HEAT PUMP OUTDOOR UNITS

ENGINEERING DATA

SEER up to 14.70 Cooling Capacity - 18,600 to 59,000 Btuh (5.4 to 17.3 kW) Heating Capacity - 17,600 to 55,000 Btuh (5.2 to 16.1 kW)
Heavy gauge steel cabinet with powder paint finish Heavy duty PVC coated Fan Guard

ELITE 13t SERIES

HP26

Bulletin No. 210023 April 2001


Supersedes July 2000

Typical Application

Defrost/Timed-Off Control HushTonet Cabinet Design reduces operating sound levels High Pressure Switch Filter Drier Expansion Valve Copeland Scroll Compressor Support feet raise unit off ground Reversing Valve

Quiet Direct Drive Fan

Lanced Aluminum Fins

CopperTube Outdoor Coil

Enhanced PVC coated Coil Guard Brass Service Valves

MODEL NUMBER IDENTIFICATION


Unit Type HP = Heat pump Outdoor Unit

HP26 - 036 - 1 Y
Series Capacity Tons (kW) 024 = 2 (7.0) 030 = 2.5 (8.8) 036 = 3 (10.6) 042 = 3.5 (12.3) 048 = 4 (14.1) 060 = 5 (17.6)

Voltage P = 208/230v-1phase-60hz Y = 208/230v 3 phase 60hz G = 460v 3 phase 60hz J = 575v 3 phase 60hz

Minor Revision Number

FEATURES

Application - SEER up to 14.70. - Heating COP up to 3.79. - HSPF (Region IV) up to 8.85. - 1.5 through 5 ton (5.3 through 17.6 kW). - Single and three phase power supply. - Vertical air discharge allows concealment behind shrubs at grade level or out of sight on a roof. - Designed for applications with remotely located indoor blower-coil units or indoor add-on coils with FM21 furnace control. See FM21 bulletin, Thermostats and Controls section. Also see Coils and Blower Coils sections for indoor unit data. - Units shipped completely factory assembled, piped and wired. Each unit is test operated at the factory insuring proper operation. - Installer must set outdoor unit, connect refrigerant lines and make electrical connections to complete job. Approvals - Certified in accordance with USE certification program which is based on ARI Standard 210/240-94. - Sound rated in Lennox reverberant sound test room in accordance with test conditions included in ARI Standard 270-95. - Tested in the Lennox Research Laboratory environmental test room. - Rated according to U.S. Department of Energy (DOE) test procedures. - Units and components within bonded for grounding to meet safety standards for servicing required by UL and CEC. - Units are UL and ULC listed. - Developed in accordance with ISO 9002 quality standards. Equipment Warranty - Compressor limited warranty for ten years in residential installations, five years in non residential installations. - All other covered components limited warranty for five years in residential installations, one year in non residential installations. - Refer to Lennox Equipment Limited Warranty certificate included with unit for specific details. High Pressure Switch - Shuts off unit if abnormal operating conditions cause the discharge pressure to rise above setting. - Protects compressor from excessive condensing pressure. - Automatic reset.

NOTE - Due to Lennox' ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. 2001 Lennox Industries Inc. Installation and service must be performed by a qualified installer and servicing agency.

FEATURES

CopelandR Compliant Scrollt Compressor - Compressor features high efficiency with uniform suction flow, constant discharge flow and high volumetric efficiency and quiet operation. - Compressor consists of two involute spiral scrolls matched together to generate a series of crescent shaped gas pockets between them. - During compression, one scroll remains stationary while the other scroll orbits around it. - Gas is drawn into the outer pocket, the pocket is sealed as the scroll rotates. - As the spiral movement continues, gas pockets are pushed to the center of the scrolls. Volume between the pockets is simultaneously reduced. - When pocket reaches the center, gas is now at high pressure and is forced out of a port located in the center of the fixed scrolls. - During compression, several pockets are compressed simultaneously resulting in a smooth continuous compression cycle. - Continuous flank contact, maintained by centrifugal force, minimizes gas leakage and maximizes efficiency. - Scroll compressor is tolerant to the effects of slugging and contaminants. If this occurs, scrolls separate, allowing liquid or contaminants to to be worked toward the center and discharged. - Low gas pulses during compression reduces operational sound levels. - Compressor motor is internally protected from excessive current and temperature. - Compressor is installed in the unit on resilient rubber mounts for vibration free operation. Cabinet - Heavy gauge galvanized steel cabinet with five station metal wash process. - Powder paint finish provides superior rust and corrosion protection. - Separate compressor and control compartment insulated with thick fiberglass insulation. Compartment provides protection from the weather and keeps sound transmission at a minimum. - Control box is located in the compressor and controls compartment with all controls factory wired. - Large removable access panel provides complete service access. - Drainage holes are provided in base section for moisture removal. - High density polyethylene feet raise the unit off of the mounting surface away from damaging moisture. - Non corrosive PVC (polyvinyl chloride) coated steel wire outdoor coil guard is furnished. Outdoor Fan - Direct drive fan moves large air volumes uniformly through entire outdoor coil for high refrigerant cooling capacity. - Vertical air discharge minimizes operating sounds and eliminates damage to lawn and shrubs. - Motor totally enclosed for maximum protection from weather, dust and corrosion. - Rain shield on motor provides additional protection from moisture. - Corrosion resistant PVC (polyvinyl chloride) coated steel wire fan guard is furnished as standard. - Fan service access accomplished by removal of fan guard. Copper Tube/Enhanced Fin Coil - Lennox designed and fabricated coil. - Ripple-edged aluminum fins. - Copper tube construction is corrosion resistant and easy to service. - Precise coil circuiting gives uniform refrigerant distribution for high efficiency. - Wrap around U" shaped configuration provides extra large surface area with low air resistance. - Fin collars grip tubing for maximum contact area. - Inverted coil circuiting prevents ice buildup at coil base in low ambients. - Discharge gas enters bottom of coil during defrost and heat of refrigerant flows counter to water drainage resulting in extremely clean and unobstructed fins and tubes. - Fin spacing allows rapid and complete water drainage. - Flared shoulder tubing connections/silver soldering construction. - Coil is factory tested under high pressure to insure leakproof construction. - Entire coil is accessible for cleaning. Defrost/Timed Off Control - Solid state defrost control board is furnished as standard equipment. It gives a defrost cycle (14 minutes) for every 30, 60 or 90 minutes (adjustable) of compressor on" time at outdoor temperature below 35_F (2_C). - Sensing element mounted on the liquid line determines when the defrost cycle is required and also when to terminate a cycle. - Diagnostic LED on control board furnished as an aid for servicing. - Prevents compressor short cycling and allows time for suction and discharge pressure to equalize, permitting the compressor to start in an unloaded condition. - Automatic reset control provides a five minute time delay between compressor shutoff and start up. Refrigerant Line Connections, Electrical Inlets and Service Valves - Vapor and liquid lines are located inside unit cabinet and are made with sweat connections. See dimension drawing. - Fully serviceable brass service valves prevent corrosion and provide access to refrigerant system. Vapor valve can be fully shut off, while liquid valve may be front seated to manage refrigerant charge while servicing system. - Vapor and liquid line service valves and gauge ports are located inside the cabinet. - High capacity drier with internal check valve and strainer are furnished and factory installed in the liquid line. - Field wiring inlets conveniently located for ease of entry. See dimension drawing. Reversing Valve - 4 way interchange reversing valve effects a rapid change in direction of refrigerant flow resulting in quick changeover from cooling to heating and vice versa. - Valve operates on pressure differential between outdoor unit and indoor unit of the system. Factory installed. Expansion Valve - Designed and sized specifically for use in heat pump system. - Sensing bulb is located on the suction line between reversing valve and compressor thus sensing suction temperature in any cycle. - Factory installed and piped. Service Light Thermostat - Factory installed on the compressor discharge line. - Required for operation of conditioned area thermostat with service light. Ambient Compensating Thermistor - Reduces thermostat droop to improve the operating characteristics of the heat pump system. - Thermistor varies the heat anticipator resistance as ambient temperature changes. - Factory installed in the discharge air stream.

HP26 / Page 2 "

OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA

Thermostat - Thermostat is not furnished with the unit and must be ordered extra. - See Thermostats and Controls section and Lennox Price Book. Check and Expansion Valve Kit - Field installed on certain indoor units. - See ARI Ratings table. Refrigerant Line Kits - Refrigerant lines (vapor & liquid) are shipped refrigeration clean. Lines are cleaned, dried, pressurized and sealed at factory. - Vapor line fully insulated. - L15 lines are stubbed at both ends. - See Refrigerant Line Kit table for selection. - Kit is not available for HP26-060 model and must be field fabricated. - Refrigerant line length should not exceed 50 ft. (15 m) in any installation. If longer length lines are required, contact your Lennox Field Technical Consultant. Low Ambient Kit - Units will operate satisfactorily in the cooling mode down to 45_F (7_C) outdoor air temperature without any additional controls. - Kit LB 57113BM (27J00) can be added in the field enabling unit to operate properly down to 30_F (-1_C). Outdoor Thermostat Kit - An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable. - Outdoor thermostat maintains the heating load on the low power input as long as possible before allowing the full power load to come on the line. - Thermostat kit LB 29740BA (56A87) and mounting box M 1595 (31461) or BM 10260 (33A09) (Canada Only) must be ordered extra. Mounting Base - Provides permanent foundation for condensing units. - High density polyethylene structural material is lightweight, sturdy, sound absorbing and will withstand the rigors of the sun, heat, cold, moisture, oil and refrigerant. Will not mildew or rot. - Can be shipped singly or in packages of 6 to a carton. - See Specifications table.

FIELD WIRING
THERMOSTAT (Optional) DISCONNECT SWITCH (By Others) DISCONNECT SWITCH (By Others) LENNOX OPTIONAL SUPPLEMENTAL ELECTRIC HEAT

A B C D

Two or Three Wire Power (see Electrical Data) Two or Three Wire Power (size to heater capacity) Two Wire Power (size to indoor coil blower motor) Two Wire Low Voltage Eight Wire Low Voltage 18 ga. minimum 18 ga. minimum with Electric Heat

A E
OPTIONAL OUTDOOR THERMOSTAT

B D

LENNOX OUTDOOR UNIT

DISCONNECT SWITCH (By Others)

Ten Wire Low Voltage with Optional Outdoor Thermostat F Four Wire Low Voltage Three Wire Low Voltage 18 ga. minimum 18 ga. minimum

C G

LENNOX INDOOR UNIT

Field Wiring Not Furnished All wiring must conform to NEC or CEC and local electrical codes.

REFRIGERANT LINE KITS


Outdoor Unit M d lN Model No. Line Set Model No No. L15 26 20 HP26 018 L15 26 25 L15 26 35 L15 26 50 L15 41 20 HP26 024 HP26 030 HP26 036 L15 41 30 L15 41 40 L15 41 50 HP26 042 HP26 048 HP26 060
NOTE

INSTALLATION CLEARANCES - IN. (MM)


in. 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 mm 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 in. 5/8 5/8 5/8 5/8 3/4 3/4 3/4 3/4 7/8 7/8 7/8 1 1/8 mm 15.9 15.9 15.9 15.9 19 19 19 19 22.2 22.2 22.2 22.2

ft. 20 25 35 50 20 30 40 50 30 40 50

m 6 8 11 15 6 9 12 15 9 12 15

L15 65 30 L15 65 40 L15 65 50

Field Fabricate

Refrigerant line set should not exceed 50 ft. (15 m) in any installation.

K One side of unit may be 12 in. (305 mm) One of the remaining sides may be 6 in. (152 mm) NOTE - 48 in (1219 mm) clearance required on top of unit NOTE - 24 in. (610 mm ) required between two units


K36 (914) 30 (762) K36 (914) K36 (914)

Line Length

Liquid Line (o.d.)

Vapor Line (o.d.)

HP26 / Page 3 "

SPECIFICATIONS
General Data D t Connections (sweat) Refrigerant Outdoor Coil Model No. Nominal Tonnage Liquid line (o.d.) in. (mm) Vapor line (o.d.) in. (mm) *HCFC22 charge furnished Net face area sq. ft. (m2) sq ft Outer coil Inner coil HP26018 1.5 3/8 (9.5) 5/8 (16) 7 lbs. 1 oz. (3.20 kg) 11.9 (1.11) 8.3 (0.77) 5/16 (7.9) 2 22 (866) 20 (508) 4 1/10 (75) 1860 (880) 825 165 193 (88) HP26024 2 3/8 (9.5) 3/4 (19) 6 lbs. 8 oz. (2.95 kg) 11.9 (1.11) 8.3 (0.77) 5/16 (7.9) 2 22 (866) 20 (508) 4 1/10 (75) 1860 (880) 825 165 194 (88) HP26030 2.5 3/8 (9.5) 3/4 (19) 8 lbs. 12 oz. (3.97 kg) 16.0 (1.59) 15.6 (1.45) 5/16 (7.9) 2 22 (866) 24 (610) 3 1/6 (124) 3000 (1415) 825 230 242 (110) HP26036 3 3/8 (9.5) 3/4 (19) 9 lbs. 8 oz. (4.31 kg) 16.0 (1.59) 15.6 (1.45) 5/16 (7.9) 2 22 (866) 24 (610) 3 1/6 (124) 1/4 (187) 3000 (1415) 3900 (1840) 825 230 345 252 (114) HP26042 3.5 3/8 (9.5) 7/8 (22.2) 11 lbs. 0 oz. (4.99 kg) 18.3 (1.70) 17.8 (1.65) 5/16 (7.9) 2 22 (866) 24 (610) 3 1/6 (124) 1/4 (187) 3100 (1465) 3900 (1840) 825 230 345 263 (119) HP26048 4 3/8 (9.5) 7/8 (22.2) 12 lbs. 8 oz. (5.67 kg) 24.1 (2.24) 23.3 (2.17) 5/16 (7.9) 2 22 (866) 24 (610) 4 1/4 (187) 1/4 (187) 4200 (1980) 4200 (1980) 825 345 345 330 (150) HP26060 5 3/8 (9.5) 11/8 (28.6) 13 lbs. 6 oz. (6.07 kg) 24.1 (2.24) 23.3 (2.17) 5/16 (7.9) 2 22 (866) 24 (610) 4 1/4 (187) 1/4 (187) 4200 (1980) 4200 (1980) 825 345 345 360 (163)

Tube diameter in. (mm) Number of rows Fins per inch (m) Outdoor Coil Fan Diameter in. (mm) Number of blades Motor hp (W) 208/230v 460v Cfm (L/s) 208/230v 460v Rpm Watts 208/230v 460v Shipping Data (1 package) lbs. (kg)

OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA


Low Ambient Kit Mounting Base Net Weight 27J00 27J00 27J00 27J00 27J00 27J00 27J00 (LB57113BM) (LB57113BM) (LB57113BM) (LB57113BM) (LB57113BM) (LB57113BM) (LB57113BM) MB2S (69J06) 6 lbs. (3 kg) MB2S (69J06) 6 lbs. (3 kg) MB2L MB2L MB2L MB2L MB2L (69J07) (69J07) (69J07) (69J07) (69J07) 15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg) 15 lbs. (7 kg) 56A87 (LB29740BA) 31461 (M1595) or 33A09 (BM10260) (Canada Only)

Outdoor Thermostat

Thermostat Kit Control Box

*Refrigerant charge sufficient for 20 ft. (6.1 m) length of refrigerant lines.

ELECTRICAL
General D t Data Model No. Line voltage data 60hz Rec. maximum fuse size (amps) *Minimum circuit ampacity Compressor p Rated load amps Power factor Locked rotor amps Condenser Fan M t F Motor Full load amps Locked rotor amps HP26018 208/230v1ph 15 11.3 8.4 0.96 47 0.8 1.6 HP26024 208/230v1ph 20 13.7 10.3 0.96 56 0.8 2.0 HP26030 208/230v1ph 30 18 13.5 0.96 72.5 1.1 2.0 208/230v1ph 35 21.2 16.1 0.97 88 1.1 2.0 HP26036 208/230v3ph 20 14 10.3 0.82 77 1.1 2.0 460v3ph 10 7.5 5.1 0.82 39 1.1 2.0

*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.

ELECTRICAL
General Data D t Model No. Rec. maximum fuse size (amps) *Minimum circuit ampacity Compressor p Rated load amps Power factor Locked rotor amps Condenser Fan Motor F M t Full load amps Locked rotor amps 40 23.6 18.0 0.97 104 1.1 2.0 HP26042 25 16.8 12.5 0.82 88 1.1 2.0 10 8.3 5.8 0.82 44 1.1 2.0 45 25.7 23.8 .94 129 1.7 3.8 HP26048 30 18.6 13.5 .87 120 1.7 3.8 15 10.4 7.4 .87 49.5 1.1 2.2 60 38 28.9 .94 169 1.7 3.8 HP26060 40 24.5 17.4 .85 123 1.7 3.8 20 12.4 9.0 .85 62 1.1 2.2 Line voltage data 60hz 208/230v1ph 208/230v3ph 460v3ph 208/230v1ph 208/230v3ph 460v3ph 208/230v1ph 208/230v3ph 460v3ph

*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.

HP26 / Page 4 "

ARI RATINGS
Outdoor Unit Model No. Unit Size *Sound Rating Number

LARI Standard 210/240 Ratings Efficiency HSPF IV V Total Total Total High Low High Low Cool. Htg. H Htg. Htg. Cool H Htg. Htg Htg Watts Watts Watts COP COP

Cooling High Temp. Low Temp. Heating Heating Capacity Capacity Capacity

Btuh kW Btuh kW Btuh kW SEER EER

Indoor Unit Model No.

**Check and Expansion Valve Kit Required DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed

Blower 18,600 5.4 17,800 5.2 11,400 3.3 12.00 10.30 7.15 6.35 1805 1695 1555 3.10 2.17 CB29M-21/26 (Multi) Coil Units 18,800 5.5 17,800 5.2 11,400 3.3 12.00 10.30 7.10 6.30 1825 1705 1565 3.08 2.15 CB29M-31 (Multi) 19,600 5.7 18,000 5.3 11,400 3.3 12.50 10.75 7.40 6.50 1820 1640 1525 3.23 2.22 CB30M-21/26 (Multi) 19,600 5.7 18,000 5.3 11,400 3.3 12.50 10.75 7.40 6.50 1820 1640 1525 3.23 2.22 CB30U-21/26 (Up-Flow) 20,000 5.9 18,000 5.3 11,400 3.3 13.00 11.15 7.50 6.55 1795 1595 1485 3.31 2.26 CB30M-31 (Multi) 20,000 5.9 18,000 5.3 11,400 3.3 13.00 11.15 7.50 6.55 1795 1595 1485 3.31 2.26 CB30U-31 (Up-Flow)

18,800 5.5 18,000 5.3 11,800 3.5 12.10 10.35 7.40 6.70 1815 1690 1505 3.12 2.32 CVP10-26/EC10 (Up-Flow) DFactory Installed HP26-018 HP26 018 1.5 Ton (72 db) Up-Flow 18,800 5.5 17,800 5.2 11,400 3.3 12.00 10.35 7.10 6.30 1815 1710 1570 3.07 2.15 C26-21 Coils 19,200 5.6 18,000 5.3 11,400 3.3 12.10 10.55 7.20 6.35 1820 1685 1560 3.14 2.17 C33-24A/B 19,200 5.6 18,000 5.3 11,400 3.3 12.10 10.55 7.20 6.35 1820 1685 1560 3.14 2.17 C26-26 20,000 5.9 18,000 5.3 11,400 3.3 12.60 10.95 7.30 6.40 1830 1650 1540 3.20 2.19 C26-31 Down-Flow 18,600 5.4 17,800 5.2 11,400 3.3 11.70 10.25 7.00 6.20 1815 1750 1595 2.99 2.11 CR26-18N-F Coils 19,800 5.8 17,800 5.2 11,400 3.3 12.50 10.85 7.25 6.35 1825 1670 1545 3.15 2.18 CR26-30N-F Horizontal 18,800 5.5 17,600 5.2 11,200 3.3 11.80 10.35 7.00 6.15 1815 1740 1590 2.98 2.09 CH23-21 Coils 18,600 5.4 17,800 5.2 11,200 3.3 12.00 10.25 7.05 6.20 1815 1710 1575 3.05 2.12 CH23-31 19,400 5.7 17,800 5.2 11,400 3.3 12.20 10.65 7.20 6.30 1825 1665 1560 3.16 2.14 CH33-36A/B/C-F 19,400 5.7 17,800 5.2 11,400 3.3 12.20 10.65 7.20 6.30 1825 1665 1560 3.16 2.14 CH23-41 Blower 22,200 6.5 22,000 6.4 14,400 4.2 11.85 10.20 7.85 6.85 2170 2000 1825 3.32 2.33 CB29M-21/26 (Multi) Coil Units 23,000 6.7 22,600 6.6 14,400 4.2 12.10 10.50 7.80 6.80 2190 2000 1830 3.31 2.32 CB29M-31 (Multi) 23,200 6.8 22,800 6.7 14,600 4.3 12.10 10.50 8.00 6.90 2210 1975 1825 3.38 2.34 CB29M-41 (Multi) 24,000 7.0 22,800 6.7 14,400 4.2 12.70 10.95 8.05 7.00 2190 1940 1795 3.45 2.37 CB30M-21/26 (Multi) 24,000 7.0 22,800 6.7 14,400 4.2 12.70 10.95 8.05 7.00 2190 1940 1795 3.45 2.37 CB30U-21/26 (Up-Flow) 24,400 7.1 22,400 6.6 14,200 4.2 13.40 11.45 8.25 7.10 2125 1840 1710 3.60 2.44 CB30M-31 (Multi) 24,400 7.1 22,400 6.6 14,200 4.2 13.40 11.45 8.25 7.10 2125 1840 1710 3.60 2.44 CB30U-31 (Up-Flow) DFactory Installed 56J19 (LB-85759F) DFactory Installed DFactory Installed 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed

22,800 6.7 22,600 6.6 14,200 4.2 12.05 10.40 7.80 6.80 2195 1980 1825 3.35 2.31 CVP10-26/EC10 (Up-Flow) DFactory Installed HP26-024 HP26 024 2 Ton (72 db) Up-Flow 22,400 6.6 22,600 6.6 14,600 4.3 11.80 10.20 7.80 6.85 2195 2005 1835 3.32 2.33 C26-21 Coils 23,000 6.7 22,800 6.7 14,600 4.3 12.10 10.45 8.00 6.95 2195 1970 1815 3.41 2.36 C33-24A/B 23,000 6.7 22,800 6.7 14,600 4.3 12.10 10.45 8.00 6.95 2195 1970 1815 3.41 2.36 C26-26 24,000 7.0 22,800 6.7 14,400 4.2 12.70 10.90 8.10 7.00 2200 1925 1795 3.48 2.38 C26-31 Down-Flow 22,000 6.4 22,600 6.6 14,400 4.2 11.50 10.05 7.70 6.75 2185 2050 1860 3.23 2.29 CR26-18N-F Coils 23,800 7.0 22,800 6.7 14,400 4.2 12.50 10.80 8.00 6.95 2200 1960 1805 3.42 2.36 CR26-30N-F Horizontal 22,600 6.6 22,200 6.5 14,200 4.2 11.80 10.30 7.60 6.75 2190 2035 1860 3.22 2.26 CH23-21 Coils 22,800 6.7 22,400 6.6 14,400 4.2 12.00 10.40 7.75 6.80 2190 2000 1835 3.30 2.30 CH33-24/30A-F 22,800 6.7 22,400 6.6 14,400 4.2 12.00 10.40 7.75 6.80 2190 2000 1835 3.30 2.30 CH23-31 23,600 6.9 22,600 6.6 14,400 4.2 12.35 10.75 8.00 6.95 2195 1935 1805 3.44 2.35 CH33-36A/B/C-F 23,600 6.9 22,600 6.6 14,400 4.2 12.35 10.75 8.00 6.95 2195 1935 1805 3.44 2.35 CH23-41 DFactory Installed 56J19 (LB-85759F) DFactory Installed DFactory Installed 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F)

*Sound Rating Number in accordance with test conditions included in ARI Standard 270. LCertified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines; Cooling Ratings 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering indoor coil air. High Temperature Heating Ratings 47_F (8_C) db/43_F (6_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. Low Temperature Heating Ratings 17_F (-8.3_C) db/15_F (-9.4_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. DFurnished as standard with coil unit. **Kit is required and must be ordered extra, unless shown as factory installed. NOTE - Use FM21 Control with any listed coil and furnace that meets system design requirements. See FM21 page in Thermostats and Controls section for additional data. Canada Only Most popular blower coil combination.

HP26 / Page 5 "

ARI RATINGS
Outdoor Unit Model No. Unit Size *Sound Rating Number

LARI Standard 210/240 Ratings Efficiency HSPF IV V Total Total Total High Low High Low Cool. Htg. H Htg. Htg. Cool H Htg. Htg Htg Watts Watts Watts COP COP

Cooling High Temp. Low Temp. Heating Heating Capacity Capacity Capacity

Btuh kW Btuh kW Btuh kW SEER EER

Indoor Unit Model No.

Blower 29,400 8.6 31,000 9.1 20,200 5.9 12.50 10.95 8.25 7.30 2690 2695 2420 3.38 2.46 CB29M-41 (Multi) Coil Units 30,200 8.8 30,000 8.8 20,200 5.9 13.05 11.30 8.75 7.85 2675 2650 2200 3.46 2.71 CB30M-21/26 (Multi) 30,200 8.8 30,000 8.8 20,200 5.9 13.05 11.30 8.75 7.85 2675 2650 2200 3.46 2.71 CB30U-21/26 (Up-Flow) 31,000 9.1 31,000 9.1 20,000 5.9 13.70 12.00 8.65 7.60 2585 2510 2285 3.62 2.56 CB30M-31 (Multi) 31,000 9.1 31,000 9.1 20,000 5.9 13.70 12.00 8.65 7.60 2585 2510 2285 3.62 2.56 CB30U-31 (Up-Flow) 31,000 9.1 31,000 9.1 20,000 5.9 13.70 11.90 8.70 7.60 2605 2505 2295 3.65 2.56 CB30M-41 (Multi) 31,000 9.1 31,000 9.1 20,000 5.9 13.70 11.90 8.70 7.60 2605 2505 2295 3.65 2.56 CB30U-41/46 (Up-Flow) 31,000 9.1 31,000 9.1 20,000 5.9 13.70 11.85 8.65 7.55 2615 2510 2300 3.63 2.55 CB30M-46 (Multi) 31,400 9.2 30,600 9.0 19,600 5.7 14.70 12.65 8.85 7.75 2480 2380 2170 3.79 2.65 CB31MV-41 (Multi)

**Check and Expansion Valve Kit Required DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed

29,600 8.7 31,000 9.1 20,200 5.9 12.75 11.05 8.50 7.75 2680 2675 2215 3.41 2.68 CVP10-31/EC10 (Up-Flow) DFactory Installed HP26-030 2.5 Ton ( db) (74 ) 30,000 8.8 30,000 8.8 20,200 5.9 13.05 11.20 8.35 7.35 2685 2630 2395 3.48 2.48 CVP10-41/EC10 (Up-Flow) DFactory Installed 30,000 8.8 30,000 8.8 20,200 5.9 13.05 11.20 8.35 7.35 2685 2630 2395 3.48 2.48 CVP10-46/EC10 (Up-Flow) DFactory Installed Up-Flow 30,600 9.0 30,600 9.0 20,200 5.9 13.05 11.40 8.40 7.40 2685 2630 2390 3.49 2.49 C26-31 p Coils 30,600 9.0 30,600 9.0 20,200 5.9 13.05 11.40 8.50 7.45 2685 2605 2380 3.53 2.50 C33-38A/B 30,600 9.0 30,600 9.0 20,200 5.9 13.05 11.40 8.50 7.45 2685 2605 2380 3.53 2.50 C26-41 30,800 9.0 30,600 9.0 20,000 5.9 13.05 11.45 8.50 7.50 2685 2615 2410 3.50 2.45 C33-48B/C 30,800 9.0 30,600 9.0 20,000 5.9 13.05 11.45 8.50 7.50 2685 2615 2410 3.50 2.45 C26-46 Down-Flow Coils 30,600 9.0 30,600 9.0 20,200 5.9 13.05 11.40 8.35 7.30 2685 2600 2360 3.53 2.53 CR26-36N/W-F Horizontal 30,000 8.8 30,000 8.8 20,000 5.9 12.80 11.20 8.30 7.35 2685 2645 2400 3.45 2.46 CH33-36A-F Coils 30,000 8.8 30,000 8.8 20,000 5.9 12.80 11.20 8.30 7.35 2685 2645 2400 3.45 2.46 CH23-41 30,600 9.0 31,200 9.1 20,200 5.9 13.05 11.40 8.45 7.40 2685 2600 2375 3.52 2.49 CH33-42B-F 30,600 9.0 31,200 9.1 20,200 5.9 13.05 11.40 8.45 7.40 2685 2600 2375 3.52 2.49 CH23-51 30,800 9.0 31,200 9.1 20,200 5.9 13.05 11.45 8.55 7.50 2685 2570 2355 3.58 2.52 CH23-65 Blower 35,000 10.3 35,000 10.3 23,200 6.8 13.20 11.20 8.10 7.25 3120 3030 2695 3.51 2.53 CB30M-31 (Multi) Coil Units 35,000 10.3 35,000 10.3 23,200 6.8 13.20 11.20 8.10 7.25 3120 3030 2695 3.51 2.53 CB30U-31 (Up-Flow) 35,200 10.3 35,000 10.3 23,400 6.9 12.90 10.90 8.20 7.05 3225 3130 2805 3.42 2.46 CB29M-46 (Multi) 35,400 10.4 35,400 10.4 23,800 7.0 12.40 10.65 7.80 7.00 3330 3210 2895 3.37 2.42 CB29M-51 (Multi) 35,600 10.4 35,600 10.4 23,400 6.9 13.20 11.20 8.20 7.30 3175 3005 2705 3.55 2.53 CB30M-41 (Multi) 35,600 10.4 35,600 10.4 23,400 6.9 13.20 11.20 8.20 7.30 3175 3005 2705 3.55 2.53 CB30U-41/46 (Up-Flow) 35,800 10.5 35,800 10.5 23,200 6.8 13.50 11.45 8.25 7.30 3120 2940 2675 3.62 2.56 CB30M-46 (Multi) 36,200 10.6 35,800 10.5 22,800 6.7 14.05 12.00 8.50 7.45 3050 2860 2570 3.69 2.62 CB31MV-41 (Multi) DFactory Installed 56J19 (LB-85759F) DFactory Installed 56J19 (LB-85759F) DFactory Installed 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed

34,000 10.0 34,000 10.0 23,400 6.9 12.40 12.00 7.75 7.00 3210 3160 2820 3.36 2.43 CVP10-31/EC10 (Up-Flow) DFactory Installed 34,600 10.1 36,400 10.7 23,400 6.9 12.65 10.75 8.00 7.00 3215 3105 2790 3.44 2.47 CVP10-41/EC10 (Up-Flow) DFactory Installed HP26-036 3 Ton (74 db) 34,600 10.1 36,400 10.7 23,400 6.9 12.65 10.75 8.00 7.00 3215 3105 2790 3.44 2.47 CVP10-46/EC10 (Up-Flow) DFactory Installed Up-Flow 35,200 10.3 35,200 10.3 23,400 6.9 12.80 10.90 7.85 7.00 3220 3140 2815 3.39 2.44 C26-31 p Coils 35,600 10.4 35,600 10.4 23,400 6.9 12.80 11.05 8.00 7.10 3225 3110 2795 3.43 2.46 C33-38A/B 35,600 10.4 35,600 10.4 23,400 6.9 12.80 11.05 8.00 7.10 3225 3110 2795 3.43 2.46 C26-41 35,800 10.5 35,800 10.5 23,200 6.8 13.05 11.10 7.80 7.00 3225 3130 2815 3.39 2.42 C33-48B/C 35,800 10.5 35,800 10.5 23,200 6.8 13.05 11.10 7.80 7.00 3225 3130 2815 3.39 2.42 C26-46 Down-Flow 34,400 10.1 34,400 10.1 22,800 6.7 12.55 10.65 7.80 6.95 3225 3090 2780 3.37 2.42 CR26-48N/W-F Coils 35,400 10.4 35,400 10.4 23,600 6.9 12.80 10.85 8.00 7.15 3265 3090 2800 3.48 2.48 CR26-36N/W-F Horizontal 34,800 10.2 34,800 10.2 23,200 6.8 12.70 10.80 7.75 6.95 3220 3165 2830 3.35 2.41 CH33-36A-F Coils 34,800 10.2 34,800 10.2 23,200 6.8 12.70 10.80 7.75 6.95 3220 3165 2830 3.35 2.41 CH23-41 35,600 10.4 35,600 10.4 23,200 6.8 13.05 11.05 7.80 7.05 3225 3100 2795 3.43 2.45 CH33-42B-F 35,600 10.4 35,600 10.4 23,200 6.8 13.05 11.05 7.80 7.05 3225 3100 2795 3.43 2.45 CH23-51 36,000 10.5 36,000 10.5 23,400 6.9 13.10 11.15 8.00 7.15 3230 3055 2765 3.50 2.48 CH23-65 DFactory Installed 56J19 (LB-85759F) DFactory Installed 56J19 (LB-85759F) DFactory Installed 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F) 56J19 (LB-85759F)

*Sound Rating Number in accordance with test conditions included in ARI Standard 270. LCertified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines; Cooling Ratings 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering indoor coil air. High Temperature Heating Ratings 47_F (8_C) db/43_F (6_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. Low Temperature Heating Ratings 17_F (-8.3_C) db/15_F (-9.4_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. DFurnished as standard with coil unit. **Kit is required and must be ordered extra, unless shown as factory installed. NOTE - Use FM21 Control with any listed coil and furnace that meets system design requirements. See FM21 page in Thermostats and Controls section for additional data. Canada Only Most popular blower coil combination.

HP26 / Page 6 "

ARI RATINGS
Outdoor Unit Model No. Unit Size *Sound Rating Number

LARI Standard 210/240 Ratings Efficiency HSPF IV V Total Total Total High Low High Low Cool. Htg. H Htg. Htg. Cool H Htg. Htg Htg Watts Watts Watts COP COP

Cooling High Temp. Low Temp. Heating Heating Capacity Capacity Capacity

Btuh kW Btuh kW Btuh kW SEER EER

Indoor Unit Model No.

Blower 40,500 11.9 40,000 11.7 26,400 7.7 12.05 10.25 7.85 7.10 3970 3840 3470 3.09 2.24 CB29M-46 (Multi) Coil Units 40,500 11.9 42,000 12.3 27,800 8.1 12.05 10.40 7.80 7.05 3930 3910 3455 3.17 2.36 CB29M-51 (Multi) 40,500 11.9 40,500 11.9 27,200 8.0 12.70 10.95 8.20 7.35 3735 3645 3240 3.37 2.47 CB30M-41 (Multi) 40,500 11.9 40,500 11.9 27,200 8.0 12.70 10.95 8.20 7.35 3735 3645 3240 3.37 2.47 CB30M-41 (Multi) 40,500 11.9 40,500 11.9 26,800 7.9 12.75 10.95 8.35 7.40 3730 3630 3245 3.33 2.43 CB30M-46 (Multi) 41,000 12.0 41,200 12.1 27,200 8.0 12.40 10.70 7.85 7.05 3855 3830 3375 3.20 2.37 CB29M-65 (Multi) 41,000 12.0 41,000 12.0 26,800 7.9 13.05 11.20 8.20 7.35 3680 3560 3170 3.39 2.49 CB31MV-41 (Multi) 42,000 12.3 41,500 12.2 27,000 7.9 13.05 11.25 8.25 7.30 3725 3575 3230 3.43 2.46 CB30M-51 (Multi) 42,000 12.3 41,500 12.2 27,000 7.9 13.05 11.25 8.25 7.30 3725 3575 3230 3.43 2.46 CB30U-51 (Up-Flow) 40,500 11.9 42,500 12.4 26,400 7.7 13.65 11.75 8.30 7.40 3625 3450 3115 3.48 2.50 CB31MV-51 (Multi) 40,200 11.8 42,500 12.4 27,400 8.0 12.10 10.45 8.00 7.15 3840 3780 3325 3.23 2.42 CVP10-41/EC10Up-Flow) HP26-042 3.5 Ton (74 db) Up-Flow 40,500 11.9 40,200 11.8 27,200 8.0 12.30 10.65 7.85 7.10 3820 3805 3365 3.19 2.38 C33-38A/B p Coils 40,500 11.9 40,200 11.8 27,200 8.0 12.30 10.65 7.85 7.10 3820 3805 3365 3.19 2.38 C26-41 41,000 12.0 41,000 12.0 27,000 7.9 12.40 10.75 7.70 6.95 3825 3830 3415 3.17 2.33 C26-46 41,000 12.0 41,000 12.0 27,000 7.9 12.40 10.75 7.70 6.95 3825 3830 3415 3.17 2.33 C33-48B/C 41,500 12.2 41,000 12.0 27,000 7.9 12.60 10.90 7.80 7.05 3830 3770 3385 3.22 2.35 C33-50/60C 41,500 12.2 41,000 12.0 27,000 7.9 12.60 10.90 7.80 7.05 3830 3770 3385 3.22 2.35 C26-51/65 Down-Flow 40,000 11.7 40,000 11.7 27,400 8.0 12.25 10.45 8.00 7.20 3860 3780 3310 3.24 2.43 CR26-36N/W-F Coils 41,000 12.0 41,000 12.0 27,000 7.9 12.50 10.75 7.75 7.05 3830 3835 3375 3.16 2.36 CR26-48N/W-F 42,000 12.3 41,000 12.0 27,000 7.9 12.80 11.05 8.00 7.20 3840 3700 3295 3.29 2.41 CR26-60N/W-F Horizontal 40,000 11.7 41,000 12.0 27,000 7.9 12.20 10.55 7.70 7.00 3820 3895 3375 3.10 2.36 CH23-41 Coils 41,000 12.0 41,000 12.0 27,200 8.0 12.40 10.75 8.00 7.15 3825 3795 3330 3.20 2.40 CH33-42B-F 41,000 12.0 41,000 12.0 27,200 8.0 12.40 10.75 8.00 7.15 3825 3795 3330 3.20 2.40 CH23-51 41,500 12.2 41,000 12.0 27,200 8.0 12.50 10.85 8.05 7.25 3830 3720 3285 3.29 2.44 CH23-65 Blower 46,000 13.5 46,000 13.5 30,000 8.8 12.40 10.60 7.70 6.90 4370 4310 3785 3.14 2.33 CB30M-46 (Multi) Coil Units 47,000 13.8 46,500 13.6 30,800 9.0 11.80 10.15 7.40 6.65 4635 4600 4080 2.99 2.22 CB29M-51 (Multi) 47,000 13.8 46,000 13.5 30,400 8.9 12.20 10.45 7.45 6.70 4535 4495 3970 3.03 2.24 CB29M-65 (Multi) 47,500 13.9 45,500 13.3 29,600 8.7 13.20 11.10 8.00 7.00 4310 4090 3665 3.27 2.37 CB31MV-51 (Multi) 48,000 14.1 46,000 13.5 30,000 8.8 12.60 10.85 7.75 6.90 4440 4230 3800 3.19 2.32 CB30M-51 (Mult) 48,000 14.1 46,000 13.5 30,000 8.8 12.60 10.85 7.75 6.90 4440 4230 3800 3.19 2.32 CB30U-51 (Up-Flow) 49,000 14.3 45,000 13.2 29,400 8.6 13.20 11.35 7.85 6.95 4325 4095 3670 3.25 2.35 CB31MV-65 (Multi) 49,200 14.4 45,500 13.3 28,800 8.4 12.80 11.15 7.80 6.90 4415 4235 3770 3.16 2.25 CB30M-65 (Multi) 49,200 14.4 45,500 13.3 28,800 8.4 12.80 10.30 7.80 6.90 4415 4235 3770 3.16 2.25 CB30U-65 (Up-Flow) HP26-048 4 Ton (76 db)

**Check and Expansion Valve Kit Required DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed 56J20 (LB-85759G) DFactory Installed DFactory Installed 56J20 (LB-85759G) 56J20 (LB-85759G) DFactory Installed 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed

40,200 11.8 41,600 12.2 27,400 8.0 12.10 10.45 8.00 7.15 3840 3780 3325 3.23 2.42 CVP10-46/EC10 (Up-Flow) DFactory Installed

45,800 13.4 45,000 13.2 30,200 8.8 12.00 10.30 7.50 6.75 4455 4445 3980 3.07 2.23 CVP10-46/EC10 (Up-Flow) DFactory Installed 46,000 13.5 45,500 13.3 30,200 8.8 12.00 10.30 7.50 6.50 4460 4380 3980 3.07 2.23 CVP10-51/EC10 (Up-Flow) DFactory Installed Up-Flow 48,000 14.0 45,500 13.3 30,200 8.8 12.50 10.70 7.50 6.70 4495 4390 3975 3.07 2.23 C33-50/60C p Coils 48,000 14.0 45,500 13.3 30,200 8.8 12.50 10.70 7.50 6.70 4495 4390 3975 3.07 2.23 C26-51/65 49,500 14.5 46,000 13.5 30,000 8.8 12.80 11.00 7.50 6.65 4515 4320 3980 3.13 2.22 C33-62D 49,500 14.5 46,000 13.5 30,000 8.8 12.80 11.00 7.50 6.65 4515 4320 3980 3.13 2.22 C26-65EAP Down-Flow 47,000 13.8 45,500 13.3 30,200 8.8 12.20 10.55 7.35 6.65 4485 4495 4005 2.99 2.22 CR26-48N/W-F Coils 49,000 14.3 46,000 13.5 30,000 8.8 12.60 10.85 7.60 6.80 4510 4315 3890 3.13 2.27 CR26-60N/W-F Horizontal 48,000 14.0 46,000 13.5 30,400 8.9 12.40 10.70 7.60 6.85 4495 4345 3890 3.11 2.29 CH33-44/48B-F Coils 48,000 14.0 46,000 13.5 30,400 8.9 12.40 10.70 7.60 6.85 4495 4345 3890 3.11 2.29 CH23-65 49,000 14.3 46,000 13.5 30,400 8.9 12.70 10.95 7.85 7.00 4515 4195 3795 3.24 2.36 CH33-50/60C-F 49,000 14.3 46,000 13.5 30,400 8.9 12.70 10.95 7.85 7.00 4515 4195 3795 3.24 2.36 CH23-68 56J20 (LB-85759G) DFactory Installed 56J20 (LB-85759G) DFactory Installed 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G)

*Sound Rating Number in accordance with test conditions included in ARI Standard 270. LCertified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines; Cooling Ratings 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering indoor coil air. High Temperature Heating Ratings 47_F (8_C) db/43_F (6_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. Low Temperature Heating Ratings 17_F (-8.3_C) db/15_F (-9.4_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. DFurnished as standard with coil unit. **Kit is required and must be ordered extra, unless shown as factory installed. NOTE - Use FM21 Control with any listed coil and furnace that meets system design requirements. See FM21 page in Thermostats and Controls section for additional data. Canada Only Most popular blower coil combination.

HP26 / Page 7 "

ARI RATINGS
Outdoor Unit Model No. Unit Size *Sound Rating Number

LARI Standard 210/240 Ratings Efficiency HSPF IV V Total Total Total High Low High Low Cool. Htg. H Htg. Htg. Cool H Htg. Htg Htg Watts Watts Watts COP COP

Cooling High Temp. Low Temp. Heating Heating Capacity Capacity Capacity

Btuh kW Btuh kW Btuh kW SEER EER

Indoor Unit Model No.

Blower 55,000 16.1 53,500 15.7 35,200 10.3 12.30 10.10 7.45 6.65 5446 5058 4390 3.10 2.35 CB31MV-51 (Multi) Coil Units 56,000 16.4 53,000 15.5 35,200 10.3 12.00 10.00 7.50 6.70 5600 5178 4485 3.00 2.30 CB30M-51 (Multi) 56,000 16.4 53,000 15.5 35,200 10.3 12.00 10.00 7.50 6.70 5600 5178 4485 3.00 2.30 CB30U-51 (Up-Flow) 56,500 16.5 53,500 15.7 35,400 10.4 12.50 10.50 7.45 6.65 5381 5058 4359 3.10 2.38 CB31MV-65 (Multi) 57,500 16.8 54,000 15.8 35,400 10.4 12.00 10.20 7.35 6.55 5637 5275 4511 3.00 2.30 CB30M-65 (Multi) HP26-060 5 Ton (80 db) ( ) 57,500 16.8 54,000 15.8 35,400 10.4 12.00 10.20 7.35 6.55 5637 5275 4511 3.00 2.30 CB30U-65 (Up-Flow) 55,000 16.1 54,000 15.8 35,800 10.5 11.30 9.60 7.35 57,000 16.7 54,500 16.0 35,800 10.5 11.75 10.00 7.35 Up-Flow 59,000 17.3 54,500 16.0 35,800 10.5 12.10 10.30 7.45 p Coils 59,000 17.3 54,500 16.0 35,800 10.5 12.10 10.30 7.45 6.5 6.5 6.6 6.6 5729 5105 4465 3.10 2.35 CVP10-51/EC10(Up-Flow) 5728 5324 4602 3.00 2.28 C33-62D 5728 5324 4602 3.00 2.28 C26-65EAP

**Check and Expansion Valve Kit Required DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed DFactory Installed 56J20 (LB-85759G) DFactory Installed 56J20 (LB-85759G) 56J20 (LB-85759G) 56J20 (LB-85759G)

5700 4992 4409 3.20 2.38 CVP10-65/EC10 (Up-Flow) DFactory Installed

Down-Flow Coils 57,000 16.7 53,500 15.7 35,800 10.5 11.50 9.90 7.35 6.55 5758 5058 4562 3.10 2.30 CR26-60N/W-F Horizontal 59,000 17.3 55,000 16.1 35,800 10.5 12.10 10.30 7.65 6.75 5728 4945 4390 3.26 2.39 CH33-62D-F Coils 59,000 17.3 55,000 16.1 35,800 10.5 12.10 10.30 7.65 6.75 5728 4945 4390 3.26 2.39 CH23-68

*Sound Rating Number in accordance with test conditions included in ARI Standard 270. LCertified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines; Cooling Ratings 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering indoor coil air. High Temperature Heating Ratings 47_F (8_C) db/43_F (6_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. Low Temperature Heating Ratings 17_F (-8.3_C) db/15_F (-9.4_C) wb outdoor air temperature and 70_F (21_C) db entering indoor coil air. DFurnished as standard with coil unit. **Kit is required and must be ordered extra, unless shown as factory installed. NOTE - Use FM21 Control with any listed coil and furnace that meets system design requirements. See FM21 page in Thermostats and Controls section for additional data. Canada Only Most popular blower coil combination.

DIMENSIONS - INCHES (MM)


INLET Model No. HP26 018 in. HP26 024 mm HP26 030 in. HP26 036 mm HP26 042 in. mm A B C D E F G H J 27 7/8 25 7/8 29 7/8 12 1/4 22 7/16 14 7/16 22-1/4 1-13/16 6-7/16 708 784 886 1140 657 816 816 816 759 865 865 865 311 324 349 362 570 676 676 676 367 473 473 473
565 702 702 702 46 2-1/4 57 2-1/4 57 2-1/4 57 164 9-1/8 232 9-1/8 232 9-1/8 232

AIR

30 7/8 32 1/8 34 1/16 12 3/4 26 5/8 18 5/8 27-5/8 34 7/8 32 1/8 34 1/16 13 3/4 26 5/8 18 5/8 27-5/8 44 7/8 32 1/8 34 1/16 14 1/4 26 5/8 18 5/8 27-5/8

INLET COMPRESSOR AIR

HP26 048 in. HP26 060 mm

INLET

AIR

ELECTRICAL INLETS VAPOR LINE INLET

TOP VIEW
C
DISCHARGE AIR

4 1/2 (114) LIQUID LINE INLET

2 9/16 (65)

3 1/8 (79)

3 1/8 (79)

3 1/8 (79)

2 3/4 (70) 1 3/8 (35)

H
HP26 / Page 8 "

ACCESS VIEW

4 (102)

F E

4 (102)

SIDE VIEW

6 1/16 (154)

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CB29M-21/26 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .68 1.25 .75 1.26 .83 1.25 .54 1.27 .58 1.27 .63 1.26 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .98 .65 .72 .81 .52 .57 .62

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 16.7 4.9 1.42 .68 1.00 18.2 5.3 1.43 .76 1.00 19.2 5.6 1.44 .85 .75 18.0 5.3 1.43 .54 .87 19.4 5.7 1.44 .59 .96 20.1 5.9 1.45 .64 .62 19.3 5.7 1.44 .42 .70 20.7 6.1 1.46 .43 .78 21.4 6.3 1.46 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .99 .65 .73 .82 .52 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.62 .69 1.63 .78 1.64 .86 1.63 .55 1.65 .60 1.65 .65 1.65 .42 1.66 .44 1.66 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .83 .95 1.86 .79 .95 1.00 1.86 .88 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .76 .92 1.87 .66 .86 1.00 1.87 .42 .53 .64 1.88 .44 .59 .74 1.88 .46 .65 .84

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.3 18.8 19.8 18.6 20.1 20.8 20.0 21.4 22.2 5.1 5.5 5.8 5.5 5.9 6.1 5.9 6.3 6.5

85_F kBtuh kW 29_C .91 16.1 4.7 1.00 17.5 5.1 1.00 18.5 5.4 .76 17.3 5.1 .88 18.6 5.5 .98 19.3 5.7 .63 18.6 5.5 .71 19.9 5.8 .80 20.6 6.0

85_F kBtuh kW 29_C .93 15.5 4.5 1.00 16.7 4.9 1.00 17.8 5.2 .77 16.6 4.9 .90 17.8 5.2 .99 18.4 5.4 .63 17.9 5.2 .72 19.0 5.6 .82 19.6 5.7

HP26-018
Entering Wet Bulb Tempera ture

CB29M-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.26 .68 1.27 .75 1.28 .83 1.27 .54 1.28 .58 1.29 .63 1.28 .42 1.29 .43 1.30 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .65 .72 .81 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.1 5.0 1.44 .68 1.00 18.4 5.4 1.45 .77 1.00 19.4 5.7 1.46 .84 .76 18.3 5.4 1.45 .55 .86 19.6 5.7 1.46 .59 .96 20.3 5.9 1.47 .64 .62 19.6 5.7 1.46 .42 .70 20.9 6.1 1.47 .44 .79 21.6 6.3 1.48 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .99 .66 .74 .82 .53 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.64 .69 1.65 .78 1.66 .86 1.65 .55 1.67 .60 1.67 .65 1.66 .42 1.68 .44 1.68 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 .99 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.87 .70 .83 .94 1.88 .79 .95 1.00 1.89 .88 1.00 1.00 1.88 .55 .67 .79 1.89 .60 .77 .92 1.90 .66 .86 .99 1.89 .42 .53 .64 1.90 .44 .59 .74 1.91 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.6 19.1 20.0 18.9 20.3 21.1 20.3 21.7 22.4 5.2 5.6 5.9 5.5 5.9 6.2 5.9 6.4 6.6

85_F kBtuh kW 29_C .91 16.5 4.8 1.00 17.8 5.2 1.00 18.8 5.5 .77 17.7 5.2 .88 18.9 5.5 .97 19.6 5.7 .63 19.0 5.6 .71 20.2 5.9 .80 20.8 6.1

85_F kBtuh kW 29_C .93 15.8 4.6 1.00 17.0 5.0 1.00 18.1 5.3 .77 17.0 5.0 .89 18.1 5.3 .98 18.7 5.5 .63 18.2 5.3 .72 19.3 5.7 .81 19.9 5.8

HP26-018 - CB29-21/26 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.58 1.37 1.27 45_F (7_C) Total Heating Capacity kBtuh 16.3 17.0 17.5 kW 4.8 5.0 5.1 Comp. Motor kW Input 1.50 1.29 1.19 25_F (-4_C) Total Heating Capacity kBtuh 11.5 12.2 12.7 kW 3.4 3.6 3.7 Comp. Motor kW Input 1.41 1.20 1.10 5_F (-15_C) Total Heating Capacity kBtuh 8.2 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.30 1.09 .99 -15_F (-26_C) Total Heating Capacity kBtuh 3.8 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input 1.00 .79 .69

HP26-018 - CB29-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.8 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.56 1.35 1.25 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.0 17.5 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.48 1.27 1.17 25_F (-4_C) Total Heating Capacity kBtuh 11.4 12.2 12.7 kW 3.3 3.6 3.7 Comp. Motor kW Input 1.40 1.19 1.09 5_F (-15_C) Total Heating Capacity kBtuh 8.1 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.28 1.07 .97 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .99 .78 .68

HP26-018 - CB29-21/26 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.37 1.35 1.33 1.32 1.30 1.29 1.26 1.23 1.22 1.20 1.19 1.19 1.18 1.16 1.09 1.01 .94 .86 .79 .71 Total Output kBtuh 21.6 20.5 19.5 18.4 17.8 17.0 15.1 13.1 12.7 12.2 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.3 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26-018 - CB29-31 - HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.35 1.33 1.32 1.30 1.28 1.27 1.24 1.21 1.20 1.19 1.18 1.17 1.16 1.14 1.07 1.00 .92 .85 .78 .70 Total Output kBtuh 21.6 20.5 19.5 18.4 17.8 17.0 15.1 13.1 12.7 12.2 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.3 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26 / Page 9 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CB30M-21/26 - CB30U-21/26 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.25 .67 1.27 .75 1.27 .83 1.26 .54 1.28 .58 1.28 .63 1.28 .42 1.29 .43 1.30 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .65 .72 .80 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.7 5.2 1.43 .68 1.00 19.2 5.6 1.45 .76 1.00 20.2 5.9 1.45 .85 .75 19.0 5.6 1.44 .54 .86 20.4 6.0 1.46 .59 .96 21.2 6.2 1.46 .64 .62 20.4 6.0 1.46 .42 .70 21.8 6.4 1.47 .44 .78 22.6 6.6 1.48 .45

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.64 .69 1.65 .78 1.66 .86 1.65 .55 1.66 .60 1.67 .65 1.66 .42 1.67 .44 1.68 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.86 .70 .83 .95 1.87 .79 .95 1.00 1.88 .88 1.00 1.00 1.87 .55 .67 .78 1.88 .61 .77 .92 1.89 .66 .86 1.00 1.88 .42 .53 .64 1.90 .44 .59 .74 1.90 .46 .65 .84 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 1.00 .65 .74 .82 .52 .57 .63

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.3 19.8 20.9 19.6 21.2 22.0 21.1 22.6 23.4 5.4 5.8 6.1 5.7 6.2 6.4 6.2 6.6 6.9

85_F kBtuh kW 29_C .91 17.0 5.0 1.00 18.4 5.4 1.00 19.5 5.7 .76 18.3 5.4 .88 19.6 5.7 .98 20.4 6.0 .62 19.7 5.8 .71 21.0 6.2 .80 21.7 6.4

85_F kBtuh kW 29_C .92 16.3 4.8 1.00 17.6 5.2 1.00 18.8 5.5 .78 17.5 5.1 .90 18.8 5.5 1.00 19.5 5.7 .63 18.9 5.5 .72 20.1 5.9 .82 20.7 6.1

HP26-018
Entering Wet Bulb Tempera ture

CB30M-31 - CB30U-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .67 1.26 .75 1.27 .83 1.25 .54 1.27 .58 1.28 .63 1.27 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .78 .90 .99 .64 .72 .81 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.9 5.2 1.42 .68 1.00 19.4 5.7 1.44 .76 1.00 20.5 6.0 1.45 .84 .75 19.2 5.6 1.43 .54 .86 20.7 6.1 1.45 .59 .96 21.6 6.3 1.46 .64 .62 20.7 6.1 1.45 .42 .70 22.2 6.5 1.46 .43 .78 23.0 6.7 1.47 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .91 1.00 .65 .73 .82 .52 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.62 .69 1.64 .77 1.64 .87 1.63 .55 1.65 .60 1.65 .65 1.65 .42 1.66 .44 1.67 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .82 .94 1.86 .79 .95 1.00 1.87 .88 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .77 .92 1.88 .66 .86 1.00 1.87 .42 .53 .64 1.88 .44 .59 .74 1.89 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.5 20.1 21.2 19.9 21.5 22.4 21.4 23.0 23.9 5.4 5.9 6.2 5.8 6.3 6.6 6.3 6.7 7.0

85_F kBtuh kW 29_C .91 17.2 5.0 1.00 18.7 5.5 1.00 19.8 5.8 .76 18.5 5.4 .88 19.9 5.8 .98 20.7 6.1 .62 19.9 5.8 .71 21.3 6.2 .80 22.1 6.5

85_F kBtuh kW 29_C .92 16.5 4.8 1.00 17.9 5.2 1.00 19.1 5.6 .77 17.8 5.2 .90 19.0 5.6 1.00 19.8 5.8 .63 19.1 5.6 .72 20.4 6.0 .82 21.1 6.2

HP26-018 - CB30M-21/26 - CB30U-21/26 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 21.2 21.9 22.4 kW 6.2 6.4 6.6 Comp. Motor kW Input 1.55 1.34 1.25 45_F (7_C) Total Heating Capacity kBtuh 16.5 17.2 17.7 kW 4.8 5.0 5.2 Comp. Motor kW Input 1.47 1.26 1.16 25_F (-4_C) Total Heating Capacity kBtuh 11.6 12.3 12.8 kW 3.4 3.6 3.8 Comp. Motor kW Input 1.38 1.17 1.08 5_F (-15_C) Total Heating Capacity kBtuh 8.2 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.27 1.06 .96 -15_F (-26_C) Total Heating Capacity kBtuh 3.8 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .98 .77 .67

HP26-018 - CB30M-31 - CB30U-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 21.2 22.0 22.5 kW 6.2 6.4 6.6 Comp. Motor kW Input 1.51 1.31 1.21 45_F (7_C) Total Heating Capacity kBtuh 16.4 17.2 17.7 kW 4.8 5.0 5.2 Comp. Motor kW Input 1.43 1.23 1.13 25_F (-4_C) Total Heating Capacity kBtuh 11.4 12.2 12.7 kW 3.3 3.6 3.7 Comp. Motor kW Input 1.34 1.14 1.05 5_F (-15_C) Total Heating Capacity kBtuh 8.0 8.8 9.3 kW 2.3 2.6 2.7 Comp. Motor kW Input 1.23 1.03 .94 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .95 .75 .65

HP26-018 - CB30M-21/26 - CB30U-21/26 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.34 1.32 1.30 1.28 1.27 1.26 1.23 1.19 1.18 1.17 1.16 1.16 1.15 1.13 1.06 .98 .91 .84 .77 .69 Total Output kBtuh 21.9 20.8 19.7 18.7 18.0 17.2 15.2 13.2 12.8 12.3 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.4 6.1 5.8 5.5 5.3 5.0 4.5 3.9 3.8 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26-018 - CB30M-31 - CB30U-31 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.31 1.29 1.27 1.25 1.24 1.23 1.20 1.17 1.16 1.14 1.13 1.13 1.12 1.10 1.03 .96 .89 .82 .75 .68 Total Output kBtuh 22.0 20.9 19.8 18.7 18.0 17.2 15.2 13.2 12.7 12.2 11.7 11.4 11.0 9.9 8.8 7.7 6.6 5.6 4.5 3.4 kW 6.4 6.1 5.8 5.5 5.3 5.0 4.5 3.9 3.7 3.6 3.4 3.3 3.2 2.9 2.6 2.3 1.9 1.6 1.3 1.0

HP26 / Page 10 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CVP10-26/EC10Q3 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .67 1.25 .75 1.26 .83 1.25 .54 1.26 .58 1.27 .63 1.26 .42 1.27 .43 1.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .89 .99 .64 .72 .81 .52 .56 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .89 16.9 5.0 1.41 .68 1.00 18.4 5.4 1.43 .76 1.00 19.4 5.7 1.43 .84 .75 18.2 5.3 1.42 .54 .86 19.6 5.7 1.44 .59 .96 20.3 5.9 1.44 .64 .61 19.5 5.7 1.44 .42 .70 20.9 6.1 1.45 .44 .78 21.7 6.4 1.46 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .99 .65 .73 .82 .52 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.61 .69 1.63 .77 1.63 .86 1.62 .55 1.64 .60 1.64 .65 1.63 .42 1.65 .44 1.65 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.84 .70 .83 .94 1.85 .79 .95 1.00 1.86 .87 1.00 1.00 1.85 .55 .67 .79 1.86 .61 .77 .92 1.86 .66 .86 1.00 1.86 .42 .53 .64 1.87 .44 .59 .74 1.88 .46 .65 .84

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.5 19.0 20.0 18.8 20.3 21.1 20.2 21.7 22.5 5.1 5.6 5.9 5.5 5.9 6.2 5.9 6.4 6.6

85_F kBtuh kW 29_C .91 16.3 4.8 1.00 17.7 5.2 1.00 18.7 5.5 .76 17.5 5.1 .87 18.8 5.5 .98 19.5 5.7 .63 18.8 5.5 .71 20.1 5.9 .80 20.8 6.1

85_F kBtuh kW 29_C .93 15.6 4.6 1.00 16.9 5.0 1.00 18.0 5.3 .78 16.8 4.9 .89 18.0 5.3 .98 18.7 5.5 .63 18.1 5.3 .73 19.3 5.7 .81 19.9 5.8

HP26-018
Entering Wet Bulb Temperat ure

C26-21 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.25 .68 1.26 .76 1.27 .83 1.26 .54 1.27 .58 1.27 .63 1.27 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .90 .98 .65 .73 .81 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.0 5.0 1.43 .69 1.00 18.4 5.4 1.44 .77 1.00 19.3 5.7 1.45 .85 .76 18.3 5.4 1.44 .55 .87 19.5 5.7 1.45 .59 .96 20.2 5.9 1.45 .64 .62 19.6 5.7 1.45 .42 .71 20.8 6.1 1.46 .43 .79 21.5 6.3 1.47 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .91 .99 .66 .74 .83 .53 .58 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.63 .70 1.64 .78 1.65 .86 1.64 .55 1.65 .60 1.66 .65 1.65 .42 1.66 .44 1.67 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .82 .93 1.00 .66 .76 .85 .53 .59 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.86 .71 .83 .95 1.87 .80 .95 1.00 1.87 .89 1.00 1.00 1.87 .56 .67 .80 1.88 .61 .77 .92 1.88 .66 .87 1.00 1.88 .43 .54 .65 1.89 .44 .59 .75 1.89 .46 .66 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.6 19.0 20.0 18.8 20.2 20.9 20.2 21.5 22.2 5.2 5.6 5.9 5.5 5.9 6.1 5.9 6.3 6.5

85_F kBtuh kW 29_C .92 16.4 4.8 1.00 17.7 5.2 1.00 18.7 5.5 .77 17.6 5.2 .89 18.8 5.5 .97 19.4 5.7 .63 18.9 5.5 .72 20.0 5.9 .80 20.7 6.1

85_F kBtuh kW 29_C .93 15.8 4.6 1.00 17.0 5.0 1.00 18.0 5.3 .78 16.9 5.0 .90 18.0 5.3 .99 18.6 5.5 .64 18.1 5.3 .74 19.2 5.6 .82 19.8 5.8

HP26-018 - CVP10-26/EC10Q3 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.7 21.7 21.9 kW 6.1 6.4 6.4 Comp. Motor kW Input 1.60 1.42 1.30 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.2 17.4 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.48 1.30 1.18 25_F (-4_C) Total Heating Capacity kBtuh 11.6 12.6 12.8 kW 3.4 3.7 3.8 Comp. Motor kW Input 1.34 1.16 1.04 5_F (-15_C) Total Heating Capacity kBtuh 8.3 9.3 9.5 kW 2.4 2.7 2.8 Comp. Motor kW Input 1.20 1.02 .90 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.7 4.9 kW 1.1 1.4 1.4 Comp. Motor kW Input .93 .75 .63

HP26-018 - C26-21 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.8 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.57 1.36 1.26 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.0 17.5 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.49 1.28 1.18 25_F (-4_C) Total Heating Capacity kBtuh 11.4 12.2 12.7 kW 3.3 3.6 3.7 Comp. Motor kW Input 1.41 1.20 1.10 5_F (-15_C) Total Heating Capacity kBtuh 8.1 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.29 1.08 .98 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .99 .78 .68

HP26-018 - CVP10-26/EC10Q3 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.42 1.39 1.36 1.33 1.31 1.30 1.25 1.21 1.19 1.16 1.14 1.13 1.12 1.09 1.02 .95 .88 .81 .75 .68 Total Output kBtuh 21.7 20.6 19.6 18.6 18.0 17.2 15.3 13.4 13.0 12.6 12.1 11.9 11.5 10.5 9.3 8.2 7.0 5.9 4.7 3.6 kW 6.4 6.0 5.7 5.5 5.3 5.0 4.5 3.9 3.8 3.7 3.5 3.5 3.4 3.1 2.7 2.4 2.1 1.7 1.4 1.1

HP26-018 - C26-21 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.36 1.34 1.33 1.31 1.29 1.28 1.25 1.22 1.21 1.20 1.19 1.18 1.17 1.15 1.08 1.00 .93 .86 .78 .71 Total Output kBtuh 21.6 20.5 19.5 18.4 17.8 17.0 15.1 13.1 12.7 12.2 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.3 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26 / Page 11 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

C26-26 - C33-24A/B COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.25 .67 1.26 .75 1.27 .83 1.25 .54 1.27 .59 1.27 .63 1.27 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .65 .73 .81 .52 .57 .62 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.5 5.1 1.42 .68 1.00 18.9 5.5 1.43 .77 1.00 20.0 5.9 1.44 .85 .75 18.8 5.5 1.43 .54 .87 20.1 5.9 1.45 .59 .96 20.9 6.1 1.45 .64 .62 20.2 5.9 1.45 .42 .70 21.5 6.3 1.46 .43 .79 22.2 6.5 1.47 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .92 1.00 .65 .74 .82 .52 .58 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.63 .70 1.64 .78 1.65 .86 1.64 .55 1.65 .60 1.66 .66 1.65 .42 1.66 .43 1.67 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .83 .94 1.86 .79 .95 1.00 1.87 .89 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .77 .92 1.88 .66 .86 1.00 1.87 .42 .54 .65 1.88 .44 .60 .75 1.89 .47 .66 .84

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.1 19.6 20.6 19.4 20.8 21.6 20.8 22.3 23.0 5.3 5.7 6.0 5.7 6.1 6.3 6.1 6.5 6.7

85_F kBtuh kW 29_C .91 16.9 5.0 1.00 18.2 5.3 1.00 19.3 5.7 .77 18.1 5.3 .89 19.4 5.7 .98 20.1 5.9 .63 19.4 5.7 .72 20.7 6.1 .80 21.4 6.3

85_F kBtuh kW 29_C .92 16.2 4.7 1.00 17.5 5.1 1.00 18.6 5.5 .78 17.4 5.1 .90 18.5 5.4 .99 19.2 5.6 .63 18.6 5.5 .73 19.8 5.8 .82 20.4 6.0

HP26-018
Entering Wet Bulb Tempera ture

C26-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.26 .67 1.27 .75 1.28 .83 1.27 .54 1.28 .58 1.29 .63 1.28 .42 1.30 .43 1.30 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .65 .72 .81 .52 .56 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 18.1 5.3 1.44 .68 1.00 19.6 5.7 1.45 .76 1.00 20.7 6.1 1.46 .85 .75 19.4 5.7 1.45 .54 .86 20.9 6.1 1.46 .59 .96 21.7 6.4 1.47 .64 .62 20.9 6.1 1.46 .42 .70 22.4 6.6 1.48 .43 .78 23.2 6.8 1.48 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 1.00 .65 .74 .82 .52 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.64 .69 1.66 .78 1.66 .86 1.65 .55 1.67 .60 1.67 .65 1.67 .42 1.68 .44 1.69 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.87 .69 .82 .94 1.88 .79 .95 1.00 1.89 .89 1.00 1.00 1.88 .55 .67 .78 1.89 .60 .77 .92 1.90 .66 .86 1.00 1.89 .42 .53 .64 1.90 .44 .59 .74 1.91 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.7 20.3 21.4 20.1 21.7 22.6 21.6 23.2 24.1 5.5 5.9 6.3 5.9 6.4 6.6 6.3 6.8 7.1

85_F kBtuh kW 29_C .91 17.4 5.1 1.00 18.9 5.5 1.00 20.0 5.9 .76 18.7 5.5 .88 20.1 5.9 .98 20.9 6.1 .62 20.1 5.9 .71 21.5 6.3 .80 22.3 6.5

85_F kBtuh kW 29_C .93 16.7 4.9 1.00 18.1 5.3 1.00 19.2 5.6 .78 17.9 5.2 .90 19.2 5.6 .99 20.0 5.9 .63 19.3 5.7 .73 20.6 6.0 .82 21.3 6.2

HP26-018 - C26-26 - C33-24A/B HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 21.2 21.9 22.4 kW 6.2 6.4 6.6 Comp. Motor kW Input 1.60 1.39 1.30 45_F (7_C) Total Heating Capacity kBtuh 16.5 17.2 17.7 kW 4.8 5.0 5.2 Comp. Motor kW Input 1.50 1.30 1.20 25_F (-4_C) Total Heating Capacity kBtuh 11.6 12.3 12.8 kW 3.4 3.6 3.8 Comp. Motor kW Input 1.41 1.20 1.11 5_F (-15_C) Total Heating Capacity kBtuh 8.2 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.28 1.08 .98 -15_F (-26_C) Total Heating Capacity kBtuh 3.8 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .99 .78 .69

HP26-018 - C26-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 21.1 21.9 22.4 kW 6.2 6.4 6.6 Comp. Motor kW Input 1.51 1.31 1.21 45_F (7_C) Total Heating Capacity kBtuh 16.4 17.2 17.7 kW 4.8 5.0 5.2 Comp. Motor kW Input 1.45 1.25 1.15 25_F (-4_C) Total Heating Capacity kBtuh 11.5 12.3 12.8 kW 3.4 3.6 3.8 Comp. Motor kW Input 1.39 1.19 1.09 5_F (-15_C) Total Heating Capacity kBtuh 8.1 8.9 9.4 kW 2.4 2.6 2.8 Comp. Motor kW Input 1.29 1.09 .99 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .99 .78 .69

HP26-018 - C26-26 - C33-A/B HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.39 1.37 1.35 1.33 1.31 1.30 1.26 1.23 1.21 1.20 1.19 1.18 1.17 1.15 1.08 1.00 .93 .86 .78 .71 Total Output kBtuh 21.9 20.8 19.7 18.7 18.0 17.2 15.2 13.2 12.8 12.3 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.4 6.1 5.8 5.5 5.3 5.0 4.5 3.9 3.8 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26-018 - C26-31 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.31 1.30 1.28 1.27 1.26 1.25 1.22 1.20 1.19 1.19 1.18 1.18 1.17 1.16 1.09 1.01 .93 .86 .78 .71 Total Output kBtuh 21.9 20.8 19.7 18.7 18.0 17.2 15.2 13.2 12.8 12.3 11.8 11.5 11.1 10.0 8.9 7.8 6.7 5.6 4.5 3.5 kW 6.4 6.1 5.8 5.5 5.3 5.0 4.5 3.9 3.8 3.6 3.5 3.4 3.3 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26 / Page 12 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CR26-18N-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.23 .67 1.24 .74 1.25 .81 1.24 .54 1.25 .58 1.26 .62 1.25 .42 1.26 .43 1.27 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .89 .97 .65 .72 .79 .52 .56 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 16.7 4.9 1.41 .68 .99 18.0 5.3 1.42 .75 1.00 18.9 5.5 1.43 .83 .75 18.0 5.3 1.42 .54 .85 19.2 5.6 1.43 .58 .94 19.9 5.8 1.44 .63 .62 19.2 5.6 1.43 .42 .69 20.5 6.0 1.44 .43 .77 21.2 6.2 1.45 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .98 .65 .73 .80 .53 .57 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.61 .69 1.62 .76 1.63 .84 1.62 .55 1.63 .59 1.64 .64 1.63 .42 1.64 .43 1.65 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .91 .99 .66 .74 .82 .53 .58 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.84 .70 .83 .94 1.85 .78 .93 1.00 1.85 .87 1.00 1.00 1.84 .55 .67 .79 1.85 .60 .76 .90 1.86 .65 .84 .98 1.85 .42 .53 .65 1.86 .44 .59 .74 1.87 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.3 18.6 19.5 18.5 19.9 20.6 19.9 21.2 21.9 5.1 5.5 5.7 5.4 5.8 6.0 5.8 6.2 6.4

85_F kBtuh kW 29_C .91 16.1 4.7 1.00 17.4 5.1 1.00 18.3 5.4 .77 17.3 5.1 .87 18.5 5.4 .96 19.1 5.6 .63 18.6 5.5 .70 19.8 5.8 .78 20.4 6.0

85_F kBtuh kW 29_C .93 15.5 4.5 1.00 16.7 4.9 1.00 17.6 5.2 .77 16.6 4.9 .88 17.7 5.2 .97 18.3 5.4 .63 17.8 5.2 .72 18.9 5.5 .80 19.5 5.7

HP26-018
Entering Wet Bulb Tempera ture

CR26-30N-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.25 .68 1.26 .75 1.27 .83 1.26 .54 1.27 .58 1.28 .63 1.27 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .98 .64 .72 .80 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.7 5.2 1.42 .68 1.00 19.2 5.6 1.44 .76 1.00 20.2 5.9 1.44 .84 .75 19.0 5.6 1.43 .54 .86 20.4 6.0 1.45 .59 .96 21.2 6.2 1.46 .64 .62 20.4 6.0 1.45 .42 .70 21.8 6.4 1.46 .43 .78 22.6 6.6 1.47 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 1.00 .65 .74 .82 .52 .57 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.63 .69 1.64 .78 1.65 .86 1.64 .55 1.65 .60 1.65 .65 1.65 .42 1.66 .44 1.67 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .92 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .82 .94 1.86 .79 .95 1.00 1.87 .88 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .77 .92 1.88 .66 .86 1.00 1.87 .42 .53 .64 1.88 .44 .59 .74 1.89 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.3 19.8 20.9 19.7 21.2 22.0 21.1 22.6 23.4 5.4 5.8 6.1 5.8 6.2 6.4 6.2 6.6 6.9

85_F kBtuh kW 29_C .91 17.1 5.0 1.00 18.5 5.4 1.00 19.5 5.7 .76 18.3 5.4 .88 19.6 5.7 .97 20.4 6.0 .63 19.7 5.8 .71 21.0 6.2 .80 21.7 6.4

85_F kBtuh kW 29_C .93 16.4 4.8 1.00 17.7 5.2 1.00 18.8 5.5 .78 17.6 5.2 .89 18.8 5.5 .99 19.5 5.7 .63 18.9 5.5 .72 20.1 5.9 .82 20.7 6.1

HP26-018 - CR26-18N-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 21.0 22.0 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.66 1.44 1.33 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.2 17.5 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.56 1.34 1.23 25_F (-4_C) Total Heating Capacity kBtuh 11.2 12.2 12.5 kW 3.3 3.6 3.7 Comp. Motor kW Input 1.45 1.23 1.12 5_F (-15_C) Total Heating Capacity kBtuh 7.8 8.8 9.1 kW 2.3 2.6 2.7 Comp. Motor kW Input 1.32 1.10 .99 -15_F (-26_C) Total Heating Capacity kBtuh 3.5 4.5 4.8 kW 1.0 1.3 1.4 Comp. Motor kW Input 1.02 .80 .69

HP26-018 - CR26-30N-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.53 1.33 1.23 45_F (7_C) Total Heating Capacity kBtuh 16.3 17.0 17.5 kW 4.8 5.0 5.1 Comp. Motor kW Input 1.46 1.26 1.16 25_F (-4_C) Total Heating Capacity kBtuh 11.5 12.2 12.7 kW 3.4 3.6 3.7 Comp. Motor kW Input 1.38 1.18 1.08 5_F (-15_C) Total Heating Capacity kBtuh 8.1 8.8 9.3 kW 2.4 2.6 2.7 Comp. Motor kW Input 1.27 1.07 .97 -15_F (-26_C) Total Heating Capacity kBtuh 3.8 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .98 .77 .68

HP26-018 - CR26-18N-F HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.44 1.41 1.39 1.37 1.35 1.34 1.30 1.26 1.24 1.23 1.21 1.20 1.19 1.17 1.10 1.02 .95 .87 .80 .72 Total Output kBtuh 22.0 20.9 19.8 18.7 18.0 17.2 15.1 13.1 12.6 12.2 11.7 11.4 11.0 9.9 8.8 7.7 6.6 5.6 4.5 3.4 kW 6.4 6.1 5.8 5.5 5.3 5.0 4.4 3.8 3.7 3.6 3.4 3.3 3.2 2.9 2.6 2.3 1.9 1.6 1.3 1.0

HP26-018 - CR26-30N-F HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.33 1.31 1.30 1.28 1.27 1.26 1.23 1.20 1.19 1.18 1.17 1.17 1.16 1.14 1.07 1.00 .92 .85 .77 .70 Total Output kBtuh 21.6 20.6 19.5 18.4 17.8 17.0 15.1 13.1 12.6 12.2 11.7 11.4 11.0 9.9 8.8 7.7 6.7 5.6 4.5 3.4 kW 6.3 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.6 3.4 3.3 3.2 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26 / Page 13 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CH23-21 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .68 1.25 .75 1.26 .83 1.25 .54 1.26 .58 1.27 .63 1.26 .42 1.27 .43 1.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .98 .65 .73 .81 .52 .57 .62

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.1 5.0 1.42 .68 1.00 18.5 5.4 1.43 .77 1.00 19.4 5.7 1.44 .84 .76 18.3 5.4 1.43 .55 .87 19.6 5.7 1.44 .59 .96 20.4 6.0 1.45 .64 .62 19.7 5.8 1.44 .42 .70 21.0 6.2 1.45 .43 .79 21.6 6.3 1.46 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .99 .66 .74 .82 .52 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.62 .69 1.63 .78 1.64 .86 1.63 .55 1.64 .60 1.65 .65 1.64 .42 1.65 .44 1.66 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .83 .94 1.86 .79 .95 1.00 1.86 .88 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .77 .91 1.87 .66 .86 .99 1.86 .42 .53 .65 1.88 .44 .59 .75 1.88 .46 .65 .84

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.7 19.1 20.1 18.9 20.3 21.1 20.3 21.7 22.4 5.2 5.6 5.9 5.5 5.9 6.2 5.9 6.4 6.6

85_F kBtuh kW 29_C .91 16.5 4.8 1.00 17.8 5.2 1.00 18.8 5.5 .77 17.7 5.2 .88 18.9 5.5 .97 19.6 5.7 .62 19.0 5.6 .71 20.2 5.9 .80 20.8 6.1

85_F kBtuh kW 29_C .93 15.8 4.6 1.00 17.1 5.0 1.00 18.1 5.3 .78 17.0 5.0 .90 18.1 5.3 .99 18.7 5.5 .64 18.2 5.3 .73 19.3 5.7 .82 19.9 5.8

HP26-018
Entering Wet Bulb Tempera ture

CH23-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .67 1.25 .75 1.26 .83 1.25 .54 1.26 .59 1.27 .63 1.26 .42 1.27 .43 1.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .65 .73 .81 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.2 5.0 1.42 .69 1.00 18.6 5.5 1.43 .76 1.00 19.6 5.7 1.44 .84 .75 18.5 5.4 1.43 .55 .86 19.8 5.8 1.44 .59 .96 20.6 6.0 1.44 .64 .62 19.8 5.8 1.44 .42 .70 21.2 6.2 1.45 .43 .78 21.9 6.4 1.46 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .91 .99 .65 .74 .82 .53 .57 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.62 .69 1.63 .78 1.64 .86 1.63 .55 1.64 .60 1.64 .65 1.64 .42 1.65 .44 1.65 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .84 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.84 .70 .83 .94 1.85 .79 .95 1.00 1.86 .88 1.00 1.00 1.85 .56 .67 .79 1.86 .61 .77 .92 1.87 .66 .86 1.00 1.86 .42 .53 .64 1.87 .44 .59 .74 1.88 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 17.8 19.3 20.3 19.1 20.5 21.3 20.5 21.9 22.7 5.2 5.7 5.9 5.6 6.0 6.2 6.0 6.4 6.7

85_F kBtuh kW 29_C .91 16.6 4.9 1.00 18.0 5.3 1.00 19.0 5.6 .76 17.8 5.2 .88 19.1 5.6 .97 19.8 5.8 .63 19.1 5.6 .71 20.4 6.0 .80 21.1 6.2

85_F kBtuh kW 29_C .93 15.9 4.7 1.00 17.2 5.0 1.00 18.3 5.4 .78 17.1 5.0 .90 18.3 5.4 .99 18.9 5.5 .63 18.4 5.4 .73 19.5 5.7 .82 20.2 5.9

HP26-018 - CH23-21 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.6 21.4 21.9 kW 6.0 6.3 6.4 Comp. Motor kW Input 1.58 1.38 1.27 45_F (7_C) Total Heating Capacity kBtuh 16.0 16.8 17.3 kW 4.7 4.9 5.1 Comp. Motor kW Input 1.52 1.32 1.21 25_F (-4_C) Total Heating Capacity kBtuh 11.2 12.0 12.5 kW 3.3 3.5 3.7 Comp. Motor kW Input 1.46 1.26 1.15 5_F (-15_C) Total Heating Capacity kBtuh 7.8 8.6 9.1 kW 2.3 2.5 2.7 Comp. Motor kW Input 1.36 1.16 1.05 -15_F (-26_C) Total Heating Capacity kBtuh 3.6 4.4 4.9 kW 1.1 1.3 1.4 Comp. Motor kW Input 1.03 .83 .72

HP26-018 - CH23-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.9 21.7 22.2 kW 6.1 6.4 6.5 Comp. Motor kW Input 1.65 1.45 1.35 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.0 17.5 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.54 1.33 1.23 25_F (-4_C) Total Heating Capacity kBtuh 11.3 12.1 12.6 kW 3.3 3.5 3.7 Comp. Motor kW Input 1.42 1.22 1.12 5_F (-15_C) Total Heating Capacity kBtuh 7.9 8.7 9.2 kW 2.3 2.5 2.7 Comp. Motor kW Input 1.28 1.08 .98 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input .99 .79 .69

HP26-018 - CH23-21 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume\
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.38 1.37 1.35 1.34 1.33 1.32 1.29 1.27 1.26 1.26 1.26 1.25 1.25 1.24 1.16 1.07 .99 .91 .83 .75 Total Output kBtuh 21.4 20.4 19.3 18.2 17.6 16.8 14.9 12.9 12.5 12.0 11.5 11.2 10.8 9.7 8.6 7.6 6.5 5.5 4.4 3.4 kW 6.3 6.0 5.7 5.3 5.2 4.9 4.4 3.8 3.7 3.5 3.4 3.3 3.2 2.8 2.5 2.2 1.9 1.6 1.3 1.0

HP26-018 - CH23-31 HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.45 1.42 1.39 1.37 1.35 1.33 1.29 1.25 1.24 1.22 1.20 1.19 1.18 1.15 1.08 1.01 .93 .86 .79 .71 Total Output kBtuh 21.7 20.6 19.5 18.5 17.8 17.0 15.0 13.1 12.6 12.1 11.6 11.3 10.9 9.8 8.7 7.7 6.6 5.5 4.5 3.4 kW 6.4 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.5 3.4 3.3 3.2 2.9 2.5 2.3 1.9 1.6 1.3 1.0

HP26 / Page 14 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-018
Entering Wet Bulb Tempera ture

CH23-41 - CH33-36A/B/C-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.24 .67 1.26 .75 1.27 .83 1.25 .54 1.27 .58 1.28 .63 1.27 .42 1.28 .43 1.29 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .79 .90 .99 .64 .73 .81 .52 .57 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .90 17.4 5.1 1.42 .68 1.00 18.9 5.5 1.44 .77 1.00 20.0 5.9 1.44 .85 .75 18.7 5.5 1.43 .55 .87 20.2 5.9 1.45 .59 .97 21.0 6.2 1.45 .64 .62 20.1 5.9 1.44 .42 .70 21.6 6.3 1.46 .43 .79 22.3 6.5 1.47 .45

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.62 .68 1.64 .77 1.64 .87 1.63 .55 1.65 .60 1.65 .65 1.65 .42 1.66 .43 1.67 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .81 .93 1.00 .66 .75 .85 .53 .58 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 1.85 .70 .82 .94 1.86 .79 .95 1.00 1.87 .89 1.00 1.00 1.86 .55 .67 .79 1.87 .61 .77 .92 1.87 .67 .87 1.00 1.87 .42 .53 .64 1.88 .44 .59 .74 1.89 .46 .66 .84 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .80 .92 1.00 .65 .74 .82 .52 .57 .63

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 400 600 800 400 600 800 400 600 800

L/s kBtuh kW 190 285 380 190 285 380 190 285 380 18.0 19.6 20.7 19.4 20.9 21.8 20.8 22.4 23.2 5.3 5.7 6.1 5.7 6.1 6.4 6.1 6.6 6.8

85_F kBtuh kW 29_C .91 16.8 4.9 1.00 18.2 5.3 1.00 19.3 5.7 .76 18.0 5.3 .88 19.4 5.7 .98 20.1 5.9 .62 19.4 5.7 .71 20.7 6.1 .80 21.4 6.3

85_F kBtuh kW 29_C .93 16.1 4.7 1.00 17.4 5.1 1.00 18.6 5.5 .77 17.3 5.1 .90 18.5 5.4 1.00 19.2 5.6 .63 18.6 5.5 .73 19.8 5.8 .82 20.5 6.0

HP26-024
Entering Wet Bulb Tempera ture

CB29-21/26 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .72 1.54 .78 1.54 .84 1.54 .57 1.54 .60 1.54 .64 1.54 .42 1.54 .44 1.55 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .75 .82 .54 .59 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 20.8 6.1 1.73 .73 1.00 21.9 6.4 1.74 .79 1.00 22.7 6.7 1.74 .86 .81 22.2 6.5 1.74 .57 .90 23.1 6.8 1.74 .61 .97 23.7 6.9 1.75 .65 .66 23.8 7.0 1.75 .42 .73 24.6 7.2 1.75 .44 .79 25.2 7.4 1.75 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .77 .84 .55 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .74 1.96 .81 1.96 .87 1.96 .57 1.97 .62 1.97 .66 1.97 .43 1.97 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.21 .75 .90 .99 2.21 .82 .98 1.00 2.21 .89 1.00 1.00 2.21 .58 .72 .86 2.22 .63 .80 .95 2.22 .67 .87 1.00 2.22 .43 .57 .70 2.22 .44 .61 .78 2.22 .47 .66 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 21.6 22.7 23.5 23.1 24.0 24.6 24.6 25.6 26.3 6.3 6.7 6.9 6.8 7.0 7.2 7.2 7.5 7.7

85_F kBtuh kW 29_C .98 20.1 5.9 1.00 21.1 6.2 1.00 22.0 6.4 .83 21.4 6.3 .91 22.2 6.5 .98 22.8 6.7 .67 22.9 6.7 .75 23.7 6.9 .81 24.2 7.1

85_F kBtuh kW 29_C .99 19.2 5.6 1.00 20.2 5.9 1.00 21.2 6.2 .85 20.5 6.0 .93 21.3 6.2 .99 21.8 6.4 .68 21.9 6.4 .76 22.7 6.7 .83 23.2 6.8

HP26-018 - CH23-41 - CH33-36A/B/C-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 400 600 800 L/s 190 285 380 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 20.8 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.51 1.31 1.21 45_F (7_C) Total Heating Capacity kBtuh 16.2 17.0 17.5 kW 4.7 5.0 5.1 Comp. Motor kW Input 1.46 1.26 1.16 25_F (-4_C) Total Heating Capacity kBtuh 11.4 12.2 12.7 kW 3.3 3.6 3.7 Comp. Motor kW Input 1.41 1.21 1.11 5_F (-15_C) Total Heating Capacity kBtuh 8.0 8.8 9.3 kW 2.3 2.6 2.7 Comp. Motor kW Input 1.32 1.11 1.02 -15_F (-26_C) Total Heating Capacity kBtuh 3.7 4.5 5.0 kW 1.1 1.3 1.5 Comp. Motor kW Input 1.01 .80 .71

HP26-024 - CB29M-21-26 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.2 27.5 28.0 kW 7.7 8.1 8.2 Comp. Motor kW Input 1.88 1.67 1.53 45_F (7_C) Total Heating Capacity kBtuh 20.5 21.8 22.3 kW 6.0 6.4 6.5 Comp. Motor kW Input 1.77 1.56 1.42 25_F (-4_C) Total Heating Capacity kBtuh 14.8 16.1 16.6 kW 4.3 4.7 4.9 Comp. Motor kW Input 1.66 1.45 1.31 5_F (-15_C) Total Heating Capacity kBtuh 9.9 11.2 11.7 kW 2.9 3.3 3.4 Comp. Motor kW Input 1.50 1.29 1.15 -15_F (-26_C) Total Heating Capacity kBtuh 4.4 5.7 6.2 kW 1.3 1.7 1.8 Comp. Motor kW Input 1.14 .94 .79

HP26-018 - CH23-41 - CH33-36A/B/C-F HEATING PERFORMANCE at 600 cfm (285 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.31 1.30 1.29 1.28 1.27 1.26 1.23 1.21 1.21 1.21 1.20 1.20 1.20 1.19 1.11 1.03 .96 .88 .80 .72 Total Output kBtuh 21.6 20.6 19.5 18.4 17.8 17.0 15.1 13.1 12.6 12.2 11.7 11.4 11.0 9.9 8.8 7.7 6.7 5.6 4.5 3.4 kW 6.3 6.0 5.7 5.4 5.2 5.0 4.4 3.8 3.7 3.6 3.4 3.3 3.2 2.9 2.6 2.3 2.0 1.6 1.3 1.0

HP26-024 - CB29M-21-26 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.67 1.65 1.62 1.59 1.58 1.56 1.53 1.49 1.47 1.45 1.43 1.42 1.41 1.38 1.29 1.20 1.12 1.03 .94 .85 Total Output kBtuh 27.5 26.1 24.8 23.4 22.6 21.8 19.9 18.0 17.0 16.1 15.1 14.5 14.0 12.6 11.2 9.9 8.5 7.1 5.7 4.4 kW 8.1 7.6 7.3 6.9 6.6 6.4 5.8 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 15 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CB29M-31 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .72 1.53 .78 1.54 .84 1.53 .56 1.53 .60 1.54 .64 1.54 .43 1.54 .43 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 .98 .69 .75 .82 .54 .58 .62

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.6 6.3 1.73 .73 1.00 22.7 6.7 1.73 .79 1.00 23.6 6.9 1.74 .85 .81 23.1 6.8 1.73 .57 .90 24.0 7.0 1.74 .60 .97 24.6 7.2 1.74 .65 .66 24.7 7.2 1.74 .43 .73 25.6 7.5 1.75 .44 .79 26.2 7.7 1.75 .46 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .77 .83 .55 .59 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.95 .81 1.96 .87 1.95 .57 1.96 .62 1.97 .66 1.96 .43 1.97 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .85 .56 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .89 1.00 2.20 .82 .98 1.00 2.21 .89 1.00 1.00 2.20 .58 .72 .86 2.21 .62 .80 .95 2.21 .67 .87 1.00 2.21 .43 .56 .69 2.21 .44 .61 .78 2.22 .46 .66 .85

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.4 23.5 24.5 23.9 25.0 25.6 25.6 26.7 27.4 6.6 6.9 7.2 7.0 7.3 7.5 7.5 7.8 8.0

85_F kBtuh kW 29_C .97 20.8 6.1 1.00 21.9 6.4 1.00 22.8 6.7 .83 22.2 6.5 .91 23.1 6.8 .98 23.7 6.9 .67 23.7 6.9 .74 24.6 7.2 .81 25.1 7.4

85_F kBtuh kW 29_C .99 19.9 5.8 1.00 21.0 6.2 1.00 22.0 6.4 .84 21.3 6.2 .93 22.1 6.5 .99 22.7 6.7 .68 22.8 6.7 .76 23.6 6.9 .83 24.1 7.1

HP26-024
Entering Wet Bulb Tempera ture

CB29M-41 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.54 .78 1.54 .84 1.53 .56 1.54 .60 1.54 .63 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .92 .99 .69 .75 .82 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.8 6.4 1.73 .72 1.00 22.9 6.7 1.74 .79 1.00 23.9 7.0 1.74 .85 .81 23.3 6.8 1.74 .56 .89 24.3 7.1 1.75 .60 .97 25.0 7.3 1.75 .65 .65 24.9 7.3 1.75 .43 .72 26.0 7.6 1.75 .44 .79 26.6 7.8 1.75 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .77 .83 .55 .59 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.96 .80 1.96 .87 1.96 .57 1.96 .61 1.97 .66 1.97 .43 1.97 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .85 .56 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .89 1.00 2.20 .82 .98 1.00 2.21 .89 1.00 1.00 2.21 .58 .72 .86 2.21 .62 .80 .95 2.22 .67 .87 1.00 2.21 .43 .56 .69 2.22 .45 .61 .77 2.22 .47 .66 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.6 23.8 24.8 24.2 25.3 26.0 26.0 27.1 27.8 6.6 7.0 7.3 7.1 7.4 7.6 7.6 7.9 8.1

85_F kBtuh kW 29_C .98 20.9 6.1 1.00 22.0 6.4 1.00 23.0 6.7 .82 22.4 6.6 .91 23.3 6.8 .98 23.9 7.0 .67 23.9 7.0 .74 24.9 7.3 .81 25.5 7.5

85_F kBtuh kW 29_C .99 20.1 5.9 1.00 21.1 6.2 1.00 22.2 6.5 .84 21.4 6.3 .93 22.3 6.5 .99 22.9 6.7 .68 23.0 6.7 .76 23.8 7.0 .83 24.3 7.1

HP26-024 - CB29M-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.9 27.5 28.0 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.87 1.67 1.52 45_F (7_C) Total Heating Capacity kBtuh 21.2 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.76 1.55 1.41 25_F (-4_C) Total Heating Capacity kBtuh 15.4 16.0 16.5 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.63 1.43 1.28 5_F (-15_C) Total Heating Capacity kBtuh 10.5 11.1 11.6 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.47 1.27 1.12 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.13 .92 .78

HP26-024 - CB29M-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.2 27.8 28.4 kW 8.0 8.1 8.3 Comp. Motor kW Input 1.78 1.57 1.42 45_F (7_C) Total Heating Capacity kBtuh 21.4 22.0 22.6 kW 6.3 6.4 6.6 Comp. Motor kW Input 1.70 1.49 1.34 25_F (-4_C) Total Heating Capacity kBtuh 15.5 16.1 16.7 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.62 1.41 1.26 5_F (-15_C) Total Heating Capacity kBtuh 10.6 11.2 11.8 kW 3.1 3.3 3.5 Comp. Motor kW Input 1.48 1.27 1.12 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.3 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.13 .92 .77

HP26-024 - CB29M-31 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.67 1.64 1.61 1.58 1.57 1.55 1.51 1.48 1.45 1.43 1.41 1.39 1.38 1.35 1.27 1.18 1.09 1.01 .92 .84 Total Output kBtuh 27.5 26.2 24.8 23.4 22.6 21.8 19.9 18.0 17.0 16.0 15.0 14.4 13.9 12.5 11.1 9.8 8.4 7.0 5.7 4.3 kW 8.1 7.7 7.3 6.9 6.6 6.4 5.8 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26-024 - CB29M-41 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.57 1.55 1.53 1.51 1.50 1.49 1.46 1.44 1.42 1.41 1.39 1.38 1.38 1.36 1.27 1.18 1.09 1.01 .92 .83 Total Output kBtuh 27.8 26.4 25.0 23.6 22.8 22.0 20.1 18.1 17.1 16.1 15.1 14.5 13.9 12.6 11.2 9.8 8.5 7.1 5.7 4.4 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 16 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CB30M-21/26 - CB30U-21/26 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.52 .71 1.53 .77 1.53 .84 1.53 .56 1.53 .60 1.53 .63 1.53 .42 1.53 .43 1.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 .99 .68 .75 .81 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 22.3 6.5 1.73 .72 1.00 23.5 6.9 1.73 .79 1.00 24.5 7.2 1.74 .85 .81 23.9 7.0 1.73 .56 .89 25.0 7.3 1.74 .61 .97 25.7 7.5 1.74 .65 .66 25.6 7.5 1.74 .43 .72 26.7 7.8 1.75 .44 .79 27.4 8.0 1.75 .46

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.95 .73 1.95 .81 1.96 .87 1.95 .57 1.96 .62 1.96 .66 1.96 .43 1.97 .44 1.97 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .71 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.19 .75 .89 1.00 2.20 .82 .98 1.00 2.20 .90 1.00 1.00 2.20 .58 .72 .86 2.20 .63 .80 .95 2.21 .67 .87 1.00 2.21 .43 .56 .69 2.21 .45 .61 .78 2.21 .47 .66 .85 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .69 .76 .83 .55 .59 .64

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 23.2 24.5 25.5 24.9 26.0 26.8 26.7 27.9 28.6 6.8 7.2 7.5 7.3 7.6 7.9 7.8 8.2 8.4

85_F kBtuh kW 29_C .97 21.5 6.3 1.00 22.6 6.6 1.00 23.7 6.9 .82 22.9 6.7 .91 23.9 7.0 .98 24.6 7.2 .67 24.6 7.2 .74 25.6 7.5 .81 26.2 7.7

85_F kBtuh kW 29_C .99 20.6 6.0 1.00 21.7 6.4 1.00 22.8 6.7 .84 22.0 6.4 .93 22.9 6.7 1.00 23.5 6.9 .68 23.6 6.9 .76 24.4 7.2 .83 25.0 7.3

HP26-024
Entering Wet Bulb Tempera ture

CB30M-31 - CB30U-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.54 .77 1.54 .84 1.54 .56 1.54 .60 1.54 .63 1.54 .43 1.54 .43 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 1.00 .68 .75 .81 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 22.4 6.6 1.74 .72 1.00 23.6 6.9 1.74 .79 1.00 24.7 7.2 1.75 .86 .80 24.0 7.0 1.75 .56 .89 25.1 7.4 1.75 .61 .97 25.8 7.6 1.75 .65 .65 25.8 7.6 1.75 .42 .72 26.9 7.9 1.76 .44 .79 27.6 8.1 1.76 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .94 1.00 .69 .76 .83 .54 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.96 .73 1.97 .80 1.97 .87 1.97 .57 1.97 .61 1.98 .66 1.98 .43 1.98 .44 1.99 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .70 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .74 .89 1.00 2.21 .82 .98 1.00 2.21 .90 1.00 1.00 2.21 .58 .72 .85 2.22 .62 .80 .95 2.22 .67 .88 1.00 2.22 .43 .56 .69 2.22 .45 .61 .77 2.23 .47 .67 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 23.3 24.6 25.6 25.0 26.2 27.0 26.8 28.1 28.9 6.8 7.2 7.5 7.3 7.7 7.9 7.9 8.2 8.5

85_F kBtuh kW 29_C .98 21.5 6.3 1.00 22.6 6.6 1.00 23.8 7.0 .82 23.0 6.7 .91 24.0 7.0 .98 24.7 7.2 .66 24.7 7.2 .74 25.7 7.5 .81 26.3 7.7

85_F kBtuh kW 29_C .99 20.6 6.0 1.00 21.7 6.4 1.00 22.9 6.7 .83 22.0 6.4 .93 23.0 6.7 1.00 23.6 6.9 .68 23.6 6.9 .75 24.6 7.2 .83 25.1 7.4

HP26-024 - CB30M-21/26 - CB30U-21/26 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.2 27.8 28.3 kW 8.0 8.1 8.3 Comp. Motor kW Input 1.83 1.63 1.49 45_F (7_C) Total Heating Capacity kBtuh 21.4 22.0 22.5 kW 6.3 6.4 6.6 Comp. Motor kW Input 1.72 1.52 1.38 25_F (-4_C) Total Heating Capacity kBtuh 15.4 16.0 16.5 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.60 1.40 1.26 5_F (-15_C) Total Heating Capacity kBtuh 10.5 11.1 11.6 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.44 1.24 1.10 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.10 .90 .76

HP26-024 - CB30M-31 - CB30U-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.9 27.5 27.9 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.69 1.51 1.39 45_F (7_C) Total Heating Capacity kBtuh 21.1 21.7 22.1 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.63 1.45 1.32 25_F (-4_C) Total Heating Capacity kBtuh 15.2 15.8 16.2 kW 4.5 4.6 4.7 Comp. Motor kW Input 1.56 1.38 1.25 5_F (-15_C) Total Heating Capacity kBtuh 10.3 10.9 11.3 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.43 1.25 1.12 -15_F (-26_C) Total Heating Capacity kBtuh 5.0 5.6 6.0 kW 1.5 1.6 1.8 Comp. Motor kW Input 1.08 .90 .78

HP26-024 - CB30M-21/26 - CB30U-21/26 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.63 1.61 1.58 1.55 1.53 1.52 1.48 1.44 1.42 1.40 1.38 1.36 1.35 1.32 1.24 1.15 1.07 .99 .90 .82 Total Output kBtuh 27.8 26.4 25.0 23.6 22.8 22.0 20.0 18.1 17.1 16.0 15.0 14.4 13.8 12.4 11.1 9.7 8.4 7.0 5.7 4.3 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.4 4.2 4.0 3.6 3.3 2.8 2.5 2.1 1.7 1.3

HP26-024 - CB30M-31 - CB30U-31 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.51 1.50 1.48 1.47 1.46 1.45 1.42 1.40 1.39 1.38 1.37 1.36 1.35 1.34 1.25 1.16 1.08 .99 .90 .82 Total Output kBtuh 27.5 26.1 24.7 23.3 22.5 21.7 19.8 17.8 16.8 15.8 14.8 14.2 13.6 12.3 10.9 9.6 8.3 6.9 5.6 4.3 kW 8.1 7.6 7.2 6.8 6.6 6.4 5.8 5.2 4.9 4.6 4.3 4.2 4.0 3.6 3.2 2.8 2.4 2.0 1.6 1.3

HP26 / Page 17 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CVP10-26/EC10Q3 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.52 .71 1.53 .77 1.53 .84 1.53 .56 1.53 .60 1.53 .63 1.53 .42 1.53 .44 1.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 .99 .68 .75 .81 .54 .58 .62 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.2 6.2 1.72 .72 1.00 22.4 6.6 1.73 .79 1.00 23.3 6.8 1.73 .86 .81 22.7 6.7 1.73 .56 .90 23.7 6.9 1.74 .60 .97 24.4 7.2 1.74 .65 .66 24.3 7.1 1.74 .42 .72 25.3 7.4 1.74 .44 .79 26.0 7.6 1.75 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .94 1.00 .69 .76 .83 .55 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.94 .73 1.95 .80 1.95 .87 1.95 .57 1.96 .61 1.96 .66 1.96 .43 1.96 .44 1.97 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .70 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.19 .74 .89 1.00 2.19 .82 .98 1.00 2.20 .89 1.00 1.00 2.20 .58 .72 .85 2.20 .63 .79 .95 2.21 .67 .87 1.00 2.20 .43 .56 .69 2.21 .45 .61 .77 2.21 .47 .66 .85

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.0 23.2 24.2 23.6 24.7 25.4 25.3 26.4 27.1 6.4 6.8 7.1 6.9 7.2 7.4 7.4 7.7 7.9

85_F kBtuh kW 29_C .97 20.4 6.0 1.00 21.5 6.3 1.00 22.5 6.6 .82 21.8 6.4 .91 22.7 6.7 .98 23.4 6.9 .67 23.3 6.8 .74 24.3 7.1 .81 24.9 7.3

85_F kBtuh kW 29_C .99 19.6 5.7 1.00 20.6 6.0 1.00 21.7 6.4 .84 20.9 6.1 .93 21.8 6.4 .99 22.4 6.6 .68 22.4 6.6 .75 23.3 6.8 .83 23.8 7.0

HP26-024
Entering Wet Bulb Temperat ure

C26-21 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .72 1.53 .78 1.54 .85 1.53 .56 1.53 .60 1.54 .64 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .76 .82 .54 .58 .63 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.1 6.2 1.72 .73 1.00 22.2 6.5 1.73 .80 1.00 23.1 6.8 1.74 .86 .82 22.5 6.6 1.73 .57 .91 23.4 6.9 1.74 .61 .97 24.0 7.0 1.74 .65 .66 24.1 7.1 1.74 .43 .73 25.0 7.3 1.74 .44 .80 25.5 7.5 1.75 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .95 1.00 .70 .77 .84 .55 .60 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .74 1.95 .81 1.96 .88 1.95 .58 1.96 .62 1.96 .66 1.96 .43 1.97 .45 1.97 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .79 .86 .56 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .90 1.00 2.20 .83 .98 1.00 2.20 .90 1.00 1.00 2.20 .58 .73 .86 2.21 .63 .81 .95 2.21 .68 .88 1.00 2.21 .43 .57 .70 2.21 .45 .62 .78 2.21 .47 .67 .86

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 21.9 23.0 23.9 23.4 24.3 25.0 25.0 26.0 26.6 6.4 6.7 7.0 6.9 7.1 7.3 7.3 7.6 7.8

85_F kBtuh kW 29_C .98 20.4 6.0 1.00 21.4 6.3 1.00 22.3 6.5 .83 21.7 6.4 .92 22.5 6.6 .98 23.1 6.8 .68 23.2 6.8 .75 24.0 7.0 .82 24.5 7.2

85_F kBtuh kW 29_C .99 19.5 5.7 1.00 20.6 6.0 1.00 21.5 6.3 .84 20.8 6.1 .93 21.6 6.3 .99 22.1 6.5 .69 22.2 6.5 .77 23.0 6.7 .84 23.5 6.9

HP26-024 - CVP10-26/EC10Q3 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.0 27.6 28.1 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.78 1.61 1.56 45_F (7_C) Total Heating Capacity kBtuh 21.2 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.68 1.50 1.46 25_F (-4_C) Total Heating Capacity kBtuh 15.3 15.9 16.4 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.57 1.39 1.35 5_F (-15_C) Total Heating Capacity kBtuh 10.4 11.0 11.5 kW 3.0 3.2 3.4 Comp. Motor kW Input 1.42 1.24 1.20 -15_F (-26_C) Total Heating Capacity kBtuh 5.0 5.6 6.1 kW 1.5 1.6 1.8 Comp. Motor kW Input 1.08 .90 .86

HP26-024 - C26-21 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.0 27.6 28.1 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.87 1.66 1.51 45_F (7_C) Total Heating Capacity kBtuh 21.3 21.9 22.4 kW 6.2 6.4 6.6 Comp. Motor kW Input 1.76 1.55 1.40 25_F (-4_C) Total Heating Capacity kBtuh 15.6 16.2 16.7 kW 4.6 4.7 4.9 Comp. Motor kW Input 1.65 1.44 1.29 5_F (-15_C) Total Heating Capacity kBtuh 10.7 11.3 11.8 kW 3.1 3.3 3.5 Comp. Motor kW Input 1.50 1.29 1.14 -15_F (-26_C) Total Heating Capacity kBtuh 5.2 5.8 6.3 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.15 .94 .79

HP26-024 - CVP10-26/EC10Q3 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.61 1.58 1.56 1.53 1.52 1.50 1.47 1.44 1.41 1.39 1.37 1.36 1.35 1.33 1.24 1.16 1.07 .99 .90 .82 Total Output kBtuh 27.6 26.2 24.8 23.4 22.6 21.8 19.9 17.9 16.9 15.9 14.9 14.3 13.7 12.4 11.0 9.7 8.3 7.0 5.6 4.3 kW 8.1 7.7 7.3 6.9 6.6 6.4 5.8 5.2 5.0 4.7 4.4 4.2 4.0 3.6 3.2 2.8 2.4 2.1 1.6 1.3

HP26-024 - C26-21 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.66 1.63 1.61 1.58 1.57 1.55 1.52 1.48 1.46 1.44 1.42 1.41 1.40 1.37 1.29 1.20 1.11 1.02 .94 .85 Total Output kBtuh 27.6 26.2 24.9 23.5 22.7 21.9 20.0 18.1 17.1 16.2 15.2 14.6 14.1 12.7 11.3 9.9 8.5 7.2 5.8 4.4 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.5 4.3 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 18 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

C26-26 - C33-24A/B COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.54 .78 1.54 .84 1.53 .56 1.54 .60 1.54 .64 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .76 .82 .54 .58 .63 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.6 6.3 1.73 .73 1.00 22.7 6.7 1.74 .79 1.00 23.7 6.9 1.74 .86 .81 23.1 6.8 1.74 .57 .90 24.0 7.0 1.74 .61 .97 24.7 7.2 1.75 .65 .66 24.7 7.2 1.74 .43 .73 25.7 7.5 1.75 .44 .80 26.3 7.7 1.75 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .95 1.00 .70 .77 .84 .55 .59 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.96 .81 1.96 .88 1.96 .57 1.97 .61 1.97 .66 1.97 .43 1.98 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .86 .56 .61 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .89 1.00 2.20 .83 .98 1.00 2.21 .90 1.00 1.00 2.21 .58 .73 .86 2.21 .62 .80 .96 2.21 .67 .88 1.00 2.21 .43 .56 .70 2.21 .45 .61 .78 2.22 .47 .67 .86

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.4 23.6 24.6 24.0 25.0 25.8 25.7 26.8 27.5 6.6 6.9 7.2 7.0 7.3 7.6 7.5 7.9 8.1

85_F kBtuh kW 29_C .98 20.8 6.1 1.00 21.9 6.4 1.00 22.9 6.7 .83 22.2 6.5 .92 23.1 6.8 .98 23.7 6.9 .67 23.7 6.9 .74 24.6 7.2 .81 25.2 7.4

85_F kBtuh kW 29_C .99 19.9 5.8 1.00 21.0 6.2 1.00 22.0 6.4 .84 21.2 6.2 .94 22.1 6.5 1.00 22.7 6.7 .68 22.7 6.7 .76 23.6 6.9 .83 24.1 7.1

HP26-024
Entering Wet Bulb Tempera ture

C26-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.54 .77 1.54 .84 1.54 .56 1.54 .59 1.54 .64 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 .99 .68 .75 .81 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 22.4 6.6 1.74 .72 1.00 23.6 6.9 1.74 .79 1.00 24.6 7.2 1.75 .85 .80 23.9 7.0 1.74 .56 .89 25.0 7.3 1.75 .60 .97 25.8 7.6 1.75 .65 .65 25.7 7.5 1.75 .42 .72 26.8 7.9 1.76 .44 .79 27.5 8.1 1.76 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .94 1.00 .69 .76 .83 .54 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.96 .80 1.97 .88 1.97 .57 1.97 .62 1.98 .66 1.97 .43 1.98 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .70 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .89 1.00 2.21 .82 .98 1.00 2.21 .90 1.00 1.00 2.21 .58 .72 .86 2.21 .62 .80 .95 2.22 .68 .87 1.00 2.22 .43 .56 .69 2.22 .45 .61 .78 2.23 .47 .66 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 23.2 24.5 25.6 24.9 26.1 26.9 26.8 28.0 28.8 6.8 7.2 7.5 7.3 7.6 7.9 7.9 8.2 8.4

85_F kBtuh kW 29_C .98 21.5 6.3 1.00 22.6 6.6 1.00 23.8 7.0 .82 23.0 6.7 .91 24.0 7.0 .98 24.6 7.2 .67 24.6 7.2 .74 25.6 7.5 .81 26.3 7.7

85_F kBtuh kW 29_C .99 20.6 6.0 1.00 21.7 6.4 1.00 22.8 6.7 .84 22.0 6.4 .93 22.9 6.7 1.00 23.6 6.9 .68 23.6 6.9 .75 24.5 7.2 .83 25.1 7.4

HP26-024 - C26-26 - C33-24A/B HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.1 27.7 28.2 kW 7.9 8.1 8.3 Comp. Motor kW Input 1.78 1.58 1.43 45_F (7_C) Total Heating Capacity kBtuh 21.4 22.0 22.5 kW 6.3 6.4 6.6 Comp. Motor kW Input 1.71 1.51 1.36 25_F (-4_C) Total Heating Capacity kBtuh 15.6 16.2 16.7 kW 4.6 4.7 4.9 Comp. Motor kW Input 1.64 1.43 1.28 5_F (-15_C) Total Heating Capacity kBtuh 10.7 11.3 11.8 kW 3.1 3.3 3.5 Comp. Motor kW Input 1.50 1.30 1.15 -15_F (-26_C) Total Heating Capacity kBtuh 5.2 5.8 6.3 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.14 .94 .79

HP26-024 - C26-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.2 27.8 28.3 kW 8.0 8.1 8.3 Comp. Motor kW Input 1.70 1.50 1.35 45_F (7_C) Total Heating Capacity kBtuh 21.4 22.0 22.5 kW 6.3 6.4 6.6 Comp. Motor kW Input 1.65 1.45 1.31 25_F (-4_C) Total Heating Capacity kBtuh 15.5 16.1 16.6 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.61 1.41 1.26 5_F (-15_C) Total Heating Capacity kBtuh 10.6 11.2 11.7 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.49 1.29 1.15 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.13 .93 .79

HP26-024 - C26-26 - C33-24A/B HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.58 1.56 1.54 1.53 1.52 1.51 1.48 1.45 1.44 1.43 1.42 1.41 1.40 1.39 1.30 1.21 1.12 1.03 .94 .85 Total Output kBtuh 27.7 26.4 25.0 23.6 22.8 22.0 20.1 18.2 17.2 16.2 15.2 14.6 14.1 12.7 11.3 9.9 8.5 7.1 5.8 4.4 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.5 4.3 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26-024 - C26-31 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.50 1.49 1.48 1.47 1.46 1.45 1.43 1.42 1.41 1.41 1.40 1.40 1.39 1.38 1.29 1.20 1.11 1.02 .93 .84 Total Output kBtuh 27.8 26.4 25.0 23.6 22.8 22.0 20.1 18.1 17.1 16.1 15.1 14.5 13.9 12.6 11.2 9.8 8.5 7.1 5.7 4.4 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 19 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CR26-18N-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.52 .71 1.53 .77 1.53 .83 1.53 .56 1.53 .59 1.53 .62 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .92 .97 .68 .74 .80 .54 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .95 20.7 6.1 1.72 .72 1.00 21.7 6.4 1.73 .78 1.00 22.5 6.6 1.73 .84 .80 22.1 6.5 1.73 .56 .88 23.0 6.7 1.73 .60 .95 23.6 6.9 1.74 .63 .65 23.6 6.9 1.74 .42 .71 24.5 7.2 1.74 .44 .78 25.1 7.4 1.74 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .75 .81 .54 .58 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.94 .72 1.95 .79 1.95 .85 1.95 .57 1.95 .61 1.96 .65 1.96 .43 1.96 .44 1.97 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .95 1.00 .70 .77 .84 .55 .59 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .74 .88 .99 2.20 .81 .96 1.00 2.20 .88 1.00 1.00 2.20 .57 .71 .85 2.21 .61 .78 .93 2.21 .65 .85 .99 2.20 .43 .56 .69 2.21 .44 .60 .76 2.21 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 21.4 22.4 23.3 22.9 23.9 24.5 24.5 25.5 26.1 6.3 6.6 6.8 6.7 7.0 7.2 7.2 7.5 7.6

85_F kBtuh kW 29_C .97 19.9 5.8 1.00 20.9 6.1 1.00 21.7 6.4 .82 21.3 6.2 .90 22.1 6.5 .97 22.6 6.6 .67 22.7 6.7 .73 23.6 6.9 .79 24.1 7.1

85_F kBtuh kW 29_C .98 19.1 5.6 1.00 20.1 5.9 1.00 20.9 6.1 .83 20.4 6.0 .92 21.2 6.2 .98 21.7 6.4 .67 21.8 6.4 .75 22.6 6.6 .81 23.1 6.8

HP26-024
Entering Wet Bulb Tempera ture

CR26-30N-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.54 .78 1.54 .84 1.53 .56 1.54 .60 1.54 .63 1.54 .42 1.54 .43 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 .99 .68 .75 .82 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 22.2 6.5 1.73 .72 1.00 23.4 6.9 1.74 .79 1.00 24.4 7.2 1.74 .85 .81 23.7 6.9 1.74 .57 .89 24.8 7.3 1.75 .61 .97 25.4 7.4 1.75 .65 .66 25.4 7.4 1.75 .43 .72 26.5 7.8 1.75 .44 .79 27.1 7.9 1.75 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .76 .83 .55 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.96 .81 1.96 .87 1.96 .57 1.97 .62 1.97 .66 1.97 .43 1.97 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .71 .78 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .75 .89 1.00 2.20 .83 .98 1.00 2.21 .89 1.00 1.00 2.21 .58 .72 .86 2.21 .63 .80 .95 2.22 .67 .87 1.00 2.21 .43 .56 .69 2.22 .44 .61 .77 2.22 .47 .66 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 23.0 24.3 25.3 24.7 25.8 26.5 26.5 27.6 28.3 6.7 7.1 7.4 7.2 7.6 7.8 7.8 8.1 8.3

85_F kBtuh kW 29_C .97 21.3 6.2 1.00 22.5 6.6 1.00 23.5 6.9 .82 22.8 6.7 .91 23.7 6.9 .98 24.4 7.2 .67 24.4 7.2 .74 25.4 7.4 .81 26.0 7.6

85_F kBtuh kW 29_C .99 20.5 6.0 1.00 21.5 6.3 1.00 22.6 6.6 .84 21.8 6.4 .93 22.7 6.7 1.00 23.3 6.8 .68 23.4 6.9 .76 24.3 7.1 .83 24.8 7.3

HP26-024 - CR26-18N-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.9 27.5 28.0 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.97 1.75 1.60 45_F (7_C) Total Heating Capacity kBtuh 21.2 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.82 1.60 1.45 25_F (-4_C) Total Heating Capacity kBtuh 15.5 16.1 16.6 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.66 1.45 1.29 5_F (-15_C) Total Heating Capacity kBtuh 10.6 11.2 11.7 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.48 1.26 1.11 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.14 .92 .77

HP26-024 - CR26-30N-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 27.2 27.8 28.3 kW 8.0 8.1 8.3 Comp. Motor kW Input 1.81 1.61 1.46 45_F (7_C) Total Heating Capacity kBtuh 21.4 22.0 22.5 kW 6.3 6.4 6.6 Comp. Motor kW Input 1.71 1.50 1.36 25_F (-4_C) Total Heating Capacity kBtuh 15.5 16.1 16.6 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.60 1.39 1.25 5_F (-15_C) Total Heating Capacity kBtuh 10.6 11.2 11.7 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.44 1.24 1.09 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.11 .90 .76

HP26-024 - CR26-18N-F HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.75 1.72 1.68 1.64 1.62 1.60 1.56 1.51 1.48 1.45 1.42 1.40 1.38 1.35 1.26 1.18 1.09 1.01 .92 .84 Total Output kBtuh 27.5 26.1 24.8 23.4 22.6 21.8 19.9 18.0 17.0 16.1 15.1 14.5 14.0 12.6 11.2 9.9 8.5 7.1 5.7 4.4 kW 8.1 7.6 7.3 6.9 6.6 6.4 5.8 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26-024 - CR26-30N-F HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.61 1.58 1.56 1.53 1.52 1.50 1.47 1.43 1.41 1.39 1.37 1.36 1.35 1.32 1.24 1.15 1.07 .98 .90 .82 Total Output kBtuh 27.8 26.4 25.0 23.6 22.8 22.0 20.1 18.1 17.1 16.1 15.1 14.5 13.9 12.6 11.2 9.8 8.5 7.1 5.7 4.4 kW 8.1 7.7 7.3 6.9 6.7 6.4 5.9 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 20 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CH23-21 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.53 .78 1.54 .84 1.53 .56 1.53 .60 1.54 .64 1.54 .42 1.54 .44 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .75 .82 .54 .58 .62

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.3 6.2 1.72 .73 1.00 22.4 6.6 1.73 .79 1.00 23.3 6.8 1.74 .86 .81 22.7 6.7 1.73 .57 .90 23.6 6.9 1.74 .61 .96 24.3 7.1 1.74 .65 .66 24.3 7.1 1.74 .42 .73 25.2 7.4 1.74 .44 .80 25.8 7.6 1.75 .46 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .77 .84 .55 .59 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .74 1.96 .81 1.96 .87 1.95 .57 1.96 .62 1.97 .66 1.96 .43 1.97 .44 1.97 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .71 .78 .85 .56 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .74 .89 1.00 2.20 .82 .98 1.00 2.20 .89 1.00 1.00 2.20 .58 .72 .86 2.21 .63 .80 .95 2.21 .68 .87 1.00 2.21 .43 .56 .70 2.21 .45 .61 .78 2.22 .47 .66 .85

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.1 23.2 24.1 23.6 24.6 25.3 25.2 26.3 26.9 6.5 6.8 7.1 6.9 7.2 7.4 7.4 7.7 7.9

85_F kBtuh kW 29_C .98 20.5 6.0 1.00 21.6 6.3 1.00 22.5 6.6 .82 21.9 6.4 .91 22.7 6.7 .98 23.3 6.8 .67 23.4 6.9 .75 24.2 7.1 .81 24.8 7.3

85_F kBtuh kW 29_C .99 19.7 5.8 1.00 20.7 6.1 1.00 21.7 6.4 .84 21.0 6.2 .93 21.8 6.4 .99 22.3 6.5 .68 22.4 6.6 .76 23.2 6.8 .83 23.7 6.9

HP26-024
Entering Wet Bulb Tempera ture

CH23-31 - CH33-30A-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.53 .78 1.54 .84 1.53 .56 1.54 .60 1.54 .64 1.54 .43 1.54 .43 1.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .93 .99 .69 .75 .82 .54 .58 .62 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 21.4 6.3 1.73 .72 1.00 22.5 6.6 1.74 .79 1.00 23.4 6.9 1.74 .86 .81 22.8 6.7 1.74 .57 .90 23.8 7.0 1.74 .61 .97 24.5 7.2 1.74 .65 .66 24.4 7.2 1.74 .43 .72 25.4 7.4 1.75 .44 .79 26.0 7.6 1.75 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .94 1.00 .70 .76 .83 .55 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 1.95 .73 1.96 .80 1.96 .87 1.96 .57 1.97 .61 1.97 .66 1.97 .43 1.97 .44 1.98 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .96 1.00 .71 .79 .85 .55 .60 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.20 .74 .89 1.00 2.20 .82 .98 1.00 2.21 .90 1.00 1.00 2.21 .58 .72 .86 2.21 .63 .80 .95 2.21 .67 .88 1.00 2.21 .43 .56 .69 2.22 .45 .61 .77 2.22 .46 .66 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.1 23.3 24.3 23.7 24.8 25.5 25.4 26.5 27.2 6.5 6.8 7.1 6.9 7.3 7.5 7.4 7.8 8.0

85_F kBtuh kW 29_C .98 20.5 6.0 1.00 21.6 6.3 1.00 22.6 6.6 .82 21.9 6.4 .91 22.8 6.7 .98 23.5 6.9 .67 23.5 6.9 .74 24.4 7.2 .81 24.9 7.3

85_F kBtuh kW 29_C .99 19.7 5.8 1.00 20.8 6.1 1.00 21.8 6.4 .84 21.0 6.2 .93 21.9 6.4 .99 22.4 6.6 .68 22.5 6.6 .76 23.3 6.8 .83 23.9 7.0

HP26-024 - CH23-21 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.5 27.1 27.6 kW 7.8 7.9 8.1 Comp. Motor kW Input 1.91 1.70 1.55 45_F (7_C) Total Heating Capacity kBtuh 20.9 21.5 22.0 kW 6.1 6.3 6.4 Comp. Motor kW Input 1.79 1.58 1.42 25_F (-4_C) Total Heating Capacity kBtuh 15.2 15.8 16.3 kW 4.5 4.6 4.8 Comp. Motor kW Input 1.66 1.45 1.30 5_F (-15_C) Total Heating Capacity kBtuh 10.5 11.1 11.6 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.49 1.28 1.13 -15_F (-26_C) Total Heating Capacity kBtuh 5.0 5.6 6.1 kW 1.5 1.6 1.8 Comp. Motor kW Input 1.15 .94 .78

HP26-024 - CH23-31 - CH33-30A-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.8 27.4 27.9 kW 7.9 8.0 8.2 Comp. Motor kW Input 1.85 1.65 1.50 45_F (7_C) Total Heating Capacity kBtuh 21.1 21.7 22.2 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.74 1.53 1.38 25_F (-4_C) Total Heating Capacity kBtuh 15.4 16.0 16.5 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.62 1.42 1.27 5_F (-15_C) Total Heating Capacity kBtuh 10.5 11.1 11.6 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.47 1.26 1.11 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.12 .92 .77

HP26-024 - CH23-21 HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.70 1.67 1.64 1.61 1.59 1.58 1.54 1.50 1.48 1.45 1.43 1.41 1.40 1.37 1.28 1.20 1.11 1.02 .94 .85 Total Output kBtuh 27.1 25.8 24.4 23.1 22.3 21.5 19.7 17.8 16.8 15.8 14.9 14.3 13.8 12.4 11.1 9.7 8.4 7.0 5.6 4.3 kW 7.9 7.6 7.2 6.8 6.5 6.3 5.8 5.2 4.9 4.6 4.4 4.2 4.0 3.6 3.3 2.8 2.5 2.1 1.6 1.3

HP26-024 - CH23-31 - CH33-30A-F HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.65 1.62 1.59 1.56 1.55 1.53 1.50 1.46 1.44 1.42 1.40 1.38 1.37 1.35 1.26 1.17 1.09 1.00 .92 .83 Total Output kBtuh 27.4 26.0 24.7 23.3 22.5 21.7 19.8 17.9 16.9 16.0 15.0 14.4 13.9 12.5 11.1 9.8 8.4 7.1 5.7 4.3 kW 8.0 7.6 7.2 6.8 6.6 6.4 5.8 5.2 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26 / Page 21 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-024
Entering Wet Bulb Tempera ture

CH23-41 - CH33-36A/B/C-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.53 .71 1.53 .78 1.53 .85 1.53 .56 1.53 .60 1.53 .64 1.53 .43 1.53 .43 1.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .84 .93 1.00 .69 .75 .82 .54 .58 .63 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .96 22.0 6.4 1.73 .72 1.00 23.2 6.8 1.73 .79 1.00 24.3 7.1 1.74 .86 .80 23.5 6.9 1.74 .56 .90 24.6 7.2 1.74 .61 .97 25.4 7.4 1.74 .65 .66 25.3 7.4 1.74 .42 .72 26.4 7.7 1.75 .44 .80 27.0 7.9 1.75 .46

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.95 .73 1.95 .81 1.96 .88 1.96 .57 1.96 .61 1.97 .66 1.96 .43 1.97 .44 1.98 .47 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .97 1.00 .71 .78 .86 .55 .60 .66 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.19 .74 .90 1.00 2.20 .83 .99 1.00 2.20 .90 1.00 1.00 2.20 .58 .72 .86 2.20 .63 .80 .96 2.21 .68 .88 1.00 2.21 .43 .56 .69 2.21 .45 .61 .78 2.22 .47 .67 .86 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .95 1.00 .69 .77 .84 .55 .59 .64

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 600 800 1000 600 800 1000 600 800 1000

L/s kBtuh kW 285 380 470 285 380 470 285 380 470 22.9 24.2 25.2 24.5 25.7 26.5 26.3 27.6 28.3 6.7 7.1 7.4 7.2 7.5 7.8 7.7 8.1 8.3

85_F kBtuh kW 29_C .98 21.1 6.2 1.00 22.3 6.5 1.00 23.4 6.9 .82 22.6 6.6 .92 23.6 6.9 .99 24.3 7.1 .66 24.2 7.1 .74 25.2 7.4 .82 25.8 7.6

85_F kBtuh kW 29_C .99 20.2 5.9 1.00 21.4 6.3 1.00 22.5 6.6 .84 21.6 6.3 .94 22.6 6.6 1.00 23.2 6.8 .68 23.2 6.8 .76 24.1 7.1 .84 24.7 7.2

HP26-030
Entering Wet Bulb Tempera ture

CB29M-41 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .92 .97 .69 .74 .80 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 27.7 8.1 2.04 .73 1.00 28.8 8.4 2.04 .78 1.00 29.7 8.7 2.05 .84 .82 29.5 8.6 2.04 .57 .89 30.5 8.9 2.05 .60 .95 31.1 9.1 2.05 .63 .67 31.6 9.3 2.05 .43 .72 32.5 9.5 2.05 .44 .77 33.2 9.7 2.06 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .98 .71 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.30 .74 2.30 .80 2.31 .85 2.30 .58 2.31 .61 2.32 .64 2.31 .43 2.32 .44 2.32 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .95 1.00 .72 .78 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.60 .76 .90 1.00 2.60 .82 .97 1.00 2.60 .87 1.00 1.00 2.60 .58 .73 .87 2.60 .62 .79 .94 2.60 .66 .85 .99 2.61 .43 .57 .70 2.61 .44 .61 .77 2.61 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

Comp Motor kW 75_F L/s kBtuh kW Input 24_C 380 28.7 8.4 1.80 .72 470 29.8 8.7 1.80 .77 565 30.8 9.0 1.81 .82 380 30.7 9.0 1.80 .56 470 31.7 9.3 1.80 .59 565 32.4 9.5 1.80 .62 380 32.9 9.6 1.80 .43 470 33.9 9.9 1.80 .43 565 34.6 10.1 1.80 .45

85_F kBtuh kW 29_C .98 26.6 7.8 1.00 27.7 8.1 1.00 28.6 8.4 .84 28.4 8.3 .91 29.2 8.6 .96 29.9 8.8 .68 30.4 8.9 .74 31.2 9.1 .79 31.8 9.3

85_F kBtuh kW 29_C .99 25.6 7.5 1.00 26.6 7.8 1.00 27.6 8.1 .85 27.2 8.0 .93 28.0 8.2 .98 28.6 8.4 .69 29.1 8.5 .75 29.9 8.8 .81 30.4 8.9

HP26-024 - CH23-41 - CH33-36A/B/C-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 600 800 1000 L/s 285 380 470 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 26.9 27.5 28.0 kW 7.9 8.1 8.2 Comp. Motor kW Input 1.79 1.59 1.45 45_F (7_C) Total Heating Capacity kBtuh 21.2 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.67 1.47 1.32 25_F (-4_C) Total Heating Capacity kBtuh 15.4 16.0 16.5 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.53 1.33 1.18 5_F (-15_C) Total Heating Capacity kBtuh 10.5 11.1 11.6 kW 3.1 3.3 3.4 Comp. Motor kW Input 1.43 1.23 1.08 -15_F (-26_C) Total Heating Capacity kBtuh 5.1 5.7 6.2 kW 1.5 1.7 1.8 Comp. Motor kW Input 1.09 .89 .75

HP26-030 - CB29M-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.7 37.4 37.9 kW 10.8 11.0 11.1 Comp. Motor kW Input 2.47 2.25 2.08 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.27 2.05 1.88 25_F (-4_C) Total Heating Capacity kBtuh 21.1 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 2.06 1.84 1.67 5_F (-15_C) Total Heating Capacity kBtuh 15.2 15.9 16.4 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.84 1.62 1.45 -15_F (-26_C) Total Heating Capacity kBtuh 7.3 8.0 8.5 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.41 1.19 1.02

HP26-024 - CH23-41 - CH33-36A/B/C-F HEATING PERFORMANCE at 800 cfm (380 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 1.59 1.56 1.54 1.51 1.50 1.47 1.39 1.31 1.32 1.33 1.34 1.35 1.34 1.31 1.23 1.14 1.06 .98 .89 .81 Total Output kBtuh 27.5 26.2 24.8 23.4 22.6 21.8 19.9 18.0 17.0 16.0 15.0 14.4 13.9 12.5 11.1 9.8 8.4 7.0 5.7 4.3 kW 8.1 7.7 7.3 6.9 6.6 6.4 5.8 5.3 5.0 4.7 4.4 4.2 4.1 3.7 3.3 2.9 2.5 2.1 1.7 1.3

HP26-030 - CB29M-41 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.25 2.20 2.15 2.11 2.08 2.05 1.97 1.89 1.86 1.84 1.81 1.80 1.78 1.73 1.62 1.51 1.40 1.30 1.19 1.08 Total Output kBtuh 37.4 35.6 33.9 32.1 31.0 29.8 26.8 23.8 22.8 21.8 20.9 20.3 19.6 17.8 15.9 13.9 11.9 10.0 8.0 6.1 kW 11.0 10.4 9.9 9.4 9.1 8.7 7.9 7.0 6.7 6.4 6.1 5.9 5.7 5.2 4.7 4.1 3.5 2.9 2.3 1.8

HP26 / Page 22 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CB30M-21/26 - CB30U-21/26COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .75 .80 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.4 8.3 2.07 .73 1.00 29.5 8.6 2.08 .78 1.00 30.5 8.9 2.08 .84 .82 30.3 8.9 2.07 .57 .89 31.3 9.2 2.08 .60 .94 32.0 9.4 2.08 .63 .67 32.4 9.5 2.08 .43 .72 33.4 9.8 2.09 .44 .77 34.1 10.0 2.09 .45

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.34 .75 2.34 .80 2.34 .85 2.34 .58 2.35 .61 2.35 .64 2.35 .43 2.35 .44 2.35 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .95 1.00 .72 .78 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.64 .76 .90 1.00 2.63 .82 .97 1.00 2.64 .87 1.00 1.00 2.64 .58 .73 .87 2.64 .62 .79 .94 2.64 .66 .85 .99 2.64 .43 .57 .70 2.65 .45 .61 .77 2.65 .46 .65 .83 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .98 .70 .76 .81 .55 .59 .62

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

Comp Motor kW 75_F L/s kBtuh kW Input 24_C 380 29.5 8.6 1.83 .72 470 30.6 9.0 1.83 .77 565 31.7 9.3 1.83 .82 380 31.5 9.2 1.83 .57 470 32.6 9.6 1.83 .59 565 33.3 9.8 1.83 .62 380 33.8 9.9 1.83 .42 470 34.9 10.2 1.83 .43 565 35.6 10.4 1.83 .45

85_F kBtuh kW 29_C .99 27.3 8.0 1.00 28.4 8.3 1.00 29.4 8.6 .84 29.1 8.5 .90 30.0 8.8 .96 30.7 9.0 .68 31.1 9.1 .74 32.0 9.4 .79 32.7 9.6

85_F kBtuh kW 29_C 1.00 26.2 7.7 1.00 27.2 8.0 1.00 28.2 8.3 .85 27.9 8.2 .92 28.7 8.4 .98 29.3 8.6 .69 29.8 8.7 .75 30.7 9.0 .81 31.2 9.1

HP26-030
Entering Wet Bulb Tempera ture

CB30M-31 - CB30U-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .44 1.83 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .74 .79 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.8 8.4 2.07 .73 1.00 30.0 8.8 2.08 .78 1.00 31.0 9.1 2.08 .84 .82 30.8 9.0 2.08 .57 .89 31.9 9.3 2.08 .60 .94 32.6 9.6 2.08 .63 .66 33.0 9.7 2.09 .43 .72 34.1 10.0 2.09 .44 .77 34.9 10.2 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.35 .85 2.35 .57 2.35 .61 2.36 .65 2.36 .43 2.36 .44 2.36 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .71 .77 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.64 .81 .97 1.00 2.64 .87 1.00 1.00 2.64 .58 .73 .87 2.64 .62 .79 .95 2.65 .66 .85 1.00 2.65 .43 .57 .70 2.65 .45 .61 .77 2.65 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 29.9 31.2 32.3 32.1 33.2 34.1 34.4 35.6 36.4 8.8 9.1 9.5 9.4 9.7 10.0 10.1 10.4 10.7

85_F kBtuh kW 29_C .99 27.7 8.1 1.00 28.8 8.4 1.00 29.8 8.7 .83 29.6 8.7 .90 30.5 8.9 .96 31.2 9.1 .68 31.7 9.3 .73 32.6 9.6 .79 33.3 9.8

85_F kBtuh kW 29_C 1.00 26.5 7.8 1.00 27.6 8.1 1.00 28.7 8.4 .85 28.3 8.3 .93 29.2 8.6 .98 29.8 8.7 .69 30.3 8.9 .75 31.2 9.1 .81 31.8 9.3

HP26-030 - CB30M-21/26 - CB30U-21/26 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.7 37.4 37.9 kW 10.8 11.0 11.1 Comp. Motor kW Input 2.50 2.28 2.11 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.20 1.98 1.81 25_F (-4_C) Total Heating Capacity kBtuh 21.1 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 1.89 1.67 1.51 5_F (-15_C) Total Heating Capacity kBtuh 15.2 15.9 16.4 kW 4.5 4.7 4.8 Comp. Motor kW Input 1.62 1.40 1.24 -15_F (-26_C) Total Heating Capacity kBtuh 7.3 8.0 8.5 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.26 1.04 .88

HP26-030 - CB30M-31 - CB30U-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 37.0 37.6 38.0 kW 10.8 11.0 11.1 Comp. Motor kW Input 2.33 2.13 1.99 45_F (7_C) Total Heating Capacity kBtuh 29.2 29.8 30.2 kW 8.6 8.7 8.9 Comp. Motor kW Input 2.17 1.97 1.83 25_F (-4_C) Total Heating Capacity kBtuh 21.0 21.6 22.0 kW 6.2 6.3 6.4 Comp. Motor kW Input 2.00 1.80 1.66 5_F (-15_C) Total Heating Capacity kBtuh 14.9 15.5 15.9 kW 4.4 4.5 4.7 Comp. Motor kW Input 1.81 1.61 1.47 -15_F (-26_C) Total Heating Capacity kBtuh 7.3 7.9 8.3 kW 2.1 2.3 2.4 Comp. Motor kW Input 1.37 1.17 1.03

HP26-030 - CB30M-21/26 - CB30U-21/26 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.28 2.21 2.13 2.06 2.02 1.98 1.88 1.77 1.72 1.67 1.62 1.59 1.56 1.49 1.40 1.31 1.22 1.13 1.04 .95 Total Output kBtuh 37.4 35.6 33.9 32.1 31.0 29.8 26.8 23.8 22.8 21.8 20.9 20.3 19.6 17.8 15.9 13.9 11.9 10.0 8.0 6.1 kW 11.0 10.4 9.9 9.4 9.1 8.7 7.9 7.0 6.7 6.4 6.1 5.9 5.7 5.2 4.7 4.1 3.5 2.9 2.3 1.8

HP26-030 - CB30M-31 - CB30U-31 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.13 2.10 2.06 2.02 2.00 1.97 1.90 1.83 1.82 1.80 1.78 1.77 1.76 1.72 1.61 1.50 1.39 1.28 1.17 1.06 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 23 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CB30M-41 - CB30U-41/46 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .43 1.82 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .98 .69 .74 .79 .54 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.8 8.4 2.07 .73 1.00 30.0 8.8 2.08 .78 1.00 31.1 9.1 2.08 .84 .82 30.9 9.1 2.08 .57 .89 31.9 9.3 2.08 .60 .95 32.7 9.6 2.09 .63 .66 33.1 9.7 2.09 .43 .72 34.2 10.0 2.09 .44 .77 35.0 10.3 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .58 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.35 .85 2.35 .57 2.35 .61 2.36 .64 2.35 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .71 .77 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.64 .81 .97 1.00 2.64 .87 1.00 1.00 2.64 .58 .73 .87 2.65 .62 .79 .95 2.65 .66 .85 1.00 2.65 .43 .57 .70 2.65 .45 .61 .77 2.65 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.0 31.3 32.3 32.2 33.4 34.2 34.6 35.8 36.6 8.8 9.2 9.5 9.4 9.8 10.0 10.1 10.5 10.7

85_F kBtuh kW 29_C .99 27.7 8.1 1.00 28.8 8.4 1.00 29.9 8.8 .83 29.6 8.7 .90 30.6 9.0 .97 31.3 9.2 .67 31.7 9.3 .73 32.7 9.6 .79 33.4 9.8

85_F kBtuh kW 29_C 1.00 26.5 7.8 1.00 27.6 8.1 1.00 28.8 8.4 .85 28.3 8.3 .93 29.2 8.6 .98 29.9 8.8 .69 30.4 8.9 .75 31.2 9.1 .81 31.9 9.3

HP26-030
Entering Wet Bulb Tempera ture

CB30M-46 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .43 1.82 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .98 .69 .74 .79 .54 .57 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.9 8.5 2.07 .73 1.00 30.1 8.8 2.08 .78 1.00 31.2 9.1 2.08 .84 .82 31.0 9.1 2.08 .57 .89 32.0 9.4 2.08 .60 .95 32.8 9.6 2.09 .63 .66 33.2 9.7 2.09 .42 .72 34.3 10.1 2.09 .44 .77 35.1 10.3 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.35 .85 2.35 .58 2.35 .61 2.36 .65 2.35 .43 2.36 .44 2.36 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .77 .83 .56 .59 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.64 .81 .97 1.00 2.64 .88 1.00 1.00 2.64 .58 .73 .87 2.65 .62 .79 .95 2.65 .66 .85 1.00 2.65 .43 .56 .70 2.65 .44 .61 .77 2.65 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.1 31.4 32.4 32.3 33.5 34.3 34.7 35.9 36.7 8.8 9.2 9.5 9.5 9.8 10.1 10.2 10.5 10.8

85_F kBtuh kW 29_C .99 27.8 8.1 1.00 28.9 8.5 1.00 30.0 8.8 .83 29.7 8.7 .90 30.7 9.0 .97 31.4 9.2 .67 31.8 9.3 .73 32.8 9.6 .79 33.5 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.7 8.1 1.00 28.9 8.5 .85 28.4 8.3 .93 29.3 8.6 .98 30.0 8.8 .69 30.5 8.9 .75 31.3 9.2 .81 32.0 9.4

HP26-030 - CB30M-41 - CB30U-41/46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 37.1 37.6 38.0 kW 10.9 11.0 11.1 Comp. Motor kW Input 2.26 2.06 1.91 45_F (7_C) Total Heating Capacity kBtuh 29.3 29.8 30.2 kW 8.6 8.7 8.9 Comp. Motor kW Input 2.12 1.92 1.77 25_F (-4_C) Total Heating Capacity kBtuh 21.1 21.6 22.0 kW 6.2 6.3 6.4 Comp. Motor kW Input 1.97 1.77 1.62 5_F (-15_C) Total Heating Capacity kBtuh 15.0 15.5 15.9 kW 4.4 4.5 4.7 Comp. Motor kW Input 1.80 1.60 1.45 -15_F (-26_C) Total Heating Capacity kBtuh 7.4 7.9 8.3 kW 2.2 2.3 2.4 Comp. Motor kW Input 1.36 1.16 1.01

HP26-030 - CB30M-46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 37.0 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.31 2.11 1.96 45_F (7_C) Total Heating Capacity kBtuh 29.2 29.8 30.3 kW 8.6 8.7 8.9 Comp. Motor kW Input 2.14 1.94 1.79 25_F (-4_C) Total Heating Capacity kBtuh 21.0 21.6 22.1 kW 6.2 6.3 6.5 Comp. Motor kW Input 1.97 1.77 1.62 5_F (-15_C) Total Heating Capacity kBtuh 14.9 15.5 16.0 kW 4.4 4.5 4.7 Comp. Motor kW Input 1.79 1.59 1.44 -15_F (-26_C) Total Heating Capacity kBtuh 7.3 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.36 1.16 1.01

HP26-030 - CB30M-41 - CB30U-41/46 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.06 2.03 2.00 1.96 1.94 1.92 1.86 1.80 1.78 1.77 1.76 1.75 1.74 1.71 1.60 1.49 1.38 1.27 1.16 1.05 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26-030 - CB30M-46 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.11 2.07 2.03 1.99 1.97 1.94 1.88 1.81 1.79 1.77 1.76 1.75 1.73 1.69 1.59 1.48 1.37 1.26 1.16 1.05 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 24 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CB31MV-41 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .43 1.82 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .98 .69 .74 .79 .54 .57 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.9 8.5 2.07 .73 1.00 30.1 8.8 2.08 .78 1.00 31.2 9.1 2.08 .84 .82 31.0 9.1 2.08 .57 .89 32.0 9.4 2.08 .60 .95 32.8 9.6 2.09 .63 .66 33.2 9.7 2.09 .42 .72 34.3 10.1 2.09 .44 .77 35.1 10.3 2.09 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.35 .85 2.35 .58 2.35 .61 2.36 .65 2.35 .43 2.36 .44 2.36 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .77 .83 .56 .59 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.64 .81 .97 1.00 2.64 .88 1.00 1.00 2.64 .58 .73 .87 2.65 .62 .79 .95 2.65 .66 .85 1.00 2.65 .43 .56 .70 2.65 .44 .61 .77 2.65 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.1 31.4 32.4 32.3 33.5 34.3 34.7 35.9 36.7 8.8 9.2 9.5 9.5 9.8 10.1 10.2 10.5 10.8

85_F kBtuh kW 29_C .99 27.8 8.1 1.00 28.9 8.5 1.00 30.0 8.8 .83 29.7 8.7 .90 30.7 9.0 .97 31.4 9.2 .67 31.8 9.3 .73 32.8 9.6 .79 33.5 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.7 8.1 1.00 28.9 8.5 .85 28.4 8.3 .93 29.3 8.6 .98 30.0 8.8 .69 30.5 8.9 .75 31.3 9.2 .81 32.0 9.4

HP26-030
Entering Wet Bulb Tempera ture

CVP10-31/EC10Q3 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .74 .79 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 27.9 8.2 2.05 .73 1.00 29.1 8.5 2.05 .78 1.00 30.1 8.8 2.06 .83 .82 29.8 8.7 2.05 .57 .89 30.8 9.0 2.06 .60 .95 31.6 9.3 2.06 .63 .66 32.0 9.4 2.06 .43 .72 33.0 9.7 2.07 .44 .77 33.7 9.9 2.07 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .98 .70 .76 .81 .55 .58 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.31 .74 2.31 .79 2.32 .85 2.32 .57 2.32 .61 2.33 .64 2.33 .43 2.33 .44 2.33 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .71 .77 .83 .56 .59 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.61 .75 .90 1.00 2.61 .81 .97 1.00 2.61 .87 1.00 1.00 2.61 .58 .73 .87 2.61 .62 .79 .94 2.62 .66 .85 .99 2.62 .43 .57 .70 2.62 .45 .60 .77 2.62 .46 .64 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

Comp Motor kW 75_F L/s kBtuh kW Input 24_C 380 29.0 8.5 1.81 .72 470 30.2 8.9 1.81 .77 565 31.2 9.1 1.81 .82 380 31.0 9.1 1.81 .56 470 32.1 9.4 1.81 .59 565 32.9 9.6 1.81 .62 380 33.3 9.8 1.81 .42 470 34.4 10.1 1.81 .43 565 35.2 10.3 1.81 .45

85_F kBtuh kW 29_C .98 26.9 7.9 1.00 28.0 8.2 1.00 29.0 8.5 .83 28.7 8.4 .90 29.6 8.7 .96 30.3 8.9 .68 30.7 9.0 .73 31.6 9.3 .79 32.3 9.5

85_F kBtuh kW 29_C 1.00 25.7 7.5 1.00 26.8 7.9 1.00 27.9 8.2 .85 27.4 8.0 .92 28.3 8.3 .98 29.0 8.5 .69 29.4 8.6 .75 30.3 8.9 .81 30.9 9.1

HP26-030 - CB31MV-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.8 37.4 37.8 kW 10.8 11.0 11.1 Comp. Motor kW Input 2.24 2.07 1.94 45_F (7_C) Total Heating Capacity kBtuh 28.9 29.5 29.9 kW 8.5 8.6 8.8 Comp. Motor kW Input 2.10 1.92 1.80 25_F (-4_C) Total Heating Capacity kBtuh 20.7 21.3 21.7 kW 6.1 6.2 6.4 Comp. Motor kW Input 1.95 1.77 1.65 5_F (-15_C) Total Heating Capacity kBtuh 14.6 15.2 15.6 kW 4.3 4.5 4.6 Comp. Motor kW Input 1.77 1.59 1.47 -15_F (-26_C) Total Heating Capacity kBtuh 7.1 7.7 8.1 kW 2.1 2.3 2.4 Comp. Motor kW Input 1.33 1.16 1.03

HP26-030 - CVP10-31/EC10Q3 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 35.4 35.9 36.6 kW 10.4 10.5 10.7 Comp. Motor kW Input 2.28 2.17 2.04 45_F (7_C) Total Heating Capacity kBtuh 28.4 28.9 29.6 kW 8.3 8.5 8.7 Comp. Motor kW Input 2.04 1.93 1.80 25_F (-4_C) Total Heating Capacity kBtuh 21.0 21.5 22.2 kW 6.2 6.3 6.5 Comp. Motor kW Input 1.78 1.67 1.54 5_F (-15_C) Total Heating Capacity kBtuh 15.4 15.9 16.6 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.55 1.44 1.31 -15_F (-26_C) Total Heating Capacity kBtuh 7.5 8.0 8.7 kW 2.2 2.3 2.5 Comp. Motor kW Input 1.17 1.06 .93

HP26-030 - CB31MV-41 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.07 2.04 2.00 1.97 1.95 1.92 1.86 1.80 1.79 1.77 1.76 1.75 1.74 1.70 1.59 1.49 1.38 1.27 1.16 1.05 Total Output kBtuh 37.4 35.5 33.7 31.8 30.7 29.5 26.4 23.4 22.3 21.3 20.2 19.6 18.9 17.0 15.2 13.3 11.4 9.6 7.7 5.9 kW 11.0 10.4 9.9 9.3 9.0 8.6 7.7 6.9 6.5 6.2 5.9 5.7 5.5 5.0 4.5 3.9 3.3 2.8 2.3 1.7

HP26-030 - CVP10-31 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.17 2.11 2.06 2.00 1.96 1.93 1.84 1.75 1.71 1.67 1.63 1.61 1.59 1.53 1.44 1.34 1.25 1.15 1.06 .97 Total Output kBtuh 35.9 34.2 32.6 31.0 30.0 28.9 26.0 23.2 22.4 21.5 20.7 20.2 19.5 17.9 15.9 14.0 12.0 10.0 8.0 6.1 kW 10.5 10.0 9.6 9.1 8.8 8.5 7.6 6.8 6.6 6.3 6.1 5.9 5.7 5.2 4.7 4.1 3.5 2.9 2.3 1.8

HP26 / Page 25 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CVP10-41/EC10Q3 - CVP10-46/EC10Q4 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .74 .79 .54 .57 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.2 8.3 2.05 .72 1.00 29.4 8.6 2.06 .78 1.00 30.5 8.9 2.06 .83 .82 30.2 8.9 2.06 .57 .88 31.3 9.2 2.06 .60 .94 32.1 9.4 2.07 .63 .66 32.4 9.5 2.07 .43 .71 33.5 9.8 2.07 .44 .77 34.3 10.1 2.07 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .75 .81 .55 .58 .62

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.32 .74 2.32 .80 2.33 .85 2.33 .58 2.33 .61 2.33 .64 2.33 .43 2.34 .44 2.34 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .71 .77 .83 .56 .59 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.61 .75 .90 1.00 2.61 .81 .97 1.00 2.62 .87 1.00 1.00 2.61 .58 .73 .86 2.62 .62 .79 .94 2.63 .66 .85 .99 2.62 .43 .56 .70 2.63 .44 .60 .76 2.63 .46 .65 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

Comp Motor kW 75_F L/s kBtuh kW Input 24_C 380 29.3 8.6 1.81 .72 470 30.6 9.0 1.81 .77 565 31.7 9.3 1.81 .81 380 31.5 9.2 1.81 .56 470 32.7 9.6 1.82 .59 565 33.5 9.8 1.81 .62 380 33.8 9.9 1.81 .43 470 35.0 10.3 1.81 .43 565 35.9 10.5 1.81 .45

85_F kBtuh kW 29_C .98 27.1 7.9 1.00 28.3 8.3 1.00 29.3 8.6 .83 29.0 8.5 .90 30.0 8.8 .96 30.7 9.0 .67 31.1 9.1 .73 32.1 9.4 .78 32.8 9.6

85_F kBtuh kW 29_C 1.00 26.0 7.6 1.00 27.1 7.9 1.00 28.2 8.3 .85 27.8 8.1 .92 28.7 8.4 .98 29.3 8.6 .68 29.8 8.7 .74 30.7 9.0 .80 31.3 9.2

HP26-030
Entering Wet Bulb Temperat ure

C26-31 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .43 1.83 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .92 .97 .69 .74 .79 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.8 8.4 2.07 .73 1.00 30.0 8.8 2.07 .78 1.00 31.0 9.1 2.08 .84 .82 30.8 9.0 2.08 .57 .89 31.8 9.3 2.08 .60 .94 32.6 9.6 2.08 .63 .66 33.0 9.7 2.08 .43 .72 34.0 10.0 2.09 .44 .77 34.8 10.2 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.34 .85 2.34 .57 2.35 .61 2.35 .65 2.35 .43 2.35 .44 2.36 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .72 .77 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.63 .81 .97 1.00 2.64 .87 1.00 1.00 2.64 .58 .73 .87 2.64 .62 .79 .95 2.64 .66 .85 .99 2.65 .43 .57 .70 2.65 .45 .61 .77 2.65 .46 .64 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 29.9 31.2 32.2 32.1 33.2 34.0 34.4 35.5 36.3 8.8 9.1 9.4 9.4 9.7 10.0 10.1 10.4 10.6

85_F kBtuh kW 29_C .98 27.7 8.1 1.00 28.8 8.4 1.00 29.8 8.7 .83 29.6 8.7 .90 30.5 8.9 .96 31.2 9.1 .68 31.7 9.3 .74 32.6 9.6 .79 33.3 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.6 8.1 1.00 28.7 8.4 .85 28.3 8.3 .92 29.2 8.6 .98 29.8 8.7 .69 30.3 8.9 .75 31.2 9.1 .81 31.8 9.3

HP26-030 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 35.4 35.9 36.6 kW 10.4 10.5 10.7 Comp. Motor kW Input 2.14 2.03 1.90 45_F (7_C) Total Heating Capacity kBtuh 28.4 28.9 29.6 kW 8.3 8.5 8.7 Comp. Motor kW Input 2.04 1.93 1.80 25_F (-4_C) Total Heating Capacity kBtuh 21.0 21.5 22.2 kW 6.2 6.3 6.5 Comp. Motor kW Input 1.93 1.82 1.69 5_F (-15_C) Total Heating Capacity kBtuh 15.4 15.9 16.6 kW 4.5 4.7 4.9 Comp. Motor kW Input 1.78 1.67 1.54 -15_F (-26_C) Total Heating Capacity kBtuh 7.5 8.0 8.7 kW 2.2 2.3 2.5 Comp. Motor kW Input 1.32 1.21 1.08

HP26-030 - C26-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.34 2.12 1.95 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.16 1.94 1.77 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.97 1.76 1.59 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.0 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.77 1.56 1.39 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.35 1.14 .97

HP26-030 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.03 2.01 1.98 1.96 1.95 1.93 1.87 1.82 1.82 1.82 1.82 1.82 1.81 1.79 1.67 1.55 1.44 1.32 1.21 1.09 Total Output kBtuh 35.9 34.2 32.6 31.0 30.0 28.9 26.0 23.2 22.4 21.5 20.7 20.2 19.5 17.9 15.9 14.0 12.0 10.0 8.0 6.1 kW 10.5 10.0 9.6 9.1 8.8 8.5 7.6 6.8 6.6 6.3 6.1 5.9 5.7 5.2 4.7 4.1 3.5 2.9 2.3 1.8

HP26-030 - C26-31 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.12 2.08 2.04 2.00 1.97 1.94 1.87 1.80 1.78 1.76 1.73 1.72 1.70 1.66 1.56 1.45 1.35 1.24 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 26 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

C26-41 - C33-38A/B COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .43 1.83 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .74 .79 .54 .57 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.8 8.4 2.07 .73 1.00 30.0 8.8 2.08 .78 1.00 31.0 9.1 2.08 .84 .82 30.8 9.0 2.08 .57 .88 31.9 9.3 2.08 .60 .94 32.7 9.6 2.08 .63 .66 33.1 9.7 2.09 .43 .72 34.1 10.0 2.09 .44 .77 34.9 10.2 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.35 .85 2.35 .57 2.35 .61 2.36 .64 2.36 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .95 1.00 .71 .77 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .91 1.00 2.64 .81 .97 1.00 2.64 .87 1.00 1.00 2.64 .59 .73 .87 2.64 .62 .79 .95 2.65 .66 .85 1.00 2.65 .43 .57 .70 2.65 .44 .61 .77 2.65 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.0 31.2 32.3 32.1 33.3 34.1 34.5 35.7 36.5 8.8 9.1 9.5 9.4 9.8 10.0 10.1 10.5 10.7

85_F kBtuh kW 29_C .98 27.7 8.1 1.00 28.8 8.4 1.00 29.9 8.8 .83 29.6 8.7 .91 30.6 9.0 .96 31.3 9.2 .67 31.7 9.3 .73 32.7 9.6 .79 33.3 9.8

85_F kBtuh kW 29_C 1.00 26.5 7.8 1.00 27.6 8.1 1.00 28.8 8.4 .85 28.3 8.3 .93 29.2 8.6 .98 29.9 8.8 .69 30.4 8.9 .75 31.3 9.2 .81 31.8 9.3

HP26-030
Entering Wet Bulb Tempera ture

C26-46 - C33-48B/C COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .63 1.83 .42 1.83 .43 1.82 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .98 .69 .74 .80 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 29.0 8.5 2.07 .73 1.00 30.2 8.9 2.08 .79 1.00 31.3 9.2 2.08 .84 .81 31.0 9.1 2.08 .57 .89 32.1 9.4 2.08 .60 .95 32.9 9.6 2.09 .64 .66 33.2 9.7 2.09 .43 .72 34.4 10.1 2.09 .44 .77 35.1 10.3 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .82 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.35 .80 2.35 .86 2.35 .58 2.36 .61 2.36 .65 2.36 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .84 .56 .60 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.64 .75 .91 1.00 2.64 .82 .98 1.00 2.64 .88 1.00 1.00 2.64 .58 .73 .87 2.65 .62 .79 .95 2.65 .66 .86 1.00 2.65 .43 .57 .70 2.65 .45 .61 .77 2.66 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.1 31.5 32.5 32.3 33.5 34.4 34.7 36.0 36.8 8.8 9.2 9.5 9.5 9.8 10.1 10.2 10.6 10.8

85_F kBtuh kW 29_C .99 27.8 8.1 1.00 28.9 8.5 1.00 30.1 8.8 .83 29.7 8.7 .91 30.7 9.0 .97 31.4 9.2 .67 31.9 9.3 .74 32.8 9.6 .79 33.5 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.7 8.1 1.00 29.0 8.5 .85 28.4 8.3 .93 29.4 8.6 .99 30.0 8.8 .69 30.5 8.9 .75 31.4 9.2 .81 32.0 9.4

HP26-030 - C26-41 - C33-38A/B HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.2 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.34 2.12 1.96 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.4 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.16 1.94 1.78 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.2 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.98 1.76 1.59 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.1 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.78 1.56 1.39 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.5 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.36 1.14 .97

HP26-030 - C26-46 - C33-48B/C HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.34 2.12 1.96 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.16 1.94 1.78 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.97 1.76 1.60 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.0 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.77 1.56 1.40 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.35 1.14 .98

HP26-030 - C26-41 - C33-38A/B HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.12 2.08 2.04 2.00 1.97 1.94 1.87 1.80 1.78 1.76 1.73 1.72 1.70 1.66 1.56 1.45 1.35 1.24 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26-030 - C26-46 - C33-48B/C HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.12 2.08 2.04 2.00 1.97 1.94 1.87 1.80 1.78 1.76 1.73 1.72 1.70 1.66 1.56 1.45 1.35 1.24 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 27 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CR26-36N/W-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.83 .44 1.83 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .97 .69 .74 .79 .54 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.9 8.5 2.07 .73 1.00 30.1 8.8 2.08 .78 1.00 31.1 9.1 2.08 .84 .82 30.9 9.1 2.08 .57 .89 31.9 9.3 2.08 .60 .94 32.7 9.6 2.08 .63 .66 33.1 9.7 2.09 .43 .72 34.1 10.0 2.09 .44 .77 34.9 10.2 2.09 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.34 .80 2.34 .85 2.34 .58 2.35 .61 2.35 .64 2.35 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .72 .77 .83 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .75 .90 1.00 2.63 .82 .97 1.00 2.64 .87 1.00 1.00 2.64 .58 .73 .87 2.64 .62 .79 .94 2.65 .66 .85 .99 2.65 .43 .57 .70 2.65 .44 .61 .77 2.65 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.0 31.3 32.3 32.1 33.3 34.1 34.5 35.6 36.4 8.8 9.2 9.5 9.4 9.8 10.0 10.1 10.4 10.7

85_F kBtuh kW 29_C .99 27.8 8.1 1.00 28.9 8.5 1.00 29.9 8.8 .83 29.6 8.7 .90 30.6 9.0 .96 31.3 9.2 .68 31.7 9.3 .73 32.7 9.6 .79 33.4 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.7 8.1 1.00 28.8 8.4 .85 28.4 8.3 .92 29.3 8.6 .98 29.9 8.8 .69 30.4 8.9 .75 31.3 9.2 .81 31.9 9.3

HP26-030
Entering Wet Bulb Tempera ture

CH23-41 - CH33-36A-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .93 .98 .70 .75 .80 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 28.3 8.3 2.07 .73 1.00 29.5 8.6 2.08 .79 1.00 30.5 8.9 2.08 .84 .82 30.2 8.9 2.08 .57 .89 31.3 9.2 2.08 .61 .95 32.0 9.4 2.08 .64 .67 32.4 9.5 2.09 .43 .72 33.4 9.8 2.09 .44 .78 34.1 10.0 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .71 .76 .82 .55 .59 .63 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .75 2.34 .80 2.34 .86 2.34 .58 2.35 .62 2.35 .65 2.35 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .96 1.00 .72 .78 .84 .56 .60 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .76 .91 1.00 2.63 .82 .98 1.00 2.64 .88 1.00 1.00 2.64 .59 .73 .87 2.64 .63 .80 .95 2.65 .66 .86 1.00 2.65 .43 .57 .71 2.65 .45 .61 .77 2.65 .46 .65 .84

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

Comp Motor kW 75_F L/s kBtuh kW Input 24_C 380 29.4 8.6 1.83 .72 470 30.7 9.0 1.83 .77 565 31.7 9.3 1.83 .82 380 31.5 9.2 1.83 .57 470 32.6 9.6 1.83 .60 565 33.4 9.8 1.83 .63 380 33.8 9.9 1.83 .42 470 34.9 10.2 1.83 .44 565 35.7 10.5 1.83 .45

85_F kBtuh kW 29_C .99 27.2 8.0 1.00 28.4 8.3 1.00 29.4 8.6 .84 29.0 8.5 .91 30.0 8.8 .97 30.7 9.0 .68 31.1 9.1 .74 32.0 9.4 .80 32.6 9.6

85_F kBtuh kW 29_C 1.00 26.1 7.6 1.00 27.2 8.0 1.00 28.3 8.3 .86 27.8 8.1 .93 28.7 8.4 .98 29.3 8.6 .69 29.8 8.7 .76 30.6 9.0 .81 31.2 9.1

HP26-030 - CR26-36N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.2 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.34 2.12 1.96 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.4 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.16 1.94 1.78 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.2 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.97 1.76 1.59 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.1 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.77 1.56 1.39 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.5 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.35 1.14 .97

HP26-030 - CH23-41 - CH33-36A-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.37 2.16 1.99 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.20 1.98 1.82 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 2.01 1.80 1.63 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.0 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.82 1.61 1.44 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.39 1.17 1.01

HP26-030 - CR26-36N/W-F HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.12 2.08 2.04 2.00 1.97 1.94 1.87 1.80 1.78 1.76 1.73 1.72 1.70 1.66 1.56 1.45 1.35 1.24 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26-030 - CH23-41 - CH33-36A-F HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.16 2.12 2.07 2.03 2.01 1.98 1.91 1.84 1.82 1.80 1.78 1.77 1.75 1.71 1.61 1.50 1.39 1.28 1.17 1.06 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 28 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-030
Entering Wet Bulb Tempera ture

CH23-51 - CH33-42B-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .63 1.83 .42 1.83 .44 1.83 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .92 .98 .69 .75 .80 .55 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.8 8.4 2.08 .73 1.00 30.0 8.8 2.08 .79 1.00 31.1 9.1 2.08 .84 .82 30.8 9.0 2.08 .57 .89 31.9 9.3 2.08 .60 .95 32.6 9.6 2.09 .64 .67 33.0 9.7 2.09 .43 .72 34.1 10.0 2.09 .44 .78 34.8 10.2 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .82 .55 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .75 2.34 .80 2.35 .86 2.35 .58 2.35 .61 2.36 .65 2.36 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .72 .78 .84 .56 .60 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.63 .76 .91 1.00 2.64 .82 .98 1.00 2.64 .88 1.00 1.00 2.64 .58 .73 .87 2.64 .62 .79 .95 2.65 .66 .86 1.00 2.65 .43 .57 .70 2.65 .45 .61 .77 2.65 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 29.9 31.2 32.3 32.1 33.2 34.1 34.4 35.6 36.4 8.8 9.1 9.5 9.4 9.7 10.0 10.1 10.4 10.7

85_F kBtuh kW 29_C .99 27.7 8.1 1.00 28.8 8.4 1.00 29.9 8.8 .83 29.5 8.6 .91 30.5 8.9 .97 31.2 9.1 .68 31.6 9.3 .74 32.6 9.6 .79 33.3 9.8

85_F kBtuh kW 29_C 1.00 26.5 7.8 1.00 27.6 8.1 1.00 28.8 8.4 .85 28.3 8.3 .93 29.2 8.6 .99 29.8 8.7 .69 30.3 8.9 .75 31.2 9.1 .81 31.8 9.3

HP26-030
Entering Wet Bulb Tempera ture

CH23-65 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 1.83 .72 1.83 .77 1.83 .82 1.83 .56 1.83 .59 1.83 .62 1.83 .42 1.82 .43 1.82 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .85 .92 .98 .69 .74 .80 .54 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 28.9 8.5 2.07 .73 1.00 30.2 8.9 2.08 .79 1.00 31.3 9.2 2.08 .84 .81 31.0 9.1 2.08 .57 .89 32.1 9.4 2.09 .60 .95 32.9 9.6 2.09 .64 .66 33.3 9.8 2.09 .43 .72 34.4 10.1 2.09 .44 .77 35.1 10.3 2.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .94 .99 .70 .76 .81 .55 .58 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.34 .74 2.35 .80 2.35 .86 2.35 .58 2.36 .61 2.36 .65 2.36 .43 2.36 .44 2.36 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .96 1.00 .71 .78 .84 .56 .60 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 2.64 .75 .90 1.00 2.64 .82 .98 1.00 2.64 .88 1.00 1.00 2.64 .58 .73 .87 2.65 .62 .80 .95 2.65 .66 .86 1.00 2.65 .43 .57 .70 2.65 .45 .61 .77 2.66 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 800 1000 1200 800 1000 1200 800 1000 1200

L/s kBtuh kW 380 470 565 380 470 565 380 470 565 30.1 31.4 32.6 32.3 33.5 34.4 34.7 36.0 36.9 8.8 9.2 9.6 9.5 9.8 10.1 10.2 10.6 10.8

85_F kBtuh kW 29_C .99 27.8 8.1 1.00 28.9 8.5 1.00 30.1 8.8 .83 29.7 8.7 .91 30.7 9.0 .97 31.4 9.2 .67 31.8 9.3 .73 32.8 9.6 .79 33.5 9.8

85_F kBtuh kW 29_C 1.00 26.6 7.8 1.00 27.7 8.1 1.00 28.9 8.5 .85 28.4 8.3 .93 29.3 8.6 .99 30.0 8.8 .69 30.5 8.9 .75 31.4 9.2 .81 32.0 9.4

HP26-030 - CH23-51 - CH33-42B-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.34 2.12 1.96 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.13 1.91 1.75 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.89 1.67 1.50 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.0 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.78 1.56 1.39 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.36 1.14 .97

HP26-030 - CH23-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 800 1000 1200 L/s 380 470 565 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 36.9 37.6 38.1 kW 10.8 11.0 11.2 Comp. Motor kW Input 2.28 2.07 1.90 45_F (7_C) Total Heating Capacity kBtuh 29.1 29.8 30.3 kW 8.5 8.7 8.9 Comp. Motor kW Input 2.09 1.88 1.71 25_F (-4_C) Total Heating Capacity kBtuh 20.9 21.6 22.1 kW 6.1 6.3 6.5 Comp. Motor kW Input 1.87 1.66 1.49 5_F (-15_C) Total Heating Capacity kBtuh 14.8 15.5 16.0 kW 4.3 4.5 4.7 Comp. Motor kW Input 1.78 1.57 1.40 -15_F (-26_C) Total Heating Capacity kBtuh 7.2 7.9 8.4 kW 2.1 2.3 2.5 Comp. Motor kW Input 1.35 1.14 .97

HP26-030 - CH23-51 - CH33-42B-F HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.12 2.08 2.04 2.00 1.97 1.91 1.75 1.60 1.63 1.67 1.70 1.72 1.70 1.66 1.56 1.45 1.35 1.24 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26-030 - CH23-65 HEATING PERFORMANCE at 1000 cfm (470 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.07 2.03 1.99 1.96 1.94 1.88 1.73 1.58 1.62 1.66 1.70 1.72 1.71 1.67 1.57 1.46 1.35 1.25 1.14 1.03 Total Output kBtuh 37.6 35.8 33.9 32.1 31.0 29.8 26.7 23.7 22.7 21.6 20.6 20.0 19.3 17.4 15.5 13.6 11.7 9.8 7.9 6.0 kW 11.0 10.5 9.9 9.4 9.1 8.7 7.8 6.9 6.7 6.3 6.0 5.9 5.7 5.1 4.5 4.0 3.4 2.9 2.3 1.8

HP26 / Page 29 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CB30M-31 - CB30U-31 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .81 2.25 .57 2.26 .60 2.26 .62 2.27 .43 2.27 .44 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.1 9.7 2.53 .74 1.00 34.2 10.0 2.54 .78 1.00 35.2 10.3 2.54 .83 .83 35.3 10.3 2.54 .58 .89 36.2 10.6 2.55 .60 .94 37.0 10.8 2.55 .63 .68 37.8 11.1 2.56 .43 .72 38.7 11.3 2.56 .44 .77 39.4 11.5 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.87 .80 2.87 .85 2.88 .58 2.88 .61 2.88 .64 2.89 .43 2.90 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 85_F 75_F 80_F 85_F kBtuh kW Input 29_C 24_C 27_C 29_C 1.00 30.5 8.9 3.24 .77 .92 1.00 1.00 31.6 9.3 3.24 .82 .97 1.00 1.00 32.6 9.6 3.25 .86 1.00 1.00 .87 32.5 9.5 3.26 .59 .74 .88 .92 33.3 9.8 3.26 .62 .79 .95 .97 33.9 9.9 3.26 .65 .84 .99 .70 34.8 10.2 3.27 .43 .57 .72 .75 35.6 10.4 3.28 .45 .61 .77 .80 36.2 10.6 3.28 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.3 35.4 36.4 36.6 37.6 38.4 39.2 40.2 40.9 10.1 10.4 10.7 10.7 11.0 11.3 11.5 11.8 12.0

85_F kBtuh kW 29_C .99 31.9 9.3 1.00 32.9 9.6 1.00 33.9 9.9 .85 33.9 9.9 .91 34.8 10.2 .95 35.5 10.4 .69 36.3 10.6 .74 37.2 10.9 .78 37.8 11.1

HP26-036
Entering Wet Bulb Tempera ture

CB29M-46 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .82 2.25 .57 2.26 .59 2.26 .62 2.27 .43 2.27 .43 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.5 9.8 2.53 .74 1.00 34.6 10.1 2.54 .78 1.00 35.6 10.4 2.54 .83 .83 35.8 10.5 2.54 .58 .89 36.7 10.8 2.55 .60 .94 37.4 11.0 2.55 .63 .68 38.3 11.2 2.56 .43 .72 39.2 11.5 2.56 .44 .77 39.9 11.7 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.87 .80 2.87 .85 2.88 .58 2.88 .61 2.88 .64 2.89 .43 2.90 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.24 .82 .97 1.00 3.25 .87 1.00 1.00 3.26 .59 .74 .89 3.26 .62 .80 .95 3.26 .65 .84 .99 3.27 .43 .58 .72 3.28 .45 .61 .77 3.28 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.8 35.9 36.9 37.1 38.1 38.8 39.7 40.7 41.4 10.2 10.5 10.8 10.9 11.2 11.4 11.6 11.9 12.1

85_F kBtuh kW 29_C .99 32.3 9.5 1.00 33.3 9.8 1.00 34.3 10.1 .85 34.4 10.1 .91 35.2 10.3 .96 35.9 10.5 .69 36.8 10.8 .74 37.7 11.0 .78 38.3 11.2

85_F kBtuh kW 29_C 1.00 30.9 9.1 1.00 32.0 9.4 1.00 33.0 9.7 .87 32.9 9.6 .92 33.7 9.9 .97 34.4 10.1 .70 35.2 10.3 .75 36.0 10.6 .80 36.6 10.7

HP26-036 - CB30M-31 - CB30U-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.4 44.0 44.5 kW 12.7 12.9 13.0 Comp. Motor kW Input 2.81 2.62 2.48 45_F (7_C) Total Heating Capacity kBtuh 33.8 34.4 34.9 kW 9.9 10.1 10.2 Comp. Motor kW Input 2.59 2.40 2.26 25_F (-4_C) Total Heating Capacity kBtuh 23.6 24.2 24.7 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.37 2.18 2.03 5_F (-15_C) Total Heating Capacity kBtuh 17.4 18.0 18.5 kW 5.1 5.3 5.4 Comp. Motor kW Input 2.11 1.92 1.78 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.59 1.40 1.26

HP26-036 - CB29M-46 - HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.8 44.4 44.9 kW 12.8 13.0 13.2 Comp. Motor kW Input 2.88 2.68 2.51 45_F (7_C) Total Heating Capacity kBtuh 34.1 34.7 35.2 kW 10.0 10.2 10.3 Comp. Motor kW Input 2.64 2.44 2.27 25_F (-4_C) Total Heating Capacity kBtuh 23.8 24.4 24.9 kW 7.0 7.2 7.3 Comp. Motor kW Input 2.39 2.19 2.02 5_F (-15_C) Total Heating Capacity kBtuh 17.5 18.1 18.6 kW 5.1 5.3 5.5 Comp. Motor kW Input 2.12 1.91 1.75 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.61 1.40 1.24

HP26-036 - CB30M-31 - CB30U-31 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.62 2.57 2.52 2.46 2.43 2.40 2.33 2.25 2.22 2.18 2.14 2.12 2.10 2.05 1.92 1.79 1.66 1.53 1.40 1.27 Total Output kBtuh 44.0 41.8 39.7 37.5 36.2 34.4 29.9 25.4 24.8 24.2 23.6 23.2 22.3 20.2 18.0 15.8 13.6 11.4 9.2 7.0 kW 12.9 12.3 11.6 11.0 10.6 10.1 8.8 7.4 7.3 7.1 6.9 6.8 6.5 5.9 5.3 4.6 4.0 3.3 2.7 2.1

HP26-036 - CB29M-46 - HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.68 2.62 2.56 2.51 2.47 2.44 2.35 2.27 2.23 2.19 2.15 2.12 2.10 2.04 1.91 1.79 1.66 1.53 1.40 1.28 Total Output kBtuh 44.4 42.2 40.0 37.8 36.5 34.7 30.2 25.6 25.0 24.4 23.8 23.4 22.5 20.3 18.1 15.9 13.7 11.5 9.2 7.0 kW 13.0 12.4 11.7 11.1 10.7 10.2 8.9 7.5 7.3 7.2 7.0 6.9 6.6 5.9 5.3 4.7 4.0 3.4 2.7 2.1

HP26 / Page 30 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CB29M-51 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.25 .73 2.25 .77 2.26 .81 2.26 .57 2.26 .60 2.27 .62 2.27 .43 2.28 .44 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 34.0 10.0 2.54 .74 1.00 35.1 10.3 2.54 .78 1.00 36.1 10.6 2.55 .83 .83 36.3 10.6 2.55 .58 .89 37.3 10.9 2.55 .60 .94 38.0 11.1 2.56 .63 .67 38.8 11.4 2.56 .43 .72 39.8 11.7 2.56 .44 .77 40.5 11.9 2.57 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.87 .75 2.87 .80 2.88 .84 2.88 .58 2.88 .61 2.89 .64 2.90 .43 2.90 .44 2.91 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 1.00 .73 .77 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.25 .82 .97 1.00 3.26 .86 1.00 1.00 3.25 .59 .74 .88 3.26 .62 .79 .95 3.27 .65 .84 .99 3.28 .43 .57 .72 3.28 .45 .61 .77 3.29 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.2 36.4 37.4 37.6 38.7 39.4 40.3 41.3 42.1 10.3 10.7 11.0 11.0 11.3 11.5 11.8 12.1 12.3

85_F kBtuh kW 29_C .99 32.7 9.6 1.00 33.8 9.9 1.00 34.7 10.2 .85 34.8 10.2 .91 35.8 10.5 .96 36.4 10.7 .69 37.3 10.9 .74 38.2 11.2 .78 38.9 11.4

85_F kBtuh kW 29_C 1.00 31.3 9.2 1.00 32.4 9.5 1.00 33.4 9.8 .87 33.4 9.8 .93 34.2 10.0 .98 34.8 10.2 .70 35.7 10.5 .75 36.6 10.7 .80 37.2 10.9

HP26-036
Entering Wet Bulb Tempera ture

CB30M-41 - CB30U-41/46 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.25 .73 2.25 .77 2.26 .81 2.26 .57 2.26 .59 2.27 .62 2.27 .43 2.28 .44 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.6 9.8 2.54 .74 1.00 34.8 10.2 2.54 .78 1.00 35.7 10.5 2.55 .83 .83 35.9 10.5 2.55 .58 .89 36.9 10.8 2.55 .60 .94 37.6 11.0 2.56 .63 .67 38.4 11.3 2.56 .43 .72 39.4 11.5 2.56 .44 .76 40.1 11.8 2.57 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.87 .75 2.87 .80 2.88 .85 2.88 .58 2.88 .61 2.89 .64 2.90 .43 2.90 .44 2.91 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .72 .77 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.25 .82 .98 1.00 3.26 .87 1.00 1.00 3.25 .59 .74 .88 3.26 .62 .79 .95 3.27 .65 .84 .99 3.28 .43 .57 .71 3.28 .44 .61 .77 3.29 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.9 36.0 37.0 37.3 38.3 39.0 39.9 40.9 41.6 10.2 10.6 10.8 10.9 11.2 11.4 11.7 12.0 12.2

85_F kBtuh kW 29_C .99 32.3 9.5 1.00 33.4 9.8 1.00 34.4 10.1 .85 34.5 10.1 .91 35.4 10.4 .96 36.1 10.6 .69 36.9 10.8 .74 37.8 11.1 .78 38.5 11.3

85_F kBtuh kW 29_C 1.00 31.0 9.1 1.00 32.0 9.4 1.00 33.1 9.7 .86 33.0 9.7 .93 33.9 9.9 .98 34.5 10.1 .70 35.4 10.4 .75 36.2 10.6 .80 36.8 10.8

HP26-036 - CB29M-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.9 44.6 45.2 kW 12.9 13.1 13.2 Comp. Motor kW Input 2.79 2.56 2.37 45_F (7_C) Total Heating Capacity kBtuh 34.3 35.0 35.6 kW 10.1 10.3 10.4 Comp. Motor kW Input 2.60 2.37 2.18 25_F (-4_C) Total Heating Capacity kBtuh 24.0 24.7 25.3 kW 7.0 7.2 7.4 Comp. Motor kW Input 2.41 2.18 1.99 5_F (-15_C) Total Heating Capacity kBtuh 17.8 18.5 19.1 kW 5.2 5.4 5.6 Comp. Motor kW Input 2.17 1.94 1.75 -15_F (-26_C) Total Heating Capacity kBtuh 8.7 9.4 10.0 kW 2.5 2.8 2.9 Comp. Motor kW Input 1.64 1.41 1.23

HP26-036 - CB30M-41 - CB30U-41/46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.7 44.2 44.6 kW 12.8 13.0 13.1 Comp. Motor kW Input 2.83 2.55 2.80 45_F (7_C) Total Heating Capacity kBtuh 34.1 34.6 35.0 kW 10.0 10.1 10.3 Comp. Motor kW Input 2.62 2.34 2.60 25_F (-4_C) Total Heating Capacity kBtuh 23.9 24.4 24.8 kW 7.0 7.2 7.3 Comp. Motor kW Input 2.41 2.13 2.39 5_F (-15_C) Total Heating Capacity kBtuh 17.6 18.1 18.5 kW 5.2 5.3 5.4 Comp. Motor kW Input 2.16 1.88 2.14 -15_F (-26_C) Total Heating Capacity kBtuh 8.7 9.2 9.6 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.66 1.38 1.63

HP26-036 - CB29M-51 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.56 2.51 2.47 2.42 2.40 2.37 2.30 2.23 2.20 2.18 2.15 2.13 2.11 2.07 1.94 1.81 1.67 1.54 1.41 1.28 Total Output kBtuh 44.6 42.4 40.3 38.1 36.8 35.0 30.4 25.9 25.3 24.7 24.2 23.8 22.9 20.8 18.5 16.2 14.0 11.7 9.4 7.1 kW 13.1 12.4 11.8 11.2 10.8 10.3 8.9 7.6 7.4 7.2 7.1 7.0 6.7 6.1 5.4 4.7 4.1 3.4 2.8 2.1

HP26-036 - CB30M-41 - CB30U-41/46 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.55 2.50 2.45 2.40 2.37 2.34 2.27 2.20 2.16 2.13 2.10 2.08 2.06 2.01 1.88 1.76 1.63 1.50 1.38 1.25 Total Output kBtuh 44.2 42.0 39.9 37.7 36.4 34.6 30.1 25.6 25.0 24.4 23.8 23.4 22.5 20.4 18.1 15.9 13.7 11.5 9.2 7.0 kW 13.0 12.3 11.7 11.0 10.7 10.1 8.8 7.5 7.3 7.2 7.0 6.9 6.6 6.0 5.3 4.7 4.0 3.4 2.7 2.1

HP26 / Page 31 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CB30M-46 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.25 .73 2.25 .77 2.26 .81 2.26 .57 2.26 .59 2.27 .62 2.27 .43 2.28 .44 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.6 9.8 2.54 .74 1.00 34.8 10.2 2.54 .78 1.00 35.7 10.5 2.55 .83 .83 35.9 10.5 2.55 .58 .89 36.9 10.8 2.55 .60 .94 37.6 11.0 2.56 .63 .67 38.4 11.3 2.56 .43 .72 39.4 11.5 2.56 .44 .76 40.1 11.8 2.57 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.87 .75 2.87 .80 2.88 .85 2.88 .58 2.88 .61 2.89 .64 2.90 .43 2.90 .44 2.91 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .72 .77 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.25 .82 .98 1.00 3.26 .87 1.00 1.00 3.25 .59 .74 .88 3.26 .62 .79 .95 3.27 .65 .84 .99 3.28 .43 .57 .71 3.28 .44 .61 .77 3.29 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.9 36.0 37.0 37.3 38.3 39.0 39.9 40.9 41.6 10.2 10.6 10.8 10.9 11.2 11.4 11.7 12.0 12.2

85_F kBtuh kW 29_C .99 32.3 9.5 1.00 33.4 9.8 1.00 34.4 10.1 .85 34.5 10.1 .91 35.4 10.4 .96 36.1 10.6 .69 36.9 10.8 .74 37.8 11.1 .78 38.5 11.3

85_F kBtuh kW 29_C 1.00 31.0 9.1 1.00 32.0 9.4 1.00 33.1 9.7 .86 33.0 9.7 .93 33.9 9.9 .98 34.5 10.1 .70 35.4 10.4 .75 36.2 10.6 .80 36.8 10.8

HP26-036
Entering Wet Bulb Tempera ture

CB31MV-41 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.25 .73 2.25 .77 2.26 .81 2.26 .57 2.26 .59 2.27 .62 2.27 .43 2.28 .44 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.8 9.9 2.54 .74 1.00 35.0 10.3 2.54 .79 1.00 35.9 10.5 2.55 .83 .83 36.1 10.6 2.55 .58 .89 37.1 10.9 2.55 .60 .94 37.8 11.1 2.56 .63 .68 38.7 11.3 2.56 .43 .72 39.7 11.6 2.56 .44 .77 40.4 11.8 2.57 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.87 .75 2.87 .80 2.88 .85 2.88 .58 2.88 .61 2.89 .64 2.90 .43 2.90 .44 2.91 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .73 .78 .82 .56 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .76 .92 1.00 3.25 .82 .98 1.00 3.26 .86 1.00 1.00 3.25 .59 .74 .88 3.26 .62 .79 .95 3.27 .65 .84 .99 3.28 .43 .58 .72 3.28 .45 .61 .77 3.29 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.1 36.3 37.2 37.5 38.5 39.3 40.1 41.1 41.9 10.3 10.6 10.9 11.0 11.3 11.5 11.8 12.0 12.3

85_F kBtuh kW 29_C .99 32.5 9.5 1.00 33.6 9.8 1.00 34.6 10.1 .85 34.7 10.2 .91 35.6 10.4 .96 36.3 10.6 .69 37.2 10.9 .73 38.1 11.2 .78 38.7 11.3

85_F kBtuh kW 29_C 1.00 31.2 9.1 1.00 32.2 9.4 1.00 33.3 9.8 .86 33.2 9.7 .93 34.1 10.0 .97 34.7 10.2 .70 35.6 10.4 .75 36.4 10.7 .80 37.0 10.8

HP26-036 - CB30M-46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.5 44.0 44.4 kW 12.7 12.9 13.0 Comp. Motor kW Input 2.73 2.55 2.40 45_F (7_C) Total Heating Capacity kBtuh 33.9 34.4 34.8 kW 9.9 10.1 10.2 Comp. Motor kW Input 2.53 2.35 2.21 25_F (-4_C) Total Heating Capacity kBtuh 23.7 24.2 24.6 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.33 2.15 2.00 5_F (-15_C) Total Heating Capacity kBtuh 17.5 18.0 18.4 kW 5.1 5.3 5.4 Comp. Motor kW Input 2.09 1.91 1.76 -15_F (-26_C) Total Heating Capacity kBtuh 8.7 9.2 9.6 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.57 1.39 1.24

HP26-036 - CB31MV-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.1 43.6 44.1 kW 12.6 12.8 12.9 Comp. Motor kW Input 2.68 2.50 2.37 45_F (7_C) Total Heating Capacity kBtuh 33.5 34.0 34.5 kW 9.8 10.0 10.1 Comp. Motor kW Input 2.49 2.31 2.18 25_F (-4_C) Total Heating Capacity kBtuh 23.3 23.8 24.3 kW 6.8 7.0 7.1 Comp. Motor kW Input 2.30 2.12 1.99 5_F (-15_C) Total Heating Capacity kBtuh 17.1 17.6 18.1 kW 5.0 5.2 5.3 Comp. Motor kW Input 2.06 1.88 1.75 -15_F (-26_C) Total Heating Capacity kBtuh 8.5 9.0 9.5 kW 2.5 2.6 2.8 Comp. Motor kW Input 1.55 1.37 1.24

HP26-036 - CB30M-46 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.55 2.50 2.45 2.41 2.38 2.35 2.28 2.21 2.18 2.15 2.12 2.10 2.08 2.03 1.91 1.78 1.65 1.52 1.39 1.26 Total Output kBtuh 44.0 41.8 39.7 37.5 36.2 34.4 29.9 25.4 24.8 24.2 23.6 23.2 22.3 20.2 18.0 15.8 13.6 11.4 9.2 7.0 kW 12.9 12.3 11.6 11.0 10.6 10.1 8.8 7.4 7.3 7.1 6.9 6.8 6.5 5.9 5.3 4.6 4.0 3.3 2.7 2.1

HP26-036 - CB31MV-41 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.50 2.46 2.41 2.37 2.34 2.31 2.25 2.18 2.15 2.12 2.09 2.07 2.06 2.01 1.88 1.76 1.63 1.50 1.37 1.25 Total Output kBtuh 43.6 41.4 39.3 37.1 35.8 34.0 29.6 25.1 24.5 23.8 23.2 22.8 21.9 19.8 17.6 15.5 13.3 11.1 9.0 6.8 kW 12.8 12.1 11.5 10.9 10.5 10.0 8.7 7.4 7.2 7.0 6.8 6.7 6.4 5.8 5.2 4.5 3.9 3.3 2.6 2.0

HP26 / Page 32 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CVP10-31/EC10Q3 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.24 .77 2.25 .82 2.25 .57 2.25 .59 2.26 .62 2.26 .43 2.27 .44 2.27 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 32.6 9.6 2.53 .74 1.00 33.6 9.8 2.53 .78 1.00 34.6 10.1 2.54 .83 .84 34.7 10.2 2.53 .58 .89 35.6 10.4 2.54 .60 .94 36.3 10.6 2.55 .63 .68 37.1 10.9 2.55 .43 .72 38.0 11.1 2.55 .44 .77 38.6 11.3 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.85 .76 2.86 .80 2.87 .85 2.87 .58 2.87 .61 2.88 .64 2.88 .43 2.89 .44 2.89 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 85_F 75_F 80_F 85_F kBtuh kW Input 29_C 24_C 27_C 29_C 1.00 30.0 8.8 3.23 .77 .92 1.00 1.00 31.1 9.1 3.24 .82 .97 1.00 1.00 32.1 9.4 3.24 .87 1.00 1.00 .87 31.9 9.3 3.25 .59 .74 .88 .92 32.7 9.6 3.25 .62 .80 .95 .97 33.4 9.8 3.25 .65 .84 .99 .70 34.2 10.0 3.26 .43 .58 .72 .75 35.0 10.3 3.27 .45 .61 .77 .80 35.5 10.4 3.28 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 33.7 34.8 35.7 36.0 36.9 37.6 38.4 39.4 40.1 9.9 10.2 10.5 10.6 10.8 11.0 11.3 11.5 11.8

85_F kBtuh kW 29_C .99 31.3 9.2 1.00 32.4 9.5 1.00 33.3 9.8 .85 33.4 9.8 .91 34.2 10.0 .96 34.9 10.2 .69 35.7 10.5 .74 36.5 10.7 .78 37.1 10.9

HP26-036
Entering Wet Bulb Tempera ture

CVP10-41/EC10Q3 - CVP10-46/EC10Q4 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .81 2.25 .57 2.26 .59 2.26 .62 2.26 .42 2.27 .43 2.27 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .92 .97 .70 .74 .79 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.0 9.7 2.53 .74 1.00 34.1 10.0 2.53 .78 1.00 35.1 10.3 2.54 .83 .83 35.2 10.3 2.54 .57 .89 36.1 10.6 2.54 .60 .94 36.9 10.8 2.55 .63 .67 37.7 11.0 2.55 .43 .72 38.6 11.3 2.56 .44 .76 39.3 11.5 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .71 .76 .80 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.86 .80 2.86 .84 2.87 .58 2.87 .61 2.88 .64 2.89 .43 2.89 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .72 .77 .82 .56 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 85_F 75_F 80_F 85_F kBtuh kW Input 29_C 24_C 27_C 29_C 1.00 30.4 8.9 3.23 .76 .91 1.00 1.00 31.4 9.2 3.24 .82 .97 1.00 1.00 32.5 9.5 3.25 .86 1.00 1.00 .86 32.4 9.5 3.25 .59 .74 .88 .92 33.2 9.7 3.25 .62 .79 .94 .97 33.9 9.9 3.26 .65 .84 .99 .70 34.7 10.2 3.27 .43 .57 .71 .75 35.5 10.4 3.27 .45 .61 .77 .80 36.1 10.6 3.28 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.2 35.3 36.3 36.5 37.5 38.3 39.0 40.1 40.8 10.0 10.3 10.6 10.7 11.0 11.2 11.4 11.8 12.0

85_F kBtuh kW 29_C .99 31.7 9.3 1.00 32.8 9.6 1.00 33.8 9.9 .84 33.8 9.9 .90 34.7 10.2 .95 35.4 10.4 .68 36.2 10.6 .73 37.1 10.9 .78 37.8 11.1

HP26-036 - CVP10-31/EC10Q3 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 41.6 42.0 42.6 kW 12.2 12.3 12.5 Comp. Motor kW Input 2.56 2.49 2.33 45_F (7_C) Total Heating Capacity kBtuh 32.9 33.3 33.9 kW 9.6 9.8 9.9 Comp. Motor kW Input 2.41 2.35 2.19 25_F (-4_C) Total Heating Capacity kBtuh 23.7 24.1 24.7 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.26 2.19 2.03 5_F (-15_C) Total Heating Capacity kBtuh 18.0 18.4 19.0 kW 5.3 5.4 5.6 Comp. Motor kW Input 2.05 1.98 1.82 -15_F (-26_C) Total Heating Capacity kBtuh 8.9 9.3 9.9 kW 2.6 2.7 2.9 Comp. Motor kW Input 1.50 1.44 1.28

HP26-036 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 41.6 42.0 42.7 kW 12.2 12.3 12.5 Comp. Motor kW Input 2.44 2.38 2.22 45_F (7_C) Total Heating Capacity kBtuh 32.9 33.3 34.0 kW 9.6 9.8 10.0 Comp. Motor kW Input 2.32 2.26 2.10 25_F (-4_C) Total Heating Capacity kBtuh 23.7 24.1 24.8 kW 6.9 7.1 7.3 Comp. Motor kW Input 2.19 2.13 1.97 5_F (-15_C) Total Heating Capacity kBtuh 18.0 18.4 19.1 kW 5.3 5.4 5.6 Comp. Motor kW Input 1.99 1.93 1.77 -15_F (-26_C) Total Heating Capacity kBtuh 8.9 9.3 10.0 kW 2.6 2.7 2.9 Comp. Motor kW Input 1.46 1.40 1.24

HP26-036 - CVP10-31/EC10Q3 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.49 2.46 2.42 2.39 2.37 2.35 2.29 2.23 2.21 2.19 2.18 2.16 2.15 2.12 1.98 1.84 1.71 1.57 1.44 1.30 Total Output kBtuh 42.0 40.0 38.1 36.2 35.0 33.3 29.1 24.9 24.5 24.1 23.6 23.4 22.6 20.7 18.4 16.1 13.9 11.6 9.3 7.0 kW 12.3 11.7 11.2 10.6 10.3 9.8 8.5 7.3 7.2 7.1 6.9 6.9 6.6 6.1 5.4 4.7 4.1 3.4 2.7 2.1

HP26-036 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.38 2.35 2.33 2.30 2.28 2.26 2.21 2.15 2.14 2.13 2.11 2.11 2.09 2.06 1.93 1.80 1.66 1.53 1.40 1.26 Total Output kBtuh 42.0 40.0 38.1 36.2 35.0 33.3 29.1 24.9 24.5 24.1 23.6 23.4 22.6 20.7 18.4 16.1 13.9 11.6 9.3 7.0 kW 12.3 11.7 11.2 10.6 10.3 9.8 8.5 7.3 7.2 7.1 6.9 6.9 6.6 6.1 5.4 4.7 4.1 3.4 2.7 2.1

HP26 / Page 33 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Temperat ure

C26-31 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .78 2.25 .81 2.25 .57 2.26 .60 2.26 .62 2.26 .43 2.27 .43 2.27 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .71 .75 .79 .55 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.6 9.8 2.53 .74 1.00 34.7 10.2 2.54 .79 1.00 35.6 10.4 2.54 .83 .84 35.8 10.5 2.54 .58 .89 36.7 10.8 2.55 .60 .94 37.4 11.0 2.55 .63 .68 38.3 11.2 2.55 .43 .72 39.2 11.5 2.56 .44 .77 39.9 11.7 2.56 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.86 .80 2.87 .85 2.87 .58 2.88 .61 2.88 .64 2.88 .43 2.89 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.24 .82 .98 1.00 3.25 .86 1.00 1.00 3.25 .59 .74 .89 3.26 .62 .79 .94 3.26 .65 .84 .99 3.27 .43 .58 .72 3.28 .45 .61 .77 3.28 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.8 35.9 36.9 37.1 38.1 38.8 39.7 40.7 41.4 10.2 10.5 10.8 10.9 11.2 11.4 11.6 11.9 12.1

85_F kBtuh kW 29_C .99 32.3 9.5 1.00 33.4 9.8 1.00 34.4 10.1 .85 34.4 10.1 .91 35.3 10.3 .96 36.0 10.6 .69 36.8 10.8 .74 37.7 11.0 .78 38.3 11.2

85_F kBtuh kW 29_C 1.00 31.0 9.1 1.00 32.0 9.4 1.00 33.0 9.7 .87 33.0 9.7 .93 33.8 9.9 .97 34.4 10.1 .70 35.3 10.3 .75 36.1 10.6 .80 36.7 10.8

HP26-036
Entering Wet Bulb Tempera ture

C26-41 - C33-38A/B COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .81 2.25 .57 2.26 .59 2.26 .62 2.27 .43 2.27 .43 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 34.0 10.0 2.53 .74 1.00 35.1 10.3 2.54 .79 1.00 36.0 10.6 2.54 .83 .83 36.2 10.6 2.54 .58 .89 37.1 10.9 2.55 .60 .94 37.9 11.1 2.55 .63 .68 38.8 11.4 2.56 .43 .72 39.7 11.6 2.56 .44 .77 40.4 11.8 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .72 .76 .80 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.87 .80 2.87 .85 2.88 .58 2.88 .61 2.88 .64 2.89 .43 2.90 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.24 .82 .98 1.00 3.25 .86 1.00 1.00 3.26 .59 .74 .89 3.26 .62 .79 .94 3.26 .65 .84 .99 3.27 .43 .57 .72 3.28 .45 .61 .77 3.28 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.2 36.3 37.3 37.5 38.5 39.3 40.2 41.2 41.9 10.3 10.6 10.9 11.0 11.3 11.5 11.8 12.1 12.3

85_F kBtuh kW 29_C .99 32.7 9.6 1.00 33.7 9.9 1.00 34.7 10.2 .85 34.8 10.2 .91 35.7 10.5 .96 36.4 10.7 .69 37.2 10.9 .74 38.1 11.2 .78 38.8 11.4

85_F kBtuh kW 29_C 1.00 31.3 9.2 1.00 32.3 9.5 1.00 33.4 9.8 .87 33.3 9.8 .93 34.1 10.0 .97 34.8 10.2 .70 35.7 10.5 .75 36.5 10.7 .80 37.1 10.9

HP26-036 - C26-31 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.4 43.9 44.4 kW 12.7 12.9 13.0 Comp. Motor kW Input 2.82 2.61 2.44 45_F (7_C) Total Heating Capacity kBtuh 33.9 34.4 34.9 kW 9.9 10.1 10.2 Comp. Motor kW Input 2.63 2.42 2.25 25_F (-4_C) Total Heating Capacity kBtuh 23.8 24.3 24.8 kW 7.0 7.1 7.3 Comp. Motor kW Input 2.44 2.23 2.06 5_F (-15_C) Total Heating Capacity kBtuh 17.7 18.2 18.7 kW 5.2 5.3 5.5 Comp. Motor kW Input 2.20 1.99 1.82 -15_F (-26_C) Total Heating Capacity kBtuh 8.8 9.3 9.8 kW 2.6 2.7 2.9 Comp. Motor kW Input 1.66 1.45 1.28

HP26-036 - C26-41 - C33-38A/B HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.7 44.2 44.8 kW 12.8 13.0 13.1 Comp. Motor kW Input 2.88 2.67 2.51 45_F (7_C) Total Heating Capacity kBtuh 34.1 34.6 35.2 kW 10.0 10.1 10.3 Comp. Motor kW Input 2.64 2.43 2.27 25_F (-4_C) Total Heating Capacity kBtuh 23.9 24.4 25.0 kW 7.0 7.2 7.3 Comp. Motor kW Input 2.40 2.19 2.03 5_F (-15_C) Total Heating Capacity kBtuh 17.6 18.1 18.7 kW 5.2 5.3 5.5 Comp. Motor kW Input 2.13 1.92 1.76 -15_F (-26_C) Total Heating Capacity kBtuh 8.7 9.2 9.8 kW 2.5 2.7 2.9 Comp. Motor kW Input 1.61 1.40 1.24

HP26-036 - C26-31 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.61 2.56 2.52 2.47 2.45 2.42 2.35 2.28 2.25 2.23 2.20 2.18 2.17 2.12 1.99 1.85 1.72 1.58 1.45 1.31 Total Output kBtuh 43.9 41.7 39.6 37.5 36.2 34.4 30.0 25.5 24.9 24.3 23.7 23.4 22.5 20.4 18.2 15.9 13.7 11.5 9.3 7.0 kW 12.9 12.2 11.6 11.0 10.6 10.1 8.8 7.5 7.3 7.1 6.9 6.9 6.6 6.0 5.3 4.7 4.0 3.4 2.7 2.1

HP26-036 - C26-41 - C33-38A/B HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.67 2.61 2.55 2.50 2.46 2.43 2.35 2.27 2.23 2.19 2.15 2.13 2.10 2.05 1.92 1.79 1.66 1.53 1.40 1.28 Total Output kBtuh 44.2 42.0 39.9 37.7 36.4 34.6 30.1 25.6 25.0 24.4 23.8 23.4 22.5 20.4 18.1 15.9 13.7 11.5 9.2 7.0 kW 13.0 12.3 11.7 11.0 10.7 10.1 8.8 7.5 7.3 7.2 7.0 6.9 6.6 6.0 5.3 4.7 4.0 3.4 2.7 2.1

HP26 / Page 34 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

C26-46 - C33-48B/C COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .82 2.26 .57 2.26 .59 2.27 .62 2.27 .43 2.28 .44 2.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .70 .75 .79 .55 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 34.1 10.0 2.53 .74 1.00 35.2 10.3 2.54 .79 1.00 36.2 10.6 2.54 .83 .83 36.3 10.6 2.55 .58 .89 37.3 10.9 2.55 .60 .94 38.0 11.1 2.56 .63 .68 38.9 11.4 2.56 .43 .72 39.8 11.7 2.57 .44 .77 40.5 11.9 2.57 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.87 .75 2.87 .80 2.88 .85 2.88 .58 2.88 .61 2.89 .64 2.89 .43 2.90 .44 2.90 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.25 .82 .98 1.00 3.25 .87 1.00 1.00 3.26 .59 .74 .89 3.26 .62 .80 .95 3.27 .66 .85 .99 3.28 .43 .58 .72 3.28 .45 .61 .77 3.29 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.3 36.5 37.5 37.7 38.7 39.5 40.3 41.3 42.1 10.3 10.7 11.0 11.0 11.3 11.6 11.8 12.1 12.3

85_F kBtuh kW 29_C 1.00 32.7 9.6 1.00 33.8 9.9 1.00 34.9 10.2 .85 34.9 10.2 .91 35.8 10.5 .96 36.5 10.7 .69 37.3 10.9 .74 38.3 11.2 .79 38.9 11.4

85_F kBtuh kW 29_C 1.00 31.4 9.2 1.00 32.4 9.5 1.00 33.5 9.8 .87 33.4 9.8 .93 34.2 10.0 .98 34.9 10.2 .70 35.7 10.5 .75 36.6 10.7 .80 37.2 10.9

HP26-036
Entering Wet Bulb Tempera ture

CR26-48N/W-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .72 2.25 .76 2.25 .80 2.25 .56 2.26 .59 2.27 .61 2.27 .42 2.28 .43 2.28 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .91 .96 .69 .74 .78 .55 .57 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 32.7 9.6 2.53 .73 1.00 33.8 9.9 2.54 .78 1.00 34.7 10.2 2.54 .81 .82 35.0 10.3 2.55 .57 .88 35.9 10.5 2.55 .60 .93 36.7 10.8 2.56 .62 .67 37.5 11.0 2.56 .43 .71 38.4 11.3 2.57 .43 .75 39.2 11.5 2.57 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .97 .71 .75 .79 .55 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .74 2.87 .79 2.87 .83 2.88 .58 2.88 .60 2.89 .63 2.89 .43 2.90 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .99 .72 .77 .81 .56 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 85_F 75_F 80_F 85_F kBtuh kW Input 29_C 24_C 27_C 29_C 1.00 30.1 8.8 3.24 .76 .91 1.00 1.00 31.1 9.1 3.24 .81 .96 1.00 1.00 32.0 9.4 3.25 .85 1.00 1.00 .85 32.2 9.4 3.26 .59 .73 .87 .91 33.0 9.7 3.26 .62 .78 .93 .96 33.6 9.8 3.27 .64 .83 .98 .69 34.5 10.1 3.28 .43 .57 .71 .74 35.3 10.3 3.28 .44 .60 .76 .78 35.9 10.5 3.29 .45 .63 .80

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 33.9 35.0 35.9 36.3 37.3 38.1 38.9 39.9 40.7 9.9 10.3 10.5 10.6 10.9 11.2 11.4 11.7 11.9

85_F kBtuh kW 29_C .99 31.5 9.2 1.00 32.5 9.5 1.00 33.4 9.8 .84 33.6 9.8 .89 34.5 10.1 .95 35.2 10.3 .68 36.1 10.6 .72 36.9 10.8 .77 37.6 11.0

HP26-036 - C26-46 - C33-48B/C HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.4 44.0 44.5 kW 12.7 12.9 13.0 Comp. Motor kW Input 2.83 2.62 2.45 45_F (7_C) Total Heating Capacity kBtuh 33.8 34.4 34.9 kW 9.9 10.1 10.2 Comp. Motor kW Input 2.62 2.42 2.25 25_F (-4_C) Total Heating Capacity kBtuh 23.6 24.2 24.7 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.41 2.21 2.04 5_F (-15_C) Total Heating Capacity kBtuh 17.4 18.0 18.5 kW 5.1 5.3 5.4 Comp. Motor kW Input 2.16 1.96 1.79 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.63 1.43 1.26

HP26-036 - CR26-48N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 42.4 43.0 43.5 kW 12.4 12.6 12.7 Comp. Motor kW Input 2.74 2.54 2.37 45_F (7_C) Total Heating Capacity kBtuh 33.0 33.6 34.1 kW 9.7 9.8 10.0 Comp. Motor kW Input 2.55 2.35 2.19 25_F (-4_C) Total Heating Capacity kBtuh 23.1 23.7 24.2 kW 6.8 6.9 7.1 Comp. Motor kW Input 2.36 2.16 1.99 5_F (-15_C) Total Heating Capacity kBtuh 17.1 17.7 18.2 kW 5.0 5.2 5.3 Comp. Motor kW Input 2.12 1.92 1.75 -15_F (-26_C) Total Heating Capacity kBtuh 8.4 9.0 9.5 kW 2.5 2.6 2.8 Comp. Motor kW Input 1.60 1.40 1.23

HP26-036 - C26-46 - C33-48B/C HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.62 2.57 2.52 2.48 2.45 2.42 2.35 2.27 2.24 2.21 2.18 2.16 2.14 2.09 1.96 1.83 1.69 1.56 1.43 1.30 Total Output kBtuh 44.0 41.8 39.7 37.5 36.2 34.4 29.9 25.4 24.8 24.2 23.6 23.2 22.3 20.2 18.0 15.8 13.6 11.4 9.2 7.0 kW 12.9 12.3 11.6 11.0 10.6 10.1 8.8 7.4 7.3 7.1 6.9 6.8 6.5 5.9 5.3 4.6 4.0 3.3 2.7 2.1

HP26-036 - CR26-48N/W-F HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.54 2.49 2.45 2.41 2.38 2.35 2.28 2.21 2.18 2.16 2.13 2.11 2.09 2.05 1.92 1.79 1.66 1.53 1.40 1.27 Total Output kBtuh 43.0 40.9 38.8 36.7 35.4 33.6 29.3 24.9 24.3 23.7 23.1 22.8 22.0 19.9 17.7 15.5 13.4 11.2 9.0 6.8 kW 12.6 12.0 11.4 10.8 10.4 9.8 8.6 7.3 7.1 6.9 6.8 6.7 6.4 5.8 5.2 4.5 3.9 3.3 2.6 2.0

HP26 / Page 35 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CR26-36N/W-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .77 2.25 .81 2.25 .57 2.26 .60 2.26 .62 2.27 .43 2.27 .44 2.27 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .97 .71 .75 .79 .55 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 33.8 9.9 2.53 .74 1.00 34.9 10.2 2.54 .79 1.00 35.8 10.5 2.54 .83 .84 36.0 10.6 2.54 .58 .89 36.9 10.8 2.55 .60 .94 37.6 11.0 2.55 .63 .68 38.5 11.3 2.55 .43 .72 39.4 11.5 2.56 .44 .77 40.1 11.8 2.56 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .98 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .76 2.86 .80 2.87 .85 2.87 .58 2.88 .61 2.88 .64 2.89 .43 2.89 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.24 .82 .97 1.00 3.25 .87 1.00 1.00 3.25 .59 .74 .88 3.25 .62 .79 .94 3.26 .65 .84 .99 3.27 .43 .57 .72 3.28 .45 .61 .77 3.28 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.0 36.1 37.1 37.3 38.3 39.0 39.9 40.9 41.6 10.3 10.6 10.9 10.9 11.2 11.4 11.7 12.0 12.2

85_F kBtuh kW 29_C .99 32.5 9.5 1.00 33.6 9.8 1.00 34.6 10.1 .85 34.6 10.1 .91 35.5 10.4 .96 36.2 10.6 .69 37.0 10.8 .74 37.9 11.1 .79 38.5 11.3

85_F kBtuh kW 29_C 1.00 31.2 9.1 1.00 32.2 9.4 1.00 33.2 9.7 .86 33.1 9.7 .93 34.0 10.0 .97 34.6 10.1 .70 35.5 10.4 .75 36.3 10.6 .80 36.8 10.8

HP26-036
Entering Wet Bulb Tempera ture

CH23-41 - CH33-36A-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.24 .78 2.25 .82 2.25 .57 2.25 .60 2.26 .63 2.26 .43 2.26 .44 2.27 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .98 .71 .76 .80 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 33.3 9.8 2.52 .75 1.00 34.4 10.1 2.53 .79 1.00 35.4 10.4 2.53 .84 .84 35.4 10.4 2.53 .58 .90 36.3 10.6 2.54 .61 .95 37.1 10.9 2.55 .64 .68 37.9 11.1 2.55 .43 .73 38.8 11.4 2.56 .44 .78 39.4 11.5 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .99 .72 .77 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .76 2.86 .81 2.86 .86 2.87 .59 2.87 .62 2.88 .65 2.88 .43 2.89 .44 2.89 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 1.00 .73 .79 .83 .57 .60 .64 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.23 .78 .93 1.00 3.24 .82 .98 1.00 3.24 .87 1.00 1.00 3.25 .60 .75 .89 3.25 .63 .80 .95 3.26 .66 .85 .99 3.26 .44 .58 .72 3.27 .45 .61 .78 3.27 .46 .65 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 34.5 35.6 36.6 36.7 37.7 38.4 39.3 40.2 40.9 10.1 10.4 10.7 10.8 11.0 11.3 11.5 11.8 12.0

85_F kBtuh kW 29_C 1.00 32.0 9.4 1.00 33.1 9.7 1.00 34.1 10.0 .86 34.1 10.0 .92 34.9 10.2 .96 35.6 10.4 .69 36.4 10.7 .74 37.3 10.9 .79 37.9 11.1

85_F kBtuh kW 29_C 1.00 30.7 9.0 1.00 31.8 9.3 1.00 32.9 9.6 .87 32.6 9.6 .93 33.5 9.8 .98 34.1 10.0 .71 34.9 10.2 .76 35.7 10.5 .81 36.2 10.6

HP26-036 - CR26-36N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.7 44.2 44.7 kW 12.8 13.0 13.1 Comp. Motor kW Input 2.80 2.59 2.43 45_F (7_C) Total Heating Capacity kBtuh 34.1 34.6 35.1 kW 10.0 10.1 10.3 Comp. Motor kW Input 2.59 2.39 2.23 25_F (-4_C) Total Heating Capacity kBtuh 23.9 24.4 24.9 kW 7.0 7.2 7.3 Comp. Motor kW Input 2.38 2.18 2.02 5_F (-15_C) Total Heating Capacity kBtuh 17.6 18.1 18.6 kW 5.2 5.3 5.5 Comp. Motor kW Input 2.13 1.93 1.77 -15_F (-26_C) Total Heating Capacity kBtuh 8.7 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.61 1.41 1.25

HP26-036 - CH23-41 - CH33-36A-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.1 43.7 44.2 kW 12.6 12.8 13.0 Comp. Motor kW Input 2.88 2.67 2.49 45_F (7_C) Total Heating Capacity kBtuh 33.6 34.2 34.7 kW 9.8 10.0 10.2 Comp. Motor kW Input 2.57 2.36 2.19 25_F (-4_C) Total Heating Capacity kBtuh 23.5 24.1 24.6 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.21 2.00 1.83 5_F (-15_C) Total Heating Capacity kBtuh 17.4 18.0 18.5 kW 5.1 5.3 5.4 Comp. Motor kW Input 2.16 1.95 1.78 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.64 1.43 1.25

HP26-036 - CR26-36N/W-F HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.59 2.55 2.50 2.45 2.42 2.39 2.32 2.24 2.21 2.18 2.15 2.13 2.11 2.06 1.93 1.80 1.67 1.54 1.41 1.28 Total Output kBtuh 44.2 42.0 39.9 37.7 36.4 34.6 30.1 25.6 25.0 24.4 23.8 23.4 22.5 20.4 18.1 15.9 13.7 11.5 9.2 7.0 kW 13.0 12.3 11.7 11.0 10.7 10.1 8.8 7.5 7.3 7.2 7.0 6.9 6.6 6.0 5.3 4.7 4.0 3.4 2.7 2.1

HP26-036 - CH23-41 - CH33-36A-F HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.67 2.61 2.56 2.51 2.48 2.36 2.09 1.81 1.90 2.00 2.10 2.16 2.14 2.09 1.95 1.82 1.69 1.56 1.43 1.30 Total Output kBtuh 43.7 41.5 39.4 37.3 36.0 34.2 29.8 25.3 24.7 24.1 23.6 23.2 22.3 20.2 18.0 15.8 13.6 11.4 9.2 7.0 kW 12.8 12.2 11.5 10.9 10.6 10.0 8.7 7.4 7.2 7.1 6.9 6.8 6.5 5.9 5.3 4.6 4.0 3.3 2.7 2.1

HP26 / Page 36 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-036
Entering Wet Bulb Tempera ture

CH23-51 - CH33-42B-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.24 .73 2.25 .78 2.25 .82 2.25 .57 2.26 .60 2.26 .63 2.26 .43 2.27 .44 2.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .97 .71 .75 .80 .55 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 34.0 10.0 2.53 .74 1.00 35.1 10.3 2.53 .79 1.00 36.1 10.6 2.54 .84 .84 36.2 10.6 2.54 .58 .90 37.1 10.9 2.55 .61 .95 37.9 11.1 2.55 .63 .68 38.7 11.3 2.56 .43 .73 39.6 11.6 2.56 .44 .77 40.3 11.8 2.56 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .99 .72 .77 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .76 2.86 .80 2.87 .85 2.87 .59 2.88 .62 2.88 .64 2.89 .43 2.89 .44 2.90 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 1.00 .73 .78 .83 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.23 .77 .92 1.00 3.24 .82 .98 1.00 3.25 .87 1.00 1.00 3.25 .59 .74 .89 3.26 .62 .80 .95 3.27 .66 .85 .99 3.27 .44 .58 .72 3.27 .45 .61 .78 3.28 .46 .65 .83

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.2 36.4 37.4 37.5 38.5 39.3 40.1 41.1 41.9 10.3 10.7 11.0 11.0 11.3 11.5 11.8 12.0 12.3

85_F kBtuh kW 29_C .99 32.6 9.6 1.00 33.8 9.9 1.00 34.8 10.2 .85 34.8 10.2 .91 35.7 10.5 .96 36.4 10.7 .69 37.2 10.9 .74 38.1 11.2 .79 38.7 11.3

85_F kBtuh kW 29_C 1.00 31.3 9.2 1.00 32.4 9.5 1.00 33.5 9.8 .87 33.3 9.8 .93 34.1 10.0 .98 34.8 10.2 .70 35.6 10.4 .76 36.4 10.7 .81 37.0 10.8

HP26-036
Entering Wet Bulb Tempera ture

CH23-65 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.25 .73 2.25 .77 2.26 .82 2.26 .57 2.26 .60 2.27 .62 2.27 .43 2.28 .44 2.28 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .93 .98 .70 .75 .80 .55 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 34.2 10.0 2.53 .74 1.00 35.4 10.4 2.54 .79 1.00 36.4 10.7 2.55 .83 .83 36.5 10.7 2.55 .58 .90 37.5 11.0 2.55 .60 .95 38.3 11.2 2.56 .63 .68 39.1 11.5 2.56 .43 .73 40.1 11.8 2.57 .44 .77 40.8 12.0 2.58 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .99 .72 .76 .81 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 2.86 .75 2.87 .80 2.88 .85 2.88 .58 2.88 .61 2.89 .64 2.89 .43 2.90 .44 2.91 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .96 1.00 .73 .78 .83 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.24 .77 .92 1.00 3.25 .82 .98 1.00 3.25 .87 1.00 1.00 3.26 .59 .74 .89 3.27 .62 .80 .95 3.27 .66 .85 1.00 3.27 .43 .58 .72 3.29 .45 .61 .77 3.29 .46 .64 .83

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1000 1200 1400 1000 1200 1400 1000 1200 1400

L/s kBtuh kW 470 565 660 470 565 660 470 565 660 35.5 36.7 37.7 37.9 38.9 39.7 40.5 41.6 42.4 10.4 10.8 11.0 11.1 11.4 11.6 11.9 12.2 12.4

85_F kBtuh kW 29_C 1.00 32.9 9.6 1.00 34.0 10.0 1.00 35.0 10.3 .85 35.0 10.3 .91 36.0 10.6 .96 36.7 10.8 .69 37.5 11.0 .74 38.5 11.3 .79 39.1 11.5

85_F kBtuh kW 29_C 1.00 31.5 9.2 1.00 32.6 9.6 1.00 33.7 9.9 .87 33.5 9.8 .93 34.4 10.1 .98 35.1 10.3 .70 35.9 10.5 .75 36.7 10.8 .81 37.4 11.0

HP26-036 - CH23-51 - CH33-42B-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.4 44.0 44.5 kW 12.7 12.9 13.0 Comp. Motor kW Input 2.85 2.65 2.49 45_F (7_C) Total Heating Capacity kBtuh 33.8 34.4 34.9 kW 9.9 10.1 10.2 Comp. Motor kW Input 2.54 2.34 2.17 25_F (-4_C) Total Heating Capacity kBtuh 23.6 24.2 24.7 kW 6.9 7.1 7.2 Comp. Motor kW Input 2.16 1.96 1.79 5_F (-15_C) Total Heating Capacity kBtuh 17.4 18.0 18.5 kW 5.1 5.3 5.4 Comp. Motor kW Input 2.10 1.90 1.73 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.59 1.39 1.22

HP26-036 - CH23-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1000 1200 1400 L/s 470 565 660 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 43.6 44.2 44.7 kW 12.8 13.0 13.1 Comp. Motor kW Input 2.76 2.56 2.40 45_F (7_C) Total Heating Capacity kBtuh 34.0 34.6 35.1 kW 10.0 10.1 10.3 Comp. Motor kW Input 2.54 2.34 2.18 25_F (-4_C) Total Heating Capacity kBtuh 23.8 24.4 24.9 kW 7.0 7.2 7.3 Comp. Motor kW Input 2.33 2.13 1.97 5_F (-15_C) Total Heating Capacity kBtuh 17.5 18.1 18.6 kW 5.1 5.3 5.5 Comp. Motor kW Input 2.07 1.87 1.71 -15_F (-26_C) Total Heating Capacity kBtuh 8.6 9.2 9.7 kW 2.5 2.7 2.8 Comp. Motor kW Input 1.57 1.37 1.21

HP26-036 - CH23-51 - CH33-42B-F HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.65 2.60 2.54 2.48 2.45 2.34 2.05 1.77 1.86 1.96 2.05 2.10 2.08 2.02 1.90 1.77 1.64 1.52 1.39 1.26 Total Output kBtuh 44.0 41.8 39.7 37.5 36.2 34.4 29.9 25.4 24.8 24.2 23.6 23.2 22.3 20.2 18.0 15.8 13.6 11.4 9.2 7.0 kW 12.9 12.3 11.6 11.0 10.6 10.1 8.8 7.4 7.3 7.1 6.9 6.8 6.5 5.9 5.3 4.6 4.0 3.3 2.7 2.1

HP26-036 - CH23-65 HEATING PERFORMANCE at 1200 cfm (565 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 2.56 2.51 2.46 2.41 2.37 2.34 2.27 2.19 2.16 2.13 2.09 2.07 2.05 2.00 1.87 1.75 1.62 1.49 1.37 1.24 Total Output kBtuh 44.2 42.0 39.9 37.7 36.4 34.6 30.1 25.6 25.0 24.4 23.8 23.4 22.5 20.4 18.1 15.9 13.7 11.5 9.2 7.0 kW 13.0 12.3 11.7 11.0 10.7 10.1 8.8 7.5 7.3 7.2 7.0 6.9 6.6 6.0 5.3 4.7 4.0 3.4 2.7 2.1

HP26 / Page 37 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CB29M-46 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.75 .73 2.76 .77 2.77 .80 2.77 .57 2.77 .59 2.78 .61 2.79 .43 2.79 .44 2.80 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .74 .78 .56 .58 .60

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.6 11.6 3.10 .75 1.00 40.6 11.9 3.11 .78 1.00 41.6 12.2 3.12 .82 .84 42.1 12.3 3.12 .58 .89 43.0 12.6 3.12 .60 .93 43.7 12.8 3.13 .62 .68 45.0 13.2 3.14 .43 .72 45.8 13.4 3.14 .44 .76 46.5 13.6 3.15 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.50 .76 3.51 .80 3.51 .83 3.51 .59 3.52 .61 3.53 .63 3.54 .43 3.55 .44 3.55 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .95 .99 .73 .77 .81 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.94 .77 .92 1.00 3.95 .81 .97 1.00 3.95 .85 .99 1.00 3.96 .59 .75 .89 3.98 .62 .79 .94 3.97 .65 .83 .98 3.99 .43 .58 .72 4.00 .45 .61 .77 4.00 .46 .63 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.0 42.1 43.0 43.7 44.6 45.3 46.6 47.5 48.2 12.0 12.3 12.6 12.8 13.1 13.3 13.7 13.9 14.1

85_F kBtuh kW 29_C 1.00 38.1 11.2 1.00 39.1 11.5 1.00 40.0 11.7 .86 40.5 11.9 .91 41.3 12.1 .95 41.9 12.3 .69 43.2 12.7 .74 44.0 12.9 .77 44.6 13.1

85_F kBtuh kW 29_C 1.00 36.5 10.7 1.00 37.5 11.0 1.00 38.5 11.3 .87 38.7 11.3 .92 39.5 11.6 .96 40.1 11.8 .71 41.4 12.1 .75 42.1 12.3 .79 42.7 12.5

HP26-042
Entering Wet Bulb Tempera ture

CB29M-51 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .80 2.74 .57 2.75 .59 2.76 .61 2.77 .43 2.77 .44 2.78 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .56 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.1 11.5 3.08 .75 1.00 40.2 11.8 3.09 .78 1.00 41.1 12.0 3.09 .82 .84 41.6 12.2 3.09 .58 .89 42.5 12.5 3.10 .60 .93 43.2 12.7 3.11 .62 .68 44.5 13.0 3.11 .43 .72 45.3 13.3 3.12 .44 .76 46.0 13.5 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .76 3.48 .80 3.48 .84 3.49 .59 3.50 .61 3.50 .63 3.51 .43 3.52 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .98 .73 .77 .81 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .93 1.00 3.92 .81 .97 1.00 3.93 .85 1.00 1.00 3.93 .59 .75 .89 3.94 .62 .79 .94 3.94 .65 .83 .98 3.96 .44 .58 .72 3.96 .44 .61 .77 3.97 .45 .64 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.6 41.6 42.6 43.2 44.1 44.9 46.1 47.1 47.8 11.9 12.2 12.5 12.7 12.9 13.2 13.5 13.8 14.0

85_F kBtuh kW 29_C .99 37.6 11.0 1.00 38.6 11.3 1.00 39.6 11.6 .85 40.0 11.7 .90 40.8 12.0 .95 41.5 12.2 .69 42.7 12.5 .73 43.5 12.7 .77 44.2 13.0

85_F kBtuh kW 29_C 1.00 36.0 10.6 1.00 37.0 10.8 1.00 38.0 11.1 .87 38.3 11.2 .92 39.1 11.5 .96 39.7 11.6 .71 40.9 12.0 .75 41.7 12.2 .79 42.2 12.4

HP26-042 - CB29M-46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 48.3 48.8 49.3 kW 14.2 14.3 14.4 Comp. Motor kW Input 3.52 3.30 3.12 45_F (7_C) Total Heating Capacity kBtuh 38.1 38.6 39.1 kW 11.2 11.3 11.5 Comp. Motor kW Input 3.25 3.03 2.85 25_F (-4_C) Total Heating Capacity kBtuh 27.3 27.8 28.3 kW 8.0 8.1 8.3 Comp. Motor kW Input 2.98 2.76 2.58 5_F (-15_C) Total Heating Capacity kBtuh 20.1 20.6 21.1 kW 5.9 6.0 6.2 Comp. Motor kW Input 2.66 2.44 2.26 -15_F (-26_C) Total Heating Capacity kBtuh 10.0 10.5 11.0 kW 2.9 3.1 3.2 Comp. Motor kW Input 2.00 1.78 1.60

HP26-042 - CB29M-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.2 50.8 51.3 kW 14.7 14.9 15.0 Comp. Motor kW Input 3.59 3.35 3.16 45_F (7_C) Total Heating Capacity kBtuh 39.7 40.3 40.8 kW 11.6 11.8 12.0 Comp. Motor kW Input 3.27 3.03 2.84 25_F (-4_C) Total Heating Capacity kBtuh 28.6 29.2 29.7 kW 8.4 8.6 8.7 Comp. Motor kW Input 2.94 2.71 2.52 5_F (-15_C) Total Heating Capacity kBtuh 21.2 21.8 22.3 kW 6.2 6.4 6.5 Comp. Motor kW Input 2.59 2.35 2.16 -15_F (-26_C) Total Heating Capacity kBtuh 10.4 11.0 11.5 kW 3.0 3.2 3.4 Comp. Motor kW Input 1.96 1.73 1.54

HP26-042 - CB29M-46 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.30 3.23 3.17 3.11 3.07 3.03 2.94 2.84 2.80 2.76 2.72 2.69 2.66 2.60 2.44 2.27 2.11 1.94 1.78 1.61 Total Output kBtuh 48.8 46.5 44.1 41.8 40.4 38.6 34.1 29.6 28.7 27.8 26.9 26.4 25.5 23.1 20.6 18.1 15.5 13.0 10.5 7.9 kW 14.3 13.6 12.9 12.3 11.8 11.3 10.0 8.7 8.4 8.1 7.9 7.7 7.5 6.8 6.0 5.3 4.5 3.8 3.1 2.3

HP26-042 - CB29M-51 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.35 3.28 3.20 3.12 3.08 3.03 2.93 2.82 2.76 2.71 2.65 2.62 2.59 2.51 2.35 2.20 2.04 1.88 1.73 1.57 Total Output kBtuh 50.8 48.4 46.0 43.6 42.2 40.3 35.7 31.0 30.1 29.2 28.3 27.8 26.8 24.4 21.8 19.1 16.4 13.7 11.0 8.3 kW 14.9 14.2 13.5 12.8 12.4 11.8 10.5 9.1 8.8 8.6 8.3 8.1 7.9 7.2 6.4 5.6 4.8 4.0 3.2 2.4

HP26 / Page 38 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CB30M-41 - CB30M-46 - CB30U-41/46 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .81 2.74 .57 2.75 .59 2.76 .61 2.77 .43 2.77 .43 2.78 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .55 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 38.8 11.4 3.08 .75 1.00 39.9 11.7 3.09 .78 1.00 40.8 12.0 3.09 .82 .84 41.3 12.1 3.09 .58 .89 42.2 12.4 3.10 .60 .93 42.9 12.6 3.11 .62 .68 44.2 13.0 3.11 .43 .72 45.0 13.2 3.12 .44 .76 45.7 13.4 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .97 .72 .76 .80 .56 .59 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 105_F (41_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.47 .76 3.48 .80 3.48 .83 3.49 .58 3.50 .61 3.50 .64 3.51 .43 3.52 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .95 .98 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .92 1.00 3.92 .81 .97 1.00 3.93 .85 1.00 1.00 3.93 .59 .75 .89 3.94 .62 .79 .94 3.94 .65 .83 .98 3.96 .44 .58 .72 3.96 .44 .61 .77 3.97 .46 .63 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.3 41.3 42.3 42.9 43.8 44.5 45.8 46.7 47.4 11.8 12.1 12.4 12.6 12.8 13.0 13.4 13.7 13.9

85_F kBtuh kW 29_C 1.00 37.3 10.9 1.00 38.3 11.2 1.00 39.3 11.5 .85 39.7 11.6 .90 40.5 11.9 .95 41.2 12.1 .69 42.4 12.4 .73 43.2 12.7 .77 43.9 12.9

85_F kBtuh kW 29_C 1.00 35.8 10.5 1.00 36.8 10.8 1.00 37.7 11.0 .87 38.0 11.1 .92 38.8 11.4 .96 39.4 11.5 .71 40.6 11.9 .75 41.4 12.1 .79 41.9 12.3

HP26-042
Entering Wet Bulb Tempera ture

CB29M-65 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .80 2.74 .57 2.75 .59 2.76 .61 2.77 .43 2.77 .43 2.78 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .56 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.6 11.6 3.08 .74 1.00 40.6 11.9 3.09 .78 1.00 41.6 12.2 3.09 .82 .84 42.1 12.3 3.09 .58 .89 43.0 12.6 3.10 .60 .93 43.7 12.8 3.11 .62 .68 45.0 13.2 3.11 .43 .72 45.9 13.5 3.12 .44 .76 46.5 13.6 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .76 3.48 .80 3.48 .83 3.49 .59 3.50 .61 3.50 .63 3.51 .43 3.52 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .95 .99 .73 .77 .81 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .92 1.00 3.92 .82 .97 1.00 3.93 .85 1.00 1.00 3.93 .59 .75 .89 3.94 .62 .79 .94 3.94 .65 .83 .98 3.96 .43 .58 .72 3.96 .44 .61 .77 3.97 .46 .63 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.0 42.1 43.0 43.7 44.6 45.4 46.6 47.6 48.3 12.0 12.3 12.6 12.8 13.1 13.3 13.7 14.0 14.2

85_F kBtuh kW 29_C 1.00 38.0 11.1 1.00 39.1 11.5 1.00 40.0 11.7 .85 40.4 11.8 .90 41.3 12.1 .95 42.0 12.3 .69 43.2 12.7 .73 44.0 12.9 .77 44.7 13.1

85_F kBtuh kW 29_C 1.00 36.4 10.7 1.00 37.4 11.0 1.00 38.4 11.3 .87 38.7 11.3 .92 39.5 11.6 .96 40.1 11.8 .71 41.4 12.1 .75 42.1 12.3 .79 42.7 12.5

HP26-042 - CB30M-41 - CB30M-46 - CB30U-41/46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.1 50.6 51.0 kW 14.7 14.8 14.9 Comp. Motor kW Input 3.44 3.24 3.08 45_F (7_C) Total Heating Capacity kBtuh 39.4 39.9 40.3 kW 11.5 11.7 11.8 Comp. Motor kW Input 3.16 2.96 2.80 25_F (-4_C) Total Heating Capacity kBtuh 28.2 28.7 29.1 kW 8.3 8.4 8.5 Comp. Motor kW Input 2.87 2.68 2.52 5_F (-15_C) Total Heating Capacity kBtuh 20.7 21.2 21.6 kW 6.1 6.2 6.3 Comp. Motor kW Input 2.54 2.35 2.19 -15_F (-26_C) Total Heating Capacity kBtuh 10.3 10.8 11.2 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.91 1.72 1.56

HP26-042 - CB29M-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.0 50.6 51.1 kW 14.7 14.8 15.0 Comp. Motor kW Input 3.54 3.32 3.14 45_F (7_C) Total Heating Capacity kBtuh 39.3 39.9 40.4 kW 11.5 11.7 11.8 Comp. Motor kW Input 3.23 3.02 2.83 25_F (-4_C) Total Heating Capacity kBtuh 28.1 28.7 29.2 kW 8.2 8.4 8.6 Comp. Motor kW Input 2.92 2.71 2.52 5_F (-15_C) Total Heating Capacity kBtuh 20.6 21.2 21.7 kW 6.0 6.2 6.4 Comp. Motor kW Input 2.58 2.36 2.18 -15_F (-26_C) Total Heating Capacity kBtuh 10.2 10.8 11.3 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.95 1.73 1.55

HP26-042 - CB30M-41 - CB30M-46 - CB30U-41/46 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.24 3.18 3.11 3.04 3.00 2.96 2.87 2.77 2.72 2.68 2.63 2.60 2.57 2.51 2.35 2.19 2.03 1.88 1.72 1.56 Total Output kBtuh 50.6 48.1 45.7 43.3 41.8 39.9 35.2 30.6 29.6 28.7 27.8 27.2 26.2 23.8 21.2 18.6 16.0 13.4 10.8 8.2 kW 14.8 14.1 13.4 12.7 12.3 11.7 10.3 9.0 8.7 8.4 8.1 8.0 7.7 7.0 6.2 5.5 4.7 3.9 3.2 2.4

HP26-042 - CB29M-65 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.32 3.25 3.17 3.10 3.06 3.02 2.91 2.81 2.76 2.71 2.65 2.62 2.59 2.52 2.36 2.21 2.05 1.89 1.73 1.57 Total Output kBtuh 50.6 48.1 45.7 43.3 41.8 39.9 35.2 30.6 29.6 28.7 27.8 27.2 26.2 23.8 21.2 18.6 16.0 13.4 10.8 8.2 kW 14.8 14.1 13.4 12.7 12.3 11.7 10.3 9.0 8.7 8.4 8.1 8.0 7.7 7.0 6.2 5.5 4.7 3.9 3.2 2.4

HP26 / Page 39 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CB31MV-41 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .80 2.74 .57 2.75 .59 2.76 .62 2.77 .43 2.77 .43 2.78 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .55 .58 .60

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.0 11.4 3.08 .74 1.00 40.1 11.8 3.09 .78 1.00 41.0 12.0 3.09 .82 .84 41.5 12.2 3.09 .58 .89 42.4 12.4 3.10 .60 .93 43.1 12.6 3.11 .62 .68 44.3 13.0 3.11 .43 .72 45.2 13.2 3.12 .44 .76 45.9 13.5 3.13 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .76 3.48 .80 3.48 .83 3.49 .58 3.50 .61 3.50 .63 3.51 .43 3.52 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .92 1.00 3.92 .81 .97 1.00 3.93 .85 1.00 1.00 3.93 .60 .75 .89 3.94 .62 .79 .94 3.94 .65 .83 .98 3.96 .43 .58 .72 3.96 .45 .61 .77 3.97 .46 .63 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.4 41.5 42.4 43.1 44.0 44.7 46.0 46.9 47.6 11.8 12.2 12.4 12.6 12.9 13.1 13.5 13.7 14.0

85_F kBtuh kW 29_C .99 37.5 11.0 1.00 38.5 11.3 1.00 39.4 11.5 .85 39.9 11.7 .90 40.7 11.9 .95 41.4 12.1 .69 42.6 12.5 .73 43.4 12.7 .77 44.0 12.9

85_F kBtuh kW 29_C 1.00 35.9 10.5 1.00 36.9 10.8 1.00 37.9 11.1 .87 38.2 11.2 .92 38.9 11.4 .96 39.6 11.6 .71 40.8 12.0 .75 41.5 12.2 .79 42.1 12.3

HP26-042
Entering Wet Bulb Tempera ture

CB30M-51 - CB30U-51 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.74 .73 2.75 .77 2.76 .80 2.76 .57 2.77 .59 2.78 .61 2.78 .43 2.79 .43 2.80 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .70 .74 .78 .55 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.7 11.6 3.09 .74 1.00 40.8 12.0 3.10 .78 1.00 41.8 12.3 3.11 .82 .83 42.4 12.4 3.11 .58 .89 43.4 12.7 3.12 .60 .93 44.1 12.9 3.13 .62 .68 45.4 13.3 3.13 .43 .72 46.3 13.6 3.14 .44 .76 47.1 13.8 3.15 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .71 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.48 .75 3.49 .80 3.50 .84 3.50 .58 3.52 .61 3.52 .63 3.53 .43 3.54 .44 3.55 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.93 .77 .92 1.00 3.94 .81 .97 1.00 3.95 .86 1.00 1.00 3.95 .59 .74 .89 3.96 .62 .79 .94 3.97 .65 .83 .99 3.98 .44 .58 .72 3.99 .44 .60 .76 3.99 .45 .63 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.2 42.4 43.4 44.0 45.1 45.9 47.1 48.1 48.9 12.1 12.4 12.7 12.9 13.2 13.5 13.8 14.1 14.3

85_F kBtuh kW 29_C 1.00 38.2 11.2 1.00 39.2 11.5 1.00 40.2 11.8 .85 40.7 11.9 .90 41.6 12.2 .95 42.3 12.4 .69 43.6 12.8 .73 44.4 13.0 .77 45.1 13.2

85_F kBtuh kW 29_C 1.00 36.5 10.7 1.00 37.5 11.0 1.00 38.6 11.3 .87 38.9 11.4 .92 39.7 11.6 .97 40.4 11.8 .70 41.6 12.2 .75 42.5 12.5 .79 43.1 12.6

HP26-042 - CB31MV-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.3 49.8 50.2 kW 14.4 14.6 14.7 Comp. Motor kW Input 3.40 3.21 3.06 45_F (7_C) Total Heating Capacity kBtuh 38.9 39.4 39.8 kW 11.4 11.5 11.7 Comp. Motor kW Input 3.11 2.92 2.77 25_F (-4_C) Total Heating Capacity kBtuh 27.8 28.3 28.7 kW 8.1 8.3 8.4 Comp. Motor kW Input 2.82 2.63 2.48 5_F (-15_C) Total Heating Capacity kBtuh 20.4 20.9 21.3 kW 6.0 6.1 6.2 Comp. Motor kW Input 2.49 2.30 2.15 -15_F (-26_C) Total Heating Capacity kBtuh 10.1 10.6 11.0 kW 3.0 3.1 3.2 Comp. Motor kW Input 1.88 1.69 1.54

HP26-042 - CB30M-51 - CB30U-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.3 50.7 51.1 kW 14.7 14.9 15.0 Comp. Motor kW Input 3.39 3.19 3.04 45_F (7_C) Total Heating Capacity kBtuh 39.5 39.9 40.3 kW 11.6 11.7 11.8 Comp. Motor kW Input 3.13 2.93 2.78 25_F (-4_C) Total Heating Capacity kBtuh 28.2 28.6 29.0 kW 8.3 8.4 8.5 Comp. Motor kW Input 2.86 2.66 2.51 5_F (-15_C) Total Heating Capacity kBtuh 20.6 21.0 21.4 kW 6.0 6.2 6.3 Comp. Motor kW Input 2.55 2.35 2.20 -15_F (-26_C) Total Heating Capacity kBtuh 10.3 10.7 11.1 kW 3.0 3.1 3.3 Comp. Motor kW Input 1.92 1.72 1.56

HP26-042 - CB31MV-41 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.21 3.14 3.07 3.00 2.96 2.92 2.83 2.73 2.68 2.63 2.58 2.55 2.52 2.46 2.30 2.15 1.99 1.84 1.69 1.53 Total Output kBtuh 49.8 47.4 45.0 42.6 41.2 39.4 34.7 30.1 29.2 28.3 27.4 26.8 25.8 23.4 20.9 18.3 15.7 13.2 10.6 8.0 kW 14.6 13.9 13.2 12.5 12.1 11.5 10.2 8.8 8.6 8.3 8.0 7.9 7.6 6.9 6.1 5.4 4.6 3.9 3.1 2.3

HP26-042 - CB30M-51 - CB30U-51 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.19 3.13 3.07 3.01 2.97 2.93 2.84 2.75 2.71 2.66 2.62 2.60 2.57 2.51 2.35 2.19 2.03 1.88 1.72 1.56 Total Output kBtuh 50.7 48.2 45.7 43.3 41.8 39.9 35.2 30.5 29.5 28.6 27.6 27.0 26.0 23.5 21.0 18.4 15.8 13.2 10.7 8.1 kW 14.9 14.1 13.4 12.7 12.3 11.7 10.3 8.9 8.6 8.4 8.1 7.9 7.6 6.9 6.2 5.4 4.6 3.9 3.1 2.4

HP26 / Page 40 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CB31MV-51 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .80 2.75 .57 2.75 .59 2.76 .61 2.77 .43 2.78 .43 2.79 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .70 .74 .78 .55 .58 .60

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.8 11.7 3.07 .74 1.00 40.9 12.0 3.09 .78 1.00 41.9 12.3 3.09 .82 .83 42.5 12.5 3.10 .58 .89 43.5 12.7 3.11 .60 .93 44.2 13.0 3.11 .62 .68 45.5 13.3 3.12 .43 .72 46.4 13.6 3.13 .44 .76 47.2 13.8 3.13 .44 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .98 .72 .75 .79 .56 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .75 3.48 .80 3.49 .84 3.49 .58 3.50 .61 3.50 .63 3.51 .43 3.53 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .92 1.00 3.92 .81 .97 1.00 3.93 .85 1.00 1.00 3.93 .59 .74 .89 3.94 .62 .79 .94 3.95 .65 .83 .99 3.96 .43 .58 .72 3.97 .44 .60 .77 3.97 .46 .63 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.3 42.5 43.5 44.1 45.2 46.0 47.2 48.2 49.0 12.1 12.5 12.7 12.9 13.2 13.5 13.8 14.1 14.4

85_F kBtuh kW 29_C 1.00 38.2 11.2 1.00 39.3 11.5 1.00 40.3 11.8 .85 40.8 12.0 .90 41.7 12.2 .95 42.4 12.4 .69 43.7 12.8 .73 44.5 13.0 .77 45.2 13.2

85_F kBtuh kW 29_C 1.00 36.6 10.7 1.00 37.6 11.0 1.00 38.7 11.3 .87 39.0 11.4 .92 39.8 11.7 .97 40.5 11.9 .70 41.7 12.2 .75 42.5 12.5 .79 43.2 12.7

HP26-042
Entering Wet Bulb Tempera ture

CVP10-41/EC10Q3 - CVP10-46/EC10Q4 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.72 .73 2.73 .77 2.74 .80 2.74 .57 2.74 .59 2.75 .61 2.76 .43 2.76 .43 2.77 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .70 .74 .78 .55 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 38.7 11.3 3.07 .74 1.00 39.7 11.6 3.08 .78 1.00 40.7 11.9 3.09 .82 .84 41.2 12.1 3.08 .58 .89 42.1 12.3 3.09 .60 .93 42.8 12.5 3.10 .62 .68 44.0 12.9 3.10 .43 .72 44.8 13.1 3.11 .44 .76 45.5 13.3 3.12 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .97 .72 .76 .79 .56 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .75 3.47 .80 3.47 .83 3.48 .58 3.49 .61 3.49 .63 3.50 .43 3.51 .44 3.52 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .98 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.90 .77 .92 1.00 3.91 .81 .97 1.00 3.91 .85 1.00 1.00 3.92 .59 .74 .89 3.93 .62 .79 .94 3.94 .65 .83 .98 3.95 .43 .58 .72 3.96 .44 .61 .77 3.96 .45 .63 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.1 41.2 42.1 42.7 43.6 44.4 45.6 46.5 47.3 11.8 12.1 12.3 12.5 12.8 13.0 13.4 13.6 13.9

85_F kBtuh kW 29_C .99 37.2 10.9 1.00 38.2 11.2 1.00 39.2 11.5 .85 39.6 11.6 .90 40.4 11.8 .94 41.1 12.0 .69 42.3 12.4 .73 43.1 12.6 .77 43.7 12.8

85_F kBtuh kW 29_C 1.00 35.6 10.4 1.00 36.6 10.7 1.00 37.6 11.0 .87 37.9 11.1 .92 38.6 11.3 .96 39.3 11.5 .71 40.5 11.9 .75 41.2 12.1 .79 41.8 12.3

HP26-042 - CB31MV-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.0 49.4 49.8 kW 14.4 14.5 14.6 Comp. Motor kW Input 3.27 3.08 2.94 45_F (7_C) Total Heating Capacity kBtuh 38.6 39.0 39.4 kW 11.3 11.4 11.5 Comp. Motor kW Input 3.04 2.86 2.72 25_F (-4_C) Total Heating Capacity kBtuh 27.5 27.9 28.3 kW 8.1 8.2 8.3 Comp. Motor kW Input 2.81 2.63 2.49 5_F (-15_C) Total Heating Capacity kBtuh 20.1 20.5 20.9 kW 5.9 6.0 6.1 Comp. Motor kW Input 2.52 2.34 2.20 -15_F (-26_C) Total Heating Capacity kBtuh 10.0 10.4 10.8 kW 2.9 3.0 3.2 Comp. Motor kW Input 1.89 1.70 1.56

HP26-042 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 47.5 47.6 48.5 kW 13.9 14.0 14.2 Comp. Motor kW Input 3.15 3.12 2.91 45_F (7_C) Total Heating Capacity kBtuh 38.2 38.3 39.2 kW 11.2 11.2 11.5 Comp. Motor kW Input 2.90 2.87 2.66 25_F (-4_C) Total Heating Capacity kBtuh 28.3 28.4 29.3 kW 8.3 8.3 8.6 Comp. Motor kW Input 2.65 2.62 2.41 5_F (-15_C) Total Heating Capacity kBtuh 21.7 21.8 22.7 kW 6.4 6.4 6.7 Comp. Motor kW Input 2.34 2.31 2.10 -15_F (-26_C) Total Heating Capacity kBtuh 10.8 10.9 11.8 kW 3.2 3.2 3.5 Comp. Motor kW Input 1.72 1.69 1.48

HP26-042 - CVP10-41/EC10Q3 - CVP10-46/EC10Q4 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.12 3.06 3.00 2.94 2.90 2.87 2.79 2.71 2.66 2.62 2.58 2.55 2.53 2.47 2.31 2.16 2.00 1.84 1.69 1.53 Total Output kBtuh 47.6 45.5 43.4 41.3 40.0 38.3 34.0 29.7 29.1 28.4 27.8 27.4 26.6 24.5 21.8 19.0 16.3 13.6 10.9 8.2 kW 14.0 13.3 12.7 12.1 11.7 11.2 10.0 8.7 8.5 8.3 8.1 8.0 7.8 7.2 6.4 5.6 4.8 4.0 3.2 2.4

HP26-042 - CB31MV-51 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.08 3.03 2.98 2.92 2.89 2.86 2.78 2.70 2.66 2.63 2.59 2.57 2.55 2.49 2.34 2.18 2.02 1.86 1.70 1.54 Total Output kBtuh 49.4 47.0 44.6 42.2 40.8 39.0 34.4 29.8 28.8 27.9 27.0 26.4 25.4 23.0 20.5 18.0 15.5 13.0 10.4 7.9 kW 14.5 13.8 13.1 12.4 12.0 11.4 10.1 8.7 8.4 8.2 7.9 7.7 7.4 6.7 6.0 5.3 4.5 3.8 3.0 2.3

HP26 / Page 41 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Temperat ure

C26-41 - C33-38B COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.71 .73 2.72 .77 2.73 .80 2.73 .57 2.73 .59 2.74 .61 2.75 .43 2.75 .44 2.76 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .56 .58 .60 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.0 11.4 3.06 .74 1.00 40.0 11.7 3.07 .78 1.00 40.9 12.0 3.07 .82 .84 41.5 12.2 3.07 .58 .89 42.3 12.4 3.08 .60 .93 43.0 12.6 3.09 .62 .68 44.3 13.0 3.09 .43 .72 45.1 13.2 3.10 .44 .76 45.8 13.4 3.11 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.45 .76 3.46 .80 3.46 .83 3.46 .59 3.47 .61 3.48 .63 3.49 .43 3.50 .44 3.50 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .81 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.89 .77 .92 1.00 3.89 .82 .97 1.00 3.90 .85 1.00 1.00 3.91 .60 .75 .89 3.92 .62 .79 .94 3.92 .65 .83 .98 3.93 .43 .58 .72 3.94 .45 .61 .77 3.94 .46 .63 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.4 41.5 42.4 43.0 43.9 44.6 45.9 46.8 47.5 11.8 12.2 12.4 12.6 12.9 13.1 13.5 13.7 13.9

85_F kBtuh kW 29_C .99 37.5 11.0 1.00 38.5 11.3 1.00 39.4 11.5 .85 39.9 11.7 .90 40.7 11.9 .94 41.3 12.1 .70 42.6 12.5 .74 43.3 12.7 .78 44.0 12.9

85_F kBtuh kW 29_C 1.00 36.0 10.6 1.00 36.9 10.8 1.00 37.9 11.1 .87 38.2 11.2 .92 38.9 11.4 .96 39.5 11.6 .71 40.8 12.0 .75 41.5 12.2 .79 42.1 12.3

HP26-042
Entering Wet Bulb Tempera ture

C26-46 - C33-48B/C COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.72 .73 2.73 .77 2.73 .81 2.73 .57 2.74 .60 2.75 .62 2.75 .43 2.76 .43 2.77 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .97 .71 .75 .79 .56 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.4 11.5 3.07 .75 1.00 40.5 11.9 3.07 .79 1.00 41.5 12.2 3.08 .83 .84 41.9 12.3 3.09 .58 .89 42.8 12.5 3.09 .60 .94 43.6 12.8 3.10 .63 .69 44.8 13.1 3.11 .43 .73 45.7 13.4 3.11 .44 .77 46.3 13.6 3.12 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .80 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .76 3.46 .80 3.47 .84 3.48 .59 3.48 .61 3.49 .64 3.50 .43 3.50 .44 3.51 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.89 .78 .93 1.00 3.90 .82 .98 1.00 3.91 .86 1.00 1.00 3.92 .60 .75 .89 3.92 .62 .80 .95 3.94 .65 .84 .99 3.94 .44 .58 .73 3.95 .45 .61 .77 3.96 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.9 42.0 43.0 43.5 44.5 45.2 46.4 47.4 48.1 12.0 12.3 12.6 12.7 13.0 13.2 13.6 13.9 14.1

85_F kBtuh kW 29_C 1.00 37.9 11.1 1.00 39.0 11.4 1.00 39.9 11.7 .86 40.3 11.8 .91 41.1 12.0 .95 41.8 12.3 .70 43.0 12.6 .74 43.8 12.8 .78 44.5 13.0

85_F kBtuh kW 29_C 1.00 36.3 10.6 1.00 37.3 10.9 1.00 38.4 11.3 .87 38.5 11.3 .93 39.3 11.5 .97 40.0 11.7 .71 41.2 12.1 .75 41.9 12.3 .80 42.5 12.5

HP26-042 - C26-41 - C33-38B HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.4 49.9 50.4 kW 14.5 14.6 14.8 Comp. Motor kW Input 3.54 3.33 3.15 45_F (7_C) Total Heating Capacity kBtuh 39.1 39.6 40.1 kW 11.5 11.6 11.8 Comp. Motor kW Input 3.22 3.00 2.83 25_F (-4_C) Total Heating Capacity kBtuh 28.1 28.6 29.1 kW 8.2 8.4 8.5 Comp. Motor kW Input 2.88 2.67 2.49 5_F (-15_C) Total Heating Capacity kBtuh 20.8 21.3 21.8 kW 6.1 6.2 6.4 Comp. Motor kW Input 2.53 2.31 2.14 -15_F (-26_C) Total Heating Capacity kBtuh 10.3 10.8 11.3 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.91 1.70 1.52

HP26-042 - C26-46 - C33-48B/C HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.2 49.7 50.1 kW 14.4 14.6 14.7 Comp. Motor kW Input 3.44 3.23 3.04 45_F (7_C) Total Heating Capacity kBtuh 38.9 39.4 39.8 kW 11.4 11.5 11.7 Comp. Motor kW Input 3.21 2.99 2.81 25_F (-4_C) Total Heating Capacity kBtuh 27.9 28.4 28.8 kW 8.2 8.3 8.4 Comp. Motor kW Input 2.97 2.75 2.57 5_F (-15_C) Total Heating Capacity kBtuh 20.6 21.1 21.5 kW 6.0 6.2 6.3 Comp. Motor kW Input 2.67 2.45 2.27 -15_F (-26_C) Total Heating Capacity kBtuh 10.2 10.7 11.1 kW 3.0 3.1 3.3 Comp. Motor kW Input 2.00 1.78 1.60

HP26-042 - C26-41 - C33-38B HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.33 3.25 3.17 3.09 3.05 3.00 2.89 2.79 2.73 2.67 2.61 2.58 2.54 2.47 2.31 2.16 2.01 1.85 1.70 1.55 Total Output kBtuh 49.9 47.6 45.2 42.8 41.4 39.6 35.0 30.4 29.5 28.6 27.7 27.2 26.3 23.9 21.3 18.6 16.0 13.4 10.8 8.2 kW 14.6 14.0 13.2 12.5 12.1 11.6 10.3 8.9 8.6 8.4 8.1 8.0 7.7 7.0 6.2 5.5 4.7 3.9 3.2 2.4

HP26-042 - C26-46 - C33-48B/C HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.23 3.17 3.11 3.06 3.03 2.99 2.91 2.82 2.79 2.75 2.72 2.69 2.67 2.62 2.45 2.28 2.12 1.95 1.78 1.62 Total Output kBtuh 49.7 47.4 45.0 42.6 41.2 39.4 34.8 30.2 29.3 28.4 27.5 27.0 26.1 23.7 21.1 18.5 15.9 13.3 10.7 8.1 kW 14.6 13.9 13.2 12.5 12.1 11.5 10.2 8.9 8.6 8.3 8.1 7.9 7.6 6.9 6.2 5.4 4.7 3.9 3.1 2.4

HP26 / Page 42 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

C26-51 - C33-50C COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.73 .77 2.74 .81 2.75 .57 2.75 .59 2.76 .62 2.77 .43 2.77 .44 2.78 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .97 .71 .75 .78 .56 .58 .60 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 40.0 11.7 3.07 .75 1.00 41.1 12.0 3.08 .78 1.00 42.1 12.3 3.09 .82 .84 42.5 12.5 3.09 .58 .89 43.5 12.7 3.10 .60 .94 44.3 13.0 3.11 .63 .68 45.5 13.3 3.12 .43 .72 46.4 13.6 3.12 .44 .76 47.2 13.8 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .76 3.47 .80 3.48 .84 3.48 .59 3.50 .61 3.50 .64 3.51 .43 3.52 .44 3.52 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 1.00 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.90 .77 .93 1.00 3.92 .82 .98 1.00 3.92 .86 1.00 1.00 3.93 .59 .75 .89 3.94 .62 .79 .95 3.94 .65 .84 .99 3.95 .44 .58 .72 3.97 .45 .61 .77 3.97 .46 .64 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.4 42.6 43.6 44.2 45.2 46.0 47.2 48.2 49.0 12.1 12.5 12.8 13.0 13.2 13.5 13.8 14.1 14.4

85_F kBtuh kW 29_C 1.00 38.4 11.3 1.00 39.4 11.5 1.00 40.4 11.8 .85 40.8 12.0 .91 41.7 12.2 .95 42.5 12.5 .69 43.7 12.8 .74 44.5 13.0 .78 45.2 13.2

85_F kBtuh kW 29_C 1.00 36.7 10.8 1.00 37.7 11.0 1.00 38.9 11.4 .87 39.1 11.5 .93 39.9 11.7 .97 40.6 11.9 .71 41.8 12.3 .75 42.5 12.5 .79 43.2 12.7

HP26-042
Entering Wet Bulb Tempera ture

CR26-36N/W-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.72 .73 2.73 .77 2.73 .80 2.74 .57 2.74 .59 2.75 .62 2.76 .43 2.76 .43 2.77 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.0 11.4 3.07 .74 1.00 40.0 11.7 3.07 .78 1.00 40.9 12.0 3.08 .82 .84 41.4 12.1 3.08 .58 .89 42.2 12.4 3.09 .60 .93 42.9 12.6 3.09 .62 .68 44.2 13.0 3.11 .43 .72 45.0 13.2 3.11 .44 .76 45.7 13.4 3.11 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .76 3.47 .80 3.47 .84 3.48 .59 3.49 .61 3.49 .63 3.50 .43 3.50 .44 3.51 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .98 .73 .77 .82 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.90 .78 .92 1.00 3.91 .81 .97 1.00 3.91 .85 1.00 1.00 3.92 .60 .75 .89 3.93 .62 .79 .94 3.94 .64 .84 .98 3.94 .43 .58 .72 3.95 .44 .61 .77 3.96 .45 .64 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.4 41.4 42.3 42.9 43.8 44.5 45.8 46.7 47.4 11.8 12.1 12.4 12.6 12.8 13.0 13.4 13.7 13.9

85_F kBtuh kW 29_C .99 37.5 11.0 1.00 38.5 11.3 1.00 39.4 11.5 .86 39.8 11.7 .90 40.6 11.9 .95 41.2 12.1 .69 42.5 12.5 .74 43.3 12.7 .77 43.9 12.9

85_F kBtuh kW 29_C 1.00 35.9 10.5 1.00 36.9 10.8 1.00 37.8 11.1 .88 38.1 11.2 .92 38.9 11.4 .96 39.4 11.5 .71 40.7 11.9 .75 41.4 12.1 .79 42.0 12.3

HP26-042 - C26-51 - C33-50C HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.4 50.0 50.5 kW 14.5 14.7 14.8 Comp. Motor kW Input 3.56 3.30 3.11 45_F (7_C) Total Heating Capacity kBtuh 38.9 39.5 40.0 kW 11.4 11.6 11.7 Comp. Motor kW Input 3.26 3.01 2.81 25_F (-4_C) Total Heating Capacity kBtuh 27.9 28.5 29.0 kW 8.2 8.4 8.5 Comp. Motor kW Input 2.96 2.70 2.51 5_F (-15_C) Total Heating Capacity kBtuh 20.5 21.1 21.6 kW 6.0 6.2 6.3 Comp. Motor kW Input 2.62 2.36 2.17 -15_F (-26_C) Total Heating Capacity kBtuh 10.1 10.7 11.2 kW 3.0 3.1 3.3 Comp. Motor kW Input 1.99 1.73 1.54

HP26-042 - CR26-36N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.6 49.8 50.3 kW 14.8 14.6 14.7 Comp. Motor kW Input 3.14 3.31 3.10 45_F (7_C) Total Heating Capacity kBtuh 40.4 39.6 40.1 kW 11.8 11.6 11.8 Comp. Motor kW Input 2.83 3.00 2.79 25_F (-4_C) Total Heating Capacity kBtuh 29.5 28.7 29.2 kW 8.6 8.4 8.6 Comp. Motor kW Input 2.51 2.69 2.47 5_F (-15_C) Total Heating Capacity kBtuh 22.3 21.5 22.0 kW 6.5 6.3 6.4 Comp. Motor kW Input 2.16 2.34 2.12 -15_F (-26_C) Total Heating Capacity kBtuh 11.7 10.9 11.4 kW 3.4 3.2 3.3 Comp. Motor kW Input 1.54 1.72 1.50

HP26-042 - C26-51 - C33-50C HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.30 3.23 3.16 3.09 3.05 3.01 2.90 2.80 2.75 2.70 2.65 2.62 2.59 2.52 2.36 2.21 2.05 1.89 1.73 1.57 Total Output kBtuh 50.0 47.6 45.2 42.8 41.4 39.5 34.9 30.3 29.4 28.5 27.5 27.0 26.0 23.6 21.1 18.5 15.9 13.3 10.7 8.1 kW 14.7 14.0 13.2 12.5 12.1 11.6 10.2 8.9 8.6 8.4 8.1 7.9 7.6 6.9 6.2 5.4 4.7 3.9 3.1 2.4

HP26-042 - CR26-36N/W-F HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.31 3.24 3.16 3.09 3.05 3.00 2.90 2.79 2.74 2.69 2.63 2.60 2.57 2.50 2.34 2.18 2.03 1.87 1.72 1.56 Total Output kBtuh 49.8 47.5 45.1 42.8 41.4 39.6 35.0 30.4 29.6 28.7 27.9 27.4 26.5 24.1 21.5 18.8 16.2 13.5 10.9 8.2 kW 14.6 13.9 13.2 12.5 12.1 11.6 10.3 8.9 8.7 8.4 8.2 8.0 7.8 7.1 6.3 5.5 4.7 4.0 3.2 2.4

HP26 / Page 43 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CR26-48N/W-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.72 .72 2.73 .76 2.74 .79 2.74 .57 2.75 .59 2.76 .61 2.76 .43 2.77 .43 2.77 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .91 .94 .70 .73 .77 .55 .57 .59

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 39.2 11.5 3.07 .73 1.00 40.2 11.8 3.08 .77 1.00 41.1 12.0 3.09 .81 .83 41.8 12.3 3.09 .57 .87 42.7 12.5 3.10 .59 .92 43.4 12.7 3.10 .61 .67 44.7 13.1 3.11 .43 .71 45.6 13.4 3.12 .43 .74 46.3 13.6 3.13 .44 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .74 .78 .55 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .75 3.47 .79 3.48 .82 3.49 .58 3.49 .60 3.50 .62 3.51 .43 3.52 .44 3.52 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .76 .91 1.00 3.91 .80 .96 1.00 3.92 .84 .99 1.00 3.93 .59 .74 .88 3.94 .61 .78 .93 3.94 .64 .81 .97 3.95 .43 .57 .71 3.96 .44 .60 .75 3.97 .45 .62 .79

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.6 41.7 42.6 43.4 44.3 45.1 46.3 47.3 48.1 11.9 12.2 12.5 12.7 13.0 13.2 13.6 13.9 14.1

85_F kBtuh kW 29_C .99 37.7 11.0 1.00 38.6 11.3 1.00 39.5 11.6 .84 40.2 11.8 .89 41.0 12.0 .93 41.7 12.2 .68 43.0 12.6 .72 43.8 12.8 .76 44.4 13.0

85_F kBtuh kW 29_C 1.00 36.1 10.6 1.00 37.0 10.8 1.00 37.9 11.1 .86 38.4 11.3 .91 39.2 11.5 .95 39.9 11.7 .70 41.1 12.0 .74 41.9 12.3 .77 42.5 12.5

HP26-042
Entering Wet Bulb Tempera ture

CR26-60N/W-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.74 .73 2.75 .77 2.75 .80 2.76 .57 2.76 .59 2.77 .61 2.78 .43 2.78 .43 2.79 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .92 .96 .71 .74 .78 .55 .58 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 40.5 11.9 3.09 .74 1.00 41.6 12.2 3.09 .78 1.00 42.6 12.5 3.10 .82 .84 43.1 12.6 3.11 .58 .89 44.1 12.9 3.11 .60 .93 44.9 13.2 3.12 .62 .68 46.1 13.5 3.13 .43 .72 47.1 13.8 3.14 .44 .76 47.8 14.0 3.14 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .94 .97 .72 .76 .80 .56 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.48 .75 3.49 .80 3.50 .83 3.50 .58 3.51 .61 3.52 .63 3.53 .43 3.53 .44 3.54 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .81 .57 .60 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.92 .77 .92 1.00 3.93 .81 .97 1.00 3.94 .85 1.00 1.00 3.94 .59 .74 .89 3.96 .62 .79 .94 3.96 .65 .83 .99 3.97 .43 .58 .72 3.98 .44 .61 .76 3.99 .46 .63 .81

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 42.0 43.2 44.2 44.8 45.8 46.6 47.9 48.9 49.7 12.3 12.7 13.0 13.1 13.4 13.7 14.0 14.3 14.6

85_F kBtuh kW 29_C 1.00 38.9 11.4 1.00 39.9 11.7 1.00 40.9 12.0 .85 41.4 12.1 .90 42.3 12.4 .95 43.0 12.6 .69 44.3 13.0 .73 45.2 13.2 .77 45.9 13.5

85_F kBtuh kW 29_C 1.00 37.2 10.9 1.00 38.2 11.2 1.00 39.3 11.5 .87 39.6 11.6 .92 40.5 11.9 .97 41.1 12.0 .70 42.4 12.4 .75 43.2 12.7 .79 43.8 12.8

HP26-042 - CR26-48N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 50.9 49.7 50.2 kW 14.9 14.6 14.7 Comp. Motor kW Input 3.17 3.37 3.16 45_F (7_C) Total Heating Capacity kBtuh 40.6 39.4 39.9 kW 11.9 11.5 11.7 Comp. Motor kW Input 2.77 2.96 2.75 25_F (-4_C) Total Heating Capacity kBtuh 29.6 28.4 28.9 kW 8.7 8.3 8.5 Comp. Motor kW Input 2.31 2.50 2.29 5_F (-15_C) Total Heating Capacity kBtuh 22.3 21.1 21.6 kW 6.5 6.2 6.3 Comp. Motor kW Input 2.16 2.36 2.15 -15_F (-26_C) Total Heating Capacity kBtuh 11.9 10.7 11.2 kW 3.5 3.1 3.3 Comp. Motor kW Input 1.53 1.73 1.52

HP26-042 - CR26-60N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.4 50.0 50.4 kW 14.5 14.7 14.8 Comp. Motor kW Input 3.36 3.16 2.98 45_F (7_C) Total Heating Capacity kBtuh 38.9 39.5 39.9 kW 11.4 11.6 11.7 Comp. Motor kW Input 3.02 2.82 2.64 25_F (-4_C) Total Heating Capacity kBtuh 27.9 28.5 28.9 kW 8.2 8.4 8.5 Comp. Motor kW Input 2.62 2.42 2.24 5_F (-15_C) Total Heating Capacity kBtuh 20.5 21.1 21.5 kW 6.0 6.2 6.3 Comp. Motor kW Input 2.51 2.31 2.13 -15_F (-26_C) Total Heating Capacity kBtuh 10.1 10.7 11.1 kW 3.0 3.1 3.3 Comp. Motor kW Input 1.89 1.69 1.51

HP26-042 - CR26-60N/W-F HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.16 3.10 3.03 2.97 2.93 2.82 2.53 2.25 2.33 2.42 2.50 2.55 2.53 2.46 2.31 2.15 2.00 1.84 1.69 1.53 Total Output kBtuh 50.0 47.6 45.2 42.8 41.4 39.5 34.9 30.3 29.4 28.5 27.5 27.0 26.0 23.6 21.1 18.5 15.9 13.3 10.7 8.1 kW 14.7 14.0 13.2 12.5 12.1 11.6 10.2 8.9 8.6 8.4 8.1 7.9 7.6 6.9 6.2 5.4 4.7 3.9 3.1 2.4

HP26-042 - CR26-48N/W-F HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.37 3.29 3.21 3.13 3.09 2.96 2.66 2.35 2.43 2.50 2.58 2.62 2.59 2.51 2.36 2.20 2.04 1.89 1.73 1.57 Total Output kBtuh 49.7 47.4 45.0 42.6 41.2 39.4 34.8 30.2 29.3 28.4 27.5 27.0 26.1 23.7 21.1 18.5 15.9 13.3 10.7 8.1 kW 14.6 13.9 13.2 12.5 12.1 11.5 10.2 8.9 8.6 8.3 8.1 7.9 7.6 6.9 6.2 5.4 4.7 3.9 3.1 2.4

HP26 / Page 44 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CH23-41 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.72 .74 2.73 .78 2.74 .81 2.74 .58 2.74 .60 2.75 .62 2.76 .43 2.76 .44 2.77 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .97 .71 .75 .79 .56 .58 .61

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 38.9 11.4 3.07 .75 1.00 39.9 11.7 3.08 .79 1.00 40.8 12.0 3.08 .83 .85 41.2 12.1 3.08 .58 .90 42.1 12.3 3.09 .61 .94 42.7 12.5 3.10 .63 .69 44.0 12.9 3.11 .43 .73 44.8 13.1 3.11 .44 .77 45.4 13.3 3.11 .45 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.46 .77 3.47 .80 3.47 .85 3.48 .59 3.49 .62 3.49 .64 3.50 .43 3.50 .44 3.51 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 .99 .74 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.90 .78 .93 1.00 3.91 .82 .97 1.00 3.91 .86 1.00 1.00 3.92 .60 .76 .90 3.93 .63 .80 .95 3.94 .65 .84 .99 3.94 .44 .59 .73 3.95 .45 .61 .78 3.96 .46 .65 .82

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 40.2 41.3 42.2 42.7 43.6 44.3 45.6 46.4 47.1 11.8 12.1 12.4 12.5 12.8 13.0 13.4 13.6 13.8

85_F kBtuh kW 29_C 1.00 37.4 11.0 1.00 38.4 11.3 1.00 39.4 11.5 .86 39.6 11.6 .91 40.4 11.8 .95 41.1 12.0 .70 42.3 12.4 .75 43.0 12.6 .78 43.6 12.8

85_F kBtuh kW 29_C 1.00 35.9 10.5 1.00 36.9 10.8 1.00 37.9 11.1 .88 37.9 11.1 .93 38.7 11.3 .97 39.3 11.5 .72 40.5 11.9 .76 41.2 12.1 .80 41.7 12.2

HP26-042
Entering Wet Bulb Tempera ture

CH23-51 - CH33-42B-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .74 2.74 .78 2.74 .81 2.74 .58 2.75 .60 2.76 .62 2.76 .43 2.77 .44 2.77 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .97 .71 .75 .79 .56 .58 .61 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.6 11.6 3.07 .75 1.00 40.7 11.9 3.08 .79 1.00 41.6 12.2 3.09 .83 .84 42.0 12.3 3.09 .58 .90 42.9 12.6 3.10 .60 .94 43.6 12.8 3.11 .63 .69 44.9 13.2 3.11 .43 .73 45.7 13.4 3.12 .44 .77 46.4 13.6 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .81 .57 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .76 3.47 .80 3.48 .84 3.49 .59 3.49 .61 3.50 .64 3.51 .43 3.52 .44 3.52 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 .99 .74 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .78 .93 1.00 3.91 .82 .98 1.00 3.92 .86 1.00 1.00 3.93 .60 .75 .89 3.94 .62 .80 .95 3.94 .65 .84 .99 3.95 .44 .58 .73 3.96 .45 .61 .77 3.97 .46 .64 .82

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.0 42.1 43.1 43.6 44.5 45.3 46.5 47.5 48.2 12.0 12.3 12.6 12.8 13.0 13.3 13.6 13.9 14.1

85_F kBtuh kW 29_C 1.00 38.1 11.2 1.00 39.1 11.5 1.00 40.1 11.8 .86 40.4 11.8 .91 41.2 12.1 .95 41.9 12.3 .70 43.1 12.6 .74 43.9 12.9 .78 44.5 13.0

85_F kBtuh kW 29_C 1.00 36.5 10.7 1.00 37.5 11.0 1.00 38.6 11.3 .88 38.7 11.3 .93 39.5 11.6 .97 40.1 11.8 .71 41.3 12.1 .76 42.0 12.3 .80 42.6 12.5

HP26-042 - CH23-41 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.2 49.7 50.1 kW 14.4 14.6 14.7 Comp. Motor kW Input 3.69 3.47 3.29 45_F (7_C) Total Heating Capacity kBtuh 38.9 39.4 39.8 kW 11.4 11.5 11.7 Comp. Motor kW Input 3.33 3.10 2.92 25_F (-4_C) Total Heating Capacity kBtuh 27.9 28.4 28.8 kW 8.2 8.3 8.4 Comp. Motor kW Input 2.95 2.73 2.55 5_F (-15_C) Total Heating Capacity kBtuh 20.6 21.1 21.5 kW 6.0 6.2 6.3 Comp. Motor kW Input 2.57 2.34 2.16 -15_F (-26_C) Total Heating Capacity kBtuh 10.2 10.7 11.1 kW 3.0 3.1 3.3 Comp. Motor kW Input 1.95 1.73 1.55

HP26-042 - CH23-51 - CH33-42B-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.3 49.9 50.4 kW 14.4 14.6 14.8 Comp. Motor kW Input 3.53 3.33 3.15 45_F (7_C) Total Heating Capacity kBtuh 39.0 39.6 40.1 kW 11.4 11.6 11.8 Comp. Motor kW Input 3.21 3.00 2.82 25_F (-4_C) Total Heating Capacity kBtuh 28.0 28.6 29.1 kW 8.2 8.4 8.5 Comp. Motor kW Input 2.87 2.67 2.49 5_F (-15_C) Total Heating Capacity kBtuh 20.7 21.3 21.8 kW 6.1 6.2 6.4 Comp. Motor kW Input 2.52 2.31 2.13 -15_F (-26_C) Total Heating Capacity kBtuh 10.2 10.8 11.3 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.90 1.70 1.52

HP26-042 - CH23-41 HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.47 3.38 3.29 3.20 3.15 3.10 2.98 2.86 2.80 2.73 2.66 2.62 2.59 2.50 2.34 2.19 2.04 1.88 1.73 1.57 Total Output kBtuh 49.7 47.4 45.0 42.6 41.2 39.4 34.8 30.2 29.3 28.4 27.5 27.0 26.1 23.7 21.1 18.5 15.9 13.3 10.7 8.1 kW 14.6 13.9 13.2 12.5 12.1 11.5 10.2 8.9 8.6 8.3 8.1 7.9 7.6 6.9 6.2 5.4 4.7 3.9 3.1 2.4

HP26-042 - CH23-51 - CH33-42B-F HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.33 3.25 3.17 3.09 3.05 3.00 2.89 2.79 2.73 2.67 2.61 2.58 2.54 2.47 2.31 2.16 2.01 1.85 1.70 1.55 Total Output kBtuh 49.9 47.6 45.2 42.8 41.4 39.6 35.0 30.4 29.5 28.6 27.7 27.2 26.3 23.9 21.3 18.6 16.0 13.4 10.8 8.2 kW 14.6 14.0 13.2 12.5 12.1 11.6 10.3 8.9 8.6 8.4 8.1 8.0 7.7 7.0 6.2 5.5 4.7 3.9 3.2 2.4

HP26 / Page 45 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-042
Entering Wet Bulb Tempera ture

CH23-65 - CH33-48C-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 2.73 .73 2.74 .77 2.74 .81 2.75 .57 2.75 .60 2.76 .62 2.77 .43 2.77 .44 2.78 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .79 .56 .58 .61 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 39.9 11.7 3.08 .75 1.00 41.0 12.0 3.08 .79 1.00 42.0 12.3 3.09 .82 .84 42.4 12.4 3.10 .58 .89 43.3 12.7 3.10 .60 .94 44.1 12.9 3.11 .63 .68 45.3 13.3 3.12 .43 .73 46.2 13.5 3.12 .44 .76 46.9 13.7 3.13 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .94 .98 .72 .76 .80 .56 .59 .62 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.47 .76 3.47 .80 3.48 .84 3.49 .59 3.50 .61 3.51 .64 3.51 .43 3.52 .44 3.53 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .96 .99 .73 .78 .82 .57 .60 .63 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 3.91 .77 .93 1.00 3.92 .82 .98 1.00 3.93 .86 1.00 1.00 3.93 .60 .75 .90 3.94 .62 .79 .95 3.95 .65 .84 .99 3.95 .44 .58 .72 3.96 .45 .61 .77 3.98 .46 .64 .81

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1200 1400 1600 1200 1400 1600 1200 1400 1600

L/s kBtuh kW 565 660 755 565 660 755 565 660 755 41.3 42.5 43.5 44.0 45.0 45.8 47.0 48.0 48.7 12.1 12.5 12.7 12.9 13.2 13.4 13.8 14.1 14.3

85_F kBtuh kW 29_C 1.00 38.3 11.2 1.00 39.4 11.5 1.00 40.4 11.8 .86 40.7 11.9 .91 41.6 12.2 .95 42.3 12.4 .70 43.5 12.7 .74 44.4 13.0 .78 45.0 13.2

85_F kBtuh kW 29_C 1.00 36.7 10.8 1.00 37.7 11.0 1.00 38.8 11.4 .87 39.0 11.4 .93 39.8 11.7 .97 40.4 11.8 .71 41.7 12.2 .75 42.4 12.4 .80 43.0 12.6

HP26-048
Entering Wet Bulb Tempera ture

CB30M-46 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.12 .73 3.13 .76 3.14 .79 3.14 .57 3.15 .59 3.16 .61 3.17 .43 3.18 .43 3.19 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .71 .74 .77 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 44.3 13.0 3.52 .74 1.00 45.3 13.3 3.53 .78 1.00 46.2 13.5 3.54 .80 .84 47.1 13.8 3.54 .58 .88 48.0 14.1 3.55 .60 .92 48.7 14.3 3.56 .62 .68 50.4 14.8 3.57 .43 .71 51.2 15.0 3.58 .44 .75 51.9 15.2 3.59 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .72 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.97 .76 3.99 .79 3.99 .82 4.00 .58 4.01 .61 4.02 .63 4.03 .43 4.04 .44 4.06 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .97 .73 .77 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.50 .77 .92 1.00 4.51 .80 .96 1.00 4.51 .84 .99 1.00 4.52 .59 .74 .89 4.53 .61 .78 .93 4.54 .64 .82 .96 4.55 .44 .58 .72 4.57 .44 .60 .76 4.58 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 45.9 46.9 47.8 48.8 49.7 50.5 52.2 53.1 53.8 13.5 13.7 14.0 14.3 14.6 14.8 15.3 15.6 15.8

85_F kBtuh kW 29_C .99 42.6 12.5 1.00 43.6 12.8 1.00 44.5 13.0 .85 45.3 13.3 .89 46.1 13.5 .93 46.8 13.7 .69 48.4 14.2 .73 49.2 14.4 .76 49.8 14.6

85_F kBtuh kW 29_C 1.00 40.8 12.0 1.00 41.8 12.3 1.00 42.7 12.5 .87 43.4 12.7 .91 44.2 13.0 .95 44.8 13.1 .70 46.4 13.6 .74 47.2 13.8 .78 47.7 14.0

HP26-042 - CH23-65 - CH33-48C-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1200 1400 1600 L/s 565 660 755 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 49.4 49.9 50.3 kW 14.5 14.6 14.7 Comp. Motor kW Input 3.39 3.18 3.01 45_F (7_C) Total Heating Capacity kBtuh 39.1 39.6 40.0 kW 11.5 11.6 11.7 Comp. Motor kW Input 3.10 2.89 2.72 25_F (-4_C) Total Heating Capacity kBtuh 28.1 28.6 29.0 kW 8.2 8.4 8.5 Comp. Motor kW Input 2.79 2.59 2.42 5_F (-15_C) Total Heating Capacity kBtuh 20.8 21.3 21.7 kW 6.1 6.2 6.4 Comp. Motor kW Input 2.46 2.26 2.09 -15_F (-26_C) Total Heating Capacity kBtuh 10.3 10.8 11.2 kW 3.0 3.2 3.3 Comp. Motor kW Input 1.86 1.66 1.49

HP26-048 - CB30M-46 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.4 55.9 56.3 kW 16.2 16.4 16.5 Comp. Motor kW Input 3.88 3.74 3.62 45_F (7_C) Total Heating Capacity kBtuh 43.8 44.3 44.7 kW 12.8 13.0 13.1 Comp. Motor kW Input 3.55 3.41 3.29 25_F (-4_C) Total Heating Capacity kBtuh 31.7 32.2 32.6 kW 9.3 9.4 9.6 Comp. Motor kW Input 3.21 3.07 2.95 5_F (-15_C) Total Heating Capacity kBtuh 22.9 23.4 23.8 kW 6.7 6.9 7.0 Comp. Motor kW Input 2.80 2.66 2.55 -15_F (-26_C) Total Heating Capacity kBtuh 11.4 11.9 12.3 kW 3.3 3.5 3.6 Comp. Motor kW Input 2.09 1.95 1.84

HP26-042 - CH23-65 - CH33-48C-F HEATING PERFORMANCE at 1400 cfm (660 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.18 3.11 3.04 2.97 2.93 2.89 2.79 2.69 2.64 2.59 2.54 2.51 2.48 2.41 2.26 2.11 1.96 1.81 1.66 1.51 Total Output kBtuh 49.9 47.6 45.2 42.8 41.4 39.6 35.0 30.4 29.5 28.6 27.7 27.2 26.3 23.9 21.3 18.6 16.0 13.4 10.8 8.2 kW 14.6 14.0 13.2 12.5 12.1 11.6 10.3 8.9 8.6 8.4 8.1 8.0 7.7 7.0 6.2 5.5 4.7 3.9 3.2 2.4

HP26-048 - CB30M-46 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.74 3.66 3.58 3.49 3.45 3.41 3.31 3.21 3.14 3.07 3.00 2.96 2.92 2.84 2.66 2.49 2.31 2.13 1.95 1.77 Total Output kBtuh 55.9 53.2 50.5 47.8 46.2 44.3 39.6 35.0 33.6 32.2 30.8 30.0 28.9 26.2 23.4 20.5 17.6 14.7 11.9 9.0 kW 16.4 15.6 14.8 14.0 13.5 13.0 11.6 10.3 9.8 9.4 9.0 8.8 8.5 7.7 6.9 6.0 5.2 4.3 3.5 2.6

HP26 / Page 46 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CB29M-51 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.38 .77 3.39 .81 3.40 .84 3.41 .60 3.42 .62 3.43 .64 3.45 .44 3.46 .44 3.47 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .92 .96 .99 .75 .78 .82 .58 .60 .63 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C 1.00 40.6 11.9 3.81 .78 1.00 41.6 12.2 3.82 .82 1.00 42.6 12.5 3.84 .86 .89 43.0 12.6 3.85 .60 .93 43.7 12.8 3.86 .62 .97 44.4 13.0 3.86 .65 .72 45.9 13.5 3.89 .44 .76 46.6 13.7 3.90 .45 .80 47.2 13.8 3.90 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .94 .98 1.00 .76 .80 .84 .59 .61 .64 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.30 .80 4.31 .84 4.33 .88 4.34 .61 4.35 .63 4.35 .66 4.38 .44 4.39 .45 4.40 .46 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .95 .99 1.00 .78 .82 .86 .60 .62 .65 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.86 .82 .97 1.00 4.88 .86 1.00 1.00 4.89 .90 1.00 1.00 4.89 .62 .79 .95 4.90 .65 .84 .99 4.92 .67 .87 1.00 4.94 .45 .61 .77 4.95 .46 .64 .81 4.96 .47 .67 .85

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 42.2 43.1 44.0 44.7 45.4 46.0 47.7 48.4 49.0 12.4 12.6 12.9 13.1 13.3 13.5 14.0 14.2 14.4

85_F kBtuh kW 29_C 1.00 39.1 11.5 1.00 40.0 11.7 1.00 41.1 12.0 .91 41.3 12.1 .95 42.0 12.3 .98 42.5 12.5 .74 44.1 12.9 .78 44.7 13.1 .81 45.2 13.2

85_F kBtuh kW 29_C 1.00 37.4 11.0 1.00 38.4 11.3 1.00 39.5 11.6 .93 39.5 11.6 .97 40.2 11.8 1.00 40.7 11.9 .75 42.2 12.4 .79 42.8 12.5 .83 43.3 12.7

HP26-048
Entering Wet Bulb Tempera ture

CB29M-65 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.14 .73 3.15 .76 3.16 .79 3.17 .57 3.17 .59 3.18 .61 3.20 .43 3.21 .43 3.22 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .71 .74 .77 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 45.7 13.4 3.54 .74 1.00 46.7 13.7 3.56 .78 1.00 47.6 14.0 3.56 .81 .84 48.6 14.2 3.57 .58 .88 49.5 14.5 3.58 .60 .92 50.2 14.7 3.59 .62 .68 51.9 15.2 3.60 .43 .71 52.8 15.5 3.61 .44 .74 53.5 15.7 3.62 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .93 .96 .72 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.00 .76 4.02 .79 4.02 .82 4.03 .58 4.04 .60 4.05 .62 4.06 .43 4.07 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .97 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW 75_F 80_F 85_F Input 24_C 27_C 29_C 4.53 .77 .92 1.00 4.54 .81 .96 1.00 4.55 .84 .99 1.00 4.55 .59 .74 .89 4.57 .62 .78 .93 4.57 .64 .82 .97 4.59 .43 .58 .72 4.60 .44 .60 .76 4.61 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 47.3 48.4 49.3 50.4 51.3 52.1 53.8 54.7 55.5 13.9 14.2 14.4 14.8 15.0 15.3 15.8 16.0 16.3

85_F kBtuh kW 29_C .99 43.9 12.9 1.00 44.9 13.2 1.00 45.9 13.5 .85 46.7 13.7 .89 47.6 14.0 .93 48.2 14.1 .69 49.9 14.6 .73 50.8 14.9 .76 51.4 15.1

85_F kBtuh kW 29_C 1.00 42.1 12.3 1.00 43.1 12.6 1.00 44.1 12.9 .87 44.8 13.1 .91 45.5 13.3 .95 46.2 13.5 .71 47.9 14.0 .74 48.6 14.2 .78 49.2 14.4

HP26-048 - CB29M-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 57.0 56.4 55.9 kW 16.7 16.5 16.4 Comp. Motor kW Input 3.84 3.77 3.75 45_F (7_C) Total Heating Capacity kBtuh 45.5 44.9 44.4 kW 13.3 13.2 13.0 Comp. Motor kW Input 3.52 3.45 3.43 25_F (-4_C) Total Heating Capacity kBtuh 33.5 32.9 32.4 kW 9.8 9.6 9.5 Comp. Motor kW Input 3.19 3.13 3.11 5_F (-15_C) Total Heating Capacity kBtuh 24.7 24.1 23.6 kW 7.2 7.1 6.9 Comp. Motor kW Input 2.80 2.73 2.71 -15_F (-26_C) Total Heating Capacity kBtuh 12.8 12.2 11.7 kW 3.8 3.6 3.4 Comp. Motor kW Input 2.06 2.00 1.98

HP26-048 - CB29M-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.2 55.7 56.2 kW 16.2 16.3 16.5 Comp. Motor kW Input 3.90 3.74 3.63 45_F (7_C) Total Heating Capacity kBtuh 43.8 44.3 44.8 kW 12.8 13.0 13.1 Comp. Motor kW Input 3.57 3.42 3.31 25_F (-4_C) Total Heating Capacity kBtuh 32.0 32.5 33.0 kW 9.4 9.5 9.7 Comp. Motor kW Input 3.24 3.09 2.98 5_F (-15_C) Total Heating Capacity kBtuh 23.3 23.8 24.3 kW 6.8 7.0 7.1 Comp. Motor kW Input 2.84 2.69 2.58 -15_F (-26_C) Total Heating Capacity kBtuh 11.6 12.1 12.6 kW 3.4 3.5 3.7 Comp. Motor kW Input 2.12 1.97 1.86

HP26-048 - CB29M-51 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.77 3.69 3.62 3.54 3.49 3.45 3.36 3.26 3.19 3.13 3.06 3.02 2.99 2.91 2.73 2.55 2.36 2.18 2.00 1.81 Total Output kBtuh 56.4 53.7 51.1 48.4 46.8 44.9 40.2 35.6 34.2 32.9 31.6 30.8 29.7 27.1 24.1 21.1 18.2 15.2 12.2 9.2 kW 16.5 15.7 15.0 14.2 13.7 13.2 11.8 10.4 10.0 9.6 9.3 9.0 8.7 7.9 7.1 6.2 5.3 4.5 3.6 2.7

HP26-048 - CB29M-65 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.74 3.66 3.59 3.51 3.46 3.42 3.32 3.22 3.16 3.09 3.02 2.98 2.95 2.87 2.69 2.51 2.33 2.15 1.97 1.79 Total Output kBtuh 55.7 53.0 50.4 47.8 46.2 44.3 39.7 35.1 33.8 32.5 31.2 30.4 29.3 26.7 23.8 20.8 17.9 15.0 12.1 9.1 kW 16.3 15.5 14.8 14.0 13.5 13.0 11.6 10.3 9.9 9.5 9.1 8.9 8.6 7.8 7.0 6.1 5.2 4.4 3.5 2.7

HP26 / Page 47 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CB31MV-51 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.14 .73 3.15 .76 3.16 .79 3.17 .57 3.18 .59 3.19 .60 3.21 .43 3.22 .43 3.23 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .73 .76 .55 .57 .59

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 45.1 13.2 3.54 .74 1.00 46.2 13.5 3.55 .77 1.00 47.2 13.8 3.56 .80 .83 48.2 14.1 3.57 .57 .88 49.1 14.4 3.58 .59 .91 49.9 14.6 3.59 .61 .67 51.5 15.1 3.61 .43 .71 52.5 15.4 3.63 .43 .74 53.2 15.6 3.64 .44 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .75 4.01 .79 4.02 .82 4.03 .58 4.04 .60 4.05 .62 4.08 .43 4.08 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .98 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.52 .77 .92 1.00 4.53 .80 .96 1.00 4.54 .84 .99 1.00 4.54 .59 .74 .88 4.56 .61 .78 .93 4.57 .63 .81 .97 4.59 .43 .58 .72 4.60 .44 .60 .75 4.62 .45 .62 .79

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 46.8 47.9 48.9 50.0 51.0 51.8 53.5 54.4 55.3 13.7 14.0 14.3 14.7 14.9 15.2 15.7 15.9 16.2

85_F kBtuh kW 29_C .99 43.4 12.7 1.00 44.4 13.0 1.00 45.4 13.3 .85 46.2 13.5 .89 47.1 13.8 .93 47.9 14.0 .69 49.5 14.5 .72 50.4 14.8 .76 51.1 15.0

85_F kBtuh kW 29_C 1.00 41.5 12.2 1.00 42.5 12.5 1.00 43.5 12.7 .87 44.3 13.0 .91 45.1 13.2 .95 45.8 13.4 .70 47.4 13.9 .74 48.2 14.1 .77 48.8 14.3

HP26-048
Entering Wet Bulb Tempera ture

CB30M-51 - CB30U-51 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.14 .73 3.15 .76 3.16 .79 3.17 .57 3.18 .59 3.19 .60 3.21 .43 3.22 .43 3.23 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .73 .77 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 46.0 13.5 3.54 .74 1.00 47.1 13.8 3.55 .77 1.00 48.1 14.1 3.56 .80 .83 49.1 14.4 3.57 .57 .88 50.1 14.7 3.58 .59 .91 50.8 14.9 3.59 .61 .68 52.5 15.4 3.61 .43 .71 53.5 15.7 3.63 .44 .74 54.3 15.9 3.64 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .75 4.01 .79 4.02 .82 4.03 .58 4.04 .60 4.05 .62 4.08 .43 4.08 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .98 .73 .76 .80 .56 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.52 .77 .92 1.00 4.53 .80 .96 1.00 4.54 .84 .99 1.00 4.54 .59 .74 .88 4.56 .61 .78 .93 4.57 .64 .81 .97 4.59 .43 .58 .72 4.60 .44 .60 .75 4.62 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 47.7 48.9 49.9 50.9 51.9 52.8 54.5 55.5 56.3 14.0 14.3 14.6 14.9 15.2 15.5 16.0 16.3 16.5

85_F kBtuh kW 29_C .99 44.2 13.0 1.00 45.3 13.3 1.00 46.2 13.5 .85 47.1 13.8 .89 48.1 14.1 .93 48.8 14.3 .69 50.5 14.8 .72 51.4 15.1 .76 52.1 15.3

85_F kBtuh kW 29_C 1.00 42.3 12.4 1.00 43.4 12.7 1.00 44.4 13.0 .86 45.1 13.2 .91 46.0 13.5 .95 46.7 13.7 .70 48.3 14.2 .74 49.2 14.4 .77 49.8 14.6

HP26-048 - CB31MV-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.8 55.2 55.5 kW 16.1 16.2 16.3 Comp. Motor kW Input 3.74 3.61 3.49 45_F (7_C) Total Heating Capacity kBtuh 43.3 43.7 44.0 kW 12.7 12.8 12.9 Comp. Motor kW Input 3.45 3.32 3.20 25_F (-4_C) Total Heating Capacity kBtuh 31.4 31.8 32.1 kW 9.2 9.3 9.4 Comp. Motor kW Input 3.16 3.03 2.91 5_F (-15_C) Total Heating Capacity kBtuh 22.6 23.0 23.3 kW 6.6 6.7 6.8 Comp. Motor kW Input 2.79 2.66 2.54 -15_F (-26_C) Total Heating Capacity kBtuh 11.3 11.7 12.0 kW 3.3 3.4 3.5 Comp. Motor kW Input 2.08 1.94 1.83

HP26-048 - CB30M-51 - CB30U-51 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.1 55.6 56.0 kW 16.1 16.3 16.4 Comp. Motor kW Input 3.70 3.56 3.45 45_F (7_C) Total Heating Capacity kBtuh 43.6 44.1 44.5 kW 12.8 12.9 13.0 Comp. Motor kW Input 3.43 3.29 3.18 25_F (-4_C) Total Heating Capacity kBtuh 31.7 32.2 32.6 kW 9.3 9.4 9.6 Comp. Motor kW Input 3.16 3.02 2.91 5_F (-15_C) Total Heating Capacity kBtuh 22.9 23.4 23.8 kW 6.7 6.9 7.0 Comp. Motor kW Input 2.80 2.67 2.55 -15_F (-26_C) Total Heating Capacity kBtuh 11.4 11.9 12.3 kW 3.3 3.5 3.6 Comp. Motor kW Input 2.08 1.94 1.83

HP26-048 - CB31MV-51 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.61 3.54 3.47 3.40 3.35 3.32 3.23 3.15 3.09 3.03 2.97 2.93 2.91 2.84 2.66 2.48 2.30 2.12 1.94 1.76 Total Output kBtuh 55.2 52.5 49.9 47.2 45.6 43.7 39.1 34.5 33.1 31.8 30.4 29.6 28.5 25.9 23.0 20.2 17.4 14.5 11.7 8.9 kW 16.2 15.4 14.6 13.8 13.4 12.8 11.5 10.1 9.7 9.3 8.9 8.7 8.4 7.6 6.7 5.9 5.1 4.2 3.4 2.6

HP26-048 - CB30M-51 - CB30U-51 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.56 3.50 3.43 3.37 3.33 3.29 3.21 3.13 3.08 3.02 2.97 2.94 2.91 2.85 2.67 2.49 2.31 2.12 1.94 1.76 Total Output kBtuh 55.6 52.9 50.3 47.6 46.0 44.1 39.5 34.8 33.5 32.2 30.8 30.0 28.9 26.3 23.4 20.5 17.6 14.8 11.9 9.0 kW 16.3 15.5 14.7 14.0 13.5 12.9 11.6 10.2 9.8 9.4 9.0 8.8 8.5 7.7 6.9 6.0 5.2 4.3 3.5 2.6

HP26 / Page 48 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CB31MV-65 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.14 .73 3.15 .76 3.16 .79 3.17 .57 3.18 .59 3.19 .61 3.21 .43 3.22 .43 3.23 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .73 .77 .55 .57 .59

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 46.4 13.6 3.54 .74 1.00 47.5 13.9 3.55 .77 1.00 48.5 14.2 3.56 .80 .83 49.4 14.5 3.57 .57 .87 50.4 14.8 3.58 .60 .91 51.2 15.0 3.59 .61 .68 52.9 15.5 3.61 .43 .71 53.9 15.8 3.63 .44 .74 54.7 16.0 3.64 .44 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .75 4.01 .79 4.02 .82 4.03 .58 4.04 .60 4.05 .62 4.08 .43 4.08 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .98 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.52 .77 .92 1.00 4.53 .80 .96 1.00 4.54 .84 .99 1.00 4.54 .59 .74 .88 4.56 .61 .78 .93 4.57 .64 .81 .97 4.59 .43 .57 .71 4.60 .44 .60 .75 4.62 .45 .62 .79

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 48.1 49.2 50.2 51.3 52.3 53.2 54.9 55.9 56.7 14.1 14.4 14.7 15.0 15.3 15.6 16.1 16.4 16.6

85_F kBtuh kW 29_C 1.00 44.6 13.1 1.00 45.6 13.4 1.00 46.6 13.7 .85 47.5 13.9 .89 48.4 14.2 .93 49.1 14.4 .69 50.8 14.9 .72 51.8 15.2 .76 52.5 15.4

85_F kBtuh kW 29_C 1.00 42.7 12.5 1.00 43.7 12.8 1.00 44.7 13.1 .86 45.5 13.3 .91 46.3 13.6 .95 47.0 13.8 .70 48.7 14.3 .74 49.5 14.5 .77 50.2 14.7

HP26-048
Entering Wet Bulb Tempera ture

CB30M-65 - CB30U-65 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.16 .73 3.17 .76 3.17 .79 3.18 .57 3.20 .59 3.20 .60 3.22 .43 3.23 .43 3.24 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .74 .77 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 46.9 13.7 3.56 .74 1.00 48.0 14.1 3.57 .77 1.00 49.0 14.4 3.57 .80 .83 50.0 14.7 3.59 .58 .87 51.0 14.9 3.60 .59 .91 51.8 15.2 3.61 .61 .68 53.5 15.7 3.63 .43 .71 54.5 16.0 3.64 .43 .74 55.3 16.2 3.65 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.01 .75 4.02 .79 4.04 .82 4.05 .58 4.06 .60 4.07 .62 4.10 .43 4.10 .44 4.11 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .98 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.54 .77 .92 1.00 4.55 .80 .96 1.00 4.56 .84 .99 1.00 4.56 .59 .74 .89 4.58 .61 .78 .93 4.60 .63 .81 .97 4.61 .43 .57 .71 4.62 .44 .60 .75 4.64 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 48.6 49.8 50.8 51.9 52.9 53.8 55.5 56.6 57.4 14.2 14.6 14.9 15.2 15.5 15.8 16.3 16.6 16.8

85_F kBtuh kW 29_C .99 45.1 13.2 1.00 46.1 13.5 1.00 47.1 13.8 .85 48.0 14.1 .89 49.0 14.4 .93 49.7 14.6 .69 51.4 15.1 .72 52.3 15.3 .76 53.1 15.6

85_F kBtuh kW 29_C 1.00 43.2 12.7 1.00 44.2 13.0 1.00 45.2 13.2 .87 46.0 13.5 .91 46.9 13.7 .95 47.5 13.9 .70 49.3 14.4 .74 50.1 14.7 .77 50.7 14.9

HP26-048 - CB31MV-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.6 55.0 55.4 kW 16.0 16.1 16.2 Comp. Motor kW Input 3.73 3.59 3.48 45_F (7_C) Total Heating Capacity kBtuh 43.2 43.6 44.0 kW 12.7 12.8 12.9 Comp. Motor kW Input 3.44 3.30 3.19 25_F (-4_C) Total Heating Capacity kBtuh 31.2 31.6 32.0 kW 9.1 9.3 9.4 Comp. Motor kW Input 3.15 3.01 2.90 5_F (-15_C) Total Heating Capacity kBtuh 22.5 22.9 23.3 kW 6.6 6.7 6.8 Comp. Motor kW Input 2.77 2.63 2.52 -15_F (-26_C) Total Heating Capacity kBtuh 11.2 11.6 12.0 kW 3.3 3.4 3.5 Comp. Motor kW Input 2.06 1.92 1.81

HP26-048 - CB30M-65 - CB30U-65 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.4 55.9 56.3 kW 16.2 16.4 16.5 Comp. Motor kW Input 3.74 3.60 3.49 45_F (7_C) Total Heating Capacity kBtuh 43.8 44.3 44.7 kW 12.8 13.0 13.1 Comp. Motor kW Input 3.46 3.32 3.21 25_F (-4_C) Total Heating Capacity kBtuh 31.7 32.2 32.6 kW 9.3 9.4 9.6 Comp. Motor kW Input 3.18 3.03 2.92 5_F (-15_C) Total Heating Capacity kBtuh 22.9 23.4 23.8 kW 6.7 6.9 7.0 Comp. Motor kW Input 2.81 2.67 2.56 -15_F (-26_C) Total Heating Capacity kBtuh 11.4 11.9 12.3 kW 3.3 3.5 3.6 Comp. Motor kW Input 2.09 1.95 1.84

HP26-048 - CB31MV-65 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.59 3.52 3.45 3.38 3.34 3.30 3.21 3.13 3.07 3.01 2.95 2.91 2.88 2.81 2.63 2.46 2.28 2.10 1.92 1.75 Total Output kBtuh 55.0 52.3 49.7 47.0 45.4 43.6 38.9 34.3 33.0 31.6 30.2 29.4 28.3 25.7 22.9 20.1 17.2 14.4 11.6 8.8 kW 16.1 15.3 14.6 13.8 13.3 12.8 11.4 10.1 9.7 9.3 8.9 8.6 8.3 7.5 6.7 5.9 5.0 4.2 3.4 2.6

HP26-048 - CB30M-65 - CB30U-65 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.60 3.53 3.46 3.39 3.35 3.32 3.23 3.15 3.09 3.03 2.98 2.94 2.92 2.85 2.67 2.49 2.31 2.13 1.95 1.77 Total Output kBtuh 55.9 53.2 50.5 47.8 46.2 44.3 39.6 35.0 33.6 32.2 30.8 30.0 28.9 26.2 23.4 20.5 17.6 14.7 11.9 9.0 kW 16.4 15.6 14.8 14.0 13.5 13.0 11.6 10.3 9.8 9.4 9.0 8.8 8.5 7.7 6.9 6.0 5.2 4.3 3.5 2.6

HP26 / Page 49 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CVP10-46/EC10Q4 COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.11 .73 3.12 .76 3.13 .79 3.14 .57 3.14 .59 3.15 .61 3.17 .43 3.17 .43 3.18 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .71 .74 .77 .55 .57 .59 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 44.0 12.9 3.51 .74 1.00 45.0 13.2 3.52 .77 1.00 45.9 13.5 3.53 .81 .84 46.8 13.7 3.53 .58 .88 47.7 14.0 3.54 .60 .92 48.4 14.2 3.55 .61 .68 50.0 14.7 3.57 .43 .71 50.8 14.9 3.58 .44 .75 51.5 15.1 3.58 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .72 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.97 .75 3.98 .79 3.99 .82 3.99 .58 4.00 .60 4.01 .63 4.02 .43 4.03 .44 4.04 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .97 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.50 .77 .92 1.00 4.50 .80 .96 1.00 4.51 .84 .99 1.00 4.51 .59 .74 .88 4.52 .61 .78 .93 4.53 .64 .82 .96 4.54 .43 .58 .72 4.55 .44 .60 .76 4.57 .45 .62 .79

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 45.5 46.6 47.5 48.5 49.4 50.1 51.8 52.7 53.4 13.3 13.7 13.9 14.2 14.5 14.7 15.2 15.4 15.6

85_F kBtuh kW 29_C .99 42.3 12.4 1.00 43.3 12.7 1.00 44.2 13.0 .85 45.0 13.2 .89 45.8 13.4 .93 46.5 13.6 .69 48.1 14.1 .73 48.9 14.3 .76 49.5 14.5

85_F kBtuh kW 29_C 1.00 40.6 11.9 1.00 41.6 12.2 1.00 42.5 12.5 .87 43.1 12.6 .91 43.9 12.9 .95 44.5 13.0 .70 46.1 13.5 .74 46.9 13.7 .78 47.4 13.9

HP26-048
Entering Wet Bulb Tempera ture

CVP10-51/EC10Q4 COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.10 .73 3.11 .76 3.12 .79 3.12 .57 3.13 .59 3.15 .60 3.16 .43 3.17 .43 3.18 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .73 .76 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 44.2 13.0 3.50 .74 1.00 45.3 13.3 3.51 .77 1.00 46.2 13.5 3.51 .80 .83 47.2 13.8 3.52 .57 .87 48.1 14.1 3.54 .59 .91 48.8 14.3 3.54 .61 .67 50.4 14.8 3.56 .43 .71 51.3 15.0 3.57 .43 .74 52.1 15.3 3.58 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .74 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.95 .75 3.95 .78 3.96 .82 3.98 .58 3.99 .60 4.00 .62 4.02 .43 4.03 .44 4.04 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .97 .72 .76 .80 .56 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.46 .77 .92 1.00 4.47 .80 .96 1.00 4.48 .84 .99 1.00 4.49 .59 .74 .88 4.50 .61 .78 .93 4.51 .63 .81 .96 4.53 .43 .57 .71 4.54 .44 .60 .75 4.55 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 45.8 46.9 47.9 48.9 49.9 50.7 52.3 53.3 54.0 13.4 13.7 14.0 14.3 14.6 14.9 15.3 15.6 15.8

85_F kBtuh kW 29_C .99 42.5 12.5 1.00 43.6 12.8 1.00 44.5 13.0 .85 45.3 13.3 .89 46.2 13.5 .93 46.9 13.7 .69 48.5 14.2 .72 49.3 14.4 .75 50.0 14.7

85_F kBtuh kW 29_C 1.00 40.7 11.9 1.00 41.7 12.2 1.00 42.7 12.5 .86 43.4 12.7 .91 44.2 13.0 .95 44.9 13.2 .70 46.4 13.6 .74 47.3 13.9 .77 47.9 14.0

HP26-048 - CVP10-46/EC10Q4 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.3 55.2 55.2 kW 15.9 16.2 16.2 Comp. Motor kW Input 3.92 3.86 3.66 45_F (7_C) Total Heating Capacity kBtuh 43.1 44.0 44.0 kW 12.6 12.9 12.9 Comp. Motor kW Input 3.55 3.49 3.29 25_F (-4_C) Total Heating Capacity kBtuh 31.4 32.3 32.3 kW 9.2 9.5 9.5 Comp. Motor kW Input 3.18 3.12 2.92 5_F (-15_C) Total Heating Capacity kBtuh 22.7 23.6 23.6 kW 6.7 6.9 6.9 Comp. Motor kW Input 2.75 2.69 2.49 -15_F (-26_C) Total Heating Capacity kBtuh 11.1 12.0 12.0 kW 3.3 3.5 3.5 Comp. Motor kW Input 2.03 1.97 1.78

HP26-048 - CVP10-51/EC10Q4 HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.3 55.2 55.3 kW 15.9 16.2 16.2 Comp. Motor kW Input 3.86 3.80 3.62 45_F (7_C) Total Heating Capacity kBtuh 43.1 44.0 44.1 kW 12.6 12.9 12.9 Comp. Motor kW Input 3.55 3.49 3.31 25_F (-4_C) Total Heating Capacity kBtuh 31.4 32.3 32.4 kW 9.2 9.5 9.5 Comp. Motor kW Input 3.24 3.18 3.00 5_F (-15_C) Total Heating Capacity kBtuh 22.7 23.6 23.7 kW 6.7 6.9 6.9 Comp. Motor kW Input 2.84 2.79 2.60 -15_F (-26_C) Total Heating Capacity kBtuh 11.1 12.0 12.1 kW 3.3 3.5 3.5 Comp. Motor kW Input 2.09 2.04 1.85

HP26-048 - CVP10-46/EC10Q4 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.86 3.77 3.68 3.59 3.53 3.49 3.38 3.27 3.19 3.12 3.04 2.99 2.96 2.87 2.69 2.51 2.33 2.15 1.97 1.80 Total Output kBtuh 55.2 52.6 50.0 47.4 45.8 44.0 39.4 34.8 33.5 32.3 31.0 30.2 29.2 26.6 23.6 20.7 17.8 14.9 12.0 9.1 kW 16.2 15.4 14.7 13.9 13.4 12.9 11.5 10.2 9.8 9.5 9.1 8.9 8.6 7.8 6.9 6.1 5.2 4.4 3.5 2.7

HP26-048 - CVP10-51/EC1-Q4 HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.80 3.73 3.65 3.58 3.53 3.49 3.40 3.31 3.25 3.18 3.12 3.08 3.05 2.98 2.79 2.60 2.41 2.22 2.04 1.85 Total Output kBtuh 55.2 52.6 50.0 47.4 45.8 44.0 39.4 34.8 33.5 32.3 31.0 30.2 29.2 26.6 23.6 20.7 17.8 14.9 12.0 9.1 kW 16.2 15.4 14.7 13.9 13.4 12.9 11.5 10.2 9.8 9.5 9.1 8.9 8.6 7.8 6.9 6.1 5.2 4.4 3.5 2.7

HP26 / Page 50 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Temperat ure

C26-51/65 - C33-50C COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.13 .73 3.15 .76 3.15 .79 3.16 .57 3.18 .59 3.18 .61 3.20 .43 3.21 .43 3.22 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .71 .74 .77 .55 .57 .60 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 46.2 13.5 3.54 .74 1.00 47.4 13.9 3.54 .78 1.00 48.4 14.2 3.55 .81 .84 49.2 14.4 3.57 .58 .88 50.2 14.7 3.58 .60 .92 51.0 14.9 3.58 .62 .68 52.6 15.4 3.60 .43 .72 53.6 15.7 3.62 .44 .75 54.3 15.9 3.63 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .96 .72 .75 .79 .56 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .76 4.00 .79 4.01 .83 4.02 .59 4.03 .61 4.04 .63 4.07 .43 4.08 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .95 .98 .73 .77 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.51 .77 .92 1.00 4.52 .81 .96 1.00 4.53 .84 .99 1.00 4.54 .60 .75 .89 4.55 .62 .79 .94 4.56 .64 .82 .97 4.59 .44 .58 .72 4.59 .44 .60 .76 4.60 .45 .63 .80

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 47.9 49.1 50.1 51.1 52.1 52.9 54.6 55.6 56.4 14.0 14.4 14.7 15.0 15.3 15.5 16.0 16.3 16.5

85_F kBtuh kW 29_C 1.00 44.4 13.0 1.00 45.5 13.3 1.00 46.5 13.6 .85 47.3 13.9 .90 48.2 14.1 .94 48.9 14.3 .69 50.6 14.8 .73 51.5 15.1 .76 52.2 15.3

85_F kBtuh kW 29_C 1.00 42.6 12.5 1.00 43.7 12.8 1.00 44.7 13.1 .87 45.3 13.3 .92 46.1 13.5 .96 46.8 13.7 .71 48.4 14.2 .74 49.3 14.4 .78 49.9 14.6

HP26-048
Entering Wet Bulb Tempera ture

C26-65EAP - C33-62D COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.16 .73 3.17 .76 3.18 .79 3.19 .57 3.20 .59 3.21 .60 3.23 .43 3.24 .43 3.25 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .70 .73 .76 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 47.3 13.9 3.56 .74 1.00 48.5 14.2 3.57 .77 1.00 49.5 14.5 3.58 .80 .83 50.5 14.8 3.60 .58 .88 51.6 15.1 3.60 .59 .91 52.4 15.4 3.62 .61 .68 54.1 15.9 3.64 .43 .71 55.1 16.1 3.65 .44 .74 55.9 16.4 3.66 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.02 .75 4.03 .79 4.05 .82 4.06 .58 4.07 .60 4.08 .62 4.10 .43 4.11 .44 4.12 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .98 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.54 .77 .92 1.00 4.56 .80 .96 1.00 4.57 .84 .99 1.00 4.58 .59 .74 .88 4.59 .61 .78 .93 4.60 .63 .81 .97 4.62 .43 .57 .72 4.63 .44 .60 .75 4.64 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 49.1 50.3 51.3 52.4 53.5 54.4 56.1 57.2 58.0 14.4 14.7 15.0 15.4 15.7 15.9 16.4 16.8 17.0

85_F kBtuh kW 29_C 1.00 45.5 13.3 1.00 46.6 13.7 1.00 47.6 14.0 .85 48.5 14.2 .89 49.5 14.5 .93 50.2 14.7 .69 52.0 15.2 .72 52.9 15.5 .76 53.7 15.7

85_F kBtuh kW 29_C 1.00 43.6 12.8 1.00 44.6 13.1 1.00 45.6 13.4 .86 46.4 13.6 .91 47.3 13.9 .95 48.0 14.1 .70 49.8 14.6 .74 50.6 14.8 .77 51.3 15.0

HP26-048 - C26-51/65 - C33-50C HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.7 55.2 55.7 kW 16.0 16.2 16.3 Comp. Motor kW Input 3.84 3.69 3.55 45_F (7_C) Total Heating Capacity kBtuh 43.5 44.0 44.5 kW 12.7 12.9 13.0 Comp. Motor kW Input 3.58 3.43 3.29 25_F (-4_C) Total Heating Capacity kBtuh 31.8 32.3 32.8 kW 9.3 9.5 9.6 Comp. Motor kW Input 3.32 3.16 3.03 5_F (-15_C) Total Heating Capacity kBtuh 23.1 23.6 24.1 kW 6.8 6.9 7.1 Comp. Motor kW Input 2.96 2.80 2.67 -15_F (-26_C) Total Heating Capacity kBtuh 11.5 12.0 12.5 kW 3.4 3.5 3.7 Comp. Motor kW Input 2.20 2.04 1.91

HP26-048 - C26-65EAP - C33-62D HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.1 55.6 56.0 kW 16.1 16.3 16.4 Comp. Motor kW Input 3.71 3.56 3.45 45_F (7_C) Total Heating Capacity kBtuh 43.6 44.1 44.5 kW 12.8 12.9 13.0 Comp. Motor kW Input 3.45 3.31 3.19 25_F (-4_C) Total Heating Capacity kBtuh 31.7 32.2 32.6 kW 9.3 9.4 9.6 Comp. Motor kW Input 3.19 3.05 2.93 5_F (-15_C) Total Heating Capacity kBtuh 22.9 23.4 23.8 kW 6.7 6.9 7.0 Comp. Motor kW Input 2.84 2.70 2.58 -15_F (-26_C) Total Heating Capacity kBtuh 11.4 11.9 12.3 kW 3.3 3.5 3.6 Comp. Motor kW Input 2.11 1.96 1.85

HP26-048 - C26-51/65 - C33-50C HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.69 3.62 3.56 3.50 3.46 3.43 3.35 3.26 3.21 3.16 3.11 3.08 3.06 2.99 2.80 2.61 2.42 2.23 2.04 1.85 Total Output kBtuh 55.2 52.6 50.0 47.4 45.8 44.0 39.4 34.8 33.5 32.3 31.0 30.2 29.2 26.6 23.6 20.7 17.8 14.9 12.0 9.1 kW 16.2 15.4 14.7 13.9 13.4 12.9 11.5 10.2 9.8 9.5 9.1 8.9 8.6 7.8 6.9 6.1 5.2 4.4 3.5 2.7

HP26-048 - C26-65EAP - C33-62D HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.56 3.50 3.44 3.37 3.34 3.31 3.23 3.15 3.10 3.05 3.00 2.97 2.94 2.88 2.70 2.51 2.33 2.15 1.96 1.78 Total Output kBtuh 55.6 52.9 50.3 47.6 46.0 44.1 39.5 34.8 33.5 32.2 30.8 30.0 28.9 26.3 23.4 20.5 17.6 14.8 11.9 9.0 kW 16.3 15.5 14.7 14.0 13.5 12.9 11.6 10.2 9.8 9.4 9.0 8.8 8.5 7.7 6.9 6.0 5.2 4.3 3.5 2.6

HP26 / Page 51 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CR26-48N/W-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.13 .72 3.14 .75 3.15 .78 3.16 .57 3.17 .58 3.17 .60 3.19 .43 3.20 .43 3.21 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .86 .90 .93 .70 .72 .75 .55 .57 .58

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .97 45.3 13.3 3.53 .73 1.00 46.3 13.6 3.54 .76 1.00 47.2 13.8 3.55 .79 .82 48.4 14.2 3.56 .57 .87 49.3 14.4 3.56 .59 .90 50.0 14.7 3.57 .61 .67 51.7 15.2 3.59 .43 .70 52.6 15.4 3.60 .43 .73 53.4 15.6 3.61 .44 Total Cooling Capacity Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .71 .74 .77 .56 .57 .59 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .74 4.00 .77 4.01 .81 4.02 .58 4.03 .60 4.04 .61 4.05 .43 4.06 .43 4.07 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .96 .72 .75 .78 .56 .58 .60 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.52 .76 .91 1.00 4.53 .79 .95 1.00 4.53 .82 .98 1.00 4.54 .59 .73 .87 4.55 .61 .77 .91 4.56 .62 .80 .95 4.57 .43 .57 .71 4.59 .44 .59 .74 4.60 .45 .61 .78

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 46.9 48.0 48.9 50.1 51.1 51.8 53.6 54.5 55.3 13.7 14.1 14.3 14.7 15.0 15.2 15.7 16.0 16.2

85_F kBtuh kW 29_C .98 43.6 12.8 1.00 44.6 13.1 1.00 45.5 13.3 .84 46.5 13.6 .88 47.4 13.9 .92 48.0 14.1 .68 49.8 14.6 .71 50.6 14.8 .74 51.3 15.0

85_F kBtuh kW 29_C 1.00 41.8 12.3 1.00 42.8 12.5 1.00 43.6 12.8 .86 44.6 13.1 .90 45.3 13.3 .93 46.0 13.5 .69 47.7 14.0 .73 48.5 14.2 .76 49.1 14.4

HP26-048
Entering Wet Bulb Tempera ture

CR26-60N/W-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.13 .73 3.14 .76 3.15 .79 3.16 .57 3.17 .59 3.18 .61 3.19 .43 3.21 .43 3.22 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .94 .70 .73 .77 .55 .57 .59 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .98 47.0 13.8 3.53 .74 1.00 48.1 14.1 3.54 .77 1.00 49.1 14.4 3.55 .80 .83 50.1 14.7 3.56 .58 .88 51.0 14.9 3.58 .59 .92 51.8 15.2 3.58 .61 .68 53.6 15.7 3.60 .43 .71 54.5 16.0 3.61 .43 .74 55.3 16.2 3.63 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .88 .92 .96 .71 .75 .78 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 3.99 .75 4.00 .79 4.01 .82 4.02 .58 4.03 .60 4.04 .62 4.06 .43 4.08 .44 4.08 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .94 .97 .73 .76 .80 .57 .59 .61 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.51 .77 .92 1.00 4.52 .80 .96 1.00 4.53 .84 .99 1.00 4.55 .59 .74 .89 4.55 .61 .78 .93 4.56 .64 .82 .97 4.59 .43 .58 .72 4.59 .44 .60 .75 4.60 .45 .62 .79

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 48.7 49.8 50.9 51.9 53.0 53.8 55.5 56.5 57.4 14.3 14.6 14.9 15.2 15.5 15.8 16.3 16.6 16.8

85_F kBtuh kW 29_C 1.00 45.1 13.2 1.00 46.2 13.5 1.00 47.2 13.8 .85 48.1 14.1 .89 49.0 14.4 .93 49.7 14.6 .69 51.5 15.1 .72 52.3 15.3 .76 53.1 15.6

85_F kBtuh kW 29_C 1.00 43.3 12.7 1.00 44.3 13.0 1.00 45.3 13.3 .87 46.0 13.5 .91 46.9 13.7 .95 47.6 14.0 .70 49.3 14.4 .74 50.1 14.7 .77 50.8 14.9

HP26-048 - CR26-48N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.8 55.2 55.7 kW 16.1 16.2 16.3 Comp. Motor kW Input 4.01 3.86 3.75 45_F (7_C) Total Heating Capacity kBtuh 43.6 44.0 44.5 kW 12.8 12.9 13.0 Comp. Motor kW Input 3.64 3.49 3.38 25_F (-4_C) Total Heating Capacity kBtuh 31.9 32.3 32.8 kW 9.3 9.5 9.6 Comp. Motor kW Input 3.27 3.12 3.01 5_F (-15_C) Total Heating Capacity kBtuh 23.2 23.6 24.1 kW 6.8 6.9 7.1 Comp. Motor kW Input 2.84 2.69 2.58 -15_F (-26_C) Total Heating Capacity kBtuh 11.6 12.0 12.5 kW 3.4 3.5 3.7 Comp. Motor kW Input 2.12 1.97 1.86

HP26-048 - CR26-60N/W-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.1 55.6 56.1 kW 16.1 16.3 16.4 Comp. Motor kW Input 3.70 3.56 3.47 45_F (7_C) Total Heating Capacity kBtuh 43.6 44.1 44.6 kW 12.8 12.9 13.1 Comp. Motor kW Input 3.44 3.31 3.21 25_F (-4_C) Total Heating Capacity kBtuh 31.7 32.2 32.7 kW 9.3 9.4 9.6 Comp. Motor kW Input 3.18 3.05 2.95 5_F (-15_C) Total Heating Capacity kBtuh 22.9 23.4 23.9 kW 6.7 6.9 7.0 Comp. Motor kW Input 2.83 2.70 2.60 -15_F (-26_C) Total Heating Capacity kBtuh 11.4 11.9 12.4 kW 3.3 3.5 3.6 Comp. Motor kW Input 2.10 1.96 1.87

HP26-048 - CR26-48N/W-F HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.86 3.77 3.68 3.59 3.53 3.49 3.38 3.27 3.19 3.12 3.04 2.99 2.96 2.87 2.69 2.51 2.33 2.15 1.97 1.80 Total Output kBtuh 55.2 52.6 50.0 47.4 45.8 44.0 39.4 34.8 33.5 32.3 31.0 30.2 29.2 26.6 23.6 20.7 17.8 14.9 12.0 9.1 kW 16.2 15.4 14.7 13.9 13.4 12.9 11.5 10.2 9.8 9.5 9.1 8.9 8.6 7.8 6.9 6.1 5.2 4.4 3.5 2.7

HP26-048 - CR26-60N/W-F HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.56 3.50 3.44 3.37 3.34 3.31 3.23 3.15 3.10 3.05 3.00 2.97 2.94 2.88 2.70 2.51 2.33 2.15 1.96 1.78 Total Output kBtuh 55.6 52.9 50.3 47.6 46.0 44.1 39.5 34.8 33.5 32.2 30.8 30.0 28.9 26.3 23.4 20.5 17.6 14.8 11.9 9.0 kW 16.3 15.5 14.7 14.0 13.5 12.9 11.6 10.2 9.8 9.4 9.0 8.8 8.5 7.7 6.9 6.0 5.2 4.3 3.5 2.6

HP26 / Page 52 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-048
Entering Wet Bulb Tempera ture

CH23-65 - CH33-44B-F COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.14 .74 3.15 .77 3.16 .80 3.16 .57 3.17 .59 3.18 .61 3.20 .43 3.21 .43 3.21 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .71 .74 .78 .56 .58 .60 Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil Total Air Ai Volume 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 46.2 13.5 3.54 .75 1.00 47.3 13.9 3.55 .78 1.00 48.3 14.2 3.56 .81 .84 49.1 14.4 3.57 .58 .88 50.0 14.7 3.58 .60 .92 50.8 14.9 3.59 .62 .68 52.5 15.4 3.60 .43 .72 53.4 15.6 3.61 .44 .75 54.1 15.9 3.63 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .96 .72 .76 .79 .56 .58 .61 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.00 .76 4.01 .79 4.02 .83 4.02 .59 4.04 .61 4.05 .63 4.06 .43 4.08 .44 4.09 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .91 .95 .98 .73 .77 .81 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.52 .77 .92 1.00 4.53 .81 .97 1.00 4.54 .85 .99 1.00 4.55 .60 .75 .89 4.56 .62 .79 .94 4.57 .64 .82 .97 4.59 .43 .58 .72 4.60 .44 .60 .76 4.60 .45 .63 .80

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 47.9 49.0 50.0 50.9 51.9 52.7 54.4 55.4 56.1 14.0 14.4 14.7 14.9 15.2 15.4 15.9 16.2 16.4

85_F kBtuh kW 29_C 1.00 44.4 13.0 1.00 45.5 13.3 1.00 46.5 13.6 .86 47.2 13.8 .90 48.1 14.1 .94 48.8 14.3 .70 50.5 14.8 .73 51.3 15.0 .77 52.0 15.2

85_F kBtuh kW 29_C 1.00 42.6 12.5 1.00 43.6 12.8 1.00 44.7 13.1 .87 45.2 13.2 .92 46.0 13.5 .96 46.7 13.7 .71 48.3 14.2 .75 49.1 14.4 .78 49.8 14.6

HP26-048
Entering Wet Bulb Tempera ture

CH23-68 - CH33-50C-F COOLING CAPACITY


Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) Total Cooling Capacity Comp Motor kW Input 75_F 24_C 3.15 .73 3.16 .76 3.18 .79 3.19 .57 3.20 .59 3.21 .61 3.23 .43 3.24 .43 3.25 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .87 .91 .95 .70 .74 .77 .55 .57 .60 Total Cooling Capacity 95_F (35_C) Comp Motor kW 85_F 75_F kBtuh kW Input 29_C 24_C .99 47.2 13.8 3.55 .74 1.00 48.3 14.2 3.57 .78 1.00 49.4 14.5 3.58 .81 .84 50.3 14.7 3.59 .58 .88 51.4 15.1 3.60 .60 .92 52.2 15.3 3.61 .62 .68 53.9 15.8 3.63 .43 .71 54.9 16.1 3.64 .44 .75 55.7 16.3 3.66 .44 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .89 .93 .97 .72 .75 .79 .56 .58 .60 Total Cooling Capacity 105_F (41_C) Comp Motor kW Input 75_F 24_C 4.01 .76 4.03 .79 4.04 .83 4.05 .58 4.06 .61 4.07 .63 4.09 .43 4.11 .44 4.12 .45 Sensible To Total Ratio (S/T) Dry Bulb 80_F 27_C .90 .95 .99 .73 .77 .80 .57 .59 .62 Total Cooling Capacity 115_F (46_C) Sensible To Total Comp Ratio (S/T) Motor Dry Bulb kW Input 75_F 80_F 85_F 24_C 27_C 29_C 4.53 .77 .92 1.00 4.55 .81 .97 1.00 4.56 .85 1.00 1.00 4.56 .59 .74 .89 4.58 .62 .78 .94 4.59 .64 .82 .98 4.61 .43 .58 .72 4.62 .44 .60 .76 4.64 .45 .63 .80

Total Air Ai Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C) 1400 1600 1800 1400 1600 1800 1400 1600 1800

L/s kBtuh kW 660 755 850 660 755 850 660 755 850 49.0 50.2 51.2 52.3 53.3 54.2 55.9 57.0 57.8 14.4 14.7 15.0 15.3 15.6 15.9 16.4 16.7 16.9

85_F kBtuh kW 29_C 1.00 45.3 13.3 1.00 46.4 13.6 1.00 47.5 13.9 .85 48.3 14.2 .90 49.3 14.4 .94 50.0 14.7 .69 51.7 15.2 .73 52.6 15.4 .76 53.3 15.6

85_F kBtuh kW 29_C 1.00 43.3 12.7 1.00 44.4 13.0 1.00 45.6 13.4 .87 46.2 13.5 .92 47.1 13.8 .96 47.8 14.0 .70 49.5 14.5 .74 50.3 14.7 .78 51.0 14.9

HP26-048 - CH23-65 - CH33-44B-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 54.9 55.4 55.9 kW 16.1 16.2 16.4 Comp. Motor kW Input 3.83 3.69 3.58 45_F (7_C) Total Heating Capacity kBtuh 43.7 44.2 44.7 kW 12.8 13.0 13.1 Comp. Motor kW Input 3.50 3.37 3.26 25_F (-4_C) Total Heating Capacity kBtuh 31.9 32.4 32.9 kW 9.3 9.5 9.6 Comp. Motor kW Input 3.17 3.04 2.93 5_F (-15_C) Total Heating Capacity kBtuh 23.3 23.8 24.3 kW 6.8 7.0 7.1 Comp. Motor kW Input 2.78 2.64 2.53 -15_F (-26_C) Total Heating Capacity kBtuh 11.6 12.1 12.6 kW 3.4 3.5 3.7 Comp. Motor kW Input 2.07 1.94 1.83

HP26-048 - CH23-68 - CH33-50C-F HEATING CAPACITY


Indoor Coil Air Volume 70_F db (21_C db) cfm 1400 1600 1800 L/s 660 755 850 Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 55.5 56.0 56.4 kW 16.3 16.4 16.5 Comp. Motor kW Input 3.60 3.48 3.38 45_F (7_C) Total Heating Capacity kBtuh 44.0 44.5 44.9 kW 12.9 13.0 13.2 Comp. Motor kW Input 3.26 3.13 3.04 25_F (-4_C) Total Heating Capacity kBtuh 32.0 32.5 32.9 kW 9.4 9.5 9.6 Comp. Motor kW Input 2.86 2.74 2.64 5_F (-15_C) Total Heating Capacity kBtuh 23.2 23.7 24.1 kW 6.8 6.9 7.1 Comp. Motor kW Input 2.71 2.58 2.49 -15_F (-26_C) Total Heating Capacity kBtuh 11.5 12.0 12.4 kW 3.4 3.5 3.6 Comp. Motor kW Input 2.01 1.88 1.79

HP26-048 - CH23-65 - CH33-44B-F HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.69 3.61 3.53 3.45 3.41 3.37 3.27 3.17 3.11 3.04 2.97 2.93 2.90 2.82 2.64 2.47 2.29 2.11 1.94 1.76 Total Output kBtuh 55.4 52.8 50.2 47.6 46.0 44.2 39.6 35.0 33.7 32.4 31.2 30.4 29.4 26.8 23.8 20.9 17.9 15.0 12.1 9.1 kW 16.2 15.5 14.7 14.0 13.5 13.0 11.6 10.3 9.9 9.5 9.1 8.9 8.6 7.9 7.0 6.1 5.2 4.4 3.5 2.7

HP26-048 - CH23-68 - CH33-50C-F HEATING PERFORMANCE at 1600 cfm (755 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 3.48 3.41 3.35 3.28 3.24 3.13 2.87 2.60 2.67 2.74 2.81 2.85 2.82 2.76 2.58 2.41 2.23 2.06 1.88 1.71 Total Output kBtuh 56.0 53.3 50.7 48.0 46.4 44.5 39.9 35.2 33.9 32.5 31.2 30.4 29.3 26.7 23.7 20.8 17.9 15.0 12.0 9.1 kW 16.4 15.6 14.9 14.1 13.6 13.0 11.7 10.3 9.9 9.5 9.1 8.9 8.6 7.8 6.9 6.1 5.2 4.4 3.5 2.7

HP26 / Page 53 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-060
Entering E t i Wet Bulb Tempera ture

CB30M-51 - CB30U-51 - COOLING CAPACITY


Total Cooling Capacity

Total Air Volume cfm

L/s kBtuh kW 55.8 56.8 57.7 59.3 60.2 60.9 63.3 64.2 64.9 16.4 16.6 16.9 17.4 17.6 17.8 18.6 18.8 19.0

63_F (17_C) 67_F (19_C) 71_F (22_C)

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Outdoor Air Temperature Entering Outdoor Coil 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C) Sensible To Total Sensible To Total Sensible To Total Sensible To Total Total Total Total Ratio (S/T) Ratio (S/T) Ratio (S/T) Ratio (S/T) Comp Comp Comp Comp Cooling Cooling Cooling Motor M t Motor Motor Motor Capacity M t Capacity M t Capacity M t Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.10 .74 .89 .99 53.9 15.8 4.63 .76 .90 1.00 51.8 15.2 5.23 .77 .92 1.00 49.7 14.6 5.89 .78 .94 1.00 4.11 .77 .92 1.00 54.8 16.1 4.64 .78 .93 1.00 52.8 15.5 5.23 .80 .95 1.00 50.6 14.8 5.89 .81 .97 1.00 4.12 .79 .95 1.00 55.8 16.4 4.64 .81 .96 1.00 53.7 15.7 5.24 .82 .98 1.00 51.5 15.1 5.91 .84 .99 1.00 4.13 .58 .72 .85 57.2 16.8 4.66 .58 .73 .87 55.0 16.1 5.25 .59 .74 .89 52.7 15.4 5.91 .60 .76 .90 4.14 .59 .74 .89 58.0 17.0 4.67 .60 .76 .90 55.8 16.4 5.26 .61 .77 .92 53.4 15.6 5.93 .62 .79 .94 4.15 .61 .77 .92 58.7 17.2 4.67 .62 .79 .93 56.5 16.6 5.27 .63 .80 .95 54.0 15.8 5.93 .64 .82 .97 4.16 .43 .56 .69 61.0 17.9 4.69 .43 .57 .70 58.7 17.2 5.29 .43 .58 .72 56.2 16.5 5.95 .44 .59 .73 4.17 .43 .58 .72 61.9 18.1 4.70 .44 .58 .73 59.5 17.4 5.29 .44 .59 .75 57.0 16.7 5.96 .44 .61 .76 4.18 .44 .59 .75 62.5 18.3 4.71 .44 .60 .76 60.1 17.6 5.30 .45 .61 .78 57.5 16.9 5.97 .45 .63 .80 Outdoor Air Temperature Entering Outdoor Coil

HP26-060
Entering Wet Bulb Tempera ture

CB31MV-51 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 95_F (35_C) Sensible To Total Ratio (S/T) Total Cooling Capacity 105_F (41_C) Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.08 .74 .88 .99 52.5 15.4 4.60 .75 .90 1.00 50.5 14.8 5.20 .77 .92 1.00 48.4 14.2 5.85 .78 .94 1.00 4.09 .77 .92 1.00 53.5 15.7 4.61 .78 .93 1.00 51.5 15.1 5.20 .80 .95 1.00 49.3 14.4 5.86 .81 .97 1.00 4.09 .79 .95 1.00 54.4 15.9 4.61 .81 .96 1.00 52.3 15.3 5.20 .82 .98 1.00 50.2 14.7 5.87 .84 .99 1.00 4.10 .58 .72 .85 55.7 16.3 4.63 .58 .73 .87 53.6 15.7 5.22 .59 .74 .88 51.4 15.1 5.88 .60 .76 .91 4.12 .59 .75 .89 56.6 16.6 4.64 .60 .76 .90 54.4 15.9 5.23 .61 .77 .92 52.1 15.3 5.89 .62 .79 .94 4.12 .61 .77 .92 57.3 16.8 4.64 .62 .79 .93 55.0 16.1 5.23 .63 .80 .95 52.7 15.4 5.89 .64 .82 .97 4.14 .43 .56 .69 59.5 17.4 4.66 .43 .57 .70 57.2 16.8 5.26 .43 .58 .72 54.8 16.1 5.92 .44 .59 .73 4.15 .44 .58 .72 60.3 17.7 4.67 .44 .59 .73 58.0 17.0 5.26 .44 .59 .75 55.5 16.3 5.92 .45 .61 .76 4.16 .44 .59 .75 61.0 17.9 4.68 .44 .60 .76 58.6 17.2 5.27 .45 .61 .78 56.1 16.4 5.93 .45 .63 .80 Air Temperature Entering Outdoor Coil 25_F (-4_C) Total Heating Capacity kBtuh 38.1 38.3 38.5 kW 11.2 11.2 11.3 Comp. Motor kW Input 3.78 3.65 3.56

Total Air Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 54.4 55.4 56.3 57.8 58.6 59.4 61.7 62.5 63.2 15.9 16.2 16.5 16.9 17.2 17.4 18.1 18.3 18.5

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CB30M-51 - CB30U-51 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 63.5 63.7 63.9 kW 18.6 18.7 18.7 Comp. Motor kW Input 4.75 4.62 4.53 45_F (7_C) Total Heating Capacity kBtuh 51.0 51.2 51.4 kW 14.9 15.0 15.1

5_F (-15_C) Total Heating Capacity Comp. Motor kW Input 3.27 3.14 3.05

-15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.0 14.2 kW 4.0 4.1 4.2 Comp. Motor kW Input 2.44 2.31 2.22

Comp. Motor kW Input 4.27 4.14 4.05

kBtuh 27.4 27.6 27.8

kW 8.0 8.1 8.1

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CB31MV-51 HEATING CAPACITY


Air Temperature Entering Outdoor Coil 65_F (18_C) Total Heating Capacity kBtuh 63.8 64.5 64.7 kW 18.7 18.9 19.0 Comp. Motor kW Input 4.77 4.64 4.34 45_F (7_C) Total Heating Capacity kBtuh 51.0 51.7 51.9 kW 14.9 15.2 15.2 Comp. Motor kW Input 4.26 4.13 3.83 25_F (-4_C) Total Heating Capacity kBtuh 37.7 38.4 38.6 kW 11.0 11.3 11.3 Comp. Motor kW Input 3.74 3.61 3.30 5_F (-15_C) Total Heating Capacity kBtuh 26.8 27.5 27.7 kW 7.9 8.1 8.1 Comp. Motor kW Input 3.23 3.10 2.79 -15_F (-26_C) Total Heating Capacity kBtuh 13.3 14.0 14.2 kW 3.9 4.1 4.2 Comp. Motor kW Input 2.42 2.29 1.98

HP26-060 CB30M-51/CB30U-51 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.62 4.50 4.39 4.27 4.20 4.14 3.98 3.83 3.74 3.65 3.56 3.51 3.47 3.35 3.14 2.94 2.73 2.52 2.31 2.11 Total Output kBtuh 63.7 60.7 57.7 54.8 53.0 51.2 46.7 42.2 40.3 38.3 36.4 35.2 34.0 31.0 27.6 24.2 20.8 17.4 14.0 10.6 kW 18.7 17.8 16.9 16.1 15.5 15.0 13.7 12.4 11.8 11.2 10.7 10.3 10.0 9.1 8.1 7.1 6.1 5.1 4.1 3.1

HP26-060 CB31MV-51 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.64 4.52 4.40 4.28 4.20 4.13 3.95 3.78 3.69 3.61 3.52 3.47 3.42 3.30 3.10 2.90 2.69 2.49 2.29 2.08 Total Output kBtuh 64.5 61.4 58.4 55.3 53.5 51.7 47.1 42.5 40.5 38.4 36.4 35.2 34.0 30.9 27.5 24.1 20.7 17.4 14.0 10.6 kW 18.9 18.0 17.1 16.2 15.7 15.2 13.8 12.5 11.9 11.3 10.7 10.3 10.0 9.1 8.1 7.1 6.1 5.1 4.1 3.1

HP26 / Page 54 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-060
Entering Wet Bulb Tempera ture

CB30M-65 - CB30U-65 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil 105_F (41_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T)

Total Air Volume

95_F (35_C)

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 57.2 58.2 59.2 60.8 61.7 62.5 64.9 65.8 66.5 16.8 17.1 17.3 17.8 18.1 18.3 19.0 19.3 19.5

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.14 .74 .88 .99 55.2 16.2 4.68 .75 .90 1.00 53.1 15.6 5.28 .77 .92 1.00 50.9 14.9 5.95 .78 .94 1.00 4.15 .77 .92 1.00 56.2 16.5 4.68 .78 .93 1.00 54.1 15.9 5.28 .80 .95 1.00 51.9 15.2 5.95 .81 .97 1.00 4.16 .79 .95 1.00 57.2 16.8 4.69 .81 .96 1.00 55.1 16.1 5.29 .82 .98 1.00 52.8 15.5 5.97 .84 .99 1.00 4.17 .58 .72 .85 58.6 17.2 4.71 .59 .73 .87 56.4 16.5 5.31 .59 .74 .89 54.0 15.8 5.97 .60 .76 .90 4.19 .59 .74 .89 59.5 17.4 4.71 .60 .76 .90 57.2 16.8 5.31 .61 .77 .92 54.8 16.1 5.99 .62 .79 .94 4.19 .61 .77 .92 60.2 17.6 4.72 .62 .79 .93 57.9 17.0 5.32 .63 .80 .95 55.4 16.2 5.99 .64 .82 .97 4.21 .43 .56 .69 62.6 18.3 4.74 .43 .57 .70 60.2 17.6 5.34 .43 .58 .72 57.7 16.9 6.01 .44 .59 .73 4.22 .43 .58 .72 63.4 18.6 4.75 .44 .59 .73 61.0 17.9 5.35 .44 .60 .75 58.4 17.1 6.02 .45 .61 .77 4.23 .44 .59 .75 64.1 18.8 4.75 .44 .60 .76 61.6 18.1 5.35 .45 .61 .78 59.0 17.3 6.03 .45 .63 .80 Outdoor Air Temperature Entering Outdoor Coil 95_F (35_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 105_F (41_C) Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C)

HP26-060
Entering Wet Bulb Tempera ture

CB31MV-65 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T)

Total Air Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 55.8 56.9 57.8 59.4 60.2 61.0 63.3 64.2 64.9 16.4 16.7 16.9 17.4 17.6 17.9 18.6 18.8 19.0

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.02 .74 .89 .99 53.9 15.8 4.54 .75 .90 1.00 51.9 15.2 5.13 .77 .92 1.00 49.7 14.6 5.78 .78 .94 1.00 4.03 .77 .92 1.00 54.9 16.1 4.55 .78 .93 1.00 52.8 15.5 5.13 .80 .95 1.00 50.7 14.9 5.78 .81 .97 1.00 4.04 .79 .95 1.00 55.8 16.4 4.55 .81 .96 1.00 53.8 15.8 5.14 .82 .98 1.00 51.6 15.1 5.79 .84 .99 1.00 4.05 .58 .72 .85 57.3 16.8 4.57 .58 .73 .87 55.1 16.1 5.15 .59 .74 .88 52.7 15.4 5.80 .60 .76 .90 4.06 .59 .74 .89 58.1 17.0 4.58 .60 .76 .90 55.8 16.4 5.16 .61 .77 .92 53.5 15.7 5.81 .62 .79 .94 4.07 .61 .77 .92 58.8 17.2 4.58 .62 .79 .94 56.5 16.6 5.17 .63 .80 .95 54.1 15.9 5.82 .64 .82 .97 4.09 .43 .56 .69 61.1 17.9 4.60 .43 .57 .70 58.8 17.2 5.19 .43 .58 .72 56.3 16.5 5.84 .44 .59 .73 4.09 .43 .58 .72 61.9 18.1 4.61 .44 .59 .73 59.5 17.4 5.19 .44 .59 .75 57.0 16.7 5.85 .45 .61 .77 4.10 .44 .59 .75 62.6 18.3 4.62 .44 .60 .76 60.2 17.6 5.20 .45 .61 .78 57.6 16.9 5.85 .45 .63 .80 Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 4.35 4.23 4.14 Total Heating Capacity kBtuh 38.5 38.7 38.9 kW 11.3 11.3 11.4 Comp. Motor kW Input 3.82 3.70 3.60 5_F (-15_C) Total Heating Capacity kBtuh 27.5 27.7 27.9 kW 8.1 8.1 8.2 Comp. Motor kW Input 3.27 3.15 3.06 -15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.0 14.2 kW 4.0 4.1 4.2 Comp. Motor kW Input 2.45 2.33 2.23

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CB30M-65 - CB30U-65 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 65.0 65.2 65.4 kW 19.0 19.1 19.2 Comp. Motor kW Input 4.88 4.76 4.66 45_F (7_C) Total Heating Capacity kBtuh 51.9 52.1 52.3 kW 15.2 15.3 15.3

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CB31MV-65 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 64.1 64.4 64.6 kW 18.8 18.9 18.9 Comp. Motor kW Input 4.68 4.56 4.31 45_F (7_C) Total Heating Capacity kBtuh 51.4 51.7 51.9 kW 15.1 15.2 15.2

Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 4.20 4.08 3.83 Total Heating Capacity kBtuh 38.3 38.6 38.8 kW 11.2 11.3 11.4 Comp. Motor kW Input 3.71 3.58 3.34 5_F (-15_C) Total Heating Capacity kBtuh 27.5 27.8 28.0 kW 8.1 8.1 8.2 Comp. Motor kW Input 3.20 3.08 2.83 -15_F (-26_C) Total Heating Capacity kBtuh 13.7 14.0 14.2 kW 4.0 4.1 4.2 Comp. Motor kW Input 2.39 2.27 2.02

HP26-060 CB30M-65/CB30U-65 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.76 4.63 4.51 4.38 4.30 4.23 4.07 3.90 3.80 3.70 3.60 3.54 3.49 3.36 3.15 2.95 2.74 2.54 2.33 2.12 Total Output kBtuh 65.2 62.1 59.0 55.9 54.0 52.1 47.5 42.8 40.8 38.7 36.6 35.4 34.2 31.1 27.7 24.2 20.8 17.4 14.0 10.6 kW 19.1 18.2 17.3 16.4 15.8 15.3 13.9 12.5 12.0 11.3 10.7 10.4 10.0 9.1 8.1 7.1 6.1 5.1 4.1 3.1

HP26-060 CB31MV-65 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.56 4.44 4.33 4.21 4.14 4.08 3.92 3.76 3.67 3.58 3.49 3.44 3.39 3.28 3.08 2.87 2.67 2.47 2.27 2.07 Total Output kBtuh 64.4 61.3 58.3 55.3 53.5 51.7 47.1 42.6 40.6 38.6 36.6 35.4 34.2 31.2 27.8 24.3 20.9 17.5 14.0 10.6 kW 18.9 18.0 17.1 16.2 15.7 15.2 13.8 12.5 11.9 11.3 10.7 10.4 10.0 9.1 8.1 7.1 6.1 5.1 4.1 3.1

HP26 / Page 55 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-060
Entering Wet Bulb Tempera ture

CVP10-51/EC10Q4 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil 105_F (41_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T)

Total Air Volume

95_F (35_C)

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 55.2 56.3 57.2 58.7 59.6 60.3 62.6 63.5 64.2 16.2 16.5 16.8 17.2 17.5 17.7 18.3 18.6 18.8

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.11 .74 .89 .99 53.4 15.6 4.63 .75 .90 1.00 51.4 15.1 5.24 .77 .91 1.00 49.3 14.4 5.91 .78 .93 1.00 4.12 .77 .92 1.00 54.4 15.9 4.65 .78 .93 1.00 52.4 15.4 5.25 .80 .95 1.00 50.3 14.7 5.91 .81 .96 1.00 4.13 .79 .95 1.00 55.3 16.2 4.65 .81 .96 1.00 53.3 15.6 5.25 .82 .98 1.00 51.2 15.0 5.92 .84 .99 1.00 4.14 .58 .72 .85 56.7 16.6 4.66 .58 .73 .87 54.5 16.0 5.26 .59 .74 .89 52.2 15.3 5.93 .60 .76 .90 4.14 .59 .74 .89 57.5 16.9 4.67 .60 .76 .90 55.3 16.2 5.27 .61 .77 .92 52.9 15.5 5.95 .62 .79 .94 4.15 .61 .77 .92 58.2 17.1 4.68 .62 .79 .93 56.0 16.4 5.28 .63 .80 .95 53.6 15.7 5.94 .64 .82 .97 4.17 .43 .56 .69 60.5 17.7 4.69 .43 .57 .70 58.2 17.1 5.29 .43 .58 .72 55.7 16.3 5.97 .44 .59 .73 4.18 .43 .58 .72 61.3 18.0 4.70 .44 .59 .73 58.9 17.3 5.31 .44 .59 .75 56.5 16.6 5.97 .44 .61 .76 4.18 .44 .60 .75 62.0 18.2 4.71 .44 .60 .76 59.6 17.5 5.31 .45 .61 .78 57.0 16.7 5.98 .45 .63 .80 Outdoor Air Temperature Entering Outdoor Coil 105_F (41_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T)

HP26-060
Entering Wet Bulb Tempera ture

CVP10-65/EC10Q5 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity

Total Air Volume

95_F (35_C)

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 57.3 58.4 59.4 60.7 61.6 62.4 64.8 65.6 66.3 16.8 17.1 17.4 17.8 18.1 18.3 19.0 19.2 19.4

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.08 .75 .90 1.00 55.4 16.2 4.61 .77 .91 1.00 53.3 15.6 5.21 .78 .93 1.00 51.1 15.0 5.87 .80 .95 1.00 4.09 .78 .93 1.00 56.4 16.5 4.62 .80 .95 1.00 54.4 15.9 5.21 .81 .96 1.00 52.2 15.3 5.88 .83 .98 1.00 4.11 .81 .96 1.00 57.4 16.8 4.63 .82 .98 1.00 55.4 16.2 5.21 .84 .99 1.00 53.3 15.6 5.88 .86 1.00 1.00 4.11 .58 .73 .87 58.6 17.2 4.63 .59 .74 .88 56.4 16.5 5.23 .60 .76 .90 54.0 15.8 5.90 .61 .77 .92 4.12 .60 .76 .90 59.5 17.4 4.64 .61 .77 .92 57.2 16.8 5.24 .62 .79 .94 54.8 16.1 5.91 .63 .80 .95 4.13 .62 .79 .94 60.2 17.6 4.65 .63 .80 .95 57.9 17.0 5.25 .64 .82 .97 55.5 16.3 5.91 .65 .84 .98 4.15 .43 .57 .71 62.5 18.3 4.67 .43 .58 .72 60.2 17.6 5.26 .44 .58 .73 57.6 16.9 5.93 .44 .60 .75 4.15 .44 .59 .74 63.3 18.6 4.67 .44 .60 .75 60.9 17.8 5.27 .44 .61 .76 58.3 17.1 5.94 .45 .62 .78 4.16 .44 .61 .77 64.0 18.8 4.68 .45 .62 .78 61.5 18.0 5.28 .45 .63 .80 58.9 17.3 5.94 .46 .64 .81 Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 4.07 3.95 3.85 Total Heating Capacity kBtuh 38.6 39.0 39.3 kW 11.3 11.4 11.5 Comp. Motor kW Input 3.62 3.50 3.40 5_F (-15_C) Total Heating Capacity kBtuh 27.7 28.1 28.4 kW 8.1 8.2 8.3 Comp. Motor kW Input 3.14 3.02 2.92 -15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.2 14.5 kW 4.0 4.2 4.2 Comp. Motor kW Input 2.34 2.22 2.12

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CVP10-51/EC10Q4 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 64.5 64.9 65.2 kW 18.9 19.0 19.1 Comp. Motor kW Input 4.52 4.40 4.30 45_F (7_C) Total Heating Capacity kBtuh 51.8 52.2 52.5 kW 15.2 15.3 15.4

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CVP10-65/EC10Q5 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 65.3 65.7 67.1 kW 19.1 19.3 19.7 Comp. Motor kW Input 4.36 4.25 4.15 45_F (7_C) Total Heating Capacity kBtuh 52.2 52.6 54.0 kW 15.3 15.4 15.8

Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 3.96 3.84 3.75 Total Heating Capacity kBtuh 38.7 39.1 40.5 kW 11.3 11.5 11.9 Comp. Motor kW Input 3.54 3.43 3.33 5_F (-15_C) Total Heating Capacity kBtuh 27.6 28.0 29.4 kW 8.1 8.2 8.6 Comp. Motor kW Input 3.10 2.98 2.89 -15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.2 15.6 kW 4.0 4.2 4.6 Comp. Motor kW Input 2.30 2.19 2.09

HP26-060 CVP10-51/EC10Q4 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.40 4.29 4.18 4.08 4.01 3.95 3.81 3.66 3.58 3.50 3.42 3.37 3.33 3.22 3.02 2.82 2.62 2.42 2.22 2.02 Total Output kBtuh 64.9 61.9 58.9 55.8 54.0 52.2 47.6 43.0 41.0 39.0 37.0 35.8 34.6 31.6 28.1 24.6 21.1 17.7 14.2 10.7 kW 19.0 18.1 17.3 16.4 15.8 15.3 14.0 12.6 12.0 11.4 10.8 10.5 10.1 9.3 8.2 7.2 6.2 5.2 4.2 3.1

HP26-060 CVP10-65/EC10Q5 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.25 4.15 4.05 3.96 3.90 3.84 3.71 3.57 3.50 3.43 3.36 3.31 3.28 3.18 2.98 2.78 2.58 2.39 2.19 1.99 Total Output kBtuh 65.7 62.6 59.5 56.4 54.5 52.6 47.9 43.3 41.2 39.1 37.0 35.8 34.6 31.4 28.0 24.5 21.1 17.6 14.2 10.7 kW 19.3 18.3 17.4 16.5 16.0 15.4 14.0 12.7 12.1 11.5 10.8 10.5 10.1 9.2 8.2 7.2 6.2 5.2 4.2 3.1

HP26 / Page 56 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-060
Entering Wet Bulb Tempera ture

C33-62D - C26-65EAP - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil 105_F (41_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T)

Total Air Volume

95_F (35_C)

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 58.7 59.8 60.8 62.7 63.7 64.5 67.1 68.1 68.9 17.2 17.5 17.8 18.4 18.7 18.9 19.7 20.0 20.2

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.10 .73 .87 .98 56.7 16.6 4.63 .74 .89 .99 54.6 16.0 5.23 .75 .90 1.00 52.3 15.3 5.90 .77 .92 1.00 4.11 .75 .90 1.00 57.7 16.9 4.64 .77 .92 1.00 55.6 16.3 5.24 .78 .93 1.00 53.3 15.6 5.91 .80 .95 1.00 4.12 .78 .93 1.00 58.7 17.2 4.65 .79 .95 1.00 56.5 16.6 5.25 .81 .96 1.00 54.2 15.9 5.91 .82 .98 1.00 4.14 .57 .70 .84 60.6 17.8 4.66 .58 .71 .85 58.3 17.1 5.26 .58 .73 .87 55.8 16.4 5.93 .59 .74 .89 4.14 .58 .73 .87 61.5 18.0 4.67 .59 .74 .89 59.1 17.3 5.27 .60 .75 .90 56.6 16.6 5.94 .61 .77 .92 4.15 .60 .75 .90 62.3 18.3 4.67 .61 .77 .92 59.8 17.5 5.28 .61 .78 .93 57.3 16.8 5.94 .62 .80 .95 4.17 .43 .55 .68 64.8 19.0 4.69 .43 .56 .69 62.3 18.3 5.29 .43 .57 .70 59.7 17.5 5.97 .43 .58 .72 4.18 .43 .57 .70 65.7 19.3 4.70 .43 .58 .72 63.2 18.5 5.31 .44 .58 .73 60.5 17.7 5.97 .44 .59 .75 4.18 .44 .58 .73 66.5 19.5 4.71 .44 .59 .74 63.9 18.7 5.31 .44 .60 .76 61.2 17.9 5.98 .45 .61 .78 Outdoor Air Temperature Entering Outdoor Coil 95_F (35_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 105_F (41_C) Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C)

HP26-060
Entering Wet Bulb Tempera ture

CR26-65 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T)

Total Air Volume

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 57.3 58.3 59.2 60.8 61.7 62.4 64.9 65.7 66.5 16.8 17.1 17.3 17.8 18.1 18.3 19.0 19.3 19.5

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.18 .74 .88 .99 55.3 16.2 4.72 .75 .90 1.00 53.2 15.6 5.33 .77 .92 1.00 51.0 14.9 6.01 .78 .94 1.00 4.20 .77 .92 1.00 56.3 16.5 4.73 .78 .93 1.00 54.2 15.9 5.34 .80 .95 1.00 52.0 15.2 6.02 .81 .97 1.00 4.20 .79 .95 1.00 57.2 16.8 4.74 .81 .96 1.00 55.1 16.1 5.35 .82 .98 1.00 53.0 15.5 6.02 .84 .99 1.00 4.21 .58 .72 .85 58.7 17.2 4.75 .58 .73 .87 56.4 16.5 5.36 .59 .74 .89 54.1 15.9 6.04 .60 .76 .90 4.22 .59 .75 .89 59.5 17.4 4.76 .60 .76 .90 57.2 16.8 5.37 .61 .77 .92 54.8 16.1 6.05 .62 .79 .94 4.23 .61 .77 .92 60.2 17.6 4.77 .62 .79 .93 57.9 17.0 5.38 .63 .80 .95 55.5 16.3 6.05 .64 .82 .97 4.25 .43 .56 .69 62.6 18.3 4.78 .43 .57 .71 60.2 17.6 5.39 .43 .58 .72 57.7 16.9 6.08 .44 .59 .73 4.26 .44 .58 .72 63.4 18.6 4.79 .44 .59 .74 61.0 17.9 5.40 .44 .60 .75 58.4 17.1 6.09 .45 .61 .77 4.26 .44 .60 .75 64.1 18.8 4.80 .44 .60 .76 61.6 18.1 5.41 .45 .62 .78 59.0 17.3 6.08 .45 .63 .80 Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 4.28 4.17 4.08 Total Heating Capacity kBtuh 38.7 39.1 39.4 kW 11.3 11.5 11.5 Comp. Motor kW Input 3.77 3.66 3.57 5_F (-15_C) Total Heating Capacity kBtuh 27.6 28.0 28.3 kW 8.1 8.2 8.3 Comp. Motor kW Input 3.24 3.13 3.04 -15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.2 14.5 kW 4.0 4.2 4.2 Comp. Motor kW Input 2.42 2.31 2.22

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

C33-62D - C26-65EAP HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 65.3 65.7 66.0 kW 19.1 19.3 19.3 Comp. Motor kW Input 4.77 4.66 4.57 45_F (7_C) Total Heating Capacity kBtuh 52.2 52.6 52.9 kW 15.3 15.4 15.5

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CR26-65 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 69.7 69.7 48.5 kW 20.4 20.4 14.2 Comp. Motor kW Input 4.87 4.79 3.97 45_F (7_C) Total Heating Capacity kBtuh 54.9 54.9 33.7 kW 16.1 16.1 9.9

Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 4.30 4.22 3.40 Total Heating Capacity kBtuh 39.7 39.7 18.5 kW 11.6 11.6 5.4 Comp. Motor kW Input 3.72 3.64 2.82 5_F (-15_C) Total Heating Capacity kBtuh 27.5 27.5 6.3 kW 8.1 8.1 1.8 Comp. Motor kW Input 3.15 3.08 2.25 -15_F (-26_C) Total Heating Capacity kBtuh 14.1 14.1 -7.1 kW 4.1 4.1 -2.1 Comp. Motor kW Input 2.36 2.28 1.46

HP26-060 HEATING PERFORMANCE C33-62D - C26-65EAP at 2000 cfm (945 L/s)


Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.66 4.54 4.42 4.30 4.23 4.17 4.00 3.84 3.75 3.66 3.56 3.51 3.46 3.34 3.13 2.93 2.72 2.52 2.31 2.11 Total Output kBtuh 65.7 62.6 59.5 56.4 54.5 52.6 47.9 43.3 41.2 39.1 37.0 35.8 34.6 31.4 28.0 24.5 21.1 17.6 14.2 10.7 kW 19.3 18.3 17.4 16.5 16.0 15.4 14.0 12.7 12.1 11.5 10.8 10.5 10.1 9.2 8.2 7.2 6.2 5.2 4.2 3.1

HP26-060 CR26-65 HEATING PERFORMANCE at 2000 cfm (945 L/s) Indoor Coil Air Volume
Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.79 4.65 4.51 4.38 4.29 4.22 4.04 3.86 3.75 3.64 3.53 3.47 3.41 3.28 3.08 2.88 2.68 2.48 2.28 2.08

Total Output kW 20.4 19.4 18.4 17.3 16.7 16.1 14.6 13.1 12.4 11.6 10.9 10.5 10.1 9.1 8.1 7.1 6.1 5.1 4.1 3.1

kBtuh 69.7 66.2 62.7 59.1 57.0 54.9 49.8 44.6 42.2 39.7 37.3 35.8 34.4 30.9 27.5 24.1 20.8 17.4 14.1 10.7

HP26 / Page 57 "

NOTE - Cooling capacities are gross and do not include indoor coil blower motor heat deduction. Heating capacities include defrost cycles in the temperature range where they occur. NOTE - Heating performance outdoor temperature 70% relative humidity. Indoor temperature 70F (21). NOTE - For Temperatures and Capacities not shown in tables, see bulletin Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

RATINGS

HP26-060
Entering Wet Bulb Tempera ture

CH33-62D-F - CH23-68 - COOLING CAPACITY


85_F (29_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity

Outdoor Air Temperature Entering Outdoor Coil 105_F (41_C) Total Cooling Capacity Sensible To Total Ratio (S/T) Total Cooling Capacity 115_F (46_C) Sensible To Total Ratio (S/T)

Total Air Volume

95_F (35_C)

cfm 63_F (17_C) 67_F (19_C) 71_F (22_C)

L/s kBtuh kW 59.2 60.4 61.4 62.8 63.8 64.7 67.0 68.0 68.8 17.3 17.7 18.0 18.4 18.7 19.0 19.6 19.9 20.2

1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015 1750 825 1950 920 2150 1015

Sensible To Total Ratio (S/T) Comp Comp Comp Comp Motor Motor Motor Motor Dry Bulb Dry Bulb Dry Bulb Dry Bulb kW kW kW kW Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F Input 75_F 80_F 85_F kBtuh kW kBtuh kW kBtuh kW 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 4.11 .75 .89 1.00 57.1 16.7 4.64 .76 .91 1.00 54.9 16.1 5.23 .78 .93 1.00 52.6 15.4 5.90 .79 .95 1.00 4.13 .78 .93 1.00 58.2 17.1 4.65 .79 .95 1.00 56.0 16.4 5.24 .80 .96 1.00 53.7 15.7 5.91 .82 .98 1.00 4.13 .81 .96 1.00 59.3 17.4 4.66 .82 .98 1.00 57.1 16.7 5.25 .84 .99 1.00 54.9 16.1 5.92 .86 1.00 1.00 4.15 .58 .72 .86 60.6 17.8 4.67 .59 .74 .88 58.2 17.1 5.26 .60 .75 .89 55.7 16.3 5.93 .61 .77 .91 4.15 .60 .75 .90 61.5 18.0 4.67 .61 .77 .91 59.1 17.3 5.28 .62 .78 .93 56.5 16.6 5.94 .63 .80 .96 4.16 .62 .78 .93 62.3 18.3 4.69 .62 .80 .95 59.8 17.5 5.28 .64 .81 .97 57.2 16.8 5.94 .65 .83 .99 4.18 .43 .57 .70 64.6 18.9 4.70 .43 .57 .71 62.1 18.2 5.30 .44 .58 .73 59.4 17.4 5.97 .44 .59 .74 4.19 .44 .58 .73 65.5 19.2 4.71 .44 .59 .74 62.9 18.4 5.31 .44 .60 .76 60.1 17.6 5.98 .45 .61 .78 4.19 .44 .60 .76 66.2 19.4 4.72 .45 .61 .78 63.6 18.6 5.31 .45 .62 .79 60.8 17.8 5.98 .46 .64 .81 Air Temperature Entering Outdoor Coil 25_F (-4_C) Comp. Motor kW Input 3.91 3.80 3.71 Total Heating Capacity kBtuh 38.8 39.2 39.5 kW 11.4 11.5 11.6 Comp. Motor kW Input 3.51 3.40 3.31 5_F (-15_C) Total Heating Capacity kBtuh 27.5 27.9 28.2 kW 8.1 8.2 8.3 Comp. Motor kW Input 3.08 2.97 2.88 -15_F (-26_C) Total Heating Capacity kBtuh 13.8 14.2 14.5 kW 4.0 4.2 4.2 Comp. Motor kW Input 2.29 2.18 2.09

HP26-060
Indoor Coil Air Volume 70_F db (21_C db) cfm 1800 2000 2200 L/s 850 945 1040

CH33-62D-F - CH23-68 HEATING CAPACITY


65_F (18_C) Total Heating Capacity kBtuh 66.1 66.5 66.8 kW 19.4 19.5 19.6 Comp. Motor kW Input 4.29 4.18 4.09 45_F (7_C) Total Heating Capacity kBtuh 52.7 53.1 53.4 kW 15.4 15.6 15.6

HP26-060 HEATING PERFORMANCE CH33-62D-F - CH23-68 at 2000 cfm (945 L/s)


Outdoor Temperature _F 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 -15 -20 _C 18 16 13 10 8 7 4 2 -1 -4 -7 -8 -9 -12 -15 -18 -21 -23 -26 -29 Compressor Motor kW Input 4.18 4.09 4.00 3.91 3.85 3.80 3.67 3.53 3.47 3.40 3.34 3.30 3.26 3.17 2.97 2.77 2.57 2.38 2.18 1.98

Total Output kBtuh 66.5 63.3 60.1 56.9 55.0 53.1 48.3 43.5 41.4 39.2 37.1 35.8 34.5 31.3 27.9 24.5 21.0 17.6 14.2 10.7 kW 19.5 18.6 17.6 16.7 16.1 15.6 14.2 12.7 12.1 11.5 10.9 10.5 10.1 9.2 8.2 7.2 6.2 5.2 4.2 3.1

HP26 / Page 58 "