DESCRIPTION
SunlineTM 2000 series convertible package rooftop models have two independent refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All models are available with three different outdoor air damper options:

TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

DM300 CONSTANT VOLUME 25 NOMINAL TONS (WORLD 50 HZ)

Single enthalpy economizer Single enthalpy economizer with power exhaust Motorized outdoor air damper
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide "free" cooling. The rainhood is painted to match the basic unit and must be fieldassembled before installing. Power exhaust is not available as a field installed option.

1
This product was manufactured in a plant whose quality system is certified/ registered as being in conformity with ISO9001.

SUNLINE TM 2000

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

036-21060-004-A-1102

TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 3 FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 4 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 6 LIST OF FIGURES
Fig. # 1 2 3 4 5 6 7 8 9 10 11 Pg. # FIELD WIRING - DM ELECTRIC/ELECTRIC AND GAS/ELECTRIC UNITS . . . . . . . . . . . . . . . . . . . . . 18 UNIT DIMENSIONS - DM COOL & COOL/ELECTRIC HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 UNIT DIMENSIONS - DM GAS HEAT . . . . . . . . . . . . 19 ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 UNIT WITH RAIN HOOD . . . . . . . . . . . . . . . . . . . . . . 20 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 20 ROOF CURB DIMENSIONS (ALL MODELS) . . . . . . 21 ROOF CURB BENEFITS . . . . . . . . . . . . . . . . . . . . . . 21 UNIT CURB AND APPLICATIONS . . . . . . . . . . . . . . 21 TYPICAL APPLICATION . . . . . . . . . . . . . . . . . . . . . . 22 TYPICAL ROOF-TOP INSTALLATION . . . . . . . . . . . 22 Tbl. # 1 2 3 4 5 6 7 8 9 10

LIST OF TABLES
Pg. # CAPACITY RATINGS - COOLING . . . . . . . . . . . . . . 12 CAPACITY RATINGS - GAS HEAT. . . . . . . . . . . . . . 12 COOLING CAPACITIES - 87 KW (DM300) . . . . . . . . 12 COOLING CAPACITIES - 25 TON (DM300) CFM . . 13 BLOWER PERFORMANCE - DM300 . . . . . . . . . . . . 14 STATIC RESISTANCES - EXTERNAL STATIC PRESSURE DROP . . . . . . . . . . . . . . . . . . . . . . . . . 15 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . 15 PHYSICAL DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 ELECTRICAL DATA - COOLING ONLY UNITS AND UNITS WITH GAS HEAT . . . . . . . . . . . . . . . . . . . . 16 ELECTRICAL DATA - UNITS WITH ELECTRIC HEAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Unitary Products Group

036-21060-004-A-1102

DESCRIPTION (Contd.)
A fixed outdoor air intake assembly is shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. All compressors include internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filterdrier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch, to protect all system components. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty. Simplicity Controls - Simplicity control boards have standardized a number of features previously available only as options or by utilizing additional controls. Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0F outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available. Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a

three times, youre out philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor. On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit. All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit. It can also be routed knockout in the wiring panel on the front of the unit. All models are available with factory mounted BAS Control. Options are Novar, Honeywell, Johnson, or CPC. All internal factory wiring is color coded and numbered for ease in servicing and troubleshooting.

FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

Unitary Products Group

036-21060-004-A-1102

The rainhood is painted to match the basic unit and must be field-assembled before installing. Power exhaust is not available as a field installed option. POWER EXHAUST - Our single economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. The exhaust fan, motor and controls are installed and wired at the factory. The rain hood and the back-draft damper need to be assembled and installed in the field. The power exhaust option can only be used on bottom duct configurations. MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection. ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. FILTER OPTIONS - Standard units are shipped with 2 throw-away filters installed. 2 pleated and 4 pleated filters are offered as a factory installed option. BAS - See Additional Options section in the product nomenclature. SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly. PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition. DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit

thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. HINGED FILTER DOOR/TOOLESS BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. NOTE: Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. Power exhaust is not available as a field installed option. MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. Power exhaust is not available as a field installed option. ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

Unitary Products Group

036-21060-004-A-1102

SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust. BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. WOOD SKID - Allows unit to be handled with 90 forks. CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits. COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. Model 1CG0415. PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition.

Unitary Products Group

036-21060-004-A-1102

PRODUCT NOMENCLATURE

25T Sunline 2000 Model Number Nomenclature


York Brand
D M 300 N 24 A 7 A AA 1
Product Category D = Air Cond., Single Package Product Generation 1 = First Generation Product Identifier M = R-22 Standard Efficiency

Voltage 7 = 380/415-3-50 Nominal Cooling Capacity - MBH 300 = 25 Ton

Heat Type & Nominal Heat Capacity C00 = Cooling Only. No field installed electric heat Gas Heat Options N24 = 240 MBH Output Aluminized Steel N32= 320 MBH Output Aluminized Steel Electric Heat Options E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW

Installation Options A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Options 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4, & 5 Options 1 = Disconnect 2 = Non-Pwr'd Conv Oultet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet

Additional Options (See Next Page)

Airflow A= Std Motor/Drive B = Std Mtr/Drive/Single Input Econo C = Std Mtr/Drive/Single Input Econo/Power Exhaust* D = Std Mtr/Drive/Motorized Damper F = Std Mtr/Drive/4" Filters G = Std Mtr/Drive/4" Filters/Single Input Econ H = Std Mtr/Drive/4" Filters/Single Input Econ/Power Exhaust* L = Std Mtr/Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters M = Std Mtr/Drive/BAS Ready Econ (No BAS Controller)/Power Exhaust w/2" Pleated Filters*

Unitary Products Group

036-21060-004-A-1102

PRODUCT NOMENCLATURE - Continued


25T Sunline 2000 Model Number Nomenclature
Additional Options AA AB AC AD AE AF AG AH BA BB BC BD BE BF BG BH CA CB CC CD CE CF CG CH CJ CK CL CM CN CP CQ CR DA DB DC DD DE DF DG None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, & Dirty Filter Switch Hinged Filter Door & Tooless Access Panels Phase Monitor, Hinged Filter Door & Tooless Access Panels Coil Guard, Hinged Filter Door & Tooless Access Panels Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Phase Monitor & Coil Guard, Hinged Filter Door & Tooless Access Panels Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Coil Guard & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels CPC Controller with Dirty Filter Switch & Air Proving Switch CPC Controller, DFS, APS & Phase Monitor CPC Controller, DFS, APS & Coil Guard CPC Controller, DFS, APS, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Cond. Coil CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Evap. Coil CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels

Unitary Products Group

036-21060-004-A-1102

Additional Options DH DJ DK DL DM DN DP DQ DR EA EB EC ED EE EF EG EH EJ EK EL EM EN EP EQ ER GA GB GC GD GE GF GG GH GJ GK GL GM GN GP GQ GR CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels

Unitary Products Group

036-21060-004-A-1102

Additional Options HA HB HC HD HE HF HG HH HJ HK HL HM HN HP HQ HR JA JB JC JD JE JF JG JH JJ JK JL JM JN JP JQ JR NA NB NC ND NE NF NG NH NJ Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch Honeywell Excel 10 Controller, DFS, APS & Phase Monitor Honeywell Excel 10 Controller, DFS, APS & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch Johnson UNT Controller, DFS, APS & Phase Monitor Johnson UNT Controller, DFS, APS & Coil Guard Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch Novar ETC-3 Controller, DFS, APS & Phase Monitor Novar ETC-3 Controller, DFS, APS & Coil Guard Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil

Unitary Products Group

036-21060-004-A-1102

Additional Options NK NL NM NN NP NQ NR PA PB PC PD PE PF PG PH PJ PK PL PM PN PP PQ PR RC TA TB TC TD TE TF TG TH TJ TK TL TM TN TP TQ TR TS Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Tooless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Factory Coil Guard and Small Made in USA American Flag Decal Technicoat Condenser Coil Technicoat Condenser Coil & Phase Monitor Technicoat Condenser Coil & Coil Guard Technicoat Condenser Coil & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, & Coil Guard Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator Coil Technicoat Evaporator Coil & Phase Monitor Technicoat Evaporator Coil & Coil Guard Technicoat Evaporator Coil & Dirty Filter Switch Technicoat Evaporator Coil, Phase Monitor, & Coil Guard Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils

10

Unitary Products Group

036-21060-004-A-1102

Additional Options TT TU TV TW TX TY TZ UA UB UC UD UE UF UG UH UJ UK UL UM UN UP UQ UR US UT UU UV UW UX UY UZ Technicoat Evaporator & Condenser Coils & Phase Monitor Technicoat Evaporator & Condenser Coils & Coil Guard Technicoat Evaporator & Condenser Coils & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Condenser Coil, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Tooless Access Panels

Unitary Products Group

11

036-21060-004-A-1102

TABLE 1: CAPACITY RATINGS - COOLING


MODEL 300 TOTAL OUTPUT KW/ MBH 85.2 / 293 TOTAL INPUTKW 35.4 COP 2.4 EER 8.3 ELECTRIC HEAT NOMINAL CAPACITY KW 18, 36, 54, 72

TABLE 2: CAPACITY RATINGS - GAS HEAT


MODEL DM300 LOW HEAT HIGH HEAT TOTAL OUTPUT kW/ MBH 85.2 / 293 85.2 / 293 TOTAL INPUT kW 35.4 35.4 COP 2.4 2.4 EER 8.3 8.3 GAS HEAT RATINGS MBH INPUT 300 380 MBH OUTPUT 240 304

TABLE 3: COOLING CAPACITIES - 87 KW(DM300) M3/S


Temperature of Air on Condenser Coil Air On Evaporator Coil Total Cap kW1 m /sec.
3

OD Dry Bulb - 27 Sensible Capacity Power Input kW2 Entering Dry Bulb C 31 108 100 94 94 106 98 91 91 104 96 88 88 24.8 24.0 23.5 23.5 24.6 23.9 23.2 23.2 24.5 23.8 23.0 23.0 68 90 94 94 64 84 91 91 60 78 88 88 28 51 71 94 94 48 67 87 90 45 62 80 87 25 33 53 74 88 32 50 69 85 31 48 65 82 22 35 55 76 34 52 71 33 50 66
1

OD Dry Bulb - 35 Total Cap kW1 101 94 90 89 100 92 86 86 98 90 83 83 Power Input kW2 27.3 26.4 25.9 25.8 27.1 26.2 25.5 25.5 26.9 26.0 25.1 25.1 Sensible Capacity Entering Dry Bulb C 31 67 89 90 89 63 82 86 86 58 76 83 83 28 49 69 89 89 46 65 84 86 44 61 79 83 25 32 51 72 83 31 48 67 80 30 46 63 78 22 34 53 74 32 50 69 31 48 65
1

OD Dry Bulb - 46 Total Cap kW1 88 83 79 79 86 81 76 76 85 78 73 73 Power Input kW2 32.0 31.2 30.5 30.5 31.8 30.7 30.0 30.0 31.6 30.3 29.5 29.5 Sensible1 Capacity Entering Dry Bulb C 31 62 83 79 79 58 76 76 76 54 71 73 73 28 45 64 77 77 42 60 75 75 40 56 72 72 25 28 47 66 72 27 44 62 70 26 41 58 67 22 30 47 67 28 45 63 27 43 59

WB 23

4.72

20 17 14 23

4.25

20 17 14 23

3.78

20 17 14

1. These capacities are gross ratings. For net capacity deduct the heat of the supply air blower motor MBH = 3.415 x kw. Refer to the appropriate Blower Performance table for the kw of the supply air blower motor. 2. These ratings include the condenser fan motors and the compressor motors, but not the supply air blower motor.

12

Unitary Products Group

036-21060-004-A-1102

TABLE 4: COOLING CAPACITIES - 25 TON (DM300) CFM


Temperature of Air on Condenser Coil Air On Evaporator Coil OD Dry Bulb - 80.0 Total Cap1 MBH 368 341 322 322 362 334 311 310 357 328 300 299 Power Input kW2 24.8 24.0 23.5 23.5 24.6 23.9 23.2 23.2 24.5 23.8 23.0 23.0 Sensible Capacity Entering Dry Bulb F
88 82 77 72
1

OD Dry Bulb - 95.0 Total Power Cap. Input MBH1 kW2 346 321 306 305 341 315 295 295 336 308 285 284 27.3 26.4 25.9 25.8 27.1 26.2 25.5 25.5 26.9 26.0 25.1 25.1 Sensible *Capacity Entering Dry Bulb F
88 82 77 72
1

OD Dry Bulb - 115.0 Total Power Cap. Input MBH1 kW 2 300 283 268 268 295 275 259 258 291 266 250 249 32.0 31.2 30.5 30.5 31.8 30.7 30.0 30.0 31.6 30.3 29.5 29.5 Sensible1 Capacity Entering Dry Bulb F
88 82 77 72

CFM

WB

73 10000 68 63 57 73 9000 68 63 57 73 8000 68 63 57

233 309 322 322 219 287 311 310 204 266 300 299

173 243 320 320 164 228 296 309 155 213 274 298

113 180 252 301 110 171 236 291 106 162 221 281

120 187 258 116 178 242 113 169 227

229 304 306 305 214 282 294 294 200 260 285 284

168 237 303 302 158 222 285 292 150 208 268 282

108 175 245 284 105 166 229 274 101 157 214 265

114 181 251 111 172 236 107 163 221

213 283 268 268 200 261 259 258 186 244 250 249

155 220 265 265 144 206 258 258 137 192 248 248

96 162 227 247 93 151 213 241 89 141 199 230

103 162 230 96 155 216 93 148 203

1. These capacities are gross ratings. For net capacity deduct the heat of the supply air blower motor MBH = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor. 2. These ratings include the condenser fan motors and the compressor motors, but not the supply air blower motor.

Unitary Products Group

13

036-21060-004-A-1102

TABLE 5: BLOWER PERFORMANCE - DM300 - BOTTOM DUCT CONNECTIONS (COOLING APPLICATIONS)


DM300 UNIT - DOWNFLOW DUCT CONNECTIONS BLOWER SPEED (rpm) 945 975 1005 1040 1070 1100 1130 PULLEY TURNS OPEN ESP (iwg) OUTPUT (bhp) 6.0 5.0 4.0 3.0 2.0 1.0 0.0 1.2 1.4 1.6 1.8 2.0 2.1 2.3 5.6 5.9 6.2 6.6 6.9 7.3 7.6 3.53 m3/Sec. INPUT (kW) 4.6 4.9 5.1 5.4 5.7 6.0 6.2 ESP (Pa) 198 244 291 347 396 445 495 7500 CFM 8750 cfm INPUT (kW) 4.6 4.9 5.1 5.4 5.7 6.0 6.2 ESP (iwg) 0.8 1.0 1.2 1.4 1.6 1.8 2.0 OUTPUT (bhp) 7.0 7.3 7.7 8.1 8.5 8.9 9.3 4.13 m3/Sec. OUTPUT (bhp) 7.0 7.3 7.7 8.1 8.5 8.9 9.3 8750 cfm INPUT (kW) 4.6 4.9 5.1 5.4 5.7 6.0 6.2 ESP (iwg) 0.3 0.5 0.7 0.9 1.1 1.3 1.5 OUTPUT (bhp) 7.0 7.3 7.7 8.1 8.5 8.9 9.3 4.13 m3/sec. ESP (Pa) 87 133 180 236 285 334 384 OUTPUT (bhp) 7.0 7.3 7.7 8.1 8.5 8.9 9.3 INPUT (kW) 5.7 6.0 6.3 6.7 7.0 7.3 7.6 INPUT (kW) 5.7 6.0 6.3 6.7 7.0 7.3 7.6 INPUT (kW) 5.7 6.0 6.3 6.7 7.0 7.3 7.6 ESP (Pa) 71 120 169 228 280 332 385 INPUT (kW) 5.7 6.0 6.3 6.7 7.0 7.3 7.6 10000 cfm ESP (iwg) OUTPUT (bhp) 0.3 0.5 0.7 0.9 1.1 1.3 1.5 8.4 8.8 9.2 9.7 10.2 10.6 11.0 4.72 m3/Sec. OUTPUT(bhp) 8.4 8.8 9.2 9.7 10.2 10.6 11.0 10000 cfm ESP (iwg) OUTPUT (bhp) 0.2 0.4 0.6 0.8 9.7 10.2 10.6 11.0 4.72 m3/sec. ESP (Pa) OUTPUT (bhp) 43 94 146 199 9.7 10.2 10.6 11.0 INPUT (kW) 8.0 8.3 8.7 9.0 INPUT (kW) 8.0 8.3 8.7 9.0 INPUT (kW) 6.9 7.2 7.6 8.0 8.3 8.7 9.0 INPUT (kW) 6.9 7.2 7.6 8.0 8.3 8.7 9.0

DM300 UNIT - DOWNFLOW DUCT CONNECTIONS BLOWER SPEED (rpm) 945 975 1005 1040 1070 1100 1130 PULLEY TURNS OPEN ESP (Pa) OUTPUT (bhp) 6.0 5.0 4.0 3.0 2.0 1.0 0.0 303 347 391 443 489 536 583 5.6 5.9 6.2 6.6 6.9 7.3 7.6

DM300 UNIT - DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS BLOWER SPEED (rpm) 945 975 1005 1040 1070 1100 1130 7500 CFM PULLEY TURNS OPEN ESP (iwg) OUTPUT (bhp) 6.0 5.0 4.0 3.0 2.0 1.0 0.0 1.0 1.2 1.4 1.6 1.8 2.0 2.2 5.6 5.9 6.2 6.6 6.9 7.3 7.6

DM300 UNIT - DOWNFLOW DUCT CONNECTIONS - GAS HEAT MODELS BLOWER SPEED (rpm) 945 975 1005 1040 1070 1100 1130 3.53 m3/sec. PULLEY TURNS OPEN ESP (Pa) OUTPUT (bhp) INPUT (kW) 6.0 5.0 4.0 3.0 2.0 1.0 0.0 258 301 345 398 444 490 537 5.6 5.9 6.2 6.6 6.9 7.3 7.6 4.6 4.9 5.1 5.4 5.7 6.0 6.2

14

Unitary Products Group

036-21060-004-A-1102

TABLE 6: STATIC RESISTANCES1 - EXTERNAL STATIC PRESSURE DROP


RESISTANCE, Pa / iwg DESCRIPTION 3.78/ 8,000 WET COIL GAS HEAT 18 KW ELECTRIC HEAT OPTIONS 36 KW 54 KW 72 KW ECONOMIZER OPTION HORIZONTAL DUCT CONNECTIONS 25 / 0.1 25 / 0.1 25 / 0.1 25 / 0.1 50 / 0.2 50 / 0.2 25 / 0.1 50 / 0.2 m3/s / CFM 4.25 / 9,000 25 / 0.1 25 / 0.1 25 / 0.1 50 / 0.2 75 / 0.3 100 / 0.4 25 / 0.1 75 / 0.3 4.72 / 10,000 25 / 0.1 25 / 0.1 25 / 0.1 75 / 0.3 100 / 0.4 150 / 0.6 25 / 0.1 125 / 0.5

1.Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections Add these values due to less airflow resistance.

TABLE 7: BLOWER MOTOR AND DRIVE DATA


MOTOR1 MODEL SIZE BLOWER RANGE (RPM) ADJUSTABLE MOTOR PULLEY2 DESIGNATION DIA. mm (IN.) 1LVP58 B70A FIXED BLOWER PULLEY (NOTCHED)

kW / HP

FRAME

EFF. (%)

PITCH

BORE

DESIGNATION

PITCH DIA.

BORE

DESIGNATION

PITCH LENGTH 2134 (84)

QTY

300

950 /1130

7.5 / 10

254T

89

157-188 6.2-7.4)

A2 BUSHING

1B5V94

241 (9.5)

B BUSHING

5VX840

1. All motors have a nominal speed of 1450 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because they are located in the moving air, upstream of any heating service. 2. Do NOT close this pulley below one turn.

Unitary Products Group

15

036-21060-004-A-1102

TABLE 8: PHYSICAL DATA


COMPONENT DESCRIPTION DIA. X. WD. (mm) DIA. X. WD. (in.) kW / HP ROWS DEEP INDOOR COIL FACE AREA PROPELLER DIA. OUTDOOR FANS (Two Per Unit) FAN MOTOR NOMINAL AIRFLOW ROWS DEEP OUTDOOR COIL FINS PER 25mm (1 in.) FACE AREA COMPRESSOR (Qty. Per Unit) m / Ft.
2 2

UNIT MODEL 300 457 x 381 18 x 15 7.5 / 10 4 13.5 m / Ft.


2 2

SUPPLY AIR BLOWER

CENTRIFUGAL BLOWER FAN MOTOR

FINS PER 25mm (1 in.)

2.3/25.0 762 / 30 ea. 0.7 / 1 ea. 3.40 ea. 7200 ea. 3 15 4.02 / 43.3 2 2

mm / in. kW / HP m3 / s CFM

TANDEM (12.5 TON NOMINAL CAPACITY) QUANTITY PER UNIT 406 x 508 x 51 (mm) 16 x 20 x 2 (in.) 406 x 635 x 51 (mm) 16 x 25 x 2 (in.) 457 x 610 x 51 (mm) 14 x 20 x 2 (in.) m2 / Ft.2 SYS. #1 (kg. / lbs.) SYS. #2 (kg. / lbs.)

AIR FILTERS (4 or 102mm optional)

QUANTITY PER UNIT

QUANTITY PER UNIT TOTAL FACE AREA CHARGE REFRIGERANT 22

3 9.1/ 21.4 9.3/20.5 9.1/20.0

VOLTAGE

LIMITATIONS1

POWER SUPPLY 380/415-3-50

VOLTAGE MIN. 342 MAX. 457

1. Rated in accordance with ARI Standard, utilization range A.

TABLE 9: ELECTRICAL DATA - COOLING ONLY UNITS AND UNITS WITH GAS HEAT
COMPRESSORS MODEL POWER SUPPLY (QTY. 2) Tandems RLA (Each) DM300 380/415-3-50 24 LRA (Each 202 COND. FAN MOTORS #1 & #2 SUPPLY AIR BLOWER MOTOR HP 10 FLA 19.0 MINIMUM CIRCUIT AMPACITY (AMPS) 76 MAXIMUM OVERCURRENT DEVICE1 (AMPS)

HP 1.0

FLA 2.1

90

1. Dual element, time delay fuse or HACR breaker.

16

Unitary Products Group

036-21060-004-A-1102

TABLE 10: ELECTRICAL DATA - UNITS WITH ELECTRIC HEAT


HEATER OPTION MODEL DM POWER SUPPLY MODEL E018 380-3-50 E036 E054 E072 E018 415-3-50 E036 E054 E072
1 2

KW1 11.3 22.6 33.8 45.1 13.5 26.9 40.4 53.8

STAGES 1 2 2 2 1 2 2 2

AMPS 17.1 34.3 51.4 68.6 18.7 37.4 56.2 74.9

MINIMUM CIRCUIT AMPACITY (AMPS) 76.0 76.0 87.9 109.4 76.0 76.0 94.0 98.6

MAXIMUM OVERCURRENT DEVICE2 (AMPS) 90 90 90 110 90 90 100 110

300

Electric Heat CORRECTION FACTORS: Dual element time delay fuse or HACR breaker.

NOMINAL VOLTAGE 415 WEIGHTS (KG. / LBS.)

VOLTAGE 400

KW CAP. MULTIPLIER 0.93

DM300 (Cooling only) BASIC UNIT DM300 (Gas / Electric) N24 N32

1238 / 2730 1332 / 2930 1360 / 2992

OPTIONS / ACCESSORIES 18 KW Electric Heater (Elec/Elec only) 36 KW 54 KW 72 KW Economizer Motorized Damper Roof Curb Barometric Damper Wood Skid
1

11.4 / 25 13.6 / 30 15.9 / 35 18.2 / 40 73 / 160 68 / 150 84 / 185 20 / 45 100 / 220

1. Allows handling of unit using 90 (2300mm) long forks.

Unitary Products Group

17

036-21060-004-A-1102

THERMOSTAT TERMINALS

CONTROL TERMINAL BLOCK

W1 W2 Y1 Y2 G R C
2 1

W1 W2 Y1 G OCC P P1 Y2 X R SD
5

Smoke Detector

R SD SD

Jumper

RC OCC X

24 VAC Class 2

TERMINALS ON A LIMITED NUMBER OF THERMOSTATS

1 2 3 4 5 6

Second stage heating not required on single stage heating units. Second stage cooling not required on single stage cooling units. Jumper is required if there is no Smoke Detector circuit. Jumper is required for any combination of R, RC, or RH. OCC is an output from the thermostat to indicate the Occupied condition. X is an input to the thermostat to display Error Status conditions.

FIGURE 1: FIELD WIRING - DM ELECTRIC/ELECTRIC AND GAS/ ELECTRIC UNITS

18

Unitary Products Group

036-21060-004-A-1102

Return Air Supply Air Condenser Air Outdoor Air


Note: All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request. HOLE A OPENING (DIA.) (mm / in.) 29 / 1-1/8" KO 19 / 3/4" NPS (Fem.) 92 / 3-5/8" KO B C D 76 / 3" NPS (Fem.) 60 / 2-3/8" KO 43 / 1-11/16" Hole Power Wiring USED FOR Control Wiring Front Bottom Front Bottom

Gas Piping (Front) Gas Piping (Bottom)1

1. Opening in the bottom of the unit can be located by the slice in the insulation.

FIGURE 2 : UNIT DIMENSIONS - DM COOL & COOL/ ELECTRIC HEAT

CLEARANCES (mm/in.)
Front Back Left Side (Filter Access) Right Side (Cond. Coil) Below Unit1 Above Unit2 914 / 36" 610 / 24" (Less Economizer) 1245 / 49" (With Economizer) 610 / 24" (Less Economizer) 1372 / 54" (With Economizer) 914 / 36" 0 / 0" 1829 / 72" With 914 / 36" Maximum Horizontal Overhang (For Condenser Air Discharge)

1. Units (applicable in U.S.A. only) may be installed on combustible floors made from wood or class A, B or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. Note: Cool-Only Models: Units and ductwork are approved for zero clearance to combustible materials when equipped with electric heaters. Gas Heat Models: A 1-inch clearance must be provided between any combustible materials and the supply air ductwork for a distance of 3 feet from the unit. The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least: Three (3) feet above any forced air inlet located within ten (10) horizontal feet (excluding those integral to the unit). Four (4) feet below, four (4) horizontal feet from, or one (1) foot above any door or gravity air inlet into the building Four (4) feet from electric meters, gas meters, regulators and relief equipment.

FIGURE 3 : UNIT DIMENSIONS - DM GAS HEAT

Note: All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.

Unitary Products Group

19

036-21060-004-A-1102

CONDENSER SECTION GAUGE LINE ACCESS

EVAPORATOR SECTION

DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications:

40-3/8"

DOT PLUG (For pressure drop reading) FILTER ACCESS SUPPLY AIR

1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. (Duct openings are closed with sheet metal covers except when the unit includes a power exhaust option. The covering consists of a black paper composition.)

5-1/2" COMPRESSOR ACCESS

RETURN AIR OUTDOOR AIR 40-1/2" 18-5/8" 1" NPT FEMALE COND. DRAIN CONNECTION OUTDOOR AIR COMPARTMENT ACCESS

SUPPLY AIR ACCESS

3. Replace the side supply and return air compartment panels. For side duct applications: 1. Replace the side panels on the supply and return air compartments with the accessory flange kit panels. 2. Connect ductwork to the duct flanges on the rear of the unit.

27-3/4" RETURN AIR ACCESS 5-1/8"

REAR VIEW

39-5/8"

FIGURE 4: ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGS

SUPPLY AIR COMPARTMENT

POWER EXHAUST RAIN HOOD (on Return Air Compartment)

ECONOMIZER MOTORIZED DAMPER RAIN HOOD (on Outdoor Air Compartment)

ECONOMIZER / MOTORIZED DAMPER AND POWER EXHAUST RAIN HOODS

870 (34-1/4")
410 (16-1/8")

FIXED OUTDOOR AIR INTAKE HOOD (located on Return Air Compartment)

25 (1") CONDENSTATE DRAIN (Must be trapped)

127 (5") 914 (36") 1689 (66-1/2") 51 (2") 921 (36-1/4") 2337 (92")

REAR VIEW

LH VIEW

FIGURE 5: UNIT WITH RAIN HOOD

BACK

APPR XIMATE APPROXIMA TE CENTER OF GRA GRAVITY VITY CONDENSER COIL END

2254 (92")

1376 (56") 1078 (44") 3338 " (136-1/4") FRONT

FIGURE 6: CENTER OF GRAVITY

20

Unitary Products Group

036-21060-004-A-1102

* Supply and Return air (including duct support rails) as shown, are typical for Downflow duct applications For location of Sideflow duct applications (on back of unit), refer to Unit Dimension details.

FIGURE 7: ROOF CURB DIMENSIONS (ALL MODELS)

FIGURE 8: ROOF CURB BENEFITS

FIGURE 9: UNIT CURB AND APPLICATIONS

Unitary Products Group

21

036-21060-004-A-1102

FIGURE 10: TYPICAL APPLICATION

FIGURE 11: TYPICAL ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)

22

Unitary Products Group

036-21060-004-A-1102

Unitary Products Group

23

Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 2002. All rights reserved. Unitary Products Group 5005 York Drive