Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Beam reference : STAIR COMPOSITE BEAM 2

DATA General parameters Main span Edge beam Width on the left Width on the right Slab Slab with profiled sheeting Total thickness = 12.00 cm L1 = L2 = 0.150 m 1.500 m Max. participating width Max. participating width L1 = L2 = 0.150 m 0.750 m COMPOSITE BEAM L = 9.600 m

Profiled steel sheeting ''Corus_CF46 1.20 TATA'' , perpendicular to the beam (h = 46.0 mm ; e = 225.0 mm ; b1 = 105.0 mm ; b2 = 158.0 mm ; t = 1.2 mm ; 2 2 fy = 280 N/mm ; M = 13.00 kg/m ) Section HE 360 A - S355 ht bf tw tf r = = = = = 350.0 mm 300.0 mm 10.0 mm 17.5 mm 27.0 mm A Av Iy Iz It Iw W el.y W pl.y = = = = = = = = 142.76 cm 2 48.96 cm 4 33089.79 cm 4 7886.84 cm 4 148.82 cm 6 2176576.00 cm 3 1890.85 cm 3 2088.47 cm
2

Materials Steel Steel grade S355 Concrete slab C25/30 fck = Ecm = Modular ratio for LONG TERM Modular ratio for SHORT TERM Density of the concrete (slab) Reinforcement steel Ceq = Ceq = = fyk = 25 N/mm 31476 N/mm 24.13 6.67 25.00 kN/m
3 2 2 2

E fy

= 210000 N/mm 3 = 7850 kg/m = 345 N/mm

500 N/mm

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 1 / 8

GEG
Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Connection Beam reference : STAIR COMPOSITE BEAM 2 Connectors TRW Nelson KB 3/4"-100 h fy fu Main span Total number of connectors : 43 Lateral restraint of the beam - The beam is laterally restrained at supports = = = = 19.0 mm 100.0 mm 2 350.0 N/mm 2 450.0 N/mm e = 0.225 m n = 1 row(s)

L = 9.600 m

Propping in the construction stage

Full propping No calculation is carried out in the construction stage.

Loads Permanent loads Dead weight of the profile Dead weight of the slab ( 2.52 kN/m ) Span Surface load = 3.00 kN/m Line load :
2 2

1.10 kN/m 2.27 kN/m

xo xe

= =

3.00 m 6.00 m

qo = qe =

44.40 kN/m 44.40 kN/m

Live load case n 1 ( 0 = 0.70) Span Surface load = 5.00 kN/m Line load :
2

xo xe

= =

3.00 m 6.00 m

qo = qe =

22.30 kN/m 22.30 kN/m

Partial Factors Permanent loads G.sup = 1.35 G.inf = 1.00 Live loads Q = 1.50 Structural steel Structural steel (instabilities) Concrete Reinforcement bars Connectors Shear resistance of the steel sheeting M0 M1 c s v ap = 1.00 = 1.00 = 1.50 = 1.15 = 1.25 = 1.10

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 2 / 8

GEG
Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Combinations of actions ULS combination(s) SLS combination(s) 1.35 G + 1.50 Q1 G + Q1 Beam reference : STAIR COMPOSITE BEAM 2

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 3 / 8

GEG
Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Beam reference : STAIR COMPOSITE BEAM 2

FINAL stage Participating width on left support L / 4 (= 2.400 m) 3 L / 4 (= 7.200 m) on right support Moments of inertia Long-term Short-term Resistance of the connectors Verification of the degree of connection Minimum degree of connection = 0.525 FSteel FConcrete = = 4925.14 kN 943.50 kN ...at mid-span 48608 cm 72647 cm
4 4

0.803 m 0.900 m 0.900 m 0.803 m

PRd =

74.29 kN

Degree of connection = 1.654 > 1 The degree of connection is calculated for the section with maximum bending moment Plastic resistance - Full connection Plastic shear force resistance No risk of shear buckling ( hw / tw < 72 / ) ULS combination : 1.35 G + 1.50 Q1 Support reactions RV 1 = RV 2 = Calculation of the transverse reinforcement ratio of slab : At > 0.59 cm /m At + Ab > 1.55 cm /m MEd,max(+) = VEd,max = 737.01 kN.m -220.55 kN MEd,max(-) = 0.00 kN.m M = V = MV = Vh = 0.819 0.226 0.819 0.421 (x = 4.640 m) (x = 0.000 m) (x = 4.640 m)
2 2

Vpl.Rd =

975.17 kN

( = 1.20)

220.56 kN 203.04 kN

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 4 / 8

GEG
Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Beam reference : STAIR COMPOSITE BEAM 2

Longitudinal shear resistance of the slab - Transverse reinforcing bars Minimum transverse reinforcement ratio : (EN 1994-1-1 6.6.6.3 & EN 1992-1-1 9.2.2(5)) Reinforcement ratio (EN 1992-1-1 6.2.4) : w,min = 0.08 % At > 0.59 cm /m At + Ab > 1.55 cm /m Note: this result is provided as an indication. Calculations must be performed in order to take into account specific conceptual details. Note particularly that the calculations do not include the design of the slab. Plastic moment in span Maximum criterion for bending resistance Maximum criterion for shear force resistance Maximum criterion for bending moment - shear force interaction Maximum criterion for longitudinal shear force resistance of slab Mpl.Rd = M.max = V.max = MV.max = Vh.max = 899.39 kN.m 0.819 0.226 0.819 0.421
2 2

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 5 / 8

GEG
Project name : THIQAR STADIUM Project reference : 933.0 ArcelorMittal Beams Calculator v3.02 Beam reference : STAIR COMPOSITE BEAM 2

Serviceability Limit States Deflections per load case Case 'Dead weight' Case 'Other permanent loads' Case 'Q1' Case 'Shrinkage' vmax = vmax = vmax = vmax = 3.7 mm (L / 2628) 25.8 mm (L / 372) 11.0 mm (L / 876) 3.4 mm (L / 2792)

Deflections per combination Combination SLS ' G + Q1' vmax = 40.4 mm (L / 238)

Estimation of the first natural frequency G + 0.00 Q1 : 3.57 Hz G + 0.10 Q1 : 3.47 Hz G + 0.20 Q1 : 3.37 Hz G + 0.30 Q1 : 3.29 Hz G + 0.40 Q1 : 3.20 Hz G + 0.50 Q1 : 3.13 Hz G + 0.60 Q1 : 3.06 Hz G + 0.70 Q1 : 2.99 Hz G + 0.80 Q1 : 2.93 Hz G + 0.90 Q1 : 2.88 Hz G + 1.00 Q1 : 2.82 Hz Resistance criteria satisfied in the FINAL stage

User's name : SGONCALVES Date : 17-01-2014


D:\...\VRIOS\ESTRUTURAS MISTAS\MADRE ESCADA APOIO 2.PMX

Page 6 / 8