COMPRESSOR AND CRITICAL MACHINE PROTECTION ILLUSTRATED BY EXAMPLE

Uma Electronics Enterprise, 2012 http://www.umaelectronics.com

28th April 2014

Version 2

AN003
.

GML-3 is useful in compressor protection or critical machinery. GML-3 provides all energy parameters and also some useful parameters like run hour, load hour, voltage unbalance, current unbalance in all three phases. Generally most compressor and machine fault is caused by over-voltage, overcurrent and over load. Gml-3 provides relay facility for those events and also SMS ALARM is sent to your number or any two numbers you want to notify.The direct email alert is also sent to track events.

EXAMPLE
Now lets we have to save our Compressor from over current. We assume Compressor maximum current is 20 A. Change alarm parameter to current as image 1. (To change alarm parameter refer manual.) Now we have to set for which condition we want to set alarm. We want alarm if current is more ALARM PARAMETER OLD:VOLTAGE(ANY) NEW:CURRENT(ANY) ALARM TYPE OLD-LOW NEW-HIGH ALARM VALUE OLD -5.000A NEW-20.000A IMAGE 3

IMAGE 2 IMAGE 1 than 20 A. So set the alarm type at HIGH as image 2.

Now set the current value to 20 A as shown in image 3. ALARM DURATION The main feature we included for compressor protection is OLD-60 SECOND alarm duration. Compressor takes high current for some NEW-10 SECOND time at their startup. So we put an extra feature as alarm IMAGE 4 duration(image 4) in which you can set time in which motor takes high current. If we assume that for 10 second at startup motor takes high current then set the alarm duration at 10 second.

So if the current raising beyond set value you will got an SMS and also email. You can also set relay for that which can off the motor if alarm occur. So your Compressor will be protected. You can set various alarms in GML-3 according to your requirement.

Uma Electronics Enterprise, 2012 http://www.umaelectronics.com

28th April 2014

Version 2

AN003
.

You can view log of all energy parameter on www.emdata.in . From where you can view your motor energy status online from anywhere anytime. If you are using the generator and other energy source then you can find by graph which source cause your motor damage. By above graph you can see your compressor running status, how much current it takes, when it gone on and off. You can view all parameters by graph and analysis by yourself.

IMAGE 5

FEATURES FOR COMPRESSOR AND CRITICAL MACHINE PROTECTION:


1. Over current protection 2. Over voltage protection 3. Phase reversal protection system 4. Any Phase missing protection system 5. Low P.F. protection 6.Mobile SMS on Alarm and event. 7. Direct email on alarm and event. 8. Set various alarm on same time. 9. Continuous data logging on server www.emdata.in . 10. Low cost and highly reliable.