york airside products

Air movement made easy

On the cover... This shapes lines are taken from the ultra-modern building shape of the Montreal Biodome. Building Efficiency provides all heating and air conditioning controls to deliver safe and comfortable conditions for the facilitys different inhabitants - ranging from Antarctic temperatures for the penguins to hot and humid conditions for the tropical plants.

york airside products

A more comfortable, safe and sustainable world

york airside products

04/05

When it comes to comfort cooling or air conditioning, Johnson Controls meets all your product needs.
Whether it be air handling units, fan coil units or close control air conditioning, we have been providing energy efficient air handling units to the HVAC industry for over 50 years. During this time, focus on quality customer service as well as quality products have always come first. We specify the right air handling unit (AHU) or fan coil units (FCU) working directly with you. We then manufacture and deliver the solution for your project, taking into consideration acoustics, energy, controls, indoor air quality and budget. A tailored product for specific needs. You can depend on us When it comes to AHUs, FCUs, and other airside products the reputation and experience of the manufacturer is as important as the product. Our YORK by Johnson Controls products have a well earned reputation for quality, for the benefit of those specifying, installing and servicing HVAC equipment. We dont rest on our merits though. We are constantly improving our products. We analyse every aspect of our products to make them more energy efficient, whilst maintaining reliability and ease of installation and use.

We offer expert knowledge and practical solutions in a proactive and friendly way, and we always deliver on our promises.

Johnson Controls has become a lead technology and energy-efficiency partner for the Clinton Climate Initiative that aims to reduce greenhouse gases in 40 major cities worldwide.

york airside products

Catalogue contents
Page

Air Handling Systems


YMA Custom Air Handling Units YMA-C Hygienic Air Handling Units 12 21

Fan Coil Units


YFCN Fan Coil unit YFCN Inverter Fan Coil unit LASER Fan Coil unit LOW BODY Fan Coil unit YEFB Hydro Blower YGFC Fan Coil Unit YHK Hydro Cassette YHK-ECM Inverter Hydro Cassette YFCC Coanda Hydro Cassette YHM Hydro High Wall 26 28 30 32 34 36 38 40 42 44

06/07

Page

Close Control Units


YC-P Close Control units 48

Air to Air Packaged Rooftop Units


YRPE RTR/RTP Air to air packaged rooftop units 56

Factory Packaged Control Solutions


SmartPac 66

york airside products

08/09

Air Handling Systems & Terminal Devices


custom & hygienic air handling units fan coil units close control units yrpe rooftop custom series smartpac - factory packaged controls

york airside products

So why choose YORK Air Handling Units?


We recognise that your reputation depends on the quality of the products you choose and how well they are installed. Thats why we work hard to make selecting, installing and operating our products as easy as possible. Our YMA range includes a number of additional options that make YORK Air Handling Units the professionals choice.
Factory Packaged controls Save money and time avoiding to mount controls on-site. Johnson Controls offers YORK Air Handling Units complete with Metasys factory packaged controls so it is ready connect to the site network when it arrives. Our Factory Packaged controls undergo a detailed testing process at the factory to ensure that all wiring is installed correctly, and that all control panels and end devices work appropriately before the AHU is shipped. Factory Packaged Controls option  AHUs Metasys factory packaged controls specified option available.  Panel Power wiring, Controls wiring and the Variable Speed Drive are included. The pre-engineered controller and required peripheral devices are all supplied factory fitted and tested.  Guaranteed compliance with European installation regulations.  Simplified final commissioning through the units keypad and display.

Heat-recovery wheels reduce the cost of conditioning supply air.

Energy recovery options The exhaust air stream from an AHU represents another opportunity to save energy. A heat recovery thermal wheel can economically transfer heat and moisture between the exhaust-air and outside-air paths, reducing the cost of conditioning the supply air. For the simplest form of heat recovery, you can take advantage of free cooling with mixing box sections. During spring and autumn operation, cool/dry outside air cools and dehumidifies the facility, reducing the need for mechanical cooling. Alternatively, you can use recuperative plate heat exchangers. These also allow free cooling in summer by use of face and bypass dampers which by-pass the air around the exchanger so that it is not warmed by the extracted air. We can also offer refrigerant heat pipe and heat recovery coils on your AHU to maximise energy savings.

Reduce fan operating costs In an AHU, the fan is traditionally the largest source of energy consumption. We can help reduce this by offering a range of energy-saving options. High- or premium-efficiency motors can be specified.  Direct-drive plenum fans eliminate belt-and-pulley energy losses.  If the air system is designed for variable-air volume (VAV), YORK AHUs fitted with variable speed drives offer the most efficient method of VAV fan control.  Factory-mounting a variable speed drive reduce jobsite labour costs, unit energy consumption and unit Life Cycle Costs.

10/11

The YORK by Johnson Controls YMA range encompasses our extensive knowledge of air-handling, offering a highly reliable, economical and energy efficient product capable of addressing all of your needs.

Features
The YMA family of air handling units consists of a range of models having air volumes ranging from 0.25 m3/s to 50 m3/s and total static pressures as high as 2000 Pascal: to ensure maximum flexibility and the best solution for your application, units are available in increments of 40mm in height and 50mm in width. YMA Air Handling Units can be manufactured in varied configurations, with a wide selection of components, to meet customer requirements. Units are also available in line with the requirements of hospital sector specifications. Dimensional flexibility. Space constraints are a reality on most construction projects. YORK AHUs design is based on variable aspect ratios, so the unit can be specified to fit the application and space. Material flexibility. Different environments require different materials so we offer a number of construction materials, including galvanized steel, pre-coated steel, stainless steel, and aluminium. Component flexibility. To meet any AHU requirement, our units offer every available air-handling component. And as applicable technology creates new capabilities, Johnson Controls will apply this to our product range. Over the past 50 years we have supplied air handling units for:  Commercial space: office buildings, cinemas, concert halls Institutional space: schools, universities, churches  Industrial manufacturing: automotive, aerospace, chemical, petrochemical  Hygienic systems: hospitals, life sciences, R&D facilities, food processing, clean rooms  Process manufacturing: pharmaceutical, electronics, semiconductor

Air Handling Systems & Terminal Devices

Introducing the YMA range of Air Handling Units

york airside products

YMA
Custom Air Handling Units
A complete range from 0.25 to 50 m3/s

Main features
 Accurate computer selection, for cost effective matching of all components  Air mixing boxes  ATEX Certification  Completely removable panels  Cooling and heating coils  Dessicant and thermal wheels  DIN 1946-4 & VDI 6022 APPROVED  Eurovent certified range  Extruded aluminium profiles unit frames  Flush fitting panels and doors, to provide aesthetically pleasing lines  Fully sealed thermally insulated rigid enclosure, for optimal acoustic performance  Gas fired burners  Humidifiers  Heat recovery systems  UV sterilising lamps

Possible combinations
Single or double decked units Stacked or side-by-side configuration Indoor or outdoor applications Outdoor units are available with a flat or sloping roof, louvres, rainhoods, birdscreens and special finishes. Site assembled units Where space constraints restrict the size of a single item modules can easily be aligned and locked together by gaskets and stainless steel bolts inserted into factory predrilled assembly holes.

12/13

The Frame
 Low weight, corrosion resistant, marine aluminium alloy twin box section profile, designed to provide strenght and stability  Gaskets between the frameworks panels and profiles, to allow efficient cleaning and prevent trapping and harmful bacteria growth  Optional thermal bridge free profile  Unit sections mounted on a 3mm thick galvanized steel bolted base frame

Standard Construction

Cold Bridge Free Construction

Panels
 Standard 60mm thick (40mm optional) double skinned galvanized panels  0.7mm internal and external skins with 40kg/m density pressure injected polymerised polyurethane foam insulation  Returned K value of 0.2W/m C  Optional panels manufacturing from pre-plastic coated steel, pre-painted metal or stainless steel  Mineral wool infill panel of 100kg/m3 density available  88mm panels available upon request

Access
 Fully removable panels  Access doors equipped with half turn nylon handles and cam locks  Fibreglass reinforced plastic hinges with stainless steel pivots  Double glazed viewing portholes (optional)

Mechanical characteristics- prEN 1886:2007*


*EUROVENT DIPLOMA 05.02.314 APPLIES

PANEL TYPE

CASING STRENGTH

CASING AIR LEAKAGE

THERMAL TRANSMITTANCE

THERMAL BRIDIGING

PU6040TB PU6055ST PU6055TB PU4017TB

D1M D1M D1M D1M

L1 L1 L1 L3

T2 T3 T2 T3

TB2 TB3 TB2 TB3

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

Fans (*)
 One or two double inlet, double width forward or backward curved centrifugal fans  Aerodynamic inlets design, with static and dynamic balancing of the wheels according to airflow and speed  Sealed for life bearings for smaller fans , whereas larger versions have block type self aligning ball journals and split blocks with grease points  Removable fan guards dedicated to vee belt fan drives  Motors protection is ensured by an enclosed fan cooled type class F insulation to IP55 (Category 2 Zone 1 ATEX certified motors available as an option)  Total fan assembly installed on a separate frame isolated from the unit structure by spring anti-vibration mounts  Plenum type fans available for applications where plant space is a premium. The plenum fan pressurises an acoustically lined fan chamber and circular or rectangular discharge duct connections can be located on the external faces of the chamber. This reduces the length of the air handling plant by eliminating the need for external attenuators or complicated duct transformation pieces.

Drive Options Dual speed fan motors Direct drive fans Variable speed drives

Plenum Fan Configuration

A Acoustically Lined Fan Section B Supply Air Ducts

(*) Please contact local sales office for fan application details.

14/15

Cooling and Heating Coils


Cooling and heating coils are computer selected to achieve the optimum thermal and psychrometric efficiency with low air and water pressure drops. Coils  Mechanically bonded to aluminium fins copper tubes standard coils, with threaded steel headers, all contained in a galavanised steel frame  Air vents and drain connections provided  Coils leak tested at 30 bar and maximum 15 bar design pressure  Cooling coil assembly located in a drain pan within the coil section on slide rails for easy withdrawal from either side  Dry pan, 3 directions inclined design insulated condensate pans, to ensure complete condensate removal, and manufactured from a choice of stainless steel or aluminium alloy  Drop eliminators fitted after cooling coils, when velocity exceeds 2.5m/s Coil options Medium/high pressure steam coils Copper fins Electro-tinned copper fins Pre-painted and epoxy coated fins Copper headers All steel coils All aluminium coils Direct expansion coils Stainless steel slide rails Stainless steel frame Aluminium and PPTM droplet eliminators Fully removable drain pan

Computer Selection Programme


The flexible computerised programme provides the optimum equipment selection to satisfy the specified conditions and provides full technical information plus General Arrangement drawings.

Electric Heating Coils  Manufactured from low temperature screened stainless steel tube  Spiral fin heating elements secured to a heavy gauge steel frame  Fitted manual reset safety thermostat, high temperature cutout and airflow switch - Step or modulating controls options available

Gas Burners
 Indirect gas fired burners with an optional choice of on/off, staged, or fully modulating control, and are suitable for use in both draw through and blow through applications  Burner design ensures no transition sections from the fan are necessary on draw through systems, thereby reducing fabrication cost  Burners can be horizontally mounted on downflow applications, eliminating the need for turning sections and saving cost, space and weight  Low NOx / carbon monoxide free burners also available in order to increase safety and reduce atmospheric pollution

Air Handling Systems & Terminal Devices

york airside products

Humidifiers
Generated Steam Humidifier Consists of immersed electrodes, steam cylinder, stainless steel distribution pipe and electronic controls for water regulation and automatic flushing. Air Washer  Externally mounted pump, with a removable strainer, draws water from an aluminium alloy tank, which has a liquid level regulator, overflow, drain and flushing device  Spray distribution (through single or double row sprays) is via a nylon pipe and nozzles  Incorporated air tight access hatch, with porthole, an internal light, a perforated air equaliser plate and a droplet eliminator Wet Deck Humidifier  Viscose-coated evaporating pack moistened with water, circulated by an internally mounted pump with removable strainer, from a header tank  Base tank includes a ball valve, overflow and drain  Assembly is constructed from aluminium alloy sheets Direct Injection Humidifier  Electrically or pneumatically operated steam humidifiers can be installed to inject dry, sterile steam into the airstream via steam distribution pipes  Units are normally supplied with a control valve for actuation by others

Filters
Filter sections are designed for easy front or side withdrawal of the following filter types: Prefilters Synthetic or glass-fibre media panel filters, class EU2 to EU4 (EU3 supplied as standard) arranged in galvanized steel frames or sliding rails. Main Filters Synthetic or glass-fibre media bag filters, class EU5 to EU8 (EU6 supplied as standard) arranged in galvanized steel frames with gaskets to avoid air bypass. Final Filters High efficiency compact cell filters, class H10 to H14 according to EN 1822, fixed with brackets, nuts and bolts or clamps to a heavy galvanized steel gasketted structure. Stainless steel welded frames and DOP testing of filter bank available if required.

Dampers
Extruded aluminium dampers are the opposed or parallel blade type. The flanged frame is pre-drilled for ductwork connection. Side gaskets are installed to minimise air leakage. Spindles are manufactured from aluminium and have Teflon or nylon bushes. Control links are aluminium.

16/17

Heat Recovery
YMA air handling units are available with a range of Heat recovery devices that reduce energy usage and lower the equipment running costs Plate Heat Exchanger Manufactured from aluminium or plastic plates (optional stainless steel or polycarbonate) and turbulation channels to permit heat transfer from warm to colder air systems without mixing the two air streams. Heat Pipe Vertically mounted tubes, charged with refrigerant, exchange heat by the evaporation of warm air stream in the lower section and re-condensation in the cold air stream in the upper section.

Sound Attenuation
Standard attenuation sections comprise baffles of galvanized steel and non-hygroscopic material, with option for either perforated plate or melonex liners.

Thermal Wheel Available with a hygroscopic or non-hygroscopic rotor for recovering and transferring heat energy from the exhaust to the supply air streams.

Lighting & Electrical


Optional water resistant bulkhead lights and switches can be supplied. Fan motors and other electrical items can be pre-wired to local isolators and /or terminal.

Factory Packaged Controls


All units can be supplied with factory fitted controls, sensors and control panels. Using YORK SmartPAC packaged control system incorporating Johnson Controls range of system controllers, units are supplied to site pre-wired, programmed and tested thus saving time and money associated with traditional site installation and commissioning methods. All installations will be compliant with the latest applicable National/European codes.

Air Handling Systems & Terminal Devices

york airside products

YMA Quick Size Guide

YMA Size 610/750 690/900 690/1050 970/950 970/1150 970/1350

Duty (m3/s) 0.25-0.44 0.42-0.74 0.55-0.95 0.79-1.39 1.08-1.90 1.37-2.40

Cross Section (mm) H 610 690 690 970 970 970 1210 1210 1210 1210 H1 100 100 100 100 W 750 900 950 1150

D 1/1 D 1/2 kg 9 12 15 18 22 26 27 34 39 43 39 48 54 59 55 58 68 78 68 79 87 98 91 113 122 113 138 158 kg 5 6 8 9 11 13 14 17 19 21 20 24 27 29 28 29 34 39 34 39 43 49 46 50 56 61 56 64 69 74 79 l

1B (1) kg 40 49 57 61 70 80 82 94 104 114 l

MB kg 43 49 56 66 75 81 113 123 132

CM (1a) l 1000 1000 1000 1200 1200 kg 71 82 93 111 138 181 215 l 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350

PF kg 34 39 44 47 52 58 60 66 72 78 72 79 87 93 88 94 100 107 104 109 116 123 118 124 132 140 134 141 148 157 168 l

MF kg 66 76 86 86 96 109 110 124 145 139 152 171 180 175 185 204 214 206 215 227 243 234 251 274 298 262 286 309 319 33 2 136 l N/A N/A N/A

GB kg # # # l 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450 450

EC kg 77 84 93 125 153 187 181 209 237 265 320 343 356 369 175 399 204 497 446 493 550 607 570 636 702 769 721 787 853 919 984

HC l 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350

350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350

500 500 500 600 600 600 800 800 800 800

800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800

100 1050

1200 124

100 1350 100 1250 100 1500 100 1700 100 2000

1210/1250 1.63-2.86 1210/1500 2.11-3.70 1210/1700 2.50-4.37 1210/2000 3.07-5.38 1530/1500 2.77-4.85 1530/1750 3.40-5.95 1530/2000 4.03-7.06 1530/2200 4.54-7.94 1890/1700 4.21-7.37 1890/1900 4.86-8.51 1890/2150 5.51-9.64 1890/2400 6.32-11.06 2170/1950 5.76-10.1 2170/2150 6.53-11.42 2170/2400 7.49-13.1 2170/2650 8.45-14.78 2410/2250 7.78-13.61 2410/2500 8.86-15.50 2410/2750 9.94-17.40

103 1600 1600

1600 198 1600 232

1530 100 1500 1530 100 1750 1530 100 2000 1530 100 2200 1890 100 1700 1890 100 1900 1890 100 2150 1890 100 2400 2170 100 1950 2170 100 2150 2170 100 2400 2170 100 2650 2410 100 2250 2410 100 2750

106 1000 150 2000 268 120 1000 162 2000 289 131 133 141 157 172 174 1000 173 2000 310 1250 1250 1250 1250 207 2500 385 220 2500 411 234 2500 437 248 2500 462 142 1000 185 2000 331

158 1400 268 2800 491 1400 283 2800 520 188 1400 298 2800 548 204 1400 314 2800 577 193 225 227 262 278 293 1600 339 3200 628 356 3200 660 373 3200 693 1600 207 1600

2410 100 2500 100

2410/2950 10.80-18.90 2410 100 2950 2650/2550 10.08-17.64 2650 100 2550 2650/2800 11.28-19.74 2650/3050 12.48-21.84 2650 100 3050 2650/3550 14.8-26.0 2650 100 3550

240 1600 390 3200 725 1700 399 3400 740 1700 435 3400 809 1700 453 3400 843 1700 470 3400 877 247 1700 418 3400 774

2650 100 2800 128

2650/3300 13.68-23.94 2650 100 3300 148

1. IB weight with D1/1 1a. CM data for 100% fresh air/exhaust 2. Section length variable 600mm - 1800mm dependent on module arrangement 3. HC weight for 1 row dry coil

4. CC weight for 6 row dry coil 5. Adiabatic evaporating pack 6. AW dry weight 7. CF weight includes motor and drive set

Dimensions are for guidance only - units are available in increments of 40mm in height and 50mm in width. Section

Dimensions & weights variable dependent on duty & application. Please contact your local YORK office for verification.

18/19

(3) kg 34 40 47 50 57 64 66 75 83 91 86 95 105 113 106 118 127 138 129 141 152 163 155 167 189 192 182 196 208 223 236

CC (4) kg 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 650 l 60 74 88 100 120 140 152 178 205 231 215 247 281 308 296 330 364 401 373 417 463 508 472 523 574 625 584 640 698 754 811

DE kg 5 10 20 10 20 25 30 35 45 50 50 60 70 80 80 90 105 115 109 125 145 165 140 155 170 185 170 175 185 200 220 l

EH (5) kg

AW (6) l kg l

CF (7) kg 140 154 168 175 197 216 335 360 393 452 493 541 633 654 762 791 818 842 879 907 l 350 350 350 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700

DS kg 33 40 46 75 85 94 96 107 117 126 119 128 140 149 141 152 163 173 165 176 188 198 189 199 212 223 215 224 237 245 256 l

SA (8) kg 107 119 142 154 183 213 216 251 285 297 298 339 353 393 357 406 451 502 505 517 571 626 627 689 701 713 763 832 900 968 980 l

FF (9) kg 36 42 45 45 60 80 85 100 140 165 140 175 200 240 210 250 290 330 290 340 375 425 395 480 505 550 500 540 590 630 680 l 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600

ES kg 48 56 64 66 75 82 82 91 98 106 100 107 115 122 116 124 133 140 133 142 148 157 150 159 166 174 168 176 183 191 198

HW (10) l 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 kg 160 170 180 170 220 245 200 240 265 299 252 301 376 410 333 412 447 482 424 483 523 568 495 570 609 619 676 686 730 740 754 l

PX kg 90 110 155 147 176 242 195 240 280 320 350 415 470 534 560 635 720 795 885

EP kg 9 12 15 18 22 26 27 34 39 43 39 48 54 59 55 58 68 78 68 79 87 98 91 100 113 122 113 128 138 148 158

N/A #### N/A #### 1100 N/A #### N/A #### 1100 N/A #### N/A #### 1100 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 125 140 161 174 195 216 236 216 243 270 296 262 291 322 351 329 358 388 417 380 421 461 500 472 506 540 574 609 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 1600 195 223 252 273 297 321 345 346 382 417 453 404 440 478 517 517 555 593 630 577 623 669 715 684 725 764 806 847 1300 1300 1300 1700 1700 1700 1700 1900 1900 1900 1900 2100 2100 2100 2100 2400 2400

1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050

350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350 350

1050 1050 1050 1400 1400 1400 1600 1600 1600 1600 1600 1600 1600 1600 1900 1900 1900 1900 1900

1900 1005 1900 1115 1900 1235 2200 1242 2200 1411 2200 1542 2200 1610 2500 1600 2500 1785 2500 1970 2500 2150 2500 2330

2400 1053 2400 1081 2700 1171 2700 1368 2700 1542 2700 1576 3000 1622 3000 1660 3000 1922 3000 1958 3000 2446

8. SA based on standard splitter length of 900mm, 600mm, 750mm, 1200mm, 1500mm, 1800mm long also available 9. Minimum of 1 ES required for access/replacement of cells 10. Add 1 ES before and after HW

11. ALL DIMENSIONS AND WEIGHTS ARE APPROXIMATE ONLY 12.  Lengths shown are for individually constructed sections; where 2 or more sections are manufactured in a single casing, subtract 75mm for each component section from total length

lengths are sized to the nearest millimetre, with flexible shipping splits, to ensure the best solution to your application.

Air Handling Systems & Terminal Devices

york airside products

20/21

Hygienic Air Handling Units


Air Volume Range 0.8 m3/s to 60 m3/s

A range of YORK HygienicAir Handling Units, offering unique solutions to the application of Central Station Air Conditioning in a sterile environment.
There are many factors affecting air quality, comfort conditions and the efficient operation of Air Handling Units. These include: Mechanical performance Thermal transmission through the Air Handling Unit casing Air leakage Noise transmission Bacteria protection Air cleanliness and filter efficiency Fan and motor efficiency Dehumidification Humidification These factors are valid for the air conditioning of commercial buildings and hotels etc., as well as hygiene sensitive environments such as hospitals, laboratories, clean rooms, food processing and a variety of other process systems. YORK YMA-C AHUS have been specifically designed to address all of these factors: Mechanical performance Thermal efficiency Air leakage and cleanliness

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

YMA-C

york airside products

Flexibility
 YMA-C Air Handling Units can be manufactured in varied configurations, with a wide selection of components, to meet customer requirements.  To ensure maximum flexibility and guarantee the best solution for each application, units are available in 50mm increments in both height and width.  Units are also available in line with the requirements of all European hospital sector specifications.  In other types of air handling unit constructions, the majority of air leakage occurs between the frame and the panels. This is why YMA-C units are manufactured from 88mm thick sheet metal panels insulated with CFC free PU foam. YMA-C Air Handling Units comprise an extremely rigid sealed frame construction, therefore gaps between panel junctions are minimal, and consequently air leakage is greatly reduced.  Non-metallic isolating frame around the internal perimeter of each panel is also included, thus eliminating thermal transmission through the casing. An external aluminium profile maintains structural integrity and air-tightness without compromising the thermal-bridging characteristics of the unit.  The construction of the units achieves the highest classification available for both thermal transmittance (T1) and thermal bridge factor (TB1) when measured against Eurovent test standards of prEN 1886:2007.

Mechanical characteristics-prEN 1886:2007


PANEL TYPE CASING STRENGTH CASING AIR LEAKAGE THERMAL TRANSMITTANCE THERMAL BRIDIGING

88

D1

L1

T1

TB1

Casing Materials Prepainted Steel Plastic Coated steel Stainless Steel Aluminium

Centrifugal Fans Forward Curved Backward Curved External motor option Plug Fan Panel

Filters

Cooling Coils Chilled Water Direct Expansion

Heating Coils Hot Water Electric Steam

Heat Recovery Cross Flow Run-Around Dessicant Thermal Wheel

Humidifiers Electronic Steam Mains Steam Cell Spray

Bag or HEPA Carbon Activated

22/23

Bacteria Protection
To protect the system from bacteria development and maximise Indoor Air Quality, two main conditions must occur: 1. Prevent the moist conditions that encourage bacterial and fungal development by using steam humidifiers rather than water spray systems. 2. Ensure that the Air Handling Unit is frequently cleaned.  The internal construction of the unit avoids that any of the interior support member is exposed and ensures the internal surface is perfectly smooth without obstructions or crevices, thus offering no sanctuary for harmful bacteria to settle and breed and ensuring high IAQ and cleanliness levels.  The whole AHU interior can be made from stainless steel, and has an option for all floor panels to be sloped to give continuous drainage for all sections and provide maximum opportunity for internal cleaning.  All units can be tested for air leakage at the factory, and HEPA filter installations can also be particulate (DOP) tested to eliminate any risk of contamination from dust, dust mites, moulds, mildew, pet dander, pollen and other micro-organisms. Other components available include silencers, dampers, and a range of accessories.  Units can also be supplied with an on board DDC control package incorporating the JCI SmartPAC control system, which allows units to be pre-engineered, wired and tested before shipment. Where units are delivered in sections, a plug-andplay quick connection system allows fast installation.  Accurate computer selection ensures cost effective matching of all components to satisfy the specified conditions. (*)

(*)  please contact your local Johnson Controls sales office for Air Handling Unit selections and further information

Air Handling Systems & Terminal Devices

york airside products

YORK Fan Coil units


Driven by innovative trends and modern technology, the YORK Fan Coil Units have been designed around a platform of models, versions and accessories, which have been independently tested and certified by Eurovent. The YORK Fan Coil range meets todays demanding requirements of performance, size, acoustics, low energy, ease of installation and maintenance.

24/25

An extensive offering
 One of the most versatile ranges of fan coils on the market today. Wall and ceiling mounted units, exposed or concealed with centrifugal fan, are included, and with cooling capacities ranging from 0.6 kW to 14 kW.  Dramatic electrical consumption reduction of up to 40% comparative to previous models. This is achieved thanks to the supply of all YORK Fan Coil Units equipped with centrifugal fans and electric motors, and with 6 speed motors as standard to offer greater flexibility in the selection of products. E  nergy saving brushless motor technology option available. Its combination with a dedicated frequency inverter and unit controller to regulate the fan speed enables higher efficiencies, even at low rotational speeds, lower unit noise, constant speed characteristics and an increase in motor lifetime expectancy. In comparison to the traditional units equipped with asynchronous three-speed-motors, units with brushless motors can obtain a considerable energy saving, by reducing the power consumption by up to 70%. A  full range of factory fitted Johnson Controls valve and preconfigured control options is offered. This in addition to a patented wireless control option - offering greater flexibility in the installation of units, with the highest precision in monitoring and maintaining the desired comfort conditions. H  igh pressure Blower units are also available. They can offer up to 23kw of cooling at External Static Pressures of up to 250Pa, and are complemented with a full range of options and accessories covering items such as electrical heating battery, air inlet/outlet diffusers and condensate pumps.

Iconography

Infrared or Wired control

Wired control

Dry mode

Timer

Auto Restart

Sleep mode

Auto Sweep

Ducted Installation

4 Way Air Flow

Air Filter

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YFCN Fan Coil Unit


with centrifugal fan
2 & 4 pipe system A complete range from 0.7 kW to 7.6 kW
Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals

Infrared control

YFCN is a range of Fan Coil Units that continues the YORK tradition based on high reliability and low noise levels. It is the result of great commitment in terms of energy and resources to offer a more modern product from every point of view: every detail has been carefully studied to guarantee the symmetric feet, the wide valve space (170 mm) and easy access to the filter in all models. Moreover each version has the same internal structure, identical in both horizontal and vertical models, in order to standardise production and guarantee a greater flexibility in distribution and installation.

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

Features
 New casing, improved aesthetics, suitable for any modern indoor ambient  Full range for all needs: 9 sizes suitable for horizontal or vertical mounting with or without casing Wireless control option  Low noise operation 3 fan speeds (possible choice between 6 fan speeds) Single piece discharge grid  Several coil choices. Single: 3 or 4 rows; Dual: 3 rows cooling & 2 rows heating Electrical heater optional Suction and discharge plenum optional  Factory fitted valve (on/off or modulating) and controller packages Painted back panel option 4 available versions in all range: VC = Vertical Discharge with Casing VCB = Vertical Discharge with Casing (floor installation) HC = Horizontal Discharge with Casing CD = Concealed unit without Casing

Selection software

26/27

YFCN Fan Coil Unit with centrifugal fan


0.7 to 7.6 kW

Technical features
Model max Total cooling capacity [kW] (1) med min max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Air flow [m3/h] med min max Sound power level [dB(A)] med min max Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth max max mm mm mm 33 0.16 530 670 225 40 0.18 530 770 225 49 0.23 530 985 225 57 0.26 530 985 225 (3) med min 140 1.23 1.02 0.67 0.97 0.79 0.51 229 189 126 5.6 4 1.9 1.6 1.32 0.84 275 227 144 7.3 5.2 2.4 220 175 105 45 39 32 36 30 23 240 1.81 1.43 1.01 1.38 1.07 0.74 335 265 186 13.9 9.2 4.9 2.25 1.76 1.21 387 303 208 16.7 10.8 5.6 295 220 145 47 40 30 38 31 21 340 2.57 1.89 1.65 1.9 1.38 1.2 475 349 304 11.5 6.7 5.3 3.14 2.28 1.98 540 392 341 13.2 7.5 5.8 385 270 235 49 40 36 40 31 27 440 3.12 2.28 1.83 2.34 1.68 1.34 576 421 339 15.5 9 6.1 3.87 2.79 2.21 666 480 380 18.1 10.2 6.8 485 335 265 47 39 33 38 30 24 540 4.1 3.25 2.2 2.07 2.4 1.6 757 600 404 31.3 20.8 10.4 4.93 3.89 2.58 848 669 444 35.7 23.5 11.4 650 495 315 48 41 31 39 32 22 230 / 1 / 50 + E 61 0.27 530 1200 225 88 0.39 530 1200 225 103 0.47 530 1415 225 130 0.58 530 1415 255 176 0.78 530 1415 255 640 4.8 3.86 2.83 3.6 2.86 2.07 884 714 523 36.2 24.8 14.4 6.05 4.8 3.46 1041 826 595 44.9 29.9 16.8 760 590 415 52 46 37 43 37 28 740 5.58 4.64 3.56 4.23 3.47 2.62 1032 857 657 27.7 20 12.5 6.88 5.68 4.29 1183 977 738 32.8 23.5 14.3 925 735 535 56 51 42 47 42 33 840
6.47 5.73 4.03 5.06 4.43 3.04 1201 1061 746 17.5 14.1 7.6 8.77 7.65 5.23 1508 1316 900 24.5 19.3 9.9

940
7.6 6.54 4.88 6.05 5.11 3.72 1410 1213 903 23.2 17.8 10.6 10.53 8.87 6.44 1811 1526 1108 33.8 25 14.3

1200 1020 655 60 56 45 51 47 36

1500 1210 830 64 58 50 55 49 41

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 Data shown is for 4 row cooling version, 2 pipe system. For performance of 3 row cooling version and/or 4 pipe system unit please contact your local Johnson Controls sales office

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

ECM Technology
Running costs. Energy consumption. Life cycle. These are 3 issues that are becoming more and more important in the choice of Fan Coil Units. With these criteria in mind, Johnson Controls offers the ECM range of FCU.

ECM technology comprises a brushless motor combined to a dedicated electronic device (inverter). In comparison to conventional units equipped with asynchronous three-speed motors, the fancoil and cassette units with brushless motors can obtain a considerable energy saving, by reducing power consumption up to 70%. Air flow rate can be varied in continuous by means of a 1-10 V signal generated both by our controls or by independent controls systems. The continuous air flow control improves the acoustic comfort and allows a more punctual reply to the variation of the thermal loads, enhancing the stability of ambient temperature.

Technology
ECM technology consists of a brushless motor combined with an inverter managed by specific regulators. The controller uses a modulating signal with 0-10VDC tension to regulate the fan speed. The brushless electric motor is composed of a rotor having permanent magnets, whose magnetic fields interact with the ones produced by the stator winding. The transfer of current is no longer by mechanical commutator (sliding contacts) but by an electronic commutation system: one electronic controller (inverter) powers the motors stator and generates rotating magnetic fields, that in turn determine the rotors speed. Brusless motor develop much less heat than the traditional brushed motors and they have much lower mechanical resistance than the standard asynchronous maintenance. The absence of brushes eliminates also the main source of electromagnetic noise.

Features
Brushless motor with inverter. 0-10VDC control signal. Low mechanical resistance and heat gain Continuous regulation of the fan speed.  Specifically designed electronic and digital regulators, also for BMS systems.  Possibility to manually set the desired three fan speeds (MIN/MED/MAX).  Available for fan coil and cassette units.

Advantages (compared to traditional brushed motors)


Energy saving: electrical absorption reduced up to 70%.  Higher efficiency: possibility to adapt the air volume and the capacities accordingly to the actual room loads.  Higher comfort: reduced variation of the temperature and relative humidity in the room. Extremely quiet operation. Reduced wear and higher reliability. Longer life expectancy of the motor.

Power consumption: YFCN versus YFCN-ECM (W/kW)


YFCN 430 W/kW

YFCN 730 W/kW

YFCN 430 YFCN-ECM 430

YFCN 730 YFCN-ECM 730

2.50 3.50 4.50 5.50

0.50

1.50

2.50

3.50

28/29

YFCN-ECM Fan Coil Unit with centrifugal fan


0.7 to 7.1 kW

Technical features
Model max 10v Total cooling capacity [kW] (1) med 5v min 1v max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Heating capacity 4 pipes [kW] (3) med min max Water flow in heating 4 pipes [l/h] (3) med min max Pressure drop in heating 4 pipes [kPa] (3) med min max Air flow [m3/h] med min max Sound power level [dB(A)] med min max Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Height Dimensions Width Depth max mm mm mm 20.5 530 770 225 20.5 530 770 225 25 530 985 225 25 530 985 225 (4) med min 230 1.61 1.19 0.74 1.3 0.93 0.56 299 220 137 7.9 4.6 2 2.22 1.59 0.95 383 274 163 10 5.6 2.2 1.63 1.23 0.81 140 106 70 4.3 2.6 1.3 330 220 120 51 41 30 42 32 21 240 1.88 1.33 0.78 1.44 0.99 0.57 348 245 145 16.9 9.1 3.6 2.45 1.68 0.96 421 289 165 19.4 10 3.7 325 210 115 51 41 30 42 32 21 430 2.97 2.19 1.42 2.28 1.65 1.04 550 406 262 32.9 19.3 8.9 3.87 2.78 1.74 665 478 300 37.9 21.2 9.3 2.74 2.1 1.47 238 181 126 13.6 8.5 4.5 515 350 210 51 42 30 42 33 21 440 3.19 2.28 1.44 2.48 1.61 1.04 592 421 266 18.5 10.1 4.5 4.04 2.81 1.73 694 484 298 19.5 10.3 4.4 505 340 200 51 42 30 42 33 21 630 3.99 2.94 1.97 3.11 2.23 1.47 738 544 365 21.6 12.6 6.3 5.1 3.7 2.4 879 635 415 24.1 13.6 6.4 3.68 2.8 2 317 241 172 4.5 2.8 1.5 735 495 305 54 44 33 45 35 24 32 530 1200 225 640 4.54 3.2 2.06 3.41 2.35 1.49 839 590 379 37.4 20.2 9.2 5.76 3.96 2.48 991 681 426 41.2 21.3 9.3 720 475 290 54 44 33 45 35 24 32 530 1200 225 730 4.98 3.7 2.61 3.84 2.79 1.93 921 684 4.82 37.1 22 11.9 6.26 4.58 3.15 1077 788 542 40.1 23.2 12 4.63 3.56 2.65 398 306 228 7.8 4.9 2.9 890 610 400 57 48 37 48 39 28 41 530 1415 225 740 5.34 3.84 2.62 4.03 2.84 1.91 987 710 484 29.1 16.3 8.3 6.68 4.72 3.15 1149 812 542 31.2 16.9 8.3 875 585 380 57 48 37 48 39 28 41 530 1415 225 930 6.36 4.86 3.47 5.2 3.83 2.65 1180 900 642 25.4 15.8 8.7 9.13 6.68 4.61 1570 1149 793 34.5 19.9 10.4 5.98 4.62 4 514 397 292 12.3 7.8 4.6 1395 945 605 64 55 44 55 46 35 99 530 1415 255 940 7.14 5.25 3.61 5.63 4.03 2.71 1324 972 669 23.7 13.8 7.1 9.79 6.94 4.63 1685 1194 796 29.8 16.3 8 1365 910 575 64 55 44 55 46 35 99 530 1415 255

230 / 1 / 50 + E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,5 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

LASER Fan Coil Unit


2 & 4 pipe system A complete range from 0.8 kW to 9.5 kW

CSL00 (Built in) CSR00 (Wall mounted) Fan speed selector

CEL00 (Built in) CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CEL20 (Built in) CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over

CML00 (Built in) CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over

CEL30 (Built in) CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

LASER fan coil units are simple and elegant, discreet in their design. High standards of quality and reliability, combined with a wide range of accessories ensure a total solution for all comfort cooling and heating requirements.

Features
 10 unit sizes, suitable for horizontal or vertical mounting Models with or without casing 6 speed fan (3 speeds pre-wired) Multi-way adjustable discharge grilles Single coil 2, 3, or 4 rows Double coil 3 or 4 rows (cooling) & 1 row (heating) Electric heating factory fitted Suction and delivery plenum option Up to 40 pa static pressure  Factory fitted valve (on/off or modulating) and controller packages Painted steel feet and back panel option ECM variable speed motor option

Selection software

30/31

LASER Fan Coil Unit


0.8 to 9.5 kW

Technical features
Model max Total cooling capacity [kW] (1) med min max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Heating capacity 4 pipes [kW] (3) med min max Water flow in heating 4 pipes [l/h] (3) med min max Pressure drop in heating 4 pipes [kPa] (3) med min max Air flow [m3/h] med min max Sound power level [dB(A)] med min max Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth max max mm mm mm 46 0.22 538 648 224 48 0.23 538 773 224 57 0.27 538 898 224 81 0.39 538 1023 224 (4) med min 110 1.16 0.99 0.79 0.98 0.82 0.64 201 173 140 3.4 2.8 2 1.57 1.28 1 100 86 71 2.7 2.3 1.7 1.12 1.02 0.79 100 86 71 2 1.6 1.07 239 192 143 48 42 36 38 33 28 112 1.64 1.35 1.1 1.37 1.09 0.86 300 244 197 7.1 5 3.4 2.16 1.73 1.35 163 134 110 6.1 4.7 3.1 1.52 1.31 1.1 163 134 110 4.4 3.4 2.4 328 246 185 50 45 38 40 35 29 114 2.41 2.1 1.75 1.96 1.68 1.36 394 345 284 5.8 4.6 3.3 3.05 2.43 2 199 176 147 4.8 3.7 2.8 2.25 2.06 1.68 199 176 147 8.83 7 6.27 409 336 263 54 49 42 42 38 32 216 3.36 2.72 2.24 2.73 2.17 1.74 596 487 398 11.3 9.5 6.5 4.11 3.44 2.75 307 259 214 11.9 8.5 5.7 3.38 2.98 2.5 307 259 214 19.3 15.2 11.4 659 495 378 53 48 44 41 36 29 218 3.58 3.05 2.5 3.14 2.57 2.04 654 553 452 13.6 9.8 6.7 4.95 4.16 3.35 346 294 241 12.5 9.1 6.3 3.64 3.19 2.7 346 294 241 6.3 5 3.5 780 610 459 56 51 43 43 39 32 86 0.41 538 1148 224 220 4.53 3.75 2.99 3.62 2.91 2.25 802 687 567 24.1 17.4 11.6 5.71 4.65 3.61 445 382 318 20 14.3 9.5 4.92 4.16 3.38 445 382 318 13 9.7 6.7 906 727 559 54 48 40 41 35 29 107 0.48 614 1273 254 222 5.63 4.86 4.24 4.54 3.83 3.27 958 863 741 28.4 21.8 17.2 7.19 6.08 5.25 499 449 386 23.5 18 14.2 5.53 4.92 4.36 499 449 386 14.5 11.9 9.6 1117 956 768 60 56 50 47 42 38 156 0.52 614 1273 254 224 6.57 5.87 4.7 5.2 4.56 3.53 1167 1074 842 18.8 15.5 10.5 7.83 6.94 5.45 608 562 448 15.5 12.7 8.7 6.92 6.3 5.16 608 562 448 34.1 28.8 20.3 1219 1086 786 58 55 47 45 44 37 147 0.66 614 1523 254 226 7.41 6.81 5.61 5.86 5.32 4.26 1306 1224 977 21 18.1 12.8 9.33 8.51 6.86 642 604 489 20.5 17.6 12.4 7.18 6.8 5.71 642 604 489 40 36.4 26.8 1374 1253 924 63 60 53 50 47 41 162 0.68 614 1523 254 228 9.50 7.75 6.18 7.71 6.08 4.69 1715 1286 1008 36.9 25.8 17.3 11.80 9.48 7.43 839 654 525 30.4 21.3 14.3 9.05 7.73 6.34 839 654 525 53.6 40.7 28.6 1795 1210 886 67 60 55 53 45 36 211 0.87 614 1773 254

230 / 1 / 50 +E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

LASER Fan Coil Unit


2 & 4 pipe system A complete range from 0.7 kW to 3.4 kW

430
mm
Height

CSL00 (Built in) CSR00 (Wall mounted) Fan speed selector

CEL00 (Built in) CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CEL20 (Built in) CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over

CML00 (Built in) CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over

CEL30 (Built in) CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

LOW BODY units are part of the LASER Fan Coils Units family. The reduced height cabinet makes them the ideal solution for new or replacement applications where dimensional limitations apply.

Features
5 unit sizes, suitable for vertical mounting Models with or without casing 6 speed fan (3 speeds pre-wired) Single coil 2 or 3 rows Double coil 2 or 3 rows (cooling) & 1 row (heating) Electric heating factory fitted Suction and delivery plenum option  Factory fitted valve (on/off or modulating) and controller packages Painted steel feet and back panel option

Selection software

32/33

LASER Fan Coil Unit


0.7 to 3.4 kW

Technical features
Model max Total cooling capacity [kW] (1) med min max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Heating capacity 4 pipes [kW] (3) med min max Water flow in heating 4 pipes [l/h] (3) med min max Pressure drop in heating 4 pipes [kPa] (3) med min max Air flow [m3/h] med min max Sound power level [dB(A)] med min max Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth max max mm mm mm 46 0.22 430 648 254 48 0.23 430 773 254 (4) med min 110 0.94 0.84 0.69 0.83 0.72 0.57 162 145 119 2.1 1.7 1.2 1.26 1.1 0.87 109 96 76 0.8 0.7 0.4 1.15 1.02 0.83 101 90 73 2.2 1.7 1.2 243 203 149 50 44 37 40 34 27 112 1.46 1.22 0.97 1.19 0.97 0.75 251 211 168 4 2.9 1.9 1.81 1.48 1.14 157 128 99 1.4 1 0.6 1.83 1.53 1.22 161 134 107 4.6 3.3 2.2 321 246 178 51 46 39 41 36 29 114 2.11 1.77 1.42 1.69 1.38 1.09 364 305 246 12.6 9.3 6.3 2.55 2.09 1.64 221 181 143 4.3 3 2 2.43 2.03 1.64 213 177 144 10.5 7.6 5.2 446 343 253 54 49 43 44 39 33 230 / 1 / 50 + E 57 0.28 430 898 254 81 0.39 430 1023 254 86 0.42 430 1148 224 216 2.72 2.37 1.95 2.16 1.86 1.5 467 409 336 6.9 5.5 3.9 3.27 2.81 2.26 284 244 196 346 299 257 3.27 2.85 2.34 286 250 205 18.9 14.9 10.5 574 470 356 54 48 41 44 38 31 218 3.37 2.95 2.58 2.64 2.29 1.97 580 509 444 18.4 14.6 11.5 3.99 3.45 2.97 2.3 1.8 1.2 6.1 4.7 3.6 3.65 3.2 2.8 320 280 245 5.7 4.5 3.6 691 570 470 56 51 44 46 41 34

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YEFB Hydro Blower


2 & 4 pipe system A complete range from 3.2 kW to 23.3 kW

CSR00 (Wall mounted) Fan speed selector

CMR00 (Wall mounted) Thermostat with manual fan speed and S/W change over

CER00 (Wall mounted) Thermostat with manual fan speed and automatic change over CER20 (Wall mounted) Thermostat with auto. fan speed and automatic change over CER30 (Wall mounted) Thermostat with auto. fan speed and automatic change over for modulating valve

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

YEFB Blower units are available in 4 sizes for horizontal concealed installations: thanks to their high ESP fans that can handle up to 250Pa, they are the ideal solution for air conditioning large environments.

Features
4 unit sizes for horizontal mounting  Handles high external static pressure up to 250Pa Choice of 2 or 4 pipe systems Twin centrifugal fans Horizontal air return Air distribution plenum Electric heater option Optional paint finish F5 grade filter option

Selection software

34/35

YEFB Hydro Blower


3.2 to 23.3 kW

Technical features at 50 Pa external static pressure


Model max Total cooling capacity [kW] (1) med min max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Heating capacity 4 pipes [kW] (3) med min max Water flow in heating 4 pipes [l/h] (3) med min max Pressure drop in heating 4 pipes [kPa] (3) med min max Air flow [m3/h] med min max Sound power level [dB(A)] med min max Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Height Dimensions Width Depth max max mm mm mm 186 0.81 331 989.6 800 186 0.81 331 989.6 800 419 1.95 331 989.6 800 419 1.95 331 989.6 800 (4) med min YEFB 130 6.01 5.13 3.22 4.72 3.95 2.38 1033 882 554 6.3 27.4 12.1 8.24 6.87 4.08 1430 1192 708 51.8 37.6 15 13.19 10.98 6.5 1154 961 568 33.1 24 9.5 1153 916 494 67 62 52 57 52 43 YEFB 140 6.92 5.81 3.49 5.29 4.36 2.52 1189 999 600 20.6 15.2 6.2 9.25 7.57 4.3 1604 1313 746 28.3 19.9 7.4 1130 898 484 67 62 52 57 52 43 YEFB 230 8.81 7.27 6.08 7.45 5.9 4.79 1515 1250 1045 70.9 50.5 36.9 13.08 10.34 8.36 2269 1793 1451 116.8 77.2 53.2 21 16.57 13.37 1836 1449 1169 75 49.4 33.9 2158 1553 1174 71 65 60 61 56 50 YEFB 240 10.61 8.55 7.01 8.71 6.74 5.37 1824 1470 1205 43.8 30 21.1 15.44 11.89 9.4 2678 2061 1630 69.7 44 29.1 2116 1523 1151 71 65 60 61 56 50 230 / 1 / 50 569 2.59 350 1 239.6 900 569 2.59 350 1 239.6 900 984 4.45 439.3 1 633 900 984 4.45 439.3 1 633 900 YEFB 330 11.15 9.39 7.51 9.13 7.48 5.81 1916 1615 1291 45.1 33.4 22.5 16.02 13.08 10.1 2779 2268 1752 70.2 49.1 31.2 25.7 20.96 16.17 2247 1833 1414 45 31.5 19.9 2639 1994 1422 71 65 59 62 56 50 YEFB 340 14.06 11.58 9.00 11.2 8.95 6.75 2417 1991 1547 39.6 28.2 18.1 19.76 15.69 11.72 3426 2721 2033 59.2 39.5 23.6 2587 1955 1394 71 65 59 62 56 50 YEFB 430 17.86 16.28 14.40 14.39 12.86 11.57 3071 2798 2475 23.7 20.1 16.1 25.46 22.69 19.55 4414 3934 3390 38.2 31 23.7 41.1 36.66 31.58 3596 3205 2761 24.8 20.2 15.4 4129 3505 2853 78 75 70 69 66 61 YEFB 440 23.31 20.95 18.21 17.73 16.5 13.34 4008 3602 3130 21.9 18.1 14 31.27 27.48 23.26 5421 4765 4032 31.6 25.1 18.6 4048 3436 2797 78 75 70 69 66 61

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 4 pipe system not available with 4R coil

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YGFC Fan Coil Unit


2 & 4 pipe system A complete range from 1.9 kW to 14 kW

Commercial Fan Coil Unit range, the YGFC Series is designed specially to meet the varied requirements of zone cooling or heating using chilled water or hot water. However in order to meet the growing demand in city centres where loads are high and space at a premium, YGFC units have a coil option suitable for use in district cooling systems, thus helping reduce pumping power while increasing the overall system efficiency.

Features
10 unit sizes, suitable for horizontal or vertical mounting Models with or without casing 3 speed whisper quiet fans  District cooling coil option allows reduction in pump power and increase in system efficiency Single coil 3, or 4 rows Double coil 3 or 4 rows (cooling) & 1 row (heating) Electric heating option Suction and delivery plenum option  Range of coil protection options for increased product longevity

Selection software

36/37

YGFC Fan Coil Unit


1.9 to 14 kW

Technical features
Model max Total cooling capacity [kW] (1) med min max Sensible cooling capacity [kW] (1) med min max Water flow in cooling [l/h] (1) med min max Pressure drop in cooling [kPa] (1) med min max Heating capacity 2 pipes [kW] (2) med min max Water flow in heating 2 pipes [l/h] * (2) med min max Pressure drop in heating 2 pipes [kPa] (2) med min max Heating capacity 4 pipes [kW] (3) med min max Water flow in heating 4 pipes [l/h] (3) med min max Pressure drop in heating 4 pipes [kPa] (3) med min max Air flow [m3/h] med min max Sound power level [dB(A)] Power supply [V-ph-Hz] Power input [W] Height Dimensions Width Depth max mm mm mm 37 560 840 263 49 560 940 263 66 560 1040 263 89 560 1122 263 med min 02 ST CB 03 ST CB 04 ST CB 05 ST CB 06 ST CB 07 ST CB 08 ST CB 10 ST CB 2.6 2.5 1.9 1.9 1.8 1.4 410 396 313 19 18.6 14.4 3.09 2.97 2.3 447 428 331 14.3 14 11.3 2.23 2.20 1.91 191 173 166 8.34 8.1 6.3 435 413 296 54 53 45 3.7 3.6 2.8 2.5 2.4 1.9 547 515 513 38.8 37.1 28.9 3.77 3.7 2.9 633 612 479 26.8 25.6 20.2 2.91 2.83 2.44 252 245 209 14.4 13.7 10.5 518 506 370 56 54 47 4.5 4.4 3.3 3.2 3.1 2.4 752 720 544 21.5 18.5 13.2 5 4.8 3.74 785 756 576 18.2 15.7 11.3 3.69 3.54 2.99 316 306 260 23.7 22 16.1 732 691 499 59 57 50 5.3 5.10 4.3 3.8 3.7 3 839 767 619 25.7 23.8 18.7 5.7 5.56 4.58 918 886 734 21.3 19.7 15.6 4.6 4.36 3.63 396 375 313 37.4 33.8 24.1 831 805 620 62 59 53 6.6 6.4 5.1 4.8 4.6 3.6 994 944 752 37.7 36.2 24.9 7.47 7.21 5.66 1145 1094 882 30.8 29.6 20.4 5.64 5.49 4.58 486 472 393 56.6 53.8 38.4 1133 1081 773 64 62 56 120 560 1260 263 7.4 7 5.7 5.5 5.2 4.2 1141 1076 868 25.5 24.5 18.7 8.69 8.28 6.64 1274 1210 990 22 21 16 7.18 6.94 6.02 619 598 518 102 95.6 73.4 1312 1225 904 64 63 58 145 560 1460 263 8.1 7.7 6.4 6 5.7 4.6 1163 1102 896 32.9 29.4 23.5 9.45 9.12 7.39 1390 1328 1101 28.3 25.3 20.1 7.93 7.74 6.74 684 666 580 129 123 94.7 1415 1349 1007 62 60 53 139 560 1560 263 9.2 8.7 7.2 7 6.6 5.3 1512 1411 1159 16.9 15.1 11.8 10.9 10.3 8.3 1584 1498 1238 13.8 12.3 9.3 7.79 7.39 6.2 670 637 533 35.5 32.2 23.2 1714 1599 1176 66 63 55 202 560 1660 263 12 T CB 11 10.5 8.4 8.3 7.8 6.1 1775 1732 1368 25.6 24.2 17.3 12.9 12.3 9.6 1890 1800 1451 21.5 20.2 14.1 9.32 9.15 7.35 809 788 633 53.9 52.1 34.6 2036 1899 1340 66 64 54 214 560 1860 263 14 ST CB 14 13 10.2 10.2 9.5 7.3 2304 2127 1710 44.9 40.6 26.1 15.6 14.7 11.3 2412 2232 1764 37.7 34.1 21.4 11.8 11.3 9.38 1011 972 806 93.1 86.7 61 2399 2220 1548 68 66 61 257 560 2160 263

230 / 1/ 50 + E

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YHK Hydro Cassette


2 & 4 pipe system A complete range from 1.3 kW to 11.1 kW
Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals

Infrared control

Coloured versions available as an option

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

YHK Hydro Cassette units are simple and elegant, discreet in their design. High standards of quality and reliability, combined with a wide range of accessories ensure a total solution for all comfort cooling and heating requirements.

Features
Cooling duty from 1.3 to 11.1 kW 2 & 4 pipes systems in all range 2 sizes: 600 x 600 & 800 x 800 Possible choice between 6 fan speeds Condensate pump integrated in all range 2/3 way valves fitted or supplied loose in all range  Coloured versions, possible to change the colour of the grill and the frame Possible to select a complete range of controls Electric heater fitted as an option for all range (2 pipe only) All metal parts insulated to avoid condensations

Selection software

38/39

YHK Hydro Cassette


1.3 to 11.1 kW

Technical features
Model -2 pipes Total cooling capacity 2 Pipes [kW] Sensible cooling capacity 2 Pipes [kW] Water flow in cooling 2 Pipes [l/h] Pressure drop in cooling 2 Pipes [kPa] Heating capacity 2 pipes [kW] Water flow in heating 2 pipes [l/h] * Pressure drop in heating 2 pipes [kPa] Heating capacity 2 pipes [kW] Water flow in heating 2 pipes [l/h] Pressure drop in heating 2 pipes [kPa] Model -4 pipes Total cooling capacity 4 Pipes [kW] (1) max med min max med min max med min max med min max med min max med min max med min max med min max med min max med min max max Height Width Depth mm mm mm (1) (1) (1) (1) (2) (2) (2) (3) (3) (3) max med min max med min max med min max med min max med min max med min max med min max med min max med min max med min YHK 20-2 2.0 1.6 1.3 1.6 1.3 1.0 340 280 219 10 7 4.5 2.6 2.1 1.6 340 280 219 9 6 4 4.6 3.7 2.8 393 315 240 9.9 6.5 4 YHK 20-4 2.3 2.0 1.5 1.9 1.6 1.2 401 337 260 13.5 10 6 3.0 2.5 2.0 261 219 169 14.5 10.5 6.5 610 420 310 49 40 33 40 31 24 44 0.20 8.0 275 575 575 YHK 25-2 2.7 2.3 1.8 2.0 1.8 1.4 461 402 316 9.7 7.6 4.9 3.4 2.9 2.2 461 402 316 8.2 6.3 4.1 5.7 4.9 4.2 488 422 360 8.4 6.4 4.8 YHK 25-4 2.7 2.4 1.9 2.0 1.7 1.3 464 406 318 8.8 6.9 4.6 3.5 3.0 2.4 298 260 209 10.8 8.5 5.7 520 420 310 45 40 33 36 31 24 44 0.20 1.4 275 575 575 YHK 40-2 4.3 3.3 2.3 3.2 2.4 1.6 745 574 387 15.1 9.4 4.6 5.2 3.9 2.6 745 574 387 11.4 7.3 3.5 9.3 7 4.9 795 598 415 12.5 7.6 4 YHK 40-4 3.3 2.7 1.9 2.6 2.0 1.3 574 456 318 13.4 8.8 4.6 4.4 3.5 2.4 378 298 209 16.6 10.8 5.7 710 500 320 53 45 33 44 36 24 68 0.32 2.1 275 575 575 YHK 50-2 5.0 3.9 2.9 3.7 2.8 2.1 863 667 506 19.7 12.4 7.5 6.2 4.6 3.4 863 667 506 17.7 11.2 6.7 10.6 8.3 6.1 914 709 524 16 10 5.9 YHK 50-4 3.8 3.0 2.4 3.0 2.3 1.8 655 519 406 17 11.2 7.2 5.0 4.0 3.1 426 341 267 20.5 13.8 8.8 880 610 430 59 49 41 50 40 32 230V/1ph/50hZ 90 0.45 2.1 275 575 575 YHK 65-2 6.2 4.9 4.2 4.6 3.6 3.0 1 060 845 724 21.6 14.3 10.9 7.8 6.0 5.1 1 060 845 724 15.1 9.9 6.7 13.1 10.7 8.6 1 130 874 741 17.5 11.3 8.4 YHK 65-4 6.3 5.0 4.1 4.7 3.7 3.0 1 090 865 712 18.9 12.5 8.8 9.1 7.2 5.9 783 618 508 21.4 14 9.8 1140 820 630 48 40 33 39 31 24 77 0.36 3.0 303 820 820 YHK 95-2 9.5 6.8 5.3 6.5 4.5 3.5 1 636 1 166 913 26.9 14.7 9.4 11.7 8.0 6.1 1 636 1 166 913 23 12.4 7.9 19.8 13.4 10.3 1 699 1 155 882 20.9 10.6 6.7 YHK 95-4 7.7 5.7 4.5 5.8 4.2 3.3 1 326 974 777 26.9 15.4 10.3 11.0 8.1 6.5 946 697 555 29.9 17.4 11.5 1500 970 710 53 40 34 44 31 25 120 0.53 4.0 303 820 820 YHK 110-2 11.1 8.5 5.3 8.3 6.1 3.7 1 909 1 453 913 35.6 21.8 9.4 14.0 10.3 6.1 1 909 1 453 913 30.6 18.6 7.9 23.7 17.3 10.3 2 037 1 484 882 28.9 16 6.7 YHK 110-4 8.9 6.9 4.5 6.8 5.2 3.3 1 529 1 192 777 34.7 22.1 10.3 12.7 10.0 6.5 1 092 858 555 38.8 25.3 11.5 1 820 1 280 710 58 48 34 49 39 25 170 0.74 4.0 303 820 820

Sensible cooling capacity 4 Pipes [kW] (1) Water flow in cooling 4 pipes [l/h] Pressure drop in cooling 4 pipes [kPa] Heating capacity 4 pipes [kW] Water flow in heating 4 pipes [l/h] Pressure drop in heating 4 pipes [kPa] Air flow [m3/h] Sound power level [dB(A)] Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Absorbed current [A] Water content (2 pipes) [l] Dimensions (4) (1) (1) (3) (3) (3)

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YHK ECM Inverter Hydro Cassette


2 & 4 pipe system A complete range from 1.8 kW to 10.8 kW

Wired control
ETN-ECM Wall-mounted controller that can be connected allowing an inverter control with a 0-10V signal. The same controller can be connected to one or several cassettes (master-slave function).

Infrared control

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

Coloured versions available as an option

YHK ECM water cassette is the result of significant technical and design research focused on providing an avant-garde product in terms of performance, low noise and control flexibility. YHK ECM series uses an innovative brushless electric motor controlled by an inverter card that varies the air flow continuously by means of a 1-10 V signal. The extreme efficiency, also at a low speed, makes it possible to greatly reduce electrical consumption (more than 75% less in comparison to a traditional motor) with absorption values, under normal operating conditions, that are no greater than 10 Watt in the entire range.

Features
Cooling duty from 1.8 to 10.8 kW YHKH: models with infrared control (standard) YHKY: models with wired control (accessory) 2 (-2) & 4 (-4 or -6) pipes systems 2 sizes: 600 x 600 & 800 x 800 Condensate pump integrated in all range 2/3 way valves fitted or supplied loose in all range  Coloured versions, possible to change the colour of the grid and the frame All metal parts insulated to avoid condensations Inverter fan motor for a very quiet operation Electrical consumption reduced by up to 75% Specific range of controllers with master-slave function

Selection software

40/41

YHK ECM Inverter Hydro Cassette


1.8 to 10.8 kW

Technical features
Model -2 pipes Total cooling capacity 2 Pipes [kW] Sensible cooling capacity 2 Pipes [kW] Water flow in cooling 2 Pipes [l/h] Pressure drop in cooling 2 Pipes [kPa] Heating capacity 2 pipes [kW] Pressure drop in heating 2 pipes [kPa] Model -4 pipes Total cooling capacity 4 Pipes [kW] (1) max med min max med min max med min max med min max med min max med min max med min max med min max med min max med min max Height Width Depth mm mm mm (1) (1) (1) (1) (2) (2) max med min max med min max med min max med min max med min max med min YHK-ECM 25-2 2.8 2.2 1.8 2.1 1.6 1.4 473 373 317 10.1 6.6 4.9 3.4 2.7 2.2 8.7 5.5 4.0 YHK-ECM 25-4 2.8 2.2 1.9 2.1 1.6 1.3 476 375 318 9.5 6.2 4.6 3.6 2.9 2.4 311 245 209 11.7 7.6 5.7 535 380 310 47 39 33 38 30 24 16 1.4 275 575 575 YHK-ECM 40-2 4.3 3.1 2.2 3.2 2.2 1.6 744 524 385 15.1 9.4 4.6 5.2 3.6 2.6 13.1 6.6 3.6 YHK-ECM 40-6 3.9 2.8 2.1 3.0 2.0 1.5 676 483 359 10.5 5.7 3.5 3.4 2.5 2.0 288 217 170 9.0 5.5 3.5 710 445 310 54 43 33 45 34 24 31 2.1 275 575 575 YHK-ECM 50-2 5.0 3.9 2.6 3.7 2.8 1.8 864 666 441 19.7 12.4 5.9 6.2 4.6 3.0 17.7 10.5 4.7 YHK-ECM 50-6 4.5 3.5 2.4 3.5 2.6 1.7 779 608 409 13.1 8.4 4.1 3.8 3.1 2.2 326 263 189 11.0 7.5 4.5 880 610 360 60 50 37 51 41 28 230V/1ph/50hZ 62 2.1 275 575 575 YHK-ECM 65-2 6.3 5.2 4.2 4.7 3.8 3.0 1 089 885 723 22.7 15.6 10.9 8.0 6.4 5.1 19.5 12.8 8.7 YHK-ECM 65-4 6.5 5.3 4.3 4.8 3.8 3.1 1 120 908 740 19.8 13.6 9.4 9.4 7.5 6.1 805 649 528 22.5 15.5 10.5 1 165 870 630 48 39 33 39 30 24 53 3.0 303 820 820 YHK-ECM 95-2 10.8 7.7 5.3 7.9 5.5 3.7 1 848 1 328 909 33.6 18.5 9.4 12.7 8.8 5.9 28.8 14.9 7.2 YHK-ECM 95-6 9.9 7.2 5.0 7.4 5.2 3.5 1 697 1 233 856 30.1 17.0 8.8 9.5 7.2 5.2 818 616 449 18.0 11.0 6.5 1 770 1 130 710 57 47 34 48 38 25 108 4.0 303 820 820

Sensible cooling capacity 4 Pipes [kW] (1) Water flow in cooling 4 pipes [l/h] Pressure drop in cooling 4 pipes [kPa] Heating capacity 4 pipes [kW] Water flow in heating 4 pipes [l/h] Pressure drop in heating 4 pipes [kPa] Air flow [m3/h] Sound power level [dB(A)] Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Water content (2 pipes) [l] Dimensions (4) (1) (1) (3) (3) (3)

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YFCC Coanda Hydro Cassette


2 & 4 pipe system A complete range from 0.9 kW to 4.0 kW

Wired controls
BR Remote three speeds controller TR BR + Electronic thermostat and Summer/Winter switch ATR Automatic TR DTR Digital Automatic Remote controller TMO 503 SV2 Digital Automatic Remote controller to be mounted in the standard light wall box DRC - DI Centralized controller up to 60 terminals

Infrared control
Thanks to its unique diffuser, YFCC cassette units generate an airflow with a coanda effect. The unit is suitable for installation in a suspended ceiling. Air intake is from the bottom while the air is supplied parallel to the ceiling. The resulting coanda effect creates excellent draft free distribution of the air inside the room. Units can be supplied with 1 coil (2 pipe system) with optional electric heating element, or with 2 coils (4 pipe system) with one or two rows.

Features
 Coanda effect units, allowing easier and cheaper installation Cooling duty from 0.9 to 4.0 kW 2 & 4 pipes systems in all range 3 sizes: 600 x 600, 600 x 1000 & 600 x 1200 2/3 way valves fitted or supplied loose in all range Left and right hand (optional) water connections 6 fan speeds (3 pre-wired) Air throw till 7.6m (cooling) and 9.5m (heating) ECM variable speed motor option

Selection software Coanda effect

42/43

YFCC Coanda Hydro Cassette


0.9 to 4.0 kW

Technical features
Model -2 pipes Total cooling capacity 2 Pipes [kW] (1) max med min max med min max med min max med min max med min max med min max med min max med min max mm mm mm max med min max med min max med min max med min max med min max med min max med min max med min max mm mm mm YFCC 130 1.5 1.1 0.9 1.2 0.8 0.7 6.1 3.3 2.4 1.9 1.3 1.1 4.9 2.6 1.8 280 180 140 52 41 35 43 32 26 49 309 592 592 YFCC 130+1 1.5 1.1 0.9 1.2 0.8 0.7 6.1 3.3 2.4 1.5 1.1 0.9 3.6 2.1 1.6 280 180 140 52 41 35 43 32 26 49 309 592 592 YFCC 140 1.7 1.2 1.0 1.3 0.9 0.7 12.9 6.7 4.7 2.1 1.4 1.1 10.7 5.4 3.7 280 180 140 52 41 35 43 32 26 44 309 592 592 YFCC 230 YFCC 240 2.4 2.6 1.6 1.7 1.4 1.4 1.8 1.9 1.2 1.2 1.0 1.0 7.6 12.1 3.9 6.0 2.9 4.4 2.9 3.1 1.9 2.0 1.6 1.7 6.3 10.2 3.1 4.8 2.3 3.5 380 380 240 240 200 200 48 48 36 36 33 33 39 39 27 27 24 24 230V/1ph/50Hz 59 49 309 309 592 592 970 970 YFCC 230+1 2.4 1.6 1.4 1.8 1.2 1.0 7.6 3.9 2.9 2.4 1.7 1.5 2.0 1.2 0.9 380 240 200 48 36 33 39 27 24 230V/1ph/50Hz 44 309 592 970 YFCC 330 3.3 2.8 2.0 2.5 2.1 1.4 16.2 12.1 6.4 4.0 3.4 2.3 13.4 9.8 5.2 540 440 290 52 46 35 43 37 26 44 309 592 1 192 YFCC 330+1 3.3 2.8 2.0 2.5 2.1 1.4 16.2 12.1 6.4 3.3 2.9 2.1 4.3 3.4 2.0 540 440 290 52 46 35 43 37 26 59 309 592 1 192 YFCC 340 4.0 3.6 2.5 3.0 2.6 1.8 15.5 12.6 6.7 4.8 4.2 2.9 12.6 10.0 5.5 620 540 360 55 52 41 46 43 32 72 309 592 1 192

Sensible cooling capacity 2 Pipes [kW]

(1)

Pressure drop in cooling 2 Pipes [kPa]

(1)

Heating capacity 2 pipes [kW]

(2)

Pressure drop in heating 2 pipes [kPa]

(2)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions Model -4 pipes Total cooling capacity 4 Pipes [kW]

(4)

Height Width Depth

(1)

Sensible cooling capacity 4 Pipes [kW] (1)

Pressure drop in cooling 4 pipes [kPa]

(1)

Heating capacity 4 pipes [kW]

(3)

Pressure drop in heating 4 pipes [kPa]

(3)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions

(4)

Height Width Depth

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Room temperature 20C - Water inlet temperature: 70/60C (4) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YHM Hydro High Wall


2 pipe system A complete range from 1.7 kW to 4.7 kW

The York YHM high wall fan coils harmoniously combine the needs of performance, silence, ease of installation and simple maintenance, through a range of four models.

Features
Wired control or infrared control Automatic air sweep  3 way valves fitted (YHMH 20V and 30V models) or 2 way valves supplied loose in all range Condensate collection tray Air filter included Heat exchange coil
TR - Wired control Remote three speeds controller, electronic thermostat and Summer/Winter switch ATR - Wired control Automatic TR

Selection software

2 Way Valve ON/OFF with thermoelectric actuator. Suitable for the connection with 12 mm pipes

Rear Frame for installation of valves (accessory)

Electronic Infrared Control

FX03 Terminal unit controller BacNET and N2 Metasys network compatible

44/45

YHM Hydro High Wall


1.7 to 4.7 kW

Technical features
Model Total cooling capacity [kW] (1) max med min max med min max med min max med min max med min max med min max mm mm mm YHMY(H) 20 2.2 1.9 1.7 1.8 1.6 1.5 2.7 2.3 2.0 436 376 334 45 38 32 36 33 29 24 270 845 180 YHMY(H) 30 2.8 2.0 1.8 2.5 1.8 1.6 3.6 2.6 2.2 632 522 403 52 42 39 43 33 30 230 / 1 / 50 + E Height Width Depth 28 270 845 180 40 298 920 200 50 298 920 200 YHMY(H) 40 4.0 3.4 3.1 3.4 2.9 2.6 4.9 4.2 3.8 780 691 570 55 52 48 46 43 39 YHMY(H) 50 4.7 3.9 3.4 3.6 3.3 2.9 5.8 4.9 4.2 920 810 697 60 56 53 51 47 44

Sensible cooling capacity [kW]

(1)

Heating capacity [kW]

(2)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions

(3)

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Technical features with valve fitted


Model Total cooling capacity [kW] (1) max med min max med min max med min max med min max med min max med min max mm mm mm YHMY(H) 20 1.7 1.6 1.2 1.3 1.1 0.9 2.4 2.0 1.7 450 383 323 53 47 41 44 38 32 230 / 1 / 50 + E Height Width Depth 50 270 845 180 60 298 920 200 YHMY(H) 50 3.2 2.8 2.4 2.4 2.1 1.8 4.5 3.9 3.4 650 560 490 59 52 47 50 43 38

Sensible cooling capacity [kW]

(1)

Heating capacity [kW]

(2)

Air flow [m3/h]

Sound power level [dB(A)]

Sound pressure level [dB(A)] Power supply [V-ph-Hz] Power input [W] Dimensions

(3)

(1) Room temperature 27C d.b., 19C w.b. - Water temperature 7/12 C (2) Room temperature 20C - Water inlet temperature: 50C (3) Sound pressure level in a 100 m2 room, at 1,5 m distance and riverberating time of 0,3 s. * Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YORK Close Control units


Maintaining a constant temperature, purity and humidity of air is essential for ensuring a stable environment for critical electronic and computer equipment, this is why there is the need for close control air conditioning. Unlike comfort air conditioning, close control systems must operate constantly 24/7 requiring high reliability and minimal power consumption. Johnson Controls knows that no two close control requirements are the same, this is why the YORK range of custom close control units offers quiet, compact and energy efficient equipment that can be configured to needed requirements.

46/47

An extensive offering
 cooling capacities of up to 220kW (chilled water) or 100kW (direct expansion) with optional free cooling models. Up flow or down flow configuration, either as self-contained packaged units or suitable for connection to remote condensers, are also available  optional direct expansion units fitted with scroll compressors, which have much lower noise and energy consumption than reciprocating compressors R410a refrigerant units available  optional Free Cooling coil to reduce energy consumption required through use of mechanical cooling  plug fan with Electronically Commuted EC fans option, to allow fully modulating control of airflow  low component face velocities, for a lower total pressure drop and reduced energy consumption  minimised dimensions, enabling one of the markets greatest ratios between sensible cooling capacity and base foot print

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

YORK YC-P Series Close Control Air Conditioners


A complete range from 6.6 kW up to 200 kW

High energy efficiency and minimum environmental impact


P Series air conditioners for close control applications are specialised machines with design and operating features which clearly differentiate them from standard air conditioning units. The P Series air conditioners offer very high energy efficiency values in all operating conditions which translates into less CO2 emissions and particularly low running costs. Though optimised for use in data centers and telephone exchanges, they are equally valid in special applications such as measurement laboratories, TV recording studios, museums, control rooms for electricity power stations and railway junctions and other areas where there are prevalent sensible thermal loads and crowding is negligible. Their application is also ideal in widely varied industrial sectors: optics, electronics, electromedical equipment, electronic equipment production, musical instrument production etc.

Optimal efficiency
Johnson Controls P Series design offers the highest sensible cooling capacity with the minimum footprint possible, which translates into optimal ratio levels of cooling capacity to footprint area. This is an important feature in reducing the space needed by machinery, allowing more room in the space for IT equipment. This advantage is especially important given the progressive increases in capacity required by data centers and other computer applications which, over time, need the addition of extra air conditioners. Clean efficiency is also ensured by the use of the R-410A refrigerant, respectful to the ozone layer.

48/49

Features and performance


Silent operation and high energy efficiency
 The scroll compressors of YORK YC-P Series air conditioners with direct expansion coil are quieter than conventional reciprocating compressors.  Scroll compressors have a much lower energy consumption than reciprocating compressors.  The cooling coils of the downflow units (YC-UP), both in chilled water and direct expansion versions, have aluminium fins with a hydrophylic treatment that alleviates the risk of condensation and the coil face being covered with water, which would compromise the thermal performance and therefore the air conditioning capacity. The aluminum fins have specialisation of the TURBO/COIL profile, perfected in the LU-VE SpA research labs. They produce a predetermined turbulence of the crossing air which therefore increases the coefficient of heat exchange.  The use of the environmentally friendly refrigerant HFC R410A does not contribute to the depletion of the ozone layer (R134a available on request).  Thanks to its larger surface area, the filter on the coil allows lower face velocity, which results in lower pressure drop.  The lower energy consumption of these air conditioners, at the same efficiency, results in a much reduced TEWI (Total Equivalent Warming Impact). The application of EC plug fans reduces both energy consumption and noise levels.

Microprocessor regulation
The Standard digital microprocessor  allows management of all typical air-conditioning functions: cooling, heating, humidification, dehumidification and filtering  ensures a regular and optimised operation as to both performance and consumption, providing as well alarm management and self-diagnosis  in case of need to install any component requiring analogue control (modulating valve or electronic hot-gas by-pass valve), an optional modulating controller, with semigraphic display, shall be installed in lieu of standard. This alternative controller is also installed as standard microprocessor on special versions such as Free cooling, Two Sourcesand Fresh air units.

Local network management or remote control


YORK YC-P Series air conditioners are capable of standalone operation, local private network with multiple units (up to 12) or fully integrated with Metasys Building Management System from Johnson Controls. In local network applications, one machine is the master, and the remaining slaves follow the same algorithm. The slave units are rotated at predetermined intervals and switch to the master role to balance the number of working hours of the compressors. In remote applications, the machines can be controlled from remote positions interfacing with common Building Management Protocols such as BacNET, LON and Modbus, either via GSM Modem or TCP/IP Internet Protocol. For total integration with Johnson Control Metasys Building Management Systems (BMS) the units can be equipped with an RS485 card working with BacNET MS/TP protocol.

Downflow unit with 2 fans and side compartment; full front access for both fans (covered) and technical compartment

Cooling circuit
The air conditioners with direct expansion coil have a frigorific circuit equipped with: scroll compressor with all necessary protective devices, high pressure (manual reset) and low pressure (automatic reset) switches, thermal expansion valve, dehydrating filter with refrigerant sight glass. YC-OPA, YC-UPA models for pairing with remote condensers, are already equipped with a pressurisation nitrogen charge. The refrigerant charge, and the oil top-up (if required), shall be made by the installer on site. YC-OPA and YC-UPA air conditioners in self-contained packaged format with built-in water-cooled condensers (accessory), are supplied with full refrigerant and oil charge.

Downflow unit with 2 fans and side compartment; full front access for both fans (not covered) and technical compartment on the side. No side maintanance space is required for accessing components

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

Electronic expansion valve (*)


Electronic expansion valves are one of the most recent pieces of equipment that enable us to improve the energy efficiency at partial loads of direct expansion machines. These valves are installed at the inlet of the evaporator, substituting the traditional thermostatic expansion ones: this allows more precise control of the quantity of refrigerant entering the evaporator, and guarantees good capacity regulation, typically between 100% and 50%. Electronic expansion valves also allows control of the amount of overheated gas at the outlet of the evaporator, thus allowing a significant reduction of the condensation pressure during winter or night-time operation whilst maintaining the evaporation pressure unchanged. Adoption of the electronic expansion valve (optional) guarantees a significant increase of the EER values.

Control Panel
All the units are equipped with a complete control panel with main isolator switch. Magnetothermic switches, contactors, and all necessary protection is provided, as required by legal codes and standards. The control panel of the units equipped with compressors (A as third letter of the identification code) has as standard a phase sequencer, which prevents the compressor from getting damaged when counter running. Also, the control panel has two spare terminals for remote indication of a cumulative alarm, as well as two terminals for starting up and stopping the unit from remote position. The control panel does not include the fan speed controller(s) for the fans of the air cooled remote condensers (winter control). This device is included as standard in the CEA and CEA/LN air cooled condensers from Johnson Controls. Should you decide to match the unit with a condenser from another manufacturer, the controller(s) can be ordered as accessory.

One or two completely independent compressors


Models with 1 as the last digit of the unit model number have a single circuit and a single compressor. Those with 2 as the last digit on the other hand have two completely independent refrigerant circuits and two compressors. The circuits are fitted with all the safety and regulation devices necessary for efficient and reliable operation. The evaporator coil can be single or double circuit depending on the number of compressors.

Hydraulic circuit
Air conditioners with chilled water coil, YC-OPU and YC-UPU, include a finned coil and a three-way throttling motorised valve for water flow regulation. The hydraulic circuit is provided with copper tubes with anti-condensate insulation. The coils are optimised for both water with a temperature of 7/12 and for higher ones such as 15/20. The standard throttling valve (3 points) allows good modulation of the cooling capacity as a function of the environmental conditions, especially with constant thermal loads.

Modulating controller display and keypad

Large surface filters


The units are equipped with self-extinguishing media class G4 filters. The filters are installed inclined before the cooling coil in order to offer a larger surface and allow lower air crossing speeds, with lower energy consumption. A 450 mm high duct (accessory) can be installed for holding a F7 class filter, vertically on supply air discharge.

Modulating regulation of the cooling capacity (**)


If a very precise regulation and high response speed are required, a modulating valve (optional) can be installed in lieu of the throttling one. The installation of this valve is recommended in case of functionment with a lot of fresh air. However, the modulating valve needs an analogue signal, not digital, so the installation of the optional modulating controller is necessary.

Design suitable to civil environments


YORK YC-P Series air conditioners have a pleasant and functional design, suitable for installation in civil environments. Their structure consists of aluminium profiles and closing panels hinged on them. Both panels and profiles are coated with a dark grey PVC layer (anthracites), thermoacoustically insulated by polyurethane layer, and further coated with an anti scratch plastic film. Two versions are available for up flow units (YC-OP): front grille & top air discharge (standard), or blind front panel, suction from the bottom and top discharge (optional).

(*) units equipped with frigorific circuit (**) units equipped with chilled water coil

50/51

Fan section
Standard fans
The standard fan section is made up by one or more backward curved, free running impeller, radial fans (plug fan) with single speed motors which offer a particularly low noise level as well as a high efficiency. The free running impeller assures a very high efficiency and an easy cleaning of the blades too. These fans offer a high available static pressure, perfect for most applications. The final air flow comes as a consequence of the real pressure drop of the installation; anyhow it can be calculated through our selection software. Standard fans with AC motors have two operating speeds and therefore two different airflows and static pressures, which can be selected through their terminal strip cabling.

Regulation Options
Johnson Controls provides four different alternatives for the regulation of the airflow of the EC fans depending on the requirements of the installation: 1.  Constant fan rotation speed. The available high static pressure is ideal for most applications. The effective air flow depends on the real pressure drop of the aeraulic system of the installation, however it can be calculated through Johnson Controls computerised selection program. 2.  Constant airflow independent of the pressure drop of the filters. In order to maintain a constant airflow, an internal sensor guides the microprocessor management system to vary the airflow handled by the fan, depending on the degree of clogging of the filters. This ensures that insufficient cooling does not occur due to reduced airflow arising from dirty filters. 3.  Variable airflow depending on the cooling capacity required by the installation. This is the classic VAV (Variable Air Volume) plant arrangement which responds to increased demand by a proportionate increase in airflow and vice versa. This type of plant offers interesting energy advantages at partial loads, which occur extensively throughout the year, especially at night. 4.  Airflow as a function of pressure in the raised floor. This regulation alternative is envisaged for plants with raised floors where the air is distributed under the floor itself. The microprocessor management system maintains constant under-floor pressure. In particular, in very large areas subdivided into multiple local zones with partition dampers driven by individual thermostats, constant regulation of the pressure is necessary to avoid imbalances in the distribution of the air.

Electronically commutated fans (EC) for a perfect air flow regulation


Plug fans, made up by one or more backward curved, free running impeller, radial fans, offer several advantages: - particularly silent operation; - extremely high performance; - easy cleaning of the blades. Plug fans factory fitted with EC (electronically commutated) constant current brushless motors with external rotors are the latest innovation in energy saving when it comes to the fan sector. They are about 25-30% more efficient than traditional asynchronous alternating current motors. They also allow continuous speed variation depending on the external sensor signal on the microprocessor control of the machine, without the need for an inverter or other electronic devices. At equal operating conditions, the combination of EC motors and plug fans therefore offers several advantages: - better functionality; - improved energy efficiency; - lower sound level; - absence of vibration in operation and soft start (lower absorbed current on starting).

Air Handling Systems & Terminal Devices

york airside products

Special versions
Water to air free cooling: using renewable energy sources
YC-OPW/FC, YC-UPW/FC air conditioners are equipped with a Free cooling system consisting of an additional chilled-water cooling coil integrated in the aluminium fins of the units direct expansion one, with a three-way modulating valve controlled by the modulating controller. As long as the outside conditions allow the water to respond totally or partially to the cooling request, the controller cuts out or minimises the compressors intervention, so reducing substantially the energy consumption. The water cooled condensers of the frigorific circuit are equipped with a pressostatic system for the regulation of the condensing pressure (flooding valves). The pumps and the expansion tank are not included in Johnson Controls supply. Units in free cooling version cannot install the optional hot water heating coil, only the electric one, and have as standard the analogue modulating controller. The system widely uses the outdoor aira renewable energy sourcein lieu of or in addition to the mechanical cooling.

Two Sources option utilising excess energy from building HVAC systems
This system consists of the same chilled-water cooling coil as the Free cooling, but fed by the building water chiller. A built in frigorific circuit enters in operation in case of lack of chilled water. The result is the maximum security or a remarkable reduction of both consumption and running costs. This system can also use the direct-expansion coil circuit as primary cooling source and, in case of an emergency, the chilled-water coil connected with the tap water network. The Two Sources version is available for units with direct expansion circuit YC-OPA./TS, YC-UPA./TS as well as units with built in water cooled condenser (accessory) and with double chilled water coil YC-OPU/TS, YC-UPU/TS: one for district water and the other for tap water or water from a chiller (emergency). Units in Two Sources cannot install the optional hot water heating coil, only the electric one, and have as standard the analogue modulating controller.

50 kW upflow 2 circuits direct expansion air conditioner

52/53

Fittings and accessories


Numerous accessories and options are available for the P Series air conditioners to personalise the installation depending on the requirements of the plant and its design. Divided by function, they include:

Free cooling or two sources


Additional Free cooling circuit. Additional Two sources circuit.

Direct expansion unit cooling capacity regulation


Electronic expansion valve.  Electronic hot-gas injection system for the regulation of cooling capacity (100-10%).

Alarms
Water alarm (supplied loose). Out-of-range air discharge temperature alarm. Smoke/fire alarm terminals.

Heating, reheating and humidification


 Single-step or double-step low thermal inertia electrical heating/reheating coil.  Immersed-electrode modulating humidifier and dehumidification control.  Humidity sensor for the single control of dehumidification.

Water cooled condensers and pressostatic valves


Welded stainless steel water cooled plate condenser.  2 way pressostatic valve (only if the water condenser is selected).

Boards and sensors


 Humidity sensor and board for external humidification control not supplied by Johnson Controls.  RS 485 communication board.

Sound proofing devices


 Sound damped duct for air suction or discharge (h=550 mm). Allows a reduction of approx 4 dB(A) of the SPL of the unit.  Double layer sound damping panels. Reduces SPL by approx 2 dB(A) in upflow units (OP series), and approx.4 dB(A) in downflow units ((UP series).  Double-layer sandwich thermo-acoustic insulation panels.

Dampers
 Gravity-operated overpressure dampers on the air outlet (OP series).  Motorised overpressure dampers on the air intake (UP series).

Panels and base


Blind front panel (OP) and open base for bottom air intake. Front panel with grille in the lower part (UP) and closed base.

Under bases
 Adjustable under base (OP only). (Precise height to be specified with order).  Adjustable under base with air deflector (UP only). (Precise height to be specified with order).

Plenum
 Plenum (h=550 mm) for air discharge or intake with front grille.  Plenum (h=550 mm) for air discharge or intake with front and side grilles.

Fans and filters


 Electronic EC fans with incorporated inverter for constant rotation speed regulation.  Electronic EC fans with incorporated inverter for the regulation of air flow in relation to the required cooling capacity.  Electronic EC fans with incorporated inverter for the regulation of constant pressure in the raised floor.  Electronic two-speed AC fans.  F7 filter to be installed on the air intake as substitute for the standard G4.  Monophase condenser-fan rotation speed variator

Air Handling Systems & Terminal Devices

york airside products

Performance at JOHNSON CONTROLS test conditions*


Technical Characteristics
YC-OPA: direct expansion air conditioners with air cooled or water condensers and up-flow air supply
Models Performances Total cooling capacity Sensible cooling capacity Airflow EER Sound pressure level Dimensions & weight Lenght Depth Height Net weight mm mm mm kg 750 630 1990 170 750 630 1990 170 750 630 1990 170 860 880 1990 210 860 880 1990 270 750 880 1965 270 1410 880 1990 300 1410 880 1990 315 1750 880 1990 330 1750 880 1990 400 1750 880 1990 420 1750 880 1990 440 2300 880 990 420 2300 880 990 490 2300 880 990 315 2640 880 1990 330 dB(A) kW kW m3/h 7.2 6.7 2200 3.09 49 11.2 10.6 3200 3.11 49 14.3 11.8 3200 3.15 49 20.9 19.8 7000 3.12 56 25.2 21.7 7000 3.05 56 30.4 29.4 8700 3.10 58 30.6 27.7 8700 3.18 58 38.2 31.0 8700 2.96 58 33.8 31.5 2.55 63 47.2 46.2 3.38 63 42.2 41.5 3.12 63 51.2 45.0 3.06 63 64.3 58.2 3.21 68 67.5 59.8 3.11 68 84.3 67.3 3.14 68 96.0 83.5 3.41 69 71 111 141 211 251 301 302 372 361 461 422 512 612 662 852 932

14500 14500 14500 14500 17900 17900 17900 22500

* The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 45% RH; for chilled water: 7/12C; The SPL is referred to 2 m distance, 1,5 m height, free field and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Efficiency Ratio = Total cooling capacity / Compressors + fans + condensers fans power input. The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.

Technical Characteristics
YC-UPA: direct expansion air conditioners with air cooled or water condensers and down-flow air supply
Models Performances Total cooling capacity Sensible cooling capacity Airflow EER Sound pressure level Dimensions & weight Lenght Depth Height Net weight mm mm mm kg 750 630 1990 170 750 630 1990 170 750 630 1990 170 860 880 1990 210 860 880 1990 255 750 880 1965 270 1410 880 1990 300 1410 880 1990 315 1750 880 1990 330 1750 880 1990 400 1750 880 1990 420 1750 880 1990 440 2300 880 990 420 2300 880 990 470 2300 880 990 315 2640 880 1990 330 dB(A) kW kW m3/h 7.2 6.7 2200 3.09 49 11.2 10.6 3200 3.11 49 14.3 11.8 3200 3.15 49 20.9 19.8 7000 3.12 56 25.2 21.7 7000 3.05 56 30.4 29.4 8700 3.10 58 30.6 27.7 8700 3.18 58 38.2 31.0 8700 2.96 58 33.8 31.5 2.55 63 47.2 46.2 3.38 63 42.2 41.5 3.12 63 51.2 45.0 3.06 63 64.3 58.2 3.21 68 67.5 59.8 3.11 68 84.3 67.3 3.14 68 96.0 83.5 3.41 69 71 111 141 211 251 301 302 372 361 461 422 512 612 662 852 932

14500 14500 14500 14500 17900 17900 17900 22500

* The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 45% RH; for chilled water: 7/12C; The SPL is referred to 2 m distance, 1,5 m height, free field and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Efficiency Ratio = Total cooling capacity / Compressors + fans + condensers fans power input. The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.

54/55

Performance at JOHNSON CONTROLS test conditions*


Technical Characteristics
YC-OPU: with chilled water coil and up-flow air supply
Models Performances Total cooling capacity Sensible cooling capacity Airflow Sound pressure level Dimensions & weight Lenght Depth Height Net weight mm mm mm kg 750 630 1990 155 750 630 1990 155 860 880 1990 180 860 880 1990 250 1750 880 1990 450 1750 880 1990 450 2640 880 1990 650 3496 880 1990 900 kW kW m3/h dB(A) 10.6 9.9 2200 47 19.6 17.2 3400 49 31.4 31.4 7800 57 41.3 38.8 8300 56 71.2 68.0 16000 59 92.5 83.2 17000 61 148.4 131.2 26400 64 178.8 148.7 34800 82 10 20 30 50 80 110 160 220

* The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 45% RH; for chilled water: 7/12C; The SPL is referred to 2 m distance, 1,5 m height, free field and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Efficiency Ratio = Total cooling capacity / Compressors + fans + condensers fans power input. The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.

Technical Characteristics
YC-UPU: with chilled water coil and down-flow air supply
Models Performances Total cooling capacity Sensible cooling capacity Airflow Sound pressure level Dimensions & weight Lenght Depth Height Net weight mm mm mm kg 750 630 1990 155 750 630 1990 155 860 880 1990 180 860 880 1990 250 1750 880 1990 450 1750 880 1990 450 2640 880 1990 650 3495 880 1990 900 kW kW m3/h dB(A) 11.1 8.4 2400 47 19.3 13.8 3500 49 30.6 24.5 7800 57 39 30 8300 56 69.2 53 16000 59 88 64.9 17000 61 151 106.5 26400 64 175.8 129.5 34000 82 10 20 30 50 80 110 160 220

* The performances are referred to: refrigerant R410; condensing temperature: 45C; inlet air: 24C - 45% RH; for chilled water: 7/12C; The SPL is referred to 2 m distance, 1,5 m height, free field and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Efficiency Ratio = Total cooling capacity / Compressors + fans + condensers fans power input. The above performances dont consider the heat generated by the fans which must be added to the thermal load of the system.

Air Handling Systems & Terminal Devices

york airside products

YORK YPRE RTR/RTP SERIES


Air to air packaged rooftop units
Cooling only and heat pump versions Refrigerant R407C Extreme flexibility Cooling range from 110 kW to 406 kW

Johnson Controls recognizes that large, single packaged units can have a significant impact on a buildings energy bill. For that reason, YORK YPRE units have been designed to address the economic concerns of facility owners and designers.
High-efficiency scroll compressors, multiple-step capacity control, and fully modulating gas heat deliver superior energy performance and better comfort. The microprocessor control ensures the proper quantity of ventilation air, eliminating the cost of conditioning excess air. An airside economizer enables compressor-free cooling when outdoor air is cool and dry, and Variable Speed drives significantly reduce the power consumption of the drive motors. An option for cross flow plate heat exchangers gives added heat recovery and can reduce energy costs even further.

Application Flexibility
Flexible design configurations simplify the design process,making YORK YPRE units applicable for virtually any building application: commercial buildings, schools, hospitals, and more. Airflow configurations support variable air volume (VAV), changeover/bypass, and constant-volume applications. Supply-duct connections are configurable in multiple orientations. In addition to cooling-only models, available heating configurations include staged gas, modulating gas, electric resistance and hot water.

56/57

Air to air packaged units with Scroll compressors and refrigerant R407C
The YORK YPRE series of units have been conceived to be extremely flexible and to offer a wide range of custom- made options. They are direct expansion packaged air to air units, suitable for outdoor installation, designed for air conditioning of large areas, pre-configured for direct connection to the air distribution ducts. They represent, therefore, both from the performance and the economical perspective, the ideal solution for the summer cooling and the winter heating of supermarkets, commercial centres, exhibition halls, restaurants, hospital, facilities for food production /conservation and laboratories. The roof-top units-are available in the following versions: RTR.K cooling only (refrigerant R407C) RTP.K r everse cycle heat pump (refrigerant R407C) The units can be supplied, depending on the different air treatment required, in the following three configurations, as detailed in the following pages: 2S  Mixing of re- circulating and external air (2 dampers) 3S  Mixing of re-circulating and fresh air and discharge of the exhaust air through a suitable fan (3 dampers) TR  All re-circulating air (no mixing between re-circulating and external air) In order to allow the installation of these units in an increased range of applications and to conform with regulations concerning the energy saving, the following options can be installed on the units: Cross-flow heat recovery. Air heating by gas fired burner.  Air heating by water coil, with supplementary gas boiler. The compressors are of high efficiency scroll hermetic type, with in-built protection against high temperature, installed on rubbertype vibration dampers and provided with crankcase heater. The air treatment coils are made of copper pipes suitable for refrigerant media, and high efficiency aluminium fins. There is a stainless steel grade 304 drip pan for the internal refrigerant coil. The external heat exchange coils are also made of copper pipes and high efficiency aluminium fins. Filtering section made of washable pleated filters in polyester with G4 metal frame (in conformity with EN779:2002 standard); the filter cells are easily removable, through a hinged opening door, for periodical cleaning and/or replacement. Air outlet fan section with DIDW forward curved centrifugal fans, statically and dynamically balanced, installed on rubber-type vibration dampers. The fans are driven, through belt and pulley transmissions, by 4-pole tri-phase electrical motors on slides; the motor pulley is of variable diameter type. It is also provided with a device to switch off the unit in case of accidental stoppage of the fan. Fans for condensing coils are of axial type with high aerodynamic efficiency blades directly joined to electrical motors suitable for fans speed regulation. The motor are provided with in-built thermal protection. An external mesh protection fitted for safety. The units are supplied with two cooling circuits to increase their reliability and to adjust the cooling capacity to the exact requirements, keeping a high energy efficiency. Each circuit is made by a thermostatic expansion valve with external equalizer, liquid sight glass, safety valve, high and low pressure switches; in case of heat pump version, besides the above components, there are also a liquid receiver with shut-off valve, an additional thermostatic valve for winter operation, the 4-way valve for the cycle inversion and check valves on the liquid line. Electrical control panel compliant to CE standard, complete with door interlock isolator, fuses for compressors, remote control switches, protection switches for the centrifugal fans motor, low voltage auxiliary circuit and terminal board. All units are provided with electronic microprocessor to automatically manage all the functions of control, status alarm and diagnostics. The units are supplied complete with R407C refrigerant charge and non-freezing oil. Before delivery, all units are factory tested. The units are made in conformity with the European standards in force (regarding Low voltage Directive, Electromagnetic compatibility Directive, PED Directive and Machine Directive).

Main Components
The structure is comprised of a base-frame made in carbon steel profiles, protected against corrosion by an epoxy powder primer, kiln-polymerized, painted with polyester powder. The structural frame is made from aluminium profiles and complete with aluminium panels; the internal division plates are made of galvanized steel. The external panels of the sections in contact with the treated air are of 50mm thickness sandwich type with the internal surface in galvanized steel plate, insulated by a high-density foam polyurethane sheet. The parts of the base-frame and the internal steel plates in contact with the conditioned air are thermally insulated with close-cell insulating material. The external panels can be easily dismantled, so to allow access to internal components. The customer can gain to the main components of the cooling circuits, to the air filters and to the control panel through hinged doors and turn closures, to make the maintenance operations easier.

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

york airside products

Possible Configurations
Mixing of return and external air, version 2S This configuration allows the mixing of the ambient return air with the external air. There is an adjustable damper on the external air inlet for correct mixing; the damper is pre-arranged for motorization. Usually this damper is ducted; alternatively, it is possible, on demand, to supply weatherproof protection. On the return air inlet there is a damper, also pre-arranged for motorization.
inlet of RETURN AIR outlet of TREATED AIR

Mixing of ambient and external air, version 2S

external air

Mixing of return and external air with exhaust section, version 3S The version 3S is similar to the previous one, with an additional section and a centrifugal fan. The unit is provided with two dampers for the discharge of the exhaust air and for the inlet of the fresh air, plus a third internal damper for the re-circulating air. The three dampers are controlled by motors, allowing the operation with all re-circulating air, with a mixing of recirculating air and external air or with all external air and total exhaust of the ambient return air. The control of the dampers can be managed by an external signal 0-10V, or on demand, according to the thermohygrometric conditions (free-cooling operation) or to the quality of the internal air.
inlet of RETURN AIR outlet of TREATED AIR

Mixing of ambient and external air with exhaust section, version 3S


expulsion external air

All re-circulating air with no mixing, version TR This is the basic version on which the 2S and 3S versions are based. The unit is pre-arranged for the air inlet directly from the ambient space. As an alternative to all air to air units, it is possible to provide water to air units, with external refrigerant/water exchangers, for use in water loop plants (please contact your local Sales Dept.). On demand, the fans of the external coils could be of ductable type so to allow the indoor installation (please contact your local Sales Dept.)

All re-circulating air with no mixing, version TR

inlet of RETURN AIR

outlet of TREATED AIR

58/59

Available Options
1M / 2M CENTRIFUGAL FANS FOR HIGHER SYSTEM PRESSURES In case of ducts with high pressure drops, it is necessary to increase the available pressure to the inlet and outlet centrifugal fans, increasing the power of the electrical motor and consequently adjusting the transmission. AF CLOGGED FILTER ALARM A suitable differential pressure switch detects an excessive pressure drop on the air filters due to their dirty condition; the control system of the unit displays the problem, without switching off the unit. AFL SMOKE ALARM In case of smoke, detected by an optical sensor, the unit is switched off and the motorized dampers will be suitably positioned. BC HEATING WITH WATER COIL Coil with copper pipes, aluminium fins and copper manifolds, used for winter heating. The coil is fed by external hot water through a suitable 3-way mixing valve, controlled by the microprocessor. BC1 WATER POST-HEATING COIL Coil with copper pipes, aluminium fins and copper manifolds, located after the evaporating coil; this coil is used to keep the air temperature within the requested value, when the evaporator is used to reduce the supply air relative humidity. The coil is fed by external hot water through a suitable 3-way mixing valve, controlled by the microprocessor. BG HOT GAS POST-HEATING COIL Coil with copper pipes, aluminium fins and copper manifolds; this coil is used to re-adjust the air temperature to the requested value, when the evaporator is used to reduce the supply air relative humidity. The coil is supplied by the hot gas coming out from the compressor, through a solenoid valve controlled by the microprocessor, therefore there is no need for external heating sources. BT REGULATION OF CONDENSING PRESSURE Device for the regulation of the condensing pressure, through the control of the fans speed rotation. In case of cooling operation, the phase regulation electronic equipment reduces the external fans speed rotation when the condensing pressure decreases, so as to allow suitable working conditions. Also suitable for use for low external air temperatures. F FREE-COOLING OPERATION On the base of the comparison between the internal and the external temperature, the microprocessor controls the motorized dampers, to use, in the best way, the energy in the external air so to satisfy the heating loads. In this way, the working time of the compressors and of the external fans is remarkably reduced and, as a consequence, also the electrical consumption. On demand, it is possible to use enthalpic control of freecooling, so to use the external air for controlling the internal relative humidity, when possible. Where the unit is also equipped with heat recovery, the standard version will be provided with 3 dampers. On demand, it is possible to supply a 5 damper version. FT BAG FILTERS Rigid bag filters with filtering efficiency F7 (in conformity with EN779:2002), complete with G4 pre-filters (in conformity with EN779:2002). The filters are placed at the inlet of the air treatment coil, so to assure a high filtering efficiency, without too high pressure drops. However, note that the length of the unit increases by 500 mm. F5 F5 PLEATED FILTERS Glass fibre washable pleated filters with F5 metal frame (in conformity with EN779:2002). The filters are placed at the inlet of the air treatment coil, instead of the standard G4 filters.

Air Handling Systems & Terminal Devices

york airside products

H HUMIDIFIER Steam production equipment of immersed electrode type device, installed inside the unit and controlled by the microprocessor on a ON/OFF basis, to maintain the value of the treated air relative humidity within the pre-set limits. The steam produced by this equipment is distributed into the unit through a suitable sparge pipe. IH RS 485 SERIAL INTERFACE Electronic card allowing the connection of the unit to a BMS supervision system, to allow complete control from a remote working station. On demand, it is possible to connect the unit to supervision systems with different communication protocols. MS MOTORIZED DAMPERS Motor controlled by an external 0-10V. MTB HEATING SECTION WITH GAS FIRED HEATING COIL Additional in-built section, where one or more heating modules of forced draft type are installed, each made of a gas fired burner and an air/smoke steel exchanger. This module will heat the air to be introduced in the space, the air passes through the heat exchanger. For the heat pump version this module can be used as an additional heating section or, as an alternative to the heat pump itself. This section is manufactured in conformity with the regulations in force. MTC HEATING SECTION WITH BOILER Additional in-built section, where one or more boilers of watertight condensing type are installed, producing hot water necessary to supply, through a close circuit, a heating coil. The water circuit is complete with circulator, non return and check valves. This section is manufactured in conformity with the regulations in force. PA RUBBER-TYPE VIBRATION DAMPERS Kit of rubber-type vibration dampers, to be placed between the base-frame and the supporting surface, suitably selected to isolate the vibrations produced during the unit operation.

PM SPRING-TYPE VIBRATION DAMPERS Kit of metal vibration dampers, to be placed between the base-frame and the supporting surface, more efficiently than the rubber-type dampers, so to isolate the vibrations produced during the unit operation. PQ REMOTE MICROPROCESSOR Additional display for controlling the unit from a remote working station. RC CROSS-FLOW HEAT RECOVERY Cross-flow static heat exchanger with aluminium plates, installed in a suitable section of the unit, so to partially allow the transfer to the fresh air of the heating load present in the exhaust air, increasing the energy efficiency of the unit. The exchanger has no moving components and therefore there is no energy consumption: the two air flows involved are hermetically divided and therefore there is no possibility of mixing. The condensing water is collected in stainless steel drain pans and externally discharged. A bypass damper is positioned side by side to the heat recovery. On demand, the heat recovery section can be supplied in the 5 dampers version. RE ELECTRICAL POST-HEATING COIL Electrical heaters with carbon steel finning, placed after the evaporating coil; the electrical heaters are used to readjust the air temperature to the requested value, when the evaporator is used to lower the relative humidity in the supply air. The coil is supplied via the electrical board of the units and it is controlled by the microprocessor on a several step basis. VS - SOLENOID VALVE Electrovalve for the liquid refrigerant at the compressors stop.

60/61

Quick selection chart


P[kW] 400,0 350,0

Q [m3/h] Treated air flow P [kW] Total cooling capacity


3662

3102 300,0 250,0 2322 200,0 150,0 100,0 50,0 0,0 0 10.000 20.000 30.000 Q[m3/h] 40.000 50.000 60.000 70.000 1102 992 1112 1302 1292 1662 1472 1992 2802 2492

Air inlet and outlet available configurations


S2 Inlet Outlet S3 D2 D3

S4 S1

Q.E.

Std

Std

In case of order, if not clearly indicated, the units will be supplied with air inlet and outlet at the bottom (Std) Legend D1 - Air outlet on the front of the unit D2 - Air outlet on the top of the unit D3 - Air outlet on the back of the unit S1 - Air inlet on the front of the unit S2 - Air inlet on the top of the unit S3 - Air inlet on the back of the unit S4 - Air inlet on the left side of the unit

Note In case of D1 and D3, the length of the unit could be different from standard.

Air Handling Systems & Terminal Devices

york airside products

Nominal performances
Cooling Only - Size
Versions 2S - 3S Total cooling capacity (1) Sensible cooling capacity (1) Input power of compressors (1) Compressors absorbed current (1) Versions 2S - 3S Total cooling capacity (2) Sensible cooling capacity (2) Input power of compressors (2) Compressors absorbed current (2) Versions 2S-3S-TR Total cooling capacity (3) Sensible cooling capacity (3) Input power of compressors (3) Compressors absorbed current (3) Compressors Cooling circuits Capacity steps Refrigerant Refrigerant charge per circuit (1-2-3)

RTR
kW kW kW A kW kW kW A kW kW kW A nr. / type nr. nr. kg

992
110 66.8 30.7 51 119 62.4 31.5 53 99.4 72.6 29.2 49 2 / sll 2 2 13

1102
123 72.3 36.8 64 133 67.6 37.8 66 111 78.6 35 61 2 / sll-t 2 4 16

1302
144 83.7 39.9 65 156 78.3 41 67 130 91 38 63 2 / sll 2 2 R407C 22

1292
143 84.2 41.4 72.4 155 78.7 42.6 75 129 91.5 39.4 70 2 4 17

1 472
155 91.5 46.8 80.1 168 85.6 48.2 82 140 99.5 44.6 77 2 / sll-t 2 4 17

1 662
184 113 51.2 86.3 199 106 52.7 89 166 123 48.8 83 2 4 24

Heat Pump - Size


Heating capacity (4) Input power of compressors (4) Compressors absorbed current (4) Refrigerant charge per circuit (4) Fans for treated air Air flow Available pressure STANDARD Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 1M) Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 2M) Speed rotation Motor power Absorbed current Weight of electrical motor External fans Air flow Speed rotation Motor power Absorbed current Tot.sound pressure level STD/1M/ 2M (5) Electrical data Standard available pressure Max absorbed current Total inrush current -Direct start 1M Available pressure Max absorbed current Total inrush current -Direct start 2M Available pressure Max absorbed current Total inrush current -Direct start Power supply Dimensions Length - versions 2S and TR Length - version 3S Width Height Weight versions RTR Weight version RTP

RTP
kW kW A kg nr./type mc/h Pa rpm kW A kg Pa rpm kW A kg Pa rpm kW A kg nr./type mc/h rpm kW A dB(A)

992
94.3 21.5 39.2 16 19,800 645 5.5 12 41.9 645 5.5 12 41.9 801 7.5 15.4 51 2 / axial 37,600 870 2.2 10 76

1102
107 25.8 48.9 20 20,900 671 5.5 12 41.9 749 7.5 15.4 51 821 7.5 15.4 51 36,000 870 2.2 10 76

1302
123 28 50 26 22,000

1292
123 29 55.4 25

1 472
136 32.8 61.3 25 30,800 598 11 22.4 88.5 659 11 15.4 51 697 11 22.4 88.5 49,000 915 4.2 10 77

1 662
158 35.9 66.1 31 33,000 659 11 22.4 88.5 689 11 22.4 88.5 770 15 29 106.5 54,000 915 4.2 10 78

1 / centrifugal 27,500 100 715 556 7.5 7.5 15.4 15.4 51 51 200 788 618 7.5 7.5 15.4 15.4 51 51 300 856 686 11 11 22.4 22.4 88.5 88.5 4 / axial 35,600 49,000 870 915 2.2 4.2 10 10 77 76

A A A A A A type mm mm mm mm kg kg

86 252 86 252 89 255

102 205 105 208 105 208

107 291 107 291

113 218 113 218

130 248 123 241 130 248

140 280 140 280 147 287

114 120 298 225 400 V / 3ph / 50 Hz +E+N

4,400 6,300 2,100 1,404 1,469 1,750 1,586 1,660 1,633 1,708 1,993 2,097

5,100 7,540 2,300 2,100 2,108 2,217 2,159 2,270

(1) Ambient air : 27C / 50% U.R. - External air : 35C/70% U.R.; 30% fresh air (2) Ambient air : 27C / 50% U.R. - External air : 35C/70% U.R.; 50% fresh air (3) Inlet air to the internal coil: 27C / 50% U.R. - External air : 35C (4) Ambient air: 20C - External air : +5C / 70% U.R. (5) Average value estimated at 1 m from unit (for versions 2S and TR) in open field according to UNI EN 3746, with ducted outlet fan

62/63

Nominal performances
Cooling Only - Size
Versions 2S - 3S Total cooling capacity (1) Sensible cooling capacity (1) Input power of compressors (1) Compressors absorbed current (1) Versions 2S - 3S Total cooling capacity (2) Sensible cooling capacity (2) Input power of compressors (2) Compressors absorbed current (2) Versions 2S - 3S - TR Total cooling capacity (3) Sensible cooling capacity (3) Input power of compressors (3) Compressors absorbed current (3) Compressors Cooling circuits Capacity steps Refrigerant Refrigerant charge per circuit (1-2-3)

RTR
kW kW kW A kW kW kW A kW kW kW A nr./type nr. nr. type kg.

1 992
221 132 64.1 104 239 123 65.9 107 199 143 61 100

2 322
255 148 74.7 121 275 138 76.8 125 229 161 71.1 116

2 492
276 160 84.8 137 299 150 87.3 141 249 174 80.8 132 2 / sll-t 2 4 R407C

2 802
317 184 90.3 149 343 172 92.9 153 286 200 86 143

3 102
344 197 97.9 162 372 184 101 167 310 214 93.2 156

3 662
406 233 123 205 439 218 126 211 366 253 117 197

23

27

30

32

32

40

Heat Pump - Size


Heating capacity (4) Input power of compressors (4) Compressors absorbed current (4) Refrigerant charge per circuit (4) Fans for treated air Air flow Available pressure STANDARD Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 1M) Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 2M) Speed rotation Motor power Absorbed current Weight of electrical motor External fans Air flow Speed rotation Motor power Absorbed current Tot.sound pressure level STD/1M/2M (5) Electrical data Standard available pressure Max absorbed current Total inrush current -Direct start 1M Available pressure Max absorbed current Total inrush current -Direct start 2M Available pressure Max absorbed current Total inrush current -Direct start Power supply Dimensions Length - versions 2S and TR Length - version 3S Width Height Weight versions RTR Weight version RTP

RTP
kW kW A kg nr./type mc/h Pa rpm kW A kg Pa rpm kW A kg Pa rpm kW A kg nr./type mc/h rpm kW A dB(A)

1 992
155 58 95.7 38 38,500 434 11 22.4 88.5 200 490 11 22.4 88.5 546 15 29 107 84,000 870 8 16.8 78

2 322
179 67.5 111 42 41,000 465 11 22.4 88.5 200 549 15 29 107 574 15 29 107 4 / axial 82,000 870 8 16.8 79

2 492
196 76.8 127 45 44,000 490 15 29 107 200 538 15 29 107 590 15 29 107 80,000 870 8 16.8 80

2 802
221 81.7 137 47

3 102
239 88.5 150 47 55,000 479 18.5 40 121 200 522 18.5 40 121 562 22 42 140 6 / axial 126,000 870 12 25.2 82

3 662
288 111 189 55 66,000 548 30 57.3 146 200 581 30 57.3 146 619 37 69.1 207 120,000 870 12 25.2 84

1 / centrifugal 49,500 100 528 15 29 107 200 576 18.5 40 121 300 622 18.5 40 121 126,000 870 12 25.2 82

A A A A A A type mm mm mm mm kg kg

167 333 167 333 174 340

197 381 207 391 214 398

210 394 210 394

240 460 251 471

273 493 273 493 275 495

333 580 333 580 344 592

210 251 394 471 400 V / 3ph / 50 Hz +E+N

6,000 9,110 2,300 2,500 2,669 2,831 2,757 2,923 2,834 3,004 3,150 3,329

7,150 10,260

3,217 3,400

3,418 3,610

(1) Ambient air : 27C / 50% U.R. - External air : 35C/70% U.R.; 30% fresh air (2) Ambient air : 27C / 50% U.R. - External air : 35C/70% U.R.; 50% fresh air (3) Inlet air to the internal coil: 27C / 50% U.R. - External air : 35C (4) Ambient air: 20C - External air : +5C / 70% U.R. (5) Average value estimated at 1 m from unit (for versions 2S and TR) in open field according to UNI EN 3746, with ducted outlet fan

Air Handling Systems & Terminal Devices

york airside products

Nominal performances - Version 3S - Exhaust Fans


RTR / RTP - Size
Fans for treated air Air flow Available pressure STANDARD Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 1M) Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 2M) Speed rotation Motor power Absorbed current Weight of electrical motor Tot.sound pressure level. STD/1M/2M (1) Electrical data Standard available pressure Max absorbed current Total inrush current -Direct start 1M Available pressure Max absorbed current Total inrush current -Direct start 2M Available pressure Max absorbed current Total inrush current -Direct start Power supply Dimensions Length Width Height Weight version RTR Weight version RTP mm mm mm kg kg 1,734 1,790 6,300 2,100 1,750 1,916 1,985 1,973 2,039 2,483 2,571 7,540 2,300 2,100 2,608 2,703 2,659 2,755 A A type 101 267 117 220 126 310 136 241 153 271 169 309 A A 95 261 115 218 119 303 125 230 139 257 163 303 A A 93 259 109 212 117 301 125 230 146 264 156 296 nr./type mc/h Pa rpm kW A kg Pa rpm kW A kg Pa rpm kW A kg dB(A) 638 5.5 12 41.9 77 650 5.5 12 41.9 77 657 5.5 12 41.9 78 555 4 9.4 30.4 569 4 9.4 30.4 581 5.5 12 41.9 300 580 7.5 15 51 77 606 11 22 88.5 78 622 11 22 88.5 79 470 3 6.7 22.4 486 3 6.7 22.4 503 4 9.4 30.4 200 544 7.5 15.4 51 564 11 22.4 88.5 378 7.5 15.4 51 19,800 20,900 22,000 100 443 5.5 12 41.9 479 7.5 15.4 51 504 7.5 15.4 51

992

1102

1302
1 / centrifugal

1292
27,500

1472
30,800

1662
33,000

400 V / 3ph / 50 Hz +T+N

(1) Average value estimated at 1 m from the unit in open field according to UNI EN 3746, with ducted outlet and inlet fans

64/65

Nominal performances - Version 3S - Exhaust Fans


RTR / RTP - Size
Fans for treated air Air flow Available pressure STANDARD Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 1M) Speed rotation Motor power Absorbed current Weight of electrical motor Available pressure (opt. 2M) Speed rotation Motor power Absorbed current Weight of electrical motor Tot.sound pressure level. STD/1M/2M (1) Electrical data Standard available pressure Max absorbed current Total inrush current -Direct start 1M Available pressure Max absorbed current Total inrush current -Direct start 2M Available pressure Max absorbed current Total inrush current -Direct start Power supply Dimensions Length Width Height Weight version RTR Weight version RTP mm mm mm kg kg 3,351 3,479 3439 3619 3,527 3,663 9,110 2,300 2,500 3,943 4,091 4,065 4,219 4,286 4,451 10,260 A A type 196 362 214 398 232 416 280 500 304 524 384 632 A A 183 349 207 391 232 416 274 494 296 516 362 609 A A 179 345 197 381 225 409 263 483 296 516 362 609 nr./type mc/h Pa rpm kW A kg Pa rpm kW A kg Pa rpm kW A kg dB(A) 439 11 22 88.5 79 447 11 22.4 88.5 79 453 11 22 88.5 80 398 11 22.4 88.5 388 7.5 15.4 51 421 11 22.4 88.5 300 473 15 29 106.5 82 393 15 29 107 83 416 18.5 40 121 85 313 5.5 12 41.9 325 5.5 12 41.9 339 7.5 15.4 51 200 342 11 22.4 88.5 371 15 29 107 371 15 29 107 38,500 41000 44,000 100 366 11 22.4 88.5 288 11 22.4 88.5 324 15 29 107

1992

2322

2492
1 / centrifugal

2802
49,500

3102
55,000

3662
66,000

400 V / 3ph / 50 Hz +T+N

(1) Average value estimated at 1 m from the unit in open field according to UNI EN 3746, with ducted outlet and inlet fans

Air Handling Systems & Terminal Devices

york airside products

SmartPac
SmartPac from Johnson Controls offers factory packaged control solutions that reduce cost, enhance quality and optimise site time. Once on site, the equipment can be started immediately. Commissioning time is dramatically reduced, allowing to better control the project costs through simplifying equipment installation and commissioning. Quality is ensured through application and testing to European Installation regulations at the factory. Preinstalled software is configured to deliver air at the specified volume, temperature and humidity.

100% 90% 80% 70% 60% 50% 40% 30% 20% 10% 0%

Wiring & Installation Control Panel

Commissioning Engineering
Site Fitted Manufacturer Factory Fitted SmartPac

Controls

SmartPac and YORK Air Handling units


The Air Handling Unit arrives on site ready to connect to the site network, and final commission is simplified through the units keypad and display. Panel Power wiring, controls wiring, Variable Speed Drive, preengineered controller and required peripheral devices are all supplied, factory fitted and tested.

66/67

SmartPac and YORK Roof Top & Close Control units


Factory packaged controls solution enable, to dramatically reduce on-site commissioning costs. Both are delivered to site with pre-installed controls, factory tested and ready to apply the power.

SmartPac and YORK Fan Coil units


YORK Fan Coil Units are available with factory packaged controls and numerous options for controllers and valves to allow reduced installation time on site. Either EUBAC approved or alternative configurable controllers are offered, and a choice of BACNet, N2 Open or LON communication options is no extra cost. Valve requirements can also be met with a wide range of modulating and on/off actuators and isolation valves available and factory fitted.

SmartPac and YORK Standard Control panel


With a standardized design the YORK Airside Equipment is a cost effective solution. Furthermore, Variable Speed Drives give extra efficiency communicating the Johnson controller in either full native BACNet or LON or N2 protocols allowing seamless communication with existing control systems.

Manufacturer reserves the rights to change specifications without prior notice.

Air Handling Systems & Terminal Devices

About Johnson Controls


Johnson Controls delivers products, services and solutions that increase energy efficiency and lower operating costs in buildings for more than one million customers. Operating from 500 branch offices in more than 150 countries, we are a leading provider of equipment, controls and services for heating, ventilating, air-conditioning, refrigeration and security systems. We have been involved in more than 500 renewable energy projects including solar, wind and geothermal technologies. Our solutions have reduced carbon dioxide emissions by 15 million metric tons and generated savings of $7.5 billion since 2000. Many of the worlds largest companies rely on us to manage 1.5 billion square feet of their commercial real estate.

Johnson Controls, 2011

www.johnsoncontrols.com

PUBL-6751

Johnson Controls Inc, Building Efficiency, De Kleetlaan 3, Diegem Zuid - Pegasus Park, Brussels, Belgium B-1831.
Johnson Controls reserve the right, in line with continuing research and development, to amend or change specifications without notice.

You might also like