MOULDED CASE CIRCUIT BREAKERS

DS
.ixed Overload & .ixed Short-circuit

Page

DTH..E
.ixed Overload & .ixed Short-circuit release with High Breaking Capacity Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions

Page

DG

Page

Adjustable Overload & .ixed Short-circuit release with Normal Breaking Capacity 2/11 2/27 2/36 2/46 2/58 Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions 2/12 2/28 2/37 2/47 2/59,2/60

release with Normal Breaking Capacity Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions 2/9,2/10 2/26 2/36 2/45 2/56,2/57

DH
Adjustable Overload & .ixed Short-circuit release with Standard Breaking Capacity Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions

Page

DL
Adjustable Overload & .ixed Short-circuit release with High Breaking Capacity

Page

DTH

Page

Adjustable Overload & .ixed Short-circuit release (Conventional MCCBs) with High Breaking Capacity 2/15 2/30 2/39 2/49 2/63,2/64 Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions 2/16,2/17 2/31 2/40 2/50 2/65,2/66

2/13,2/14 2/29 2/38 2/48 2/61,2/62

Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions

MOULDED CASE CIRCUIT BREAKERS

DX..S

Page

DX..H

Page

DM
Motor protection MCCBs

Page

Adjustable Overload & adjustable Shortcircuit with standard Breaking Capacity 3 & 4 Pole Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions 2/18,2/19 2/32-2/34 2/41 2/51,2/52 2/67-2/71

Adjustable Overload & adjustable Shortcircuit with high Breaking Capacity 3 & 4 Pole Technical Data I-t Characteristic Curves MCCB Ordering Data Accessories Ordering Data Overall Dimensions 2/20-2/22 2/32-2/35 2/42 2/51-2/53 2/67-2/75

Technical Data MCCB Ordering Data Accessories Ordering Data Overall Dimensions Type 2 Co-ordination Chart

2/23 2/43 2/54 2/76,2/77 2/83

DTH Instantaneous
Instantaneous MCCBs Technical Data MCCB Ordering Data Accessories Ordering Data Overall Dimensions

Page

D.
.use Monitoring device

Page

2/24 2/44 2/55 2/78

Technical Data Ordering Data Accessories Ordering Data Overall Dimensions Wiring Diagram

2/25 2/44 2/55 2/79 2/79

MOULDED CASE CIRCUIT BREAKERS

L&T was the first company to introduce Moulded case circuit Breakers (MCCBs) in India. Over the years, it has developed & enhanced the products to growing requirements of market conditions. L&T MCCBs use latest technologies for circuit interruption under faults. These MCCBs comply with standards IS 13947, IEC 60947 and EN 60947-2 and are certified at independent and approved test authorities. L&T offers a wide range of MCCBs with current ratings from 0.63A to 1600A in 3-Pole & 4-Pole versions & breaking capacity from 6kA to 100kA. These MCCBs are available with Thermal-Magnetic as well as with Electronic release (above 125A in DX range). These MCCBs are available in .ixed or Drawout versions. They are also available in utilisation category A or B. L&T MCCBs are complemented with a wide variety of internal and external accessories.

APPLICATIONS
Distribution .eeders Ideally suited for incoming and outgoing feeder circuits on distribution boards. Transformers DG Sets AP.C Systems DC Loads UPS Motors Provide effective protection to distribution transformers as outgoing breakers on the LT side. Used for protection and control of diesel generating sets against overloads and short circuits. Suitable for controlling LT capacitors for power factor corrections. Suitable for both AC as well as DC applications. Hence find application in protecting rectifier panels. Used for UPS & Electronic equipment protection. Specially designed MCCBs for Motor back-up protection provide Type-2 co-ordination (as per IEC 60947) in conjunction with suitably rated contactors and relays. .urnaces Suitable for high frequency systems upto 400Hz and can be used for control of high frequency furnaces. Also used in induction furnaces along with semiconductor fuses.

WORKING PRINCIPLE
L&Ts new range of MCCBs operate on Current limiting principle. This helps in very fast clearance (less than 10 mS) of short-circuit faults. This is achieved by 1. Quick opening of main contacts. 2. Guiding the arc rapidly away from the contacts into the arcing chamber. 3. Quick quenching of arc by using effective arc quenching devices. As a result peak short circuit current (Ip) is limited to cut-off current (I c). Thus, I2t let through (proportional to the shaded area) is considerably reduced, resulting in lower thermal stresses in downstream equipments and connecting cables.

2/1

MOULDED CASE CIRCUIT BREAKERS

PRODUCT HIGHLIGHTS
1. Operating mechanism is quick-make, quick-break and trip free. It is independent of manual speed of operation. Contacts cannot be teased into position, nor can the breaker be held closed under fault conditions. 2. Clear indication of ON, O.. & TRIP position. 3. Suitable for both AC & DC applications. 4. Terminals suitable for both copper & aluminium terminations. 5. Push to trip facility to verify healthiness of mechanism. 6. Wide range of site fittable accessories. 7. Low let through energy. 8. No load line bias in new range of MCCBs. 9. Rotary operating mechanism has door interlock facility with an option of defeating interlock by an authorized person. 10. Housing is made of heat resistant insulating material. 11. Silver alloy contacts have long electrical life. The mechanism is so designed there is no arcing on the current carrying part of the contact. The strong wipe action of the contact system keeps the contact surface clear of oxide films.

MOUNTING POSITION
L&Ts new range of MCCBs can be mounted up to 900 in any direction.

MCCBs .OR MOTOR BACK-UP PROTECTION


MCCBs are increasingly being used in motor application as a back- up protection device due to following advantages: Low down time Reduced running cost No risking of single phasing Availability of various accessories

TYPICAL MOTOR .EEDER


A typical motor protection scheme comprises a starter (contractor and thermal overload relay) and a short circuit protective device(SCPD) e.g.MCCB. Thermal overload relay provides close protection to the motor against single phasing and moderate overloads like stalling etc. Protection against higher overcurrents, beyond capability of the starter including short circuit faults is offered by MCCB. It is necessary to have proper discrimination between thermal overload relay and SCPD for any effective protection scheme. Type DM MCCBS are hence designed with instantaneous release to ensure proper discrimination.

.USE MONITORING DEVICE


L&Ts range of MCCBs also includes the .use Monitoring Device type D., designed to monitor the operation of fuse. In the motor feeders, where Switch Disconnector .use units are used for motor backup protection, there is every possibility of only one of the three fuses blowing due to a fault, resulting in single phasing. This can be avoided by using .use Monitoring Device along with Switch Disconnector .use units of any fuse ratings (refer page 2/79 for connection diagram).

2/2

ACCESSORIES
INTERNAL

SHUNT RELEASE
The shunt release provides remote tripping of the circuit breaker. The coil of shunt release is designed for short time as well as continuous operation (DX range). The operation voltage is : 85% to 110% of the rated voltage in AC 75% to 125% of the rated voltage in DC Shunt release coil is short time rated, micro-switch is provided in the release to cut off the supply. Once the MCCB trips, this prevents burning of coil even if the supply to shunt coil is continuously fed.

UNDER VOLTAGE RELEASE


The under voltage release is used for protecting the installation against low voltage situation. The under voltage release is designed to operate when the voltage drops below a tripping threshold. This can also be used for remote tripping & electrical interlocking purpose. The tripping threshold is : 35% to 70% of rated in AC 35% to 70% of rated in DC Circuit breaker closing is possible only if the voltage exceeds 85% of the rated voltage.

AUXILIARY CONTACT BLOCK


The auxiliary contact block is used for remote signaling and control purposes. This consists of one or more than one potential free change-over contacts. It indicates the circuit breaker status- whether open or closed.

TRIP ALARM CONTACT


The trip alarm contact gives tripping indication once the MCCB trips. The potential free change- over contacts can be used for indication or for control circuit.

Note : .or ordering information, refer pages 2/45 - 2/55 2/3

ACCESSORIES
EXTERNAL
.OR DX RANGE
ANNUNCIATION UNIT Annunciation unit indicates the differential remote and local operating states like - Tripping by Overload release - Tripping be Short-circuit release - Early-alarm in the event that the Overload release setting is about to be exceeded. Annunciation unit has 1NO+1NC. RESIDUAL CURRENT OPERATED RELAYS These are factory fitted with adjustable rated fault current and delay time. MECHANICAL INTERLOCK .or mechanical interlocking of Two or Three MCCBs with Toggle or Rotary drive in the same distribution panel. PARALLELING MECHANISM .or simultaneous operation of two MCCBs mounted side by side, using a Rotary drive. SIDE WALL OPERATOR This is to be used for actuating the Breaker from the side of the control panel or for changing the Rotary movement by 90o WITHDRAWABLE UNIT Three position Withdrawable units are available for 3 and 4 PoleMCCBs (250A and above). PLUG-IN ADAPTORS 3 pole DX range of MCCBs (upto 250A) are also available with plug-in adaptor modules.

ELECTRICAL & MECHANICAL INTERLOCK

PARALLELING MECHANISM

ADAPTOR TERMINAL WITH SHROUD / SPREADER LINKS WITH BARRIERS


Adaptor terminals / Spreader links can be connected to basic MCCBs to facilitate termination of higher size of cables / links. The barrier is made of material with high dielectric strength. It is used to ensure the electrical clearance between breaker terminals. It also prevents troubles caused by contact of conductive material to the terminals. Shrouds are used on both the sides of MCCB to provide additional safety and are made of superior insulating material with good mechanical & electrical properties. The shrouds are designed for click-fit fixing & thus do not need any fixing hardware. Shroud prevents accidental contact to bare terminals.

ADAPTOR TERMINAL

SHROUD

Note : .or ordering information, refer pages 2/45 - 2/55 2/4

ACCESSORIES
EXTERNAL

ROTARY OPERATING MECHANISM


The circuit breaker has a toggle handle operating mechanism, which also serves as swtiching position indicator ON, O.., TRIP . But when the circuit breaker is installed in switchgear cubicles or distribution boards, it requires to be operated outside of the switchgear cubicles or distribution boards. The mechanism is designed for direct attachment to the MCCB and transforms the toggle handle movement into a rotation. It facilitates operation of MCCB when the panel door is closed. ITS .EATURES Easy operation Door interlock mechanism. It doesnt allow the circuit breaker to be ON when the door of switchgear cubicles or distribution boards is open thus prevents the operator from an unsafe condition. Door interlock defeat facility. This enables only authorized personnel to open the door with MCCB in ON condition for the purpose of inspection.

.OR DX RANGE REMOTE OPERATOR (MOTORISED)


.or remote ON and O.. of circuit breakers. Local switching by hand also possible.

Note : .or ordering information, refer pages 2/45 - 2/55 2/5

ACCESSORIES
EXTERNAL
EARTH .AULT MODULES (Type G.1, G.2, G.11)
Protection against earth faults Built-in CBCT solid state design (G.11 to be used with external C.T.)
G.1

10 50% adjustable current setting 100 / 200 mS selectable trip time delay Suitable for both 3 phase 3 wire & 3 phase 4 wire7 systems. Built in test facility. Potential free NO contact to trip MCCB through shunt trip. Manual reset for positive fault acknowledgment

G.2

(for Technical / Dimensional Details, refer page 2/80 and 2/81)

G.11

S. S. ENCLOSURE
Enclosure is made of CRCA material with superior quality paint for better adherence and to enhance weather resistance. MCCB mounted in Enclosure is ideally suited to be used as fuseless mains. .eatures of Enclosure Isolable neutral Earthing terminal Positive indication of breaker position Door lock and additional lock on enclosure prevents accidental switching of MCCB. (for Dimensional Details, refer page 2/82)

Note : .or ordering information, refer pages 2/45 - 2/55 2/6

ACCESSORIES RANGE

2
Auxiliary Contacts Standard Early make General Trip alarm Contact alarm Separate contact alarm Under voltage release Non-delayed Off-delayed Shunt release Without early make aux. Contact With early make aux. Contact Remote operator Rotary operating mechanism Paralleling mechanism Mechanical interlock Castell lock Earth-fault module Earth-leakage module Plug-in module Withdrawable module Adaptor terminals Spreader terminals Enclosure

DS

DTH..E

DG

DH

DL

DTH

DX..S

DX..H

DM

D.

l l -

l l -

l l -

l l -

l l -

l l -

l l l l l

l l l l l

l l -

l l -

l -

l -

l -

l -

l -

l -

l l

l l

l -

l l l l l

l l l -

l l l l l

l l l l l l

l l l l l -

l l l -

l l l l l l l l l l l -

l l l l l l l l l l l -

l l l l l -

l -

l Available; Not Available Note : Accessories mounting / location as per page 2/45 to 2/55 2/7

ACCESSORIES .OR MCCB

UV RELEASE

TRIP ALARM CONTACT

AUXILIARY CONTACT BLOCK

ROTARY OPERATING MECHANISM

SHUNT RELEASE

Note : Except DX Range 2/8

TECHNICAL DATA - DS

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V AC V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Hz V C

DS 100

DS 125

DS 160

100 8 415 250 50/60 690 -5 to +55 III/3 17

125 8 415 250 50/60 690 -5 to +55 III/3 17

160 8 415 250 50/60 690 -5 to +55 III/3 32

Rated ultimate S.C. breaking capacity - Icu at 415V ac Rated Service S.C. breaking capacity - Ics at 415V ac Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism 2/9 (1NO+1NC) y y y y y (1NO+1NC) y y y y y (1NO+1NC) y y y y y kg mm2 mm Thermal-Magnetic .ixed 9*In 1.7 50 16 Thermal-Magnetic .ixed 9*In 1.7 70 22 Thermal-Magnetic .ixed 8*In 1.7 95 22 kA 50% A 50% A As per standard IS 13947-2 / IEC 60947-2 50% A kA 10 10 16

TECHNICAL DATA - DS

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V AC V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Hz V C

DS 200

DS 250

DS 400

200 8 415 250 50/60 690 -5 to +55 III/3 32

250 8 415 250 50/60 690 -5 to +55 III/3 52.5

400 8 415 250 50/60 690 -5 to +55 III/3 52.5

Rated ultimate S.C. breaking capacity - Icu at 415V ac Rated Service S.C. breaking capacity - Ics at 415V ac Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism (1NO+1NC) y y y y y (2NO+2NC) y y y y y (2NO+2NC) y y y y y 2/10 kg mm2 mm Thermal-Magnetic .ixed 6*In 2.4 150 30 Thermal-Magnetic .ixed 6*In 5 300 40 Thermal-Magnetic .ixed 6*In 5 300 40 kA 50% A 50% A As per standard IS 13947-2 / IEC 60947-2 50% A kA 16 25 25

TECHNICAL DATA - DTH...E

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Hz V C

DTH 200E

DTH 250E

DTH 400E

DTH 630E

DTH 800E

200 415 250 50/60 600 -5 to +55 III/3

250 8 415 250 50/60 600 -5 to +55 III/3 105

400 8 415 250 50/60 600 -5 to +55 III/3 105

630 8 415 250 50/60 600 -5 to +55 III/3 105

800 8 415 250 50/60 600 -5 to +55 III/3 105

Rated ultimate S.C. breaking capacity - Icu at 660V ac at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac Rated Service S.C. breaking capacity - Ics at 415V ac kA 20 70 A Ops. Ops. 8000 2000 50% 20 100 A 8000 2000 50% 20 160 A 8000 1200 50% 20 240 A 8000 1200 50% 20 240 A 8000 1200 kA kA kA kA kA kA 35 10 25 35 50 50 60 10 25 35 50 50 60 10 25 35 50 50 60 10 25 35 50 50 60

DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Utilisation category Mechanical life (As per standard) Electrical life (As per standard) Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Earth fault module Rotary operating mechanism 2/11 kg mm
2

kVAR

Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic Thermal-Magnetic .ixed 8*In 3 185 36 .ixed 3-8*In 10 2*240 40 (Max. 15 thk.) .ixed 3-8*In 10 2*240 .ixed 3-8*In 10 2*240 .ixed 3-8*In 10 2*240 40 (Max. 15 thk.)

mm

40 (Max. 15 thk.) 40 (Max. 15 thk.)

1 NO + 1 NC y y y y

2 NO + 2 NC y y y y

2 NO + 2 NC y y y y

2 NO + 2 NC y y y y

2 NO + 2 NC y y y y

TECHNICAL DATA - DG

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V AC V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated ultimate S.C. breaking capacity - Icu at 415V ac Rated Service S.C. breaking capacity - Ics at 415V ac Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism kg mm2 mm kA kA Hz V C

DG 125

DG 200

DG 250

DG 400

125 8 415 250 50/60 690 -5 to +55 III/3

200 8 415 250 50/60 690 -5 to +55 III/3

250 8 415 250 50/60 690 -5 to +55 III/3

400 8 415 250 50/60 690 -5 to +55 III/3

10

16

25

25

75% A

75% A

75% A

75% A

As per standard IS 13947-2 / IEC 60947-2

Thermal-Magnetic 80-100% 4*In 1.8 70 22

Thermal-Magnetic 80-100% 4*In 2.4 150 30

Thermal-Magnetic 80-100% 4*In 5 300 40

Thermal-Magnetic 80-100% 4*In 5 300 40

(1NO+1NC) y y y y y

(1NO+1NC) y y y y y

(2NO+2NC) y y y y y

(2NO+2NC) y y y y y 2/12

TECHNICAL DATA - DH

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue

DH 100

DH 125

DH 160

DH 200

A kV V V DC

100 8 415 250 50/60 690 -5 to +55 III/3

125 8 415 250 50/60 690 -5 to +55 III/3 73.5 7 18 25 35 35 60 75% 10 50 A

160 8 415 250 50/60 690 -5 to +55 III/3 73.5 7 18 25 35 35 60 75% 10 70 A

200 8 415 250 50/60 690 -5 to +55 III/3 73.5 7 18 25 35 35 60 50% 10 70 A

.requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm

Hz V C

kA

52.5 5 12 18 25 25 50 100% 10 35 A

Rated ultimate S.C. breaking capacity - Icu at 660V ac kA at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac kA kA kA kA kA

Rated Service S.C. breaking capacity - Ics at 415V ac kA DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism 2/13 kg mm2 mm kVAR

As per standard IS 13947-2 / IEC 60947-2 Thermal-Magnetic 80-100% 9*In 1.7 50 16 (1NO+1NC) y y y y y Thermal-Magnetic 80-100% 9*In 1.7 50 16 (1NO+1NC) y y y y y Thermal-Magnetic 80-100% 8*In 1.7 95 22 (1NO+1NC) y y y y y Thermal-Magnetic 80-100% 6*In 2.4 150 30 (1NO+1NC) y y y y y

TECHNICAL DATA - DH

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue

DH 250

DH 400

DH 630

A kV V V DC

250 8 415 250 50/60 690 -5 to +55 III/3

400 8 415 250 50/60 690 -5 to +55 III/3 73.5 7 18 25 35 35 60 75% 20 160 A As per standard IS 13947-2 / IEC 60947-2

630 8 415 250 50/60 690 -5 to +55 III/3 73.5 7 18 25 35 35 60 75% 20 160 A

.requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm

Hz V C

kA

73.5 7 18 25 35 35 60 75% 20 100 A

Rated ultimate S.C. breaking capacity - Icu at 660V ac kA at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac kA kA kA kA kA

Rated Service S.C. breaking capacity - Ics at 415V ac kA DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism kg mm2 mm kVAR

Thermal-Magnetic 80-100% 6*In 5.5 300 40 (2NO+2NC) y y y y y

Thermal-Magnetic 80-100% 6*In 5.5 300 40 (2NO+2NC) y y y y y

Thermal-Magnetic 80-100% 6*In 6.5 400 2x40 (2NO+2NC) y y y y y 2/14

TECHNICAL DATA - DL

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm at 660V ac at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac Rated Service S.C. breaking capacity - Ics at 415V ac kA kA kA kA kA kA kA kA Hz V C

DL 100

DL 160

DL 250

DL 400

100 8 415 250 50/60 690 -5 to +55 III/3 105 10 25 35 50 50 65 100% 20 50 A

160 8 415 250 50/60 690 -5 to +55 III/3 105 10 25 35 50 50 50 100% 25 70 A

250 8 415 250 50/60 690 -5 to +55 III/3 105 10 25 35 50 50 65 100% 25 100 A

400 8 415

50/60 690 -5 to +55 III/3 105 10 25 35 50 50 65 100% 25 160 A

Rated ultimate S.C. breaking capacity - Icu

DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism 2/15 kg mm
2

kVAR

Ops.

As per standard IS 13947-2 / IEC 60947-2 Thermal-Magnetic 80-100% 9*In 1.7 50 16 Thermal-Magnetic 80-100% 8*In 1.8 95 22 Thermal-Magnetic 80-100% 6 In 5 300 40 Thermal-Magnetic 80-100% 6 In 5 300 40

mm

(1NO+1NC) y y y y y

(1NO+1NC) y y y y y

(2NO+2NC) y y y y y

(2NO+2NC) y y y y y

TECHNICAL DATA - DTH

Type Designation Rated Uninterrupted current at 40o C - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated ultimate S.C. breaking capacity - P1 at 415V ac kA Hz V C

DTH 100

DTH 200

100 415 250 50/60 600 -5 to +55 III/3

200 415 250 50/60 600 -5 to +55 III/3

10 5 25 30000 4500 Thermal-Magnetic 70-100% 700 A

35 20 70 8000 2000 Thermal-Magnetic 70-100% 8*In 3 185 36

DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism kg mm2 mm kVAR Ops. Ops.

1.35 70 22.5

y y

1 NO + 1 NC y y y y y

2/16

TECHNICAL DATA - DTH

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue A kV V V DC .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm at 660V ac at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac Rated Service S.C. breaking capacity - Ics at 415V ac kA kA kA kA kA kA kA kA Hz V C

DTH 250

DTH 400

DTH 630

DTH 800

250 8 415 250 50/60 600 -5 to +55 III/3 105 10 25 35 50 50 60 50% 20 100 A

400 8 415 250 50/60 600 -5 to +55 III/3 105 10 25 35 50 50 60 50% 20 160 A 8000 1200 Thermal-Magnetic 70-100% 3-8*In 10 2*240 40 (Max. 15 thk.)

630 8 415 250 50/60 600 -5 to +55 III/3 105 10 25 35 50 50 60 50% 20 240 A 8000 1200 Thermal-Magnetic 70-100% 3-8*In 10 2*240 40 (Max. 15 thk.)

800 8 415 250 50/60 600 -5 to +55 III/3 105 10 25 35 50 50 60 50% 20 240 A 8000 1200 Thermal-Magnetic 70-100% 3-8*In 10 2*240 40 (Max. 15 thk.)

Rated ultimate S.C. breaking capacity - Icu

DC Breaking capacity at 250 V, L/R <= 15mS kA Capacitor rating at 415 V, 50 Hz Utilisation category Mechanical life Electrical life Release Type Overload release setting Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism 2/17 kg mm2 mm Ops. Ops. kVAR

8000 1200 Thermal-Magnetic 70-100% 3-8*In 10 2*240 40 (Max. 15 thk.)

2 NO + 2 NC y y y y y

2 NO + 2 NC y y y y y

2 NO + 2 NC y y y y y

2 NO + 2 NC y y y y y

TECHNICAL DATA - DX..S (3/4 POLE)

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Rated ultimate S.C. breaking capacity - Icu at 690V ac kA at 500V ac at 415V ac at 230V ac Rated Service S.C. breaking capacity - Ics (of Icu) DC Breaking capacity at 440 V Utilisation category Rated short-time withstand current Icw (1 Sec)kA Mechanical life Electrical life (AC3, 400V) Release Type Overload release setting Short Circuit release setting Mechanical Shock resistance Weight (3 - Pole) (4 - Pole) Accessories Auxiliary contacts Shunt release Under voltage release Trip indicating auxiliary contacts Earth fault module Rotary operating mechanism Residual-current protection module Remote operator Withdrawable unit Plug-in module Mechanical interlock Paralleling mechanism Load monitoring g kg kg Ops. Ops. kA kA kA kA kA

DX 100S

DX 125S

DX 160S

DX 200S

A kV V V DC Hz V C

100 8 415 440 50/60 690 -5 to +55 III/3 94.5 6 12 35 45 100% 20 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

125 8 415 440 50/60 690 -5 to +55 III/3 94.5 6 12 35 45 100% 20 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

160 8 415 440 50/60 690 -5 to +55 III/3 94.5 6 12 35 45 100% 20 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

200 8 415 440 50/60 690 -5 to +55 III/3 94.5 6 12 35 45 100% 20 A 20000 3500 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

2/18

TECHNICAL DATA - DX..S (3/4 POLE)

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui OperatingTemperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Rated ultimate S.C. breaking capacity - Icu at 690V ac kA at 500V ac at 415V ac at 230V ac Rated Service S.C. breaking capacity - Ics (of Icu) DC Breaking capacity at 440 V Utilisation category Rated short-time withstand current Icw (1 Sec) kA Mechanical life Electrical life (AC3, 400V) Release Type Overload release setting Short Circuit release setting Mechanical Shock resistance Weight (3 - Pole) (4 - Pole) Accessories Auxiliary contacts Shunt release Under voltage release Trip indicating auxiliary contacts Earth fault module Rotary operating mechanism Residual-current protection module Remote operator Withdrawable unit Mechanical interlock Paralleling mechanism Load monitoring 2/19 g kg kg Ops. Ops. kA kA kA kA kA

DX 250S

DX 400S

DX 630S

A kV V V DC Hz V C

250 8 415 440 50/60 690 -5 to +55 III/3 94.5 6 12 35 45 100% 20 A 20000 3500 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y

400 8 415 50/60 690 -5 to +55 III/3 220 25 42 65 100 50% A/B 8 20000 1250 Electronic 50-100% 2-12*In 20 9.1 11.9 y y y y y y y y y y y

630 8 415 50/60 690 -5 to +55 III/3 220 25 42 65 100 50% A/B 8 20000 1250 Electronic 50-100% 2-12*In 20 9.1 11.9 y y y y y y y y y y y

TECHNICAL DATA - DX..H (3/4 POLE)

Type Designation Rated Uninterrupted current at 40C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Rated ultimate S.C. breaking capacity - Icu at 690V ac kA at 500V ac at 415V ac at 230V ac Rated Service S.C. breaking capacity - Ics (of Icu) DC Breaking capacity at 440 V Utilisation category Rated short-time withstand current Icw (1 Sec) kA Mechanical life Electrical life (AC3, 400V) Release Type Overload release setting Short Circuit release setting Mechanical Shock resistance Weight (3 - Pole) (4 - Pole) Accessories Auxiliary contacts Shunt release Under voltage release Trip indicating auxiliary contacts Earth fault module Rotary operating mechanism Residual-current protection module Remote operator Withdrawable unit Plug-in module Mechanical interlock Paralleling mechanism Load monitoring g kg kg Ops. Ops. kA kA kA kA kA A kV V V DC Hz V C

DX 100H

DX 125H

DX 160H

DX 200H

100 8 415 440 50/60 690 -5 to +55 III/3 220 8 20 65 100 75% 25 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

125 8 415 440 50/60 690 -5 to +55 III/3 550 8 20 65 100 75% 25 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

160 8 415 440 50/60 690 -5 to +55 III/3 220 8 20 65 100 75% 25 A 20000 6000 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

200 8 415 440 50/60 690 -5 to +55 III/3 220 8 20 65 100 75% 25 A 20000 3500 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y y

2/20

TECHNICAL DATA - DX..H (3/4 POLE)

Type Designation Rated Uninterrupted current at 40C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA Rated ultimate S.C. breaking capacity - Icu at 690V ac kA at 500V ac at 415V ac at 230V ac Rated Service S.C. breaking capacity - Ics (of Icu) DC Breaking capacity at 440 V Utilisation category Rated short-time withstand current Icw (1 Sec) kA Mechanical life Electrical life (AC3, 400V) Release Type Overload release setting Short Circuit release setting Mechanical Shock resistance Weight (3 - Pole) (4 - Pole) Accessories Auxiliary contacts Shunt release Under voltage release Trip indicating auxiliary contacts Earth fault module Rotary operating mechanism Residual-current protection module Remote operator Withdrawable unit Mechanical interlock Paralleling mechanism Load monitoring 2/21 g kg kg Ops. Ops. kA kA kA kA kA

DX 250H

DX 400H

DX 630H

DX 800H

A kV V V DC Hz V C

250 8 415 440 50/60 690 -5 to +55 III/3 220 8 20 65 100 75% 25 A 20000 3500 Thermal-Magnetic 80-100% 6-12*In 20 1.7 1.7 y y y y y y y y y y

400 8 415 50/60 690 -5 to +55 III/3 440 30 65 100 200 50% A/B 8 20000 5000 Electronic 50-100% 2-12*In 20 9.1 11.9 y y y y y y y y y y y

630 8 415 50/60 690 -5 to +55 III/3 440 30 65 100 200 50% A 8 20000 5000 Electronic 50-100% 2-12*In 20 9.1 11.9 y y y y y y y y y y y

800 8 415 50/60 690 -5 to +55 III/3 275 25 45 65 100 75% B 15 (0.3 S) 2500 500 (AC1) Electronic 50-100% 2-12*In 20 20.4 26.4 y y y y y y y y y y

TECHNICAL DATA - DX..H (3/4 POLE)

Type Designation Rated Uninterrupted current at 40C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm at 690V ac at 500V ac at 415V ac at 230V ac Rated Service S.C. breaking capacity - Ics (of Icu) Utilisation category Rated short-time withstand current Icw (1 Sec) kA Mechanical life Electrical life (AC3, 400V) Release Type Overload release setting Short Circuit release setting Mechanical Shock resistance Weight (3 - Pole) (4 - Pole) Accessories Auxiliary contacts Shunt release Under voltage release Trip indicating auxiliary contacts Earth fault module Rotary operating mechanism Residual-current protection module Remote operator Withdrawable unit Side wall operator Mechanical interlock Load monitoring g kg kg Ops. Ops. kA kA kA kA kA kA A kV V Hz V C

DX 1000H

DX 1250H

DX 1600H

1000 8 415 50/60 690 -5 to +55 III/3 275 25 45 65 100 75% B 15 (0.3 S) 2500 500 (AC1) Electronic 50-100% 2-12*In 20 20.4 26.4

1250 8 415 50/60 690 -5 to +55 III/3 275 25 45 65 100 75% B 15 (0.3 S) 2500 500 (AC1) Electronic 50-100% 2-12*In 20 20.4 26.4

1600 8 415 50/60 690 -5 to +55 III/3 275 45 65 85 125 75% B 20 (0.3 S) 2500 500 (AC1) Electronic 50-100% 2-12*In 20 20.4 26.4

Rated ultimate S.C. breaking capacity - Icu

y y y y y y y y y y

y y y y y y y y y y

y y y y y y y y y y 2/22

TECHNICAL DATA - DM

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated Short-circuit making capacity - Icm kA A kV V Hz V C

DM 16

DM 100

DM 160

DM 250

DM 400

16 8 415 50/60 690 -5 to +55 III/3 105

70 8 415 50/60 690 -5 to +55 III/3 105

160 8 415 50/60 690 -5 to +55 III/3 105

250 8 415 50/60 690 -5 to +55 III/3 105

400 8 415 50/60 690 -5 to +55 III/3 105

Rated ultimate S.C. breaking capacity - Icu at 660V ac at 550V ac at 500V ac at 415V ac at 380V ac at 240V ac Rated Service S.C. breaking capacity - Ics at 415V ac Utilisation category Mechanical life Electrical life Release Type Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Rotary operating mechanism 1 NO + 1 NC y y y 1 NO + 1 NC y y y y 1 NO + 1 NC y y y y 2 NO + 2 NC y y y y 2 NO + 2 NC y y y y kg mm2 mm Magnetic 12*In 1 10 Magnetic 12*In 1.65 50 16 Magnetic 12*In 4.8 185 36 Magnetic 12*In 5.5 300 40 Magnetic 12*In 5.5 300 40 kA 100% A 100% A 100% A 100% A 100% A kA kA kA kA kA kA 10 25 35 50 50 85 10 25 35 50 50 85 10 25 35 50 50 85 10 25 35 50 50 85 10 25 35 50 50 85

As per standard IS 13947-2 / IEC 60947-2

2/23

TECHNICAL DATA - DTH 800 INST.

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated ultimate S.C. breaking capacity - Icu at 415V ac Rated Service S.C. breaking capacity - Ics at 415V ac (of Icu) Utilisation category Mechanical life Electrical life Release Type Short Circuit release setting (+/- 20%) Weight Terminal capacity Cables Links Accessories Auxiliary contacts Shunt release Under voltage release Trip alarm contacts Earth fault module Rotary operating mechanism kg mm2 mm Ops. Ops. kA kA A kV V Hz V C

DTH 800 INST.

800 8 415 50/60 600 -5 to +55 III/3

50

50% A 8000 1200 Magnetic 360A, 550A, 850A, 1050A 10 2*240 40 (Max. 15 thk.)

y y y y y y

2/24

TECHNICAL DATA - D.

Type Designation Rated Uninterrupted current at 40o C. - Ith (AC/DC) Rated impulse withstand voltage - Uimp Rated operational voltage - Ue .requency Rated insulation voltage - Ui Operating Temperature Overvoltage category / pollution degree Rated ultimate S.C. breaking capacity - Icu at 415V ac Magnetic Threshold Mechanical life Electrical life Overload release setting (.ixed) Weight Terminal capacity Without lugs With lugs Accessories Auxiliary contact Shunt release Auxiliary contact Trip alarm contacts kA A Ops. Ops. A kg mm2 mm2 A kV V Hz V C

D.

1 8 415 50/60 600 -5 to +55 III/3

50 2 10000 6000 1 0.65 4 16

1 CO, 5A-250V y y y

2/25

I-t CHARACTERISTIC CURVES


MCCB - TYPE DS

DS 100

DS 125/160

DS 200
Note: Short Circuit tripping values indicated as multiple of rated current

DS 250/400

2/26

I-t CHARACTERISTIC CURVES


MCCB - TYPE DTH...E

DTH 200E

DTH 250E

DTH 400E

DTH 630E

DTH 800E

Note: Short Circuit tripping values indicated as multiple of rated current 2/27

I-t CHARACTERISTIC CURVES


MCCB - TYPE DG

DG 125

DG 160

DG 200
Note: Short Circuit tripping values indicated as multiple of rated current

DG 250/400

2/28

I-t CHARACTERISTIC CURVES


MCCB - TYPE DH

DH 100/125

DH 160

DH 200
Note: Short Circuit tripping values indicated as multiple of rated current 2/29

DH 250/400/630

I-t CHARACTERISTIC CURVES


MCCB - TYPE DL

DL 100

DL 160

DL 250/400
Note: Short Circuit tripping values indicated as multiple of rated current 2/30

I-t CHARACTERISTIC CURVES


MCCB - TYPE DTH

DTH 100

DTH 200

DTH 250

DTH 400

DTH 630

DTH 800

Note: Short Circuit tripping values indicated as multiple of rated current 2/31

I-t CHARACTERISTIC CURVES


DX 100-250 S/H (3/4 POLE)

Note: Short Circuit tripping values indicated as multiple of rated current 2/32

I-t CHARACTERISTIC CURVES


DX 400 S/H (3/4 POLE)

2
 # #

Note: Short Circuit tripping values indicated as multiple of rated current 2/33

I-t CHARACTERISTIC CURVES


DX 630 S/H (3/4 POLE)

Note: Short Circuit tripping values indicated as multiple of rated current 2/34

I-t CHARACTERISTIC CURVES


DX 800-1600 H (3/4 POLE)

DX 800 H

DX 1000 H

DX 1250 H
Note: Short Circuit tripping values indicated as multiple of rated current 2/35

DX 1600 H

ORDERING DATA - DS RANGE

MCCB

Rating (A)

Current Rating (A) 16 20 25 32 40 50 63 80 100

Breaking Capacity, Icu(kA) 10 10 10 10 10 10 10 10 10 10 16 16 25 25 25

Overload Setting (A) 16 20 25 32 40 50 63 80 100 125 160 200 250 320 400

Short-Circuit Setting 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 6*In 6*In 6*In 6*In

Std. Pack 12 12 12 12 12 12 12 12 12 12 12 12 1 1 1

Catalogue No. Ordering Suffix SL97917 SL97918 SL97919 SL97920 SL97921 SL97922 SL97923 SL97924 SL97925 SL97929 SL97930 SL97931 SL94541 SL94542 SL94543 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DS 100

100

DS 125 DS 160 DS 200 DS 250 DS 400

125 160 200 250 320 400

125 160 200 250 320 400

ORDERING DATA - DTH...E RANGE

MCCB

Rating (A)

Current Rating (A) 200 250 400 630 800

Breaking Capacity, Icu(kA) 35 50 50 50 50

Overload Setting (A) 200 250 400 630 800

Short-Circuit Setting 8*In 3-8*In 3-8*In 3-8*In 3-8*In

Std. Pack 1 1 1 1 1

Catalogue No. Ordering Suffix ST 30513 ST 30543 ST 30545 ST 30514 ST 30546 OOOO OOOO OOOO OOOO OOOO 2/36

DTH 200E DTH 250E DTH 400E DTH 630E DTH 800E

200 250 400 630 800

ORDERING DATA - DG RANGE

MCCB

Rating (A)

Current Rating (A) 16 20 25 32 40 50 63 80 100 125

Breaking Capacity, Icu(kA) 10 10 10 10 10 10 10 10 10 10 16 16 25 25 25

Overload Setting (A) 12 - 16 16 - 20 20 - 25 25 - 32 32 - 40 40 - 50 50 - 63 63 - 80 80 - 100 100 - 125 128 - 160 160 - 200 200 - 250 250 - 320 320 - 400

Short-Circuit Setting 6*In 6*In 6*In 6*In 6*In 6*In 4*In 4*In 4*In 4*In 4*In 4*In 4*In 4*In 4*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix SL97941 SL97942 SL97943 SL97944 SL97945 SL97946 SL97947 SL97948 SL97949 SL97950 SL97951 SL97953 SL97957 SL97958 SL97959 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DG 125

125

DG 200

200

160 200

DG 250 DG 400

250 400

250 320 400

2/37

ORDERING DATA - DH RANGE

MCCB

Rating (A)

Current Rating (A) 16 20 25 32 40 50 63 80 100

Breaking Capacity, Icu(kA) 25 25 25 25 25 25 25 25 25 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35

Overload Setting (A) 12 - 16 16 - 20 20 - 25 25 - 32 32 - 40 40 - 50 50 - 63 63 - 80 80 - 100 12 - 16 16 - 20 20 - 25 25 - 32 32 - 40 40 - 50 50 - 63 63 - 80 80 - 100 100 - 125 128 - 160 160 - 200 160 - 200 200 - 250 250 - 320 320 - 400 400 - 500 500 - 630

Short-Circuit Setting 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 8*In 6*In 6*In 6*In 6*In 6*In 6*In 6*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix SL 97201 SL 97202 SL 97203 SL 97204 SL 97205 SL 97206 SL 97207 SL 97208 SL 97209 SL 98556 SL 98557 SL 98558 SL 98559 SL 98560 SL 98561 SL 98562 SL 98563 SL 98564 SL 98555 SL 98566 SL 97869 SL 97881 SL 97882 SL 97883 SL 97884 SL 94531 SL 94532 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO 2/38

DH 100

100

DH 125

125

16 20 25 32 40 50 63 80 100 125

DH 160 DH 200 DH 250

160 200 250

160 200 200 250

DH 400

400

320 400

DH 630

630

500 630

ORDERING DATA - DL RANGE

MCCB

Rating (A)

Current Rating (A) 16 20 25 32 40 50 63 80 100

Breaking Capacity, Icu(kA) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Overload Setting (A) 12 - 16 16 - 20 20 - 25 25 - 32 32 - 40 40 - 50 50 - 63 63 - 80 80 - 100 80 - 100 100 - 125 128 - 160 160 - 200 200 - 250 250 - 320 320 - 400

Short-Circuit Setting 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 9*In 8*In 8*In 8*In 6*In 6*In 6*In 6*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix SL 97801 SL 97802 SL 97803 SL 97804 SL 97805 SL 97806 SL 97807 SL 97808 SL 97809 SL97128 SL 97129 SL 97130 SL 97541 SL 97542 SL 97543 SL 97544 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DL 100

100

DL 160

160

100 125 160

DL 250

250

200 250

DL 400

400

320 400

2/39

ORDERING DATA - DTH RANGE

MCCB

Rating (A)

Current Rating (A) 16 20 25 32 40 50 63 80 100

Breaking Capacity, Icu(kA) 6 6 6 6 6 6 8 10 10 35 35 35 35 50 50 50 50 50 50 50

Overload Setting (A) 12 - 16 16 - 20 20 - 25 25 - 32 30 - 40 38 - 50 48 - 63 60 - 80 70 -100 70 -100 90 -125 120 -160 140 -200 125 - 175 175 - 250 225 - 320 280 - 400 360 - 500 460 - 630 600 - 800

Short-Circuit Setting 700 700 700 700 700 700 700 700 700 8*In 8*In 8*In 8*In 3-8*In 3-8*In 3-8*In 3-8*In 3-8*In 3-8*In 3-8*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix SL 94473 SL 94474 SL 94475 SL 94476 SL 94477 SL 94478 SL 94479 SL 94480 SL 94481 SL 94512 SL 94513 SL 94514 SL 94515 SL 94466 SL 94467 SL 94468 SL 94469 SL 94470 SL 94471 SL 94472 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DTH 100

100

DTH 200

200

100 125 160 200

DTH 250

250

175 250

DTH 400

400

320 400

DTH 630

630

500 630

DTH 800

800

800

ORDERING DATA - DTH 100 4-POLE


MCCB Rating (A) DTH 100 100 Current Rating (A) 100 100 100 100 100 100 100 100 100 Breaking Capacity, Icu(kA) 6 6 6 6 6 6 8 10 10 Overload Setting (A) 12 - 16 16 - 20 20 - 25 25 - 32 30 - 40 38 - 50 48 - 63 60 - 80 70 -100 Short-Circuit Setting 700 700 700 700 700 700 700 700 700 Std. Pack 1 1 1 1 1 1 1 1 1 SL 94525 SL 94525 SL 94525 SL 94525 SL 94525 SL 94525 SL 94525 SL 94526 SL 94525 Catalogue No. Ordering Suffix OOBO OOCO OODO OOEO OO.O OOGO OOHO OOOO OOOO 2/40

ORDERING DATA - DX..S (3 POLE)

MCCB

Rating (A)

Utilisation Category A

Current

Breaking

Overload Setting (A) 25 - 40 40 - 63 63 - 80 80 - 100 80 - 125 125 - 160 160 - 200 200 - 250 125 - 250 200 - 400 300 - 630

Short-Circuit Setting 9.5*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-10*In 2-12*In 2-12*In 2-12*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix ST 31038 ST 31039 ST 31040 ST 31041 ST 31042 ST 31043 ST 31044 ST 31045 ST 31058 ST 31059 ST 31060 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Rating (A) Capacity, Icu(kA) 40 63 80 100 35 35 35 35 35 35 35 35 65 65 65

DX 100S

100

DX 125S DX 160S DX 200S DX 250S DX 400S

125 160 200 250 400

A A A A A / B* A / B*

125 160 200 250 250 400 630

DX 630S

630

A / B*

ORDERING DATA - DX..S (4 POLE)

MCCB

Rating (A)

Utilisation Category A

Current

Breaking

Overload Setting (A) 25 - 40 40 - 63 63 - 80 80 - 100 80 - 125 125 - 160 160 - 200 200 - 250 125 - 250 200 - 400 300 - 630

Short-Circuit Setting 9.5*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-10*In 2-12*In 2-12*In 2-12*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix ST 31001 ST 31002 ST 31003 ST 31004 ST 31005 ST 31006 ST 31007 ST 31008 ST 31019 ST 31021 ST 31023 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Rating (A) Capacity, Icu(kA) 40 63 80 100 35 35 35 35 35 35 35 35 65 65 65

DX 100S

100

DX 125S DX 160S DX 200S DX 250S DX 400S

125 160 200 250 400

A A A A A / B* A / B*

125 160 200 250 250 400 630

DX 630S * To be specified 2/41

630

A / B*

ORDERING DATA - DX..H (3 POLE)

MCCB

Rating (A)

Utilisation Category A

Current

Breaking

Overload Setting (A) 25 - 40 40 - 63 63 - 80 80 - 100 80 - 125 125 - 160 160 - 200 200 - 250 125 - 250 200 - 400 300 - 630 400 - 800 500 - 1000 630 - 1250 800 - 1600

Short-Circuit Setting 9.5*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-10*In 2-12*In 2-12*In 2-12*In 3-12*In 3-12*In 3-12*In 3-12*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix ST 31046 ST 31047 ST 31048 ST 31049 ST 31050 ST 31051 ST 31052 OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Rating (A) Capacity, Icu(kA) 40 63 80 100 65 65 65 65 65 65 65 65 100 100 100 85 85 85 100

DX 100H

100

DX 125H DX 160H DX 200H DX 250H DX 400H DX 630H DX 800H DX 1000H DX 1250H DX 1600H

125 160 200 250 400 630 800 1000 1250 1600

A A A A A A B B B B

125 160 200 250 250 400 630 800 1000 1250 1600

ORDERING DATA - DX..H (4 POLE)

MCCB

Rating (A)

Utilisation Category A

Current

Breaking

Overload Setting (A) 25 - 40 40 - 63 63 - 80 80 - 100 80 - 125 125 - 160 160 - 200 200 - 250 125 - 250 200 - 400 300 - 630 400 - 800 500 - 1000 630 - 1250 800 - 1600

Short-Circuit Setting 9.5*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-12*In 6-10*In 2-12*In 2-12*In 2-12*In 3-12*In 3-12*In 3-12*In 3-12*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix ST 31011 ST 31012 ST 31013 ST 31014 ST 31015 ST 31016 ST 31017 ST 31018 ST 31020 ST 31022 ST 31024 ST 31025 ST 31026 ST 31027 ST 31028 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO 2/42

Rating (A) Capacity, Icu(kA) 40 63 80 100 65 65 65 65 65 65 65 65 100 100 100 85 85 85 100

DX 100H

100

DX 125H DX 160H DX 200H DX 250H DX 400H DX 630H DX 800H DX 1000H DX 1250H DX 1600H

125 160 200 250 400 630 800 1000 1250 1600

A A A A A A B B B B

125 160 200 250 250 400 630 800 1000 1250 1600

ORDERING DATA - DM RANGE

MCCB

Rating (A)

Current Rating (A) 0.63 1.0 1.6 2.5 4.0 5.0 6.3 7.5 10 12 16

Breaking Capacity, Icu(kA) 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50

Overload Setting (A) 0.63 1.0 1.6 2.5 4.0 5.0 6.3 7.5 10 12 16 16 25 30 35 50 60 70 100 120 160 200 230 250 275 325 350 400

Short-Circuit Setting 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In 12*In

Std. Pack 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Catalogue No. Ordering Suffix SL 97581 SL 97582 SL 97583 SL 97584 SL 97585 SL 97586 SL 97587 SL 97588 SL 97589 SL 97590 SL 97591 SL 97811 SL 97812 SL 97816 SL 97813 SL 97814 SL 97817 SL 97815 SL 97123 SL 97703 SL 97124 SL 97551 SL 97552 SL 97553 SL 97554 SL 97555 SL 97556 SL 97557 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DM 16

16

DM 100

100

16 25 30 35 50 60 70

DM 160

160

100 120 160

DM 250

250

200 230 250

DM 400

400

275 325 350 400

2/43

ORDERING DATA - DTH INST. RANGE

MCCB

Rating (A)

Current Rating (A) 800 800 800 800

Breaking Capacity, Icu(kA) 50 50 50 50

Overload Setting (A) -

Short-Circuit Setting 360 550 850 1050

Std. Pack 1 1 1 1

Catalogue No. Ordering Suffix SB 95052 SB 95053 SB 95054 SB 95055 OOOO OOOO OOOO OOOO

DTH 800

800

ORDERING DATA - D.
.USE MONITORING DEVICE
MCCB Thermal Rating (A) D. 1 Breaking Capacity, Icu(kA) 50 Magnetic Threshold (A) 2 1 SL 97020 Std. Pack Catalogue No. Ordering Suffix OOOO

2/44

ACCESSORIES - ORDERING DATA


TYPE DS

Accessory

Coil Voltage / Type

Location

Std. Pack

Catalogue No.

Ordering Suffix

DS 100/125/160/200
Shunt Release 110/240/415 V AC 24 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block 1 NO + 1 NC L L L L R L Trip Alarm contact Rotary operating handle Earth .ault module2) S S Enclosure1) G.1 R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 SL 97299 SL 97299 SL 97610 SL 97611 SL 97296 SL 97297 SL 97298 SL 97301 ST 27745 ST 29967 OMOO O4OO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DS 250/400
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block Trip Alarm contact Spreader Links with Barrier * Rotary operating handle Earth .ault module 2) Note : 2 NO + 2 NC ROM G.2 R/L R/L L L L/R R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 SL 97575 SL 97576 SL 97579 SL 97580 SL 97573 SL 97574 Std. Kit SL 97562 ST 27746 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * Along with DS400 1) Dimension on page 2/82 2) Dimension and wiring diagram on pages 2/80 & 2/81

2/45

ACCESSORIES - ORDERING DATA


TYPE DTH..E
Accessory Coil Voltage / Type Location Std. Pack Catalogue No. Ordering Suffix

DTH 200E
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC 110 V AC Under Voltage Release* 415 V AC 240 V AC 110 V AC Auxiliary contact Block 1 NO + 1 NC R L Rotary operating mechanism Earth .ault module1) ROM G.2 Ext. Ext. L R 1 1 1 1 1 1 1 1 1 1 SL 94331 SL 94331 SL 94331 SL 94332 SL 94332 SL 94332 SL 94330 SL 94329 SL 94336 ST 27746 ODOO OBOO OAOO DOOO BOOO AOOO OOOO OOOO OOOO OOOO

DTH 250E / 400E / 630E / 800E


Shunt Release 110 V AC 415 V AC/220 V DC 24 V DC 240 V AC/110 V DC Under Voltage Release 110 V AC 240 V AC 415 V AC Auxiliary contact Block Rotary operating mechanism Earth .ault module1) 1 NO + 1 NC ROM G.11 R R L R L L L L/R 1 1 1 1 1 1 1 1 1 1 SL 98523 SL 98526 SL 98531 SL 98534 SL 98543 SL 98545 SL 98548 SL 94217 SL 94337 ST 28594 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Note :

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * 24 V, 48 V, 110 V & 220 V DC are also available on request 1) Dimension and wiring diagram on pages 2/80 & 2/81 2/46

ACCESSORIES - ORDERING DATA


TYPE DG

Accessory

Coil Voltage / Type

Location

Std. Pack

Catalogue No.

Ordering Suffix

DG 125/200
Shunt Release 110/240/415 V AC 24 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block 1 NO + 1 NC L L L L R L Trip Alarm contact Rotary operating handle Spreader Links with Barrier Earth .ault module 2) S S Enclosure 1) G.1 R Ext. Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 1 SL 97299 SL 97299 SL 97610 SL 97611 SL 97296 SL 97297 SL 97298 SL 97301 Std. Kit ST 27745 ST 29967 OOOO OOOO OMOO O4OO OOOO OOOO OOOO OOOO OOOO OOOO

DG 250/400
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block Trip Alarm contact Spreader Links with Barrier * Rotary operating mechanism Earth .ault module 2) Note : 2 NO + 2 NC ROM G.2 R/L R/L L L L/R R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 SL 97575 SL 97576 SL 97579 SL 97580 SL 97573 SL 97574 Std. Kit SL 97562 ST 27746 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * To be used with DS 125 & above 1) Dimension on page 2/82 2) Dimension and wiring diagram on pages 2/80 & 2/81

2/47

ACCESSORIES - ORDERING DATA


TYPE DH
Accessory Coil Voltage / Type Location Std. Pack Catalogue No. Ordering Suffix

DH 100/125/160/200
Shunt Release 110/240/415 V AC 24 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block 1 NO + 1 NC L L L L R L Trip Alarm contact Rotary operating mechanism Adaptor terminal with shroud Terminal shroud Spreader Links with Barrier Earth .ault module 2) S S Enclosure 1) G.1 ROM R Ext. Ext. Ext. Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 1 1 1 SL 97299 SL 97299 SL 97610 SL 97611 SL 97296 SL 97297 SL 97298 SL 97301 ST 27745 ST 29967 OMOO O4OO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DH 250/400/630
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC Under Voltage Release 415 V AC 240 V AC Auxiliary contact Block Trip Alarm contact Adaptor terminal (3) with shroud (1) - 1 Set Terminal shroud Spreader Links with Barrier * Rotary operating mechanism Earth .ault module 2) 1 NO + 1 NC ROM G.2 G.11# Note : Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * To be used with DS 125 & above # To be used with DH 630 1) Dimension on page 2/82 2) Dimension and wiring diagram on pages 2/80 & 2/81 2/48 R/L R/L L L L/R R Ext. Ext. Ext. Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 1 1 SL 97575 SL 97576 SL 97579 SL 97580 SL 97573 SL 97574 SL 97564 SL 97563 Std. Kit SL 97562 ST 27746 ST28594 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

ACCESSORIES - ORDERING DATA


TYPE DL

Accessory

Coil Voltage / Type

Location

Std. Pack

Catalogue No.

Ordering Suffix

DL 100
Shunt Release Under Voltage Release Auxiliary contact Block Trip Alarm contact Rotary operating handle Earth .ault module 2) S S Enclosure 1) G.1 110/240/415 V AC 24 V DC 415 V AC 240 V AC 1 NO + 1 NC L L L L R L R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 SL 97299 SL 97299 SL 97610 SL 97611 SL 97296 SL 97297 SL 97298 SL 97301 ST 27745 ST 29967 OMOO O4OO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

DL 160
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC 110 V AC Under Voltage Release* 415 V AC 240 V AC 110 V AC Auxiliary contact Block Trip Alarm contact # Rotary operating mechanism Earth .ault module 2) 1 NO + 1 NC ROM G.2 R L R Ext. Ext. L R 1 1 1 1 1 1 1 1 1 1 1 SL 94331 SL 94331 SL 94331 SL 94332 SL 94332 SL 94332 SL 94330 SL 94329 SL 94336 ST 27746 ODOO OBOO OAOO DOOO BOOO AOOO OOOO OOOO OOOO OOOO

.actory assembled

DL 250/400
Shunt Release Under Voltage Release Auxiliary contact Block Trip Alarm contact Spreader Links with Barrier Rotary operating mechanism Earth .ault module 2) Note : 415 V AC/220 V DC 240 V AC/110 V DC 415 V AC 240 V AC 1 NO + 1 NC ROM G.2 R/L R/L L L L/R R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 SL 97575 SL 97576 SL 97579 SL 97580 SL 97573 SL 97574 Std. Kit SL 97562 ST 27746 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * 24 V, 48 V, 110 V & 220 V DC are also available on request # On request 1) Dimension on page 2/82 2) Dimension and wiring diagram on pages 2/80 & 2/81

2/49

ACCESSORIES - ORDERING DATA


TYPE DTH
Accessory Coil Voltage / Type Location Std. Pack Catalogue No. Ordering Suffix

DTH 100
Rotary operating handle Earth .ault module 1) G.1 Ext. Ext. 1 1 SL 94286 ST 27745 OOOO OOOO

DTH 200
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC 110 V AC Under Voltage Release* 415 V AC 240 V AC 110 V AC Auxiliary contact Block 2 NO + 2 NC R L Trip Alarm contact # Rotary operating mechanism Earth .ault module 1) ROM G.2 R Ext. Ext. L R 1 1 1 1 1 1 1 1 1 1 1 SL 94331 SL 94331 SL 94331 SL 94332 SL 94332 SL 94332 SL 94330 SL 94329 ODOO OBOO OAOO DOOO BOOO AOOO OOOO OOOO

.actory assembled SL 94336 ST 27746 OOOO OOOO

DTH 250/400/630/800
Shunt Release 110 V AC 415 V AC/220 V DC 24 V DC 240 V AC/110 V DC Under Voltage Release 110 V AC 240 V AC 415 V AC Auxiliary contact Block Trip Alarm contact # Rotary operating mechanism Earth .ault module 1) Note : 1 NO + 1 NC ROM G.11 R R L R L L L L/R R 1 1 1 1 1 1 1 1 1 1 1 SL 98523 SL 98526 SL 98531 SL 98534 SL 98543 SL 98545 SL 98548 SL 94217 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

.actory assembled SL 94337 ST 28594 OOOO OOOO

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * 24 V, 48 V, 110 V & 220 V DC are also available on request # On request. 1) Dimension and wiring diagram on pages 2/80 & 2/81 2/50

ACCESSORIES - ORDERING DATA


TYPE DX (100/125/160/200/250)S / DX(100/125/160/200/250)H ... (3/4 POLE)

Accessory

Type

Std. Pack

Catalgoue No.

Ordering Suffix OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Shunt Release

415 V AC/DC 240 V AC/DC 110 V AC/DC 48 V AC/DC 24 V AC/DC With early-make auxiliary contacts 440 V AC 415 V AC 240 V AC Off-delayed With early-make auxiliary contacts

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

ST 33007 ST 33006 ST 33005 ST 33004 ST 33003 ST 33010 ST 33009 ST 33008 ST 33001 ST 33002 ST 33021 ST 33016 ST 33017 ST 33018 ST 33013

Under Voltage Release

Auxiliary contact Block

NO NC Early make Trip indicating

Door coupling rotary handle Toggle to rotary convert Extension shaft Remote operator Residual-current protection module Paralleling mechanism Mechanical interlock Plug-in adaptor Side wall operator

ROM

240 V AC

1 1 1 1 1 1

Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)

2/51

ACCESSORIES - ORDERING DATA


TYPE DX (400/630)S / DX(400/630)H ... (3/4 POLE)
Accessory Type Std. Pack Catalgoue No. Ordering Suffix OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO 2/52

Time selectivity block

125-250A 200-400A 300-630A 125-250A (1000-6000) 200-400A (1000-9000) 300-630A (1000-9000)

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

ST 33053 ST 33054 ST 33055 ST 33056 ST 33057 ST 33058 ST 33034 ST 33035 ST 33036 ST 33037 ST 33038 ST 33039 ST 33030 ST 33045 ST 33046 ST 33047 ST 33048 ST 33042 ST 33043 ST 33049 ST 33050 ST 33051 ST 33031 ST 33040 ST 33064 ST 33063 ST 33061 ST 33062 ST 33044

Shunt Release

110 V AC/DC 240 V AC / DC 415 V AC / DC

Under Voltage Release

240 V AC 415 V AC 440 V AC Off-delayed (AC)

Auxiliary contact Block

2NO + 2 NC Early make General trip indicating

Annunciation unit Door coupling rotary handle Toggle to rotary convert Extension shaft Rotary handle Remote operator Residual-current protection module Paralleling mechanism Mechanical interlock

ROM

Used with Rotary drive 240 V AC 415 V AC 240 V AC 415 V AC

1 1 1 1 1 1

.or 2 MCCBs .or 2 MCCBs with Remote operator .or 3 MCCBs 3 & 4 Pole with Toggle or Rotary drive

1 1 1 1

Annunciation unit Earth-fault Release (.itted to Breaker) Residual-current operated relays (AC) 3 Pole 4 Pole 3 Pole (230 V) 3 Pole (415 V) 4 Pole (230 V) 4 Pole (415 V) Withdrawable unit Withdrawable unit auxiliary contact Toggle switch interlock 3 Pole 4 Pole .or connection indication To connect Earth-fault release .or upto 3 Pad locks

1 1 1 1 1 1 1 1 1 1 1

Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)

ACCESSORIES - ORDERING DATA


TYPE DX (800/1000/1250/1600)H ... (3/4 POLE)

Accessory

Type

Std. Pack

Catalgoue No.

Ordering Suffix

Shunt Release

200 - 480 V AC 110 V AC

1 1 1 1 1 1 1 1 1 1 1

Under Voltage Release Under Voltage Release Auxiliary contact Block Trip type indicator Load monitoring Door coupling rotary handle Toggle to rotary convert Extension shaft Remote operator Mechanical interlock Earth-fault Release (.itted to Breaker) Withdrawable unit

200 - 480 V AC 110 V AC Off-delayed (AC) 2NO + 2 NC 240 V AC 200 - 240 V AC ROM

230 V AC

1 1 1

800 A 1250 A 1600 A

1 1 1

Note: ROM consists of (Door coupling rotary handle + Toggle to rotary convert + Extension shaft)

2/53

ACCESSORIES - ORDERING DATA


TYPE DM
Accessory Coil Voltage / Type Location Std. Pack Catalogue No. Ordering Suffix

DM 16
Shunt Release Auxiliary contact Block Trip Alarm contact Rotary operating mechanism 110/240/415 V AC 1 NO + 1 NC ROM L R L R Ext. 1 1 1 1 1 SL 97042 SL 97023 SL 97025 SL 97037 SL 97044 OOOO OOOO OOOO OOOO OOOO

DM 100
Shunt Release Under Voltage Release Auxiliary contact Block Trip Alarm contact Rotary operating mechanism Spreader Links with Barrier Earth .ault module G.1 110/240/415 V AC 24 V DC 415 V AC 240 V AC 1 NO + 1 NC ROM L L L L R L R Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 ST 27745 OOOO SL 97299 SL 97299 SL 97610 SL 97611 SL 97296 SL 97297 SL 97298 SL 97301 OMOO O4OO OOOO OOOO OOOO OOOO OOOO OOOO

DM 160
Shunt Release 415 V AC/220 V DC 240 V AC/110 V DC 110 V AC 415 V AC 240 V AC 110 V AC 1 NO + 1 NC ROH G.2 R 1 1 1 1 1 1 1 1 1 1 1 SL 94331 SL 94331 SL 94331 SL 94332 SL 94332 SL 94332 SL 94330 SL 94329 SL 94336 ST 27746 ODOO OBOO OAOO DOOO BOOO AOOO OOOO OOOO OOOO OOOO

Under Voltage Release*

Auxiliary contact Block Trip Alarm contact # Rotary operating handle Earth .ault module

R L R Ext. Ext.

.actory assembled

DM 250/400
Shunt Release Under Voltage Release Auxiliary contact Block Trip Alarm contact Adaptor terminal (3) with shroud (1) - 1 Set Terminal shroud Spreader Links with Barrier Rotary operating handle Earth .ault module Note : 415 V AC/220 V DC 240 V AC/110 V DC 415 V AC 240 V AC 1 NO + 1 NC ROH G.2 R/L R/L L L L/R R Ext. Ext. Ext. Ext. Ext. 1 1 1 1 1 1 1 1 1 1 1 SL 97575 SL 97576 SL 97579 SL 97580 SL 97573 SL 97574 SL 97564 SL 97563 Std. Kit SL 97562 ST 27746 OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * 24 V, 48 V, 110 V & 220 V DC are also available on request # On request. 2/54

ACCESSORIES - ORDERING DATA


TYPE DTH 800 INST.

Accessory

Coil Voltage / Type 110 V AC 415 V AC/220 V DC 24 V DC 240 V AC/110 V DC

Location

Std. Pack

Catalogue No.

Ordering Suffix OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO OOOO

Shunt Release

R R L R L L L L/R Ext.

1 1 1 1 1 1 1 1 1

SL 98523 SL 98526 SL 98531 SL 98534 SL 98543 SL 98545 SL 98548 SL 94217 SL 94337

Under Voltage Release *

110 V AC 240 V AC 415 V AC

Auxiliary contact Block Rotary operating mechanism Note :

1 NO + 1 NC ROM

Any two internal accessories can be fitted simultaneously in a breaker R To be mounted on right side L To be mounted on left side L/R Can be mounted on either side Ext. External * 24 V, 48 V, 110 V & 220 V DC are also available on request

ACCESSORIES - ORDERING DATA


TYPE D.
Accessory Coil Voltage / Type 110/240/415 V AC 1 NO + 1 NC Location Std. Pack Catalogue No. Ordering Suffix OOOO OOOO OOOO

Shunt Release Trip Alarm contact Auxiliary contact Block Note : Any one can be used. R To be mounted on right side

R R R

1 1 1

SL 97042 SL 97037 SL 97023

2/55

OVERALL DIMENSIONS
MCCB - TYPE DS

MOUNTING AND DOOR CUTOUT DETAILS

MOUNTING AND DOOR CUTOUT DETAILS

DS 100

DS 125/160/200

MOUNTING AND DOOR CUTOUT DETAILS

DS 250/400
Note: All dimensions are in mm. 2/56

OVERALL DIMENSIONS
DIMENSIONAL DETAILS O. ROTARY OPERATING MECHANISM - TYPE DS

DS 100/125/160/200

DS 250/400
Note: All dimensions are in mm. 2/57

OVERALL DIMENSIONS
MCCB - TYPE DTH..E

MOUNTING AND DOOR CUTOUT DETAILS

DTH 200E

DTH 250/400/630/800 E

ROTARY OPERATING MECHANISM .OR TYPE DTH..E

DTH 200E
Note: All dimensions are in mm.

DTH 250/400/630/800 E
2/58

OVERALL DIMENSIONS
MCCB - TYPE DG

MOUNTING AND DOOR CUTOUT DETAILS

DG 125/200

MOUNTING AND DOOR CUTOUT DETAILS

DG 250/400
Note: All dimensions are in mm. 2/59

OVERALL DIMENSIONS
DIMENSIONAL DETAILS O. ROTARY OPERATING MECHANISM - TYPE DG

DG 125/200

DG 250/400

EXPLODED VIEW O. ROTARY OPERATING MECHANISM

Note: All dimensions are in mm. 2/60

OVERALL DIMENSIONS
MCCB - TYPE DH

MOUNTING AND DOOR CUTOUT DETAILS

MOUNTING AND DOOR CUTOUT DETAILS

MOUNTING AND DOOR CUTOUT DETAILS

DH 100

DH 125/160

DH 200

MOUNTING AND DOOR CUTOUT DETAILS

DH 250
Note: All dimensions are in mm. 2/61

DH 400

DH 630

OVERALL DIMENSIONS
DIMENSIONAL DETAILS O. ROTARY OPERATING MECHANISM - TYPE DH

DH 100/125/160/200

DH 250/400

DH 630
Note: All dimensions are in mm. 2/62

OVERALL DIMENSIONS
MCCB - TYPE DL

DL 100

DL 160/200

DL 250/400
Note: All dimensions are in mm. 2/63

OVERALL DIMENSIONS
DIMENSIONAL DETAILS O. ROTARY OPERATING MECHANISM - TYPE DL

DL 100

DL 160

DL 250/400
Note: All dimensions are in mm. 2/64

OVERALL DIMENSIONS
MCCB - TYPE DTH

DTH 100 3 POLE / 4 POLE

DTH 200

MOUNTING AND DOOR CUTOUT DETAILS

DTH 250/400/630.800
Note: All dimensions are in mm. 2/65

OVERALL DIMENSIONS
ROTARY OPERATING MECHANISM .OR TYPE DTH

PANEL CUT OUT

DTH 100

DTH 200

DTH 250/400/630/800
Note: All dimensions are in mm. 2/66

OVERALL DIMENSIONS
DX 100-250 S/H ... 3/4 POLE

ROTARY DRIVE / ROTARY HANDLE .OR SUR.ACE MOUNTING BREAKERS


Note: All dimensions are in mm. 2/67

OVERALL DIMENSIONS
DX 100-250 S/H... 3/4 POLE

EXTENSION SHA.T

DOOR COUPLING ROTARY HANDLE .OR REAR MOUNTING SWITCHES

REMOTE OPERATOR
Note: All dimensions are in mm. 2/68

OVERALL DIMENSIONS
DX 160 S/H, DX 200-250 S/H

PLUG-IN ADAPTER
Note: All dimensions are in mm. 2/69

OVERALL DIMENSIONS
DX 400-630 S/H (3/4 POLE)

DIMENSIONAL DETAILS O. ROTARY OPERATING MECHANISM

ROTARY DRIVE

DOOR COUPLING ROTARY HANDLE


Note: All dimensions are in mm. 2/70

OVERALL DIMENSIONS
DX 400-630 S/H ... 3/4 POLE

REMOTE OPERATOR

PUSH-BUTTONS .OR REMOTE OPERATION ENCLOSED BREAKERS

WITHDRAWABLE UNIT
Note: All dimensions are in mm. 2/71

OVERALL DIMENSIONS
DX 800-1250 H ... 3/4 POLE

DX 1600 H ... 3/4 POLE

Note: All dimensions are in mm. 2/72

OVERALL DIMENSIONS
DX...H 800-1600 A (3/4 POLE)

MOUNTING BRACKETS
Note: All dimensions are in mm. 2/73

REAR CONNECTION

OVERALL DIMENSIONS
DX 800-1600 H ... 3/4 POLE

ROTARY DRIVE

DOOR COUPLING ROTARY HANDLE

REMOTE OPERATOR
Note: All dimensions are in mm. 2/74

OVERALL DIMENSIONS
DX 800-1600 H ... 3/4 POLE

WITHDRAWABLE UNIT
Note: All dimensions are in mm. 2/75

OVERALL DIMENSIONS
MCCB - TYPE DM

MOUNTING AND DOOR CUTOUT DETAILS

DM 16

DM 100

MOUNTING AND DOOR CUTOUT DETAILS

MOUNTING AND DOOR CUTOUT DETAILS

DM 160
Note: All dimensions are in mm.

MOUNTING AND DOOR CUTOUT DETAILS

DM 250/400

2/76

OVERALL DIMENSIONS
ROTARY OPERATING MECHANISM .OR MOTOR BACK-UP PROTECTION RANGE .OR TYPE DM

DM 16

DM 100

DM 160
Note: All dimensions are in mm. 2/77

DM 250/400

OVERALL DIMENSIONS
MCCB - TYPE DTH 800 INST.

ROTARY OPERATING MECHANISM .OR DTH 800 INST.

Note: All dimensions are in mm. 2/78

OVERALL DIMENSIONS & CONNECTION DIAGRAM


.USE MONITORING DEVICE TYPE D.

Caution : Connect terminals of D. in parallel with the fuse links. Note: All dimensions are in mm. 2/79

OVERALL DIMENSIONS
EARTH .AULT MODULES - G.1, G.2, G.11

G.1

G.2

G.11
Note: All dimensions are in mm. 2/80

WIRING DIAGRAM
EARTH .AULT MODULES - G.1, G.2, G.11

G.1 & G.2

G.11

2/81

OVERALL DIMENSIONS
SS ENCLOSURE

Note: All dimensions are in mm. 2/82