You are on page 1of 1

Pump Head Calculation

Project:

DIC R & D

System:
Design By:

Condenser water system


Vasudevan

Pipe Dia
(mm)
supply pipe
3
2
1.5
0.75
Return pipe
6"
6"
4"
3"

Pipe
length (ft) flow rate

Check By:
Total
Bends/ Valves
Equiv
Equivalen
No. of
Length
Loss in Ft. t length
Fittings
(ft)
(ft)

Job No:
Friction
Loss/100ft
(ft/s)

Total Static
Head (ft)

60
50
50
10

96
36
18
6

8
3
4
2

16
16
10
7.5

128
48
40
15

188
98
90
25

2
2
2
4

3.76
1.96
1.8
1

150
150
70
40

590
340
125
85

8
3
4
2

16
16
10
7.5

128
48
40
15

278
198
110
55

5
2
4
4

13.9
3.96
4.4
2.2

3
1
2
1
2
1
2
1

7
110
7
60
3.2
42
3.2
84

21
110
14
60
6.4
42
6.4
84

21
110
14
60
6.4
42
6.4
84

5
5
5
5
4
4
4
4

1.05
5.5
0.7
3
0.256
1.68
0.256
3.36

Sub Total
10%

48.782
4.8782
53.6602

Valve
6" gate valve
6" strainer
6" flexible
6" check valve
3" gate valve
3" strainer
3" flexible
3" bal. valve

Allowance
Chiller Pressure Loss (ft)
Air Handling Pressure Loss (ft)
Cooling Tower Static Head (ft)
Production Machine Pressure Loss (ft)
Plate Heat Exchanger Pressure Loss (ft)
Total Head

14
15

82.6602