You are on page 1of 10

SITRAIN Training for

Automation and Industrial Solutions


ST-SERV2
Training Units and Addressing Page 1
Date: 18.11.2005
File: SERV2_01E.1
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
Training Units and Addressing
Contents Page
Training Area Setup with S7-300 ...................................................................................................... 2
Configuration of the S7-300 Training Unit ......................................................................................... 3
The Simulator ................................................................................................................................... 4
The Conveyor Model ..................................................................................................................... 5
Complete Symbol List (1) ................................................................................................................. 6
Complete Symbol List (2) .................................................................................................................. 7
If You Want to KnowMore .............................................................................................................. 8
Training Area Setup with S7 - 400 .................................................................................................. 9
Configurationof the S7 - 400 Training Unit ..................................................................................... 10
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 2
Date: 18.11.2005
File: SERV2_01E.2
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
Training Area Setup with S7 - 300
S7 - 300 Training Area The training area consists of the following components:
An S7-300 programmable logic controller with the CPU 315-2 DP
Digital input and output modules, analog module
Simulator with digital and analog sections
Conveyor model
ET 200S distributed peripheral
MM420 Micromaster with PROFIBUS module
TP170B Touchpanel
Programming device or PC
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 3
Date: 18.11.2005
File: SERV2_01E.3
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
Configuration of the S7 - 300 Training Unit
PS
1
CPU
2
DI 32
4
0
DO 32
5
4
DI8/DO8
6
8
AI 2
7
304
Module -->
Slot No. -->
I/O Address -->
(32-channel
I/O modules)
Configuration The programmable controller is configured with the following modules:
Slot 1: Power Supply 24V/5A
Slot 2: CPU 315-2 DP
Slot 4: Digital input 32x24V Inputs from the simulator
and thumbwheel buttons
Slot 5: Digital output 32x24V/0.5A Outputs from the simulator
and digital display
Slot 6: Digital input and output Conveyor model
module 8X24V/ 8x24V 0.5A
Slot 7: Analog input 2 AI Analog section from the simulator
Addresses For the training unit with the CPU 315-2DP and for the S7-400 training unit, you
can set the starting addresses of the modules by parameter assignment
(freely).
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 4
Date: 18.11.2005
File: SERV2_01E.4
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
The Simulator
V
0 8 1 5
AI1 AI2 AO1 AO2
AI2
AI1
-15V...+15V -15V...+15V
AI1
AI2 AO1
AO2
V
DI DO
.0
.1
.2
.3
.4
.5
.6
.7
.0
.1
.2
.3
.4
.5
.6
.7
.0
.1
.2
.3
.4
.5
.6
.7
.0
.1
.2
.3
.4
.5
.6
.7
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
..........
Switches
/ Pushbuttons
LEDs Thumbwheel Buttons
Digital Display
Potentiometers for
setting the
analog vales
Design Two cables connect the simulator to the S7-300or S7-400training unit. The
simulator is divided into the following three sections:
Binary section with 16 switches / pushbuttons and 16 LEDs
Digital section with 4 thumbwheel buttons and a digital display. The
thumbwheel and digital (BCD) display use BCD values,
Analog section with a voltmeter for displaying the values at analog channels
0 and 1 or the analog outputs 0 and 1. You use the selector switch to choose
the voltage value you want to monitor. There are two separate
potentiometers for setting the values for the analog inputs.
Addressing You use the following addresses to address the inputs and outputs in your user
program :
Sensor / Actuator
Switch / Pushb.
LEDs
Thumb. buttons
Digital display
Analog channels
(DI32, DO32)
IW0
QW4
IW2
QW6
PIW304/306
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 5
Date: 18.11.2005
File: SERV2_01E.5
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
The Conveyor Model
LB1
I8.0
BAY_1
I 8.5
BAY_2
I 8.6
BAY_3
I 8.7
K_RT (Q 8.5)
K_LT (Q 8.6)
L_Bay_2
Q 8.2
T_Bay_2
I 8.2
L_Bay_1
Q 8.1
T_Bay_1
I 8.1
L_Bay_3
Q 8.3
T_Bay_3
I 8.3
L_FinalAssy
Q 8.4
T_FinalAssy
I 8.4
Horn
Q 8.7
Design The slide shows a diagramof the conveyor model with its sensors and
actuators.
Addresses
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 6
Complete Symbol List (1)
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 7
Complete Symbol List (2)
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 8
Date: 18.11.2005
File: SERV2_01E.8
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
If You Want to Know More
Note The following pages contain either further information or are for reference to
complete a topic.
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 9
Date: 18.11.2005
File: SERV2_01E.9
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
Training Area Setup with S7- 400
Contents of the The training area consists of the following components:
Training Area An S7-400 programmable logic controller with a CPU 412 or CPU 413-2DP)
Digital input and output modules, analog module
Simulator with digital and analog section
Conveyor model
ET 200S distributedperipheral
MM420 Micromaster with PROFIBUS module
TP170B Touchpanel
Programming device or PC
SITRAIN Training for
Automation and Industrial Solutions
ST-SERV2
Training Units and Addressing Page 10
Date: 18.11.2005
File: SERV2_01E.10
SIMATIC S7
Siemens AG 2005. All rights reserved.
SITRAIN Training for
Automation and Industrial Solutions
Configuration of the S7-400 Training Unit
PS
Default Address:
CPU DI
32
28
18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Slot No.
DI
32
32
DO
32
36
DO
32
40
AI
8
1216
Design You can see the design of the S7-400 training unit in the slide above.
Configuration The UR 1 rack is configured with the following modules:
Slot 1: Power Supply 24V and 5V/20A
Slot 2: - " -
Slot 3: - " -
Slot 4: CPU 412 or other
Slot 5: vacant (when the CPU only has a single width)
Slot 6: vacant
Slot 7: vacant
Slot 8: Digital input 32x24V (from simulator)
Slot 9: Digital input 32x24V (from conveyor model)
Slot 10: Digital output 32x24V 0.5A (to simulator)
Slot 11: Digital output 32x24V 0.5A (to conveyor model)
Slot 12: Analog input 8x13 Bit (from potentiometer on simulator)
Slot 13: vacant
Slot 14: vacant
Slot 15: vacant
Slot 16: vacant
Slot 17: vacant
Slot 18: vacant
Addressing You have the default addresses, as shown in the slide above, as long as no
configuration or parameter settings have been made.

You might also like