Aux Disable Relay 5 Energizes On
Genbrkr Open Aux Disable Use Relay # 6 ? No
use Remote Aux Setting Relay # 6 is Level Switch ?
Remote Aux Max Rate Relay 6 is Level Sw For
Aux Unit Of Measure Relay 6 ON Level
Relay 6 Off Level
Relay 6 Energizes On
COMUNICATION :-
Use Comunication ? No