Terminal Box

Site QTAR Protection Degree


Site Condition same as body frame IP 55
Ambient Temperature : Max 55 Min 3 deg C cable Outlet Orientation
Humidity : Max 100% Min 50 Deg C Changeable by 90 deg Step Yes
relative Absolute Cable entry
Altitude : Max 1000 m above sea level Cable Gland M20
Sun Temperature : Max 85 deg C type of Lead
Standards : IEC Wire Lead Stud
Wire lead with Terminal Block NA
Motor Type Inducton Motor Phase seperation NA
Synchronous Motor Seperated or Segregrated
Rating 0.37 KW Space Heater terminal bx
Phase 3 Phase independent NA
Voltage 400V Instrumentation terminal box
Voltage Variation +/- 10 % independent NA
Frequency 50 Hz accessory
Frequency Variation +/- 2 Hz with cable gland NA
Insulation F Painting
Temp. Rise B Color 7004 Signal Grey
Dielectric Test kV material As per Specification
Voltage Min Accessories
Protection Degree IP W 55 Grounding terminal inside of TB & Frame of Motor
Space Heater terminal bx NA
Special Treat Tropical Anti Corrosive for Motors above 30 KW rating
Salty Dusty, Sand strom Type
Winding temprature detector NA
Cooling Type IEC 411, 511 or 611 for Motors above 30 KW rating
Starting Current for Lv motors 700% Type PT 100
With out Tolerance for MV motors 650% selector switch/indicator supplied
Vibrtion Max By Motor Maker Purchase
Noisel Level Max: 79 B (A) Bearing temperature detector NA
at Full Load for Motors above 30 KW rating
At no Load type
at 1 meter from Motor selector switch NA
Bearing Life More than 40000 hRs by Motor Maker Purchaser
Minimum Voltage for 80% of the rated voltage CT's for differential protection
acceleration for 2000KW and above motor Qty 1 phase.
cable Gland
Characteristics of Motor Minimum Efficiency Drain Hole
Minimum Power factor Sun Shade
Item No. Name plate & rating Plate
Lubricating oil or Grease for intial charge
Touch up paint
Lifting hook or eye bolts
Warning Label (suitable Position for maintenance Purpose
Bearing Grease Terminal Marking
Notes
TBC : To be Confirmed By Manufacturer
RAS ABU FONTAS A2
DESALINATION PROJECT
PROJECT: MOTOR DATASHEET
Make
Type Squirrel cage Wound rotor Service factor 1.15
Permissible GD2 of Driven Machine TBC
Drw No. Outline Motor startingTime 15 secs
sect Sectional
Terminal Box NA Permissible No of consecutive starts:
Cold Start 3 Times,
Insulation F Class Hot start 2 Times,
Temperature rise B
Cooling type IEC IC Operation Cycle
Motor Connection Delta Wye
No of Lead 3 6 others
Rated output 0.37 KW Volt 400 V Pole 2 Pole
Electrical Charcteristics
Slip% Eff % P.F Amp. A
No Load 60.4 0.22 0.7
1/4 Load Bearing
1/2 load Ball /Roll Drive Ball
3/4 Load 5.2 65.2 0.8 1.18 Bearing No. Non Drive
4/4 load 5.8 65.9 0.83 1.4 sleevel end Play NA mm
at start TBC TBC TBC TBC Self Lubricating Self Cooling
at oper. TBC TBC TBC TBC Water cooled Force OilCooled
transient
Thermal characteristics Fan rotation
warm
/cold
Warm
/Cold warm/ cold
Uni directional reverisble
Amp. TBC TBC TBC
Premises Time (sec) TBC TBC TBC Spaceheater NA Ph V W
Slip TBC TBC TBC Vibration mm total amp
Noise 80 dB (A) at full Load
Torque Characteristics Slip % Torque % 72 dB (A) at NO Load
T0 Transient at Start TBC TBC Weight 7.4 Kg Net
TBC TBC
T2 Pull up TBC TBC Cooling Water NA 1/Min Kg/cm3
T3 Pull out TBC TBC Inlet C Outlet C
T4 rated Nm TBC 100
Lubricant Oil NA 1/Min Kg/cm3
Wound Rotor Type Inlet C Outlet C
Secondary Voltage NA
Secondary Current NA
Notes
TBC : To be Confirmed By Manufacturer
MOTOR DATASHEET PROJECT:
RAS ABU FONTAS A2 DESALINATION
PROJECT
T1 Breakaway Locked
Motor Data by Motor Maker Motor Data by Motor Maker
3000556-SEMCO-R-XS-0001
3000556-SEMCO-R-XE-0001
TBC
TBC
Qty
Motor Supplied by Motor Maker End Play
Machine Maker Inclusively vibration
Rated Output KW 0.37 Volt 400 Pole 2 Torque Pulation
Pole Speed Pole rpm 3000 Unbalanced load
Speed Reducer
Yes No
Ratio Type Driven Machine GD2 at at Ns rpm
Rotation Direction Motor starting torque over
Counter Clockwise Driven machine torque, curve
Clockwise no
Reversible 1
Mounting Construction 2
IM B3 B5 V1 3
Horizontal Motor Starting
Vertical With Drive End at Top
Vertical With Drive End at Bottom
Foot Mounted Flange Mounted 100% speed
with base with anchor bolts NS
with slide base 120 x Hz
pole
Shaft Exension
Single Cylindrical WITH Key
with tapped hole
coupling furnished by 100% torque =
Machine maker Motor Maker 9552 x kw
Ns
Driven Machine Datasheet at Motor Shaft
Nature
Maker Electrical requrement
Type Direct Online Starter
Power Design Max KW reactor tart
ON At Norm Opration Kw Main Terinal Box
Shaft At initial oper. W Location viewed from drive end
Load Factor % top
service continuous hr/day left
intermittent right
(Run Hr Rest Hr. )x times
No of Possible Starts
up to consecutive starts from cold and starts from hot cable entryfrom
Coupling non drive end
Direct with out axial/radial thrust vable spec
direct with axial/radial thrust ground wire
belt chain gear
MOTOR DATASHEET
Harardous clssification Safe Area
zone class
explosive group NA
ignition group NA
protective type NA
corrosive nature NA
heavy normal
installation indoor outdoor
Noise level At Indoor dB
at Full Load At Outdoor dB
Sheet No
Rev. 0
Rev. 1
Rev.2
mm
mm total amp
Torque and intertia
Driven Machine GD2 at at Ns rpm Kg/m2
Motor starting torque over %
Driven machine torque, curve
remark condition
no full load
on full load
rpm
Nm
Electrical requrement
Direct Online Starter star delta reversible
inverter drive
Main Terinal Box
Location viewed from drive end
non drive end bottom above
MOTOR DATASHEET
item No
Equip. Name
Coupling Type
Direct withradial axial thrust
belt
chain
gear
COUPLIN G DATA
Arrangement-Horizontal
Arrangement- Vertical
Diameter of driving Pulley/Sprocket
Diameter of Driven Pulley/Sprocket
Distance between axies
Height between axies
Width of driving pulley rim / Sproket
Force center from Shaft end shoulder
Rotation Speed driving pulley /Sprocket
Rotation Speed driving pulley /Sprocket
Type and nature of belt /Sprocket
Quantity of belt Sprocket
Square dimension of belt
Radial thrust on Motor Shaft as operation
Radial thrust on Motor Shaft at stop
Direction of radial thrust
Axial thrust on Motor Shaft at oper\ton
Axial thrust on Motor Shaft at Stop
Direction of Axial thrust
Over load Factor
V belt String Factor
M: Motor Driven Machine
Filling Pump
60GDE10AP001
Dosing Pump
60GDE14AP001
Filling Pump
60GDE20AP001
Dosing Pump
60GDE24AP001
Voltage V
Current A
Pump Start
Pump Stop
Emergency Stop
Acknowledgement
Pump TRIP on High
Level and Lamp
Indication
Pump TRIP on Low
Level and Lamp
Indication
Description of test
ACID SKID INHIBITOR SKID
Filling Pump
60GDE30AP001
Dosing Pump
60GDE34AP001
CAUSTIC SODA SKID