Professional Documents
Culture Documents
Power Flow Control and Islanding Detection of the Local Generation System with Induction Generator
R. M. Martinez. *, J. A. Pomilio * and L. C. Pereira da Silva*
* School of Electrical and Computer Engineering FEEC State University of Campinas - UNICAMP, Postal Box 6101 13081 970 Campinas SP Brazil
connected to the VSC through the bi-directional boost converter and buck converter unit. Both converters are controlled to manage the dc power flow when the LGS has to operate in autonomous form. The battery set is used as power back up. With the voltage grid in normal condition, and with the LGS connected to the grid, the boost converter is controlled to keep the battery charged. With the LGS operating in autonomous form, the control employs a procedure to reconnect with the grid when the AC voltage is reestablished. The control of the LGS incorporates voltage and frequency protection and active islanding detection.
Induction Generator
Ps Qs PLoad is QLoad
Local Load
VT
VS
S S1
Utility
I. INTRODUCTION In the references [1]-[2] a single to three-phase conversion system was presented to connect a three-phase IG to the single-phase grid. The system improves the local power quality for linear and non-linear loads, transfer power to the grid at unity power factor using VSC operating in line-interactive form. In references [3][4] two low-power isolated induction generator systems were presented, in which the dc voltage monitoring is used to control the system operation. In the first scheme the speed-governor is operated to maintain DC bus voltage, tracking the reference value in order to attain the systems power balance. In the second system, the speed regulator is not included and the power is determinate by the prime mover. Without control in the power generated, the regulation of the DC bus voltage is accomplished by sending the excess of energy (non consumed by the ac load) to the utility grid through a current inverter connected to the single-phase line. A new scheme of local generation system (LGS) is proposed in this paper as shown in Fig. 1. In this system the induction generator is connected to the grid. The VSC behaves as an on-line power-conditioning device for any source connected to its dc link terminals and as a line-interactive converter for the induction generator connected to AC terminals. The power generated by the IG is determinate by the primer mover, supplying partially or totally the power of the local load (linear or non-linear and unbalanced load as well), exporting or importing active power to the grid at unity power factor. In the DC bus circuit, a battery set is
This work was supported by FAPESP (proc. 05/54525-0).
978-1-4244-1664-6/08/$25.00 2008 IEEE
if
iload
Vdc iboost
iz Rz C
Buck Converter
The goals of this article are: 1) to present a strategy to keep the DC bus voltage constant by controlling the phase angle of the local voltage, VC, when the grid is connected or by the control of the bi-directional boost converter and buck converter when the LGS operate in autonomous form; 2) A new strategy of islanding detection is proposed, combining an active and passive methods; 3) Non-linear and unbalanced load can be supplied by the LGS without injection of harmonic current to the grid and without local voltage distortion. II. CONTROL STRATEGIES A. Grid connected mode In grid-connected mode the LGS is controlled to inject or absorbs the excess or deficit of power production of the IG to keep the active power balance of the system, expressed by the equation (1).
958
(1) (2)
grid as show Fig. 2c calculated by a PLL system [15], shown in Fig. 4. The voltage controller is that described in reference [2] and shown in Fig. (3). The V_Reg stand for multiple P + Resonant controllers for selective compensation of low-order voltage harmonics [1][6].
G2
PS is the grid active power, PIG is the active power generated by the IG and PLoad is the active power consumed by the local load. is the angle between VC and VS. The power balance is obtained by the power angle regulation that controls the active power flow to the grid according to equation (2). VC is the voltage at the filter capacitors terminals, VS is the voltage of the grid, XLs is the coupling reactance with the grid. The operation of the LGS at unity power factor can be obtained making Qs = 0 from equation (3), for the reactive power balance, and can be kept by adjusting the amplitude of the voltage VC according to equation (4).
sCf
G1 + + PIi +
Vc , ref
+ -
V Reg.
+ +
i f ,ref
i f
+ -
e
e
Vc , ref
Vc
+ V Reg. + +
i f ,ref
PIi
+ +
Vc
sCf
G1
i f
G2
(3) (4)
Qs is the reactive power of the grid, QLoad is the reactive power consumed by the local load, QIG is the reactive power consumed by the IG and Qinv is the reactive power of the VSC. Fig. 2a and 2b show the block diagram of these controllers.
Vdc,ref
2 + 0 1 2 PI
The outputs of the voltage controller are the input signal to the space vector modulator to generate the command pulses for the VSC. Note that by imposing sinusoidal voltage on the load bus, the VSC automatically compensate the harmonic and the reactive power of the load.
sinc
PIr
1
wsinc
1 2
dp = 0
1
+
+
ref
2 1
PI
0
+ +
wg
dp
1 s
Vdc
(a)
Qs
Qs,ref = 0
1 + + 2 2 0 0 PI
1 T0
Vsinc
PI 1
w0
dp
Vc
+ + +
v u
vTa vTb vTc
u a ub uc
sin (+120)
Vc, ref
Qs,dist(t)
Vc,nom
(b)
Vc, abc
abc
Vc
Vc
Vc, ref
ref
dq
Vcq,ref
Vc,ref
VT
PLL
if
if
......
Voltage Controller
SVPWM
Vcd,ref
dq
Vc,ref
1 2
B. Autonomous operation mode In the autonomous operation the LGS is not anymore connected to the grid and the VCS is controlled to keep the amplitude and frequency of the local voltage constant. This is obtained by changing the position of the switch in the figure 2a, 2b and 4 from position 1 to 2 [11]-[12]. Without the grid voltage, the DC bus voltage is no longer controlled by the power angle . Instead the buck and the boost converters control the DC bus voltage. When the IG power is lower than the power consumed by the load, the DC bus voltage decreases. If it reaches the lower limit, current injection by the boost converter is turned on (battery discharged) as show in Fig. 5(a). The current increases the DC voltage; if it reaches the upper limit, the current is turning off, to keep the DC voltage inside the voltage band. When the IG power is greater than the power load, the DC voltage increase, if it reaches
i f , abc
abc
(c) Fig. 2. Control block diagrams of the LGS (a) of outer DC voltage control loop, (b) outer power factor control loop. (c) VSC controller
These two reference signals are transformed to alfabeta frame using the angular position of the voltage
959
the upper limit, the buck converter is turned on to consume power in the resistance RZ and reduce the DC voltage as shown in Fig. 5b. Fig. 6 shows the boost and buck converters control scheme, including the battery charge function.
V dc
V d c, n o m V d c , ma x
recommended value, the charge process continues at constant voltage. III. ISLANDING DETECTION The unbalance between the power of the IG and the local load powers can be used to detect the islanding operation. After switch S opens (islanding) there is not power flow to the grid and the power mismatch flows to the DC bus. The DC voltage control changes the angle , trying to keep the DC voltage constant, to reestablish the previous power balance. The consequence is the variation of the frequency of the local voltages VC and VT until be detected by the frequency protection. No islanding detection happens when the power generated by the IG is equal to the power consumed by the local load [8]-[11] in this case, there are not amplitude and frequency variations of the voltage VT (VT is equal to VC) and DC neither in the bus voltage value.
VT , rms
Peak Value
V d c , mi n
i_ bo o st
I _ b oo st
t1
t (s )
(a)
V
Vdc,max
dc
Vdc,min Vdc,nom
i V
dc
/R
V T , rms
t1
t (s )
0 S 1_status
BPF
(b) Fig. 5. DC bus voltage control (a) When IG power is lower than power load (b) When IG power is higher than the power load
Battery Discharge
(a)
S1_status
i_batt i_batt,ref
+
1 0
X
+
lim
+
V T ,rms
td
Comparator
T1
Monostable
S1
PIi
boost
VLimit
Battery state
hi
+I_batt discharge
low 0
(b) Fig. 7. Islanding detection system (a) Detection disturb diagram block (b) Islanding discriminator diagram block.
Battery Charge
1 0 V _ batt
1 0
i_batt_limit
+ -
V _batt,ref
Buck control
To overcome this problem, an active islanding detection method is used, in which a reactive power disturbance Qs , dist is injected [9] on the power factor control block (Fig. 2b) equation (7)
PI V
1 0
1 0
buck
(7)
When the LGS is connected to the grid the battery bank will be charged or kept charged by the outer voltage control loop. The active and reactive power balance, in the autonomous operation, are expressed by (5) and (6)
(5) (6)
is the disturbance amplitude, fdist is the disturbance frequency. Fig. 7 shows the islanding detection system. A band pass filter (BPF) used to detect the disturb (with central frequency at 15 Hz). When the peak value is higher than the threshold, the output signal of the AND logical port is activate. A delay block introduces a delay time td to discriminate the actual signal of others produced by voltage disturbances. IV. RECONNECTION TO THE GRID After the grid voltage recovers, the reconnection initiated with the reduction of the phase and amplitude voltage differences, if exist [14]. Fig. 2b shows the voltage difference detector that adjusts the local voltage ( Vc , nom Vc ) with a PI regulator to reduce de voltage
When the DC voltage (Vdc) is in discharge range, depending on battery state of charge the current injection is regulated by the PIi current control. When Vdc voltage is in the battery charged range, the voltage control PIV is enabled. If the battery is deeply discharged, it will be charged at constant current. After the voltage reaches
960
difference ( Vsinc ). Fig. 4 shows the phase difference detector that adjusts the frequency ( w0 wsinc ) of the LGS to reduce de phase difference ( sinc ). With the differences adequately reduced, a command signal is send to close the switch S1, reconnecting the LGS with the grid, with minimum transient. V. SIMULATION RESULTS The system of Fig. 1 is simulated (PSCAD/EMTDC environment) with a parallel RLC local load. Tables I and II show the parameters of the system.
TABLE I SYSTEM PARAMETERS Dc-link voltage Dc-link capacitor Inverter filter inductor Inverter filter capacitor Coupling inductor of the LGS with the grid Battery voltage Boost inductor Three phase RLC load (Q = 2.5) RMS line voltage of utility Frequency Z-grid 600 V 4200 uF 2,5 mH 110 uF 1,5 mH 300 V 1,0 mH 2000 W 5000 Var -5000 Var 220 V 60 Hz 0.144 ohm
Ps
Qs
1.00
1.50
2.00
2.50
3.00
3.50
Time (s)
Time (s)
2.50
3.00
3.50
TABLE II INDUCTION GENERATOR PARAMETERS Rate RMS phase voltage 220 V Frequency 60 Hz Power 3 HP Stator resistance 0,435 Stator leakage inductance 4,0 mH Rotor resistance 0,816 Rotor leakage inductance 2,0 mH Magnetizing inductance 69,31 mH Inertia 0,05 kg.m2 No. of poles 4
At t = 2 s islanding is simulated by opening the switch S (Fig. 1). A voltage ripple ( V = 0.14 V), of the same frequency of the reactive disturbance, appears in the voltage VT, as shown in Fig. 11. Fig. 12 shows the output signal of BPF and its peak value, used for islanding detection. The islanding is confirmed after 300 ms The switch S1, opens letting the LGS in autonomous operation, supplying the local load with constant frequency and voltage amplitude.
127.6 127.4 127.2 V_nom vt_ef
Voltage (V)
127.0 126.8 126.6 126.4 126.2 1.00 1.50 2.00 2.50 3.00 3.50
= The parameters of the disturbance signal are: Q 10.0 var, fdist = 15.0 Hz. Fig. 8 shows the active power of the load, the induction generator (IG) and the grid. At t = 1.0 s the load is connected with minimum power generated by the IG. Therefore, all the power of the local load is imported from the grid at unity power factor, as show the Fig. 9 (active and reactive power of the grid) and by the active and reactive power of the VSC as show in Fig. 10. At t = 1.5 s the power of IG is increased to compensated the power of the local load totally and therefore the power mismatch is equal to zero.
4.0 Pload Pig Ps
Time (s)
Voltage (V)
0.10 0.05 0.00 - 0.05 - 0.10 - 0.15 - 0.20 - 0.25 - 0.30 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
3.0 2.0 1.0 0.0 -1.0 -2.0 -3.0 -4.0 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
Fig. 8. Active power of the load Pload, grid PS and induction generator Pig
At t = 2.5 s a power unbalance is introduced, by reducing 50% the power generated by the IG (Fig. 8). DC bus voltage decreases until turning-on the boost converter to transfer power of the battery to the dc link capacitor, keeping the dc voltage within the hysteresis band (580V, 550V), as show the Fig. 13. The IG and the battery feed the local load. The current injected by the boost converter, setting in 4.0 A, is shown in Fig. 14.
961
700 600
Vdc
Vdc_ref
15.0 12.5 10.0 7.5 5.0 2.5 0.0 -2.5 -5.0 -7.5 -10.0 -12.5
Isa
Voltage (V)
500 400 300 200 100 0.00 -100 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
Current (A)
1.00
1.50
2.00
2.50
3.00
3.50
Current (A)
5.0 4.0 3.0 2.0 1.0 0.0 -1.0 1.00 1.50 2.00 2.50 3.00 3.50
A single-phase non-linear local load, parameters are shown in table III, was tested:
TABLE III SINGLE-PHASE RECTIFIER Active power 2000 W Filter capacitor 800 uF Load resistance 40.0
whose
Time (s)
At t = 2.5 s the switch S was closed to simulate the grid voltage Vs recovering, with phase angle of 30 degrees delayed of the voltage VT. Once detected the grid voltage by the control scheme, the re-synchronization process is started. The re-synchronization process reduces the amplitude and phase differences between VT and VS. Fig. 15 shows the frequency command generated by the PLL system to reduce the phase difference. At t = 3.2 s, with minimum phase difference, the switch S1 is closed, reconnecting the LGS with the grid. The transient process is shown in Fig. 16. With the LGS reconnected to the grid, the DC bus voltage returns to the reference value (Fig. 13). The boost converter is turned-off and therefore, no more active power is injected by the battery or VSC as show in Fig. 10 and 14.
60.80 60.60 fr2 fr_nom
The non-linear load is connected at t = 0.9 s. At t = 1.3 s, the induction generation inject 3.25 kW more than the power consumed by the load. The power mismatch is exported to the grid at the unity power factor, as shown in Fig. 17. At t = 1.8 s the islanding is simulated and at t = 1.85 s it is detected by the frequency protection, disconnect the LGS of the grid, as show Fig. 18. Fig. 19 shows the DC bus voltage. The power excess is dissipated in the resistance RZ of the buck converter, keeping the dc voltage within predetermined hysteresis band (650V, 620V). Fig. 20 shows the distorted load current that is compensated by the VSC, as show in Fig. 21. Fig. 22 shows the grid current. At t = 2.2 s, the reconnection with the grid begin.
Active (KW) & Reactive (KVar) Power
4.0 3.0 2.0 1.0 0.0 -1.0 -2.0 -3.0 -4.0 1.00 1.50 2.00 2.50 3.00 3.50 Ps Qs
Frequency (Hz)
60.40 60.20 60.00 59.80 59.60 59.40 59.20 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
T ime (s)
The system imports the power deficit from the grid automatically, as show the Fig. 8 and 9, supplying the local load. Fig. 16 shows the line current and its transient behavior at the reconnection.
Frequency (Hz)
60.50 60.40 60.30 60.20 60.10 60.00 59.90 59.80 59.70 59.60 59.50 59.40 59.30 59.20 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
962
Vdc
Vdc_ref
[5] [6]
500 400 300 200 100 0.00 -100 1.00 1.50 2.00 2.50 3.00 3.50
Time (s)
[7]
[8]
[9]
Time (s)
[10]
[11]
[12]
1.610 1.620 1.630 1.640 1.650 1.660 1.670 1.680 1.690
Time (s)
[13]
[14]
[15]
Time (s)
Transaction on Industrial Electronics, vol. 47, No. 4, August 2000, pp. 908-914. J. -C. Wu and H. -L. Jou: Simplified control method for the singlephase active power filter, IEE Proc.-Electr. Power Appl., vol. 143, No. 3, May 1996, pp. 219-224. Paolo Mattavelli: Synchronous-Frame Harmonic Control for High-Performance AC Power Supplies, IEEE Transaction on Industry Applications, Vol. 37, No. 3, May/June 2001, pp. 864 872. R. Teodorescu, F. Blaabjerg, M. Liserre and P.C. Loh: Proportional-resonant controllers and filters for grid-connected voltage-source converters, IEE Proc.-Electr. Power Appl., Vol. 153, No. 5, September 2006, pp. 750-762. Z. Ye, R. Walling, L. Garces, R. Zhou, L. Li, and T. Wang: Study and Development of Anti Islanding Control for Grid-Connected Inverters, National Renewable Energy Laboratory (NREL/SR 560-36243), May 2004. Guillermo Hernandez-Gonzalez and Reza Iravani: Current Injection for Active Islanding Detection of ElectronicallyInterfaced Distributed Resources, IEEE Transaction on Power Delivery, vol. 21, No. 3, July 2006, pp. 1698-1705. Zhihong Ye, Amol Kolwalkar and Yu Zhang, Pengwei Du, and Reigh Walling: Evaluation of Anti-Islanding Schemes Base on No detection Zone Concept, IEEE Transactions on Power Electronics, vol. 19, No. 5, September 2004, pp. 1171-1176. C. Jeraputra and P. N. Enjeti: Development of Robust antiIslanding Algorithm for Utility Interconnection of distributed fuel cell power generation, IEEE Transactions on Power Electronics, vol. 19, No. 5, September 2004, pp. 1163-1170. Frede Blaabjerg, Remus Teodorecu, Marco Liserre and Adrian V. Timbus: Overview of Control and Grid Synchronization for Distributed Power Generation Systems, IEEE Transaction on Industrial Electronics, Vol. 53, No.5, October 2006, pp. 13981409. Remus Teodorescu, and F. Blaabjerg: Flexible Control of Small Wind Turbines With Grid Failure Detection Operating in StandAlone and Grid-Connected Mode, IEEE Transactions on Power Electronics, vol. 19, No. 5, September 2004, pp. 1323-1332. Yunwei Li, D. M. Vilathgamuwa and P. C. Loh: Design, Analysis, and Real-Time Testing of a Controller for Multibus Microgrid System, IEEE Transactions on power electronics, vol. 19, No. 5, September 2004, pp. 1195-1203. F.P. Marafo, S.M. Deckmann and E.K. Luna: A Novel Frequency and Positive Sequence Detector for Utility Applications and Power Quality Analysis, International Conference on Renewable Energy and Power Quality (ICREPQ), 2004.
Current (A)
Voltage (V)
VI. CONCLUSIONS The simulation results show that the parallel operation of the VSC in the LGS with the IG can supply a local load, importing or exporting power to the grid at unity power factor. In islanding operation, the LGS can keep the continuity of the power to the local load, supported by the IG and the battery set. The effectiveness of the islanding detection method and the reconnection procedure of LGS with the grid were confirmed. REFERENCES
[1] Ricardo Quadros Machado, Simone Busso, and Jos Antenor Pomilio: A Line-Interactive Single-Phase to Three-Phase Converter System, IEEE Transaction on Power Electronics, vol. 21, No. 6, November 2006, pp. 1628-1636. R. Q. Machado, S. Buso, J. A. Pomilio, and F. P. Marafo: Threephase to single-phase direct connection for rural co-generation systems, in Proc. IEEE APEC, Feb. 2004, pp. 753-758 E. G. Marra, J. A. Pomilio: Self-Excited Induction Generator Controlled by a VS-PWM Bi-directional Converter for Rural Application: IEEE Transaction on Industry Applications, vol. 35, No. 4, July/August 1999, pp. 877-883. E. G. Marra, J. A. Pomilio: Induction-Generator-Based System Providing Regulated Voltage with Constant Frequency, IEEE
[2] [3]
[4]
963