You are on page 1of 9

December 2013

ZOZIK Ref. number:

Rev.: A

O/C and E/F Protection Service Setting


TANJARO SS 132/33/11 kV

Over-current and Earth-Fault protection Service Setting


-

132 kV Switchgear

33 kV Switchgear

11 kV Switchgear

Voltage Functions Service Setting


-

Busbar VT Metering 33 kV

Busbar VT Metering 11 kV

VT Transformer Incoming Feeder 11 kV

73. TANJARO SS Service Setting Plan

Page 1

December 2013
ZOZIK Ref. number:

Rev.: A

O/C and E/F Protection Service Setting


TANJARO SS 132/33/11 kV

Date: December.2013
Subject: Sulaimanya Selectivity study dE:ZK^^132/33/11 kV S/S
The purpose of this document is to show the settings of the O/C and E/F relays and the relevant
selectivity. Refer to the attached single line diagrams 132 kV, 33 kV and 11 kV to locate the relays.
1. O/C relays
Three levels of selectivity are to be considered:
Selectivity 132 kV between bus coupler and O/H line. As the O/C relay of O/H line is set
directional, it isnt involved in the selectivity regarding 33 kV and 11 kV.
Selectivity 132 kV/33 kV.
Selectivity 132 kV/11 kV.
For O/H lines, to ensure an enough margin, the minimum time will be 400 ms higher than
the distance protections zone 2, i.e. 400 + 400 = 800 ms. For the transformer 132/33/11
kV, an instantaneous high set threshold can be set in order to get a fast tripping in case of
internal fault 132 kV side. This threshold I> can be set to 10 times, the Ie> to 5 times, i.e.
864 A prim. (I> 10 x 5 and Ie> 5x5) with a tripping time of 70/35 ms respectively.
All tripping curves will be set in standard inverse type (SI) to ensure fast tripping time in
case of heavy faults. The O/C relays of O/H lines and transformers are set directional
respectively toward O/H lines and transformers.
2. E/F relays
The 3 voltage levels have their independent earthing systems :
132 kV solidly earthed,
33 kV : Low reactance earthed limited to 1000 A 10 s and
11 kV : Low resistance earthed limited to 300 A 30 sec.
The O/C relays of O/H lines and transformers are set directional respectively toward O/H
lines and transformers.
For the I> stages, standard inverse curves (SI) are recommended, while definite time will be
used for I>> stages at 132, 33 kV and 11 kV.
Conservative values of service setting for O/G feeders experienced as suitable for Kurdistan
network are applied taking into consideration equipment safety, system stability and reliability of
consumers power supply.
Ratings of electrical equipment, short time current withstand level, duty cycles and other relevant
factors are considered as well.
Attachments:
- PH to PH and PH to Neutral settings summary tables :
Single line diagram 132 kV Switchgear
Single line diagram 33 kV Switchgear
Single line diagram 11 kV Switchgear
-

73.TANJARO SS Service Setting Plan

Page 2

Client : KRG-MOE

Contract: KRG-MOE-SS 6a/2011 -Sulaimanya S/S Stage 6

7$1-$5266 132/33/11 kV 2x63/50/40MVA

Switchgear : 132 kV, 33 kV, 11 kV

SERVICE SETTING PLAN O/C and E/F protection


Basic Service Setting Data

BAY - SWITCHGEAR

Switchgear 132 kV
CT RATIO: 1200/5

Incoming

Protection: 7SJ64-1

Siemens

Ip= 5A
TMS= 0.5 s.
I>= 20 A
T>= 0.9 sec.

Characteristic: NINV directional


Secondary Protection

DIR.
CT RATIO: 1200/5

Outgoing

Protection: 7SJ64-1

Siemens

Secondary Protection
DIR.
Transformer Feeder 132 kV
CT RATIO: 300/5

Siemens

Characteristic: NINV directional


Secondary Protection
Bus Coupler 132 kV
CT RATIO: 1600/5
Protection: 7SJ64-1

Siemens

Characteristic: NINV directional

Iep= 2 A

RCA= -600

Dir

Iep= 2 A

TMS= 0.5 s.
I>= 20 A

TMS= 0.3 s.
Ie>= 15 A

T>= 0.9 sec.


RCA= +300
O/C

T>= 0.6 sec.


RCA= -600
E/F

Ip= 5 A

Dir

Iep= 5 A

TMS= 0.5s.
I>= 50 A

TMS= 0.15 s.
Ie>= 25 A

T>= 0.7 sec.


RCA= +300
O/C

T>= 0.35 sec.


RCA= -600
E/F

Ip= 3.25 A
TMS= 0.4s.
I>= 12 A
T>= 0.8 sec

Dir.

TMS= 0.3 s.
I>= 15 A
T>= 0.6 sec.

RCA= +300
Ip= 5A

Characteristic: NINV directional

Protection: 7SJ64-1

Dir

Dir.

Dir

Iep= 1.5 A
TMS= 0.2 s.
Ie>= 10 A
T>= 0.5 sec.

Switchgear 33kV
Transformer Feeder 33 kV
CT RATIO: 1200/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


Bus Coupler 33 kV
CT RATIO: 1250/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


Outgoing Feeder 33 kV
CT RATIO: 600/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.

73. dE:ZK^^ Stage 6 Service setting .xlsx

O/C

E/F

Ip= 4 A

Iep= 0.8 A

TMS= 0.25s.
I>= 15 A
T>= 0.55 sec.
O/C

TMS= 0.25 s.
Ie>= Off
T>= Off
E/F

Ip= 3.2 A

Iep= 0.65 A

TMS= 0.25 s.
I>= 20 A
T>= 0.55 sec.
O/C
Ip= 5 A
TMS= 0.2 s.
I>= 20 A
T>= 0.5 sec.

TMS= 0.2 s.
Ie>= Off
T>= Off
E/F
Iep= 0.75 A
TMS= 0.25 s.
Ie>= 2.5 A
T>= 0.7sec.

Client : KRG-MOE

Contract: KRG-MOE-SS 6a/2011 -Sulaimanya S/S Stage 6

7$1-$5266 132/33/11 kV 2x63/50/40MVA

Switchgear : 132 kV, 33 kV, 11 kV

SERVICE SETTING PLAN O/C and E/F protection


Basic Service Setting Data

BAY - SWITCHGEAR
Capacitor Feeder 33 kV
CT RATIO: 300/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV Nondir

Unballance protection 7SJ

Siemens

Alarm: I>=0.5A; DEF time, 5 sec.


NP 33 Stand- by E/F

O/C
Ip= 3.5 A
TMS= 0.15 s.
I>= 20 A
T>= 0.3 sec.
N. Point CT 10/5 A
Trip: I>>=1.1A; DEF time, 0.1 sec.
O/C
Ip= N/A

CT RATIO: 300/5
7SJ62-1
Stand-By in Tr Incoming Feeder 33 kV
Characteristic: Def time.

TMS= N/A
I>= N/A
T>= N/A

E/F
Iep= 1 A
TMS= 0.15 s.
Ie>= 2.5 A
T>= 0.25 sec.
Cap. Bank Q=10 MVAr
E/F
Ie>= 4 A
T>= 8 s.
Ie>>= 10 A
T>>= 1.3 sec.

Switchgear 11 kV
Transformer incoming 11 kV
CT RATIO: 2500/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


Bus Coupler 11 kV
CT RATIO: 2500/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


Outgoing Feeder 11 kV
CT RATIO: 300/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


Auxiliary Grounding Transformer 11 kV
CT RATIO: 40/5
Protection: 7SJ62-1

Siemens

Characteristic: NINV nondir.


NP 11 kV Stand- by E/F Ptn
CT RATIO: 150/5
Protection: 7SJ62-1

Siemens

Characteristic: DEF.Time

73.dE:ZK^^ Stage 6 Service setting .xlsx

O/C

E/F

Ip= 4.2 A

Iep= 0.25 A

TMS= 0.45 s.
I>= 12.5 A
T>= 0.6 sec.
O/C
Ip= 4 A
TMS= 0.20 s.
I>= 10 A
T>= 0.45 sec.
O/C
Ip= 5 A

TMS= 0.2 s.
Ie>= Off
T>= Off
E/F
Iep= 0.25 A
TMS= 0.15s.
Ie>= Off
T>= Off
E/F
Iep= 1 A

TMS= 0.2 s.
I>= 25 A
T>= 0.35 sec.
O/C

TMS= 0.1 s.
Ie>= 2.5 A
T>= 0.3 sec.
E/F

Ip= 5.5 A

Iep= 15.5 A

TMS= 0.25 s.
I>= 15 A
T>= 0.3 sec.
O/C

TMS= 0.25 s.
Ie>= Off
T>= Off
E/F

Ip= Off
tp= Off
I>= Off
T>= Off

Ie>= 2.5 A
T>= 12 sec.
Ie>>= 8 A
T>>= 3.2 sec.

Client : KRG-MOE

Contract: KRG-MOE-SS 6a/2011 -Sulaimanya S/S Stage 6

7$1-$5266 132/33/11 kV 2x63/50/40MVA

Switchgear : 132 kV, 33 kV, 11 kV

SERVICE SETTING PLAN O/C and E/F protection


BAY - SWITCHGEAR

Basic Service Setting Data

BUS VT 33 kV - 27, 59,64, 81 LOAD SHEDDING AND ACO


Busbar VT Metering 33 kV
VT RATIO: 33/V3//0.11/V3/0.11/3
Protection: 7SJ62-1

Siemens

Function

Setting

Undervoltage U</Un = 29.4 kV; 2 sec D.O ratio 1.05


Undervoltage U<</Un = 29.1 kV; 2 sec D.O. ratio 1.05
Overvoltage U>/Un = 35.1 kV; 5 sec ; D.O. ratio 0.95
Overvoltage U>/Un = 36.0 kV; 1 sec ; D.O. ratio 0.95
Min Required Voltage 27.9 kV; D.O diff= 0 kV
Load shedding Stage 1 f1< = 49.5 Hz; 10 sec
Load shedding Stage 2 f2< = 49.0 Hz; 5.0 sec
Load shedding Stage 3 f3< = 48.5 Hz; 3.0 sec
Load shedding Stage 4 f4< = 48.0 Hz; 0.0 sec
Sensitive E/F 3U0> 16.5 kV; 9.0 sec

BUS VT 11 kV - 27, 59, 64, 81 LOAD SHEDDING AND ACO


Busbar VT Metering 11 kV
VT RATIO: 11/V3//0.11/V3/0.11/3
Protection: 7SJ62-1

Siemens

Function
Setting
Undervoltage U</Un = 10.0 kV; 2 sec D.O ratio 1.05
Undervoltage U<</Un = 9.0 kV; 2 sec D.O. ratio 1.05
Overvoltage U>/Un = 12.5 kV; 5 sec ; D.O. ratio 0.95
Overvoltage U>/Un = 13.0kV; 1 sec ; D.O. ratio 0.95
Min Required Voltage 8.5 kV; D.O diff= 0 kV
Load shedding Stage 1 f1< = 49.5 Hz; 10 sec
Load shedding Stage 2 f2< = 49.0 Hz; 5.0 sec
Load shedding Stage 3 f3< = 48.5 Hz; 3.0 sec
Load shedding Stage 4 f4< = 48.0 Hz; 0.0 sec
Sensitive E/F 3U0> 3.5 kV; 13.0 sec

Transformer incoming Feeder VT 11 kV


VT RATIO: 11/V3//0.11/V3/0.11/3
Protection: 7SJ62-1

Siemens

Function
Setting
Undervoltage U</Un = 10.0 kV; 2 sec D.O ratio 1.05
Undervoltage U<</Un = 9.0 kV; 2 sec D.O. ratio 1.05
Overvoltage U>/Un = 12.5 kV; 5 sec ; D.O. ratio 0.95
Overvoltage U>/Un = 13.0kV; 1 sec ; D.O. ratio 0.95
Min Required Voltage 8.5 kV; D.O diff= 0 kV
Load shedding Stage 1 f1< = 49.5 Hz; 10 sec
Load shedding Stage 2 f2< = 49.0 Hz; 5.0 sec
Load shedding Stage 3 f3< = 48.5 Hz; 3.0 sec
Load shedding Stage 4 f4< = 48.0 Hz; 0.0 sec
Sensitive E/F 3U0> 3.5 kV; 13.0 sec

73. dE:ZK^^ Stage 6 Service setting .xlsx

LEGEND
M

Motor operated
disconnector

Hand operated
disconnector

OHL No.1

OHL No.2

OHL No.3

OHL No.4

-T5

-T5

-T5

-T5

Circuit Breaker
132 0.11 0.11
3X /
/
kV
3 3 3

132 0.11 0.11


3X /
/
kV
3 3 3

Current Transformer

-Q9

-Q9

1200-600/5/5/5/5 A

Circuit Breaker
Busbar Disconnecting Switch
Disconn. Switch with Earthing
Busbar Disconnecting Switch
Single Pole N. P. Disconnecting
Main Power Transformer
120 kV Lightning Arrester
84 kV Lightning Arrester
Current Transformer
Current Transformer
Current Transformer
Current Transformer
Capacitive Voltage Transformer
Inductive Voltage Transformer
132 kV N.P. Current Transformer
33 kV N.P. Current Transformer
33 kV N.P. Current Transformer
33 kV Neutral Grounding Reactor

Ratio

Core

CT Data

Cl.0.5 FS5, 60-30 VA; Rct=1.0-0.5

2
OHL
Feeder

-T1 1200-600/5/5/5/5 A 3

5P20, 60-30 VA; Rct=1.0-0.5

BB1

=E00

-Q25
H

132 0.11
/
kV
3
3

VOLTAGE TRANSFORMERS
Core

-Q0

-Q0

1250 A

1250 A

1250 A

1250 A

-Q2

-Q1

132 0.11 0.11


/ kV
-T5 3X /
3 3 3
2

5P20, 60-30 VA; Rct=1.0-0.5

=E06
=E05

-Q2

Main
Transformer
Feeder

-T2 300-150/5/5/5/5 A

Cl.0.5 FS5, 60-30 VA; Rct=1.0-0.5

5P20, 60-30 VA; Rct=1.0-0.5

5P20, 60-30 VA; Rct=1.0-0.5

Bus
Coupler

-T61

21/21N/68/27W/50HS/79/25/FL

50/50N/51/51N/67/67N/74TC/
/86/BCU

Protection 7SJ64

5P20, 60-30 VA; Rct=1.0-0.5

Protection 7SS52 Zone 1 & 2; Check 87BB/50BF - Low Impedance

-Q61 P2

-T62

P1

5P20, 30-15 VA; Rct=1.0-0.5

Protection ( IE in 7UT613 in TR. F. )

-T62
Neutral Point
33 kV
-T63

1200-600/5 A

5P20, 30-15 VA; Rct=1.0-0.5

Protection

5P20, 60-15 VA; Rct=1.0-0.5

Protection

5P20, 60-15 VA; Rct=1.0-0.5

Protection (Spare Core for 33 kV LI-REF)

300-150/5/5 A

Date

Signature Function
PREPARED

REV :

DESCRIPTION :

Name

( Low Impedance REF


in 7UT613 in 132 kV RP )
( Stand-By E/F in 7SJ6x in
Transformer Incomer F. )

Date

Azam Sabrihafizovic 12.11.2012

CHECKED

Mujo Terko

12.11.2012

APPROVED

Salar Abdulah

12.11.2012

Signature

-Q0
-Q0
-Q0
-Q1;-Q2
-Q1;-Q2
-Q1;-Q2
-Q8;-Q9
-Q15;-Q25
-Q61
-TR 1, 2
-F1
-F61
-T1
-T2
-T3

1 Cl.0.5, 100 VA Measuring V and F


132 0.11 0.11
3X / / kV
3 3 3
-T25
2 3P, 100 VA Protection
-T15

300-150/5 A

=E12
=E11

-Q2

-Q1

-Q2

-Q1

1250 A

-Q0

-Q0

-P1

-P1

87N - 132 kV IE
87N - 33 kV LI - REF
51N - 33 kV Stand-By E/F

-T5
-T15; -T25
-T61
-T62
-T63
-L63

1000A / 10s

-T61

(ONAN) / ONAF
(44.1/35/28 MVA)
63/50/40 MVA
YNyn0d11

-T62

P1

33 kV XLPE Cu
2x(3x1x400mmsq)

PRIMARY EQUIPMENT LIST


Feeder
Manufacturer
Type
Line
SIEMENS
3AP1 FG 145 kV
Buscoupler
SIEMENS
3AP1 FG 145 kV
Transformer
SIEMENS
3AP1 FG 145 kV
3DN1CB145
Line
Buscoupler
3DN1CB145
SIEMENS /
Transformer
3DN1CB145
COELME
Line
3DN1CB145EB
Measuring Bay
3DN1CB145
Transformer
3DN1EB123
Transformer
SIEMENS
Transformer
SIEMENS
3EP4 120-2PF31-1DA1
Transformer
SIEMENS
3EP4 084-2PF31-1DA1
Line
TRENCH
IOSK 145
Transformer
TRENCH
IOSK 146
Buscoupler
TRENCH
IOSK 147
TRENCH
TRENCH

TRENCH

TCVT 145
VEOT 145
Bushing Type
Bushing Type
Outdoor Type
NGR 170/1000/17

ZOZIK COMPANY

KRG - MOE

POWER SECTOR
ENGINEERING DEPARTMENT

KURDISTAN REGIONAL GOVERNMENT


MINISTRY OF ELECTRICITY

P2

P1

-Q8

132 0.11 0.11


/
kV
3X /
3 3 3

132 0.11 0.11


/
kV
3X /
3 3 3

1200-600/5 A

17

-L63 33 kV

-T63

-Q8

1328x1.25%/332x2.5%/11.5 kV

-Q61 P2

11 kV XLPE Cu
4x(3x1x400mmsq)

-T1
-P2

-Q9

TR 2

P2

-F61

300-150/5/5 A

Line
Measuring Bay
Transformer
Transformer
Transformer
Transformer

-Q9

300-150/5 A

1200-600/5 A

-L63 17
33 kV

1200-600/5/5/5/5 A

-P2

P1

-T1

1200-600/5/5/5/5 A

-P2

-F1

1328x1.25%/332x2.5%/11.5 kV

-F61

50/50N/51/51N/67/67N/74TCS/
/86/49/BCU
87/87N ( 132 kV LE & 33 kV LI - REF)

5P20, 60-30 VA; Rct=1.0-0.5

N. P. 132 kV -T61

=E10

1250 A

-T2

300-150/5/5/5/5 A

(ONAN) / ONAF
(44.1/35/28 MVA)
63/50/40 MVA
YNyn0d11

-T63

Measuring
Bay

Future T. Line

=E09

-P1

TR 1

P2

300-150/5 A

P2

Measuring A, W, Var, V and F; 7SG11 25

-T3 1600-800/5/5/5 A

-Q0

-P2

P1

Protection 7SA61

( Voltages provided from BB VTs )

1250 A

-Q0

ANSI Code

Protection 7SS52 Zone 1 & 2; Check 87BB/50BF - Low Impedance

Cl.0.5 FS5, 60-30 VA; Rct=1.0-0.5

Future T. Line

Future TR. No 3
Feeder

-Q1

1250 A

-T2

-F1

Designation

-Q1

-Q0

Measuring A, W, Var, V and F

5P20, 60-30 VA; Rct=1.0-0.5

=E08
=E07

-P1

1600 A

Protection 7SJ64

Protection 7UT6135 ( -4EB22-1BC1 )

-Q2

-Q2

1600-800/5/5/5 A

50/50N/51/51N/67/67N/74TC/
/86//27/59/81/BCU

Protection 7SJ64

-Q1

-Q1

Protection 7SS52 Zone 1 & 2; Check 87BB/50BF - Low Impedance

( Voltages provided from BB VTs )

-Q1

-P1

=E03

P1

-Q2

=E04

Cl.0.5, 100 VA Measuring A, W, Var, V and F

5P40, 60-30 VA; Rct=1.0-0.5

=E01

-Q2

-P2

Type

3P, 100 VA

-Q1

=E02

-Q2

METERS & RELAYS

VT Data

-T1

-P1

Duty
Ratio

1200-600/5/5/5/5 A

-T1

-Q0

300-150/5/5/5/5 A

Desig
nation

-P2

-P1

-P1

3X

1200-600/5/5/5/5 A

-T1

-T15
-T3

-P2

-Q0

M
M

-Q9

-P1

-Q15

-T25

CURRENT TRANSFORMERS
Desig
nation

BB2

AIS 1600 A,
40 kA /1 sec

1200-600/5/5/5/5 A

-Q8

Feeder
Type

-Q9
-P2

-T1

PRIMARY EQUIPMENT DESCRIPTION

-Q8

-P2

Surge Arrester with


operation counter

-Q8

Capacitive VT with
two secondaries

-Q0
-Q1;-Q2
-Q8;-Q9
-Q15;-Q25
-Q61
-TR 1, 2
-F1
-F61
-T1
-T2
-T3
-T4
-T5
-T15; -T25
-T61
-T62
-T63
-L63

-Q8
Inductive VT with
two secondaries

132 0.11 0.11


3X /
/
kV
3 3 3

-P2

Designation

132 0.11 0.11


3X /
/
kV
3 3 3

-P1

1000A / 10s

11 kV XLPE Cu
4x(3x1x400mmsq)

300-150/5/5 A

33 kV XLPE Cu
2x(3x1x400mmsq)

-T5

-T5

OHL No.5

OHL No.6

SWITCHGEAR DATA
Frequency
Nominal Voltage of a System
Maximum Operating Voltage of Equipment
Rated Lightning Impulse Withstand Voltage (BIL)
Rated Short Time Power Frequency Withstand
Rated Switching Impulse Withstand Voltage ( SIL )
Initial Symmetrical Short Circuit Current
Thermal Equivalent Short-Time Current
Duration of Short-Circuit Current
Rated Peak Withstand Current
Busbar Rated Current
Feeder Rated Current
Bus Coupler Rated Current
Ambient Temperature ( min. / average / max. )
KRG-MOE-SS06a/2011 & SS06b/20011 Sulaimanyah SS Stage 6

TYPE 1 Rev 2 S/S 132/33/11.5 kV, 2 x 63/50/40 MVA


SINGLE LINE DIAGRAM 132 kV Switchgear
Applicable for S/S HS & TN

3 AC
f
UN
Um
UrB
UrPF
UrS
I"K3
Ith
Tk
Ip3
IN
IN
IN

50 Hz
132 kV
145 kV
650 kV
275 kV
___ kV
40 kA
40 kA
1s
100 kA
1600 A
1250 A
1600 A
(+55 /

No. SS6-Type 1 Rev 2 -HS, TN 132 kV SLD - Z Rev03

Scale

Sheet

NTS

Sheets

VT Feeder/
Metering 1

Outgoing
Feeder No 1

+H01
=HZ02

Outgoing
Feeder No 2

Outgoing
Feeder No 3

TR 1
Incoming

+H03
=HZ01

+H04
=HZ01

+H05
=HZ03

+H02
=HZ01

Outgoing
Feeder No 4

Outgoing
Capacitor
Feeder No 5 Feeder No 1

+H06
=HZ01

+H08
=HZ06

+H07
=HZ01

Bus Riser/ Outgoing


Metering 2 Feeder No 6
+H11
+H10
=HZ01
=HZ05

Bus
Sectionalizer

+H09
=HZ04

TR 2
Incoming

Outgoing
Feeder No 8

Outgoing
Feeder No 7

+H13
=HZ01

+H12
=HZ01

Outgoing
Feeder No 10

Outgoing
Feeder No 9
+H15
=HZ01

+H14
=HZ03

Capacitor
Feeder No 2
+H17
=HZ06

+H16
=HZ01

Q8

Q0
M

1250 A

Q0
M

Q0

1250 A

1250 A

Q0

Q0

Q0

1250 A

Q0

1250 A

Q0

1250 A

Q0

1250 A

Q0

1250 A

Q0

1250 A

1250 A

1250 A

Q0

Q0

Q0

1250 A

Q0

1250 A

1250 A

1250 A

2A

Q8

3X

Q8

Q8

Q8

Q8

Q8

T16
33 0.11 0.11
kV
/
/
3 3 3

Q8

Q8

Q8

T1

P1

3
T1

P1

T2

P2

P1

T1
3

P2

P1

P2

Q8

2A

3
T1

P1

P1

3
T1

T4

P2

P1

P2

P1

3X

P1

T1
3

T16

P2

P2

2A

P1

3
T3

T1

P1

T1
3

P2

33 0.11 0.11
kV
/
/
3 3 3

P1

T2

P2

P2

XLPE, Cu,33 kV
3x1x400 mm.sq.

XLPE, Cu,33 kV
3x1x400 mm.sq.

XLPE, Cu,33 kV
2(3x1x400) mm.sq.

XLPE, Cu,33 kV
3x1x240 mm.sq.

XLPE, Cu,33 kV
3x1x400 mm.sq.

XLPE, Cu,33 kV
3x1x400 mm.sq.

2A

T15

P1

1200-600/5A

P2

10 MVAr

XLPE, Cu,33 kV
3x1x400 mm.sq.

-T63
300-150/5/5

=-C1

P2

To 132 kV

P1 1

4(3 x1x 400) mm.sq Cu


11 kVXLPE

P1

XLPE, Cu,33 kV
3x1x240 mm.sq.

XLPE, Cu,33 kV
3x1x400 mm.sq.

Q9

-T63

P2

300-150/5/5

Q8

-L63
1

P2

=-C1

To 132 kV

-T64

4(3 x1x 400) mm.sq Cu


11 kV XLPE

P1

P1 1

OHL
Feeder
Transformer
Incoming
Feeder

CURRENT TRANSFORMERS
Desig
nation

-T1

Ratio

VOLTAGE TRANSFORMERS

CT Data

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

5P20, 30-15 VA; Rct=1.0-0.5

Cl.1 FS5, 30 VA; Rct=0.4

5P10, 30 VA; Rct=0.4

SIEMENS Type 8BT2 Slim

Date

REV :

DESCRIPTION :

Rated short time withstand current


31.5 kA/1 sec.

Signature Function

Name

Current Ratings
Busbars
Bus Sectionalizer
1250 A @ 40C 1250 A @ 40C
1122 A @ 50C 1122 A @ 50C

Date

PREPARED

Mujo Terko

CHECKED

Azam Sabrihafizovic 10.04.2012

APPROVED

Salar Abdulah

10.04.2012

10.04.2012

Signature

Feeders &
Transf. Incomer
1250 A @ 40C
1165 A @ 50C

ZOZIK COMPANY
POWER SECTOR
ENGINEERING DEPARTMENT

3X

33 0.11 0.11
/
/
kV
2
3 3 3

VT Data

Cl.1, 90 VA
3P, 90 VA

1.9 / 8 Hours

33 0.11 0.11
3X /
/
kV
-T16
3 3 3
1.9 / 8 Hours

-T4

Core

Cl.1 FS5, 30-15 VA; Rct=0.6-0.3

5P10, 30-15 VA; Rct=0.6-0.3

300-150/5/5 A

ANSI Code

Measuring A, W, Var, V
Protection 7SJ6225-4EB22-1FE1

Cl.1, 90 VA

3P, 90 VA

Measuring
50/50N/51/51G/51N/74TCS/86/
&
7SJ6245-4EB22-1FE4
/25/27/59/49/60
Protection ( Diff & Low Impedance REF

50/50N/51/51G/51N/74TCS/86/
25/27/59/

Measuring V, f
&
Protection 7SJ6245-4EB22-1FE4

27/59/81U/81O/60/
/59N/64 - 33 kV Stand-By E/F

Measuring A, W, Var, V
( Voltage provided from BB VTs &
Voltage Selection Schema )

Protection 7SJ6225-4EB22-1FE1

50/50N/51/51G/51N/74TCS/86/
/27/59

Protection 7SJ80 / Estasym 3D

50/50N/51N/46

50/5 A

5P10, 15 VA; Rct=

1200-600/5 A

5P20, 30-15 VA; Rct=1.0-0.5

Protection

5P10, 30-15 VA; Rct=1.0-0.5

Protection

5P20, 30-15 VA; Rct=1.0-0.5

Protection ( Spare Core for LI - REF )

KRG - MOE

KURDISTAN REGIONAL GOVERNMENT


MINISTRY OF ELECTRICITY

87/87N

Measuring A, W, Var, V, f
&
Protection 7SJ6245-4EB22-1FE4

-T62

300-150/5/5 A

50/50N/51/51G/51N/74TCS/86/
/79/27/59

A, W, Var, V, f

-T64

Neutral Point
33 kV
-T63

Type

in 7UT613 in 132 kV RP )

( Voltage provided from BB VTs &


Voltage Selection Schema )

1250/5/5 A

Bus Riser &


Metering
(VT) Feeders
Capacitor
Feeder

Ratio

( Voltage provided from BB VTs &


Voltage Selection Schema )

-T15

RELAYS
Duty

Desig
nation

Core

600-300/5/5 A

-T2 1200-600/5/5/5 A

Bus
-T3
Sectionalizer

Rated Voltage
36 kV

P2

50/5 A 5P 10
Feeder
Type

Operating Voltage
33 kV

=-R1

10 MVAr

50/5 A 5P 10
-T64

System / Rated Ferquency


3. ph, 50 Hz

P2

33 kV, 1250 A

17 Ohm, 33 kV
1000 A, 10 sec.

-L63
1

P1

P2

1328x1.25%/332x2.5%/11.5 kV
(ONAN)/ONAF
-T62 1 P2
(44.1/35/28 MVA)
1200-600/5A
63/50/40 MVA
YNyn0d11
P1

=-R1

P1

17 Ohm, 33 kV
1000 A, 10 sec.

3
T.4

P1

XLPE, Cu,33 kV
2(3x1x400) mm.sq.

Q9

Q8
1

P2

-TR. 2
-T62

Q8

P1

3
T1

T1
3

XLPE, Cu,33 kV
3x1x400 mm.sq.

33 kV, 1250 A

-TR. 1
1328x1.25%/332x2.5%/11.5 kV
(ONAN)/ONAF
(44.1/35/28 MVA)
63/50/40 MVA
YNyn0d11

Q8
P2

P2

XLPE, Cu,33 kV
3x1x400 mm.sq.

XLPE, Cu,33 kV
3x1x400 mm.sq.

P1

P2

XLPE, Cu,33 kV
3x1x400 mm.sq.

Q8

Q8

T15
3

Q8

P2

( Low Impedance REF


in 7UT613 in 132 kV RP )
( Stand-By E/F in 7SJ62 in
Transformer Incomer F. )

KRG-MOE-SS06b/2011 Sulaimanyah SS Stage 6


S/S TANJARO 132/33/11.5 kV, 2 x 63/50/40 MVA
SINGLE LINE DIAGRAM
33 kV Switchgear

No.

87N - 33 kV LI - REF
51N - 33 kV Stand-By E/F

SS6A-TB-33 kV SLD Z Rev0

Scale

Sheet

NTS

Sheets

Outgoing
Feeder No 13

Outgoing
Feeder No 14

VT Feeder/
Metering 2
+K21
=KZ04

+K20
=KZ01

+K19
=KZ01

TR. 2
Incoming

Outgoing
Feeder No 11

Outgoing
Feeder No 12

+K16
=KZ02

+K17
=KZ01

+K18
=KZ01

Outgoing
Outgoing
Feeder No 19 Feeder No 9

Outgoing
Feeder No 8

+K14
=KZ01

+K15
=KZ01

Aux.Tr. 2
Feeder

Bus
Sectionalizer

+K12
=KZ03

+K13
=KZ01

+K11
=KZ05

Q8

Q0

Q0

630 A

Q0

630 A

Q0

630 A

Q0

630 A

Q0

2500 A

Q0

630 A

Q0

630 A

Q0

630 A

Q0

630 A

2500 A

5A
3

P1

T.15
T1

3
T1

P1

3
T1

P2

P1

P2

P1

3
T1

P1

T2

P2

P2

P1

3
T1

3
T1

P1

3
T1

P2

P1

3
T4

3
T3

P2

P2

P1

P2

P1

3
P2

P2
Q8

XLPE, Cu,11 kV
3x1x185 mm.sq.

Q8

XLPE, Cu,11 kV
3x1x185 mm.sq.

Q8

XLPE, Cu,11 kV
3x1x185 mm.sq.

Q8

Q8

Q8

5A

XLPE, Cu,11 kV
3x1x185 mm.sq.

XLPE, Cu,11 kV
3x1x185 mm.sq.

3
T6

Q8

Q8

XLPE, Cu,11 kV
3x1x185 mm.sq.

XLPE, Cu,11 kV
3x1x185 mm.sq.

XLPE, Cu,11 kV
3x1x185 mm.sq.

11,52x2.5% / 0.4 kV
ONAN
1000 A for 10 s
Cycle Time : 1 hour
23 /phase +20-0%
ZNyn1
250 kVA; 400 V

(ONAN)/ONAF

(44.1/35/28 MVA)
63/50/40 MVA

YNyn0d11 -T62

P2
P1

-L63
-T63

P2
P1

-T61

1200-600/5 A

17 , 33 kV
1000A / 10s

P2
P1

300-150/5 A

To 132 kV
H

300-150/5/5 A

-Q61

12 kV 400 A

21.1
12 kV
300 A / 30 s

-NER 2
P2

-F61

7.2 kV 10 kA

Feeder
Type
OHL
Feeder

CURRENT TRANSFORMERS
Desig
nation

-T1

Ratio

Transformer
Incoming
Feeder

P1

CT Data

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

5P20, 30-15 VA; Rct=1.0-0.5

Cl.1 FS5, 30 VA; Rct=0.4

5P10, 30 VA; Rct=0.4

300-150/5/5 A

-T2 2500-1250/5/5/5

Bus
-T3
Sectionalizer

SIEMENS Type NxAir


Operating Voltage
11 kV

Rated Voltage
12 kV

Date

Rated short time withstand current


31.5 kA/1 sec.

Signature Function

Name

Date

PREPARED

Mujo Terko

CHECKED

Azam Sabrihafizovic 10.04.2012

APPROVED

Salar Abdulah

10.04.2012

10.04.2012

Current Ratings
Busbars
Feeders
2500 A @ 40C 630 A @ 40C
2255 A @ 50C 630 A @ 50C
Signature

Bus Sectionalizer
& Transf. Incomer
2500 A @ 40C
2140 A @ 50C

ZOZIK COMPANY
POWER SECTOR
ENGINEERING DEPARTMENT

Neutral Point
-T65
11 kV

Duty
Ratio

2500/5/5 A

-T15

3X

11 0.11 0.11
/
/
kV
3 3 3

Cl.1 FS5, 30 VA; Rct=0.2


5P10, 30 VA; Rct=0.2

3P, 90 VA

Type

ANSI Code

Measuring A, W, Var, V
Protection 7SJ6225-4EB22-1FE1

in 7UT613 in 132 kV RP )

Cl.1, 90 VA

3P, 90 VA

50/50N/51/51G/51N/74TCS/86/
/79/27/59

A, W, Var, V; f; TAPCON 230(Tr. Voltage Regulation )


Measuring
50/50N/51/51G/51N/74TCS/86/
&
7SJ6245-4EB22-1FE4
/25/27/59/49/60
Protection ( Diff & Low Impedance REF
87/87N

Measuring A, W, Var, V, f
&
Protection 7SJ6245-4EB22-1FE4

50/50N/51/51G/51N/74TCS/86/
25/27/59/

Measuring V, f
&
Protection 7SJ6245-4EB22-1FE4

27/59/81U/81O/60/
/59N/64 - 11 kV Stand-By E/F

A, W, Var, V
Measuring
7SJ6225-4EB22-1FE1

50/50N/51/51G/51N/74TCS/86/
/27/59

( Stand-By E/F in 7SJ62 in


Transformer Incomer F. )

51N - 11 kV Stand-By E/F

5P10, 30-15 VA; Rct=1.0-0.5

Protection

5P20, 30-15 VA; Rct=1.0-0.5

Protection ( Spare Core )

300-150/5/5 A

KRG - MOE

Cl.1, 90 VA

( Voltage provided from BB VTs &


Voltage Selection Schema )

40/5/5 A

KURDISTAN REGIONAL GOVERNMENT


MINISTRY OF ELECTRICITY

1.9 / 8 Hours

1.9 / 8 Hours

VT Data

( Voltage provided from BB VTs &


Voltage Selection Schema )

11 0.11 0.11
3X /
/
kV
-T16
3 3 3
1

Core

( Voltage provided from BB VTs &


Voltage Selection Schema )

Bus Riser &


Metering
(VT) Feeders
Earthing/Aux.
Transformer -T4
Feeder

RELAYS

VOLTAGE TRANSFORMERS
Desig
nation

Core

1 -T65

300-150/5/5

33 kV XLPE Cu
2x(3x1x400mmsq)

DESCRIPTION :

TO SECTION 1

XLPE, Cu,11 kV
4(3x1x400 mm.sq.)

Grounding / Aux. Tr. No.2

TR. 2

1328x1.25%/332x2.5%/11.5 kV

REV :

Q8

XLPE, Cu,11 kV
3x(1x185) mm.sq.

11 kV XLPE Cu
4x(3x1x400mmsq)

System / Rated Ferquency


3. ph, 50 Hz

Q8

KRG-MOE-SS06b/2011 Sulaimanyah SS Stage 6


S/S TANJARO 132/33/11.5 kV, 2 x 63/50/40 MVA
SINGLE LINE DIAGRAM
11 kV Switchgear Section 2

No.

SS6A-TB-11 kV SLD Z Rev0

Scale

Sheet

NTS

Sheets

Bus Riser /
Metering 1

Outgoing
Feeder No 7

Outgoing
Feeder No 6

+K09
=KZ01

+K10
=KZ06

Q0
M

Outgoing
Feeder No 5

+K08
=KZ01

Q0

630 A

+K07
=KZ01

Q0

630 A

Q0

Q0

2500 A

Outgoing
Feeder No 3

+K05
=KZ01

+K06
=KZ02

630 A

Outgoing
Feeder No 4

TR. 1
Incoming

Outgoing
Feeder No 2

Outgoing
Feeder No 1

+K03
=KZ01

+K02
=KZ01

+K04
=KZ01

Q0

630 A

Q0

630 A

Q0

630 A

Aux.Tr. 1
Feeder
+K01
=KZ03

Q0

630 A

630 A

Q8

5A

3
T1

P1

P1

3
T1

T1

P2

T16

P1

P1

3
T1

T2

P2

P2

P1
T1 T1

P1

3
T1

P2

P1

3
T1

P2

P1

3
T4

P2

P1

P2

P2

P2
Q8

Q8

XLPE, Cu,11 kV
3x(1x185) mm.sq.

TO SECTION 2

Q8

Q8

XLPE, Cu,11 kV
3x(1x185) mm.sq.

XLPE, Cu,11 kV
3x(1x185) mm.sq.

Q8

Q8

5A

XLPE, Cu,11 kV
3x(1x185) mm.sq.

Q8

XLPE, Cu,11 kV
3x(1x185) mm.sq.

Q8

XLPE, Cu,11 kV
3x(1x185) mm.sq.

XLPE, Cu,11 kV
3x(1x185) mm.sq.

Grounding / Aux. Tr. No.1

TR. 1

11,52x2.5% / 0.4 kV
ONAN
1000 A for 10 s
Cycle Time : 1 hour
23 /phase +20-0%
ZNyn1
250 kVA; 400 V

1328x1.25%/332x2.5%/11.5 kV
(ONAN)/ONAF

(44.1/35/28 MVA)
63/50/40 MVA

YNyn0d11 -T62

P2
P1

-L63
-T63

P2
P1

-T61

1200-600/5 A

17 , 33 kV
1000A / 10s

P2
P1

300-150/5 A

To 132 kV
H

300-150/5/5 A

-Q61

12 kV 400 A

21.1
12 kV
300 A / 30 s

-NER 1
P2

-F61

7.2 kV 10 kA

Feeder
Type
OHL
Feeder

CURRENT TRANSFORMERS
Desig
nation

-T1

Ratio

Transformer
Incoming
Feeder

P1

CT Data

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

Cl.1 FS5, 30-15 VA; Rct=0.8-0.4

5P10, 30-15 VA; Rct=0.8-0.4

5P20, 30-15 VA; Rct=1.0-0.5

Cl.1 FS5, 30 VA; Rct=0.4

5P10, 30 VA; Rct=0.4

300-150/5/5 A

-T2 2500-1250/5/5/5

Bus
-T3
Sectionalizer

SIEMENS Type NxAir


Operating Voltage
11 kV

Rated Voltage
12 kV

Date

Rated short time withstand current


31.5 kA/1 sec.

Signature Function

Name

Date

PREPARED

Mujo Terko

CHECKED

Azam Sabrihafizovic 10.04.2012

APPROVED

Salar Abdulah

10.04.2012

10.04.2012

Current Ratings
Busbars
Feeders
2500 A @ 40C 630 A @ 40C
2255 A @ 50C 630 A @ 50C
Signature

Bus Sectionalizer
& Transf. Incomer
2500 A @ 40C
2140 A @ 50C

ZOZIK COMPANY
POWER SECTOR
ENGINEERING DEPARTMENT

Neutral Point
-T65
11 kV

Duty
Ratio

2500/5/5 A

-T15

3X

11 0.11 0.11
/
/
kV
3 3 3

Cl.1 FS5, 30 VA; Rct=0.2


5P10, 30 VA; Rct=0.2

3P, 90 VA

Type

ANSI Code

Measuring A, W, Var, V
Protection 7SJ6225-4EB22-1FE1

in 7UT613 in 132 kV RP )

Cl.1, 90 VA

3P, 90 VA

50/50N/51/51G/51N/74TCS/86/
/79/27/59

A, W, Var, V; f; TAPCON 230(Tr. Voltage Regulation )


Measuring
50/50N/51/51G/51N/74TCS/86/
&
7SJ6245-4EB22-1FE4
/25/27/59/49/60
Protection ( Diff & Low Impedance REF
87/87N

Measuring A, W, Var, V, f
&
Protection 7SJ6245-4EB22-1FE4

50/50N/51/51G/51N/74TCS/86/
25/27/59/

Measuring V, f
&
Protection 7SJ6245-4EB22-1FE4

27/59/81U/81O/60/
/59N/64 - 11 kV Stand-By E/F

A, W, Var, V
Measuring
7SJ6225-4EB22-1FE1

50/50N/51/51G/51N/74TCS/86/
/27/59

( Stand-By E/F in 7SJ62 in


Transformer Incomer F. )

51N - 11 kV Stand-By E/F

5P10, 30-15 VA; Rct=1.0-0.5

Protection

5P20, 30-15 VA; Rct=1.0-0.5

Protection ( Spare Core )

300-150/5/5 A

KRG - MOE

Cl.1, 90 VA

( Voltage provided from BB VTs &


Voltage Selection Schema )

40/5/5 A

KURDISTAN REGIONAL GOVERNMENT


MINISTRY OF ELECTRICITY

1.9 / 8 Hours

1.9 / 8 Hours

VT Data

( Voltage provided from BB VTs &


Voltage Selection Schema )

11 0.11 0.11
3X /
/
kV
-T16
3 3 3
1

Core

( Voltage provided from BB VTs &


Voltage Selection Schema )

Bus Riser &


Metering
(VT) Feeders
Earthing/Aux.
Transformer -T4
Feeder

RELAYS

VOLTAGE TRANSFORMERS
Desig
nation

Core

1 -T65

300-150/5/5

33 kV XLPE Cu
2x(3x1x400mmsq)

DESCRIPTION :

XLPE, Cu,11 kV
3x(1x185) mm.sq.

XLPE, Cu,11 kV
3x(1x185) mm.sq.

11 kV XLPE Cu
4x(3x1x400mmsq)

REV :

Q8

XLPE, Cu,11 kV
4(3x1x400 mm.sq.)

T15

System / Rated Ferquency


3. ph, 50 Hz

Q8

KRG-MOE-SS06b/2011 Sulaimanyah SS Stage 6


S/S TANJARO 132/33/11.5 kV, 2 x 63/50/40 MVA
SINGLE LINE DIAGRAM
11 kV Switchgear Section 1

No.

SS6A-TB-11 kV SLD Z Rev0

Scale

Sheet

NTS

Sheets