You are on page 1of 63

Rebecca Dick

Structural Option
Dr. Memari
Spring 2012 Senior Thesis
April 4, 2012
Blast Design and Analysis
National Business Park- Building 300
300 Sentinel Drive
Annapolis Junction, MD, 20701
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 2

Acknowledgments

A very special thank you Dr. John O. Hallquist, President, Livermore Software Technology Corporation
(LSTC), and Marsha J. Victory, President, FEA Information Inc, for providing me access to the LS-DYNA
finite element software for free for my senior thesis and to Gunther Blankenhorn and Todd P Slavik for
the invaluable technical support and troubleshooting they provided.
Additional thanks to Michael Baker, Jr., Inc. for the use of National Business Park- Building 300,
especially Mr. Erik Spicker.
Special Thanks to:

My Family:
Thank you to my dad for always answering my questions for the last five years. Thank you to my mom
for listening to me complain all the time and putting up with my breakdowns. Thank you to my brother
for giving me academic competition.
Penn State Faculty:
Dr. Memari
Dr. Hanagan
Dr. Parfitt
Ryan Solnosky
My Friends:
Brian Rose
Dave Tran
Mike Kostick
Ryan Blatz
Liz Kimble
Rob Livorio
RJ Fazio
The past five years have been a blast and I couldnt have made it through without you guys. Youve kept
me as close to sane as any AE can be through all the crazy projects, late night study sessions, and post-
exam celebrations. I will always love you guys!
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 3


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 4

Table of Contents
Acknowledgments ......................................................................................................................................... 2
Special Thanks to: ................................................................................................................................. 2
Executive Summary ....................................................................................................................................... 6
National Business Park- Building 300 ............................................................................................................ 8
Structural Background .................................................................................................................................. 9
Foundations .............................................................................................................................................. 9
Floors....................................................................................................................................................... 12
Load Path ............................................................................................................................................ 12
Columns .................................................................................................................................................. 13
Lateral System ......................................................................................................................................... 14
Load Path ............................................................................................................................................ 15
Impact of Lateral System on Calculations ........................................................................................... 16
Design Codes ............................................................................................................................................... 17
Material Properties ..................................................................................................................................... 18
Original Design ........................................................................................................................................ 18
Reinforcement: ................................................................................................................................... 18
Structural Steel: .................................................................................................................................. 18
Metal Deck: ......................................................................................................................................... 18
Concrete: ............................................................................................................................................. 18
Blast Redesign ......................................................................................................................................... 19
Reinforcement: ................................................................................................................................... 19
Structural Steel: .................................................................................................................................. 19
Metal Deck: ......................................................................................................................................... 19
Concrete: ............................................................................................................................................. 19
Gravity Loads............................................................................................................................................... 20
Dead Load ............................................................................................................................................... 20
Live Load ................................................................................................................................................. 20
Snow Load ............................................................................................................................................... 20
Structural Proposal ..................................................................................................................................... 21
Blast Design ................................................................................................................................................. 22
Procedure .................................................................................................................................................... 23
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 5

Blast Load Determination ........................................................................................................................... 24
Column Design ............................................................................................................................................ 28
Beam Design ............................................................................................................................................... 30
Girder Design .............................................................................................................................................. 32
Slab Design .................................................................................................................................................. 33
Moment Connection Design ....................................................................................................................... 36
Final Design ................................................................................................................................................. 39
LS-DYNA Modeling ...................................................................................................................................... 40
Comparison of Results ................................................................................................................................ 44
Additional Comments and Conclusion ........................................................................................................ 48
Lateral System Implications .................................................................................................................... 48
Effects on Foundations ........................................................................................................................... 48
MAE Requirements ..................................................................................................................................... 49
Breadth Topic I: Site Redesign .................................................................................................................... 50
Breadth Topic II: Faade Redesign and Heat Transfer ................................................................................ 54
Faade Design ......................................................................................................................................... 55
Heat Transfer .......................................................................................................................................... 57
Cost Estimates ............................................................................................................................................. 61
Conclusion ................................................................................................................................................... 63



Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 6

Executive Summary

National Business Park- Building 300 is a seven story office building located in Annapolis Junction,
Maryland. It was designed in 2007 and construction was completed in 2009. The structure of NBP-300
is composed of a composite steel system and utilizes four eccentrically braced frames for the lateral
system located at the core of the building.
National Business Park- Building 300 was not designed to resist blast, and therefore, were an attack
made on the building, heavy structural damage would likely result. For this reason, it will be assumed
that NBP-300 will be redesigned as a high risk building for terroristic threats, and as such would be
required to meet certain criteria for blast loading. Designing for interior blast has many challenges, as
well as many solutions. There is no clear cookie-cutter method to designing for blast, which makes it
one of the most intriguing and interesting new topics of study. Blast design isnt new per say, but in the
realm of structural design, it has only be in consideration for the last 50 years or so. Although
progressive collapse is a major issue when designing for blast, the scope of this redesign will be limited
to strength factors only due to time restraints, and redundancy of design will be ignored.
A specific situation has been created for the design. It can be assumed that the greatest threat in terms
of explosives will be a briefcase sizes device detonated in the interior of the lobby on the second floor.
The UFC -340-02 documents outlining blast requirements were used to identify threat levels, design site
security, and find blast loads. The blast load from this situation was calculated and a typical bay located
at the lobby location was designed to withstand the blast loading found. Additionally, the faade of
NBP-300 was redesigned to allow venting of the interior during the blast. The large percentage of glass
currently on the faade could potentially be harmful to occupants when the faade fails.
LS-DYNA Blast Modeling software was used to analyze a critical portion of the original and redesigned
structure. A comparative study was completed where the assumed explosive for this situation was
detonated in the original LS-DYNA model and the redesigned LS-DYNA model. The intent was to
minimize structural damage as much as economically possible through this redesign. By comparing the
original structure to the redesign it became apparent that the redesign was highly conservative, but
overall, withstood the blast load and incurred very little damage.
In addition to the blast design and analysis, a site redesign was completed. Also, a faade breadth was
completed, including a faade redesign with anchored blowout panel and a heat transfer study of the
new faade.
MAE coursework was incorporated into several aspects of the redesign for NBP-300, including building
modeling techniques (AE 597A), a moment connection design (AE534), and a faade design (AE542).


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 7


Going into this thesis design, the following goals were set forth and achieved:
Design a typical beam, girder, column, moment connection, and floor system
Use a finite element analysis software (LS-DYNA Blast) to model the effects of blast in the
original structure and redesigned structure, and compare the results
Show that designs using hand calculations are overly conservative
Redesign the site of NBP-300 to mitigate large exterior blasts
Redesign the faade of NBP-300 to allow venting of the interior during an interior explosion
Calculate heat transfer through the new faade and determine if the new design is acceptable


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 8

National Business Park- Building 300

National Business Park- Building 300 is an office building located in an industrial park in Annapolis
Junction, Maryland. Owned by COPT, the seven story office building, which has an additional
mechanical penthouse on the roof, was designed in 2007 and construction was completed in 2009. As
part of an industrial park, the architecture was intended to complement the existing offices in the
surrounding area. Shown below in Figures 1 and 2 is the building footprint of National Business Park-
Building 300 and a satellite view of the building, respectively.
NBP-300 is a 212,019 gross square foot, 116.92 tall, composite steel framed building that utilizes braced
frames for its lateral system. Foundations consist of strip and spread footings, but since the first story is
only a partial floor plan, and is sub-grade at a few locations, footings are located below both the first
and second stories at their respective locations. The faade system is composed of a glass and precast
concrete curtain wall that is tied into the structural system at each floor level.


Figure 1: NBP-300 Footprint on Site Figure 2: Satellite View of NBP-300 provided by
Courtesy of Baker and Associates Google Maps, 2011



Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 9

Structural Background

Foundations
Since the first floor is only a partial floor and the grading on the site is such that the second floor is at
ground level at the main entrance, foundations occur below both the first and second floors at the
respective areas where no preceding floor exists below. Figure 3, on the following page, outlines the
area of the partial first floor. Figure 4, also on the following page, provides more detail by showing a
section cut in the North-South direction, which shows the partial first floor and the slab on grade and
foundations on the second floor. Additionally, two side of the first floor will be supported by basement
walls. These walls are reinforced with #7 bars at 10 on center, each face, vertically, and #5 bars at 12
on center, each face, horizontally. These walls will see lateral pressure from soil, which was noted to be
60 psf per foot of depth in the structural notes.
The foundations of NBP-300 consist of strip and spread footings with a 5 slab-on-grade on the partial
first floor and on the second floor where it does not sit over the first floor, and were designed to meet
the suggestions set forth in the geotechnical report prepared by Hillis-Carnes Engineering Associates,
Inc. 6x6 W2.0xW2.0 Welded Wire Fabric was used in all slabs-on-grade. A bearing pressure of 3.5 ksi
was required for all foundations. 4 of compacted backfill meeting AASHTO 57 course aggregate was
also a requirement below the slabs-on-grade.
The strip and spread footings are located around the perimeter of the partial first floor and at the
perimeter locations on the second floor that contain the slab on grade. Additionally, interior columns
are supported by spread footings. These range in size from 8 square to 19 square, depending on the
location and the load. The depths of the spread foundations also vary between 24 to 46. A
5-0x5-0 footing at piers is typical, reinforced with #5@12 on center, each way.
Additionally, the mechanical room on the first floor is sunken 3 below the standard floor level which
required the foundations to be stepped down at the transition locations.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 10



Figure 3: Outline of Partial First Floor Plan on Foundations, Courtesy of Baker and Associates


Figure 4: Building section showing partial first floor and slab on grade at second floor,
Courtesy of Baker and Associates
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 11


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 12

Floors
NBP-300 was constructed using a composite steel system. For the floors, this entailed the use of
cambered composite beams and girders. A 3 lightweight concrete topping (117 pcf) on 3x20 gage
metal floor deck, bonding type, was used on each elevated floor for the composite slab, reinforced with
6x6 W2.0xW2.0 welded wire mesh. Additional reinforcement was required over filler beams and girders
along column lines. This additional reinforcement consists of #3 bars at 18 on center, 8-0 long.
Composite action is obtained through the use of diameter, 5 long shear studs spaced equally
along beams. See Figure 5, below, for a typical section cut through the composite floor system.
Floor beams vary in size and vary per floor, but are cambered 0, , or 1, depending on the location.
The exterior girders also vary in size, but are not cambered. Beams typically span 35 at 10 on-center,
while girders typically span 30 at 35 on-center.
Load Path
Gravity loads on each floor are transferred from the composite slab to the beams. The load is
then transferred to the girders, which then transfer the load to the columns. The gravity loads
terminate at the foundations at the second level or at the partial first level.







Figure 5: Typical Composite Floor System,
Courtesy of Baker and Associates






Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 13

Columns
Wide flange columns are used throughout NBP-300. Although the weight of the columns differs
throughout the building and across floor levels, most wide flanges are W14 and all conform to ASTM A-
992 Grade 50 steel requirements. Splices occur at levels 4 and 6 for most columns. This information is
presented in a column schedule, of which a partial view can be seen in Figure 6, below. At the
penthouse level, square HSS posts are used around the perimeter of the enclosure to support the
penthouse cladding.
Base plates are used to connect the steel columns to the foundations or shear walls located on the first
floor. The base plates vary in size, but conform to ASTM A-36 type steel.


Figure 6: Partial Column Schedule,
Courtesy of Baker and Associates




Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 14

Lateral System
The main lateral system used in NBP-300 consists of four different eccentrically braced frames. These
occur at column lines D, E, 4, and 11, each spanning about one full bay (See Figure 9 on the
following page). This provides two lateral bracing frames in each direction. The frame at column line
D begins on the first floor, while the other three frames begin on the second floor, supported by
concrete shear walls on the first level. Two wind bracing frames are shown below, in Figures 7 and 8, to
show the difference in height. The shear walls at the base of the three shorter frames are 1-2 thick
and are reinforced with #7 bars at 10 on center, each way on each face of the wall.
HSS tubes are used for the bracing, and vary in size from frame to frame, but conform to ASTM A-500
Grade C steel and have a yield strength of 46 ksi. All connections in the braced frames are slip-critical.
Shear studs at wind bracing beams occur at 12 on center, and are in diameter and 5 in length. At
the base plates, an 8x4x3/4 angle at 1-6 in length is used on each side of the gusset plate to resist
100% of the design shear. Additionally, 7/8 diameter by 8 long shear studs are used at the shear wall
connections for the three elevated braced frames.

Figures 7 and 8: Wind Braced Frames, Courtesy of Baker and Associates
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 15



Figure 9: Location of Braced Frames at Core of building, Courtesy of Baker and Associates


Load Path
As wind lateral forces are applied to NBP-300, they are transferred from the faade to the
composite floor system through bearing connections. From there, the load is transferred from
the floor system to the four braced frames, which travel through the height of the building to
foundations and shear walls on the first and second floor. Where braced frames connect to
shear walls, the load is then resisted by the shear wall and ultimately transferred to the
foundations below.
Ground motion due to seismic loads is resisted by the foundations, first floor shear walls, and
braced frames that run the height of the building. As each floor is seismically loaded, the force
is transferred to the braced frames, which transfers the load to the foundations and shear walls
at the base of the building.








Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 16


Impact of Lateral System on Calculations
The lateral system used in the design of NBP-300 consists of four eccentrically braced frames. In
ASCE 7-05, this system provides a Response Modification Coefficient of 7, but since the
structural documents provided for NBP-300 specifically state that seismic resistance was not a
controlling factor in design (see Figure 10 below), an R value of 3 was used instead, to allow
comparison between the calculations presented in this document and the design criteria of NBP-
300. This assumption effected the seismic calculations, namely the value of the seismic
response coefficient. By using R=3, a higher base shear was calculated, making this a
conservative assumption for design. In regards to detailing, this system may be more
complicated and expensive. Eccentrically braced frames are used more in regions with high
seismic activity, but by using an R=3, the stability will be affected during design and will have to
be compensated through other detailing methods.



Figure 10: Response Modification Coefficient Assumption,
Courtesy of Baker and Associates









Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 17

Design Codes

National Business Park- Building 300 was designed in 2007 and constructed in 2009. At this point in
time, the following codes were used to complete the design of the project:
International Building Code (IBC) 2003 (with local amendments for Anne Arundel County,
Maryland)
The Life Safety Code, 2006 (NFPA 101)
ASCE 7-02
AISC, 13
th
Edition
ACI 318-02
AISI Specification for the Design of Light Gage Cold-Formed Structural Steel Members and the
Steel Deck Institutes Design Requirements
Specifications for Masonry Structures, ACI 530.1/ASCE 6/TMS 602-92
Structural Welding Code, 2006, D1.1



In the redesign, the codes listed below were used to complete the analysis of National Business Park-
Building 300.
International Building Code (IBC) 2009
ASCE 7-05
AISC, 13
th
Edition
ACI 318-05
Vulcraft 2008 Decking Manual
UFC-340-02
AISC Seismic Design Manual


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 18

Material Properties

Original Design
Reinforcement:
Reinforcing Bars ASTM A615, Grade 60
Welded Wire Fabric (WWF) ASTM A-185
Reinforcing Bar Mats ASTM A184
Lap Splices ACI 318
Structural Steel:
Grade 50: ASTM A992, Grade 50, F
y
= 50 ksi
HSS Pipes: ASTM A500, Grade C, F
y
= 46ksi
Steel Tubes: ASTM A500, Grade B, F
y
= 46ksi
All other steel: ASTM A 36, F
y
= 36 ksi
Bolts: ASTM A325, with threads included in shear planes,
or 7/8 diameter
Shear Studs: diameter x 5 long, uniformly spaced at 24
maximum
Metal Deck:
Floors: 3x20 gage, bonding type
Roof: 3x22 gage

Concrete:

Minimum Concrete Compressive Strengths (f'
c
)
Member 28 Day Strength (psi)
Elevated Slabs 3500
Slab-on-Grade 3500
Walls, Piers, and Grade Beams 4000
Interior Concrete Topping 3500
Concrete Exposed to Freezing 4500
Grout 3000
All Other Concrete 3000

Table 1: Minimum Concrete Compressive Strengths


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 19

Blast Redesign

The following material properties were used in the redesign:

Reinforcement:
Reinforcing Bars ASTM A615, Grade 60
Welded Wire Fabric (WWF) ASTM A-185
Lap Splices ACI 318
Structural Steel:
Grade 50: ASTM A992, Grade 50, F
y
= 50 ksi
All other steel: ASTM A572, Grade 50, F
y
= 50 ksi
Bolts: ASTM A325, with threads included in shear planes, 1.5
diameter
Metal Deck:
Floors: 3VLI16, composite

Concrete:

Minimum Concrete Compressive Strengths (f'
c
)
Member 28 Day Strength (psi)
Elevated Slabs 4000
Slab-on-Grade 4000
Walls, Piers, and Grade Beams 4000
Interior Concrete Topping 4000
Concrete Exposed to Freezing 4000

Table 2: Minimum Concrete Compressive Strengths






Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 20

Gravity Loads
Using IBC 200, ASCE 7-05, and estimation, the dead, live, and snow loads were calculated for NBP-300.
Tables 2, 3, and 4 that follow show the loads used for the analysis presented in this paper compared to
the loads used in the original design of NBP-300.
Dead Load

Superimposed Dead Loads
Area Design Load
Floors 15 psf
Roofs 15 psf
MEP 20 psf
Table 3: Superimposed Dead Loads
Live Load

Live Loads
Area Design Load ASCE 7-05 Load
Floors (including partition load) 100 psf 80 + 20 psf
Mechanical Room 125 psf -
Elevator Machine Room 150 psf -
Penthouse Floor 150 psf -
Stairs 100 psf 100 psf
Slab-on-Grade 150 psf -
Screen Enclosure and Roof Area 60 psf 60 psf
Table 4: Live Loads
Note: (-) signifies that there was no recommended value from ASCE 7-05 for the specified loading
condition and the design load was assumed to be correct.
Snow Load

Snow Loads
Load Type Design Load ASCE 7-05 Load
Roof Snow Load 20 17.5
Drift Load Not available 81.94
Table 5: Snow Loads

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 21

Structural Proposal

National Business Park-300 was designed initially as a typical office building. For the purpose of this
thesis, it will be assumed that National Business Park- Building 300 will be designed as a Federal office
building with the potential to be a target of terrorism. This means that, to protect the life and safety of
the occupants of NBP-300, it will be required to be designed for blast loading.
The first step in designing for blast is to determine the type and level of threat expected. It was decided
that the site would be redesigned and the security of the site increased to eliminate a vehicular
explosion from being the controlling blast load. It was then determined that the controlling load would
be a small-device, and that it most likely would be an interior explosion.
Using these specific design constraints, a typical bay of National Business Park- Building 300 was
redesigned to withstand the blast load. This includes the design of a column, a beam, a girder, and the
floor slab. A typical moment connection will also be discussed. Due to time constraints, progressive
collapse and a lateral system analysis were not completed, but would be investigated in depth if given
more time.
The intent of this redesign is to show a difference in the amount of structural damage between a
building designed for blast and a building not designed for blast, and to determine the effectiveness of
minimizing structural damage using blast design and analysis. This thesis will also look at the
effectiveness of modeling only critical sections of a building designed for blast. This will be achieved
through the use of LS-DYNA Blast Modeling software, a finite element analysis program. Comparisons
between the two structures and their reactions to an explosive event will be discussed in detail, and
through design and analysis, it will be shown that the linear elastic method is highly conservative.


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 22

Blast Design

Until the 1960s, blast design was reserved for facilities where accidental or chemical explosions could
occur. Blast design was not considered for ordinary structures. In the 1960s, though, design guides for
blast started to emerge, mostly for buildings with the potential for chemical explosions. In todays
world, terrorism is an unfortunate reality, and designing for the safety of the occupants in high risk
structures has become more important. After the Oklahoma City bombing in 1995, blast design gained
significant popularity as a design consideration for life safety. Since 9-11, blast design has become a
well-sought after design not only for federal and military building, but other high risk buildings such as
hospitals, banks, and international business buildings, to name a few, and is an issue of life safety.
Blast design has to take into consideration both impact loads from the initial wave front of the blast, and
additional time-dependent pressures, which can occur due to thermal effects behind the wave front.
Reflected pressures must be taken into account as well as ventilation to relieve built up pressures in
confined explosions. In some cases, shrapnel from the explosive container may act as a projectile, and
could cause serious damage, such as breaching.
Much of blast design is based on the members behaving plastically. Therefore, there are strict limits on
their ductility ratios and support rotations. The ductility ratio is an approximate measure of plastic
strain based on the assumption that the curvature in the maximum moment regions increase
proportionally with deflection after yielding and plane sections remain plane, as stated in the
Handbook for Blast Resistant Design of Buildings. The limit on the ductility ratio makes sure the
members plastic deflections are within the allowable range. The limit on the support rotation
maintains that tension membrane action that may develop in a member will be limited so as not to
cause connection failures.
Due to the unpredictable nature of blast design, often times it is overly conservative. Sometime,
though, this over conservative nature leads to unreasonable designs or costs. For that reason, structural
elements are allowed to be damaged, as long as collapse is prevented.
The principles of blast design were researched throughout this redesign and will be presented through
calculations, diagrams, tables, and figures throughout this thesis.




Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 23

Figure 11: UFC-340-02 Cover Page
Procedure

The first step in designing for blast is to decide what the maximum threat on the building will be during
the life of the building. As stated in earlier section, in this case, it was determined that an interior blast
from a briefcase sized explosive would be the design scenario. To eliminate the possibility of any other
type of blast controlling, both building setback and site control had to be determined. This information
will be presented in the Site Redesign Breadth.
Next, the blast load was determined by using
engineering judgment to estimate the type of
explosives in the blast. In this scenario, C-4 was used to
estimate the blast load. By following the UFC-340-02
(seen to the right in Figure 11) prescribed technique,
blast pressures were determined for the specific
situation set forth in the problem statement.
After determining blast loads, the member designs
were completed. A typical column, an interior beam,
the exterior girder, and the floor slab were designed for
the determined blast pressures. Plasticity was
considered in each design. Additionally, a moment
connection design was investigated.
After the hand calculations were completed for the
member designs, LS-DYNA was used to build a partial
model of NBP-300. A 3 bay by 3 bay by 3 story model of
NBP-300 was built to demonstrate several findings.
Firstly, it was a goal of this thesis to show that since the
stress in structural members decreases significantly as distance from the bay of detonation increases it
is not necessary to show an entire model. The blast forces may not even be significant in bays that are
two or three bays from the initiation of the blast in some cases. Additionally, due to the sophistication
of the LS-DYNA program and the tedious nature of the input, it was deemed not in the scope of this
thesis to build the entire model.
All hand calculations, Excel spreadsheets, tables and figures used in the design process will be presented
in the appendices of this document, and will be referenced in the detailed explanations in each section.



Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 24

Figure 12: 3D Blast Wave Projections

Blast Load Determination

Blast loads are pressure waves caused by the rapid
release of energy during a chemical reaction. The
wave propagation is spherical in nature and
dissipates with distance from the blast initiation,
which can be seen in Figure 12 to the right. Although
the spherical nature of a blast wave will cause
differential pressures along the length of certain
elements, such as columns, it can be assumed to be
linear for simplification of design and analysis.
Generally, the design process using a single degree
of freedom method is conservative, so this assumption will still provide a valid design.
The first step of the actual design process in blast design requires that the blast event load be
determined. As C-4 was assumed to be the explosive compound being used in this analysis/redesign, a
determination of a reasonable weight of the explosive needed to be calculated. Since C-4 has properties
similar to clay, it was assumed that about 50 pounds of C-4 could fit inside a large briefcase or small
rolling suitcase. Since NBP-300 is an office building, it was assumed that the explosives would have to
be camouflaged to fit into the everyday environment of the workspace, hence a briefcase or a small
business suitcase.
The weight of C-4 then needed to be converted into equivalent TNT weight. Not a lot of research has
been done with explosives other than TNT to date, so all the tables and charts in the UFC used in blast
design were designed around data collected with TNT testing. Much is known about the explosive
power of this compound, but not of many others. Therefore, the weight of actual explosives assumed in
this scenario had to be converted into equivalent pounds of TNT. The conversion was performed by
dividing the weight of C-4 by the weight conversion factor found in Table 6.1 of The Handbook for Blast
Resistant Design of Buildings, and an excerpt from the table can be seen in Figure 13 on the following
page. The equivalent mass for pressure was used since design pressures would be the critical values for
the structural design.

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 25

Figure 13: C-4 Equivalency Conversion Factors, from
The Handbook for Blast Resistant Design of Buildings
Figure 14: Simplified Floor Plan of Lobby Area
with members to be designed highlighted



The equivalent weight was found to be 36.5 pounds of TNT.
Next, the scaled distance needed to be found, which is representative of the front of the pressure wave.
The equation

was used to find the scaled distance, which equaled to 4.5 ft/lb
1/3
assuming a
standoff distance of 15 feet since that would be the average distance of the explosive to the closest
structural elements in the lobby. See Figure 14 below for a simplified floor plan of the lobby area. From
this information the peak incident overpressure value of 50 psi was found using Figure 6.6 of The
Handbook for Blast Resistant Design of Buildings, which can be found in Appendix B.



Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 26

From these values the peak reflected pressure was found using the UFC figures. Interpolation between
Figures 2-100 and 2-97 provided a peak reflected pressure of 117 psi. Peak reflected pressure is
important in confined explosions because as the wave front encounters barriers, some of the pressures
are reflected off these materials, thereby increasing the pressure created by the blast. This is a critical
component for determining design loads.
Additionally, the

value was found similarly by interpolation between Figures 2-149 and 2-146
to give a value of 81 psi-ms/lb
1/3
. These values were then used to find the effective duration of the blast
from the UFC. An effective duration of 4.6ms was calculated.
This is only half of the battle, though. Since it is assumed, for the purpose of this thesis, that the
explosion will be a confined event, the gas pressure must also be calculated to account for the pressure
build up behind the initial front that occurs during an explosion due to the heat released during the
explosion. Gas pressure loading density was calculated by dividing the equivalent weight of TNT by the
free volume of the space. Then, Figure 2-152 of the UFC was used to determine the peak gas pressure.
Additionally, the scaled gas impulse was found using Figure 7-15 of The Handbook for Blast Resistant
Design of Buildings.
No fragmentation was accounted for in the determination of blast loads because it was assumed that
debris would be negligible. As stated previously, the explosives would likely be contained in a briefcase
or suitcase, which is assumed to disintegrate from tremendous heat and pressure at the initiation of
blast.
A summary of the pressure and impulse design values are summarized in Table 6 on the next page and a
diagram of the bilinear pulse blast loading expected can be seen in Figure 15 on the next page. The full
calculations are provided in Appendix B.









Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 27

Figure 15: Peak Reflected Pressure and Peak
Gas Pressure vs. Time

Table 6: Summary of Blast Load Data
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 28

Column Design

In blast design, there are many additional factors that affect the design process as compared to a
simpler design for service loads only. Certain ductility requirements must be met. Additionally, there
are both dynamic increase factors and overstrength factors that have to be considered during design.
The dynamic increase factors account for the increased yield and tensile strengths of steel due to rapid
loading.
The overstrength factor accounts for the fact that steel actually has a higher yield stress than specified
by the AISC. The Department of Defense Explosives Safety Board allows the use of this higher yield
stress in design and analysis.
There is an additional load combination to be checked, also: 1.0B+1.0D+0.25L. Since the controlling
load combination in the original design was 1.2D+1.6L for the gravity system, this was again used as the
controlling gravity load. Both load combinations were checked to determine the overall controlling
design load for the column.
In the original design, all connections were shear connections. As stated previously, the lateral system
was composed of four eccentrically braced frames, so the columns in the lobby took no lateral load as
they were not part of the original lateral system. Although the redesign requires all connections to be
moment connections, the controlling load combination for blast does not require other lateral loads to
be accounted for due to the probability of having maximum blast load simultaneously with maximum
wind or earthquake loads being very minimal. Therefore, the only lateral load applied to the column
was the blast load.
Another assumption made was that the column would behave plastically during the blast loading. This
allows the use of higher allowable strength values described previously.
To begin the design, several more assumptions had to be made. Firstly, the column was assumed to be
pinned-pinned. This assumption follows the procedure set forth in the UFC to allow for more simplified
calculations in the linear elastic analysis procedure. Additionally, due to the orientation of the columns
in the bay, it was assumed that only the flange would be loaded during the blast. Realistically, the load
would be distributed to both the web and the flange as it would originate at about a 45 angle to the
flange face.
Finally, it was assumed that the 117 psi peak reflected pressure would be the controlling pressure in this
design. The blast pressures were determined assuming that the explosion would detonate in the center
of the bay at floor level. As stated previously, the relationship between pressure and distance is not
linear, and the closer the blast is to a structural element, the higher the blast and impulse on that
member. Although the space will be fully vented and the reflected pressure is unlikely to ever reach 117
psi, the possibility of the blast being detonated much closer to the column exists. This would inflict the
most stress and have the highest probability of damaging the structure, so the 117 psi was used to
account for the possibility of this situation. This may be conservative, but column failure could result in
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 29

Figure 16: 3D model of typical bay with column called out
progressive collapse of the structure or pancaking of floors from above, so it is important to design the
column to withstand a direct blast load.
Once these assumptions were
established, the distributed and axial
loads on the column could be calculated.
Then the maximum moment and shear
values were calculated. An unbraced
length of 15 was used. The dynamic
yield strength was calculated by
multiplying the 50 ksi yield strength by
both the dynamic increase factor for yield
and the overstrength factor to get 71 ksi
yield strength. A preliminary section was
selected based on the required section
modulus, calculated by dividing the
maximum moment by the yield strength,
and the requirement that b
f
/2t
f
7. A
W14x159 was found to be the smallest
section that met the required 8.64 in
3

section modulus and the compact section
criteria.
The W14x159 was then analyzed to
determine if it met all the requirements for blast. This included checking the d/t
w
ratio, web shear, the
plastic section modulus, plastic moment, plastic axial load, slenderness ratio, allowable axial stress,
allowable moment, and the Euler buckling load. Modified interaction equations for blast loading and
plastic behavior were used to account for the combined axial and bending. These calculations can be
found in Appendix C.
It was determined that the member met all the design requirements, and so a W14x159 was used as the
typical column in the final design. Figure 16 above shows a typical column for the redesign.
Additionally, after designing a typical beam and girder, the column was again checked to make sure it
had the capacity for the transferred elastic moment from the moment connections in each frame. It
was determined to be adequate and a W14x159 was used as the column members in the LS-DYNA
model, which will be discussed further in later sections.

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 30

Figure 17: 3D model of typical bay with beams called out
Beam Design

As for the column design, some assumptions
had to be made before jumping right into
the design process. The beam was assumed
to be simply supported with a maximum
support rotation of 2. Additionally, it was
assumed that the blast load would only act
over the width of the flange of the beam.
This system was not designed as a composite
system, so tributary uplift between beams
would not be an issue. Had the system been
designed as a composite system, the uplift
on the floor slab from the blast would be
transferred to the beams, and the beams
would have to be designed to withstand the
larger blast load. Finally, it was assumed
that the pressure-time loading on the beam
would be the most critical. The reason for
this is that the longer duration will have an
overall larger effect on the structure.
Additionally, since the probability of the space reaching 117 psi is minimal it can be considered not to be
the most critical condition.
Two different bay configurations were designed. Initially it was believed that using three infill beams as
opposed to two would allow a significant decrease in the weight of the system. Since only the flange of
the beams were assumed to be taking the blast load (not a tributary width of floor slab transferring the
load to the beam as with composite systems), it was believed that a beam with a smaller flange width
would carry less blast load and could therefore be designed as a lighter member. A second design was
also performed using the original bay configuration with two infill beams. In the end, it was realized
that the larger members obtained in the second design with the original beam layout was a much lighter
system even though the beams had to withstand a larger blast load. Figure 17, above, shows the beams
that were designed and the final bay layout using two infill beams equally spaced.
Due to the strict rotational limitations, many iterations of the design process had to be completed. After
performing several iterations by hand, an Excel spreadsheet was set up to calculate most of the values,
with the exception of a few values that had to be read from tables in the UFC. An example hand
calculation of the first iteration can be found in Appendix and the Excel spreadsheets for the two
different bay layouts can be found in Appendix D.
To begin the design, both service load combinations and blast load combinations were checked to find
the controlling combination. Blast was found to be the controlling load, again using the combination
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 31

1.0D+0.25L+1.0B. This equation accounts for the direction of the loading, in this case uplift from blast
but gravity loads from the superimposed dead loads, estimated self-weights, and live loads. From the
controlling distributed load, the moment was calculated. Plastic moment capacity was used to
determine the required section modulus for the beam. Additionally, the local buckling requirements
were determined. From these requirements, an initial member was chosen. Plastic moment was
determined to make sure it was less than the plastic moment capacity of the chosen member. The
natural period of vibration was calculated to find the ductility ratio of the beam. Additionally, the strain
rate of the beam was calculated to determine if the DIF originally estimated was accurate. The ductility
ratio and rotation of the member were calculated and compared to the criteria established at the
beginning of the design. Finally, ultimate shear capacity was compared to maximum support shear using
the dynamic shear yield stress.
Several iterations of this process were completed in order to determine that a W 27x161 was the
smallest beam that worked. The ductility ratio of this member was found to be 1.0, which means that
the DIF assumed at the beginning of the design was adequate. This means that the maximum deflection
is expected to be the equivalent elastic deflection. Also, lateral bracing was checked, and was calculated
to be required at every 3 feet along the length of the beam. This requirement will be met by the slab on
deck floor system that will produce an unbraced length of zero across the length of the beam.
Additionally, rebound of the member was checked. Rebound is the reversal of load and deflection that
occurs after the blast wave has passed. The member must have a rebound resistance greater that that
specified in Figure 5-13 of the UFC. This allows the member to remain elastic during the rebound phase.
It was determined that the member had sufficient rebound resistance.
Live load and total load deflections were also checked under service loads only. The beam was found to
be adequate in live load and total load deflections.

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 32

Figure 18: 3D model of typical bay with girders called out
Girder Design

The girder design followed the same design
principles and procedure as the beam design,
differing only in their distribution of loading.
The interior girder was designed using point
loads from the reaction values from the
second scenario of the beam design. This
meant that there were two point loads
equally spaced along the length of the beam
with combined uplift and gravity, and a
distributed uplift blast load acting on the
bottom flange of the girder. Again, time-
pressure loading was determined to be the
more critical design pressure as it occurs
over a much longer period of time, relatively,
than the peak incident pressure. This design
may be conservative for the exterior beam,
but will be used for simplicity of design.
Again, plastic moment capacity was used to determine the required section modulus for the beam.
Additionally, the local buckling requirements were determined. From these requirements, an initial
member was chosen. A W30 x116 was chosen as a trial member. The following checks were performed
on the member to find if it met the blast requirements:
Plastic moment capacity must be greater than member plastic moment.
The strain rate of the girder was calculated to determine if the DIF originally estimated was
accurate.
The ductility ratio and rotation of the member were calculated and compared to the criteria
established at the beginning of the design.
Finally, ultimate shear capacity was compared to maximum support shear using the dynamic
shear yield stress.
Rebound resistance of the member must be greater than the required resistance.

Since the W30x116 met the specified requirements, it was chosen as the most economical member for
the design. An additional check for deflection under gravity loads only was performed. Both live load
deflection and dead load deflection were found to be less than the allowable deflections. The final
member chosen for the design was the W30x116. Figure 18, above, locates the girders that were
designed.
Hand calculations for the girder design can be found in Appendix E.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 33

Slab Design

Initially, it was intended to design a slab on deck for the redesign. After a few initial calculations,
though, it became evident that the capacity of such a slab would not be enough to withstand the time-
pressure loading caused by the explosion. At this point, it was decided that a two-way slab on shored
form deck could be designed to satisfy the requirements instead.
It was chosen to design the slab as a Type II Slab as defined by the UFC. This means that rebound
reinforcement will not be required because damage will be allowed and accepted in the slab if rebound
does occur. Therefore, rebound calculations were not performed on the slab, as they were unnecessary.
The slab, needing to withstand a significant uplift force without intermediate supports, was designed
with two-way reinforcement at the top. Being the more critical force on the slab, this reinforcement
was also used on the bottom of the slab to provide the same amount of resistance if the blast were from
above. Calculations for the two-way slab on shored deck form can be found in Appendix F. The design
yielded a 16.5 concrete slab on shored form deck held in place by shear studs. This was not designed
as a composite system, though, so the shear studs are intended only for holding the slab in place. Figure
19 on the next page shows a detailed section of the slab.
Although this slab design provides a solution, there are some problems. This slab is 10 deeper than the
original system. This means that the ceiling height on each floor may have to be decreased in order to
fit all the mechanical, electrical, and telecom equipment, especially since the girders and beams
remained at nearly the same depth as designed originally. Reducing the ceiling height to less than 9
may make the space feel very crowded and cramped, which would be unpleasant for the occupants.
The other solution would be to increase the building height by 10 per floor, which would result in an
overall building height increase of 70. This would add significant cost to the building, and would likely
be upsetting to the owner.
The system also does not provide the required lateral bracing for the beams. Although lateral bracing
can be provided by other means than a floor slab, it will add additional cost to the design. Utilizing the
floor slab as lateral bracing for the beams is the most common method of providing stability to beams
due to the economy of the design. Therefore, this would be an inefficient design in that respect, as well.
In addition to the issue of system depth, there are the issues of constructability and reasonable
solutions. A slab with a depth of 16.5 seems highly conservative for a floor system for day to day loads.
There is a lot of extra weight and cost to this system as compared to a traditional slab on deck. Many
times, it is not economical to design slabs for blast. There are rarely solutions that are both cost
effective and provide complete safety to the occupants. For this reason, it is suggested that the
redesign utilize a composite slab on deck system. Damage will most certainly occur, including but not
limited to cracking and spalling of concrete and possible breach. As stated previously, damage is
allowed as long as collapse does not occur.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 34

After further research into slab design, it was determined that since the space would be vented at 5 psi,
this pressure could be used to design a floor system. This allowed a second look into slab on deck
systems. A composite deck with slab was designed, and it was found that a 3VLI16 with a 4.5 topping
would provide adequate strength for the gravity system. These calculations can also be found in
Appendix F. This gives a total system depth of 7.5, which is only a 1 increase in system depth from the
original. A 1 decrease in the ceiling cavity depth should not be an issue with coordinating the MEP.
Additionally, this system will be much less costly, both in materials cost and labor. Overall, this system
provides an alternative solution if damage is not considered to be an issue.
Additionally, further investigation into Aluminum Foam Composite Sandwich Panels , lightweight
sandwich panels composed of aluminum foam cores, could be utilized. This innovative material takes
advantage of the high stiffness and high compressive strains of aluminum foams. Large deformations of
the sandwich panels give them the ability to absorb high quantities of energy. Placed underneath the
slab on deck system, this material could possibly provide the necessary energy dissipation to mitigate
structural failures thinner floor systems. Cost data was not looked into for this system, so no
recommendations can be made on the economy of the system as a whole. With more time, research
into this new discovery would have been completed, and a design capitalizing on this technology may
have been possible.














Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 35

Figure 19: Two-Way Slab on Shored Form Deck Detail
Figure 20: 3VLI16 Slab on Deck Diagram taken from Vulcraft
2008 Cut Sheet



















Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 36

Moment Connection Design



A typical moment connection at the exterior of the building between a beam and a column was
designed as part of the MAE requirement for thesis. Figure 21 above shows the location of the moment
connection at the exterior of the building. This is important to note because the columns at the interior
may need to be upsized to meet the strong column- weak beam requirements. With more time, an
interior connection between two beams and a column would have been investigated.
In this design, the moment connection must allow the beam to develop its full plasticity. That said, the
overstrength factors that are present in the beam calculations are not accounted for in the connection.
This is because it is necessary for the connection to be designed to develop the full strength of the
connecting members.
It was decided to use seismically prequalified connections in this design. This is because seismic
detailing has many of the same requirements as blast design. Additionally, the design can be
significantly simplified using the prequalified connections specified in the AISC Seismic Design Manual.
The column must have a higher plastic moment capacity than the beam in both situations, providing a
strong column- weak beam connection. In this type of framing, the intention is to have failure occur in
the beam before the column, since column failure could lead to pancaking of floors and ultimately
building collapse. This also helps distribute the inelastic deformations to the rest of the structure.
Another similarity is that member rotation is limited to .04 radians. Since the beam was designed for
this limit, the prequalified connections could be utilized for the design. Finally, seismic design using
prequalified connections ensures that ductile limit states will control, which is the objective in blast
design.
Figure 21: 3D model of typical bay with connection location called out
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 37

One difference to note between seismic connection design and blast connection design is that there are
different compact section requirements. The AISC Seismic Design Manual specifies the limiting ratios for
seismically compact sections. These differ somewhat from the blast requirements for compact sections.
The blast requirements were met in the design of the column, and therefore engineering judgment was
used to follow those requirements rather than the seismic requirements. Additionally, the seismically
compact limiting ratios only apply to members of seismic load resisting systems, which this is not.
The design of the connection followed the requirements for Special Moment Frames, which are defined
as frames expected to withstand significant inelastic deformations in the AISC Seismic Design
Manual since the members in blast design are expected to withstand the large inelastic deformations
that may occur as a result of blast loading.
The guidelines for prequalified connections design was used, which can be found in the specifications of
the AISC Seismic Design Manual. The beam limitations in section 5.3.1 of the specification for the AISC
Seismic Design Manual were met in accordance with the blast design requirements. Additionally, all
column limitations in section 5.3.2 were met. Additional requirements in Table 6.1 were met
throughout the design process.
Finally, the beam-column relationship requirements of sections 9.6 and 5.4 of the specification were
met. The overstrength factor used in seismic design for this calculation should not be used in blast
calculations. It was determined that the plastic capacity of the column was greater than the plastic
capacity of the beam, and therefore met the requirements for a strong column- weak beam connection.
To begin the actual design, a prequalified connection was chosen. Based on the large expected plastic
moments, an Eight-Bolt Stiffened connection was chosen, or 8ES. Next, a dog-bone, otherwise known
as a reduced beam section, was added to the beam to ensure that a plastic hinge occurs in the beam
and not at the connection. The reduced beam section was sized according to AISC design requirements.
The reduced beam section modulus, reduced beam shear, and the expected plastic capacity upon yield
were then calculated.
Next, the end plate and bolts were designed. It was found that shear yield in the plate controlled the
plate design. The plate was determined to be a 2.25 thick plate. The bolts were determined to be 1.5
A325N bolts.
On the column side, it was determined that stiffeners would be required. Web crippling was
determined to be the controlling limit state, and stiffener plates were designed accordingly. It was
determined that a 1.5 thick stiffener plate was required at the top and bottom beam flange locations.
The same stiffener was used in both locations to account for load reversal during rebound of the beam.
Full penetration groove welds were determined to be required at all welded locations. It is noted that
this is quite costly, but it is also understood that this is the unfortunate downside to blast design.
Figure 22 on the following page shows a side and top view detail of the exterior moment connection.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 38

Figure 22: 8ES Moment Connection Detail


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 39

Figure 23: Partial Floor Plan of Final Design with Members Labeled
Final Design

Figure 23 below shows a portion a floor plan of the redesigned structure with members labeled. This
was used for the LS-DYNA Redesign model, which will be discussed in later sections.


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 40

LS-DYNA Modeling

LS-DYNA Blast is a finite element analysis software used for modeling and analyzing blast events.
Although not created specifically for use in the building industry, it can be used to model a building
structure to determine member reactions during a blast event. In this thesis, LS-DYNA computer
modeling and analysis will be used to meet the AE597A MAE requirements.
A partial model of NBP-300 was created in LS-DYNA to compare the results using a blast modeling
software to the hand calculations performed in the first half of the structural depth. A partial model, as
opposed to the model of the entire building was used for several reasons. Firstly, blast loads decrease
significantly with increasing distance from the origin. By building a partial model, it can be shown that
members as close as one to two bays away from the blast really dont see much stress. Therefore, it can
be accurately assumed that a partial model will provide adequate stress-strain data. A full model would
be required for a lateral analysis though.
Second, each member had to be created individually in a text file as opposed to the user interface. This
made the process of building the model very tedious and time consuming. The scope of this thesis did
not allow for that in-depth of a modeling study.
Finally, since LS-DYNA is a finite element analysis software full of dynamic analysis equations and coding,
the run time for large, complicated models increases drastically as compared to smaller less complicated
models. In order to run several iterations, this time issue had to be taken into account.
The model was created using a base keycard file. This file has preset cards which are recognized
commands for the LS-DYNA programming. This is where the blast load is defined using the
*LOAD_BLAST card. The equivalent weight of TNT, the (x,y,z) location of the blast initiation, and the
delay time between the start of the model and the blast initiation were identified to define the blast.
This keyword takes into account incident pressures and reflected pressures.
The first member, a W14x159 was created in the user interface using a block mesh command (BMESH).
Figure 24 on the next page shows an example of the mesh for the beam. Initially a rectangular section
was created using five indices in the x-direction, 5 indices in the y-direction, and 6 indices in the z-
direction. The distances between indices in each direction were entered to develop the outline of the
cross section of a W-flange. Finally, material was removed from the square on either side of the
outlined web to create the W-flange shape. This created the I shape used for wide flanges. Then the
dimensions for the web and flanges were defined and a height was given to the column.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 41



Each member was created using this process. In the cases where beams framed into girders, copes were
created by adding more indices in the x-direction and z-direction, and then subtracting out the space
where the cope was required. A standard 3 cope was used and every location required for simplicity.
Once one member was created in the user interface, the file was saved, and then the text file for that
column was opened. From here, each member was created using the format from the first member.
The model was checked periodically during the text input to make sure that the geometry created was
accurate. A sample of this text is available in Appendix H.
The floor slab was created using the block mesh command again. Individual quadrants were created
and restrained at interfaces with one another. Cutouts were created at the column corners. This can
also be seen in the sample text file.
Fixed end moment connections at the ends of the beams and girders were modeled using the
*CONTACT_TIED_SURFACE_TO_SURFACE_CONSTRAINED_OFFSET option.
Once the model was built and the *LOAD_BLAST card was defined, the model was run. The blast was
defined to detonate at 2.5ms into the run time of the model. This process was repeated for the
redesigned structure using the blast members.
Figures 25 through 28 on the following pages show several isometric snapshots from the LS-DYNA
output model, including the frame, the frame with slab, and a connection detail.
Figure 24: View of Block Mesh used in LS-DYNA with Indices
Labeled in I and j directions
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 42

Figure 25: Isometric view of structural elements of partial LS-
DYNA Model (slab not shown)
Figure 26: Isometric view of structural elements of partial LS-
DYNA Model (slab shown)







Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 43

Figure 27: Isometric view of underside of structural elements
of partial LS-DYNA Model (slab shown)
Figure 28: Close-up of Connection in LS-DYNA model









Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 44

Comparison of Results

The results of the LS-DYNA model revealed a lot about the blast design process. It showed that the
stresses are lower than expected in the redesign, and that the hand calculations may be too
conservative. Plastic strain was never reached in the redesign, so the members should not yield.
Spikes in stresses and strains occur as pressures are reflected back into the structure, causing the
stresses in the members to build. This is more noticeable in the redesigned structure since it would be
stiffer, and therefore would have a less flexible response to the blast load.
Von Mises stresses were compared to the allowable stresses for the structural steel in dynamic loading.
Von Mises stresses are calculated using the following equation:


This defines a stress plane based on stresses in the 1
st
, 2
nd
, and 3
rd
principle stresses. Within this plane,
stresses are below allowable. Outside the plane, yield occurs. The Von Mises stresses obtained from
the LS-DYNA output should be below the dynamic yield stresses of the structural steel, and were
compared to determine the effectiveness of the redesign. In the original structure, the stresses are well
below dynamic yield. Additionally, in the model designed for blast, we can see that no failures occur, as
the stresses are below dynamic yield stress, or 71,000 psi. This can be seen in Graphs 1 and 2 on the
following page.
Figure 29 (pages 46-47) shows several still pictures of the blast wave propagation through the structure.
As stated previously, the blast was detonated at 2.5ms into the model. Significant stresses arent
immediately felt by the members, though. It takes several more milliseconds for the blast wave to
induce stresses in the members. Additionally, it can be seen that the pressure distribution over the
members is not equal. The base of the column sees the pressure wave many milliseconds before the
top of the column. In the hand calculations, it was assumed that the pressure would be evenly
distributed along the beam. In reality, this would not be the case, and so the member may be overly
conservative in its design. This is true of other members in the bay as well, such as the beams, which
would see the blast load at the center of the span before either of the ends.
In addition to checking the stresses in the members, the pressure from the blast was checked. It was
found that the pressures from the blast were very close to what was calculated by hand. This data was
presented in the Blast Load Determination section previously. The maximum pressure was found to
be 147 psi, which occurred at 7 ms. The blast was detonated at 2.5 ms into the analysis. This drops off
quickly and remains between 22 psi and 15 psi between 14 ms and 20 ms. This is very close to the 117
peak pressure and 21 gas overpressure that was found through hand calculations. On the following
pages a progression of still images from the pressure analysis video obtained from LS-DYNA output can
be seen.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 45

Graph 1: Stress in Original Structure

Graph 2: Stress in Blast Designed Structure

19116
-5000
0
5000
10000
15000
20000
25000
0 5 10 15 20 25
V
o
n

M
i
s
e
s

S
t
r
e
s
s

(
p
s
i
)

Time (ms)
Stress over Time
Columns
Beams b/t
Columns
Infill Beams
Girders
Slab
-10000
0
10000
20000
30000
40000
50000
60000
70000
0 5 10 15 20 25
V
o
n

M
i
s
e
s

S
t
r
e
s
s

(
p
s
i
)

Time (ms)
Stress over Time
Columns
Beams b/t
Columns
Infill Beams
Girders
Slab
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 46


Time= 7ms
Time= 0ms
Time= 8ms
Time= 9ms
Time= 10ms
Time= 11ms
Time= 12ms
Time= 13ms
Figure 29: Blast Pressure Progression
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 47


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 48

Additional Comments and Conclusion

Lateral System Implications

The redesign of NBP-300 will likely have several implications to the lateral system. Originally, as stated
previously, the lateral system was composed of four eccentrically braced frames. Of the changes made
during blast design, one of the most important to note is that moment frames would be utilized.
Moment frames can provide more ductility than the present eccentrically braced frames in the building,
which would help distribute the large amount of energy and pressure produced by the blast.
With the increased weight of the structure, the seismic lateral loads would increase, and produce a
larger design load in both directions. Seismic load controlled the design in the east-west direction
originally, and would remain the controlling design load. In the north-south direction, though, wind
loads controlled the lateral design, so this would need to be checked to determine if that were still true.
Seismic loading may control in the redesign due to the incredible amount of weight added to the
structure.
A further look into how ground shock affects the buildings foundations would be the next step to
determine additional strength requirements for the foundations. This is another area where additional
research and design could yield some interesting results, but as it was not in the scope of work for this
thesis, redesign of the foundations was not performed.

Effects on Foundations

As stated previously, the redesign adds tremendous weight to the structure. This means that the
current foundations may not be large enough or strong enough to support the additional weight.
Additionally, the lateral loads would increase, so overturning moments in the foundations would have to
be rechecked. Finally, due to ground shock from blast, the slab on grade may need additional strength.
A further look into how ground shock affects the buildings foundations would be then next step to
determine additional strength requirements for the foundations. This is another area where additional
research and design could yield some interesting results, but as it was not in the scope of work for this
thesis, redesign of the foundations was not performed.


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 49

MAE Requirements

As an MAE student, certain masters courses were utilized in this thesis redesign. Overall, three masters
courses were used throughout this thesis. A moment connection was designed using the information
taught in AE 534. Computer modeling was used to model and analyze the original and redesigned
structure, using material and information from AE 597A. Finally, AE 542 information on building faade
systems and glazing was utilized to complete a faade redesign.


Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 50

Breadth Topic I: Site Redesign

To redesign the site of NBP-300 several aspects of the site had to be taken into consideration. There
was originally parking located on-site, as well as truck access for garbage collection and delivery drop-
offs. Several pedestrian access points existed on multiple sides of the lot. Waste water management
also had to be considered during any modification to the site. Native plants and materials to the region
were researched. Any plants, trees, or shrubs that were to be planted had to be able to grow in the
climate and soil conditions present for the NBP-300 site. Figure 30 below shows a comparison between
the original site and the redesigned site.
Firstly, all on-site parking was eliminated. This negates the possibility of a car being used as an explosive
at a close range to the building. It will be assumed that the parking structure to the north-east of the
NBP-300 lot has the capacity to take on parking load eliminated from the site. Additionally, this lot will
also require a security system to prevent it from becoming a hazard.
The site was also expanded to meet the setback requirement of 400 ft. This means that at any point on
the building, the closest vehicular access way must be at least 400 ft away. Since there was only one
road running in front of NBP-300, the building could easily be moved further back on the site. The
driveway at the top of the site will remain, but will be for deliveries only and will have a security
checkpoint. The problem with moving the building back on the site is that this will add to the cost of the
project. An additional 80,856 square feet, or 1.86 acres would be required to meet the setback rule.
This is about a 50% increase from the original size. The cost benefit tradeoff makes this purchase worth
the money. If no setback is maintained, then the structure would be required to be designed for other,
possibly higher, blast loads.
An important change to the waste-water management had to be made. The distance to the main hook-
up was increased with the increase in setback. Fortunately, a clear path between the main run and the
building was able to be maintained, and so this wasnt seen as a critical issue in the redesign.
The other issue that had to be dealt with is the grading of the site. Since NBP-300 has a partial
basement that is exposed at one side, it was preferable to keep this architecture undisturbed. After
looking at the site grading from the original CAD file, it was determined that the site slopes gradually
away from the back side of the building toward the east. Ultimately, it was not seen as an issue for the
architectural integrity or constructability of the building.
Site access for delivery trucks and maintenance vehicles was maintained, but moved. A gated access
road to the north of the site leads to the loading dock at the northwest corner of the building. This
provides a security checkpoint for any vehicle entering the site, and meets the blast requirements for
site security. The road loops around to provide both entrance and exit points from site. There is a
spacious turn around area and parking area for any vehicle that may require such. The road maintains
at minimum a 24width to provide adequate space for trucks.

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 51


Next, a perimeter wall was designed to surround the site of NBP-300. This consisted of an 8 high cast in
place concrete wall. The wall was sized for wind loads and overturning moments. Foundations were
sized up to a standard size rather than using the actual calculated sizes, as they were too small for the
wall size. A CAD drawing of the wall can be seen in Figure 31 on the following page. In front of the wall,
decorative boulders will be used to protect the wall from vehicular impact.
More sidewalks and patio areas were added to the site to form a friendlier environment for the
occupants. There are three circular paths with bench seating connected by curved paths. This provides
a nice outdoor walking space for the occupants. Additionally, there is an outdoor patio with tables,
chairs, and umbrellas for those occupants who may wish to eat outside. Birch trees were chosen to line
the perimeter wall to obscure the view of NBP-300 from outside people. Birch trees were chosen for
their clean look, expected growth height, and ability to grow well in the area. Additional plants, such as
annual and perennial flowers would be expected on site in planters and flower beds. These were not
specifically detailed as this would be up to the owner and/or occupants.
This would have drastic impact on the industrial park as a whole. As it is now, most of the lots are open
and unobstructed from view. All buildings are visible from the roads and sidewalks through the
industrial park. By adding a site wall, barriers, and tall trees, NBP-300 will become almost invisible to
drivers and pedestrians in the park.
On one hand, this creates a peaceful and quite atmosphere on site for the occupants. There will be less
noise from traffic due to the perimeter wall, and less exposure to the public. With more outside areas,
the occupants may feel more comfortable with eating lunch outside or taking a walk around the site
after their lunch break.
On the other hand, the building had a very unique architecture, even after the faade change that is
discussed in the next sections, and it is a shame to hide it from the public eye. Unfortunately, for safety
reasons, it is a precaution that must be taken. There is also the possibility of the occupants finding the
site and building too closed off from the rest of the park. Both perspectives are important to consider in
this redesign.
Appendix I contains additional information to the redesign of the site.






Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 52

Figure 30: Comparison between original
site (left) and redesigned site (bottom).



Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 53



Figure 31: Perimeter Wall Section

8-0
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 54

Figure 32:
Comparison
between original
faade (left) and
redesigned faade
(bottom)
Breadth Topic II: Faade Redesign and Heat Transfer

In order to vent the interior in the case of an explosion, special care needed to be taken in the design of
the faade. It was determined that the glazing would be required to fail, but this presented a challenge.
Glazing is not allowed to shatter or become a projectile during blast because it becomes a safety issue.
Research into blowout panels and cable catch systems led to some interesting new research in anchored
glazing system. This proved to be very valuable information as it allowed the glazing to blowout, but
remain in the framing so as not to become a danger to outside persons.
The faade redesign utilizes this unique anchored film system. Wet glazing is used at the head of the
window, while dry glazing is used around the jambs and sill. The reason for the two types of glazing
because the glass is supposed to dislodge from its supports so as to provide a pressure release for the
interior. The top of the glass must remain in its supports so as not to become a dangerous projectile.











Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 55

Faade Design

The faade redesign presented many challenges. The need to ventilate the interior space during the
explosion combined with the strict provisions against glass debris made finding a solution somewhat
tricky.
Initially, the intent was to design a system that would allow the glazing and framing to be forced from
the wall system at 5 psi, but would be tethered to a short retractable cable system so as not to become
debris. This proved to require more research than the tight schedule permitted, and so the idea was put
on the back burner so to speak. It is believed to be a viable system, but would require testing and
significant research, which was not in the scope of this thesis. Instead, anchored glazing film systems
were researched. This proved to be a much more constructible system that would likely be significantly
cheaper.
The glazing needed to be designed to withstand estimated wind pressures, but needed complete wet
blanket failure at 5 psi in order to properly ventilate the interior space during the blast. A wet
blanket failure is a failure mode of glass where the pane remains in tack but loses all stiffness and load
carrying capacity. It behaves as a blanket and becomes very pliable.
The glazing in the faade was sized to withstand the design wind load calculated in Technical Report 1,
or 23 psf. An IGU (Insulating Glass Unit) unit composed of two lites of FT (fully tempered) glazing was
decided on as the glass type for the redesign. The reasons for this choice were two-fold. One, this type
of glazing would provide the desired failure mode. Two, this glazing would provide good resistance to
heat loss and gain through the faade.
A GTF of 4 was used since FT glass was used. Load sharing factors were used, but it was decided to use
the same thickness for both lites, so LS1 and LS2 were determined to be 2.0 each. A 3/8 air space was
used between the two lites of glass. The overall design yielded a glazing system of two lites of FT
glass. The overall thickness of the system was determined to be 7/8 thick.
This glazing was then verified to have less strength than the blast force of 5 psi, or 720 psf. With only
25.08 psf capacity, the window system will definitely fail before the 5 psi blast load is reached.
Next, the wet glazing needed to be sized in order to provide adequate strength in tension so as not to
come lose when the glazing fails. This is the anchorage part of the system. Through research, it was
found that GE provides high strength glazing, specifically for use in blast design. From their
manufacturers catalog it was determined that UltraGlaze SSG4000 could be used as the wet glazing. It
has a tensile strength of 340 psi, well over the 5 psi blowout pressure and the peak pressure of 117 psi
determined in the blast analysis. A bead of the UltraGlaze SSG4000 will ensure that the top of the
glazing will remain in its joint even when the other three sides of the glazing are dislodged. Additionally,
GlassLock wedge gaskets will be used at the top to restrain the glazing in its joint as part of the
anchorage system.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 56

Finally, and most importantly, an 8mil safety film was applied to the interior of the IGU. This is twice the
required thickness for post-breakage retention of glazing. The factor of safety of 2 was used to account
for tearing due to flapping motion of the broken panels. This would, of course, need to be verified
with testing, but such was not in the scope of work for the redesign of the faade system.
It should be noted that the connections were not designed for the new faade, but would be required to
withstand over 5 psi of pressure since that is the highest vented pressure that would occur.


The spandrel area at each floor level was changed to the precast panel system used on the un-curved
portions of the faade. This allows for a better anchorage system at the top of the window. The corners
were left fully glazed to create architectural interest. The anchorage system would still be used at these
locations, but would have to be installed at the horizontal mullions in each glazing panel. The solid glass
column at the corners eases the building into the surroundings. The precast panels create a very harsh
Figure 33: Glazing Anchor System Detail
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 57

feeling, so the glass creates a nice transition between the harshness of the concrete and the softness of
the surrounding nature.
A comparison between the facades can be seen in Figure 32, and a detailed section through the head of
the glazing system can be seen in Figure 33.
Hand calculations and additional information for the faade redesign and glazing system design can be
found in Appendix J. Additionally, the work performed for the redesign meets MAE requirements.

Heat Transfer

Heat loss and heat gain through faade systems are of great significance to building systems. The more
heat that is transferred through the wall system, the more energy is required to condition the inside
environment to mitigate the transfer. Poor faade and glazing systems can cause a lot of energy costs,
not to mention unhappy occupants.
After the faade system was decided upon and the glazing sized, heat transfer through the spandrel and
glazing areas were calculated. This was done for both mid-summer (July) and mid-winter (January),
when outside temperatures are at their extremes.
Weather data for Annapolis Junction, Maryland was research. It was found that the extreme high
expected in the summer would be 88F, and the extreme low in the winter would be 24F. These values
were used for the outside air temperatures to calculate the heat loss and gain due to air temperature
differences.
A general wall section for the precast spandrel area was decided upon. After choosing the materials and
components of the wall section, HAM was used to find the best location for the vapor barrier. It was
determined that the vapor barrier would be best located between the air cavity and the plywood
sheathing. No condensation occurred in the wall system using this configuration for either winter or
summer. This data can be viewed in Appendix K.
One assumption that was made during this process was that the heat gain and loss values would be
calculated for one half of a single floor level. This was for ease of calculations and to determine if the
output data seemed reasonable. The values presented in the following tables would be required to be
multiplied by 2 to get the heating and cooling loads per floor level. The equipment would also need to
be sized according to the adjusted loads.
R-values for each component of the wall were found using tables provided in Mechanical and Electrical
Equipment for Buildings. HAM was used to check the values. The total R-Values were very close. The
data from HAM for the R-Value Analysis can be found in Appendix K. Table 7 on the next page
summarizes the R-Value data.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 58

R-Values
Component R
Inside Air 0.68
Gyp Board 0.32
Batt Insulation 15
plywood 0.62
vapor retarder -
Air Cavity 0.68
Rigid Insulation 11
Precast Concrete 0.87
Outside Air 1.35

IGU Glazing 3
(two FT lites with film)
Table 7: R-Values of Spandrel Wall Section
An Excel spreadsheet was used to calculate the U-value of the wall assembly and the glazing in the
winter. The U-value of the wall assembly and the glazing was used to calculate heat loss in the winter.
Tables 8 and 9 below show the calculations for heat loss through the wall components and overall heat
loss in the winter. A total heat loss of over 77,000 Btu/hr is expected in the winter, or 154,000 Btu/hr
per floor level..
U
concrete
= 0.0328
U
glazing
= 0.3333


Winter Thermal Gradient
Component R R R/RT T
Room Air - - - 70.0
Inside Air Film 0.68 0.68 1.0 69.0
Gyp Board 0.32 1 1.5 68.5
Batt Insulation 15 16 24.1 45.9
Plywood 0.62 16.62 25.0 45.0
Vapor Retarder - 16.62 25.0 45.0
Air Cavity 0.68 17.3 26.1 43.9
Rigid Insulation 11 28.3 42.7 27.3
Precast Concrete 0.87 29.17 44.0 26.0
Outside Air Film 1.35 30.52 46.0 24.0
Outside Air - - - 24.0
30.52
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 59

Table 8: Winter Thermal Gradient
Winter Heat Loss

A= 4575 ft
2


U
concrete
= 0.0328

U
glazing
= 0.3333

T
winter
= 46 F

T
summer
= 18 F


through concrete through glazing
sensible heat loss(winter)-= 6895.5 70150
latent heat loss can be neglected due to high efficiency vapor retarder
Total: 77045.5 Btu/hr
Table 9: Winter Heat Loss

Summer presents different heat transfer issues than winter. In the summer, heat gain through a wall
assembly must take into account radiant heat from the sun, outside air temperature, electrical heat loss
from lighting, equipment, and people. These factors were taken into account during the heat gain
calculations. Additionally, latent heat gain was estimated as a percentage of the sensible heat gain and
was included in the total expected heat gain. Tables 10 and 11 below show the data used for the
summer heat gain calculations.










Table 10: Summer
Summer Thermal Gradient
Component R R R/RT T
Room Air - - - 75.0
Inside Air Film 0.68 0.68 0.3 75.3
Gyp Board 0.32 1 0.4 75.4
Batt Insulation 15 16 6.8 81.8
Plywood 0.62 16.62 7.1 82.1
Vapor Retarder - 16.62 7.1 82.1
Air Cavity 0.68 17.3 7.4 82.4
Rigid Insulation 11 28.3 12.1 87.1
Precast Concrete 0.87 29.17 12.4 87.4
Outside Air Film 1.35 30.52 13.0 88.0
Outside Air - - - 88.0
30.52
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 60

Thermal Gradient
Summer- Heat Gain

A= 4575 ft2
U
concrete
= 0.1700
U
glazing
= 0.81
DETD= 10
DCLF= 56
IF= 1.1
N= 300 people
P
lights
= 54600 Btu/hr
P
equipment
= 9600 Btu/hr computers
6000 Btu/hr printers
10000 Btu/hr copiers
2000 Btu/hr misc.


Sensible Heat Gain:

Envelope: 2567 Btu/hr
Glass: 171654 Btu/hr

Outdoor
Air: 5033 Btu/hr
People: 69000 Btu/hr
Lights 54600 Btu/hr
Equipment: 27600 Btu/hr

Total: 330453 Btu/hr

Latent Heat Gain:

Total: 66091 Btu/hr



Total Summer Heat Gain: 396544 Btu/hr
Table 11: Summer Heat Gain

Based on the calculations, the HVAC system would need to be sized to accommodate about 400,000
Btu/hr of cooling in the summer and about 77,000 Btu/hr of heating in the winter. This seems
reasonable since there is floor to ceiling glazing on each floor level, so high heat gain would be expected
in the summer and high heat loss would be expected in the winter.
Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 61

Cost Estimates

Minor cost estimates were performed for this redesign. A comparison of cost between an original
typical bay and the redesigned typical bay for blast can be seen in the Table 12 below. It is apparent
that the cost of design for blast is tremendously larger than a typical design, with a price increase of over
40% from the original. The increase in member sizes combined with the labor costs creates a much
more expensive design.
The original cost of construction of National Business Park- Building 300 was $38 million dollars. With a
price increase of 40%, the new cost of NBP-300 would be $53.2 million dollars. This is a significant price
increase, but if life safety is the issue then the extra cost would be well worth it.
This estimate only includes the structural steel in a typical bay. It does not account for the faade
redesign, the additional cost from the site redesign, or the cost of connections or foundations. A much
more detailed cost estimate would show a truer comparison of costs, but was not in the scope of work
for the breadth topics.















Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 62






Table 12: Cost Data for Structural Steel in a Typical Bay


MEMBER LENGTH (ft)
NUMBER OF
MEMBERS
TOTAL COST PER
LINEAR FOOT
TOTAL W/ O&P (PER
LINEAR FOOT
TOTAL TOTAL W/ O&P
W14X99 15 2 142.02 $ 158.10 $ 4,260.60 $ 4,743.00 $
W14X159* 15 2 225.00 $ 252.00 $ 6,750.00 $ 7,560.00 $
W27X84 35.1 1 120.64 $ 134.00 $ 4,234.46 $ 4,703.40 $
W27X94 40.9 2 133.64 $ 149.00 $ 10,931.75 $ 12,188.20 $
W27X102* 40.9 3 144.94 $ 161.00 $ 17,784.14 $ 19,754.70 $
TOTAL 43,960.95 $ 48,949.30 $
MEMBER LENGTH (ft)
NUMBER OF
MEMBERS
TOTAL COST PER
LINEAR FOOT
TOTAL W/ O&P (PER
LINEAR FOOT
TOTAL TOTAL W/ O&P
W14X159* 15 4 225.00 $ 252.00 $ 13,500.00 $ 15,120.00 $
W27X161 40.9 4 225.80 $ 251.00 $ 36,940.88 $ 41,063.60 $
W30X116 35.1 2 164.77 $ 182.00 $ 11,566.85 $ 12,776.40 $
TOTAL 62,007.73 $ 68,960.00 $
141% 141%
NOTE: Members with (*) were interpolated/extrapolated from data in RSMeans 2012
% INCREASE FOR REDESIGNED STRUCTURE:
ORIGINAL DESIGN
COST ANALYSIS OF STRUCTURAL MEMBERS
BLAST REDESIGN

Spring Thesis
Rebecca Dick | Structural Option

Advisor: Dr. Memari Page | 63

Conclusion

National Business Park- Building 300 was redesigned for interior blast using the UFC-340-02 and
following linear elastic design criteria. Throughout this design process it became evident that, while
much simpler to follow, the linear elastic design method yields over-conservative results.
A column, a beam, a girder, a floor system, and a moment connection were successfully designed for the
blast load. Linear elastic design and analysis was used for the hand calculations, and LS-DYNA was used
to verify the results. A successful design was accomplished. Through modeling and analysis in LS-DYNA,
it was shown that the redesign withstands the blast load and sustains minimal damage.
It was also determined that a partial model is acceptable to analyze a structure for blast if a lateral
analysis is not to be performed simultaneously. In the models shown previously, the pressure waves
barely reached the far bays of the design. Obviously, the quantity of modeling would be dependent on
the expected blast load. For much larger explosive loads, a larger model may be required. Ultimately,
though, it was shown that for this specific case, a three bay by three bay by three story model was
sufficient for the analysis.
A brief cost estimate was performed, showing that a 41% increase in cost from the original could be
expected in the redesign of the structure. As it was not a goal of this redesign to reduce cost, this is
viewed as acceptable.
In addition to blast design, a site redesign was completed to provide site security. This reduced the risk
of a higher blast controlling the design of the structure. In addition to the requirement for more land,
parking had to be moved offsite. More outdoor spaces were added for the occupants. Landscaping was
provided to beautify the site and to obscure the view of the structure from off site.
The faade of NBP-300 was also redesigned. A unique top anchored film system was used on the
interior of the glazing to allow the windows to fail and dislodge from their mullions at three edges to
vent the interior but remain attached to the system at the top. This prevents any glass from becoming a
dangerous projectile but also allows the interior space to shed some of the blast load. This was crucial
to the design process as it allowed the slab to be designed for the 5 psi blowout load rather than a much
higher pressure.
Heat transfer through the new faade was calculated. The values obtained were determined to be
reasonable considering the large interior space and high percentage of glazing over the faade system.
A heating load of 154,000 Btu/hr per floor was found for winter and a cooling load of around 800,000
Btu/hr per floor was calculated for summer.
Ultimately, the redesign of National Business Park-Building 300, its site, and the faade system is viewed
as a success. The goals of the thesis were met and exceeded, and the results provided invaluable insight
into blast design and finite element analysis, in addition to solidifying the basics of structural
engineering knowledge.