TECHNICAL MANUAL
Collection data
PACKAGED AIR-CONDITIONER
(Split system, Air to air heat pump type)
Alternative refrigerant R410A use models
CEILING RECESSED TYPE
FDTVA151HEN
201HEN
251HEN
FDTA301HEN
301HES
401HEN
401HES
501HES
601HES
FDENA301HEN
301HES
401HEN
401HES
501HES
601HES
FDKNA301HEN
301HES
FDURA301HEN
301HES
401HEN
401HES
501HES
601HES
CONTENTS
1 GENERAL INFORMATION................................................................................. 1
1.1 Specific features ......................................................................................... 1
1.2 How to read the model name ..................................................................... 1
2 SELECTION DATA ............................................................................................. 2
2.1 Specifications .............................................................................................. 2
2.2 Range of usage & limitations ................................................................... 33
2.3 Exterior dimensions ................................................................................. 34
2.4 Inside view ................................................................................................. 52
2.5 Exterior appearance ................................................................................. 53
2.6 Piping system ............................................................................................ 55
2.7 Selection chart .......................................................................................... 57
2.8 Characteristics of fan ............................................................................... 59
2.9 Noise level ................................................................................................. 60
3 ELECTRICAL DATA ......................................................................................... 64
3.1 Electrical wiring ........................................................................................ 64
4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER .................... 75
5 APPLICATION DATA ........................................................................................ 94
5.1 Installation of indoor unit ......................................................................... 95
5.2 Installation of remote controller ............................................................ 114
5.3 Installation of outdoor unit..................................................................... 115
6 MAINTENANCE DATA ................................................................................... 128
6.1 Servicing .................................................................................................. 128
6.2 Trouble shooting for refrigerant circuit ................................................ 129
6.3 Diagnosing of microcomputer circuit ................................................... 130
6.4 Check display on wireless specification models (FDEN FDKN)....... 162
GENERAL INFORMATION
1.1
Specific features
(1)
A new refrigerant, R410A, which causes no damage to the earths ozone layer, is used. R410A is a pseudoazeotropic refrigerant, so
there is little formation of separate vapor and liquid layers, and it is possible to add refrigerant on-site.
(2)
Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has been
reduced by more than 50%.
(3)
The microcomputer chip is installed in the indoor unit and outdoor unit. There is no need for the unit to communicate between the
outdoor and indoor units so the unit is more resistant to electromagnetic noise thus the incidence of microcomputer malfunction
has been reduced. The compressor in the outdoor unit has its own self protection function, that reacts according to abnormal high
pressure and excessive high temperature.
(4)
There are only three power lines between the outdoor and indoor unit. One cabtyre cable with 3 wires encased in one sheath is
enough for conducting the wiring work between the outdoor unit and the indoor unit. This contributes to simpler wiring work in the
field.
(5)
All air supply ports have auto swing louvers. (Only case of FDT, FDEN and FDKN models). The indoor fan motor has three speeds
of high, medium and low.
(6)
All models have service valves protruding from the outdoor unit for faster flare cannection work in the field.
(7)
The size and weight of the outdoor units in the 151~251 Series have been greatly reduced. Use of an inverter has also improved
energy conservation and economy.
1.2
A 25 1 H EN
Applicable power source ... See the specifications
Heat pump type
Series No.
Product capacity
R410A models
V : Inverter specification
: It is not an inverter specification
(blank)
Model name
1-
SELECTION DATA
2.1 Specifications
(1) Ceiling recessed type (FDT)
Model FDTVA151HEN
FDTVA151HEN
Model
Item
FDTA151
FDCVA151HEN
W
W
4000 [1800~4700]
4500 [2000~5400]
Power source
Cooling input
kW
Operation data(3)
1.222.90/2.96
[0.35~1.55]
5.4 5.1/5.5
[1.6~6.9]
Heating input
86/75
98
1.322.54/2.60
[0.40~1.74]
5.9 4.6/4.8
[1.8~7.7]
kW
Noise level
35
dB(A)
52
Exterior dimensions
mm
kg
84/75
97
45
5
Powerful mode Hi:36 Me:33 Lo:32
48
40
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.7
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 1
14 1
Starting method
Air flow
CMM
34 1
Line starting
Motor
Line starting
41
Available
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
2-
Model FDTVA201HEN
FDTVA201HEN
Model
Item
FDTA201
FDCVA201HEN
5400 [2500~6300]
5000 [2200~5600]
Power source
kW
6.35.1/5.5
[1.9~7.4]
98
86/75
1.49 [0.50~1.87]
2.54/2.60
6.64.6/4.8
[2.2~8.3]
Operation data(3)
Cooling input
Heating input
kW
Noise level
5
dB(A)
52
Exterior dimensions
mm
kg
98
84/75
5
45
Powerful mode Hi:36 Me:33 Lo:32
3
48
40
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.9
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 1
14 1
Starting method
Air flow
CMM
34 1
Line starting
Motor
Line starting
41
Available
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
3-
Model FDTVA251HEN
FDTVA251HEN
Model
Item
FDTA251
FDCVA251HEN
W
W
5600 [2800~6300]
6700 [3100~7100]
Power source
1.64 2.90/2.96
[0.54~1.90]
7.3 [2.4~8.4]
5.15.5
98
86/
kW
1.78 2.54/2.60
[0.57~1.93]
7.9 [2.5~8.6]
4.6/4.8
98
84/
Operation data(3)
Cooling input
Heating input
Noise level
dB(A)
5
Exterior dimensions
mm
kg
5
Powerful mode Hi:38 Me:35 Lo:33
48
52
Mild mode Hi:35 Me:33 Lo:31
Unit 270 840 840
40
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
1.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 1
14 1
Starting method
Air flow
CMM
34 1
Line starting
Motor
Line starting
41
Available
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
4-
Model FDTA301HEN
FDTA301HEN
Model
Item
FDTA301
FDCA301HEN
W
W
7200
7300
Power source
2.17
10.0
94
kW
2.10
9.5
96
Operation data(3)
Cooling input
Heating input
Noise level
35
dB(A)
52
Exterior dimensions
mm
kg
63
Powerful mode Hi:38 Me:35 Lo:33
53
75
ZP26K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 1
20 1
Starting method
Air flow
CMM
55 1
Line starting
Motor
Line starting
46
Available
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
5-
Model FDTA301HES
FDTA301HES
Model
Item
FDTA301
FDCA301HES
W
W
7200
7300
Power source
2.17
3.8
82
kW
2.10
3.7
82
Operation data(3)
Cooling input
Heating input
Noise level
5
dB(A)
52
Exterior dimensions
mm
kg
34
Powerful mode Hi:38 Me:35 Lo:33
53
75
ZP26K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 1
20 1
Starting method
Air flow
CMM
55 1
Line starting
Motor
Line starting
46
Available
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
6-
Model FDTA401HEN
FDTA401HEN
Model
Item
FDTA401
FDCA401HEN
W
W
10000
11200
Power source
3.55
16.4
94
kW
3.49
15.7
97
100
Operation data(3)
Cooling input
Heating input
Noise level
35
dB(A)
52
Exterior dimensions
mm
kg
54
92
ZP41K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.0
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 2
40
40 2
Line starting
Motor
Line starting
Starting method
Air flow
CMM
64
Available
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
7-
Model FDTA401HES
FDTA401HES
Model
Item
FDTA401
FDCA401HES
W
W
10000
11200
Power source
3.48
6.3
80
kW
3.42
6.2
80
Operation data(3)
Cooling input
Heating input
Noise level
35
dB(A)
52
Exterior dimensions
mm
kg
46
Powerful mode Hi:46 Me:43 Lo:41
54
92
ZP41K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.0
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 2
40
40 2
Line starting
Motor
Line starting
Starting method
Air flow
CMM
64
Available
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
8-
Model FDTA501HES
FDTA501HES
Model
Item
FDTA501
FDCA501HES
W
W
12500
13600
Power source
4.30
7.7
81
kW
3.77
6.8
80
Operation data(3)
Cooling input
Heating input
Noise level
5
dB(A)
52
Exterior dimensions
mm
kg
67
Powerful mode Hi:48 Me:45 Lo:43
56
112
ZP54K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.75
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 2
120 1
Starting method
Air flow
CMM
55 2
Line starting
Motor
Line starting
100
Available
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
9-
Model FDTA601HES
FDTA601HES
Model
Item
FDTA601
FDCA601HES
W
W
14300
16200
Power source
4.33
7.5
83
kW
5.05
8.4
87
Operation data(3)
Cooling input
Heating input
Noise level
5
dB(A)
52
Exterior dimensions
mm
kg
77
Powerful mode Hi:48 Me:45 Lo:43
57
126
ZP57K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
4.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Turbo fan 1
Propeller fan 2
120 1
Starting method
Air flow
CMM
55 2
Line starting
Motor
Line starting
100
Available
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Decorative Panel
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
10 -
Model
Item
FDENA151
FDCVA151HEN
3800 [1800~4700]
W
W
4500 [2000~5400]
Power source
1.18 [0.40~1.66]
5.3 [1.8~7.3]
97
kW
1.32 [0.42~1.76]
5.9 [1.9~7.8]
97
Operation data(3)
Cooling input
Heating input
Noise level
5
Powerful mode Hi:42 Me:39 Lo:38
dB(A)
Exterior dimensions
48
mm
30
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.7
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
25 1
Starting method
34 1
Line starting
Powerful mode Hi:12 Me:11 Lo:9
Air flow
CMM
Line starting
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
Installation data
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
11 -
Model FDENVA201HEN
FDENVA201HEN
Model
Item
FDENA201
FDCVA201HEN
5000 [2200~5600]
W
W
5400 [2500~6300]
Power source
1.54 [0.47~1.82]
6.9 [2.1~8.1]
97
kW
1.57 [0.52~1.96]
7.0 [2.3~8.7]
98
Operation data(3)
Cooling input
Heating input
Noise level
5
Powerful mode Hi:42 Me:39 Lo:38
dB(A)
Exterior dimensions
48
mm
30
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.9
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
25 1
Starting method
Air flow
34 1
Line starting
Motor
Line starting
CMM
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
12 -
Model FDENVA251HEN
FDENVA251HEN
Model
Item
FDENA251
FDCVA251HEN
W
W
5600 [2800~6300]
6700 [3100~7100]
Power source
1.74 [0.55~2.01]
Operation data(3)
Cooling input
7.8 [2.5~8.9]
98
kW
1.87 [0.58~2.03]
8.3 [2.6~9.0]
98
Heating input
Noise level
5
Powerful mode Hi:44 Me:41 Lo:39
dB(A)
Exterior dimensions
48
mm
36
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
1.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
25 2
Starting method
Air flow
34 1
Line starting
Motor
Line starting
CMM
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
13 -
Model FDENA301HEN
FDENA301HEN-SB
Model
Item
FDENA301
FDCA301HEN
W
W
6400
7100
Power source
2.26
10.3
95
kW
2.19
10.2
93
Operation data(3)
Cooling input
Heating input
Noise level
63
Powerful mode Hi:44 Me:41 Lo:39
dB(A)
Exterior dimensions
53
mm
36
75
Net weight
kg
ZP26K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
25 2
Starting method
Air flow
55 1
Line starting
Motor
Line starting
CMM
46
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
14 -
Model FDENA301HES
FDENA301HES
Model
Item
FDENA301
FDCA301HES
W
W
6400
7100
Power source
2.26
4.0
82
kW
2.19
3.9
81
Operation data(3)
Cooling input
Heating input
Noise level
34
Powerful mode Hi:44 Me:41 Lo:39
dB(A)
Exterior dimensions
53
mm
36
75
Net weight
kg
ZP26K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
25 2
Starting method
Air flow
Propeller fan 1
55 1
Line starting
Powerful mode Hi:20 Me:18 Lo:14
CMM
Line starting
46
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
15 -
Model FDENA401HEN
FDENA401HEN
Model
Item
FDENA401
FDCA401HEN
W
W
10000
11200
Power source
3.44
15.9
94
kW
3.10
13.9
97
100
Operation data(3)
Cooling input
Heating input
Noise level
dB(A)
Exterior dimensions
54
mm
46
92
Net weight
kg
ZD41K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.0
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 2
30 2
Starting method
Air flow
40 2
Line starting
Motor
Line starting
CMM
64
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
16 -
Model FDENA401HES
FDENA401HES
Model
Item
FDENA401
FDCA401HES
W
W
10000
11200
Power source
3.32
6.0
80
kW
3.05
5.5
80
Operation data(3)
Cooling input
Heating input
Noise level
46
Powerful mode Hi:46 Me:44 Lo:41
dB(A)
Exterior dimensions
54
mm
46
92
Net weight
kg
ZP41K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.0
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 2
30 2
Starting method
Air flow
40 2
Line starting
Motor
Line starting
CMM
64
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
17 -
Model FDENA501HES
FDENA501HES
Model
Item
FDENA501
FDCA501HES
W
W
12600
13300
Power source
4.65
8.2
82
kW
3.84
6.8
82
Operation data(3)
Cooling input
Heating input
Noise level
67
Powerful mode Hi:48 Me:46 Lo:44
dB(A)
Exterior dimensions
56
mm
46
112
Net weight
kg
ZP54K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
3.75
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
33 2
Starting method
Air flow
Propeller fan 2
55 2
Line starting
Powerful mode Hi:31 Me:29 Lo:26
CMM
Line starting
100
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
18 -
Model FDENA601HES
FDENA601HES
Model
Item
FDENA601
FDCA601HES
W
W
14200
15900
Power source
4.69
8.0
85
kW
4.38
7.2
88
Operation data(3)
Cooling input
Heating input
Noise level
77
Powerful mode Hi:48 Me:46 Lo:44
dB(A)
Exterior dimensions
57
mm
46
126
Net weight
kg
ZP57K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
4.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 2
40 2
Starting method
Air flow
55 2
Line starting
Motor
Line starting
CMM
100
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1 JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
19 -
Model
Item
FDKNA151
FDCVA151HEN
4000 [1800~4700]
W
W
4500 [2000~5400]
Power source
Operation data(3)
1.30 [
Cooling input
5.8 [
97
%
kW
1.30 [
5.8 [
Heating input
Noise level
97
5
Powerful mode Hi:44 Me:42 Lo:40
dB(A)
Exterior dimensions
48
mm
12
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.7
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Tangential fan 1
33 1
Starting method
Air flow
Propeller fan 1
34 1
Line starting
Powerful mode Hi:12 Me:11 Lo:10
CMM
Line starting
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
20 -
Model FDKNVA201HEN
FDKNVA201HEN
Model
Item
FDKNA201
FDCVA201HEN
5000 [2200~5600]
W
W
5400 [2500~6300]
Power source
Operation data(3)
1.66 [
Cooling input
7.4 [
98
%
kW
1.58 [
7.1 [
Heating input
Noise level
97
5
Powerful mode Hi:47 Me:44 Lo:41
dB(A)
Exterior dimensions
48
mm
12
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.9
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Tangential fan 1
Propeller fan 1
33 1
Starting method
Air flow
34 1
Line starting
Motor
Line starting
CMM
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
21 -
Model FDKNVA251HEN
FDKNVA251HEN
Model
Item
FDKNA251
FDCVA251HEN
5600 [2800~6000]
W
W
6300 [3100~7100]
Power source
Operation data(3)
1.99 [
Cooling input
8.9 [
97
%
kW
1.85 [
8.2 [
Heating input
Noise level
98
5
Powerful mode Hi:48 Me:45 Lo:42
dB(A)
Exterior dimensions
48
mm
12
40
Net weight
kg
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
1.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Tangential fan 1
Propeller fan 1
33 1
Starting method
Air flow
34 1
Line starting
Motor
Line starting
CMM
41
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range
22 -
Model FDKNA301HEN
FDKNA301HEN
Model
Item
FDKNA301
FDCA301HEN
W
W
6700
7300
Power source
2.28
10.3
96
kW
2.22
10.4
93
Operation data(3)
Cooling input
Heating input
Noise level
63
Powerful mode Hi:49 Me:46 Lo:43
dB(A)
Exterior dimensions
53
mm
13.5
75
Net weight
kg
ZP26K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Tangential fan 1
Propeller fan 1
40 1
Starting method
Air flow
55 1
Line starting
Motor
Line starting
CMM
46
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
23 -
Model FDKNA301HES
FDKNA301HES
Model
Item
FDKNA301
FDCA301HES
W
W
6700
7300
Power source
2.28
4.0
82
kW
2.22
4.0
80
Operation data(3)
Cooling input
Heating input
Noise level
34
Powerful mode Hi:49 Me:46 Lo:43
dB(A)
Exterior dimensions
53
mm
13.5
75
Net weight
kg
ZP26K3E-TFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
2.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Tangential fan 1
Propeller fan 1
40 1
Starting method
Air flow
55 1
Line starting
Motor
Line starting
CMM
46
Unavailable
Electric heater
Operation control
Operation switch
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
24 -
Model
Item
FDURA201
FDCVA201HEN
5000 [2200~5600]
W
W
5400 [2500~6300]
Power source
1.64 [0.58~1.88]
7.3 [2.6~8.4]
98
kW
1.58 [0.60~1.96]
7.0 [2.7~8.7]
98
Operation data(3)
Cooling input
Heating input
Noise level
dB(A)
39
40
Net weight
kg
48
mm
Exterior dimensions
Hi:40 Lo:36
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
0.9
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
90 1
34 1
Line starting
Line starting
CMM
Hi:17 Lo:13.5
41
Pa
Motor
Starting method
Air flow (Standard)
Available static pressure
Fresh air intake
Electric heater
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Suction grille
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
25 -
Model FDURVA251HEN
FDURVA251HEN
Model
Item
FDURA251
FDCVA251HEN
5600 [2800~6300]
W
W
6400 [3100~7100]
Power source
1.98 [0.69~2.33]
8.8 [3.1~10.3]
98
kW
1.77 [0.68~2.04]
7.9 [3.0~9.1]
97
Operation data(3)
Cooling input
Heating input
Noise level
dB(A)
40
40
Net weight
kg
48
mm
Exterior dimensions
Hi:41 Lo:37
5CS102XFD 1
Refrigerant equipment
Compressor type & Qty
kW
Starting method
Heat exchanger
1.5
Motor
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
r
Refrigerant oil
Defrost control
MC controlled de-icer
Propeller fan 1
130 1
CMM
Pa
Line starting
Hi:20 Lo:17
Starting method
34 1
Line starting
Motor
41
Operation control
Operation switch
(Optional : RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Flare piping
Drain hose
Accessories
Optional parts
Suction grille
Standards
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
26 -
Model FDURA301HEN
FDURA301HEN
Model
Item
FDURA301
FDCA301HEN
W
W
6700
7100
Power source
kW
2.38
11.0
94
kW
2.21
10.4
92
Cooling input
Operation data(3)
Heating input
Noise level
63
Hi:41 Lo:37
53
mm
kg
Exterior dimensions
dB(A)
40
75
ZP26K3E-PFJ 1
Refrigerant equipment
Compressor type & Qty
Motor
Heat exchanger
2.5
kW
Starting method
Line starting
Refrigerant control
Refrigerant
R410A
Quantity
kg
Refrigerant oil
Defrost control
MC controlled de-icer
230 1
55 1
Line starting
Line starting
CMM
Hi: 25 Lo: 20
46
Pa
Starting method
Air flow (Standard)
Available static pressure
Propeller fan 1
Operation control
Operation switch
(Optional: RC-E1)
Thermostat by electronics
Safety equipment
mm
(in)
Connecting method
Drain hose
Flare piping
(Connectable with VP25)
Accessories
Optional parts
Suction grille
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
27 -
Standards
ISO-T1, JIS B8616
Model FDURA301HES
FDURA301HES
Model
Item
FDURA301
FDCA301HES
6700
7100
3 Phase, 380/400/415V 50Hz
2.38
4.2
82
2.21
4.0
80
34
W
W
53
kg
40
75
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Available static pressure
Hi: 41 Lo: 37
mm
Operation data(3)
kW
A
%
kW
A
%
A
dB(A)
ZP26K3E-TFD 1
2.5
Line starting
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Electronic expansion valve
R410A
kW
kg
r
Propeller fan 1
CMM
230 1
Line starting
Hi: 25 Lo: 20
55 1
Line starting
46
Pa
mm
(in)
nternal
DB
WB
DB
WB
27C
20C
19C
35C
7C
24C
6C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
28 -
Standards
ISO-T1, JIS B8616
Model FDURA401HEN
FDURA401HEN
Model
Item
FDURA401
FDCA401HEN
10000
11200
1 Phase, 220/230/240V 50Hz
3.56
16.5
94
3.28
14.7
97
100
W
W
Hi:42 Lo:37
54
mm
kg
63
92
Operation data(3)
kW
A
%
kW
A
%
A
dB(A)
ZP41K3E-PFJ 1
3.0
Line starting
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Electronic expansion valve
R410A
kW
kg
r
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Available static pressure
MC controlled de-icer
Multiblade centrifugal fan 2
Propeller fan 2
CMM
280 1
Line starting
Hi: 34 Lo: 27
40 2
Line starting
64
Pa
mm
(in)
Inter-
Operation
Cooling
DB
27C
WB
19C
DB
35C
WB
24C
Heating
20C
7C
6C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
29 -
Standards
ISO-T1, JIS B8616
Model FDURA401HES
FDURA401HES
Model
Item
FDURA401
FDCA401HES
10000
11200
3 Phase, 380/400/415V 50Hz
3.32
6.0
80
3.10
5.6
80
46
W
W
Hi: 42 Lo: 37
54
mm
kg
63
92
Operation data(3)
kW
A
%
kW
A
%
A
dB(A)
ZP41K3E-TFD 1
3.0
Line starting
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Electronic expansion valve
R410A
kW
kg
r
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Available static pressure
MC controlled de-icer
Multiblade centrifugal fan 2
Propeller fan 2
CMM
280 1
Line starting
Hi: 34 Lo: 27
40 2
Line starting
64
Pa
mm
(in)
Inter-
DB
WB
DB
WB
27C
20C
19C
35C
7C
24C
6C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
30 -
Standards
ISO-T1, JIS B8616
Model FDURA501HES
FDURA501HES
Model
Item
FDURA501
FDCA501HES
12500
13600
3 Phase, 380/400/415V 50Hz
4.66
8.4
80
3.89
7.0
80
67
W
W
Hi:43 Lo:38
56
mm
kg
65
112
Operation data(3)
kW
A
%
kW
A
%
A
dB(A)
ZP54K3E-TFD 1
3.75
Line starting
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Electronic expansion valve
R410A
kW
kg
r
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Available static pressure
MC controlled de-icer
Multiblade centrifugal fan 2
Propeller fan 2
CMM
460 1
Line starting
Hi: 42 Lo: 33.5
55 2
Line starting
100
Pa
mm
(in)
Inter-
DB
WB
DB
WB
27C
20C
19C
35C
7C
24C
6C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
31 -
Standards
ISO-T1, JIS B8616
Model FDURA601HES
FDURA601HES
Model
Item
FDURA601
FDCA601HES
14400
16000
3 Phase, 380/400/415V 50Hz
4.79
8.2
84
4.63
7.5
89
77
W
W
Hi:43 Lo:38
57
mm
kg
65
126
Operation data(3)
kW
A
%
kW
A
%
A
dB(A)
ZP57K3E-TFD 1
4.5
Line starting
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Electronic expansion valve
R410A
kW
kg
r
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Available static pressure
MC controlled de-icer
Multiblade centrifugal fan 2
460 1
Line starting
Hi: 42 Lo: 33.5
W
CMM
55 2
Line starting
100
Pa
Propeller fan 2
mm
(in)
Inter-
DB
WB
DB
WB
27C
20C
19C
35C
7C
24C
6C
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 UNITARY AIR-CONDITIONERS
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
32 -
Standards
ISO-T1, JIS B8616
301~601 models
Item
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Rating 10%
Voltage at starting
Compressor
ON-OFF
Frequency
Max. 50m
Cycle Time
Stop Time
3 minutes or more
33 -
Fresh air
opening for
ducting
950
630
Control box
Exhaust air
opening for
ducting
420
422
637
Liquid piping
6.35(1/4")
B
267
332
Air outlet
VIEW A
310
Gas piping
151,201: 12.7(1/2")
251: 15.88(5/8")
Drain hose
(Accessories)
(Local setting)
840
Suspension bolts
Drain
(Connectable with VP25)
Control box
270
187
700 or less
(Max. Drain up)
Lug for
suspension bolts
35
45or more
95
137
212
295~325
VIEW B
A
Holes for
tapping screws
4-4
140
80
Holes
VIEW C
100
VIEW D
-
34 -
2500 or more
52
122
160
Holes
100
123
43
55
25
140
Holes for
tapping screws
4-4
Obstacle
1000
or more
Model FDTA301
unit : mm
Decorative Panel
Fresh air
opening for
ducting
950
630
Control box
Exhaust air
opening for
ducting
420
422
637
Liquid piping
9.52(3/8")
B
267
332
Air outlet
VIEW A
310
Gas piping
15.88(5/8")
Drain hose
(Accessories)
(Local setting)
840
Suspension bolts
Drain
(Connectable with VP25)
Control box
270
187
700 or less
(Max. Drain up)
Lug for
suspension bolts
35
45or more
95
137
212
295~325
VIEW B
A
Holes for
tapping screws
4-4
140
80
Holes
VIEW C
100
VIEW D
35 -
2500 or more
52
122
160
Holes
100
123
43
55
25
140
Holes for
tapping screws
4-4
Obstacle
1000
or more
Model FDTA401
unit : mm
Decorative Panel
Fresh air
opening for
ducting
950
630
Control box
Exhaust air
opening for
ducting
420
422
637
Liquid piping
9.52 (3/8")
332
Gas piping
15.88 (5/8")
310
Air outlet
267
VIEW A
Drain hose
(Accessories)
(Local setting)
840
295~325
Lug for
suspension bolts
Control box
700 or less
187
295
35
45 or more
95
137
212
Drain
(Connectable with VP25)
Suspension bolts
VIEW B
60
77
Hole
140
147
160
80
2500 or more
140
Hole
100
148
68
55
Holes for
tapping screws
4-4
140
25
Holes for
tapping screws
4-4
100
Obstacle
VIEW C
VIEW D
-
36 -
1000
or more
Fresh air
opening for
ducting
950
630
Exhaust air
opening for
ducting
420
637
422
Control box
Liquid piping
9.52 (3/8")
267
332
Air outlet
310
VIEW A
Gas piping
15.88 (5/8")
Drain hose
(Accessories)
(Local setting)
840
Suspension bolts
Drain
(Connectable with VP25)
700 or less
365
Control box
35
45 or more
187
137
269
95
Lug for
suspension bolts
VIEW B
A
Holes for
tapping screws
4-4
140
55
60
80
2500 or more
215
147
Hole
100
140
Hole
160
218
138
25
140
Holes for
tapping screws
4-4
100
Obstacle
VIEW C
VIEW D
37 -
1000
or more
295~325
135
24
145
410
68
Liquid piping
52
990
215
53
109
40
210
173
Gas piping
40
690
1070
Drain hole
connection(1)
(VP20)
195
235
Air outlet
271
Indication board
308
(VP20)
Gas piping
12.7(1/2")
76
75
Liquid piping
6.35(1/4")
110
135
Drain hole
connection(1)
100
or more
(VP20)
300
or more
Drain hole
connection(1)
53
10
150
or more
or more
Obstacles
135
24
410
68
Liquid piping
52
Gas piping
40
1240
40
53
109
173
210
215
24
Unit : mm
690
1320
195
Drain hole
connection(1)
(VP20)
235
271
Indication board
308
76
Gas piping
15.88(5/8")
Drain hole
connection(1)
(VP20)
75
110
Liquid piping
251:6.35(1/4")
301:9.52(3/8")
135
100
or more
300 or more
Drain hole
connection(1)
(VP20)
53
10
150
or more
Obstacles
38 -
5
or more
410
135
24
68
52
Liquid piping
Gas piping
40
40
1540
53
109
173
250
255
24
690
1620
195
235
Drain hole
connection(1)
(VP20)
271
Indication board
308
75 Liquid piping
110 9.52(3/8")
Gas piping
15.88(5/8")
Drain hole
connection(1)
(VP20)
135
100
or more
300 or more
Drain hole
connection(1)
(VP20)
76
53
10
150
or more
5
or more
Obstacles
(c)
Liquid piping
6.35(1/4")
67(Right)
60 (Left)
298
Gas piping
12.7(1/2")
40
Outlet for piping
44
50
100
60
or
more
or
more
15
Indication board
or
more
39 -
8.5
Outlet for
electric wiring
284.2
44.5
53.5
15
63.5
387.5
457.5
515
Service
space
220.5
240
50
25
Drain hose
(VP16)
840
182.5
5.3
50
73.5
450
Service
40 space
207.5
44.5
14.5
44
60
60
44
60
693
5073.5
47.5
813
3 60
Service
space 100
Unit
or more
4-1281
long hole
Mounting plate
Service
space
Model FDKNA251
Unit : mm
Installation position diagram and installation space, from the front.
240
Liquid piping
6.35(1/4")
298
67(Right)
60 (Left)
Gas piping
15.88 (5/8")
40
50
8.5
or
more
15
60
100
or
more
44
Indication board
or
more
Outlet for
electric wiring
Service
space
63.5
387.5
457.5
515
53.5
Drain hose
(VP16)
15
44.5
25
44.5
220.5
44
60
50
284.2
50
840
182.5
or more
14.5
60
44
60
47.5
813
73.5
450
5.3
693
5073.5
207.5
3 60
Service
space 100
Unit
Service
40 space
Mounting plate
Service
space
4-1281
long hole
Model FDKNA301
Unit : mm
1145
75
45
75
51
51
35
196
1155
55
298
Mounting plate
Indication board
Outlet for
electric wiring
51
Outlet for
piping
Unit
54
Mounting plate
Service
space
220
690
245
50
450
50
50
450
245
Drain hose
(VP16)
Liquid piping
9.52 (3/8")
Gas piping
15.88 (5/8")
65
6.5
37
209
72
465
515
600
40 -
50
100
or
more
or
more
15
long hole
or
more
8-1281
282.5
4-5.551
long hole
Service space
40
40
60
45
50
100
54
1047
or more
50
25
245
25
475
240
420
525
35
480
80
30
295
18
45
650
18
560
(Suspension bolts pitch)
145
Control box
Suspension bolts
(M10 4pcs)
70
Liquid piping
45
30
6.35 (1/4)
58
Air outlet duct
71
25
Gas piping
100
201:12.7 (1/2)
251:15.88 (5/8)
Drain (Connectable
with VP25)
150
260
(Max.Drain up)
850
600
600
635
Drain hose(Accessories)
(Local Locality)
Air outlet
1200
Ceiling surface
Inspection hole
41 -
Model FDURA301
Unit : mm
295
25
245
25
45
560
(Suspension bolts pitch)
18
240
420
480
525
35
475
80
30
18
650
145
Control box
Suspension bolts
(M10 4pcs)
70
Liquid piping
45
30
9.52 (3/8)
58
Air outlet duct
71
25
Gas piping
100
15.88 (5/8)
Drain (Connectable
with VP25)
150
260
(Max.Drain up)
850
600
600
635
Drain hose(Accessories)
(Local Locality)
Air outlet
1200
Ceiling surface
Inspection hole
42 -
Unit : mm
Air inlet duct
Control box
Suspension bolts
(M10 4pcs)
173
25
475
240
420
525
35
480
80
30
300
25
45
650
350
18
560
(Suspension bolts pitch)
18
70
25
58
45
30
Liquid piping
9.52 (3/8)
77
100
Gas piping
15.88 (8/5)
150
260
Drain (Connectable
with VP25)
(Max.Drain up)
1370
600
600
635
Drain hose(Accessories)
(Local Locality)
Air outlet
1720
Ceiling surface
Inspection hole
43 -
Wire
(Recessed)
LCD display
Electrical box
(Locally Purchased)
120
19
46
Remote controller
outline
120
83.5
23
45
42
44
Attachment hole
94.5 Long hole(4 pcs.)
11.5
0.5 mm2
0.75 mm2
1.25 mm2
2.0 mm2
Earth
3 cores
3 cores
3 cores
3 cores
Indoor unit
(This side is not grounded)
44 -
Unit: mm
FILTER
MODE
OFF AM
PM
TEMP
ON/OFF
161.5
ON AM
PM
20.5
60
45 -
Unit: mm
50
471.5
14
49.6
340
312.5
51.9
45.4
132
58.6
290
2-R
13.5
12
286.4
43.1
463
106
17.5
164
510
67
780
Terminal block
90.6
29.7
96.5
14.4
L2
Air inlet
Installation
type
L3
Mark
L4
L1
( Maintenance )
space
Air
inlet
Air outlet
Open
280
280
L2
100
75
Open
L3
100
80
80
L4
250
Open
250
L1
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
46 -
35
35
42.5
595
Model FDCVA251HEN
Unit: mm
50
471.5
14
49.6
340
312.5
51.9
45.4
132
58.6
290
2-R
13.5
12
286.4
43.1
463
106
17.5
164
510
67
780
Terminal block
90.6
29.7
96.5
14.4
L2
Air inlet
Installation
type
L3
Mark
L4
L1
( Maintenance )
space
Air
inlet
Air outlet
Open
280
280
L2
100
75
Open
L3
100
80
80
L4
250
Open
250
L1
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
47 -
35
35
42.5
595
40
53
38
95
Liquid piping: 9.52 (3/8")
(Flare connecting)
Terminal block
55
110
482
195
15
50
50
Opening for
piping and
electric wring
50
10
195
460
110
845
Opening for
electric wring
Opening for
piping and
electric wring
50
50
27
880
50
Opening for
piping and
electric wring
Opening for
piping and
electric wring
55
15
150
70
340
40
580
50
310
222
15
50
47
150
103
380
40
150
60
20
20
Opening for
electric wring
40
15
50
VIEW A
Required space for maintenance and air flow
L2
Installation
type
Open
Open
500
300
Open
L3
100
150
100
L4
Mark
L4
Air
inlet
L1
Air inlet
L2
L3
L1
Maintenance
space
Air outlet
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
48 -
40
53
48
99
Terminal block
1050
50
195
110
600
50
55
50
10
195
110
578
Opening for
electric wring
50
27
15
50
340
15
55
40
50
50
15
295
237
150
47
70
103
380
40
165
60
20
20
920
40
15
50
VIEW A
Open
500
300
Open
L3
150
300
150
L4
L1
Maintenance
space
Open
Mark
L4
Air
inlet
L1
Air inlet
L2
L3
L2
Air outlet
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
49 -
Model FDCA501HES
Liquid piping: 9.52 (3/8")
(Flare connecting)
Unit: mm
53
48
40
99
Terminal block
Liquid piping: 9.52 (3/8")
(Flare connecting)
Gas piping: 15.88 (5/8")
(Flare connecting)
Opening for electric wring
1300
195
110
650
55
50
50
50
10
195
110
628
15
50
27
50
15
40
190
60
388
15
50
262
60
150
60
70
38
103
55
370
40
20
20
410
970
40
15
VIEW A
50
L2
L3
Installation
type
Open
Open
500
L2
300
Open
L3
150
300
150
L4
L1
Maintenance
space
Mark
L4
Air
inlet
L1
Air inlet
Air outlet
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
50 -
Model FDCA601HES
Liquid piping: 9.52 (3/8")
(Flare connecting)
Unit: mm
48
50
46
100
Terminal block
Liquid piping: 9.52 (3/8")
(Flare connecting)
Gas piping: 15.88 (5/8")
(Flare connecting)
Opening for electric wring
1300
195
110
648
55
50
50
50
10
195
110
589
15
50
27
50
40
190
60
388
15
50
262
60
150
60
70
38
103
55
370
40
20
20
410
970
40
15
VIEW A
50
L2
L3
Installation
type
Open
Open
500
L2
300
Open
L3
150
300
150
L4
L1
Maintenance
space
Mark
L4
Air
inlet
L1
Air inlet
Air outlet
Notes
(1) It is prohibited to install in a space enclosed with walls
at four sides.
(2) Unit must be secured with anchor bolts.
Anchor bolt should not protrude more than 15 mm above
the surface.
(3) Where strong winds blow, the blow outlet must be
oriented at right angle against the wind direction.
(4) Secure a space of 1 m or more above the unit.
(5) Barrier standing in front of the blow outlet must be lower
than the height of unit.
51 -
unit : mm
Electronic expansion
valve
Control box
4-way valve
Receiver
(Heating)
Receiver
(Cooling)
Service valve
(Liquid side)
Service valve
(Gas side)
Compressor
Models FDCA401HEN,401HES
Electronic expansion
valve
Control box
Accumlator
4-way valve
Service valve
(Liquid side)
Service valve
(Gas side)
High pressure
switch
(63H1)
Compressor
52 -
Pearl white
Light gray
Pearl white
(Horizontal louver)
(Front panel)
Pearl white
(Side panel)
Pearl white
(Front panel)
Pearl white
(Air inlet grille)
(c)
Model FDKNA301
Ivory white
(Air inlet grill)
Ivory white
(Front panel)
Ivory white
(Base)
Noble white
Ivory white
(Flap)
(d) Ceiling mounted duct type (FDUR) ................... Zinc steel plate
53 -
Models FDCA301HEN,301HES
Sutakko white
Polar white
Models FDCA401HEN,401HES
Models FDCA501HES,601HES
Polar white
Polar white
54 -
Indoor unit
Outdoor unit
Gas line
151, 201:12.7
251:15.88
Strainer
Cooling cycle
Check joint
Check joint
Service valve
(Flare connecting)
Heat exchanger
Heating cycle
Heat exchanger
4way valve
Muffler
Thermistor
(ThI-A)
Thermistor
(ThO-A)
Thermistor
(ThO-D)
Discharge
Compressor
Muffler
Suction
Thermistor
(ThI-R2)
Thermistor
(ThI-R1)
Thermistor
(ThO-R)
Receiver
(Heating) Electronic expansion valve
(EEV)
Strainer
Liquid line
(6.35)
Service valve
(Flare connecting)
Strainer
Receiver
(Cooling)
Strainer
Note (1) A FDE type strainer only should be used for the indoor unit.
Indoor unit
Outdoor unit
Cooling cycle
Heating cycle
Check joint
Strainer
Gas line
(15.88)
Check joint
Service valve
(Flare connecting)
4way valve
Heat exchanger
Thermistor
(ThI-A)
Muffler
Thermistor
(ThO-D)
Compressor
Thermistor
(ThI-R2)
Thermistor
(ThI-R1)
Strainer
Thermistor
(ThO-A)
Heat exchanger
Service valve
(Flare connecting)
Liquid line
(9.52)
Note (1) A FDE type strainer only should be used for the indoor unit.
55 -
Discharge
Accumlator
Suction
Thermistor
(ThO-R2)
Thermistor
(ThO-R1)
Sub-Cooling
Coil
Mark
Equipped
unit
ThI-R
Indoor unit
OFF 1.0C
ON 10C
Thermistor
(for frost prevention)
Thermistor
(for detecting discharge pipe temp.)
High pressure switch
(for protection)
Tho-D
63H1
OFF 105C
ON 80C
Outdoor unit
Outdoor unit
OFF 121C
ON 80C
OFF 4.15MPa
ON 3.15MPa
56 -
Cooling operation
Heating operation
FDTA151, 201
FDTA251, 301
FDTA401
FDTA501
FDTA601
Hi
0.186
0.040
0.027
0.025
0.028
Me
0.160
0.031
0.021
0.021
0.022
Lo
Air flow
0.151
0.025
0.018
0.017
0.017
FDENA151, 201
FDENA251, 301
FDENA401
FDENA501, 601
0.017
0.026
0.020
0.023
Me
0.014
0.022
0.016
0.020
Lo
0.009
0.015
0.013
0.016
57 -
FDKNA151, 201
FDKNA251
FDKNA301
0.056
0.063
0.043
Hi
Air flow
Me
0.041
0.048
0.034
Lo
0.028
0.034
0.025
FDUR201
FDUR251
FDUR301
FDUR401
FDUR501, 601
Hi
0.111
0.053
0.069
0.106
0.050
Lo
0.083
0.037
0.049
0.079
0.034
(2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
(3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Equivalent piping length(1) m
7.5
10
15
20
25
30
35
40
45
50
55
Heating
1.0
0.995
0.992
0.990
0.987
0.984
0.981
0.978
0.975
0.972
0.970
151 series
1.0
0.997
0.991
0.985
0.980
0.974
0.968
0.962
0.956
201 series
1.0
0.996
0.989
0.981
0.973
0.966
0.958
0.951
0.943
251 series
1.0
0.995
0.986
0.977
0.967
0.958
0.948
0.939
0.930
301 series
1.0
0.996
0.989
0.982
0.974
0.967
0.959
0.952
0.945
0.937
0.930
401 series
1.0
0.995
0.986
0.976
0.967
0.957
0.948
0.938
0.929
0.919
0.910
501 series
1.0
0.994
0.982
0.969
0.957
0.945
0.933
0.921
0.908
0.896
0.884
601 series
1.0
0.993
0.978
0.963
0.948
0.933
0.918
0.903
0.888
0.873
0.858
Cooling
Note
(4) When the outdoor unit is located at a lower height than the indoor unit in cooling operation and when the outdoor unit is located
at a higher height than the indoor unit in heating operation, the following values should be subtracted from the values in the
above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
5m
10m
15m
20m
25m
30m
Adjustment coefficient
0.01
0.02
0.03
0.04
0.05
0.06
Item
Max. one way piping length
301~601 models
40m
Note
50m
7200
FDTA301HEN
1.00
Air flow
High
(0.989 - 0.01)
Length 15m.
Height difference 5 m
58 -
1.0
7049 w
Factor by air
temperatures
FDURA201
Model
110
100
100
90
e
ee
60
r
er
o
ow
-L
rd
ar
nd
an
St
d
rd-L
10
r
er
o
ow
13 12 14
15
17
16
Lower
limit
18
Standard
air flow
19
limi
Sta
20
d
nda
10
pper
17
18
19
Upper
limit
Air flow(m3/min)
FDURA301
Model
200
180
160
FDURA401
200
180
160
140
itt
m
lim i
eerr li
pp
Up p
d
eed--U
spe
igh
H
120
Hi
Hig
gh
h ss
pe
pee
edd-H
Hiig
gh
h
-L
o
o
ow
pper
limit
r
r
ar
n
n
nd
Sta
rd-U
-H
-H
d-H
e
er
27
Lower
limit
Upper
limit
g
g
igh
-L
-Low
ow
r
rd-L
Standard
air flow
h sp
da
Stan
ow
ed-L
29
31
33 34 35
37
Standard
air flow
Air flow(m3/min)
Air flow(m3/min)
59 -
imi
er l
Hig
da
dard
20
20 21 22 23 24 25 26 27 28 29 30
Lower
limit
80
St
Stan
n
nda
100
60
Standard
50
pressure
40
h
h
gh
Hiiig
d--H
arrdna
n da
nd
Sta
Stta
mt
limiit
per
-Up
dard
Stan
S
Sta
20
ow
L
L
d-
e
pe
60
Standard
50
pressure
40
Hig
d
ee
sp
s
g
gh
mt t
lilimi i
w err
Loowe
edeeed-L
p
h ssp
Higgh
Hi
Hi
gh
sp
ee
dHi
gh
ed
spe
h
h
gh
Hi
80
120
mi
r li
pe
Up
Hi
100
140
Static pressure (Pa)
23
22
Standard
air flow
Air flow(m3/min)
Model
21
20
Lower
limit
Upper
limit
h
Hig
t
limi
d-U
ndar
30
t
Sta
20
60
40
g
igh
30
70
h
h
igh
-H
a
a
ard
n
n
nd
Sta
40
sp
ee
dHi
gh
wer
-Lo
d
spee
Standard
pressure 50
-H
ad
dar
tan
Sta
it
lim
per
-Up
rd
nda
Sta
Hi
gh
h
Hig it
lim
80
w
w
Standard
pressure 50
per
-Up
ed
spe
Lo
d
de
ee
s
sp
g
gh
H
Hi
e
werr
Lo w
ed--L o
pe d
h ssp ee
g
Hiig h
H it
lim t
90
h
gh
Hi
d
d-
w
ow
-- o
-LLo
e
e dd
pe e
hp
hhss
H
Hi
Higg
70
s
sp
80
gh
Hi
peerr
Uppp
edd--U
ssppeee
h
Hiiggh itt
H mi
lliim
120
110
120
FDURA251
39
41
Upper
limit
200
180
160
120
gh
Hi
100
it
lim
er
pp
-U
ed
spe
Hi
gh
sp
ee
d-
Hi
gh
Hi
s
g
gh
80
L
L
d
dee
pe
140
w
ow
Standard
pressure
o
o
ow
rd
rd
rd-L
n
n
nda
Sta
20
imit
per l
d-Up
ndar
Sta
g
gh
H
Hi
d
dee
sp
g
gh
H
Hi
60
50
40
it
er lim
-Low
speed
High
0
33.5 35.5 37.5 39.5 41.5 43.5 45.5 47.5 49.5
Lower
50
42
limit
Upper
Standard
air flow
limit
Air flow(m3/min)
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
20
N1
N20
10
63
125
250
500
1000
2000
4000
10
8000
60
Model FDTA251
Noise level 38 dB (A) at HIGH
35 dB (A) at MEDIUM
33 dB (A) at LOW
Model FDTA301
Noise level 38 dB (A) at HIGH
35 dB (A) at MEDIUM
33 dB (A) at LOW
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
20
N20
N1
10
63
125
250
500
1000
2000
4000
10
8000
60 -
60
N60
50
50
N50
40
40
N40
30
30
N30
20
20
N20
N1
10
63
125
250
500
1000
2000
4000
10
8000
Model FDTA401
Noise level 46 dB (A) at HIGH
43 dB (A) at MEDIUM
41 dB (A) at LOW
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
20
N1
N20
10
63
125
250
500
1000
2000
60
50
50
N50
40
40
N40
30
30
N30
20
20
N20
N1
10
8000
10
10
8000
4000
60
N60
63
125
250
500
1000
2000
4000
Unit
1m
1m
Model FDENA401
Models FDENA251, 301
Noise level 46 dB (A) at HIGH
Noise level 44 dB (A) at HIGH
44 dB (A) at MEDIUM
41 dB (A) at MEDIUM
41 dB (A) at LOW
39 dB (A) at LOW
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
20
63
125
250
500
1000
2000
20
8000
4000
70
70
60
60
N60
50
50
N50
40
40
N40
30
30
20
63
125
250
500
70
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
1000
2000
4000
20
8000
N70
60
N30
N2
0
70
70
N70
20
8000
61 -
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
(c)
Unit
1m
50
50
N50
40
40
N40
30
30
N2
N30
20
63
125
250
500
1000
2000
4000
20
8000
Model FDKNA251
Noise level 48 dB (A) at HIGH
45 dB (A) at MEDIUM
42 dB (A) at LOW
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
70
70
N70
125
250
500
1000
2000
4000
60
N60
70
70
N70
60
Mike
(Center & Low points)
Model FDKNA201
Noise level 47 dB (A) at HIGH
44 dB (A) at MEDIUM
41 dB (A) at LOW
Model FDKNA151
Noise level 44 dB (A) at HIGH
42 dB (A) at MEDIUM
40 dB (A) at LOW
70
1m
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
20
8000
63
125
250
500
1000
2000
4000
20
8000
Model FDKNA301
Noise level 49 dB (A) at HIGH
46 dB (A) at MEDIUM
43 dB (A) at LOW
Souud Pressure Level
(standard 0.0002 bar)
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
Model FDKN251
Noise level 41 dB (A) at HIGH
37 dB (A) at LOW
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
70
70
Model FDKN301
Noise level 41 dB (A) at HIGH
37 dB (A) at LOW
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
20
63
125
250
500
1000
2000
4000
20
8000
62 -
Model FDURA201
Noise level 40 dB (A) at HIGH
36 dB (A) at LOW
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
N30
20
63
125
250
500
1000
2000
4000
20
8000
Model FDURA401
Noise level 42 dB (A) at HIGH
37 dB (A) at LOW
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
20
8000
4000
70
N70
63
125
250
500
1000
2000
4000
20
8000
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
70
70
20
8000
4000
60
50
40
30
60
N60
50
50
N50
40
40
N40
30
30
N30
20
250
500
1000
30
N30
N2
0
63
125
250
500
1000
2000
4000
20
8000
70
2000
4000
20
8000
60
125
40
N40
20
70
63
50
N50
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
63 -
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
20
8000
N70
N2
60
N60
Model FDCA601HES
Noise level 57 dB (A)
70
70
70
N70
Model FDCA501HES
Noise level 56 dB (A)
220/240V 15V
1
2
3
4
CnW1
5
Power board
Y/GN
OR
RD
BL
P
BR
BK
X3
CnJ
SW5
SW9
SW2
2
3
RD
WH
BK
TB
X
RD
WH
BK
1
1 3 5 7 9
OR
CnM3
CnR
DM
CnR2
FS
CnV
CnI2
Y/GN
CnY
Printed circuit
board
SW9-4
ON
OFF
FMI
Function number A
Function description B
01
Hi CEILING SET
Meaning of marks
Parts name
Fan motor
Capacitor for FMI
Drain motor
Float switch
Louver motor
Thermistor
Thermistor
Thermistor
Thermistor
Remote controller communication address
Remote
controller
WH
BR
BK
BL
RD
64 -
CnF
CnI
CFI
OR
Mark
FMI
CFI
DM
FS
LM1~4
ThI-A
ThI-R1
ThI-R2
ThC
SW2
ThC
CnW5
RD
BK
BK
X1
WH
BL
CnW8
CnJ2
CnB
X4
2/N
LED 2
WH
BR
BK
BL
RD
WH
X2
X6
C
UH
H
M
L
to outdoor unit
Power line 1 2/N
Signal line 3
F(3.15A)
CnT
LED 1
CnW2 CnW10
1
WH 3
BL
TB
1 RD
CnN1
XR5
RD
RD
RD 1
CnH
CnW7
BR
BK
BK
BK
BK
CnW4
XR3
Mark
SW5-3,4
SW9-3
TrI
F
LED1
LED2
XR1
XR2
XR3
XR4
Parts name
Filter sign
Emergency operation
Transformer
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Heating output(DC12V output)
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Mark
XR5
X1,2,3,6
X4
TB
CnB~Z
mark
Parts name
Setting C
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
P
Pink
RD
Red
WH
White
Y
Yellow
Y/GN
Yellow/Green
ELECTRICAL DATA
XR1
BKTrI RD
CnN3
CnN4
XR4
XR2
Option
ThI-R2
Models FDTA151,201,251,301,401
ThI-A ThI-R1
Option
XR2
RD 1
15V
Y/GN
CnJ2
BL
BK
BK
XR5
CnT
SW5
CnW8
CnW9
CnM2
CnW6
2 3 4
3
1
WH
RD
LED 2
X4
65 -
CnF
WH
BK
TB
X
RD
WH
BK
ThC
Remote
controller
Printed circuit
board
CnY
CnV
CnI2
CnR2
DM
CnD1
CnI
CnR
SW9
SW2
RD
RD
1
2
3
4
CnJ
CnB
1
3
CnW1
CnM1
Power board
LED 1
RD
CnW5
F(3.15A)
WH 3
BL
CnW7
WH
2/N
CnN1
BR
RD
BK
BR
to outdoor unit
Power line 1 2/N
Signal line 3
RD
XR3
BL 5
220/240V 15V
TB
1
WH 3
RD
CnW2 CnW3
CnH
CnW4
BK
BK
BK
BK
4
17V
BK
TrI
BK BR
XR1
XR4
OR
RD
CnN3
CnN4
P
BR
ThI-R2
ThI-A ThI-R1
FS
SW9-4
CnD2
FMI
Function description B
Setting C
01
Hi CEILING SET
Meaning of marks
Mark
FMI
DM
FS
LM1~4
ThI-A
ThI-R1
ThI-R2
ThC
SW2
SW5-3,4
Parts name
Fan motor
Drain motor
Float switch
Louver motor
Thermistor
Thermistor
Thermistor
Thermistor
Remote controller communication address
Filter sign
Mark
SW9-3
TrI
F
LED1
LED2
XR1
XR2
XR3
XR4
XR5
Parts name
Emergency operation
Transformer
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Heating output(DC12V output)
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Remote operation input(volt-free contact)
Mark
X4
TB
CnB~Z
mark
Parts name
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
P
Pink
RD
Red
WH
White
Y
Yellow
Y/GN
Yellow/Green
Wired specification
XR4
to outdoor unit
Power line 1 2/N
Signal line 3
2/N
3
WH
BL
BK
BK
CnW0
X6
X2
X4
Y/GN
1
2
3
4
5
CnM3
UH
CnR
CnI
CnY
CnV
Remote
controller
Wireless specification
2
3
RD
WH
BK
CnB
TB
X
AMP
LED3
SW2
LED1
SW1
LED2
Z
CnB2
CnO
Remote controller
66 -
BK
BL
WH
BR
SW9-4
FMI2
ON
OFF
2 By means of function setting from the wired remote controller unit,set the setting
2 "I/U FUNCTIONL" (indoor unit function) to "STANDARD (Mild mode)."
CnF2
*1
Function number A
Function description B
01
Hi CEILING SET
Fan motor
Capacitor for FMI
Louver motor
Thermistor
Thermistor
Thermistor
Thermistor
Remote controller communication address
Filter sign
Emergency operation
Transformer
Mark
F
LED1
LED2
XR1
XR2
XR3
XR4
XR5
X1,2,3,6
TB
CnB~Z
of
Meaning of marks
Parts name
Setting C
BK
CFI1
CFI2
15V
LED 2
3
ThC
SW9
SW2
LED 1
CnF1
Y/GN
RD
SW5
CnJ1
WH
FMI1
BK
220/240V
X3
CnW2
X1
BL
P
BR
OR
RD
RD
RD
CnW1
F (3.15A)
3
5
BK
TrI
Y/GN
LM
TB
X
CnN1
CnH
CnT
RD
BK
BK
1
CnN3
CnN2
XR5
BK
XR3
BK
XR1
TB
1
ThI-R2
Parts name
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Heating output(DC12V output)
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Remote operation input(volt-free contact)
Auxiliary relay(For FM)
Terminal block( mark)
Connector
Mark
mark
LED1
LED2
LED3
SW1
SW2
Parts name
Closed-end connector
Indication lamp(Green-Operation)
Indication lamp(Yellow-Timer/Check)
7-segement indicator(For check)
Switch(For setting)
Backup switch(Operation/Stop)
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
P
Pink
RD
Red
WH
White
Y
Yellow
Y/GN
Yellow/Green
XR2
ThI-R1
ThI-A
Option
ThI-R2
TrI
LM
2/N
2/N
3
RD
CnH
1 2
CnN1
RD
RD
Wired specification
5 4 3 2 1
CnW1
CnJ
14V
BR
BR
BK
BK
BL
P
BR
OR
RD
BK
BK
BK
1
RD
BK
F (3.15A)
17V
CnW2
CnB
WH
S
3
SW2
BL/WH
LED R
SW5
Y/GN
RD
WH
BK
TB1
X
RD
WH
BK
ThC
Remote
controller
Wireless specification
LED G
SW9
Y/GN
6
5
CnL
3
BK
WH
RD
CnT
4
3
2
1
BL
CnM
SW
LED5
LED3
Remote controller
XR3
XR5
67 -
XR4
FMI
AMP
to outdoor unit
Power line 1
Signal line 3
TB
1
BK
BK
220/
240V
XR1
XR2
Option
ON
OFF
2 By means of function setting from the wired remote controller unit,set the setting
2 "I/U FUNCTIONL" (indoor unit function) to "STANDARD (Mild mode)."
Function number A
Mark
SW9-3
LED3
LED5
TrI
F
LED R
LED G
XR1
XR2
Setting C
01
Meaning of marks
Mark
Parts name
FMI
Fan motor
LM
Louver motor
ThI-A
Thermistor
ThI-R1 Thermistor
ThI-R2 Thermistor
ThC
Thermistor
SW
Backup switch(ON/OFF)
SW2
Remote controller communication address
SW5-3,4 Filter sign
Function description B
Hi CEILING SET
Parts name
Emergency operation
Indication lamp(Green-Run)
Indication lamp(Yellow-Inspection alert)
Transformer
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Heating output(DC12V output)
Mark
XR3
XR4
XR5
TB
CnA~Z
AMP
Parts name
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Remote operation input(volt-free contact)
Terminal block( mark)
Connector
Wirelss receiver
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
RD
Red
WH
White
Y
Yellow
P
Pink
BL/WH Blue/White
Y/GN
Yellow/Green
of
ThI-A
ThI-R1
ThI-R1
ThI-A
ThI-R2
Model FDKNA301
LM
to outdoor unit
Power line 1
Signal line 3
RD
WH
BL/WH
Y/GN
BL
P
BR
OR
RD
BK
BK
1
RD
BK
F (3.15A)
BK
TB
1
BK
BK
Wired specification
1 2
CnN1
CnH
CnJ
CnB
SW2
J
SW5
2
3
LED R
RD
WH
BK
TB1
X
RD
WH
BK
ThC
Remote
controller
LED G
SW9
Wireless specification
1
CnC
SW1
4
BL
3
Y
RD
CnT
CnA
WH
CnM
1
LED5
LED3
2
3
XR3
XR5
XR1
AMP
Remote controller
68 -
XR2
XR4
FMI
Option
Blower fan tap switch
1 Set SW9-4 provided on the indoor unit PCB to OFF.
SW9-4
ON
OFF
2 By means of function setting from the wired remote controller unit,set the setting
2 "I/U FUNCTIONL" (indoor unit function) to "STANDARD (Mild mode)."
Function number A
Function description B
Hi CEILING SET
of
Setting C
01
Meaning of marks
Mark
Parts name
FMI
Fan motor
LM
Louver motor
ThI-A Thermistor
ThI-R1 Thermistor
ThI-R2 Thermistor
ThC
Thermistor
SW1
Backup switch(ON/OFF)
SW2
Remote controller communication address
Mark
SW5-3,4
SW9-3
LED3
LED5
F
LED R
LED G
XR1
Parts name
Filter sign
Emergency operation
Indication lamp(Yellow-Timer/Inspction alert)
Indication lamp(Green-Run)
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Mark
XR2
XR3
XR4
XR5
TB
CnA~Z
AMP
Parts name
Heating output(DC12V output)
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Remote operation input(volt-free contact)
Terminal block( mark)
Connector
Wirelss receiver
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
RD
Red
WH
White
Y
Yellow
P
Pink
BL/WH Blue/White
Y/GN
Yellow/Green
ThI-R2
ThI-R1
BL
RD
RD
BK
RD
RD
RD
XR5
5
CnT
CnW2
CnW1
LED 1
SW2
SW5
X6
X2
X1
5
H
BL GR
BL
WH
Y/GN
UH
CnI
CnR 1 3
9
L
RD
BK
CnF1
CnI2
DM
FS
OR
69 -
CnB
2
Z TB
CnR2
FMI
RD WH BK
ThC
Remote
controller
CFI
LED 2
SW9
RD
CnM3 1
SW6
X3
RD
Y/GN
X4
RD
CnW0
BR
2/N
CnN1
15V
XR4
XR3
BK
2/N
CnH
XR1
F (3.15A)
WH
3 2
220/
240V
WH
RD
to outdoor unit
Power line 1
Signal line 3
BK
RD
XR2
TrI
CnN3
RD
RD
BK
CnN2
BK
CnH2
RD
BK
RD
BK
Option
ON
OFF
2 By means of function setting from the wired remote controller unit,set the setting
"I/U FUNCTIONL" (indoor unit function) to "Hi CEILING1"
Function number A
Function description B
Hi CEILING SET
of
Setting C
01
Hi CEILING1
Meaning of marks
Mark
Parts name
FMI
Fan motor
CFI
Capacitor for FMI
DM
Drain motor
FS
Float switch
ThI-A
Thermistor
ThI-R1 Thermistor
ThI-R2 Thermistor
ThC
Thermistor
SW2
Remote controller communication address
Mark
SW5-3,4
SW6
SW9-3
TrI
F
LED1
LED2
XR1
XR2
Parts name
Filter sign
Model setup
Emergency operation
Transformer
Fuse
Indication lamp(Red)
Indication lamp(Green)
Operation output(DC12V output)
Heating output(DC12V output)
Mark
XR3
XR4
XR5
X1,2,3,6
X4
TB
CnA~Z
mark
Parts name
Thermo ON output(DC12V output)
Inspection output(DC12V output)
Remote operation input(volt-free contact)
Auxiliary relay(For FM)
Auxiliary relay(For DM)
Terminal block( mark)
Connector
Closed-end connector
Color marks
Mark
Color
BK
Black
BL
Blue
BR
Brown
GR
Gray
OR
Orange
RD
Red
WH
White
Y
Yellow
Y/GN
Yellow/Green
ThI-A
Y/GN
BK
CNS
BR
BR
CNR
Y/GN
FMo
CM
T1
CNI2 CNI3
T2
T4
BL
SW5
SM
BK
BK
BK
OR
RD
WH
BR
BL
2
Y
70 -
CNQ
LED1
CNL
CNTR
CNM
BK
WH
BK
WH
U
V W
T6 T7 T8
BL
WH
RD
Reactor
10
OR
T5
Y/GN
2/N
T28 T27
20S
CH
BR
T26
T30
CNI1
BK
T22
to indoor unit
Power line 1
Signal line 3
2/N
BK
GR
T25
BK
WH
TB
1
OR
T24
T21
BK
RD
Tho-IPM
Tho-R
Meaning of marks
Mark
Parts name
Crankcase heater
CH
Compressor motor
CM
CNA~Z Connector( mark)
Fuse
F
Fan motor
FMo
Indication lamp(Red)
LED1
SM
Stepping motor(for EEV)
SW5-1 Defrost control switch
SW5-2 Snow prevented fan control switch
SW5-4 Operate test run switch(Cooling/Heating)
Mark
SW9
TB
Tho-A
Tho-D
Tho-IPM
Tho-R
20S
mark
Tho-A
Tho-D
Parts name
Pump down switch
Terminal block( mark)
Thermistor(outdoor air temp.)
Thermistor(discharge temp.)
Thermistor(Power transistor temp.)
Thermistor(outdoor H.EX. temp.)
4 way valve(coil)
Fasuton terminal
Color mark
Mark
Color
BK
Black
BL
Blue
BR
Brown
GR
Gray
OR
Orange
RD
Red
WH
White
Y
Yellow
Y/GN Yellow/Green
U
RD
V
WH
W
BK
Compressor terminal
arrangement
SW9
F5 (20A)
RD
TB
Power source
1Phase
220-240V 50Hz
RD
WH
BK/WH
FMo1
20S
(49Fo1)
52C
A1
SM
A2
CF
CNM3
CNS
CNR
CNO
71 -
SW2
OFF 1 2 3 4
Xo4
Xo2
Xo5
Xo3
Xo6
BK
CNE
(Checker)
CNQ
(Test)
Mark
SM
SW2
SW5-1
SW5-2
SW5-4
TB
Tho-A
Tho-D
Tho-R1,2
Tro
Parts name
Stepping motor(for EEV)
Test run switch
Defrost control switch
Snow prevented fan control switch
Operate test run switch
Terminal block( mark)
Thermistor(outdoor air temp.)
Thermistor(discharge temp.)
Thermistor(outdoor H.EX. temp.)
Transformer
Mark
Xo1
Xo2,3,4
Xo5
Xo6
20S
49C
49Fo1
52C
63H1
Parts name
Auxiliary relay(for 52C)
Auxiliary relay(for FMo)
Auxiliary relay(for 20S)
Auxiliary relay(for CH)
4 way valve(coil)
Internal thermostat for CM
Internal thermostat for FMo1
Magnetic contactor for CM
High pressure switch
4 3
2 1
CNL
14V
LED-G
1 2 3 4 5 6
CNV1
LED-R
13V
BR
CNA1
Meaning of marks
Mark
Parts name
Cc
Capacitor for CM
CFo1
Capacitor for FMo1
CH
Crankcase heater
CM
Compressor motor
CNA~Z Connector( mark)
CT1
Current sensor
F
Fuse
FMo1
Fan motor
LED-G Indication lamp(Green)
LED-R Indication lamp(Red)
6 5
RD
220/240V
Xo1
8 7
Tro
CNP1
SW5
ON
BR
BR
BR
BR
CNM1
BK
OR
CNW
Tho-D
63H1
CFo 1
OR
OR
11
CH
CF
BK
WH
Hi
BR
CT1
UHi Lo
BL
(49C)
BL/WH
C CM
RD/Y
WH
RD
Cc
WH
Y
OR
BL
BR
RD
BL BL
WH
RD
52C
BK
to indoor unit
Power line 1 2/N
Signal line 3
RD
BL/WH
1
2/N
BK
F(10A)
RD
TB
BK
Y/GN
WH
Power source
1Phase
220-240V 50Hz
Y/GN
Normal
CNA2
Color mark
Mark
Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
Pink
P
Red
RD
Check
Mark
WH
Y
BK/WH
BL/WH
RD/Y
Y/GN
Color
White
Yellow
Black/White
Blue/White
Red/Yellow
Yellow/Green
Model FDCA301HEN
TB
F(10A)
BK/WH
BL
L3
TB
RD
WH
L2
BL/WH
to indoor unit
Power line 1 2/N
Signal line 3
2/N
3
FMo1
20S
(49Fo1)
52C
Tho-R2 Tho-R1 Tho-A
72 -
SW2
Meaning of marks
Mark
Parts name
Capacitor for FMo1
CFo1
CH
Crankcase heater
CM
Compressor motor
CNA~Z Connector( mark)
CT1,2 Current sensor
F
Fuse
FMo1
Fan motor
LED-G Indication lamp(Green)
LED-R Indication lamp(Red)
SM
Stepping motor(for EEV)
OFF 1 2 3 4
Mark
SW2
SW5-1
SW5-2
SW5-4
TB
Tho-A
Tho-D
Tho-R1,2
Tro
Xo1
Xo1
Xo4
Xo2
Xo5
CNS
CNR
Xo3
CNE
Xo6 (Checker)
Parts name
Test run switch
Defrost control switch
Snow prevented fan control switch
Operate test run switch
Terminal block( mark)
Thermistor(outdoor air temp)
Thermistor(discharge temp)
Thermistor(outdoor H.Ex.temp)
Transformer
Auxiliary relay(for 52C)
BR
BR
CNO
8 7
Tro
CNP1
BK
CNQ
(Test)
Mark
Xo2,3,4
Xo5
Xo6
20S
49C
49Fo1
52C
63H1
14V
Parts name
Auxiliary relay(for FMo)
Auxiliary relay(for 20S)
Auxiliary relay(for CH)
4 way valve(coil)
Internal thermostat for CM
Internal thermostat for FMo1
Magnetic contactor for CM
High pressure switch
4 3
2 1
1 2 3 4 5 6
CNV
LED-G
LED-R
13V
Normal
BR
CNA1
6 5
CNL
RD
220/240V
SW5
ON
CNM3
BR
BR
CNM1
BK
BK
CNW
Tho-D
63H1
CFo1
OR
11
CH
OR
OR
CF
CF
BK
WH
Hi
BR
CM T3
CT1
CT2
(49C)
UHi Lo
BL
T1
WH
BL
T2
BL/WH
RD
SM
A2
6
RD/Y
BK/WH
WH
A1
WH
Y
OR
BL
BR
RD
BK
BK
52C
RD
BL
BK/WH
RD
Y/GN
RD
L1
WH
Power source
3Phase
380-415V 50Hz
Y/GN
CNA2
Color mark
Mark Color
BK
Black
BL
Blue
BR
Brown
OR
Orange
P
Pink
RD
Red
Check
Mark
WH
Y
BK/WH
BL/WH
RD/Y
Y/GN
Color
White
Yellow
Black/White
Blue/White
Red/Yellow
Yellow/Green
Model FDCA301HES
TB
RD
WH
BK/WH
2/N
20S
(49Fo2)
52C
A1
SM
A2
CNM4
CNS
CNR
CNO
Xo1
73 -
SW2
OFF 1 2 3 4
Xo4
Xo2
Xo5
Xo3
Xo6
BR
8 7
Tro
CNP1
BK
CNE
(Checker)
CNQ
(Test)
Meaning of marks
Mark
Parts name
Cc
Capacitor for CM
CFo1,2 Capacitor for FMo1,2
CH
Crankcase heater
CM
Compressor motor
CNA~Z Connector( mark)
CT1
Current sensor
F
Fuse
FMo1,2 Fan motor
LED-G Indication lamp(Green)
LED-R Indication lamp(Red)
Mark
SM
SW2
SW5-1
SW5-2
SW5-4
TB
Tho-A
Tho-D
Tho-R1,2
Tro
Parts name
Stepping motor(for EEV)
Test run switch
Defrost control switch
Snow prevented fan control switch
Operate test run switch
Terminal block( mark)
Thermistor(outdoor air temp.)
Thermistor(discharge temp.)
Ther mistor(outdoor H.EX. temp.)
Transformer
14V
Mark
Xo1
Xo2,3,4
Xo5
Xo6
20S
49C
49Fo1,2
52C
63H1
Parts name
Auxiliary relay(for 52C)
Auxiliary relay(for FMo)
Auxiliary relay(for 20S)
Auxiliary relay(for CH)
4 way valve(coil)
Internal thermostat for CM
Internal thermostat for FMo1,2
Magnetic contactor for CM
High pressure switch
4 3
2 1 1 2 3 4 5 6
LED-G
CNV1
LED-R
13V
BR
CNA1
6 5
CNL
RD
220/240V
SW5
ON
BR
BR
BR
CNM2
BK
CNM3
BK
Tho-D
63H1
CFo2
GR
OR
11
CH
CF
CF
BK
WH
CFo 1
Hi
BR
CNM1
CNW
UHi Lo
BL
CF
OR
CF
OR
WH
1 11
Hi
OR
BL
BL/WH
BR
CT1
RD/Y
(49C)
WH
S
C CM
UHi Lo
BK
Cc
WH
Y
OR
BL
BR
RD
(49Fo1)
RD
WH
FMo2
FMo1
4
BL BL
BK
52C
GR
to indoor unit
Power line 1
Signal line 3
RD
BL/WH
1
2/N
BK
F(10A)
RD
TB
RD
Y/GN
WH
Power source
1Phase
220-240V 50Hz
Y/GN
Model FDCA401HEN
TB
Normal
Color mark
Mark
Color
BK
Black
BL
Blue
BR
Brown
GR
Gray
OR
Orange
P
Pink
RD
Red
Check
CNA2
Mark
WH
Y
BK/WH
BL/WH
RD/Y
Y/GN
Color
White
Yellow
Black/White
Blue/White
Red/Yellow
Yellow/Green
F(10A)
BK/WH
BL
L3
TB
RD
WH
L2
BL/WH
to indoor unit
Power line 1 2/N
Signal line 3
2/N
3
BL
BK/WH
FMo1
FMo2
(49Fo1)
20S
(49Fo2)
52C
Tho-R2 Tho-R1 Tho-A Tho-D
74 -
SW2
OFF 1 2 3 4
Xo1
Xo4
Xo2
Xo5
CNM4
CNS
CNR
CNO
8 7
Tro
CNP1
Xo3
Xo6
BR
BR
BR
BR
BK
CNM2
BK
CNM3
GR
63H1
CFo2
GR
OR
11
CH
BK
CNE
(Checker)
14V
Mark
SW2
SW5-1
SW5-2
SW5-4
TB
Tho-A
Tho-D
Tho-R1,2
Tro
Xo1
Parts name
Test run switch
Defrost control switch
Snow prevented fan control switch
Operate test run switch
Terminal block( mark)
Thermistor(outdoor air temp)
Thermistor(discharge temp)
Thermistor(outdoor H.Ex.temp)
Transformer
Auxiliary relay(for 52C)
CNQ
(Test)
Mark
Xo2,3,4
Xo5
Xo6
20S
49C
49Fo1,2
52C
63H1
2 1 1 2 3 4 5 6
CNV1
LED-G
LED-R
Normal
BR
Parts name
Auxiliary relay(for FMo)
Auxiliary relay(for 20S)
Auxiliary relay(for CH)
4 way valve(coil)
Internal thermostat for CM
Internal thermostat for FMo1,2
Magnetic contactor for CM
High pressure switch
4 3
13V
CNA1
Meaning of marks
Mark
Parts name
CFo1,2 Capacitor for FMo1,2
CH
Crankcase heater
CM
Compressor motor
CNA~Z Connector( mark)
CT1,2 Current sensor
F
Fuse
FMo1,2 Fan motor
LED-G Indication lamp(Green)
LED-R Indication lamp(Red)
SM
Stepping motor(for EEV)
6 5
CNL
RD
220/240V
SW5
ON
CF
CF
BK
WH
CNM1
Hi
BR
UHi Lo
BL
OR
1 11
CNW
CFo1
OR
OR
BK
CF
WH
CF
BR
CM T3
CT1
CT2
(49C)
BL
T1
WH
BL
T2
UHi Lo
Hi
BL/WH
RD
SM
A2
6
RD/Y
BK/WH
WH
A1
WH
Y
OR
BL
BR
RD
BK
BK
52C
RD
RD
Y/GN
RD
L1
WH
Power source
3Phase
380-415V 50Hz
Y/GN
CNA2
Mark
BK
BL
BR
GR
OR
P
RD
Color
Black
Blue
Brown
Gray
Orange
Pink
Red
Check
Mark
WH
Y
BK/WH
BL/WH
RD/Y
Y/GN
Color
White
Yellow
Black/White
Blue/White
Red/Yellow
Yellow/Green
TB
Vent Indicator
TIMER switch
Operation/Stop switch
27C
MODE switch
This switch is used to switch between
operation modes.
VENT switch
Switch that operates the
connected ventilator.
GRILL switch
This switch has no function.
When this switch is pressed,
(Invalid Operation)
is displayed, but it does not mean a failure.
LOUVER switch
This switch is used to operate/stop
the swing louver.
SET switch
TEST switch
RESET switch
CHECK switch
75 -
Signal sender
Fan speed
Auto swing
Indicates the selection of swing louver.
Temperature indicator
AUTO COOL DRY FAN HEAT
FAN HI ME LO
Timer ON time
Indicates the timer ON time.
When the timer mode is CONT or OFF,
the present time is indicated.
FILTER
ON AM
PM
OFF AM
PM
MODE
TEMP
ON/OFF
ON/OFF button
FAN SPEED
AIR FLOW
FILTER
SET
ACL
TIME
Filter button
Used to reset (turn off) the filter sign.
(Press for more than 1 second.)
Press the button only after completing
the filter cleaning.
TIME button
Set button
Reset switch
Used to reset the microcomputer when something is wrong on the remote controller display.
Clock switch
Press this before setting the present time.
76 -
Cooling operation
ON
OFF
OFF (52C)
+1
Set temp.by thermostat
-1
+1
Set temp.by thermostat
-1
Cooling operation
Heating operation
Ready for
heating
56
59
Indoor heat exchanger temperature (C)
(c)
Cooling
Thermostat Thermostat
ON
OFF
Fan
Thermostat
ON
Heating
Thermostat
Defrost
OFF
Note (1)
Louver motor
Condensate motor
Indoor fan
Dry
Thermostat Thermostat
HOT START
ON
OFF
(5min. ON)
:ON
:OFF
/ :According to control other than temperature control.
77 -
(5min. ON)
-2
Low
A
+3
High
Pattern of operation
Operation
block
CM, FMO: ON
FMI : ON
(16 minutes)
(8 minutes)
Continuous cooling operation (FMI:Lo)
A
Normal cooling operation
The air flow is set at 1 speed lower than the set air flow.
(8 minutes)
CM, FM0
FMI
(8 minutes)
(8 minutes)
CM, FM0
CM, FM0
FMI
FMI
(e)
Timer Operation
1) Simple Timer
This sets the amount of time from the current time that the air conditioner goes OFF.
The off time can be selected in 10 steps, from Off 1 hour from now to Off 10 hours from now. After the simple timer
is set, the number of hours until the air conditioning goes off is displayed in one hour units from the current time.
2) Time Off Timer
The time the air conditioner goes OFF can be set in 10-minute increments.
3) Time On Timer
The time the air conditioner goes ON can be set in 10-minute increments. The set temperature can also be set at the same
time.
78 -
4) Weekly Timer
Each day, it is possible to set this timer's operation up to 4 times (On time, or Off timer).
5) Possible joint use timer operation setting combinations
Simple Timer
Time On Timer
Simple Timer
Time Off Timer
Time On Timer
Weekly Timer
Weekly Timer
(f)
Thermostat OFF
Thermostat ON
Fan
OFF
30
25
30
Compressor ON
Defrosting ends
Compressor OFF
Defrosting starts
45
40
20
30
(g) FM control with the heating thermostat turned off (For cold draft prevention)
In order to prevent a cold draft while the heating thermostat is turned off, the indoor blower is controlled in response to the
temperature of the indoor heat exchanger as illustrated below. It should be noted that if jumer wire J2 (SW7-2) on the indoor
PCB is turned off, the indoor blower will stop so far as the temperature of the indoor heat exchanger is lower than 40C. It will
be turned to the Lo operation 5 minutes later.
(Setting air flow)
Lo
Note (1) After the thermostat is reset, it returns to the hot start
control.
40
45
79 -
Standard
Compressor
Operation
Stop
1
If J4 (SW7-4) is disconnected
(if it is turned ON),
Stop
+2
+1
Set temperature
+4
Set temperature
(i)
Operation
Compressor
Filter sign
If operating time (the length of time the ON/OFF switch is ON) totals 180 hours (1), FILTER CLEANING is displayed on
the remote control unit. (This is displayed whether the system is running or not, when the unit is broken down, and when
there is central control.)
Notes (1) The following controls are enabled by the combination of the ON/OFF settings of 2 switches on the indoor unit PCB, SW5-3 and SW5-4.
(They are switched OFF when the unit is shipped from the factory. The setting time is 180 hours.)
Switch
Function
SW5-3 OFF
SW5-4 OFF
SW5-3 OFF
SW5-4 ON
SW5-3 ON
SW5-4 OFF
SW5-3 ON
SW5-4 ON
Notes (2) When SW5-3, SW5-4 is switched ON, the message FILTER CLEANING is displayed after the setting time has passed, then the unit stops after
another 24 hours have passed (including stop time).
(j)
(Heating Preparation) display goes off, the LCD display also returns to the original display.
80 -
(k)
Condensate pump motor (DM) Control [FDT and FDUR models only]
(a) Drain motor is started no sooner than the compressor is turned ON during cooling or dehumidifying operation. The drain
motor continues to operate for 5 minutes after the stop of unit operation, stop with the error stop, thermostat stop and at
switching from cooling or dehumidifying operation to blowing or heating operation. When there is any unit subjected to oil
return control, the drain motor is operated for 5 minutes at such occasion.
(b) Overflow detection is performed by the float switch at all times regardless of the operating mode. If the float switch
circuit is detected to be open continuously for 3 seconds (or when the float switch is disconnected or a wire is broken), an
abnormal stop (E9) is performed and the condensate pump motor runs until the float switch recovers.
(l)
FDUR model
SW9-4 OFF
SW9-4 ON
(Mild Mode Control) (Powerful mode Control)
Hi, Me, Lo
DIP SW
Item
UHi, Hi, Me
SW9-4 OFF
(Standard)
SW9-4 ON
(High speed)
Hi, Lo
UHi, Hi
63
10
81 -
(q) Using 1 remote controller to control multiple units (indoor units - up to 16 units)
1) Function
A single remote control switch can be used for group control of multiple units (indoor units - up to 16 units). All units in
the group that have had the remote control switch set at [Operating Mode] can be turned on and off in order of the unit
number.
This functions independently of the thermostat and protection functions of each unit.
Notes (1) The unit number is set by a switch (SW2) on the circuit board for the indoor unit.
Set SW2 : 0~9, A~F
Outdoor unit
0
F
Refrigerant piping
indoor unit
Remote controller wire
Remote controller
Notes (2) If unit number is not important, random can be used. However, setting in order from 0, 1, 2, to F will ensure setting without error.
or
button
displays the indoor units in the order of lowest to highest assigned No.
4) Error
a) If an error occurs (protection device activation) with some of the units in the group, those units will have an error
stop, but the properly operating units will continue operation.
b) Wiring outline
Route the wire connecting each of the indoor and outdoor units as it would be for each unit. Use the terminal block
(X, Y, Z) for the remote control for the group controller and use a jumper wire among each of the rooms.
(r)
82 -
CnT Input
ON
OFF
OFF
ON
Air Conditioner A
Air Conditioner B
OFF
OFF
*ON
*ON
ON
OFF
ON
OFF
OFF
ON
OFF
CnT Input
ON
OFF
OFF
OFF
ON
Air Conditioner A
Air Conditioner B
OFF
OFF
ON
ON
OFF
83 -
DRY
COOL
FAN
HEAT
AUTO
SW2
SW2
A
B
M
SW1
SW1
Red
White
Z Black
Function
SW1
Note (1) SW2 is not normally used, so do not change the selection.
84 -
Units: rps
Model
Outdoor unit
151 model
201 model
251 model
75 [70](1)
95 [90](2)
125
30
30
40
Item
2) Heating operation
Units: rps
Model
Outdoor unit
151 model
201 model
251 model
80
95
125
30
30
40
Item
FDCVA151, 201
30
64
FDCVA251
40
64
Model
85 -
FDCVA151, 201
30
64
FDCVA251
40
64
Model
Thermostat ON start
When the thermostat
When the thermostat
is OFF, there is an
is OFF, there is no
operating mode change. operating mode change.
Protective start II
Protective start II
Protective start II
Protective start I
Protective start I
Protective start I
Protective start II
Protective start II
Protective start II
[Conditions]
The discharge pipe temperature (Tho-D) and outdoor air temperature (Tho-A) are detected.
If the discharge pipe temperature (Tho-D) minus the outdoor air temperature (Tho-A) is > 15 degrees, protective start II is
=
implemented.
If the discharge pipe temperature (Tho-D) minus the outdoor air temperature (Tho-A) is < 15 degrees, protective start III is
implemented.
(c) Compressor protective control according to operating speed (FDCVA 151~251 models only)
1) Compressor protection during high speed operation
When the compressor is operated at speeds exceeding 100 rps for 30 minutes, the upper limit for the compressors speed
is made 100 rps for 3 minutes.
2) Compressor protection during low speed operation
When the compressor is operated at speeds below 26 rps for 60 minutes, the lower limit for the compressors speed is
made 30 rps for 15 seconds.
(d) Outdoor fan control
FDCVA151~ 251 models
(i)
Outdoor fan tap and fan motor control contents during control
FDCVA151, 201
Cooling
less than 46
46 to less than 66
66 to less than 80
80 or more
4th speed (520 rpm) 5th speed (570 rpm) 6th speed (685 rpm) 7th speed (740 rpm)
less than 62
62 to less than 82
82 to less than 92
92 or more
4th speed (520 rpm) 5th speed (570 rpm) 6th speed (685 rpm) 7th speed (740 rpm)
86 -
FDCVA251
Compressor speed (rps)
Outdoor unit fan tap
Compressor speed (rps)
Heating
Outdoor unit fan tap
Cooling
66 to less than 80
less than 46
46 to less than 66
4th speed (520 rpm) 5th speed (570 rpm) 6th speed (685 rpm)
82 to less than 104
less than 62
62 to less than 82
4th speed (520 rpm) 5th speed (570 rpm) 6th speed (685 rpm)
80 or more
7th speed (740 rpm)
104 or more
7th speed (740 rpm)
A-Zone
Retain
48
B-Zone
25
29
a) After detecting the B-zone temperature, the outdoor fan tap speed is immediately raised to 4th speed and this
speed is retained for 60 seconds. 4th speed is made the upper limit and 1st speed is made the lower limit. Also,
sampling of the outdoor heat exchanger temperature is done at 60-second intervals and the outdoor unit fan
taps speed transitions are made immediately.
b) Control is cancelled when it is judged that the outdoor temperature is in the A-Zone and the outdoor fan tap is
running in 3rd speed or higher. Also, if it is running at 2nd speed and ends up in the A-Zone, if the outdoor heat
exchanger temperature is 48C or higher, this control is cancelled.
2) Outdoor unit fan tap control during heating
If the outdoor air temperature (sensed by Tho-A) is detected in the B-Zone for 5 minutes continuously, the outdoor
fan tap speed is increased by 2 speeds and thereafter, this may be repeated, but the upper limit is made 7th speed.
A-Zone
B-Zone
0
3) When the compressor is ON and the outdoor unit fan motors outputting, if the outdoor fan motors speed is 75 rpm
or lower for 30 seconds or longer, the compressor is stopped immediately. 3 minutes after the compressor is stopped,
if the thermostat ON conditions are satisfied, the compressor is started.
4) If the condition in item 3) is detected 5 times within 60 minutes after the first detection, an abnormal stop occurs
and an error message (E48) is displayed.
FDCA301~ 601 models
1) Outdoor fan tap control during cooling
The outdoor fan is controlled according to the outdoor heat exchanger temperature (sensed by Tho-R) and outdoor
C Zone
A-Zone
50
E Zone
B-Zone
22
39
25
B
UHi
Hi
Hi
43
55
Lo
87 -
A-Zone
D Zone
B-Zone
3
0
Outdoor heat exchanger temperature (C)
3
5
Outdoor air temperature (C)
Zone
C
D
B
Hi
Hi
UHi
ON
3
Defrosting
1) Defrosting start conditions
Defrosting operation starts when all the following conditions are satisfied.
a) If 45 minutes (35) (1) of cumulative compressor operating time have passed since defrosting ended and cumulative compressor operating time of 30 minutes have passed since heating operation started (Remote controller: ON)
b) If 5 minutes have passed since the compressor went ON.
c) 5 minutes of outdoor fan operation have
passed.
(f)
5
7
10
14
15
20
20 18
)
ard
nd
Sta
e(
tur
era
mp
Defrosting operation start
t te
r
temperature zone
sta
on
ati
per
go
stin
fro
De
15
10
88 -
5 6
10
L1 L2 L3 N
Wire connections
L3 L1 L2 N
L1 L2 L3 N
L2 L3 L1 N
(iii) Open-phase protection (FDCA 301~601 3-phase models only), Abnormal compressor winding
temperature
1) When the detected current on the secondary side of the 52C is 1.5 ~ 2 A or lower continuously for 4 seconds while the
compressor is ON, it is judged that there is an open-phase problem and the compressor is stopped. After a 3-minute
delay, the compressor is restarted, but if the problem occurs a second time within 60 minutes of the first detection, an
abnormal stop (E34) is performed.
2) When the temperature of the compressor windings is abnormal, and internal thermostat built into the compressor
operates. This is judged as an open-phase problem and results in an abnormal stop (E32). In single phase machines,
this is sensed by CT1.
Note (1) If the internal thermostat operates, it takes a long time to recover. Please do not mistake this as a defect in the compressor.
89 -
Retention
Release
151~251 models
301~601 models
80
90
90
100
105 (121)
b) If the abnormal discharge pipe temperature occurs 2 (5) times in 60 minutes, or continues at 105 (121C) or
higher for 60 minutes, including when the compressor is stopped, the unit performs an abnormal stop (E36).
Note (1) If the abnormal discharge pipe temperature continues for 45 minutes from the time it first occurs and does not drop below 80C,
the compressor cannot be operated again.. (It can be reset using the remote control unit.)
b) When the outdoor air temperature (sensed by Tho-A) is 17C or higher, the compressors speed is reduced and
the outdoor units fan motor tap is changed to 2nd speed, in order to raise the high pressure under the heating
overload conditions. Furthermore, the upper limit of the compressors speed during control is 60 rps.
2) Cooling
a) When the temperature at the outdoor heat exchanger (sensed by Tho-R) and the outdoor air temperature (sensed
by Tho-A) is 41C or higher after the compressor starts, the compressors speed is reduced and the outdoor
units fan motor tap is changed to high speed operation at 7th speed.
Item
Model
FDCVA151~251
b) If the outdoor heat exchanger temperature (sensed by Tho-R) is sensed 5 times in 60 minutes during compressor operation, or sensed continuously for 10 minutes, including when the compressor is stopped, an abnormal
stop is performed.
Item
Model
FDCVA151~251
90 -
FDCA301~601 models
1) Heating
a) After the compressor starts, the temperature at the indoor heat exchanger temperature (ThI-R) is checked,
and when all the following conditions are met, the electronic expansion valve (EEV) is controlled to control
the high pressure rise.
1 The indoor heat exchanger temperature (ThI-R) is 60 (56)C or higher while the compressor is running.
2 The electronic expansion valves (EEV) opening angle is 470 pulses or lower.
b) This control ends when the indoor heat exchanger temperature (ThI-R) becomes 57 (54) C or lower.
Note (1) Values in (
) show the setting when DIP switch SW 5-3 is ON. (It is normally OFF.)
2) Cooling
a) After the compressor starts, when all the following conditions are met, the electronic expansion valve
(EEV) is controlled to control the high pressure rise.
1 The outdoor heat exchanger temperature (Tho-R) is 58C or higher while the compressor is running.
2 The outdoor air temperature (Tho-A) is 41C or higher.
3 The outdoor fan motor runs continuously for 30 seconds or longer at the UHi tap.
4 The electronic expansion valves (EEV) opening angle is 470 pulses or lower.
b) This control ends when the temperature at the outdoor heat exchanger (Tho-R) becomes 53C or lower.
3) High pressure abnormal
a) Heating, cooling
1 If the high pressure switch (63H1) opens (4.15 MPa), the compressor stops (the outdoor units fan
motor stops after running for 30 seconds longer). After a 3-minute delay, when the high pressure switch
(63H1) is restored to the closed state (3.15 MPa), the compressor restarts. If the same condition occurs
5 times within 60 minutes after the first detection, an abnormal stop is performed and an error message
(E40) is displayed.
b) Cooling
1 If the outdoor heat exchanger temperature (sensed by Tho-R) is 65C or higher 5 times within 60
minutes while the compressor is operating, or if that temperature is detected continuously for 60 minutes, an abnormal stop is performed.
2 If the outdoor heat exchanger temperature becomes 48C or lower, it becomes possible to reset the unit
using the remote control unit.
(vii) Heating low outdoor temperature protection control (FDCVA 151~251 models only)
If a temperature of 10C is sensed at the heat exchanger (sensed by Tho-R) continuously for 1 minute during operation, the upper limit of the compressor speed is changed to 100 rps.
ON
OFF
-7
-10
Thermistor disconnection (discharge pipe, outdoor heat exchanger and outdoor temperature thermistor)
1) Outdoor heat exchanger temperature, outdoor air temperature thermistor
If the detected temperature is 30C or lower at the outdoor heat exchanger temperature thermistor and outdoor air
temperature thermistor continuously for 5 seconds during the interval from 2 minutes to 2 minutes 20 seconds after the
compressor goes ON, the compressor is stopped. After a 3-minute delay, the compressor is restarted, but in the case of the
151~251 models, if this condition is detected 3 times in a 40-minute period, or if it is detected again within a 60-minute
period in the case of the 301~601 models, an abnormal stop is performed.
Note (1) The temperature is not detected during defrosting or for 3 minutes after defrosting is ended.
91 -
(j)
Speed
FDCVA151, 201
FDCVA251
25
(k) Abnormal stop due to starting of the compressor (FDCVA 151~251 models only)
(a) If the compressors DC motors rotor position detection operation cannot be executed 5 seconds after compressor
starting conditions are established, it is switched to the stop state temporarily, then after 3 minutes the detection operation is executed.
(b) If the position detection operation cannot be executed the second time, compressor start is judged to be abnormal, and
an abnormal stop (E59) is performed.
(l) Compressor rotor lock trouble (FDCVA 151~251 models only)
If, within 4 seconds after changing to compressor rotor position detection operation, the rotors position cannot be detected a
second time, the compressor is stopped. After 3 minutes, the compressor recovers automatically, but if this condition recurs
4 times in a 15-minute period, an abnormal stop (E60) is performed.
(m) Insufficient refrigerant protection control
FDCVA 151~251 models
1 minute after the compressor is started in the case of cooling and dehumidification, and 9 minutes after in the case of heating,
the indoor heat exchanger temperature (sensed by Thi-R) and indoor return air temperature (sensed by Thi-A) are detected and
the compressor is stopped.
1) If the following conditions continue uninterrupted for 1 minute or longer
During cooling and dehumidification: The indoor heat exchanger temperature (Thi-R) is 4 degrees higher than the
indoor return air temperature (Thi-A).
During heating: The indoor heat exchanger temperature (Thi-R) is 4 degrees lower than the indoor return air tempera
ture (Thi-A).
2) If the controls in item 1) are implemented 3 times within 30 minutes, an abnormal stop is performed and an error message
is displayed (E57).
FDCA 301~601models
1) 3 minutes after the compressor starts in the case of cooling and dehumidification, and 4 minutes after in the case of heating,
the indoor heat exchanger temperature (sensed by Thi-R) and indoor return air temperature (sensed by Thi-A) are detected
and at the point when all the following conditions are satisfied, stop control is performed.
a) When the following conditions are detected continuously for 5 minutes or longer.
During cooling and dehumidification: The indoor heat exchanger temperature (Thi-R) is 4 degrees higher than the
indoor return air temperature (Thi-A).
During heating: The indoor heat exchanger temperature (Thi-R) is 6 degrees lower than the indoor return air
temperature (Thi-A).
b) If the controls in item a) are implemented 3 times within 30 minutes, an abnormal stop is performed and an error
message is displayed (E57).
2) If the compressor is starting for the first time after the power is turned ON, and abnormal stop is performed the first time
and an error message (E57) is displayed.
Note (1) A defrost operation or pump down control are excluded.
92 -
After pressing
continuously
for 1 second
ON
Cooling test operation
OFF
Heating test operation
Test operation is ended by pressing SW9 (SW2) during test operation.
SW5-4
The initial set temperature for heating (preparation) is 30C and the return air
Heating operation temperature is displayed in the return air temperature display.
93 -
APPLICATION DATA
SAFETY PRECAUTIONS
Please read these Safety Precautios first then accurately execute the installation work.
WARNING and
CAUTION , those
Though the precautionary points indicated herein are divided under two headings,
points which are related to the strong possibility of an installation done in error resulting in death or serious injury are listed
in the
WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed
in the
CAUTION section as well.
In either case, important safety related information is indicated, so by all means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain
operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owners manual.
Moreover, ask the customer to keep this sheet together with the owners manual.
WARNING
Installation should be performed by the dealer or a company speciallizing in this type of installarion. If you install the equipment
yourself, installation errors could result in water leaks, electric shock, and/or a fire, as well as other hazards.
Conduct installation work in accordance with the instructions in this installation manual. Installation errors could result in water leaks,
electric shock, or fire.
Sling the unit at the specified points with ropes property reted for the weight in liftting it for portage. An improper manner of portage can
result in a fail of the unit resulting in an accident invoiving personal death or injury.
When installing a unit in a small rooms, take measure so that if the refrigerant leaks, it does not exceed the concertration limit. For
information regarding measures to prevent the concertration limit from being exceed, please contact the dealer.
It refrigerant leaks and the concentration limit is exceeded, suffocation could occur.
Install the equipment in a location that can sufficiently support the weight of the equipment. If the area is not strong enough, an
accident could result from the unit falling.
Install the equipment in a location that can withstand strong winds, such as typhoons, and earthquakes. If the installation is not
secure, an accident could result from the unit falling.
Always turn off power before work is performed inside the unit such as for installation or servicing. A failure to observe this instruction
can cause a danger or electric shock.
Electrical work should be done by a licensed electrician who shall do the work in accordance with the Technical Standards Regarding Electrical Equipment. Indoor Wiring Provisions, and this installation manual. The electrician shall use specified circus for the
equipment. If the power supply circuit capacity is insuficient or the work is not done correcty, it could result in electric shock or a fire.
For wiring, the specified cable should be used, the connections should be secure, and the fixtures shall be strong enough to prevent
cabies from being pulted out from the terminal connections. Incorrect connections or work fixtures could result in heat generation or
a fire.
In cabling, arrange cables suitably so that they may not get off their support and then fix the service panel securely. Improper installation
can cause heat generation and a resultant fire. Please prevent any substance other than the specified refrigerant (R410A) such as air
from entering the refrigerant cycle in installing or moving the air conditioning system. Contamination by air or a foreign substance can
cause an abnormal pressure build-up inside the refrigerant cycle and a resultant explosion and personaly injury.
Use only parts supplied with the unit and specified supply parts for installation. The use of unauthorized parts may cause the leaking
of water or electricitly causing a danger of electric shock or a fire, a refrigerant leak, performance degradation, and control failures.
Do not open operation valves (either liquid or gas or both) until refrigerant piping, an air-tightness test and an air purge are completed.
When a leak of refrigerant gas occurs during piping work, stop brazing pipes and ventilate the room. Refrigerant gas, when it comes into
contact with bare fire, can generate a toxic gas.
When installation is completed, check for refrigerant gas leaks. If the refrigerant gas leaks indoors, it could come in contact with a tan
heater, burner, or hot plate, which could generate a poisonous gas.
CAUTION
Ground the equipment. Do not connect the ground wire to gas piping, water piping, a lightning rod, or telephone ground
wires. It grounding is not performed correctly electric shock could occur.
Depending on the installation location, a circuit breaker may need to be installed. It a circuit breaker is not installed, electric shock
may occur.
Please follow this manual faithfully in performing installation work. Improper installation work can cause abnormal vibrations and
noise generation.
Do not install the equipment in areas where there is danger of flammable gas leaks. It such gas does leak it could collect around the
units and cause a fire.
Install the drain piping in accordance with the installation manual so that it properly discharges waste water and is maintained at a
temperature that prevents condensation.
Do not install the outdoor unit where winds from its dan blow directly onto a plant, etc. Winds can affect adversely to the plant, etc.
Secure a space for inspection and maintenance as specified in the manual. An insufficient space can result in an accident such as
a fall from the installation point and a resultant personal injury.
When the outdoor unit is installed on a roof or at an elevated point, provide permanent ladders and handrails along the access route
and fences and handrails around the outdoor unit.
In tightening a flare nut, use a double spanner and observe the specified tightening torque. Care must be taken so as not to overtighten a nut and damage the flare part. (Please refer to the tightening torque) The loosening or damage of the flare part can cause
a refrigerant gas leak and a resultant lack-of-oxygen accident.
Please dress the refrigerant piping with a heat insulation material for prevention of dew condensation. Improper heat insulation for
prevention of dew condensation can cause the leaking or dripping of water and a resultant soaking of household effects.
When refrigerant piping is completed, check its air-tighteness with nitrogen gas to make sure it does not have a leak. A leak of
refrigerant gas in a narrow room beyond the safety limit concentration can cause a lack-of oxygen accident.
94 -
2500 or more
Fresh air
opening for
ducting
Control box
Hanging bolt
OA intake
420
637
Power intake
F
310
E
267
332
B
C
422
Drain hose
(Accessories)
(Local setting)
840
Model
b
270
Lug for
suspension bolts
187
35
45or more
95
137
FDT401
Control box
95 -
212
295
FDT501, 601
269
365
(c) Suspension
Please arrange four sets of a hanging bolt (M10 or M8), a nut matching the bolt, a flat washers and a spring washer on the
installation site.
When suspension from the ceiling
1) In the case of the standard series: Cut and openign of 860~890.
In cutting an operating on the ceiling, use the units cardboard container for shipment as a reference of the size of
opening.
The center of the opening on the ceiling must accord with the center of the unit.
2) Determine the positions of suspension bolts (675780).
3) Use four suspension bolts, each fastened in such a manner that it can withstand pull force of 50 kgf.
4) Make suspension bolts to the length that leaves approximately 70 mm of them above the ceiling.
5) After hoisting in the unit, attach level gauges supplied as accessories and determine the unit position (height).
Refrigerant piping
Main
body
33~38
Suspension
bolt
Drain
Nut
Washer
Spring
Washer
Ceiling
member Level gauge (insulation)
Level gauge
6) Use a transparent tube with water filled inside to check the level of the unit. (A tolerable height difference at an end of the
unit is within 3 mm)
Indoor unit
Hose
96 -
Improper piping
Avoid riding across an elevation
1.5 m ~ 2 m
Air vent
Heat
A downhill grade
insulation of 1/100 or more
700 mm or less
2) When connecting the drain pipe to unit, pay sufficient attention not to applay excess force to the piping on the unit side.
Also, fix the piping at a point as close as possible to the unit.
Stage
3) For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1)
difference Drain hose
Drain socket part
which can be purchased locally. When connecting, insert a PVC pipe
end securely into the drain socket before tightening securely using
VP25 joint
the attached drain hose and clamp. Adhesive must not be used conPipe cover (large) (field purchased)
[for insuation]
nection of the drain socket and drain hose (accessory).
(accessory)
4) When consturcting drain piping for several units, position the com- Indoor unit
mon pipe about 100 mm below the drain outlet of each unit as shown
Drain hose
VP25
in the sketch. Use VP-30(11/4) or thicker pipe for this purpes.
(accessory)
(field purchased)
Clamp
Adhesion
5) Be sure to provide heat insulation to hard PVC pipes of indoor place- Drain socket (accessory)
Pipe cover
[for insuation]
Pipe cover (small)
ment.
(field purchased)
[for insuation]
6) Do not ever provide an air vent.
(accessory)
7) The height of the drain head can be elevated up to a point 700 mm
Secure the elevation as high as possible
ablve the ceiling and, when an obstacle exisits in the ceiling space,
(approx. 100 mm)
elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the needed height is
too high, the back-flow quantity of drain at the event of interruption
A downhill grade of
VP30
of the operation gets too much and it may cause overflow at the drain
1/100 or more
pan. Therefore, make the height of the drain pipe within the distance
given in the sketeh below.
295 ~ 325 mm
100 mm or less
8) Avoid positioning the drain piping outlet at a place where generation
of odor may be stimulated. Do not lead the drain piping direct into a
Drain hose
sewer from where sulfur gas may generate.
9) The purpose of drain hose is to absorb minute discrepancy of the unit
or the drain piping occurred when they are installed. Therefore, when
it is bent intentionally or used under expanded condition, it may be
VP25 joint
(field purchased)
damaged and result in water leakage.
Drainage test
1 Check that water is draining thoroghly during test run, and that there are no water leaks from the joints and the drain pan.
2 The test has to be performed even if the unit is installed in the season when the unit is used for healting.
3 In a new house, perform the test before the ceiling is fitted.
Put the tip of the feed water pump
in the drain pan of the unit body
Using a water pump, pour about 1000 cc of water to the drain pan through
the blowing outlet.
Check the transparent drain-out section of the drain hose for normal flow
of drainage.
* While observing the noise from the drain motor, test drain operation.
Take off the drain plug to release the water. After the water is drained, place
the drain pulg back where it was..
* While observing the noise from the drain motor, test drain operation.
Drain plug
97 -
SELECT ITEM
TEST RUN
SET
TEST RUN
to be displayed.
3 When the SET button is pressed, a drain pump operation will start.
Display: DRAIN PUMP RUN
STOP
Quantity
Air filter
Suspension bolts
Remarks
10~25
33~38
Ceiling
member
3) Unit installation direction and panel and air inlet grille direction
(a)
(b)
The panel and air inlet grille installation orientation is not directional.
If you are changing the direction of the air inlet grille, change the panels striker installation position to the Pull
character position direction on the surface of the grille.
98 -
Screws
Corner panel
6) Panel installation
1 Screw in lightly 2 of the 4 air conditioner unit suspension bolts in opposite corners from each other by about 5 mm.
(Fasten the drain piping side and the opposite corner temporarily.)
2 Hang the panel on the two suspension bolts to install it temporarily.
3 Install the two remaining suspension bolts and tighten all four of the bolts.
Notes (1) : If the suspension bolts are not tightened sufficiently, it
could cause the following trouble, so tighten the bolts
securely.
Note (2) : If there is still a gap between the ceiling and the decorator
panel even after the suspension bolts are tightened, readjust
the height of the indoor unit.
Air leakage
Air leakage at ceiling
Dirt collects
Condensation forms,
condensation drips
Note (3) : The units installation height can be minutely adjusted with the decorator panel as is as long as the indoor unit is level and drain piping are
not affected.
99 -
1 2
trol box.
Note (1) : If the air outlet louver does not operate using
the remote controller, check the connectors
connection, then turn the main power supply
OFF for 10 seconds or longer and turn the
power ON again.
Drain plug
4
1 2
Striker
Refrigerant
piping
Air screen
Drain piping
Screw
Louver motor
Louver
L
L
<Setting Range>
Connector
Louver motor
Vertical air-flow
direction criterion
Horizontal 30
Downward 70
L Dimension (mm)
36.5
22.5
* It can be set anywhere desires as long as it is within a range of 22.5 and 36.5 mm.
Note (1) : Do not set the position outside this range.
Doing so causes condensate to drip and to form as well as dirtying of the ceiling surface, and could cause abnormal operation.
100 -
Pin
Pin
A
a
Screw
Claws
101 -
Unit : m
Models
FDE151, 201
FDE251, 301
Air throw
7.5
Conditions
(1) Installation height: 2.4 ~ 3.0 m above the floor
(2) Fan speed: Hi
(3) Location: Free space without obstacles
(4) Distance of reach indicates the horizontal distance after the wind touched down the floor.
(5) Air velocity at the throw: 0.5 ( m/sec.)
2) A place where ceiling has enough strength to support the unit.
3) A place where there is no obstruction to the return air inlet and supply air outlet ports.
4) Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or
damage in molded synthetic resin parts.
5) A place where the space shown below may be secured.
Ceiling mouting installation
Unit : mm
300 or more
100 or more
150 or more
5 or more
Obstacle
6) This unit uses a microcomputer as a control device. Therefore avoid installing the unit near the equipment that generates
strong electromagnetic waves and noise.
(b) Installation preparation
1) Remove the air inlet grille.
Slide the stoppers (4 places).
Filter
Pin
Side panel
102 -
Suspension
lug screws (M4)
Loosening
margin
8~12 mm
Indoor unit
Suspension
lug mounting
bolt (M8)
Lug for
suspension
Lug for
suspension
Paper
pattern
A
B
24
Air outlet
B
1022
FDE251, 301
1320
1272
1572
290
1070
215
FDE151, 201
Lug for
suspension
Suspension
bolts
Model
690
25mm or more
45mm or less
Unit : mm
Celing board
24
Wall
(c) Installation
1) Fasten the suspension lugs to the suspension bolts.
<If there is ceiling material>
Air outlet
Suspension bolts
Suspension bolts
Lug for suspension
Nut
Flat washer
Ceiling board
Unit
Flat washer
(accessory parts)
Unit
Flat washer
(accessory parts)
*Double nuts
*Double nuts
Lug for suspension
*Fasten it securely with double nuts.
Lug for
suspension
Lug for
suspension
(M4)
Suspension bolts
(M8)
After sliding the side panels on from the front to rear, fasten them securely with the screws.
103 -
3) IN order to make it easier for water to drain out. install the unit so that the water drain side slopes
downward.
Front-rear direction
Left-right direction
0 ~ 3mm
0 ~ 3mm
53
Slope inside
unit: 10 mm
271
109
53
Liquid pipe
10
Unit : mm
Drain piping
(left)
110
76
Drain piping
(right)
Unit : mm
Top Cover
Drain piping
(For left back)
17
60
100
Back cutout
27
27 108
19
Top cutout
Right side
cutout
60
31
120
Drain piping
(For left)
47
60
Back cover
Cutting margin
104 -
WARNING
Use the fitting supplied with the unit to connect the drain hose, fastening it at the lowest point so that there is no slack, and
establishing a 10 mm drain slope. * Keep electrical wiring from running beneath the drain hose.
Drain hose
10mm
Drain hose
Hose Clamp
It can be fastened
from inside or
outside the unit.
Lowest Point
After piping has been installed, check to make sure water drains well and that there is no overflow.
(3) Wall mounted type (FDK)
(a) Selection of installation location
40
or more
Unit: mm
100 or more
50 or more
1) Select the installation location that meets the following conditions and obtain
the customer's consent.
a) Location where cold and warm air spread all over the room
b) Location where piping and wiring to the outdoors can easily be laid down.
c) Location where the drain can be discharged completely.
d) Location where the wall to mount the unit is rigid.
e) Location where there is no wind obstruction to the return air and supply air
grills.
f) Location not exposed to direct sunshine.
g) Avoid the location exposed to oil splash or vapor.
h) Avoid the location near to the machine emitting high-frequency radio wave.
i) Avoid the location where the receiver of remote control is subject to strong
illumination.
j) Select the location where the unit can securely be operated by the wireless
remote controller referring to the Article Effective distance of wireless remote controller indicated at the backside.
k) Secure the space for inspection and maintenance work.
Floor
2m
1m
W
ith
in
With
in With
30
30
Within 60
Within 5 m
Illumination over suction grill-800 lus.
105 -
in
(Plan view)
3m
5m
5m
5m
ux
0l
72
ux
0l
36
Effective scope
Effective scope
7.5 m
ux
0l
18
60
60
60
Leveling Plates
3) Adjust the level of mounting plate under the condition that four screws are tightened temporarily.
Reference hole
4) Turn the mounting plate around the reference hole to adjust the levelness.
WARNING
Install the unit where it can bear the weight with sufficient strength margin. In the case of insufficient strength or insufficient
installation work, the unit may fall and cause injury.
(d) Procedure for making hole on the wall
Make a downgrade (5) from the indoors toward the outdoors.
Wall
Sealing plate
The indoors
Wall
The outdoors
Sleeve
65mm
Sleeve
b) Tape winding
Drain hose
Note (1) After forming of piping and before tape winding, confirm that the connecting wire is securely fixed to the terminal block.
106 -
Right
For left running horizontal piping
Rear
Left
Down
Left rear
Down (1)
(f)
Installation of unit
Claw (2 places)
(FDKN301 : 3 places)
Indoor unit
Mounting plate
(1) Hang the upper portion of indoor unit on the mounting plate.
No trap is allowed.
107 -
27.5
12.4
16.4
2) Select places for installation satisfying the following conditions and, at the same time, obtain the consent on the part of
your client user,.
a) Places where chilled or heated air circulates freely. When the installation height exceeds 3m, warmed air stays close
to the ceiling. In such cases, suggest your client users to install air circulators.
b) Places where perfect drainage can be prepared and sufficient drainage gradient is available.
c) Places free from air disturbances to the return air port and supply hole of the indoor unit, places where the fire alarm
may not malfunction to short circuit.
d) Places with the environmental dew-point temperature is lower than 28C and the relative humidity is less than 80%.
( When installing at a place under a high humidity environment, pay sufficient attention to prevention of dewing such
as thermally insulating the unit properly.)
3) Check if the selected place for installation is rigid enough to stand the weight of thew unit.
Otherwise, apply reinforcement using boards and beams before starting the installation work.
600
635
Inspection hole
Unit : mm
Models
Mark
1720
100
1200
(b) Suspension
Be sure to observe the finished length of the suspension bolts given below.
Unit : mm
560
Models
Mark
108 -
886
1406
Insert
Concrete
Suspension bolt M10
Suspension bolt
M10 nuts
M10 Washer
Indoor unit
60mm or less
Indoor unit
Wood base
When installing the unit, heed must be taken that the side touching
the wood frame is the top surface of the unit.
hanger bolts.
Note
When the dimensions of indoor unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging
bracket.
1) Adjusting the units levelness
a) Adjust the out-levelness using a level vial or by the following method.
Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose
becomes given below.
Piping side
Supply water
Water level
0 ~ 5 mm
PVC hose
b) Unless the levelness is adjusted properly, the malfunction of the float switch will occur.
2) Blower fan switching.
To effect the same setting with SW9-4 ON (fan control high tap) from the remote controller. Set to Hi CEILING 1.
Unit : Pa
Static Pressure
Standard tap
High tap
FDUR201,251
50
85
FDUR301,401,501,601
50
130
Models
109 -
CAUTION
Taps should not be used under static pressure outside the unit mentioned above. Dew
condensation may occur with the unit and wet the ceiling or furniture.
Do not use under static pressure outside the unit of 50Pa or less. Water drops may be blown
from the diffuser outlet of the unit and wet the ceiling or furniture.
(d) Drain piping
1) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or makeing traps.
Improper piping
Good piping
Suspension
bolts
1.5 m ~ 2m
Air vent
Heat
insulation
A downhill grade
of 1/100 or more
2) When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side.
Also, fix the piping at a point as close as possible to the unit.
Level difference part
3) For drain pipe, use hard PVC general purpose pipe VP-25 which can be purDrain socket
Drain hose
chased locally. When connecting, insert a PVC pipe end securely into the drain
socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose ( accessory).
Pipe cover (large)[insulation]
(accessory)
Indoor
unit
VP-25
(local procurement)
Drain hose
Clamp
Drain socket
(accessory) (accessory)
Pipe cover [insulation]
Pipe cover (small)[insulation]
Adhesion (local procurement)
(accessory)
4) When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each
unit as shown in the sketch below. Use VP-30 or thicher pipe for this purpose.
Secure the elevation as high as possible
(approx. 100 mm)
A downhill grade of
1/100 or more
VP30
600
Drain hose
Maximum local
drain up dimension
295 ~ 325
Right overhead
110 -
8) Avoid positioning the drain piping outlet at a place where generation of odor may stimulated. Do not lead the drain piping
direct into a sewer from where sulfur gas may generate.
9) Drainage test
a) Conduct a drainage test after completion of the electrical work.
b) During the trial, make sure that drain flows properly through the piping and that no water leaks from connections.
c) In case of a new building, conduct the test before it is furnished with the ceiling.
d) Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
1 Supply about 1000 cc of water to the unit through ghe air outlet by using a feed water pump.
2 Check the drain while cooling operation.
Attached drain hose clamp
Insert water supply hose for
20mm ~ 30mm to suply water.
(Insert hose facing toward bottom.)
Indoor unit
Remove grommet
Make sure to install
it back after test.
Connection of pipes
(Removing drain motor connector) Remove
drain motor connector CNP (blue) as shown
in the drawing on the nght. (Note: If the
connector is left connected, drain water is
discharged from the conncting port of top
pipes, causing leakage.)
Insulating material
Remove
Drain motor connector
CNR 2P Blue
111 -
STOP
2. To cancel a drain pump operation.
4 If either SET or ON/OFF button is pressed, a forced drain pump operation will stop.
The air conditioning system will become OFF.
(e) Duct work
to be displayed.
Air conditioner
iundoor unit
Ceiling surface
Suction grille
Suction grille (Locality)
(option)
3 Suction duct
(marketed item)
Ceiling surface
4 Blow outlet
5 Inspection hole
(option) 2 Blowout duct
(optional or marketed item)
1 Suction hole
(marketed item)
(with air fillter)
1) A corrugated board (for preventing sputtering) is attached to the main body of the air conditioner (on the outlet port). Do
not remove it until connecting the duct.
a) An air filter is provided on the main body of the air conditioner (on the inlet port). Remove it when connecting the
duct on the inlet port.
2) Blowout duct
a) Reduce the length of duct as much as possible.
b) Reduce the number of bends as much as possible.
c) (Corner R should be as larger as possible.)
Bad example
3)
4)
5)
6)
Bad example
Good example
112 -
Louver to
outdoor air
For ventilation
(f)
7) If a duct is not provided at the suction side but it is substituted with the space over the ceiling, humidity in the space will
increase by the influence of capacity of ventilation fan, strength of wind blowing against the out door air louver, weather
(rainy day) and others.
a) Moisture in air is likely to condense over the external plates of the unit and to drip on the ceiling.
Unit should be operated under the conditions as listed in the above table and within the limitation of wind volume.
When the building is a concrete structure, especially immediately after the construction, humidity tends to rise even
if the space over the ceiling is not substituted in place of a duct.
In such occasion, it is necessary to insulate the entire unit with glass wool (25mm). (Use a wire net or equivalent to
hold the glass wool in place.)
b) It may run out the allowable limit of unit operation (Example: When outdoor air temperature is 35C DB, suction air
temperature is 27C WB) and it could result in such troubles as compressor overload, etc..
c) There is a possibillty that the blow air volume may exceed the allowable range of operation due to the capacity of
ventilation fan or strength of wind blowing against external air louver so that drainage from be heat exchanger may
fail to reach the drain pan but leak outside (e. g. drip on to the ceiling) with consequential water leakage in the room.
Control box (Only case of FDURA401, 501, 601)
During bottom side suction, the orientation of the control box can be changed to allow the control box to be maintained
from the inlet port.
1) Remove the bottom plate (on the inlet port side),
and all wiring connectors from the control box.
2) Remove the three screws that fasten the cabinet inside the
control box.
3) Pull the control box toward the outside of the unit.
4) Change the ejection of the wiring inside the control box.
5) Fit the control box from the inside of the unit.
6) Fit the three screws that fasten the cabinet.
7) Correctly connect all wiring connectors.
113 -
Remote
controller cord
Electrical box
Not included
Upper
Lower case
Put a screw driver (flat-head) into the concavity made on the upper part of a remote controller unit and twist it lightly to open the casing.
2) The cord of a remote controller unit can only
be pulled out in the upward direction.
Cable outlet
Lower
Upper
Cut off with a knife or the like thin walled parts
intended for screw holes, and then fix it with
screws.
Lower
Lower case
Cable outlet
Lower
Lower case
Lower
4) Connect the remote controller to the terminal block. Connect the terminals of the remote controller to the indoor unit with the
same numbers. Because the terminal block
has polarity, the device becomes inoperative
if there are wrong connections.
Two M4 screws
(Head diameter must be 8mm)
(not included)
Upper
Upper case
Board
Lower
Wiring
Note (1) Use cables up to 0.5mm2 (maximum) for those laid inside
the remote controller unit casing and connect to a different
size cable at a vicinity point outside the remote controller
unit, if necessary.
100.Within 100-200m0.55 mm2 3 cores
Within 300m0.75 mm2 3 cores
Within 400m1.25 mm2 3 cores
Within 600m2.05 mm2 3 cores
Length of the
section where a
sheath is removed
Earth
Indoor unit
114 -
a
b
c
d
e
f
g
h
(1) Installation
(a) Accessories (only case of FDCA301~601 models)
Confirm accessories shown below are attached in the bag with this installation manual.
1) Edging for protection of electric wires from opening edge.
(b) Selection of installation location
Select the installation location after obtaining the approval of customer.
1) The place where the foundation can bear the weight of Outdoor unit.
2) The place where there is no concern about leakage of combustible gas.
3) The place where it is not stuffy.
4) The place where free from thermal radiation of other thermal source.
5) The place where flow of drain is allowed.
6) The place where noise and hot air blast do not trouble neighboring houses.
7) When the unit is installed at the particular location as shown below, corrosion or failure may be caused. Please consult
the dealer from which you purchased the air-conditioner.
a) The place where corrosive gas is generated (hot spring, etc.).
b) The place where wind containing salt blows (seaside area).
c) The place where enveloped by oil mist.
d) The place where there is a machine that radiates electromagnetic wave.
Restrict the height of obstruction wall in front of the discharge air port to the height of unit or less.
Do not enclose around the unit by the obstruction. Secure the top space for 1 m or more.
When installing the units side by side in series, secure a space of 10 mm between units.
When installing the unit where there is a concern about the short circuit, attach the guide louver in front of
discharge air port to prevent the short circuit.
When installing plural units in a group, secure sufficient intake space to prevent the short circuit.
When installing the unit where it is covered by snow, provide appropriate snow break means.
(c) The minimum space for installation
Select the space considering the direction of refrigerant piping.
Request
Unit : mm
Installation FDCVA151, 201, 251
example
Air inlet
Distance
Open
space
L1
Air
inlet
Air outlet
(Service space)
FDCA301
280
280
Open
space
Open
space
500
Open
space
Open
space
500
L2
100
75
Open
space
300
Open
space
300
Open
space
L3
100
80
80
100
150
100
150
300
150
250
Open
space
250
L4
115 -
Where the unit is likely to be subjected to strong winds, guard it from winds with the following measures.
A failure to give protection against winds may cause performance degradation, a rise of high pressure resulting is an
operation interruption, a broken fan, etc.
3) Where the foundation is not stable,
1) Install the unit directing the dis- 2) Install the unit directing the discharge air port to the wall.
500
or
mo
re
Carry-in
Protection plate
1) When carrying-in the unit, carry it in as packed condition to the installation site as near as
possible.
2) If you are compelled to carry-in the unit unpacked condition, lift the unit by the rope
Wood base
using a nylon sling or applying protection plates so that the unit is not marred.
CAUTION Rope the unit taking the discrepancy of center of gravity into consideration.
(b) Moving
Heavier on
the right side
1) The unit is heavier on the right side looking from the front of unit (air
Conner
pillar
outlet port side). Therefore, sufficient caution is required for the person
who carries the right side of unit. The person who carries the left side
must hold the handle of front panle and the conner pillar with both
hands.
(c)
Air inlet
Item
Model
FDCVA151, 201, 251
106
164
312.5
510
14
13.5
150
150
380
580
20
20
FDCA401
Anchor bolt position
(4 places)
FDCA301
Air outlet
165
175
380
580
20
20
FDCA501, 601
190
200
410
580
20
20
1) To install the unit, secure the legs of unit by below mentioned bolts without fail.
Secure with bolts.
(M10 to 12)
Bury the foundation deeper
into the ground.
Make the foundation wider.
2) Limit the protrusion height of front side anchor bolts to 15 mm at the maximum.
3) Install the unit firmly so that it does not fall by earthquake and strong wind.
4) Make the concrete foundation by referring the above illustration.
5) Install the unit in level. (The height difference between right and left is within 5 mm.)
116 -
Outdoor unit
Unit : mm
Gas pipe
12.7 t0.8
15.88 t1.0
15.88 t1.0
Liquid pipe
6.35 t0.8
6.35 t0.8
9.52 t0.8
117 -
Internal hook
Fixing screw
Service panel
Screw for earth
Note (1) Piping can be run toward the back only of the FDCVA151~251 models.
Vacuuming completed
Vacuuming begins
When the vacuum gauge's needle pointer creeps up, there is moisture left in the system
or a leak. Pull air again after you have checked the system for a leak and rectified it. Use
a reverse flow stop adapter to prevent the vacuum pump's lubricant oil from flowing into
the refrigerant system.
When a vacuum air purge is completed, remove the valve rod cap nuts and open the service valves (both liquid and gas sides)
as illustrated below. After you have made sure that the valves are in the full-open position, lighten the cap nuts (for the valve
rads and charge ports).
118 -
Pressure gauge
Gauge manifold
(for R410A only)
Handle Hi
-101KPa (-755mmHg)
Handle Lo
Charge hose (for R410A only)
Charge hose
(for R410A only)
Open
Charge valve
Vacuum adapter
(for R410A only)
Charge port
Liquid/gas operation
Vacuum
pump
You can purge air with either liquid operation valve or gas
operation valve.
Pin
Factory setting
(close)
Open
(Example) If the FDCA301 model is newly installed and the piping length is 45 m.
Additional Charge Amount: 0.60 kg = (45 30) m 040.0 kg/m
(c) If the system is recharged during servicing, etc., recharge in accordance with the following.
1) Models 151, 201, 251
If the piping length is 15 m or less, recharge the system with the standard charge in the above table. If the piping length
is greater than 15 m, charge with the standard charge plus an additional charge amount corresponding to the length of
piping that exceeds 15 m.
(Example) If the model FDCVA151, with a piping length of 40 m is being recharged:
Recharge Amount: 1.75 kg = 1.25 kg + (40 15) m 020.0 kg/m
2) Models 301~ 601
If the piping length is 30 m or less, recharge the system with the standard charge in the above table. If the piping length
is greater than 30 m, charge with the factory charge amount plus an additional charge amount corresponding to the length
of piping that exceeds 30 m.
(Example) If the model FDCA601, with a piping length of 50 m is being recharged:
Recharge Amount: 4.7 kg = 3.9 kg + (50 30) m 040.0 kg/m
(6) Drain piping work
Execute drain piping by using a drain elbow and drain grommets supplied separately as optional parts, where water drained
from the outdoor units is a problem.
There are 3 (FDCVA 151~251: 5) drain holes provided on the bottom plate of an outdoor unit to discharge condensed water.
When condensed water needs to be led to a drain, etc., install the unit on a flat base (supplied separately as an optional part)
or concrete blocks.
Connect a drain elbow as shown in the illustration and close the other two drain holes with grommets.
119 -
Models FDCVA151~251
Models FDCA301~601
Drain grommet
(2 pcs.)
(local procurement)
OIMPORTANT
Electric wiring work should be conducted only by authorized personnel.
Use copper conductor only.
Power source wires and Interconnecting wires shall not be lighter than polychloroprene
sheathed flexible cord (design HO5RN-F IEC 57).
Do not connect more than three wires to the terminal block.
Use round type crimped terminal lugs with insulated grip on the end of the wires.
Select wire sizes and circuit protection from Table 2.
Table 2
Item
Phase
Earth leakage
breaker
Model
FDCVA151HEN
FDCVA201HEN
FDCVA251HEN
FDCA301HEN
FDCA301HES
FDCA401HEN
FDCA401HES
FDCA501HES
FDCA601HES
(b)
Over-current protector
rated capacity (A)
Power source
wires
(minimum)
15
15A, 30mA,
0.1 sec or less
3
1
Circuit breaker
2.0mm2
20
15
40
15
Switch breaker
(A)
3.5mm2
2.0mm2
5.5mm2
Interconnecting
and grounding
wires (minimum)
30
40
30
20
1.6
3.5mm2
Wiring connection.
1) Connect the same terminal number between the Indoor unit and Outdoor unit as shown in the following diagram.
2) Secure the wiring with wiring clamp so that no external force is transmitted to the connecting portion of terminal.
3) There is a ground (Earth) terminal in the control box.
(a)
(b)
1 phase model
Circuit breaker
Outdoor
unit
TB
L
N
1
2/N
3
Earth leakage
breaker
HIGH VOLTAGE
Indoor
unit
3 phase model
Circuit breaker
Outdoor
unit
TB
L1
L2
L3
N
TB
1
2
3
Earth leakage
breaker
HIGH VOLTAGE
1
2/N
3
Interconnecting
wires
Interconnecting
wires
120 -
Indoor
unit
TB
1
2
3
Indoor unit
Remote SW1
controller M
Remote SW1
controller S
b) Set the SW1 select switch on the slave remote controller on the Slave setting. (It is set on the Master setting at the
factory.)
Note (1) Remote controller sensor activation settings are possible only with the master remote controller. Install the master remote controller in a
location where it can sense the room temperature.
Upper
Function
Switch
M
SW1
S
SW2
SW1
PCB
SW1
Lower
b) Set the remote controller communications address on 0 ~ F using rotary switch SW2 on the indoor units
control board, taking care not to overlap the addresses of any of the units.
Black
White
Red
(c)
Remote controller
c) After turning the power on, press the AIR CON No. button to display the indoor units address. Be sure to confirm
that the settings are displayed correctly in the remote controller by using the
and
buttons to display the
address of each connected indoor unit.
121 -
Function description B
FUNCTION
Factory
setting
Setting C
Function description B
Setting C
INVALID
01
GRILLE
Grille lift
SET panel setting
Hi CEILING SET
ON/OFF
04
INVALID
FANSPEED S/W
08
Heating
FAN CONTROL fan control
VALID
TIMER S/W
INVALID
09
10
SENSOR ON (Valid)
VALID
VENTI SET
DISP CHARGE
Indoor unit
I/U FA SPEED fan speed setting
NO DISP CHARGE
3 FAN SPEED
2 FAN SPEED
1 FAN SPEED
HEAT PUMP
MODEL TYPE
COOLING ONLY
15
16
INDIVIDUAL OPERATION
SAME OPERATION FOR ALL UNITS
ERROR DISP
NO ERROR DISP
VALID
NORMAL OPERATION
TEMP SHIFT +3C
LOW FAN
STOPLOW FAN (Intermittent operation)
TEMP Lo
FAN CONTROL OFF
13
NORMAL OPERATION
FAN CONTROL ON
INVALID
POWER FAILURE
COMPENSATION SET
PULSE INPUT
TEMP Hi
Remote control
SENSOR S/W
sensor setting
C/F SET
OPERATION PERMISSION
PROHIBITED
07
INVALID
18
06
VALID
LOUVER S/W
LEVEL INPUT
INVALID
12
17
05
VALID
VALID
ON/OFF
1000HSTOP
INVALID
Louver
POSITION
control setting
AFTER 600H
INVALID
VALID
NO VENTI LINK
14
AFTER 1000H
NO VENTI
11
03
VALID
MODE S/W
AFTER 180H
TEMP S/W
Factory
setting
NO DISPLAY
AUTO RUN ON
122 -
Function number: A
Confirm Button
SELECT ITEM
SET"
ON/OFF Button
FUNCTION SET
FUNCTION SET
Start Button
Selector button
FUNCTION
.
4) Check which category your desired setting belongs to,
FUNCTION
FUNCTION
5) Press either
Select either
button.
FUNCTION
or I/U FUNCTION
FUNCTION
I/U FUNCTION
When
is selected.
FUNCTION
or
button.
Function number: A, Function description: B from the list of remote controller unit functions will be displayed one
by one. Select a desired function.
3 Press the SET button.
The screen display will be switched as follows:
SETTING
4 Press either
or
A list of Settings: C will be displayed one by one. Select your desired setting.
5 Press the SET button.
The selected setting is displayed
* When
Function description: B
AUTO RUN ON
Setting: C
AUTO RUN ON
SET COMPLETE
123 -
I/U No.00
or
button.
2 Press either
Select the indoor unit number that you want to change settings. If only one indoor unit is connected, the indoor unit
number will not charge, so please proceed to Step 3.
If ALL I/U
is selected while indoor group control is in effect, you can set all units to the same settings.
3 Press the SET button.
Indoor unit number indication will change from blinking to lit continuously, The screen display will be switched as
follows:
"DATA LOADING" (blinking for about 2 to 23 seconds)
FUNCTION
Hi CEILING SET
(Function number: A, Function description: B)
* When
Hi CEILING SET
Function description: B
4 Press either
or
button.
Function number: A, Function description: B from the list of indoor unit functions will be displayed one by one.
Select a desired function.
5 Press the SET button.
The screen display will be switched as follows:
SETTING
Setting: C (ex. STANDARD)
STANDARD
Settings: C
6 Press either
or
button.
A list Setting: C will be displayed one by one. Select your desired setting.
7 Press the SET button.
The selected setting is displayed for 2 seconds, then followed by SET COMPLETE and the function setting process is
completed.
Then the screen display will be switched to Function number: A, Function description: B so if you want to continue to set
another function, repeat the stepa as explained above. To finish the function setting process, please proceed to Step 8.
8 Press AIR CON No. button.
The screen display will go back to the indoor unit selection screen (ex. I/U No.00).
If you want to continue to set another indoor unit, please follow the steps explained above.
(c) Press the ON/OFF button.
This ends a function setting process. Even if a function setting process is not completed, this ends the process.
Please note that any setting that is not complated will become void.
Pressing the RESET button during a function setting process will allow you to go back the previous
step. Please note that any setting that is not completed will become void.
Method of checking the current setting
While following the above mentioned step, the setting that appears when the SET button is pressed for each Function
number: A, Function description: B is the current setting Stting: C. (When "ALL I/U " is selected, the setting of
the indoor unit with the lowest number is displayed)
Settings are stored in the controller and not lost even a power outage occurs.
124 -
SELECT ITEM
SET
FUNCTION SET
b) Press the
button once. The display will change to TEMP RANGE
.
c) Press the SET button to enter the temperature range setting mode.
or Lo LIMIT SET
d) Using the
or
button, select Hi LIMIT SET
, the press the SET button.
e) If Hi LIMIT SET is selected,
1 The display changes from
SET UP
Hi LIMIT 22C
(flashing).
2 Using the
button, select the upper limit value. Display example: Hi LIMIT 22C
(flashing)
3 Press the SET button to fix the setting. Display example: Hi LIMIT 22C (lighted up)
f) If Lo LIMIT SET is selected,
1 The display changes from
SET UP
Lo LIMIT 26C
(flashing).
2 Using the
button, select the upper limit value. Display example: Lo LIMIT 26C
(flashing)
3 Press the SET button to fix the setting. Display example: Lo LIMIT 26C (lighted up)
g) Press the ON/OFF button to end the setting procedure.
(The procedure also ends if the ON/OFF button is pressed during the setting operation. However, settings which have
not been fixed become invalid, so exercise caution.)
If the RESET button is pressed during a setting operation, the display returns to the previously displayed setting screen.
However, settings which have not been fixed become invalid, so exercise caution.
* If NO DISP CHANGE is selected in No. 12, TEMP RANGE SET of the remote controllers functions, No. 1 of
the function setting modes, the remote controllers display does not change even if the temperature range has been
changed.
(Example) If the upper limit is set at 28C
Function No. A
Setting Contents C
Control Contents
DISP CHANGE
12
Function Contents B
NO DISP CHANGE
125 -
TEST RUN
SELECT ITEM
SET"
TEST RUN
is displayed, press the SET button to begin the cooling test operation. The display shows
TEST RUN.
(b) Canceling the Cooling Test Operation
Pressing the ON/OFF button or the
The
SELECT ITEM
SET"
01
DATA ITEM
Operation mode
02
Temperature setting
Number
.
is displayed, pres the SET button.
(flashing).
03
Intake temperature
04
display.
05
(When there is only one indoor unit connected, the indoor unit No. does not
07
change.)
11
21
22
23
24
Operation Hz
26
Low pressure
27
28
29
CT current
31
32
33
63H2 ON/OFF
34
63H1 ON/OFF
35
Defrost ON/OFF
36
37
38
Using the
or
OPERATION DATA
5 Display the other data in order from the currently displayed operation data No.
01 by using the
or
button.
6 To change the indoor unit, press the AIR CON No. button and return to the
indoor unit selection display.
7 Press the ON/OFF button to end the data check.
If the RESET button is pressed during the setting operation, the screen returns to the previous setting screen.
126 -
Cooling
Heating
127 -
MAINTENANCE DATA
6.1 Servicing
(1) Evacuation
The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigerant equipment by
using a vacuum pump. Since the refrigerant R410A is very insoluble in water, even a small amount of moisture left in the refrigerant equipment will freeze, causing what is called ice clogging.
Evacuation procedure
Make sure that the both service valves of gas and liquid line are fully opened.
(a)
Indoor unit
Check to ensure that there is no internal pressure in the unit. If there is an internal pressure, it should be relived through the service
port.
(b)
Gus line
Outdoor unit
Liquid line
Gauge manifold
(for R410A only)
No increase in the
reading of the
vacuum gauge's
needle pointer.
Handle Hi
Charge hose A
(for R410A only)
Handle Lo
Vacuuming completed
(c)
Charge hose
(for R410A only)
Charge valve
Vacuum adapter
(for R410A only)
Vacuum
pump
3
Refrigerant
cylinder
Notes (1) Refer to the exterior-view drawing for the position of the service valve.
Notes (2) When connecting of ther service valve, flare connection for both the
indoor and outdoor unit.
128 -
After the evacuation shown in the above, change the connection of the charge hose A to the refrigerant cylinder.
(b)
(c)
Open valves 1 and 3 then gas refrigerant begins flowing from the cylinder into the unit.
When refrigerant has been charged into the unit to some extent, refrigerant flow becomes stagnant. When that happens, start
the compressor in cooling cycle until the system is filled with the specified amount of gas, then close valves 1 and 3 and
remove the gauge manifold. Cover the service port with caps and tighten them securely.
(d)
Check for gas leakage by applying a gas leak detector around the piping connection.
(e)
Start the air conditioner and make sure of its operating condition.
High side
Low side
High side
Low side
Trouble cause
Too high
A little
high
Normal
A little low
Circuit
High side
Low side
High side
Low side
High side
Low side
Too low
Pressure
Indication
129 -
6.3
Cause
Green
Red
Green
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
Normal
Stays OFF
Keeps flashing
Stays OFF
Stays OFF
Stays OFF
Keeps flashing
Stays OFF
Stays OFF
Keeps flashing
*3 time flash
Keeps flashing
Stays OFF
Remote controller wires X and Y are reversely connected. *For wire breaking at
power ON, the LED is OFF. Remote controller wire is open. (X wire breaking : A
beep is produced and no indication is made. Z wire breaking : No beep and no
indication) The remote controller wires Y and Z are reversely connected.
Keeps flashing
Stays OFF
Keeps flashing
2 time flash
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
When multiple remote controllers are used for control, the power supply to some
indoor units is OFF.
Stay OFF
Keeps flashing
Stays OFF
Keeps flashing
Stay OFF
Keeps flashing
Stays OFF
The remote controller wire Y is open. The remote controller wires X and Y are
reversely connected. Noise is penetrating the remote control lines. The remote
controller or indoor control PCB is faulty. (The communications circuit is faulty.)
Keeps flashing
2 time flash
Keeps flashing
2 time flash
Keeps flashing
2 time flash
Stays OFF
Stays OFF
Keeps flashing
2 time flash
Keeps flashing
Stays OFF
E6
E7
Keeps flashing
Keeps flashing
1 time flash
1 time flash
Keeps flashing
Keeps flashing
Stays OFF
Stays OFF
E8
Keeps flashing
1 time flash
Keeps flashing
Stays OFF
E9
Keeps flashing
1 time flash
Keeps flashing
Stays OFF
E10
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
E16
E28
Keeps flashing
Keeps flashing
Stays OFF
Stays OFF
Keeps flashing
Keeps flashing
Stays OFF
Stays OFF
No-indication
LCD flashes
continuously
or is off.
130 -
E1
E5
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Red
Green
Red
Green
Red
E32
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E33
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
Cause
Wiring is open or reversal phase (FDCA 301~601 type)
Inverter primary side current is abnormal. (FDCVA151~251 type)
Abnormal current cut of compressor (FDCA 301~601 type)
E34
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E35
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E36
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E37
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E38
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E39
131 -
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E40
Keeps flashing
Stays OFF
Keeps flashing
1 time flash
E42
Keeps flashing
Stays OFF
1 time flash
E47
Keeps flashing
Stays OFF
1 time flash
E48
Keeps flashing
Stays OFF
1 time flash
E52
Keeps flashing
Stays OFF
E56
Keeps flashing
Stays OFF
E57
Keeps flashing
Stays OFF
Keeps flashing
Lights contiously
1 time flash
Keeps flashing
1 time flash
Insufficient refrigerant.
1 time flash
E59
Keeps flashing
Stays OFF
2 time flash
3 time flash
E60
Keeps flashing
Stays OFF
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
1 time flash
Display section
Displays the error of higher priority (When plural errors are persisting)
Error code
Wait
After 1 or more communications of the indoor unit with the remote controller
following power on, transmission errors cause an interruption for 2 minutes.
Error code
132 -
Memory
Reset
Notes
(1) Priority is in the order of E1 > ... > E10 > ... > E60.
Indoor unit
: Press the ON/OFF button on the remote controller. Or disconnect and reconnect the power supply connector
(CNW1 or CNW0) on the indoor unit control PCB or turn the main power supply OFF.
Outdoor unit
Error
Check of unit
controller
Note (1) It means the operation to turn off the power and back on again more than 1 min. later in order to reset the malfunction of microcomputer due to the
effect of power supply conditions or accidental noise.
Parts number
PJA505A122ZD
PJA505A122ZC
PJA505A128ZF
Model
FDKA 151~251
FDKA 301
FDUR
133 -
Parts number
PHA505A018ZF
PHA505A018ZG
PJA505A131ZC
Fan motor
(151~401)
ZD1
To power supply
(CNW7)
C41
CNV
CNM3
Fan motor
(501, 601)
CNW9
52X8-1
KN1
52X1
52X2
52X3
C12
C13
C1
CNM2
PC3
IC8
C11
IC12
IC7
D2
F1
IC11
C58
Z2D
Z3D
Z4D
Z5D
X1
CNE
IC2
IC3
C2
CNW8
R17
PC2 PC1
CNG
L1
CNB
Remote
controller
C3
SW7
C5
J1
J2
J3
J4
C4
TVS1
Connector
(CNT)
J5
J6
J7
J8
IC9
CNT
J8
J10
J11
J12
Address switch
(SW2)
CNY
J2 (SW7-2)
J3 (SW7-3)
J4 (SW7-4)
J5 (SW8-1)
J6 (SW8-2)
J1~J4
(SW7)
SW9
ON
DIP switch
(SW9)
1 2 3 4
CNN1
J5~J6
(SW8)
DIP switch
(SW5)
Heat exchanger
J9~J11
thermistor
(SW10)
(Thi-R2)
SW8
SW5
CNI
CNH
ON
1 2 3 4
SW2
SW10
Name
F2
LED2 LED1
J1 (SW7-1)
Louver motor
52X4
PC5
L2
C23
52X7
52X8-2
52X6
TM1
R16
CNW7
CNR
CNJ
Function
Input signal - Reverse invalid
Input signal - Rus stop
Heating thermostat OFF-Lo
Heating thermostat OFF-Stop, Lo
Normal operation operable
Operation permission prohibited
Normal
Heating temp. +3
Louver free stop control - Invalid
Louver free stop control - Effective
Freeze prevention fan control activated.
Freeze prevention fan control deactivated.
Switch
ON
SW5-4 OFF
ON
OFF
OFF
ON
SW5-3
Function
Setting time : 1000hrs. (Unit stop)
Setting time : 1000hrs. (Display)
Setting time : 600hrs. (Display)
Setting time : 180hrs. (when shipped from factory)
SW9-3
Note (1) None means that jumper wire is not provided on the PCB or the
connection is cut
(2) The replacement board is not equipped with jumpers J1 ~ J6. Instead,
SW7 and 8, with the same functions as jumpers J1~J6, are used in the
position where the jumpers were previously. Set SW7 and 8 locally in
accordance with the above table.
SW9-4
Function
Emergency operation
Normal
Fan control : Powerful mode
Fan control : Mild mode
134 -
OFF
ON
OFF
OFF
SW10-3 ON
OFF
ON (J11) ON
Function
Auto swing fanction - None
Auto swing function - With
Remote controller air flow
Remote controller air flow 1 speed
Remote controller air flow 2 speed
Remote controller air flow 3 speed
L2
CNW0
CNM1
L3
F1
52X3 52X5
IC7
IC8
CNW2
ZNR
52X2
52X4 52X6 52X2
L1
CNB
CNJ2
CNM3
LED1
LED2
CNE
52X8-1
DIP switch
(SW5)
SW2
SW5
SW8
J5, J6
(SW8)
52X7
KN1
CNV
52X8-2
CNR
Fan motor
CNW1
SW10
SW9
SW7
C57
CNQ
CNH CNN1
CNT
J1~J4
(SW7)
Connector
(CNT)
Heat exchanger thermistor,
Return air thermistor
(Thl-R1, Thl-A)
J1 (SW7-1)
J2 (SW7-2)
J3 (SW7-3)
J4 (SW7-4)
J5 (SW8-1)
J6 (SW8-2)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
J9~J11
(SW10)
DIP switch
(SW9)
Address switch
(SW2)
Function
Input signal - Reverse invalid
Input signal - Rus stop
Heating thermostat OFF-Lo
Heating thermostat OFF-Stop, Lo
Normal operation operable
Operation permission prohibited
Normal
Heating temp. +3
Louver free stop control - Invalid
Louver free stop control - Effective
Freeze prevention fan control activated.
Freeze prevention fan control deactivated.
Switch
ON
SW5-4 OFF
ON
OFF
OFF
ON
SW5-3
Function
Setting time : 1000hrs. (Unit stop)
Setting time : 1000hrs. (Display)
Setting time : 600hrs. (Display)
Setting time : 180hrs. (when shipped from factory)
SW9-3
Note (1) None means that jumper wire is not provided on the PCB or the
connection is cut
(2) The replacement board is not equipped with jumpers J1 ~ J6. Instead,
SW7 and 8, with the same functions as jumpers J1~J6, are used in the
position where the jumpers were previously. Set SW7 and 8 locally in
accordance with the above table.
SW9-4
Function
Emergency operation
Normal
Fan control : Powerful mode
Fan control : Mild mode
135 -
OFF
ON
OFF
OFF
SW10-3 ON
OFF
ON (J11) ON
Function
Auto swing fanction - None
Auto swing function - With
Remote controller air flow
Remote controller air flow 1 speed
Remote controller air flow 2 speed
Remote controller air flow 3 speed
J31
Remote controller
TB,3
R16
Dip switch
(SW5)
R17
CNH
CNN1
CNZ
CNB
SW10
L2
SW5
TB,1
J11
J10
J9
J9~J11
(SW10)
Dip switch
(SW9)
TB,2
L1
G
J31
SW8
SW9
CNW1
J8
J7
J6
J5
J5~J8
(SW8)
IC11
J4
J3
J2
J1
SW7
J1~J4(SW7)
R151
CNE
L4
C104
C2
SW2
IC9
IC10
C92
IC8
CNG
LED1
R62
Adress switch
(SW2)
BZ
CNT
CNL
CNY
CNM
CNJ
Louver motor
J1 (SW7-1)
J2 (SW7-2)
J3 (SW7-3)
J4 (SW7-4)
J5 (SW8-1)
J6 (SW8-2)
J8 (SW8-4)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
Fan motor
Connector
(CNT)
Function
Input signal - Reverse invalid
Input signal - Rus stop
Heating thermostat OFF-Lo
Heating thermostat OFF-Stop, Lo
Normal operation operable
Operation permission prohibited
Normal
Heating temp. +3
Louver free stop control - Invalid
Louver free stop control - Effective
Freeze prevention fan control activated.
Freeze prevention fan control deactivated.
Model 151~251
Model 301
Switch
ON
SW5-4 OFF
ON
OFF
OFF
ON
SW5-3
Function
Setting time : 1000hrs. (Unit stop)
Setting time : 1000hrs. (Display)
Setting time : 600hrs. (Display)
Setting time : 180hrs. (when shipped from factory)
SW9-1
SW9-2
Note (1) None means that jumper wire is not provided on the PCB or the
connection is cut
(2) The replacement board is not equipped with jumpers J1 ~ J8. Instead,
SW7 and 8, with the same functions as jumpers J1~J8, are used in the
position where the jumpers were previously. Set SW7 and 8 locally in
accordance with the above table.
SW9-3
SW9-4
Function
Custom code - Change
Custom code - Normal
Power failure security - Effective
Power failure security - Invalid
Emergency operation
Normal
Fan control : Powerful mode
Fan control : Mild mode
136 -
OFF
ON
OFF
OFF
SW10-3 ON
OFF
ON (J11)
ON
Function
Auto swing fanction - None
Auto swing function - With
Remote controller air flow
Remote controller air flow 1 speed
Remote controller air flow 2 speed
Remote controller air flow 3 speed
CNH
CNB
J10~J11
(SW10)
CNQ
SW2
SW10
CNO
SW5
CNR
Drain motor
SW8
SW9
52X4
F1
CNG
CNW2
CNM3
CNW0
J3 (SW7-3)
J4 (SW7-4)
J6 (SW8-2)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
With
None (1)
CNK2
Power supply
F3
F2
CNE
52X6
CNK1
J2 (SW7-2)
CNI
SW7
L4
52X1
L1
52X2
CNW1
J1 (SW7-1)
CNZ
LED1
52X5
CNJ2
52X3
Float switch
J1~J4
(SW7)
LED2
L2
L3
DIP switch
(SW9)
CNO
CNV
CNT
DIP switch
(SW5)
Remote controller
Connector
(CNT)
J6
(SW8)
Address swith
(SW2)
CNA
Function
Input signal - Reverse invalid
Input signal - Rus stop
Heating thermostat OFF-Lo
Heating thermostat OFF-Stop, Lo
Normal operation operable
Operation permission prohibited
Normal
Heating temp. +3
Freeze prevention fan control activated
Freeze prevention fan control deactivated
Switch
ON
SW5-4 OFF
ON
OFF
OFF
ON
SW5-3
Function
Setting time : 1000hrs. (Unit stop)
Setting time : 1000hrs. (Display)
Setting time : 600hrs. (Display)
Setting time : 180hrs. (when shipped from factory)
Note (1) None means that jumper wire is not provided on the PCB or the
connection is cut
(2) The replacement board is not equipped with jumpers J1 ~ J4, J6.
Instead, SW7 and 8, with the same functions as jumpers J1~J4, J6, are
used in the position where the jumpers were previously. Set SW7 and 8
locally in accordance with the above table.
ON
OFF
ON
OFF
SW9-3
SW9-4
Function
Emergency operation
Normal
Fan control : High speed (High Ceiling)
Fan control : Standard
137 -
OFF
SW10-3 ON
OFF
ON (J11)
ON
OFF
Function
Remote controller air flow
Remote controller air flow 1 speed
Remote controller air flow 2 speed
Remote controller air flow 3 speed
Indoor unit
Outdoor unit
Red LED
Stays OFF
Red LED
Stays OFF
Green LED
Stays OFF
Green LED
Stays OFF
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Start
Is the voltage
between 1 and 2/N of the indoor
units terminal block
AC220/240V?
NO
YES
Voltage between
1 and 2/N of the outdoor units
terminal block is
AC220/240V.
YES
NO
NO
Fuse
OK?
YES
YES
Fuse exchange
Is the voltage at
CNW3 or 10(1) (red red) on the
transformers secondary side
14 V or higher?
NO
Transformer exchange
YES
(1)(2)
Is the voltage
between CNW5 2 and 3
DC 12V?
NO
YES
Note (1) 3 is GND
(1)(2)
Is the voltage
between CNW8 2 and 3
DC 12V?
NO
Harness disconnection
YES
Does it return
to normal when the power
supply is reset?
YES
Unit is normal.
(Malfunction was due to noise, etc.)
NO
138 -
NO
Indoor unit
3 time flash
Keeps flashing
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Green LED
Red LED
Red LED
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Remote
controller wiring
connect check (Red
WhiteBlack)
NO
Correction
OK
(1)
Approximately
10 ~ 11 V between
X and Z.
NO
YES
NO
Power supply reset
Normal?
YES
Maltifunction by
accidental noise
YES
Remeasure
between X~Z.
10~11V.
YES
NO
Is the voltage
between CNW8 1-3
12V?
NO
Check the
CNW5-8 harness.
OK
YES
NG
Harness exchange
Replacement indoor
unit control PCB
139 -
Error display
Red LED
Green LED
WAIT
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
2 time flash
Keeps flashing
Notes (1) If trouble occurs during communications, the error code E5 is displayed (Outdoor, Red LED flashes 2 times). The check procedure is as shown below. (However, excluding
connection related problems) Also, if the power supply is reset after E5 occurs, if the trouble is intermittent, it will be displayed in the LCD(
WAIT
).
(2) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
151~251
301~601
YES
Power supply
fuse exchange
NO
Noise filter
exchange
(1)
NO
NO
NO
NO
YES
Are the wires connecting the indoor
and outdoor units connected
according to specifications?
YES
Measure the voltage between 2/N and
3 of the outdoor units terminal block.
Approx.
0V DC
(1)
Is the outdoor red LED
flashing 2 times?
NO
YES
Are the wires connecting the indoor
and outdoor units connected according
to specifications?
NO
Outdoor unit
control PCB
defect
Measure the voltage between 2/N and
3 of the indoor units terminal block.
Approx.
0V DC
Approx.
20V DC
YES
NO
Nois filter
exchange
NO
Replacement outdoor
unit control PCB
NO
YES
Is the outdoor red LED
flashing 2 times?
NO
YES
Are the wires connecting the indoor
and outdoor units connected according
to specifications?
YES
NO
Measure the voltage between 2/N
and 3 of the outdoor units
terminal block.
Reactor
exchange
Approx. 20V DC
NO
Repair the
connection
lines.
Approx.
0V DC
140 -
The indoor/outdoor
control board is faulty.
The remote controller
is faulty.
The X or Z lines in the
remote controller are
disconnected.
Approx. 0V DC
Approx. 20V DC
Indoor unit
control PCB
defect
Fuse
exchange
NO
Transformer
defect
NO
The remote
controller
wires are
short
circuited.
YES
Power supply
fuse exchange
NO
YES
YES
Outdoor unit
control PCB
defect
Approx.
0V DC
YES
defect
DC 20V
NO Transformer
YES
Approx.
0V DC Connection wires are
faulty (disconnection)
Noise
YES
Outdoor unit
control PCB defect
DC 20V
Fuse
exchange
YES
DC 20V
Measure the voltage between 2/N and
3 of the indoor units terminal block.
PCB defect
YES
Is the outdoor units control red
LED flashing 2 times?
NO
YES
Connects
corrently
YES
Is the indoor units green LED
flashing?
NO
YES
(1)
YES
NO
YES
YES
YES
Remote
controller
defect
Error display
Red LED
Green LED
e1
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Voltage
between X and Z
approximately
10~11 V?
YES
Replacement remote
controller
Remote controller
wire is removed
NO
Voltage
fluctuates between
5~11 V between
Y and Z.
YES
NO
Is the
NO
resistance between
Y~Z on the remote controller
approximately
10k?
Replacement
remote controller
YES
Voltage
fluctuates between
5~10 V between
Y and Z
indoors.
NO
Remote controller
wire disconnection
Resistance is
approximately 10k
between indoor
Y~Z.
YES
NO
Replacement indoor
unit control PCB
YES
Voltage
fluctuates between
5~10 V between
CNB Y and Z.
NO
Remote controller
wire short circuit
YES
Indoor unit
resets every
4 minutes.
YES
NO
Power supply reset
YES
Power supply reset
Noise?
Normal?
YES
Normal?
Noise
NO
Replacement indoor
unit control PCB
Outdoor unit
Indoor unit
Red LED
Stays OFF
Green LED
Stays OFF
Red LED
Green LED
Keeps flashing
YES
Disconnection ?
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
NO
Is the
voltage at the transfomer's
secondary side (red-red) 15V
or higher?
Stays OFF
Is the voltage
between CNW8
2-3 12V?
Lighting
Harness
exchange
NO
NO
Transformer
exchange
YES
YES
NO
Replacement indoor
unit control PCB
Is it normalized?
NO
YES
The unit is normal.
(The malfunction is due to noise, etc.)
Power supply
reset
141 -
YES
Unit is normal.
(Runaway of indoor
unit CPU due to
noise, etc.
Transient trouble)
Error display
Red LED
Green LED
e6
Indoor unit
1 time flash
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Is the indoor
unit heat exchanger
thermistor connector
connection OK?
YES
Are characteristics
of indoor unit heat
exchanger thermistor OK
or is there any
broken wire?
Resistance (k)
YES
15
10
5k at 25C
NO
NO
Correction
10 20 30 40
Temperature (C)
Note (1) 22.5 k at -6C
50
Display condition
If a temperature of 50C or lower is detected continuously for 5 seconds or longer by the thermistor, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected again within 60 minutes after the
first detection.
Error display
Red LED
Green LED
e7
Indoor unit
1 time flash
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
YES
NO
NO
YES
Correction
Display condition
If a temperature of 50C or lower is detected continuously for 5 seconds or longer by the thermistor, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected again within 60 minutes after the
first detection.
142 -
Error display
e8
[Heating overload]
Indoor unit
1 time flash
Keeps flashing
Red LED
Green LED
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
YES
Notes (1) Check if the overload state exists or not using the following check points.
Is there a short circuit?
Is the indoor heat exchanger dirty or clogged?
Is the outdoor units fan control normal?
Is the indoor or outdoor air temperature too high?
(2) See the figure page 142 for indoor heat exchanger thermistor characteristics.
Clean it.
YES
NO
YES
NO
YES
Repair
Adjust
NO
Heating is
possible.
Display condition
An abnormal stop occurs if this state is detected 5 times within 60 minutes of the
56
63
Error display
Red LED
Green LED
e9
[Drain trouble]
Indoor unit
1 time flash
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Is there any
overflow?
DC 12 V
at both terminals
of CNI?
NO
NO
Replacement indoor
unit PCB
YES
YES
DM
operation
NO
AC 220/240 V
at both terminals
of CNR?
YES
YES
Is drain
piping unclogged?
Is the slop OK?
DM check of
motor wiring
NO
Correction
YES
DM check
143 -
NO
Replacement indoor
unit control PCB
Error display :
Red LED
Green LED
e10
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Are more
than 17 units connected
to a remote
controller?
YES
Reduce to 16 units
or less
NO
Defective indoor unit control PCB
Replacement
Error display :
Red LED
Green LED
e16
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
NO
Fan ON?
YES
White is GND.
CNM1
1 and 3 (Red White)
DC280V?
NO
Replacement indoor
unit power supply PCB
YES
Was it reproduced?
YES
3 is GND.
CNW9
1 and 3
DC15V?
NO
Check the
circumstances.
YES
Secondary
side of transformer
(red-red) 15V
or more
NO
NO
YES
NO
When the
motor is turning, does
the voltage at CNM2 2
fluctuate between
0 ~ 15 V?
Replacement transformer
(1)
DC 15V
between CNW9- 3 and
CNM2 4 ?
NO
YES
Replacement indoor
unit control PCB
Replacement indoor
unit control PCB
YES
Does the
fan motor turn
smoothly by
hand?
NO
Display conditions
YES
(2)
Is the voltage
at CNM2 3 DC 1V
or higher?
YES
200 rpm continuously for 30 seconds, the fan motor stops for 2
seconds. After 2 seconds, it starts again, but this occurs 4 times
NO
Replacement indoor
unit control PCB
144 -
NO
Fan ON?
YES
3 (Black) is GND.
CNM
1 and 3 (Red Black)
DC280V?
NO
Replacement indoor
unit control PCB
YES
Was it reproduced?
YES
3 (Black) is GND.
CNM
4 and 3 (White-Black)
DC15V?
NO
NO
Check the
circumstances.
YES
Secondary
side of transformer
(red-red) 14V
or more
NO
NO
When the
(1)
motor is turning, does
the voltage at CNM 6 (Blue)
fluctuate between
DC 0 ~ 15 V?
YES
Replacement transformer
YES
Does the
fan motor turn
smoothly by
hand?
NO
YES
(2)
Is the voltage
at CNM 5 (Yellow) DC 1V
or higher?
YES
Display conditions
NO
200 rpm continuously for 30 seconds, the fan motor stops for 2
Replacement indoor
unit control PCB
NO
YES
3 (black) is GND.
CNM
1 and 4 (Red-Blue)
DC 0~60V ?
NO
YES
NO
Replacement fan
motor
NO
Check the
circumstances.
YES
YES
YES
Was it reproduced?
(1)
When
the motor is turning,
does the voltage at CNM 5
(White) fluctuate between
DC 0 ~ 15 V?
Fan ON ?
YES
YES
NO
Replacement fan
motor
Replacement indoor
unit control PCB
Check the
circumstances.
Replacement indoor
unit control PCB
Display conditions
If an indoor unit fan motors speed is detected to be less than
200 rpm continuously for 30 seconds, the fan motor stops for 2
seconds. After 2 seconds, it starts again, but this occurs 4 times
within a period of 1 hour.
145 -
10
Error display :
Red LED
Green LED
e28
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Are characteristics of
remote controller thermistor OK or is there any
broken wire?
YES
NO
YES
NO
Correction
65
14
33
30
16
46
8.5
62
16
30
32
15
48
7.8
59
18
27
34
14
50
7.3
53
20
25
36
13
52
6.7
48
22
23
38
12
54
6.3
44
24
21
40
11
56
5.8
10
40
26
19
42
9.9
58
5.4
12
36
28
18
44
9.2
60
5.0
146 -
2) Set the model using the model setting switch (SW6). (In the case of the 151~251 only).
Switch Setting Table (All switches are set in the OFF position when shipped from the factory.)
Model
151
201
251
4
2
4
3
2
ON
ON
2
1
ON
3) Set the overcurrent value using the overcurrent setting switch for CM (SW3). (In the case of the 301~601 only)
Switch Setting Table (All switches are set in the OFF position when shipped from the factory.)
ON
5
4
3
2
1
ON
ON
14
6
12
6
6
5
4
1
3
2
ON
11
5
4
3
2
1
ON
27
10
6
17
ON
Model
4) Set the control select switch to match the previously set settings on the previous board.
If the previously set settings were set with jumper wires, the control select switch should be set in the ON position if there
was a jumper wire and in the OFF position if there wasnt a jumper wire.
5) Connect the faston terminals and connectors to the control board.
When connecting the wires to the faston terminals, connect each wire to the terminal printed with the same color on the
board.
Note (1) When connecting the faston terminals to the control board, connect them so that there is no deformation of the far end of the circuit board.
147 -
Reactor
Fan motor
Stepping motor
CNM
F3
CNV1
CNI2
F1
T5
T2
T1
CNW
T8
CNL
CNI3
CNTR
CNI
F2
T4
T7
T6
CN
SW7
CNE
CNQ
DIP switch
(SW6)
SW6
DIP switch
(SW7)
JA1 (SW7-1)
JA5 (SW6-1)
JA6 (SW6-2)
JA7 (SW6-3)
JA8 (SW6-4)
151
None
None
None
None
With
201
None
None
With
None
With
251
None
None
None
With
With
Notes (1) None means that jumper wire is not provided on the PCB or the connection is cut
Notes (2) The replacement PCB is not equipped with jumper wires JA1 and JA5~JA8. Instead, SW6 and 7
are mounted in the same position and have the same functions as jumper wires JA1 and JA5~JA8.
Carry out the local settings in accordance with the table using SW6 and 7.
Note (1) None means that jumper wire is not provided on the
PCB or the connection is cut.
External PCB
SW5
SW9
Test run operation switch
SW9
SW5
Function
Defrost Setting Select For cold regions.
Normal
Snow-guard fan control-Effective
Snow-guard fan control-Invalid
Low refrigerant protection control-Effective
Low refrigerant protection control-Invalid
Test run operation-Heating
Test run operation-Cooling
CNQ1
148 -
FDCA301~601 type
Stepping motor
PCB power supply connector
(Secondary side)
L6
C3
L5
C6
C5
CNA2
C13
C7
IC12
C4
C8
C1
HT1
C2
CNW
CNL
L7
C6
L8
SW3
C11
C9
L10
C12
LED-R
CNP1
SW4
J4
J3
J2
J1
SW5
1 2 3 4
CNP2
CNV1
J16
J15
J14
J13
J12
J11
J8
J7
J6
J5
LED-G
L12
L11
SW4
SW3
SW6
SW5
CNA1
C10
SW6
CNE
X04
X03
X02
X07
X05
X01
X06
Crankcase heater
KN1
CNM3
KN2
CNS
CNM2
CNR
CT1
CNM1
CNP3
CT2
CNQ
SW2
SW2
(Test run operation switch)
CNO
CNM4
Magnetic contactor
(52C)
4 way valve
Capacitor for FMo
Fan motor
Function
Switch
ON
OFF
ON
SW5-2
OFF
ON
SW5-3
OFF
ON
SW5-4
OFF
1 Phase
3 Phase
Cooling
Heating
Defrost recovery temperature 14C
Defrost recovery temperature (See page 88)
Defrost prohibited temperature 45 min.
Defrost prohibited temperature 37 min.
SW5-1
Function
Defrost Setting Select For cold regions.
Normal
Snow-guard fan control-Effective
Snow-guard fan control-Invalid
Low refrigerant protection control-Effective
Low refrigerant protection control-Invalid
Test run operation-Heating
Test run operation-Cooling
Overcurrent Setting
Notes (1) None means that jumper wire is not provided on the
PCB or the connection is cut
Notes (2) The replacement board is not equipped with jumper
wires JA1~JA8. Instead, SW4 and 6 are mounted in
the same position and have the same functions as
jumper wires JA1~JA8. Carry out the local settings in
accordance with the above table using SW4 and 6.
Model
301HEN 301HES 401HEN 401HES 501HES 601HES
Setting Value (A)
17
10
27
11
12
14
J11 (SW3-1)
J12 (SW3-2)
J13 (SW3-3)
With
None(1)
None(1)
With
None(1)
None(1)
With
None(1)
With
With
None(1)
With
With
With
None(1)
With
With
With
Notes (1) None means that jumper wire is not provided on the PCB or the
connection is cut
Notes (2) The replacement board is not equipped with jumper wires J11~J13.
Instead, SW3 is mounted in the same position and has the same functions as jumper wires J11~J13. Carry out the local settings in accordance with the above table using SW3.
(3) The overcurrent setting value becomes the above setting value (A)
automatically in accordance with the settings on J11(SW3-1) ~
J13(SW3-3) and J1(SW4-1).
149 -
FDCVA151~251 type
T24
T25
150 -
TB
Fuse Check: There should be
continuity.
Gray
Sub PCB
(Noise filter) T26
CNI1
CM
To indoor unit
Brown
T30
T28 T27
100
10
T< 80C
T > 80C
50
0
0
20
50
80
100 120
Temperature [ T ] (C)
T6
T7
T8
T2
T4
CnTR
T1 T5
F2 (250V 20A)
Control PCB
F3 (250V 1A)
LED1
Red
DC280V
1 2 3 4 6
FM0
Y/NG
T21
T22
White
Orange
Black
F5 (20A)
Red
Red
White
TB
DC Reactor Continuity
Check: 50 m or higher,
less than 100 m.
Yellow
Orange
Error display
Red LED
Green LED
e5
Indoor unit
2 time flash
Keeps flashing
Red LED
Green LED
Outdoor unit
2 time flash
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
(1)
(2)
Is the connection
of the signal wires at the NO
outdoor unit poor?
Is the connection
NO
of the signal wires at the
indoor unit poor?
YES
Reset power
supply.
YES
Repair
WAIT
YES
The unit is normal.
Malfunction was due to
transient noise, etc.
Repair
Notes (1) Check for poor connections (disconnection, looseness) on the outdoor units terminal block.
(2) Check for poor connections or disconnection of the signal lines between the indoor and outdoor units.
Red LED
Green LED
Indoor unit
2 time flash
Keeps flashing
Red LED
Green LED
Outdoor unit
Stays OFF
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
YES
NO
Outdoor units control PCB is
faulty. (Network communications
circuit is faulty.)
Replace
Error display
Red LED
Green LED
e32
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
YES
Outdoor unit
1 time flash
Keeps flashing
Repair
NO
NO
Repair
YES
151 -
WAIT
Error display
e33
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
NO
Red LED
Outdoor unit
1 time flash
Display Conditions
Restore it to the
normal state.
If the inverters primary current exceeds the set value for 3 sec-
YES
Restore it to the
normal state.
Red LED
Green LED
Indoor unit
Stays OFF
Keeps flashing
Is the voltage
AC220/240V between the
L1 and L3 phases and between the L2
and L3 phases on the 52C
secondary side?
NO
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
YES
52C is faulty.
There is a disconnection between
52C and CM or in the L1 and L2
phases between TB1 and 52C.
Check the unit side.
(1)
Is there overcurrent
at the compressor?
YES
NO
Replace
152 -
Error display :
Red LED
Green LED
e34
[Open phase at L3 phase of 52C secondary side] (Only case of 301~601 type)
Indoor unit
Stays OFF
Keeps flashing
(1)
52C
secondary side L3 phase
open?
Red LED
Green LED
YES
NO
Outdoor unit
1 time flash
Keeps flashing
Notes (1) Also check if there is voltage at the L3 phase on the 52C primary
side, but no voltage on the secondary side (coil wire disconnection or faulty contacts).
(2) If there is voltage at the L3 phase on the 52C primary side and it
is not abnormal, the outdoor unit control PCB is faulty.
Repair
(2)
AAA
AAAAAAAAAAAAAAAAAAAAAAAA
If the unit is operated with the service valve closed, 49C (internal thermostat) operates. E34 may also be displayed. Check the service valve.
AAA
AAAAAAAAAAAAAAAAAAAAAAAA
Error display :
e35
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
YES
NO
Replace the outdoor heat
exchanger thermistor.
(1) The compressors speed drops when all the following conditions are met
(151~251). In the case of the 301~601, expansion valve control is performed.
1 Outdoor heat exchanger temperature: AC or higher
2 Outdoor air temperature: 41C or higher
3 The outdoor units fan runs at 7 speed (UHi)(1) continuously for
30 seconds or longer.
(2) Control is cancelled when the temperature drops to BC or lower.
Item
A
B
Model
151~251 type
NO
The outdoor control PCB
is faulty. Replace
58.5
53.5
53.5
48.5
48.5
43.5
58
53
301~601 type
Return
Note (1) Values in ( ) show for the case of the 301~601 models.
48
65(1)
Display Conditions
If the outdoor heat
less than 88
65 or more
exchanger temperature
60 or more
108 or higher
55 or more
15
within 60 minutes,
including while the
compressor is stopped,
or if it continues at that
temperature for 10
Resistance(k)
10
5k at 25C
minutes or longer.
153 -
10
20 30 40
Temperature (C)
50
Error display :
e36
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Is the
discharge pipe thermistror characteristics
normal?
Discharge
YES temperature error?
(At cooling/heating
operation)
NO
Discharge pipe thermistor replacement
Is discharge temperature
control normal?
Is the unit
normalized
NO
Hold
Display conditions
Release
151~251 type
301~601 type
80
90
90
100
Note (1) Values in ( ) show for the case of the 301~601 models.
301~601 type
100
Operoble
Error stop
Thermistor resistance
Error stop
Operoble
80
105
80
121
50
0
0
20
40
60
80
100
120
140
Error display :
e37
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Temperature-resistance characteristics
of discharge pipe thermistor (Tho-D)
100
10
T< 80C
T >80C
50
0
0
0
50
80
100
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
Is the outdoor
unit heat exchanger
thermistor connector
OK?
YES
NO
Repair
NO
YES
15
Display conditions
If the temperature sensed by the thermistor is 30C or lower continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds
after the compressor goes ON, the compressor stops. After a 3 minute
delay, the compressor restarts. If this state is detected 3 times in 40
Resistance(k)
301~601 type
151~251 type
Temperature-resistance characteristics
of discharge pipe thermistor (Tho-D)
151~251 type
10
5k at 25C
(60) minutes.
Note (1) Values in ( ) show for the case of the 301~601 models.
154 -
10
20
30
40
Temperature (C)
50
Error display :
e38
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
Red LED
Green LED
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
YES
Is the outdoor
air temperature thermistor
characteristics OK, is there
no broken wire?
YES
NO
NO
400
Display conditions
If the temperature sensed by the thermistor is 30C or lower continuously for 5 seconds between 2 minutes and 2 minutes 20 seconds after
the compressor goes ON, the compressor stops. After a 3 minute delay,
Repair
Temperature-resistance
characteristics of outdoor air
temperature thermistor (ThO-A)
300
40
30
200
20
T < 0C
T > 0C
100
10
Is the outdoor
air temperature thermistor
connector connection
OK?
Error display :
Red LED
Green LED
e39
0
50
Temperature [T](C)
Indoor unit
Stays OFF
Keeps flashing
Outdoor unit
1 time flash
Red LED
Keeps flashing
Green LED
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
NO
Repair
YES
YES
Temperature-resistance
characteristics of discharge
pipe thermistor (ThO-D)
NO
Defective discharge pipe
thermistor
Replacement
Display conditions
If the temperature sensed by the thermistor is 10C or lower continuously for 5 seconds between 10 minutes and 10 minutes 20
seconds (2minutes and 2minutes 20seconds) after the compressor
goes ON, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 (60) minutes.
100
10
T< 80C
T> 80C
50
0
0
0
20
50
80
100 120
Note (1) Values in ( ) show for the case of the 301~601 models.
155 -
Is the discharge
pipe thermistor
connector connection
OK?
0
---50
10
Error display :
Red LED
Green LED
e40
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
YES
1. During Cooling
Is the outdoor unit fan motor running?
Is there a short circuit in the outdoor unit?
Is there enough space for inlet and outlet?
2. During Heating
Is the indoor unit heat exchanger thermistor separated
from the sensing case?
Is the filter clogged?
3. During Cooling and Heating
Is the refrigerant overcharge?
Is the service valve fully open?
Indoor unit
Stays OFF
Keeps flashing
(1)
52C
primary side L3 phase
open?
NO
Red LED
Green LED
YES
Outdoor unit
1 time flash
Keeps flashing
Repair
Notes (1) Also check if there is voltage at the L3 phase on the 52C primary
side, but no voltage on the secondary side (coil wire disconnection
or faulty contacts).
(2) If there is voltage at the L3 phase on the 52C primary side and it is
not abnormal, the outdoor unit control PCB is faulty.
(2)
11
Error display :
Red LED
Green LED
e42
Indoor unit
Stays OFF
Keeps flashing
Is the power
supply voltage
proper?
YES
Red LED
Is the service
valve fully open?
NO
Outdoor unit
1 time flash
Is the high
pressure during operation
proper?
YES
NO
NO
Check the
compressor's insulation
resistance and winding
resistance.
YES
Open it fully.
YES
NO
Display conditions
If the inverters output current exceeds the set value, the compressor stops. After a 3-minute delay, it
restarts, but if this occurs 3 times
Check the
power transistor module
(See page 160)
NG
OK
within 20 minutes.
Is the installation space for the indoor and outdoor
YES
units proper?
Is there a short circuit in the indoor or outdoor
units?
During cooling: Is FMo operating?
Is the service valve fully open?
During heating: Is FMI operating?
Is the service valve fully open?
Is the filter clogged?
Is liquid flowing back to the compressor?
Is the compressor making abnormal noises?
156 -
Does it return to
normal if the power
supply is reset
(2 of 3 times)?
NO
YES
It may be malfunction due to transient noise. If
there is a noise source nearby, take measures to
eliminate it.
12
Error display
e47
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Red LED
Outdoor unit
1 time flash
NO
YES
Replace
Display Conditions
NO
If the inverter voltage exceeds 340V, (3 times in 20 minutes), this error is displayed. After 3 minutes passes, it
13
Error display :
Red LED
Green LED
e48
Indoor unit
Stays OFF
Keeps flashing
Is any foreign
object wedged into the
rotating parts of the
fan motor?
Red LED
Turn the
fan by hand several
revolutions. Does itturn
smoothly?
YES
NO
YES
Outdoor unit
1 time flash
Is there
foreign matter
such as dust or dirt on
the soldered surfaces
of the control
PCB?
NO
YES
NO
Is fuse F3
(250V, 1A)
blown?
YES
NO
Display conditions
When the DC fan motors output is ON, if the fan motors speed drops to 75 rpm or lower continuously
for 30 seconds or longer, the compressor stops. After a 3-minute delay, the compressor is restarted, but
if this state is detected 5 times within 60 minutes.
14
Error display :
Red LED
Green LED
e52
Indoor unit
Stays OFF
Keeps flashing
Is E52
Cooling operation
E52 Heating operation
displayed in the remote
controllers
screen?
YES
Red LED
Green LED
Outdoor unit
Lights contiously
Keeps flashing
157 -
Red LED
Green LED
e56
Indoor unit
Stays OFF
Keeps flashing
Is the
power transistor thermistor
connector connection
OK?
Red LED
Outdoor unit
1 time flash
Are the
power transistor
thermistor characteristics
OK, is there no
broken wire?
YES
NO
YES
Temperature-resistance
characteristics of power
transistor thermistor (ThO-D)
NO
Defective power transistor
thermistor Replacement
Repair
Display conditions
If the temperature sensed by the thermistor is 10C or lower continuously for 5 seconds between 10 minutes and 10 minutes 20
seconds after the compressor goes ON, the compressor stops. After a 3 minute delay, the compressor restarts. If this state is detected 3 times in 40 minutes.
100
10
T< 80C
T> 80C
50
0
0
0
20
50
80
Error display :
15
100 120
Error display :
Red LED
Green LED
e57
Indoor unit
Stays OFF
Keeps flashing
Red LED
Green LED
Outdoor unit
1 time flash
Keeps flashing
Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.
NO
Fully opened.
YES
Are the
connections of the connectors
to the indoor heat exchanger and return
air thermistor OK?
15
NO
Normal
Resistance(k)
16
YES
Are the
characteristics of the indoor
heat exchanger and return air
thermistor OK?
NO
10
5k at 25C
YES
0
NO
10
20 30 40
Temperature (C)
Display conditions
If insufficient refrigerant protection (See page 92) is implemented
3 times within 30 minutes.
158 -
50
17
Error display :
Red LED
Green LED
e59
Indoor unit
Stays OFF
Keeps flashing
Is the power
supply voltage
correct proper?
YES
Red LED
Outdoor unit
1 time, 2 time, 3 time flash
Check
Is the balance
the compressors
YES
pressure appropriate
insulation resistance
during starting?
and winding
resistance.
NO
NO
NG
Replacement
compressor
OK
Check of
power transistor
module
(Reference to 160)
Inverter
OK
Inverter
NG
Replacement
control PCB
(1)
Did it improve?
NO
Replacement
compressor
Display conditions
Note (1) If the test operation is repeated 2 or 3 times, the liquid refrigerant inside the compressor may be expelled from the
compressor may recover from its starting abnormality.
18
Error display :
Red LED
Green LED
e60
Indoor unit
Stays OFF
Keeps flashing
Red LED
Outdoor unit
1 time flash
Again
YES
Operation
Does the compressor
start?
NO (E59)
E59 diagnosis
It
doesnt.
Does E42 occur?
It
Does it
Does the
doesnt.
return to normal
compressor make
when the power
any abnormal
is reset?
noise?
It does.
E42 diagnosis
It does.
Compressor check
E60 recurs.
Replacement
control PCB
It doesnt
recur.
It is possible that
transient noise
could be causing
malfunction. If
there is a noise
source, take countermeasures to
prevent it.
Display conditions
(1) If a rotor position detection operation is conducted, then the rotor position cannot be detected again after that (4 times in 15
minutes), an abnormal state is displayed.
(2) After 3 minutes passes, it is reset with the remote controller is possible.
159 -
Is the power
transistor module
cracked or burnt?
NO
YES
Is there a
short circuit between the
power transistor module
terminals? 1
NO
YES
Compressor operation
Is the balance
between the compressor
current phases good?
NO
If there is a 10% or greater difference
in the current in different phases.
(except during acceleration or deceleration)
YES
Replacement
control PCB
Normal
160 -
(2)
Press the
(3)
Press the SET button to enter the abnormal operation data display mode.
(4)
If there are abnormalities from the past, they will be displayed by an error code and unit No.
(Example)
E8 (Lighted up)
I/U No. 00
(5)
Using the
or
(Flashing)
button, select the indoor unit No. you want to display the error data for.
If only one indoor unit is connected, the indoor unit No. does not change.
(6)
Fix the selection using the SET button. (The displayed indoor unit No. will change from flashing to light up continuously.)
(Example)
E8
DATA LOADING (This message flashes while data are being read.)
E8
ERROR DATA
The data are then displayed beginning with item No. 01.
Displayed items are as shown below.
(7)
Display the other data for when the error occurred in order from the currently displayed operation data No. 01 using
the
or
button.
Depending on the model, items for which corresponding data do not exist are not displayed.
(8)
To change the indoor unit, press the AIR CON No. button and return to the indoor unit selection display.
(9)
Press the ON/OFF button to end the abnormal operation data check.
If you press the RESET button during the settings, the display returns to the previous setting screen.
No.
01
02
03
04
05
07
11
21
22
23
24
26
27
28
29
31
32
34
35
36
37
38
Data item
Operation mode (Example: )
SET TEMP.
27C
RETURN AIR
28C
I/U HEAT EXCH1
6C
I/U HEAT EXCH2
5C
I/U FAN
Hi
TOTAL I/U RUN
10500H
OUTDOOR
35C
O/U HEAT EXCH1 55C
O/U HEAT EXCH2 55C
COMP HERTZ
85.0Hz
Lo PRESSURE
0.40MPa
DISCHARGE
98C
DOME BOTTOM
56C
CT
26A
O/U FAN
Hi
SILENT MODE ON
63H1 ON/OFF
DEFROST OFF
TOTAL COMP RUN 8500H
EEV1
480PULS
EEV2
480PULS
161 -
Backup switch
TIMER
CHECK RUN
Check monitor
(Error code display E1~E60)
Error code [
~]
RUN
162 -
PACKAGED AIR-CONDITIONER
No.110(1A) R