Instruction Manual
The Digiplex Programming Guide is required to program the PGM Activation and Deactivation Events
Section [003], [005], [007] and [009] A PGM Activation Event determines which event will activate a PGM output. The 4-Output Bus Modules PGM Activation Events are programmed in the same manner as those in the control panel. Each PGM can be programmed with a different activation event. Use the PGM Programming Table in the Digiplex Programming Guide to program the 4-Output Bus Modules PGM Activation Events. The following activation and deactivation events CANNOT be used with the 4-Output Bus Module: Intellizone and Access from Event Group Status 3 and all the events from the event group Status 4.
S PECIF ICATIONS
Power input: Number of outputs: 9 to16 VDC 4 form C relays rated @ 125V, 5A receptive load Current Consumption: Typical 13mA, 150mA max. (all PGMs active) Power-up indication: Green LED illuminates Proper operation: Red LED flashes Locate indication: Green LED flashes Bus fault indication: Green and red LEDs flash alternately Humidity: 95% maximum
INSTA LLATION
The 4-Output Bus Module is connected to the control panels communication bus. Connect the four terminals labeled red, black, green, and yellow of the module to the corresponding terminals on the control panel as shown in Figure 1. Refer to the Digiplex Installation & Reference Manual for the maximum allowable installation distance from the panel.
P ULSED O UTPUT
FOR
FIRE A LARM
Section [001] Option [2] When a PGM is programmed with this feature and a fire alarm occurs in the system, the 4-Output Bus Module will provide a pulsed fire alarm output for any PGM programmed with the Fire Alarm event as described in the Digiplex Reference & Installation Manual until the fire alarm is resolved. The PGM Deactivation Event(s) and the PGM Timer(s) for the PGM(s) programmed with this feature will be ignored. How Do I Program a PGM as a Pulsed Output? STEP 1: Enter Module Programming Mode STEP 2: Enter section [001] and enable option [2] STEP 3: Enter section [002] and program the PGM Deactivation Option corresponding to the desired PGM to Follow Event . Disable: Option [1] for PGM 1 Option [5] for PGM 3 Option [3] for PGM 2 Option [7] for PGM 4 Step 4: Enter the section corresponding to the desired PGMs Activation Event and program the Fire Alarm event. Enter: Section [003] for PGM 1 Section [007] for PGM 3 Section [005] for PGM 2 Section [009] for PGM 4
PGM T I MER
Section [011], [012], [013] and [014] Once a PGM output activates and its PGM Deactivation Option is set to follow the PGM Timer, the PGM will remain activated until the programmed value has elapsed. For each PGM enter a 3-digit decimal value between 001 and 255. Refer to the PGM Time Base Selection to determine whether the value will be in seconds or minutes.
P ROGRAMMI NG G UIDE
STEP 1: Press and hold the [0] key STEP 2: Enter the [INS TALLER CODE] STEP 3: Enter section [953] STEP 4: Enter the 4-Output Bus Modules 8-digit [SE RIAL NUMBER ] STEP 5: Enter the 3-digit [SECTION ] that you want to program STEP 6: Enter the required data SECTION [001]: General Options Option OFF [1] Future Use l N/A [2] Pulse Output for Fire Alarm l Disabled [3] Future Use l N/A [4] Future Use l N/A [5] Future Use l N/A [6] Future Use l N/A [7] Future Use l N/A [8] Future Use l N/A SECTION [002]: PGM Options Option [1] PGM 1 Deactivation Option [2] PGM 1 Time Base Selection [3] PGM 2 Deactivation Option [4] PGM 2 Time Base Selection [5] PGM 3 Deactivation Option [6] PGM 3 Time Base Selection [7] PGM 4 Deactivation Option [8] PGM 4 Time Base Selection SECTION [003] PGM 1 Activation Event(s): SECTION [004] PGM 1 Deactivation Event(s): SECTION [005] PGM 2 Activation Event(s): SECTION [006] PGM 2 Deactivation Event(s): SECTION [007] PGM 3 Activation Event(s): SECTION [008] PGM 3 Deactivation Event(s): SECTION [009] PGM 4 Activation Event(s): SECTION [010] PGM 4 Deactivation Event(s):
See section [002] to define the PGM Timers in seconds or minutes: SECTION [011] PGM 1 Timer (000 to 255) SECTION [012] PGM 2 Timer (000 to 255) SECTION [013] PGM 3 Timer (000 to 255) SECTION [014] PGM 4 Timer (000 to 255)
___/___ /___
default = 000
___/___ /___
default = 000
___/___ /___
default = 000
___/___ /___
default = 000
Serial Number: __/__/__/__/__/__/__/__ The serial number is on the 4-Output Bus Modules PC board.
OFF ON l Follow Event l Follow Timer l Seconds l Minutes l Follow Event l Follow Timer l Seconds l Minutes l Follow Event l Follow Timer l Seconds l Minutes l Follow Event l Follow Timer l Seconds l Minutes
___/___
(1 2 3 4 5 6 7 8)
___/___
(1 2 3 4 5 6 7 8)
___/___ ___/___
(1 2 3 4 5 6 7 8) (1 2 3 4 5 6 7 8)
___/___ ___/___
(1 2 3 4 5 6 7 8) (1 2 3 4 5 6 7 8)
___/___
(1 2 3 4 5 6 7 8)
___/___
(1 2 3 4 5 6 7 8)