DUCT CONSTRUCTION All ductwork will be built to SMACNA guidelines All ductwork will be built out of G-60 coated galvanized steel of lockforming grade conforming to ASTM Standards A-525 and A-527, unless otherwise specified. Duct sides that are 19” and over are 20 gauge or less, with more than 10sq. Ft. of unbraced panel area shall be beaded 12” on center as in fig. 1-8, page 1-45 of SMACNA HVAC Duet Construction. Al longitudinal seam will be Pittsburgh seam. (Type L-1) Fig. 1-5 Page 1-40 SMACNA HVAC Duet Construction. Also on large duct we may use standing seams for stiffness and seam. Transverse joint reinforcement will be: Class A connection Flat Drive Table 1-18 pg. 1-43 Class B & C connection Standing S T-10 Table I-11 pg. 1-24 Class D connection TDC or Elgen Flange see insert Class E connection TDC or Elgen Flange see insert Class F connection TDC or Elgen Flange see insert Class G connection TDC or Elgen Flange see insert Class H-J K connection TDC or Elgen Flange see insert + Pocket depth from Yi, to % in. + Use on straight duct and fittings ‘ASO SEAL THS [| BOcKeT Ar EAS + To+10in.we WHEN SEALING SEANG! PITTSBURGH LOCK id NITS b f zl + %in. pocket depth for 20, 22, and 24 ga +. Yin. pocket depth for 24 and 26 ga + Tot4in. wg ‘+ Sorews must be added at the ends ofall duct of 4 in. wg and at the ends of 3 in. wg when the duct i is over 48 in. width BUTTON PUNGH SNAP LOCK a + welones “3 GROQVED SEAM ‘ALSO CALLED FLAT LOGKAND PIPE LOCK + To 10 in. wg * 1 in, seam up to duct width of 42 in. * 1% in. seam for larger ducts © May be used on duct interiors ‘© Fasten at 2 in, maximum from ends and at 8 in, ‘SEE FIG.2-7 ALSO LA STANDING SEAM rooriownieticrale . + To+10in. we + Fasten as per L-4 L-S SINGLE CORNER SEAM * Assemble per Figure 2-17 Tv * Ratings may be adjusted with El-rated bar stock | ‘or members from Tables 2-29 and 2-30 + Supplemental members may be attached to the uct wall on both sides of the joint FLANGED FLANGED 3 + Single members may be used if they are fastened (WITH GASKET (WITH GASKET) 1-250 T-250 through both mating flanges TOC * Gasket to be located to form an effective seal FIGURE 2-2 RECTANGULAR DUCT/LONGITUDINAL SEAMS 210 HVAC Duct Construction Standards Metal and Flexible + Third Edition Rat + T 1 | tt 12 a T-10 T- T-12 T-14 en StandingS | StandingS | StandingS | Standing S wr wr Wr Wr Wr | ax x xt [YT] ax xT+ Er HxT iF HxT LF HxT LF ‘HxT LF a ‘HR iF A | 0.43 | UseB UseB %x26 ga 05 | UseB UseD B| 10 |1Kx26a | 04 |ix26m | 06 [EX | 06 l1xa6m | 07 |ueD CLs [Thx [06 [Ix | 08 [xz | 08 ixatm | 08 [UeD 1#x20 ga 120 ge 1% x24 ga p| a7 jikxism | os |1%5%M | os [Txcoe | os lim xz | 10 | ee | 14 ine z | 65 viet | 10 [raise | v0 [| 12 [er 1X22 ga F | as UeG UeG Wem | 15 14x20 9 [iss Vextse [13 vixit | is [1x28 [17 1% x18 ga H | 26a Team | 20 NOT GIVEN - te 1] 6 nonGims 2xaxK | 29 N ane (OT GIVEN Noreen [ecibg J | 80 2x2x%e 37 ‘Angle x [ios N L | 207 ror: Table 2-31 Transverse Joint Reinforcement See Section 2.1.4. *Effective El is number listed times 105 before adjustment for bending moment capacity. T-2 and 7-10 through T-14 are restricted to 30 in. length at 4 in. wg, to 36 in, length at 3 in. wg and are not recommended for service above 4 in. wg. (+) indicates positive pressure use only. 2.74 HVAC Duet Construction Standards Metal and Flexible » Third Edition ED TR J oar! wn» | eq, ft | Bee 1 T25a 4 Flanged LT Harkin | om ‘ anenay GASKET | qt GASKEN Seen) Tow wit caer siaiatl ae 1-24 T-24a T-25b Slip-On Flan a am Flanged ged Flanged Flange 7 wr wr] uxt LWT] uxt [wr Be) xT [oe | TS For] Wom) [or | Wom) [oF B [10 [UeE Use Used Teed. C | 19 |UseE Use D: Use D ‘Use D D | 27 [Use 26g | 05 [ixazm | 04 [26 [05 | const manntac- E [6s [cixé [17 [4 | 06 [User 24 gx >| 06 | turers for ratings established by per- F [usar [17 jaw [or [eme| 0 ze 07 by pe 2® x o mented to fine G | 158 | xh 21 2G 1.0 | 1kx18 ga] 08 20 ga 10 tional exieeria ia Chapter 11. See a | 264 [CXR | 26 lize | 8m | 1a | ere on pee 1 | © |txh 3.7 [20ga(R) | 10 20 ®) | 10 ~ exh SEE TIE ROD a | 90 [eo a7 |wa@ |i. Text [i8mq@ | 11 K | 103 [ax%e 3 [te® [1 Bae [i L [207 [waxk [65 |we@ [1a we ®) | 1 2.76 Table 2-32 Transverse Joint Reinforcement See Section 2.1.4. "Effective EI is number listed times 10° before adjustment for bending moment capacity. For T-22, ‘ee tie rod downsize options in Tables 2-1 to 2-7; one rod for two angles. (R) means Tie Rodded. Accepted Pressure Mode for T-24ais (+) or (-)2 in. wg maximum. See Figures 2-5 and 2-6 and tie rod text. (+) indicates positive pressure use only, HVAC Duct Construction Standards Metal and Flexible » Third Edition RE ALTERNATE FLANGE STYLE. The joint may bbe formed without the %" (9.5 mm) flange if the duct is held Yo" (3.2 mm) back from the vertical face of thé angle and tackwelded to the flange ‘along the edge of the duct. The angle is otherwise fastened normally. For additional tightness, place sealant between the angle and duct or seal the weld. Ifthe faces of flanges are flush, thick-consistency sealant may be used in lieu of gasket. Otherwise, use a gasket suitable for the specific service and fit it up uniformly to avoid its protruding inside the duct, ‘Joint T-24, FORMED FLANGE: Mating flanges are formed on the ends of the duct in double flange style to create a tee shape when assembled. A minimum of 16 gage (1.61 mm) thickness steel comer pieces with %" (9.5 mm) minimum diame- ter bolts shall be used to close comers. J4" (6.4mm)by e" (13 mm) minimum gaskets of suit- able density and resiliency shall be continuous around the jointand shall be located to form an ef- fective seal. Mating flanges shall be locked to- gether by 6" (152 mm) long clips located within 6* (152 mm) of each comer. Clips shall also be spaced at centers not exceeding 15" (381 mm) for 3" wg (750 Pa) or lower static pressure, and not exceeding 12" (305 mm) for 4" (1000 Pa), 6* (1500), and 10" (2500 Pa) wg Flanges may also be assembled per Figure 1-15. Joint T-24a. This is a modified version of T-24 that is ‘assembled per Figure 1-15. Unless supplemental reinforcements are incorporated itis limited to2" ‘we (500 Pa) maximum service, Joints T-25a and T-25b. These systems are also known bythe trade names TDC® and TDF®, respecti ly, Assembly specifications are given in Figure 1-15. Ratings in Table 1-12 may be adjusted when combined with EI rated flat bar stock or members from Table 1-10. The supplemental reinforce- ‘ments may be attached to the duct wall on both sides of the joint or use single membersifsuch are fastened through both mating flanges. ‘See Figure 1-4A fora commentary on proprietary joint systems, and see Chapter VII for joint performance evaluation, ‘See Tables I-11, 1-12, and T-13 for additional joint specifications. ‘See Figure 1-11 for attachment of joint backup rein- forcements to the duct. ‘See Figures 1-2 and 1-3 for use of tie rods. ‘See Figures 1-13 through 1-16 for comer closures at Joints. 1.15 COMMENTS ‘There are several proprietary duct connection systems available and in use, Because such systems are propri- etary or have proprietary elements, SMACNA does not evaluate or grade them. However, SMACNA does encourage the development and use of new technology and it invites authorities to consider alternative ‘constructions. Authorities may evaluate alternatives ‘using analyses and tests such as those described in Sec tion VII of the standards or using other means they deem appropriate. Consult the manufacturers of alter- native systems for ratings, assembly requirements and recommendations. ‘Note that joints previously shown in earlier editions can still be used. T-4, 9, 17, 18, 9, 20, and 23, omitted due toinfrequentuse, may still beused perthe firstedi- tion if acceptable to the specifying authority. % in. we Static Reinforcement Code for Duct Gage Number Pos. or Neg. Ne. i Reinforcement a Required Reinforcement Spacing Options = 10k | 8k | 6R | SR | 4h | 3H | MA] 28 © ® ®@/1|O|O|O/0O ©| © Tim. andunder | 26 ga. Hi in 26 ga. 13-14 in, 26 ga. Not Required 15-16 in. 26 ga. 17—18 in. 26 ga. 19-20 in. 24 ga. B26 | B26 | B26 | B26 | B26 | B26 | A26 | A26 21-2 in, 22 ga. B26 | B26 | B26 | B26 | B26 | B26 | B26 | A26 23-24 in, 22 ga. C26 | 626 | c26 [B26 | B26 | B26 | B26 | B26 25-26 in. 20 ga. C26 | 626 | 626 [C26 | B26 | B26 | B26 | B26 27-28 in, 18 ga. C24 | 626 | C26 [626 | 026 | B26 | B26 | B26 29-30 in, 18 ga. 24 | 626 | C26 [626 | C26 | B26 | B26 | B26 31—36in, 18 ga. p22 | D-24 | c26 | C26 | C26 | C26 | C26 | BIG 37-42in, 16 ga. E20 | B24 | D2 | p26 | C26 | C26 | 026 | 26 43-48 in. 16 ga. E20 | £22 | B24 | £26 | D26 | D-26 | 026 | C-26 | 49 54in, Fis | F20 | B22 | £26 | E26 | E26 | p26 | C26 55-60 in. Gis | F20 | F22 | B24 | B24 | £26 | B26 | D26 61 7in, wis | His | F20 | F22 | F24 | B24 | B24 | B24 B84 in. Not Designed 116G [HisG |w22G | G24 | F24 | R24 | R24 85-96 in, 1166 | Fis |w20G [H2G | G22 | Fa | F2 97 — 108 in. T16G | bisG | Fi8G | H18G | HA18G | G18 109 - 120 in. E166 | F166 | ri8G | H-18G [H-18G. 214 Table 2-1 Rectangular Duct Reinforcement HVAC Duet Construction Standards Metal and Flexible « Third Edition Re Tin. state Reinforcement Code for Duct Gage Number Pos. or Neg. No Reinforcement Dect Required Reinforcement Spacing Options Dimenaien. 10k | 8R | OR | 5R | 4R | 38 | MR] 28 © @ ©|O/O|O/O|O/O|(®@ T0in, and under | 26 ga, ll 12in, 26 ga. Net Roquied 13-14 in. 26 ga. I 15 — 16 in. 26 ga. 1 17—18in. 24 ga. [p26 [326 [B26 [B26 [-B26 | B26 | B26 1920 in. 24 ga. | c26 [cas | C26 [C26 | B26 | B26 | B26 21-22in. 22 ga. 24 | 24 | 26 | C26 | C26 | B26 | B26 | B26 23-24 in, 22 ga. cz | c24 | C26 [C26 | 626 | C26 | B26 | B26 25-26 in, 20 ga. D2 | D-24 | C26 | C26 | 26 | C26 | C26 | B26 27-28 in, 18 ga. D2 | D24 | D26 | C26 | 626 | C26 | C26 | C26 29-30in, 18 ga. E22 | D24 | D26 | p26 | 26 | C26 | C26 | C26 31-36in 18 ga. E20 | B22 | B24 | D24 | D26 | C26 | C26 | C26 37—42in, 16 ga. Fis | F20 | £22 | 24 | B26 | D26 | D26 | C26 3— 48 in, 16 ga. Gis | Gis | F20 | 2 | B24 | £26 | E26 | Das 4954 in, His | His | G20 | F22 | F24 | B24 | B24 | B24 35_ Oia, is | wis | G20 | G22 | F24 | Fos | B24 [ Ema 61 7in, LisG | HisG | HisG |H22G | F24 | F248 | P24 73-84 in, Not Designed Lise | Lise | 1206 | w2G [H2G | G22 85-96 in. Tien | rise | Cis | 1206 [W206 | #226 97108 in. Hien | Fis | F186 | rise | risa 109 — 120 in. : ‘iow | risH | risa | risa Table 2-2 Rectangular Duct Reinforcement 2i6 HVAC Duet Construction Standards Metal and Flexible Third Edition CE Zin. we Static a Reinforcement Code for Duet Gage Number Fos oF Net | netnforcement _ Required Reinforcement Spacing Options Diacacian ok | 8R | 6A | sR | 4h | 3R [MA] 2k | ® ® ©|O/O/O/O © Tin and under | 26g Not Required 1 Din 26 ga. 1B 14a, 24 ga B26 | B26 | B26 | B26 | B26 | B26 | B26 15 16in, 24 ga. ©26 | 626 | C26 | C26 | C26 | B26 | B26 17-180. Zsa. ©26 | 626 | C26 | C26 | C26 | C26 | B26 19-20 in. 20 ga. cz | c2 | c26 | c26 | C26 | C26 | C26 | C26 21-21, 18 ga. D2 | D24 | D26 | D26 | C26 | C26 | C26 | C26 23-24 in. 18 ga. ER | £24 | D26 | D26 | D26 | C26 | C26 | C26 25-26 in. 18 ga, E2 | E22 | B24 | D26 | D26 | C26 | C26 | C26 27=28in, 18 ga. F20 | B20 | B22 | B24 | D26 | D26 | C26 | C26 29 ~30in 18g. F20 | F20 | B22 | B24 | B26 | D.26 | D26 | C26 31-36in, 16g. Gis | G20 | F22 | F24 | B24 | B26 | D26 | D26 37—@2in Hl6 | Hs | 620 | G22 | F24 | B26 | B26 | B26 848 in ris | 20 | H22 | G22 | F24 | F24 | B24 49-54. T16G | F18G [1206 | #206 | G24 | F24 | F24 35-60 in. Tse | 1206 |H-20G | G22 | G24 | P24 o-2ia. Not Designed HIGH | FisH | 1206 | H22G [226 | 24 73 84in. | TioH | 1-206 | 1206 | £226 | 1-226 3596 in ‘is | FIs | F20H | 122m 108 in : K-l6l | Kesh | 18H | Lise Kiet | Kis | F181 Table 2-3 Rectangular Duct Reinforcement 218 HVAC Duct Construction Standards Metal and Flexible « Third Edition CH 3 in. we Static Reinforcement Code for Duct Gage Number Pos. or Neg. No Reinforcement Duet Required Reinforcement Spacing Options ee a ie ion | 8& | 6h | sh | 4& | 3h | mA] 28 © @ ©|©|O/O}|O|9O/oe Tin andunder | 24 ga, Not Required | B26 | B26 | B26 | B26 | B26 | B26 Hin, 24 ga. B26 | B26 | B26 | B26 | B26 | B26 Bin 22 ga cas | C24 | 626 | C26 [ B26 | B26 15 16im. 22 ga. cm | cm [26 | c26 | 026 | 626 17-18in. 20 ga D2 | D2 | C24 | C26 | C26 | C26 | C26 19-20 in. 18 ga. p22 | D22 | p24 | p24 | C26 | C26 | C26 21-22in, 18 ga. E2 | 2 | p24 | p24 | D2 | c26 | C26 23-24 in, 18 ga. E20 | 2 | £24 | £24 | D26 | D26 | C26 25 ~26 in. 18 ga. F20 | Bm | B24 | £24 | D26 | D26 | C26 27-28, 18 ga. F20 | F20 | F2 | £24 | B26 | D26 | DI 29—30in, 18 ga. G20 | 20 | F22 | E24 | £26 | £26 | D26 31—36in ign |wisG [Husa |H18G | G20 | F22 | F24 | B26 | B26 37-42 in 1i6G [wise |H20G | G22 | R24 | R24 | B26 B—48in, Hien | 1186 | ri8G | #20 | G22 | G24 | 24 9 —S4in, FieH | rac | ric [H2G | G24 | G24 55 — 60 in. Hie | 1186 | rise | 1-206 [#226 | G24 61 72in, Not Designed Fiat | si8H | 1206 | 126 | 1246 B84 in Laat | K-16H | eign | 20H | 1-226 85-96 in, Lig | K-ist [Fie | 1200 97 = 108 in. Lag | List | Kist 109 — 120 in. Lie | List | Kish Table 2-4 Rectangular Duct Reinforcement 2.20 HVAC Duct Construction Standards Metal and Flexible « Third Edition Ee in. we Static Reinforcement Code for Duct Gage Number Pos. or Neg. No Reinforcement Duct Required Reinforcement Spacing Options imenalon: lok | 8R | 6h | SA | 4R | 3% | WHA[ 2A © ® ©|©|O|O/O ©|® Sin. and under 2A ga. B26 | B26 | B26 | B26 | B26 | B26 9=10in 2 ga. Not Required “324 | B26 | B26 | B26 | B26 | B26 iin, 22 ga. B24 | C24 | C26 | C26 | 026 | B26 | B26 13-14 in. 20 ga. cz | cm | crm | C26 | 626 | c26 | 026 15— 16 in. 20 ga. p22 | D2 | c2s | C26 | 626 | c26 | C26 17-18 im. 18 ga. p22 | D2 | p24 | p26 | 626 | C26 | C26 19—20in. 18 ga. £20 | B22 | B24 | D24 | p26 | C26 | C26 21-2in. 18 ga. £20 | £20 | B24 | B24 | p26 | p26 | C26 23-24 in, 18 ga. F20 | F20 | B22 | B24 | £26 | D26 | D26 2526 in. 16 ga. Gis | Gis | F20 | Fa | E24 | B26 | B26 | D26 27-28 in, 16ea | H18G | Gis | G20 | F22 | P24 | 26 | B26 | D-26 29—30in, Ieee | H8G |Hi8G | Gis | G22 | F24 | B26 | B26 | £26 31-36 in, len | ri6G | HisG | H-20 | G22 | F246 | F26 | E26 37-42in, Tien | 1166 | 1186 | H-206 | 6-22 | 624 | F26 3 48in, FleH | 1186 | r18G | H22G [H-24G | G24 954i, Flan | Fis | 8G | £206 | H226 | W274 35-60 in. He 1206 | 1236 | #246 61-72in. Not Designed — HisH | 1208 | 1226 73-84 in, Kast | rist_| 1208 85-96 in. Lie | K-18 | 3-201 97-108 in. 7 Lt | L-tsi | L-ist 109 — 120 in. Lie | Liss | Liss Table 2-5 Rectangular Duct Reinforcement 2.22 HVAC Duct Construction Standards Metal and Flexible « Third Edition SE 6in. wg Static Reinforcement Code for Duet Gage Number Pos. or Neg. No Reinforcement back ‘Required Reinforcement Spacing Options pimeaiies oR | sf | OR | 5H | 4k | 3R | MAR] 28 © ® ®|O/9O}O|O ©|© Bin andunder | __24 ea C26 | ©26 | B26 | B26 | B26 . Not Required 9-10in. 2A ga. B24 | C24 | C24 | B26 | B26 | B26 1-1in. 20 a. cm | cm | cr | cr | C26 | C26 | C26 1B-Isin, 20 ga. cz | b20 | p22 | cr | C26 | C26 | C26 15— 16a 18 ga p20 | D20 | D2 | p24 | p26 | c26 | C26 17-18 in Be. | E20 | £20 | B22 | B24 | D26 | D26 | C26 19-20. 16 ga. Fis | F20 | F20 | B22 | B24 | D2 | D26 | D26 212i, 16 ga. Fis | Fis | F20 | P22 | F24 | £24 | £26 | D26 23-24 in, 16 ga. Gis | Gis | G20 25-26 in. H16G | H-16G | G18 27-28 in. TE16G | H-i86 29-30 in. 1166 | H-18G 31-36%, Hie 37 ain. GH 8-4 in. 49~ S4in. 3560 in, Not Designed in. 73— 84 in. 8596 in, 97—108 in. 109 — 120 in. Table 2-6 Rectangular Duct Reinforcement NOTE: t following Reinforcement Class letter code indicates tie rod required. 2.24 HVAC Duct Construction Standards Metal and Flexible « Third Edition SED 10in. we Static Reinforcement Code for Duct Gage Number Pos. or Neg. No Reinforcement reek Required Reinforcement Spacing Options Dineeasion oR | 8h | 6k | sR | 4m | 38 | eA ® ORRCHECHECHECH ECE EC) 2. C20 | ea | C26 | C25 | C26 | 026 20 ga. Not Required C29 | c22 | C24 | ©26 | 026 | C26 18 ga e20 | p20 | p22 | p24 | C26 | 26 | €26 18 ga p20 | E20 | £20 | p22 | D2 | p26 | C26 16g. | E18 | Exe | Eve | £20 | £20 | B24 | D2 | D26 16 ga. Fis | Fis | Fis | F20 | F20 | E24 | B24 | D26 Gis | Gis | Gis | Gis | F20 | Fm | B26 | B24 Wi6G | HisG |H-18G| Gis | G20 | F22 | Fas | B24 TisG | rec [H-18G [#-i8G |H-20G | G22 | F2s | P24 7166 | F166 [w-18G | H-20G | G22 | F246 | P24 Tic | rise |H-18G |H22G | G24 | F24 7166 | Fisa | 1186 [H22G |H24G | G24 Tie | F18H | 1200 [H20G | H-24G Hot) Fist] 1186 | F20H | 1226 viet | S18 | bist | 1-228 Not Designed Lia | K-1s | 18H | P20 | cae | K-ret [ 3-201 | Lia_| Last | Lier Lag | Lier “[e6 Leis 109 — 120 in. Leis Table 2-7 Rectangular Duct Reinforcement NOTE: t following Reinforcement Class letter code indicates tie rod required. 2.26 HVAC Duct Construction Standards Metal and Flexible « Third Edition SE 10in. we Static Be Reinforcement Code for Duct Gage Number Pos oF Net _| Reinforcement Dect Required Reinforcement Spacing Options Dimension on | @f | 6R | SR | 4h | 3M | wR | 2 ® ® ORRCH ECE ECHEG) ®| © Sin end under | __22 a cx | C24 | C26 | C26 | C26 | C26 9 10in 20 ga. Not Required C29 | C22 | C24 | C26 | C26 | C26 11-12 in, 18 ga c20 | p20 | p22 | p2s | c26 | 26 | 26 B= 1in, 18 ga. p20 | £20 | £20 | p22 | p24 | D26 | C26 15—I6in, 16 ga. Els | E18 | £18 | £20 | £20 | £24 | D24 | D26 17-18 in, 16 ga. Fis | Fis | Fis | F20 | F20 | B24 | B24 | D-26 19-20 in, Gis | Gis | Gis | Gis | F20 | Fm | B28 | BA 21 22in. H-6G [His |H-isG | G18 | G20 | P22 | R24 | B24 23-26 in. T16G | FisG [H-sG |H-i80 |H20G | G22 | F24 | P24 25-26 in, 16 | F166 |H-186 | H-20G | G22 [F248 | P24 27-28 in. 1H6G | FisG [Hse | #226 | G24 | F246 29-30 in. 166 | F186 | 11aG | #226 |H28G | G24 31-36in. Ti6H | Fis | 1206 | #226 | H24G 37-42 in. Tit | F181 | 1186 | F20H | 1-226 43 —48 in. va | Far | eis | -22H 49-54 in. Not Designed Ls | K-tat | seit | -20n 3560 in. Lia | K-18 | 5-201 6 2in. TA | List | Lisi B84 in, L-l6t | Lis 35-96 in. "[Lei6 97 108 in. Ltl6 109 120 in. Le16 NOTE: t following Reinforcement Class leter code indicates tie rod required. 2.26 Table 2-7 Rectangular Duct Reinforcement HVAC Duct Construction Standards Metal and Flexible + Third Edition CEE RS 16 ga 18 ga 20 ga 22ga 24 ga 26 ga oF To96) Tosa) To60) | hin one To96(1) TBA). To 60(1) kis 2k To96(1) To 84(1)__To 60(1) 3h To 961)" To 84(1)* To 72(1)* To 60(l) To 48(1) 85-96(2) 73-842) —_61-72(2) Hin Din To96(I)* To84(1)* To 72(1)* To6O(1) To 48(1) we. 85.962) 73-842) 61-722) 28 To96(1)* To84(1)* To721)To72(1) To 48(1) 85-96(2) 73-96(2) 38 To 84(1)* To 601)" ‘Toa8(I)* ‘ToaX(l) To 36(1) To 96(2) 61-842) 49-72(2) 43-54(2) £2 in. 2% ft To84(1)* To 72(1)* To 60(1)* ‘To 54(1) To 42(1) we 85-96(2) 73-96(2)61-84(2)—55-60(2) 2 To 96(1)* To 72(1)* To 60(1) ‘To 60(1) ‘To 42(1) 73-96(2) _61-96(2)_61-72(2) 3 ft To 7(1)* To S4(1)* ‘To 48(1)‘To42(1) ‘To 30(1) 73842) $5-722)_49-54(2) Sin 2% ft To72(1)* To60(1)* ToS4(1)* To42(1)—To 36(1) we To.96(2) «61-84(2) 55-7202) 43-542) 2 To 84(1)* To 72(1)* To 60(1)* To S4(1) To 42(1) 85-96(2) __73-96(2)__61-84(2)__$5-72(2) 3 To842) To 60(1)" Tosa) _To48(1) _‘To36(1) To 30(1) 61-722) 55-6002) Ain. 2h Rt To72(1)* To60(1)* To48(1)~ To48(1) To 36(1) we 73-96(2) 61-72(2)—-49.60(2) 2f To 84(1)* To 60(1)* To 60(1) To 48(1) To 421) 85.96(2) 61-962) 61-722) __49-60(2) 3 To72@) ToSay* To421)_‘To3@1) —~«NA NA 55-602) 43-602) +6in 2% in. To 96(2) To 72(1)* ToS4(1) To 48(1)_— To 36(1) NIA wg To 84(2) 55-60(2) 28 To72(1)* To 60(1)* To48(1)_— To 36(1) N/A 73:96@)__61-72) __49-60(2) Table 2-41 Midpanel Tie Rod (MPT) Schedule (RS) NOTES: a, Table cells give duct width limit range in inches for use of one (1) and two (2) tie rods at midpanel (MPT) as a substitute for Table 2-29 intermediate reinforcements that would be centrally located between two other- wise qualified transverse joins. Joint spacings greater than six feet are not available for this alternative. 1N/A refers to a ga not available to RS condition. RS is the Reinforcement Spacing. ©. For some conditions and joint types, the MPT option is contingent on use of tie rods at joints (ITR). Jn some cases use of the MPT option would require that the gage be increased above those in Tables 2-1 to 2-6, An asterisk in Table 2-41 denotes a one tie rod thickness option when less thickness requires two rods. 2.100 HVAC Duct Construction Standards Metal and Flexible ¢ Third Edition cra) VERSA-CLEAT DESCRIPTION Snap-On Cleat BASIC USE Can be used in conjunction with a variety of TDC conneetions along with Ductmate 6451 AVAILABLE SIZES Desetnion ‘Guandiy | Unear Feet | Weight DVRCGA | © Srmpon TDC Chat | 250Pes./8or| 12578 | bss Bor DvIeCaA| 10 Grap-On TOC Chet] 1OLenste | T07/Bunde | 251! Bunte| ee SSS Galvanized Galvanneal PVC Coated 316 Stainless Aluminized MANUFACTURED BY: E)aearare Certairleed Specification Sheet ToughGard R Duct 1. PRODUCT NAME ‘ToughGard™ R Duct Liner 2. MANUFACTURER CertairTeed Corporation PO. Box 860 Valley Forge, PA 19482-0105 Phone: (610) 341-7 (600) 233. Fax: (610) 341-7571 Fax-On-Demand: (800) 947-0057 Website: wwwcertainteed.com 3. PRODUCT DESCRIPTION Basic Use: ToughGard R Duct Liner Insulation Is used primarily as an acoustical liner in HVAC sheet metal ducts to absorb unwanted crosstalk, equipment and air rush noise. ‘ToughGard R can be used in most types cofheating and cooling ductsysterns, oper- ating at velocities up to 6,000 fpm (30.5 ims) and temperatures fo 250°F (121°C). Benefits: ToughGard R provides excellent thermal properties, exhibits low air flow resistance and meets all applicable fire resitanpe standards and building code requirements. This product is durable, resistant to microbial growth ‘and easy-to-clean. ToughGard R’has a factory-applied edge coating that assures sealing of the transverse edges as SMACNA and NAIMA Installation Standards. The product can be precision cut using both manual and automatic cutting equipment. ‘Composton and Materials: Com perce, of carpe pas Ses fly mnded together with a thermoset rein overad with an exerely tough and durable fire-esistant, black com- posite surface on the air stream side. ‘The air stream surface contains an EPA registered anti-microblal agent in order to reduce the potential of microbial growth that may affectithis product. The antimicrobial properties are intended to only protect this product. Liner Limitations: Insulation should be kee clean and cry drng shipping ser , installation and system operation. °F Sirs: See he table below for aval- able sizes. Contact CertainTeed for avall- ability and minimum order quantities. 4, TECHNICAL DATA Applicable Standards: ‘+ Model Building Codes: (BOCA, CABO ICBO, SBCCI, ICC) — California Title 24 * Material Standards — (ASTM 1071) Type | * Fire Safety Standards = (NFPA 90, NFPA 90B) Fire Resistance: «Fire Hazard Classification: (UL 723, ASTM E 84, NFPA 255) Max. Flame Spread Index; 25 ‘Max Smoke Developed Index; 50 * Limited Combustible: (NFPA 259) -< 3500 Bulb i Properties: ‘Thermal Performance: — See table on back page. ‘Acoustical Performance: ~ See table on back page. * Operating Limits: — Temperature: (ASTM C 411) Max. 250°F (121°C) ~Air Velocity: (ASTM C 1071) ‘Max. 6,000 fpm (30.5 m/s) * Water Vapor Sorption: —(ASTM C 1104) < 3% by weight * Corrosion Resistance: (ASTM C 665) — Pass + Bacteria Resistance: (ASTM G 22) =No Growth + Fungi Resistance: (ASTM C 665 & ASTM G 21) Pass; No Growth 7 Certainfeed was the first fiber glass insulation manufacturer in the industry to have all its plants certi- fied to ISO 9002 standards. 5. INSTALLATION All duct liner shall be installed in accor- dance with the requirements of the NAIMA Fibrous Glass Duct. Liner Standard, or SMACNA HVAC Duct Construction Standard and the project specification. The liner shall be cut and fitted to assure all joints are neatly and tightly buted with no interruptions or gaps. Al duct liner products shall be adhered to the sheet metal ductwork using an adhesive meeting the requirements of ‘ASTM C 916. The adhesive film cover- age shall be a minimum 90% of the metal surface. Additionally, secure duct, liner as required to the sheet metal ductwork using mechanical fasteners (impact-criven or weld-secured). These = [te [= |. 1 [as] soso] 1267 _| sera | ooerets ised aa [ aa s0-t00_| is2.305 | 3472 [ooree9 = G2 kya) 2 [si | so7s_[s2-a29 | 3072 [ores 20 Be |» fs [seam | sae | 207 [eorias fasteners vary. in length and type, ‘Mechanical fasteners of the speci type and length sal be used assuring than 10% compression of the tne thickness Mavimurn festenet spac ing shall be in accordance with or SMACNA standards. ‘ToughGard R provides clean “buttered” transverse edges. However, some circumstances will require the use of adhesive to “butter” raw: liner ‘edges. Final job site “buttering” may be required to coat duct cut-ins and/or minor installation damage. jard Duct Liner fabricated duct sysems shall be hep clean and from the point of job lation and system com- missioning. Special precautions at the IMA job site may be necessary to accom- plish this. Design Considerations: + “Butter” all raw exposed edges High, in-duct air turbulence areas require special procedures, ie. pertrsted ‘inner metal liner, etc. ‘+ Metal nosings shall be securely installed over transversely oriented liner edges facing air stream at fan discharge and at any interval of lined duct preceded by unlined duct. re ee | Be | om wae | ae A Bu Ww Ts oom | _o20 | oe aso [ie [ae 02 | ons | ore | om © 10 2s 24 | oss | or | oss | 0a var [Zo 3 a2 0035 owe | 27a 2 oa? Therwal conducance (and vessance FD valics ae darved fom te matral thermal conducvty sale Tested in accordance wth ASTM C518 andl ASTM C 177 175° Ga" Ch mean temper tis woe as nc [as] 006 a7 1s0 [a [ae] ore 30 2 [| eae wea one Sound absorption vested In accordance with ASTM C 423 tnleg Type A mounting per ASTIN E705 ‘ASaint-Gobain Comosny 6. AVAILABILITY AND COST Manufactured nd sold throughout and Canada. For availability and cost contact your local distributof, or call CertainTeed warranty for ToughGard™ R Fiber Glass Duct Liner (30-33-01). 8, MAINTENANCE ‘An inspection abd preventative main- tenance progrart for the HVAC system is recom to ensure optimum performance. Uke NAIMA guidelines duct cleaning methods and proce- dures. ‘9. TECHNICAL|SERVICES Technical assst{nce can be obtained either from the lpcal CertainTeed sales representative, | or by calling Certainifeed in) Valley Forge, PA at (800) 233-8990. 10. FILING S¥: S Files, 15075/CER 1. No. 30-36-04 information avail- Visit us onjour website at www.certaintepd.com for the most Up-to-date product information, EN Sass NOTE: SEE TYPICAL DUCT BRANCH ENTRY CONDITION IN FIG. 2-6. pe NETAL NOSING MUST BE USED WHEREVER LINER IS PRECEDED Sy ONUNED METAL OTHERWISE WHEN VELOGITY EXCEEDS Aa 4000 FPM (20.3 MPS) USE METAL NOSING ON EVERY LEADING 7 Be Mesh way be Fomes ov oust on secuwwee — f/”\| OR ZEE ATTAGHED BY SORENS, RIVETS OR WELD ETAL - A METAL NOSING CHANNEL OR ZEE INTERIOR WDTH OF 8° (200 mm) AND LESS DOES NOT PINS. REQUIRE i AND BUTTED CORNER go SS Ln” “ THE VELOCITY RATED SIDE_OF LINER MUST FACE THE AIR FLOW ALL TRANSVERSE TO BE ATED WITH ADHESIVE. EXCEPT SECTION WHEN NOSNG IS (TYPICALLY 4 FT. Ss 2m) ‘OR 5 FT. (1.52 m) MAXIMUM SPACING FOR FASTENERS, UNER ADHERED To ACTUAL INTERVALS ARE. APPROXIMATE. aceite AREA COVERAC “ALIN ROW MAY BE OMITTED WHEN METAL NOSING IS (EN STARTS FROM THE NOSING. OF ADHESIVE ; Dimensions Seloatfy A B c D E ‘0 — 2500 FPM x ]osel a | or | te UNLESS A LOWER (0127 ws) | 78a) (805) | (102) | (152) | (457) LeveL Is SET BY = 6000 FPM el oa | gt | as OR LISTING = SOS MPS] (78.2) | (152) | (102) | (182) | (as) een FLEXIBLE DUCT LINER INSTALLATION FIG. 2-19 2.24 HVAC Duct Construction Standards Metal and Flexible - Second Edition we ‘SUBMITTAL RECORD Jo8 LOCATION SUBMITTED TO, SUBMITTAL PREPARED BY APPROVED BY DATE DESCRIPTION: When iner i placed inside airconditioning or heating duct ‘work, the movement of ar could cause the insulation 10 delaminate. 0 prevent this SMACNA Specifications call for the use of Fasteners in adc tion to achesive to secure the nec “The fasteners may be of three types: A” ADHESIVE: This fastener Is bonded to the ductwork with an ap- propriate achesive and alowed to setup, Alter sufficient drying time {he liner is impaled on the pin and a washer added to retain the lines B, MECHANICAL: This type of fastener attaches itself to the duct work. The mast popular syle is a hardened nal with an at- (WELDED FASTENERS CCP Washer Diameter—1.0", Gauge—.015-.017 Zinc Plated CRS Area—.785/s9.”, Pin Gauge—.15 dia. Zinc Plated. Approx. Pin Length me W ‘After Weld ITEM # — Deserip. Belore We Use Ci 26023 cPi2 49 385 *#" insulation 26024 CPs4 560531 eth # density 26025 CP100 906 Tai 1" 2#-3# 5 26032 cpii8 TIFTC Washer Diameter— 1.0, Gauge—015-017 Area —.785 69,", Pin Gauge— 130 dia. Zine Plated rox. Pin Length Descrip. elo Weld. Aer Weld TEM # 26072 FTCI2 49 365 ‘f" insulation (26073 FTC3a 856 531 1" Vet # (26074 FTCI00 906 781 1" 2#-3# ITEM # — Descrip. Approx. Pia Length Use 26001 PN34 7 17" insulation 26002 PNi14 125 1” insulation (2 26003 PN200 20 1-2" insulation 26004 PN250 25 2-3" insulation CULN Pins ————_ Pin Diameter 16 Gauge galvanized ITEM # Descrip. Approx. Pin Length Use (126149 LN 34 15 1" Insulation (26148 LN150 15 1 Insulation 026147 LN250 25 4114'-2" Insulation 26150 LN350 a5 2-3" Insulation (26151 LN450 45 3-4" Insulation 26152 LNS5O 55 4°-5" Insulation ( Washers for Spotter Pins Tem # —— Descrp, 026017 PC 3.0 1.4375 sq.” 026145) Lc1 Galvanized (26021 NCi —Nylon “Stop Clip” 12h" dia 0 26161 NC2 1 SCPM Stamped feed cl ¥8 Gauge (047 min) Zinc Coated CRS Appa. Pin Length ac” | ITEM # — Descrip. Before Weld After Weld Use 526042 SCPM-12 445-460 320 ‘/" insulation 55 26047 SCMP-100 1822-831 787 1" insulation Specification Forn DDIF-689 Insulation Fastene [DURO) DYNE tached washer. Ths fastener is impact driven through the liner a forms a postive mechanical grip withthe metal WELD: Ths fastener forms 2 permanent bond to the duct work t Decoming pat oft as inary weld. WO styl ae curently in si One Hke the mechanical fasteners dren through the ner an wel fed To the duct work undemeath. The second fastener is 2 pin whic iS welded to the ductwork prior tothe insulation. The ner i the impaled (much ie he adhesive fastener) over the pin and secu bya washer (CJ MECHANICAL FASTENERS (C786 Tripod Bangers—Washer Diameter —1" Gauge .015 Zinc Plated ‘Area—.77 sq,", Pin Diameter—.136 Zinc Plated hegre. ang After ITEM # —Deserip. Setting Setting Use (26129 TEG-12 475-375 ‘hs insulatior 26130 TBG-100 625 5251" 1-24 (526135 TBG-10H 750 650 1"3# Washer Diameter—1", inc Plated, Setting Use z 375 fs" insulatior BGTI00 62552517 1-2# BGTIOH 750-6501" 3# BGTIVH ‘900 800 1" 4-64 S118 1.250 1.150 TAT" 1500 1:400 C ADHESIVE FASTENERS Self Adhesive > Pin Diameter min, 13 Gauge Base Dimension 2 x 2 galvanized 28 Gauge stee! ‘Adhesive Polyethylene foam impregnated with rubber base adhesive. ‘Approx. ITEM # Descrp. Length Use (26067 SAH34 75 ‘ig insulation 26088 = SAHT14 1125 4 insulation (28069 SAHI34 175 1A" 1-1 26070 © SAH200 2.00 1h" 28+ 26071 SAH212 25 2 insulation = 1 Perforated Base Adhesive Hangers Pin 14 Gauge galvanized Base 2 x 2 28 Gauge galvanized ‘Agpror. ITEM # Descrp. engin Use 26075 = PBH34 15 1" insulation 26076 9 PBHII4 125 1 insulation (26077 PBHi34 175 VW" 11 ek 526078 = PBH200 20 1a e+ 526078 PBH212 25 2" insulation Oct-28-97 10:48A PROtack & PROtack HV PROUCK is a heh vscosy premiongtuaiy, water ase! duc ner ulhesve specifically formulated for spray and roller coai applications PROLack and PROtACK HV are used f0 bord fibrous duc ner insulation ‘w gulrained dact work, sea cut edges of fiberglass insulation, bond kraft backed foil covering to fiberglass and urethane fat stock or pipe insulation, and bond multiple layers of Obrous insulation beard. Piste Lea e eee ey Fire retardant. moisture resistant UL Classified Son eb-webbi Water cleanup uf tools and equipment PACKAGING INFORMATION Part No, Descuirrioy — Quaxrrry & Wetcirrs PROTACK PROTACKI 1Gal 4-1 gal pails @ 38 Ibe/es PROTAGS 5 Gal 1-5 gal pall @ 46 Ives PROTACKS4 54Gal 1-34 gal pail @ 510 Iby/drum | PROTACK HIGH VISCOSITY PROTACKIVI 1 Gal 41 pal pails @ 41 Ibs/es | PROTACKHYS 5 Gal 1-5 gal pail @ 51 Ihv/es | PROTACKHVS4 54 Gal 1-54 yal pail @ 600 Ibsdrum LIMITED PRODUCT WARRANTY Micro mesa helo pec damages: Tee ae mr {Urpin wars incon art ol aes spars pens ‘rou ha anc thn mt rk ys ea ‘Teo moras yer SNe ye aot Corer Paes Roc war re om ey mal ec ara aed want ete {sane naw ny War hoe eee tne of pes Bot ieey catlocarer wil wr skeen dr ar red ar eel parce pce ‘hae do ot pr the rls oh a Pick aa eee ‘Stn rca ear of ad awd tyra af ral eee oe ‘Sioa aan anager (ony, ca 05. enue ine Duct Liner Adhesive at BASE: Synthetic Latex covor: Black SOWENT: war WEIGHT PER GALLON: ROUCK_ BA PROMCKIV 22 soups PROUack 022% PROWKHY = 2% viscosity PreOuck 500 CP PROUCK IW $500 CPS APPLICATION ‘TEMPERATURE: 45°F (0 0"F STORAGE TEMPERATURE: 95° 0 90°F OPEN TIME: Dependent on temperature, humidity and application but yeneraly 19-20 minutes FLAMMABILITY: None FLASH POINT ‘No Mash to boiling COVERAGE: {)pkeal spay application may ye up 1400 x4 fVgallon SUBLE LIFE: (Unopened! containers) 1 year PACKAGING: Avallable in 1, 5 oF 54 gallons eee ERO ae (Can be applied hy brush, roller standard spray equipment, o roller coated. Maybe applied weer the annette ore Horo insulation, Al stel and/or fll surfaces shoul be free from all din, ol ‘and grease, For best results adhesive should not he thinned. ~, UNDERWRITERS LABORATORIES ING. j.)CLASSIFIED SY ADHESIVE. SURIACE: BURNING CHARACTERISTICS ROCK Duc Liner Adhesive apps tn inorganic ecru ard Fame Spread 5 Smoke Developed 0 ese appli at a coverage of 4.7 9 MV Hash post a igo tes (closed cop), mo Mash baling " 509 Distributed By, AS tts, Feb-17-97 12:20P SHEET METAL CONNECTORS, INC. 112 19th AVENUE NORTHEAST + MINNEAPOLIS, MINNESOTA 55418 Call toll free 1-800-328-1966 Locally, call 781-4811 FAX 612-781-2605 2” PUSH TYPE SIDE RAILS MATERIAL (SMC 324) 2" PUSH TYPE SIDE RAILS Made from 24 GA Galy Stee! 2" HOLLOW TURNING VANES (smc 226) bIMPLED SMC 324 EZ RAIL ——— STOCK LENGTH 10° 10 PCS PER BOX MATERIAL 2° Tuning Vane Made ftom 26a Gah Stee! US. PAT. # 4.467829 ‘This NEW EZ rail eliminates any need for dowels,screws or nails. Just one sharp rap a In the right place does it all! 3 SMC 226 stock LENGTHS 10 Storia Gate 2" — 10 PCS PER BUNDLE ‘ Effective: Dec. 1, 1990 ‘SUBMITTAL RECORD [DURO) © Specification Form ise DYNE SuuirTeDTo, DDFDC-1190 SUBMITTAL PREPARED BY ‘APPROVED BY Flexible Duct Connec one RELATED NFPA 90A & 90B DESCRIPTION STANDARDS: All air duct installations for heating, cooling or ventilation are attached to mechanical equipment containing 2 fn or blows Vibrations, noises and rattles resulting from operation of the fan or blower are transmitted into the metal ducts which carry the noises throughout the system. In order to isolate the vibration and noises to the source, an air-tight flexible joint, consisting of a fabric which is attached to sheet metal on both sides, must be inserted between the equip- ment and the ductwork. This vibration isolator is called a “Flexible Duct Connector’ O “METAL-FAB” Gauge: 24 Dimensions: 3 metal ‘S" fabrio—3" met ‘Seam: "Grip Loc 21.23 Vibrato Islan connectors induct sya te made oan approves lane relarcart lac Shall of steve jas th packing ot approved mara ha Hae sen ang of lot 22nd «se vs tng nto rate on cat Of ac sano exceed TO nches in ong NFPA N ‘sat 2.1.1 exe 3 Vibraton lation connectors induct sn ea a ego ae cra ae fongat al seve pls wih packing © approve fonbustble mera Vibration slsn connector Struc o ial shal at exceed 10 Inches in engi oso 1960 “SUPER meTaLras® 3 ‘8 fabrie—3" metal ‘Seam: "Grip Loo’ FABRIC COMPARISONS Excelon [MI Neoprene C1 Durolon Cnsuitlex _OThermatad Continuous Temp. Range —40°F to 180° MN —40°F to 200° 25°F to 250° 40°F to 180" 75°F. to SOO Color Black Black White Black Green Weight Per Sq. Yd. 2 30 4 28 (Composite Weight) w Abrasion Resistance 115,000 cycies {600 cycles ‘500 cycles ‘500 cycles 125 cycles Leakage Resistance 2 350 595, 250 125 15 Minimum Radiation Resistance of Fabric 319 x 10° 55 x 108 19 x 108 19 x 108 10 x 108 Tear Strength 4 wie wie an 78 Tensile Strength 5 500/450 225/300 70770 125/82 ‘ened! Pu Exolent Ozone and Low Smoke Emi Very Low Smoke Lo eal Furose, Ee aerng insulted” Emission Hh Resistance. 3-4-3 Configuration. Temperature Best overall Acid Resistant Resistance, Codes. Wela-rab MBX (#10159) MN MFN (#10000) FD (10002) IDC (#IOT73) MFT (#10005) Super Metal-Fab — MBGX (#10160) MFEN (#10012) MFOD (#10011) MEET (#10073) ‘Abrasion resstance a per Federal Test Standard 191 Method #306 using CS 17 wheal wit 250 Gram a0, Leakage resistance as por Federal Tost Standard 191 Method #5512. Resuts in P.S\. (To conve to Inches of water mulipy PS.1. 27.176.) Radiation resistance shawn fs In Racs and represents the amount of reiaton the fabric can withstand and stil ain 95% of ts tense srengh Teatsrengh in tongue pounds as por Federal Test Standard 191 Method #5134.1\(warp/l}) Tensile strength in grab pounds 25 per Federal Test Slandard 181 Method #5100 jwarp/), SUGGESTED SPECIFICATION Vibration Isolating Flexible Duct Connector for Heating, Cooling & Exhaust Supplies & Returns. At the inlet and discharge of all air handiing equipment (unless otherwise noted) furnish and install vibration isolators. Vibration isolators shall be @ coated woven fabric named and shall be ‘‘Underwriters Laboratories Tlassified™ Vibration Isolators shall have a Tear Strength of not less than . an abrasion resistance of not less than : and a continuous temperature range of vi Isolators shall be preassembled metal fo exposed fat metal. Fabric and metal shall be joined by means of a « lock seam. Vibration Isolators shall be Code (called F Duct Connectors) as manufactured by Duro Dyne Corpo Farmingdale, N.Y. 03-12-1996 @1: 05M FROM POTTORFE To 13106916399 P.21 SERIES 60 POTTOREFF [moder Han 60 & CAD 60 duct access door * Zine plated continwos piano type hinge (HAD models only) ‘+ Door-to-frame & frame-to-duct foam gasket. ‘+ HAD models with 'B'<14” have one lock, doors with B>14" have tw Jecks. + Cod models with 'B'< 14° have two locks, doors with B>14" have locks, + Outside frame size fts hole 1° smaller than door size, 1 Minimum size is 6'w x47. Maximum size i 24°w x 267. oo oo 9150 oGa ‘POTTORFF COMPANY INC. 700 SOUTH VAIL AVENUE MONTEBELLO, CA 90640 (218) 728-0008 TOTAL P.@1 Elevated Dial Regulators 627 VENTLOK ‘:" ELEVATED DIAL REGULATOR FOR 1" INSULATION This regulator is similar to our standard #620 Regulator except that it is on an elevated platform 11 high for use on insulated ducts. You may order by sets or individual parts. A set consists of one dial regulator, one #627 Square End Bearing, which has a 2" long shaft to reach the dial, and one standard #620 Spring End Bearing. Weight per 100 sets, 45 lbs. 628 VENTLOK ‘4" ELEVATED DIAL REGULATOR FOR 1/2" INSULATION Same regulator as #627, except platform is 1%" high. Order by sets or individual parts. Weight per 100 sets, 50 Ibs. 637 VENTLOK %" ELEVATED DIAL REGULATOR FOR 1" INSULATION This regulator is similar to our standard #635 regulator except that it is on an elevated platform 1%" high for use on insulated ducts. You may order by sets or individual parts. A set consists of: one elevated dial regulator; one #637 square end bearing which has 2%" shaft to reach the dial; and one standard #635 spring end bearing. Weight per 100 sets, 64 lbs. 638 VENTLOK %" ELEVATED DIAL REGULATOR FOR 1'/2" INSULATION fanaa aL Same regulator as #637 above, except platform AesuATOR is 1%" high. Order by sets or individual parts. Weight per 100 sets, 68 lbs. 639 VENTLOK 7%" ELEVATED DIAL REGULATOR FOR 2" INSULATION Same regulator as #637 above, except the platform is 2%" high and the square end bearing is 2%" long to reach the dial. Order by sets or individual parts. Weight per 100 sets, 72 lbs. 636 LONG PIN SPRING END BEARING This spring end bearing is designed for use on dampers in ducts insulated on the inside. The pin is one inch longer than our standard #635 spring end bearing, so that when released the pin extends 1% inches beyond the pin holder. Weight per 100, 14 Ibs. VENTFABRICS, INC. CHICAGO. WINO'S —1-800621-1207 Two more Cc innovations DAMPER CLIPS — Just “clip on” and spot weld! SURE-LOC BUSHINGS - They “snap in” and stay tight! SPRAL SEAM ALT Tos 10 in. wg ALS LAP AND RIVET OR TACK WELD ON 6" (182 mm) SRVAL, SPOTWELD ON oe (61 my) INTERVAL. To+4in.wg Acceptable to 10 in. wg if spot welded on 1 in. intervals or tack welded on 3 in. intervals To+ 10 in. wg (OR LAP SEMMWELDED) we ON To 10in. wg GROQVED SEAM To-3 in. wg Alar toe wea a +20. we we eS To-1in. wg [SNAPLOGK SEAMS FIGURE 3-2 ROUND DUCT LONGITUDINAL SEAMS TE HVAC Duet Construction Standards Metal and Flexible « Third Edition Diameter, in. | Longitudinal Seam Spiral Seam 4 28 28 6 28 28 8 28 28 10 28 28 12 28 28 4 28 28 16 26 26 i8 26 26 20 24 26 2 4 26 m4 4 26 30 2 24 36 2 24 2 2 PI 8 20 2 4 20 2 60. 20 2 66 w 2 2 18 20 78 18 20 4 18 20 90 18 20 96 18 20. Table 3-5 Round Duct Gage Unreinforced Positive Pressure To 10 in. wg HVAC Duct Construction Standards Metal and Flexible Third Edition SEH

You might also like