50ZPA

Base 13 SEER
Single---Packaged Air Conditioner System
With R---22 Refrigerant Single and Three Phase
2 to 5 Nominal Tons (Sizes 024---060)

Product Data

A05194

Unit 50ZPA
The 50ZPA unit is a packaged air conditioner for manufactured
housing, residential, and light commercial applications. The
50ZPA unit design is the result of our firm commitment to the
development of the finest air conditioners that modern technology
can offer.
The 50ZPA unit is built in one basic cabinet size and features a
round side--by--side duct configuration.

FEATURES/BENEFITS
FACTORY--ASSEMBLED PACKAGE is a compact, fully
self--contained, electric cooling unit with horizontal supply and
return ducts. The 50ZPA units are available in a variety of standard
cooling sizes with voltage options to meet residential and light
commercial requirements. Unit installs easily on a ground level
pad.
EASY TO INSTALL -- 50ZPA units are small, compact, and easy
to handle. Every 50ZPA unit has an identical 32 x 51--in. (813 x
1295 mm) footprint to make planning simple. The concise design
uses less sheet metal and makes the 50ZPA units lighter than other
units. The unit can be easily positioned on the job site with the
hand holds built into the unit basepan. Drop--in cartridge style
heaters are utilized to minimize installation time. The 50ZPA unit
was designed with potential safety hazards in mind; with no sharp
edges or corners which could injure a worker.
NEW AND IMPROVED AERODYNAMIC FAN BLADE
DESIGN reduces the overall sound now as low as 72dBA.
SERVICE ACCESS makes installation and maintenance quicker
and easier. The 50ZPA units are designed to be serviced from both
the side and rear. The new design allows easy access for installation

and maintenance procedures on the unit. Routine maintenance


tasks such as coil cleaning are sped up with the new multiple access
side panels.
NO--RUST BASEPAN WITH INTEGRATED DRAIN PAN is
standard on all units. The 50ZPA units feature a tough, hightech,
composite material basepan with integrated drain pan. The
composite material eliminates the potential problems of rust and
premature replacement which are common with standard metal
basepans.
DURABLE PRE--PAINTED STEEL CABINET protects
against harsh weather. The watertight construction and corrosion-resistant finish of the 50ZPA unit will keep it looking like new for
years. The paint treatment process ensures quality protection
against the elements. A compact, low--profile design utilizes a
louvered coil enclosure for protection against vandalism and hail
damage.
INDOOR AIR QUALITY is designed into the 50ZPA units. A
sloped drain pan minimizes the amount of standing water inside
the unit, which limits mold and mildew growth. The drain pan is
made of a rust--proof material and will not deteriorate or release
foreign matter into the airstream.
LIGHTWEIGHT, COMPACT CONSTRUCTION is ideal for
manufactured housing and residential applications. The 50ZPA
unit is one of the lightest, most compact packaged units ever
designed. Its light weight (268 lb (121.6 kg) for the 50ZPA024
unit) makes the unit easier to handle. The low height keeps
ductwork connections to a minimum and makes units less visible.
The 50ZPA units utilize a structural beam design to form the four
sides of the cabinet. Only 12 different pieces of sheet metal are
used in the unit construction to simplify the unit for greater
reliability.
EFFICIENT, DEPENDABLE PERFORMANCE with durable
compressors designed for efficiency. The 50ZPA units offer 13.0
SEER (Seasonal Energy Efficiency Ratio) cooling performance
efficiencies. This performance level can reduce cooling expenses
by as much as 25% compared to older cooling equipment. A
high--efficiency, multi--speed blower motor system ensures quality
performance with most duct systems. The computer--designed
blower wheel is balanced for quiet operation.
DURABLE, DEPENDABLE, COMPRESSORS are designed
for high efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable
operation. Vibration isolation provides quiet operation.
Compressors have internal high--pressure and overcurrent
protection.

DIRECT--DRIVE MULTISPEED, BLOWER MOTOR is


standard on all models. Direct--drive, PSC condenser--fan motors
are designed to help reduce energy consumption and provide for
cooling operation down to 40F (4.4C).
REFRIGERANT SYSTEM is designed to provide dependability.
Liquid refrigerant strainers are used to promote clean, unrestricted
operation. Each unit leaves the factory with a full refrigerant
charge. Refrigerant service connections make checking operating
pressures easier.

ACCESSORY ELECTRIC HEATERS A variety of


accessory electric heaters are available for the 50ZPA units. These
heaters are comprised of a separate heater module mounted on the
blower inlet and remote mounted controls located in the unit
control box. Single point electrical connections are available for
powering both the heater and the unit.
LIMITED WARRANTYStandard 5--year limited warranty on
all parts and 5--year limited warranty on compressor.

50ZPA

TABLE OF CONTENTS
Page
FEATURES/BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ARI CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BASE UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7--13
TYPICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14--17
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TYPICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

MODEL NUMBER NOMENCLATURE

50ZPA

024

--- --- ---

--- ---

Type of Unit
50ZPA--- Single Packaged Electric
Cooling Unit
Options
TP --- Base unit with tin plated indoor coil hairpins

Nominal Cooling Capacity


024 --- 2.0 Tons
030 --- 2.5 Tons
036 --- 3.0 Tons
042 --- 3.5 Tons
049 --- 4.0 Tons
048 --- 4.0 Tons
060 --- 5.0 Tons

N/A

Only used if ordering an option

Packaging
Series

Electrical Supply
3 --- 208/230--- 1--- 60
5 --- 208/230--- 3--- 60

ARI* CAPACITY RATINGS


UNIT 50ZPA
(SERIES)
024
030
036
042
049
048
060

NOMINAL TONS

STANDARD CFM

2.0
2.5
3.0
3.5
4.0
4.0
5.0

800
1000
1200
1400
1600
1600
1900

NET COOLING CAPACITIES


AT 95F (35C) (Btuh)
23,000
28,600
35,000
40,000
46,000
44,500
52,000

SOUND
RATINGS} (dBA)
72
72
75
77
77
77
80

SEER**
13.0
13.2
13.2
13.2
13.2
13.2
13.0

* Air Conditioning & Refrigeration Institute.


{ Rated in accordance with U.S. Government DOE Department of Energy test procedures and/or ARI Standards 210/240.
} Rated in accordance with ARI Standard 270.
**All units have factory ---installed time ---delay relay.
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat.
2. Cooling Standard: 80F (27C) db, 67F (19C) wb indoor entering air temperature and 95F (35C) db outdoor entering---air temperature.

50ZPA

LEGEND
dBADecibels --- A weighted
dbDry Bulb
wbWet Bulb
SEERSeasonal Energy Efficiency Ratio

ISO 9001:2000

REGISTERED

Complies with 2001 requirements


of ASHRAE Standards 90.1.

PHYSICAL DATA
UNIT SIZE
NOMINAL CAPACITY (ton)
SHIPPING WEIGHT (lb.)
(kg)
Compressor
Refrigerant (R-- 22) Quantity (lb)
(kg)
REFRIGERANT METERING DEVICE
Orifice ID (in.)
CONDENSER COIL
RowsFins/in.
Face Area (sq. ft.)
CONDENSER FAN

221
11.1
Propeller

Nominal Cfm
Diameter (in.)
(mm)
Motor HP (RPM)

2600
20
508
1/8 (825)

2600
20
508
1/8 (825)

317
4.3

417
4.9

800
10 x 8
254 x 203.2
1/2 (1050)

1000
10 x 8
254 x 203.2
1/2 (1050)

EVAPORATOR COIL
RowsFins/in.
Face Area (sq. ft.)
Evaporator Blower
Nominal Airflow (Cfm)
Size (in.)
(mm)
Motor HP (RPM)
CONNECTING DUCT SIZES
Supply Air (in.)
(mm)
Return Air (in.)
(mm)
Return -- Air Filters Throwaway* (in.)
(mm)

024
2
298
135
6.8
3.0
0.067

030
2--- 1/2
329
149

036
042
049
3
3--- 1/2
4
382
394
386
173
179
175
Scroll
9.5
9.5
11.1
10.0
4.3
4.3
5.0
4.5
AccuRatert
0.067
0.082
0.086

Copper Tubes, Aluminum Plate Fins


221
221
221
221
12.7
15.8
15.8
13.3
3200
3200
3200
20
20
20
508
508
508
1/4 (1100)
1/4 (1100)
1/4 (1100)
Copper Tubes, Aluminum Plate Fins
417
417
417
4.9
6.1
4.9

048
060
4
5
389
438
176
199
Ultra Tech Scroll
10.7
12.5
4.9
5.7
TXV

221
13.3

221
15.8

3200
20
508
1/4 (1100)

3300
20
508
1/2 (1100)

417
4.9

417
6.1

1600
11 x 10
279.4 x 254
1 (1050)

1875
11 x 10
279.4 x 254
1 (1050)

Direct Drive
1200
11 x 9
279.4 x 228.6
3/4 (1050)

24 x 24
610 x 610

1400
11 x 9
279.4 x 228.6
3/4 (1050)
Round
14
355.6
14
355.6

1600
11 x 10
279.4 x 254
1 (1050)

30 x 30
762 x 762

*Required filter sizes shown are based on the ARI (Air Conditioning and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway type or 450
ft/min for high capacity type. Recommended filters are 1 ---in. (25.4 mm) thick.

ACCESSORIES

50ZPA

Corporate Thermostat These provide cooling control for unit.


Autochangeover and manual changeover types are available.
The MotorMaster II Low Ambient Kit Kit permits
operation down to 0F (--17.8C). Use when mechanical cooling is
required when outdoor air temperature is between 40F (4.4C)
and 0F (--17.8C).
Crankcase Heater Warms crankcase oil to reduce refrigerant
migration and ensure proper compressor lubrication.
Recommended for low ambient or commercial applications.
Solid--State Time Guard Device Package Consists of a
control to be field--wired into the unit controls, and provides a
5--minute delay in compressor operation between cooling cycles.
Prevents compressor short cycling when rapid compressor cycles
may be a problem.
Controls Upgrade Kit Contains high-- and low--pressure
switches to protect the unit from running at unsuitable pressures.
Provides additional safety features when needed.

Outdoor Thermostat Accessory provides control when


outdoor--air temperature falls below set point. Helps to bring
second stage of 2--stage electric heater on line.
Electric Heaters ranging from 5.0 to 20.0 kW provide heat in the
unit when required. Each package has a heater module that mounts
on the blower inlet; mounting this module requires removal of the
blower assembly and attachment of the module to the blower
standoffs provided. Each package also includes an associated
heater control package that must be mounted in the unit control
box. Integral harnesses provided with both the heater module and
control package allow connection of the two components via
in--line plugs. Approved heaters could be with or without circuit
breakers and provide the ability to supply power to the entire unit
from a single circuit.

Accessory Electric Heaters


USED WITH SIZES

CATALOG
ORDERING NO.

NOMINAL
CAPACITY
(kW)

CPHEATER096A00

3.8 / 5.0

No

CPHEATER098A00

5.6 / 7.5

No

CPHEATER100A00

7.5 / 10.0

No

CPHEATER101A00

7.5 / 10.0

Yes

CPHEATER102A00

11.3 / 15.0

Yes

CPHEATER103A00

15.0 / 20.0

Yes

CIRCUIT
BREAKER
(Yes/No)

STAGES

024

030

036

042

049

048

060

ELECTRIC HEATERS (208/230 -- SINGLE PHASE-- 60Hz)

ELECTRIC HEATERS (208/230 -- THREE PHASE-- 60Hz)


CPHEATER115A00

3.8/5

No

CPHEATER116A00

7.5/10

No

CPHEATER118A00

11.3/15

No

CPHEATER120A00

15.0/20

Yes

X=Approved combination

Multiplication Factors
HEATER kW RATING
240

VOLTAGE DISTRIBUTION
200
208
230
240

Example: 15.0 kW (at 240v) heater on 208v


= 15.0 (.75 mult factor)
= 11.25 capacity at 208v

MULTIPLICATION FACTOR
.69
.75
.92
1.00

50ZPA

DIMENSIONAL DRAWINGS 50ZPA024--060

A08322

SELECTION PROCEDURE

50ZPA

A. DETERMINE
COOLING
AND
HEATING
REQUIREMENTS AT DESIGN CONDITIONS.
Given:
Required Cooling Capacity (TC) . . . . . . . . . . 34,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 25,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . . . 15,000 Btuh
Outdoor Entering--Air Temperature . . . . . . . . 95F (35C)
Indoor Entering--Air Temperature . . . 80F edb (26.7C);
67F (19.4C) ewb
Indoor--Air Quantity . . . . . . . . . . . . . . . . . . . . . . 1200 cfm
External Static Pressure . . . . . . . . . . . . . . . . . 0.20 IN. W.C.
Electrical Characteristics (V--Ph--Hz) . . . . . . . . . 230--1--60
B. SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY.
Enter Cooling Capacities table at condenser entering temperature
of 95F (35C), indoor air entering at 1200 cfm and 67F
(19.4C) ewb. The 50ZPA036 unit provides a total cooling
capacity of 35,000 Btuh and a sensible heat capacity of 25,200
Btuh.
For indoor--air temperature other than 80F (26.7C) edb,
calculate sensible heat capacity correction, as required, using the
formula found following the Cooling Capacities tables.
NOTE: Unit ratings are net capacities.

C. SELECT ELECTRIC HEAT.


The required heating capacity is 15,000 Btuh (given).
Determine the electric heat capacity in kW.
15,000 Btuh
3414 Btuh/kW

= 3.8 kW of heat required

Enter the Accessory Electric Heater table on page 4 for 208/230,


single--phase, 50ZPA036 unit. The 5--kW heater at 240v most
closely satisfies the heating required. To calculate kW at 230 V,
multiply the heater kW by multiplication factor 0.92 found in the
Multiplication Factors table on page 4.
5 kW x 0.92 = 4.6 kW
4.6 kW x 3414 Btuh/kW = 15,704 Btuh
D. DETERMINE
FAN
SPEED
AND
POWER
REQUIREMENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total static
pressure required. From the given, Filter Pressure Drop table, the
Accessory Electric Heat Pressure Drop table, and the Wet Coil
Pressure Drop table, find:
External static pressure
0.20 IN. W.C.
Filter
0.10 IN. W.C.
Electric Heat
0.13 IN. W.C.
Wet Coil
0.09 IN. W.C.
Total static pressure
0.52 IN. W.C.
Enter the table for Dry Coil Air Delivery Horizontal Discharge.
At 0.5 IN. W.C. external static pressure and high speed, the motor
delivers 1297 cfm. Interpolating for 0.52 IN. W.C. delivers 1276
cfm, which satisfies the job requirements.

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

19.86
20.44
16.50
17.20
13.85
20.72
20.96
17.77
18.54
14.60
21.48
21.55
17.26
17.93
12.33

1.7
1.7
1.7
1.7
1.7
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
1.9

26.73
27.76
28.46
30.79
33.42
27.84
28.43
29.08
31.38
33.81
28.81
28.98
29.54
31.80
34.04

26.73
25.54
21.06
21.86
17.38
27.84
27.29
22.10
22.91
17.92
28.81
28.98
23.34
24.17
18.38

2.1
2.1
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.3
2.3
2.3
2.3
2.3

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

19.86
20.44
20.88
22.63
24.74
20.72
20.96
21.41
23.18
25.18
21.48
21.55
21.85
23.59
24.18

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

See Legend and Notes on page 11.

1125 / 0.10

1000 / 0.09

875 / 0.08

CFM / BF

EWB F
(C)

EVAPORATOR AIR

50ZPA030

900 / 0.11

800 / 0.10

700 / 0.08

CFM / BF

EWB F
(C)

EVAPORATOR AIR

50ZPA024

Cooling Capacities

PERFORMANCE DATA

19.13
19.51
16.14
16.82
13.63
19.94
19.81
17.35
17.92
14.17
20.64
20.64
16.83
17.58
13.64

1.9
1.9
1.9
1.9
1.9
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.1

25.73
26.46
27.06
29.39
32.32
26.76
27.04
27.58
29.98
32.79
27.67
27.67
28.05
30.42
33.09

25.73
24.87
20.30
21.16
17.13
26.76
26.50
21.51
22.49
17.71
27.67
27.67
22.72
23.73
18.20

2.3
2.3
2.3
2.3
2.3
2.4
2.4
2.4
2.4
2.4
2.5
2.5
2.5
2.5
2.5

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens

19.13
19.51
19.93
21.56
23.91
19.94
20.01
20.41
22.12
24.43
20.64
20.64
20.78
22.54
24.80

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens
18.37
18.57
15.74
16.23
13.01
19.14
19.14
16.87
17.43
13.78
19.80
19.80
16.38
17.09
13.31

2.1
2.1
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.3
2.3

17.54
17.57
17.90
19.45
21.68
18.28
18.27
18.30
19.88
22.19
18.90
18.90
18.61
20.20
22.58

17.54
17.57
15.22
15.75
12.57
18.28
18.27
16.29
16.90
13.31
18.90
18.90
15.82
16.56
12.87

2.3
2.3
2.3
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.5
2.5
2.5
2.5
2.5

24.73
25.21
25.78
28.01
31.00
25.72
25.77
26.24
28.60
31.51
26.57
26.56
26.62
28.97
31.86

24.73
24.20
19.59
20.45
16.43
25.72
25.77
20.99
22.02
17.33
26.57
26.56
22.09
23.18
17.84

2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.7
2.7
2.7
2.7
2.7

23.67
23.89
24.42
26.53
29.60
24.62
24.61
24.85
27.07
30.08
25.40
25.40
25.18
27.45
30.42

23.67
23.65
19.05
19.90
15.98
24.62
24.61
20.38
21.39
16.84
25.40
25.40
21.40
22.51
17.64

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.9
2.9
2.9
2.9
2.9
3.0
3.0

16.62
16.62
14.56
15.35
12.04
17.33
17.33
15.73
16.42
12.93
17.92
17.92
15.29
16.11
12.32

2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.6
2.7
2.7
2.7
2.7
2.7
2.8

22.53
22.53
22.95
25.02
28.06
23.42
23.42
23.34
25.44
28.59
24.19
24.18
23.64
25.78
28.93

22.53
22.53
18.36
19.27
15.43
23.42
23.42
19.61
20.61
16.30
24.19
24.18
20.80
21.91
17.07

3.0
3.0
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
3.3

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

16.62
16.62
16.73
18.27
20.41
17.33
17.33
17.10
18.66
20.85
17.92
17.92
17.38
18.95
21.24

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

18.37
18.57
18.96
20.54
22.83
19.14
19.14
19.39
23.00
23.36
19.80
19.80
19.73
21.36
23.77

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

15.81
15.67
14.07
14.88
11.59
16.48
16.16
15.22
15.89
12.51
17.03
17.01
14.80
15.65
12.32

2.8
2.8
2.8
2.8
2.9
2.9
2.9
2.9
2.9
2.9
3.0
3.0
3.0
3.0
3.0

21.48
21.22
21.57
23.58
26.72
22.32
22.17
21.91
23.96
27.29
23.04
22.98
22.17
24.28
27.65

21.48
21.78
17.68
18.62
14.95
22.32
22.45
18.98
20.03
15.89
23.04
22.98
20.17
21.35
16.74

3.3
3.3
3.3
3.3
3.4
3.4
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.6

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

15.81
15.67
15.69
17.18
19.33
16.48
16.42
16.02
17.53
19.77
17.03
17.01
16.26
17.79
20.51

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA042

1350 / 0.10

1200 / 0.08

1050 / 0.07

CFM / BF

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

32.66
29.48
23.88
24.95
20.04
34.06
31.56
25.47
26.25
21.30
35.24
35.04
26.97
27.84
22.07

2.6
2.6
2.6
2.7
2.6
2.7
2.7
2.7
2.7
2.8
2.7
2.8
2.8
2.8
2.8

37.90
38.80
40.20
40.90
43.70
37.70
40.30
39.60
43.60
43.90
37.60
40.10
40.20
42.50
44.70

37.90
38.41
28.94
29.04
22.29
37.70
39.90
30.10
31.83
23.27
37.60
38.10
31.36
32.73
24.59

3.0
3.3
3.3
3.2
3.6
3.1
3.3
3.3
3.3
3.3
3.4
3.4
3.5
3.4
3.4

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

32.66
33.89
34.61
37.24
40.89
34.06
34.68
35.37
38.04
41.76
35.24
35.39
35.96
38.66
42.44

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

See Legend and Notes on page 11.

1575 / 0.14

1400 / 0.12

1225 / 0.11

CFM / BF

EWB F
(C)

EVAPORATOR AIR

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

EWB F
(C)

EVAPORATOR AIR

50ZPA036

COOLING CAPACITIES (CONT)

31.63
28.67
23.28
24.35
19.68
32.95
30.66
24.79
25.95
20.48
34.08
34.08
26.23
27.47
21.61

2.9
2.9
2.9
2.9
2.9
2.9
3.0
3.0
3.0
3.0
3.0
3.1
3.1
3.1
3.1

36.10
36.70
38.50
40.10
42.70
37.20
38.60
39.00
40.60
43.60
37.40
39.80
39.60
42.20
44.60

36.10
37.43
31.19
31.28
24.34
37.20
38.21
30.03
30.86
23.98
37.40
39.40
32.08
33.34
25.42

3.4
3.4
3.4
3.4
3.6
3.4
3.5
3.5
3.6
3.5
3.6
3.6
3.6
3.6
3.6

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens

31.63
32.58
33.26
35.81
39.35
32.95
33.33
33.96
36.55
40.15
34.08
34.08
34.51
37.12
40.78

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens
30.54
28.09
22.63
23.68
18.87
31.80
31.62
24.38
25.20
20.01
32.87
32.87
25.74
26.64
21.09

3.2
3.2
3.2
3.2
3.2
3.3
3.2
3.2
3.3
3.3
3.4
3.3
3.3
3.4
3.4

29.41
29.80
30.41
32.78
36.07
30.60
30.60
30.99
33.39
36.75
31.61
31.61
31.45
33.86
37.27

29.41
27.42
22.20
22.95
18.40
30.60
30.60
23.55
24.71
19.48
31.61
31.61
25.16
26.07
20.50

3.5
3.5
3.5
3.5
3.5
3.6
3.5
3.5
3.6
3.6
3.7
3.6
3.6
3.7
3.7

35.10
35.90
36.70
39.30
42.20
36.60
37.20
37.40
40.00
42.40
37.00
38.10
36.50
40.50
42.80

35.10
35.90
27.53
28.30
22.37
36.60
37.20
29.55
30.40
23.32
37.00
37.72
30.66
32.81
24.82

3.7
3.7
3.7
3.7
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.9
3.9

32.80
33.90
34.30
36.80
39.30
34.80
35.20
34.90
37.40
39.70
33.90
34.10
33.40
36.00
39.90

32.80
33.56
26.41
27.23
21.22
34.80
35.20
28.27
29.55
22.23
33.90
33.76
28.72
30.24
22.74

4.1
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.1
4.1
4.1
4.1
4.1
4.1
4.2

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

30.54
31.21
31.87
34.32
37.74
31.80
31.94
32.51
35.00
38.48
32.87
32.87
33.00
35.52
39.06

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Total
Capacity
Capacity
Total
System
MBtuh
MBtuh
System
KW
Total
Sens
Total
Sens
KW
28.22
28.07
21.38
22.44
17.85
29.34
29.33
22.95
23.78
18.87
30.28
30.28
24.46
25.39
19.83

3.9
3.8
3.8
3.9
3.9
4.0
3.9
3.9
3.9
3.9
4.1
4.0
3.9
4.0
4.0

31.30
32.20
32.30
34.80
36.00
33.90
34.10
33.40
36.00
39.90
32.10
32.70
32.70
32.70
36.60

31.30
32.20
25.52
26.45
19.08
33.90
33.76
28.72
30.24
22.74
32.10
32.37
29.80
30.03
22.33

4.5
4.3
4.3
4.4
4.3
4.6
4.7
4.4
4.4
4.5
4.8
4.8
4.8
4.8
4.9

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

28.22
28.35
28.89
31.16
34.33
29.34
29.33
29.42
31.71
34.94
30.28
30.28
29.83
32.14
35.41

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA

27.11
27.71
20.75
21.81
17.31
28.16
28.77
22.32
23.17
18.26
29.04
29.09
23.83
24.78
19.27

4.3
4.2
4.2
4.2
4.2
4.4
4.2
4.3
4.3
0.3
4.5
4.3
4.3
4.3
4.4

28.00
28.60
27.40
31.30
33.00
28.20
28.80
27.60
30.00
32.90
29.00
29.70
27.90
30.60
32.80

28.00
28.50
24.70
25.10
19.50
28.20
28.60
24.90
26.10
19.40
29.00
29.50
27.20
28.00
18.10

5.0
4.9
4.9
4.8
5.1
4.7
4.7
4.7
4.8
5.1
4.9
4.9
4.8
4.8
4.9

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

27.11
26.97
27.46
29.64
32.69
28.16
27.99
27.93
30.13
33.24
29.04
29.00
28.30
30.51
33.65

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

43.90
45.10
46.00
49.52
54.55
45.87
46.26
47.01
50.59
55.71
47.54
47.54
47.79
51.42
56.60

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

EWB F
(C)

3.05
3.06
3.07
3.11
3.16
3.12
3.12
3.13
3.17
3.22
3.19
3.19
3.19
3.23
3.28

41.83
43.10
43.99
46.97
50.32
43.63
44.04
44.78
47.65
50.84
45.02
45.01
45.32
48.08
51.19

41.83
39.65
32.55
33.35
26.17
43.63
42.72
34.48
35.26
27.45
45.02
45.01
36.26
37.02
28.15

3.6
3.6
3.6
3.6
3.6
3.7
3.7
3.7
3.7
3.7
3.8
3.8
3.8
3.8
3.8

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

See Legend and Notes on page 11.

1800 / 0.09

1600 / 0.08

1400 / 0.07

CFM / BF

EVAPORATOR AIR

43.90
43.19
35.30
36.49
29.74
45.87
46.57
37.73
39.08
31.39
47.54
47.54
40.09
41.59
32.98

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA048 High Capacity

1800 / 0.09

1600 / 0.08

1400 / 0.07

CFM / BF

EWB F
(C)

EVAPORATOR AIR

50ZPA049

COOLING CAPACITIES (CONT)

42.26
41.55
33.84
35.02
28.41
44.13
43.93
36.20
37.54
30.01
45.70
45.70
38.50
39.99
31.56

3.52
3.53
3.54
3.58
3.64
3.59
3.59
3.60
3.65
3.71
3.66
3.66
3.66
3.71
3.77

40.45
41.39
42.33
45.55
49.32
42.24
42.38
43.15
46.31
49.90
43.69
43.69
43.74
46.83
50.28

40.45
38.91
31.75
32.80
26.14
42.24
41.96
33.66
35.20
27.45
43.69
43.69
35.87
37.00
28.16

3.9
3.9
3.9
4.0
4.0
4.0
4.0
4.0
4.0
4.1
4.1
4.1
4.1
4.1
4.2

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens

42.26
43.11
43.94
47.34
52.19
44.13
44.23
44.87
48.32
53.26
45.70
45.70
45.59
49.08
54.07

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens
40.57
39.90
32.37
33.55
27.08
42.33
42.32
34.68
36.00
28.64
43.81
43.81
36.91
38.38
30.15

4.04
4.05
4.06
4.11
4.18
4.13
4.13
4.13
4.18
4.25
4.20
4.20
4.19
4.25
4.31

38.82
39.01
39.67
42.81
47.31
40.47
40.47
40.43
43.62
48.18
41.86
41.86
41.03
44.25
48.84

38.82
38.22
30.92
32.08
25.76
40.47
40.47
33.15
34.47
27.28
41.86
41.86
35.32
36.78
28.75

4.64
4.64
4.65
4.71
4.79
4.73
4.73
4.72
4.78
4.86
4.81
4.81
4.79
4.85
4.93

38.95
39.50
40.42
43.72
47.83
40.68
40.68
41.22
44.50
48.50
42.12
42.11
41.81
45.06
48.94

38.95
37.92
30.72
31.92
25.83
40.68
40.68
32.98
34.27
27.16
42.12
42.11
35.12
36.50
28.39

4.3
4.3
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.5
4.5
4.5
4.5
4.5

37.33
37.48
38.31
41.63
45.99
38.99
38.98
39.05
42.39
46.66
40.37
40.37
39.62
42.94
47.15

37.33
37.11
29.88
31.22
24.83
38.99
38.98
32.02
33.49
26.60
40.37
40.37
34.07
35.64
27.82

4.7
4.7
4.7
4.7
4.7
4.8
4.8
4.8
4.8
4.9
4.9
4.9
4.9
4.9
4.9

37.02
37.02
29.46
30.62
24.46
38.57
38.57
31.64
32.94
25.92
39.86
39.86
33.73
35.19
27.35

5.30
5.30
5.31
5.38
5.46
5.40
5.40
5.39
5.45
5.54
5.48
5.48
5.46
5.52
5.61

35.59
35.59
36.03
39.31
43.84
37.17
37.16
36.71
40.04
44.51
38.49
38.48
37.24
40.64
44.96

35.59
35.59
28.82
30.27
24.11
37.17
37.16
30.84
32.43
25.82
38.49
38.48
33.14
34.54
26.98

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.3
5.3
5.3
5.3
5.3
5.4
5.4

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

37.02
37.02
37.45
40.47
44.78
38.57
38.57
38.14
41.19
45.56
39.86
39.86
38.67
41.75
46.14

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Total
Capacity
Capacity
Total
System
MBtuh
MBtuh
System
KW
Total
Sens
Total
Sens
KW

40.57
41.07
41.83
45.11
49.78
42.33
42.32
42.68
46.00
50.75
43.81
43.81
43.33
46.69
51.48

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

35.17
35.17
28.02
29.16
23.16
36.61
36.60
30.13
31.42
24.58
37.80
37.80
32.15
33.60
25.97

6.04
6.04
6.03
6.11
6.21
6.14
6.14
6.11
6.19
6.29
6.23
6.23
6.19
6.27
6.36

35.30
35.40
35.30
38.10
42.00
36.80
36.80
36.00
38.90
42.80
38.00
38.10
36.60
39.40
43.30

34.50
34.50
28.10
29.40
23.00
35.90
36.00
30.30
31.80
24.50
37.10
37.20
32.40
34.10
26.00

5.6
5.6
5.6
5.7
5.7
5.7
5.7
5.7
5.7
5.8
5.8
5.8
5.8
5.8
5.9

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

35.17
35.17
35.17
38.06
42.20
36.61
36.60
35.79
38.71
42.88
37.80
37.80
36.27
39.22
43.39

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

EWB F
(C)

29.40
30.30
30.80
33.10
36.30
30.90
31.10
31.50
33.90
37.10
32.10
32.20
32.20
34.50
37.70

Total

10

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

EWB F
(C)

2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.3
2.3
2.3
2.3
2.3
2.4

KW

51.50
52.10
52.80
56.70
62.00
52.70
52.80
53.40
57.20
62.60
55.50
55.50
54.80
58.60
64.00

48.93
47.93
38.54
40.26
31.62
50.07
49.63
40.05
41.76
32.55
52.73
52.73
43.84
45.71
35.20

4.30
4.30
4.30
4.40
4.50
4.40
4.40
4.40
4.50
4.60
4.50
4.50
4.50
4.60
4.70

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens

See Legend and Notes on page 11.

2000 / 0.09

1875 / 0.08

1750 / 0.07

CFM / BF

EVAPORATOR AIR

28.70
27.40
22.20
23.00
18.60
30.20
29.80
23.90
24.90
19.80
31.40
31.40
25.60
26.70
20.90

Sens

75 (24)
Total
Capacity
System
MBtuh

50ZPA060 High Capacity

1250 / 0.08

1100 / 0.07

950 / 0.06

CFM / BF

EVAPORATOR AIR

50ZPA048 Low Capacity

COOLING CAPACITIES (CONT)

10

28.00
26.90
21.70
22.60
18.20
29.30
29.30
23.50
24.40
19.30
30.50
30.50
25.10
26.20
20.50

Sens
2.4
2.4
2.4
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
2.7

KW

49.70
49.90
50.50
54.10
59.20
50.70
50.80
51.00
54.60
59.70
53.30
53.40
52.20
55.90
60.90

47.22
46.91
37.37
38.95
30.78
48.17
48.26
38.76
40.40
31.64
52.73
52.73
43.84
45.71
35.20

4.70
4.70
4.70
4.80
4.90
4.80
4.80
4.80
4.90
5.00
5.00
5.00
4.90
5.00
5.10

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens

28.60
29.30
29.80
32.00
35.10
30.00
30.20
30.50
32.70
35.80
31.20
31.30
31.00
33.30
36.40

Total

85 (29)
Total
Capacity
System
MBtuh

27.10
26.40
21.30
22.10
17.70
28.40
28.50
23.00
23.90
18.90
29.50
29.60
24.60
25.70
20.00

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.9
2.9
2.9
2.9
2.9
3.0
3.0

26.90
27.10
27.50
29.60
32.50
28.20
28.20
28.20
30.20
33.10
29.20
29.30
28.70
30.70
33.60

26.30
25.90
20.80
21.60
17.20
27.50
27.50
22.50
23.40
18.40
28.50
28.60
24.10
25.20
19.50

3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
3.2
3.3
3.3
3.3
3.3
3.3
3.3

47.80
47.80
48.10
51.50
56.30
48.70
48.80
48.60
52.00
56.80
51.20
51.20
49.70
53.10
57.90

45.41
45.41
36.56
38.11
29.84
46.27
46.36
37.91
39.52
30.67
48.64
48.64
41.75
44.07
33.58

5.20
5.20
5.20
5.30
5.40
5.30
5.30
5.30
5.40
5.50
5.40
5.40
5.40
5.50
5.60

45.80
45.90
45.80
49.00
53.50
46.70
46.80
46.20
49.40
53.90
48.90
49.00
47.20
50.40
54.80

43.51
43.61
35.72
37.24
28.89
44.37
44.46
36.96
38.53
29.65
46.46
46.55
41.06
42.84
32.33

5.70
5.70
5.70
5.80
5.90
5.80
5.80
5.80
5.90
6.00
5.90
5.90
5.90
6.00
6.10

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

27.80
28.20
28.70
30.80
33.80
29.10
29.20
29.40
31.50
34.50
30.20
30.30
29.90
32.00
35.10

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens
25.30
25.30
20.30
21.10
16.70
26.50
26.50
22.00
22.90
17.90
27.50
27.50
23.60
24.70
19.00

3.5
3.5
3.5
3.5
3.6
3.6
3.6
3.6
3.6
3.7
3.7
3.7
3.7
3.7
3.7

43.80
43.80
43.40
46.30
50.40
44.60
44.70
43.70
46.70
50.60
46.60
46.70
44.70
47.60
51.40

41.61
41.61
34.72
36.11
27.72
42.37
42.47
35.83
37.36
28.34
44.27
44.37
39.78
41.89
31.35

6.30
6.30
6.30
6.30
6.40
6.40
6.40
6.40
6.50
6.50
6.50
6.50
6.50
6.50
6.60

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

25.90
26.00
26.30
28.30
31.10
27.10
27.20
26.90
28.90
31.70
28.10
28.20
27.40
29.40
32.10

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA

24.30
24.30
19.70
20.60
16.20
25.40
25.40
21.40
22.40
17.30
26.30
26.30
23.00
24.10
18.50

3.9
3.9
3.9
4.0
4.0
4.0
4.0
4.0
4.0
4.1
4.1
4.1
4.1
4.1
4.2

41.60
41.70
40.80
43.60
47.90
42.40
42.40
41.20
44.00
48.10
44.20
44.30
42.00
44.70
48.40

39.50
39.60
33.50
35.00
26.80
40.20
40.30
34.90
36.50
27.70
42.00
42.00
38.70
40.60
30.30

6.90
6.90
6.90
6.90
7.10
7.00
7.00
7.00
7.00
7.10
7.10
7.10
7.10
7.10
7.20

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

24.90
24.90
25.00
26.90
29.60
26.00
26.10
25.60
27.50
30.10
26.90
27.00
26.00
27.90
30.50

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

11

57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)
57 (14)
62 (17)
63* (17)
67 (19)
72 (22)

EWB F
(C)

34.10
35.10
35.80
38.70
42.60
35.70
36.10
36.60
39.50
43.40
37.40
37.50
37.50
40.40
44.20

33.90
32.30
25.90
27.00
21.60
35.40
34.80
27.70
28.90
22.80
37.10
37.20
30.00
31.40
24.30

2.70
2.60
2.60
2.60
2.60
2.70
2.70
2.70
2.70
2.70
2.70
2.80
2.80
2.80
2.80

75 (24)
Capacity
Total
MBtuh
System
KW
Total
Sens
33.10
33.80
34.40
37.20
41.00
34.50
34.70
35.20
38.00
41.70
36.20
36.20
36.00
38.80
42.50

32.80
31.70
25.30
26.40
21.00
34.30
34.10
27.10
28.30
22.20
35.90
36.00
29.40
30.80
23.70

3.00
2.90
2.90
2.90
2.90
3.00
3.00
3.00
3.00
3.00
3.00
3.10
3.10
3.10
3.10

85 (29)
Capacity
Total
MBtuh
System
KW
Total
Sens
32.00
32.40
33.00
35.70
39.40
33.40
33.40
33.70
36.40
40.10
34.90
35.00
34.50
37.20
40.70

31.70
31.00
24.70
25.80
20.40
33.10
33.10
26.50
27.70
21.60
34.60
34.70
28.70
30.10
23.10

3.30
3.20
3.20
3.20
3.20
3.30
3.30
3.30
3.30
3.30
3.30
3.40
3.40
3.40
3.40

30.90
31.10
31.60
34.20
37.70
32.20
32.20
32.30
34.80
38.10
33.70
33.70
33.00
35.50
39.10

30.60
30.40
24.10
25.20
19.80
31.90
32.00
25.80
27.00
20.90
33.40
33.70
28.10
29.50
22.60

tlwb

air leaving evaporator coil (hlwb)

Wet--bulb temperature corresponding to enthalpy

1.10 x cfm

3.70
3.60
3.60
3.60
3.60
3.70
3.70
3.70
3.70
3.70
3.70
3.70
3.70
3.80
3.80

29.80
29.80
30.20
32.70
36.20
31.00
31.10
30.80
33.30
36.70
32.40
32.40
31.50
33.90
37.10

29.50
29.60
23.50
24.60
19.30
30.80
30.80
25.20
26.40
20.40
32.10
32.20
27.50
28.80
21.80

4.10
4.00
4.00
4.00
4.00
4.10
4.10
4.10
4.10
4.10
4.10
4.20
4.20
4.20
4.20

115 (46)
Capacity
Total
MBtuh
System
KW
Total
Sens

50ZPA

CONDENSER ENTERING AIR TEMPERATURES F (C)


95 (35)
105 (41)
Capacity
Capacity
Total
Total
MBtuh
MBtuh
System
System
KW
KW
Total
Sens
Total
Sens

* At 75F entering dry bulb --- Tennessee Valley Authority (TVA) rating conditions; all others at 80F dry bulb.
LEGEND
BF Bypass Factor
total capacity (Btuh)
hlwb = hewb -Ewb Entering Wet---Bulb
4.5 x cfm
kW Total Unit Power Input
SHC Sensible Heat Capacity (1000 Btuh)
Where: hewb = Enthalpy of air entering evaporator coil3. The SHC is
TC Total Capacity (1000 Btuh) (net)
based on 80 F (26.7C) edb temperature of air entering indoor coil.
NOTES:
Below 80 F (26.7C) edb, subtract (corr factor x cfm) from SHC.
1. Direct interpolation is permissible. Do not extrapolate.
Above 80 F (26.7C) edb, add (corr factor x cfm) to SHC.
2. The following formulas may be used:
Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
Sensible capacity (Btuh)
tldb = tedb -

1500 / 0.07

1300 / 0.06

1150 / 0.05

CFM / BF

EVAPORATOR AIR

50ZPA060 Low Capacity

COOLING CAPACITIES (CONT)

28.70
28.70
28.90
31.10
35.10
29.90
29.90
29.40
31.80
35.30
31.00
31.40
30.00
32.10
35.10

28.50
28.50
22.90
24.00
18.90
29.60
29.70
24.60
25.80
19.90
30.70
31.20
26.90
28.10
21.20

4.50
4.50
4.50
4.50
4.50
4.60
4.60
4.50
4.60
4.60
4.60
4.60
4.60
4.60
4.70

125 (52)
Capacity
Total
MBtuh
System
KW
Total
Sens

Wet Coil Pressure Drop (IN. W.C.)


STANDARD CFM (S.C.F.M.)
UNIT
SIZE
024
030
036
042
049
048
060

600

700

800

900

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

0.027

0.034
0.036

0.040
0.042

0.047
0.050
0.050

0.053
0.055
0.055
0.042

0.063
0.063
0.049

0.072
0.072
0.052
0.072
0.072

0.081
0.081
0.059
0.081
0.081

0.090
0.065
0.090
0.090

0.097
0.071
0.097
0.097
0.071

0.078
0.108
0.108
0.078

0.085
0.120
0.120
0.085

0.091
0.129
0.129
0.091

0.139
0.139
0.098

0.114

Filter Pressure Drop (IN. W.C.)


FILTER SIZE in.
(mm)
24 x 24
(609.6 x 609.6)
30 x 30
(762 x 762)

UNIT SIZE

50ZPA

024--036
042--060

024--036
042--060

600

700

800

CFM
900

1000

1100

1200

1300

0.06

0.07

0.08

0.08

0.09

0.09

0.09

0.10

0.11

0.08

CFM

FILTER SIZE in.


(mm)
24 x 24
(609.6 x 609.6)
30 x 30
(762 x 762)

UNIT SIZE

500

1400

1500

1600

1700

1800

1900

2000

2100

2200

2300

0.12

0.14

0.15

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.18

Accessory Electric Heat Pressure Drop (IN. W.C.)


HEATER kW
5-- 20

CFM
600

800

1000

1200

1400

1600

1800

2000

2200

0.06

0.08

0.10

0.13

0.15

0.18

0.20

0.23

0.25

12

UNIT
SIZE

SPEED
TAP
1

024
2
2
030
3
1
036
2
3
042
4
1
2
049
3
4
1
2
048
3
4
1
2
060
3
4

AIR
DELIVERY
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM
Watts
CFM

0.1

180
1344

269
1440

386
1680

386
1680

224
1334

608
1931
737
2093

0.2
99
848

155
1108

166
1215

283
1404

204
1129

398
1652
440
1745
204
1129

398
1652
440
1745
235
1288

626
1900
755
2061

0.3
100
793

146
995

179
1172

305
1369
418
1572
209
1087
233
1164
409
1625
448
1717
209
1087
233
1164
409
1625
448
1717
251
1259
286
1333
643
1878
770
2028

208 VOLT HORIZONTAL DISCHARGE


External Static Pressure (IN. W.C.)
0.4
0.5
0.6
0.7
118
130
142

757
698
632

222
233

970
918
157
170

951
884

261
275

1117
1053
191
204
216

1136
1095
1051

261
276
290
301
1343
1304
1272
1234
321
336
349
360
1333
1301
1273
1239
432
450
465
480
1543
1504
1475
1441
216
229
236
249
1027
994
932
881
245
254
266
276
1122
1066
1025
954
418
425
435
438
1583
1555
1515
1477
457
462
469
477
1684
1651
1612
1573
216
229
236
249
1027
994
932
881
245
254
266
276
1122
1066
1025
954
418
425
435
438
1583
1555
1515
1477
457
462
469
477
1684
1651
1612
1573
266
277
291
298
1224
1181
1157
1117
301
311
325
333
1296
1261
1232
1199
660
668
685
697
1844
1817
1789
1755
787
799
817
826
2001
1971
1934
1899

0.8

244
861

286
1014

316
1190

490
1418

289
906
441
1444
480
1537

289
906
441
1444
480
1537

344
1170

812
1850

0.9

257
795

291
980

329
1148

503
1380

451
1403
485
1508

451
1403
485
1508

370
1062

782
1757

1.0

260
729

315
877

342
1100

518
1332

486
1470

486
1470

*Air delivery values are based on operating voltage of 230v or dry coil, without filter or electric heater. Deduct wet coil, filter, and electric heater pressure drops to obtain
external static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows
below this point.
2. Dashes indicate portions of the table that are beyond the blower motor capacity or are not recommended.

13

50ZPA

Dry Coil Delivery*Horizontal Discharge (Deduct 10% for 208--Volt Operation)

50ZPA

TYPICAL WIRING SCHEMATIC208/230--1--60 50ZPA024--042 AND 049

A07912

14

50ZPA

TYPICAL WIRING SCHEMATIC208/230--1--60 50ZPA048 AND 060

A07896

15

50ZPA

TYPICAL THREE--PHASE UNIT ELECTRICAL DIAGRAM (SIZES 030--042 AND 049)

A07913

16

50ZPA

TYPICAL THREE--PHASE UNIT ELECTRICAL DIAGRAM (SIZES 048 AND 060)

A06337

17

50ZPA

TYPICAL FIELD WIRING

A05209

Single--Phase Accessory Electric Heater Wiring

A06327

Three--Phase Accessory Electric Heater Wiring

18

Electrical Data
NOMINAL
V--- PH --- HZ

VOLTAGE
RANGE
MIN
MAX

COMPRESSOR

OFM

IFM

RLA

LRA

FLA

FLA

024

208/230 ---1 ---60

187

253

10.9

54.0

0.9

4.1

030

208/230 ---1 ---60

187

253

13.5

72.5

0.9

4.1

030

208/230 ---3 ---60

187

253

9.0

63.0

0.9

4.1

036

208/230 ---1 ---60

187

253

16.0

88.0

1.4

6.0

036

208/230 ---3 ---60

187

253

10.7

77.0

1.4

6.0

042

208/230 ---1 ---60

187

253

17.9

104.0

1.4

6.0

042

208/230 ---3 ---60

187

253

12.4

88.0

1.4

6.0

049

208/230 ---1 ---60

187

253

19.2

97.0

1.4

7.6

049

208/230 ---3 ---60

187

253

12.7

88.0

1.4

7.6

048

208/230 ---1 ---60

187

253

21.5

116.0

1.4

7.6

048

208/230 ---3 ---60

187

253

13.3

91.0

1.4

7.6

060

208/230 ---1 ---60

187

253

24.1

118.0

3.0

7.6

060

208/230 ---3 ---60

187

253

17.0

123.0

3.0

7.6

* kW @ 208/240
** Circuit breaker

19

ELECTRIC HEAT
NOMINAL
FLA
kW *
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
11.3/15
54.1/62.5
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.4/36.1
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
11.3/15
54.1/62.5
15.0/20.0
72.1/83.3
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.4/36.1
15.0/20.0
41.4/47.9
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
11.3/15
54.1/62.5
15.0/20.0
72.1/83.3
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.4/36.1
15.0/20.0
41.4/47.9
---/ -----/ --3.8/5
18.1/20.8
5.6/7.5
27.1/31.3
7.5/10
36.1/41.7
11.3/15
54.2/62.5
15.0/20.0
72.2/83.3
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.3/36.1
14.9/19.9
41.5/47.9
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
11.3/15
54.1/62.5
15.0/20.0
72.1/83.3
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.4/36.1
15.0/20.0
41.4/47.9
---/ -----/ --3.8/5
18.0/20.8
5.6/7.5
27.0/31.3
7.5/10
36.1/41.7
11.3/15
54.1/62.5
15.0/20.0
72.1/83.3
---/ -----/ --3.8/5
10.4/12.0
7.5/10
20.8/24.1
11.3/15
31.4/36.1
15.0/20.0
41.4/47.9

POWER SUPPLY
MCA

MOCP **

18.6/18.6
27.6/31.1
38.9/44.3
50.3/57.3
21.8/21.8
27.6/31.1
38.9/44.3
50.3/57.3
72.8/83.3
16.3/16.3
18.1/20.1
31.1/35.3
44.4/50.3
27.4/27.4
30.0/33.5
41.3/46.6
52.6/59.6
75.1/85.6
97.6/111.6
20.8/20.8
20.5/22.5
33.5/37.6
46.8/52.6
59.3/67.4
29.8/29.8
30.0/33.5
41.3/46.6
52.6/59.6
75.1/85.6
97.6/111.6
23.0/23.0
23.0/23.0
33.5/37.6
46.8/52.6
59.3/67.4
33.0/33.0
33.0/33.5
43.3/48.6
54.6/61.6
77.2/87.6
99.8/113.7
24.9/24.9
24.9/24.9
35.6/39.6
48.6/54.6
61.4/69.3
35.9/35.9
35.9/35.9
43.3/48.6
54.6/61.6
77.1/87.6
99.6/113.6
25.6/25.6
25.6/25.6
35.5/39.6
48.8/54.6
61.3/69.4
40.7/40.7
40.7/40.7
43.3/48.6
54.6/61.6
77.1/87.6
99.6/113.6
31.9/31.9
31.9/31.9
35.5/39.6
48.8/54.6
61.3/69.4

25/25
30/35
40/45
60/60
30/30
30/35
40/45
60/60
80/90
25/25
25/25
35/40
45/60
40/40
40/40
45/50
60/60
80/90
100/125
30/30
30/30
35/40
50/60
60/70
40/40
40/40
45/50
60/60
80/90
100/125
35/35
35/35
35/40
50/60
60/70
50/50
50/50
50/50
60/70
80/90
100/125
35/35
35/35
40/40
50/60
70/70
50/50
50/50
50/50
60/70
80/90
100/125
35/35
35/35
40/40
50/60
70/70
60/60
60/60
60/60
60/70
80/90
100/125
45/45
45/45
45/45
50/60
70/70

50ZPA

UNIT

LEGEND
FLA
Full Load Amps
LRA
Locked Rotor Amps
MCA
-- Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps

EXAMPLE: Supply voltage is 230-3-60.


AB = 228 v
BC = 231 v
AC = 227 v

NO TES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NE C
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit break er.
2. Minimum wire size is based on 60o C copper wire. I f other than
60oC wire is used, or if length exceeds wire length in table,
determine siz e from NEC.
.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
average voltage
Heater capacity (kW) based on heater voltage of 208v & 240v.
If power distribution voltage to unit varies from rated heater
voltage, heater kW will vary accordingly.

Average Voltage =

Determine maximum deviation from average voltage.


(AB) 229 - 228 = 1 v
(BC) 231 - 229 = 2 v
(AC) 229 - 227 = 2 v
Maximum deviation is 2 v.
Determine percent of voltage imbalance.
2
229

% Voltage Imbalance = 100 x

= 0.8%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

50ZPA

228 + 231 + 227


3
686
=
3
= 229

OPERATING SEQUENCE
Cooling Operation (024 -- 042 and 049)

Heating Operation (024 -- 042 and 049)

With a call for cooling (Y/Y2), the indoor fan energizes


immediately whereas the contactor energizes after a 5 minute time
delay (in case of an initial start up) starting the compressor and the
outdoor fan motor. When the cooling demand is met, Y/Y2
de--energizes, shutting the compressor, indoor fan and the outdoor
fan.

With a call for heating (W2), the auxiliary or electric heat energizes
along with the indoor blower. In case of staged heating, W3 is
energized if the demand is not met. The highest airflow selected is
run while the electric heat is in operation. When heating demand is
met, W3 and W2 sequentially de--energize shutting the indoor fan
and the electric heater.

Cooling Operation (048 and 060)

Heating Operation (048 and 060)

These units utilize a 2--stage indoor thermostat. With a first stage


call for cooling (Y1), the indoor fan (low stage) energizes
immediately where as the contactor energizes after a 5 minute time
delay (in case of an initial start up) starting the compressor (low
stage) and the outdoor fan motor. If the low stage operation cannot
satisfy the cooling demand, the second stage cooling (Y2)
energizes switching the compressor into high stage cooling through
energizing an internal solenoid valve inside the scroll compressor
and switching the indoor fan into high stage. When second stage
cooling is satisfied, Y2 de--energizes switching the compressor and
the indoor fan into low stage cooling. When the low stage cooling
demand is met, Y1 de--energizes shutting the compressor, indoor
fan and the outdoor fan.

With a call for heating (W2), the auxiliary electric heater is


energized along with the indoor blower. If the demand is not met,
W3 is energized in case of staged heating. When heating demand is
satisfied, W3 and W2 sequentially de--energize along with the
indoor fan blower.

Continuous Fan
With the continuous indoor fan option selected on the thermostat,
G is continuously energized. In case of 024 -- 042 and 049 units,
the selected airflow setting is provided. In case of 048 and 060
units, the system runs low stage (Y1) airflow for continuous fan
operation.

20

TYPICAL INSTALLATION
INDOOR
THERMOSTAT

RETURN
AIR

FROM
POWER
SOURCE

50ZPA

TOP COVER

POWER AND
LOW-VOLTAGE
ENTRY
COMPOSITE
RUST-PROOF
BASEPAN
Power Wiring
Control Wiring

DISCONNECT
PER NEC
(UNIT AND
ELECTRIC
HEATER)

CONDENSATE
DRAIN
CONNECTION

Condenser Airflow
Evaporator Airflow
A08207

APPLICATION DATA
Condensate trap A 2--in. (51 mm) condensate trap must be field
supplied.
1 (25 mm) MIN.
TRAP
OUTLET
2 (51 mm) MIN.

A08001

Maximum cooling airflow To minimize the possibility of


condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm/ton.
Minimum cooling airflow The minimum cooling airflow is
350 cfm/ton.
Minimum cooling operating outdoor air temperature All
standard units have a minimum ambient operating temperature of
40F (4.4C). With accessory low ambient temperature kit, units
can operate at temperatures down to 0F (--17.8C).
Maximum operating outdoor air temperature Maximum
outdoor operating air temperature for cooling is 125F (51.7C).

21

ENGINEERS SPECIFICATION GUIDE


GENERAL
Furnish and install outdoor package, electrically controlled, air
conditioner utilizing a reciprocating compressor for cooling duty.
Unit shall discharge supply air horizontally or vertically as shown
on contract drawings.
Nominal unit electrical characteristics shall be ______ v, ______
ph, 60 Hz. The unit shall be capable of satisfactory operation
within voltage limits of ______ v to ______ v. Unit power wiring
shall enter unit cabinet at a single location.
Separate power supply shall not be required for electric heat.

50ZPA

COOLING CAPACITY

CONDENSER SECTION
Condenser fan shall be of the direct--driven propeller type with
aluminum blades, riveted to corrosion--resistant steel spiders, and
shall be dynamically balanced and discharge air horizontally or
vertically upwards.
Condenser coils shall have aluminum--plate fins mechanically
bonded to seamless copper tubes with all joints brazed.
Tube sheet openings shall be belled to prevent tube wear.

EVAPORATOR SECTION

Total cooling capacity of the unit shall be _____ Btuh or greater,


and sensible capacity shall be ______ Btuh or greater at conditions
of ______ cfm indoor air entering unit at ______F dry bulb,
_____ F wet bulb and outdoor entering air of ______F dry bulb.
Total design conditions shall be a minimum of ______ Btuh/Watt.
The unit shall be capable of cooling operation down to 40_F
(4.4_C) as shipped from the factory.

Fan shall be multi--speed with direct drive motor as shown on the


equipment drawings.
Fan wheel shall be made from steel, be double--inlet type with
forward--curved blades with a corrosion--resistant finish and
dynamically balanced.
Evaporator coils shall have aluminum--plate fins mechanically
bonded to seamless copper tubes with all joints brazed.
Tube sheet openings shall be belled to prevent tube wear.

CABINET

MOTORS

Unit cabinet shall be constructed of phosphated, bonderized,


zinc--coated, prepainted steel. Basepan shall be made of a
single--piece non--corrosive, composite material.
Evaporator--fan compartment interior cabinet surfaces shall be
insulated with a minimum 1/2--in. (12.7 mm) thick, flexible
fiberglass insulation, coated on the air side with aluminum foil.
Cabinet panels shall be easily removable for servicing.
Outdoor coil shall be protected by metal louvered panels.

Compressor motors shall be of the refrigerant cooled type with line


break thermal and current overload protection.
All fan motors shall have permanently lubricated bearings, and
inherent automatic reset thermal overload protection.
Condenser fan motor shall be open drip--proof.

COMPRESSOR
Compressor shall be fully hermetic type with internal and external
vibration isolation.

COMPRESSOR ROTATION
On 3--phase units it is important to be certain compressor is
rotating in the proper direction. To determine whether or not
compressor is rotating in the proper direction:
1. Connect service gauges to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure
should rise, as is normal on any start--up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
1. Turn off power to the unit and tag disconnect.
2. Reverse any two of the unit power leads.
3. Turn on power to the unit.
The suction and discharge pressure levels should now move to
their normal start--up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes an elevated level of noise and does not provide
cooling.

Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231

Printed in U.S.A.

REFRIGERANT SYSTEM
Refrigerant system shall include fixed orifice or TXV metering
system.

CONTROLS
Unit shall be complete with self--contained low voltage control
circuit.

APPROVALS
Unit shall be UL listed as a total package for safety requirements.
All wiring shall be in accordance with NEC.
Unit shall be rated in accordance with ARI Standards 210/240.
Cabinet insulation shall conform to ASHRAE Standard 62.2
Insulation and adhesive shall meet NFPA 90A requirements for
flame spread and smoke generation.
Unit shall have a sloped drain pan that conforms to ASHRAE
Standard 62.2.

ACCESSORIES
Field--installed accessories shall include solid--state compressor
short--cycle device, outdoor thermostat, thermostat and subbase,
electric heaters with single--point connection, crankcase heater,
low-- and high pressure switch kits, and low--ambient kit.

Edition Date: 08/08

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

22

Catalog No: 50ZPA ---06PD


Replaces: 50ZPA--- 05PD