Professional Documents
Culture Documents
0 0
, s
1 1 ,
s
2 2 ,
s
3 3 ,
s
sensor 2
r
2
(t)
n n
s
,
sensor n
r
n
(t)
PD SOURCE
x(t)
sensor i
r
i
(t)
Figure C.1 PD source with sensors located on the external surface of the transformer tank
Let the PD source be located as shown in Figure C.1. The different sensors are located at different positions on the
transformer tank, shown in Figure C.2. Let r
i
(t) be the measurements received at the n sensors consisting of the
signal
i
corrupted by Gaussian noise n
i
(t), independent and identically distributed, with mean zero and variance
sigma square [B58, B59, B60, B61, B62, B63, B64].
) ( ) ( t n
s
t
x
s
t r
i
i
i
i
i
i
+
=
= + x t n t
i i
( ) ( ) (1)
where
jwt
e
t
e t x
2
) (
= (2)
i
and s
i
are the times taken by the signal to go from the source to sensor i.
is the wavelet kernel used to describe the signal ) (t x , which is sinusoidally varying and symmetrically
decreasing.
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
41
Then the wavelet transform of the reference measurement received at sensor 0 and the measurement at sensor i is
given by
dt
s
t
r t r
s
s r W
i i r
0
) (
1
) , (
0
(3)
dt
s
t
x t x
s
s x W
i i x
0
) (
1
) , (
0
(4)
W x s
s s
W x s
s
s
s
s
x i
i
i
x
i
i
i
0
0
0
0 0
( , ) ,
=
+
(5)
Since W x
x
will have a maximum value at (s,) = (1, 0), equation (5) will have a peak when
s
s
s
i
=
0
and =
i
i
s
s
0
0
(6)
( ) x t x
t
s
i
i
i
=
and ( ) x t x
t
s
0
0
0
=
(7)
If = t t
0
(8)
then ( ) t t
i i
=
0
(9)
Hence ( ) ( )
( )
x t x t x
t
s
i i
i
i
= + =
0
0
(10)
and ( )
( ) x t x t x
t
s
0 0 0
0
= + =
(11)
Now ( ) x t
0
and ( ) x t
i
are scaled and delayed versions of ( ) x t . In the new time domain, using the scale/delay
property of WT, equation 5 will have a peak when
s
s
s
i
=
0
and =
i 0
(12)
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
42
(x,y,z)
PD
sensor 1
(x
1
,y
1
,z
1
)
sensor 0
(x
0
,y
0
,z
0
)
sensor 2
(x
2
,y
2
,z
2
)
sensor n
(x
n
,y
n
,z
n
)
x
y
z
(0,0,0)
Figure C.2 Representation of 3-D transformer tank with sensor locations for calculation of PD
source location coordinates
If the speed of sound in oil is C meters/second, then, in Figure C.2,
2 2 2 2 2
) ( ) ( ) (
i i i i
C z z y y x x = + + (13)
From the above equation the location of the PD source (x, y, z) can be easily estimated.
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
43
Annex D (Informative)
Tutorial and case studies for detection and location of AE from PD
D.1 Introduction
Acoustic detection systems can be used to detect and/or locate PD in transformers.
a) AEs are transient elastic waves in the range of ultrasound, usually between 20 kHz and 1 MHz, generated
by the rapid release of energy from a source
b) PDs are pulse-like and cause mechanical stress waves (acoustic waves) to propagate within the transformer
c) If the stress waves propagate to the transformer tank wall, they may be detected with a transducer that is
tuned to the right frequency
d) PD sources can be located by measuring the relative time of arrival of acoustic waves at multiple transducer
locations
As shown in Figure D.1, sensors, generally attached to the outside of the transformer tank, detect the stress waves
caused by PD. This acoustic wave is converted to a voltage signal by the sensor, which is processed and displayed,
and combined with other signals or otherwise processed to aid in interpretation of the acoustic disturbance.
Figure D.1 A PD source emits stress waves that are detected by a sensor on the tank wall. This
signal is processed to validate that it is PD and to determine the location.
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
44
The advantages of the acoustic system are:
a) It can be used when the transformer is on-line
b) It can be used during transformer applied voltage or induced voltage tests
c) It is non-invasive
d) Some commercial systems can differentiate between actual PD and other acoustic noises
Problems in interpretation of signals can be caused by the different velocities of propagation in steel, oil and
insulation. Blocking of signals may be caused by magnetic shields and other obstructions.
D.2 Types of systems
Many different types of acoustic PD systems are in use to detect and/or locate PD. These generic systems include:
a) Digital oscilloscopes with the ability to display multiple channels of waveforms
b) Automated workstations with or without electrical PD triggers
c) On-line continuous monitoring systems
D.3 Sensors
The sensors most often used in AE applications have a sensitive range centered at about 60 kHz or 150 kHz. The
higher frequency sensor is often chosen for field work because of fewer potentially interfering noises.
D.4 Acoustic PD systems are often used in the following situations:
a) When DGA indicates the possible presence of PD
b) When static electrification is suspected
c) When electrical PD is detected, for confirmation and source location
d) As a diagnostic warning tool for suspect or very important transformers
e) For PD detection during factory impulse testing
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
45
D.5 Case Studies
Case 1
During induced voltage test in the lab, PD activity in a 3-phase 250 MVA 400/121/10.5 kV auto transformer
manufactured in 1998 was measured by the analog electrical method. Location was carried out using the acoustic
method with a workstation-type automated instrument. Results of the location test are shown in Figure D.2. After
partial dismantling of the transformer, an internal flashover was located in phase A; see Figure D.3. Insulation
between the upper stress ring of the 110 KV winding and the upper yoke was broken. The accuracy of the three-
dimensional location was in the range of 0.3 0.5 meters.
Figure D.2 Views of the workstation screen showing PD hits vs. time and the location of the
source of PD in the transformer tank
Acoustic Emissions from Partial Discharge
Figure D.3 Internal flashover
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
46
Case 2
DGA results recorded in Table D.1 showed high hydrogen levels in a three-phase 330 MVA, 400/115/35 kV
autotransformer manufactured in 1976. Unstable PD activity was detected during a 14-hour acoustic testing period.
A workstation-type automated instrument indicated location as shown in Figure D.4. Using design drawings, the
fault was located near the core cooling duct of phase A. After consideration of DGA results and PD signals, it was
decided to keep the transformer in service.
Table D.1 DGA history of the transformer with PD activity
Acoustic Emissions from Partial Discharge
DGA history
Acoustic Emissions from Partial Discharge
3D location
Figure D.4 Acoustic activity and three-dimensional PD source location in a 330 MVA,
400/115/35 kV transformer
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
47
Case 3
Single phase Autotransformer: 500/230/13.8 kV, ONAN/ONAF/ONAF, 146/194/243 MVA, core form.
After two years in operation of three sister units that are part of the same bank, Phase C started gassing. A steady
increase in hydrogen started being detected in February 2005. The other two phases remained stable.
Representative dissolved gas analysis values, shown in Table D.2 below, indicate the existence of partial discharge
activity.
Table D.2 - Dissolved gas analysis values
The utility Asset Management Engineers decided to perform an acoustic emission test in order to determine the
location of the gassing site. This test was performed in May 2005.
The autotransformer was monitored continuously for five days. During this period of time it was observed that
significant acoustic activity was detected. This activity was sporadic (only active at certain periods of time); see
Figure D.5.
Figure D.5 - Plot showing the time (horizontal) when the acoustic activity produces locatable events (vertical)
for a portion of the test.
As can be observed on the above figure, if the test had been done with fewer sensors or for a shorter period of time,
the fault might have not been detected. On the other hand, an on-line continuous monitoring system might have
allowed detection of this fault earlier and provided more information about its trends.
When analyzing the other data collected during the test, it was observed that the AE was detected when load was at
minimum value; see Figure D.6. This behavior suggested a source only active when the voltage was at its maximum
value.
2 hours
1 hr 13 m
2 hr 59 m
1 hr 29 m
3 hr 25 m
Fault active
DATE
H2
CO
CO2
CH4
C2H6
C2H4
C2H2
TDCG
05/31/
05
192
187
728
17
5
3
0
404
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
48
Figure D.6 - Load current versus acoustic activity.
In order to verify that hypothesis, the voltage profile of the transformer was requested from the utility. It was
observed that the fault was active when the system reached the maximum voltage values; see Figure D.7.
Figure D.7 - Voltage profile
Load current
Line indicates when acoustic
activity produced locatable
events
AE starts AE ends
Secondary voltage
Values for
May 23
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
49
After five days of continuous monitoring, two areas where the acoustic activity occurred inside the transformer were
obtained. These areas are presented as three dimensional plots. From the average coordinates and correlation to pre-
tanking photographs, the possible areas of concern were at the bottom and top core yokes; see Figure D.8.
Figure D.8 - Three dimensional plots vs. construction photographs showing two clusters of acoustic activity
Cluster
1
Left
HV
Bushing/control
Tertiary
bushings
side
X1 Bushing
side
Cluster
2
Left
side
HV
Bushing/control
Tertiary
bushings
side
X1
Bushing
side
IEEE PC57.127/D10.0, December 29, 2006
Copyright 2006 IEEE. All rights reserved
This is an unapproved IEEE Standard subject to change
50
Additional tests were planned and an overhaul was being planned after the summer. The transformer failed on July
2, 2005.
Internal inspection indicated that the predicted locations were right on the areas where the degradation was
observed; see Figure D.9.
Figure D.9 - Internal inspection findings after unit failed.
D.6 Conclusions
Detection and location of PD using acoustic measurements is not a perfect science. All PD systems require
knowledge of how the system is recording and processing data in order to interpret data correctly. Remote operation
of these systems is difficult.
a) High level PD can be detected and located. It is difficult to detect low PD levels.
b) PD sources in outer parts (leads, etc.) can be detected and located more easily than PD in inner parts. PD
within the winding block might be impossible to detect or location might be false even at high levels of
activity.
c) The correlation is weak between measured and real PD level due to attenuation
d) For exact location, detailed design drawings are needed
e) Correlation to on-site operating parameters is needed to separate PD from other acoustic sources, e.g.
mechanical noises, rain, hail.
Core damage at bottom of center limb (cluster1) Upper core
damage (cluster 2)