ETAP

Project:

12.6.0H

Location:
Contract:

1
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Electrical Transient Analyzer Program


Short-Circuit Analysis
IEC 60909 Standard
3-Phase, LG, LL, & LLG Fault Currents

Swing

V-Control

Load

Total

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

Synchronous
Generator

Power
Grid

Synchronous
Motor

Induction
Machines

Lumped
Load

Total

Number of Machines:

System Frequency:

50.00 Hz

Unit System:

Metric

Project Filename:

tugasptt

Output Filename:

E:\PROGRAM\Program elektro instalan\ETAP 12.6.0\tugasptt\shortcircuit.SI2

Number of Buses:

Number of Branches:

ETAP

Project:

12.6.0H

Location:
Contract:

2
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Apply
Temperature Correction

Percent

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Degree C

Revision:

Base

Config.:

Normal

ETAP

Project:

12.6.0H

Location:
Contract:

3
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Bus Input Data

Bus
ID

Type

Bus1

SWNG

Bus2
Bus3
Bus4

Initial Voltage
Nom. kV

Base kV

Sub-sys

%Mag.

Ang.

150.000

150.000

100.00

0.00

Load

20.000

20.000

100.00

0.00

Load

20.000

20.000

100.00

0.00

Load

20.000

20.000

100.00

0.00

4 Buses Total
All voltages reported by ETAP are in % of bus Nominal kV.
Base kV values of buses are calculated and used internally by ETAP .

Revision:

Base

Config.:

Normal

ETAP

Project:

12.6.0H

Location:
Contract:

4
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Line/Cable Input Data

Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable

Length
Size

Adj. (m)

% Tol.

Line1

506

10000.0

0.0

75

0.0730002

0.2962939

0.000004

0.2177232

1.542493

0.0000014

Line2

506

5000.0

0.0

75

0.0730002

0.2962939

0.000004

0.2177232

1.542493

0.0000014

ID

Library

Line / Cable resistances are listed at the specified temperatures.

#/Phase

T (C)

R1

X1

Y1

R0

X0

Y0

ETAP

Project:

12.6.0H

Location:
Contract:

5
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID
T2

Rating
MVA

Prim. kV

Sec. kV

60.000

150.000

20.000

Z Variation
%Z

X/R

12.50

45.00

% Tap Setting

+ 5%

- 5%

% Tol.

Prim.

Sec.

Adjusted

Phase Shift

%Z

Type

Angle

12.5000

YNyn

0.000

2-Winding Transformer Grounding Input Data


Grounding
Transformer
ID
T2

Rating

Conn.

MVA

Prim. kV

Sec. kV

Type

60.000

150.000

20.000

Y/Y

Primary
Type
Solid

kV

Secondary
Amp

Ohm

Type
Solid

kV

Amp

Ohm

ETAP

Project:

12.6.0H

Location:
Contract:

6
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch

Connected Bus ID

ID

Type

From Bus

% Impedance, Pos. Seq., 100 MVAb


To Bus

T2

2W XFMR

Bus1

Bus2

0.45

20.25

20.25

Line1

Line

Bus2

Bus3

18.25

74.07

76.29

0.0158837

Line2

Line

Bus2

Bus4

9.13

37.04

38.14

0.0079419

ETAP

Project:

12.6.0H

Location:
Contract:

7
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Power Grid Input Data

Power Grid

Connected Bus

ID
U1

ID
Bus1

Total Connected Power Grids ( = 1 ): 60.000 MVA

% Impedance
100 MVA Base

Rating
MVASC

kV

60.000

150.000

R
16.58395

X"
165.83950

Grounding
R/X"
0.10

Type
Wye - Solid

ETAP

Project:

12.6.0H

Location:
Contract:

8
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

SHORT- CIRCUIT REPORT

Fault at bus:
Nominal kV
Voltage c Factor

Bus3
= 20.000
= 1.10 (User-Defined)
Contribution

From Bus
ID

3-Phase Fault
To Bus
ID

%V
From Bus

Positive & Zero Sequence Impedances


Looking into "From Bus"

Line-To-Ground Fault

kA
Symm. rms

% Voltage at From Bus


Va
Vb
Vc

kA Symm. rms
Ia
3I0

R1

% Impedance on 100 MVA base


X1
R0

X0

Bus3

Total

0.00

1.137

0.00

116.30

115.79

0.828

0.828

3.69E+001

2.77E+002

7.31E+001

5.88E+002

Bus2

Bus3

27.32

1.137

47.03

100.00

100.00

0.828

0.828

3.69E+001

2.77E+002

7.31E+001

5.88E+002

Bus4

Bus2

27.32

0.000

47.03

100.00

100.00

0.000

0.000

Bus1

Bus2

34.44

1.137

52.26

100.00

100.00

0.828

0.828

1.87E+001

2.03E+002

1.87E+001

2.03E+002

Initial Symmetrical Current (kA, rms)


Peak Current (kA), Method C
Breaking Current (kA, rms, symm)
Steady State Current (kA, rms)

:
:
:
:

3-Phase
1.137
2.697
1.137

L-G

L-L
0.828
1.962
0.828
0.828

# Indicates a fault current contribution from a three-winding transformer


* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer

0.985
2.335
0.985
0.985

L-L-G
1.040
2.465
1.040
1.040

ETAP

Project:

12.6.0H

Location:
Contract:

9
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Short-Circuit Summary Report


3-Phase, LG, LL, LLG Fault Currents
Bus
ID
Bus3

3-Phase Fault
kV
20.000

Line-to-Ground Fault

Line-to-Line Fault

*Line-to-Line-to-Ground

I"k

ip

Ik

I"k

ip

Ib

Ik

I"k

ip

Ib

Ik

I"k

ip

Ib

Ik

1.137

2.697

1.137

0.828

1.962

0.828

0.828

0.985

2.335

0.985

0.985

1.040

2.465

1.040

1.040

All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.

ETAP

Project:

12.6.0H

Location:
Contract:

10
24-06-2015

SN:

Engineer:
Filename:

Page:
Date:

Study Case: SC

tugasptt

Revision:

Base

Config.:

Normal

Sequence Impedance Summary Report


Bus
ID
Bus3

Positive Seq. Imp. (ohm)


kV
20.000

Negative Seq. Imp. (ohm)

Zero Seq. Imp. (ohm)

Fault Zf (ohm)

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

Resistance

Reactance

Impedance

1.47769

11.06977

11.16796

1.47769

11.06977

11.16796

2.92492

23.53176

23.71285

0.00000

0.00000

0.00000