You are on page 1of 8

APPD.

Saudi Electricity Company


Eastern Region Branch

DESCRIPTION

CHKD.

CERT.

132kV CABLE SHEATH VOLTAGE CALCULATIONS


BY NO.
DRAWN BY DATE CHKD BY

DATE

REVISIONS
G.A.G 10/2007 V.S.PANDIT

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

CERTIFIED
BY: DATE: ____________

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

1 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

APPD.

Saudi Electricity Company


Eastern Region Branch

CERT.

CHKD.

Contents
1.0 2.0 PREAMBLE DESIGN BASIS CABLE SHEATH VOLTAGE CALCULATION FOR 1CX2000 SQ MM CABLE/ PH FOR AL-JOUF TIE LINE CIRCUIT CABLE SHEATH VOLTAGE CALCULATION FOR 1CX1200 SQ MM CABLE/ PH FOR DAWMAT & SAKAKA-A CIRCUIT CABLE SHEATH VOLTAGE CALCULATION FOR 1CX800 SQ MM CABLE/ PH FOR GEN-8 & GEN-9 CIRCUITS ATTACHMENTS

DESCRIPTION

3.0 4.0

5.0 6.0

NO.

DRAWN BY DATE CHKD BY

DATE

BY

REVISIONS
G.A.G 10/2007 V.S.PANDIT

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

CERTIFIED
BY: DATE: ____________

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

1.0 PREAMBLE

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

2 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

APPD.

Saudi Electricity Company


Eastern Region Branch This document covers 132kV cable sheath voltage calculation( provided by the cable vendor) for New AL-JOUF Power plant to Exist Al-Jouf Tie line circuits, Dawmat AlJandal Line-2,Sakaka-A S/S line-1 and Gen-8 & Gen-9 circuits. 2.0 DESIGN BASIS: 2.1 System Details: a) Nominal System Voltage Breaker interrupting capacity : 132 kV : 40 kA

DESCRIPTION

CHKD.

CERT.

b)

2.3 Cable Ampacity Cable Ampacity as per Cable design requirements specified in P.T.S. Page: 83 are as follows Cable Ampacity for 132kV,2000 Sq Mm Cu,XLPE Cable = 875A
BY

Cable Ampacity for 132kV, 1200 Sq Mm Cu,XLPE Cable =700A

Cable Ampacity for 132kV 800 Sq Mm Cu,XLPE Cable


DATE NO.

= 550A

2.4 Reference document


REVISIONS

Reference Standard Sheath bonding method :

:ANSI/IEEE STD 575-1988 Single Point Bonded System

DRAWN BY DATE CHKD BY

G.A.G 10/2007 V.S.PANDIT

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

CERTIFIED
BY: DATE: ____________

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

3.0 SHEATH VOLTAGE CALCULATION FOR 132KV 2000MM 2 CABLE FOR TIE LINE CIRCUITS 1 & 2

3.1. Induced Voltage on Cable Shield


INDEX PLANT NO. DRAWING NO. SHEET NO. REV. NO.

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

FA415

EE-031579

3 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

APPD.

Saudi Electricity Company


Eastern Region Branch a. Sheath Voltage Calculations Circuit configuration : Cable in Duct Reference Standard Sheath bonding method Axial phase spacing (S) : : = = = = = = ANSI/IEEE STD 575-1988 (as per Electra CIGRE 1973 Report) Single Point Bonded System 184 mm 113.6 mm 133 mm 875 Amps 40000 Amps 40000 Amps

DESCRIPTION

CHKD.

CERT.

Mean sheath diameter (d) Cable outer diameter Full load current 3 phase symmetrical fault current 1 phase to ground fault current

BY

b.Induced Sheath Voltage under normal operating condition


DATE

Please find the attached sheath voltage calculation from vendor for normal condition Max. route length = 415 m

NO.

REVISIONS
DRAWN BY DATE CHKD BY G.A.G 10/2007 V.S.PANDIT

The maximum induced sheath voltage is = 32.18V The above value is less than allowable limit of 65 V for sheath voltage requirement, and hence SVL is not required. c.. Induced Sheath Voltage under Fault Condition Three & Single phase symmetrical fault With A fault current of 40000 A for both Three Phase & single Phase.
.

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

Please find the attached vendor calculation for different fault cases. As per The Conclusion Maximum induced sheath voltage is 4.34kV. Since the maximum induced voltage developed between sheaths is 4340 Volts which is less than the permissible voltage of 5 kV during short circuit., Hence a 5kV sheath voltage limiter will be provided Conclusion:

CERTIFIED
BY: DATE: ____________

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

4 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

APPD.

Saudi Electricity Company


Eastern Region Branch 132 kV 2000 mm2 line cable sheath shall be grounded at the Existing Al-Jouf side through 5kV sheath voltage limiter. 4. SHEATH VOLTAGE CALCULATION FOR 132KV 1200MM 2 CABLE FOR SAKAKA-A & DAWMAT
LINE CIRCUITS

DESCRIPTION

CHKD.

CERT.

4.1. Cable Ampacity Line current @ normal Operating condition = 700A

4.2. Induced Voltage on Cable Shield a. Sheath Voltage Calculations Circuit configuration Reference Standard Sheath bonding method : : = = = = ANSI/IEEE STD 575-1988 (as per Electra CIGRE 1973 Report) Single Point Bonded System 200 mm( cable in duct in trefoil) 99 mm 40000 Amps 40000 Amps

BY

Axial phase spacing (S) Mean sheath diameter (d) 3 phase symmetrical fault current

NO.

DATE

REVISIONS
DRAWN BY DATE CHKD BY G.A.G 10/2007 V.S.PANDIT

1 phase to ground fault current

b. Induced Sheath Voltage under normal operating condition Please find the attached vendor calculation Maximum induced voltage = Maximum induced voltage = Max. route length =
.

APPROVED ENG. DEPT.


BY: DATE: ____________

105.28 x 10-6 x I V/m 105.28x10-6 x 700 = 0.07369V/m 350 m = 0.07369 x 350 = 25.79 V

- -

OPRG. DEPT.
BY: DATE: ____________

- -

Max. sheath voltage induced

CERTIFIED
BY: DATE: ____________

The above value is less than allowable limit of 65V for sheath voltage requirement, and hence SVL is not required. C. Induced Sheath Voltage under Fault Condition a. Three phase symmetrical fault Please find the attached vendor calculation.
DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA
/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

JOB ORDER NO.

23051002001

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

5 of 8

00

APPD.

Saudi Electricity Company


Eastern Region Branch

CHKD.

CERT.

(i) Three Phase Symmetrical Fault The maximum induced voltage =65.49 x 10-6 x I V/m

DESCRIPTION

Maximum induced voltage = Max. route length =

65.49x10-6 x 40000= 2.6196V/m 350 m = 2.6196 x 350 = 916.86 V

Max. sheath voltage induced


D

(ii) Phase Phase Fault The maximum induced voltage = 65.50 x 10-6 x I V/m Maximum induced voltage = Max. route length = 65.50x10-6 x 40000= 2.62V/m 350 m = 2.62 x 350 = 917 V

Max. sheath voltage induced


BY

(ii) Phase Earth Fault The maximum induced voltage = 7.693 V/m Max. route length = 350 m = 7.693 x 350 = 2692.55 V

NO.

DATE

REVISIONS
DRAWN BY DATE CHKD BY G.A.G 10/2007 V.S.PANDIT

Max. sheath voltage induced

APPROVED ENG. DEPT.


BY: DATE: ____________

In the above case, the maximum induced voltage developed between sheaths is 2692.55V, which is less than the permissible voltage limit of 5 kV. Hence a 5kV sheath voltage limiter is provided Conclusion: 132 kV, 1200 mm2 cable sheath shall be grounded at the Gantry side( for Dawmat & Sakaka-A line) through 5kV sheath voltage limiter. 5. SHEATH VOLTAGE CALCULATION FOR 132KV 1200MM 2 CABLE FOR SAKAKA-A & DAWMAT
LINE CIRCUITS

- -

OPRG. DEPT.
BY: DATE: ____________

- -

CERTIFIED
BY: DATE: ____________

5.1. Cable Ampacity Line current @ normal Operating condition = 550A 5.2. Induced Voltage on Cable Shield a. Sheath Voltage Calculations
DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA
/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

JOB ORDER NO.

23051002001

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

6 of 8

00

APPD.

Saudi Electricity Company


Eastern Region Branch

CHKD.

CERT.

Circuit configuration Reference Standard : : = = = = ANSI/IEEE STD 575-1988 (as per Electra CIGRE 1973 Report) Single Point Bonded System 150 mm( cable in duct in trefoil) 89.2 mm 40000 Amps 40000 Amps

DESCRIPTION

Sheath bonding method Axial phase spacing (S)

Mean sheath diameter (d) 3 phase symmetrical fault current 1 phase to ground fault current

b. Induced Sheath Voltage under normal operating condition Please find the attached vendor calculation
BY

Maximum induced voltage = Maximum induced voltage =

91.45 x 10-6 x I V/m 91.45x10-6 x 550 = 0.05V/m 300 m = 0.05 x 300 = 15 V

DATE

Max. route length = Max. sheath voltage induced

NO.

REVISIONS
DRAWN BY DATE CHKD BY G.A.G 10/2007 V.S.PANDIT

The above value is less than allowable limit of 65V for sheath voltage requirement, and hence SVL is not required. C. Induced Sheath Voltage under Fault Condition a. Three phase symmetrical fault Please find the attached vendor calculation. (i) Three Phase Symmetrical Fault
.

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

The maximum induced voltage =66.68 x 10-6 x I V/m Maximum induced voltage = 66.68x10 -6 x 40000= 2.66V/m 300 m = 2.66 x 300 = 800 V

CERTIFIED
BY: DATE: ____________

- -

Max. route length

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

Max. sheath voltage induced (ii) Phase Phase Fault

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

7 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc

APPD.

Saudi Electricity Company


Eastern Region Branch The maximum induced voltage = 66.68 x 10-6 x I V/m Maximum induced voltage = Max. route length = 66.68x10 -6 x 40000= 2.66V/m 300 m = 2.66 x 300 = 800 V

DESCRIPTION

CHKD.

CERT.

Max. sheath voltage induced (ii) Phase Earth Fault

The maximum induced voltage = 7.539 V/m Max. route length = 300 m = 7.539 x 300 = 2261.7 V

Max. sheath voltage induced

In the above case, the maximum induced voltage developed between sheaths is 2261.7V, which is less than the permissible voltage limit of 5 kV. Sheath Voltage limiter is not required, However a 5kV sheath voltage limiter is provided
BY

Conclusion: 132 kV, 800 mm 2 cable sheath shall be grounded at the Cable Termination Near Generator Transformer side through 5kV sheath voltage limiter. 6.0 Attachments

NO.

DATE

REVISIONS
DRAWN BY DATE CHKD BY G.A.G 10/2007 V.S.PANDIT

a) Vendor Supplied Cable sheath Voltage calculations

APPROVED ENG. DEPT.


BY: DATE: ____________

- -

OPRG. DEPT.
BY: DATE: ____________

- -

CERTIFIED
BY: DATE: ____________

- -

THIS DRAWING IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED

JOB ORDER NO.

23051002001

DRAWING TITLE
132kV CABLE SHEATH VOLTAGE CALCULATION NEW AL-JOUF POWER PLANT 132kV SUBSTATION AL-JOUF SAUDI ARABIA

INDEX

PLANT NO.

DRAWING NO.

SHEET NO.

REV. NO.

FA415

EE-031579

8 of 8

00

/var/www/apps/conversion/current/tmp/scratch12320/95938128.doc