STEAM TURBINE CONTROL SYSTEM

10

Classe di Riservatezza
confidential class

HW INTERFACE I/O LIST

Volume N.

Prodotto/Struttura

volume no.

product/structure

Tipo doc.

Codice EmittenteTeamcenter

Ente Emittente

Edizione in lingua

Derivato da

Rev.

doc. type

teamcenter issuer code

issued by

language

derived from

rev.

MPO

AUT

TVP/MTV

ENG

Commessa Progetto

Cliente

job no.

client

project

COCHRANE
THERMOELECTRIC POWER PLANT

0521
Rev.

Descrizione

rev.

00
01
02
03

kind of revision

First issue
REVISED
As tested (according to Posco Comments : CCR-POH (PEN)-AEN-T0082)
REVISED ACCORDING TO CCR-POH(PEN)-AEN-T-00118

MAIELLA
TP
MAIELLA
TP
MAIELLA
TP

M. DE PAOLI

F.CAGLIANI

IPI/TVP /MTV

IPI/TVP/CTEC

M. DE PAOLI

F.CAGLIANI

IPI/TVP /MTV

IPI/TVP/CTEC

M. DE PAOLI

F.CAGLIANI

IPI/TVP /MTV

IPI/TVP/CTEC

GB

M. DE PAOLI

F.CAGLIANI

GC

IPI/TVP /MTV

IPI/TVP/CTEC

C. BIMA

26/02/2015

IPI/TVP/MTV
C. BIMA

18/01/2015

IPI/TVP/MTV
C. BIMA

18/07/2014

IPI/TVP/MTV
C. BIMA

27/09/2013

IPI/TVP/MTV

Rev

Scopo

Preparato

Controllato

Verificato

Verificato

Approvato

Data

rev.

scope

prepared

checked

verified

verified

Approved

Date

COCHRANE

TITLE THERMOELECTRIC

STEAM TURBINE CONTROL SYSTEM HW INTERFACE I/O LIST

POWER PLANT
PREPARED

Posco

ELECT.SIGN D:De Paoli C:De Paoli A1:Cagliani A2:Bima A3:- (26/02/2015)


Approved.
For Construction.

0521TXMAYI704

SIGNA
TURE
DATE

CHECKED

REVIEWED

APPROVED

Posco
DWG
no.

0-WD240 EJ451 00704

Ansaldo Energia s.p.a. si riserva tutti i diritti su questo documento che non pu essere riprodotto neppure parzialmente senza la sua autorizzazione scritta
Ansaldo Energia s.p.a. reserves all rights on this document that can not be reproduced in any part without its written consent

Progetto / Titolo

Identificativo

Rev.

Pagina

Di

Project / title

document no.

rev.

page

of

0521 COCHRANE

0521TXMAYI704

10

Classe di Riservatezza
confidential class

1. GENERAL
The present document covers hardwire Input/Output relative to the Steam Turbine Control
System (STCS) supplied by AEN for the Cochrane Thermal Electrical Power Station 270MW in
Chile.
The following systems are involved:

MAA - HP section
MAB - IP section
MAC - LP section
MAD - ST Supervisory Instrument System for ST and generator bearing
MAV - Lube and jacking oil System
MAK - ST Turning gear
MAL - Drain valves system
MAW -Gland seal system
MAX - Hydraulic oil system for control and protection
MK* generator and excitation system
HW Interface with DCS and other systems supplied by the Client
SAM - Ventilation system for the steam turbine and generator enclosures

For Cochrane Power Station the steam turbine control system (STCS) will be integrated in the plant
control system managed by a DCS (supplied by the Client). The STCS Operator Stations will be
located in the MCR. The interface between STCS and DCS will be performed by HW connection for
protection signals and via Redundant TCP/IP MODBUS protocol for the interface between STCS
and DCS
2. REFERENCE DOCUMENTS
0521 TXMAVS525
0521 TXMAWS524
0521 TX1MAXS526
0521 TXMA*S527
0521 GXMKAU019
0521 TXMAYI005
0521 TXMA*S538
0521 A0VVCU119
0521 A0VVCU153

P&ID Hydraulic and lube oil system


P&ID Steam seal & drain system
P&ID Control and protection system
P&ID -ST Supervisory Instrument System
Generator Measuring Point Diagram
STCS HW I/O List
Steam Turbine Instrument Setup List
Steam Turbine Electrical Load List
ST Generator - Electrical Functional Diagram

3. DESIGNATION
Data contained in the individual column will be referred to the following designation.

Ansaldo Energia s.p.a. si riserva tutti i diritti su questo documento che non pu essere riprodotto neppure parzialmente senza la sua autorizzazione scritta
Ansaldo Energia s.p.a. reserves all rights on this document that can not be reproduced in any part without its written consent

Progetto / Titolo

Identificativo

Rev.

Pagina

Di

Project / title

document no.

rev.

page

of

0521 COCHRANE

0521TXMAYI704

10

Classe di Riservatezza
confidential class

3.1.
NUMBER
Progressive number.

3.2

Prefix : X2 (X=1 for unit1 and X=2 for unit 2)

3.3

TAG NAME
Signal TAG identification according to KKS Identification Codes

3.4

DESCRIPTION
Signal service description

3.5

SYGNAL TYPE

DI : digital input coming from a free voltage contact SPST


DI2 : digital input coming from a proximity limit switches 2 wires (Namur type)
DDI: digital input coming from SPDT contact
DO: output signal , normally open contact means free voltage contact
AI : analogue input 4-20mA , 2 wires technique, system powered
AI2: analogue input 4-20mA, 2 wires techniques, fed by external system
AI3 analog input, 3 wires technique, 15 Vdc system powered ()
AI4: analog input 4-20mA, 4 wires technique system powered
AIX: voltage signal (0 20Vdc)
SI: frequency signal speed pick up
AO: analog output signal, 4-20mA, 2 wires technique, system powered
RTD: input signal coming from thermoresistance, 3 wires technique
TC: input signal coming from thermocouple

3.6.

REF. DOCUMENT
Document (e.g. P&ID tag identification) indicating the measuring point / instrument /
actuator which generates the signal.

3.7.

E.U.
Engineering unit relative to each signal

3.8.

Range
Range of the analog signal

Ansaldo Energia s.p.a. si riserva tutti i diritti su questo documento che non pu essere riprodotto neppure parzialmente senza la sua autorizzazione scritta
Ansaldo Energia s.p.a. reserves all rights on this document that can not be reproduced in any part without its written consent

Progetto / Titolo

Identificativo

Rev.

Pagina

Di

Project / title

document no.

rev.

page

of

0521 COCHRANE

0521TXMAYI704

10

Classe di Riservatezza
confidential class

3.9.

CONNECTED TO/FROM

There will be indicate, if applicable, the Power/Control Panel or Junction Box


indicating the origin or destination of the signal, in order to define the electrical
interconnections from/to control system.
X2CJM01 STCS power Distribution Cabinet
X2MAV21GS031 Emergency oil pump starter
X2MAV50GS002 Emergency jacking oil pump
ST JB ST junction boxes
*AA *(es. MAC10AA041) MOV actuator starter integrated
Soft Starter power cabinet with soft starter for turning gear
MKA10GD001/004 Generator Supervision
MKD10/20GD001 Field Generator bearing Junction Box
MKA10 Excitation Transformer
MKA20 Excitation Control Panel
METERING Electrical Metering Panel
GEN/PROT- Electrical Generator Protection Panel
SYNCH Electrical Synchronization Panel
*/Plant components supplied by the others (see also the doc.
0521TXMAYI005 HW I/O List)
TTS Tripping System (HCU01 cabinet)
X2CJJ03 Termination Unit Cabinet of the STCS (HCU01 see overview
architecture)
X2CXU01 Fire fighting panel

3.10 TYPICAL CONNECTION INTERFACE


In the present document the typical interface to the control system is shown
(see the document TXMAYI714/rev.0 STCS Control Logic Typical Interface
Diagram)
MMA: signals relative to a typical hardware interface to a motor (fed by MCC):
2DI+2DO
SOFT STARTER signal interface to/from motor soft starter (ST turning gear):
2DI+1DO
MMC1/2: signals relative to a typical hardware interface to a motor fed by
c.c.starter
VMA: signals relative to a typical hw interface to an ON-OFF motor driven
valve without intermediate stop :
VPA: signals relative to a typical HW interface to a ON-OFF solenoid valve,
fail closed 3DI+2DO in case of valve limit switches and 2DI +2DO in case
valve limit switches are missing
VPB: as above open ON-OFF solenoid valve

Ansaldo Energia s.p.a. si riserva tutti i diritti su questo documento che non pu essere riprodotto neppure parzialmente senza la sua autorizzazione scritta
Ansaldo Energia s.p.a. reserves all rights on this document that can not be reproduced in any part without its written consent

Progetto / Titolo

Identificativo

Rev.

Pagina

Di

Project / title

document no.

rev.

page

of

0521 COCHRANE

0521TXMAYI704

10

Classe di Riservatezza
confidential class

VSA: signals relative to a typical HW interface to a ON-OFF solenoid valve


with test/command purpose, fail closed: 2DI+1DO in case of afeedback limit
switche isand 1DI +1DO in case valve limit switche is missing
VSE: TV protection solenoid valve typical HW interface 2DI+1DO
VSF: Double solenoid valve for test purpose 1DI+2DO
CPA: signals relative to a typical hw interface to a control pneumatic valve:
1AI+1AO +2DI
CHA: signals relative to a typical hw interface to a hydraulic control valve:
2AI3+2AO

3.11 NOTE:
3.11.1 STCS is divided in:
DEHC section dedicated to control/regulation of the steam turbine (ST governor)
RSE section dedicated to data processing turbine (acceleration gradient for turbine
run-up and loading up)
TTS section dedicated to turbine protections.
ST Auxiliary control / monitoring system including Turbine Run - Up
TSI Turbine Suipervisory Instrumentation (by Bently Nevada)
Vickers cards will manage the position control loop of the steam hydraulic
control valve. These cards will be supplied by AE and will be mounted in the
DEHC cabinet.
DCS means plant automation system supplied by others
3.11.2 Where the section is not specified, it is intended that the signals belong to the ST
auxiliary/monitoring system.
3.11.3 The signals picked up by the TSI are transferred to STCS via hardwired way..
3.12 DOC. REVISION:
4. DESIGNATION
Pg. 6-9
The table is ordered by progressive number (N) and then by KKS tag

Ansaldo Energia s.p.a. si riserva tutti i diritti su questo documento che non pu essere riprodotto neppure parzialmente senza la sua autorizzazione scritta
Ansaldo Energia s.p.a. reserves all rights on this document that can not be reproduced in any part without its written consent

STEAM TURBINE
STCS - HW Interface I/O Signal List

AnsaldoEnergia
COCHRANE
N. item

PREFI
X

TAG NAME

DESCRIPTION

SYGNAL
TYPE

E.U.

REF. DOCUMENT

0521 TXMAYI704 rev.3

FUNCTION

CONNECTED
FROM/TO

TYPICAL
CONNECTION
INTERFACE

NOTE

FUNCTI
ONAL
GROUP

Rev.

129,0

X2

MAW30AN001 XB01

GLAND CONDENSER BLOWER in service

DI

TXMAWS524/1

MCC/Plant

MMA

FG04

130,0

X2

MAW30AN001 XB03

GLAND CONDENSER BLOWER unavailable

DI

TXMAWS524/1

MCC/Plant

MMA

FG04

131,0

X2

MAW30AN001 YB01

GLAND CONDENSER BLOWER cmd. START

DO

TXMAWS524/1

MCC/Plant

MMA

FG04

132,0

X2

MAW30AN001 YB02

GLAND CONDENSER BLOWER cmd. STOP

DO

TXMAWS524/1

MCC/Plant

MMA

FG04

133,0

X2

MAW30AN002 XB01

GLAND CONDENSER BLOWER in service

DI

TXMAWS524/1

MCC/Plant

MMA

FG04

134,0

X2

MAW30AN002 XB03

GLAND CONDENSER BLOWER unavailable

DI

TXMAWS524/1

MCC/Plant

MMA

FG04

135,0

X2

MAW30AN002 YB01

GLAND CONDENSER BLOWER cmd. START

DO

TXMAWS524/1

MCC/Plant

MMA

FG04

136,0

X2

MAW30AN002 YB02

GLAND CONDENSER BLOWER cmd. STOP

DO

MCC/Plant

MMA

FG04

MCC/Plant

MMA

FG01

MCC/Plant

MMA

FG01

241,0

X2

MAV02AN001 XB01

OIL TANK GAS EXTRACTOR in service

DI

TXMAWS524/1
TXMAVS525

242,0

X2

MAV02AN001 XB03

OIL TANK GAS EXTRACTOR unavailable

DI

TXMAVS525

243,0

X2

MAV02AN001 YB01

OIL TANK GAS EXTRACTOR cmd. START

DO

TXMAVS525

MCC/Plant

MMA

FG01

DO

TXMAVS525

MCC/Plant

MMA

FG01

244,0

X2

MAV02AN001 YB02

OIL TANK GAS EXTRACTOR cmd. STOP

245,0

X2

MAV02AN002 XB01

OIL TANK GAS EXTRACTOR in service

DI

TXMAVS525

MCC/Plant

MMA

FG01

246,0

X2

MAV02AN002 XB03

OIL TANK GAS EXTRACTOR unavailable

DI

TXMAVS525

MCC/Plant

MMA

FG01

247,0

X2

MAV02AN002 YB01

OIL TANK GAS EXTRACTOR cmd. START

DO

TXMAVS525

MCC/Plant

MMA

FG01

248,0

X2

MAV02AN002 YB02

OIL TANK GAS EXTRACTOR cmd. STOP

DO

TXMAVS525

MCC/Plant

MMA

FG01

249,0

X2

MAV21AP021 XB01

AUX LUBE OIL PUMP in service

DI

TXMAVS525

MCC/Plant

MMA

FG01

250,0

X2

MAV21AP021 XB03

AUX LUBE OIL PUMP unavailable

DI

TXMAVS525

MCC/Plant

MMA

FG01

251,0

X2

MAV21AP021 YB01

AUX LUBE OIL PUMP cmd. START

DO

TXMAVS525

MCC/Plant

MMA

FG01

252,0

X2

MAV21AP021 YB02

AUX LUBE OIL PUMP cmd. STOP

DO

TXMAVS525

MCC/Plant

MMA

FG01

265,0

X2

MAK80AE001 XB01

ST TURNING GEAR in service

DI

TXMAVS525

MCC/Plant

SOFT STARTER

FG02

266,0

X2

MAK80AE001 XB03

ST TURNING GEAR unavailable

DI

TXMAVS525

MCC/Plant

SOFT STARTER

FG02

267,0

X2

MAK80AE001 YB01

ST TURNING GEAR cmd. START/STOP

DO

TXMAVS525

MCC/Plant

SOFT STARTER

FG02

274,0

X2

MAV50AP001 XB01

JACKING OIL PUMP in service

DI

TXMAVS525

MCC/Plant

MMA

FG02

275,0

X2

MAV50AP001 XB03

JACKING OIL PUMP unavailable

DI

TXMAVS525

MCC/Plant

MMA

FG01

276,0

X2

MAV50AP001 YB01

JACKING OIL PUMP cmd. START

DO

TXMAVS525

MCC/Plant

MMA

FG02

277,0

X2

MAV50AP001 YB02

JACKING OIL PUMP cmd. STOP

DO

TXMAVS525

MCC/Plant

MMA

FG02

288,0

X2

MAX11AP001 XB01

HYDRAULIC OIL PUMP in service

DI

TXMAXS526/1

MCC/Plant

MMA

FG05

289,0

X2

MAX11AP001 XB03

HYDRAULIC OIL PUMP unavailable

DI

TXMAXS526/1

MCC/Plant

MMA

FG05

290,0

X2

MAX11AP001 YB01

HYDRAULIC OIL PUMP cmd. START

DO

TXMAXS526/1

MCC/Plant

MMA

FG05

291,0

X2

MAX11AP001 YB02

HYDRAULIC OIL PUMPcmd. STOP

DO

TXMAXS526/1

MCC/Plant

MMA

FG05

292,0

X2

MAX11AP002 XB01

HYDRAULIC OIL PUMP in service

DI

TXMAXS526/1

MCC/Plant

MMA

FG05

293,0

X2

MAX11AP002 XB03

HYDRAULIC OIL PUMP unavailable

DI

TXMAXS526/1

MCC/Plant

MMA

FG05

294,0

X2

MAX11AP002 YB01

HYDRAULIC OIL PUMP cmd. START

DO

TXMAXS526/1

MCC/Plant

MMA

FG05

295,0

X2

MAX11AP002 YB02

HYDRAULIC OIL PUMPcmd. STOP

DO

TXMAXS526/1

MCC/Plant

MMA

FG05

377,0

X2

SAM01AN001 XB01

GEN ENCLOSURE FAN N.1

DI

MCC/Plant

MMA

378,0

X2

SAM01AN001 XB03

GEN ENCLOSURE FAN N.1 unavailable

DI

MCC/Plant

MMA

379,0

X2

SAM01AN001 YB01

GEN ENCLOSURE FAN N.1 cmd. START

DO

MCC/Plant

MMA

380,0

X2

SAM01AN001 YB02

GEN ENCLOSURE FAN N.1 cmd. STOP

DO

MCC/Plant

MMA

381,0

X2

SAM01AN002 XB01

GEN ENCLOSURE FAN N.2

DI

MCC/Plant

MMA

0521_TXMAYI704_REV3

in service

in service

pag 6 of 10 pag

STEAM TURBINE
STCS - HW Interface I/O Signal List

AnsaldoEnergia
COCHRANE

0521 TXMAYI704 rev.3

CONNECTED
FROM/TO

TYPICAL
CONNECTION
INTERFACE

DI

MCC/Plant

MMA

DO

MCC/Plant

MMA

DO

MCC/Plant

MMA

TURBINE ENCLOSURE FAN N.1 in service

DI

MCC/Plant

MMA

SAM01AN003 XB03

TURBINE ENCLOSURE FAN N.1 unavailable

DI

MCC/Plant

MMA

X2

SAM01AN003 YB01

TURBINE ENCLOSURE FAN N.1 cmd. START

DO

MCC/Plant

MMA

390,0

X2

SAM01AN003 YB02

TURBINE ENCLOSURE FAN N.1 cmd. STOP

DO

MCC/Plant

MMA

391,0

X2

SAM01AN004 XB01

TURBINE ENCLOSURE FAN N.2 in service

DI

MCC/Plant

MMA

392,0

X2

SAM01AN004 XB03

TURBINE ENCLOSURE FAN N.2 unavailable

DI

MCC/Plant

MMA

393,0

X2

SAM01AN004 YB01

TURBINE ENCLOSURE FAN N.2 cmd. START

DO

MCC/Plant

MMA

394,0

X2

SAM01AN004 YB02

TURBINE ENCLOSURE FAN N.2 cmd. STOP

DO

MCC/Plant

MMA

395,0

X2

SAM01AN005 XB01

TURBINE ENCLOSURE FAN N.3 in service

DI

MCC/Plant

MMA

396,0

X2

SAM01AN005 XB03

TURBINE ENCLOSURE FAN N.3 unavailable

DI

MCC/Plant

MMA

397,0

X2

SAM01AN005 YB01

TURBINE ENCLOSURE FAN N.3 cmd. START

DO

MCC/Plant

MMA

398,0

X2

SAM01AN005 YB02

TURBINE ENCLOSURE FAN N.3 cmd. STOP

DO

MCC/Plant

MMA

399,0

X2

SAM01AN006 XB01

TURBINE ENCLOSURE FAN N.4 in service

DI

MCC/Plant

MMA

400,0

X2

SAM01AN006 XB03

TURBINE ENCLOSURE FAN N.4 unavailable

DI

MCC/Plant

MMA

401,0

X2

SAM01AN006 YB01

TURBINE ENCLOSURE FAN N.4 cmd. START

DO

MCC/Plant

MMA

402,0

X2

SAM01AN006 YB02

TURBINE ENCLOSURE FAN N.4 cmd. STOP

DO

MCC/Plant

MMA

403,0

X2

SAM01AN007 XB01

TURBINE ENCLOSURE FAN N.5 in service

DI

MCC/Plant

MMA

404,0

X2

SAM01AN007 XB03

TURBINE ENCLOSURE FAN N.5 unavailable

DI

MCC/Plant

MMA

405,0

X2

SAM01AN007 YB01

TURBINE ENCLOSURE FAN N.5 cmd. START

DO

MCC/Plant

MMA

406,0

X2

SAM01AN007 YB02

TURBINE ENCLOSURE FAN N.5 cmd. STOP

DO

MCC/Plant

MMA

407,0

X2

SAM01AN008 XB01

TURBINE ENCLOSURE FAN N.6 in service

DI

MCC/Plant

MMA

408,0

X2

SAM01AN008 XB03

TURBINE ENCLOSURE FAN N.6 unavailable

DI

MCC/Plant

MMA

409,0

X2

SAM01AN008 YB01

TURBINE ENCLOSURE FAN N.6 cmd. START

DO

MCC/Plant

MMA

410,0

X2

SAM01AN008 YB02

DO

MCC/Plant

MMA

525,0

X2

MKA13AH001 XB01

TURBINE ENCLOSURE FAN N.6 cmd. STOP


GENERATOR HEATER in/out of service

DI

GXMKAU019

MCC/Plant

MMA

526,0

X2

MKA13AH001 XB03

GENERATOR HEATER unavailable

DI

GXMKAU019

MCC/Plant

MMA

527,0

X2

MKA13AH001 YB01

GENERATOR HEATER cmd. START

DO

GXMKAU019

MCC/Plant

MMA

528,0

X2

GENERATOR HEATER cmd. STOP

DO

GXMKAU019

MCC/Plant

MMA

N. item

PREFI
X

382,0

X2

SAM01AN002 XB03

GEN ENCLOSURE FAN N.2 unavailable

383,0

X2

SAM01AN002 YB01

GEN ENCLOSURE FAN N.2 cmd. START

384,0

X2

SAM01AN002 YB02

GEN ENCLOSURE FAN N.2 cmd. STOP

387,0

X2

SAM01AN003 XB01

388,0

X2

389,0

TAG NAME

DESCRIPTION

SYGNAL
TYPE

E.U.

REF. DOCUMENT

678,0

X4

MKA13AH001 YB02
BHD01EG001 XB01

STG UNIT 0,4kV MCC-A UNDERVOLTAGE

DI

679,0

X4

BHD02EG001 XB01

STG UNIT 0,4kV MCC-B UNDERVOLTAGE

DI

680,0

X4

BHD01GS001 XB01

STG UNIT 0,4kV MCC-A INCOMING LINE OPEN

DI

681,0

X4

BHD02GS001 XB01

STG UNIT 0,4kV MCC-B INCOMING LINE OPEN

DI

19,0

X2

LBQ20CG011 YG01

HP6 EXTR. CHECK VALVE AA061 - open

DO

27,0

X2

LBQ20CG031 YG01

TXMAWS524/1

X2

LBQ10CG011 YG01

HP6 EXTR. MOT. SHUTOFF VALVE - open


HP5 EXTR. 1st CHECK VALVE AA061 - open

DO

35,0

DO

TXMAWS524/2

43,0

X2

LBQ10CG031 YG01

TXMAWS524/2

X2

LBQ10CG021 YG01

HP5 EXTR. MOT. SHUTOFF VALVE - open


HP5 EXTR. 2nd CHECK VALVE AA062 - open

DO

51,0

DO

TXMAWS524/2

0521_TXMAYI704_REV3

TXMAWS524/1

FUNCTION

NOTE

FUNCTI
ONAL
GROUP

Rev.

permissive
permissive
permissive
permissive

MCC/Plant

MCC/Plant

MCC/Plant

GS

DCS/Plant

VPA

GS

DCS/Plant

VMA

GS

DCS/Plant

VPA

GS

DCS/Plant

VMA

GS

DCS/Plant

VPA

MCC/Plant

1
1

pag 7 of 10 pag

STEAM TURBINE
STCS - HW Interface I/O Signal List

AnsaldoEnergia
COCHRANE
N. item

PREFI
X

TAG NAME

DESCRIPTION

SYGNAL
TYPE

E.U.

0521 TXMAYI704 rev.3

REF. DOCUMENT

FUNCTION

CONNECTED
FROM/TO

TYPICAL
CONNECTION
INTERFACE

NOTE

FUNCTI
ONAL
GROUP

Rev.

59,0

X2

LBD10CG011 YG01

DEAREAT EXTR. 1st CHECK VALVE AA061 - open

DO

TXMAWS524/2

GS

DCS/Plant

VPA

67,0

X2

LBD10CG031 YG01

DO

TXMAWS524/2

GS

DCS/Plant

VMA

75,0

X2

LBD10CG021 YG01

DEAREAT EXTR. MOT. SHUTOFF VALVE - open


DEAREAT EXTR. 2nd CHECK VLV AA062 - open

DO

TXMAWS524/2

GS

DCS/Plant

VPA

1
1

83,0

X2

LBS20CG011 YG01

LP2 EXTR. CHECK VALVE AA041 - open

DO

TXMAWS524/2

GS

DCS/Plant

VPA

91,0

X2

LBS20CG031 YG01

DO

TXMAWS524/2

GS

DCS/Plant

VMA

99,0

X2

LBS30CG011 YG01

LP2 EXTR. MOT. SHUTOFF VALVE - open


LP3 EXTR. CHECK VALVE AA041 -open

DO

TXMAWS524/2

GS

DCS/Plant

VPA

107,0

X2

LBS30CG031 YG01

LP3 EXTR. MOT. SHUTOFF VALVE - open

DO

TXMAWS524/2

GS

DCS/Plant

VMA

123,0

X2

MAW01CG001YG01

SEAL STM SUPPLY MOV from AUX STM - open

DO

TXMAWS524/1

GS

DCS/Plant

VMA

587,0

X2

LBA21CP901 YQ01

AO

588,0

X2

LBA21CT901 YQ01

HP STEAM ADMISSION PRESS TO DCS


HP STEAM ADMISSION TEMP to DCS

AO

589,0

X2

LBA10AA541 XQ01

HP BOILER STEAM vent valve position

AI2

590,0

X2

MAA10CF901 YQ01

HP STEAM FLOW to ST (calculated) to DCS CH.A

AO

591,0

X2

MAA10CF901 YQ11

HP STEAM FLOW to ST (calculated) to DCS CH.B

AO

592,0

X2
X2

HP TBN FIRST STAGE PRESS TO DCS


IP STEAM ADMISSION PRES to DCS

AO

593,0

MAA10CP901 YQ01
LBB21CP901 YQ01

594,0

X2

LBB21CT901 YQ01

AO

595,0

X2

MAB10CP101 YQ01

IP STEAM ADMISSION TEMP to DCS


IP TBN FIRST STAGE PRESS TO DCS

596,0

X2

597,0

X2

MKA01CE903 YQ01
MKA01CE904 YQ01

GENERATOR MW CH.A
GENERATOR MVAR

AO
AO

598,0

X2

MKA01CE905 YQ01

GENERATOR VOLTAGE

AO

599,0

X2

MKA01CE906 YQ01

GENERATOR FREQUENCY

AO

600,0

X2
X2

ONE CIRCUL. PMP & ONE EXTRACT. PMP IN OPERATION


CLOSED COOLING SYSTEM IN OPERATION

DI
DI

TXMAYI708

601,0

CJB01EC003 XG01
CJB01EC001 XG01

602,0

X2

CJB01EC005 XG01

VACUUM SYSTEM IN OPERATION.

603,0

X2

CJB01EC008 XG01

604,0

X2

605,0
606,0

BAR
C
%
kg/s
kg/s
BAR
BAR
C
BAR

TXMAYI706

MW

1
FG04

DCS/Plant

DCS/Plant

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

TXMAYI706

DCS/Plant

DCS/Plant

DCS/Plant

DCS/Plant

permissive

DCS/Plant

TXMAYI708

permissive

DCS/Plant

DI

TXMAYI708

permissive

DCS/Plant

HP/IP CYCLE DRAIN VALVE OPEN

DI

TXMAYI708

permissive

DCS/Plant

CJB01EC028 XG01

RELEASE FROM ELECTRICAL SYSTEM

DI

permissive

DCS/Plant

X2

LAD20FL101 XG01

HP6 PREHEATER - HH LEVEL ch.A

DI

TXMAYI706

protection

DCS/Plant

X2

LAD20FL101 XG11

HP6 PREHEATER - HH LEVEL ch.B

DI

TXMAYI706

protection

DCS/Plant

607,0

X2

LAD10FL101 XG01

HP5 PREHEATER - HH LEVEL ch.A

DI

TXMAYI706

protection

DCS/Plant

608,0

X2

LAD10FL101 XG11

HP5 PREHEATER - HH LEVEL ch.B

DI

TXMAYI706

protection

DCS/Plant

609,0

X2

LAA10FL101 XG01

DEAEREATOR HH LEVEL ch.A

DI

TXMAYI706

protection

DCS/Plant

610,0

X2

LAA10FL101 XG11

DEAEREATOR HH LEVEL ch.B

DI

TXMAYI706

protection

DCS/Plant

611,0

X2

LCC30FL101 XG01

LP3 PREHEATER - HH LEVEL ch.A

DI

TXMAYI706

protection

DCS/Plant

612,0

X2

LCC30FL101 XG11

LP3 PREHEATER - HH LEVEL ch.B

DI

TXMAYI706

protection

DCS/Plant

613,0

X2

LCC20FL101 XG01

LP2 PREHEATER - HH LEVEL ch.A

DI

TXMAYI706

protection

DCS/Plant

614,0

X2

LCC20FL101 XG11

LP2 PREHEATER - HH LEVEL ch.B

DI

TXMAYI706

protection

DCS/Plant

615,0

X2

REM/LOC SELECTOR IN REMOTE SELECTION

DO

TXMAYI708

selection

DCS/Plant

616,0

X2

CJB01EC010 YG01
MAW50EZ001 YG01

GLAND SEAL SYSTEM IN OPERATION

DO

TXMAYI706

status

DCS/Plant

617,0

X2

CJB01EC011 YG01

ST - SPEED CONTROL SELECTED

DO

TXMAYI715

selection

DCS/Plant

618,0

X2

CJB01EC012 YG01

TCS GOV MODE OPERATION

DO

TXMAYI715

selection

DCS/Plant

0521_TXMAYI704_REV3

AO
AO

TXMAYI706
TXMAYI708

permissive

MVar
V
Hz

pag 8 of 10 pag

STEAM TURBINE
STCS - HW Interface I/O Signal List

AnsaldoEnergia
COCHRANE
N. item

PREFI
X

619,0

X2

MAY00DE003 YQ01

VALVE POSITION TARGET

620,0

X2

MAY00DE004 YQ01

LOAD RATE LIMIT BY STRESS CONTROL

X2

CJB01EC014 YG01

ST FOLLOWS MODE SELECTED (PRESS. CNTR)

X2

MAY00DE006 XG01

TURBINE FOLLOW MODE (FOR MSP PERMISSION)

621,0

X2

MAY00DE009 XQ01

MAIN STEAM PRESSURE LIMIT SET POINT

AI2

622,0

X2

MAY00DE006 XG01

REMOTE MODE REQUEST FROM DCS

623,0

X2

MAY00DE008 XG51

LOCAL MODE REQUEST FROM DCS

624,0

X2

CJB01EC013 YG01

625,0

X2

626,0

CONNECTED
FROM/TO

TYPICAL
CONNECTION
INTERFACE

FUNCTI
ONAL
GROUP

FUNCTION

AO

TXMAYI715

current

DCS/Plant

AO

TXMAYI715

status

DCS/Plant

DO

TXMAYI715

selection

DCS/Plant

DI

TXMAYI715

selection

TXMAYI715

set point

DCS/Plant
DCS/Plant

DI

TXMAYI715

selection

DCS/Plant

DI

TXMAYI715

selection

DCS/Plant

REMOTE MODE SELECTED

DO

TXMAYI715

selection

DCS/Plant

CJB01EC013 YG51

LOCAL MODE SELECTED

DO

TXMAYI715

selection

DCS/Plant

X2

MAY00DE008 YG01

ST SHUT-DOWN SEQUENCE COMPLETED STATUS

DO

TXMAYI708

DCS/Plant

627,0

X2

MAY00DE010 XQ01

TURBINE MASTER DEMAND

AI2

TXMAYI715

set point

DCS/Plant

628,0

X2

MAY00DE011 YQ01

FREQUENCY BIAS TO BOILER (KdeltaF)

AO

TXMAYI715

ctrl request

DCS/Plant

629,0

X2

CJB01EC018 YG01

TURBINE STRESS CONTROL MODE

DO

TXMAYI715

selection

DCS/Plant

630,0

X2

MAY00DE005 XG01

RUN BACK REQUEST FROM DCS

DI

TXMAYI715

run back

DCS/Plant

X2

MAY00DE020 YG01

DESCRIPTION

SYGNAL
TYPE

REF. DOCUMENT

632,0

TAG NAME

0521 TXMAYI704 rev.3

ALL MAIN VALVES CLOSED CH.A

E.U.

BAR

DO

TXMAYI715

NOTE

C
C

Rev.

1
1
1

pulse

DCS/Plant

"1"=required
protection

DCS/Plant

"1"=required
protection

633,0

X2

MAY00DE020 YG11

ALL MAIN VALVES CLOSED CH.B

634,0

X2

MAY00DE022 YG01

AVAILABLE

DCS/Plant

635,0

X2

MAY00DE022 YG11

AVAILABLE

DCS/Plant

636,0

X2

MAY00DE005 YG11

ST RUN BACK to DCS

DO

TXMAYI715

637,0

X2

MAY00EZ001 ZV01

ST TRIP RESET

DI

TXMAYI706

reset

DCS/Plant

pulse

638,0

X2

MAY00GS001 XG04

ST TRIP CCR PB Ch.A

DI

TXMAYI706

trip

DCS/Plant

manteined

639,0

X2

MAY00GS001 XG05

ST TRIP CCR PB Ch.B

DI

TXMAYI706

trip

DCS/Plant

manteined

640,0

X2

MAY00GS001 XG06

ST TRIP CCR PB Ch.C

DI

TXMAYI706

trip

DCS/Plant

manteined

641,0

X2

MAY10EZ001 ZV01

ST TRIPPED ch.A to DCS

DO

TXMAYI706

status

DCS/Plant

642,0

X2

MAY10EZ001 ZV02

ST TRIPPED ch.B to DCS

DO

TXMAYI706

status

DCS/Plant

643,0

X2

MAY10EZ001 ZV03

ST TRIPPED ch.C to DCS

DO

TXMAYI706

status

DCS/Plant

648,0

X2

MAY01EZ001 XG01

ST TRIP REQUESTED BY DCS Ch.A

DI

TXMAYI706

trip

DCS/Plant

manteined

649,0

X2

MAY01EZ001 XG11

ST TRIP REQUESTED BY DCS Ch.B

DI

TXMAYI706

trip

DCS/Plant

manteined

650,0

X2

MAY01EZ001 XG21

ST TRIP REQUESTED BY DCS Ch.C

DI

TXMAYI706

trip

DCS/Plant

manteined

651,0

X2

MAY01EZ003 XG01

ST TRIP REQUESTED BY MFT Ch.A

DI

TXMAYI706

trip

DCS/Plant

manteined

652,0

X2

MAY01EZ003 XG11

ST TRIP REQUESTED BY MFT Ch.B

DI

TXMAYI706

trip

DCS/Plant

manteined

653,0

X2

MAY01EZ003 XG21

ST TRIP REQUESTED BY MFT Ch.C

DI

TXMAYI706

trip

DCS/Plant

manteined

654,0

X2

X2

TURBINE SPEED
ST ZERO SPEED

AO

655,0

MAD20CS901 YQ01
MAD20CS100 YG01

656,0

X2

MAY00EC001 XG01

ST START UP SEQUENCE by DCS

DO

TXMAYI715

RPM

DCS/Plant

1
1
1"=run back operatedn back operated

DO

TXMAYI706

status

DCS/Plant

DI

TXMAYI708

command

DCS/Plant

TXMAYI708

command

DCS/Plant

DCS/Plant

TXMAYI706

1
1
1

pulse
pulse

1
1

657,0

X2

MAY00EC001 XG02

ST SHUT DOWN SEQUENCE by DCS

DI

683,0

X2

CJJ01GH001 YG83

TCS NORMAL

DO

684,0

X2

MAY00DE010 YG83

TURBINE MASTER LINK PERMISSIVE

DO

TXMAYI715

DCS/Plant

685,0

X2

MAY00DE010 YG84

GOV / LL REVERSED

DO

TXMAYI715

DCS/Plant

0521_TXMAYI704_REV3

DCS/Plant

pag 9 of 10 pag

STEAM TURBINE
STCS - HW Interface I/O Signal List

AnsaldoEnergia
COCHRANE
N. item

PREFI
X

TAG NAME

DESCRIPTION

SYGNAL
TYPE

688,0

X2

MAA10CT101 YQ01

HP INLET STEM TEMPERATURE CH.A

689,0

X2

MAA10CT101 YQ11

HP INLET STEM TEMPERATURE CH.B

690,0

X2

MAB10CT101 YQ01

IP INLET STEM TEMPERATURE CH.A

691,0

X2

MAB10CT101 YQ11

IP INLET STEM TEMPERATURE CH.B

AO
AO
AO
AO

692,0

X4

ADA01EZ003 YG01

HVCB CLOSED

DO

693,0

X2

MAY00DE013 XG01

ST COLD MODE STATUS

DO

694,0

X2

MAY00DE014 XG01

ST WARM MODE STATUS

695,0

X2

MAY00DE015 XG01

631,0

X2

644,0

X2

658,0

E.U.

REF. DOCUMENT

0521 TXMAYI704 rev.3

FUNCTION

CONNECTED
FROM/TO

TYPICAL
CONNECTION
INTERFACE

NOTE

FUNCTI
ONAL
GROUP

Rev.

TXMAYI715

DCS/Plant

TXMAYI715

DCS/Plant

TXMAYI715

DCS/Plant

TXMAYI715

DCS/Plant

DCS/Plant

TXMAYI715

DCS/Plant

DO

TXMAYI715

DCS/Plant

ST HOT MODE STATUS

DO

TXMAYI715

DCS/Plant

MAY00DE005 YG01

ST RUN BACK to RTU

DO

TXMAYI706

RTU/Plant

X4

MAY10EZ001 ZV04
MAD20CS901 YB01

ST TRIPPED to RTU
ST SPEED < 20 rpm (Permissive to close earth disc.switch)

DO

TXMAYI706

659,0

X4

ADA01GS001 XB01

HV CIRCUIT BREAKER OPEN ch. A

DI

660,0

X4

ADA01GS001 XB11

HV CIRCUIT BREAKER OPEN ch.B

661,0

X4

ADA01EZ003 XG01

662,0

X4

663,0
668,0

X4
X4

645,0
646,0

RTU/Plant

DO

1
1"=run back operatedn back operated
"1"=ST tripped

"=ST tripped

1
1
1

HVCB/Plant

A0VVCU153

permissive
trip

HVCB/Plant

TTS

DI

A0VVCU153

trip

HVCB/Plant

TTS

GENERATOR CONNECTED TO THE GRIG CH.A

DI

A0VVCU153

load rejection

HVCB/Plant

DEHC

ADA01EZ003 XG11

GENERATOR CONNECTED TO THE GRIG CH.B

DI

A0VVCU153

load rejection

HVCB/Plant

DEHC

ADA01GS001 XB02
ADA01DE002 XB01

HV CIRCUIT BREAKER CLOSE


220KV BAY READY FOR SYNCHRONISATION

DI
DI

A0VVCU153
A0VVCU153

feedback
permissive

spare

1
1

X2

MAY10EZ003 ZV01

ST TRIPPED ch.A to boiler protection

DO

TXMAYI706

status

HVCB/Plant
HVCB/Plant
BOILER/Plant

X2

MAY10EZ003 ZV02

ST TRIPPED ch.B to boiler protection

DO

TXMAYI706

status

BOILER/Plant

647,0

X2

ST TRIPPED ch.C to boiler protection

DO

TXMAYI706

status

BOILER/Plant

682,0

X4

MAY10EZ003 ZV03
XJ*01DE001 XB01

X2

MAA10CY910 YQ01

DI
AO

DG LCP/Plant

476,0

EMERGENCY DIESEL IN OPERATION


HP DIFFERENTIAL EXPANSION measure

TXMA*S527

YIAR

VMS/Plant

477,5

X2

MAB10CY910 YQ01

IP DIFFERENTIAL EXPANSION measure

AO

TXMA*S527

YIAR

VMS/Plant

478,5

X2

MAC10CY910 YQ01

LP DIFFERENTIAL EXPANSION measure

AO

TXMA*S527

YIAR

VMS/Plant

0521_TXMAYI704_REV3

permissive

1
1

pag 10 of 10 pag