ONE BINONDO

MIXED-USE DEVELOPMENT
MORIONES ST. COR. JUAN LUNA ST. BINONDO, MANILA
PROPOSED
AUTOMATIC FIRE SPRINKLER SYSTEM LAYOUT
AND
SPRINKLER SUPPLY LOOP W/ DISTRIBUTION
OF FHC & PFE SYSTEM LAYOUT

F. P. GENERAL NOTES
1.

ALL WORKS HEREIN INCLUDED SHALL BE EXECUTED ACCORDING


TO THE PROVISION OF THE NATIONAL FIRE PROTECTION
ASSOCIATION (USA) AND LOSS PREVENTION COUNCIL (UK).

2.

THE WORKS SHALL BE EXECUTED IN CLOSE COORDINATION


WITH ALL TRADES.

3.

THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR THE


EXACT LOCATION AND DIMENSIONS OF ALL REQUIRED WALL
AND FLOOR OPENINGS.

4.

5.

FIRE PROTECTION DRAWING INDEX


SHEET NO.
FP-01

THE EXACT LOCATION OF ALL SPRINKLER HEADS SHALL BE


COORDINATED WITH THE ARCHITECTURAL CEILING LAYOUT
AND SHALL BE SUBJECTED TO BOTH THE ARCHITECTS AND
FIRE PROTECTION ENGINEERS APPROVAL.

FP-02

FP-03

LOCATION OF DRAIN PIPES AND OF THE BACK-UP SUPPLY LINES

SHEET CONTENTS

F. P. LEGENDS & SYMBOLS

GENERAL NOTES, LEGENDS & SYMBOLS, DRAWING INDEX,


SCHEDULE OF PIPE SLEEVE, PIPE SIZE CONVERSION TABLE,
SCHEDULE OF EQUIPMENTS, SITE DEVELOPMENT PLAN
- AUTOMATIC FIRE SPRINKLER SYSTEM LAYOUT
- SPRINKLER SUPPLY LOOP & DISTRIBUTION OF
FHC & PFE SYSTEM LAYOUT

GROUND FLOOR PLAN

- AUTOMATIC FIRE SPRINKLER SYSTEM LAYOUT


- SPRINKLER SUPPLY LOOP & DISTRIBUTION OF
FHC & PFE SYSTEM LAYOUT

SECOND FLOOR PLAN

SHALL BE COORDINATED WITH THE PLUMBING CONTRACTOR.


6.

LOCATION AND MOUNTING OF FIRE HOSE CABINETS SHALL BE


COORDINATED WITH ARCHITECTURAL FINISHES AND BE SUBJECTED
TO BOTH THE ARCHITECTS AND FIRE PROTECTION ENGINEERS APPROVAL.

7.
8.

9.

SIZE OF RISER NIPPLES SHALL CONFORM TO PIPE SCHEDULES


AS DELINEATED IN NFPA 13.

FP-04

THIRD FLOOR PLAN

- AUTOMATIC FIRE SPRINKLER SYSTEM LAYOUT


- SPRINKLER SUPPLY LOOP & DISTRIBUTION OF
FHC & PFE SYSTEM LAYOUT

FP-05

ROOF DECK PLAN

- AUTOMATIC FIRE SPRINKLER SYSTEM LAYOUT


- SPRINKLER SUPPLY LOOP & DISTRIBUTION OF
FHC & PFE SYSTEM LAYOUT

FP-06

PIPE SUPPORTS, HANGERS AND BRACING SHALL BE OF THE


APPROVED TYPE AND SHALL BE INDEPENDENT FROM CEILING
AND DUCT SUPPORTS.

MISCELLANEOUS DETAILS

SCHEDULE OF PIPE SLEEVE

WET STAND PIPE (WSP)

FLEXIBLE COUPLING

DRY STAND PIPE (DSP)

FEEDMAIN (FM)

ALARM CHECK VALVE (ACV)

CROSSMAIN (CM)

BLIND FLANGE

BRANCHLINE (BL)

PIPE HANGER

FIRE DEP'T. CONN. (FDC)

FLOOR CONTROL VALVE (FCV)

BUTTERFLY VALVE (BV)

TWO WAY SWAY BRACE

GATE VALVE (GV)

FOUR WAY SWAY BRACE

ELBOW TURNED DOWN

FIRE HOSE CABINET (FHC-R) RECESSED

ELBOW TURNED UP

FIRE HOSE CABINET (FHC-S) SURFACED

CHECK VALVE

UPRIGHT SPRINKLER HEAD

FLUSHING CONNECTION

PENDENT SPRINKLER HEAD

UNION PATENTE

COMBINED SSP/SSU

NOMINAL SIZE

LOAD SIDE POWER SUPPLY CONDUIT, ROUGH-INS, AND WIRING TO THE


FIRE PROTECTION EQUIPMENT SHALL BE BY THE FIRE SPRINKLER
CONTRACTOR.

10. CONTROL WIRING AND TERMINATION FROM FLOW SWITCHES TO


SPRINKLER SUPERVISORY ALARM CONTROL PANEL SHALL BE BY THE
FIRE SPRINKLER CONTRACTOR.

PIPE SIZE

25

32

40

50

65

80

100

150

200

SLEEVE SIZE

50

50

65

100

125

125

200

250

300

PIPE SLEEVE

PUMP PRESSURE SETTING

PIPE SIZE CONVERSION TABLE


NOMINAL SIZE

11. SUPPLY, INSTALLATION AND COMMISSIONING OF SUPERVISORY


ALARM CONTROL PANEL SHALL BE BY FIRE SPRINKLER CONTRACTOR.

32

40

50

65

DESIGNATION

MM. (DIAMETER)

25

IN. (DIAMETER)

1" 11/4" 11/2" 2" 21/2" 3"

12. ACCESS FOR CONTROL VALVES SHOULD BE LOCATED AT COMMON AREAS.

4"

6"

CUT OFF

95 PSI

MANUAL STOP

110 PSI

125 PSI

AAV

SCHEDULE OF EQUIPMENT
PUMP
CHARACTERISTICS

14. ALL PIPES PASSING THRU WALLS AND FLOORS, PROVIDE PIPE SLEEVES.
PIPE SLEEVE SHOULD HAVE PLASTIC WATERPROOF HEAT RESISTANT
CAULKING COMPOUND WITH MINERAL WOOL PACKING.

DESIGNATION

15. PROVIDE PIPE HANGER @ EVERY 2 METERS, SWAY BRACE AND


CLEVIS SUPPORT @ EVERY 12 METERS.

QUANTITY

FIRE PUMP

JOCKEY PUMP

SIDEWALL SPRINKLER HEAD (ORDINARY)

ROOF MANIFOLD (RM)

SIDEWALL SPRINKLER HEAD (EXTENDED)

INSPECTOR TEST
CONNECTION (ITC)

8"

JP - 1

13. SHOP DRAWINGS SHALL BE PREPARED BY THE CONTRACTOR FOR


FIRE PUMP LAYOUT, PIPE HANGER AND OTHER INSTALLATION AS
REQUIRED AND INDICATED IN THE SPECIFICATION.

CUT IN

FLANGE CONNECTION

80 100 150 200

FP - 1

\\192.168.5.32\residential projects\FILINVEST BINONDO SHOWROOM\DRAWING IN\032715 One Binondo Showroom frm flfa\FIRE PRO\FP-01_FRONT PAGE.dwg, 3/31/2015 6:09:40 PM, DWG To PDF.pc3

RISER NIPPLE (RN)

TYPE
VERTICAL
TURBINE
VERTICAL
TURBINE

DRIVE

MOTOR DATA

PFE CO2

CAPACITY
(GPM)

HEAD
(PSI)

SPEED
(RPM)

RATING
(HP) VOLTAGE PHASE CYCLE

ELECTRIC

500

120

1770

60

380

60 Hz

ELECTRIC

40

125

3550

7.5

380

60 Hz

10 LBS.
HCFC 123 PFE
CEILING TYPE

AUTOMATIC AIRRELEASE VALVE


15 LBS. CARBON DIOXIDE
PORTABLE FIRE
EXTINGUISHER

WFE AFFF

50 LBS. AQUEOUS FILM FORMING FOAM (AFFF)


WHEELED TYPE FIRE EXTINGUISHER

WFE ABC

50 LBS. ABC MULTI- PURPOSE DRY-CHEMICAL


WHEELED TYPE FIRE EXTINGUISHER

PFE ABC

20 LBS.
HCFC PFE

20 LBS. AUTOMATIC WALL TYPE


HALOGENIC AGENT TYPE
PORTABLE FIRE EXTINGUISHER
HYDROCHLOROFLUOROCARBON(HCFC)

15 LBS.
HCFC PFE

15 LBS. AUTOMATIC WALL TYPE


HALOGENIC AGENT TYPE
PORTABLE FIRE EXTINGUISHER
HYDROCHLOROFLUOROCARBON(HCFC)

10 LBS. HCFC 123 PFE


CEILING TYPE

NOTE:
PUMP SUPPLIER/ FIRE PROTECTION CONTRACTOR SHOULD
FOLLOW THE VOLTAGE REQUIREMENTS OF THE
ELECTRICAL DESIGNER/ CONSULTANT.

16. PROVIDE FLANGE CONNECTION EVERY 12 METERS, AND ONE SIDE


OF EVERY FITTING CONNECTION.

15 LBS. ABC DRY-CHEMICAL


PORTABLE FIRE EXTINGUISHER

17. LATERAL BRACES SHOULD BE SPACED NO MORE THAN


24.4 METERS (80FT.) APART. (FEEDAMIN & CROSSMAIN PIPE)
18. LATERAL BRACES SHOULD PROVIDED WITHIN 0.60 METERS (2FT.)
FROM PIPE CHANGES IN DIRECTION FOR PIPE RUNS LONGER THAN
1.80 METERS (6 FT.) IT SHOULD BE SPACED MAXIMUM 12.20 METERS
(40FT.) CENTER OF THE PIPE. LATERAL BRACES SHOULD BE PROVIDED
WITHIN 1.80 METERS (6 FT.) OF THE PIPE END. (FEEDMAIN & CROSSMAIN)

SEAL

STRUCTURAL

DESIGNER

REPUBLIC ACT 9266

PLUMBING & FIRE PRO

ELECTRICAL

MECHANICAL

PROJECT TITLE & LOCATION

FERDINAND L. FIGUEROA
P.M.E
3554
2282035

100-355-030
01-06-2015

CAVO F. SANCHEZ STREET, MANDALUYONG CITY,


PHILIPPINES
Tel. Nos. (632) 531-7721
Fax No. (632) 719-4811
E-mail Address: flfigueroa111@yahoo.com

MECHANICAL ENGINEER

REG.NO.

REG.NO.

2691

REG.NO.

REG.NO.

PTR.NO.

PTR.NO.

PTR.NO.

PTR.NO.

TIN.

TIN.

DATE:

DATE:

TIN.

TIN.

2282033
253-866-002

DATE:

DATE:

01-06-2015

LEGENDS & SYMBOLS, DRAWING INDEX, GEN. NOTES,


SCHEDULE OF PIPE SLEEVE, PIPE SIZE CONVERSION
TABLE, SCHEDULE OF EQUIPMENTS

SHEET
CONTENTS

F.L. FIGUEROA & ASSOCIATES Inc.


670

SHEET NO.

LAND OWNER & DEVELOPER

1704
0181375
123-451-284
01-07-15

ONE BINONDO
MIXED-USE DEVELOPMENT
LOCATION: MORIONES ST. COR. JUAN LUNA ST. BINONDO, MANILA

DATE

MARCH 27, 2015

SCALE

CADD

RVLJJDIDDRAG

REVISION

CHECKED

FLFA

PROJECT NO.

APPROVED

FLFA

1:100 MTS.

FP