Type: ADR141A
(ADI TYA Series)
(Preliminary)
Features:
4 Element (3 Phase + EF) Over current
IDMT with instant trip.
Back - lit LCD display for settings.
Display of fault current. / Load current.
Selection of Curve: Six selectable curves
(Normal Inverse1 (C1), Normal Inverse2
(C2), Very Inverse (C3), Extremely Inverse
(C4), Long Time Inverse (C5) & Definite
Time (C6).
Separate curve selection for phase and EF.
Design using DSP technology.
Latching of fault current up-to last 5 fault
Password protection for setting.
Site selectable CT secondary (in Model
AM00103xxxxx)
Relay can be made ether IDMT or Define time
Programmable operating time in instantaneous element
Breaker Fail Function (in Model AM00104xxxxx)
General:
The ADR141A is member of Ashida Numerical Relay family (Aditya Series) design to meet demand of
low and medium switchgear control. The ADR141A is a 3 OC and 1 EF relay with Instantaneous high set
and programmable output to simplify feeder protection wiring. The ADR141A continuously monitors all 3
phase and earth current, through CT connections. The high-speed micro-controller samples this current
through a 12-bit A/D converter. The micro-controller performs powerful Digital Algorithms to find out
Amplitude of current signal, and then this value is use for protection and metering function. All
measurement is tuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD
display for metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3)
Measurement
The Relay can be supplied with different model. It can be either Definite Time or IDMT.
ASHIDA Numerical OC/EF
Protection Relay
ASHIDA
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 2 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
1. Protection Functions:
The ADR141A give maximum benefit/cost ratio. The ADR141A give all the advantage of numerical
relay at affordable cost. Following is summery of different protection functions provided by relay.
ANSI IEC Protection Functions
50 I >> Instantaneous Over current Protection (OC-Inst.)
50N I
E
>> Instantaneous Earth Fault Protection (EF-Inst.)
51 I>t, Ip Time Over current Protection (Phase) (OC-IDMT.)
51N I
E
>t, I
EP
Time Over current Protection (Earth) (EF-IDMT.)
1.1. Over current / EF protection:
The ADR141A has 4 sensing element 3 OC and 1 EF. The tripping current can be set from 50% to
200% for phase and 5% to 80% for Earth fault in steps of 1% by Keys switch provided on front
panel. The unit has got selection of IDMT characteristic of international IEC standard Very inverse /
Extremely Inverse / Long Inverse and Standard inverse (both 3.0 sec and 1.3sec at 10 times). The
unit also has Time Multiplier Setting (TMS) from x0.01 to x1.0 for IDMT delay multiplication. The
instantaneous tripping function is having range of 100% - 3000% for phase and 100% - 1200% for
EF and can be set in steps of 100%. The high speed CPU continuously monitor the all four current
inputs and compare with IDMT as well as instantaneous setting. If any one current is above
instantaneous setting the relay provide immediate trip command bypassing IDMT delay. If is input
current is less than instantaneous setting but more than IDMT setting, CPU calculate IDMT delay as
per selected IDMT characteristic multiply it with TMS setting and provide trip command if fault is
persist even after this time delay.
All the settings are password protected to prevent unauthorised change.
The relay is available in verity of model for different application
Ref. Ordering information
1.2. Extra Alarm Contact:
Any Protection panel required extra contacts for provide visual ALARM and ANNUNCIATION
indication for operator. Also some status contacts for SCADA or remote indications. Usually
separate electromechanical relay used for contact multiplication of protection relay contacts. This
added extra wiring and extra hardware. The ADR141A provide separate programmable ALARM
contact for such application. Maximum 4 nos. of extra contacts can be provided. These contacts
can be programmed as follows
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 3 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
For Model: AM 00102xxxxx
Function ANN1 ANN2 ANN3 ANN4
Type 1 OC1 OC2 OC3 EF
Type 2 OCIDMT OC-Inst. EF-IDMT EF-Inst.
For Model: AM 00104xxxxx and AM00105xxxxx
Function ANN1 ANN2
Type 1 Phase EF
Type 2 IDMT HF
And Breaker Fail contact
For Model: AM 00110xxxxx
Function ANN1 ANN2
Type 1 Common Alarm BF
Type 2 Phase EF
2. Supervision Function:
2.1 Self-supervision:
The continuously keeping track on its internal hardware and the movement it detect any failure of
any component, it give message on LCD display, This feature is very useful to give pre information
to avoid any mall - operation. In such situation it use some default setting and remain in protection
mode.
3. Measurement Function:
In normal condition this display shows all settings. Via keyboard the display can be program to show
the actual current flowing through the relay. If current excesses set value the relay gives trip
command. The type of fault is displayed on LCD display. During the fault condition the relay
measure the fault current and store in non-volatile memory. The fault current can be read via
keyboard on LCD display Last 5 fault values along with tripping counter can be view via key-
board. All settings are save in Electrically erasable read only memory and remain.
Ordering Information:
The relay is available with nos. of different option. The option is specified by model no. It is user
responsibility to specify correct model no. while ordering.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 4 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
While Ordering Specify the following I nformation for ADR141A Relay
Orderi ng i nf ormat i on :
A D R 1 4 1 A - A M - X X X - X X - X - X - X X - X
Exampl e
ADR141A AM- 001- 02- 2- 0- 2- 0
Type : ADR141A
Back Ter mi nal Layout : With 4 Programmable extra contact, Fix CT.
Cabi net Type : CSA- 150 non Dr awout
Auxi l i ar y Suppl y : 77- 250Vdc
CT sec : 5 Amp.
AM XXX XX X
3OC + 1EF Relays
001 01 Relay without extra contacts, Fix CT. CSA 150 1 / 2
02 Relay with 4 Programmable extra contact, Fix CT. CSA 150 1 / 2
03 Relay without extra contact, with Site Selectable CT
Sec,
CSA 150 3
04 Relay with Breaker Fail contact, 2 Ann. contact, with Fix
CT.
CSA 150 1/ 2
05 Relay with Breaker Fail contact, 2 Ann. contact, with
Site Selectable CT,
CSA 150 3
06 Reserved - -
07 Relay Without extra contacts, Fix CT. CSA 150D Drawout 1 / 2
08 Relay without extra contact, with Site Selectable CT
Sec,
CSA 150D Drawout 3
09 Reserved - -
10 Relay with 2 Programmable Extra contacts, Fix CT. CSA 150D Drawout 1/2
D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s
AM XXX XX X X XX X
Auxiliary Supply
01 = 18 52 V dc 06 = 110 V dc
02 = 77 250 V dc 07 = 220 V dc
03 = 24 V dc
04 = 30 V dc
05 = 48 V dc
Reserved for Future Use
PT Secondary
0
CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 5 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
Technical Specifications:
Sr. No. Specification Particulars
I. For Model AM001xx
[ 3OC + 1EF relay ]
: Model
AM00101xxxxx ,
AM00102xxxxx ,
AM00104xxxxx ,
AM00107xxxxx ,
AM00109xxxxx &
AM00110xxxxx
Fix CT 1A or 5A specify wihile ordering Inputs
: Model
AM00103xxxxx &
AM00108xxxxx
Suitable for CT secondary 1.0 Amp or 5.0 Amp.
(Selectable)
: Setting For phase 50% - 200 %
For EF 5% - 80%
: Operating Time Normal Inverse 1 (C1)
Normal Inverse 2 (C2)
Very Inverse (C3)
Extremely Inverse (C4)
Long Time Inverse (C5)
Definite Tme (C6) 00(Inst) 99.9Sec
: Inst. Setting For phase 100% - 3000%. or bypass
For EF 100% - 1200% or bypass
Protection Relay Setting
Range
: Inst Operating Time 00(Inst) 1.0Sec
Inst = < 50ms
: Model
AM00101xxxxx
1) 2 NO Trip duty contact for Alarm and Trip
: Model
AM00102xxxxx
1) 2 NO Trip duty contact for Alarm and Trip
2) 4 programmable NO contacts for ALARM
: Model
AM00103xxxxx ,
AM00107xxxxx &
AM00108xxxxx
2 NO Trip duty contact for Alarm and Trip
: Model
AM00104xxxxx ,
AM00105xxxxx ,
AM00106xxxxx &
AM00109xxxxx.
2 NO Trip duty contact for Alarm, 1NO Alarm
Contact for Breaker Fail and 2 programmable NO
contacts for ALARM
Output contacts
: Model
AM00110xxxxx
1) 2 NO Trip duty contact for Alarm and Trip.
2) 2 NO Ann. Duty Programmable Contacts.
II. Pickup Current : Within 1.1 times of set current value.
III. Resetting Current : 90% of set value.
IV. Time Accuracy : Within class 2.5 As per IS: 3231.
V. Burden on CTs : Less than 0.2VA.
VI. Aux. Supply : 18 52VDC or 77 250VDC. To be specified while ordering.
VII. Burden on Aux. Supply : Less than 10VA on any supply.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 6 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
VIII. Contact Rating Trip Duty : Make and carry for 3sec. 7500VA with max. 30A & 660VAC/DC
: Make and carry for continuous 1250VA with max. 5A & 660VAC/DC
: Break AC 1250 VA DC 100 W resistive 50W inductive.
IX. Operational Indicators (Flags)
ON : Green LED indicates Relay OK
: In case of following condition led become off
1. Problem in relay Hardware.
2. Auxiliary supply is not sufficient for relay operation.
FAULT : Red LEDs indicates the OC/EF relay trip, Hand Reset (HR) Type.
PKP : Red LED indicates OC/EF relay Pickup.
TRIP : Indicates that Trip pulse is being executed. When BYPASS P.B. is
pressed, actual trip is not executed.
X. Thermal Withstand Capacity : x40 times the normal current for 3sec.
: x2 Continuous
XI. High Voltage Test : IEC 60255-5
: Except DC Voltage 2.0 kV (RMS), 50Hz
: Only DC voltage - 2.8 kV DC
: Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz
: Between Open contact of ALARM 1kV (RSM) 50Hz
XII. Impulse Voltage Test (all
circuit class III)
: IEC60255-5
: 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse at interval
of 5 sec
XIII. High Frequency test : IEC 60255-22-1, Class III
: 2.5 kV (peak) 1MHz , = 15s 400 surges / s duration 2 s
XIV. Electro static Discharge : IEC 60255-22-2 Class III and IEC 61000-4-2 class III
: 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri
330
XV. Irradiation with radio
frequency field, pulse-
modulated,
: IEC 60255-22-3 and IEC 61000-4-2 class III
: 10V/m; 80 to 1000MHz; 80%; 1kHz AM
XVI. Fast transient
interference/bursts
: IEC 60255-22-3 and IEC 61000-4-3, class III
: 4kV; 5/50ns; 5kHz burst duration = 15ms;
: Repetition rate 300ms; Both polarities; Ri = 50; duration 1 min.
XVII. Shock Test : IEC 60255-21-2 class 1
: Semi-Sinusoidal
: 5g acceleration, duration 11ms,
: Each 3 shocks in both direction of the 3 axes
XVIII. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6
: Sinusoidal 10 to 60Hz 0.035 mm
: Amplitude, 60 to 150Hz, 0.5g acceleration
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 7 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
XIX. Seismic Test : IEC 60255-21-3
: In single axis sine sweep in X-axis
01- sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn
(whichever is less)
: In single axis sine sweep in Y-axis
01- - weep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn
(whichever is less)
XX. Bump Test : IEC 60255-21-2 Class-1
: 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each
of the two opposite direction per axis as per IEC60255-21-2 class 1 No.
of axes . 3.
XXI. Shock Withstand : IEC 60255-21-2 Clas-1
: 3 shocks of 15gn peak acceleration and 11ms pulse in each of two
opposite direction . No. of axis : 3
XXII. Shock Response Test : IEC 60255-21-2 Clas-1
: 3 shocks of 1gn peak acceleration and 11ms pulse in each of two
opposite direction . No. of axis : 3
XXIII. Vibration Endurance Test : IEC60255-21-1
20-sweeps (@ a sweep rate of 1octave / minutes) vibration in the
frequency range (10-150Hz) at 1 gn (9,8m/s2) acceleration in each of the
3 mutually perpendicular axes
XXIV. Environmental withstand
(cold, Dry heat & steady state
Damp Heat)
: IEC60068-2
Cold 2 hours operational condition at (40 +/- 3) deg C as per
IEC60068-2-1
Dry 2 Hours dry heat operational condition at(55+/2 2 deg. C as per
IEC60068-2-2
Steady state damp heat - 2 hours steady sate damp heat operational
condition at temperature at (55 +/- 2) deg. C & humidity 95% RH as per
IEC60068-2-78
Drawing References : For Cabinet Type CSA -150 - MAC00101
: For Operating
Characteristics
C1 - APR02201
C2 - APR01801
C3 - APR05101
C4 - APR05201
C5 - APR05301
XXV.
: For Electrical
Connection
3OC + 1EF AM00101/02xxxxx - APR06801
3OC + 1EF AM00103xxxxx - APR06802
3OC + 1EF AM00104xxxxx - APR06803
3OC + 1EF AM00105xxxxx &
AM00106xxxxx
- APR06804
3OC + 1EF AM00107xxxxx &
AM00109xxxxx
- APR06805
3OC + 1EF AM00108xxxxx - APR06806
3OC + 1EF AM00110xxxxx - APR06809
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
ASHIDA ELECTRONICS PVT LTD.
Plot No. A-308, Road No. 21,
Wagle Industrial Estate,
Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com
Web: www.ashidaelectronics.com
Ref.: ADR141A
Issue: 07 15.11.07
Page 8 / 8
Type: ADR141A
(ADI TYA Series)
(Preliminary)
Datasheet Change Log for ADR141A
Issue No.
(Revision)
Date Description /Changes
01 26.06.04 Original Revision
02 04.12.04 1) Description of Extra ALARM contacts added
2) Model no. Ordering Information added
03 28.10.05 Model AM00103 & AM00104 Added
04 28.01.06 Model AM00105 added
05 15.04.06 Ordering Information added.
05A 08.03.07 Reset current is changed from 80 -- 90%
06 11.05.07 Model Am00107,Am00108 &Am00109 Added.
06A 09.06-07 IEC test added
Seismic Test
Bump Test
Shock Withstand
Shock Response Test
Vibration Endurance Test
Environmental withstand (cold, Dry heat & steady state Damp Heat)
07 15.11.07 Model: AM 001 10 Added.