You are on page 1of 2

HRT 12100

(12V10Ah)

+RT 12100 is a general purpose battery with 5 years


floating design life , meet with IEC, JIS standard .With
heavy duty grid, thickness plates, special additives, +RT
series battery have long and reliable standby service life.

Specification
Cells Per Unit

Voltage Per Unit

12

Capacity

10Ah@20hr-rate to 1.75V per cell @25 o C

Weight

Approx. 3.20 Kg

Max. Discharge Current

100 A (5 sec)

Internal Resistance

Approx. 15 m

Operating Temperature Range

Discharge: -20 C ~60 C


Charge: 0 o C~50 o C
Storage: -20 o C~60 o C

Normal Operating Temperature Range

25 oC5 oC

Float charging Voltage

13.7 to 13.9 VDC/unit Average at 25 o C

Recommended Maximum Charging


Current Limit

3A

Equalization and Cycle Service

14.6 to 14.8 VDC/unit Average at 25 o C

Self Discharge

+,7$&2 Valve Regulated Lead Acid (VRLA) batteries can be stored


o
for more than 6 months at 25 C. Self-discharge ratio less than 3%
o
per month at 25 C. Please charge batteries before using.

Terminal

Faston Tab 187(F1)/Faston tab 250(F2)

Constainer Material

A.B.S. (UL94-HB) , Flammability resistance of UL94-V2


can be available upon request.

Dimensions
Unit: mm

Dimension: 151(L)98(W)95(H)

Constant Current Discharge Characteristics : A(25 o C)


F.V/Time

5MIN

10MIN

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

9 .60 V

4 0.6 6

26 .6 6

20 .9 0

1 1 .73

6 .97 0

4 .01 4

2 .7 2 8

2.1 8 3

1.8 1 3

1 .1 55

1 .0 00

0 .56 1

1 0.0 V

3 9.1 9

25 .9 9

20 .2 3

1 1 .58

6 .78 0

3 .93 3

2 .6 7 8

2.1 5 3

1.7 8 2

1 .1 50

0 .9 89

0 .54 1

1 0.2 V

3 6.8 9

24 .7 1

19 .6 6

1 1 .40

6 .71 6

3 .89 2

2 .6 5 4

2.1 3 2

1.7 6 3

1 .1 40

0 .9 74

0 .53 1

1 0.5 V

3 3.1 6

23 .1 0

18 .5 5

1 1 .09

6 .58 4

3 .84 1

2 .6 3 0

2.1 1 1

1.7 4 2

1 .1 29

0 .9 69

0 .51 5

1 0.8 V

2 9.7 1

21 .5 4

17 .5 0

1 0 .72

6 .46 5

3 .80 9

2 .5 9 9

2.1 0 1

1.7 2 3

1 .1 25

0 .9 53

0 .48 5

1 1.1 V

2 5.9 9

19 .7 5

16 .1 4

1 0 .31

6 .29 2

3 .65 6

2 .5 4 9

2.0 8 2

1.7 0 6

1 .1 16

0 .9 38

0 .47 7

Constant Power Discharge Characteristics : W(25 o C)


5MIN

10MIN

15MIN

30MIN

1HR

2HR

3HR

4HR

5HR

8HR

10HR

20HR

9 .60 V

4 27 .8

28 3 .6

22 3 .7

1 3 4 .3

8 0 .9 3

4 6.8 3

3 1.8 9

25 .8 3

21 .4 6

1 3 .83

1 1 .98

6 .72 4

1 0.0 V

4 16 .6

27 7 .7

22 0 .5

1 3 2 .9

7 9 .7 5

4 6.4 3

3 1.8 2

25 .7 7

21 .3 5

1 3 .77

1 1 .86

6 .48 4

1 0.2 V

3 96 .3

26 6 .7

21 7 .6

1 3 1 .7

7 9 .1 6

4 6.1 4

3 1.7 0

25 .5 6

21 .1 4

1 3 .67

1 1 .75

6 .36 5

1 0.5 V

3 61 .7

25 5 .7

20 6 .3

1 2 9 .0

7 8 .0 9

4 5.7 7

3 1.5 7

25 .3 3

20 .8 9

1 3 .55

1 1 .63

6 .18 5

1 0.8 V

3 26 .3

23 9 .2

19 4 .9

1 2 6 .0

7 6 .8 1

4 5.3 9

3 1.2 0

25 .2 3

20 .6 8

1 3 .49

1 1 .45

5 .82 5

1 1.1 V

2 87 .8

22 2 .7

18 3 .5

1 2 2 .5

7 5 .3 8

4 3.8 2

3 0.6 0

24 .9 8

20 .4 8

1 3 .40

1 1 .28

5 .73 3

F.V/Time

All mentioned values are average values.

HRT 12100

12V10Ah
Storage characteristic

10

100

Capacity (%)

6
Life Expectancy (years)

Supplementary charge required


(Carry out supplementary charge
before use if 100% capacity is
requires)

80
10

Supplementary charge required


before use.
This supplementary charge will help
to recover the capacity and should
be made as early as possible.

60
20

40

30

40

Supplementary charge may often


fail to recover the capacity.
The battery should never be left
standing till this state is reached

20
0
0

10

20

30

40

50

Storage Time (months)

Battery Temperature

Charge characteristic Curve for standby use


15

7.5

Discharge characteristic Curve

5.0

120

0.24

100

0.20

13

6.5

4.3

12

6.0

4.0

11

5.5

3.7

10

5.0

3.3

Chcrge Voltage

80
Discharge
100%0.05CA20h
50%0.05CA10h
Charge
Chcrge Voltage2.275V/C
Charge Current0.1CA
Temperature 25

60

40

0.16

0.12

0.08

Terminal Voltage (V)

4.7

Charge Current (CA)

7.0

Charge Volume (%)

Charge VoltageV

Chcrge Volume

14

Supplementary charge and storage


guidelines

10 12 14 16 18 20 22 24

13

6.5

4.3

12

6.0

4.0

11

5.5

3.7

0.05C

10

5.0

3.3

4.5

3.0

0.62C
1C

3C

20

0.04

0.093C

0.16C
0.35C

Charge Current

4.5

3.0
0

0.6

1.2

12

30

Charge Timeh

10

20

24

Hr

min

10 12 14 16 18 20 24 28

Discharge Time

Capacity Factors With Different Temperature


Battery Type

-20

-10

10

20

25

30

40

45

GEL
6V&12V
Battery
2V

50%

70%

83%

85%

90%

98%

100%

102%

104%

105%

60%

75%

85%

88%

92%

99%

100%

103%

105%

106%

46%

66%

76%

83%

90%

98%

100%

103%

107%

109%

55%

70%

80%

85%

92%

99%

100%

104%

108%

110%

AGM
6V&12V
Battery
2V

Maintenance & Cautions

Discharge Current VS. Discharge Voltage


Final Discharge
Voltage V/cell

1.75V

Discharge
Current (A)

A 0.2C

1.60V

1.70V

Float Service:
Every month, recommend inspection every battery voltage.

0.2CA1.0C

A1.0C

Charge the batteries at least once every six months,


if they are stored at 25 oC.
Charging Method:

Every three months, recommend equalization charge for one time.


Equalization charge method:
Discharge: 100% rate capacity discharge.
Charge: Max. current 0.3CA, constant voltage 2.4-2.45V/Cell charge 24h.

Constant Voltage

-0.2Cx2h+2.4~2.45V/Cellx24h,Max. Current 0.3CA

Constant Current

-0.2Cx2h+0.1CAx12h

Fast

-0.2Cx2h+0.3CAx4.0h

SHENZHEN RITAR POWER CO.,LTD.


URL:www.ritarpower.com

Effect of temperature on float charge voltage: -3mV//Cell.


Length of service life will be directly affected by the number of discharge
.
cycles, depth of discharge, ambient temperature and charging voltage.

Address: Rm405,Tower C, Huahan Building,Langshan Rd16, Nanshan District, ShenZhen, 518057, China

Tel:+86-755-33981668 Fax:86-755-8347-5180

2010 - Version 1