Concept Selection guide VF Ventilation systems ICL-AI/ICT-AI Air/air exchangers ICL-AG/ICT-AG Air/water exchangers CLL/CLT CLLMP/CLTMP Cooling units - Mechanical control - Electronic control RC Resistance heaters - Insulated - Standard TS Control devices Thermal management for electrical panels Support service for the PRO clima 4.0 software calculation

6/2 6/6

6/8

6/30

6/36

6/40

6/64

6/80

6/95

6/100

Thermal management for electrical and electronic switchboards: a need

6/2

What is temperature control? Technological evolution


The miniaturisation of components, the generalisation of electronics, the appearance of new products based on power electronics mean that temperature management is a need that must increasingly be taken into account in the design of electrical and/or electronic switchboards.

What are the advantages of good temperature control?


Temperature control in electrical switchboards is one of the important factors of good industrial maintenance. The risks involved through failure to have a suitable thermal solution are multiple, affecting the life of components and the performance of installations to such an extent that they may halt production. The service life of the components themselves is a function of the temperature and humidity conditions in the enclosure. Ideal are values from +15+35 C for temperature and from 30 to 90% relative humidity (RH).

Cooling, Heating, controlling


Just like the degrees of IP/IK protection suited to each installation, the equipment installed inside an enclosure needs suitable thermal protection. There are different solutions to these problems, depending on environmental conditions, the nature of the components of the electrical switchboard, etc. In some cases it is sufcient to oversize the enclosure, use fans or air-air exchangers. In other, more extreme cases, in which the ambient temperature is higher, air-water heat exchangers or cooling units must be used.

A solution for every need


With this objective in mind, Himel proposes a comprehensive Thermal Offer to secure your installation. Cooling 1. Forced ventilation system 2 . Air/air exchangers 3 . Air/water exchangers 4. Cooling units 5. Resistance heaters 6. Thermal control systems 7. PROclima 4.0 software

Heating Control Calculation

6/3

System

Natural ventilation

Forced ventilation

Air-air exchangers

Natural convection helps to reduce the temperature inside the enclosure, whereby installing (without lter) outlet grilles or raising the enclosure tops may be a suitable solution. Fans with a Himel lter have been designed to evacuate a large amount of heat economically.

They have an aluminium exchange battery that separates the two air circuits (inside and outside) and stops dust from getting inside.

This solution is only feasible in cases where the When to use them power that has to be dissipated is weak, and in atmospheres with low dust levels.

When you need to evacuate greater dissipated power, and when the outside environment is polluted.

In highly polluted atmospheres or when large amounts of heat must be evacuated without bringing the outside and inside atmospheres into contact.

Ta: ambient temperature Td: temperature required

Ta < Td

Ta < Td

Ta < Td

The inside and outside air circuits are independent.

NO

NO

YES

c Economic solution. c Economic solution. Advantages c Maintenance-free. c Easy and quick to install. c Easy maintenance. c Easy and quick to install. c Even temperature inside the enclosure. c High protection degree (IP54 or IP55).

c They do not bring the atmospheres inside and outside the enclosure into contact. c Easy maintenance. c High protection degree (IP54).

c The temperature inside the enclosure is always c The amount of heat evacuated is weak. Drawbacks c Reduction in protection degree. c Dust penetration. higher than the outside. c They bring the atmospheres inside and outside the enclosure into contact. c Maintenance is required: lter change. c The temperature inside the enclosure is always higher than the outside.

Solutions

Outlet grilles

Fans and outlet grills

Air-air exchangers

6/4

Air-water exchangers

Cooling

Heating

They cool the enclosure by means of a water-cooled exchange battery. The regulation of the temperature in the enclosure is performed by means of a thermostat that closes or opens an electro-valve. They are cooling unit devices that guarantee effective and independent cooling from the outside environment, and avoid the appearance of heat sources. Resistance heaters avoid problems of condensation inside the enclosure and guarantee maintenance of the ideal temperature for the correct operation of the electronic components.

c When a large amount of heat has to be evacuated and a water cooling installation stable in temperature and ow is available.

c Our cooling units can be used in the severest atmospheres, where the temperature can reach up to 55 C. c Our cooling units feature the temperature adjustment Resistance heaters are used to heat the electrical switchboard when the ambient temperature is too low, or to prevent the formation of condensation water.

c Particularly suitable for difcult and highly polluted atmosphere, since there is no outside air circuit.

function, as well as an indication of any anomalies by means of an alarm.

Ta > Td

Ta > Td

Ta < Td

YES

YES
c Small size.

c The inside temperature of the enclosure does not depend on the outside. c They do not bring the atmospheres inside and outside the enclosure into contact. c It has a leak detection device. c Even temperature inside the enclosure. c High protection degree (IP54). c They use ecological gas.

c Fitted with a PTC-type heating element that stabilises the surface temperature of the aluminium section. c In two versions: insulated, with low surface temperature and in aluminium with a surface temperature below < 75 C. c The fan-equipped resistance heaters guarantee the temperature inside the enclosure and prevent hot spots.

c They need cold water. c They need a specic plumbing installation.

c The installation of a drain is recommended. c Maintenance is required: lter change.

Air-water exchangers

Cooling units

Resistance heaters

6/5

THERMAL MANAGEMENT

Selection guide

A thermal solution for every environment


Ventilation systems with lter Particularly suited for installations in which: c The temperature expected outside the enclosure may be lower than the maximum required inside it. c A high degree of protection must be maintained (IP54/IP55). c The outside environment is not too dusty. Broad range of solutions: c 42 models. c In RAL-7032 and RAL-7035. c From 38 to 850 m3/h. c In 5 voltages: AC: 400/440 V, 230 V, 115 V (50/60 Hz). DC: 48 V and 24 V.

Air-air exchangers Particularly suited for installations in which: c The temperature expected outside the enclosure may be lower than the maximum required inside it. c Maintaining good watertightness is important (IP54/IP55). c The outside environment is highly polluted. Broad range of solutions: c 4 models. c Top- and side-mounting versions. c Performance from 15 to 70 W. c Voltage: 230 V (50/60 Hz).

Air-water exchangers Particularly suited for installations in which: c The temperature required inside the enclosure must be lower than the maximum expected outside. c In corrosive atmospheres, the outside and inside air circuit never come into contact. c Very polluted atmospheres, since they are water-cooled and there is no outside air circuit. c When the heat needs to be extracted from the confines of the building. Broad range of solutions: c 3 models. c Top- and side-mounting versions. c Cooling power from 2100 W and 3000 W. c Voltage: 230 V (50/60 Hz).

6/6

THERMAL MANAGEMENT

Selection guide

Cooling units They give the equipment installed in the enclosure the temperature it needs to operate correctly: Regardless of the outside temperature. They do not bring the inside and outside air circuit into contact. They reduce humidity in the enclosure. Range of solutions: c 19 models. c Top- and side-mounting versions. c Cooling power from 240 up to 3.100 W. c Tension: 230 V (50/60 Hz); 3 400/440 V (50/60 Hz). Resistance heaters With a twofold objective: c They avoid condensation problems inside the enclosure. c They guarantee maintenance of the ideal temperature for the correct operation of the electronic components. Range of solutions: c 30 models. c Insulated or aluminium versions. c Convection or circulation fan versions. c Heating power from 10 up to 550 W. c Tension: from 12 to 450 V AC/DC. Control devices Thermostats: they maintain the temperature inside the enclosure and send a signal when certain dened values are exceeded: c Maximum value (cooling action). c Minimum value (heating action). Range of solutions: c 16 models. c Two versions: adjustable or preset temperature. c Hygrostat: relative humidity regulators. They are used together with resistance heaters or fans. c Hygrometer: relative humidity control with a double-function device: hygrostat-thermostat. Calculation assistance software: PROclima We provide our clients and users with this software to help them select their temperature control equipment. The program calculates the thermal balance in the enclosure and suggests the best ventilation or cooling solution.

6/7

Ventilation systems VF Wide range of ventilation products

6 8

6/8

0.8 mm

2.2 2.3

2.1
4.5 mm

Minimum pressure loss. Better air ow. The angles of walls, the tilting of slats, the xing distance of the motor and the sizing of the unit have been studied to guarantee the best possible air conduction and minimise pressure loss.

Fixing guide (2.1). Exclusive device (patented) that centres the fan body with the machining carried out on the enclosure wall. This system corrects possible defects in sizing and in the precision of machining. It also facilitates the operation of the multiple fixing clips. Multiple thickness xing clips system (2.2). This exclusive patented device guarantees easy and reliable xing of the ventilation system on 0.8 mm to 4.5 mm thick walls without the need for any other screws. It also guarantees a perfect joint compression on the cut outline. Protection between the grille and the wall is guaranteed for all materials: steel, stainless steel, polyester, aluminium, etc. Tilted prole of the grill (2.3). This innovating profile increases the protection of the filter against vertical exposure: c Each slat is protected by the slat above it. c The external size remains small.

3 IP54-55.
Designed (patented) especially to evacuate any water that might be retained by the lter blanket for applications that may be splashed under pressure.

4 Wide offer of lters.


c For application in greasy atmospheres (OEMs). c Anti-insect filters. c Small fine filter (when greater dust protection is required).

ENVIRONMENTALLY friendly
5 Environment. c Recyclable plastic materials and filters. c Motors compliant with the ROHS legislation. c Lower electrical consumption for greater air flow. 6 Selection of plastic materials. The materials (ASA/PC) selected give the system: c Good behaviour (long service life) with regard to UV rays. c Excellent mechanical behaviour. c The colours of the grills in the standard supply are RAL-7032 and 7035. c Grill colour can be changed by mould injection (check with the sales network). 8 Fast replacement of the lter blanket. Fast, easy and secure replacement of the lter blanket, even with the fan operating.
Reversibility. The rotation of the fan motor can be easily changed on all models (extraction/discharge).

7 Strong, reliable and effortless xing that is


evident upon installation, made possible by the set of guide devices and the multiple xing clips. It also allows traditional enclosures to be xed with fasteners.

9 Motor selection. State-of-the-art motors have been


selected from leading manufacturers in the sector, with a view to achieving: c Higher flow rate. c Longer useful life. The largest range of voltages is available in the standard motor selection, both in alternating (50/60 Hz) and direct current. Self-extinguishing. Self-extinguishing according to the UL94 VO regulation.

6/9

SYSTEMS

Selection guide

VENTILATION SYSTEMS WITH FILTER

Flow rate (m3/h) Free ow (fan with lter) Fan + 1 outlet grill Fan + 2 outlet grills Voltage Type of connection (*) Total
(external) (mm)

Dimensions (mm)

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

60 Hz

Cut-out (mm)

38

39

25

26

33

34

230 V

38

39

27

28

35

36

115 V

C 137 117 92 92

58

39

47

24 DC

44

34

41

48 DC

85

98

63

72

71

83

230 V

79

92

65

74

73

79

115 V

F 170 150 125 125

80

57

77

24 DC

79

59

68

48 DC

165

193

153

171

161

175

230 V

164

192

153

171

161

174

115 V

188

171

179

24 DC

193

171

179

48 DC

F 268 248 223 223

302

350

260

307

268

311

230 V

302

348

263

305

271

314

115 V

262

221

229

24 DC

247

210

218

48 DC

562

586

473

477

481

485

230 V

582

583

485

475

494

477

115 V

B 336 316 291 291

838

803

718

568

728

585

230 V

983

944

843

642

854

667

115 V

931

803

798

568

809

585

400/440 V

(*) C = by cable, F = by connector, B = by terminal block.

NEW Fans with type of connection F include a fan connection cable (L = 2 m)


6/10

Reference

Fan with lter

Outlet grille

Fan with lter

Outlet grille

IP

RAL-7032

RAL-7032

RAL-7035

RAL-7035

VF38

VF38R35

VF38/115 FS38 VF38/24DC

VF38/115R35 FS38R35 VF38/24DCR35 54

VF38/48DC

VF38/48DCR35

VF85

VF85R35

VF85/115 FS85 VF85/24DC

VF85/115R35 FS85R35 VF85/24DCR35 54

VF85/48DC

VF85/48DCR35

VF165

VF165R35

VF165/115

VF165/115R35

VF165/24DC

VF165/24DCR35

VF165/48DC FS165 VF300

VF165/48DCR35 FS165R35 VF300R35 54

VF300/115

VF300/115R35

VF300/24DC

VF300/24DCR35

VF300/48DC

VF300/48DCR35

VF560

VF560R35

VF560/115

VF560/115R35

VF850

FS560

VF850R35

FS560R35

54

VF850/115

VF850/115R35

VF850/400

VF850/400R35

6/11

VENTILATION SYSTEMS

Selection guide

OUTLET GRILLES
Reference RAL-7032 FS38 FS85 FS165 FS560 RAL-7035 FS38R35 FS85R35 FS165R35 FS560R35 Dimensions (mm) Total (outside) 137 117 170 150 268 248 336 316 Cut-out 92 92 125 125 223 223 291 291 54 54 54 54 IP

VANDAL PROOF SYSTEM


Reference RAL-7011 ANVF ANVF ANVF ANVF 137 177 170 150 268 248 336 316 2 2 2 2 Dimensions (mm) Set of

POWER CONNECTION CABLE FOR FANS


Reference CBMV100 CBMV200 Length (mm) 1000 2000

FILTERS
Reference F38 F85 F165 F560 F85OEM F165OEM F560OEM FF85 FF165 FF560 FAIN38 FAIN85 FAIN165 FAIN560 Anti-insect lters Fine lter (G3 class conforming to EN 779) Greasy environments OEM lter Standard lter (G2 class conforming to EN 779) Concept For fans and grilles with dimensions (mm) 137 117 170 150 268 248 336 316 170 150 268 248 336 316 170 150 268 248 336 316 137 117 170 150 268 248 336 316

6/12

VENTILATION SYSTEMS

Selection guide

EMC EXTERNAL KIT IP55


Reference VF85/KITIPCEM VF165/KITIPCEM VF560/KITIPCEM For fans and grilles with dimensions (mm) 170 150 268 248 336 316

PROTECTION KIT IP55


For grilles and fans (mm) 170 150 268 248 336 316 Aluzinc RAL-7032 VF85/KITIPALZ32 VF165/KITIPALZ32 VF560/KITIPALZ32 Aluzinc RAL-7035 VF85/KITIPALZ35 VF165/KITIPALZ35 VF560/KITIPALZ35 Stainless steel VF85/KITIP VF165/KITIP VF560/KITIP Replacement lters F85/KITIP F165/KITIP F560/KITIP

Forced ventilation The movement of air inside the enclosure with the aid of a fan makes it possible to: 1 Increase thermal dissipation through the enclosure walls and, as a result, reduce the inside temperature. 2 Avoid hot spots in the enclosure (even temperature) harmful to some components.

Natural ventilation The provision of fresh air from the outside by means of ventilation grills improves the dissipation of heat by natural convection. However, this solution is feasible in cases where the power to be dissipated is weak and in atmospheres with low dust levels. There are 4 ways of ventilating, with a common principle: entry of cold air through the bottom of the enclosure by means of an accessory and the exit of hot air through the top of the enclosure by means of an accessory: 1 By elevating the ceiling of the enclosures (only in Spacial 6000 models) and adding a lterless bottom air inlet (solution 1). 2 By means of a ceiling ventilation device, adding a lterless air inlet at the bottom (solution 1).
Solution 1 Solution 2

3 By means of inlet and outlet grills (lterless) (solution 2). 4 By means of ventilation lugs (Solution for insulating enclosures).
6/13

VF

Forced ventilation system IP54 (EN 60529)

VF38 Fans
General features: c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining dust particles. c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements. c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling. Conditions of use: c The outside temperature Te should be 5 C below the temperature required Ts in the enclosure. c The filters the fans are equipped with must be cleaned or replaced periodically. c The environment should be relatively clean and over-frequent filter replacement should be avoided. c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.

Characteristics Colour RAL-7032 Colour RAL-7035 Flow rate with lter (m3/h) (50/60 Hz) Flow rate with 1 outlet grill (m3/h) (50/60 Hz) Voltage Voltage range Absorbed power (50/60 Hz) Intensity max. (50/60 Hz) Noise level Bearing IP Degree of protection (with standard lter) External dimensions (mm) Cut-out dimensions (mm) Weight Material Service temperature Storage temperature 100% operating factor Maximum static pressure (0 m3/h airow) 0.220 kg 10 a +70 C VF38 VF38R35 38/39 25/26 230 V (50/60 Hz) 150...250 V 4.5/4.8 W 0.16/0.17 A VF38/115 VF38/115R35 38/39 27/28 115 V (50/60 Hz) 75...125 V 3.3/3.5 W 0.16/0.16 A

Reference VF38/24DC VF38/24DCR35 58 39 24 V DC 10...27.6 V 3.6 W 0.18 A 40/41 dB (A) Balls 54 137 117 49 92 92 0.230 kg 10 a +70 C 40 a +70 C 100% 20 Pa Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 VF38/48DC VF38/48DCR35 44 34 48 V DC 24...55 V 4.6 W 0.074 A

Outlet grilles
Characteristics Colour RAL-7032 Colour RAL-7035 Degree of protection IP54 External dimensions (mm) (height length depth) Material Operating temperature Reference FS38 FS38R35 54 137 117 18 Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 20 a +70 C

Replacement lter
Characteristics Standard lter (G2 class conforming to EN 779) Reference F38

6/14

VF

Forced ventilation system IP54 (EN 60529)

Dimensions (mm)
FIG. 1

Fans VF38-VF38/115

13

91.85

137

80

92 92

117

49

FIG. 2

Pressure/Flow Diagram

Pa

VF38

Difference in static pressure (SP)

Flow rate

m3/h

6/15

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

VF85 Fans
General features: c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles. c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements. c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations. c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling. Conditions of use: c The outside temperature Te should be 5 C below the temperature required Ts in the enclosure. c The filters the fans are equipped with must be cleaned or replaced periodically. c The environment should be relatively clean and over-frequent filter replacement should be avoided. c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.

Characteristics Colour RAL-7032 Colour RAL-7035 Flow rate with lter (m3/h) (50/60 Hz) Flow rate with 1 outlet grill (m3/h) (50/60 Hz) Voltage Voltage range Absorbed power (50/60 Hz) Intensity max. (50/60 Hz) Noise level Bearing IP Degree of protection (with standard lter) External dimensions (mm) Cut-out dimensions (mm) Weight Material Service temperature Storage temperature 100% operating factor Maximum static pressure (0 m3/h airow) 0.780 kg 20 a +60 C VF85 VF85R35 85/98 63/72 230 V (50/60 Hz) 175...253 V 17/15 W 0.12/0.097 A VF85/115 VF85/115R35 79/92 65/74 115 V (50/60 Hz) 75...126 V 16/15 W 0.21/0.179 A

Reference VF85/24DC VF85/24DCR35 80 60 24 V DC 10...27.6 V 7.6 W 0.30 A 46/49 dB (A) Balls 54 170 150 62 125 125 0.480 kg 10 a +70 C 40 a +70 C 100% 50 Pa Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 48 V DC 25...55.2 V 8W 0.173 A VF85/48DC VF85/48DCR35

Outlet grills
Characteristics Colour RAL-7032 Colour RAL-7035 IP Outside dimensions (mm) (height width depth) Material Service temperature Reference FS85 FS85R35 54 170 150 18 Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 20 a +70 C

Replacement lter
Characteristics Standard lter (ltration capacity: G2 conforming to EN 779) OEM lter (oily environment) Fine lter Anti-insect lter Reference F85 F85OEM FF85 FAIN85

6/16

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

Dimensions (mm)
FIG. 1

Fans
15

124.85

170

119

125 125 x 125 125

150

62

FIG. 2

Pressure/Flow Diagram

Pa

VF85

Difference in static pressure (SP)

Flow rate

m3/h

6/17

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

VF165 Fans
General features: c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles. c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements. c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations. c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling. Conditions of use: c The outside temperature Te should be 5 C below the temperature required Ts in the enclosure. c The filters the fans are equipped with must be cleaned or replaced periodically. c The environment should be relatively clean and over-frequent filter replacement should be avoided. c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.

Characteristics Colour RAL-7032 Colour RAL-7035 Flow rate with lter (m3/h) (50/60 Hz) Flow rate with 1 outlet grill (m3/h) (50/60 Hz) Flow rate with 2 outlet grills (m3/h) (50/60 Hz) Voltage Voltage range Absorbed power (50/60 Hz) Intensity max. (50/60 Hz) Noise level Bearing IP Degree of protection (with standard lter) External dimensions (mm) Cut-out dimensions (mm) Weight Material Service temperature Storage temperature 100% operating factor Maximum static pressure (0 m3/h airow) 1.140 kg 20 a +60 C 230 V (50/60 Hz) 175...253 V 16.3/14.3 W 0.12 A/0.94 A VF165 VF165R35 165/193 153/171 161/175 115 V (50/60 Hz) 75...126 V 15.5/14.4 W 0.20 A/0.18 A VF165/115 VF165/115R35

Reference VF165/24DC VF165/24DCR35 190 171 179 24 V DC 10...27.6 V 8W 0.3 A 50/51 dB (A) Balls 54 268 248 104 223 223 0.810 kg 10 a +70 C 40 a +70 C 100% 50 Pa Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 48 V DC 25...55.2 V 8.7 W 0.18 A VF165/48DC VF165/48DCR35

Outlet grills
Characteristics Colour RAL-7032 Colour RAL-7035 IP Outside dimensions (mm) (height width depth) Material Service temperature Reference FS165 FS165R35 54 268 248 18 Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 20 a +70 C

Replacement lter
Characteristics Standard lter (ltration capacity: G2 conforming to EN 779) OEM lter (oily environment) Fine lter Anti-insect lter Reference F165 F165OEM FF165 FAIN165

6/18

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

Dimensions (mm)
FIG. 1

Fans VF165-VF165/115

18

222.7

268

119

223 223 x 223

248

104

9.5

FIG. 2

Pressure/Flow Diagram

Pa

VF165

Difference in static pressure (SP)

Flow rate

(m3/h)

6/19

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

VF300 Fans
General features: c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles. c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements. c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations. c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling. Conditions of use: c The outside temperature Te should be 5 C below the temperature required Ts in the enclosure. c The filters the fans are equipped with must be cleaned or replaced periodically. c The environment should be relatively clean and over-frequent filter replacement should be avoided. c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.

Characteristics Colour RAL-7032 Colour RAL-7035 Flow rate with lter (m3/h) (50/60 Hz) Flow rate with 1 outlet grill (m3/h) (50/60 Hz) Flow rate with 2 outlet grills (m3/h) (50/60 Hz) Voltage Voltage range Absorbed power (50/60 Hz) Intensity max. (50/60 Hz) Noise level Bearing IP Degree of protection (with standard lter) External dimensions (mm) Cut-out dimensions (mm) Weight Material Service temperature Storage temperature 100% operating factor Maximum static pressure (0 m3/h airow) 1.3 kg 10 a +70 C 268 248 116 230 V (50/60 Hz) 145...253 V 36/37 W 0.17/0.16 A VF300 VF300R35 300/350 260/307 268/311 115 V (50/60 Hz) 75...126 V 36/36 W 0.35/0.32 A VF300/115 VF300/115R35

Reference VF300/24DC VF300/24DCR35 262 221 229 24 V DC 12...30 V 13 W 0.53 A 55/56 dB (A) Balls 54 268 248 103,4 223 223 1.1 kg 10 a +70 C 40 a +70 C 100% 158 Pa Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 48 V DC 25...60 V 11 W 0.24 A VF300/48DC VF300/48DCR35

Outlet grills
Characteristics Colour RAL-7032 Colour RAL-7035 IP Outside dimensions (mm) (height width depth) Material Service temperature Reference FS165 FS165R35 54 268 248 18 Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 20 a +70 C

Replacement lter
Characteristics Standard lter (ltration capacity: G2 conforming to EN 779) OEM lter (oily environment) Fine lter Anti-insect lter Reference F165 F165OEM FF165 FAIN165

6/20

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

Dimensions (mm)
FIG. 1

Fans VF300-VF300/115

18

222.7 172

268

223 223 223 x 223

248

116

9.5

FIG. 2

Pressure/Flow Diagram

Pa

VF300

Difference in static pressure (SP)

Flow rate

m3/h

6/21

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

VF560... and VF850... Fans


General features: c The Himel fans are comprised of an axial motor, a protection housing for the front and rear sides, and a filter for retaining powder particles. c The filter can even be replaced during operation, without any risk of contact with the blades or other rotating elements. c Optionally, the fans can be fitted with a fine filter to provide more efficient protection for dust-sensitive installations. c The cut-out template included with the standard supply avoids drawing and protects the enclosure surface from the risk of scratches during handling. Conditions of use: c The outside temperature Te should be 5 C below the temperature required Ts in the enclosure. c The filters the fans are equipped with must be cleaned or replaced periodically. c The environment should be relatively clean and over-frequent filter replacement should be avoided. c Load losses caused by the outlet element (grill with filter, ventilation louvre or single opening) must be taken into consideration to determine ventilation flow.

Characteristics Colour RAL-7032 Colour RAL-7035 Flow rate with lter (m3/h) (50/60 Hz) Flow rate with 1 outlet grill (m3/h) (50/60 Hz) Flow rate with 2 outlet grills (m3/h) (50/60 Hz) Voltage Voltage range Absorbed power (50/60 Hz) Intensity max. (50/60 Hz) Noise level Bearing IP Degree of protection (with standard lter) External dimensions (mm) Cut-out dimensions (mm) Weight Material Service temperature Storage temperature 100% operating factor Maximum static pressure (0 m3/h airow) 140 Pa 3.2 kg 336 316 161 VF560 VF560R35 VF560/115 VF560/115R35 562/586 473/477 481/485 230 V (50/60 Hz) 207...244 V 68/85 W 0.52/0.37 A 59/59 dB (A) 115 V (50/60 Hz) 103...122 V 65/83 W 0.60/0.72 A

Reference VF850 VF850R35 838 (50 Hz) 803 (60 Hz) 718 (50 Hz) 568 (60 Hz) 728 (50 Hz) 585 (60 Hz) 230 V (50/60 Hz) 207...244 V 150/195 W 0.65/0.85 A 76/75 dB (A) Balls 54 336 316 162 291 291 4.1 kg 15 a +60 C 40 a +50 C 100% 170 Pa Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 VF850/115 VF850/115R35 983 (50 Hz) 944 (60 Hz) 843 (50 Hz) 642 (60 Hz) 854 (50 Hz) 667 (60 Hz) 115 V (50/60 Hz) 103...122 V 145/182 W 0.13/1.6 A 78/77 dB (A) VF850/400 VF850/400R35 931 (50 Hz) 803 (60 Hz) 798 (50 Hz) 568 (60 Hz) 809 (50 Hz) 585 (60 Hz) 400 V (50/60 Hz) 396...466 V 40/40 W 0.22/0.23 A 77/75 dB (A)

Outlet grills
Characteristics Colour RAL-7032 Colour RAL-7035 IP Outside dimensions (mm) (height width depth) Material Service temperature Reference FS560 FS560R35 54 336 316 18 Injected thermoplastic material (ASA PC), self-extinguishing according to UL94 V0 20 a +70 C

Replacement lter
Characteristics Standard lter (ltration capacity: G2 conforming to EN 779) OEM lter (oily environment) Fine lter Anti-insect lter Reference F560 F560OEM FF560 FAIN560

6/22

VF

Forced ventilation system IP54 (EN 60529) / IP55 (with IP55 protection kit)

Dimensions (mm)
FIG. 1

VF560-VF560/115 Fans

18

290.7

336

225

291 x 291 291 291

316

160.5

9.5

FIG. 2

VF650-VF650/115 Fans

18

290.7

336

280

291 x 291 291 291

316

162

9.5

FIG. 3

FIG. 4

Pressure/Flow Diagram

Pa
Difference in static pressure (Pa)

VF560

Pa
Difference in static pressure (Pa)

VF850

Flow rate

m3/h

Flow rate

m3/h
6/23

VF

Accessories for forced and natural ventilation systems

Circulation fan
c To circulate the air inside the enclosures. c Fixing with screws. c User protection according to DIN 31001.
Reference VC150 Flow rate (m3/h) 150 Tension 230 V 50 Hz Electrical power (W) 17 Weight (kg) 0.82

IP20 Fans
c For uses where a high degree of protection is not required (IP20). c Self-extinguishing thermoplastic grille with a black nish. c Fixing to the enclosure with four M4 screws.

Reference V65 V65/115

Flow rate (m3/h) 65 65

Tension 230 V - 50 Hz 115 V - 50 Hz

Electrical power (W) 17 17

Weight (kg) 0.69 0.69

Dimensions (mm) 124 124 55 124 124 55

Outlet grilles FS65 FS65

Standard lter F65 F65

EMC external kit IP55


c They are directly mounted onto the fans and grilles to protect the equipment from electromagnetic interference.
Reference VF85/KITIPCEM VF165/KITIPCEM VF560/KITIPCEM For fans and grilles with dimensions (mm) 170 150 268 248 336 316

6/24

VF

Accessories for forced and natural ventilation systems

Fans for 19 racks


c Height: 1 U. c Connection cable. References: CBMV100 (L = 1 m). CBMV200 (L = 2 m).

Reference VR312 VR400 VR624 VR800 VR1200


*Flow measured without counter-pressure.

Specications With 3 fans with a depth of 180 mm With thermostat and indicator light With 3 fans with a depth of 180 mm With 3 fans with a depth of 180 mm With thermostat and indicator light With 6 fans with a depth of 310 mm With 9 fans with a depth of 445 mm

Flow rate* (m3/h) 312 400 624 800 1200

Noise dB (A) 50 50 50 52 55

Tension (V/Hz) 230/50-60 230/50-60 230/50-60 230/50-61 230/50-62

Electrical power (W) 34 36 68 72 108

19 2 U tangential fan
c Fan with air drawn in from the front and vertically channelled through the 19 rack. c Height: 2 U.
Reference VTR300 Flow rate (m3/h) 300 Noise dB (A) 53 Tension (V/Hz) 230/50-60 Electrical power (W) 37

6/25

VF

Accessories for forced and natural ventilation systems

Fans
c Turbine-type fan motor for ventilation/extraction.

Ventilation lters c Outlet lter unit for enclosure ventilation. For tting to MV fans.

Protective grille c Protective grille for enclosure fan motors. For tting to MV fans.

Power connection cable for fans c For tting to the connection terminal of the fan motors. References: CBMV100 (L = 1 m). CBMV200 (L = 2 m).

Reference MV156 MV156/115 MV35 MV35/115

Flow (m3/h) 156 156 35 35

Tension (V/Hz) 230/50-60 120/50-60 230/50-60 120/50-60

Power absorbed (W) 17/15 17/15 16/14 16/14

Noise (dB) (A) 42 42 32 32

External dimensions (mm) 120 120 38 120 120 38 80 80 25 80 80 25

Filter FS156 FS156 FS35 FS35

Grille RV156 RV156 RV35 RV35

6/26

VF

Accessories for forced and natural ventilation systems

Ceiling ventilation
c Ventilation accessories to be mounted on the top of OLN enclosures..

VMT340
340 270 90 68 6 22

VFT400
340 270 90 68 6 22

290.5

290.5

270 340

270

270 340

270

228

228

External dimensions (mm) Reference VMT340 VFT400 Description Natural airing device Forced ventilation device (supplied with electric fan) Height 93 90 Width 340 340 Depth 340 340 Flow rate (m3/h) 400 Tension (V/Hz) 230/50-60 Electrical power (W) 85

190

6/27

VF

Accessories for forced and natural ventilation systems

Outlet grilles with filter IP54


c Injected thermoplastic, self-extinguishing, conforming to UL94 V0. c Operating temperature from 10 to +60 C. c IP55 with IP55 watertightness protection kit.
Reference RAL-7032 FS38 FS85 FS165 FS560 RAL-7035 FS38R35 FS85R35 FS165R35 FS560R35 Total (exterior) 137 117 170 150 268 248 336 316 Dimensions (mm) Machined 92 92 125 125 223 223 291 291

VANDAL PROOF SYSTEM


Reference RAL-7011 ANVF ANVF ANVF ANVF Dimensions (mm) 137 177 170 150 268 248 336 316 Set of 2 2 2 2

POWER CONNECTION CABLE FOR FANS


Reference CBMV100 CBMV200 Length (mm) 1000 2000

Filters
Reference F38 F85 F165 F560 F85OEM F165OEM F560OEM FF85 FF165 FF560 FAIN38 FAIN85 FAIN165 FAIN560 Concept For fans and grilles with dimensions (mm) 137 117 170 150 268 248 336 316 170 150 268 248 336 316 170 150 268 248 336 316 137 117 170 150 268 248 336 316

Standard lter (G2 class conforming to EN 779)

Greasy environments OEM lter

Fine lter (G3 class conforming to EN 779)

Anti-insect lters

Protection kit IP55


For grilles and fans (mm) 170 150 268 248 336 316 Aluzinc RAL-7032 VF85/KITIPALZ32 VF165/KITIPALZ32 VF560/KITIPALZ32 Aluzinc RAL-7035 VF85/KITIPALZ35 VF165/KITIPALZ35 VF560/KITIPALZ35 Stainless steel VF85/KITIP VF165/KITIP VF560/KITIP Replacement lter F85/KITIP F165/KITIP F560/KITIP

6/28

VF

Accessories for forced and natural ventilation systems

Lifting screws
c Lifting screws for the top of the OLN enclosures to improve ventilation c Reference: VET12.

Ventilation devices
c To connect the inside of the enclosure with the exterior atmosphere and prevent condensation. Can be fixed onto the outside (references VM25 and VN27) or onto the internal sides connected with the rear self-ventilating windows of the POLYMEL enclosures (reference VM35).

Reference VM25 VM27


VM25 VM27

Specications For coupling to the exterior of all polyester enclosures For coupling to the exterior of all polyester enclosures For coupling to the interior of POLYMEL enclosures

VM35

VM35

Ventilation slots
c Natural ventilation. Guarantee air circulation inside the enclosure. Texturised RAL-7032 colour
A F F

C 5.3 =

D E

Reference TR1 TR2 TR3 TR4 TR5 TR6

A (mm) 144 208 244 345 345 445

B (mm) 62 90 90 118 148 148

C (mm) 36 72 72 100 130 130

D (mm) 110 94 130 231 231 297

E (mm) 190 226 237 327 427

F (mm) 115.5 115.5 148.5

6/29

Air/air exchangers In details

1 2

4 3

AIR/AIR EXCHANGERS
Dimensions (mm) Reference Performance Voltage Mounting Height ICL15AI ICL35AI ICL35AILC ICL35AIN ICL60AI ICT50AI 15 W/K 35 W/K 35 W/K 35 W/K 70 W/K 50 W/K 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz 230 V 50/60 Hz Side Side Side Side Side Top 700 780 780 780 1480 340 Width 270 325 325 325 450 600 Depth 144 144 144 144 144 360 Integrated thermostat

Yes Yes No Yes Yes Yes

See the accessories on pages 6/33 and 6/35.

6/30

1 Available in two versions: c Side-mounting. c Top-mounting.


Performance from 15 to 70 W/K that allows you to install the equipment best suited to your needs in each case.

2 The exchangers come equipped with an adjustable thermostat that controls the interior temperature of the enclosure: c An auxiliary control thermostat does not need to be installed. c It guarantees the correct reading of the interior temperature of the enclosure.
Temperature control range from +20 to +50 C.

3 The air-air exchangers


do not need inlet lters, thus reducing periodic maintenance.

4 The interior and exterior air circuits are perfectly separated and maintain the IP54 watertightness of the enclosure.
Two fans guarantee air circulation in each of the circuits: c Circulation fan for air inside the enclosure. The internal circuit fan is always on, thereby maintaining a uniform temperature inside the enclosure and preventing hot spots. c Circulation fan for air outside the enclosure. The interior thermostat controls the fan and starts it when the temperature of the air inside the enclosure is above the required temperature.

5
c Fast access to the interior makes unit cleaning and maintenance easy. c The special configuration of the exchange battery makes it easy to clean. The spaces between the slats make it possible to access the inside aluminium walls for easy and fast cleaning.

6/31

ICT / ICL / AI

Air/air exchangers

Side-mounting
General features: c Main components: thermostatic adjustment system, exchange battery, circulation c The temperature required in the enclosure may be adjusted from +25 C to +50 C. c The interior and exterior air circuits are perfectly separated (IP54). Two fans guarantee air circulation in each one of the circuits; the inside circuit (that moves the enclosure air) is permanently on, which makes it possible to avoid hot spots in the electric circuits or the components. c The equipment is delivered with a drilling template, an installation guide, and a water and air-tightness gasket to be inserted between the exchanger and the enclosure. Conditions of use: c The exchangers can only be used when the outside temperature is 5 C below the temperature required inside the enclosure. c The enclosure should be airtight to avoid the penetration of outside air (IP54 minimum).

Reference ICL15AI Cooling specications Specic power (1) Exterior circuit airow Inside circuit airow Exchange surface Adjustment Type Temperature control range Nature of the uid Electrical specications Power supply voltage Start-up/rated intensity Electrical power absorbed Physical features External dimensions A B C (mm) Internal IP circuit External IP circuit Weight Noise level 700 270 144 IP54 IP22 12 kg 64 dB (A) 780 325 144 IP54 IP22 15 kg 64 dB (A) 780 325 144 IP54 IP22 15 kg 64 dB (A) 780 325 144 IP54 IP22 15 kg 64 dB (A) 1480 450 144 IP54 IP22 35 kg 64 dB (A) 230 V 50/60 Hz 2.1/0.7 A 150 W 230 V 50/60 Hz 2.1/0.7 A 150 W 230 V 50/60 Hz 2.1/0.7 A 150 W 230 V 50/60 Hz 2.1/0.7 A 150 W 230 V 50/60 Hz 2.1/0.7 A 150 W 15 W/K 200 m3/h 200 m3/h 1.23 m2 Yes Thermostatic 25-50 C Air 35 W/K 450 m3/h 450 m3/h 1.5 m2 Yes Thermostatic 25-50 C Air 35 W/K 450 m3/h 450 m3/h 1.5 m2 No Thermostatic 35 W/K 450 m3/h 450 m3/h 1.5 m2 Yes Thermostatic 25-50 C Air 70 W/K 450 m3/h 450 m3/h 6.6 m2 Yes Thermostatic 25-50 C Air ICL35AI ICL35AILC ICL35AIN (internal mounting) ICL60AI

(1) Power in W is obtained by formula: specic power temperature difference between interior and exterior of enclosure. Example: for exchanger ref. ICL35AI for a difference of 10 C, the system power is 35 10 = 350 W.

6/32

ICT / ICL / AI

Air/air exchangers

Dimensions (mm)
FIG. 1 FIG. 2

External mounting

Internal mounting

I = = J E F 136 = A 80 K D G 25 25 144 26 (C) B 28 144 (C) 26 J H = (1) (1) A 80

B I

E G =

D 136

H = F

30

(1) Filter grilles. Ref.: RPF (not included in the standard supply).

ICL15AI A B C D E F G H I J K 700 270 144 220 167 82 13 366 226 40 48

ICL35AI ICL35AILC ICL35AIN 780 325 144 294 183.5 77.5 35.5 413 266 52 48

ICL60AI 1480 450 144 420 183.5 77.5 35.5 1113 393 115 68

Accessories (side mounting)


c Optional grille to mount the exchangers inside the enclosure.

Reference RPF15AI RPF35AI RPF70AI

For mounting with the exchanger ICL15AI ICL35AI/ICL35AILC ICL60AI

Installation (internal mounting)

6/33

ICT / ICL / AI

Air/air exchangers

Top mounting
General features: c Main components: thermostatic adjustment system, exchange battery, circulation fans for air from the inside and outside circuits. c The temperature required in the enclosure may be adjusted from +25 C to +50 C. c The interior and exterior air circuits are perfectly separated (IP54). Two fans guarantee air circulation in each one of the circuits; the inside circuit (that moves the enclosure air) is permanently on, which makes it possible to avoid hot spots in the electric circuits or the components.
ICT50AI

c The equipment is delivered with a drilling template, an installation guide, and a water and air-tightness gasket to be inserted between the exchanger and the enclosure. Conditions of use: c The exchangers can only be used when the outside temperature is 5 C below the temperature required inside the enclosure. c The enclosure should be airtight to avoid the penetration of outside air.

Reference ICT50AI Cooling specications Specic power (1) Exterior circuit airow Interior circuit airow Exchange surface Adjustment Type Temperature control range Nature of the uid Electrical specications Power supply voltage Start-up/rated intensity Electrical power absorbed Physical features External dimensions A B C (mm) Internal IP circuit External IP circuit Weight Noise level (1) Power in W is obtained by formula: specic power temperature difference between inferior and exterior of enclosure. 390 600 365 IP54 IP22 19 kg 64 dB (A) 230 V 50/60 Hz 2.1/0.7 A 150 W 50 W/K 450 m3/h 450 m3/h 3.3 m2 Yes Thermostatic 20-50 C Air

6/34

ICT / ICL / AI

Air/air exchangers

Dimensions (mm)
FIG. 1

Top mounting: dimensions

600

26

360

340

115

370

300

290 360

20

70

310 600

70

Accessories (top mounting)


c Intermediate frame for coupling the MMI64 exchanger to the 600 mm wide and 400 mm deep enclosures. c Ref. MMI64.
26 360

Frame MMI64

6/35

Air/water exchangers In details

AIR/WATER EXCHANGERS
References Cooling power L35/W 10/200 l/h Dimensions (mm) Voltage Height 230 V 50/60 Hz 230 V 50/60 Hz 830 310 Width 360 600 Depth 113 365 Side Top Mounting

ICL1800AG ICT1800AG

1800 W 1800 W

6/36

Maximum Safety

ANTI-LEAK detection system

1 Available in two versions: Top and side mounting.

2 The exchangers come with an adjustable thermostat that controls the inside temperature of the enclosure: c It avoids the installation of an auxiliary control thermostat. c It guarantees the correct reading of the inside temperature of the enclosure.
Temperature adjustment range: +20 to +50 C.

3 It has an electricallyoperated valve in the water inlet which, controlled by the thermostat, adjusts temperature and avoids possible condensation. It has an anti-leak detection system that cuts off the water supply if it detects a loss in the circuit.

4 The IP54 watertightness is guaranteed. The recirculation fan of the enclosure inside air is on permanently, which maintains an even temperature inside the enclosure and thus avoids the appearance of hot spots.

5 Comfortable and easy to assemble and disassemble. Fast access to the inside makes for easy cleaning and maintenance of the unit. Because it is water cooled, there is no outside air circuit, and no lters are needed, thus reducing periodical maintenance.

6/37

ICT / ICL / AG

Air/water exchangers

Top and side mounting


General features: c Main components: control system, exchange cassette, circulation fans for internal circuit. c The temperature required in the enclosure can be controlled within a range of +25 to +50 C. c The alarm which detects an interruption in the water circuit triggers closing of an N/O contact. This contact can be used to actuate a pilot light or siren, or it can be connected to a PLC input. In the event of the alarm being triggered, the water supply is automatically cut off. c System to evacuate condensation water to the outside. Conditions of use: c The air-water exchangers can be used even if the external temperature is superior to the temperature required within the enclosure. c The enclosure should be airtight in order to prevent entry of external air, IP54 minimum.

Reference ICT1800AG Cooling specications Specic power A 35 W 10-200 l/h Max. water pressure Exterior circuit airow Adjustment Type Temperature control range Nature of the uid Electrical specications Power supply voltage Start-up/rated intensity Electrical power absorbed Type of alarm Physical features External dimensions A B C (mm) IP (EN 60529) Weight Noise level Mounting 310 600 365 IP54 26 kg 64 dB (A) Top 830 355 110 IP54 19 kg 62 dB (A) Side 230 V 50/60 Hz 1/0.5 A 90 W Dry contact 230 V 50/60 Hz 1/0.5 A 90 W Dry contact 1800 W 1 MPa 250 m3/h Yes Thermostatic 25-50 C Water 1800 W 1 MPa 350 m3/h Yes Thermostatic 25-50 C Water ICL1800AG

6/38

ICT / ICL / AG

Air/water exchangers

Dimensions
FIG. 1

Top mounting exchanger


497 = = 430 = 40.5 61.5 =

Top mounting Ref.: ICT1800AG

Included with unit: c Drilling template. c Installation accessories. c Installation and operating instructions.
268 280 236 236

332

Front of the enclosure

600

310

Water inlet-outlet Condensation water outlet

FIG. 2

Side mounting exchanger


300 20

Side mounting Ref.: ICL1800AG

Included with unit: c Drilling template. c Installation accessories. c Installation and operating instructions. c For internal or external mounting.
150 180 410 830 300 105

750

113

360

FIG. 3

Curves
Power absorbed at a water ow rate for 100 l/h
Power exchanged by el the exchangers (W) (W) Potencia disipada por intercambiador

Power absorbed at a water ow rate for 200 l/h


Power exchanged by exchangers (W) Potencia disipada por elthe intercambiador (W)

Power absorbed at a water ow rate for 300 l/h


Power exchanged by el the exchangers (W) Potencia disipada por intercambiador

3500 3000 Td=50C 2500 Td=45C


Td=40C 2000 Td=35C 1500 Td=30C Td=25C 1000 Td=20C Td = Temperatura deseada en el interior del armario

4000 3500 3000 2500 2000 1500 1000 500 0 5 10 15 20 25 30


Td=50C Td=45C Td=40C Td=35C Td=30C Td=25C Td=20C

4000 3500 Td=50C 3000 Td=45C 2500


Td=40C Td=35C

2000 Td=30C 1500 Td=25C 1000 500 0 5 10 15 20 25 30


Td=20C

500 0 5 10 15 20 25 30

Water temperature Temperatura del aguaC C

Temperatura del agua C

Water temperature C

Temperatura del aguaC C Water temperature

Example: for water at 100 l/h at 15 C with a preferred temperature of 35 C Power = 1400 W

6/39

Cooling units CLL/CLT standard control

6/40

The inside and outside air circuits are perfectly separated and maintain IP54 watertightness of the enclosure. Two fans guarantee air circulation in each one of the circuits: c Internal circuit fan. It is on permanently, which maintains an even temperature inside the enclosure, avoids the appearance of hot spots and guarantees a correct reading of the inside temperature of the enclosure by the set-point thermostat. c External circuit fan. The inside thermostat controls the fan and starts it up when the temperature of the air inside the enclosure is above the maximum value displayed.

Easy access to the condenser allows simplied cleaning through blowing. Disassemble of the cooling units is not necessary for the high temperature compressor and external fan maintenances.

The air conditioning units come with an adjustable thermostat that controls the inside temperature of the enclosure: c It avoids the installation of an auxiliary control thermostat. c It guarantees the correct reading of the inside temperature of the enclosure. Temperature adjustment range: +20 C to +50 C (supplied factory-adjusted to 35 C).

ENVIRONMENTALLY friendly
c The top mounting models feature a condensation water automatic evaporation system with an exclusive safety system that switches off the apparatus or issues an alarm if the condensation water level is exceeded. c They also feature an exclusive voluntary unloading system that makes it possible to empty the water from the condensation tray. c Available in two versions: top and side mounting versions. c The power of mechanically regulated cooling units ranges from 240 to 3100 W. There is always equipment which is suited to your needs. c Comfortable and easy to assemble and disassemble. c The side installation models can be semirecessed with the use of the specific accessory. They are equipped with an automatic reset pressostat and a contact thermostat that detects the overpressure in the compressor circuit and interrupts it and the outside circuit fan, thus avoiding possible faults. Fitted with a fault warning relay, it provides the possibility of operating an alarm indicator, shutting down the apparatus. Fitted with high pressure compressors that allow them to work at outside temperatures of up to +55 C. Environmentally friendly. Use of R134a ecological gas.

6/41

COOLING UNITS

Selection guide

SIDE-MOUNTING
References CLL240 CLL370 CLL760 CLL1050 CLLMP1100 CLLMP1400 CLLMP1400T CLL1650 CLL1650T CLLMP1800T Power EN 14511 L35 - L35 240 W (819 Btu/h) 370 W (1260 Btu/h) 760 W (2594 Btu/h) 1050 W (3584 Btu/h) 1100 W (3755 Btu/h) 1400 W (4780 Btu/h) 1400 W (4780 Btu/h) 1650 W (5631 Btu/h) 1800 W (6143 Btu/h) 1800 W (6145 Btu/h) Voltage in V-Hz 230-50/60 230-50/60 230-50/60 230-50/60 230-50/60 230-50/60 3 400 V 50 Hz/ 3 440 V 60 Hz 230-50/60 3 400 V 50 Hz/ 3 440 V 60 Hz 3 400 V 50 Hz/ 3 440 V 60 Hz Dimensions (mm) 450 350 140 620 300 170 800 350 195 900 400 195 1010 400 240 1010 400 240 1010 400 240 1000 400 220 1000 400 220 1010 400 240 Adjustment Thermostat Thermostat Thermostat Thermostat Microprocessor Microprocessor Microprocessor Thermostat Thermostat Microprocessor

6/42

COOLING UNITS

Selection guide

TOP-MOUNTING
References CLT760 CLT1050 CLTMP1400 CLT1460 CLT1650 CLTMP1800T CLT1650T CLT2450T CLT3100T Power EN 14511 L35 - L35 760 W (2.594 Btu/h) 1050 W (3.584 Btu/h) 1400 W (4.780 Btu/h) 1460 W (4.984 Btu/h) 1650 W (5.631 Btu/h) 1800 W (6.145 Btu/h) 2000 W (6.826 Btu/h) 2450 W (8.368 Btu/h) 3100 W (10.583 Btu/h) Voltage in V-Hz 230-50/60 230-50/60 230-50/60 230-50/60 230-50/60 3 400 V 50 Hz/ 3 440 V 60 Hz 3 400 V 50 Hz/ 3 440 V 60 Hz 3 400 V 50 Hz/ 3 440 V 60 Hz 3 400 V 50 Hz/ 3 440 V 60 Hz Dimensions (mm) 340 600 350 400 700 400 415 750 412 400 700 400 430 700 400 415 750 412 430 700 400 470 800 450 470 800 450 Adjustment Thermostat Thermostat Microprocessor Thermostat Thermostat Microprocessor Thermostat Thermostat Thermostat

6/43

CLL

Cooling units

Mechanical control Side mounting


Cooling units for electronic switchboards: c Respect for the environment by using the ecological gas R134a. c Cooling power of 240 W to 3100 W. c Possibility of partial flush mounting for all side mounting models. General features: c Temperature setting can be adjusted from +20 to +50 C. c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off. c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c The equipment is fitted with switches enabling an alarm report. c Cooling power of 240 W to 3100 W.
CLL760

c Possibility of partial flush mounting.

Reference Voltage Cooling power (50/60 Hz) acording to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Start-up Nominal Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature regulator Temperature setting range Maximum external temperature Noise level Airow Internal circuit External circuit Alarm type contact free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve)

CLL240

CLL370 230 V 50/60 Hz

CLL760

240 W (819 Btu/h) 190 W (649 Btu/h)

370/390 W (1263/1331 Btu/h) 300/310 W (1024/1058 Btu/h)

760/810 W (2594/2765 Btu/h) 610/640 W (2082/2184 Btu/h)

450 mm 350 mm 140 mm + (15 mm inside)

620 mm 300 mm 170 mm

800 mm 350 mm 195 mm

2.8 A 0.7 A

5.8/6.7 A 1.5/1.8 A

7.7/8.8 A 2/2.3 A

140 W 160 W

290/330 W 330/380 W

380/440 W 440/500 W

1.7

1.3/1.2 Thermostat

2.0/1.8

20 - 45 C 50 C 58 dB (A) 160 m3/h 320 m3/h 65 dB (A) 160/175 m3/h 210/230 m3/h Inverter contact 15 kg R134a (0.25 kg) 54 34 Optional Side T1.6 A T3 A 21 kg R134a (0.3 kg) 54 34

20 - 50 C 55 C 67 dB (A) 350/385 m3/h 350/385 m3/h

33 kg R134a (0.5 kg) 54 34 Yes T3 A

6/44

CLL

Cooling units

Dimensions (mm)
FIG. 1

CLL240: Dimensions

Cut-out dimensions

Ref. CLL240

External mounting

Partial ush mounting

FIG. 2

Side mounting: dimensions


A = = B C D K
Dimensions in mm A B C D E CLL370 260 0 80 40 300 540 60 620 136 300 240 170 35 0 8 CLL760 266 52 116 193,5 375 413 80 800 136 350 294 195 149 24 8

E H G Q

S
M 60

N F

F G H K L M N P

P 26
Ref. CLL370 and CLL760

30 L

Q R S

FIG. 3

Curves
CLL240 50/60 Hz
400 700

CLL370 50 Hz
700

CLL370 60 Hz

350 Ti [ C ] 300 Pf [ W ]

600 Ti [ C ] 500 45 40 400

600 Ti [ C ] 500 50 45 40 400 35 30 300 25 20

250

35 30

200

25 20

300

50 45 40 35 30 25 20

150

200

200

100 20 25 30 35 40 45 T e [ C ] 50 55 f = 50/60 Hz

100 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

100 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

CLL760 50 Hz
1400 1400

CLL760 60 Hz

1200 Ti [ C ] 50 1000 Pf [ W ] 45 40 800 35 30 25 600 20

1200

Ti [ C ] 50

1000

45 40 35

800

30 25

600

20

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

400

400

200 20

200 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

6/45

CLL

Cooling units

Side mounting
Cooling units for switchboards: c Respect for the environment by using the ecological gas R134a. c Automatic evaporation of condensation water on all top mounting models. c Cooling power of 240 W to 3100 W. c Possibility of partial flush mounting for all side mounting models. General features: c Temperature setting can be adjusted from +20 to +50 C. c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) activates compressor and external fan switch-off. c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c The equipment is fitted with switches enabling an alarm report.
CLL1650

c Cooling power of 240 W to 3100 W. c Possibility of partial flush mounting.

Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Start-up Nominal Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature setting range Control range Max. external ambient temperature Noise level Airow Internal circuit External circuit Alarm contact Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve)

CLL1050 230 V 50/60 Hz 1050/1100 W (3584/3755 Btu/h) 840/890 W (2867/3038 Btu/h)

CLL1650

CLL1650T 3 400 V 50 Hz / 3 440 V 60 Hz 1800/1900 W (6143/6485 Btu/h) 1400/1500 W (4779/5121 Btu/h)

1650/1700 W (5631/5802 Btu/h) 1300/1400 W (4438/4779 Btu/h)

900 mm 400 mm 195 mm

1000 mm 400 mm 220 mm

10.1/11.6 A 2.7/3 A

16.1/18.5 A 4.2/4.9 A

6.8/7.9 A 2.1/2.5 A

550/580 W 580/660 W

800/920 W 920/1100 W

1200/1400 W 1400/1600 W

2.1/1.9

2.1/1.9 Thermostat 20 - 50 C 55 C

1.5/1.4

67 dB (A) 350/385 m3/h 510/560 m3/h

67 dB (A) 550/600 m3/h 620/680 m3/h Potential-free

69 dB (A)

39 kg R134a (0.7 kg) 54 34

42 kg R134a (0.75 kg) 54 34 Yes Side

46 kg 54 34

T4 A

T6 A

T3 A

6/46

CLL

Cooling units

Dimensions (mm)
FIG. 1

Side mounting: dimensions

A = = B C D K

Dimensions in mm A B C D E F

CLL1050 300 0 135 30 465 840 100 900 180 400 320 195 35 195 0

CLL1650 300 0 135 30 475 840 100 1000 180 400 320 470 220 25 195 10

CLL1650T 300 0 135 30 475 840 100 1000 180 400 320 470 220 25 195 10

E H G Q

S
M 60

N F

G H K L M N P Q

P 26

30 L

FIG. 2

Curves
CLL1050 50 Hz
1800

CLL1050 60 Hz
1800

CLL1650 50 Hz
3000

1600

1600

2600

Ti [ C ]
1400

50 45

1400

Ti [ C ] 50 45
2200

Ti [ C ] 50 45
1800

Pf [ W ]

1200

40 35 30

1200

40 35

40 35 30

1000

1000

30 25
1400

800

25 20

800

25 20

20
1000

600

600

400 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

400 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

CLL1650 60 Hz
3000

CLL1650T 50 Hz
3200

CLL1650T 60 Hz
3200

Ti [ C ]
2600 2800 2800

Ti [ C ] 50 45

Ti [ C ] 50
2200

50
2400

45 40

45 40

2400

40 35
2000

Pf [ W ]

1800

35 30

35 30

2000

30
1600

1400

25 20

25 20

1600

25 20

1000

1200

1200

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

6/47

CLT

Cooling units

Top mounting
Cooling units for electrical switchboards: c Respect for the environment by using the ecological gas R134a. c Automatic evaporation of condensation water. c Cooling power of 760 W to 3100 W. General features: c Temperature setting can be adjusted from +20 to +50 C. c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off. c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c The equipment is fitted with switches enabling an alarm report. c System of automatic recovery and evaporation of condensates.

CLT1050

Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Starting current Rated current Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Control type thermostatic Temperature setting range Maximum external temperature Noise level Airow Internal circuit External circuit Alarm type free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve)

CLT760

CLT1050 230 V 50/60 Hz

CLT1460

760/810 W (2594/2765 Btu/h) 610/640 W (2082/2184 Btu/h)

1050/1100 W (3584/3755 Btu/h) 840/890 W (2867/3038 Btu/h)

1460/1500 W (4983/5121 Btu/h) 1200/1200 W (4096/4096 Btu/h)

340 mm 600 mm 350 mm

400 mm 700 mm 400 mm

7.7/8.8 A 2/2.3 A

10.1/11.6 A 2.7/3 A

14.1/16.2 A 3.7/4.3 A

380/440 W 440/500 W

550/580 W 580/660 W

730/810 W 810/930 W

2.0/1.8

2.1/1.9 Thermostat 20 - 50 C 55 C 67 dB (A)

2.1/1.9

69 dB (A) 400/440 m3/h 620/680 m3/h Inverter contact

350/385 m3/h 350/385 m3/h

33 kg R134a (0.5 kg) 54 34

41 kg R134a (0.7 kg) 54 34 Yes Top

45 kg R134a (0.75 kg) 54 34

T3 A

T4 A

T6 A

6/48

CLT

Cooling units

Dimensions (mm)
FIG. 1

Top-mounting Ref.: CLT760-CTL1050-CTL1460

26 J

8
K 250 300 C

D M*

E H

Drilling template for top mounting without intermediate frame

Reference CLT760 CLT1050 CLT1460

A 108 118 118

B 350 420 420

C 350 400 400

D 40 45 45

E 136 180 180

F 292 328 328

G 80 90 90

H 600 700 700

I 600 700 700

K 340 400 400

M 600 700 700

FIG. 2

Curves
CLT760 50 Hz
1400

CLT760 60 Hz
1400

CLT1050 50 Hz
1800

1200

Ti [ C ]

1200

Ti [ C ] 50

1600

Ti [ C ]
1400

50
1000

45 40 35 30 25

1000

45 40 35

50 45

Pf [ W ]

1200

800

800

40 35 30

30 25
1000

600

20

600

20 800

25 20

400

400

600

200 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

200 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

400 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

CLT1050 60 Hz
1800

CLT1460 50 Hz
2400

CLT1460 60 Hz
2400

1600

2100

Ti [ C ]

2100

Ti [ C ] 50

1400

Ti [ C ] 50 45
1800

50 45 40
1500 1800

45 40

Pf [ W ]

1200

40 35

35 30

1500

35 30

1000

30 25
1200

800

25 20

1200

25 20

20
900

600

900

400 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

600

600

20

25

30

35

40

45 Te [ C ]

50

55 f = 50 Hz

20

25

30

35

40

45 Te [ C ]

50

55 f = 60 Hz

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

6/49

CLT

Cooling units

Top mounting
Cooling units for electrical switchboards: c Respect for the environment by using the ecological gas R134a. c Automatic evaporation of condensation water. c Cooling power of 760 W to 3100 W. General features: c Temperature setting can be adjusted from +20 to +50 C. c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off. c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c The equipment is fitted with switches enabling an alarm report. c System of automatic recovery and evaporation of condensates.

CLT1650

Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Starting current Rated current Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature regulator Temperature setting range Maximum external temperature Noise level Airow Internal circuit External circuit Alarm type free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve)

CLT1650 230 V 50/60 Hz 1650/1700 W (5631/5802 Btu/h) 1300/1400 W (4438/4779 Btu/h)

CLT1650T 3 400 V 50 Hz / 3 440 V 60 Hz 1650/2100 W (6826/7169 Btu/h) 1600/1700 W (5462/5803 Btu/h)

430 mm 700 mm 400 mm

16.1/18.5 A 4.2/4.5 A

6.8 /7.9 A 2.1/2.5 A

800/920 W 920/1100 W

1200/1400 W 1400/1700 W

2.1/1.9 Thermostat 20 - 50 C 55 C 67 dB (A) 550/600 m3/h 620/680 m3/h Inverter contact 47 kg R134a (1.0 kg) 54 34 Yes Top T6 A

1.7/1.5

69 dB (A)

60 kg

T3 A

6/50

CLT

Cooling units

Dimensions (mm)
FIG. 1

Top mounting Ref.: CLT1650-CLT1650T

26 J

8
K 250 300 C

D M*

E H

Drilling template for top mounting without intermediate frame

Reference CLT1650 CLT1650T

A 118 118

B 420 420

C 400 400

D 45 45

E 180 180

F 328 328

G 90 90

H 700 700

I 700 700

K 430 430

M 700 700

FIG. 2

Curves
CLT1650 50 Hz
3000 3000

CLT1650 60 Hz

2600 Ti [ C ] 2200 Pf [ W ] 50 45 1800 40 35 30 1400 25 20 1000

2600 Ti [ C ] 50 2200 45 40 1800 35 30 1400 25 20 1000

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

CLT1650T 50 Hz
3200 Ti [ C ] 2800 50 2800 3200

CLT1650T 60 Hz

Ti [ C ] 50 45

2400 Pf [ W ]

45 40

2400 40 35

2000

35 30

2000 30 25 20 1200

1600

25 20

1600

1200

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

600 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

6/51

CLT

Cooling units

Top mounting
Cooling units for electrical switchboards: c Respect for the environment by using the ecological gas R134a. c Automatic evaporation of condensation water. c Cooling power of 760 W to 3100 W. General features: c Temperature setting can be adjusted from +20 to +50 C. c As standard, the units are fitted with an automatic reset pressure switch. A value higher than safety pressure value (on the high pressure circuit) actuates compressor and external fan switch-off.
CLT3100T

c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c The equipment is fitted with switches enabling an alarm report. c System of automatic recovery and evaporation of condensates.

Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Start-up Nominal Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature regulator Control range Max. external ambient temperature Noise level Internal IP circuit External IP circuit Alarm type contact free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve)

CLT2450T 3 400 V 50 Hz / 3 440 V 60 Hz 2450/2600 W (8362/8876 Btu/h) 2000/2100 W (6828/7169 Btu/h)

CLT3100T

3100/3300 W (10580/11266 Btu/h) 2500/2600 W (8532/8876 Btu/h)

470 mm 800 mm 450 mm

8.4/10.1 A 2.6/3.2 A

9.6/11.3 A 3.0/3.5 A

1500/1800 W 1800/2100 W

1700/2000 W 2000/2300 W

1.6/1.5 Thermostat 20 - 50 C 55 C 69 dB (A) 750/820 m3/h 1200/1310 m3/h Inverter contact 65 kg R134a (1.5 kg) 54 34 Yes Top T4 A

1.8/1.7

R134a (1.7 kg)

T4 A

6/52

CLT

Cooling units

Dimensions (mm)
FIG. 1

Top mounting Ref.: CLT2450T-CLT3100T

26

800

26

220

360

10
470 * 300 300 450

70

140

380 800

140

800*
* Maximum overall dimensions of the intermediate frame

FIG. 2

Curves
CLT2450T 50 Hz
4000 Ti [ C ] 50 45 3000 Pf [ W ] 45 40 35 2500 35 30 25 2000 25 20 1500 1500 2000 20 2500 30 3000 40 4000 Ti [ C ] 50

CLT2450T 60 Hz

3500

3500

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

1000 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

1000 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

CLT3100T 50 Hz
5500 5500

CLT3100T 60 Hz

4900 Ti [ C ] 4300 50 Pf [ W ] 3700 45 40 3100 35 30 2500 25 20 1900

4900 Ti [ C ] 4300 50 45 3700 40 35 3100 30 25 2500 20 1900

1300 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz

1300 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

6/53

CLL / CLT

Accessories

Frames for partial ush mounting


c For partial flush mounting of the CLL cooling units.
Reference MECL370 MECL760 MECL1050 MECL1650 To t the units CLL370 CLL760 CLL1050 CLL1650/1650T

Reference MECL370 MECL760 MECL1050 MECL1650


Partial ush unit mounting Frame for partial mounting

T 320 370 420 420

V 635 815 915 1015

V* 646 826 926 1026

W* 346 396 446 446

X 80 95 95 120

Y 90 100 100 100

* Maximum dimensions of the frame

*V

X 26

*20

*W
26

X Y

6/54

CLL / CLT

Accessories

Intermediate frame for top mounting


c For mounting the CLT760 cooling unit on the top of enclosures width = 600 mm depth = 400 mm c Colour grey RAL-7032. c Dimensions: 60 595 360 mm.
Reference MMI64 Characteristics To t enclosures 600 mm wide and 400 mm deep.

26

360

Replacement lter
Reference FCLIC Characteristics To t to all cooling units

6/55

Cooling units CLLMP/CLTMP electronic control

6/56

c Available in two versions: top- and side-mounting. c Power from 1100 W to 1800 W allowing you to install the equipment that best suits your needs in each case.

Comfortable and easy to assemble and disassemble. The side-mounted air conditioners feature an exclusive quickinstallation system: c Two retractable handles facilitate the installation of the air conditioner by a single operator. c They have an exclusive quick-fixing system without screws that facilitates mounting

on the enclosure and guarantees the IP54 degree of protection. c The electrical connection is carried out with removable connectors supplied with the cooling unit. One single machining size. The machining sizes are the same for all sidemounted cooling units.

c Fast access to the inside makes unit cleaning and maintenance easy. c Its design renders lters unnecessary in most cases. It is possible to install a lter in the exterior circuit for particularly polluted atmospheres.

c The design of the aluminium slats of the condenser makes maintenance easier and less frequent.

ENVIRONMENTALLY friendly
The inside and outside air circuits are perfectly separated and maintain the enclosures IP54 watertightness. Two fans guarantee air circulation in each of the circuits: c Recirculation fan for air inside the enclosure. The internal circuit fan is always on, thereby maintaining a uniform temperature inside the enclosure and preventing hot spots. c Fan to circulate the air outside the enclosure. The inside thermostat controls the fan and starts it up when the temperature of the air inside the enclosure is above the required temperature. All models, side-and top-mounting, have an automatic evaporation system for the condensation water. Use of R134 ecological gas.

Electronic regulation provides: c Precise control of the operating temperature: Start-up of the compressor at +1 C above the preset temperature. Switching off of the compressor at -5 C below the preset temperature. c Door contact management. c Manual alarm reset. c Manual rearming of the alarms. c Control of the idle and operation times of the compressor. Temperature adjustment range from +20 to +50 C.

6/57

CLLMP

Electronically-controlled cooling units

Side mounting
General characteristics: c Main components: high temperature compressor, two fans mounted on removable support, two exchange cassettes, ecological cooling fluid HFC R134a, electronic control and evaporation device (with anti-corrosion finish) for side and top models. c Temperature setting can be adjusted from +20 to +50 C (pre-adjustment and temperature recommended: 35 C). c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c Electronic control by microprocessor enables: v Adjustment of set temperature. v Door contact control. v Data is stored in the memory in the event of a power cut: Minimum compressor operating time. Minimum compressor idle time. v Compressor switch-on at set temperature +1 C. v Compressor switch-off at set temperature 5 C. v Alarm management. v Alarm reset by acknowledgement (manual reset). Operating conditions: c Operating temperature: +20 to +55 C. c An optional filter is required in cases of installation in the following applications: intensive welding, hot metal forging, fibres and textiles, crushing, rubber processing and other difficult environments. c The air conditioner incorporates two retractable handles to facilitate transport. c The air conditioner incorporates a quick attachment device. A circular screw/ cage nut assembly ensures locking of the unit from the exterior. c Electrical connection is by plug-in connectors, included with the unit. c Do not obstruct, even partially, air inlets and outlets. c The unit should be installed spaced at least 30 cm from walls and at least 10 cm from floor level.
Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Current Start-up Nominal Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature regulator Temperature setting range Max. external ambient temperature Noise level Airow Internal circuit External circuit Alarm type free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve) T6 A T8 A 45 kg R134a (0.85 kg) 54 34 46 kg R134a (0.85 kg) 54 34 Optional Side T2 A T3 A 62 dB (A) 575/600 m3/h 860/900 m3/h 64 dB (A) 860/900 m3/h 860/900 m3/h 12.1/13.9 A 3.2/3.7 A 600/690 W 690/790 W 1.8/1.7 CLLMP1100 CLLMP1400 230 V 50/60 Hz 1100/1200 W (3755/4097 Btu/h) 880/930 W (3004/3175 Btu/h) 1400/1500 W (4780/5121 Btu/h) 1200/1300 W (4097/4438 Btu/h) CLLMP1400T CLLMP1800T

CLLMP1400

3 400 V 50 Hz / 3 440 V 60 Hz 1400/1500 W (4780/5121 Btu/h) 1200/1300 W (4097/4438 Btu/h) 1800/1900 W (6145/6485 Btu/h) 1400/1500 W (4780/5121 Btu/h)

1,010 mm 400 mm 240 mm 18.1/22.2 A 4.8/5.8 A 900/1,100 W 1100/1300 W 1.6/1.4 3.7/4.3 A 1.2/1.4 A 700/810 W 810/930 W 2.0/1.9 5.3/6.3 A 1.8/2.1 A 1000/1200 W 1200/1300 W 1.8/1.7

Microprocessor (with display and diagnosis) 20 - 50 C 55 C 66 dB (A) 860/900 m3/h 860/900 m3/h Inverter contact 47 kg R134a (0.85 kg) 54 34 50 kg R134a (0.85 kg) 54 34 69 dB (A) 885/900 m3/h 1050/1160 m3/h

6/58

CLLMP

Electronically-controlled cooling units

Dimensions (mm)
FIG. 1

Drilling template for side mounting

Drilling template for side mounting

FIG. 2

Curves
CLLMP1100 50 Hz
2000 1800 Ti [ C ] 1600 1400 Pf [ W ] 1200 1000 800 600 400 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 50 45 40 35 30 25 20 800 600 400 20 25 30 35 40 45 50 55 Te [ C ] f = 60 Hz 1000 1200 1600 1400

CLLMP1100 60 Hz
2000 1800 Ti [ C ] 50 45 40 35 30 25 20

CLLMP1400T 50 Hz
2200 Ti [ C ] 2000 1800 1600 1400 1200 25 1000 800 600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 20 50 45 40 35 30

CLLMP1400T 60 Hz
2200 Ti [ C ] 2000 1800 1600 Pf [ W ] 1400 1200 1000 800 600 20 25 30 35 40 45 50 55 Te [ C ] f = 60 Hz 50 45 40 35 30 25 20

CLLMP1400 50 Hz
2200 Ti [ C ] 2000 1800 1600 1400 1200 1000 800 600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 50 45 40 35 30 25 20

CLLMP1400 60 Hz
2200 Ti [ C ] 2000 1800 1600 35 1400 1200 1000 800 600 20 25 30 35 40 45 50 55 Te [ C ] f = 60 Hz 30 25 20 50 45 40

CLLMP1800T 50 Hz
3000 Ti [ C ] 2800 2600 2400 2200 Pf [ W ] 2000 1800 1600 1400 1200 1000 800 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 50 45 40 35 30 25 20

CLLMP1800T 60 Hz
3000 Ti [ C ] 2800 2600 2400 2200 2000 1800 1600 1400 1200 1000 800 20 25 30 35 40 45 50 55 Te [ C ] f = 60 Hz 50 45 40 35 30 25 20

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

6/59

CLTMP

Electronically-controlled cooling units

Top mounting
General characteristics: c Main components: high temperature compressor, two fans mounted on removable support, two exchange cassettes, ecological cooling fluid HFC R134a, electronic control and evaporation device (with anti-corrosion finish) for side and top models. c Temperature setting can be adjusted from +20 to +50 C (pre-adjustment and temperature recommended: 35 C). c Internal and external air circuits are totally independent and IP54 sealing is assured between external ambient air and air within the enclosure. c The internal circuit fan which runs continuously, prevents formation of hot spots and improves thermal dissipation of the enclosure. c Electronic control by microprocessor enables: v Adjustment of set temperature. v Door contact control. v Data is stored in the memory in the event of a power cut: Minimum compressor operating time. Minimum compressor idle time. v Compressor switch-on at set temperature +1 C. v Compressor switch-off at set temperature 5 C. v Alarm management. v Alarm reset by acknowledgement (manual reset). Operating conditions: c Operating temperature: +20 to +55 C. c An optional filter is required in cases of installation in the following applications: intensive welding, hot metal forging, fibres and textiles, crushing, rubber processing and other difficult environments. c The air conditioner incorporates two retractable handles to facilitate transport. c The air conditioner incorporates a quick attachment device. A circular screw/cage nut assembly ensures locking of the unit from the exterior. c Electrical connection is by plug-in connectors, included with the unit. c Do not obstruct, even partially, air inlets and outlets. c The unit should be installed spaced at least 30 cm from walls and at least 10 cm from floor level.
Reference Voltage Cooling power (50/60 Hz) according to EN 14511 L35 - L35 L35 - L50 Dimensions Height Width Depth Intensity Starting current Rated current Electrical power absorbed L35 - L35 L35 - L50 EER energetic performance L35 - L35 Temperature regulator Temperature setting range Max. external ambient temperature Noise level Airow Internal circuit External circuit Alarm type free power Weight Cooling gas Internal IP circuit External IP circuit External circuit lter Mounting model Recommended protection (fuse curve) T8 A 48 kg R134a (0.95 kg) 54 34 Optional Top T3 A 64 dB (A) 860/900 m3/h 860/900 m3/h Inverter contact 50 kg R134a (0.95 kg) 18.1/22.2 A 4.8/5.8 A CLTMP1400 230 V 50/60 Hz 1400/1500 W (4780/5121 Btu/h) 1200/1300 W (4097/4438 Btu/h) CLTMP1800T 3 400 V 50 Hz / 3 440 V 60 Hz 1800/1900 W (6145/6485 Btu/h) 1400/1500 W (4780/5121 Btu/h)

CLTMP1400

415 mm 750 mm 412 mm 5.3/6.3 A 1.8/2.1 A

900/1100 W 1100/1300 W

1000/1200 W 1200/1300 W

1.6/1.4 Microprocessor (with display and diagnosis) 20 - 50 C 55 C

1.8/1.7

69 dB (A) 885/900 m3/h 1050/1160 m3/h

6/60

CLTMP

Electronically-controlled cooling units

Dimensions (mm)
FIG. 1

Drilling template for top mounting

Drilling template for top mounting

FIG. 2

Curves
CLTMP1400 60 Hz
2200 Ti [ C ] 2000 1800 1600 50 45 2000 1800 1600 1400 1200 1000 800 600 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 20 25 30 35 40 45 Te [ C ] 50 55 f = 60 Hz

CLTMP1400 50 Hz
2200 Ti [ C ] 50 45 40 35 30 25 20

Pf [ W]

40 35 30

1400 1200 1000 800 600

25 20

CLTMP1800T 50 Hz
3000 2800 2600 2400 2200 Pf [ W ] 2000 1800 1600 1400 1200 1000 800 20 25 30 35 40 45 Te [ C ] 50 55 f = 50 Hz 50 45 40 35 30 25 20 Ti [ C ]

CLTMP1800T 60 Hz
3000 2800 2600 2400 2200 2000 1800 1600 1400 1200 1000 800 20 25 30 35 40 45 50 55 Te [ C ] f = 60 Hz Ti [ C ] 50 45 40 35 30 25 20

Te: ambient air temperature (C) Ti: temperature inside enclosure (C) Pf: cooling power (W)

6/61

CLLMP / CLTPM

Accessories

Filter unit
c For installation in the outside circuit of the side cooling units. Reference CLLMP... c Reference: CFCLL.

CFCLL

c Replacement filter. Reference: CFLL.

CFLL

6/62

CLLMP / CLTPM

Accessories

Side panels prepared for air conditioners


c Set of 2 side panels for fixing inside or outside the enclosure. One pre-knocked panel for the direct xing of the CLLMP side-mounted cooling units
Reference 2PLOL186CLM 2PLOL188CLM 2PLOL206CLM 2PLOL208CLM Height 1,800 1,800 2,000 2,000 Depth 600 800 600 800

6/63

Insulated resistance heaters Heating safely

6/64

c Available in two versions: by convection and with fan. c Alternating or direct current. c Powers from 10 W to 550 W.

It has a plastic covering to prevent direct contact with the aluminium radiator.

c The resistors equipped with fan guarantee air recirculation and an even temperature inside the enclosure. c High-flow, silent fans.

c Small size. c Fast electrical connection by means of snap-on terminals. c Fast and simple fixing to the 35 mm DIN rail. c Maintenance-free.

c Protected from direct contact with the aluminium radiator. c Electrical connection protected from direct contact by means of a plastic terminal block cover. c Equipped with a PTC-type heating element. c Surface temperature below +70 C. c The configuration of the aluminium section produces a chimney effect. High natural convection. c Low energy consumption thanks to the autoadjustment of the PTC resistor.

Certifications

c EC Marking. c Compliant with UL and VDE across the range.

6/65

RESISTANCE HEATERS

Selection guide

INSULATED RESISTANCE HEATERS


Type of connection Reference Power W Voltage V Terminal block RC10/12-36AI RC10AI RC20/12-36AI RC20AI RC50/12-36AI RC50AI RC50/270-420AI RC100/12-36AI RC100AI RC100/270-420AI RC150/12-36AI RC150AI 10 10 21 21 55 55 55 102 102 102 147 147 12-36 DC 110-250 AC 12-36 DC 110-250 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC X X X X X X X X X X X X Cable

6/66

RESISTANCE HEATERS

Selection guide

INSULATED RESISTANCE HEATERS WITH FAN


Type of connection Reference Power W Voltage V Terminal block RCV170 170 230 AC X Cable

THERMOFANS
Typo of connection Reference Power W Voltage V Terminal block TMV350-550/120 TMV350/550 TMV350 400/550 400/550 350 120 AC 230 AC 230 AC X X X Cable

6/67

RC ... AI

Resistance heaters

Insulated RC10AI - RC20AI 10 W and 20 W insulated resistance heaters


General characteristics: c Compact resistance heater which prevents the condensation of water and ice inside the enclosures. c Innovative design for better natural convection and high thermal performance. c Compact, smaller resistance heater. c Extruded aluminium body. c Features an insulated UL94 V0 plastic cover in light grey to avoid direct contact with the heating elements (PTC) and the aluminium radiator. c Surface temperature limited to less than 70 C. c Equipped with a connection cable. c Double safety insulated (plastic). c PTC technology range. c Quick clip-fixing onto the 35 mm DIN rail. c Compliant with UL and VDE EC Marking. Usage conditions: c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed). c The enclosure must be sealed in order to prevent the penetration of external air. c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.

Characteristics RC10AI Heating power at 0 C Power supply voltage Heating element Surface temperature Electrical connection Fixing Cover Operating position Operating temperature IP Protection/Class Certications 110-250 V AC/DC 10 W 12-36 V AC/DC RC10/12-36AI

Reference RC20AI 21 W 110-250 V AC/DC PTC <70 C, except for upper protection grill Terminal board By clip for the 35 mm DIN rail (EN 50022) Plastic UL94 V0 Vertical 40 to +70 C (10 to +15 F) IP20II (double insulation) VDE and UL in process 12-36 V AC/DC RC20/12-36AI

6/68

RC ... AI

Resistance heaters

Dimensions (mm)
FIG. 1

Connections
Reference RC10AI RC20AI L (mm) 98 98

38

2 75

Clip on clip de 35 mm fijaci n para rail carril DIN


DIN de 35 mm 98 1 2

6/69

RC ... AI

Resistance heaters

RC50AI - RC100AI - RC150AI 55 W - 100 W - 147 W insulated resistance heaters


General characteristics: c Compact resistance heater which prevents the condensation of water and ice inside the enclosures. c Innovative design for better natural convection and high thermal performance. c Compact, smaller resistance heater. c Extruded aluminium body. c Features an insulated UL94 V0 plastic cover in light grey to avoid direct contact with the heating elements (PTC) and the aluminium radiator. c Surface temperature limited to less than 70 C. c Fitted with 2.5 mm2 quick-connection terminals. c Double safety insulated (plastic). c PTC technology range. c Quick clip-fixing onto the 35 mm DIN rail (EN 50022). c Certifications compliant with UL and VDE and EC Marking. Usage conditions: c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed). c The enclosure must be sealed in order to prevent the penetration of external air. c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.

Characteristics RC50AI Heating power at 0 C Power supply voltage Heating element Surface temperature Electrical connection Fixing Cover Operating position Operating temperature IP Protection /Class Certications 110-250 V AC/DC RC50/12-36AI 55 W 12-36 V AC/DC 270-420 V AC/DC RC50/ 270-420AI

Reference RC100AI RC100/ 12-36AI 102 W 110-250 V AC/DC PTC <70 C, except for upper protection grill 4 poles terminal block, 2.5 mm2 By clip for the 35 mm DIN rail (EN 50022) Plastic UL94 V0 Vertical 40 to +70 C (10 to +158 F) IP20/II (double insulation) VDE and UL in process 12-36 V AC/DC 270-420 V AC/DC 110-250 V AC/DC RC100/ 270-420AI RC 150AI 147 W 12-36 V AC/DC RC150/ 12-36AI

6/70

RC ... AI

Resistance heaters

Dimensions (mm)
FIG. 1

Reference RC50AI RC50/12-36AI RC50/270-420AI RC100AI RC100/12-36AI RC100/270-420AI RC150AI RC150/12-36AI

L (mm)

110 110 110 110 110 150 150 150

FIG. 2

Diagram

Heating power diagram - Ambient temperature

Heating power (W)

RC150AI RC100AI RC50AI

Ambient temperature (C)

6/71

RCV

Resistance heaters with fan

RCV170
General characteristics: c Compact resistance heater which prevents the condensation of water and ice inside the enclosures. c Includes an axial fan to ensure uniform heating inside the enclosure. c Compact, smaller resistance heater. c Extruded aluminium body. c Features an insulated UL94 V0 plastic cover in black to avoid direct contact with the heating elements (PTC) and the aluminium radiator. c Surface temperature limited to less than 50 C. c Fitted with 2.5 mm2 quick-connection terminals. c Double safety insulated (plastic). c PTC technology range. c Quick clip-fixing onto the 35 mm DIN rail (EN 50022). c Certifications compliant with UL and VDE and EC Marking. Usage conditions: c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed). c The enclosure should be sealed in order to prevent the penetration of external air. c An electrical protection device should be installed on the supply side of the unit.

Characteristics

Reference RCV170

Heating power at 0 C Power supply voltage Heating element Surface temperature Service life Airow Electrical connection Fixing Cover Operating position Operating temperature IP Protection/Class Certications

177 W 230 V AC 50-60 Hz PTC Max. of 50 C in the enclosure, 100 C in the upper protection grill (for an external temperature of 20 C/68 F) 40000 h to 40 C 13.8 m3/h 2 poles of 2.5 mm2 Clip for the 35 mm DIN rail (EN 50022) Plastic UL94 V0 Vertical 40 to +70 C (10 to +158 F) IP20II (double insulation) VDE and UL in process

6/72

RCV

Resistance heaters with fan

Dimensions (mm)
FIG. 1

RCV170

6/73

Standard heating resistors Traditional convection

6/74

The Himel heating resistors for electrical or electronic enclosures are equipped with PTCtype heating elements (Positive Temperature Coefcient). The use of these semi-conductors as heating elements means that: c The aluminium surface temperature of the diffuser stabilises at +75 C (for an ambient temperature of 5 C). c Electrical energy consumption is reduced.

The design of the prole of the Himel heating resistors produces a chimney effect. Thus, a uniform temperature is achieved inside the enclosure. The resistors are secured by means of fast-xing clips on the 35 mm DIN rails.

The 10 and 20 W resistors are equipped with a 2 0.75 300 mm electrical connection cable.

Higher power resistors are equipped with fastconnection terminals.

Their broad range of powers, from 10 to 400 W, means that any solution is possible. Models from 250 and 400 W with a built-in fan.

6/75

RESISTANCE HEATERS

Selection guide

RESISTANCE HEATERS
Connection type Reference Power (W) Voltage (V) Terminal block RC10/12-36 RC10 RC20/12-36 RC20 RC20/270-420 RC55/12-36 RC55 RC55/270-420 RC100/12-36 RC100 RC100/270-420 RC150/12-36 RC150 RC150/270-420 10 10 20 20 20 55 55 55 90 90 90 150 150 150 12-36 DC 110-250 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC X X X X X X X X X X Cable X X X X

6/76

RESISTANCE HEATERS

Selection guide

RESISTANCE HEATERS WITH FAN


Connection type References Power (W) Voltage (V) Terminal block RCV250 RCV400 RCV200P/115 RCV200P 250 400 200 200 230 AC 230 AC 115 AC 230 AC X X X X Cable

6/77

RC / RCV / TMV

Resistance heaters

Resistance heaters
c Range of resistance heaters from 10 to 400 W ensuring the proper heating of the enclosure to prevent condensation.

General characteristics: c Extruded aluminium body. c Surface temperature limited to less than 75 C with an ambient temperature of 5 C. c 500 mm-long power supply cable with silicone insulation (except for the RCV400, R55, 90 and 150 models, which are equipped with a connection terminal block). Usage conditions: c The resistance heaters should be used together with a temperature regulator (thermostat TS140 or TS170, hygrostat HS300 also can be installed). c The enclosure should be sealed in order to prevent the penetration of external air. c The electrical protection devices must be installed between the supply source and the resistance heaters themselves.

Reference RC10/12-36 RC10 RC20/12-36 RC20 RC20/270-420 RC55/12-36 RC55 RC55/270-420 RC90/12-36 RC90 RC90/270-420 RC150/12-36 RC150 RC150/270-420 RC250 RC400

Power (W) 10 10 20 20 20 55 55 55 90 90 90 150 150 150 250 400

Voltage (V) 12-36 DC 110-250 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 12-36 DC 110-250 AC 270-420 AC 220-230 220-230

Start-up current (A)

Nominal current (A)

Class II

Dimensions (mm) 25 50 50 25 50 50 25 50 75 25 50 75 25 50 75 70 50 140 70 50 140 70 50 140 70 50 140 70 50 140 70 50 140 70 50 220 70 50 220 70 50 220 70 50 220 70 50 220

0.80 1

0.60 1.05

II II II II II

1.50

0.24

II II II

2.40

0.40

II II II

4.50 1.10 1.70

0.65 1.10 1.70

II II II II

6/78

RC / RCV / TMV

Resistance heaters

Resistance heaters with fan


c The fan maintains an even temperature inside the electric switchboard.

Reference RCV250 RCV400

Power (W) 250 400

Voltage (V) 230 CA 230 CA

Start-up current (A) 1.20 1.80

Nominal current (A) 1.20 1.80

Class I I

Dimensions (mm) 180 85 95 80 80 248

Plain resistance heater with fan


Reference RCV200P RCV200P/115 Power (W) 200 200 Voltage (V) 230 CA 115 CA Start-up current (A) Nominal current (A) 0.90 1.80 Class I I Dimensions (mm) 120 120 47 120 120 47

Thermofans
c This device combines a the heating power of a resistor with the operation of an axial fan, offering optimal heat distribution inside the enclosure. c Fixing onto a DIN rail. c Adjustable temperature from 10 to 50 C for TMV350, and from 0 to 60 C for TMV350/550. c Power-on indicator lamp.
TMV350

Reference TMV350 TMV350/550 TMV350-550/120

Power ( W) 350 400/550 400/550

Voltage (V) 230 CA 230 CA 120 CA

Dimensions (mm) 200 45 180 180 85 95 180 85 95

TMV350/550

6/79

Selection guide

Control devices Temperature under control


Compact thermostats (adjustable) NO (blue button): with normally open contact, when the temperature increases, the contact closes, activating the fan to extract the heat. NC (red button): with normally closed contact, when the temperature falls below the preset value, the contact closes, activating the resistance heater to prevent condensation. c Broad range of temperature control. c Small size. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals. c High-power connection.

24 V DC electronic thermostat (adjustable) It can control 24 V direct-current electrical equipment by means of a potential-free inverter contact. Resistors, fan, etc. may be connected. They have a PTC temperature probe for more precise control and low hysteresis. c High DC switching capacity. c Low hysteresis (greater temperature precision). c Switching by means of an inverter contact. c Simple xing by clip onto the 35 mm DIN/EN rail.

Dual thermostat (adjustable) To control two units independently and simultaneously: a resistance heater and a fan. NC (red button): normally closed contact (NC) for resistance heater control. NO (blue button): normally open contact (NO) for fan control. c Double thermostats in the same housing, with separate adjustment and operation. c Easy access terminals. c Simple xing by clip onto the 35 mm DIN rail.

NO/NC Thermostat (adjustable) Its NO/NC inverter contact controls a resistance heater or a fan. c Switching by means of two NO/NC contacts. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals. c High-power connection.

6/80

Hygrometer (adjustable) Combination of thermostat and hygrostat in the same unit to control relative humidity. The resistance heaters or fans are switched on when the two limit values are exceeded. c Adjustable temperature and relative humidity of the air. c High switching capacity. c Visual operation indication. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals.

Compact xed thermostats c Preset factory temperature: v Red button: 5, 10 and 15 C. v Blue button: 25, 30 and 35 C. c Small size. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals. c High-power connection.

Fixed dual thermostat c To control two units independently and simultaneously: v NO/NC: fan and resistor. v NO/NO: fan and alarm. v NC /NC: resistance and alarm. c Preset factory values. c Double thermostats in the same housing, with separate operation. c Easy access terminals. c Simple xing by clip onto the 35 mm DIN rail.

Fixed hygrostat c Factory-adjusted relative humidity: 60% RH. c Switching by means of an NO contact. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals. c High-power connection.

Hygrostat (adjustable) It is used to adjust the relative humidity in the enclosure by controlling resistance heaters or fans. The hygrostat prevents condensation and the corrosion of components. c Adjustable relative humidity. c Switching by means of an inverter contact. c Simple xing by clip onto the 35 mm DIN rail. c Easy access terminals. c High-power connection.

6/81

CONTROL DEVICES

Selection guide

THERMOSTATS
References Power supply voltage (V) Control Contact type Application Control element Switching power (ohmic load)

TS140 TS140F TS141 TS141F

C F C F

NC NC NO

Resistance heaters 30 W DC 250 V AC 10 A 120 V AC 15 A Ventilation systems Bimetal

NO Resistance heaters or ventilation systems

TS170

Switch

250 V AC 10 A

DOUBLE THERMOSTAT
References Power supply voltage (V) Control Contact type Application Control element Switching power (ohmic load)

TDS1401

NC+NO

Resistance heaters and ventilation systems

Bimetal

250 V AC 10 A 120 V AC 15 A

ELECTRONIC THERMOSTAT
References Power supply voltage (V) Control Contact type Application Control element Switching power (ohmic load) NO or NC: 24 V DC 28A

TSE200

24 DC

2 NO

Resistance heaters and ventilation systems

Electronic

FIXED THERMOSTAT
References Fixed adjustment Contact type Application Switching power (ohmic load)

TS140F5 TS140F10 TS140F15 TS141F25 TS141F30 TS141F35

5 C/41 F 10 C/50 F 15 C/59 F 25 C/77 F 30 C/86 F 35 C/95 F

NC NC NC NO NO NO Ventilation systems 250 V AC 10 A 120 V AC 15 A DC 30 W Resistance heaters 250 V AC 10 A 120 V AC 15 A DC 30 W

6/82

CONTROL DEVICES

Selection guide

FIXED DUAL THERMOSTAT


References Fixed adjustment Contact type Switching power (ohmic load)

TSD1401F10/35 TSD1401F35/45 TSD1401F5/15

10 C/50 F 35 C/95 F 35 C/95 F 45 C/113 F 5 C/41 F 15 C/59 F

NC NO NO NO NC NC 250 V AC 10 A 120 V AC 15 A DC 30 W

HYGROMETER
References Power supply voltage (V) Control Contact type Application Control element Switching power (ohmic load)

THS3000

230 CA

% RH, C

Switch

Resistance heaters and ventilation systems

Bimetal

240 V AC 8 A 120 V AC 8 A

HYGROSTAT
References Power supply voltage (V) Control Contact type Application Control element Switching power (ohmic load)

HS300

% RH

Switch

Resistance heaters and ventilation systems

Bimetal

230 V AC 5 A

FIXED HYGROSTAT
References Fixed adjustment Contact type Max. control current 250 V AC 5 A DC 20 W

HS300F60

60% RH

Switch

6/83

TS

Control devices

Thermostat TS140
c Thermostat (normally closed contact (NC) for the control of resistance heaters. c Thermostat use increases service life of resistors, switching them only when required by the temperature. c Fixing onto a DIN rail. c IP20. c V0 self-extinguishing thermoplastic as per UL94. c Adjustable temperature from 0 to 60 C. c Connection: 2 x 2.5 mm2 terminals.
Reference TS140 TS140F Dimensions (mm) 60 33 43 60 33 43 Max. control current 250 V 10 A 250 V 10 A

FIG. 1 Technical specications Sensor element Contact type


load carga

Bimetal Normally closed (NC), snap action contact < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0.6) DC 30 W Terminals with two 2.5 mm poles Clip for the 35 mm DIN rail , EN 50022 V0 thermoplastic UL94, light grey 60 33 43 mm 40 g Non-dened 20 to +80 C (4 to +176 F) IP20 7 K From 0 to 60 C

2
V

Contact resistance Service life

1 L N

Max. switching capacity

Load = resistance Carga = resistencia

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis Adjustable temperature

6/84

TS

Control devices

Thermostat TS141
c Thermostat (normally open NO contact) for control of fans. c This thermostat allows the regulation of temperature in the enclosure, starting the fan only in case fresh air is required. As a result, service life of the fan is increased and its filter stays cleaner. c DIN rail fixing. c Degree of protection IP20. c V0 self-extinguishing thermoplastic as per UL94. c Adjustable temperature from 0 to 60 C. c Connection: 2 2.5 mm2 terminals.

Reference TS141 TS141F

Dimensions (mm) 60 33 43 60 33 43

Max. control current 250 V 10 A 250 V 10 A

FIG. 1

Technical specications Sensor element Contact type


load carga

Bimetal Normally open (NO), snap action contact < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0.6) DC 30 W Terminals with two 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 60 33 43 mm 40 g Non-dened 20 to +80 C (4 to +176 F) IP20 7 K From 0 to 60 C

2
V

Contact resistance Service life

1 L N

Max. switching capacity

Load = fan Carga = ventilador

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis Adjustable temperature

6/85

TS

Control devices

Thermostat TS170
c Thermostat (contact switch) to control the fan or resistance heaters. c With this device, the internal temperature of the panel may be regulated by switching on a resistor or a fan. c Fixing on a DIN rail. c IP20. c V0 self-extinguishing thermoplastic as per UL94. c Adjustable temperature from 10 to 60 C. c Connection: 4 2.5 mm2 terminals.

Reference TS170

Dimensions (mm) 67 50 44

Max. control current (NA) 5 A/(NC) 10 A

FIG. 1

Technical specications Sensor element Contact type


Load 2

Bimetal Switch contact, snap action < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 250 V AC 4 A (inductive load cos = 0.6) DC 30 W Terminals with four 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 67 50 44 mm 100 g Non-dened 20 to +80 C (4 to +176 F) IP20 7 K From 5 to 60 C

Contact resistance Service life

Load 3

>

Max. switching capacity Max. opening contact Connection

Load (2) =resistance Load (3) = fan

Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis Adjustable temperature

6/86

TS

Control devices

Dual thermostat TSD1401


c Dual temperature regulator. c Two thermostats in one single enclosure. c Separate control and operation. c Fixing clip for the 35 mm DIN rail. c IP20. c Dual thermostat (two thermostats in one single box). With the red button (normally closed contact- NC), the resistance heater can be regulated. A fan, signalling system or alarm can be controlled with the blue button (normally open contact- NO). This thermostat allows the simultaneous control of a resistance heater and a fan, making an independent temperature adjustment possible.

Reference TSD1401

Dimensions (mm) 67 50 44

Max. control current 250 V AC 10 A 120 V AC 15 A

FIG. 1

Technical specications
11 12
V

N1

L1

Sensor element Contact type Contact resistance Service life

Bimetal 1 normally open (NO), 1 normally closed (NC), snap action < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0,6) DC 30 W Terminals with six 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 67 50 44 mm 90 g Non-dened 20 to +80 C (4 to +176 F) IP20 7 K From 0 to 60 C

23 24
V

Max. switching capacity

N2

L2

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis Adjustable temperature

6/87

TS

Control devices

Thermostat TSE200
c Electronic temperature regulator. c 24 V DC supply. c Fixing by clip for 35 mm DIN rail. c IP20. c Thermostat with volt-free 2 dry contact switching relay. c Allows high number of switching operations with improved temperature accuracy ( 2 K) thanks to its PTC probe. c The miniature communication relays installed in the thermostat are powerful (230 A) and safe. c Possibility of having a thermostat with open-contact switches or inverted switches.

Reference TSE200

Dimensions (mm) 67 50 44

Max. rated current NA o NC: 24 V DC 2 8 A

FIG. 1

Technical specications Adjustable temperature


_ V + 11 12 21 22

+24 V

From 0 to +60 C 2 K 2 K PTC probe Terminals with six 2.5 mm2 poles 2 normally open (NO), snap action contact Clip for the 35 mm DIN rail, EN 50022 ABS according to UL94 V0 0 to +60 C (32 to +140 F) IP20 67 50 44 mm 80 g

Hysteresis Sensor element Connection Contact type Mounting Cover Operating temperature Degree of protection Dimensions Weight

6/88

TS

Control devices

Fixed thermostats TS140F


c Thermostat (normally closed contact - NC) to control resistance heaters. c DIN rail fixing. c Degree of protection IP20. c V0 self-extinguishing thermoplastic material as per UL94. c Factory-adjusted temperature. c Connection: 2 2.5 mm2 terminals.

Reference TS140F5 TS140F10 TS140F15

Fixed adjustment 5 C/41 F 10 C/50 F 15 C/59 F

Max. control current

250 V AC 10 A 120 V AC 15 A DC 30 W

FIG. 1

Technical specications Sensor element


Load carga1

Bimetal Normally closed (NC), snap action contact Normally closed (NC), snap action contact < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0.6) DC 30 W Terminals with two 2.5 mm2 poles Clip for the 35 mm DIN rail 35 mm, EN 50022 V0 UL94 thermoplastic, light grey 60 33 43 mm 40 g Non-dened 20 to +80 C (4 to +176 F) IP20

2
V

Contact type Contact resistance Service life

1 L N

Max. switching capacity


Load = resistance Carga = resistencia

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection

6/89

TS

Control devices

Fixed thermostats TS141F


c Thermostat (normally open - NO contact) to control fans. c Degree of protection IP20. c V0 self-extinguishing thermoplastic as per UL94. c Factory-adjusted temperature. c Connection: 2 2.5 mm2 terminals. c DIN rail fixing.
Reference TS141F25 TS141F30 TS141F35 Fixed adjustment 25 C/77 F 30 C/86 F 35 C/95 F Max. control current 250 V AC 10 A 120 V AC 15 A DC 30 W

FIG. 1

Technical specications Sensor element


carga

Bimetal Normally open (NO), snap action contact < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0.6) DC 30 W Terminals with two 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 60 33 43 mm 40 g Non-dened 20 to + 80 C (4 to +176 F) IP20 7 K

Contact type
2
V

Contact resistance Service life

1 L N

Max. switching capacity

Load = fan Carga = ventilador

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis

6/90

TS

Control devices

Fixed dual thermostat TSD1401F


c Dual temperature regulator. c Two thermostat in one enclosure with separated setting and operation. c 35 mm DIN rail clip fixing. c Factory-adjusted temperature. c This unit allows trip control of a fan and a resistance heater, independent setting and operation.
Reference TSD1401F10/35 TSD1401F35/45 TSD1401F5/15 Contact type NC: NO: NO: NO: NC: NC: Fixed adjustment 10 C/50 F 35 C/95 F 35 C/95 F 45 C/113 F 5 C/41 F 15 C/59 F

Technical specications Sensor element FIG. 1


N1 L1 11 12
V

Bimetal Snap action < 10 m > 100000 cycles 250 V AC 10 A (ohmic load) 120 V AC 15 A (ohmic load) 250/120 V AC 2 A (inductive load cos = 0.6) DC 30 W Terminals with six 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 67 50 44 mm 90 g Non-dened 20 to +80 C (4 to +176 F) IP20 7 K

Contact type Contact resistance Service life

Max. switching capacity


23 24
V

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Hysteresis

N2

L2

6/91

TS

Control devices

Hygrometer THS3000
c The device independently measures the temperature and humidity within the electrical enclosure. The resistance heater is switched on when either of the limiting values set for the two parameters is exceeded: the temperature rises and the relative humidity RH falls. The hygrometer switch should be preferably be installed in the upper part of the enclosure at a minimum distance of 50 cm from the resistance heater. c DIN rail fixing. c Degree of protection IP20. c V0 self-extinguishing thermoplastic as per UL94. c Adjustable temperature from 0 to 60 C. c Adjsutable relative humidity from 50 to 90%.
FIG. 1

c Hysteresis: 2 C, 3% RH. c Service life: >100000 cycles.

Reference

Dimensions (mm)

Max. control current 250 V AC 8 A 12 V DC 8 A 35 V DC 5 A

T RH

THS3000

67 50 43

Technical specications
1 2 3 4 5 L N
Load Carga

230 V 50 Hz

Power supply voltage Switching precision Switching precision Response time Contact type Contact resistance Service life

230 V AC 50/60 Hz Temperature 2 K (1 K) Humidity 4% (1%) Approx. 160 sec. Switch < 10 m > 100000 cycles 240 V AC 8 A (ohmic load) 240/120 V AC 4 A (inductive load cos = 0.6) 240 V DC 0.1 A 48 V DC 0.8 A 24 V DC 8 A Terminals with ve 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 67 50 43 mm 200 g Vertical 20 to +60 C (4 to +140 F) IP20 LED

Max. switching capacity

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection Power-on indicator

6/92

TS

Control devices

Hygrostat HS300
c This device only measures the relative humidity inside the enclosure. c It is used to switch on the resistance heater when the humidity rises above the set value. c DIN rail fixing. c Degree of protection IP20. c V0 self-extinguishing thermoplastic as per UL94. c Adjustable relative humidity from 30 to 90%.
Reference HS300 Dimensions (mm) 67 50 37 Max. control current 250 V AC 5 A

FIG. 1

Technical specications Control Switching precision


Load1 1 carga

35% to 95% RH Humidity 4% (3%) 15 m/sec Switch < 10 m 50000 cycles 20 V AC/DC 100 mA 230 V AC 5 A (ohmic load) 230/120 V AC 0.2 A (inductive load cos = 0.6 50 V DC 1 A/75 V DC 0.5 A (inductive load L/R = 3 ms) Terminals with three 2.5 mm2 poles Clip for the 35 mm DIN rail , EN 50022 V0 UL94 thermoplastic, light grey 67 50 37 mm 100 g Non-dened 20 to +60 C (4 to +140 F) IP20

Permissible air velocity


1
V

Contact type Contact resistance Service life Min. switching power

Load2 2 carga

Load 1= (dehumidi er) Carga 1 resistance = resistencia (deshumidificador) Load 2= er Carga 2 humidi = humidificador

Max. switching capacity

Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection

6/93

TS

Control devices

Fixed hygrostat HS300F


c This device only measures the relative humidity inside the enclosure. c It can be used to start up a resistance heater when this relative humidity exceeds the preset value. c DIN rail fixing. c Degree of protection IP20. c V0 self-extinguishing thermoplastic as per UL94. c Factory-adjusted relative humidity.
Reference HS300F60 Fixed adjustment 60% RH Max. control current 250 V AC 5 A DC 20 W

FIG. 1

Technical specications Switching precision


3

Humidity 4% (3%) 15 m/sec Switch < 10 m 50000 cycles 20 V AC/DC 100 mA 250 V AC 5 A (ohmic load) 250 V AC 0,2 A (inductive load cos = 0.6) DC 20 W Terminals with three 2.5 mm2 poles Clip for the 35 mm DIN rail, EN 50022 V0 UL94 thermoplastic, light grey 67 50 37 mm 100 g Non-dened 20 to +60 C (4 to +140 F) IP20

carga 1

Permissible air velocity Contact type

1
V

Contact resistance Service life Min. switching power

carga 2

Load 1 = resistance (dehumidier) Carga 1 = resistencia (deshumidificador) Load 22 ==humidi er Carga humidificador

Max. switching capacity Connection Mounting Cover Dimensions Weight Fitting position Operating temperature Degree of protection

6/94

HEAT CALCULATION

Thermal management for electrical control panels

Due to the miniaturisation of the components, the generalisation of electronics, and the appearance of new electronically-based power products, temperature control has become an increasingly important necessity that must be taken into account when designing electrical and/or electronic control panels, as is being done with the IP degree of protection. Reliability and the search for minimal breakdown rates are two determining factors in process industries where hourly operation costs for the installations are extremely high; the smallest breakdown can immediately result in losses totalling hundreds of thousands of pesetas. The service life of the components depends on the temperature and humidity conditions in the enclosure. The solutions to these problems are varied, and can depend on environmental conditions, the type of components in the electrical control panel and, of course, their cost! In certain cases, it is enough to oversize the enclosure or to use fans. In other cases, where ambient temperatures are higher, heat exchangers or cooling units must be used. Himel offers a wide range of solutions adapted to all situations.

To air
Natural dissipation (through the enclosure walls). In some cases, using a larger enclosure can solve the heating problem. Natural ventilation Providing fresh exterior air through ventilation outlet grilles improves heat dissipation through natural convection. Nevertheless, this solution can only be used in low-dust environments when the power to be dissipated is low.

If At > Dt

If At < Dt

At = ambient temperature. Dt = internal desired temperature.

6/95

HEAT CALCULATION

Thermal management for electrical control panels

To ventilate
Ventilation Using a fan to circulate air within the enclosure can even out the temperature and prevent hot spots which could be harmful to certain components. Forced ventilation HIMEL fans are designed to remove large quantities of heat generated by electrical control panel components. This signicantly increases component longevity, thus ensuring the durability and correct operation of the installation. The fans, which are easy to install and maintain, as well as economical, are an effective solution to the problem of rising temperatures in electrical control panels. Due to their IP degree of protection, they can be used both in industrial environments and in the tertiary sector.

To cool
Air/air exchangers HIMEL air-air exchangers combine performance and simplicity: the movement of hot air from the enclosure and cool air from the surrounding environment by means of two fans circulating on either side of sealed divider walls prevents dust and humidity from penetrating the enclosure. Warm air from the panel heats these walls, which are then cooled by the colder external air. The heat transfer always takes place from the warmer to the cooler area. For this reason, these devices can only be used if the ambient temperature is at least 5C lower than the required internal temperature of the enclosure. The aluminium exchange battery is at the heart of the system. This element can be cleaned as it is easily removed. In addition, the continuous operation of an internal fan prevents hot spots in the electrical control panel. The temperature is regulated by switching the external circuit fan on and off.

Undesired effects on the components installed in poorly-cooled environments.

6/96

HEAT CALCULATION

Thermal management for electrical control panels

To cool
Air/water exchangers The operating principle of HIMEL air/water exchangers is similar to that of the air/air exchangers: the cool external air is replaced by cold water supplied by the piping of the installation itself on the industrial site. Due to this uid exchange, much larger quantities of heat can be removed, and the temperature within the electrical control panel can be adjusted to below that of the ambient air. Temperature within the panel is regulated by modulating the water ow. The water circuit is protected by a supply shut-off device ensuring the safety of your electrical installation.

Cooling units HIMEL cooling units can be used in the most severe environments, where temperatures can reach 55C. These units are particularly suitable when the required temperature of the enclosure must be lower than the ambient temperature, or when large quantities of heat must be removed. As in the case of the exchangers, they do not affect the IP rating of the panel. Due to the lter located at the intake of the external air circuit, they can operate even when the ambient air is very dusty or greasy. This device is easy to replace and ensures that the efciency of the equipment is maintained throughout its entire service life. The cooling units have an enclosure temperature control system and an alarm function which is triggered in the event of a malfunction.

To heat
Resistance heaters There are two reasons to use resistance heaters: c To heat the electrical control enclosure when the ambient temperature is too low for the components to operate correctly. c To prevent water condensation from forming. Condensation can cause short circuits, premature contact oxidation, corrosion of metal parts (particularly those of the enclosure), and it can signicantly reduce the service life of electrical and electronic components. Condensation occurs when the temperature quickly drops below the dew point. This can be prevented by simply maintaining the temperature within the enclosure at a few degrees above the ambient temperature. The design of the HIMEL heaters facilitates natural convection and ensures a both uniform and rapid heating of the enclosure.

6/97

HEAT CALCULATION

Thermal calculation and mounting suggestions

Determining the temperature control equipment


The temperature control calculation consists of comparing the power dissipated by the operating components with the power exchanged spontaneously by the enclosure walls. It enables calculation of the internal temperature in the enclosure without use of a temperature control system and therefore determination of whether or not one should be installed, taking into account the required external and internal temperatures. The following presents a simple method of making such a selection.

Example: OLN Ref.: OLN208/40 Height = 2000 Width = 800 Depth = 400

1 ENCLOSURE CHARACTERISTICS
Formula for calculation of S (m2) Enclosure position Placement as specied by IEC 890 (A) Height Accessible from all sides Placed against a wall. End, in the case of coupling End, in the case of coupling and placed against a wall Intermediate in the case of coupling Intermediate in the case of coupling and placed against a wall Intermediate in the case of coupling and placed against a wall with the upper part covered (B) Width (C) Depth

S = 1.8 A (B+C) + 1.4 B C S = 1.4 B (A+C) + 1.8 C A S = 1.4 C (A+B) + 1.8 B A S = 1.4 A (B+C) + 1.4 B C S = 1.8 3 B 3 A + 1.4 3 B 3 C + C 3 A S = 1.4 B (A+C) + C A S = 1.4 B A + 0.7 B C + C A

Installation type: enclosure placed against a wall. S = 4.13 m2 Assume that the components dissipate 800 W. Pd = 800 W

S=

m2

2 POWER DISSIPATED BY OPERATING COMPONENTS

This is obtained by totalling the power dissipated by each component installed. If the individual values are unknown, use the tables on page which provide average values.
Pd = W

Temperature conditions are as follows: Temax = 35 C Temn = 15 C

3 CHARACTERISTICS OF AMBIENT AIR

Maximum ambient temperature. Minimum ambient temperature. Average relative humidity.


Temax Temn = = C C

Tdmax = 40 C Tdmn = 15 C

4 REQUIRED INTERNAL AVERAGE TEMPERATURES

These are characterised by the type of components and the characteristics of the ambient air. Maximum internal temperature (desired). Minimun internal temperature (desired).
Tdmn Tdmax = = C C

Cooling is required Timax = 70 C Timn = 15 C

5 FINAL ENCLOSURE TEMPERATURE WITHOUT TEMPERATURE CONTROL SYSTEM

Maximum internal temperature Timax = Pd + Temax KS Minimun internal temperature Timin = Temin (voltage-free panel). K = 5.5 W/m2 K for a metal enclosure. K = 3.5 W/m2 K for a polyester enclosure. K = 3.7 W/m2 K for a stainless steel enclosure. K = 12 W/m2 K for an aluminium enclosure.

Timn Timax

= =

C C

6/98

HEAT CALCULATION

Thermal calculation and mounting suggestions

6 DETERMINATION OF THE TYPE OF TEMPERATURE CONTROL SYSTEM AND ITS POWER PSYST
Tdmn < Timn Temperature control system not required, but circulation fan could be installed to even out temperature. Tdmn > Timn Temperature control system required: resistance heater. 1 Permanent switchboard operation Psyst = K S (Tdmn Te mn) Pd 2 Intermittent operation: Psyst = K S (Tdmn Te mn) Tdmax < Timax Temperature control system required: either fan, exchanger or cooling unit. Psis = Pd K S (Tdmax Te max) Psis = 800 5.5 4.13 (40 35) 690 W Tdmax > Timax Temperature control system not required, but a circulation fan could be installed to eliminate hot spots.

Ventilating
Temperature conditions Avoid hot spots. Solution Install circulation fans in the enclosure. Advantages of solution Highly economical maintenance-free solution. Simple installation. Installation IP maintained. Constraints of solution Quantity of heat removed is relatively low.

Cooling
Temperature conditions Solution Oversize the enclosure. Advantages of solution Economical maintenance-free solution. Simple installation. Installation IP maintained. Constraints of solution Quantity of heat removed is relatively low. Increased dimensions.

Final temperature required in the enclosure Ts (max) at least 5 C higher than the maximum ambient temperature Te (max). Td max Te max + 5 C

Install ventilation louvres.

Highly economical maintenance-free solution. Simple installation.

Quantity of heat removed is low, depending on arrangement of components. IP downgraded (dust penetration). Regular lter maintenance. IP slightly downgraded.

Install fresh air inlet fans. Psyst 3.1 m3/h D= (Tsmax-Temax) Use an air/air exchanger. q= Psyst (Tsmax-Temax) wk

Economical maintenance-free solution, simple to install. Quantity of heat removed high. Temperature control possible. Simple installation. Installation IP maintained. Temperature control as standard. Simple maintenance. Simple installation. Enables evacuation of large quantities of heat, even when ambient temperature is high. Installation IP maintain. Temperature regulation.

Regular lter maintenance.

Use a cooling unit. Final temperature required in the enclosure Ts (max) at least 5 C lower than the maximun ambient temperature Te (max). Td max Te max + 5 C Use an air/water exchanger.

Regular lter maintenance. Can not be used above ambient temperature 55 C.

Simple installation. Enables evacuation of large quantities of heat, even when ambient temperature is high. Installation IP maintain. Temperature control as standard. No lter to maintain.

Water circuit required. Water consumption cost if mains supply used.

Heating
Temperature conditions External temperature lower than the minimum temperature admissible by components. Condensation risk. Solution Heating by resistance heater. Advantages of solution Economical, reliable.Temperature in enclosure can be controlled. Economical, reliable, Humidity in enclosure can be controlled. Constraints of solution Energy consumption. Space occupied in enclosure. Energy consumption. Space occupied in enclosure.

Heating by resistance heater to maintain temperature above the dew point temperature.

6/99

ClimaSys: calculation support service PROclima 4.0


PROclima 4.0
We have developed the PROclima programme to facilitate the calculation and selection of temperature control equipment for enclosures containing electrical or electronic equipment. The programme calculates the thermal balance inside the enclosure and recommends the most suitable solution based on the values entered.

Data entry Entry of the data for the installation necessary to calculate the thermal balance. The steps to follow are: 1 Input of the project and customer data. 2 Input of the temperature data. 3 Input of the electrical data of the installation (voltage for selecting the solution and intensity for the calculation of the dissipation in the busbars). 4 Input of the power dissipated by the electrical components inside the enclosure; if the programme is not known, provide the means for its calculation: By entering the type and quantity of the installed components. In the case of manoeuvres during operation, by reading the interior/exterior temperature. 5 Select the enclosure model and the method of installation.

Results 6 Select the control system (fans, exchangers, etc.). 7 View and print the result.

Printing and drawing up of the thermal study report Once the calculation has been made, a report can be printed, which details all the calculation data, the results obtained, as well as the equipment recommended to maintain the internal temperature of the enclosure under the conditions indicated. The report provides the machining template to scale, as well as the dimensions and electrical characteristics of the recommended equipment.

6/100

1 Input the project and customer data (optional).

5 Select the enclosure model


and the method of installation (compulsory).

2 Input the internal and external


temperature data of the enclosures (compulsory).

6 Select the control system (fans,


exchangers, etc.) (compulsory).

3 Input the electrical data of the


installation (compulsory).

4 Input the power dissipated by the


electrical components inside the enclosure (compulsory).

7 View and print the result.

6/101

HEAT CALCULATION

Calculation support software

Calculation and selection assistance software

PROclima software c Calculation and selection programme for temperature control equipment for enclosures containing electrical or electronic equipment. c The programme performs the calculations presented on pages 6/98 and 6/99, as well as the dissipation surface areas, based on the dimensions of the enclosure and its position with respect to the walls. c Available on CD-ROM in two languages: Spanish and English. c Minimum requirements: PC that is IBM PC 486 SX compatible, 33 MHz, with 8 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA graphics card (640 480 pixels). c Recommended requirements: PC that is IBM Pentium 90 MHz compatible, with 16 Mb RAM, 10 Mb free hard drive, CD-ROM drive, monitor and VGA graphics card (800 600 pixels). c Required components: Microsoft DOS version 5.0 or later, Microsoft Windows version 3.1 or later, Microsoft Windows NT version 3.51.944 or later.

Project phases with the PROclima software c General project data. Customer, technical manager, name, place, and date of project. c Selection of enclosure model. Range, dimensions, placement. c Temperature data: v Minimum and maximum temperatures, possible external temperatures. v Minimum and maximum temperatures desired inside the enclosure. v Altitude. v Relative humidity. c Dissipated power assessment. It is theoretically known or can be recreated from a database: v Enter the dissipated power of the components. v And/or select all the electrical and electronic elements installed inside the enclosure to then calculate an approximate value. The thermal balance consists of comparing the energy dissipated by the components of the installation with the energy dissipated spontaneously by the walls of the enclosure. It makes it possible to dene the external temperature of the enclosure without a temperature control element and to justify the installation of equipment. c Selection of the temperature control element. A screen makes it possible to select the control system (fan, exchanger, cooling unit, resistance heaters) to proportion with the programme. After the calculation, the power, specications, and reference numbers of the temperature control element and the respective accessories are needed. The programme provides a project summary that can be printed.

6/102

HEAT CALCULATION

Calculation example

Data
Enclosure characteristics c Dimensions Height: 2000 mm Width: 800 mm Depth: 500 mm c Location: against a wall c Material: enclosure in painted sheet steel c Thermal power dissipated by operating components Pd: 950 W c Environment and temperature data: Maximum temperature expected outside the enclosure Temax: 25 C Minimum temperature expected outside the enclosure Temin: 25 C Minimum temperature dissipated inside the enclosure Temax: 35 C Minimum temperature dissipated outside the enclosure Temin: 25 C Atmosphere characteristics: little pollution with low dust levels

Selection and calculation: The maximum required temperature (Tsmax) inside the enclosure is 10 C higher than the maximum value expected outside (Timax). It is possible to cool the enclosure using ltered ventilation systems. Calculation of the fan required: Usage formulas: Psis = Pd (k S (Tsmax Temax) Flow = f Psis / (Tdmax Temax) Pd: thermal power dissipated by operating components S = 1.4 L (H+P) + 1.8 P H = 4.6 m2. Conforming to standard IEC 890. K = Constant dened by the material used to construct the enclosure K = 5.5 W/m2 C for a painted steel sheet enclosure K = 3.5 W/m2 C for a polyester enclosure K = 3.7 W/m2 C for a stainless steel enclosure For the calculation, it is necessary to know the altitude above sea level of the installation site: Altitude above sea level: 800 m f = Coefcient related to the altitude above sea level (value)

0 to 100 m f = 3.1 100 to 250 m f = 3.2 250 to 500 m f = 3.3

500 to 750 m f = 3.4 750 to 1000 m f = 3.5 ................

In our example: Psis = 950 5.5 4.6 (35 25) = 497 W Flow = 3.5 697/(35 25) = 244 m3/h Selecting from the quick-selection table of fans 1 fan with standard VF300 lter + 1 outlet grille with standard FS615 + lter 1 thermostat TS141F35 They provide a 302 m3/h ow rate The minimum expected exterior temperature is less than the minimum required temperature inside the enclosure. It is necessary to install resistance heaters: Calculation of the resistance necessary: Usage formulas: W = 5.5 4.6 (15 10) = 127 W In our example: W = 5.5 4.6 (15 10) = 127 W Selecting from the quick-selection table of resistance heaters 1 resistance heater Ref. RC150AI + 1 thermostat Ref. TS140F15

6/103

HEAT CALCULATION

Dissipation surface area

Dissipation surface area of the metal enclosures: CRN-CRNG


Against a wall

Installation mode

Accessible on all sides

At one end of a row At one end of a row, against a wall Intermediate in a row Intermediate in a row, against a wall Intermediate in a row, against a wall, closed covered top

Enclosure model CRN / CRNG Surface areas are expressed in m2. A 250 300 300 300 300 300 400 400 400 400 400 500 500 500 500 600 600 600 600 600 600 600 600 600 700 700 800 800 800 800 800 800 1000 1000 1000 1000 1000 1000 1000 1200 1200

Dimensions in mm B 200 250 250 300 300 400 300 300 400 600 600 400 400 400 500 400 400 400 500 500 500 600 600 800 500 500 600 600 600 800 800 1000 600 600 800 800 800 1000 1200 800 1000 C 150 150 200 150 200 200 150 200 200 250 300 150 200 250 250 150 200 250 150 200 250 250 300 300 200 250 200 250 300 200 300 300 250 300 200 250 300 300 300 300 300 0.20 0.27 0.31 0.31 0.35 0.44 0.39 0.44 0.54 0.82 0.90 0.58 0.65 0.73 0.85 0.68 0.76 0.84 0.81 0.90 0.99 1.13 1.22 1.52 1.02 1.12 1.32 1.43 1.55 1.66 1.92 2.29 1.74 1.87 2.02 2.17 2.32 2.76 3.20 2.71 3.23 0.18 0.24 0.28 0.27 0.32 0.39 0.34 0.40 0.48 0.73 0.80 0.50 0.57 0.65 0.75 0.58 0.66 0.75 0.69 0.78 0.87 0.98 1.08 1.33 0.88 0.98 1.13 1.24 1.36 1.41 1.66 1.97 1.50 1.63 1.70 1.85 2.00 2.36 2.72 2.33 2.75

Type of installation conforming to IEC 890

0.18 0.25 0.29 0.29 0.33 0.41 0.36 0.41 0.51 0.78 0.85 0.55 0.61 0.68 0.80 0.64 0.71 0.78 0.77 0.85 0.93 1.07 1.15 1.45 0.97 1.05 1.26 1.35 1.45 1.60 1.82 1.45 1.64 1.75 1.94 2.07 2.20 2.64 3.08 2.57 3.08

0.16 0.22 0.26 0.25 0.29 0.40 0.32 0.36 0.45 0.69 0.76 0.47 0.53 0.60 0.70 0.55 0.62 0.69 0.65 0.73 0.81 0.92 1.01 1.36 0.83 0.91 1.06 1.16 1.26 1.34 1.57 1.36 1.40 1.51 1.62 1.75 1.88 2.24 2.75 2.18 2.60

0.17 0.23 0.27 0.27 0.31 0.39 0.34 0.38 0.48 0.74 0.80 0.52 0.57 0.63 0.75 0.61 0.66 0.72 0.74 0.80 0.87 1.01 1.08 1.38 0.91 0.98 1.19 1.27 1.36 1.54 1.73 1.38 1.54 1.63 1.86 1.97 2.08 2.52 2.96 2.42 2.94

0.15 0.20 0.24 0.23 0.27 0.34 0.29 0.33 0.42 0.65 0.71 0.44 0.49 0.55 0.65 0.51 0.57 0.63 0.62 0.68 0.75 0.86 0.94 1.19 0.77 0.84 1.00 1.08 1.16 1.28 1.47 1.19 1.30 1.39 1.54 1.65 1.76 2.12 2.48 2.04 2.46

0.13 0.18 0.20 0.20 0.23 0.28 0.26 0.29 0.36 0.54 0.58 0.40 0.44 0.48 0.56 0.47 0.51 0.56 0.56 0.61 0.66 0.76 0.81 1.02 0.70 0.75 0.92 0.98 1.04 1.17 1.30 1.02 1.20 1.27 1.43 1.51 1.59 1.91 2.23 1.87 2.25

6/104

HEAT CALCULATION

Dissipation surface area

Dissipation surface area of the metal enclosures: CMO and OLN


Against a wall

Installation mode

Accessible on all sides

At one end of a row At one end of a row, against a wall Intermediate in a row Intermediate in a row, against a wall Intermediate in a row, against a wall, closed covered top

Enclosure reference number A CMO1010/30 CMO128/30 CMO1210/30 CMO1212/40 CMO146/30 CMO146/40 CMO148/30 CMO148/40 CMO1410/40 CMO1412/40 CMO166/30 CMO166/40 CMO168/30 CMO168/40 CMO1610/30 CMO1610/40 CMO1612/30 CMO1612/40 CMO186/30 CMO186/40 CMO188/30 CMO188/40 CMO188/50 CMO188/60 CMO1810/40 CMO1810/50 CMO1812/40 CMO1812/50 CMO1816/40 CMO1816/50 CMO206/30 CMO206/40 CMO208/30 CMO208/40 CMO208/50 CMO208/60 CMO2010/40 CMO2010/50 CMO2012/40 CMO2012/50 CMO2012/60 CMO2016/40 CMO2016/50 CMO2016/60 1000 1200 1200 1200 1400 1400 1400 1400 1400 1400 1600 1600 1600 1600 1600 1600 1600 1600 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000

Dimensions in mm B 1000 800 1000 1200 600 600 800 800 1000 1200 600 600 800 800 1000 1000 1200 1200 600 600 800 800 800 800 1000 1000 1200 1200 1600 1600 600 600 800 800 800 800 1000 1000 1200 1200 1200 1600 1600 1.600 C 300 300 300 400 300 400 300 400 400 400 300 400 300 400 300 400 300 400 300 400 300 400 500 600 400 500 400 500 400 500 300 400 300 400 500 600 400 500 400 500 600 400 500 600 2.76 2.71 3.23 4.13 2.52 2.86 3.11 3.47 4.09 4.70 2.84 3.22 3.50 3.90 4.16 4.95 4.82 5.28 3.17 3.58 3.90 4.34 4.77 5.21 5.10 5.56 5.86 6.35 7.38 7.92 3.49 3.94 4.30 4.77 5.24 5.71 5.60 6.10 6.43 6.96 7.49 8.10 8.68 9.26 2.36 2.33 2.75 3.55 2.18 2.52 2.66 3.02 3.53 4.03 2.46 2.83 2.99 3.39 3.52 3.95 4.06 4.51 2.74 3.14 3.32 3.76 4.20 4.63 4.38 4.84 4.99 5.48 6.22 6.77 3.01 3.46 3.66 4.13 4.60 5.07 4.80 5.30 5.47 6.00 6.53 6.82 7.40 7.98

Type of installation conforming to IEC 890

2.64 2.57 3.08 3.94 2.35 2.63 2.94 3.25 3.86 4.48 2.65 2.96 3.31 3.65 3.97 4.34 4.63 5.02 2.95 3.29 3.68 4.05 4.41 4.78 4.81 5.20 5.57 5.99 7.09 7.56 3.25 3.62 4.06 4.45 4.84 5.23 5.28 5.70 6.11 6.56 7.01 7.78 8.28 8.78

2.36 2.28 2.72 3.55 2.09 2.39 2.59 2.93 3.46 4.00 2.34 2.67 2.90 3.26 3.45 3.86 4.01 4.45 2.59 2.95 3.20 3.60 4.00 4.39 4.25 4.68 4.90 5.36 6.19 6.73 2.84 3.23 3.51 3.94 4.36 4.78 4.64 5.10 5.34 5.84 6.34 6.75 7.32 7.89

2.52 2.42 2.94 3.74 2.18 2.41 2.77 3.02 3.64 4.26 2.46 2.70 3.12 3.39 3.78 4.08 4.44 4.77 2.74 3.00 3.47 3.76 4.05 4.34 4.52 4.84 5.28 5.63 6.80 7.20 3.01 3.30 3.82 4.13 4.44 4.75 4.96 5.30 5.79 6.16 6.53 7.46 7.88 8.30

2.12 2.04 2.46 3.17 1.85 2.07 2.32 2.58 3.08 3.58 2.08 2.32 2.61 2.88 3.14 3.44 3.67 4.00 2.30 2.57 2.89 3.18 3.48 3.77 3.80 4.12 4.42 4.76 5.65 6.05 2.53 2.82 3.18 3.49 3.80 4.11 4.16 4.50 4.83 5.20 5.57 6.18 6.60 7.02

1.91 1.87 2.25 2.83 1.72 1.90 2.16 2.35 2.80 3.25 1.95 2.15 2.44 2.66 2.93 3.16 3.42 3.66 2.18 2.40 2.72 2.96 3.20 3.43 3.52 3.77 4.08 4.34 5.20 5.49 2.41 2.65 3.01 3.26 3.52 3.78 3.88 4.15 4.50 4.78 5.06 5.73 6.04 6.35

6/105

HEAT CALCULATION

Dissipation surface area


Dissipation surface area of the metal enclosures: OLN
Enclosure reference number A OLN126/40 OLN126/60 OLN126/80 OLN128/40 OLN128/60 OLN128/80 OLN146/40 OLN146/60 OLN146/80 OLN148/40 OLN148/60 OLN148/80 OLN166/60 OLN166/80 OLN168/60 OLN168/80 OLN186/40 OLN186/50 OLN186/60 OLN186/80 OLN188/40 OLN188/50 OLN188/60 OLN1810/40 OLN1810/40/2P OLN1810/50 OLN1810/50/2P OLN1810/60 OLN1810/60/2P OLN1812/40/2P OLN1812/50/2P OLN1812/60/2P OLN203/50 OLN203/60 OLN203/80 OLN206/40 OLN206/50 OLN206/60 OLN206/80 OLN208/40 OLN208/50 OLN208/60 OLN208/80 OLN2010/40 OLN2010/40/2P OLN2010/50 OLN2010/50/2P OLN2010/60 OLN2010/60/2P OLN2010/80 OLN2010/80/2P OLN2012/40/2P OLN2012/50/2P OLN2012/60/2P OLN2012/80/2P OLN226/60 OLN226/80 OLN228/60 OLN228/80 OLN2210/60 OLN2210/80 OLN2210/80/2P OLN2212/60/2P OLN2212/80/2P 1200 1200 1200 1200 1200 1200 1400 1400 1400 1400 1400 1400 1600 1600 1600 1600 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2200 2200 2200 2200 2200 2200 2200 2200 2200 B 600 600 600 800 800 800 600 600 600 800 800 800 600 600 800 800 600 600 600 600 800 800 800 1000 1000 1000 1000 1000 1000 1200 1200 1200 300 300 300 600 600 600 600 800 800 800 800 1000 1000 1000 1000 1000 1000 1000 1000 1200 1200 1200 1200 600 600 800 800 1000 1000 1000 1200 1200 C 400 600 800 400 600 800 400 600 800 400 600 800 600 800 600 800 400 500 600 800 400 500 600 400 400 500 500 600 600 400 500 600 500 600 600 400 500 600 800 400 500 600 800 400 400 500 500 600 600 800 800 400 500 600 800 600 800 600 800 600 800 800 600 800 2.50 3.70 3.70 3.04 3.70 4.35 2.86 3.53 4.20 3.47 4.20 4.93 3.96 4.70 4.70 5.50 3.58 3.98 4.39 5.21 4.34 4.77 5.21 5.10 5.10 5.56 5.56 6.02 6.02 5.86 6.35 6.84 3.09 3.49 4.30 3.94 4.38 4.82 5.71 4.77 5.24 5.71 6.66 5.60 5.60 6.10 6.10 6.60 6.60 7.60 7.60 6.43 6.96 7.49 8.54 5.26 6.22 6.22 7.23 7.18 8.25 8.25 8.14 9.26 2.21 2.81 3.41 2.66 3.31 3.97 2.52 3.19 3.86 3.02 3.75 4.48 3.58 4.32 4.19 4.99 3.14 3.55 3.96 4.78 3.76 4.20 4.63 4.38 4.38 4.84 4.84 5.30 5.30 4.99 5.48 5.98 2.85 3.25 4.06 3.46 3.90 4.34 5.23 4.13 4.60 5.07 6.02 4.80 4.80 5.30 5.30 5.80 5.80 6.80 6.80 5.47 6.00 6.53 7.58 4.73 5.69 5.51 6.53 6.30 7.37 7.37 7.08 8.21 2.30 2.81 3.31 2.85 3.41 3.97 2.63 3.19 3.75 3.25 3.86 4.48 3.58 4.19 4.32 4.99 3.29 3.62 3.96 4.69 4.05 4.41 4.78 4.81 4.81 5.20 5.20 5.59 5.59 5.57 5.99 6.41 2.69 3.01 3.66 3.62 3.98 4.34 5.07 4.45 4.84 5.23 6.02 5.28 5.28 5.70 5.70 6.12 6.12 6.96 6.96 6.11 6.56 7.01 7.90 4.73 5.51 5.69 6.53 6.65 7.54 7.54 7.61 8.56 2.02 2.52 3.02 2.46 3.02 3.58 2.30 2.86 3.42 2.80 3.42 4.03 3.19 3.81 3.81 4.48 2.86 3.19 3.53 4.20 3.47 3.84 4.20 4.09 4.09 4.48 4.48 4.87 4.87 4.70 5.12 5.54 2.45 2.77 3.51 3.14 3.50 3.86 4.59 3.81 4.20 4.59 5.38 4.48 4.48 4.90 4.90 5.32 5.32 6.16 6.16 5.15 5.60 6.05 6.94 4.20 4.98 4.98 5.82 5.77 6.66 6.66 6.55 7.50 2.11 2.52 2.93 2.66 3.12 3.58 2.41 2.86 3.30 3.02 3.53 4.03 3.19 3.68 3.94 4.48 3.00 3.26 3.53 4.06 3.76 4.05 4.34 4.52 4.52 4.84 4.84 5.16 5.16 5.28 5.63 5.98 2.29 2.53 3.02 3.30 3.58 3.86 4.43 4.13 4.44 4.7 5.38 4.96 4.96 5.30 5.30 5.64 5.64 6.32 6.32 5.79 6.16 6.53 7.26 4.20 4.81 5.16 5.82 6.12 6.84 6.84 7.08 7.86 1.82 2.23 2.64 2.27 2.74 3.20 2.07 2.52 2.97 2.58 3.08 3.58 2.81 3.30 3.42 3.97 2.57 2.83 3.10 3.62 3.18 3.48 3.77 3.80 3.80 4.12 4.12 4.44 4.44 4.42 4.76 5.11 2.05 2.29 2.78 2.82 3.10 3.38 3.95 3.49 3.80 4.11 4.74 4.16 4.16 4.50 4.50 4.84 4.84 5.52 5.52 4.83 5.20 5.57 6.30 3.67 4.28 4.46 5.12 5.24 5.96 5.96 6.02 6.80 1.66 1.98 2.30 2.05 2.40 2.75 1.90 2.27 2.63 2.35 2.74 3.14 2.56 2.96 3.09 3.52 2.40 2.62 2.84 3.29 2.96 3.20 3.43 3.52 3.52 3.77 3.77 4.02 4.02 4.08 4.34 4.61 1.95 2.17 2.61 2.65 2.89 3.13 3.62 3.26 3.52 3.78 4.29 3.88 3.88 4.15 4.15 4.42 4.42 4.96 4.96 4.50 4.78 5.06 5.63 3.42 3.94 4.12 4.67 4.82 5.40 5.40 5.52 6.13 Dimensions in mm Type of installation conforming to IEC 890

6/106

HEAT CALCULATION

Dissipation surface area of the polyester enclosures: POLYMEL


Type of installation conforming to IEC 890 Enclosure reference number A PLM3025 PLM32 PLM43 PLM54 PLM64 PLM75 PLM86 PLM108 308 310 430 530 647 747 847 1056 B 255 215 330 430 436 536 636 800 C 160 160 200 200 250 300 300 350 0.29 0.26 0.50 0.72 0.95 1.35 1.69 2.46 0.23 0.23 0.45 0.63 0.84 1.19 1.48 2.14 0.26 0.24 0.47 0.68 0.89 1.26 1.59 2.32 0.27 0.21 0.41 0.59 0.77 1.10 1.38 2.00 0.25 0.22 0.43 0.64 0.82 1.17 1.49 2.18 0.22 0.19 0.38 0.55 0.71 1.01 1.28 1.86 0.19 0.17 0.33 0.49 0.63 0.90 1.14 1.67 Dimensions in mm

Dissipation surface area of the polyester enclosures: PLA


Enclosure reference number A PLA553 PLA554 PLA573 PLA574 PLA5103 PLA5104 PLA5123 PLA5124 PLA753 PLA754 PLA773 PLA774 PLA7103 PLA7104 PLA7123 PLA7124 PLA1053 PLA1054 PLA1073 PLA1074 PLA10103 PLA10104 PLA10123 PLA10124 PLA1253 PLA1254 PLA1273 PLA1274 PLA12103 PLA12104 PLA12123 PLA12124 PLA1553 PLA1554 PLA1573 PLA1574 PLA15103 PLA15104 PLA15123 PLA15124 500 500 500 500 500 500 500 500 750 750 750 750 750 750 750 750 1000 1000 1000 1000 1000 1000 1000 1000 1250 1250 1250 1250 1250 1250 1250 1250 1500 1500 1500 1500 1500 1500 1500 1500 Dimensions in mm B 500 500 750 750 1000 1000 1250 1250 500 500 750 750 1000 1000 1250 1250 500 500 750 750 1000 1000 1250 1250 500 500 750 750 1000 1000 1250 1250 500 500 750 750 1000 1000 1250 1250 C 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 320 420 0.96 1.12 1.30 1.49 1.64 1.87 1.97 2.24 1.33 1.54 1.78 2.02 2.23 2.51 2.68 2.99 1.70 1.95 2.26 2.55 2.82 3.14 3.39 3.74 2.07 2.36 2.74 3.07 3.42 3.78 4.09 4.49 2.44 2.78 3.23 3.60 4.01 4.42 4.80 5.24 0.86 1.02 1.15 1.34 1.44 1.67 1.72 1.99 1.18 1.39 1.56 1.80 1.93 2.21 2.30 2.61 1.50 1.75 1.96 2.25 2.42 2.74 2.89 3.24 1.82 2.11 2.37 2.70 2.92 3.28 3.47 3.87 2.14 2.48 2.78 3.15 3.41 3.82 4.05 4.49 0.90 1.04 1.24 1.41 1.57 1.78 1.91 2.15 1.24 1.41 1.68 1.89 2.13 2.38 2.58 2.86 1.57 1.78 2.13 2.38 2.70 2.98 3.26 3.57 1.91 2.15 2.58 2.86 3.26 3.57 3.93 4.28 2.25 2.53 3.03 3.35 3.82 4.17 4.61 4.99 0.86 1.02 1.18 1.39 1.50 1.75 1.82 2.11 1.15 1.34 1.56 1.80 1.96 2.25 2.37 2.70 1.44 1.67 1.93 2.21 2.42 2.74 2.92 3.28 1.72 1.99 2.30 2.61 2.89 3.24 3.47 3.87 2.01 2.31 2.68 3.02 3.35 3.74 4.02 4.45 0.83 0.95 1.17 1.33 1.51 1.70 1.85 2.07 1.14 1.28 1.59 1.77 2.04 2.25 2.49 2.74 1.44 1.61 2.01 2.21 2.57 2.81 3.13 3.41 1.75 1.94 2.42 2.65 3.10 3.36 3.77 4.07 2.05 2.27 2.84 3.10 3.63 3.92 4.42 4.74 0.73 0.85 1.02 1.18 1.31 1.50 1.60 1.82 0.99 1.13 1.36 1.54 1.74 1.95 2.11 2.36 1.24 1.41 1.71 1.91 2.17 2.41 2.63 2.91 1.50 1.69 2.05 2.28 2.60 2.86 3.15 3.45 1.75 1.97 2.39 2.65 3.03 3.32 3.67 3.99 0.62 0.71 0.85 0.96 1.08 1.20 1.32 1.45 0.88 0.99 1.20 1.32 1.51 1.66 1.83 2.00 1.13 1.27 1.54 1.69 1.94 2.11 2.35 2.54 1.39 1.55 1.88 2.06 2.37 2.57 2.87 3.08 1.64 1.83 2.22 2.43 2.80 3.02 3.39 3.62 Type of installation conforming to IEC 890