You are on page 1of 36

718444-YTG-B-0412

TECHNICAL GUIDE
R-410A
AFFINITY SERIES
DNZ MODELS
2 - 5 TON
60 Hertz

Description
These York Affinity packaged cooling/heating air
conditioners are designed for outdoor installation. Only utility
and duct connections are required at the point of installation.
The single or two stage gas-fired heaters have aluminized steel
tubular heat exchangers and spark to pilot ignition. They are
available in natural gas with field conversion to propane.

Tested in accordance with:

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

718444-YTG-B-0412

Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Typical DNZ024-060 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Component Location
Cooling/Gas Unit

Direct Drive
Condenser Fan Motor

Blow-Through Design With


Reliable Aluminized Steel
Tubular Heat Exchangers

Highly Efficient Enhanced Copper


Tube/Aluminum Fin Evaporator Coil
Highly Efficient Enhanced Copper Tube/Enhanced Aluminum Fin
OR Micro-Channel Aluminum Tube/Aluminum Fin Condenser

Long Lasting Powder


Paint Finish

Decorative Protective Coil Guard


(See Features for Details)
Rear and Bottom Return Air
and Supply Airduct Openings

High Efficiency
Compressor Rigidly
Mounted
Pilot Assembly
High Grade Aluminized In-Shot Burners

Heavy Gauge
Removable Base Rails

Low Voltage Terminal Block


Self-Diagnostic Controls

Direct Drive Blower Motor With


Slide-Out Blower Assembly
Power Draft Motor

Automatic Gas Valve (1/2" - NPTF)


High Voltage
Terminal Block

Johnson Controls Unitary Products

718444-YTG-B-0412

Nomenclature
Cooling/Gas Unit

D 3

NZ

036 N 036

06

Product Category

Voltage Code

D = Single Package Air Conditioner

06 = 208/230-1-60
25 = 208/230-3-60
46 = 460-3-60

Product Generation
3 = 3rd Generation
4 = 4th Generation

Product Identifier
NZ = R-410A 13 SEER
Gas Heat/Electric

Factory Installed Gas Heat


N = Single Stage
D = Two Stage (Single Phase Only)

Nominal Cooling Capacity (MBH)


024 = 24,000 BTUH
030 = 30,000 BTUH
036 = 36,000 BTUH

Features and Benefits


Standard Features
Operating Efficiency - All gas units provide a minimum
AFUE of 80% and SEERS of 13.0. All efficiencies exceed
legislated minimum levels.
On Site Flexibility - All model sizes share a common,
compact design cabinet in a single footprint. The installer
has the flexibility of setting one curb and placing the
proper tonnage unit on that curb after the internal load has
been determined. Field convertible duct connections from
side shot to down shot allows the installer to have greater
flexibility with less inventory.
Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections.
The small base dimension means less space is required
on the ground or roof, plus, the installer can fit this unit
between the wheel wells of full size pick-up truck.
All units are completely wired, charged with R-410A and
tested prior to shipment. Unique test stations using a new
state of the art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers at assembly. Vital
run test statistics such as system pressure, motor
currents, air velocity and temperature, unit vibration, and
gas system safeties are monitored and recorded by the
system to insure unit performance.
Equal size, side supply and return duct connections
allows easy hook-up of ducts to match low crawl spaces
without transition pieces.
Utility Connections Made Easy - Gas and electric utility
knockouts are provided through the bottom as well as the
side of the unit. Utility connections can be made quickly and
with a minimum amount of field labor. A field supplied and
field installed electrical disconnect switch must be installed.
Convertible Airflow Design - The bottom duct openings
are covered when they leave the factory ready to be used

Johnson Controls Unitary Products

042 = 42,000 BTUH


048 = 48,000 BTUH
060 = 60,000 BTUH

Nominal Gas Heating Output Capacity


(Nominal Low Gas Heat Output Capacity)
036 = 36,000 BTUH
056 = 56,000 BTUH (36,400 BTUH)
065 = 65,000 BTUH
072 = 72,000 BTUH (46,800 BTUH)
090 = 90,000 BTUH (56,160 BTUH)
110 = 110,000 BTUH (70,200 BTUH)

for a side supply/side return application. If a bottom


supply/bottom return application is desired, you simply
remove the two panels from the bottom of the unit and
place them in the side supply/side return duct openings.
No panel cutting is required and no accessory panel is
necessary. Convertible airflow design allows maximum
field flexibility and minimum inventory.
Condensate Pan - A non-corrosive, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate. Less collection of stagnate
condensate will build-up. The condensate pan conforms
to ASHRAE 62-89 standards (Ventilation for Acceptable
Indoor Air Quality).
Condensate Drain - The 3/4 inch NPTF connection is
rigidly mounted to assure proper fit and leak tight seal.
Durable Finish - The cabinet is made of pre-painted
steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.
Full Perimeter Base Rails - The easily removable base
rails provide a solid foundation for the entire unit and
protects the unit during shipment. The rails provide fork lift
access from all sides, and rigging holes are also provided
so that an overhead crane can be used to place the units
on a roof. On applications where the unit is placed on a
pad, the base will keep the unit off the pad to deter
corrosion. On applications where height is limited, the inch
high base rails may be removed on location.
More Attractive Appearance - A single piece Water
Shed top cover containing a top discharge condenser fan
arrangement requires less square footage on installation
and provides a wider variety of installations. The one
piece design adds greater water integrity. Rounded
corners with water drip edges add to the attractive
appearance. The cabinet panels have a non-fibrous
insulation that will not release insulation fibers into
conditioned area.

718444-YTG-B-0412
Top Discharge - The top discharge condenser fan does
not disrupt neighboring areas or dry-out vegetation
surrounding the unit. The warm air from the top mounted fan
is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.
Condenser Coil Grille - All models utilize a decorative
Wire Form coil guard to provide impact protection
against large objects.
Low Operating Sound Level - The upward air flow
carries the normal operating noise up and away from the
living area. The rigid top panel effectively isolates any
motor sound. Isolator mounted compressor and the
rippled fins of the condenser coil muffle the normal fan
motor and compressor operating sounds. The unique
formed base pan also aids in sound alterations with it's
Super-Structure design. This design strategically places
embossments in the pan for optimum strength and rigidity.

Post Purge Induced Draft Combustion - Exhausts


combustion products from the heat exchanger upon
completion of the heating cycle to prolong the heat
exchanger life.
Self Diagnostic Fan Control Module - Due to this self
diagnostic control, less on site time is required to trouble
shoot these units.
Spark To Pilot Ignition - Provides faster heat delivery.
This ignition is highly reliable, durable and eliminates
nuisance lockouts.
Multi Port In-shot Burners - No field adjustment is
required to mix the air and gas. These burners are
constructed of high-grade corrosion-resistant, aluminizedsteel.

Fan System - All models operate over a wide range of


design conditions with an electrically commutated fan
motor. These units easily match all types of applications
and provide greater on site flexibility to match comfort
requirement. The cooling speed is factory set and can be
field adjusted to a second speed. The heating speed is
factory set to maintain mid point rise at the units heating
input, but can be field adjusted. This allows maximum
comfort conditions.

Low Maintenance - Long life, permanently lubricated


condenser and evaporator fan motor bearings need no
annual maintenance adding greater reliability to the unit.
Blower assembly can be easily cleaned by the unique
Slip- Track slide-out blower assembly.

Simple Control Circuit - A low voltage printed circuit


board contains a diagnostic indicator light and a low
voltage terminal strip. An additional set of pin connectors
is also provided to simplify the field interface of external
controls. Mate-n-lock plug connectors are used. The
electrical control box is not located in the compressor
compartment. The controls are mounted on a Control-Tilt
control panel to allow the access cover to be removed for
trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to
the unit is color/number coded.

Easy Service Access - A large, single panel covers the


electrical and gas controls makes servicing easy. The
blower compartment has an additional large panel with a
built-in handle tab. Removing this panel will allow the
blower assembly to slide-out for easy removal for
maintenance and ease of trouble shooting.

Protected Compressor - The compressor is internally


protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high
pressure relief valve and a temperature sensor which protect
the compressor if undesirable operating conditions occur.
Pressure Switches - High pressure and low pressure/
loss of charge switches standard in all units. When
abnormal conditions are sensed through the pressure
switches, the unit will lock out preventing any further
operation until reset or problem is corrected.
Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat
transfer for maximum efficiency and durability or MicroChannel aluminum tube, aluminum fin for long lasting
durability and efficient operation.
Heat Exchangers - Are corrosion-resistant, aluminizedsteel tubular construction to provide long-life, trouble-free
operation. The unique blow-through design also assures
that condensate does not collect in humid areas when in

the cooling cycle. This adds to longer heat exchanger life


and higher long term efficiencies.

Secured Service Access Ports - Protected, externally


mounted, re-usable service access ports are provided on
both the high and low lines for ease of evacuating and
charging the system. No final field mounting required.

Replacement Parts - The installer requires no special


training to replace any of the components of these units
and does not need to maintain an inventory of unique parts.
System Integration - Each unit has the internal ability to
integrate an electronic air cleaner or humidifier to work in
conjunction with the base unit.

Field Installed Accessories


Low NOx Kit - Kit includes all the necessary hardware
and instructions to field convert units to reduce emissions
to less than 40 nanogram per Joule. California
requirement on single phase models only.
Propane Conversion Kit - Kit includes burner orifices,
gas valve conversion and installation instructions
necessary to field convert unit from natural gas to propane.
High Altitude Conversion Kit (Natural Gas/Propane) - Kit
includes all necessary labels and instructions to field alter
units with natural gas/propane for installations above 2000
feet. Burner orifices must be obtained from Source 1 Parts.
Propane Conversion Kit must be obtained separately.
Economizer Down Discharge/Supply Kit - Modulating
integrated economizer provides simultaneous operation
between the mechanical cooling and economizer
operation. Independent blade design insures proper

Johnson Controls Unitary Products

718444-YTG-B-0412
control and less than 1% leak rate. Includes hood and
mesh bird screen filter integrated into the hood, dry bulb
sensor and relief damper. Separate field accessories of
single enthalpy and dual enthalpy are also available. A
built-in barometric relief of 25% is provided.
Single Enthalpy Sensor - Sensor replaces dry bulb
sensor standard in economizer kit. Provides improved
economizer operation by sensing the dry bulb
temperature from outdoors plus the enthalpy content of
the outdoor air.
Dual Enthalpy Sensor - Additional sensor to single
enthalpy sensor. Sensor senses both the return air
temperature dry bulb and humidity in conjunction with the
single enthalpy to determine the most economical mix.
Single Enthalpy sensor also required.
Hail Guard Kit - Kit contains protective grilles made of
expanded aluminum with full perimeter frame. Sloped
hoods are also included to assure maximum protection.
Anti Short Cycle Timer (DNZ Units Only) - Automatically
prevents the compressor from restarting for 5 minutes after
cycled off.Not required if Thermostat 2ET07700224 and
2ET04700224 are used.
Filter/Frame Kit (Single Phase Only) - Kit contains the
necessary hardware to field install return air filters into the
base unit. Pre-cut filter racks and appropriate cleanable
standard size filters are shipped in one kit. The filter rack
is suitable for either 1" or 2" filters. (1" filter is supplied)
This kit is available for single phase horizontal or vertical
duct application only. Standard in all 3 Phase models.
Motorized Fresh Air Damper - Designed for duct
mounted side supply/return and unit mounted down
supply/return applications. Damper capable of providing
0% through 50% of outdoor air (field supplied). Closes on
power loss, includes hood and screen assembly.
Rectangle To Round Adapters - Kit includes one supply
and one return air rectangle to round duct adapter.
Adapters are preformed and designed to fit over current
duct openings on the base unit. Transition is from side
square duct opening to 14" round duct opening.
Roof Curbs - NRCA approved curbs provide proper fit to
base unit for rooftop installations. Curbs are designed to
be assembled through hinge pins in each corner. Kit also
provides seal strip to assure a water tight seal. 8 and 14
inch high roof curbs are available.
Manual Outdoor Damper - Provides 0% through 50%
outdoor air capability (field adjustable). Designed for duct
mounted side supply/return applications. Includes hood
and screen assembly.
Wall Thermostat - The units are designed to operate with
24-volt electronic and electro-mechanical thermostats. All
units can operate with single stage heat/single stage cool
thermostats - with or without the economizer.
Low Ambient Kit - Kit provides necessary hardware to
convert unit to operate in cooling cycle down to 0 F.
Standard unit operation 45 F.

Johnson Controls Unitary Products

Transformer Kit - Kit provides necessary hardware to


provide single phase models from factory furnished 40 VA
transformer capability to 75 VA transformer capability.
(Required on installations with economizer or motorized
damper.)

Guide Specifications
General
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. YORKs Affinity package units give you
the flexibility and choices you need in todays market. These
packaged cooling/heating air conditioners are designed for
outdoor installation. Only utility and duct connections are
required at the point of installation. The single or two stage gas
fired heaters have aluminized steel tubular heat exchangers
and spark to pilot ignition. They are available in natural gas with
field conversion to propane.
Description
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor mounted
installation. For SEER ratings, refer to technical literature. They
shall have built in, equal size, field convertible duct connections
for down discharge supply/return or horizontal discharge
supply/return. The units shall be factory wired, piped, charged
with R-410A Refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded. All units
shall be manufactured in a facility certified to ISO 9001
standards, and the cooling performance shall be rated in
accordance with DOE and AHRI test procedures. The heating
performance shall be rated to DOE and GAMA test procedures.
Units shall be CSA listed and classified to ANSI Z21.47/CAN/
CSA 2.3 standards and UL 1995/CAN/CSA No. 236-M90
conditions.
Unit Cabinet
Unit cabinet shall be constructed of G-90, pre-paint textured
steel, certified at 500 hours salt spray test per ASTM-B117
standards. The unit top shall be a single piece Water Shed
design, with drip edges and no-seam corners to provide
optimum water integrity. Unit shall have a rigidly mounted
condenser coil guard to provide protection from objects and
personnel after installation. Indoor blower section shall be
insulated with up to 3/4 thick, aluminum, foil faced insulation,
fastened to prevent insulation from entering the air stream.
Cabinet panels shall be large size, easily removable for
servicing and maintenance, with built-in lift handles. Unit shall
be built on a formed, Super-Structure design base pan, with
embossments at critical points to add strength, rigidity and aid
in minimizing sound. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging, for
truck access and proper sealing on roof curb applications. Base
rails shall be removable, when required, to lower unit height.
Filters shall be furnished and be accessible through a
removable access door, sealed airtight. Units vertical discharge
and return duct configuration shall be designed to fit between

718444-YTG-B-0412
standard 24 O.C. beams without modification to building
structure, duct work and base unit. Condensate pan shall be
internally sloped and conform to ASHRAE 62-89 self-draining
standards, with 3/4 NPTF ridged mount connection.
Indoor (Evaporator) Fan Assembly
Fan shall be direct drive design. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume. Bearings shall be
sealed and permanently lubricated for longer life and no
maintenance. Fan assembly shall be Slip Track (slide-out)
design for easy removal and cleaning.
Outdoor (Condenser) Fan Assembly
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to
corrosion resistant steel spider bracket and shall be statically
balanced for smooth operation. The outdoor fan motor shall be
totally enclosed with permanently lubricated bearings and
internally protected against overload conditions.
Refrigerant Components
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of +/- 10%
of the unit nameplate voltage.
b. Shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.

Coils:
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed.
b. Evaporator coil shall be of the direct expansion, blow
through design.
c. Condenser coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed or Mircro-Channel
aluminum tube, aluminum fins.
d. Condenser coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed orifice expansion devices.
b. Filter/strainer to eliminate any foreign matter.
Gas Heating Section (If Equipped)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft
combustion with post purge logic and redundant main gas
valve. The heat exchanger shall be of the tubular type,
constructed of T1-40 aluminized steel for corrosion resistance
and allowing minimum mixed air entering temperature of 40 F.
Burners shall be of the in-shot type, constructed of aluminumcoated steel. All gas piping shall enter the unit cabinet at a
single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of evaporator fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.

Johnson Controls Unitary Products

718444-YTG-B-0412

Physical Data
DNZ024-060 Single Stage Gas Heat
Component
Nominal Tonnage
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point
(MBh)
AHRI net capacity (MBh)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE %
Steady state efficiency (%)
No. burners
No. stages
Temperature Rise Range (F)
Gas Limit Setting (F)
Gas piping connection (in.)
DIMENSIONS (inches)
Length
Width
Height
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (in.)
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
Type
Drive type
No. speeds
Number of motors
Motor HP each
RPM
Nominal total CFM
DIRECT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
FILTERS
Quantity - Size

Models
DNZ042
3.5

DNZ024
2.0

DNZ030
2.5

DNZ036
3.0

24.7

30.8

35.6

24.0
11.6
13.2
850
2.1
R-410A
3-10

30.0
11.5
13.2
940
2.7
R-410A
4-0

34.2
11.1
13.2
1200
3.2
R-410A
4-0

N036 N056
45
70
36
56
80.0
80.0
80
80
2
3
1
1
25-55 30-60
140
160
1/2

N036 N056
45
70
36
56
80.0
80.0
80
80
2
3
1
1
25-55 30-60
140
160
1/2

49 1/8
47 1/4
33 1/2
378

49 1/8
47 1/4
33 1/2
398

49 1/8
47 1/4
33 1/2
402

49 1/8
47 1/4
41 1/2
460

49 1/8
47 1/4
41 1/2
465

49 1/8
47 1/4
41 1/2
480

Recip 1-spd
1

Recip 1-spd
1

Recip 1-spd
1

Recip 1-spd
1

Scroll 1-spd
1

Scroll 1-spd
1

11.9
1
23
0.71/18

11.9
1
23
0.71/18

11.9
1
23
0.71/18

15
1
23
0.71/18

15
1
23
0.71/18

3.4
2
15
3/8
Interlaced
Orifice

3.4
3
13
3/8
Interlaced
Orifice

3.4
3
13
3/8
Interlaced
Orifice

4.4
3
16
3/8
Interlaced
Orifice

4.4
3
16
3/8
Interlaced
TXV

4.4
4
13
3/8
Interlaced
TXV

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/3
1120
3200

1
22
Prop
Direct
1
1
1/3
1120
3200

1
22
Prop
Direct
1
1
1/2
1090
3200

1
10 x 8
Centrifugal
1/2
Variable
48

1
10 x 8
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
1
Variable
48

1
11 x 10
Centrifugal
1
Variable
48

1 - 20 x 20 x 1

1 - 20 x 20 x 1

1 - 20 x 20 x 1

2 - 20 x 12 x 1

2 - 20 x 12 x 1

2 - 20 x 12 x 1

Johnson Controls Unitary Products

N036
45
36
80.0
80
2
1
25-55
140

N056
70
56
80.0
80
3
1
25-55
160
1/2

N072
90
72
80.0
80
4
1
30-60
160

DNZ048
4.0

DNZ060
5.0

43.0

50.0

59.5

41.5
11.6
13.4
1300
3.6
R-410A
4-14

48.0
11.1
13.4
1540
4.4
R-410A
4-4

57.5
10.9
13.0
1600
5.3
R-410A
5-2

N065 N090
80
108
64
87
80.0
80.0
80
80
3
4
1
1
25-55 45-75
150
175
1/2

15
1
23
0.71/18
2-pass Micro-Channel

N065
80
64
80.0
80
3
1
25-55
150

N090
108
87
80.0
80
4
1
35-65
175
1/2

N110
135
108
80.0
80
5
1
45-75
160

N065
80
64
80.0
80
3
1
25-55
150

N090
108
87
80.0
80
4
1
35-65
175
1/2

N110
135
107
80.0
80
5
1
45-75
160

718444-YTG-B-0412

DNZ024-060 Two Stage Gas Heat


Component
Nominal Tonnage
AHRI COOLING PERFORMANCE
Gross Capacity @ AHRI A point (MBh)
AHRI net capacity (MBh)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI HEATING PERFORMANCE
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE %
Steady state efficiency (%)
No. burners
No. stages
Temperature Rise Range (F)
Gas Limit Setting (F)
Gas piping connection (in.)
DIMENSIONS (inches)
Length
Width
Height
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter (in.)
Circuitry Type
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
CONDENSER FAN DATA
Quantity
Fan diameter (Inch)
Type
Drive type
No. speeds
Number of motors
Motor HP each
RPM
Nominal total CFM
DIRECT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
FILTERS
Quantity - Size

Models
DNZ024
2.0

DNZ030
2.5

DNZ036
3.0

DNZ042
3.5

DNZ048
4.0

DNZ060
5.0

24.7
24.0
11.6
13.2
850
2.1
R-410A
3-10

30.8
30.0
11.5
13.2
940
2.7
R-410A
4-0

35.6
34.2
11.1
13.2
1200
3.2
R-410A
4-0

43.0
41.5
11.6
13.4
1300
3.6
R-410A
4-14

50.0
48.0
11.6
13.4
1540
4.4
R-410A
4-4

59.5
57.5
10.9
13.0
1600
5.3
R-410A
5-2

D056
70/45.5
56/36.4
80.0
80
3
2
30-60
160
1/2

D056
70/45.5
56/36.4
80.0
80
3
2
30-60
160
1/2

D056
D072
70/45.5 90/58.5
56/36.4 72/46.8
80.0
80.0
80
80
3
4
2
2
25-55
30-60
160
160
1/2

D090
108/70.2
87/56.2
80.0
80
4
2
45-75
175
1/2

49 1/8
47 1/4
33 1/2
378

49 1/8
47 1/4
33 1/2
398

49 1/8
47 1/4
33 1/2
402

49 1/8
47 1/4
41 1/2
460

49 1/8
47 1/4
41 1/2
465

49 1/8
47 1/4
41 1/2
480

Recip 1-spd
1

Recip 1-spd
1

Recip 1-spd
1

Recip 1-spd
1

Scroll 1-spd
1

Scroll 1-spd
1

11.9
1
23
0.71/18

11.9
1
23
0.71/18

15
1
23
0.71/18

15
1
23
0.71/18

3.4
2
15
3/8
Interlaced
Orifice

3.4
3
13
3/8
Interlaced
Orifice

3.4
3
13
3/8
Interlaced
Orifice

4.4
3
16
3/8
Interlaced
Orifice

4.4
3
16
3/8
Interlaced
TXV

4.4
4
13
3/8
Interlaced
TXV

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/4
1100
2400

1
22
Prop
Direct
1
1
1/3
1100
3200

1
22
Prop
Direct
1
1
1/3
1100
3200

1
22
Prop
Direct
1
1
1/2
1090
3200

1
10 x 8
Centrifugal
1/2
Variable
48

1
10 x 8
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
3/4
Variable
48

1
11 x 10
Centrifugal
1
Variable
48

1
11 x 10
Centrifugal
1
Variable
48

1 - 20 x 20 x 1

1 - 20 x 20 x 1

1 - 20 x 20 x 1

2 - 20 x 12 x 1

2 - 20 x 12 x 1

2 - 20 x 12 x 1

11.9
15
1
1
23
23
0.71/18
0.71/18
2-pass Micro-Channel

D090
D110
D090
D110
108/70.2 135/87.8 108/70.2 135/87.8
87/56.2 108/70.2 87/56.2 108/70.2
80.0
80.0
80.0
80.0
80
80
80
80
4
5
4
5
2
2
2
2
35-65
45-75
35-65
45-75
175
170
175
170
1/2
1/2

Johnson Controls Unitary Products

718444-YTG-B-0412
DNZ Unit Limitations
Size
(Tons)

Model

Unit Voltage

Unit Limitations
Applied Voltage
Min
Max

024
(2.0)

DNZ

208/230-1-60

187

252

125

030
(2.5)

DNZ

036
(3.0)

DNZ

042
(3.5)

DNZ

048
(4.0)

DNZ

060
(5.0)

DNZ

208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60

187
187
432
187
187
432
187
187
432
187
187
432
187
187
432

252
252
504
252
252
504
252
252
504
252
252
504
252
252
504

125
125
125
125
125
125
125
125
125
115
115
115
115
115
115

Johnson Controls Unitary Products

Outdoor DB Temp
Max (F)

718444-YTG-B-0412

Capacity Performance
DNZ024-060 Cooling Capacities
DNZ024 (2.0 Ton)
Air on
Evaporator Coil
CFM

500

600

700

800

900

1000

10

WB
(F)

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

29.9
28.3
26.6
25.0
30.2
28.5
26.9
25.3
26.4
30.5
28.8
27.2
25.6
26.7
30.8
29.1
27.4
25.9
27.0
30.0
28.2
26.6
27.8
30.8
29.0
27.3
28.5

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

4.7
11.7
17.9
23.8
7.8
14.7
21.6
24.5
26.4
10.8
17.6
25.2
25.2
26.7
13.8
20.6
27.4
25.9
27.0
20.4
28.2
26.6
27.8
20.1
29.0
27.3
28.5

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

4.0
9.7
15.4
16.8
5.5
12.4
19.3
19.9
22.0
7.0
15.1
23.2
22.9
24.5
8.4
17.8
27.1
25.9
27.0
17.1
26.2
26.6
27.8
16.4
25.2
27.3
28.5

2.1
7.7
13.4
12.3
3.2
10.1
17.0
16.0
18.2
4.4
12.5
20.7
19.8
22.4
5.6
14.9
24.3
23.5
26.6
13.8
22.9
23.5
26.5
12.6
21.4
23.4
26.4

5.8
11.4
10.3
7.9
14.8
13.8
15.9
10.0
18.1
17.2
19.8
12.1
21.5
20.7
23.7
10.5
19.5
20.2
23.2
8.8
17.6
19.6
22.7

9.5
8.3
12.5
11.5
13.7
15.6
14.7
17.3
18.6
17.9
20.9
16.2
16.9
19.9
13.9
15.9
18.9

6.3
9.2
11.4
12.1
14.7
15.0
18.1
13.6
16.6
12.1
15.1

26.9
25.4
23.8
21.7
27.7
26.1
24.6
22.4
23.7
28.5
26.9
25.3
23.1
24.4
29.3
27.7
26.0
23.7
25.1
28.0
26.4
24.0
25.4
28.4
26.7
24.4
25.8

1.8
1.8
1.7
1.7
1.8
1.8
1.8
1.7
1.7
1.8
1.8
1.8
1.7
1.7
1.8
1.8
1.8
1.7
1.8
1.8
1.8
1.7
1.8
1.8
1.8
1.7
1.8

90

9.1
13.6
18.0
21.1
10.9
15.8
20.7
22.0
23.7
12.6
18.0
23.3
22.9
24.4
14.4
20.2
26.0
23.7
25.1
20.9
26.4
24.0
25.4
21.6
26.7
24.4
25.8

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

7.4
11.6
15.7
17.6
8.6
13.5
18.4
19.7
21.5
9.8
15.4
21.0
21.7
23.3
11.0
17.3
23.6
23.7
25.1
17.7
24.0
24.0
25.4
18.0
24.4
24.4
25.8

5.3
9.5
13.7
14.8
6.2
11.2
16.1
17.4
19.2
7.2
12.8
18.4
19.9
21.9
8.1
14.4
20.8
22.4
24.7
14.4
20.8
22.4
24.7
14.4
20.8
22.4
24.7

7.5
11.7
12.8
8.8
13.7
15.0
16.8
10.2
15.8
17.3
19.3
11.5
17.9
19.5
21.8
11.2
17.5
19.2
21.5
10.8
17.1
18.8
21.1

9.7
10.8
11.4
12.7
14.5
13.2
14.7
16.7
15.0
16.6
19.0
14.2
15.9
18.2
13.5
15.2
17.5

65

8.7
10.4
12.2
12.1
14.1
13.7
16.1
12.7
15.0
11.6
13.9

Johnson Controls Unitary Products

718444-YTG-B-0412
DNZ024 (2.0 Ton) (Continued)
Air on
Evaporator Coil
CFM

500

600

700

800

900

1000

WB
(F)

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57

23.9
22.5
21.1
18.5
25.2
23.7
22.3
19.5
21.0
26.5
24.9
23.4
20.5
22.1
27.8
26.2
24.6
21.5
23.2
26.1
24.5
21.5
23.1
26.1
24.5
21.4
23.1

2.0
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
2.0
1.9
1.9
1.9

12.8
15.5
18.2
18.5
14.0
16.9
19.8
19.5
21.0
15.2
18.3
21.5
20.5
22.1
16.4
19.8
23.1
21.5
23.2
21.5
23.8
21.5
23.1
23.2
24.5
21.4
23.1

Johnson Controls Unitary Products

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
95F

10.7
13.4
16.1
18.5
11.6
14.5
17.5
19.5
21.0
12.6
15.7
18.8
20.5
22.1
13.5
16.8
20.1
21.5
23.2
18.3
21.9
21.5
23.1
19.7
23.6
21.4
23.1

8.6
11.3
14.0
17.4
9.3
12.2
15.1
18.7
20.1
9.9
13.0
16.1
20.0
21.5
10.6
13.9
17.2
21.3
22.9
15.0
18.7
21.4
23.0
16.2
20.1
21.4
23.1

9.2
11.9
15.3
9.8
12.7
16.3
17.7
10.4
13.5
17.3
18.8
10.9
14.3
18.4
20.0
11.8
15.4
18.2
19.8
12.8
16.6
18.0
19.6

9.9
13.2
10.3
13.9
15.4
10.8
14.7
16.2
11.3
15.4
17.0
12.2
14.9
16.6
13.2
14.5
16.1

11.1
11.6
13.0
12.0
13.5
12.5
14.1
11.7
13.4
11.0
12.7

22.8
20.8
18.7
17.0
24.0
21.8
19.7
17.8
19.1
25.1
22.9
20.6
18.7
20.0
26.3
23.9
21.5
19.5
21.0
24.0
21.7
19.7
21.1
24.2
21.8
19.8
21.2

2.1
2.1
2.0
2.0
2.1
2.1
2.0
2.0
2.0
2.1
2.1
2.0
2.0
2.0
2.1
2.1
2.1
2.0
2.0
2.1
2.1
2.0
2.1
2.1
2.1
2.1
2.1

90

11.4
14.3
17.3
17.0
13.5
16.0
18.4
17.8
19.1
15.6
17.6
19.6
18.7
20.0
17.7
19.2
20.8
19.5
21.0
20.7
21.3
19.7
21.1
22.2
21.8
19.8
21.2

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
105F

9.3
12.2
15.2
17.0
10.5
13.5
16.5
17.8
19.1
11.8
14.8
17.9
18.7
20.0
13.0
16.2
19.3
19.5
21.0
17.4
20.3
19.7
21.1
18.6
21.3
19.8
21.2

7.4
10.2
12.9
15.1
8.1
11.1
14.1
16.6
17.7
8.8
12.1
15.4
18.0
19.2
9.5
13.1
16.6
19.4
20.7
14.0
17.8
19.6
21.0
15.0
19.1
19.8
21.2

8.1
10.8
13.0
8.7
11.7
14.1
15.2
9.4
12.6
15.2
16.4
10.0
13.5
16.4
17.6
10.7
14.5
16.3
17.6
11.4
15.5
16.2
17.6

8.7
11.0
9.3
11.7
12.8
9.9
12.5
13.7
10.5
13.3
14.5
11.2
12.9
14.3
11.9
12.6
14.0

65

8.9
9.3
10.4
9.8
10.9
10.2
11.5
9.6
11.0
9.0
10.4

11

718444-YTG-B-0412
DNZ024 (2.0 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

500

72
67
62
77
72

600

67
62
57
77
72

700

67
62
57
77
72

800

67
62
57
72

900

67
62
57
72

1000

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

21.8
19.1
16.3
15.5
22.8
19.9
17.1
16.2
17.3
23.8
20.8
17.8
16.9
18.0
24.7
21.6
18.5
17.6
18.8
22.0
18.8
17.8
19.1
22.3
19.1
18.1
19.4

2.3
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.2
2.3
2.3
2.2
2.2
2.2
2.3
2.2
2.2
2.2
2.3
2.2
2.2
2.2

10.0
13.2
16.3
15.5
13.0
15.0
17.1
16.2
17.3
15.9
16.9
17.8
16.9
18.0
18.9
18.7
18.5
17.6
18.8
20.0
18.8
17.8
19.1
21.2
19.1
18.1
19.4

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

7.9
11.1
14.2
15.5
9.5
12.5
15.6
16.2
17.3
11.0
14.0
17.1
16.9
18.0
12.5
15.5
18.5
17.6
18.8
16.5
18.8
17.8
19.1
17.5
19.1
18.1
19.4

6.2
9.0
11.8
12.9
7.0
10.1
13.2
14.4
15.2
7.8
11.2
14.6
16.0
16.9
8.5
12.3
16.0
17.6
18.5
13.0
17.0
17.8
18.9
13.8
18.0
18.1
19.4

6.9
9.7
10.8
7.6
10.7
12.0
12.8
8.3
11.8
13.2
14.0
9.1
12.8
14.3
15.3
9.6
13.6
14.4
15.5
10.1
14.3
14.4
15.7

7.6
8.7
8.3
9.5
10.3
8.9
10.3
11.2
9.6
11.1
12.1
10.1
10.9
12.0
10.6
10.7
11.9

6.6
7.1
7.8
7.5
8.4
7.9
8.9
7.5
8.5
7.0
8.2

20.8
17.4
14.0
14.0
21.6
18.0
14.5
14.6
15.5
22.4
18.7
15.0
15.1
16.0
23.2
19.3
15.5
15.6
16.5
19.9
15.9
16.0
17.0
20.4
16.4
16.5
17.5

2.4
2.4
2.3
2.3
2.4
2.4
2.3
2.3
2.3
2.5
2.4
2.3
2.3
2.3
2.5
2.4
2.3
2.3
2.4
2.4
2.4
2.3
2.4
2.4
2.4
2.4
2.4

90

10.0
12.0
14.0
14.0
13.7
14.1
14.5
14.6
15.5
17.3
16.1
15.0
15.1
16.0
20.9
18.2
15.5
15.6
16.5
19.2
15.9
16.0
17.0
20.3
16.4
16.5
17.5

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

5.9
9.9
14.0
14.0
8.6
11.6
14.5
14.6
15.5
11.4
13.2
15.0
15.1
16.0
14.2
14.8
15.5
15.6
16.5
15.6
15.9
16.0
17.0
16.4
16.4
16.5
17.5

5.1
7.8
10.6
10.6
5.9
9.1
12.2
12.3
12.8
6.7
10.3
13.8
14.0
14.5
7.5
11.5
15.5
15.6
16.3
12.0
15.9
16.0
16.9
12.6
16.4
16.5
17.5

5.8
8.5
8.5
6.5
9.7
9.8
10.3
7.3
10.9
11.1
11.6
8.1
12.1
12.3
13.0
8.4
12.6
12.5
13.3
8.8
13.2
12.7
13.7

6.5
6.5
7.2
7.3
7.8
8.0
8.2
8.7
8.8
9.0
9.6
9.0
8.9
9.7
9.3
8.8
9.9

65

4.4
4.8
5.3
5.2
5.8
5.6
6.3
5.3
6.1
5.0
6.0

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

12

Johnson Controls Unitary Products

718444-YTG-B-0412

DNZ030 (2.5 Ton)


Air on
Evaporator Coil
CFM

WB
(F)
77

850

72
67
62
57
77

900

72
67
62
57
77

950

72
67
62
57
72

1000

67
62
57
72

1125

67
62
57
72

1250

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

35.3
33.5
31.6
29.7
37.1
35.1
33.2
31.2
29.9
38.8
36.8
34.8
32.7
31.3
40.6
38.5
36.4
34.2
32.8
39.1
37.0
34.7
33.3
39.8
37.6
35.3
33.8

2.1
2.1
2.1
2.0
2.1
2.1
2.1
2.0
2.0
2.1
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1

15.9
20.8
25.7
29.7
17.0
22.4
27.8
31.2
29.9
18.0
24.0
29.9
32.7
31.3
19.1
25.6
32.0
34.2
32.8
26.5
34.1
34.7
33.3
27.4
36.1
35.3
33.8

32.4
30.0
27.5
25.1
34.1
31.5
28.9
26.4
26.2
35.7
33.0
30.3
27.6
27.4
37.4
34.6
31.7
28.9
28.7
35.1
32.2
29.3
29.1
35.6
32.7
29.8
29.6

2.6
2.5
2.5
2.4
2.6
2.5
2.5
2.4
2.4
2.6
2.5
2.5
2.4
2.4
2.6
2.6
2.5
2.5
2.5
2.6
2.5
2.5
2.5
2.6
2.5
2.5
2.5

17.1
20.9
24.7
25.1
18.3
22.4
26.5
26.4
26.2
19.5
23.9
28.4
27.6
27.4
20.7
25.5
30.3
28.9
28.7
27.3
31.5
29.3
29.1
29.1
32.7
29.8
29.6

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

12.6
17.5
22.4
27.6
13.7
19.1
24.5
29.8
29.9
14.7
20.7
26.6
32.0
31.3
15.8
22.2
28.7
34.2
32.8
22.9
29.6
34.7
33.3
23.6
30.4
35.3
33.8

90

9.3
14.2
19.0
22.8
10.4
15.8
21.2
25.3
27.1
11.4
17.3
23.3
27.9
29.9
12.5
18.9
25.4
30.4
32.6
19.4
26.0
32.1
33.2
19.8
26.6
33.8
33.8

10.8
15.7
19.5
12.4
17.8
22.0
23.8
14.0
20.0
24.6
26.6
15.6
22.1
27.1
29.3
15.8
22.4
28.6
29.7
16.0
22.8
30.0
30.0

12.4
16.1
14.5
18.7
20.5
16.7
21.3
23.2
18.8
23.8
26.0
18.9
25.0
26.1
19.0
26.2
26.2

12.8
15.4
17.2
17.9
19.9
20.5
22.7
21.5
22.5
22.4
22.4

33.9
31.7
29.6
27.4
35.6
33.3
31.1
28.8
28.0
37.3
34.9
32.5
30.2
29.4
39.0
36.5
34.0
31.5
30.7
37.1
34.6
32.0
31.2
37.7
35.1
32.5
31.7

2.3
2.3
2.3
2.2
2.4
2.3
2.3
2.2
2.2
2.4
2.3
2.3
2.3
2.3
2.4
2.3
2.3
2.3
2.3
2.4
2.3
2.3
2.3
2.4
2.3
2.3
2.3

16.5
20.8
25.2
27.4
17.6
22.4
27.2
28.8
28.0
18.8
24.0
29.1
30.2
29.4
19.9
25.5
31.1
31.5
30.7
26.9
32.8
32.0
31.2
28.2
34.4
32.5
31.7

10.2
14.0
17.8
21.9
11.1
15.2
19.3
23.9
24.5
12.0
16.5
20.9
25.9
26.5
12.9
17.7
22.5
27.8
28.6
19.0
24.1
28.8
29.1
20.2
25.7
29.8
29.6

10.5
14.3
18.5
11.6
15.8
20.3
20.9
12.8
17.2
22.1
22.8
13.9
18.7
24.0
24.7
14.8
20.0
24.7
24.9
15.8
21.3
25.4
25.2

10.8
15.0
12.2
16.7
17.3
13.5
18.4
19.1
14.8
20.1
20.8
15.8
20.5
20.8
16.9
21.0
20.7

11.6
13.1
13.8
14.7
15.4
16.2
17.0
16.4
16.6
16.5
16.3

30.7
27.8
24.9
23.0
32.1
29.1
26.1
24.1
24.0
33.4
30.3
27.2
25.1
25.0
34.8
31.6
28.3
26.1
26.0
32.1
28.8
26.5
26.5
32.6
29.2
27.0
26.9

2.8
2.7
2.6
2.6
2.8
2.7
2.7
2.6
2.6
2.8
2.7
2.7
2.6
2.6
2.8
2.8
2.7
2.6
2.6
2.8
2.7
2.7
2.7
2.8
2.7
2.7
2.7

17.4
20.4
23.5
23.0
18.8
21.8
24.9
24.1
24.0
20.2
23.2
26.2
25.1
25.0
21.6
24.6
27.6
26.1
26.0
26.4
28.4
26.5
26.5
28.2
29.2
27.0
26.9

95F
77
850

72
67
62
57
77

900

72
67
62
57
77

950

72
67
62
57
72

1000

67
62
57
72

1125

67
62
57
72

1250

67
62
57

Johnson Controls Unitary Products

13.7
17.4
21.2
25.1
14.7
18.8
22.9
26.4
26.2
15.8
20.2
24.7
27.6
27.4
16.8
21.6
26.4
28.9
28.7
23.1
28.3
29.3
29.1
24.7
30.1
29.8
29.6

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

13.1
17.5
21.8
26.3
14.2
18.9
23.7
28.1
28.0
15.2
20.4
25.6
29.8
29.4
16.3
21.9
27.6
31.5
30.7
23.0
28.9
32.0
31.2
24.1
30.3
32.5
31.7

65

9.7
14.1
18.4
22.4
10.7
15.5
20.3
24.6
25.8
11.7
16.9
22.1
26.9
28.2
12.7
18.3
24.0
29.1
30.6
19.2
25.1
30.5
31.1
20.0
26.2
31.8
31.7

10.7
15.0
19.0
12.0
16.8
21.2
22.4
13.4
18.6
23.4
24.7
14.7
20.4
25.6
27.0
15.3
21.2
26.6
27.3
15.9
22.0
27.7
27.6

11.6
15.6
13.3
17.7
18.9
15.1
19.8
21.2
16.8
22.0
23.4
17.4
22.8
23.4
17.9
23.6
23.5

12.2
14.3
15.5
16.3
17.6
18.4
19.8
18.9
19.6
19.5
19.4

9.4
13.1
16.9
20.1
10.2
14.3
18.4
21.9
22.2
11.1
15.5
20.0
23.7
24.0
11.9
16.7
21.5
25.6
25.9
17.9
23.0
26.3
26.4
19.0
24.5
27.0
26.9

9.5
13.2
16.4
10.6
14.7
18.2
18.4
11.7
16.2
19.9
20.2
12.8
17.6
21.7
21.9
13.6
18.8
22.0
22.1
14.5
19.9
22.4
22.3

9.6
12.8
10.9
14.4
14.7
12.3
16.1
16.3
13.7
17.7
18.0
14.5
17.8
17.9
15.4
17.8
17.7

9.1
10.7
10.9
12.2
12.5
13.8
14.1
13.5
13.6
13.2
13.1

105F

13.0
16.8
20.6
23.0
14.0
18.1
22.2
24.1
24.0
14.9
19.4
23.8
25.1
25.0
15.9
20.7
25.5
26.1
26.0
22.1
26.7
26.5
26.5
23.6
28.0
27.0
26.9

13

718444-YTG-B-0412
DNZ030 (2.5 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

850

72
67
62
57
77

900

72
67
62
57
77

950

72
67
62
57
72

1000

67
62
57
72

1125

67
62
57
72

1250

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

29.0
25.7
22.4
21.0
30.0
26.6
23.2
21.8
21.8
31.1
27.6
24.1
22.5
22.6
32.2
28.6
24.9
23.3
23.4
29.1
25.3
23.7
23.8
29.6
25.8
24.2
24.2

3.0
2.9
2.8
2.8
3.0
2.9
2.8
2.8
2.8
3.0
2.9
2.9
2.8
2.8
3.1
3.0
2.9
2.8
2.8
3.0
2.9
2.8
2.9
3.0
2.9
2.9
2.9

17.6
20.0
22.4
21.0
19.3
21.2
23.2
21.8
21.8
20.9
22.5
24.1
22.5
22.6
22.6
23.7
24.9
23.3
23.4
25.5
25.3
23.7
23.8
27.4
25.8
24.2
24.2

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

12.4
16.1
19.9
21.0
13.2
17.3
21.5
21.8
21.8
14.1
18.5
23.0
22.5
22.6
14.9
19.7
24.6
23.3
23.4
21.2
25.2
23.7
23.8
22.6
25.8
24.2
24.2

8.5
12.3
16.0
18.2
9.3
13.4
17.6
19.9
19.8
10.1
14.6
19.1
21.6
21.5
10.9
15.7
20.6
23.3
23.2
16.8
21.9
23.7
23.7
17.8
23.3
24.2
24.2

8.4
12.2
14.3
9.5
13.6
16.0
15.9
10.6
15.1
17.7
17.5
11.7
16.6
19.3
19.2
12.4
17.6
19.4
19.3
13.1
18.6
19.4
19.5

8.3
10.5
9.7
12.1
12.0
11.2
13.7
13.6
12.6
15.3
15.2
13.2
15.0
14.9
13.8
14.7
14.7

6.6
8.2
8.1
9.8
9.6
11.3
11.2
10.6
10.6
9.9
9.9

27.2
23.5
19.8
18.9
28.0
24.2
20.4
19.5
19.6
28.8
24.9
20.9
20.0
20.1
29.6
25.5
21.5
20.5
20.7
26.1
21.9
21.0
21.1
26.6
22.4
21.4
21.5

3.3
3.1
3.0
3.0
3.3
3.1
3.0
3.0
3.0
3.3
3.2
3.0
3.0
3.0
3.3
3.2
3.0
3.0
3.0
3.2
3.1
3.0
3.0
3.2
3.1
3.1
3.1

90

19.3
19.6
19.8
18.9
21.0
20.7
20.4
19.5
19.6
22.6
21.8
20.9
20.0
20.1
24.2
22.9
21.5
20.5
20.7
24.7
21.9
21.0
21.1
26.5
22.4
21.4
21.5

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

11.2
15.5
19.8
18.9
12.8
16.6
20.4
19.5
19.6
14.5
17.7
20.9
20.0
20.1
16.1
18.8
21.5
20.5
20.7
20.2
21.9
21.0
21.1
21.6
22.4
21.4
21.5

7.7
11.4
15.2
16.3
8.4
12.5
16.7
17.9
17.4
9.1
13.6
18.1
19.5
18.9
9.9
14.7
19.6
20.5
20.5
15.7
20.9
21.0
21.0
16.6
22.1
21.4
21.5

7.4
11.1
12.3
8.5
12.6
13.8
13.3
9.6
14.1
15.4
14.9
10.7
15.5
17.0
16.4
11.2
16.4
16.7
16.5
11.7
17.2
16.4
16.6

7.1
8.2
8.5
9.8
9.3
10.0
11.4
10.8
11.5
12.9
12.4
11.9
12.2
12.0
12.3
11.5
11.7

65

4.1
5.7
5.2
7.3
6.7
8.9
8.3
7.7
7.5
6.6
6.7

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

14

Johnson Controls Unitary Products

718444-YTG-B-0412

DNZ036 (3.0 Ton)


Air on
Evaporator Coil
CFM

WB
(F)
77

750

72
67
62
77
72

900

67
62
57
77
72

1050

67
62
57
77
72

1200

67
62
57
72

1350

67
62
57
72

1500

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

36.9
34.7
32.6
30.7
39.2
36.8
34.5
32.4
32.7
41.4
38.9
36.4
34.2
34.5
43.7
41.0
38.4
36.0
36.3
41.7
39.0
36.5
36.9
42.4
39.6
37.1
37.4

1.9
2.0
2.1
2.0
1.9
2.0
2.2
2.0
2.1
2.0
2.1
2.2
2.1
2.1
2.0
2.1
2.2
2.1
2.1
2.1
2.2
2.0
2.1
2.0
2.1
2.0
2.0

18.9
22.9
26.9
30.7
20.6
25.6
30.7
32.4
32.7
22.2
28.4
34.5
34.2
34.5
23.8
31.1
38.4
36.0
36.3
33.3
39.0
36.5
36.9
35.5
39.6
37.1
37.4

43.7
39.4
35.1
31.9
43.6
39.3
35.0
31.8
32.6
43.4
39.2
34.9
31.6
32.5
43.3
39.0
34.8
31.5
32.4
38.8
34.5
31.3
32.2
38.5
34.3
31.1
32.0

3.0
2.9
2.9
3.0
3.0
2.9
2.8
3.0
3.0
2.9
2.9
2.8
3.0
2.9
2.9
2.8
2.7
2.9
2.9
2.9
2.8
3.0
2.9
2.9
2.9
3.0
3.0

17.6
23.5
29.4
31.9
20.5
25.8
31.2
31.8
32.6
23.4
28.2
33.0
31.6
32.5
26.3
30.5
34.8
31.5
32.4
31.7
34.5
31.3
32.2
32.8
34.3
31.1
32.0

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

15.2
19.8
24.4
30.7
17.0
22.0
27.1
32.4
32.7
18.8
24.3
29.8
34.2
34.5
20.5
26.5
32.6
36.0
36.3
28.1
34.3
36.5
36.9
29.6
36.1
37.1
37.4

90

12.1
16.7
21.3
26.4
13.4
18.5
23.5
29.2
29.7
14.7
20.2
25.7
31.9
32.5
15.9
22.0
28.0
34.6
35.3
22.8
29.1
35.9
36.4
23.7
30.2
37.1
37.4

13.6
18.2
23.3
14.9
19.9
25.6
26.1
16.1
21.7
27.8
28.4
17.4
23.4
30.1
30.7
17.6
23.9
30.7
31.2
17.9
24.4
31.3
31.6

15.1
20.2
16.3
22.0
22.5
17.6
23.7
24.4
18.8
25.5
26.2
18.7
25.4
25.9
18.5
25.4
25.7

17.1
18.4
19.0
19.7
20.3
20.9
21.6
20.2
20.7
19.5
19.8

40.3
37.1
33.9
31.3
41.4
38.1
34.8
32.1
32.7
42.4
39.1
35.7
32.9
33.5
43.5
40.0
36.6
33.8
34.3
40.2
36.8
33.9
34.5
40.5
37.0
34.1
34.7

2.5
2.5
2.5
2.5
2.4
2.5
2.5
2.5
2.5
2.4
2.5
2.5
2.5
2.5
2.4
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

18.3
23.2
28.1
31.3
20.5
25.7
30.9
32.1
32.7
22.8
28.3
33.7
32.9
33.5
25.1
30.8
36.6
33.8
34.3
32.5
36.8
33.9
34.5
34.1
37.0
34.1
34.7

12.0
16.9
21.9
24.9
12.9
18.3
23.6
26.9
27.6
13.9
19.6
25.4
28.9
29.6
14.8
21.0
27.1
30.8
31.7
21.1
27.3
31.0
31.8
21.3
27.5
31.1
32.0

13.7
18.6
21.7
14.5
19.9
23.1
23.9
15.3
21.1
24.6
25.4
16.2
22.3
26.1
26.9
15.8
22.0
25.7
26.5
15.5
21.7
25.3
26.2

15.4
18.4
16.1
19.4
20.1
16.8
20.3
21.1
17.5
21.3
22.1
16.7
20.4
21.3
15.9
19.6
20.4

15.2
15.6
16.3
16.1
16.8
16.5
17.3
15.1
16.0
13.8
14.6

40.0
36.2
32.5
30.0
39.7
36.0
32.2
29.8
30.6
39.4
35.7
32.0
29.5
30.4
39.1
35.4
31.8
29.3
30.1
35.3
31.6
29.2
30.0
35.2
31.5
29.1
29.9

3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.4
3.3
3.3
3.3
3.4
3.4
3.3
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.5
3.4

16.0
22.5
29.0
30.0
19.5
24.7
29.9
29.8
30.6
23.0
26.9
30.8
29.5
30.4
26.6
29.2
31.8
29.3
30.1
30.5
31.6
29.2
30.0
31.9
31.5
29.1
29.9

95F
77
750

72
67
62
77
72

900

67
62
57
77
72

1050

67
62
57
77
72

1200

67
62
57
72

1350

67
62
57
72

1500

67
62
57

Johnson Controls Unitary Products

15.2
20.2
25.2
30.2
16.7
22.1
27.4
30.7
31.4
18.2
23.9
29.6
31.1
31.9
19.6
25.7
31.9
31.5
32.4
26.4
32.6
31.3
32.2
27.0
33.3
31.1
32.0

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

15.2
20.0
24.8
30.7
16.8
22.1
27.3
31.7
32.3
18.5
24.1
29.7
32.7
33.3
20.1
26.1
32.2
33.8
34.3
27.2
33.4
33.9
34.5
28.3
34.7
34.1
34.7

65

12.1
16.8
21.6
25.7
13.2
18.4
23.6
28.0
28.7
14.3
19.9
25.6
30.4
31.1
15.4
21.5
27.5
32.7
33.5
22.0
28.2
33.4
34.1
22.5
28.9
34.1
34.7

13.7
18.4
22.5
14.7
19.9
24.4
25.0
15.7
21.4
26.2
26.9
16.8
22.9
28.1
28.8
16.7
22.9
28.2
28.8
16.7
23.0
28.3
28.9

15.2
19.3
16.2
20.7
21.3
17.2
22.0
22.7
18.2
23.4
24.1
17.7
22.9
23.6
17.2
22.5
23.1

16.2
17.0
17.6
17.9
18.5
18.7
19.4
17.7
18.3
16.6
17.2

11.1
15.9
20.7
23.4
12.0
17.2
22.4
25.3
25.8
12.9
18.5
24.0
27.1
27.7
13.8
19.7
25.7
29.0
29.6
20.0
26.1
29.1
29.7
20.3
26.5
29.1
29.9

12.7
17.5
20.1
13.4
18.6
21.5
22.0
14.2
19.8
22.9
23.4
15.0
21.0
24.3
24.8
14.8
20.8
23.8
24.5
14.5
20.7
23.4
24.2

14.2
16.8
14.9
17.7
18.3
15.6
18.6
19.2
16.3
19.5
20.1
15.6
18.6
19.3
14.9
17.6
18.4

13.6
14.0
14.5
14.4
15.0
14.8
15.4
13.3
14.0
11.8
12.6

105F

14.3
19.2
24.1
28.9
15.7
20.9
26.2
29.0
29.5
17.2
22.7
28.2
29.2
29.8
18.6
24.4
30.3
29.3
30.1
25.3
30.7
29.2
30.0
26.1
31.0
29.1
29.9

15

718444-YTG-B-0412
DNZ036 (3.0 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

750

72
67
62
77
72

900

67
62
57
77
72

1050

67
62
57
77
72

1200

67
62
57
72

1350

67
62
57
72

1500

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

36.2
33.0
29.8
28.1
35.8
32.6
29.4
27.8
28.5
35.4
32.2
29.1
27.4
28.2
34.9
31.8
28.7
27.1
27.8
31.9
28.8
27.1
27.9
31.9
28.8
27.1
27.9

3.6
3.7
3.8
3.8
3.6
3.7
3.8
3.9
3.8
3.7
3.8
3.8
3.9
3.8
3.7
3.8
3.9
3.9
3.9
3.8
3.9
3.9
3.8
3.7
3.8
3.9
3.8

14.4
21.5
28.6
28.1
18.5
23.6
28.6
27.8
28.5
22.7
25.7
28.7
27.4
28.2
26.9
27.8
28.7
27.1
27.8
29.3
28.8
27.1
27.9
30.9
28.8
27.1
27.9

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

13.4
18.2
23.0
27.5
14.8
19.8
24.9
27.3
27.6
16.2
21.5
26.8
27.2
27.7
17.6
23.1
28.7
27.1
27.8
24.1
28.8
27.1
27.9
25.1
28.8
27.1
27.9

10.2
14.9
19.6
21.8
11.0
16.1
21.2
23.6
23.9
11.9
17.3
22.7
25.4
25.7
12.7
18.5
24.3
27.1
27.5
18.9
24.9
27.1
27.7
19.4
25.4
27.1
27.9

11.6
16.3
18.6
12.4
17.4
19.9
20.2
13.1
18.5
21.2
21.5
13.8
19.7
22.5
22.8
13.7
19.7
21.9
22.5
13.6
19.7
21.4
22.1

13.0
15.3
13.7
16.1
16.4
14.3
17.0
17.3
15.0
17.8
18.2
14.5
16.7
17.3
13.9
15.6
16.3

12.0
12.4
12.7
12.8
13.1
13.2
13.5
11.5
12.0
9.8
10.6

32.4
29.8
27.1
26.2
31.9
29.3
26.6
25.8
26.5
31.3
28.7
26.2
25.3
26.0
30.8
28.2
25.7
24.9
25.6
28.4
25.9
25.0
25.7
28.6
26.0
25.2
25.8

3.9
4.1
4.2
4.3
4.0
4.1
4.3
4.3
4.2
4.1
4.2
4.4
4.4
4.3
4.1
4.3
4.4
4.4
4.4
4.2
4.4
4.4
4.3
4.2
4.3
4.3
4.3

90

13.9
20.5
27.1
26.2
18.3
22.5
26.6
25.8
26.5
22.7
24.4
26.2
25.3
26.0
27.1
26.4
25.7
24.9
25.6
28.2
25.9
25.0
25.7
28.6
26.0
25.2
25.8

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

11.7
17.2
21.9
26.1
13.8
18.7
23.7
25.7
25.8
15.9
20.3
25.4
25.3
25.7
18.0
21.8
25.7
24.9
25.6
23.0
25.9
25.0
25.7
24.2
26.0
25.2
25.8

9.3
13.9
18.4
20.3
10.1
15.0
19.9
21.9
22.0
10.9
16.1
21.4
23.6
23.7
11.6
17.3
22.9
24.9
25.4
17.8
23.7
25.0
25.6
18.4
24.4
25.2
25.8

10.6
15.1
17.0
11.3
16.2
18.2
18.3
12.0
17.3
19.4
19.5
12.7
18.3
20.7
20.8
12.7
18.5
20.0
20.4
12.6
18.6
19.4
20.1

11.8
13.7
12.5
14.5
14.6
13.1
15.3
15.4
13.8
16.1
16.2
13.3
14.9
15.3
12.9
13.6
14.3

65

10.4
10.8
10.9
11.1
11.2
11.5
11.6
9.7
10.1
7.9
8.5

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

16

Johnson Controls Unitary Products

718444-YTG-B-0412

DNZ042 (3.5 Ton)


Air on
Evaporator Coil
CFM

WB
(F)
77

875

72
67
62
57
77

1050

72
67
62
57
77

1225

72
67
62
57
72

1400

67
62
57
72

1515

67
62
57
72

1630

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

46.4
44.6
42.8
39.1
48.9
47.0
45.0
41.2
40.1
51.4
49.3
47.3
43.3
42.1
53.8
51.7
49.5
45.3
44.2
51.7
49.5
45.4
44.2
51.7
49.6
45.4
44.2

2.7
2.6
2.6
2.5
2.7
2.7
2.6
2.6
2.5
2.7
2.7
2.6
2.6
2.6
2.7
2.7
2.7
2.6
2.6
2.7
2.7
2.6
2.6
2.7
2.7
2.6
2.6

21.7
27.5
33.3
39.1
23.1
30.8
38.5
41.2
40.1
24.5
34.1
43.6
43.3
42.1
25.9
37.3
48.8
45.3
44.2
38.5
49.2
45.4
44.2
39.7
49.6
45.4
44.2

45.2
41.1
37.0
33.9
47.3
43.1
38.8
35.5
34.9
49.5
45.0
40.5
37.1
36.4
51.6
46.9
42.3
38.7
38.0
47.3
42.6
39.0
38.3
47.6
42.9
39.2
38.5

3.2
3.1
3.1
3.0
3.2
3.2
3.1
3.1
3.1
3.2
3.2
3.1
3.1
3.1
3.3
3.2
3.1
3.1
3.1
3.2
3.2
3.1
3.1
3.2
3.2
3.1
3.1

19.8
26.5
33.2
33.9
23.7
30.0
36.2
35.5
34.9
27.7
33.5
39.3
37.1
36.4
31.6
36.9
42.3
38.7
38.0
38.9
42.6
39.0
38.3
40.8
42.9
39.2
38.5

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

16.7
23.6
30.5
39.1
18.7
26.4
34.1
41.2
40.1
20.7
29.2
37.6
43.3
42.1
22.7
31.9
41.2
45.3
44.2
32.8
42.3
45.4
44.2
33.7
43.4
45.4
44.2

90

12.9
19.8
26.7
32.1
14.3
22.0
29.7
35.8
36.4
15.8
24.3
32.7
39.4
40.1
17.3
26.5
35.8
43.1
43.8
27.1
36.6
44.2
44.0
27.7
37.4
45.4
44.2

15.9
22.8
28.2
17.6
25.3
31.4
32.0
19.4
27.8
34.5
35.2
21.1
30.4
37.7
38.4
21.4
30.8
38.5
38.3
21.6
31.3
39.3
38.1

18.9
24.4
20.9
27.0
27.6
22.9
29.6
30.3
24.9
32.3
33.0
25.1
32.8
32.5
25.3
33.3
32.1

20.5
22.6
23.2
24.7
25.4
26.8
27.6
27.0
26.8
27.3
26.1

45.8
42.9
39.9
36.5
48.1
45.0
41.9
38.4
37.5
50.4
47.2
43.9
40.2
39.3
52.7
49.3
45.9
42.0
41.1
49.5
46.1
42.2
41.2
49.6
46.2
42.3
41.3

2.9
2.9
2.9
2.8
3.0
2.9
2.9
2.8
2.8
3.0
2.9
2.9
2.8
2.8
3.0
2.9
2.9
2.8
2.8
3.0
2.9
2.9
2.8
3.0
2.9
2.9
2.8

20.8
27.0
33.2
36.5
23.4
30.4
37.3
38.4
37.5
26.1
33.8
41.4
40.2
39.3
28.7
37.1
45.5
42.0
41.1
38.7
45.9
42.2
41.2
40.3
46.2
42.3
41.3

12.9
18.5
24.1
28.6
14.4
20.7
26.9
32.0
31.1
16.0
22.9
29.8
35.3
34.4
17.5
25.1
32.6
38.7
37.7
26.2
34.1
39.0
38.1
27.4
35.7
39.2
38.5

14.5
20.1
24.6
16.1
22.3
27.3
26.5
17.6
24.5
30.0
29.1
19.1
26.7
32.8
31.8
19.9
27.8
32.7
31.8
20.7
29.0
32.5
31.8

16.1
20.6
17.7
22.7
21.8
19.2
24.8
23.8
20.8
26.8
25.8
21.5
26.3
25.5
22.3
25.8
25.1

16.6
18.0
17.2
19.5
18.6
20.9
19.9
20.0
19.2
19.1
18.4

42.2
37.7
33.3
32.4
44.0
39.4
34.8
33.9
32.2
45.9
41.1
36.3
35.3
33.6
47.8
42.8
37.8
36.8
34.9
43.1
38.0
37.0
35.2
43.4
38.3
37.3
35.5

3.5
3.4
3.3
3.3
3.5
3.4
3.3
3.3
3.3
3.5
3.4
3.4
3.3
3.3
3.5
3.5
3.4
3.3
3.3
3.5
3.4
3.3
3.3
3.5
3.4
3.4
3.4

19.4
25.4
31.4
32.4
24.2
28.9
33.5
33.9
32.2
29.1
32.3
35.6
35.3
33.6
33.9
35.8
37.8
36.8
34.9
37.7
38.0
37.0
35.2
39.6
38.3
37.3
35.5

95F
77
875

72
67
62
57
77

1050

72
67
62
57
77

1225

72
67
62
57
72

1400

67
62
57
72

1515

67
62
57
72

1630

67
62
57

Johnson Controls Unitary Products

16.9
22.5
28.1
33.9
19.1
25.3
31.6
35.5
34.9
21.3
28.2
35.1
37.1
36.4
23.4
31.0
38.6
38.7
38.0
32.5
40.5
39.0
38.3
34.1
42.4
39.2
38.5

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

16.8
23.1
29.3
36.5
18.9
25.9
32.8
38.4
37.5
21.0
28.7
36.4
40.2
39.3
23.1
31.5
39.9
42.0
41.1
32.7
41.4
42.2
41.2
33.9
42.9
42.3
41.3

65

12.9
19.1
25.4
30.4
14.4
21.4
28.3
33.9
33.7
15.9
23.6
31.3
37.4
37.2
17.4
25.8
34.2
40.9
40.7
26.7
35.4
41.6
41.0
27.5
36.5
42.3
41.3

15.2
21.5
26.4
16.8
23.8
29.4
29.2
18.5
26.2
32.3
32.2
20.1
28.5
35.2
35.1
20.6
29.3
35.6
35.0
21.2
30.1
35.9
35.0

17.5
22.5
19.3
24.8
24.7
21.1
27.2
27.1
22.9
29.5
29.4
23.3
29.6
29.0
23.8
29.6
28.6

18.6
20.3
20.2
22.1
22.0
23.9
23.7
23.5
23.0
23.2
22.2

11.9
17.2
22.5
26.7
13.4
19.4
25.4
30.0
28.3
14.9
21.6
28.2
33.4
31.4
16.4
23.7
31.0
36.8
34.6
24.8
32.4
37.0
35.0
25.9
33.8
37.3
35.5

13.1
18.4
22.6
14.7
20.6
25.3
23.5
16.2
22.8
28.0
26.0
17.7
25.0
30.7
28.5
18.3
26.0
30.6
28.6
19.0
27.0
30.4
28.6

14.4
18.5
15.9
20.6
18.8
17.4
22.6
20.6
18.9
24.7
22.5
19.5
24.1
22.1
20.1
23.6
21.7

14.4
15.8
14.1
17.2
15.2
18.6
16.4
17.7
15.6
16.7
14.8

105F

15.4
21.3
27.2
32.4
18.1
24.1
30.1
33.9
32.2
20.9
27.0
33.0
35.3
33.6
23.7
29.8
35.9
36.8
34.9
31.3
37.0
37.0
35.2
32.8
38.1
37.3
35.5

17

718444-YTG-B-0412
DNZ042 (3.5 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

875

72
67
62
57
77

1050

72
67
62
57
77

1225

72
67
62
57
72

1400

67
62
57
72

1515

67
62
57
72

1630

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

39.1
34.3
29.6
31.0
40.7
35.8
30.8
32.3
29.5
42.4
37.2
32.0
33.6
30.7
44.0
38.6
33.2
34.8
31.9
38.9
33.5
35.1
32.1
39.2
33.8
35.4
32.4

3.8
3.7
3.6
3.5
3.8
3.7
3.6
3.5
3.6
3.8
3.7
3.6
3.6
3.6
3.8
3.7
3.6
3.6
3.6
3.7
3.6
3.6
3.6
3.7
3.6
3.6
3.6

18.9
24.2
29.6
31.0
24.7
27.7
30.8
32.3
29.5
30.5
31.2
32.0
33.6
30.7
36.2
34.7
33.2
34.8
31.9
36.6
33.5
35.1
32.1
38.5
33.8
35.4
32.4

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

13.9
20.1
26.3
31.0
17.2
22.9
28.6
32.3
29.5
20.6
25.7
30.9
33.6
30.7
23.9
28.6
33.2
34.8
31.9
30.0
33.5
35.1
32.1
31.4
33.8
35.4
32.4

10.9
15.9
20.9
24.8
12.4
18.1
23.8
28.1
25.4
13.9
20.2
26.6
31.5
28.4
15.3
22.4
29.4
34.8
31.5
23.4
30.7
35.1
31.9
24.4
32.0
35.4
32.4

11.8
16.8
20.6
13.2
18.9
23.3
20.6
14.7
21.1
26.0
22.9
16.2
23.3
28.7
25.3
16.8
24.1
28.5
25.3
17.3
25.0
28.3
25.3

12.6
16.4
14.1
18.5
15.7
15.6
20.5
17.4
17.1
22.5
19.1
17.5
21.9
18.7
17.9
21.3
18.3

12.3
13.6
10.9
15.0
11.9
16.3
13.0
15.3
12.1
14.2
11.2

36.1
31.0
25.8
29.5
37.5
32.1
26.8
30.7
26.9
38.8
33.3
27.7
31.8
27.8
40.2
34.4
28.7
32.9
28.8
34.7
29.0
33.2
29.1
35.0
29.2
33.5
29.3

4.1
3.9
3.8
3.8
4.1
3.9
3.8
3.8
3.8
4.1
4.0
3.8
3.8
3.8
4.1
4.0
3.8
3.8
3.8
4.0
3.9
3.8
3.8
4.0
3.9
3.9
3.9

90

20.4
23.1
25.8
29.5
26.4
26.6
26.8
30.7
26.9
32.5
30.1
27.7
31.8
27.8
38.5
33.6
28.7
32.9
28.8
34.7
29.0
33.2
29.1
35.0
29.2
33.5
29.3

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

11.9
18.9
25.8
29.5
16.6
21.7
26.8
30.7
26.9
21.3
24.5
27.7
31.8
27.8
26.0
27.3
28.7
32.9
28.8
28.7
29.0
33.2
29.1
30.1
29.2
33.5
29.3

9.9
14.6
19.3
22.9
11.4
16.8
22.2
26.2
22.5
12.8
18.9
25.0
29.6
25.4
14.3
21.1
27.8
32.9
28.3
22.0
29.0
33.2
28.8
22.9
29.2
33.5
29.3

10.4
15.1
18.6
11.8
17.3
21.3
17.6
13.3
19.4
24.0
19.8
14.8
21.6
26.6
22.1
15.2
22.3
26.4
22.1
15.6
23.0
26.2
22.1

10.9
14.4
12.3
16.4
12.7
13.8
18.3
14.2
15.3
20.3
15.8
15.5
19.7
15.3
15.8
19.0
14.8

65

10.1
11.4
7.8
12.7
8.6
14.1
9.5
12.9
8.5
11.8
7.6

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

18

Johnson Controls Unitary Products

718444-YTG-B-0412

DNZ048 (4.0 Ton)


Air on
Evaporator Coil
CFM

WB
(F)
77

1000

72
67
62
77
72

1200

67
62
57
77
72

1400

67
62
57
77
72

1600

67
62
57
72

1735

67
62
57
72

1870

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

53.1
49.7
46.3
40.7
57.0
53.3
49.7
43.7
42.8
61.0
57.0
53.0
46.7
45.7
64.9
60.6
56.4
49.7
48.7
60.1
55.9
49.3
48.3
59.6
55.4
48.8
47.8

3.1
3.0
2.9
3.0
3.1
3.0
2.9
2.9
3.0
3.1
3.0
2.9
2.9
2.9
3.0
2.9
2.8
2.9
2.9
3.0
2.9
2.9
2.9
3.0
2.9
2.9
3.0

26.3
32.0
37.7
40.7
28.4
36.2
43.9
43.7
42.8
30.5
40.3
50.2
46.7
45.7
32.6
44.5
56.4
49.7
48.7
46.3
55.9
49.3
48.3
48.1
55.4
48.8
47.8

53.9
48.4
42.9
40.1
55.8
50.2
44.5
41.5
40.9
57.8
51.9
46.1
43.0
42.3
59.8
53.7
47.6
44.5
43.7
53.4
47.4
44.2
43.5
53.1
47.1
44.0
43.3

3.6
3.6
3.7
3.6
3.7
3.7
3.7
3.6
3.6
3.7
3.7
3.7
3.7
3.7
3.7
3.8
3.8
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.7
3.7
3.7

23.7
30.9
38.2
40.1
28.2
34.7
41.3
41.5
40.9
32.6
38.6
44.5
43.0
42.3
37.1
42.4
47.6
44.5
43.7
44.2
47.4
44.2
43.5
46.1
47.1
44.0
43.3

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

20.6
27.5
34.5
40.7
23.2
31.0
38.8
43.7
42.8
25.9
34.5
43.1
46.7
45.7
28.5
38.0
47.4
49.7
48.7
39.3
49.1
49.3
48.3
40.7
50.7
48.8
47.8

90

16.2
23.1
30.0
36.3
18.1
25.9
33.7
40.7
39.7
20.1
28.7
37.3
45.1
44.0
22.0
31.5
40.9
49.5
48.3
32.4
42.1
49.1
48.1
33.3
43.3
48.8
47.8

18.7
25.6
31.9
20.8
28.6
35.6
34.6
22.9
31.5
39.3
38.2
25.0
34.4
43.0
41.8
25.4
35.2
42.2
41.1
25.9
35.9
41.4
40.4

21.2
27.4
23.4
30.5
29.5
25.7
33.5
32.4
28.0
36.5
35.3
28.2
35.3
34.2
28.5
34.0
33.0

23.0
25.3
24.4
27.7
26.6
30.0
28.8
28.3
27.2
26.6
25.6

53.5
49.0
44.6
40.4
56.4
51.7
47.1
42.6
41.8
59.4
54.5
49.5
44.8
44.0
62.3
57.2
52.0
47.1
46.2
56.8
51.6
46.7
45.9
56.4
51.3
46.4
45.5

3.4
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.3
3.4
3.3
3.3
3.3
3.4
3.3
3.3
3.3

25.0
31.5
37.9
40.4
28.3
35.4
42.6
42.6
41.8
31.6
39.4
47.3
44.8
44.0
34.8
43.4
52.0
47.1
46.2
45.3
51.6
46.7
45.9
47.1
51.3
46.4
45.5

16.3
22.3
28.3
34.0
18.0
24.5
31.1
37.4
36.8
19.6
26.8
33.9
40.8
40.1
21.2
29.0
36.8
44.2
43.5
30.2
38.3
44.1
43.4
31.4
39.8
44.0
43.3

18.0
23.9
29.7
19.4
26.0
32.3
31.7
20.9
28.0
34.9
34.2
22.3
30.1
37.5
36.8
23.2
31.2
37.1
36.3
24.0
32.4
36.6
35.9

19.6
25.3
20.9
27.2
26.6
22.1
29.0
28.3
23.4
30.8
30.1
24.2
30.0
29.3
25.0
29.2
28.5

21.0
22.1
21.4
23.1
22.4
24.1
23.4
23.0
22.3
21.9
21.1

49.3
44.6
39.8
35.7
51.3
46.4
41.4
37.1
38.0
53.3
48.2
43.0
38.5
39.5
55.3
50.0
44.6
40.0
41.0
49.1
43.8
39.3
40.2
48.2
43.0
38.6
39.5

4.2
4.2
4.2
4.1
4.2
4.2
4.2
4.1
4.2
4.3
4.2
4.2
4.1
4.2
4.3
4.3
4.2
4.1
4.2
4.3
4.2
4.1
4.2
4.3
4.2
4.1
4.2

25.1
31.3
37.4
35.7
29.2
34.5
39.8
37.1
38.0
33.3
37.8
42.2
38.5
39.5
37.4
41.0
44.6
40.0
41.0
42.7
43.8
39.3
40.2
44.4
43.0
38.6
39.5

95F
77
1000

72
67
62
77
72

1200

67
62
57
77
72

1400

67
62
57
77
72

1600

67
62
57
72

1735

67
62
57
72

1870

67
62
57

Johnson Controls Unitary Products

20.6
26.6
32.6
40.1
23.1
29.6
36.2
41.5
40.9
25.5
32.7
39.8
43.0
42.3
27.9
35.7
43.5
44.5
43.7
37.2
45.3
44.2
43.5
38.7
47.1
44.0
43.3

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

20.6
27.1
33.5
40.4
23.2
30.3
37.5
42.6
41.8
25.7
33.6
41.5
44.8
44.0
28.2
36.8
45.4
47.1
46.2
38.3
47.2
46.7
45.9
39.7
48.9
46.4
45.5

65

16.2
22.7
29.2
35.2
18.0
25.2
32.4
39.0
38.3
19.8
27.7
35.6
42.9
42.1
21.6
30.2
38.9
46.8
45.9
31.3
40.2
46.6
45.7
32.3
41.5
46.4
45.5

18.3
24.8
30.8
20.1
27.3
33.9
33.1
21.9
29.8
37.1
36.2
23.7
32.3
40.3
39.3
24.3
33.2
39.6
38.7
24.9
34.1
39.0
38.2

20.4
26.4
22.2
28.8
28.0
23.9
31.2
30.4
25.7
33.7
32.7
26.2
32.6
31.7
26.7
31.6
30.8

22.0
23.7
22.9
25.4
24.5
27.1
26.1
25.7
24.8
24.2
23.4

14.8
20.8
26.8
29.9
16.5
23.1
29.8
33.2
34.0
18.1
25.5
32.8
36.5
37.4
19.8
27.8
35.8
39.9
40.8
28.7
37.0
39.2
40.2
29.6
38.1
38.6
39.5

15.6
21.6
24.7
17.5
24.1
27.5
28.4
19.3
26.6
30.4
31.3
21.2
29.2
33.2
34.2
21.7
29.9
32.2
33.2
22.2
30.7
31.2
32.1

16.4
19.5
18.4
21.9
22.7
20.5
24.2
25.1
22.6
26.6
27.6
22.9
25.2
26.1
23.3
23.8
24.7

14.3
16.2
17.0
18.1
19.0
20.0
21.0
18.2
19.1
16.4
17.3

105F

20.1
26.0
32.0
35.7
22.2
28.8
35.5
37.1
38.0
24.3
31.6
38.9
38.5
39.5
26.4
34.4
42.4
40.0
41.0
35.7
42.7
39.3
40.2
37.0
43.0
38.6
39.5

19

718444-YTG-B-0412
DNZ048 (4.0 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

1000

72
67
62
77
72

1200

67
62
57
77
72

1400

67
62
57
77
72

1600

67
62
57
72

1735

67
62
57
72

1870

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

44.8
40.7
36.7
31.3
46.8
42.6
38.3
32.7
35.2
48.9
44.4
40.0
34.1
36.7
50.9
46.3
41.7
35.5
38.2
44.7
40.3
34.3
37.0
43.2
38.9
33.1
35.7

4.8
4.7
4.7
4.5
4.8
4.7
4.7
4.6
4.7
4.8
4.8
4.7
4.6
4.8
4.8
4.8
4.7
4.6
4.8
4.8
4.7
4.6
4.8
4.8
4.7
4.6
4.8

26.5
31.6
36.7
31.3
30.2
34.3
38.3
32.7
35.2
33.9
36.9
40.0
34.1
36.7
37.6
39.6
41.7
35.5
38.2
41.2
40.3
34.3
37.0
42.7
38.9
33.1
35.7

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

19.5
25.5
31.5
31.3
21.3
28.0
34.7
32.7
35.2
23.1
30.6
38.0
34.1
36.7
24.9
33.1
41.3
35.5
38.2
34.2
40.1
34.3
37.0
35.3
38.9
33.1
35.7

13.4
19.3
25.3
25.9
15.0
21.8
28.5
29.1
31.3
16.7
24.2
31.6
32.3
34.8
18.3
26.6
34.8
35.5
38.2
27.2
35.6
34.3
37.0
27.9
36.5
33.1
35.7

13.2
19.2
19.7
15.5
22.2
22.8
25.0
17.8
25.2
25.9
28.4
20.0
28.3
29.0
31.7
20.2
28.7
27.3
30.0
20.4
29.1
25.7
28.2

13.1
13.6
16.0
16.6
18.8
18.8
19.5
22.0
21.7
22.4
25.1
21.7
20.3
23.0
21.6
18.3
20.8

7.5
10.3
12.5
13.1
15.6
15.9
18.6
13.4
16.0
10.8
13.4

40.3
36.9
33.6
26.9
42.3
38.8
35.3
28.2
32.3
44.4
40.7
37.0
29.6
33.9
46.4
42.6
38.7
31.0
35.5
40.4
36.7
29.4
33.7
38.3
34.8
27.7
31.9

5.4
5.3
5.2
5.0
5.4
5.3
5.2
5.0
5.3
5.3
5.3
5.2
5.0
5.3
5.3
5.3
5.2
5.0
5.3
5.3
5.2
5.0
5.3
5.3
5.2
5.1
5.3

90

30.2
31.9
33.6
26.9
32.8
34.0
35.3
28.2
32.3
35.3
36.1
37.0
29.6
33.9
37.8
38.3
38.7
31.0
35.5
39.7
36.7
29.4
33.7
38.3
34.8
27.7
31.9

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

18.1
24.9
31.1
26.9
20.4
27.2
34.0
28.2
32.3
22.7
29.5
37.0
29.6
33.9
24.9
31.8
38.7
31.0
35.5
32.7
36.7
29.4
33.7
33.6
34.8
27.7
31.9

11.9
17.9
23.9
21.8
13.5
20.4
27.2
24.9
28.6
15.2
22.9
30.5
28.0
32.1
16.9
25.3
33.8
31.0
35.5
25.7
34.3
29.4
33.7
26.1
34.8
27.7
31.9

10.9
16.9
14.8
13.5
20.4
18.1
21.7
16.2
23.8
21.4
25.4
18.9
27.3
24.7
29.1
18.8
27.4
22.5
26.8
18.6
27.4
20.3
24.4

9.9
7.8
13.5
11.3
14.9
17.2
14.7
18.8
20.9
18.2
22.7
20.4
15.5
19.8
19.9
12.8
16.9

65

0.8
4.4
8.1
8.1
12.1
11.8
16.2
8.5
12.8
5.3
9.5

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

20

Johnson Controls Unitary Products

718444-YTG-B-0412

DNZ060 (5.0 Ton)


Air on
Evaporator Coil
CFM

WB
(F)
77

1250

72
67
62
77
72

1500

67
62
57
77
72

1750

67
62
57
77
72

2000

67
62
57
72

2050

67
62
57
72

2100

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

68.8
64.6
60.4
53.8
71.2
66.8
62.5
55.6
56.6
73.6
69.1
64.5
57.5
58.5
76.0
71.3
66.6
59.4
60.4
72.4
67.7
60.3
61.4
73.5
68.7
61.2
62.3

4.1
3.9
3.8
3.8
4.0
3.9
3.7
3.8
3.7
4.0
3.8
3.7
3.7
3.7
4.0
3.8
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.8
3.7
3.7
3.7

23.2
35.1
47.0
53.8
28.1
40.8
53.5
55.6
56.6
32.9
46.5
60.1
57.5
58.5
37.8
52.2
66.6
59.4
60.4
53.1
67.7
60.3
61.4
54.1
68.7
61.2
62.3

67.7
61.5
55.3
52.7
68.7
62.4
56.1
53.5
53.3
69.7
63.3
57.0
54.3
54.1
70.7
64.2
57.8
55.0
54.9
66.2
59.6
56.7
56.6
68.3
61.4
58.5
58.3

4.7
4.7
4.7
4.6
4.7
4.8
4.8
4.6
4.6
4.8
4.8
4.8
4.7
4.6
4.8
4.8
4.9
4.7
4.7
4.8
4.9
4.7
4.7
4.9
4.9
4.7
4.7

36.2
42.3
48.4
52.7
39.0
45.2
51.5
53.5
53.3
41.7
48.1
54.6
54.3
54.1
44.4
51.0
57.7
55.0
54.9
55.6
59.5
56.7
56.6
60.1
61.4
58.5
58.3

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Total
Net
Input
Return Dry Bulb (F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75F

18.4
29.8
41.1
51.4
22.0
34.7
47.4
54.1
55.6
25.5
39.7
53.8
56.7
58.0
29.1
44.6
60.2
59.4
60.4
45.5
61.9
60.3
61.4
46.4
63.5
61.2
62.3

90

13.1
24.4
35.7
37.8
15.9
28.6
41.3
44.4
45.7
18.7
32.8
47.0
51.0
52.4
21.5
37.1
52.6
57.5
59.0
37.9
54.2
59.4
60.7
38.7
55.8
61.2
62.3

19.0
30.3
32.5
22.5
35.2
38.3
39.6
26.0
40.2
44.1
45.5
29.5
45.1
50.0
51.5
30.2
46.6
51.7
53.0
31.0
48.1
53.5
54.6

24.9
27.1
29.1
32.2
33.5
33.3
37.3
38.7
37.5
42.4
43.9
39.0
44.1
45.4
40.4
45.8
46.9

21.7
26.1
27.4
30.5
31.9
34.9
36.4
36.5
37.8
38.1
39.2

68.3
63.1
57.9
53.2
70.0
64.6
59.3
54.6
55.0
71.7
66.2
60.7
55.9
56.3
73.4
67.8
62.2
57.2
57.6
69.3
63.6
58.5
59.0
70.9
65.0
59.8
60.3

4.4
4.3
4.2
4.2
4.4
4.3
4.3
4.2
4.2
4.4
4.3
4.3
4.2
4.2
4.4
4.3
4.3
4.2
4.2
4.3
4.3
4.2
4.2
4.4
4.3
4.2
4.2

29.8
38.7
47.7
53.2
33.5
43.0
52.5
54.6
55.0
37.3
47.3
57.4
55.9
56.3
41.0
51.6
62.2
57.2
57.6
54.3
63.6
58.5
59.0
57.1
65.0
59.8
60.3

25.8
31.9
38.0
49.4
26.5
32.8
39.1
50.8
50.9
27.3
33.7
40.2
52.2
52.3
28.0
34.6
41.2
53.6
53.7
39.3
46.8
56.1
56.0
44.0
52.4
58.5
58.3

26.7
32.8
44.2
26.6
32.9
44.6
44.7
26.5
32.9
45.0
45.1
26.4
33.0
45.4
45.5
31.2
38.7
47.9
47.9
36.0
44.4
50.4
50.3

27.6
39.0
26.6
38.4
38.5
25.7
37.8
37.9
24.8
37.2
37.3
30.6
39.8
39.8
36.4
42.4
42.2

33.8
32.2
32.3
30.6
30.7
29.0
29.1
31.7
31.6
34.4
34.2

62.5
57.2
51.8
49.0
63.5
58.1
52.7
49.9
50.2
64.5
59.0
53.5
50.7
51.0
65.6
60.0
54.4
51.5
51.8
61.5
55.7
52.8
53.1
63.0
57.1
54.0
54.4

5.5
5.5
5.5
5.3
5.5
5.5
5.5
5.3
5.3
5.5
5.5
5.5
5.4
5.3
5.5
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4

29.9
38.9
48.0
49.0
34.7
42.4
50.1
49.9
50.2
39.5
45.9
52.2
50.7
51.0
44.3
49.3
54.3
51.5
51.8
52.8
55.7
52.8
53.1
56.2
57.1
54.0
54.4

95F

1250

77
72
67
62

1500

77
72
67
62
57

1750

77
72
67
62
57

2000

77
72
67
62
57

2050

72
67
62
57

2100

72
67
62
57

Johnson Controls Unitary Products

31.0
37.1
43.2
52.7
32.7
39.0
45.3
53.5
53.3
34.5
40.9
47.4
54.3
54.1
36.2
42.8
49.5
55.0
54.9
47.4
55.0
56.7
56.6
52.0
60.5
58.5
58.3

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
85F

24.7
33.4
42.1
52.1
27.4
36.9
46.4
53.8
54.4
30.0
40.3
50.6
55.5
56.0
32.6
43.7
54.8
57.2
57.6
46.5
58.4
58.5
59.0
49.2
62.0
59.8
60.3

65

19.4
28.1
36.8
43.6
21.2
30.7
40.2
47.6
48.3
23.0
33.3
43.6
51.6
52.3
24.8
35.8
46.9
55.6
56.4
38.6
50.5
57.7
58.3
41.3
54.1
59.8
60.3

22.8
31.5
38.3
24.5
34.1
41.5
42.1
26.3
36.6
44.6
45.3
28.0
39.1
47.7
48.5
30.7
42.7
49.8
50.5
33.5
46.3
52.0
52.4

26.3
33.0
27.9
35.3
36.0
29.5
37.6
38.3
31.2
39.8
40.6
34.8
42.0
42.6
38.4
44.1
44.6

27.7
29.1
29.8
30.5
31.3
31.9
32.7
34.1
34.7
36.2
36.7

21.1
28.3
35.6
43.5
22.2
29.9
37.7
45.9
45.8
23.4
31.5
39.7
48.3
48.3
24.5
33.1
41.8
50.8
50.7
36.7
46.2
52.4
52.5
40.2
50.6
54.0
54.4

23.0
30.3
38.2
23.7
31.4
39.7
39.6
24.4
32.6
41.2
41.1
25.0
33.7
42.7
42.6
28.6
38.2
44.4
44.5
32.3
42.6
46.0
46.4

25.0
32.9
25.2
33.5
33.4
25.4
34.0
33.9
25.6
34.6
34.5
30.1
36.3
36.4
34.6
38.1
38.4

27.6
27.2
27.1
26.9
26.8
26.5
26.4
28.3
28.4
30.1
30.4

105F

26.4
33.6
40.9
49.0
28.5
36.2
43.9
49.9
50.2
30.5
38.7
46.9
50.7
51.0
32.6
41.2
49.9
51.5
51.8
44.7
53.3
52.8
53.1
48.2
56.6
54.0
54.4

21

718444-YTG-B-0412
DNZ060 (5.0 Ton) (Continued)
Air on
Evaporator Coil
CFM

WB
(F)
77

1250

72
67
62
77
72

1500

67
62
57
77
72

1750

67
62
57
77
72

2000

67
62
57
72

2050

67
62
57
72

2100

67
62
57

Net
Capacity1
(MBh)

Total
Input
(kW)2

90

57.3
52.8
48.3
45.4
58.3
53.8
49.2
46.2
47.0
59.4
54.8
50.1
47.1
47.9
60.5
55.7
51.0
47.9
48.7
56.7
51.9
48.8
49.6
57.7
52.8
49.6
50.4

6.2
6.2
6.2
6.0
6.2
6.2
6.2
6.0
6.0
6.2
6.2
6.2
6.0
6.0
6.2
6.2
6.2
6.0
6.0
6.2
6.2
6.1
6.0
6.2
6.2
6.1
6.0

23.5
35.5
47.6
45.4
30.4
39.6
48.7
46.2
47.0
37.3
43.6
49.9
47.1
47.9
44.3
47.6
51.0
47.9
48.7
50.0
51.9
48.8
49.6
52.4
52.8
49.6
50.4

Temperature of Air on Condenser Coil


Sensible Capacity (MBh)
Net
Total
Return Dry Bulb (F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115F

21.8
30.2
38.5
45.4
24.2
33.3
42.5
46.2
47.0
26.6
36.5
46.4
47.1
47.9
29.0
39.6
50.3
47.9
48.7
42.0
51.6
48.8
49.6
44.4
52.8
49.6
50.4

16.4
24.8
33.2
37.5
17.9
27.1
36.2
41.0
40.8
19.5
29.4
39.3
44.5
44.2
21.0
31.7
42.3
47.9
47.7
34.1
45.6
48.8
49.0
36.5
48.8
49.6
50.4

19.4
27.8
32.2
20.8
30.0
34.7
34.5
22.3
32.2
37.3
37.1
23.7
34.4
39.9
39.7
26.1
37.6
40.8
41.1
28.5
40.9
41.7
42.5

22.4
26.8
23.7
28.5
28.3
25.1
30.2
30.0
26.4
31.9
31.7
29.6
32.8
33.1
32.9
33.7
34.6

21.4
22.3
22.0
23.1
22.9
23.9
23.7
24.9
25.1
25.8
26.6

52.0
48.4
44.8
41.7
53.1
49.4
45.8
42.6
43.9
54.2
50.5
46.7
43.5
44.8
55.3
51.5
47.6
44.4
45.7
52.0
48.1
44.8
46.1
52.4
48.5
45.2
46.5

7.0
6.9
6.9
6.8
7.0
6.9
6.9
6.8
6.7
6.9
6.9
6.8
6.7
6.7
6.9
6.9
6.8
6.7
6.7
6.9
6.8
6.7
6.7
6.9
6.8
6.7
6.7

90

19.5
32.2
44.8
41.7
27.7
36.7
45.8
42.6
43.9
36.0
41.3
46.7
43.5
44.8
44.2
45.9
47.6
44.4
45.7
47.2
48.1
44.8
46.1
48.5
48.5
45.2
46.5

Sensible Capacity (MBh)


Return Dry Bulb (F)
85
80
75
70
125F

15.6
26.7
36.2
41.7
19.9
30.5
41.1
42.6
43.9
24.2
34.3
45.9
43.5
44.8
28.5
38.1
47.6
44.4
45.7
39.3
48.1
44.8
46.1
40.6
48.5
45.2
46.5

11.7
21.3
30.8
31.6
13.7
24.2
34.8
36.1
35.7
15.6
27.2
38.8
40.6
40.2
17.5
30.2
42.9
44.4
44.6
31.4
44.9
44.8
45.6
32.7
47.0
45.2
46.5

15.8
25.3
26.1
18.0
28.5
29.8
29.4
20.1
31.8
33.5
33.1
22.3
35.0
37.2
36.7
23.6
37.0
37.2
37.7
24.8
39.1
37.3
38.6

19.9
20.7
22.3
23.6
23.2
24.7
26.4
26.0
27.1
29.3
28.9
29.2
29.3
29.8
31.2
29.4
30.7

65

15.2
17.3
16.9
19.4
19.0
21.4
21.0
21.4
21.9
21.5
22.8

1. These capacities are Net Capacities.


2. These ratings include the compressor, condenser fan and supply air blower motors.

22

Johnson Controls Unitary Products

718444-YTG-B-0412

Airflow Performance
Side Duct Application
DNZ024-060
Size
Model
(Tons)

024
(2.0)

DNZ

030
(2.5)

DNZ

036
(3.0)

DNZ

042
(3.5)

DNZ

048
(4.0)

DNZ

060
(5.0)

DNZ

Unit Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)

SCFM
719
781
902
827
988
1113
1233
1032
1185
1304
1445
1114
1223
1641
1378
1414
1713
1882
1556
1648
1767
1913
2103

0.2
W
115
137
187
163
251
322
394
236
317
395
515
176
230
404
310
331
544
703
416
489
595
739
952

SCFM
719
781
902
827
988
1113
1233
1032
1185
1304
1445
1114
1223
1641
1378
1414
1713
1882
1556
1648
1767
1913
2103

0.2
W
115
137
187
163
251
322
394
236
317
395
515
176
230
404
310
331
544
703
416
489
595
739
952

RPM
752
789
858
825
914
984
1050
789
859
913
976
642
679
751
749
763
872
931
802
843
892
946
1007

SCFM
617
691
824
937
759
916
1035
1145
921
1089
1214
1357
1498
1056
1418
1535
1665
1209
1253
1604
1786
1972
1522
1664
1819
1990

External Static Pressure (Inch Water Gauge)


0.4
0.6
0.8
W
RPM SCFM
W
RPM SCFM
W
130
858
155
891
207
949
734
223
1037
622
230
258
998
845
270
1075
722
271
933
316
1104
796
307
187
919
269
992
831
282
1067
333
1047
941
337
1108
818
329
394
1099 1040
388
1145
901
367
1078
425
1164
867
353
258
853
347
924
985
373
991
424
978
1114
448
1040
994
462
532
1041 1252
542
1097 1117
537
708
1108 1363
665
1157 1179
599
264
773
460
872
1288
492
942
1187
518
547
904
1398
582
976
1292
606
664
940
1514
701
1015 1399
720
343
840
366
851
587
940
1484
624
1005 1343
653
740
987
1671
769
1044 1522
783
946
1037 1851
949
1078 1689
927
529
917
633
954
1546
668
1015
769
996
1702
791
1049 1550
800
957
1047 1855
948
1086 1674
912

RPM
1116
1146
1162
1162
1184
1173
1098
1140
1178
997
1030
1067
1067
1099
1118
1102
1122

SCFM
1101
1203
1304
1231
1306
-

1.0
W
540
624
729
717
759
-

RPM
1044
1074
1106
1142
1142
-

SCFM
617
691
824
937
759
916
1035
1145
921
1089
1214
1357
1498
1056
1418
1535
1665
1209
1253
1604
1786
1972
1522
1664
1819
1990

External Static Pressure (Inch Water Gauge)


0.4
0.6
0.8
W
RPM SCFM
W
RPM SCFM
W
130
858
155
891
207
949
734
223
1037
622
230
258
998
845
270
1075
722
271
933
316
1104
796
307
187
919
269
992
831
282
1067
333
1047
941
337
1108
818
329
394
1099 1040
388
1145
901
367
1078
425
1164
867
353
258
853
347
924
985
373
991
424
978
1114
448
1040
994
462
532
1041 1252
542
1097 1117
537
708
1108 1363
665
1157 1179
599
264
773
460
872
1288
492
942
1187
518
547
904
1398
582
976
1292
606
664
940
1514
701
1015 1399
720
343
840
366
851
587
940
1484
624
1005 1343
653
740
987
1671
769
1044 1522
783
946
1037 1851
949
1078 1689
927
529
917
633
954
1546
668
1015
769
996
1702
791
1049 1550
800
957
1047 1855
948
1086 1674
912

RPM
1116
1146
1162
1162
1184
1173
1098
1140
1178
997
1030
1067
1067
1099
1118
1102
1122

SCFM
1101
1203
1304
1231
1306
-

1.0
W
540
624
729
717
759
-

RPM
1044
1074
1106
1142
1142
-

Bottom Duct Application


DNZ024-060
Size
Model
(Tons)

024
(2.0)

DNZ

030
(2.5)

DNZ

036
(3.0)

DNZ

042
(3.5)

DNZ

048
(4.0)

DNZ

060
(5.0)

DNZ

Unit Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)

Johnson Controls Unitary Products

RPM
752
789
858
825
914
984
1050
789
859
913
976
642
679
751
749
763
872
931
802
843
892
946
1007

23

718444-YTG-B-0412
Additional Static Resistance
Size
(Tons)

Model

024
(2.0)

DNZ

030
(2.5)

DNZ

036
(3.0)

DNZ

042
(3.5)

DNZ

048
(4.0)

DNZ

060
(5.0)

DNZ

CFM

Wet Indoor Coil

Economizer1

Filter/Frame Kit

Electric Heat

500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09

0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05

0.01
0.02
0.04
0.06
0.08
0.10
0.13
0.16
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11

1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

24

Johnson Controls Unitary Products

718444-YTG-B-0412
Gas Heat Minimum Supply Air
Supply Air (CFM)

Size
(Tons)

Model

024
(2.0)

DNZ

030
(2.5)

DNZ

036
(3.0)

DNZ

042
(3.5)

DNZ

048
(4.0)

DNZ

060
(5.0)

DNZ

Heat Size

Cooling
Min
600
600
750
750
750
1200
1200
1200
1200
1200
1050
1050
1050
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500

N036
D056
N036
N056
D056
N036
N056
D056
N072
D072
N065
N090
D090
N065
N090
D090
N110
D110
N065
N090
D090
N110
D110

Heating
Max
1000
1000
1250
1250
1250
1500
1500
1500
1500
1500
1750
1750
1750
2000
2000
2000
2000
2000
2100
2100
2100
2100
2100

Min
610
860
610
860
860
610
940
940
1110
1110
1080
1070
1070
1080
1230
1230
1330
1330
1080
1230
1230
1330
1330

Max
1330
1730
1330
1730
1730
1330
2070
2070
2220
2220
2370
1780
1780
2370
2290
2290
2220
2220
2370
2290
2290
2220
2220

Indoor Blower Specifications


Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)

HP

RPM

Motor
Eff.

SF

Frame

DNZ

1/2

Variable

0.8

1.0

48

DNZ

3/4

Variable

0.8

1.0

48

DNZ

3/4

Variable

0.8

1.0

48

DNZ

3/4

Variable

0.8

1.0

48

DNZ

Variable

0.8

1.0

48

DNZ

Variable

0.8

1.0

48

Model

Sound Performance
Outdoor Sound Power Levels
Size
(Tons)
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)

Model

Sound Rating1
dB (A)

125

Octave Band Centerline Frequency (Hz)


250
500
1000
2000
4000

8000

DNZ

77

64

65.5

68

72.5

64.5

60.5

48.5

DNZ

74

63.5

64.5

66.5

67

63

57.5

51.5

DNZ

74

66.5

66.5

69.5

68

63

59

49.5

DNZ

79

70

70.5

73.5

73

69.5

67

66

DNZ

79

70.5

71

73.5

73

70

66

66

DNZ

80

73

71.5

74.5

75

70.5

67

62.5

1. Rated in accordance with AHRI 270 standard.

Johnson Controls Unitary Products

25

718444-YTG-B-0412

Electrical Data
DNZ024-060 Gas Heat
Size
(Tons)
DNZ
024
(2.0)
030
(2.5)
036
(3.0)
042
(3.5)
048
(4.0)
060
(5.0)

Volt

Compressors
(each)
RLA LRA

MCC

OD Fan
Motors
(each)

Supply
Blower
Motor

FLA

FLA

MCA1
(Amps)

Max
Fuse2/
Breaker3
Size
(Amps)

208/230-1-60 9.3

43

15

1.4

4.1

17.1

25

208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60
208/230-1-60
208/230-3-60
460-3-60

74
68
34
74
68
34
88
68
34
115
120
50
150
120
70

21
14
7
23
14
7
25
15
8
32
25
12
41
28
15

1.3
1.3
0.75
1.3
1.3
0.8
1.7
1.7
1.0
1.7
1.7
1.0
2.3
2.3
1.3

6.0
6.0
3.0
6.0
6.0
3.0
6.0
6.0
3.0
7.6
7.6
3.8
7.6
7.6
3.8

23.7
18.1
8.6
25.7
18.7
9.4
27.3
19.3
10.4
34.9
29.3
14.4
42.7
32.3
17.1

30
25
15
35
25
15
35
25
15
45
40
20
60
40
25

13.1
8.6
4.5
14.7
9.1
4.5
15.7
9.3
5.1
20.5
16.0
7.7
26.2
17.9
9.6

1. Minimum Circuit Ampacity.


2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.

26

Johnson Controls Unitary Products

Johnson Controls Unitary Products

202/Y

COMPR

103/BR

227/BK
802/BK

102/Y

PR

BR

BK

BL

BK

(LOW)

220/BK

245/PR

RED

OUTDOOR
FAN

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

GAS VALVE

236/0

201/BR
203/BR

BLK

P1

806/BR

225/Y
800/Y

RC1

226/BL
801/BL

105/R

BK

M
230V

BLK

BR

PV/MV

MV

PV

4 281/BR

3 124/BK

2 GRN

1 127/PR

BLU

BLK

ALT
GAS VALVE

105/BL

RED

277/Y
110/BK

279/W

RC2

ID_FAN

DRAFT
MOTOR

PR

FS

IND
H-IND

HEAT
COOL
L1

CONT

PR
104/R

202/Y

227/BK
802/BK

226/BL,801/BL
229/BL,805/BL
(SEE NOTE 6)

LR (SEE NOTE 6)

ACST

ALTERNATE CAPACITOR WIRING

103/BR

PR

807/BL

103/BR

CONTROL BOX

RC1/RC2

807/BL

102/Y
104/R

104/R

BR

GND
LUG

127/PR

228/BK,803/BK,804/BK
228/BK,803/BK,804/BK

222/R

BLU
244/PR

107/PR

229/BL (SEE NOTE 6)


805/BL

BK

BK

245/PR

T2

A
M1
B
L1
L2

T1

24VAC

248/O
244/PR

236/O
205/R

205/R
224/R

215/R

W2

W1

C
G

124/BK
110/BK
100/BK

101/BK

HP

LP

CCH

PS

LS

RS

ALS

BK
101/BK

201/BR
281/BR

SEC

T1

806/BR
203/BR

224/R
215/R
222/R

230

208

100/BK

M1

COOL

AUTO

HEAT

OFF

229/BL
805/BL

TC1

TH2

TH1

TC2

TC1
ANT

TH2 ANT

TH1 ANT

TC2
ANT

ALS
ASCT
CCH
COMPR
DM
EMCB
GND
HP
IDFAN
LP
LS
M1
ODFAN
PS
RC1/RC2
RS
SC1
SR1
T1

AUTO

FAN SWITCH

ON

228/BK
803/804

ROOM THERMOSTAT

LP

L2

LEGEND
AUXILARY LIMIT SWITCH
ANTI-SHORT CYCLE TIMER (OPTIONAL)
CRANK CASE HEATER (OPTIONAL)
COMPRESSOR
DRAFT MOTOR
ELEC, MOTOR CONTROL BOARD
GROUND
HIGH PRESS. SW. OPENS @ 625PSIG (R410A) / 380PSIG (R22)
INDOOR FAN MOTOR
LOW PRESSURE SWITCH OPENS @ 7 PSIG
LIMIT SWITCH
CONTACTOR, COMPR. AND OD FAN
OUTDOOR FAN MOTOR
PRESSURE SWITCH
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
ROLLOUT SWITCH
START CAPACITOR (OPTIONAL)
START RELAY (OPTIONAL)
TRANSFORMER, 24V, 230V

CONTROL BOARD SETTINGS:


COMBUSTION BLOWER POSTPURGE: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
STRAIGHT LINE INDICATES SWITCH POSITION

BLK

W2

W1

Y2

Y1

Rc

HP

90
120
180

60

PS

L2

203/BR

201/BR

245/PR

244/PR 3

202/Y

W2

P1-5

P1-8

P1-3

W1

24VAC

P1-6

P1-9

248/O

JW6 PRESENT
WHEN HIGH
PRESSURE
SWITCH NOT
USED

K1

K3

K6

K6

K5

K5

K7

K7

JW6

K4

K2

IND

HEAT

COOL

CONT

FS

L1

180

120

90

60

P1-2

P1-1

P1-4

P1-7

H-IND

BLOWER
OFF DELAY
SELECT

SPARK
TRANSFORMER

CONTINUOUS
POWER FOR
LOGIC

ROLLOUT SWITCH INPUT


POWER TO GAS RELAY
COIL

SW1

ALS

EMCB

236/O

205/R

HIGH LIMIT INPUT

LS

110/BK

9.

7.

FIELD WIRING
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES

SELECT INDOOR BLOWER SPEED TO REMAIN WITHIN THE TEMPERATURE


RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
400 CFM/TON IN COOLING.

SHUNT CONTACT ALSO USED WITH CRANKCASE


HEATER. (OPTIONAL)

6. REMOVED

BLK

BLU

5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.

4. FACTORY WIRED FOR 230V. FOR 208V OPERATION, MOVE WIRE 107/PR TO
208V TAP ON TRANSFORMER T1.

PILOT

RED

2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING


CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERTION.IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE
REMOVED,IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600 VOLT
WIRE OREQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY
PROPER OPERATION AFTER SERVICING.
3. MOTORS INHERENTLY PROTECTED

SC1

FLAME SENSE

1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR


NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.

NOTES:

BLK

222/R

107/PR

237/Y

231/R

24V SEC
40 VA

208V
PRI

4 TUBE
042

3 TUBE
042

4 TUBE
036

3 TUBE
024-036

2 TUBE
024-036

100/BK
L2

M1
T2

279/W

277/Y

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

DEVICE

L1

M1
T1

(LOW)

5 TUBE
048-060

4 TUBE
048-060

4 TUBE
048-060

4 TUBE
042

3 TUBE
048-060

101/BK

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

GRN

DM

OD_FAN
230-1-60
1

COMPR
230-1-60
1

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/200
12
----150
6
120
9
160
12
----270
12
----140
6
110
9
160
12
----200
12
----150
6
120
9
160
12
----270
12
----175
6
145
9
160
12
----270
12
----160
6
130
9
160
12
-----

TEMPERATURE CONTROLS

M
230V

ID_FAN

PR

BR

BK

102/Y

103/BR

124/BK

DEVICE

RC2

RC1

UNIT SIZE

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/200
12
----140
6
110
9
160
12
----270
12
----160
6
130
9
160
12
----270
12
----140
6
9
130
160
12
----200
12
----140
6
110
9
160
12
----270
12
----140
6
130
9
160
12
-----

TEMPERATURE CONTROLS

SR1
2

C
T1

POWER SUPPLY USE COPPER CONDUCTORS ONLY


208/230-1-60

233/W

848766-UWD-A-0312

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT

UNIT SIZE

C
GAS_VALVE

RS

BLK

281/BR

215/R

230V

107/PR

224/R

ELEMENTARY DIAGRAM

234/BK

CONNECTION DIAGRAM

GND

104/R

OPTIONAL CCH
S/P CONFIGURATION
CCH
L1
BLK

PRP
127/PR

OPTIONAL CCH
D/P CONFIGURATION
CCH_
BLK
L1

COOLING UNIT WITH GAS HEAT

718444-YTG-B-0412

Typical DNZ024-060 Wiring Diagrams

Typical DNZ024-060 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram

27

202/Y

245/PR

BLU

YEL

222/R

244/PR

COMPR

103/BR

227/BK
802/BK

102/Y

PR

BR

BK

(LOW)

248/O

245/PR

RED

OUTDOOR
FAN

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

HI

MV

PV

BL

BK

GAS VALVE

236/0

201/BR
203/BR

BLK

P1

806/BR

225/Y
800/Y

RC1

226/BL
801/BL

105/R

BK

M
230V

BLK

RED

4 281/BR

3 124/BK

2 GRN

1 127/PR

BR

105/BL

277/Y
110/BK

279/W

RC2

ID_FAN

DRAFT
MOTOR

FS

IND
H-IND

COOL
L1

HEAT

CONT

PR
104/R

202/Y

227/BK
802/BK

226/BL,801/BL
229/BL,805/BL
(SEE NOTE 6)

LR (SEE NOTE 6)

ACST

ALTERNATE CAPACITOR WIRING

103/BR

PR

1
807/BL

103/BR

CONTROL BOX

RC1/RC2

807/BL

102/Y
104/R

104/R

BR

127/PR
107/PR WHT

228/BK,803/BK,804/BK
228/BK,803/BK,804/BK

T2

229/BL (SEE NOTE 6)


805/BL

BK

BK

T1

A
M1
B
L1
L2

24VAC

248/O
244/PR

236/O
205/R

205/R
224/R

215/R

W2

W1

C
G

124/BK
110/BK
100/BK

101/BK

HP

LP

CCH

PS

LS

RS

ALS

BK
101/BK

201/BR
281/BR

SEC

806/BR
203/BR

224/R
215/R
222/R

T1

208

230

GND
LUG

M1

TC1

TH2

TH1

TC2

ALS
ASCT
CCH
COMPR
DM
EMCB
GND
HP
IDFAN
LP
LS
LR
M1
ODFAN
PS
RC1/RC2
RS
SC1
SR1
T1

AUTO

TH2 ANT

TH1 ANT

TC2
ANT

FAN SWITCH

ON

FIELD WIRING
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES

COOL

AUTO

HEAT

OFF

TC1
ANT

ROOM THERMOSTAT

228/BK
803/804

HP

L2

AUXILARY LIMIT SWITCH


ANTI-SHORT CYCLE TIMER (OPTIONAL)
CRANK CASE HEATER (OPTIONAL)
COMPRESSOR
DRAFT MOTOR
ELEC, MOTOR CONTROL BOARD
GROUND
HIGH PRESS. SW. OPENS @ 625PSIG (R410A) / 380PSIG (R22)
INDOOR FAN MOTOR
LOW PRESSURE SWITCH OPENS @ 7 PSIG
LIMIT SWITCH
LOCK OUT RELAY (OPTIONAL)
CONTACTOR, COMPR. AND OD FAN
OUTDOOR FAN MOTOR
PRESSURE SWITCH
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
ROLLOUT SWITCH
START CAPACITOR (OPTIONAL)
START RELAY (OPTIONAL)
TRANSFORMER, 24V, 230V

LEGEND

CONTROL BOARD SETTINGS:


COMBUSTION BLOWER POSTPURGE: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
STRAIGHT LINE INDICATES SWITCH POSITION.

229/BL
805/BL
LP

BLK

W2

W1

Y2

Y1

Rc

90
120
180

60

L2

203/BR

201/BR

245/PR

244/PR 3

202/Y

W2

P1-5

P1-8

P1-3

W1

24VAC

P1-6

P1-9

248/O

EMCB

236/O

205/R

JW6 PRESENT
WHEN HIGH
PRESSURE
SWITCH NOT
USED

K1

K5

K5

K7

K7

JW6

K4

K2

CONT

P1-2

P1-1

P1-4

P1-7

FS

L1

H-IND

IND

HEAT

COOL

180

120

90

60

ALS

SW1

BLOWER
OFF DELAY
SELECT

SPARK
TRANSFORMER

K3

K6

K6

CONTINUOUS
POWER FOR
LOGIC

ROLLOUT SWITCH INPUT


POWER TO GAS RELAY
COIL

HIGH LIMIT INPUT

LS

BLU

YEL

BLK

2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING


CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERTION.IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE
REMOVED,IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600 VOLT
WIRE OREQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY
PROPER OPERATION AFTER SERVICING.

9. OPTIONAL; SC1/SR1 OR PTCR MAY BE USED; (DO NOT USE BOTH TOGETHER).

8. SELECT INDOOR BLOWER SPEEDS TO REMAIN WITHIN THE TEMPERATURE


RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
400 CFM/TON IN COOLING.

7. SHUNT CONTACT ALSO USED WITH CRANKCASE


HEATER. (OPTIONAL)

6. REMOVED.

5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.

4. FACTORY WIRED FOR 230V. FOR 208V OPERATION, MOVE WIRE 107/PR TO
208V TAP ON TRANSFORMER T1.

3. MOTORS INHERENTLY PROTECTED

PILOT

RED

231/R

9
SR1
2

C
T1

107/PR

100/BK
7
M1
L2
T2

230/BL

279/W

277/Y

L1

M1

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/270
12
----155
6
125
9
160
12
----270
12
----150
6
120
9
160
12
----270
12
----160
6
130
9
160
12
----270
12
----150
6
120
9
160
12
----270
12
----160
6
130
9
160
12
----270
12
----175
6
145
9
160
12
----270
12
----170
6
140
9
160
12
-----

3
1

P2

9
PTCR

ID_FAN

M
230V

124/BK

S2

PR

BR

BK

102/Y

103/BR

101/BK

RED

COMPR
230-1-60
1

GRN

DM

OD_FAN
230-1-60
1

112/BR

5 TUBE
048-060

4 TUBE
048-060

4 TUBE
042

4 TUBE
036

3 TUBE
036

3 TUBE
030

3 TUBE
024

UNIT SIZE

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

DEVICE

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/270
12
----150
6
120
9
160
12
----270
12
----150
6
120
9
160
12
----270
12
----160
6
130
9
160
12
----270
12
----150
6
120
9
160
12
----270
12
----170
6
140
9
160
12
----270
12
----175
6
145
9
160
12
----270
12
----170
6
140
9
160
12
-----

TEMPERATURE CONTROLS D*NZ 2-STAGE UNITS

(HIGH)

(MED/HIGH)

(MED)

140/R

RC2

111/R

RC1

851727-UWD-A-0312

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT

5 TUBE
048-060

4 TUBE
048-060

4 TUBE
042

4 TUBE
036

3 TUBE
036

3 TUBE
030

3 TUBE
024

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

DEVICE

(LOW)
(LOW/MED)

T1

TEMPERATURE CONTROLS D*NP 2-STAGE UNITS

24V SEC
40 VA

208V
PRI

UNIT SIZE

C
GAS_VALVE

HI

MV

PV

110/BK

BLK

RS

237/Y

215/R

230V

281/BR

9
SC1

FLAME SENSE

1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR


NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.

NOTES:

PS

BLK

222/R

100/BK

104/R

107/PR

224/R

ELEMENTARY DIAGRAM

234/BK

POWER SUPPLY USE COPPER CONDUCTORS ONLY


208/230-1-60

233/W

CONNECTION DIAGRAM

GND

WHT
127/PR

OPTIONAL CCH
S/P CONFIGURATION
CCH
L1
BLK

OPTIONAL CCH
D/P CONFIGURATION
CCH_
BLK
L1

28
1

COOLING UNIT WITH GAS HEAT

718444-YTG-B-0412

Typical DNZ024-060 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram

Johnson Controls Unitary Products

Johnson Controls Unitary Products

L1

212/R

244/PR

BLU

105/BL

T3

227/BK
802/BK

L2

PR

BR

BK

228/BK,803/BK,804/BK
228/BK,803/BK,804/BK

123/BL

126/Y

L3

T2

L3

BL

BK

(LOW)

248/O

245/PR

RED

OUTDOOR
FAN

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

GAS VALVE

236/0

BLK

P1

CB

200/R
212/R
225/Y
800/Y

4
C

BLU

BLK

RED

BLK

277/Y
110/BK

279/W

RC2

226/BL
801/BL

BK

M
230V

2
806/BR

281/BR

124/BK

GRN

1 127/PR

PV/MV

MV

PV

ALT
GAS VALVE

BR

105/BL

202/Y

227/BK
802/BK

226/BL,801/BL
229/BL,805/BL
(SEE NOTE 6)

LR (SEE NOTE 6)

ID_FAN

DRAFT
MOTOR

PR

FS

H-IND

IND

L1

COOL

HEAT

CONT

PR

807/BL

3
ACST

CONTROL BOX

806/BR
203/BR

126/Y

GND
LUG

201/BR
203/BR

127/PR
107/PR
PRP

229/BL (SEE NOTE 6)


805/BL

BK

BK

245/PR

248/O
244/PR

236/O
205/R

205/R
213/R

215/R
213/R

W2

W1

L2

M1

24VAC

123/BL

C
G

COMPR

121/BK

HP

LP

CCH

PS

LS

RS

ALS

202/Y

T1

807/BL

121/BK
BLK

L1

100/BK
124/BK

201/BR
281/BR

100/BK

SEC

T1

208

110/BK

215/R
200/R

230

107/PR

CONNECTION DIAGRAM

HP

CCH

TC1

TH2

TH1

TC2

TC1
ANT

TRANSFORMER, 24V, 230V

COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR


ROLLOUT SWITCH

T1

RC1/RC2
RS

PRESSURE SWITCH

OUTDOOR FAN MOTOR

CONTACTOR, COMPR. AND OD FAN

PS

ODFAN

M1

LIMIT SWITCH
LOCK OUT RELAY (OPTIONAL)

LOW PRESSURE SWITCH OPENS @ 7 PSIG

LS
LR

LP

INDOOR FAN MOTOR

HIGH PRESS. SW. OPENS @ 625PSIG (R410A) / 380PSIG (R22)

IDFAN

HP

TH2 ANT

GROUND

BLK

AUTO

TH1 ANT

TC2
ANT

GND

ELEC, MOTOR CONTROL BOARD

EMCB

CRANK CASE HEATER (OPTIONAL)


COMPRESSOR
DRAFT MOTOR

CIRCUIT BREAKER

DM

CCH
COMPR

ANTI-SHORT CYCLE TIMER (OPTIONAL)

AUXILARY LIMIT SWITCH

LEGEND

ON

BLK

FAN SWITCH

ROOM THERMOSTAT

L2

L1

CB

ASCT

ALS

COOL

AUTO

HEAT

OFF

228/BK
803/804

BLK

CONTROL BOARD SETTINGS:


COMBUSTION BLOWER POSTPURGE: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
STRAIGHT LINE INDICATES SWITCH POSITION

LP

BLK

M1

229/BL
805/BL

CCH_

OPTIONAL CCH
S/P CONFIGURATION

W2

W1

Y2

Y1

Rc

L2

L1

180

120

90

60

203/BR

201/BR

245/PR

244/PR

W2

P1-5

P1-8

P1-3

W1

24VAC

P1-6

P1-9

205/R

212/R

JW6 PRESENT
WHEN HIGH
PRESSURE
SWITCH NOT
USED

K1

K3

K6

K6

K5

K5

K7

K7

BLOWER
OFF DELAY
SELECT

EMCB

JW6

K4

K2

FS

L1

180

120

90

60

P1-2

P1-1

P1-4

P1-7

H-IND

IND

HEAT

COOL

CONT

SW1

ALS

213/R

SPARK
TRANSFORMER

CONTINUOUS
POWER FOR
LOGIC

ROLLOUT SWITCH INPUT


POWER TO GAS RELAY
COIL

HIGH LIMIT INPUT

LS

RS

9.

7.

FIELD WIRING
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES

SELECT INDOOR BLOWER SPEED TO REMAIN WITHIN THE TEMPERATURE


RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
400 CFM/TON IN COOLING.

REMOVED

6. REMOVED.

5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.

4. FACTORY WIRED FOR 230V. FOR 208V OPERATION, MOVE WIRE 107/PR TO
208V TAP ON TRANSFORMER T1.

3. MOTORS INHERENTLY PROTECTED

2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING


CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERTION.IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE
REMOVED,IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600 VOLT
WIRE OREQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY
PROPER OPERATION AFTER SERVICING.

1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR


NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.

NOTES:

PS

236/O
202/Y

248/O

GND
4

BLU

BLK

RED

208V
PRI

PILOT

CB

215/R

C
T1

100/
BK
L2

M1_
M1_

T1

L3

279/W

277/Y

T2

ALS

LS

RS

ALS

LS

RS

ALS

LS

RS

ALS

LS

RS

ALS

LS

RS

DEVICE

160

140

270

160

140

200

160

140

270

160

160

270

160

140

200

OPEN

12

12

12

12

12

12

12

12

12

12

+/-

---

130

---

---

110

---

---

130

---

---

130

---

---

110

---

CLOSE

OPERATING TEMPERATURE (DEG F

T3

PRP

M1_

105/BL

+/-

---

---

---

---

---

---

---

---

---

---

5 TUBE
048-060

4 TUBE
048-060

4 TUBE
048-060

4 TUBE
042

3 TUBE
048-060

UNIT SIZE

124/BK

281/BR

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

(LOW)

127/PR

RC2

M
230V

ID_FAN

ALS

LS

RS

ALS

LS

RS

ALS

LS

RS

ALS

LS

RS

ALS

LS

L2

GRN

DM

160

160

270

160

175

270

160

150

200

160

140

270

160

150

200

OPEN

---

130

---

---

145

---

---

120

---

---

110

---

---

120

---

CLOSE

---

---

---

---

---

---

---

---

---

---

851400-UWD-C-0312

12

12

12

12

12

12

12

12

12

12

+/-

+/-

OD_FAN
230-1-60
1

L3

COMPR
230-3-60
3

L1

OPERATING TEMPERATURE (DEG F

TEMPERATURE CONTROLS

RS

DEVICE

PR

BR

BK

126/Y

123/BL

121/BK

ELEMENTARY DIAGRAM
USE COPPER CONDUCTORS ONLY

TEMPERATURE CONTROLS

L1

POWER SUPPLY
208/230-3-60

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT

4 TUBE
042

3 TUBE
042

4 TUBE
036

3 TUBE
024-036

2 TUBE
024-036

UNIT SIZE

C
GAS_VALVE

110/BK

BLK

3.2 AMP

24V SEC
75 VA

FLAME SENSE

230V

107/PR

200/R

OPTIONAL CCH
D/P CONFIGURATION

COOLING UNIT WITH GAS HEAT

718444-YTG-B-0412

Typical DNZ030-060 Cooling Unit with Single Stage Gas Heat 208/230-3-60 volt Wiring Diagram

29

215/R

BL

BK

COMPR

L2

227/BK
802/BK

126/Y

PR

BR

BK

(LOW)

248/O

245/PR

RED

(MED)

OUTDOOR
FAN

(HIGH)

(MED/HIGH)

225/Y
800/Y

BLK

BLU

BLK

202/Y

227/BK
802/BK

PRP

136/BK
124/BK

BR

PV/MV

MV

PV

ALT
GAS VALVE

TB1

RC2

4 281/BR

3 136/BK

2 GRN

1 127/PR

RED

277/Y
110/BK

279/W

127/PR
131/PR

110/BK

PR

226/BL
801/BL

105/BL

806/BR

226/BL,801/BL
229/BL,805/BL
(SEE NOTE 6)

LR (SEE NOTE 6)

ID_FAN

M
230V

3
ACST

BK

DRAFT
MOTOR

PR

FS

IND
H-IND

HEAT
COOL
L1

CONT

T2
460V

T2
575V

131/PR

136/BK
131/PR

(LOW/MED)

GAS VALVE

201/BR
203/BR

236/0

BLK

P1

200/R
212/R

108/PR
120/BK

T2

460

136/BK
131/PR

T2

228/BK,803/BK,804/BK
228/BK,803/BK,804/BK

123/BL

L3

212/R

244/PR

BLU

120/BK

126/Y
806/BR
203/BR

229/BL (SEE NOTE 6)


805/BL

BK

BK

245/PR

248/O
244/PR

236/O
205/R

205/R
224/R

T3

L3

108/PR
107/PR

105/BL

24VAC

L1

W2

W1

C
G

121/BK

HP

LP

CCH

PS

LS

RS

ALS

202/Y

T2

M1

L2

123/BL

121/BK
BK
807/BL

T1

L1

100/BK
120/BK

CB

575

201/BR
281/BR

575

SEC

230

460

215/R
200/R

230

460

807/BL

575

T1

460

230

M1

COOL

AUTO

HEAT

OFF

HP

TC1

TH2

TH1

TC2

TC1
ANT

ALS
ASCT
CB
CCH
COMPR
DM
EMCB
GND
HP
IDFAN
LP
LS
M1
ODFAN
PS
RC1/RC2
RS
TB1
T2
T1

AUTO

TH2 ANT

TH1 ANT

TC2
ANT

FAN SWITCH

ON

BLK

ROOM THERMOSTAT

228/BK
803/804

L2

LEGEND
AUXILARY LIMIT SWITCH
ANTI-SHORT CYCLE TIMER (OPTIONAL)
CIRCUIT BREAKER
CRANK CASE HEATER (OPTIONAL)
COMPRESSOR
DRAFT MOTOR
ELEC, MOTOR CONTROL BOARD
GROUND
HIGH PRESS. SW. OPENS @ 625PSIG (R410A) / 380PSIG (R22)
INDOOR FAN MOTOR
LOW PRESSURE SWITCH OPENS @ 7 PSIG
LIMIT SWITCH
CONTACTOR, COMPR. AND OD FAN
OUTDOOR FAN MOTOR
PRESSURE SWITCH
COMPRESSOR START & OUTDOOR FAN RUN CAPACITOR
ROLLOUT SWITCH
TERMINAL BLOCK
TRANSFORMER, 240V, 460V
TRANSFORMER, 24V, 460V

W2

W1

Y2

Y1

Rc

90
120
180

60

L2

OPTIONAL CCH
S/P CONFIGURATION
CCH
L1
BLK

CONTROL BOARD SETTINGS:


COMBUSTION BLOWER POSTPURGE: 30 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 30 SEC
INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
STRAIGHT LINE INDICATES SWITCH POSITION

229/BL
805/BL
LP

BLK

OPTIONAL CCH
D/P CONFIGURATION
CCH_
BLK
L1

203/BR

201/BR

245/PR

244/PR 3

W2

P1-5

P1-8

P1-3

W1

24VAC

P1-6

P1-9

RS
224/R

JW6 PRESENT
WHEN HIGH
PRESSURE
SWITCH NOT
USED

K1

K3

K6

K6

K5

K5

K7

K7

JW6

K4

K2

IND

HEAT

COOL

CONT

FS

L1

180

120

90

60

P1-2

P1-1

P1-4

P1-7

H-IND

BLOWER
OFF DELAY
SELECT

SPARK
TRANSFORMER

CONTINUOUS
POWER FOR
LOGIC

ROLLOUT SWITCH INPUT


POWER TO GAS RELAY
COIL

SW1

ALS

EMCB

205/R

212/R

HIGH LIMIT INPUT

LS

2. CAUTION: LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING


CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERTION.IF ANY OF THE WIRE, AS SUPPLIED WITH THE UNIT MUST BE
REMOVED,IT MUST BE REPLACED WITH TYPE 105 DEGREE C, 600 VOLT
WIRE OREQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION. VERIFY
PROPER OPERATION AFTER SERVICING.

BLU

BLK

RED

REMOVED

9.

FIELD WIRING
OPTIONAL WIRING AND DEVICES
FACTORY WIRING AND DEVICES

SELECT INDOOR BLOWER SPEED TO REMAIN WITHIN THE TEMPERATURE


RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
400 CFM/TON IN COOLING.

7. REMOVED

6.

5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.

215/R

C
T1
T2

L3

M1_

108/PR
120/BK

T1
M1_

279/W

277/Y

A TB1 B

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

(LOW)

5 TUBE
048-060

4 TUBE
048-060

4 TUBE
048-060

4 TUBE
042

3 TUBE
048-060

M
230V

ID_FAN

PR

BR

BK

126/Y

123/BL

121/BK

L1

DM

RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS
RS
LS
ALS

GRN

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/200
12
----150
6
120
9
160
12
----270
12
----140
6
110
9
160
12
----200
12
----150
6
120
9
160
12
----270
12
----175
6
145
9
160
12
----270
12
----160
6
130
9
160
12
-----

OD_FAN

L3

COMPR
L2 460-3-60
3

TEMPERATURE CONTROLS

DEVICE

124/BK

UNIT SIZE

281/BR

(HIGH)

(MED/HIGH)

(MED)

(LOW/MED)

127/PR

PRP

T2

RC2

T3

105/BL

OPERATING TEMPERATURE (DEG) F


OPEN
+/CLOSE
+/200
12
----140
6
110
9
160
12
----270
12
----160
6
130
9
160
12
----270
12
----140
6
9
130
160
12
----200
12
----140
6
110
9
160
12
----270
12
----140
6
130
9
160
12
-----

TEMPERATURE CONTROLS

L2

M1_

DEVICE

L1

848982-UWD-A-0312

CAUTION - OPEN ALL DISCONNECTS


BEFORE SERVICING THIS UNIT

4 TUBE
042

3 TUBE
042

4 TUBE
036

3 TUBE
024-036

2 TUBE
024-036

UNIT SIZE

100/
BK

C
GAS_VALVE

110/BK

BLK

3.2 AMP

CB

PILOT

4. FOR 575 VOLT OPERATION MOVE WIRE 108/PRP TO 575V TAP ON TRANSFORMER T2
AND WIRE 120/BK TO 575V TAP ON TRANSFORMER T2.

3. MOTORS INHERENTLY PROTECTED

107/PR

24V SEC
75 VA

460/575

FLAME SENSE

1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR


NATIONAL CODES IN EFFECT AT TIME OF INSTALLATION OF THIS UNIT.

NOTES:

PS

236/O
202/Y

248/O

GND

136/BK

CONTROL BOX

575

GND
LUG

131/PR

100/BK

460

107/PR

230

CONNECTION DIAGRAM

230

575

230

ELEMENTARY DIAGRAM

460

460/575

200/R

POWER SUPPLYUSE COPPER CONDUCTORS ONLY


460/575-3-60

575

30
P

COOLING UNIT WITH GAS HEAT

718444-YTG-B-0412

Typical DNZ030-060 Cooling Unit with Single Stage Gas Heat 460-3-60 volt Wiring Diagram

Johnson Controls Unitary Products

718444-YTG-B-0412

Weights and Dimensions


DNZ Unit Weights
Unit 4 Point Load Weight
"D"
CENTER OF
GRAVITY

FRONT
OF
UNIT

"C"

"A"

49-1/8

"B"

Weight (lbs.)
Center of Gravity
Size
Model
(Tons)
Shipping Operating
X
Y
024
DNZ
383
378
23.8
20
(2.0)
030
DNZ
403
398
24
20
(2.5)
036
DNZ
407
402
24
20
(3.0)
042
DNZ
465
460
22.7
21.3
(3.5)
048
DNZ
470
465
22.7
21.3
(4.0)
060
DNZ
485
480
23
21
(5.0)

Johnson Controls Unitary Products

47-1/4

4 Point Load Location (lbs.)


A
B
C
D
77

77

112

112

81

81

119

117

81

82

120

119

105

95

124

137

106

96

125

138

106

99

132

142

31

718444-YTG-B-0412

Gas Unit Dimensions


VENT AIR OUTLET HOOD
GAS SUPPLY
1-1/4" DIAMETER HOLE
(1/2" NPTF CONNECTION)

BLOWER SERVICE ACCESS


COMPARTMENT PANEL

CONDENSER COIL

RIG

HT

UNIT CONDENSATE
CONNECTION 3/4" NPTF
(TRAP RECOMMENDED)

HIGH VOLTAGE
CONN. 1-3/8" DIA.
KNOCKOUT

LE

2-3/8

FT

NT

O
FR

3-3/4

REFRIGERANT
CONNECTIONS

2-1/2

COMBUSTION AIR
INLET LOUVERS

GAS SUPPLY
1-1/4" DIA. KNOCKOUT
(1/2" NPTF CONNECTION)
LOW VOLTAGE
CONN.1-3/8" DIA.
KNOCKOUT x 7/8" HOLE

FRONT
5-3/8

1-1/2

11

12-3/4

47-1/4

(OVERALL)

3-1/3

49-1/8
(OVERALL)

GAS/ELECTRIC CONTROL
SERVICE ACCESS
COMPARTMENT PANEL

2-5/8

Gas Unit Dimensions


Unit Size
024, 030, 036
042, 048, 060

Dimensions
A
33-1/2
41-1/2

B
18-1/4
23-1/8

Gas Unit Clearances1 2


Direction
Top3
Front
Rear

Distance
(in.)
36
36
0

Direction
Right
Left
Bottom4

Distance
(in.)
12
24
0

1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air
discharge outlet.
4. Units may be installed on combustable floors made from wood or class A, B or C roof covering
materials.

Unit Accessory Weights

32

Unit Accessory

Model

Add Economizer

All

Weight (lbs.)
Shipping
Operating
45
40

Johnson Controls Unitary Products

718444-YTG-B-0412
Unit Dimensions Front and Bottom

HIGH VOLTAGE
CONN. 1-3/32"
DIA. KNOCKOUT

8-7/8

11-7/8

19-1/4
FRONT

GAS SUPPLY 1-5/8"


DIA. KNOCKOUT (1/2"
NPTF CONNECTION)

LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT

LOW VOLTAGE
CONN. 7/8" DIA.
KNOCKOUT

HIGH VOLTAGE
CONN. 1-31/32" x 7/8"
KNOCKOUT

4-5/8
CONDENSATE
DRAIN 3/4" NPTF

40-1/2

26-3/4
22-1/2

43-1/2
6

Unit Dimensions Back and Bottom

SIDE SUPPLY
AIR OPENING
*CONDENSER
COIL

14-1/2

28-3/8
14-1/2

BACK

BOTTOM SUPPLY
AIR OPENING

3-3/8
SIDE RETURN
AIR OPENING

14-1/2
4 4-1/4
1-3/4

15

15
1-3/4

15
28-9/16

Johnson Controls Unitary Products

3-1/2

1-3/4

BOTTOM RETURN
AIR OPENING

33

718444-YTG-B-0412
Unit Typical Duct Applications
ROOF CURB
INSTALLATION
REAR DUCT

ROOF CURB
INSTALLATION
BOTTOM DUCT

SLAB ON GROUND
INSTALLATION
Unit Typical Slab on Ground Installation (Gas Model Shown)
TO POWER SUPPLY
FIELD SUPPLIED
DISCONNECT SWITCH
LOCATED TO REAR OF UNIT

CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN AIR
DUCT
SUPPLY AIR
DUCT

TO GAS
SUPPLY LINE

MANUAL GAS
SHUT-OFF VALVE

34

Johnson Controls Unitary Products

718444-YTG-B-0412
Unit Typical Roof Curb Installation (Gas Model Shown)

MANUAL GAS
SHUT-OFF VALVE

FIELD SUPPLIED
DISCONNECT SWITCH
MOUNTED ON UNIT

TO POWER
SUPPLY

TO GAS
SUPPLY LINE
CONTROL WIRING TO
INDOOR THERMOSTAT

RETURN
AIR DUCT
SUPPLY
AIR DUCT

Unit Accessory Dimensions


Roof Curb1
RECOMMENDED
DUCT SIZE
17-1/2" x 16-3/4"
42-2/3
40-3/4

3-1/2

45-1/8
17-5/8

17-1/4

43-1/4

OPENING FOR
RETURN AIR DUCT

22

OPENING FOR
SUPPLY AIR DUCT

14

1
RECOMMENDED
DUCT SIZE
17-1/8" x 21-1/2"

1. 8 Roof Curb also available.

Johnson Controls Unitary Products

35

Roof Curb Cross Section


1"
3/4" x 1" WIDE GASKETING FOR CURB FRAME
AND ALL DUCT SUPPORT SURFACES

UNIT BASE
UNIT BASE RAIL
WOOD NAILER
COUNTERFLASHING
8" MIN. ABOVE FINISHED ROOF

14"
CANT STRIP
CURB FRAME

INSULATION AND ROOFING MATERIAL


INSULATION

ROOF DECK AND ROOFING MATERIAL

Subject to change without notice. Printed in U.S.A.


Copyright 2012 by Johnson Controls, Inc. All rights reserved.
York International Corporation
5005 York Drive
Norman, OK 73069

718444-YTG-B-0412
Supersedes: 718444-YTG-A-0811