MiCOM P143 Programmable Scheme Logic

Opto Input Mappings

Input L10 DDB #041 Input L18 DDB #049 Input L19 DDB #050 Input L20 DDB #051 Input L21 DDB #052 Input L22 DDB #053 Input L23 DDB #054 Input L25 DDB #056 Input L26 DDB #057 Input L27 DDB #058 Input L28 DDB #059 Input L29 DDB #060 Input L30 DDB #061 Input L24 DDB #055 Input L31 DDB #062 Input L32 DDB #063

MCB/VTS DDB #231 CB Aux 3ph(52-B) DDB #229 CB Aux 3ph(52-A) DDB #228 SR User Alarm 1 LS1 Closed DDB #167 SR User Alarm 2 LS1 #168 DDB Open SR User Alarm 3 ES2 Closed DDB #169 SR User Alarm 4 ES2 #170 DDB Open SR User Alarm 5 LS2 Closed DDB #171 SR User Alarm 6 LS2 #172 DDB Open SR User Alarm 7 ES3 Closed DDB #173 SR User Alarm 8 ES3 #174 DDB Open SR User Alarm 9 ES4 Closed DDB #175 SR User Alarm 10 ES4 #176 DDB Open SR User Alarm 11 ES1 Closed DDB #177 SR User Alarm 12 ES1 #178 DDB Open SR User Alarm 13 0.9Vn DDB #179

Check Synch. and Voltage Monitor Mapping

SysChks Inactive DDB #449 Check Sync 1 OK DDB #447 Check Sync 2 OK DDB #448 Live Line DDB #443 Dead Bus DDB #446 Dead Line DDB #444 Live Bus DDB #445 Input L10 DDB #041 Man Check Synch DDB #402

1 &

&
0

AR Sys Checks OK DDB #403

Straight

Output R10 DDB #009 0

& & &

MiCOM P143 Programmable Scheme Logic


I>1 Trip DDB #243 I>2 Trip DDB #247 I>3 Trip DDB #251 I>4 Trip DDB #255 I2>1 Trip DDB #513 I2>2 Trip DDB #514 I2>3 Trip DDB #515 I2>4 Trip DDB #516 Broken Line Trip DDB #260 Thermal Trip DDB #276 IN1>1 Trip DDB #261 IN1>2 Trip DDB #262 IN1>3 Trip DDB #263 IN1>4 Trip DDB #264 IN2>1 Trip DDB #265 IN2>2 Trip DDB #266 IN2>3 Trip DDB #267 IN2>4 Trip DDB #268 ISEF>1 Trip DDB #269 ISEF>2 Trip DDB #270 ISEF>3 Trip DDB #271 ISEF>4 Trip DDB #272 IREF> Trip DDB #273 V<1 Trip DDB #278 V<2 Trip DDB #282 V>1 Trip DDB #286 V>2 Trip DDB #290 V2> Trip DDB #277 VN>1 Trip DDB #274 VN>2 Trip DDB #275 F<1 Trip DDB #424 F<2 Trip DDB #425 F<3 Trip DDB #426 F<4 Trip DDB #427 F>1 Trip DDB #428 F>2 Trip DDB #429 YN> Trip DDB #436 GN> Trip DDB #437 BN> Trip DDB #438 df/dt>1 Trip DDB #485 df/dt>2 Trip DDB #486 df/dt>3 Trip DDB #487 df/dt>4 Trip DDB #488 100 100 100

Output Relay Mappings

Dwell
0

Output R1 DDB #000

100

Dwell
0

Output R2 DDB #001

Dwell

Output R3 DDB #002 0

Dwell
0

Output R8 DDB #007

MiCOM P143 Programmable Scheme Logic

Lockout Relays Supervision


86 Supervision
0 Input L1 DDB #032 0

Drop-Off
400

Straight
0

Output R6 DDB #005

50

86BF Supervision
0 Input L2 DDB #033

&
Drop-Off
400

Pick-Up
0 0

Straight
0

Output R7 DDB #006

50

&

Pick-Up
0

Latching

LED 8 DDB #071

MiCOM P143 Programmable Scheme Logic

LED Mappings

I>1 Trip DDB #243

Latching

LED 1 DDB #064

I>2 Trip DDB #247

1
I>3 Trip DDB #251

Latching

LED 2 DDB #065

IN1>1 Trip DDB #261

Latching

LED 3 DDB #066

IN1>2 Trip DDB #262

1
IN1>3 Trip DDB #263

Latching

LED 4 DDB #067

In DD In DD In DD In DD In DD In DD

In DD

MiCOM P143 Programmable Scheme Logic

Trip Circuit 1 Supervision

Input L3 DDB #034 Input L4 DDB #035 Input L5 DDB #036 Input L6 DDB #037 Input L7 DDB #038 Input L8 DDB #039

1
0 0

&

Drop-Off
400

Straight
0

Output R4 DDB #003

50

&

Pick-Up
0

Latching

LED 6 DDB #069

Trip Circuit 2 Supervision

put L11 DB #042

put L12 DB #043

1
0 0

put L13 DB #044

1 1

&

Drop-Off
400

Straight
0

Output R5 DDB #004

put L14 DB #045 50

put L15 DB #046

put L16 DB #047

&

Pick-Up
0

Latching

LED 7 DDB #070

Closing Coil Supervision


0 0

nput L17 DB #048

Drop-Off
400

Straight
0

Output R13 DDB #012

50

&

Pick-Up
0

Latching

LED 5 DDB #068

Page : 1

DDB #488 AR Trip Test DDB #372

Page : 2

Page : 3

Page : 4

Page : 5