DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO I A 1 2 3 4 PARTICULARS HVAC PLANT ROOM - SECONDARY CHW PUMP On/Off Command Run Status High current Alarm Chilled water common supply temp 1 4 4 QTY 4 4 2 Core 2 Core 2 Core 4 4 1 PUMPx-ONOF-CMD PUMPx-RUN-STS CHWS-TEMP DDC Pump Panel Pump VFD Imm.Temp Sensor Imm.Temp Sensor OD T+RH Sensor SCHW Controller DDC Pump Panel DDC DDC BMS DDC shall provide potential free (N.O.) contact to Pump panel. BMS DDC shall accept potential free (N.O.) contact from pump panel. Modbus point mapping in BMS. Pump panel shall accept potential free (N.O.) contact from BMS DDC. Pump panel shall provide potential free (N.O.) contact to BMS DDC. Through modbus from pump VFD. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

Supply, Installation, Testing & Commissioning of Provision of 1/2" NPT socket to be made for Imm Temp Sensor. Immersion Temp Sensor Thermowell installation. Supply, Installation, Testing & Commissioning of Provision of 1/2" NPT socket to be made for Imm Temp Sensor. Immersion Temp Sensor Thermowell installation. Supply, Installation, Testing & Commissionig of Outdoor Temp & RH Sensor. BMS DDC shall accept potential free (N.O.) contact from SCHW Pump controller. BMS DDC shall provide potential free (N.O.) contact to SCHW Pump controller. SCHW Pump controller shall provide potential free (N.O.) contact to BMS DDC. SCHW Pump controller shall accept potential free (N.O.) contact from BMS DDC. Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN at site. Shall provide - 1) BTU Modbus RTU RS-485 wire terminals. 2) BTU Modbus register mapping list. 3) BTU Configuration as per site requirement. 4) Demonstrate BTU communication in open Modbus software like MODSCAN at site.

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B 1 2 3 4 5 6 7 8 9 10

Chilled water common return temp Outside Air Temperature Monitoring Outside Air RH Monitoring Sec Pump Controller Common fault monitoring Sec Pump Controller Common On/Off Command VFD Integration Secondary Pump's VFD Speed Feedback Secondary Pump's VFD Frequency Secondary Pump's VFD Current Secondary Pump's VFD Voltage Secondary Pump's VFD Power Secondary Pump's VFD Run Time BTU Meter (400mm) Supply Temperature Return Temperature Delta Temperature Flow Rate Total Flow Power Energy AHU On/Off Command Run Status Auto Manual status Trip Status Filter status Supply Air Temperature Monitoring Return Air Temperature Monitoring Valve Modulation VFD control Signal VFD modulation using diff press transmitter (Location of Diff. pressure sensor to be in SA Duct within AHU room itself) 4

1 1 1 1 1 4 4 4 4 4 4 1 1 1 1 1 1 1 1 107 107 107 107

2 Core 2 Core 4 Core 2 Core 2 Core

1 1 1 1 1

CHWR-TEMP OD-TEMP OD-RH SCHW-CTLR-FAULT SCHW-CTLR-CMD

DDC DDC DDC SCHW Controller

2 Core

1 (Daisy Chain)

VFD-COMM

DDC

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. Pump VFD 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software.

2 Core

BTU-COMM

DDC

BTU

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to BTUs in daisy chain. 3) BTU point data mapping into BMS Software.

2 Core 2 Core

107 107

AHU-ONOF-CMD AHU-RUN-STS AHU-A/M-STS

DDC Air DPS AHU Panel AHU Panel Air DPS Duct Temp Sensor Duct Temp Sensor DDC DDC Air DPT

AHU Panel DDC DDC DDC DDC DDC DDC Valve Actuator AHU VFD DDC

4 Core 107 107 107 107 107 107 107 2 Core 2 Core 2 Core 4 Core 2 Core 4 Core

107 AHU-TRIP-STS 107 107 107 107 107 107 AHU-FLTR-STS AHU-SA-TEMP AHU-RA-TEMP AHU-VLV-MOD AHU-VFD-CTR AHU-DP

BMS DDC shall provide potential free (N.O.) contact to AHU panel. Supply, Installation, Testing & Commissionig of Air Diff. Pressure Switch (DPS). BMS DDC shall accept potential free (N.O.) contact from AHU panel. BMS DDC shall accept potential free (N.O.) contact from AHU panel. Supply, Installation, Testing & Commissionig of Air Diff. Pressure Switch (DPS). Supply, Installation, Testing & Commissioning of Duct Temp Sensor. Supply, Installation, Testing & Commissioning of Duct Temp Sensor. BMS DDC shall provide 0-10 Vdc signal output for 0-100% valve open to Valve Actuator. 24Vac supply to valve actuator. BMS DDC shall provide 0-10 Vdc signal output for 0-100% speed to AHU VFD.

AHU panel shall accept potential free (N.O.) contact from BMS DDC. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. AHU panel shall provide potential free (N.O.) contact to BMS DDC. AHU panel shall provide potential free (N.O.) contact to BMS DDC. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. Provision of 1/4" hole to be made on the side of duct for Duct Temp Sensor probe insertion. Provision of 1/4" hole to be made on the side of duct for Duct Temp Sensor probe insertion. Valve Actuator shall accept 0-10Vdc signal for 0100% valve open from BMS DDC. AHU VFD shall accept 0-10Vdc signal for 0100% VFD speed from BMS DDC

Supply, Installation, Testing & Commissioning of Provision of 8mm dia hole at suitable location for Air Diff. Pressure Transmitter (DPT). pressure pickup tubes installation.

Page 1 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO 11 12 13 14 15 16 17 C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 PARTICULARS VFD soft integration AHU's VFD Speed Feedback AHU's VFD Frequency AHU's VFD Current AHU's VFD Voltage AHU's VFD Power AHU's VFD Run Time FAHU Supply Air Temperature Monitoring Temperature After Heat Recovery Exhaust Temperature before heat recovery Ambient temperature Monitoring Temperature After Heat wheel Supply Fan Run Status Supply Fan Trip Status Exhaust Fan Run Status Exhaust Fan Trip Status HW Motor Run Status HW Motor Trip Status Filter before HW on Exhaust Pre Filter Fresh Air Bag Filter Fresh Air FAHU Start/Stop HOA Switch Valve Modulation VFD control Signal VFD modulation using diff press transmitter VFD soft integration AHU's VFD Speed Feedback AHU's VFD Frequency AHU's VFD Current AHU's VFD Voltage AHU's VFD Power AHU's VFD Run Time 7 7 7 7 7 7 7 6 6 6 6 QTY 107 107 107 107 107 107 107 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 2 Core 4 Core 2 Core 4 Core 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 FAHU-SA-TEMP FAHU-AHR-TEMP FAHU-BHR-TEMP FAHU-AMB-TEMP FAHU-AHW-TEMP FAHU-SF-RUN FAHU-SF-TRIP FAHU-EF-RUN FAHU-EF-TRIP FAHU-HW-RUN FAHU-HW-TRIP FAHU-HW-FLTR FAHU-PR-FLTR FAHU-BG-FLTR FAHU-ONOF-CMD FAHU-A/M-STS FAHU-VLV-MOD FAHU-VFD-CTR FAHU-DP Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor Duct Temp Sensor Air DPS FAHU Panel Air DPS FAHU Panel FAHU Panel FAHU Panel Air DPS Air DPS Air DPS DDC FAHU Panel DDC DDC Air DPT Supply, Installation, Testing & Commissioning of Duct Temp Sensor. Supply, Installation, Testing & Commissioning of DDC Duct Temp Sensor. Supply, Installation, Testing & Commissioning of DDC Duct Temp Sensor. Supply, Installation, Testing & Commissioning of DDC Duct Temp Sensor. Supply, Installation, Testing & Commissioning of DDC Duct Temp Sensor. Supply, Installation, Testing & Commissionig of DDC Air Diff. Pressure Switch (DPS). BMS DDC shall accept potential free (N.O.) DDC contact from AHU panel. Supply, Installation, Testing & Commissionig of DDC Air Diff. Pressure Switch (DPS). BMS DDC shall accept potential free (N.O.) DDC contact from AHU panel. BMS DDC shall accept potential free (N.O.) DDC contact from AHU panel. BMS DDC shall accept potential free (N.O.) DDC contact from AHU panel. Supply, Installation, Testing & Commissionig of DDC Air Diff. Pressure Switch (DPS). Supply, Installation, Testing & Commissionig of DDC Air Diff. Pressure Switch (DPS). Supply, Installation, Testing & Commissionig of DDC Air Diff. Pressure Switch (DPS). BMS DDC shall provide potential free (N.O.) FAHU Panel contact to AHU panel. BMS DDC shall accept potential free (N.O.) DDC contact from AHU panel. BMS DDC shall provide 0-10 Vdc signal output Valve for 0-100% valve open to Valve Actuator. 24Vac Actuator supply to valve actuator. BMS DDC shall provide 0-10 Vdc signal output FAHU VFD for 0-100% speed to AHU VFD. DDC DDC Provision of 1/4" hole to be for Duct Temp Sensor probe insertion. Provision of 1/4" hole to be for Duct Temp Sensor probe insertion. Provision of 1/4" hole to be for Duct Temp Sensor probe insertion. Provision of 1/4" hole to be for Duct Temp Sensor probe insertion. Provision of 1/4" hole to be for Duct Temp Sensor probe insertion. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. AHU panel shall provide potential free (N.O.) contact to BMS DDC. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. AHU panel shall provide potential free (N.O.) contact to BMS DDC. AHU panel shall provide potential free (N.O.) contact to BMS DDC. AHU panel shall provide potential free (N.O.) contact to BMS DDC. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. Provision of 8mm dia hole at suitable location for pressure pickup tube installation. AHU panel shall accept potential free (N.O.) contact from BMS DDC. AHU panel shall provide potential free (N.O.) contact to BMS DDC. Valve Actuator shall accept 0-10Vdc signal for 0100% valve open from BMS DDC. AHU VFD shall accept 0-10Vdc signal for 0100% VFD speed from BMS DDC 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software. Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN at site. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

1 (Daisy Chain)

VFD-COMM

DDC

AHU VFD

Supply, Installation, Testing & Commissioning of Provision of 8mm dia hole at suitable location for Air Diff. Pressure Transmitter (DPT). pressure pickup tubes installation. Basement floor FAHU has two SA Fan Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN at site.

2 Core

1 (Daisy Chain)

VFD-COMM

DDC

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. FAHU VFD 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software.

Page 2 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO D 1 2 3 4 5 6 7 E 1 2 3 4 5 6 7 II A 1 2 3 4 5 PARTICULARS BTU METER FOR TENANT AHU Supply Temperature Return Temperature Delta Temperature Flow Rate Total Flow Power Energy FCU FOR COMMON AREAS Space Temperature Space Temperature Setpoint FCU Valve Modulation FCU On/Off Command FCU Fan High Speed Command FCU Fan Medium Speed Command FCU Fan Low Speed Command FANS SMOKE EXTRACT FAN `Auto' position of H/O/A switch Fan trip alarm Fan Start/Stop Command Fan run status FA signal STAIRCASE PRESSURIZATION FAN + PASSAGE PRESSURIZATION FAN `Auto' position of H/O/A switch Fan trip alarm Fan Start/Stop Command Fan run status VFD Control Signal Staircase (2 nos.) pressure sensor ( 1No per every 5 floors) FA signal 15 15 1 3 3 2 Core 4 Core 2 Core 3 15 1 1 1 2 Core 1 100 100 100 100 100 4 Core 100 QTY 98 98 98 98 98 98 98 98 100 100 100 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to BTUs in daisy chain. 3) BTU point data mapping into BMS Software. Shall provide - 1) BTU Modbus RTU RS-485 wire terminals. 2) BTU Modbus register mapping list. 3) BTU Configuration as per site requirement. 4) Demonstrate BTU communication in open Modbus software like MODSCAN at site. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

BTU-COMM

DDC

BTU

2 Core 4 Core 2 Core

100 100 100

FCU-SPACE-TEMP FCU-VALVE-MOD FCU-ONOF-CMD FCU-HI-SPD-CMD FCU-MED-SPD-CMD FCU-LO-SPD-CMD

Space Temp Sensor DDC DDC DDC DDC DDC

DDC FCU Valve FCU Motor FCU Motor FCU Motor FCU Motor SITC of Space Temperature Sensor Software point BMS DDC shall provide 0-10 Vdc signal output for 0-100% valve open to Valve Actuator. 24Vac supply to valve actuator. BMS DDC shall provide potential free (N.O.) contact to FCU Unit. BMS DDC shall provide potential free (N.O.) contact to FCU Unit. BMS DDC shall provide potential free (N.O.) contact to FCU Unit. BMS DDC shall provide potential free (N.O.) contact to FCU Unit. -

Valve Actuator shall accept 0-10Vdc signal for 0100% valve open from BMS DDC. FCU Unit shall accept potential free (N.O.) contact from BMS DDC. FCU Unit shall accept potential free (N.O.) contact from BMS DDC. FCU Unit shall accept potential free (N.O.) contact from BMS DDC. FCU Unit shall accept potential free (N.O.) contact from BMS DDC.

1 1 4 Core 1 1 4 Core 1 SEF-RUN-STS SEF-FIRE-STS Fan Panel FAS CR DDC DDC 1 SEF-TRIP-STS SEF-ONOF-CMD Fan Panel DDC DDC Fan Panel SEF-A/M-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall provide potential free (N.O.) contact to Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. FAS CR Module shall be provided near DDC Panel. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. -

B 1 2 3 4 5 6 7

2+1 3 4 Core 3 3 4 Core 3 SPFx-RUN-STS SPFx-VFD-CTR SPFx-DP SPF-FIRE-STS Fan Panel DDC Air DPT FAS CR DDC Fan VFD DDC DDC 3 SPFx-TRIP-STS SPFx-ONOF-CMD Fan Panel DDC DDC Fan Panel SPFx-A/M-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall provide potential free (N.O.) contact to Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall provide 0-10 Vdc signal output for 0-100% speed to Fan VFD. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan VFD shall accept 0-10Vdc signal for 0-100% VFD speed from BMS DDC

Supply, Installation, Testing & Commissioning of Provision of 8mm dia hole at suitable location for Air Diff. Pressure Transmitter (DPT). pressure pickup tubes installation. FAS CR Module shall be provided near DDC panel. -

Page 3 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO 8 9 10 11 12 13 14 C 1 2 3 4 5 D 1 2 3 E 1 2 3 F 1 2 3 G 1 III 1 2 3 4 5 6 7 8 9 PARTICULARS VFD soft integration Fan VFD Speed Feedback Fan VFD Frequency Fan VFD Current Fan VFD Voltage Fan VFD Power Fan VFD Run Time LIFT PRESSURIZATION FAN `Auto' position of H/O/A switch Fan trip alarm Fan Start/Stop Command Fan run status Fire Signal CAR PARK JET FANS `Auto' position of H/O/A switch Fan trip alarm Fan run status EXTRACT FAN (DUAL SPEED) `Auto' position of H/O/A switch for Fire + Normal Starters Fan trip alarm Fire Mode + Normal Mode Fan run status Fire Mode + Normal Mode EXTRACT FAN (SINGLE SPEED) `Auto' position of H/O/A switch Fan trip alarm Fan run status MOTORISED FIRE DAMPER Damper On/Off Status LIFT Floor Position Door fully Closed Signal Status of Landing Floor (Open/Close) Inspection Status (Normal/Maintenance) Emergency Stop Status Fault Indication Fireman Switch Status Lift Auto/Manual Status Lift Run Status 14 14 14 14 14 14 14 14 14 14 Shall provide - 1) Lift Modbus RTU RS-485 wire terminals. 2) Lift Modbus register mapping list. 3) Lift Configuration as per site requirement. 4) Demonstrate Lift communication in open Modbus software like MODSCAN at site. 140 140 2 Core 140 MFDx-ONOF-STS Fire Damper DDC BMS DDC shall accept potential free (N.O.) contact from Fire Damper. Fire Damper shall provide potential free (N.O.) contact to BMS DDC. 6 6 6 12 6 3 4 Core 3 3 2 Core 6 6 SS-EXT-Fx-TRIP-STS SS-EXT-Fx-RUN-STS Fan Panel Fan Panel DDC DDC SS-EXT-Fx-A/M-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. 4 Core 6 4 Core DS-EXT-Fx-A/M-STS 6 DS-EXT-Fx-TRIP-STS DS-EXT-Fx-RUN-STS Fan Panel Fan Panel DDC DDC Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. 3 3 4 Core 3 3 2 Core 3 3 JETx-TRIP-STS JETx-RUN-STS Fan Panel Fan Panel DDC DDC JETx-A/M-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. 10 10 QTY 3 3 3 3 3 3 3 10 10 4 Core 10 10 2 Core 2 Core 2 Core 10 10 10 10 LPFx-TRIP-STS LPFx-ONOF-CMD LPFx-RUN-STS LPFx-FIRE-STS Fan Panel DDC Fan Panel FAS CR DDC Fan Panel DDC DDC LPFx-A/M-STS Fan Panel DDC BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. BMS DDC shall provide potential free (N.O.) contact to Fan Panel. BMS DDC shall accept potential free (N.O.) contact from Fan Panel. FAS CR Module shall be provided near DDC Panel. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. Fan Panel shall accept potential free (N.O.) contact from BMS DDC. Fan Panel shall provide potential free (N.O.) contact to BMS DDC. 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software. Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN at site. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

1 (Daisy Chain)

VFD-COMM

DDC

Fan VFD

2 Core

1 (Daisy Chain)

LIFT-COMM

DDC

LIFT

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to Lifts in daisy chain. 3) Lift point data mapping into BMS Software.

Page 4 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO IV A 1 2 3 4 B 1 2 3 C 1 2 3 4 5 6 7 8 9 D 1 2 PARTICULARS PUBLIC HEALTH ENGINEERING TRANSFER PUMP H/O/A Switch in auto position Run Status Trip Status On/Off Command SUMP PUMP Unit Fault status Run Status Auto Manual Status BOOSTER PUMP H/O/A Switch in auto position Trip Status VFD soft integration Pump VFD Speed Feedback Pump VFD Frequency Pump VFD Current Pump VFD Voltage Pump VFD Power Pump VFD Run Time FIRE WATER TANK (3 Bsmt + 3 Terrace) Tank Level High/Low Level Alarm 6 6 6 6 6 6 6 6 6 12 2 Core 1 FIRE-TANK-LVL Level Sensor DDC Supply and Installation of Level Pressure Sensor 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to Flow Meters in daisy chain. 3) Flow Meter point data mapping into BMS Software. Suitable provision for level pressure sensor installation Shall provide - 1) Flow Meter Modbus RTU RS485 wire terminals. 2) Flow Meter Modbus register mapping list. 3) Flow Meter Configuration as per site requirement. 4) Demonstrate Flow Meter communication in open Modbus software like MODSCAN at site. 1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. Pump VFD 2) Communication Cable laying from integrator to VFDs in daisy chain. 3) VFD point data mapping into BMS Software. Shall provide - 1) VFD Modbus RTU RS-485 wire terminals. 2) VFD Modbus register mapping list. 3) VFD Configuration as per site requirement. 4) Demonstrate VFD communication in open Modbus software like MODSCAN at site. 6 6 4 Core 6 6 BSTR-Px-TRIP-STS Pump Panel DDC BSTR-Px-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. 6 6 4 Core 6 6 2 Core 6 6 SUMP-Px-RUN-STS SUMP-Px-A/M-STS Pump Panel Pump Panel DDC DDC SUMP-Px-FAULT Pump Panel DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. QTY 4 4 4 Core 4 4 4 Core 4 4 TX-Px-ONOF-CMD 4 TX-Px-RUN-STS TX-Px-TRIP-STS TX-Px-A/M-STS BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) Pump Panel DDC contact from Pump Panel. BMS DDC shall accept potential free (N.O.) Pump Panel DDC contact from Pump Panel. BMS DDC shall provide potential free (N.O.) DDC Pump Panel contact to Pump Panel. Pump Panel DDC Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall accept potential free (N.O.) contact from BMS DDC. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

1 (Daisy Chain)

VFD-COMM

DDC

Water Flow Meter

14

14

2 Core

1 (Daisy Chain)

FLOW-MTR-COMM

DDC

FLOW METER

V A 1 2 3 B 1 2 3

FIRE FIGHTING SYSTEM FIRE FIGHTING PUMP Pump auto-manual status Pump run status Trip Status JOCKEY PUMP Pump auto-manual status Pump run status Trip Status

1 1 4 Core 1 1 1 1 4 Core 1 1 2 Core 1 1 JKP-RUN-STS JKP-TRIP-STS Pump Panel Pump Panel DDC DDC JKP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. 2 Core 1 1 FFP-RUN-STS FFP-TRIP-STS Pump Panel Pump Panel DDC DDC FFP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC.

Page 5 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO C 1 2 3 VI A 1 2 3 PARTICULARS DIESEL ENGINE PUMP Pump auto-manual status Pump run status Trip Status ELECTRICAL SYSTEM LV PANEL 1 Incoming breaker ON/OFF Status of each main incoming breaker Trip alarm indication of main incoming breaker Breaker Trip Command Outgoing breaker 1 2 3 4 B 1 2 3 ON/OFF Status of each main outgoing breaker Trip alarm indication of main outgoing breaker Breaker Trip Command Fire Suppression System LV PANEL 2 Incoming breaker ON/OFF Status of each main incoming breaker Trip alarm indication of main incoming breaker Breaker Trip Command Outgoing breaker 1 2 3 4 C 1 2 3 1 2 ON/OFF Status of each main outgoing breaker Trip alarm indication of main outgoing breaker Breaker Trip Command Fire Suppression System LV PANEL 3 Incoming breaker ON/OFF Status of each main incoming breaker Trip alarm indication of main incoming breaker Breaker Trip Command Outgoing breaker ON/OFF Status of each main outgoing breaker Fire Suppression System 5 5 1 2 Core 2 Core 5 1 LV-P3-OGx-ONOF-STS FIRE-SUP-SYS3-STS Panel Fire Panel DDC DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 4 Core 1 1 1 LV-P3-IC-TRIP-STS Panel DDC LV-P3-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 4 4 4 Core 1 1 2 Core 2 Core 4 1 4 LV-P2-OGx-TRIP-STS LV-P2-OGx-TRIP-CMD FIRE-SUP-SYS2-STS Panel DDC Fire Panel DDC Panel DDC LV-P2-OGx-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall provide potential free (N.O.) contact to Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 4 Core 1 1 2 Core 1 1 LV-P2-IC-TRIP-STS LV-P2-IC-TRIP-CMD Panel DDC DDC Panel LV-P2-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall provide potential free (N.O.) contact to Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. 1 4 4 4 Core 1 1 2 Core 2 Core 4 1 4 LV-P1-OGx-TRIP-STS LV-P1-OGx-TRIP-CMD FIRE-SUP-SYS1-STS Panel DDC Fire Panel DDC Panel DDC LV-P1-OGx-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall provide potential free (N.O.) contact to Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. QTY 1 1 4 Core 1 1 2 Core 1 1 DEP-RUN-STS DEP-TRIP-STS Pump Panel Pump Panel DDC DDC DEP-A/M-STS Pump Panel DDC BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. BMS DDC shall accept potential free (N.O.) contact from Pump Panel. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. Pump Panel shall provide potential free (N.O.) contact to BMS DDC. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

1 1 4 Core 1 1 2 Core 1 1 LV-P1-IC-TRIP-STS LV-P1-IC-TRIP-CMD Panel DDC DDC Panel LV-P1-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall provide potential free (N.O.) contact to Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC.

Page 6 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO D 1 PARTICULARS ESMDB Incoming breaker ON/OFF Status of each main incoming breaker Outgoing breaker 2 E 1 F 1 G 1 H 1 I 1 J 1 K 1 L 1 M 1 N 1 O 1 P 1 Q 1 ON/OFF Status of each main incoming breaker MCC - B Incoming breaker ON/OFF Status of each main incoming breaker EMCC - B Incoming breaker ON/OFF Status of each main incoming breaker SMDB - B Incoming breaker ON/OFF Status of each main incoming breaker MCC - PUMP Incoming breaker ON/OFF Status of each main incoming breaker MCC SUMP PUMP Incoming breaker ON/OFF Status of each main incoming breaker MCC ETS Incoming breaker ON/OFF Status of each main incoming breaker SMDB - G Incoming breaker ON/OFF Status of each main incoming breaker MCC - R1 Incoming breaker ON/OFF Status of each main incoming breaker MCC - R2 Incoming breaker ON/OFF Status of each main incoming breaker SMDB UR Incoming breaker ON/OFF Status of each main incoming breaker SMDB RT Incoming breaker ON/OFF Status of each main incoming breaker EMCC - R Incoming breaker ON/OFF Status of each main incoming breaker SMDB UPS Incoming breaker ON/OFF Status of each main incoming breaker 1 1 1 2 Core 1 SMDB-UPS-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 EMCC-R-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDB-RT-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDB-UR-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCCR2-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCCR1-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDBG-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCC-ETS-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 2 2 2 2 Core 2 MCC-SPUMP-ICx-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCC-PUMP-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDBB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 EMCCB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCCB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 6 6 2 Core 1 ESMDB-OGx-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. QTY 1 1 1 2 Core 1 ESMDB-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

Page 7 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO R 1 S 1 T 1 U 1 V 1 W 1 X 1 Y 1 2 Z 1 2 AA 1 2 3 4 5 6 7 8 9 10 AB 1 2 AC 1 2 PARTICULARS SMDB UPS II Incoming breaker ON/OFF Status of each main incoming breaker SMDB GYM Incoming breaker ON/OFF Status of each main incoming breaker SMDB F & B Incoming breaker ON/OFF Status of each main incoming breaker SMDB CF1 & CF2 Incoming breaker ON/OFF Status of each main incoming breaker MCC FF Incoming breaker ON/OFF Status of each main incoming breaker FLOOR SMDBs Incoming breaker ON/OFF Status of each main incoming breaker TENANT SMDBs Incoming breaker ON/OFF Status of each main incoming breaker TRANSFORMERS Signals for monitoring Signals for monitoring HT PANELS/BREAKERS Signals for monitoring Signals for monitoring LOAD MANAGERS INTEGRATION Average Current Voltage Kilowatt Run hour Power Factor Forward Active Energy Power Factor Average Line to Line Voltage Average Line to Line Neutral Average Frequency LIGHTING CONTROL Circuit open/close status Circuit open/close command AIRCRAFT WARNING LIGHT Circuit on/off status Circuit trip alarm 1 1 4 Core 1 1 AL-CKT-TRIP-STS Panel DDC AL-CKT-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 103 103 103 103 103 103 103 103 103 103 103 64 64 4 Core 64 64 LP-CKT-ONOF-CMD DDC Panel LP-CKT-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. BMS DDC shall provide potential free (N.O.) contact to Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. Panel shall accept potential free (N.O.) contact from BMS DDC. 4 3 32 2 Core 4 Core 3 16 HT-SINGx-MTR HT-SINGx-STS Panel Panel DDC DDC BMS DDC shall accept 0-10 Vdc signal from panel BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall providde 0-10Vdc signal for BMS interface with DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 3 3 16 2 Core 4 Core 3 8 TX-SINGx-MTR TX-SINGx-STS Panel Panel DDC DDC BMS DDC shall accept 0-10 Vdc signal from panel BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall providde 0-10Vdc signal for BMS interface with DDC. Panel shall provide potential free (N.O.) contact to BMS DDC. 73 73 73 2 Core 73 TENT-SMDBx-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 28 28 28 2 Core 28 FLR-SMDBx-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 MCC-FF-IC-ONOF-STS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 2 2 2 2 Core 2 SMDB-CFx-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDB-F&B-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. 1 1 1 2 Core 1 SMDB-GYM-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. QTY 1 1 1 2 Core 1 SMDB-UPS2-IC-ONOFSTS Panel DDC BMS DDC shall accept potential free (N.O.) contact from Panel. Panel shall provide potential free (N.O.) contact to BMS DDC. AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

1 (Daisy Chain)

EM-COMM

DDC

Load Manager

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to EMs in daisy chain. 3) EM point data mapping into BMS Software.

Shall provide - 1) EM Modbus RTU RS-485 wire terminals. 2) EM Modbus register mapping list. 3) EM Configuration as per site requirement. 4) Demonstrate EM communication in open Modbus software like MODSCAN at site.

Page 8 of 9

HONEYWELL
DOCUMENT : BMS I/O SUMMARY FOR SABARMATI TOWER-2, GIFT CITY GUJARAT
Sl.NO AD 1 2 3 4 5 6 7 8 9 10 VII 1 2 VIII IX X PARTICULARS UPS O/P Voltage - R O/P Voltage - Y O/P Voltage - B O/P Current - R O/P Current - Y O/P Current - Y Battery Voltage Battery Charge Remaining Frequency Alarm Status PA/BGM SYSTEM Panel power ON status Panel fault status CCTV SYSTEM INTEGRATION FIRE ALARM SYSTEM INTEGRATION ACCESS CONTROL SYSTEM TOTAL 10% Pseudo Points TOTAL 482 1054 329 843 9274 605 5961 3200 QTY 2 2 2 2 2 2 2 2 2 2 2 1 1 1 4 Core 1 PA-ONOF-STS PA-FAULT-STS Panel Panel DDC DDC PAS BY HAIL PAS BY HAIL DVM Interface Modbus Interface Tema Interface AI I/O DETAILS DI AO DO Soft Type Runs CABLE DETAILS Tag From To

DOC NO.: INB-6097-BMS-IO-01


HAIL'S Scope of Work

REVISION : 1 DATE : 20.02.2013


CLIENT'S Scope of Work

2 Core

1 (Daisy Chain)

UPS-COMM

DDC

UPS

1) Supply, Installation, Testing & Commissioning of Modbus RS485 Integrator. 2) Communication Cable laying from integrator to UPSs in daisy chain. 3) UPS point data mapping into BMS Software.

Shall provide - 1) UPS Modbus RTU RS-485 wire terminals. 2) UPS Modbus register mapping list. 3) UPS Configuration as per site requirement. 4) Demonstrate UPS communication in open Modbus software like MODSCAN at site.