GCU-10 Automatic Engine Control

TABLE OF CONTENTS

Section Page

INTRODUCTION ................................................................................................................................... 3
1. FRONT PANEL LAYOUT.................................................................................................................... 3
1.1 FRONT PANEL LAYOUT ............................................................................................................... 3
1.2 REAR PANEL LAYOUT ................................................................................................................. 3
2. OPERATION ...................................................................................................................................... 4
2.1 CONTROL...................................................................................................................................... 4
2.2 AUTO MODE OF OPERATION...................................................................................................... 4
2.3 MANUAL MODE OF OPERATION................................................................................................. 4
2.4 OFF MODE OF OPERATION ........................................................................................................ 4
3. SYSTEM WARNING AND FAILURE DESCRIPTION ........................................................................ 5
3.1 SYSTEM PROTECTION .............................................................................................................. 5
3.2 WARNING MODE ........................................................................................................................ 5
3.3 SHUTDOWN MODE ..................................................................................................................... 5
3.4 DISPLAY FUNCTION DESCRIPTION .......................................................................................... 5
3.5 DISPLAY REFERENCE TABLE ................................................................................................... 5
4. SYSTEM INSTALLATION ................................................................................................................. 6
4.1 SPECIFICATION............................................................................................................................ 6
4.2 WORKING ENVIRONMENT ......................................................................................................... 6
4.3 PANEL CUT-OUT ......................................................................................................................... 6
4.4 UNIT DIMENSIONS ..................................................................................................................... 6
4.5 CONNECTION DETAILS ............................................................................................................... 7
4.6 STANDARD WIRING DIAGRAM.................................................................................................... 8
5. TROUBLE SHOOTING ...................................................................................................................... 9

______________________________________________________________________________________
2
GCU-10 Automatic Engine Control

OPERATION TIMER CONFIGURATION

The Model GCU-10 is an Automatic Generator A-- Pre-Heat Timer


Control Module, designed to meet the demands of Adjustable from 2 to 30sec
the generator industry. The module starts and stops B--Starter Cranking Timer
the generator, and at the same time indicating the Adjustable from 2 to 15 sec
operation status and fault conditions of the genset. If C--Energize to STOP Timer (DIP SW 3 OFF)
it senses a fault it will automatically shuts down the Adjustable from 2 to 15 sec
engine and indicates the engine failure by means of D--Engine Idle (Electronic Governor Idle Control)
eight LED’s. The technician can program the Adjustable from 0 to 300sec. Set to 0 for no idle
module according to different generator E--Engine Cooldown (STOP DELAY)
requirements, as a result complying with different Adjustable from 0 to 300sec. Set to 0 if no
conditions and protections. Cooldown is needed

GCU-10

1. FRONT PANEL LAYOUT DIP SWITCH CONFIGURATION


1.1 FRONT PANEL LAYOUT
Operation of the GCU-10 is by a three position SW 1 - Nominal Frequency
waterproof switch, indicating AUTO, OFF, and ON - 50Hz
MANUAL. OFF - 60Hz

Two LED's indicate POWER ON and ENGINE SW 2 - Battery Voltage


RUNNING and the other eight LED's indicate the ON - 12 Volt
operational status and fault conditions of the genset. OFF - 24 Volt
Each LED indicates; engine start failure, high water
temperature, and low oil pressure, in addition to SW 3 - FUEL
overspeed, underspeed, emergency stop, and low ON - Energize to Start
battery voltage. One extra LED (Exclamation Point) OFF - Energize to Stop Timer
and its corresponding input is a user-defined
SW 4 - LOP Switch Contact
shutdown (For example; Low Fuel, low water,
ON - Close On Fault (NO)
breaker Open, etc.) all LED's have corresponding
OFF - Open on Fault (NC)
picture-graph that are universally recognized.
SW 5 - Crank Disconnect on Oil Pressure
1.2 LAYOUT & CONFIGURATION
ON - Disabled
In the back, the GCU-10 we have a seven-pin (J1) OFF - Enable
and an eight-pin (J2) terminal block and five
adjustment pots in addition to 5 DIP switches for
genset configuration.
_____________________________________________________________________________________
3
GCU-10 Automatic Engine Control

2. OPERATION IN MANUAL & AUTO 2.2 Automatic (Remote Start) Operation


To initiate a start sequence moves the front control By moving the knob to the "AUTO"
knob to MANUAL.
mode, the POWER SOURCE LED
will start flashing indicating the
The LED above the knob then module is in AUTO and the genset
illuminates indicating the generator can start at any time.
is in MANUAL.
In the “AUTO” position, the module monitors input
First, the pre-heat timer begins by energizing terminal 9 for a “REMOTE START” signal. Should a
terminal 4. Do not use terminal 4 if the pre-heat "REMOTE START" signal be detected a start
function is not used sequence similar to previous manual start sequence
is initiated automatically.
After pre-heat ends, the module de-energizes
terminal 4 and begins engine-starting energizing
terminal 11, together with Fuel Solenoid terminal 10, NOTE
and Engine Idle terminal 14 & 15. Even if the generator is executing an Engine
Cooldown, the Module protection system
After a 1 sec. delay, the starter motor engages, and
remains in operation and if any failure
the engine cranks for the length of the cranking
cycle. occurs, the module bypasses the Engine
Cooldown Timer shutting down the
When the engine starts, the starter motor generator immediately.
disengages and locks out by the GCU sensing the
output coming from the generator. Alternatively, the SYSTEM WARNINGS AND FAILURE-
oil pressure switch can serve as an additional PROTECTION SETTINGS
backup crank disconnect,
Engine Fail To Start Reattempt
The ENGINE RUNNING LED will constantly flash
Engine tries 3 times to start
throughout the idle period indicating the GCU is in
IDLE.
Engine High Water Temperature Protection
Shutdown activated after 3 seconds
If the engine does not start the first time, the module
Temperature Switch Type “Normally Open”
will try to start two more times.
Engine Low Oil Pressure Protection
Should the generator fail to start, Shutdown activated after 3 seconds
place the front knob on OFF Set Oil Pressure Switch Type
Normal Open or
(RESET), and then establish why
Normal Close
the engine failed to fire before
making any more start attempts Engine Overspeed Protection
Shutdown activated after 3 seconds
After the generator starts, the module allows Oil If set for 50Hz operation, Overspeed is activated at
Pressure, High Water Temp, underspeed, and the 55 Hz
Auxiliary fault input to stabilize for 20 sec. before If set for 60Hz operation, Overspeed is activated at
triggering any faults. Once the engine is running full 66 Hz
fault protection is on.
Engine Underspeed Protection
By moving the knob to OFF, the genset STOP after Shutdown activated after 5 seconds
normal engine cooldown. In addition, the ENGINE If set for 50Hz operation, Underspeed is activated at
RUNNING LED flashes throughout the cooldown 45 Hz
period showing that the generator is in If set for 60Hz operation, Underspeed is activated at
COOLDOWN. 54 Hz

_____________________________________________________________________________________
4
GCU-10 Automatic Engine Control

Emergency Shutdown 3. SYSTEM INSTALLATION


Shutdown activated by Normal Open Contacts
Install the Model GCU-10 Module on the front panel
Spare / User Define Shutdown by using the two installation clips provided. When
Activated after 5 seconds delay installed in a panel with too much vibration use
Using Normal Open Contacts appropriate anti-vibration isolators.

Low Battery Voltage Warning 4.1 SPECIFICATIONS


Activated after 5 seconds delay
DC Supply 9.0 to 36 V
For 12VDC operation set at 10 V
For 24VDC operation set at 20 V Alternator Input Range 5 ~ 300VAC
Alternator Input
Start-Up Safety-On Period 50/60 Hz
Frequency
The 20 sec. Safety-On timer activates only after Fuel Solenoid Signal
engine idle ends; in this mode, the module ignores 5 Amp @ 12/24VDC
Output
all engine alarms delaying any shutdown until
Safety-On times out, except for Emergency Stop Start Signal Output 5 Amp @ 12/24VDC
and Overspeed Warm up Signal Output 5 Amp @ 12/24VDC
Alarm Signal Output 5 Amp @ 12/24VDC
3.5 ICON REFERENCE TABLE
Idle Control Conductor
5 Amp @ 12/24VDC
ICON DESCRIPTION EXECUTION Capacity
Generator Operating Temperature -20 °C to +70 °C
Power Source
standby in Auto Relative Humidity 90% or Below
Indication
LED Flashing
Power Consumption Under 3VA
Generator LED always ON
Operating When Running Weight 100 gram
Normally Normally

Engine Start 4.2 WORKING ENVIRONMENT


Shutdown
Failure The module works over a wide temperature range
from -20 to +70º C however, make allowances for
High Water temperature rise within the control panel enclosure.
Shutdown Do not mount close to any heat sources without
Temperature
adequately ventilated; also, the humidity inside the
Low Engine Oil control panel should not exceed 90%.
Shutdown
Pressure

Overspeed Shutdown

Underspeed Shutdown

Emergency
Shutdown Shutdown
Activated

Spare Shutdown Shutdown

Low Battery
Warning Only
Voltage Warning

_____________________________________________________________________________________
5
GCU-10 Automatic Engine Control

4.3 PANEL CUT-OUT (mm)

66.0 +1.0
-0.0
66.0 +1.0
-0.0

4.4 UNIT DIMENSIONS (MEASUREMENT (mm)

50.0
72.0 44.0

GCU-10

66.0
72.0

72.0

_____________________________________________________________________________________
6
GCU-10 Automatic Engine Control

4.5 CONNECTION DETAILS


Seven pin din rail terminal J1

PIN No. DESCRIPTION NOTES


1 Generator Sensing Input Connect to Generator Output
Generator Sensing Input Same a Above (Indicate Generator Running and Also
2
Used For Crank Disconnect)
3 Oil Pressure Switch Input Negative Switched Oil Pressure Sender Input
Can Also be Used for Crank Disconnect
Pre-heat Signal Output Hook UP to Engine Pre-heat
4
Max 5 Amps @ Battery Voltage
Use For External Buzzer/Remote Enunciator
5 Failure / Warning Signal Output
Max 5 Amp @ Battery Voltage
6 DC Plant Supply Input (+V) Battery Positive
7 DC Plant Supply Input (-V) Battery Negative

Eight pin din rail terminal J2

PIN No. DESCRIPTION NOTES


8 Auxiliary Input Negative Switches Input
9 Remote Start Input Hook Up to ATS Switch Remote Start Connections
Fuel Solenoid Signal Output Control Fuel Solenoid - Governor ON etc.
10
Max 5 Amp @ Battery Voltage
Start Signal Output To Starter Motor Solenoid Output
11
Max 5 Amps @ Battery Voltage
Emergency Stop Input Negative Switched Emergency Stop Button Input
12
Terminal 12 to B-
Negative Switched Water Temp Sender Input
13 Coolant Temperature switch Input
Terminal 13 to B-
Connect to Governor (Speed Control) Idle control Dry
14 Idle Signal Output
contacts 5 Amp rated
Same as Above (Used to Control a 2 Speed Governor
15 Idle Signal Output
With Idle Control

Rear Panel layout

_____________________________________________________________________________________
7
GCU-10 Automatic Engine Control

4.6 STANDARD WIRING DIAGRAM

J1-1
L
Alternator
AC 5 V~ 300 V

J1-2
N
OIL SW

J1-3

GCU-10 GENERATOR CONTROL UNIT


Temp SW

J2-13
Emergency Stop

J2-12
AUX. Alarm

J1-8
Remote Start

J2-9
J1-7
Battery

J1-6
+

J1-4

5A

Pre-Heat
J2-11

5A

Start
J2-10

5A

Stop

Buzzer
J1-5
BZ

5A

Idle control
J2-14
Governor
Electronic

5A

Idle Control
J2-15

_____________________________________________________________________________________
8
GCU-10 Automatic Engine Control

4. TROUBLE SHOOTING
SYMPTOM PLEASE CHECK REMEDY
• Check Battery Volts on cranking (Not • Change Battery
below 6V)
In “MANUAL MODE”,
the Power Source LED • Check DC supply Voltage • Check and confirm voltage and
does not illuminate and wiring
generator fails to start. • Check DC supply fuse • Change fuse
• None of the above • Change Control Unit
• Check Battery Volts on cranking (Not • Change Battery
below 6V)
In “MANUAL MODE” • Check oil pressure switch type • Correct Oil pressure Switch type
Power Source LED to correct setting
illuminates and Starter
Motor fails to operate. • Check GCU-10 Start signal output • Change Control Unit
• Check Starting motor • Change Starting motor
• Check wiring to see if it is open circuit • Correct the fault point
In “MANUAL MODE” • Check fuel • Add fuel
Power Source LED
• Check wiring of fuel solenoid • Correct Engine Stop Mode setting
illuminates and Starter
Motor fails to crank. • Check Governor and wiring • Change Governor
• Check Battery Volts on cranking (Not • Change Battery
below 6V)
In “MANUAL MODE” • Check Starting circuit and wiring
Starter Motor cranks but • Change Wiring
engine fails to start • Check oil pressure Switch • Change appropriate oil pressure
switch or cancel the Oil Pressure
Detection Engine Start option
• Check AC Input Voltage (5~300VAC) • Change Automatic Voltage
Regulator (AVR)
Starting motor does not • Check wiring to see if it is open circuit • Correct the fault point
disengage after • Check oil pressure switch
generator starts • Change appropriate oil pressure
switch
• Check Starter motor
• Change Starting Motor
Emergency STOP LED • Check emergency stop terminal and • Select emergency stop to normal
ON. Engine not wiring open input
operating And does not
start • Check wiring to see if it is short circuit • Correct the wiring

Low oil pressure LED • Check engine oil pressure • Add engine oil / lubricant
always ON while engine • Check oil pressure switch • Change oil pressure switch
is running • Check wiring to see if it is open circuit • Correct the fault point

High water Temp LED • Check engine temperature • Change water temperature switch
always ON while engine • Check water temperature switch • Correct the fault point
is running • Check wiring for short circuit

_____________________________________________________________________________________
9
GCU-10 Automatic Engine Control

SYMPTOM PLEASE CHECK REMEDY


• Check Engine Pre-heat countdown
In "Auto Mode" the Setting to see if preset time (2 ~ 30
generator does not start sec)has been reached
with a remote start
• Check remote start signal input • Correct the fault point
signal
• Check GCU-10 start signal output • Change Control Unit
• Check wiring to see if it is open circuit • Correct the fault point
• Check Engine Pre-heat Countdown
Pre-heat does not work Setting • Reset settings
• Check GCU-10 Pre-heat signal output
• Change Control Unit
• Check Engine Cooling Countdown time • Reset Engine Cooling
setting (excessive time delayed) Countdown time
• Check Engine Stop Countdown time
Engine does not STOP setting (inadequate time delayed) • Reset Engine Stop Countdown
in OFF • Check Engine Stop Mode setting time
• Check GCU-10 Engine Shutdown • Reset Engine Stop Mode Change
output signal Control Unit
• Check Fuel Solenoid • Change Fuel Solenoid

_____________________________________________________________________________________
10