You are on page 1of 86

SUSTAV UZBUDE ABB UNITROL 6800

Dr. sc. Muharem Mehmedovi, dipl. ing. ENERGOCONTROL ZAGREB d.o.o., ZAGREB Zdravko Rabuzin, dipl. ing. ENERGOCONTROL ZAGREB d.o.o., ZAGREB Krunoslav Stijelja, ing., ENERGOCONTROL ZAGREB d.o.o., ZAGREB Josip Rado, dipl. ing., ENERGOCONTROL ZAGREB d.o.o., ZAGREB

SUSTAV UZBUDE ABB UNITROL 6800


TE TRBOVLJE TG4:
Un=13.8kV, Uf0=120V, If0=543.6A Ufn=427V, Ifn=1575A Sn=156.2MVA, n=3000min-1

SUSTAV UZBUDE ABB UNITROL 6800- TET TG4

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV REGULACIJE UZBUDE SINKRONIH GENERATORA:


Sinkroni generator Sustav uzbude

SUSTAV UZBUDE ABB UNITROL 6800 SVRHA SUSTAVA UZBUDE :


Osiguranje promjenjive istosmjerne razine struje uzbude generatora, Regulacija napona generatora sa zadovoljavajuom tonou, Osigurati stabilni pogon pri paralelnom radu na mrei, Odravati pogonske veliine generatora u dopustivom podruju, Primjeren doprinos prijelaznoj i dinamikoj stabilnosti sustava, Osigurati komunikaciju prema nadreenim upravljakim sustavima elektrane.

SUSTAV UZBUDE ABB UNITROL 6800

SOFTVERSKA STRUKTURA SUSTAVA UZBUDE UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


AUTOMATSKI REGULATOR NAPONA, LIMITERI I STABILIZATOR ELEKTROENERGETSKOG SUSTAVA

SUSTAV UZBUDE ABB UNITROL 6800 OSNOVNE FUNKCIJE SUSTAVA UZBUDE (AUTOMATSKI REGULATOR NAPONA) : Regulacija u zatvorenoj petlji (automatska regulacija napona generatora, ograniivai i druge regulacije) Naponski regulator s podesivim PID filtrom (lanom) Polagani (soft) start sustava uzbude Kompenzacija pada napona na blok transformatoru (statika)

SUSTAV UZBUDE ABB UNITROL 6800


OSTALE FUNKCIJE UNUTAR UNITROLA 6800: Individualno podesivi ograniivai (limiteri):
U naduzbudi limiter maksimalne struje uzbude te struje generatora (armature) U poduzbudi (P,Q) limiter i /ili limiter minimalne struje uzbude (koordinirane sa zatitom od gubitka uzbude) V/Hz limiter podeen neto nie od odgovarajue zatite od prevelike magnetske indukcije

Nadreene regulacije (po faktoru snage, jalovoj snazi te rastereenje po jalovoj snazi) Stabilizator elektroenergetskog sustava

SUSTAV UZBUDE ABB UNITROL 6800

OSTALE FUNKCIJE SPECIFINE ZA UNITROL 6800: MOGUNOST KONFIGURIRANJA I PARAMETRIRANJA PRAKTINO SVIH GENERATORSKIH ZATITA (izuzev diferencijalne)

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


AUTOMATSKI REGULATOR NAPONA STRUKTURA I FUNKCIJE

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800


Max-min logika slui za ispravnu propagaciju signala prema formiranju upravljakog napona Uc

SUSTAV UZBUDE ABB UNITROL 6800


UNUTAR UNITROL 6800 PRETHODNA SE STRUKTURA (PONOVLJENA LIJEVO) MOE ODABRATI TAKO DA PID LANOVI LIMITERA MOGU BITI JEDNAKI ZA SVE (DESNO)

SUSTAV UZBUDE ABB UNITROL 6800


Parametri proporcionalno-integralnog i derivacijskog lana (PID lana odnosno lanova) odabiru se tako da odziv zatvorenog sustava regulacije uzbude sa svakim od navedenih regulatora odnosno limitera bude stabilan s dovoljnim relativnim faktorom priguenja (priblino izmeu 0.7 i 1) bez bitnog gubitka brzine odziva i tonosti, Za vrlo visoku tonost u stacionarnom stanju brinut e se integralni lan, Struktura PID filtara (blokovski i priblino frekvencijski prikaza) na je na sljedeem slajdu gdje su oznaeni njegovi osnovni parametri. Vrijednosti parametara dane su u izvjetaju o putanju u pogon.

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800


MODEL SUSTAVA UZBUDE UNITROL 6800 PODRUJE PODEENJA PARAMETARA (DVOSTRUKI PID KAO NA PRETHODNOM SLAJDU)
Para-metar TR Ts KIR KIA KR(V0) TB1 TB2 TC1 TC2 Us+ Opis parametra Vremenska konstanta mjernih lanova Vremenska konstanta usmjerivaa impulsnog ureaja i Mjerna jediinica s s rj rj rj s s s s rj Opseg podeavanja 0.02 0.004 (-0.20)-(+0.20) (-0.20)-(+0.20) 10-1000 (TB1TB2) 0<TB2TC2 0.01-10 0.01-2 fiksirano zadavanjem stvarnog maksimalnog pozitivnog istosmjernog napona fiksirano zadavanjem stvarnog maksimalnog pozitivnog istosmjernog napona Tipina ili preporuena vrijednost 0.02 0.004 +0.06 0.00 300 6.67 0.08 2.00 0.08 Za turbogeneratore oko 6pu -0.85 Us+

Faktor kompenzacije jalove snage (Qstatic) Faktor kompenzacije djelatne snage (Pstatic) Pojaanje u stacionarnom stanju (NF) Vremenska konstanta kanjenja prvog filtra (TB1TB2) Vremenska konstanta kanjenja drugog filtra Vremenska konstanta prethoenja prvog filtra Vremenska konstanta prethoenja drugog filtra Faktor pozitivnog stropnog napona uzbude

Us-

Faktor negativnog stropnog napona uzbude

rj

SUSTAV UZBUDE ABB UNITROL 6800

POJEDNOSTALJENI MODEL SUSTAVA UZBUDE UNITROL 5000/6800

SUSTAV UZBUDE ABB UNITROL 6800


POLOAJ I DJELOVANJE OGRANIIVAA (LIMITERA) UNUTAR SUSTAVA UZBUDE UNITROL 5000/6800

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


AUTOMATSKI REGULATOR NAPONA STABILIZATOR EES-a (PSS)

SUSTAV UZBUDE ABB UNITROL 6800


ULOGA STABILIZATORA EES: Osigurava dodatnu komponentu elektromagnetskog momenta u svrhu da: - se dobije pozitivno ukupno priguenje i to u irokom opsegu frekvencija njihanja rotora (0.1-4)Hz da se dobije pozitivna sinkronizacijska komponenta momenta za djelominu kompenzaciju varijacija napon a generatora

SUSTAV UZBUDE ABB UNITROL 6800


Stabilizator elektroenergetskog sustava U UNITROL 6800 sustavu na izboru su dvije varijante prema IEEE Std. 421.5 od 2005.: PSS2B i PSS4B (viepojasni). Obje varijante koriste dva signala (brzinu vrtnje rotora (alternativno frekvenciju napona i djelatnu snagu). U TE Trbovlju (AG 4) primijenjen je PSS2B koji je vrlo slian varijanti PSS2A prema istom standardu, ali iz 1992. godine (slajd iza).

SUSTAV UZBUDE ABB UNITROL 6800 PSS2B

U PSS2B ugraen je jo jedan korekcijski lan (T10, T11) u izlazu PSS-a u odnosu na PSS2A

SUSTAV UZBUDE ABB UNITROL 6800

MODEL STABILIZATORA EES

SUSTAV UZBUDE ABB UNITROL 6800

PSS4B - pretvornici

SUSTAV UZBUDE ABB UNITROL 6800


PSS4B korekcija frekvencijskog spektra

SUSTAV UZBUDE ABB UNITROL 6800


MODEL STABILIZATORA EES: PODRUJE PODEENJA PARAMETARA, PSS2A i PSS2B
Parametar TW1, TW2 TW3, TW4 Ks1 Ks2 Opis parametra Mjerna jediinica s s rj integrala djelatne snage (elekttromagnetskog rj Opseg podeavanja 0.1-30 0.1-30 0.1-50 0.01-5 Tipina preporuena vrijednost TW1=2 TW2=2 TW3=2 TW4 se ne koristi ... ... ili

Vremenske konstante visokopropusnog filtra (washout filtra) za odstupanje brzine vrtnje Vremenske konstante visokopropusnog filtra (washout filtra) za djelatnu snagu Pojaanje SEES-a Faktor proprcionalnosti momenta)

Ks3 T1,T3 T2,T4 T7 T8 T9 M N UPSSMAX UPSSMIN

Fino (teinsko) podeavanje zbroja signala integrala djelatne snage i brzine vrtnje Vremenska konstanta prethoenja kompenzacijske prijenosne funkcije Vremenska konstanta kanjenja kompenzacijske prijenosne funkcije Vremenska konstanta integratora djelatne snage (elektromagnetskog moenta) generatora Vremenska konstanta prethoenja niskopropusnog ramp tracking filtra Vremenska konstanta kanjenja niskopropusnog ramp tracking filtra red nazivnika ramp tracking filtra (za N=1, inae je taj red MN) red brojnika ramp tracking filtra Maksimalna vrijednost izlaznog signakla SEES-a Minimalna vrijednost izlaznog signakla SEES

rj s s s s s -

0.01-5 0.00-2.50 0.00-2.50 3-30 0.00-2.50 0.00-2.50 2-5 1-4

1 ... ... 2.00 0.00 0.00 5 1 0.100 (susree ak i do +0.2) -0.100 se

rj rj

0.000-(+3.277) 0.000-(-3.277)

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


SRUSG - AUTOMATSKI REGULATOR NAPONA ODZIV U VREMENSKOM PODRUJU PRAZNI HOD

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod ARN - uzbuivanje na nazivni napon (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod ARN - skokovita promjena reference AVR -/+10% (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod ARN- razbuivanje s nazivnog napona invertiranjem (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod ARN - razbuivanje s nazivnog napona prekidaem (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


SRUSG - AUTOMATSKI REGULATOR NAPONA ODZIV U VREMENSKOM PODRUJU RAD NA MREI

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, rad na mrei ARN - skokovita promjena reference AVR -/+3% (kanal 1)

SUSTAV UZBUDE ABB UNITROL 6800


Udarno rastereenje agregata djelovanjem na generatorski prekida bez razbuivanja i obustave pogona iz radne toke Ug0=103.6% (14.3kV), Uf0=53% (226.9V), If0=62% (979.3A), Pg0=4.33% (6.78MW), Qg0=35.8% (56Mvar), Ig0=34.7% (2270A), kanal 1, Grafiki su u tri koordinatna sustva prikazani redom, (1) upravljaki napon (Uc), (2) napon generatora (Ugrel), struja uzbude (IfRel), struja generatora (IgRel), djelatna snaga (PRel), (3) napon uzbude (UfRel) te jalova snaga (QRel)

SUSTAV UZBUDE ABB UNITROL 6800


Udarno rastereenje (bez razbuivanja i obustave pogona)

SUSTAV UZBUDE ABB UNITROL 6800


Udarno rastereenje agregata djelovanjem na generatorski prekida putem diferencijalne zatite s obustavom pogona i razbuivanjem iz radne toke Ug0=100.% (13.8kV), Uf0=35% (145V), If0=43.2% (680A), Pg0=15% (23.4MW), Qg0=13% (20.3Mvar), Ig0=19.5% (1274A), kanal 1, Grafiki su u tri koordinatna sustva prikazani redom, (1) upravljaki napon (Uc), (2) napon generatora (Ugrel), struja uzbude (IfRel), struja generatora (IgRel), djelatna snaga (PRel), (3) napon uzbude (UfRel) te jalova snaga (QRel)

SUSTAV UZBUDE ABB UNITROL 6800


Udarno rastereenje s razbuivanjem i obustavom pogona

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


LIMITERI

SUSTAV UZBUDE ABB UNITROL 6800


POGONSKI DIJAGRAM SINKRONOG GENERATORA S KARAKTERISTIKAMA OGRANIIVAA (LIMITERA)

SUSTAV UZBUDE ABB UNITROL 6800 (P,Q) LIMITER


(P,Q) LIMITER IMA ZADAU DA SPRIJEI DA SE GENERATOR U POGONU NE NAE IZA GRANICE STABILNOSTI GDJE MOE BITI IZVJESTAN GUBITAK SINKRONIZMA!!! . STATIKA PODEENJA (P,Q) LIMITERA MORAJU BITI KOORDINIRANA SA ZATITOM OD GUBITKA UZBUDE TO JE OVOM PRIGODOM I NAINJENO!
P(pu) Q(pu) 0 -0.128 0.2 -0.128 0.4 -0.128 0.6 -0.08 0.8 -0.048 1.0 -0.013

SUSTAV UZBUDE ABB UNITROL 6800


PQ LIMITER U POGONSKOM DIJAGRAMU
TE TRBOVLJE - AG4 - ZATITA OD GUBITKA UZBUDE, PQ LIMITER, 2010-08-12 1 0.9 0.8 0.7 DJELATNA SNAGA, pu 0.6 0.5 0.4 0.3 0.2 0.1 0 -1 PQ limiter Zatita od gubitka uzbude Jedinina krunica Pmaxt=0.8 pu

-0.8

-0.6

-0.4

-0.2

0 0.2 JALOVA SNAGA, pu

0.4

0.6

0.8

SUSTAV UZBUDE ABB UNITROL 6800


Korekcija (P,Q) limitera s naponom generatora

SUSTAV UZBUDE ABB UNITROL 6800


(P,Q) LIMITER REALIZACIJA U MATLAB-SIMULINKU

SUSTAV UZBUDE ABB UNITROL 6800


Prorada ograniavaa (PQ limiter) u poduzbuenom radu iz radne toke Ug0=97.9% (13.51kV), Uf0=27.2% (116.14V), If0=33.6% (529.2A), Pg0=3.5% (5.65MW), Qg0=0.65% (1.01Mvar), Ig0=3.62% (236.5A), kanal 1 Grafiki su u tri koordinatna sustava prikazani redom, (1) napon generatora (Ugrel), struja uzbude (IfRel), struja generatora (IgRel), djelatna snaga (PRel), (2) upravljaki napon (Uc), napon uzbude (UfRel), jalova snaga (QRel) te (3) signal prorade ograniavaa (SFSLHVG_iSelectedInput)

SUSTAV UZBUDE ABB UNITROL 6800


Prorada (P,Q) ograniivaa

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE UZBUDE (IE LIMITER)

Limiter maksimalne struje uzbude ima dvije postavne vrijednosti: 1. za ogranienje struje uzbude tijekom snanih prijelaznih procesa (npr. tijekom dinamike snienja napona generatora) u odreenom ogranienom vremenskom intervalu 2. za ogranienje MCR razine tijekom trajnog normalnog pogona za sprjeavanje termikog preoptereenja Vremenske karakteristike ogranienja mogu se odabrati (fiksno vrijeme te inverzne karakteristike)

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE UZBUDE (IE LIMITER)

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE UZBUDE (IE LIMITER) REALIZACIJA U MATLAB-SIMULINKU

SUSTAV UZBUDE ABB UNITROL 6800


Prorada ograniavaa (IE limiter) u naduzbuenom radu iz radne toke Ug0=100% (13.8kV), Uf0=50.1% (214V), If0=53% (835A), Pg0=61% (95MW), Qg0=0.% (0Mvar), Ig0=61% (3986A), kanal 1, Grafiki su u tri koordinatna sustava prikazani redom, (1) upravljaki napon (Uc), signal prorade ograniavaa (SFSLHVG_iSelectedInput...3), (2) napon generatora (Ugrel), struja generatora (IgRel), djelatna snaga (PRel), struja uzbude (IfRel), (3) napon uzbude (UfRel) te jalova snaga (QRel), zajednika prijenosna funkcija PID-a

SUSTAV UZBUDE ABB UNITROL 6800


Prorada IE ograniivaa

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE GENERATORA (IG LIMITER) Limiter maksimalne struje generatora ograniava struju armature tako da generator ne bude preoptereen u smislu termike rezerve . U tom smislu integrira se kvadrat IG IGtherm i kad ta vrijednost prijee termiku rezervu postavna vrijednost limitera se smanjuje prema IGtherm . (uobiajeno od 1pu do 1.1pu) Vremenske karakteristike ogranienja mogu se odabrati (fiksno vrijeme te inverzne karakteristike Pri faktoru snage =1 i visokoj struji ova zatita ne moe tu struju ograniiti (jalova komponenta struje ve je nula), vidi sliku desno na sljedeem slajdu!

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE GENERATORA (IG LIMITER)

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER MAKSIMALNE STRUJE GENERATORA (IG LIMITER) REALIZACIJA U MATLAB-SIMULINKU

SUSTAV UZBUDE ABB UNITROL 6800


Prorada ograniavaa (IG limiter) u naduzbuenom radu po struji armature iz radne toke Ug0=100% (13.8kV), Uf0=50.1% (214V), If0=53% (835A), Pg0=61% (95MW), Qg0=0.% (0Mvar), Ig0=61% (3986A), kanal 1, Grafiki su u tri koordinatna sustava prikazani redom, (1) upravljaki napon (Uc), signal prorade ograniavaa (SFSLHVG_iSelectedInput...2), (2) napon generatora (Ugrel), struja generatora (IgRel), djelatna snaga (PRel), struja uzbude (IfRel), (3) napon uzbude (UfRel) te jalova snaga (QRel), zajednika prijenosna funkcija PID-a

SUSTAV UZBUDE ABB UNITROL 6800


Prorada IG ograniivaa

SUSTAV UZBUDE ABB UNITROL 6800 OGRANIENJE V/Hz


Ogranienje V/Hz je predvieno sa svrhom izbjegavanja tokovnog preoptereenja stroja i transformatora (npr. uzbuenom stroju pri ukljuenom ARN (AVR) u praznom hodu smanjuje se brzina vrtnje). U sluaju prekoraenja postavljenog omjera reducira se referenca regulatora tako da se ne prijee iznos postavljenog omjera. Tipina vrijednost ovog omjera je oko 1.15, a tona vrijednost ovisi o lokalnim mrenim pravilima te opsegu regulacije napona generatora. Vremenske karakteristike ogranienja mogu se odabrati (fiksno vrijeme te inverzne karakteristike).

SUSTAV UZBUDE ABB UNITROL 6800


LIMITER V/Hz REALIZACIJA U MATLAB-SIMULINKU

SUSTAV UZBUDE ABB UNITROL 6800 OSNOVNE FUNKCIJE SUSTAVA UZBUDE (RUNI MAN REGULATOR - REGULATOR PO STRUJI UZBUDE) : Regulacija u zatvorenoj petlji (automatski regulator po struji uzbude s podesivim PI filtrom) Praenje automatskog regulatora napona

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800 Runi (rezervni) regulator regulator struje uzbude PI tipa
Konane postavke PI regulatora struje uzbude u TE Trbovlje AG 4: V0=500pu/pu, Vp=4pu/pu, Ta=0.3s,

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


SRUSG - RUNI (REZERVNI) REGULATOR (STRUJE UZBUDE) ODZIV U VREMENSKOM PODRUJU PRAZNI HOD

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod RR (MAN) - uzbuivanje na nazivni napon (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod RR (MAN) - skokovita promjena reference AVR -/+10% (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod RR (MAN) - razbuivanje s nazivnog napona invertiranjem (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, prazni hod RR (MAN) - razbuivanje s nazivnog napona prekidaem (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800

FUNKCIJE SUSTAVA UZBUDE:


SRUSG - RUNI (REZERVNI) REGULATOR (STRUJE UZBUDE) ODZIV U VREMENSKOM PODRUJU RAD NA MREI

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava uzbude pri skokovitoj promjeni reference +/-5% pri radu generatora na mrei, kanal 1, rezervni regulator (regulator struje uzbude, Vp=4pu/pu, Ta=0.3s). Grafiki su prikazani redom upravljaki napon (Uc), napon uzbude (Ufrel), jalova snaga (Qrel) te napon generatora (Ugrel)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, rad na mrei RR (MAN) - skokovita promjena reference AVR +/-5% (kanal 1)

SUSTAV UZBUDE ABB UNITROL 6800


Odziv sustava regulacije uzbude generatora AG4 u TE TRBOVLJE, rad na mrei RR (MAN) - skokovita promjena reference AVR +/-5% (kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800

Koncept nadzora pri kvaru kanala ili kvaru regulatora

SUSTAV UZBUDE ABB UNITROL 6800

U TE Trbovlje AG 4 nema posebnog rezervnog regulatora struje uzbude

SUSTAV UZBUDE ABB UNITROL 6800

U TE Trbovlje AG 4 nema posebnog rezervnog regulatora struje uzbude

SUSTAV UZBUDE ABB UNITROL 6800

PRIJELAZ S REGULATORA NA REGULATOR Odziv sustava uzbude pri prijelazu iz automatskog regulatora napona generatora (AUTO) na rezervni regulator (regulatora struje uzbude, MAN) i natrag, rad generatora na mrei, kanal 1 (na donjem dijelu slike prikazni su i neki digitalni signali, a posljednji je signal prijelaza ARN-RR-ARN)

SUSTAV UZBUDE ABB UNITROL 6800


Prijelaz ARN RR- ARN

SUSTAV UZBUDE ABB UNITROL 6800

PRIJELAZ S KANALA NA KANAL

Odziv sustava uzbude pri prijelazu s kanala 1 na kanal 2 trajno, automatski regulator napona, rad generatora na mrei, (na donjem dijelu slike prikazni su i neki digitalni signali, a prvi je signal prijelaza s kanala 1 na kanal 2)

SUSTAV UZBUDE ABB UNITROL 6800


Prijelaz S KANALA NA KANAL

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800

SUSTAV UZBUDE ABB UNITROL 6800


NADREENE REGULACIJE Q REGULACIJA

Radna toka regulacije jalove snage unutar pogonskog dijagrama moe se podesiti: - lokalno putem lokalnog ECT - daljinski pomou raise(vie)/lower(nie) komande (remote ECT)

SUSTAV UZBUDE ABB UNITROL 6800


Rastereenje po jalovoj snazi

Rastereenje po jalovoj snazi posebni je sluaj Q regulacije pri kojoj je postavna vrijednost ove regulacije jednaka nuli. Prije nego li se generator odvoji od sustava djelatna i jalova snaga se reduciraju na to je mogue manji iznos. Po prijemu reference 0 Q regulator smanjuje jalovu snagu na nulu podesivom brzinom.