You are on page 1of 2

Data Sheet for HSD Closed Drain Vessel Electric Immersion Heater

1 2 3 4 5 6 7 8 9 10 11 12 13 14 Specific Heat @ temp. (21C / 65C) 15 Fouling Resistance 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Tag No. : Name: P & ID No. : Calculation Ref. : Service Unit: 02H-6010 A/B Closed Drain Vessel Electric Immersion Heater HSD-A-TS-F-DW-0201-00 02V-6010 Closed Drain Vessel Client: Plant Location: Supplier: Purchase Order No. : No. Required: 02H-6010 A/B ThangLong Joint Operating Company HSD WHP, Offshore Vietnam TBA 2 Working: 2 Standby: 0

PROCESS DESIGN Line No./Equipment No. : Fluid to be heated Volume of Liquids (Note 10) Fluid Temperature (initial) Fluid Temperature (final) Heating Duty Required

UNITS m C C kW Hydrocarbon + Water 18.0 55 128 12 (VTC, see Note 2) FLUID PROPERTIES

kJ/kg.C k.m2/w MECHANICAL DESIGN kPag 1035 C -29 / 140 mm mm 6" VTA mm Horizontal 80/20 NiCr INCOLOY 800 sheath ASTM A105N 6" 150# RF (ASME B16.5) N/A
VTA

Process Design/Test Pressure Process Design Temperature ( Min / Max ) Corrosion Allowance (Element) Vessel Nozzle Size Immersion Length Min/Max Mounting (Horizontal/Vertical) Heater / Element Material Heater / Element Housing Heater Flange Material Flange Connection Size Flange Rating/Finish Insulation Overall Length Total Weight Design Standard Project Altitude Hazardous Area Classification Explosion Proof Class Certification Ingress Protection Installation Location Ambient Temperature ( Min / Max ) Humidity 1) 2)

(Note 5) (VTC, see Note 4) (Note 1)

(VTC, see Note 4)

kg VTA SPECIFICATIONS & ENVIRONMENT GEN-A-TS-M-SP-0003 Specification for Electric Heaters HST Full Field Development & HSD Early Production System Development EL (+) 15.5m above mean sea level Class 1, Zone 2 Group IIA T3 Ex 'e' for heater junction box & Ex 'd' for heater control panel BASEEFA / CENELEC or equal IP66 Outdoor, salt laden, corrosion atmosphere, offshore platform, Vietnam C 20.7 / 34.2 Max 100% ATTACHMENTS

P&ID - Closed Drain Vessel, DWG No. HSD-A-TS-F-DW-0201-00 Rev F04 Company Specification - Specification for Electric Heaters, GEN-A-TS-M-SP-0003 Rev A01

NOTES Heater to be installed in the horizontal through the side of the Closed Drain Vessel. Refer to Attached P&ID - Closed Drain Vessel DWG No. HSD-A-TS-F-DW-0201-00 Rev F04 2) Duty based on heating volume of liquids contained in the Vessel from minimum temperature -29C to 140C. 3) Heater will be manually operated intermittently, during maintenance operations. 4) Heater to be removable through Vessel nozzle. Vendor to confirm / advise nozzle size required, if the size is different from Nozzle N8A/ N8B. 5) Heater to have a surface temperature limitation. Vendor to advise the value of surface temperature limitation. 6) Tag number to be engraved on 316SS tag plate with 10mm high lettering & fixed permanently to the frame. 7) Control and Terminal Box shall be explosion proof & weatherproof type suitable to Class 1 Zone 2 Group IIA Temperature Class T3 hazardous area. 8) Vendor shall verify and complete this data sheet. Vendor shall submit detailed fabrication drawings for review and approval. 9) Both electrical heater and its control box shall be certified to a recognized National Certifying Authority and Hazardous Area Electrical Equipment Certificate shall be provided. 10) Liquid volume up to liquid high high alarm in Closed Drain Vessel . LAHH = 1820 mm 11) All vendor furnished cable shall be flame retardant to IEC 60332 3A. 12) TBC - To Be Confirmed; TBA - To Be Advised; VTA - Vendor To Advise; VTC - Vendor To Confirm. 1)

A01 REVISION

11-Nov-11 DATE

ISSUED FOR IDC DESCRIPTION

TTH/GO BY

TJC/JL CHK'D

VR APPR'D CLIENT

THANGLONG JOINT OPERATING COMPANY HST FULL FIELD & HSD EARLY PRODUCTION SYSTEM DEVELOPMENT
Project No: Datasheet No: 11010 HSD-A-TS-M-DS-0010 PAGE Revision: 1 of 2 A01

Data Sheet for HSD Closed Drain Vessel Electric Immersion Heater
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 Tag No. : Name: P & ID No. : Calculation Ref. : Service Unit: 02H-6010 A/B Client: Closed Drain Vessel Electric Immersion Heater Plant Location: HSD-A-TS-F-DW-0201-00 Supplier: 02V-6010 Closed Drain Vessel Purchase Order No. : No. Required: ThangLong Joint Operating Company HSD WHP, Offshore Vietnam TBA 2

Working:

Standby:

ELECTRIC DESIGN SUPPLY POWER


Main Power Supply Phase & Wiring Control Power Supply (if required) Electrical Rating (kW) Nominal Current Inrush Current

: : : : : :

400V AC 50 Hz 3 Phase, 4-wire


230V AC 50Hz

12 (VTC) VTA VTA

kW Amps Amps

INFORMATION OF MAIN POWER CABLE (BY PURCHASER) RFOU Cable to IEC 60332-3-A Main Power Cable Type : TBA Main Power Cable Tag Number : Main Power Cable Size : 3C x 16 + F x 10mm2 Cable entry side & Size Bottom Entry, ISO M25 : INFORMATION OF INSTRUMENT CABLE (BY PURCHASER) Type 1B for DCS interface, type 3B for SIS trip signal InstrumentCable Type : TBA Instrument Cable Tag Number : Instrument Cable Size 1 PR x 1.5mmsq x 2 cables : Cable entry side & Size Bottom Entry, ISO M20 : INFORMATION OF THERMOCOUPLE CABLE (By Vendor) Thoumocouple Cable Type Compensation : TBA Thermocouple Cable Tag Number : Thermocouple Cable Size 1.0mm2 Conductor : Cable entry side & Size Bottom Entry, ISO M20 or ISO M25 (TBC by Vendor) : Temperature Sensing Element for Heater Temperature Control (Thermocouple): Quantity : N/A N/A Tag Number : Manufacturer : N/A Type : N/A Control Range : N/A Setting : N/A Output Signal Description : N/A Temperature Sensing Element for Heater Temperature Hi-Hi & Flange Temperature Hi (RTD) : Quantity : 4 (3 RTDs shall be mounted on the Heater element , 1 for flange temperature) TBA Tag Number : Manufacturer : VTA Type : RTD PT100 (VTC) Control Range : TBA at vendor detailed design Setting : 140 C for Heater, For flange, TBA during vendor detail design Output Signal Description : VTA Vendor shall provide all RTD cables among RTD, transmitters, junction box &immersion RTD Connection : heater control panel. Immersion Heater Control Panel Manufacturer Explosion Proof Ingress Protection : Power supply requirement Cable Entry Panel Name Plate Installation Painting Specification Earthing Stud Earth Leakage Protection Drain and breather valves Overload & Short Circuit Protection Ground Fault Protection Type of Temperature Controller Overall Dimension (L x H x D) Total Weight

: : : : : : : : : : : : : : : :

VTA Ex 'd' IP66 400V AC 3 Phase 50Hz, 12kW Incoming Bottom 316 SS Plates with black color lettering Back side bracket mounting accessories to be furnished Per GEN-A-TS-P-SP-0007 Painting and Protective Coating Specification Required Required Required MCCB with thermal & magnetic trip protection units Included Electronic type or microprocess based type (TBA during vendor detail design) VTA VTA

Refer to all Notes shown in Sheet 1 of 2 of this data sheet.

THANGLONG JOINT OPERATING COMPANY


HST FULL FIELD & HSD EARLY PRODUCTION SYSTEM DEVELOPMENT
Project No: Datasheet No: 11010 HSD-A-TS-M-DS-0010 PAGE: Revision: 2 of 2 A01