HV SOLUTIONS

High Voltage Product Catalog 69kV 230kV Cables & Accessories

SOUTHWIRE

SOUTHWIRE SOLUTIONS FOR HigH Voltage UndergroUnd


CABLES
XLPE Cables 69 through 230kV with Copper and Aluminum conductors through 4,000 kcmil Concentric neutrals, welded and corrugated sheathes in Copper or Aluminum and composite laminate sheathes in Copper or Aluminum cover all applications XLPE cables through 345 kV with cross sections up to 5,000 kcmil on special request Southwire has supplied over four million feet of HV cable to customers in North America We offer many options such as integrated or external optical fiber for distributed temperature sensing, fire retardant cable jackets and cables with the highest fault current ratings Special executions include long lengths and pipe retrofit cables

TABLE OF CONTENTS
1 Section 1: HTS Triax Superconducting Cable Section 2: 69 kV Cables 5 Copper Conductor, Traditional Wall 650 mil XLPE Copper Corrugated Sheath 7 Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath 9 Aluminum Conductor, Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath 11 Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath 13 Copper Conductor, Traditional Wall 650 mil XLPE Copper Concentric Neutral 15 Aluminum Conductor, Traditional Wall 650 mil XLPE Copper Concentric Neutral 17 Copper Conductor, Traditional Wall 650 mil XLPE Copper Neutral, Copper Composite Laminate Sheath 19 Copper Conductor, SW Standard Wall XLPE Copper Neutral, Copper Composite Laminate Sheath 21 Aluminum Conductor, Traditional Wall 650 mil XLPE Copper Neutral, Aluminum Composite Laminate Sheath 23 Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath Section 3: 115 kV Cables 27 Copper Conductor, Traditional Wall 800 mil XLPE Copper Corrugated Sheath 29 Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath 31 Aluminum Conductor, Traditional Wall 800 mil XLPE Aluminum Corrugated Sheath 33 Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath 35 Copper Conductor, Traditional Wall 800 mil XLPE Copper Neutrals, Copper Composite Laminate Sheath 37 Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath 39 Aluminum Conductor, Traditional Wall 800 mil XLPE Copper Neutrals, Aluminum Composite Laminate Sheath 41 Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath Section 4: 138 kV Cables 45 Copper Conductor, Traditional Wall 850 mil XLPE Copper Corrugated Sheath 47 Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath 49 Aluminum Conductor, Traditional Wall 850 mil XLPE Aluminum Corrugated Sheath 51 Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath 53 Copper Conductor, Traditional Wall 850 mil XLPE Copper Neutrals, Copper Composite Laminate Sheath 55 Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath 57 Aluminum Conductor, Traditional Wall 850 mil XLPE Copper Neutrals, Aluminum Composite Laminate Sheath 59 Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath Section 5: 161 kV Cables 63 Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath 65 Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath 67 Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath 69 Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath Section 6: 230 kV Cables 73 Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath 75 Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath 77 Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath 79 Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath Section 7: Accessories 83 Components 84 Design Criteria 85 Outdoor Termination 87 Switchgear & Transformer Termination 89 Joint 90 Aluminum Cable Clamps

SERVICES
Feasibility studies and conceptual engineering Ampacity Studies Detailed underground system design Pulling calculations Cable pulling Splicing and terminating services Sheath bonding and grounding Commissioning, testing AC Resonant and PD testing Construction Management Full turnkey projects including civil works Maintenance Fault location Emergency and repair services

ABOUT SOUTHWIRE A technology leader for over 60 years, Southwire Company is the leading wire and cable producer in North America. Southwire manufactures utility cable products including overhead and underground transmission and distribution cable. For more information about Southwire products, services, and technical resources please visit www.southwire.com.

ACCESSORIES
Our accessories for HV cable use premolded LSR stress cone technology throughout, made by nkt cables in Germany Outdoor terminations with porcelain or silicone rubber composite insulators GIS and Transformer terminations to IEC 60859 Dry Plug and Socket compact switchgear and transformer terminations through 145 kV Premolded cable splices Splice options include shield breaks, metal casing, DTS fiber integration, capacitive PD detection ports, bolted or compression connectors and cable size transition Transitions between different cable insulation types are available

SOUTHWIRE COMPANY ONE SOUTHWIRE DRIVE CARROLLTON, GA 30119 1.800.444.1700 www.southwire.com

DISCLAIMER

While great care has been employed to ensure that the applications, tables, standards and references and other information contained herein are free of errors, absolutely no warranties, either expressed or implied, are made as to the accuracy or completeness of any such tables and formulas contained herein. Neither Southwire nor anyone else who has been involved in the creation, production or delivery of this publication shall be liable for any direct, indirect, consequential, or incidental damages arising out of the use, the results of the use, or inability to use such publication, even if Southwire has been advised of the possibility of such damages or claim. Some states do not allow the exclusion or limitation for consequential incidental damages, so the above limitation may not apply to you.

HtS triax

Section 1

HTS Triax Superconducting Cable


MORE POWER TO MORE PEOPLE

HtS triax

HTS Triax Superconducting Cable is Southwires unique and proprietary cable design. The Triax cable locates the three electrical phases and neutral conductor concentrically on a single core. This design drastically reduces material usage and cooling requirements of the system, and therefore cost. Applications for this advanced technology address right of way and substation congestion constraints in many of todays urban environments.

compact deSignS HTS Triax allows for a retrofit of existing underground pipe and duct systems to increase power delivery, as well as reduced substation footprint in dense urban areas. eliminate emF HTS Triax cable is fully shielded. tHermal independence From SUrroUnding enVironment HTS cables utilize high performance thermal insulation to maintain operating temperatures of -200oC. This isolates the cable from the surrounding environment and eliminates the need to special back-fill. 5x cUrrent carrying capacity oF copper cableS HTS Triax operates at extremely high currents in normal, steady state conditions. enVironmentally Friendly cooling mediUm Liquid nitrogen cooling fluid is non-toxic and environmentally friendly. diStribUtion SUbStationS togetHer on lV Side oF tranSFormer HTS cables at MV can easily carry full station load (80-150 MW) at steady state operation. Benefits include increased asset utilization (share transformer capacity between distribution substations) and increased meshing of distribution grid in dense urban areas.

SUpercondUcting cable

Section 2

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE


3 4

CONDUCTOR MATERIAL AND SIzE


Conductor material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

69 kV power cables

INSULATION THICKNESS
For cables with a radial moisture barrier, Southwire Standard Wall reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended Cables referred to by Traditional Wall insulation (650 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities For applications requiring smaller cable diameters, specific designs are available upon request

SHEATH MATERIAL
Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Full wall cables with concentric neutrals are an economical option for mostly dry environments Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET
Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

69 kV power cables

Section 2

69 kV XLPE Copper Conductor


TRADITIONAL WALL 650 MIL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) in Maximum Pulling Tension Flange x Width Shipping Reel Capacity* Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm
3

500 Nominal in mm in mm in mm in mm lbs/ft in lbs 0.79 20.1 2.21 56.1 2.68 68.1 2.96 75.2 4.8 59/44 4,000

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 2.39 60.7 2.88 73.2 3.16 80.3 5.9 63/47 6,000

1.12 28.5 2.53 64.3 3.04 77.2 3.33 84.6 6.9 67/50 8,000

1.25 31.8 2.67 67.8 3.19 81.0 3.47 88.1 7.9 69/52 10,000

1.37 34.8 2.79 70.9 3.32 84.3 3.60 91.4 8.8 72/54 12,000

1.48 37.6 2.90 73.7 3.44 87.4 3.72 94.5 9.8 74/56 14,000

1.61 40.9 3.00 76.2 3.56 90.4 3.84 97.5 10.7 77/58 16,000

1.76 44.7 3.26 82.8 3.85 97.8 4.13 104.9 12.9 83/62 20,000

1.92 48.8 3.42 86.9 4.03 102.3 4.31 109.4 14.8 86/65 24,000

2.08 52.8 3.58 90.8 4.20 106.6 4.48 113.7 16.7 90/67 28,000

2.21 56.1

69 kV power cables

3.71 94.2 4.34 110.3 4.62 117.4 18.5 92/69 32,000

typical Shipping reel Size in ft 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 2,950 150x95 3,000 158x95 2,800 150x95 2,500 150x95 2,200 150x95 1,975

traditional Wall 650 mil xlpe copper corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

3.9 1.6 51.3 33.6 0.021 0.027 43.8 0.66

3.7 1.7 76.9 36.1 0.014 0.018 49.5 0.74

3.5 1.7 102.5 38.2 0.011 0.014 54.2 0.81

3.4 1.8 128.1 40 0.008 0.011 58.4 0.88

3.4 1.8 153.8 41.6 0.007 0.009 62.1 0.93

3.3 1.8 179.4 43.2 0.006 0.008 65.5 0.98

3.3 1.8 205 44.6 0.005 0.007 68.7 1.03

3.2 1.9 256.3 48.3 0.004 0.005 76.5 1.15

3.1 1.9 307.5 50.5 0.004 0.005 81.5 1.22

3.1 1.9 358.8 52.6 0.003 0.004 86.2 1.29

3.1 1.9 410 54.4 0.003 0.003 90.3 1.36

72.5 350 90 105 250 -10 AEIC, IEC 120 kV / 15 min. 0.0005 2.3

Insulation Shield Conductor Sheath

Short circuit for 0.5s

kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2 3

600 72 510 61

740 89 630 76

820 98 710 85

960 115 810 97

1040 125 880 106

1110 133 940 113

1180 142 990 119

1390 167 1181 142

1506 180 1276 153

1595 191 1432 172

1673 200 1517 182

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

69 kV power cables

Section 2

69 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded SemiConductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.79 20.1 520 20.5 1.95 49.5 2.39 60.7 2.67 67.8 4.2 53/40 4,000

0.97 24.7 490 19.3 2.07 52.5 2.51 63.8 2.80 71.0 5.2 56/42 6,000

1.12 28.5 470 18.5 2.18 55.4 2.63 66.8 2.91 73.9 6.1 58/44 8,000

1.25 31.8 450 17.7 2.27 57.7 2.73 69.3 3.01 76.5 6.9 60/45 10,000

1.37 34.8 450 17.7 2.39 60.7 2.87 72.9 3.15 80.0 7.9 63/47 12,000

1.48 37.6 440 17.3 2.48 63.0 2.96 75.2 3.24 82.3 8.8 65/49 14,000

1.61 40.9 430 16.9 2.56 65.0 3.05 77.5 3.33 84.6 9.6 67/50 16,000

1.76 44.7 430 16.9 2.82 71.6 3.35 85.0 3.63 92.1 11.7 73/54 20,000

1.92 48.8 440 17.3 2.92 74.2 3.44 87.4 3.72 94.5 13.3 74/56 24,000

2.08 52.8 450 17.7 3.1 78.7 3.64 92.5 3.92 99.6 15.3 78/59 28,000

2.21 56.1

69 kV power cables

450 17.7 3.23 82.0 3.78 96.0 4.06 103.1 17 81/61 32,000

typical Shipping reel Size

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 90 105 250 -10 72.5 350

in ft

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

150x95 2,750

150x95 2,400

158x95 2,100

SW Standard Wall xlpe copper corrUgated SHeatH

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

4.5 2.1 51.3 29.9 0.021 0.027 51.1 0.74

4.5 2.4 76.9 31.5 0.014 0.018 60.6 0.91

4.5 2.6 102.5 33 0.011 0.014 68.9 1.04

4.5 2.7 128.1 34.2 0.008 0.011 77.1 1.16

4.5 2.8 153.8 35.9 0.007 0.009 82.4 1.24

4.5 2.9 179.4 37.1 0.006 0.008 88.9 1.34

4.5 3.0 205 38.2 0.005 0.007 95.3 1.43

4.4 3.0 256.3 41.9 0.004 0.005 107.1 1.31

4.3 3.0 307.5 43.1 0.004 0.005 108.6 1.63

4.2 3.0 358.8 45.5 0.003 0.004 113.3 1.7

4.1 3.0 410 47.4 0.003 0.003 119.2 1.79

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

600 72 520 63

750 90 640 77

870 104 740 89

970 116 820 98


3

1060 127 890 107

1130 136 950 114

1200 144 1000 120

1422 170 1202 144

1544 185 1303 156

1632 196 1377 165

1714 205 1445 173

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

69 kV power cables

Section 2

69 kV XLPE Aluminum Conductor


TRADITIONAL WALL 650 MIL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded SemiConductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o 1

500 Nominal in mm in mm in mm in mm lbs/ft in lbs in ft 0.79 20.1 2.21 56.1 2.78 70.6 3.06 77.7 3.2 61/46 3,000 126x95 3,000

750

1000

1250

1500

1750

2000

0.97 24.7 2.39 60.7 2.98 75.7 3.26 82.8 3.6 65/49 4,500 126x95 3,000

1.12 28.5 2.53 64.3 3.15 80.0 3.43 87.1 4.1 69/51 6,000 126x95 3,000

1.25 31.8 2.67 67.8 3.30 83.7 3.58 90.8 4.5 72/54 7,500 126x95 3,000

1.37 34.8 2.79 70.9 3.43 87.1 3.71 94.2 4.9 74/56 9,000 126x95 2,950

1.48 37.6 2.90 73.7 3.55 90.2 3.83 97.3 5.3 77/57 10,500 150x95 3,000

1.61 40.9 3.00

69 kV power cables

76.2 3.67 93.2 3.95 100.3 5.7 79/59 12,000 150x95 3,000

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

3.9 1.6 33.8 38 0.035 0.044 43.8 0.66

3.7 1.7 50.8 40.7 0.023 0.030 49.5 0.74

3.5 1.7 67.7 43 0.017 0.022 54.2 0.81

3.4 1.8 84.6 45 0.014 0.018 58.4 0.88

3.4 1.8 101.5 46.9 0.012 0.015 62.1 0.93

3.3 1.8 118.5 48.6 0.010 0.013 65.5 0.98

3.3 1.8

traditional Wall 650 mil xlpe alUminUm corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3
1 2 3

135.4 50.1 0.009 0.011 68.7 1.03

72.5 350 90 105 250 -10

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Amps MVA Amps MVA

470 57 400 48

580 70 500 60

680 82 580 70

770 93 650 78

840 101 710 85

910 109 770 93

970 116 820 98

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

10

69 kV power cables

Section 2

69 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 430 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded SemiConductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm
2

500 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.79 20.1 520 20.5 1.95 49.5 2.47 62.7 2.75 69.9 2.7 55/41 3,000 126x95 3,000

750

1000

1250

1500

1750

2000

0.97 24.7 490 19.3 2.07 52.6 2.61 66.3 2.89 73.4 3.0 58/43 4,500 126x95 3,000

1.12 28.5 470 18.5 2.18 55.4 2.73 69.3 3.01 76.5 3.4 60/45 6,000 126x95 3,000

1.25 31.8 450 17.7 2.27 57.7 2.83 71.9 3.11 79.0 3.7 62/47 7,500 126x95 3,000

1.37 34.8 450 17.7 2.39 60.7 2.96 75.2 3.24 82.3 4.1 65/49 9,000 126x95 3,000

1.48 37.6 440 17.3 2.48 63.0 3.06 77.7 3.34 84.8 4.4 67/50 10,500 126x95 3,000

1.61 40.9 430

69 kV power cables

16.9 2.56 65.0 3.15 80.0 3.43 87.1 4.7 69/51 12,000 126x95 3,000

4.5 2.1 33.8 33.8 0.035 0.044 51.1 0.77

4.5 2.4 50.8 35.6 0.023 0.030 60.6 0.91

4.5 2.6 67.7 37.3 0.017 0.022 68.9 1.04

3.4 1.8 84.6 38.7 0.014 0.018 77.1 1.16

4.5 2.8 101.5 40.5 0.012 0.015 82.4 1.24

4.5 2.9 118.5 41.8 0.010 0.013 88.9 1.34

4.5 3.0

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3
1 2

Insulation Shield Short circuit for 0.5s Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating
3

SW Standard Wall xlpe alUminUm corrUgated SHeatH

72.5 350 90 105 250 -10

kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

135.4 43.1 0.009 0.011 95.3 1.43

470 57 410 49

590 71 510 61

690 83 590 71

780 94 660 79

860 103 720 87

920 110 780 94

990 119 820 98

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

11

12

69 kV power cables

Section 2

69 kV XLPE Copper Conductor


TRADITIONAL WALL 650 MIL XLPE COPPER CONCENTRIC NEUTRALS
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Neutrals Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA Nominal in mm in mm in mm in (mm) lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.79 20.1 2.21 56.1 2.56 65.0 2.86 72.6 4.2 57/43 4,000

0.97 24.7 2.39 60.7 2.74 69.6 3.04 77.2 5.2 61/46 6,000

1.12 28.5 2.53 64.3 2.88 73.2 3.18 80.8 6.1 64/48 8,000

1.25 31.8 2.67 67.8 3.02 76.7 3.32 84.3 7.1 66/50 10,000

1.37 34.8 2.79 70.9 3.14 79.8 3.44 87.4 8.0 69/52 12,000

1.48 37.6 2.90 73.7 3.25 82.6 3.55 90.2 8.9 71/53 14,000

1.61 40.9 3.00 76.2 3.35 85.1 3.66 93.0 9.8 73/55 16,000

1.76 44.7 3.18 80.8 3.53 89.6 3.83 97.4 11.6 77/57 20,000

1.92 48.8 3.34 84.9 3.69 93.7 3.99 101.4 13.4 80/60 24,000

2.08 52.8 3.5 88.9 3.84 97.6 4.15 105.4 15.2 83/62 28,000

2.21 56.1

69 kV power cables

3.63 92.2 3.98 101.1 4.28 108.7 17 86/64 32,000

typical Shipping reel Size in ft 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 2,950 150x95 3,000 150x95 2,700 150x95 2,400 150x95 2,150

traditional Wall 650 mil xlpe copper concentric neUtralS

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 90 105 250 -10 72.5 350

3.9 1.6 51.3 35.6 0.021 0.027 43.8 0.66

3.7 1.7 76.9 35.6 0.014 0.018 49.5 0.74

3.5 1.7 102.5 35.6 0.011 0.014 54.2 0.81

3.4 1.8 128.1 35.6 0.008 0.011 58.4 0.88

3.4 1.8 153.8 35.6 0.007 0.009 62.1 0.93

3.3 1.8 179.4 35.6 0.006 0.008 65.5 0.98

3.3 1.8 205 35.6 0.005 0.007 68.7 1.03

3.2 1.9 256.3 35.6 0.004 0.005 74.4 1.12

3.1 1.9 307.5 35.6 0.004 0.005 81.4 1.22

3.1 1.9 358.8 35.6 0.003 0.004 83.7 1.26

3.0 1.9 410 35.6 0.003 0.003 90.3 1.36

Insulation Shield Conductor Nuetrals

Short circuit for 0.5s3

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

610 73 520 63

760 91 640 77

880 106 740 89

980 118 830 100

1070 128 900 108

1150 138 960 115

1210 145 1020 122

1456 175 1226 147

1600 192 1341 161

1709 205 1432 172

1814 217 1517 182

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

13

14

69 kV power cables

Section 2

69 kV XLPE Aluminum Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Neutral Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) in Maximum Pulling Tension typical Shipping reel Size Flange x Traverse in ft Nominal in mm in mm in mm in mm lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

0.79 20.1 2.21 56.1 2.56 65.0 2.86 72.6 3.1 57/43 3,000 126x95 3,000

0.97 24.7 2.39 60.7 2.74 69.6 3.04 77.2 4.1 61/46 4,500 126x95 3,000

1.12 28.5 2.53 64.3 2.88 73.2 3.18 80.8 4.5 64/48 6,000 126x95 3,000

1.25 31.8 2.67 67.8 3.02 76.7 3.32 84.3 4.9 66/50 7,500 126x95 3,000

1.37 34.8 2.79 70.9 3.14 79.8 3.44 87.4 5.2 69/52 9,000 126x95 3,000

1.48 37.6 2.90 73.7 3.25 82.6 3.55 90.2 5.6 71/53 10,500 126x95 3,000

1.61 40.9 3.00

69 kV power cables

76.2 3.35 85.1 3.66 93.0 6.0 73/55 12,000 126x95 3,000

TRADITIONAL WALL 650 MIL XLPE COPPER CONCENTRIC NEUTRALS

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s
2

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

3.9 1.6 33.8 35.6 0.035 0.044 43.9 0.66

3.7 1.7 50.8 35.6 0.023 0.030 49.5 0.74

3.5 1.7 67.7 35.6 0.017 0.022 54.2 0.81

3.4 1.8 84.6 35.6 0.014 0.018 58.4 0.88

3.4 1.8 101.5 35.6 0.012 0.015 62.1 0.93

3.3 1.8 118.5 35.6 0.010 0.013 65.5 0.98

3.3 1.8

traditional Wall 650 mil xlpe copper concentric neUtralS

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3
1 2 3

Conductor Nuetrals conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank Power Rating
3

135.4 35.6 0.009 0.011 68.7 1.03

72.5 350 90 105 250 -10

Amps MVA Amps MVA

480 58 410 49

600 72 510 61

700 84 590 71

780 94 660 79

860 103 730 88

930 112 780 94

1000 120 830 100

Increased shipping reel capacity can be accommodated on request. Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

15

16

69 kV power cables

Section 2

69 kV XLPE Copper Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Nominal in mm in mm in mm in mm lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.79 20.1 2.21 56.1 2.59 65.8 2.91 73.9 4.5 58/44 4,000

0.97 24.7 2.39 60.7 2.77 70.4 3.09 78.5 5.5 62/46 6,000

1.12 28.5 2.54 64.5 2.92 74.2 3.24 82.3 6.5 65/49 8,000

1.25 31.8 2.67 67.8 3.06 77.7 3.38 85.9 7.4 68/51 10,000

1.37 34.8 2.79 70.9 3.18 80.8 3.50 88.9 8.4 70/53 12,000

1.48 37.6 2.90 73.7 3.29 83.6 3.61 91.7 9.3 72/54 14,000

1.61 40.9 3.00 76.2 3.39 86.1 3.71 94.2 10.2 74/56 16,000

1.78 45.2 3.18 80.8 3.59 91.2 3.91 99.3 12.1 78/59 20,000

1.98 50.2 3.34 84.8 3.75 95.3 4.07 103.4 13.8 81/61 24,000

2.08 52.8 3.5 88.9 3.91 99.3 4.23 107.4 15.7 85/63 28,000

2.21 56.1

69 kV power cables

3.63 92.2 4.04 102.6 4.36 110.7 17.5 87/65 32,000

TRADITIONAL WALL 650 MIL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAMINATE SHEATH

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Concentric Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

Maximum Pulling Tension Flange x Width Shipping Reel Capacity2 Electrical electrical Stress @ Uo

typical Shipping reel Size in ft 126x95 3,000 126x95 3,000 126x95 3,000 138x95 3,000 138x95 3,000 138x95 3,000 150x95 3,000 150x95 3,000 150x95 2,650 150x95 2350 150x95 2100

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 90 105 250 -10 72.5 350

traditional Wall 650 mil xlpe copper neUtralS WitH copper compoSite laminate SHeatH

Conductor Shield Insulation Shield Conductor Sheath

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

3.9 1.6 51.3 42.3 0.021 0.027 43.8 0.66

3.7 1.7 76.9 42.8 0.014 0.018 49.5 0.74

3.5 1.7 102.5 43.2 0.011 0.014 54.2 0.81

3.4 1.8 128.1 43.5 0.008 0.011 58.4 0.88

3.4 1.8 153.8 43.9 0.007 0.009 62.1 0.93

3.3 1.8 179.4 44.1 0.006 0.008 65.5 0.98

3.3 1.8 205 44.4 0.005 0.007 68.7 1.03

3.2 1.9 256.3 44.9 0.004 0.005 74.4 1.12

3.1 1.9 307.5 45.4 0.004 0.005 81.4 1.22

3.1 1.9 358.8 45.8 0.003 0.004 83.7 1.26

3.0 1.9 410 46.1 0.003 0.003 90.3 1.36

Short circuit for 0.5s3

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

610 73 520 63

760 91 640 77

880 106 740 89

980 118 830 100

1070 128 900 108

1150 138 960 115

1210 145 1020 122

1456 175 1226 147

1600 192 1341 161

1709 205 1432 172

1814 217 1517 182

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

17

18

69 kV power cables

Section 2

69 kV XLPE Copper Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 430 mil XLPE minimum

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.79 20.1 520 20.5 1.95 49.5 2.33 59.3 2.65 67.3 4.9 53/40 4,000

0.97 24.7 490 19.3 2.07 52.5 2.45 62.2 2.77 70.4 6.0 55/42 6,000

1.12 28.5 470 18.5 2.18 55.4 2.56 65.0 2.88 73.2 6.3 58/43 8,000

1.25 31.8 450 17.7 2.27 57.7 2.66 67.4 2.98 75.7 7.1 60/45 10,000

1.37 34.8 450 17.7 2.39 60.7 2.78 70.5 3.10 78.6 8.0 62/46 12,000

1.48 37.6 440 17.3 2.48 63.0 2.87 72.8 3.19 80.9 8.9 64/48 14,000

1.61 40.9 430 16.9 2.56 65.0 2.95 74.9 3.27 83.0 9.7 65/49 16,000

1.78 45.2 430 16.9 2.74 69.6 3.16 80.3 3.48 88.4 11.7 70/52 20,000

1.98 50.2 440 17.3 2.92 74.2 3.41 86.6 3.73 94.7 13.5 75/56 24,000

2.08 52.8 450 17.7 3.1 78.7 3.51 89.1 3.83 97.2 15.4 77/57 28,000

2.21 56.1

69 kV power cables

450 17.7 3.23 82.0 3.64 92.5 3.96 100.6 17.1 79/59 32,000

SW STANDARD WALL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAMINATE SHEATH

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2

typical Shipping reel Size in ft 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 126x95 3,000 138x95 3,000 150x95 2,800 150x95 2,500 150x95 2,200

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3 90 105 250 -10 72.5 350

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

4.5 2.1 51.3 41.7 0.021 0.027 51.1 0.77

4.5 2.4 76.9 42 0.014 0.018 60.6 0.91

4.5 2.6 102.5 42.3 0.011 0.014 68.9 1.04

4.5 2.7 128.1 42.5 0.008 0.011 77.1 1.16

4.5 2.8 153.8 42.8 0.007 0.009 82.4 1.24

4.5 2.9 179.4 43.1 0.006 0.008 88.9 1.34

4.5 3.0 205 43.3 0.005 0.007 95.3 1.43

4.4 3.0 256.3 43.8 0.004 0.005 103.8 1.56

4.3 3.0 307.5 44.5 0.004 0.005 112.1 1.68

4.2 3.0 358.8 44.7 0.003 0.004 113.3 1.702

4.1

Standard Wall xlpe copper neUtralS WitH copper compoSite laminate SHeatH

3.0 410.0 45.1 0.003 0.003 119.24 1.791

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

620 75 520 63

770 93 640 77

900 108 740 89

1010 121 830 100


3

1100 132 900 108

1180 142 960 115

1250 150 1010 121

1471 176 1235 148

1609 193 1346 161

1730 207 1444 173

1836 220 1530 183

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

19

20

Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

69 kV power cables

Section 2

69 kV XLPE Aluminum Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 650 mil XLPE

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Width in ft Nominal in mm in mm in mm in mm lbs/ft in lbs

500

750

1000

1250

1500

1750

2000

0.79 20.1 2.21 56.1 2.60 66.0 2.92 74.1 3.7 58/44 3,000 126x95 3,000

0.97 24.7 2.39 60.7 2.78 70.5 3.10 78.7 4.2 62/46 4,500 126x95 3,000

1.12 28.5 2.54 64.4 2.93 74.3 3.25 82.4 4.7 65/49 6,000 126x95 3,000

1.25 31.8 2.67 67.8 3.06 77.7 3.38 85.8 5.1 68/51 7,500 138x95 3,000

1.37 34.8 2.79 70.9 3.18 80.7 3.50 88.9 5.5 70/52 9,000 138x95 3,000

1.48 37.6 2.90 73.7 3.29 83.5 3.61 91.7 5.8 72/54 10,500 138x95 3,000

1.61 40.9 3.00

69 kV power cables

76.2 3.39 86.1 3.71 94.2 6.2 74/56 12,000 150x95 3,000

TRADITIONAL WALL 650 MIL XLPE COPPER NEUTRALS WITH ALUMINUM COMPOSITE LAMINATE SHEATH

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating
3 2

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA
3

3.9 1.6 33.8 41.6 0.035 0.043 43.9 0.66

3.7 1.7 50.8 42 0.023 0.028 49.5 0.74

3.5 1.7 67.7 42.3 0.017 0.021 54.2 0.81

3.4 1.8 84.6 42.6 0.014 0.017 58.4 0.88

3.4 1.8 101.5 42.9 0.012 0.014 62.1 0.93

3.3 1.8 118.5 43.1 0.010 0.012 65.5 0.98

3.3 1.8 135.4 43.4

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3
1 2 3

traditional Wall 650 mil xlpe copper neUtralS WitH alUminUm compoSite laminate SHeatH

72.5 350 90 105 250 -10

0.009 0.011 68.7 1.03

480 58 410 49

600 72 510 61

700 84 590 71

780 94 660 79

860 103 730 88

930 112 780 94

1000 120 830 100

Typical Double Ductbank Power Rating

Amps MVA

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

21

22

69 kV power cables

Section 2

69 kV XLPE Aluminum Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 430 mil XLPE minimum

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3 1

500 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.79 20.1 520 20.5 1.95 49.5 2.34 59.4 2.66 67.5 3.3 53/40 3,000 126x95 3,000

750

1000

1250

1500

1750

2000

0.97 24.7 490 19.3 2.07 52.5 2.46 62.4 2.78 70.5 3.7 56/42 4,500 126x95 3,000

1.12 28.5 470 18.5 2.18 55.3 2.57 65.2 2.89 73.3 4.0 58/43 6,000 126x95 3,000

1.25 31.8 450 17.7 2.27 57.7 2.66 67.5 2.98 75.7 4.3 60/45 7,500 126x95 3,000

1.37 34.8 450 17.7 2.39 60.7 2.78 70.6 3.10 78.7 4.7 62/46 9,000 126x95 3,000

1.48 37.6 440 17.3 2.48 63.0 2.87 72.9 3.19 81.0 5.0 64/48 10,500 138x95 3,000

1.61 40.9 430

69 kV power cables

16.9 2.56 65.1 2.95 75.0 3.27 83.1 5.3 65/49 12,000 138x95 3,000

SW STANDARD WALL XLPE COPPER NEUTRALS WITH ALUMINUM LAMINATE SHEATH

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

4.5 2.1 33.8 41 0.035 0.043 51.1 0.77

4.5 2.4 50.8 41.2 0.023 0.028 60.6 0.91

4.5 2.6 67.7 41.5 0.017 0.021 68.9 1.04

4.5 2.7 84.6 41.7 0.014 0.017 77.1 1.16

4.5 2.8 101.5 42 0.012 0.014 82.4 1.24

4.5 2.9 118.5 42.2 0.010 0.012 88.9 1.34

4.5 3.0 135.4 42.4

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 120 kV / 15 min. 0.0005 2.3
1 2 3

72.5 350 90 105 250 -10

Standard Wall xlpe copper neUtralS WitH alUminUm compoSite laminate SHeatH

0.009 0.011 95.3 1.43

Typical Single Ductbank Power Rating

Amps MVA Amps MVA

485 58 408 49

608 73 507 61

712 86 590 71

803 96 661 79

884 106 724 87

957 115 780 94

1023 123 829 100

Typical Double Ductbank Power Rating

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

23

24

Section 3

KNOW YOUR OPTIONS: 115 KV POWER CABLE


25 26

CONDUCTOR MATERIAL AND SIzE


Conductor material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

115 kV power cables

INSULATION THICKNESS
For cables with a radial moisture barrier, Southwire Standard Wall reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended Cables referred to by Traditional Wall insulation (800 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL
Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET
Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

115 kV power cables

Section 3

115 kV XLPE Copper Conductor


TRADITIONAL WALL 800 MIL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 800 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Width Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s3 Conductor kA kA /kft /kft pF/ft Amps/ kft per circuit
4 2

750 Nominal in mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 2.69 68.3 3.23 81.9 3.51 89.0 6.6 70/53 6,000 126x95 3,000

1000 1.12 28.5 2.84 72.1 3.39 86.1 3.67 93.2 7.6 73/55 8,000 126x95 2,950

1250 1.25 31.8 2.97 75.4 3.54 89.8 3.82 96.9 8.6 76/57 10,000 150x95 3,000

1500 1.37 34.8 3.09 78.5 3.67 93.2 3.95 100.3 9.6 79/59 12,000 150x95 3,000

1750 1.48 37.6 3.20 81.3 3.79 96.3 4.07 103.4 10.6 81/61 14,000 150x95 2,725

2000 1.61 40.9 3.30 83.9 3.90 99.1 4.18 106.2 11.6 84/63 16,000 150x95 2,750

2500 1.76 44.7 3.48 88.4 4.10 104.1 4.38 111.2 13.5 88/66 20,000 158x95 2,675

3000 1.92 48.8 3.64 92.5 4.27 108.6 4.55 115.7 15.4 91/68 24,000 150x95 2,400

3500 2.08 52.8 3.80 96.4 4.44 112.9 4.72 120.0 17.3 94/71 28,000 150x95 2,075

4000 2.21 56.1 3.93 99.8 4.59 116.6 4.87 123.7 19.2 97/73 32,000 158x95 1,875

115 kV power cables

kV/mm kV/mm

5.3 2.2 76.9 40.4 0.014 0.018 43.1 1.08

5.1 2.2 102.5 42.5 0.011 0.014 46.9 1.17

4.9 2.3 128.1 44.3 0.008 0.011 50.3 1.26

4.8 2.3 153.8 46 0.007 0.009 53.4 1.34

4.7 2.4 179.4 47.5 0.006 0.008 56.2 1.41

4.6 2.4 205 48.9 0.005 0.007 58.8 1.47

4.5 2.4 256.3 51.3 0.004 0.005 63.3 1.58

4.4 2.5 307.5 53.5 0.004 0.005 67.3 1.68

4.4 2.5 358.8 55.7 0.003 0.004 71.1 1.78

4.3 2.5 410.0

traditional Wall 800 mil xlpe copper corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2

Sheath conductor resistance

57.5 0.003 0.003 74.5 1.87

120 550 90 105 250 -10

DC @ 20o C DC @ 90 C
o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank4 Power Rating

Amps MVA Amps MVA

740 148 630 126

860 172 730 146

960 192 810 162

1040 208 870 174

1110 222 930 186

1170 234 980 196

1404 280 1159 231

1523 304 1250 249

1625 324 1326 265

1708 341 1388 277

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

27

28

115 kV power cables

Section 3

115 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 540 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Conductor
3

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 660 26.0 2.41 61.2 2.90 73.7 3.18 80.8 5.9 64/48 6,000 126x95 3,000

1000 1.12 28.5 630 24.8 2.50 63.4 3.00 76.1 3.28 83.3 6.8 66/49 8,000 126x95 3,000

1250 1.25 31.8 610 24.0 2.59 65.8 3.10 78.7 3.38 85.8 7.7 68/51 10,000 126x95 3,000

1500 1.37 34.8 590 23.2 2.67 67.8 3.18 80.9 3.46 88.0 8.5 69/52 12,000 126x95 3,000

1750 1.48 37.6 580 22.8 2.76 70.1 3.29 83.4 3.57 90.6 9.4 71/53 14,000 126x95 3,000

2000 1.61 40.9 570 22.4 2.84 72.2 3.37 85.6 3.65 92.7 10.3 73/55 16,000 126x95 2,950

2500 1.76 44.7 550 21.7 2.99 75.9 3.53 89.6 3.81 96.7 12.1 76/57 20,000 126x95 2,975

3000 1.92 48.8 540 21.3 3.12 79.3 3.68 93.3 3.96 100.5 13.9 79/59 24,000 126x95 2,750

3500 2.08 52.8 540 21.3 3.28 83.2 3.84 97.6 4.12 104.7 15.8 82/62 28,000 138x95 2,375

4000 2.21 56.1 550 21.7 3.43 87.1 4.01 101.9 4.29 109.0 17.6 86/64 32,000 138x95 2,125

115 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA
4

6.1 2.9 76.9 36.3 0.014 0.018 49.0 1.23

6.0 3.0 102.5 37.6 0.011 0.014 55.4 1.39

6.0 3.2 128.1 38.8 0.008 0.011 61.2 1.53

6.0 3.4 153.8 39.9 0.007 0.009 66.8 1.67

6.0 3.5 179.4 41.2 0.006 0.008 71.4 1.79

6.0 3.6 205 42.2 0.005 0.007 76.0 1.90

6.0 3.8 256.3 44.2 0.004 0.005 84.9 2.12

6.0 3.9 307.5 46.0 0.004 0.005 91.7 2.30

6.0 4.0 358.8 48.1 0.003 0.004 97.3 2.44

5.8 3.9 410.0 50.2 0.003 0.003 100.7 2.52

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2 3

120 550 90 105 250 -10

Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank Power Rating

SW Standard Wall xlpe copper corrUgated SHeatH

750 150 640 128

870 174 740 148

970 194 820 164

1060 212 890 178

1130 226 940 188

1200 240 990 198

1435 286 1182 236

1561 311 1279 255

1667 333 1359 271

1757 350 1425 284

Amps MVA

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

29

30

115 kV power cables

Section 3

115 kV XLPE Aluminum Conductor


CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 800 mil XLPE

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical in ft Nominal in mm in mm in mm in mm lbs/ft in lbs

750 0.97 24.7 2.69 68.3 3.50 88.8 3.78 95.9 4.3 76/57 4,500 126x95 3,000

1000 1.12 28.5 2.84 72.1 3.45 87.7 3.73 94.8 4.8 75/56 6,000 126x95 2,975

1250 1.25 31.8 2.97 75.4 3.65 92.6 3.93 99.7 5.2 79/59 7,500 150x95 3,000

1500 1.38 35.0 3.09 78.5 3.78 96.0 4.06 103.1 5.7 81/61 9,000 150x95 2,725

1750 1.49 37.8 3.20 81.3 3.90 99.2 4.18 106.3 6.1 84/63 10,500 150x95 2,750

2000 1.61 40.9 3.30 83.9 4.02 102.1 4.30 109.2 6.5 86/64 12,000 150x95 2,600

115 kV power cables

TRADITIONAL WALL 800 MIL XLPE ALUMINUM CORRUgATED SHEATH

True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Sheath
2

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

5.3 2.2 50.8 45.5 0.023 0.030 43.1 1.08

5.1 2.2 67.7 47.8 0.017 0.022 46.9 1.17

4.9 2.3 84.6 49.8 0.014 0.018 50.3 1.26

4.8 2.3 101.5 51.7 0.012 0.015 53.4 1.34

4.7 2.4 118.5 53.4 0.010 0.013 56.2 1.41

4.6 2.4 135.4 54.9 0.009 0.011 58.8 1.47

Conductor

traditional Wall 800 mil xlpe alUminUm corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

conductor resistance DC @ 20o C

120 550 90 105 250 -10 AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2 3

DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank Power Rating
3

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Amps MVA Amps MVA

580 116 500 100

680 136 580 116

770 154 650 130

840 168 710 142

910 182 760 152

970 194 810 162

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

31

32

115 kV power cables

Section 3

115 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 590 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3 1

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 660 26.0 2.41 61.2 3.00 76.1 3.28 83.2 3.7 66/49 4,500 126x95 3,000

1000 1.12 28.5 630 24.8 2.50 63.4 3.10 78.7 3.38 85.8 4.0 68/51 6,000 126x95 3,000

1250 1.26 31.9 610 24.0 2.59 65.8 3.20 81.3 3.48 88.4 4.3 70/52 7,500 126x95 3,000

1500 1.38 35.0 590 23.2 2.67 67.8 3.29 83.5 3.57 90.6 4.7 71/54 9,000 126x95 3,000

1750 1.49 37.8 580 22.8 2.76 70.1 3.39 86.1 3.67 93.2 5.0 73/55 10,500 126x95 2,950

2000 1.61 40.9 570 22.4 2.84 72.2 3.48 88.3 3.76 95.4 5.3 75/56 12,000 126x95 2,975

115 kV power cables

6.1 2.7 50.8 41 0.023 0.030 49.0 1.23

6.0 3.0 67.7 42.4 0.017 0.022 55.4 1.39

6.0 3.2 84.6 43.7 0.014 0.018 61.2 1.53

6.0 3.4 101.5 44.9 0.012 0.015 66.8 1.67

6.0 3.5 118.5 46.3 0.010 0.013 71.4 1.79

6.0 3.6 135.4 47.5 0.009 0.011 76.0 1.90

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

Conductor

SW Standard Wall xlpe alUminUm corrUgated SHeatH

120 550 90 105 250 -10 AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2

Sheath conductor resistance DC @ 20o C DC @ 90 C


o

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Amps MVA Amps MVA

590 118 500 100

690 138 580 116

780 156 650 130

860 172 720 144

920 184 770 154

980 196 820 164

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

33

34

115 kV power cables

Section 3

115 kV XLPE Copper Conductor


TRADITIONAL WALL 800 MIL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or MIlliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 800 mil True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Width Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA Nominal in mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 2.69 68.3 3.07 78.1 3.39 86.2 6.6 68/51 6,000

1.12 28.5 2.84 72.1 3.22 81.8 3.54 90.0 7.6 71/53 8,000

1.25 31.8 2.97 75.4 3.36 85.2 3.68 93.3 8.5 74/55 10,000

1.37 34.8 3.09 78.5 3.48 88.3 3.80 96.4 9.5 76/57 12,000

1.48 37.6 3.20 81.3 3.59 91.1 3.91 99.2 10.4 78/59 14,000

1.61 40.9 3.30 83.9 3.69 93.7 4.01 101.8 11.4 80/60 16,000

1.76 44.7 3.48 88.4 3.89 98.8 4.21 107.0 13.5 84/63 20,000

1.92 48.8 3.64 92.5 4.05 102.9 4.37 111.0 15.3 87/66 24,000

2.08 52.8 3.80 96.4 4.21 106.8 4.53 115.0 17.2 91/68 28,000

2.21 56.1

115 kV power cables

3.93 99.8 4.34 110.3 4.66 118.4 19.0 93/70 32,000

typical Shipping reel Size in ft 138x95 3,000 138x95 3,000 138x95 2,775 150x95 3,000 150x95 3,000 150x95 2,725 158x95 2,775 158x95 2,450 158x95 2,175 158x95 1,975

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 200 kV / 15 min. 0.0005 2.3 90 105 250 -10 120 550

traditional Wall 800 mil xlpe copper neUtralS, copper compoSite laminate SHeatH

5.3 2.2 76.9 43.6 0.014 0.018 43.1 1.08

5.1 2.2 102.5 44.0 0.011 0.014 46.9 1.17

4.9 2.3 128.1 44.3 0.008 0.011 50.3 1.26

4.8 2.3 153.8 44.6 0.007 0.009 53.4 1.34

4.7 2.4 179.4 44.9 0.006 0.008 56.2 1.41

4.6 2.4 205.0 45.2 0.005 0.007 58.8 1.47

4.5 2.4 256.3 45.9 0.004 0.005 63.3 1.58

4.4 2.5 307.5 46.4 0.004 0.005 67.3 1.68

4.4 2.5 358.8 46.8 0.003 0.004 71.1 1.78

4.3 2.5 410.0 47.1 0.003 0.003 74.5 1.87

Insulation Shield Conductor Sheath

Short circuit for 0.5s3

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

750 150 640 128

870 174 740 148

980 196 820 164

1070 214 890 178

1140 228 950 190

1210 242 1010 202

1432 286 1210 242

1574 314 1320 263

1722 343 1416 283

1830 365 1500 299

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

35

36

115 kV power cables

Section 3

115 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or MIlliken Super Smooth Conductor Shield Super Clean XLPE Insulation 540 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 660 26.0 2.41 61.2 2.79 70.9 3.11 79.1 6.0 62/47 6,000

1.12 28.5 630 24.8 2.50 63.4 2.88 73.2 3.20 81.3 6.9 64/48 8,000

1.25 31.8 610 24.0 2.59 65.8 2.98 75.6 3.30 83.7 7.7 66/49 10,000

1.37 34.8 590 23.2 2.67 67.8 3.06 77.6 3.38 85.7 8.6 68/51 12,000

1.48 37.6 580 22.8 2.76 70.1 3.15 79.9 3.47 88.0 9.4 69/52 14,000

1.61 40.9 570 22.4 2.84 72.2 3.23 82.0 3.55 90.1 10.3 71/53 16,000

1.76 44.7 550 21.7 2.99 75.9 3.39 86.1 3.71 94.3 12.3 74/56 20,000

1.92 48.8 540 21.3 3.12 79.3 3.53 89.7 3.85 97.8 14.0 77/58 24,000

2.08 52.8 540 21.3 3.28 83.2 3.69 93.6 4.01 101.8 15.6 80/60 28,000

2.21 56.1

115 kV power cables

550 21.7 3.43 87.1 3.84 97.6 4.16 105.7 17.6 83/62 32,000

typical Shipping reel Size in ft 126x95 3,000 126x95 3,000 126x95 3,000 138x95 3,000 138x95 3,000 138x95 3,000 138x95 2,775 150x95 2,775 150x95 2,400 150x95 2,175

SW Standard Wall xlpe copper neUtralS, copper compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 200 kV / 15 min. 0.0005 2.3 90 105 250 -10 120 550

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

6.1 2.9 76.9 42.9 0.014 0.018 49.0 1.23

6.0 3.0 102.5 43.1 0.011 0.014 55.4 1.39

6.0 3.2 128.1 43.3 0.008 0.011 61.2 1.53

6.0 3.4 153.8 43.5 0.007 0.009 66.8 1.67

6.0 3.5 179.4 43.8 0.006 0.008 71.4 1.79

6.0 3.6 205 44.0 0.005 0.007 76.0 1.90

6.0 3.8 256.3 44.6 0.004 0.005 84.9 2.12

6.0 3.9 307.5 45.0 0.004 0.005 91.7 2.30

6.0 4.0 358.8 45.4 0.003 0.004 97.3 2.44

5.8 3.9 410.0 45.8 0.003 0.003 100.7 2.52

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

761 152 643 129

885 177 744 149

990 198 828 165

1080 216 899 180


3

1158 231 961 192

1226 245 1015 203

1481 295 1221 244

1622 324 1331 266

1747 348 1428 285

1854 370 1512 302

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

37

38

Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

115 kV power cables

Section 3

115 kV XLPE Aluminum Conductor


TRADITIONAL WALL 800 MIL XLPE COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 800 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Width Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Sheath
2

750 Nominal in mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 2.69 68.3 3.08 78.2 3.40 86.3 4.8 68/51 4,500 138x95 3,000

1000 1.12 28.5 2.84 72.1 3.23 81.9 3.55 90.1 5.3 71/53 6,000 138x95 3,000

1250 1.26 31.9 2.97 75.4 3.36 85.3 3.68 93.4 5.7 74/55 7,500 138x95 2,775

1500 1.38 35.0 3.09 78.5 3.48 88.4 3.80 96.5 6.1 76/57 9,000 150x95 3,000

1750 1.49 37.8 3.20 81.3 3.59 91.2 3.91 99.3 6.5 78/59 10,500 150x95 3,000

2000 1.61 40.9 3.30 83.9 3.69 93.8 4.01 101.9 6.9 80/60 12,000 150x95 2,725

115 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

5.3 2.2 50.8 42.7 0.023 0.030 43.1 1.08

5.1 2.2 67.7 43.0 0.017 0.022 46.9 1.17

4.9 2.3 84.6 43.3 0.014 0.018 50.3 1.26

4.8 2.3 101.5 43.6 0.012 0.015 53.4 1.34

4.7 2.4 118.5 43.8 0.010 0.013 56.2 1.41

4.6 2.4 135.4 44.1 0.009 0.011 58.8 1.47

Conductor conductor resistance DC @ 20o C

traditional Wall 800 mil xlpe copper neUtralS, alUminUm compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

120 550 90 105 250 -10 AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2 3

DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank Power Rating
3

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Amps MVA Amps MVA

595 119 504 101

696 139 586 117

785 157 658 132

864 173 722 144

934 187 778 155

999 199 829 166

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

39

40

115 kV power cables

Section 3

115 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE COPPER NEUTRAL, ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 570 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 Conductor Sheath kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3 1

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 660 26.0 2.41 61.2 2.80 71.0 3.12 79.2 4.3 62/47 4,500 126x95 3,000

1000 1.12 28.5 630 24.8 2.50 63.4 2.89 73.3 3.21 81.4 4.6 64/48 6,000 126x95 3,000

1250 1.26 31.9 610 24.0 2.59 65.8 2.98 75.7 3.30 83.8 4.9 66/49 7,500 126x95 3,000

1500 1.38 35.0 590 23.2 2.67 67.8 3.06 77.7 3.38 85.8 5.2 68/51 9,000 138x95 3,000

1750 1.49 37.8 580 22.8 2.76 70.1 3.15 80.0 3.47 88.1 5.5 69/52 10,500 138x95 3,000

2000 1.61 40.9 570 22.4 2.84 72.2 3.23 82.1 3.55 90.2 5.8 71/53 12,000 138x95 3,000

115 kV power cables

6.1 2.7 50.8 42.0 0.023 0.030 49.0 1.23

6.0 3.0 67.7 42.2 0.017 0.022 55.4 1.39

6.0 3.2 84.6 42.4 0.014 0.018 61.2 1.53

6.0 3.4 101.5 42.6 0.012 0.015 66.8 1.67

6.0 3.5 118.5 42.8 0.010 0.013 71.4 1.79

6.0 3.6 135.4 43.0 0.009 0.011 76.0 1.90

SW Standard Wall xlpe copper neUtral, alUminUm compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

120 550 90 105 250 -10 AEIC, IEC 200 kV / 15 min. 0.0005 2.3
1 2

conductor resistance DC @ 20o C DC @ 90 C


o

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Amps MVA Amps MVA

603 121 509 102

706 141 592 118

796 159 665 133

876 175 729 146

948 189 786 157

1013 202 837 167

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

41

42

Section 4

KNOW YOUR OPTIONS: 138 KV POWER CABLES


43 44

CONDUCTOR MATERIAL AND SIzE


Conductor material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

138 kV power cables

INSULATION THICKNESS
For cables with a radial moisture barrier, Southwire Standard Wall reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended Cables referred to by Traditional Wall insulation (850 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL
Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET
Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

138 kV power cables

Section 4

138 kV XLPE Copper Conductor


TRADITIONAL WALL 850 MIL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall - 850 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Width Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA Nominal in mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 2.79 70.8 3.34 84.8 3.62 91.9 6.8 72/54 6,000

1.12 28.5 2.94 74.6 3.50 89.0 3.78 96.1 7.9 76/57 8,000

1.25 31.8 3.07 78.0 3.65 92.7 3.93 99.8 8.9 79/59 10,000

1.37 34.8 3.19 81.0 3.78 96.0 4.06 103.1 9.9 81/61 12,000

1.48 37.6 3.30 83.8 3.90 99.1 4.18 106.2 10.9 84/63 14,000

1.61 40.9 3.40 86.4 4.02 102.0 4.30 109.1 11.9 86/64 16,000

1.76 44.7 3.66 93.0 4.31 109.4 4.59 116.6 14.1 92/69 20,000

1.92 48.8 3.82 97.1 4.49 113.9 4.77 121.1 16.0 95/71 24,000

2.08 52.8 3.98 101.0 4.66 118.3 4.94 125.4 18.0 99/74 28,000

2.21 56.1

138 kV power cables

4.11 104.4 4.80 122.0 5.08 129.1 19.8 102/76 32,000

typical Shipping reel Size in ft 138x95 3,000 150x95 3,000 150x95 3,000 150x95 2,725 150x95 2,750 158x95 2,775 158x95 2,550 158x95 2,250 158x95 1,925 158x95 1,825

traditional Wall 850 mil xlpe copper corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 240 kV / 15 min. 0.0005 2.3 90 105 250 -10 145 650

6.1 2.4 76.9 41.8 0.014 0.018 41.4 1.24

5.9 2.5 102.5 43.9 0.011 0.014 45.0 1.35

5.7 2.5 128.1 45.7 0.008 0.011 48.3 1.45

5.5 2.6 153.8 47.4 0.007 0.009 51.2 1.54

5.4 2.6 179.4 48.9 0.006 0.008 53.8 1.62

5.3 2.7 205.0 50.3 0.005 0.007 56.3 1.69

5.1 2.7 256.3 54 0.004 0.005 62.4 1.87

5.0 2.8 307.5 56.2 0.003 0.005 66.2 1.99

4.9 2.8 358.8 58.3 0.003 0.004 69.8 2.10

4.9 2.9 410.0 60.2 0.003 0.003 73.0 2.19

Insulation Shield Conductor Sheath

Short circuit for 0.5s3

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

740 177 630 151

850 204 720 173

950 228 800 192

1030 247 870 208

1100 263 930 223

1170 280 970 232

1379 330 1153 276

1515 363 1243 298

1613 386 1316 315

1698 406 1378 330

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

45

46

138 kV power cables

Section 4

138 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 630 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 770 30.3 2.63 66.8 3.16 80.2 3.44 87.4 6.4 69/52 6,000

1.12 28.5 730 28.7 2.70 68.5 3.23 82.1 3.51 89.2 7.3 70/53 8,000

1.25 31.8 700 27.6 2.77 70.4 3.30 83.9 3.58 91.0 8.1 72/54 10,000

1.37 34.8 680 26.8 2.85 72.4 3.39 86.1 3.67 93.2 9.0 73/55 12,000

1.48 37.6 660 26.0 2.92 74.2 3.46 88.0 3.74 95.1 9.9 75/56 14,000

1.61 40.9 650 25.6 3.00 76.3 3.56 90.3 3.84 97.5 10.7 77/58 16,000

1.76 44.7 630 24.8 3.22 81.8 3.81 96.6 4.09 103.8 12.8 82/61 20,000

1.92 48.8 630 24.8 3.38 85.9 3.98 101.1 4.26 108.2 14.6 85/64 24,000

2.08 52.8 630 24.8 3.54 89.8 4.15 105.4 4.43 112.5 16.6 89/66 28,000

2.21 56.1

138 kV power cables

640 25.2 3.69 93.7 4.32 109.7 4.60 116.8 18.4 92/69 32,000

typical Shipping reel Size

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 240 kV / 15 min. 0.0005 2.3 90 105 250 -10 145 650

in ft

126x95 3,000

126x95 3,000

126x95 3,000

126x95 3,000

126x95 2,950

150x95 3,000

150x95 2,725

150x95 2,500

150x95 2,225

150x95 2,000

SW Standard Wall xlpe copper corrUgated SHeatH

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

6.5 2.7 76.9 39.6 0.014 0.018 44.2 1.33

6.5 3.0 102.5 40.5 0.011 0.014 50.0 1.50

6.5 3.2 128.1 41.4 0.008 0.011 55.3 1.66

6.5 3.4 153.8 42.5 0.007 0.009 60.1 1.80

6.5 3.6 179.4 43.4 0.006 0.008 64.7 1.95

6.5 3.7 205.0 44.6 0.005 0.007 68.7 2.06

6.5 3.9 256.3 47.7 0.004 0.005 78.5 2.36

6.3 4.0 307.5 49.9 0.003 0.005 83.5 2.51

6.3 4.0 358.8 52.0 0.003 0.004 88.4 2.65

6.1 4.0 410.0 54.1 0.003 0.003 91.4 2.75

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

750 180 630 151

860 206 730 175

960 230 810 194

1050 251 880 211


3

1110 266 930 223

1180 283 990 237

1423 341 1172 281

1546 370 1267 303

1651 395 1345 322

1746 418 1421 340

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

47

48

Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

138 kV power cables

Section 4

138 kV XLPE Aluminum Conductor


TRADITIONAL WALL 850 MIL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 850 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Sheath
2

750 Nominal in mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 2.79 70.8 3.44 87.4 3.72 94.5 4.5 74/56 4,500 150x95 3,000

1000 1.12 28.5 2.94 74.6 3.61 91.7 3.89 98.8 5.0 78/58 6,000 150x95 3,000

1250 1.25 31.8 3.07 78.0 3.76 95.5 4.04 102.6 5.5 81/61 7,500 158x95 2,925

1500 1.38 35.0 3.19 81.0 3.90 98.9 4.18 106.0 5.9 84/63 9,000 158x95 2,925

1750 1.49 37.8 3.30 83.8 4.02 102.1 4.30 109.2 6.3 86/64 10,500 158x95 2,775

2000 1.61 40.9 3.40 86.4 4.13 105.0 4.41 112.1 6.7 88/66 12,000 158x95 2,800

138 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

6.1 2.4 50.8 47.1 0.023 0.030 41.4 1.24

5.9 2.5 67.7 49.4 0.017 0.022 45.0 1.35

5.7 2.5 84.6 51.4 0.014 0.018 48.3 1.45

5.5 2.6 101.5 53.2 0.012 0.015 51.2 1.54

5.4 2.6 118.5 54.9 0.010 0.013 53.8 1.62

5.3 2.7 135.4 56.5 0.009 0.011 56.3 1.69

Conductor

traditional Wall 850 mil xlpe alUminUm corrUgated SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

conductor resistance DC @ 20o C

145 650 90 105 250 -10 AEIC, IEC 240 kV / 15 min. 0.0005 2.3
1 2 3

DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank*** Power Rating

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Amps MVA Amps MVA

580 139 500 120

680 163 580 139

760 182 640 153

840 201 700 168

900 216 760 182

960 230 800 192

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

49

50

138 kV power cables

Section 4

138 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 650 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3 1

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 770 30.3 2.63 66.8 3.26 82.8 3.54 89.9 4.2 71/53 4,500 126x95 3,000

1000 1.12 28.5 730 28.7 2.70 68.5 3.34 84.7 3.62 91.8 4.5 72/54 6,000 126x95 3,000

1250 1.26 31.9 700 27.6 2.77 70.4 3.41 86.6 3.69 93.7 4.7 74/55 7,500 126x95 2,950

1500 1.38 35.0 680 26.8 2.85 72.4 3.50 88.8 3.78 95.9 5.1 76/57 9,000 126x95 2,950

1750 1.49 37.8 660 26.0 2.92 74.2 3.57 90.7 3.85 97.8 5.4 77/58 10,500 150x95 3,000

2000 1.61 40.9 650 25.6 3.00 76.3 3.67 93.1 3.95 100.3 5.7 79/59 12,000 150x95 3,000

138 kV power cables

6.5 2.7 50.8 44.6 0.023 0.030 44.2 1.33

6.5 3.0 67.7 45.6 0.017 0.022 50.0 1.50

6.5 3.2 84.6 46.6 0.014 0.018 55.3 1.66

6.5 3.4 101.5 47.8 0.012 0.015 60.1 1.80

6.5 3.6 118.5 48.8 0.010 0.013 64.7 1.95

6.5 3.7 135.4 50.1 0.009 0.011 68.7 2.06

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

Conductor Sheath

SW Standard Wall xlpe alUminUm corrUgated SHeatH

145 650 90 105 250 -10 AEIC, IEC 240 kV / 15 min. 0.0005 2.3
1 2

conductor resistance DC @ 20o C DC @ 90 C


o

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Amps MVA Amps MVA

590 142 500 120

690 165 580 139

770 185 650 156

850 204 710 170

920 220 770 185

980 235 810 194

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

51

52

138 kV power cables

Section 4

138 kV XLPE Copper Conductor


TRADITIONAL WALL 850 MIL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 850 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Width Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA Nominal in mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 2.79 70.8 3.17 80.6 3.49 88.7 6.8 70/52 6,000

1.12 28.5 2.94 74.6 3.32 84.4 3.64 92.5 7.8 73/55 8,000

1.25 31.8 3.07 78.0 3.46 87.8 3.78 95.9 8.8 76/57 10,000

1.37 34.8 3.19 81.0 3.58 90.8 3.90 98.9 9.7 78/58 12,000

1.48 37.6 3.30 83.8 3.69 93.6 4.01 101.7 10.7 80/60 14,000

1.61 40.9 3.40 86.4 3.79 96.2 4.11 104.3 11.6 82/62 16,000

1.76 44.7 3.66 93.0 4.07 103.4 4.39 111.5 13.8 88/66 20,000

1.92 48.8 3.82 97.1 4.23 107.5 4.55 115.6 15.6 91/68 24,000

2.08 52.8 3.98 101.0 4.39 111.4 4.71 119.5 17.5 94/71 28,000

2.21 56.1

138 kV power cables

4.11 104.4 4.52 114.8 4.84 123.0 19.3 97/73 32,000

typical Shipping reel Size in ft 138x95 3,000 138x95 3,000 150x95 3,000 150x95 3,000 150x95 2,733 150x95 2,725 158x95 2,700 158x95 2,375 158x95 2,125 158x95 1,900

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 240 kV / 15 min. 0.0005 2.3 90 105 250 -10 145 650

traditional Wall 850 mil xlpe copper neUtralS, copper compoSite laminate SHeatH

6.1 2.4 76.9 43.9 0.014 0.018 41.4 1.24

5.9 2.5 102.5 44.2 0.011 0.014 45.0 1.35

5.7 2.5 128.1 44.6 0.008 0.011 48.3 1.45

5.5 2.6 153.8 44.9 0.007 0.009 51.2 1.54

5.4 2.6 179.4 45.2 0.006 0.008 53.8 1.62

5.3 2.7 205.0 45.5 0.005 0.007 56.3 1.69

5.1 2.7 256.3 46.2 0.004 0.005 62.4 1.87

5.0 2.8 307.5 46.6 0.003 0.005 66.2 1.99

4.9 2.8 358.8 47.0 0.003 0.004 69.8 2.10

4.9 2.9 410.0 47.4 0.003 0.003 73.0 2.19

Insulation Shield Conductor Sheath

Short circuit for 0.5s3

conductor resistance DC @ 20o C DC @ 90 C


o

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

750 180 640 153

870 208 740 177

970 232 820 196

1060 254 890 213

1140 273 950 228

1210 290 1000 240

1455 348 1206 289

1592 381 1314 315

1714 410 1410 338

1821 436 1493 357

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

53

54

138 kV power cables

Section 4

138 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 630 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 770 30.3 2.63 66.8 3.01 76.5 3.33 84.6 6.4 67/50 6,000

1.12 28.5 730 28.7 2.70 68.5 3.08 78.3 3.40 86.4 7.3 68/51 8,000

1.25 31.8 700 27.6 2.77 70.4 3.16 80.1 3.48 88.3 8.1 70/52 10,000

1.37 34.8 680 26.8 2.85 72.4 3.24 82.2 3.56 90.3 8.9 71/53 12,000

1.48 37.6 660 26.0 2.92 74.2 3.31 83.9 3.63 92.1 9.8 73/54 14,000

1.61 40.9 650 25.6 3.00 76.3 3.39 86.1 3.71 94.2 10.6 74/56 16,000

1.76 44.7 630 24.8 3.22 81.8 3.63 92.2 3.95 100.4 12.7 79/59 20,000

1.92 48.8 630 24.8 3.38 85.9 3.79 96.3 4.11 104.4 14.4 82/62 24,000

2.08 52.8 630 24.8 3.54 89.8 3.95 100.2 4.27 108.4 16.3 85/64 28,000

2.21 56.1

138 kV power cables

640 25.2 3.69 93.7 4.10 104.2 4.42 112.3 18.1 88/66 32,000

typical Shipping reel Size Flange x Traverse Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

SW Standard Wall xlpe copper neUtralS, copper compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 240 kV / 15 min. 0.0005 2.3 90 105 250 -10 145 650

in ft

126x95 3,000

138x95 3,000

138x95 3,000

138x95 3,000

138x95 3,000

138x95 2,775

150x95 3,000

150x95 2,625

150x95 2,325

158x95 2,050

kV/mm kV/mm
3

6.5 2.7 76.9 45.4 0.014 0.018 44.2 1.33

6.5 3.0 102.5 43.6 0.011 0.014 50.0 1.50

6.5 3.2 128.1 43.8 0.008 0.011 55.3 1.66

6.5 3.4 153.8 44.0 0.007 0.009 60.1 1.80

6.5 3.6 179.4 44.2 0.006 0.008 64.7 1.95

6.5 3.7 205.0 44.4 0.005 0.007 68.7 2.06

6.5 3.9 256.3 45.0 0.004 0.005 78.5 2.36

6.3 4.0 307.5 45.5 0.003 0.005 83.5 2.51

6.3 4.0 358.8 45.9 0.003 0.004 88.4 2.65

6.1 4.0 410.0 46.3 0.003 0.003 91.4 2.75

Short circuit for 0.5s

kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

760 182 640 153

880 211 740 177

980 235 820 196

1070 256 890 213


3

1150 275 960 230

1220 292 1010 242

1472 352 1214 291

1610 385 1323 317

1733 415 1419 340

1840 440 1502 360

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

55

56

Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

138 kV power cables

Section 4

138 kV XLPE Aluminum Conductor


TRADITIONAL WALL 850 MIL XLPE COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation Traditional Wall 850 mil XLPE True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Width Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Sheath
2

750 Nominal in mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 2.79 70.8 3.18 80.7 3.50 88.8 5.0 70/52 4,500 138x95 3,000

1000 1.12 28.5 2.94 74.6 3.33 84.5 3.65 92.6 5.5 73/55 6,000 138x95 3,000

1250 1.26 31.9 3.07 78.0 3.46 87.8 3.78 96.0 5.9 76/57 7,500 150x95 3,000

1500 1.38 35.0 3.19 81.0 3.58 90.9 3.90 99.0 6.3 78/58 9,000 150x95 3,000

1750 1.49 37.8 3.30 83.8 3.69 93.7 4.01 101.8 6.7 80/60 10,500 150x95 2,725

2000 1.61 40.9 3.40 86.4 3.79 96.3 4.11 104.4 7.1 82/62 12,000 150x95 2,725

138 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

6.1 2.4 50.8 42.9 0.023 0.030 41.4 1.24

5.9 2.5 67.7 43.2 0.017 0.022 45.0 1.35

5.7 2.5 84.6 43.5 0.014 0.018 48.3 1.45

5.5 2.6 101.5 43.8 0.012 0.015 51.2 1.54

5.4 2.6 118.5 44.1 0.010 0.013 53.8 1.62

5.3 2.7 135.4 44.3 0.009 0.011 56.3 1.69

Conductor conductor resistance DC @ 20o C

traditional Wall 850 mil xlpe copper neUtralS, alUminUm compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

145 650 90 105 250 -10 AEIC, IEC 240 kV / 15 min. 0.0005 2.3
1 2 3

DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Amps MVA Amps MVA

590 142 500 120

690 165 580 139

780 187 650 156

860 206 720 173

930 223 770 185

990 237 830 199

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

57

58

138 kV power cables

Section 4

138 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE COPPER NEUTRAL, ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 650 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s2 Conductor Sheath kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3 1

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 770 30.3 2.63 66.8 3.02 76.6 3.34 84.8 4.7 67/50 4,500 126x95 3,000

1000 1.12 28.5 730 28.7 2.70 68.5 3.09 78.4 3.41 86.5 5.0 68/51 6,000 138x95 3,000

1250 1.26 31.9 700 27.6 2.77 70.4 3.16 80.2 3.48 88.4 5.3 70/52 7,500 138x95 3,000

1500 1.38 35.0 680 26.8 2.85 72.4 3.24 82.2 3.56 90.3 5.6 71/53 9,000 138x95 3,000

1750 1.49 37.8 660 26.0 2.92 74.2 3.31 84.0 3.63 92.2 5.9 73/54 10,500 138x95 3,000

2000 1.61 40.9 650 25.6 3.00 76.3 3.39 86.2 3.71 94.3 6.2 74/56 12,000 138x95 2,775

138 kV power cables

6.5 2.7 50.8 42.5 0.023 0.028 44.2 1.33

6.5 3.0 67.7 42.7 0.017 0.021 50.0 1.50

6.5 3.2 84.6 42.8 0.014 0.017 55.3 1.66

6.5 3.4 101.5 43.0 0.012 0.014 60.1 1.80

6.5 3.6 118.5 43.2 0.010 0.012 64.7 1.95

6.5 3.7 135.4 43.4

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

SW Standard Wall xlpe copper neUtral, alUminUm compoSite laminate SHeatH

145 650 90 105 250 -10 AEIC, IEC 240 kV / 15 min. 0.0005 2.3
1 2

conductor resistance DC @ 20o C DC @ 90 C


o

0.009 0.011 68.7 2.06

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating

Amps MVA Amps MVA

600 144 500 120

700 168 590 142

790 189 660 158

870 208 720 173

940 225 780 187

1000 240 830 199

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

59

60

Section 5

KNOW YOUR OPTIONS: 161 KV POWER CABLE


61 62

CONDUCTOR MATERIAL AND SIzE


Conductor material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

161 kV power cables

INSULATION THICKNESS
For cables with a radial moisture barrier, Southwire Standard Wall reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL
Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET
Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

161 kV power cables

Section 5

161 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or MIlliken Super Smooth Conductor Shield Super Clean XLPE Insulation 690 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 840 33.1 2.77 70.3 3.32 84.3 3.60 91.4 6.8 72/54 6,000

1.12 28.5 790 31.1 2.82 71.6 3.36 85.4 3.64 92.5 7.6 73/55 8,000

1.25 31.8 760 29.9 2.89 73.4 3.44 87.5 3.72 94.6 8.4 74/56 10,000

1.37 34.8 730 28.7 2.95 74.9 3.51 89.2 3.79 96.3 9.3 76/57 12,000

1.48 37.6 710 28.0 3.02 76.7 3.58 91.0 3.86 98.1 10.1 77/58 14,000

1.61 40.9 690 27.2 3.08 78.3 3.65 92.7 3.93 99.8 11.0 79/59 16,000

1.76 44.7 700 27.6 3.36 85.3 3.96 100.7 4.24 107.8 13.2 85/64 20,000

1.92 48.8 710 28.0 3.52 89.4 4.14 105.2 4.42 112.3 15.1 88/66 24,000

2.08 52.8 720 28.3 3.72 94.4 4.36 110.6 4.64 117.8 17.1 93/70 28,000

2.21 56.1

161 kV power cables

730 28.7 3.87 98.3 4.52 114.9 4.80 122.0 19.0 96/72 32,000

typical Shipping reel Size

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 280 kV / 15 min. 0.0005 2.3 90 105 250 -10 169 750

in ft

138x95 3,000

126x95 2,950

126x95 2,950

126x95 2,950

150x95 3,000

150x95 3,000

158x95 2,725

150x95 2,450

150x95 2,150

158x95 1,900

SW Standard Wall xlpe copper corrUgated SHeatH

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

7.2 2.8 76.9 41.6 0.014 0.018 41.7 1.46

7.2 3.2 102.5 42.1 0.011 0.014 47.3 1.66

7.2 3.4 128.1 43.1 0.008 0.011 52.2 1.83

7.2 3.6 153.8 44.0 0.007 0.009 57.0 2.00

7.2 3.8 179.4 44.9 0.007 0.008 61.3 2.15

7.2 4.0 205.0 45.7 0.005 0.007 65.6 2.30

6.9 4.0 256.3 49.7 0.004 0.005 72.3 2.53

6.8 4.1 307.5 51.9 0.004 0.005 76.8 2.69

6.6 4.0 358.8 54.6 0.003 0.004 79.4 2.78

6.4 4.0 410.0 56.7 0.003 0.003 82.2 2.88

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

714 200 607 170

842 235 711 199

952 266 799 223

1037 290 866 242


3

1111 310 924 258

1179 329 977 273

1413 395 1163 325

1532 428 1255 350

1633 456 1330 371

1718 480 1393 389

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

63

64

Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

161 kV power cables

Section 5

161 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 690 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) in Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s
2

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 840 33.1 2.77 70.3 3.42 86.9 3.70 94.1 4.5 74/56 4,500 150x95 3,000

1000 1.12 28.5 790 31.1 2.82 71.6 3.47 88.1 3.76 95.5 4.7 75/56 6,000 150x95 3,000

1250 1.26 31.9 760 29.9 2.89 73.4 3.55 90.2 3.83 97.3 5.0 77/57 7,500 150x95 3,000

1500 1.38 35.0 730 28.7 2.95 74.9 3.62 91.9 3.90 99.0 5.3 78/58 9,000 150x95 3,000

1750 1.49 37.8 710 28.0 3.02 76.7 3.70 93.9 3.98 101.0 5.6 80/60 10,500 150x95 3,000

2000 1.61 40.9 690 27.2 3.08 78.3 3.76 95.6 4.04 102.7 5.9 81/61 12,000 150x95 2,725

161 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA
3

7.2 2.8 50.8 46.8 0.023 0.030 41.7 1.46

7.2 3.2 67.7 47.4 0.017 0.022 47.3 1.66

7.2 3.4 84.6 48.5 0.014 0.018 52.2 1.83

7.2 3.6 101.5 49.5 0.012 0.015 57.0 2.00

7.2 3.8 118.5 50.5 0.010 0.013 61.3 2.15

7.2 4.0

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 280 kV / 15 min. 0.0005 2.3
1 2

SW Standard Wall xlpe alUminUm corrUgated SHeatH

Conductor

135.4 51.4 0.009 0.011 65.6 2.30

169 750 90 105 250 -10

Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank3 Power Rating Typical Double Ductbank Power Rating

559 156 475 133

665 186 562 157

758 212 637 178

833 233 697 195

902 252 751 210

969 271 804 225

Amps MVA

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils alluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

65

66

161 kV power cables

Section 5

161 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAM INATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 690 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/ perm.) Maximum Pulling Tension Flange x Traverse Shipping Reel Capacity2 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs

750

1000

1250

1500

1750

2000

2500

3000

3500

4000

0.97 24.7 840 33.1 2.77 70.3 3.15 80.1 3.47 88.2 6.7 69/52 6,000

1.12 28.5 790 31.1 2.82 71.6 3.20 81.3 3.52 89.5 7.5 70/53 8,000

1.25 31.8 760 29.9 2.89 73.4 3.28 83.2 3.60 91.3 8.4 72/54 10,000

1.37 34.8 730 28.7 2.95 74.9 3.34 84.7 3.66 92.8 9.2 73/55 12,000

1.48 37.6 710 28.0 3.02 76.7 3.41 86.5 3.73 94.6 10.0 75/56 14,000

1.61 40.9 690 27.2 3.08 78.3 3.47 88.1 3.79 96.2 10.8 76/57 16,000

1.76 44.7 700 27.6 3.36 85.3 3.69 93.8 4.01 101.9 12.8 80/60 20,000

1.92 48.8 710 28.0 3.52 89.4 3.87 98.3 4.19 106.5 14.6 84/63 24,000

2.08 52.8 720 28.3 3.72 94.4 4.05 102.8 4.37 110.9 16.5 87/65 28,000

2.21 56.1

161 kV power cables

730 28.7 3.87 98.3 4.20 106.7 4.52 114.8 18.4 90/68 32,000

typical Shipping reel Size in ft 138x95 3,000 138x95 3,000 138x95 3,000 138x95 3,000 150x95 3,000 150x95 3,000 150x95 2,725 150x95 2,600 158x95 2,250 158x95 2,025

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 280 kV / 15 min. 0.0005 2.3 90 105 250 -10 169 750

Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C
o

SW Standard Wall xlpe copper neUtralS WitH copper compoSite laminate SHeatH

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA Amps MVA

7.2 2.8 76.9 43.8 0.014 0.018 41.7 1.46

7.2 3.2 102.5 43.9 0.011 0.014 47.3 1.66

7.2 3.4 128.1 44.1 0.008 0.011 52.2 1.83

7.2 3.6 153.8 44.3 0.007 0.009 57.0 2.00

7.2 3.8 179.4 44.5 0.007 0.008 61.3 2.15

7.2 4.0 205.0 44.6 0.005 0.007 65.6 2.30

6.9 4.0 256.3 45.2 0.004 0.005 72.3 2.53

6.8 4.1 307.5 45.7 0.004 0.005 76.8 2.69

6.6 4.0 358.8 46.1 0.003 0.004 79.4 2.78

6.4 4.0 410.0 46.5 0.003 0.003 82.2 2.88

Short circuit for 0.5s3

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank4 Power Rating Typical Double Ductbank4 Power Rating
1 2

724 202 614 172

856 239 721 202

969 271 813 227

1058 296 883 247


3

1136 317 944 264

1209 338 1001 280

1464 409 1209 338

1602 447 1317 368

1723 481 1412 394

1830 511 1495 417

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request.

67

68

Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

161 kV power cables

Section 5

161 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE COPPER NEUTRALS WITH ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 690 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank3 Power Rating
1 2 3

750 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 0.97 24.7 840 33.1 2.77 70.3 3.16 80.2 3.48 88.3 5.0 70/52 4,500 138x95 3,000

1000 1.12 28.5 790 31.1 2.82 71.6 3.21 81.4 3.53 89.6 5.2 71/53 6,000 138x95 3,000

1250 1.26 31.9 760 29.9 2.89 73.4 3.28 83.3 3.60 91.4 5.5 72/54 7,500 138x95 3,000

1500 1.38 35.0 730 28.7 2.95 74.9 3.34 84.8 3.66 92.9 5.8 73/55 9,000 138x95 3,000

1750 1.49 37.8 710 28.0 3.02 76.7 3.41 86.6 3.73 94.7 6.1 75/56 10,500 150x95 3,000

2000 1.61 40.9 690 27.2 3.08 78.3 3.47 88.2 3.79 96.3 6.4 76/57 12,000 150x95 3,000

161 kV power cables

kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit


3

7.2 2.8 50.8 42.8 0.023 0.030 41.7 1.46

7.2 3.2 67.7 42.9 0.017 0.022 47.3 1.66

7.2 3.4 84.6 43.1 0.014 0.018 52.2 1.83

7.2 3.6 101.5 43.3 0.012 0.015 57.0 2.00

7.2 3.8 118.5 43.4 0.010 0.013 61.3 2.15

7.2 4.0 135.4 43.6 0.009 0.011 65.6 2.30

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

Conductor

169 750 90 105 250 -10 AEIC, IEC 280 kV / 15 min. 0.0005 2.3

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

SW Standard Wall xlpe copper neUtral, alUminUm compoSite laminate SHeatH

Amps MVA Amps MVA

566 158 480 134

675 189 569 159

771 216 646 181

848 237 708 198

920 257 765 214

990 277 821 229

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

69

70

Section 6

KNOW YOUR OPTIONS: 230 KV POWER CABLES


71 72

CONDUCTOR MATERIAL AND SIzE


Conductor material is a matter of both customer preference and required current carrying capacity At 230 kV, copper is most common When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

230 kV power cables

INSULATION THICKNESS
For cables with a radial moisture barrier, Southwire(SW) Standard Wall reduced insulation thicknesses within AEIC specification CS9 are recommended For applications requiring smaller cable diameters, cables with reduced insulation thickness are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL
Copper and aluminum corrugated sheaths offer the best mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET
Standard outer jacket: extruded LLDPE with a co-extruded outer semi-conductive polyethylene layer for jacket integrity testing Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

230 kV power cables

Section 6

230 kV XLPE Copper Conductor


SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 850 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Welded Copper Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Nominal in mm Insulation Thickness Diameter over Insulation mils mm in mm Diameter over Sheath in mm Overall Jacket Diameter in mm Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
4 2

1000 1.12 28.5 960 37.8 3.16 80.2 3.75 95.3 4.03 102.4 8.5 81/60 8,000 158x95 2,900

1250 1.25 31.8 910 35.8 3.19 81.0 3.79 96.2 4.07 103.3 9.2 81/61 10,000 158x95 2,925

1500 1.37 34.8 890 35.0 3.27 83.1 3.87 98.4 4.15 105.5 10.1 83/62 12,000 158x95 2,925

1750 1.48 37.6 880 34.6 3.36 85.3 3.98 101.0 4.26 108.1 11.1 85/64 14,000 158x95 2,775

2000 1.61 40.9 870 34.3 3.44 87.5 4.06 103.1 4.34 110.3 12.0 87/65 16,000 158x95 2,775

2500 1.76 44.7 850 33.5 3.66 93.0 4.31 109.4 4.59 116.6 14.1 92/69 20,000 158x95 2,550

3000 1.92 48.8 850 33.5 3.82 97.1 4.49 113.9 4.77 121.1 16.0 95/71 24,000 158x95 2,250

3500 2.08 52.8 850 33.5 3.98 101.0 4.66 118.3 4.94 125.4 18.0 99/74 28,000 158x95 1,925

4000 2.21 56.1 850

230 kV power cables

33.5 4.11 104.4 4.80 121.9 5.08 129.0 19.8 102/76 32,000 158x95 1,825

lbs/ft in lbs in ft

9.0 3.5 102.5 47.0 0.011 0.014 41.6 2.08

9.0 3.9 128.1 47.5 0.008 0.011 46.1 2.31

8.9 4.1 153.8 48.5 0.007 0.009 49.6 2.48

8.8 4.2 179.4 49.8 0.006 0.008 52.5 2.63

8.7 4.3 205.0 50.9 0.005 0.007 55.3 2.77

8.6 4.5 256.3 54.0 0.004 0.005 62.4 3.12

8.5 4.6 307.5 56.2 0.004 0.005 66.2 3.31

8.2 4.7 358.8 58.3 0.003 0.004 69.8 3.49

8.1 4.8

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

Insulation Shield Short circuit for 0.5s


3

SW Standard Wall xlpe copper corrUgated SHeatH

245 1050 90 105 250 -10 AEIC, IEC 330 kV / 30 min. 0.0005 2.3

Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank Power Rating
1 2 3

410.0 60.2 0.003 0.003 73.0 3.65

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Amps MVA Amps MVA

850 339 720 287

950 379 800 319

1030 411 860 343

1100 439 920 367

1170 467 960 383

1372 547 1137 453

1486 592 1225 489

1579 630 1296 517

1659 661 1357 541

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

73

74

230 kV power cables

Section 6

230 kV XLPE Aluminum Conductor


SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 870 mil XLPE minimum True Triple Extrusion and Dry Cured Welded Aluminum Corrugated Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer Firmly Bonded Insulation Shield

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) in Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity Electrical electrical Stress @ Uo Conductor Shield kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit Amps MVA
3 1

1000 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 1.12 28.5 960 37.8 3.16 80.2 3.87 98.2 4.15 105.3 5.5 83/62 6,000 158x95 2,925

1250 1.26 31.9 910 35.8 3.19 81.0 3.90 99.1 4.18 106.2 5.8 84/63 7,500 158x95 2,925

1500 1.38 35.0 890 35.0 3.27 83.1 3.99 101.3 4.27 108.4 6.1 85/64 9,000 158x95 2,750

1750 1.49 37.8 880 34.6 3.36 85.3 4.09 104.0 4.37 111.0 6.5 87/66 10,500 158x95 2,800

2000 1.61 40.9 870 34.3 3.44 87.5 4.18 106.2 4.46 113.3 6.8 89/67 12,000 158x95 2,625

230 kV power cables

9.0 3.5 67.7 52.9 0.017 0.022 41.6 2.08

9.0 3.9 84.6 53.3 0.014 0.018 46.1 2.31

8.9 4.1 101.5 54.5 0.012 0.015 49.6 2.48

8.8 4.2 118.5 56 0.010 0.013 52.5 2.63

8.7 4.3

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

Insulation Shield Short circuit for 0.5s


2

SW Standard Wall xlpe alUminUm corrUgated SHeatH

245 1050 90 105 250 -10 AEIC, IEC 330 kV / 30 min. 0.0005 2.3
1 2

Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C


o

135.4 57.2 0.009 0.011 55.3 2.77

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank3 Power Rating Typical Double Ductbank Power Rating

670 267 570 228

760 303 640 255

830 331 700 279

900 359 750 299

960 383 800 319

Amps MVA

Increased shipping reel capacity can be accommodated on request. Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current. 3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

75

76

230 kV power cables

Section 6

230 kV XLPE Copper Conductor


SW STANDARD WALL, COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Copper, Compressed Conductor or Milliken Super Smooth Conductor Shield Super Clean XLPE Insulation 850 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Copper Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil1 Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Nominal in mm mils mm in mm in mm Overall Jacket Diameter in mm Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity2 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s3 kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
4

1000 1.12 28.5 960 37.8 3.16 80.2 3.54 90.0 3.86 98.1 8.3 77/58 8,000 150x95 3,000

1250 1.25 31.8 910 35.8 3.19 81.0 3.58 90.8 3.90 98.9 9.1 78/58 10,000 150x95 3,000

1500 1.37 34.8 890 35.0 3.27 83.1 3.66 92.8 3.98 101.0 9.9 80/60 12,000 150x95 3,000

1750 1.48 37.6 880 34.6 3.36 85.3 3.75 95.1 4.07 103.3 10.8 81/61 14,000 158x95 2,925

2000 1.61 40.9 870 34.3 3.44 87.5 3.83 97.2 4.15 105.4 11.7 83/62 16,000 158x95 2,925

2500 1.76 44.7 850 33.5 3.66 93.0 4.07 103.4 4.39 111.5 13.8 88/66 20,000 158x95 2,700

3000 1.92 48.8 850 33.5 3.82 97.1 4.23 107.5 4.55 115.6 15.6 91/68 24,000 158x95 2,375

3500 2.08 52.8 850 33.5 3.98 101.0 4.39 111.4 4.71 119.5 17.5 94/71 28,000 158x95 2,100

4000 2.21 56.1 850 33.5 4.11 104.4 4.52 114.8 4.84 123.0 19.3 97/73 32,000 158x95 1,900

230 kV power cables

lbs/ft in lbs in ft

9.0 3.5 102.5 44.8 0.011 0.014 41.6 2.08

9.0 3.9 128.1 44.9 0.008 0.011 46.1 2.31

8.9 4.1 153.8 45.1 0.007 0.009 49.6 2.48

8.8 4.2 179.4 45.3 0.006 0.008 52.5 2.63

8.7 4.3 205 45.6 0.005 0.007 55.3 2.77

8.6 4.5 256.3 46.2 0.004 0.005 62.4 3.12

8.5 4.6 307.5 46.6 0.004 0.005 66.2 3.31

8.2 4.7 358.8 47.0 0.003 0.004 69.8 3.49

8.1 4.8 410 47.4 0.003 0.003 73.0 3.65

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures ( C)
o

SW Standard Wall, copper neUtralS, copper compoSite laminate SHeatH

245 1050 90 105 250 -10 AEIC, IEC 330 kV / 30 min. 0.0005 2.3

Conductor Sheath conductor resistance DC @ 20o C DC @ 90 C


o

Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity

Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank4 Power Rating
1 2

Amps MVA Amps MVA

860 343 730 291

970 387 810 323

1050 419 880 351

1130 451 940 375

1200 479 1000 399

1435 572 1189 474

1507 601 1296 517

1689 673 1389 554

1794 715 1471 587

2500-4000 kcmil conductors are 5 segment Milliken conductors. Increased shipping reel capacity can be accommodated on request. 3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current. 4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

77

78

230 kV power cables

Section 6

230 kV XLPE Aluminum Conductor


SW STANDARD WALL, COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH
CABLE CONSTRUCTION
Reverse Concentric Stranded Aluminum, Compressed Conductor Super Smooth Conductor Shield Super Clean XLPE Insulation 870 mil XLPE minimum True Triple Extrusion and Dry Cured Firmly Bonded Insulation Shield Copper Neutrals with Aluminum Composite Laminate Sheath Polyethylene Jacket with Extruded Semi-Conductive Outer Layer

conductor Size in kcmil Dimensional Conductor Diameter Insulation Thickness Diameter over Insulation Diameter over Sheath Overall Jacket Diameter Total Weight Min. Bending Radius (install/perm.) Maximum Pulling Tension typical Shipping reel Size Flange x Traverse Shipping Reel Capacity1 Electrical electrical Stress @ Uo Conductor Shield Insulation Shield Short circuit for 0.5s kV/mm kV/mm kA kA /kft /kft pF/ft Amps/ kft per circuit
3

1000 Nominal in mm mils mm in mm in mm in mm lbs/ft in lbs in ft 1.12 28.5 960 37.8 3.16 80.2 3.55 90.1 3.87 98.2 6.0 77/58 6,000 150x95 3,000

1250 1.26 31.9 910 35.8 3.19 81.0 3.58 90.9 3.90 99.0 6.2 78/58 7,500 150x95 3,000

1500 1.38 35.0 890 35.0 3.27 83.1 3.66 92.9 3.98 101.1 6.5 80/60 9,000 150x95 3,000

1750 1.49 37.8 880 34.6 3.36 85.3 3.75 95.2 4.07 103.4 6.9 81/61 10,500 158x95 2,925

2000 1.61 40.9 870 34.3 3.44 87.5 3.83 97.3 4.15 105.5 7.2 83/62 12,000 158x95 2,925

230 kV power cables

9.0 3.5 67.7 43.7 0.017 0.022 41.6 2.08

9.0 3.9 84.6 43.8 0.014 0.018 46.1 2.31

8.9 4.1 101.5 44.0 0.012 0.015 49.6 2.48

8.8 4.2 118.5 44.2 0.010 0.013 52.5 2.63

8.7 4.3 135.4 44.4 0.009 0.011 55.3 2.77

SW Standard Wall, copper neUtralS, alUminUm compoSite laminate SHeatH

cable data Voltage Characteristics (kV) Max Voltage Rating BIL Rating Temperatures (oC) Nominal Conductor Max. Emergency Conductor Short Circuit Conductor Minimum Installation Design Characteristics Design Standards Typical Test Voltages XLPE Loss Factor Relative Permittivity AEIC, IEC 330 kV / 30 min. 0.0005 2.3
1 2 3

245 1050 90 105 250 -10

Conductor Sheath conductor resistance DC @ 20o C DC @ 90o C Capacitance Charging Current Ampacity @ 90o C Typical Single Ductbank Power Rating Typical Double Ductbank Power Rating
3

Amps MVA Amps MVA

690 275 580 232

770 307 650 259

850 339 710 283

920 367 770 307

980 391 820 327

Increased shipping reel capacity can be accommodated on request. Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current. 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9 spacing, single-point or cross bonded

79

80

Section 7

KNOW YOUR OPTIONS:

Southwire HV Solutions is proud to be North Americas exclusive supplier of NKT Cables complete line of high voltage cable accessories

HV cable accessories

HV CABLE ACCESSORIES

81

82

HV cable accessories

Section 7

HV cable accessories

Components
Silicone rubber is a preferred material for cable accessories due to its excellent mechanical and electrical properties. For more than 40 years, silicone has been used successfully as high-quality electrical insulation for voltages up to 400 kV. Silicone rubber features high quality electrical insulation, superior corona and tracking resistance, combined with high elasticity. It facilitates multi range application, where one silicone rubber body can be used for various conductor cross sections. Optimal flexibility ensures easy assembly of the accessories. outstanding features of the silicone rubber insulation material are: UV and ozone resistance Durable water rejection Weather and aging resistance Non-flammable, self-extinguishing, heat resistant Applicable for use at temperatures between -50 C and +180 C High elasticity High tracking resistance Unlimited storage life Friendly to the environment

Design Criteria
The specific electrical problems of the cable termination are found at the point between the high-grade solid electrical insulation of the cable and the gaseous insulation air, which has a significantly lower dielectric strength. In order to achieve sufficient insulating clearance, the outer conductive layer of the cable must be stripped to below the end of the core. This causes unacceptably high field intensities at the end of the outer conductive layer (figure 1) which must be eliminated by means of stress control. Figure 2 shows the field of the cable termination controlled capacitively by a funnel shaped electrode. It is dimensioned in such a way that field intensities do not exceed at any point. This prevents harmful partial discharge.

83

84

HV cable accessories

Section 7

Outdoor Termination
FeV-V oUtdoor termination WitH compoSite inSUlator The different versions of this outdoor termination type FEV-V are designed for operation under severe outdoor conditions. Main components of the termination are the composite insulator with upper metal work, metal base plate with supporting insulators and premolded stress cone for electrical field control. Integrated premolded stress control system made of silicone rubber All metal work made of corrosion resistant aluminum alloy Termination is standing on supporting pedestal insulators, so that the cable screen can be isolated from earth Silicone fluid filled Top bolt available in two versions, screw type or press type Different top bolt diameter available suiting to the cable dimensions Type tested on Southwire Cable according to IEEE 48 and IEC 60840

Outdoor Termination
FeV-p oUtdoor termination WitH porcelain inSUlator The different versions of outdoor termination type FEV-P are designed for operation under severe outdoor conditions. Main components of the termination are the porcelain insulator with upper metal work, metal base plate with supporting insulators and premolded stress cone for electrical field control. Integrated premolded stress control system made of silicone rubber All metal work made of corrosion resistant aluminum alloy Termination is standing on supporting pedestal insulators, so that the cable screen can be isolated from earth Silicone fluid filled Top bolt available in two versions, screw type or press type Different top bolt diameter available suiting to the cable dimensions Type tested on Southwire Cable according to IEEE 48 and IEC 60840

HV cable accessories

85

86

HV cable accessories

Section 7

Switchgear and Transformer Termination


KSeV/KteV dry type plUg-in termination Up to 145 kV All versions of dry-type termination are designed for installation in SF6 gas insulated switchgear (GIS) or for installation in the oil filled cable box of the transformer. The complete termination consists of epoxy resin insulator with embedded electrode, fixing ring which is fitted to the cable, comprising metal cable gland, compression device and premolded plug-in stress cone for electrical field control. Plug-in part comprising of four components (stress cone made of silicone rubber, cable gland, connection bolt, spring loaded compression device) Insulator according with IEC 60859 for GIS and transformer termination Conductor connection bolt designed as mechanical screw type connector Combination with different adapter and additional electrodes are available to fulfill the requirements of IEC 60859 Part 1 and 2 and older switchgear housings. Type test certificate in accordance with IEC 60840 available Dead-end plug available

Switchgear and Transformer Termination


SeV/teV epoxy inSUlator termination The termination is designed for direct installation in SF6 gas insulated switchgear (GIS) or in the oil filled cables box of the transformer. Major components of the termination are the pressure tight epoxy resin insulator with embedded electrode, metal fixing ring, metal cable gland and prefabricated stress cone for electrical field control. Integrated prefabricated stress control system with silicon rubber Pressure tight epoxy resin insulator is cast in one piece with integrated insulation ring at the bottom allowing to separate the cable screen from earth. Cable gland made of corrosion resistant aluminum alloy Possible installation position vertical up to 45 then up to 90 with oil expansion vessel required Type test according to IEC 60840 is available

HV cable accessories

87

88

HV cable accessories

Section 7

Joint
Sm premolded Joint This premolded joint in three piece design with compact dimensions is made of silicone rubber. Main components of the standard joint are conductor connection, cable adapters, main joint sleeve and outer protective covering. Integrated premolded stress control system with silicone rubber Three piece design with compact dimensions Screw type or compression conductor connector Minimal tool requirement Version with screen separation available Type tested on Southwire Cable according to IEEE 404 and IEC 60840

Aluminum Cable Clamps


Southwire is proud to introduce its own line of High Voltage Cable Clamps. Made of anodized aluminum, these clamps can accommodate cables diameters ranging from 3 -5 inches. Every set includes the requisite parts (nuts, bolts and washers) for secure mounting and can be equipped with compression springs to accommodate various sheathing options.

HV cable accessories

Cable Diameter 3 4 (76mm 101mm) 4 5 (101mm 127mm) 3 4 (76mm 101mm) 4 5 (101mm 127mm)

Part Number SWHV 809 Size 1 SWHV 809 Size 2 SWHV 809S Size 1 (w/ springs) SWHV 809S Size 2 (w/ springs)

89

90

HV SOLUTIONS
SoUtHWire company One Southwire Drive Carrollton, Georgia 30119 800-444-1700 www.southwire.com
edition 2011.1