OperateIT

AC 400 Connect
Version 2.1

Reference Manual

OperateIT
AC 400 Connect
Version 2.1

Reference Manual

NOTICE
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB Automation Technology Products AB. ABB Automation Technology Products AB assumes no responsibility for any errors that may appear
in this document.
In no event shall ABB Automation Technology Products AB be liable for direct, indirect,
special, incidental or consequential damages of any nature or kind arising from the use
of this document, nor shall ABB Automation Technology Products AB be liable for incidental or consequential damages arising from use of any software or hardware described
in this document.
This document and parts thereof must not be reproduced or copied without written permission from ABB Automation Technology Products AB, and the contents thereof must
not be imparted to a third party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
Voltage Directive 72/23/EEC.
Copyright 2002 ABB Automation Technology Products AB.
All rights reserved.
Release:
Document number:

May 2002
3BSE 021 945R401

TRADEMARKS
Registrations and trademarks used in this document include:
The IndustrialIT wordmark and all product names in the form XXXXXXIT mentioned herein
are registered or pending trademarks of ABB.
Process Portal A

Trademark of ABB Ltd., Switzerland.

Microsoft

Registered trademark of Microsoft Corporation.

Windows

Registered trademark of Microsoft Corporation.

Windows 2000 and MS-DOS

Registered trademarks of Microsoft Corporation.

ActiveX and Visual Basic

Registered trademarks of Microsoft Corporation.

PostScript

Registered trademark of Adobe Systems Inc.

Acrobat Reader

Registered trademark of Adobe Systems Inc.

Ghost

Registered trademark of Symantec Corporation.

TABLE OF CONTENTS
About This Book
0.1 General ........................................................................................................................9
0.2 Use of Warning, Caution, Information, and Tip Icons ..............................................10
0.3 Document Conventions .............................................................................................11
0.4 Terminology...............................................................................................................12
0.5 Related Documentation .............................................................................................14

Section 1 - Installation ......................................................................................15


Section 2 - Faceplates
2.1 Introduction ...............................................................................................................17
2.2 Faceplate Overview ...................................................................................................20
2.2.1 Header Area ................................................................................................21
2.2.2 Status and Navigation Bar...........................................................................24
2.2.3 Faceplate Element Area ..............................................................................24
2.2.4 Buttons ........................................................................................................25
2.2.5 View Selection Buttons ...............................................................................26
2.3 Using Faceplates in Runtime.....................................................................................27

Section 3 - Faceplates and Graphic Elements


3.1 AI, Analog Input........................................................................................................31
3.1.1 Faceplate .....................................................................................................31
3.1.2 Object Display.............................................................................................38
3.1.3 Graphic Element..........................................................................................44

3BSE 021 945R401

Table of Contents

3.2 AO, Analog Output ................................................................................................... 49


3.2.1 Faceplate ..................................................................................................... 49
3.2.2 Object Display ............................................................................................ 55
3.2.3 Graphic Element ......................................................................................... 59
3.3 DI, Digital input ........................................................................................................ 63
3.3.1 Faceplate ..................................................................................................... 63
3.3.2 Object Display ............................................................................................ 67
3.3.3 Graphic Elements........................................................................................ 71
3.4 DAT, Data Base Parameters ...................................................................................... 73
3.4.1 Faceplate ..................................................................................................... 73
3.4.2 Graphic Element ......................................................................................... 81
3.5 DO, Digital output..................................................................................................... 87
3.5.1 Faceplate ..................................................................................................... 87
3.5.2 Object Display ............................................................................................ 92
3.5.3 Graphic Element ......................................................................................... 95
3.6 DRICONE, Engineered drive.................................................................................... 97
3.6.1 Faceplate ..................................................................................................... 97
3.6.2 Displays .................................................................................................... 109
3.6.3 Graphic Element ....................................................................................... 167
3.7 DRICONS, Standard drive...................................................................................... 171
3.7.1 Faceplate ................................................................................................... 171
3.7.2 Displays .................................................................................................... 183
3.7.3 Graphic Element ....................................................................................... 207
3.8 GENBIN, Binary Object ......................................................................................... 211
3.8.1 Faceplate ................................................................................................... 211
3.8.2 Object Display .......................................................................................... 219
3.8.3 Graphic Element ....................................................................................... 228
3.9 GENCON, PI Controller ......................................................................................... 233
3.9.1 Faceplate ................................................................................................... 233
3.9.2 Object Display .......................................................................................... 243
3.9.3 Graphic Element ....................................................................................... 252

3BSE 021 945R401

Table of Contents

3.10 GENUSD, User Defined Object............................................................................265


3.10.1 Faceplate .................................................................................................265
3.10.2 Object Display.........................................................................................274
3.10.3 Graphic Element......................................................................................286
3.11 GROUP ALARM, Group Alarm ...........................................................................297
3.11.1 Faceplate..................................................................................................297
3.11.2 Object Display.........................................................................................303
3.11.3 Graphic Element......................................................................................308
3.12 GROUP, Group Control.........................................................................................310
3.12.1 Faceplate .................................................................................................310
3.12.2 Object Display.........................................................................................316
3.12.3 Graphic Element......................................................................................323
3.13 AC 400 Local Devices...........................................................................................329
3.13.1 Display ....................................................................................................329
3.14 MANSTN, Manual Station....................................................................................334
3.14.1 Faceplate .................................................................................................334
3.14.2 Object Display.........................................................................................345
3.14.3 Graphic Element......................................................................................352
3.15 MOTCON, Motor Control.....................................................................................360
3.15.1 Faceplate .................................................................................................360
3.15.2 Object Display.........................................................................................368
3.15.3 Graphic Element......................................................................................377
3.16 MOTCONI, Motor Control ...................................................................................386
3.16.1 Faceplate .................................................................................................386
3.16.2 Displays...................................................................................................394
3.16.3 Graphic Element......................................................................................419
3.17 PIDCONA, Adaptive PID Ctrl ..............................................................................429
3.17.1 Faceplate .................................................................................................429
3.17.2 Object Display.........................................................................................445
3.17.3 Graphic Element......................................................................................463

3BSE 021 945R401

Table of Contents

3.18 PIDCON, PID Controller ...................................................................................... 475


3.18.1 Faceplate ................................................................................................. 475
3.18.2 Object Display ........................................................................................ 488
3.18.3 Graphic Element ..................................................................................... 498
3.19 RATSTN, Ratio Station......................................................................................... 510
3.19.1 Faceplate ................................................................................................. 510
3.19.2 Object Display ........................................................................................ 520
3.19.3 Graphic Element ..................................................................................... 528
3.20 SEQ, Sequence ...................................................................................................... 536
3.20.1 Faceplate ................................................................................................. 536
3.20.2 Object Display ........................................................................................ 544
3.20.3 Graphic Element ..................................................................................... 553
3.21 TEXT, Text data .................................................................................................... 559
3.21.1 Faceplate ................................................................................................. 559
3.21.2 ObjectDisplay ......................................................................................... 562
3.21.3 Graphic Element ..................................................................................... 564
3.22 VALVECON, Valve Control ................................................................................. 567
3.22.1 Faceplate ................................................................................................. 567
3.22.2 Object Display ........................................................................................ 573
3.22.3 Graphic Element ..................................................................................... 580

3BSE 021 945R401

About This Book


0.1 General
This book describes AC 400 Connect, which enables data retrieval from the Advant
Controller 400 Series to Process Portal A. AC 400 Connect contains built in graphic
elements and faceplates for the below listed ABB standard object types:

3BSE 021 945R401

Analog Input AI

Analog Output AO

Data Base Parameters DAT(x)

Digital Input DI

Digital Output DO

Engineered drive DRICONE

Standard drive DRICONS

Binary Object GENBIN

PI Controller GENCON

User Defined Object GENUSD

Group Alarm GROUP

Group Control GROUP

Manual Station MANSTN

Motor Control MOTCON

Motor Control MOTCONI

Adaptive PID Ctrl PIDCONA

PID Controller PIDCON

Use of Warning, Caution, Information, and Tip Icons

Ratio Station RATSTN

Sequence SEQ

Text data TEXT

Valve Control VALVECON

About This Book

The Control Connection Aspects (CCA) for each object type.

Object Display.

The graphic elements aspects of each type.

A faceplate aspect for each type.

The Object types also include additional aspects such as an Icon aspect, an Alarm
List aspect (for the instantiated object), and Trend aspect. This book is focused on
describing the graphic elements and faceplates.

0.2 Use of Warning, Caution, Information, and Tip Icons


This publication includes Warning, Caution, and Information where appropriate
to point out safety related or other important information. It also includes Tip to
point out useful hints to the reader. The corresponding symbols should be
interpreted as follows:
Electrical warning icon indicates the presence of a hazard which could result in
electrical shock.

Warning icon indicates the presence of a hazard which could result in personal
injury.

Caution icon indicates important information or warning related to the concept


discussed in the text. It might indicate the presence of a hazard which could result in
corruption of software or damage to equipment/property.
Information icon alerts the reader to pertinent facts and conditions.

10

3BSE 021 945R401

About This Book

Document Conventions

Tip icon indicates advice on, for example, how to design your project or how to use
a certain function
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all Warning and Caution notices.

0.3 Document Conventions


The following conventions are used for the presentation of material:

The words in names of screen elements (for example, the title in the title bar of
a window, the label for a field of a dialog box) are initially capitalized.

Capital letters are used for the name of a keyboard key if it is labeled on the
keyboard. For example, press the ENTER key.

Lowercase letters are used for the name of a keyboard key that is not labeled on
the keyboard. For example, the space bar, comma key, and so on.

Press CTRL+C indicates that you must hold down the CTRL key while
pressing the C key (to copy a selected object in this case).

Press ESC E C indicates that you press and release each key in sequence (to
copy a selected object in this case).

The names of push and toggle buttons are boldfaced. For example, click OK.

The names of menus and menu items are boldfaced. For example, the File
menu.

3BSE 021 945R401

The following convention is used for menu operations: MenuName >


MenuItem > CascadedMenuItem. For example: select File > New > Type.

The Start menu name always refers to the Start menu on the Windows
Task Bar.

11

Terminology

About This Book

System prompts/messages are shown in the Courier font, and user


responses/input are in the boldfaced Courier font. For example, if you enter a
value out of range, the following message is displayed:
Entered value is not valid. The value must be 0 to 30.

You may be told to enter the string TIC132 in a field. The string is shown as
follows in the procedure:
TIC132
Variables are shown using lowercase letters.
sequence name

0.4 Terminology
The following is a list of terms associated with AC 400 Connect for AC 400 Series,
that you should be familiar with. The list contains terms and abbreviations that are
unique to ABB or have a usage or definition that is different from standard industry
usage.
Term

12

Description

Control connection
aspect (CCA)

Contains the name, data type, access rights (read/write)


and subscription update rate of each attribute and the
name of the corresponding OPC item (object of the
controller). CCA also contains a user interface to inspect
the object type attribute information. It can also be used
to subscribe for the current value of each attribute.

Faceplate

Faceplates are used to monitor and control process


data. A faceplate has a configuration view where you
insert faceplate elements, buttons, status indicators and
aspect links. The faceplate can have up to three runtime views: reduced, normal and extended, depending
on how much information the user wants.

Faceplate element

Faceplate elements are used both for presentation and


modification of object properties. Faceplate elements
are object aware.

3BSE 021 945R401

About This Book

Terminology

Term

Description

Graphic display

Graphic displays are aspects directly selected and


viewed by the process operator.

Graphic element

A graphic aspect that has a reference to an Aspect


Object. Normally a part of a graphic display. A graphical
object typically built up from several subelements and/or
primitive elements. Some graphic elements are provided
by ABB, while others may be built by the user.

Examples of
Graphic Elements
provided by ABB:

 00,1
ValueField

0.0

Bar

100.0

Hscale

Graphic element
browser

A tool used to select object aware (graphic) elements in


Graphics Builder.

Graphic expression

Graphic expression is used to specify a data


subscription and a relationship between process data
and data to be displayed.

Graphic libraries

Libraries of primitive elements, and standard graphic


elements, for example faceplate element, object display
and graphic element.

Object display

A graphic aspect that has a reference to an Aspect


Object.

3BSE 021 945R401

13

Related Documentation

About This Book

0.5 Related Documentation


Category

Title

Description

Installation

OperateIT AC 400 Connect


Installation Guide

This book describes the installation


procedure for AC 400 Connect.

Software

OperateIT AC 400 Connect


Users Guide

This book describes how you connect


AC 400 Series controllers to the
Process Portal A.

OperateIT AC 400 Connect


Extended Graphics Library

This book describes the library of


optional graphic elements for
AC 400 Series controllers objects.

OperateIT AC 400 Connect


Status List

This book describes how to install,


configure and operate the AC 400
Connect Status List software.

14

3BSE 021 945R401

Section 1 Installation
AC 400 Connect is a product in the OperateIT suite package. It is installed and
configured according to the instructions in the AC 400 Connect Installation Guide.

3BSE 021 945R401

15

Section 1 Installation

16

3BSE 021 945R401

Section 2 Faceplates
2.1 Introduction
The operator can view and control the process through faceplates. The faceplate
aspect of an Aspect Object can have three runtime views:

Reduced Faceplate,
where the size and contents typically have been optimized to cover most of the
normal process operator actions. This runtime view is default.

Faceplate,
which typically covers all normal process operator actions.

Extended Faceplate,
with functions and information intended for the process engineer or the
advanced operator.

3BSE 021 945R401

17

Section 2 Faceplates

Figure 2-1 Reduced Faceplate and Faceplate


All object types do not have all Faceplate views defined. Only the Faceplate view is
defined for object types where the information to display is minimal (e.g. DAT
objects).The active Faceplate view is indicated at the bottom of the Faceplates, the
corresponding view selection button is pressed in. A non-existing view has the
corresponding view selection button dimmed.

18

3BSE 021 945R401

Section 2 Faceplates

Figure 2-2 Extended Faceplate

3BSE 021 945R401

19

Faceplate Overview

Section 2 Faceplates

2.2 Faceplate Overview


The faceplates are divided into several areas. The different areas are described
below.

Header Area
Status and Navigation
Bar

Faceplate Element
Area

Buttons

View Selection Buttons

Figure 2-3 Faceplate Terminology


The different views of a Faceplate can affect the size or look of the Status and
Navigation bar area, the Faceplate element area and the Button area.

20

3BSE 021 945R401

Section 2 Faceplates

Faceplate Overview

2.2.1 Header Area


The header is included in each Faceplate. It consists of the following areas:

Object Lock

Object Name

Object Description

Alarm Control
Object Lock

Object Name &


Object Description

Alarm
Control

Figure 2-4 Example of a Header area


When the header is displayed in an Extended Faceplate with horizontally oriented
tab controls, the header rescales as shown in Figure 2-5

Figure 2-5 Header displayed in extended Faceplate


2.2.1.1 Object Lock

The object lock button is shown as sunken from the moment the user has pressed the
object lock button until the object lock is released.
You can control the object, as long as nobody else has locked it. However, if you
lock the object yourself, you are the only person allowed to control the object during
the lock period.
In case of inactivity of operation action in the faceplate, there is a certain time-out
period until the object lock is released.

3BSE 021 945R401

21

Faceplate Overview

Section 2 Faceplates

If the object is locked by another person, the object lock button is flat, and operation
is not possible.
The table below is an overview of the different states of the object lock.
Table 2-1 Lock States Displayed in the Object Lock.
Lock status

Button

Icon

Background
Color

Unlocked

Raised

Bluegrey

Locked by me

Sunken

White

Locked by other

Flat

Yellow

If the object is locked by yourself, the button is sunken/pressed and the background
is white. If it is locked by somebody else, the background is yellow and the button is
flat.
Its easy to see when the object is released by somebody else. The button changes
from flat to raised and it turns bluegrey. To lock the object simply press the button.
Possible ways to release a lock on an object, is to either click the lock button,
another way is to close the faceplate. The object lock will also be released when the
time-out period expires.
2.2.1.2 Object Name

The object name area displays the primary name of the object. If the width of the
name area is not wide enough to display the full name this is indicated by three dots,
..., at the end of the visible text. A tooltip will always show the whole name, when
the cursor is positioned above the name.

22

3BSE 021 945R401

Section 2 Faceplates

Faceplate Overview

2.2.1.3 Object Description

The object description area displays the description of the object, and the tooltip
works the same way as in the name area.
2.2.1.4 Alarm Control

The alarm control indicates the alarm state and makes it possible to acknowledge
the object alarm from the faceplate. The table below is an overview of the different
states of the alarm.
Table 2-2 Alarm status by the alarm control
Alarm state

Acknowledge
allowed

Logical colors

0 - AlarmInActive

3BSE 021 945R401

1 - AlarmActiveAck

highAlarmSymbol

2 - AlarmInActiveUnAck

warningSymbol

3 - AlarmActiveUnAck

unackHighAlarm

4 - AlarmAutoDisabled

highAlarmSymbol

23

Faceplate Overview

Section 2 Faceplates

Table 2-2 Alarm status by the alarm control (Continued)


Alarm state
5 - AlarmDisabled

Acknowledge
allowed

Logical colors
warningSymbol

Alarm not defined = no


alarm state property
found

2.2.2 Status and Navigation Bar


The Status and Navigation bar includes status indicators for the object to the left
(IN). Status indicators shows the current result of an expression, which can include
one or several object properties. Aspect links to aspects of the object are displayed
to the right.

Figure 2-6 Example of Status and Navigation bar area

2.2.3 Faceplate Element Area


Faceplate elements are displayed in the Faceplate Element area, either alone or
included in tab groups.
The faceplate element area can include several aspects and/or tab groups. Each tab
in a tab group contains an aspect.
The faceplate element area in Figure 2-7 contains 2 tab groups with a total of 3
faceplate elements. They are sorted under the tabs, Control, Block and Limits.
Only 2 faceplate elements are displayed. In order to see the third, you would have to
select the Limits tab, since Block is currently the active tab in the right part of the
faceplate element area.

24

3BSE 021 945R401

Section 2 Faceplates

Faceplate Overview

Tab group 1

Tab group 2

Figure 2-7 Example of a faceplate element area

2.2.4 Buttons
Buttons that control properties of the object can be inserted in the button area. The
number of buttons shown per row, is dependent of the width of the view.
Pressing a button in the button area is a one-step action (Apply is not required,
although present by default).

3BSE 021 945R401

25

Faceplate Overview

Section 2 Faceplates

2.2.5 View Selection Buttons


These buttons, see Figure 2-8, enable you to choose one of the three runtime views.
If a view does not exist, the button representing that view is dimmed. The current
view is indicated by the fact that the corresponding button is sunken.

Reduced
Faceplate

Faceplate

Extended
Faceplate

Figure 2-8 View selection buttons

26

3BSE 021 945R401

Section 2 Faceplates

Using Faceplates in Runtime

2.3 Using Faceplates in Runtime


This section is an overview of how to open and use the faceplate, once it is
displayed in runtime.
In this example we open the faceplate via a graphic display. One way to open a
faceplate, via a graphic display, is to left-click on the graphic element.

Click here to open up a faceplate

Figure 2-9 Graphic Display

3BSE 021 945R401

27

Using Faceplates in Runtime

Section 2 Faceplates

The faceplate now appears in runtime. Below is an explanation of how to use the
Faceplate.

1. Object Lock

2. Alarm Control

3. Indicator

4. Aspect links

5a. Bargraph
5b. Drag handle
6. Numeric
presentation

7. Direct entry window

8. Buttons
10. Apply button
9. View Selection Buttons

Figure 2-10 Faceplate in runtime

28

3BSE 021 945R401

Section 2 Faceplates

1.

Using Faceplates in Runtime

Object Lock
Click to lock, or release the object you are currently working with. In the figure
below, the icon on the object lock button, indicates the lock status.

Unlocked

Locked by me

Locked by other

Figure 2-11 Object lock states


2.

Alarm Control
Indicates the alarm state and makes it possible to acknowledge alarm. The
different indications of the alarm is shown in the Table 2-2.

3.

Indicator
Displays the status of the object.

4.

Aspect links
Click aspect links, and different aspects of the current object will be displayed.

5.

Bargraph
The bargraph displays an object property value. You can modify that value by
dragging the drag handle up or down. If you drag the handle, or simply click
the bargraph, the direct entry window (no.7) is opened. Another way to open
the direct entry window is to click the numeric presentation window (no.5).

6.

Numeric presentation window


Displays the value of some object property.

7.

Direct entry window


Open the handle via a click in the bargraph, or in the numeric presentation
window. There are several ways to modify data after the direct entry window
has been opened.

3BSE 021 945R401

Left-click on the bargraph and drag the handle up or down. The drag
handle, not the mouse position, indicates the bargraph value.

Manually type in the value in the direct entry window.

Click the spinbuttons (up and down arrows) in the direct entry window.
This changes the value a little bit (1%)

29

Using Faceplates in Runtime

Section 2 Faceplates

Use the up and down arrow keys on the keyboard.


This changes the value a little bit (1%)

Use the Page Up and Page Down keys on the keyboard.


This changes the value more (10%), than the two previous alternatives,

Apply the value:


Click the Apply button, or Press Enter on the keyboard.
Cancel and close the direct entry window (there are several ways):
Press the Esc key on the keyboard, or click in a neutral area on the side, within
the faceplate.
8.

Buttons
Click here to control the behavior of the object. When you click on a button,
the effect on the object is direct. Apply is not needed. Apply is on the other
hand needed, when controlling to get direct effect.

9.

View Selection Buttons


The view select buttons from left to right are.

Reduced Faceplate
The size and contents typically have been optimized to cover most of the
normal process operator actions.

Faceplate
This runtime view is default and mandatory, it can not be removed.

Extended faceplate
The functions and information of the extended faceplate are intended for
the process engineer or the advanced operator.

See Introduction on page 17 for more information about, the different faceplate
views.
10. Apply button
Regardless how the value has been set, it must be applied.

30

Click on the Apply button, or

Press Enter on the keyboard.


Both Enter and Apply close the direct entry window.

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements


3.1 AI, Analog Input
3.1.1 Faceplate
Presentation:

3BSE 021 945R401

31

AI, Analog Input

Section 3 Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Button

Name and Description

Status Field

3.1

Input Blk

IN Yellow

BLOCKED = 1

Input blocked

3.2

Print Blk

P Yellow

PRINT_BLK = 1

Printout blocked

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

32

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AI, Analog Input

3.1.1.1 Control and ReducedControl

Presentation:

1
2
3

5
6
7

3BSE 021 945R401

33

AI, Analog Input

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Range Max

Black

RANGEMAX

Range Max of the MV value

High Limit 2

HI_LIM2

Alarm High limit 2

HI_LIM2 >= RANGEMAX


or EN_H2 = 0

Invisible

Filled Yellow

VALUE>H2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H2 = 1

Logical color
highAlarmSymbol

Unfilled Grey

Logical color limit

HI_LIM1

Warning High limit 1

HI_LIM1 >= RANGEMAX


or EN_H1 = 0

Invisible

Filled Yellow

VALUE>H1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H1 = 1

Unfilled Grey

Logical color limit

VALUE

Object measured value

34

High Limit 1

Measured Value
Bargraph

Green

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

Low Limit 1

Default Presentation

AI, Analog Input

Condition

Remarks

LO_LIM1

Warning Low limit 1

LO_LIM1 <= RANGEMIN


or EN_L1 = 0

Invisible

Filled Yellow

VALUE<L1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L1 = 1

Unfilled Grey

Logical color limit

LO_LIM2

Alarm Low limit 2

LO_LIM2 <= RANGEMIN


or EN_L2 = 0

Invisible

Filled Yellow

VALUE<L2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L2 = 1

Unfilled Grey

Logical color limit

Black

RANGEMIN

Range Min of the MV value

Low Limit 2

Range Min

Measured Value

8.1

MV

MV Black

8.2

MV Value

X X X Red

VALUE is Bad

No contact with Controller

? ? ? Red

ERR = 1

I/O Error

Black

VALUE

Measured value

Raised

BLOCKED = 1

Input blocked

Flat

BLOCKED = 0

Black

UNIT

8.3

MV Unit

3BSE 021 945R401

The MV object value


Text in front of the value
Logical color FaceplateFg

Measured unit

35

AI, Analog Input

Section 3 Faceplates and Graphic Elements

3.1.1.2 Limits

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

ALARM LIMITS for MV

1.1

H2 Text

H2 Black

1.2

H2 Value

Black

Condition

Remarks
Alarm limits for MV
Text in front of the value

HI_LIM2

High limit 2 value

EN_H2 = 0

Invisible

2.1

H1 Text

H1 Black

2.2

H1 Value

Black

HI_LIM1

Warning High limit 1 value

EN_H1 = 0

Invisible

Text in front of the value

3.1

L1 Text

L1 Black

3.2

L1 Value

Black

LO_LIM1

Warning Low limit 1 value

EN_L1 = 0

Invisible

4.1

36

L2 Text

L2 Black

Text in front of the value

Text in front of the value

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AI, Analog Input

No

Description

Default Presentation

Condition

Remarks

4.2

L2 Value

Black

LO_LIM2

Alarm Low limit2 value

EN_L2 = 0

Invisible

5.1

Alarm Delay Text

Alarm Delay Black

5.2

Alarm Delay Value

Black

Text in front of the value


ALARM_DELAY

Alarm Delay value

3.1.1.3 Block

Presentation:

Behavior::
No

Description

Default Presentation

Block Input

Block Input Black

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

BLOCKED = 1

Deblock pressed

BLOCKED = 0

Remarks

37

AI, Analog Input

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

Block Alarm

Block Alarm Black

Block Printout

Condition

Yellow

Blocked

Block pressed

AL_BLK=1

Deblock pressed

AL_BLK = 0

Remarks

Block Printout Black

Yellow

Blocked

Block pressed

PR_BLK = 1

Deblock pressed

PR_BLK=0

3.1.2 Object Display


Presentation:
2

4 3

9
10
11
12
13

5
7

14
15
16
17
18
19

20
21
22
23
25

38

24

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AI, Analog Input

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Logical color
selected

Grey

SELECTED = 0

Logical color
static

NAME and DESCR

Object Name and


Description

Red flashing

AL_UNACK = 1

Logical color
unackHighAlarm

Yellow

BLOCKED = 1

Logical color
blockedText

Red

DISTURB = 1 or
ERR = 1

Logical color
highAlarmText

Header

Green

Logical color
text2Normal
Logical color static

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

CLASS

Object class

Range Max

Green

RANGEMAX

Range Max of the MV value

Range Min

Green

RANGEMAX

Range Min of the MV value

Measured Value Trim


Curve

VALUE

Object value - Trim curve

VALUE

Object measured value

8.1

Measured Value
Bargraph

3BSE 021 945R401

PROC_SEC

Process section
Text in front of the value

Green

Green

39

AI, Analog Input

No

Description

8.2

High Limit 2

Section 3 Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

HI_LIM2

Alarm High limit 2

HI_LIM2 >= RANGEMAX


or EN_H2 = 0

Invisible

Filled Yellow

VALUE>H2 = 1 and
AL_BLK = 1

Logical color

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H2 = 1

blocked Symbol

Unfilled Grey
8.3

High Limit 1

HI_LIM1

Warning High limit 1

HI_LIM1 >= RANGEMAX


or
EN_H1 = 0

Invisible

Filled Yellow

VALUE>H1 = 1 and
AL_BLK = 1

Logical color

AL_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol
Filled Red

VALUE>H1 = 1

Unfilled Grey
8.4

Low Limit 1

LO_LIM1

Warning Low limit 1

LO_LIM1 <= RANGEMIN


or
EN_L1 = 0

Invisible

Filled Yellow

VALUE<L1 = 1 and
AL_BLK = 1

Logical color

AL_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol
Filled Red

VALUE<L1 = 1

Unfilled Grey

40

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

8.5

Low Limit 2

Default Presentation

AI, Analog Input

Condition

Remarks

LO_LIM2

Alarm Low limit 2

LO_LIM2 <= RANGEMIN


or
EN_L2 = 0

Invisible

Filled Yellow

VALUE<L2 = 1 and
AL_BLK = 1

Logical color

AL_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol
Filled Red

VALUE<L2 = 1

Unfilled Grey
9

ALARM LIMITS for MV

Alarm limits for MV

9.1

Printout Blocked

Yellow

PR_BLK = 1

Printout blocked

9.2

Alarm Blocked

Yellow

AL_BLK = 1

Alarm blocked by operator

AL_P_BLK = 1

Alarm blocked by PCprogram

VALUE>H2 = 1

Alarm High limit 2

Bx Yellow
9.3

Alarm Indication

Red

9.4

H2 Text

H2 Grey

9.5

H2 Value

Green

HI_LIM2

High limit 2 value

EN_H2 = 0

Invisible

Text in front of the value

10.1

Printout Blocked

Yellow

PR_BLK = 1

Printout blocked

10.2

Alarm Blocked

Yellow

AL_BLK = 1

Alarm blocked by operator

AL_P_BLK = 1

Alarm blocked by PCprogram

VALUE>H1 = 1

Warning High limit 1

Bx Yellow
10.3

Alarm Indication

10.4

H1 Text

H1 Grey

10.5

H1 Value

Green

HI_LIM1

Warning High limit 1 value

EN_H1 = 0

Invisible

PR_BLK = 1

Printout blocked

11.1

Printout Blocked

3BSE 021 945R401

Red

Yellow

Text in front of the value

41

AI, Analog Input

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

11.2

Alarm Blocked

AL_BLK = 1

Alarm blocked by operator

AL_P_BLK = 1

Alarm blocked by PCprogram

VALUE<L1 = 1

Warning Low limit 1

Yellow

Bx Yellow
11.3

Alarm Indication

Red

11.4

L1 Text

L1 Grey

11.5

L1 Value

Green

LO_LIM1

Warning Low limit 1 value

EN_L1 = 0

Invisible

Text in front of the value

12.1

Printout Blocked

Yellow

PR_BLK = 1

Printout blocked

12.2

Alarm Blocked

Yellow

AL_BLK = 1

Alarm blocked by operator

AL_P_BLK = 1

Alarm blocked by PCprogram

VALUE<L2 = 1

Alarm Low limit 2

Bx Yellow
12.3

Alarm Indication

Red

12.4

L2 Text

L2 Grey

12.5

L2 Value

Green

LO_LIM2

Alarm Low limit2 value

EN_L2 = 0

Invisible

13.1

Alarm Delay Text

Alarm Delay Grey

13.2

Alarm Delay Value

Green

14

STATUS

14.1

Updated Indication

14.2

Updated text

15.1

Manual entry Indication

15.2

Manual entry text

16.1

Alarm period block


Indication

16.2

Alarm period block text

42

Text in front of the value

Text in front of the value


ALARM_DELAY

Alarm Delay value


Status

Green

UPDATED = 1

Updated Grey
Green

Updated
Updated text

MAN_ENTR = 1

Manual entry flag

AL_P_BLK = 1

Alarm blocked by PCprogram

Man Entry Grey


Yellow

Alarm Period Blk

Text behind the indication

Yellow

AL_P_BLK = 1

Grey

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

17.1

Disturbance Indication

17.2

Disturbance text

18.1

Signal error Indication

18.2

Signal error text

19.1

Overflow Indication

19.2

Overflow text

Default Presentation
Red

AI, Analog Input

Condition

Remarks

DISTURB = 1

Fault

Disturbance

Text behind the indication

Red

DISTURB = 1

Grey

Red

ERR = 1

Signal Error

Text behind the indication

Red

ERR = 1

Grey

Red

I/O Error

OVERFLOW = 1

Overflow

Overflow
Text behind the indication

Red

OVERFLOW = 1

Grey

20

PARAMETERS

Parameters

20.1

Implemented Indication

20.2

Implemented text

21.1

Normal treat Indication

21.2

Normal treat text

22.1

No overflow Indication

22.2

No overflow text

23.1

Tested Indication

23.2

Tested text

Tested Grey

Tested text

24.1

MV Text

MV Grey

Text in front of the value

24.2

MV Value

? ? ? Red

ERR = 1

I/O Error

Green

VALUE

Measured value

Green

ACT = 1

Implemented Grey
Green

Implemented text
NORM_TR = 1

Normal Treated Grey


Green

Normal object treat


Normal object treat text

OVF_CTRL = 1

No Overflow Grey
Green

Implemented

No error at overflow
No error at overflow text

TESTED = 1

Tested

24.3

MV Unit

Green

UNIT

Measured unit

25

Input Blocked

Input Blocked Yellow

BLOCKED = 1

Input blocked

BLOCKED = 0

Invisible

3BSE 021 945R401

43

AI, Analog Input

Section 3 Faceplates and Graphic Elements

3.1.3 Graphic Element


3.1.3.1 NumericMV01 and UnitMV01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

VALUE

Object value

X X X Red

VALUE is Bad

No contact with Controller

? ? ? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

ERR = 1

I/O Error

Yellow

BLOCKED =1

Input blocked

Invisible
2

44

Measured Value

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

!
p

AI, Analog Input

Default Presentation

Condition

Remarks

Red

DISTURB = 1

Alarm

Green

Unit

Object unit
Green

UNIT

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

45

AI, Analog Input

Section 3 Faceplates and Graphic Elements

3.1.3.2 BargraphMV01

Presentation:

1
4
5
2

3
6
7

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object select frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged

? Yellow

ERR = 1 and
BLOCKED = 1

Input blocked

? Red

ERR = 1

I/O Error

ERR = 0

Invisible

46

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

MV Value

Default Presentation

Condition

Remarks

VALUE

The object value

ERR = 1

Invisible - I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged

Yellow

BLOCKED = 1

Input blocked

Red

DISTURB = 1

Alarm

Green

High Limit 2

HI_LIM2

Alarm High limit 2

HI_LIM2 >= RANGEMAX


or EN_H2 = 0

Invisible

Filled Yellow

VALUE>H2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H2 = 1

Unfilled Grey

High Limit 1

HI_LIM1

Warning High limit 1

HI_LIM1 >= RANGEMAX


or EN_H1 = 0

Invisible

Filled Yellow

VALUE>H1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H1 = 1

Unfilled Grey

Low Limit 1

3BSE 021 945R401

AI, Analog Input

LO_LIM1

Warning Low limit 1

LO_LIM1 <= RANGEMIN


or EN_L1 = 0

Invisible

Filled Yellow

VALUE<L1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

47

AI, Analog Input

No

Section 3 Faceplates and Graphic Elements

Description

6
cont.

Default Presentation

Condition

Remarks

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L1 = 1

Unfilled Grey

Low Limit 2

LO_LIM2

Alarm Low limit 2

LO_LIM2 <= RANGEMIN


or EN_L2 = 0

Invisible

Filled Yellow

VALUE<L2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L2 = 1

Unfilled Grey

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

48

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AO, Analog Output

3.2 AO, Analog Output


3.2.1 Faceplate
Presentation:

3BSE 021 945R401

49

AO, Analog Output

Section 3 Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

Default Presentation

Condition

Remarks

M Cyan

MAN_MODE = 1

Manual Mode

A Magenta

MAN_MODE = 0

Auto Mode
Output blocked

3.2

Output Blk

OUT Yellow

OUTP_BLK = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

50

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Object Type Help

position 0, 0, 12

Decr

Decrease value with 1%

MAN_MODE = 1

Decrease

Incr

Increase value with 1%

MAN_MODE = 1

Increase

Man

Set to Man Mode

Set MAN_MODE = 1

Auto

Set to Auto Mode

Set MAN_MODE = 0

4
cont.
5

AO, Analog Output

Remarks

3.2.1.1 Control and ReducedControl

Presentation:

1
2

3BSE 021 945R401

51

AO, Analog Output

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

1.1

Range Max

Black

RANGEMAX

1.2

Range Min

Black

RANGEMIN

High Limitation

Remarks

HI_LIM

High limitation

HI_LIM > RANGEMAX or


EN_HI = 0

Invisible

Yellow

EN_HI = 1 and
VALUE_HI = 1

Grey

EN_HI = 1

Output Value Bargraph

VALUE

Object output value

Cyan

MAN = 1

Manual mode

Magenta

MAN = 0

Auto mode

LO_LIM

Low limitation

LO_LIM < RANGEMIN or


EN_LO = 0

Invisible

Yellow

EN_LO = 1 and
VALUE_LO = 1

Grey

EN_LO = 1

Low Limitation

Output Value

5.1

Text

OUT Black

5.2

Value

XXX Red

Value is Bad

Black, Raised

MAN = 1

Manual mode

Black, Flat

MAN = 0

Auto mode

Black

UNIT

5.3

Unit

Input Field

VALUE

52

Text in front of value

MAN = 1

input blocked

MAN = 0

Invisible

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AO, Analog Output

3.2.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Block Output

Block Output Black

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

BLOCKED = 1

Deblock pressed

BLOCKED = 0

Remarks

53

AO, Analog Output

Section 3 Faceplates and Graphic Elements

3.2.1.3 Limits

Presentation:

1
2

Behavior:
No

Description

LIMITATIONS

1.1

H Text

H Black

1.2

H Value

Black

HI_LIM

High limitation value

EN_HI = 1 and
VALUE_HI = 1

Invisible

Raised

MAN = 1

Manual mode

Flat

MAN = 0

Auto mode

Black

UNIT

1.3

1.4

Default Presentation

Condition

Remarks
Limitations for OUT
Text in front of the value

2.1

L Text

L Black

2.2

L Value

Black

LO_LIM

Low limitation value

LO_LIM < RANGEMIN or


EN_LO = 0

Invisible

Raised

MAN = 1

Manual mode

Flat

MAN = 0

Auto mode

Black

UNIT

2.3

2.4

54

Text in front of the value

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AO, Analog Output

3.2.2 Object Display


Presentation:
8

9
10

11

12
13
14
15
16

20
19

18

17

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Logical color
select

Grey

SELECTED = 0

Logical color
static

3BSE 021 945R401

55

AO, Analog Output

No

Description

Header

Section 3 Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

NAME and DESCR

Object Name and


Description

Red flashing

AL_UNACK =1

Unacknowledged

Yellow

OUTP_BLK = 1

Output blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

Manual mode

Magenta

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

Range Max
Cyan

Text in front of the value


PROC_SEC

Text in front of the value


CLASS

Object class

RANGEMAX

Range max of the Output


value

MAN = 1

Manual mode

Magenta
6

Range Min
Cyan

Auto mode
RANGEMIN

Range min of the Output


value

MAN = 1

Manual mode

Magenta
7

8.1

56

Output Value Trim Curve

Process section

Auto mode
VALUE

Object output value

Cyan

MAN = 1

Manual mode

Magenta

Auto mode

VALUE

Object output value

Cyan

MAN = 1

Manual mode

Magenta

Auto mode

Output Value Bargraph

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

8.2

High Limitation

8.3

Default Presentation

Condition

Remarks

HI_LIM

High limitation

HI_LIM > RANGEMAX or


EN_HI = 0

Invisible

Yellow

EN_HI = 1 and
VALUE_HI = 1

Grey

EN_HI = 1

Low Limitation

LIMITATIONS

9.1

High Limitation
Indication

9.2

H Text

9.3

H Value

10.1

Low Limitation Indication

10.2

L Text

10.3

L Value

11

STATUS

11.1

Signal Error Indication

3BSE 021 945R401

AO, Analog Output

LO_LIM

Low limitation

LO_LIM < RANGEMIN or


EN_LO = 0

Invisible

Yellow

EN_LO = 1 and
VALUE_LO = 1

Grey

EN_LO = 1
Limitations for OUT
Yellow

VALUE_HI = 1

H Grey

High limitation flag


Text in front of the value

HI_LIM

High limitation value

EN_HI = 1 and
VALUE_HI = 1

Invisible

Cyan

MAN = 1

Manual mode

Magenta

Auto mode

VALUE_LO = 1

Low limitation flag

Yellow

L Grey

Text in front of the value


LO_LIM

Low limitation value

LO_LIM < RANGEMIN or


EN_LO = 0

Invisible

Cyan

MAN = 1

Manual mode

Magenta

Auto mode
Status

Red

ERR = 1

Signal error

57

AO, Analog Output

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

11.2

Signal Error Text

Signal Error

Condition

Remarks
Signal error text

Red

ERR = 1

Grey

12

PARAMETERS

12.1

Implemented Indication

12.2

Implemented Text

13.1

Use Max Limitation


Indication

13.2

Use Max Lim Text

14.1

Use Min Limitation


Indication

14.2

Use Min Lim Text

15.1

Output Restart Indication

15.2

Output Restart Text

16.1

Tested Indication

16.2

Tested Text

Tested Grey

Tested text

17.1

OUT Text

OUT Grey

Text in front of the value

17.2

OUT Value

17.3

18

Parameters
Green

Implemented Grey
Green

Green

EN_HI = 1

EN_LO = 1

Use min limitation


Use min lim text

RESTART = 1

Output Restart Grey


Green

Use max limitation


Use max lim text

Use Min Lim Grey


Green

Implemented
Implemented text

Use Max Lim Grey

Output restart
Output restart text

TESTED = 1

Tested

VALUE
Cyan

MAN = 1

Manual mode

Magenta

Auto mode

OUT Unit

Output Blocked

IMPLEMENTED = 1

UNIT
Cyan

MAN = 1

Manual mode

Magenta

Auto mode

Output Blocked

OUTP_BLK = 1

Output blocked

OUTP_BLK = 0

Invisible

MAN = 0

Auto mode

Yellow
19.1

58

Auto Indication

Magenta

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

19.2

Auto Text

Auto

20.1

Man Indication

20.2

Man Text

AO, Analog Output

Condition

Remarks
Auto text

Magenta

MAN = 0

Auto mode

Grey

MAN = 1

Manual mode

MAN = 1

Manual mode

Cyan

Man

Manual text

Cyan

MAN = 1

Manual mode

Grey

MAN = 0

Auto mode

3.2.3 Graphic Element


3.2.3.1 NumericOUT01 and UnitOUT01

Presentation:

1
2

3BSE 021 945R401

59

AO, Analog Output

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Logical color
select

Invisible

SELECTED = 0

Output Value

Unit

VALUE

Object value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Yellow

OUTP_BLK = 1

Output blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

Magenta

MAN = 0

Green

UNIT

Object unit

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

60

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

AO, Analog Output

3.2.3.2 BargraphOUT01

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object select frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Output Value

3BSE 021 945R401

VALUE

The object value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Yellow

OUTP_BLK =1

Output blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

61

AO, Analog Output

No

Description

2
cont.
3

Section 3 Faceplates and Graphic Elements

Default Presentation

Condition

Magenta

MAN = 0

High Limitation

Yellow

Remarks

HI_LIM

High limitation

HI_LIM > RANGEMAX or


EN_HI = 0

Invisible

EN_HI = 1 and
VALUE_HI = 1

Grey
4

Low Limitation

Yellow

EN_HI = 1
LO_LIM

Low limitation

LO_LIM < RANGEMIN or


EN_LO = 0

Invisible

EN_LO = 1 and
VALUE_LO = 1

Grey

62

EN_LO = 1

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DI, Digital input

3.3 DI, Digital input


3.3.1 Faceplate
Presentation:

3BSE 021 945R401

63

DI, Digital input

Section 3 Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Button

Name and Description

Status Field

3.1

Input Blk

IN Yellow

BLOCKED = 1

Input Blocked

3.2

Print Blk

P Yellow

PRINT_BLK = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Set VALUE to one

BLOCKED = 1

Set VALUE = 1

Set VALUE to zero

BLOCKED = 1

Set VALUE = 0

64

On
Off

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DI, Digital input

3.3.1.1 Control and ReducedControl

Presentation:

Behavior:
No

Description

Value Text

Default Presentation

Condition

On Black

VALUE = 1

Off Black

VALUE = 0

Remarks

Value

3BSE 021 945R401

Green

VALUE = 1

Green border

VALUE = 0

65

DI, Digital input

Section 3 Faceplates and Graphic Elements

3.3.1.2 Block

Presentation:

1
2

3
4

Behavior::
No

Description

Default Presentation

Block Input

Block Input Black

Block Alarm

Block Printout

Yellow

Blocked

Block pressed

BLOCKED = 1

Deblock pressed

BLOCKED = 0

Remarks

Block Alarm Black

Yellow

Blocked

Block pressed

AL_BLK=1

Deblock pressed

AL_BLK = 0

Block Printout Black

Yellow

Blocked

Block pressed

PR_BLK = 1

Deblock pressed

PR_BLK=0

4.1

Alarm Delay Text

Alarm Delay Black

4.2

Alarm Delay Value

Black

66

Condition

Text in front of the value


ALARM_DELAY

Alarm Delay value

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DI, Digital input

3.3.2 Object Display


Presentation:
2

1
22
6
7
8
9
10
11

12
13
14
15
16
17
18
19
21

3BSE 021 945R401

20

67

DI, Digital input

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object Name and


Description

Red flashing

AL_UNACK = 1

Unacknowledged

Yellow

BLOCKED = 1

Input blocked

Red

DISTURB = 1 or
ERR = 1

Alarm

Green

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

CLASS

5.1

Value Trim Curve

Green

VALUE

5.2

Range Indicators

Filled Grey

Top indicator

Unfilled Grey

Bottom indicator

STATUS

6.1

Updated Indication

6.2

Updated text

7.1

Manual entry Indication

7.2

Manual entry text

8.1

Alarm period block


Indication

8.2

Alarm period block text

68

Text in front of the value


PROC_SEC

Process section
Text in front of the value
Object class

Status
Green

UPDATED = 1

Updated

MAN_ENTR = 1

Manual entry flag

Updated Grey
Green

Man Entry Grey


Yellow

Man Entry text


AL_P_BLK = 1

Alarm Period Blk

Alarm blocked by PCprogram


Alarm Period Blk text

Yellow

AL_P_BLK = 1

Grey

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

No

Description

9.1

Disturbance Indication

9.2

Disturbance Text

10.1

Signal error Indication

10.2

Signal error Text

11.1

Repeat fail block


Indication

11.2

Repeat fail block text

12

PARAMETERS

12.1

Alarm block Indication

12.2

Alarm block Text

13.1

Printout Indication

13.2

Printout Text

14.1

Implemented Indication

14.2

Implemented text

3BSE 021 945R401

Default Presentation

DI, Digital input

Condition

Remarks

Red flashing

AL_UNACK = 1

Unacknowledged

Red

DISTURB = 1

Fault

Disturbance

Disturbance text

Red

AL_UNACK = 1 or
DISTURB = 1

Grey

Red

ERR = 1

Signal Error

Signal Error text

Red

ERR = 1

Grey

Yellow

I/O Error

RP_F_BLK = 1

Repeat Fail Block

Repeat fail blocked


Repeat fail blocked text

Yellow

RP_F_BLK = 1

Grey

Parameters
Yellow

Alarm Block = 1

Alarm Block

Alarm blocked text

Yellow

Alarm Block = 1

Grey

Yellow

PR_BLK = 1

Printout Block
PR_BLK = 1

Grey

Implemented Grey

Printout blocked
Printout blocked text

Yellow

Green

Alarm blocked by operator

ACT = 1

Implemented
Implemented text

69

DI, Digital input

No

Description

15.1

Normal treat Indication

15.2

Normal treat text

16.1

Normal position
Indication

16.2

Normal position text

17.1

Repeat Fail Control


Indication

17.2

Repeat Fail Control text

Section 3 Faceplates and Graphic Elements

Default Presentation
Green

Condition

Remarks

NORM_TR = 1

Normal object treat

Normal Treat Grey

Normal object treat text

Green

NORM_POS = 1

Green

NORM_POS = 0

Normal Position Grey


Green

Normal position

Normal position text


RP_F_CTL = 1

Repeat Fail Control

Repeat fail control


Repeat fail control text

Grey
18.1

Inverted Indication

18.2

Inverted text

19.1

Tested Indication

19.2

Tested text

Tested Grey

Tested text

20.1

MV Text

MV Grey

Text in front of the value

20.2

Value

21

Input Blocked

Green

Inverted Grey
Green

Inverted
Inverted text

TESTED = 1

Tested

3D Display object
Green

VALUE = 1

Symbol released

Black/Green borders

VALUE = 0

Symbol pressed in

BLOCKED = 1

Input blocked

BLOCKED = 0

Invisible

Input Blocked Yellow

22.1

Alarm Delay Text

Alarm Delay Grey

22.2

Alarm Delay Value

Green

70

INV = 1

Text in front of the value


ALARM_DELAY

Alarm Delay value

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DI, Digital input

3.3.3 Graphic Elements


3.3.3.1 IndicatorBox01

Presentation:

1
3
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Invisible

VALUE

3D Display object

Black

ERR = 1

I/O Error

Black

(Inverted = 1 and VALUE = 1) Inverted or Off


or

Symbol Center Color

VALUE = 0
Flashing Red

AL_UNACK = 1

Unacknowledged alarm

Yellow

BLOCKED = 1

Updated blocked

DISTURB = 1 and

Alarm

Red

DisturbanceUsed = 1
Green

3BSE 021 945R401

VALUE = 1

71

DI, Digital input

Section 3 Faceplates and Graphic Elements

No

Description

Indicator

3.1

Quality

Default Presentation

Condition

Remarks

Q Flashing Red

AL_UNACK = 1 and

Unacknowledged alarm

ERR = 1

3.2

Label

Q Yellow

BLOCKED = 1 and
ERR = 1

Updated blocked

Q Red

ERR = 1

I/O Error

Label Grey

User defined character

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

2. Symbol

false, true

Disturbance Used

2. Symbol

true, false

Label

3. Label

, any letter

FrameWidth

1. Lock Frame

3, (0...5)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

72

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

3.4 DAT, Data Base Parameters


3.4.1 Faceplate
Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

On

Set Boolean to one

VAL_TYPE = 1

Set B0_VAL = 1

Off

Set Boolean to zero

VAL_TYPE = 1

Set B0_VAL = 0

Aspect Links

Object Type Help

position 0, 0, 12

3BSE 021 945R401

73

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

On

Set Boolean to one

VAL_TYPE = 1

B0_VAL = 1

Off

Set Boolean to zero

VAL_TYPE = 1

B0_VAL = 0

74

1 - 15 On

B1_VAL...B15_VAL = 1

1 - 15 Off

B1_VAL...B15_VAL = 0

16 - 31 On

B16_VAL...B31_VAL = 1

16 - 31 Off

B16_VAL...B31_VAL = 0

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?)

VAL_TYPE not 2

Illegal datatype

Green

VALID = 1

Object validity

Green

VALID = 0

Input Field

Valid flag

Aspect Links

3BSE 021 945R401

Object Type Help

position 0, 0, 12

75

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?) Green

VAL_TYPE not 3

Illegal datatype

Green

VALID = 1

Object validity

Green

VALID = 0

Input Field

Valid flag

76

Aspect Links

Object Type Help

position 0, 0, 12

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?) Green

VAL_TYPE not 127

Illegal datatype

Year

100-9999

Month

1-12

Day

1-31

Input Field

Valid flag

3BSE 021 945R401

Green

VALID = 1

Green

VALID = 0

Object validity

77

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?) Green

VAL_TYPE not 126

Illegal datatype

Hour

0-24

Min

0-59

Sec

0-59

78

Input Field

Valid flag

Green

VALID = 1

Green

VALID = 0

Object validity

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?) Green

VAL_TYPE not 4

Illegal datatype

Green

VALID = 1

Object validity

Green

VALID = 0

Input Field

Valid flag

Aspect Links

3BSE 021 945R401

Object Type Help

position 0, 0, 12

79

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

3.4.1.1 Control and ExtendedControl

Presentation:

2
1

Behavior:
No

Description

Default Presentation

Condition

Remarks

Value

Black

VALUE

The object value

DAT(?)

VAL_TYPE not 1

Illegal datatype

Green

VALID = 1

Object validity

Green

VALID = 0

80

Valid flag

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

3.4.2 Graphic Element


3.4.2.1 IndicatorText01

Presentation:

Note! Use this graphic element only for datatype Boolean!

Behavior:
No

Description

Background

Default Presentation

Condition

Black

Remarks

String

The object value - String

On

Green

Off Green

VALUE = true

TrueString

VALUE = false

FalseString

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

TrueString

2. String

On

FalseString

2. String

Off

NumberOfChar

2. String

40, (1..40)

Alignment

2. String

1=Left, 2=Center, 3=Right

Bitno

2. String

1, (1...32)

FrameWidth

3, (1...4)

FrameStyle

Flat, Raised, Sunken

3BSE 021 945R401

Text position in field

81

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

3.4.2.2 IndicatorBox01

Presentation:

Note! Use this graphic element only for datatype Boolean!

Behavior:
No

Description

Background

Default Presentation

Condition

Black

Indicator

Remarks

The object value Indication


Filled Green

VALUE = true

Unfilled Green

VALUE = false

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

3, (1..4)

FrameStyle

Flat, Raised, Sunken

Bitno

82

2. String

1, (1..32)

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

3.4.2.3 Numeric01

Presentation:

1
2

1
2

1
2

3BSE 021 945R401

83

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Black

Remarks

Value

VALUE

The object value

DAT(?) Green

Illegal datatype

Green

VAL_TYPE in range 2...4

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

NumberOfDec

2. Value

FrameWidth

3, (1..4)

FrameStyle

Flat, Raised, Sunken

NumberOfChar

84

2. Value

Number of decimals of the


presented value if datatype is
Real.

Including . and -

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DAT, Data Base Parameters

3.4.2.4 Date01

Presentation:

1
2

1
2

Behavior:
No

Description

Background

Default Presentation

Condition

Black

Value

VALUE

*** Green

Remarks

The object value

Internal overflow in
calculations.

DAT(?) Green

Illegal datatype

Green

VAL_TYPE = 3

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DateFormat

2. Value

1, 2

FrameWidth

1. Frame

3, (1..4)

3BSE 021 945R401

1 Long Date for 2 Short Date

85

DAT, Data Base Parameters

Section 3 Faceplates and Graphic Elements

3.4.2.5 Time01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Black

Remarks

Value

VALUE

*** Green

Internal overflow in
calculations.

DAT(?) Green
Green

The object value

Illegal datatype
VAL_TYPE = 3

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

TimeFormat

2. Value

0, 1, 2

0 = Hour Min Sec


1 = Hour Min
2 = Hour Min Sec Millisec

UnitsPerSecond

2. Value

10000

One second represented by


this value

FrameWidth

1. Frame

3, (1..4)

86

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DO, Digital output

3.5 DO, Digital output


3.5.1 Faceplate
Presentation:

3BSE 021 945R401

87

DO, Digital output

Section 3 Faceplates and Graphic Elements

2
1
4

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

Default Presentation

Condition

M Cyan

MAN_MODE = 1

A Magenta

MAN_MODE = 0

3.2

Output Blk

OUT Yellow

OUTP_BLK = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

88

Remarks

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DO, Digital output

No

Description

Default Presentation

Condition

Remarks

On

Set VALUE to one

MAN_MODE = 1

Set VALUE = 1

Off

Set VALUE to zero

MAN_MODE = 1

Set VALUE = 0

Man

Set to Man Mode

Set MAN_MODE = 1

Auto

Set to Auto Mode

Set MAN_MODE = 0

3.5.1.1 Control and ReducedControl

Presentation:

3BSE 021 945R401

89

DO, Digital output

Section 3 Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Text Value

1.1

On

On Black

VALUE = 1

1.2

Off

Off Black

VALUE = 0

Indication

Remarks
Status Line

VALUE = 1
VALUE = 0
Color

90

Cyan

MAN = 1

Manual Mode

Magenta

MAN = 0

Auto Mode

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DO, Digital output

3.5.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Block Output

Block Output Black

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

OUTP_BLK = 1

Deblock pressed

OUTP_BLK = 0

Remarks

91

DO, Digital output

Section 3 Faceplates and Graphic Elements

3.5.2 Object Display


Presentation:
2

4 3

7
8
9
10

14
13

12

92

11

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DO, Digital output

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object Name and


Description

Red flashing

AL_UNACK =1

Unacknowledged

Yellow

OUTP_BLK = 1

Output blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

Manual mode

Magenta

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

5.1

Value Trim Curve

5.2

Range Indicators

STATUS

6.1

Signal error Indication

6.2

Signal error Text

Parameters

7.1

Implemented Indication

7.2

Implemented Text

3BSE 021 945R401

Text in front of the value


PROC_SEC

Process section
Text in front of the value

CLASS

Object class

VALUE

Value

Cyan

MAN = 1

Magenta

Filled

Top indicator

Unfilled

Bottom indicator
Status

Red

ERR = 1

Signal Error

I/O Error
Signal Error text

Red

ERR = 1

Grey

Parameters
Green

Implemented Grey

ACT = 1

Implemented
Implemented text

93

DO, Digital output

Section 3 Faceplates and Graphic Elements

No

Description

Default Presentation

8.1

Tested Indication

8.2

Tested Text

9.1

Inverted Indication

9.2

Inverted Text

Inverted Grey

10.1

Start Value Indication

Last Val Green

Green

Condition

Remarks

TESTED = 1

Tested

Tested Grey
Green

Tested text
INV = 1

Inverted
Inverted text

RESTART = 1

Green

STVAL = 1 and RESTART


=0

Green

STVAL = 0 and RESTART


=0

Start value

10.2

Start Value Text

Start Value Grey

Start Value text

11.1

OUT Text

OUT Grey

Text in front of the value

11.2

Value

Color

12

Output Blocked

3D Display object
VALUE = 1

Symbol released

VALUE = 0

Symbol pressed in

Cyan

MAN = 1

Magenta

Output Blocked

OUTP_BLK = 1

Output blocked

OUTP_BLK = 0

Invisible

MAN = 0

Auto mode

Yellow
13.1

Auto Indication

13.2

Auto Text

14.1

Man Indication

14.2

Man Text

94

Magenta

Auto

Auto text

Magenta

MAN = 0

Auto mode

Grey

MAN = 1

Manual mode

MAN = 1

Manual mode

Cyan

Man

Manual text

Cyan

MAN = 1

Manual mode

Grey

MAN = 0

Auto mode

3BSE 021 945R401

Section 3 Faceplates and Graphic Elements

DO, Digital output

3.5.3 Graphic Element


3.5.3.1 IndicatorBox01

Presentation:

1
3
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

SELECTED = 0

Invisible

VALUE

3D Display object

Black

(Inverted = 1 and VALUE = 1)


or VALUE = 0

Inverted or Off

Flashing Red

AL_UNACK = 1

Unacknowledged alarm

Yellow

OUTP_BLK = 1

Updated blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

Magenta

MAN = 0

Symbol Center Color

Label

User defined character


Label Grey

3BSE 021 945R401

95

DO, Digital output

Section 3 Faceplates and Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

2. Symbol

false, true

Label

3. Label

, any letter

FrameWidth

1. Lock Frame

3, (0...5)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

96

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6 DRICONE, Engineered drive


3.6.1 Faceplate
Presentation:

3BSE 021 945R401

97

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

98

Default Presentation

Condition

M Dark green

BOOL_A = 1 and
BOOL_B = 0 and
IND2_09 = 1

A Dark green

BOOL_A = 0 and
BOOL_B = 1 and
IND2_09 = 1

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Default Presentation

Condition

Remarks

3.2

Control point

O Light brown

IND2_00 = 0

Out of service.

D Yellow

IND2_09 = 0

Drive local

J Yellow

IND2_09 = 1 and
BOOL_C = 1

Jog running from motor


place

L Dark green

IND2_09 = 1 and
BOOL_D = 1

Local controlled from


local panel

C Dark green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central controlled from


operators panel

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Interlock indications

X Yellow

(IND2_12 = 1 and IND2_02 = 1


and BOOL_F = 1
and IND2_15 = 0)
or
(IND2_13 = 1 and IND2_02 = 1
and BOOL_F = 1)

B- Interlock 3

(IND2_08 = 1) or
(IND2_10 = 1 and IND2_15 = 0 )
or
IND2_11 = 1
or
(IND2_12 = 1 and BOOL_F = 0
and IND2_15 = 0 )
or
(IND2_12 = 1 and IND2_02 = 0
and BOOL_F = 1
and IND2_15 = 0)
or
(IND2_13 = 1 and BOOL_F = 0)
or
(IND2_13 = 1 and IND2_02 = 0
and BOOL_F = 1)
or
IND2_14 = 1

C - interlock

BX Red

IND1_15 = 1

Override Interlock and


Interlock active

BX Yellow

(BOOL_C = 1 or IND2_15 = 1)
and IND1_15=0

Override Interlock and


Interlock active

X Green

3BSE 021 945R401

B - Interlock 4

B - Interlock 1
B - Interlock 2
B- Interlock 3

B - Interlock 4

IA- Interlock

99

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Aspect links

Diagnostic Fault Display

position 0, 0, 5

Diagnostic Alarm Display

position 0, 0, 6

Status and Limit Display

position 0, 0, 7

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0 , 12

100

Remarks

Start

Start motor

Set MORD_02 = 1

Stop

Stop motor

Set MORD_03 = 1

Man

Set to Man Mode

Set MORD_14 = 1

Auto

Set to Auto Mode

Set MORD_15 = 1

Cen

Set to Central Control

Set MORD_10 = 1

Loc

Set to Local Control

Set MORD_11 = 1

Jog

Set to Jog Control

Set MORD_12 = 1

OoS

Set to Out of Service


Control

Set MORD_13 = 1

O SP

Set use of operator


setpoint

Set MORD_06 = 1

E SP

Set use of external setpoint

Set MORD_07 = 1

ResF

Reset Drive fault

Set MORD_08 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.1.1 Control and Reduced Control

Presentation:
2

4
5
6
7
8
9
10
11

3BSE 021 945R401

11

101

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Presentation

Motor Status

Light brown

Condition

Remarks

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

IND2_02 = 1

Drive running

IND2_01 = 1

Drive ready to start

Green

Green

Green

Green
Ready Run

102

Running mode
Indication

Medium Green
(Centre part)

IND2_02=1

Medium Green, Light


green, Dark green, Black
(Centre part background)

All others except out of


service.
IND2_02 = 1 and

Running

Forward

speed value positive

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

2
cont.

DRICONE, Engineered drive

Condition

Remarks

IND2_02 = 1 and

Reverse

speed value negative

IND2_01 = 1

Run permitted

Comm Err Red Flash

AU_IND1_12 = 1

NLS (Communication Error)


unacknowledged fault

Comm Err Red

IND1_12 = 1

NLS (Communication Error)

Fault Red Flash

AU_IND1_11 = 1

NLS (Fault) unacknowledged


fault

Fault Red

IND1_11 = 1

NLS (Fault)

Alarm Red Flash

AU_IND1_07 = 1

NLS (Alarm) unacknowledged


alarm

Alarm Red

IND1_07 = 1

NLS (Alarm)

At Limit Red Flash

AU_IND1_09 = 1

NLS (Limit) unacknowledged


limit

At Limit Red

IND1_09 = 1

NLS (Limit)

Check Status/Limit

BOOL_G = 1

Indicate that the status word


or limit word has changed.

Not At Setpoint

IND2_02 = 1 and

Green

IND2_07 = 0

NLS (Actual value at not


reference)

IND2_01 = 1 and

NLS (Ready Run)

Green
3

Warning text

Information text

Green

Ready Run Green

ind2_02 = 0

Ready Green

IND2_00 = 1 and

NLS (Ready

IND2_02 = 0
5.1

Headline Speed

Speed Black

INTWB_00 = 1

NLS (Speed)

5.2

Speed value

Black

REAL_C

Numeric presentation of
speed value 1

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

3BSE 021 945R401

103

DRICONE, Engineered drive

No

Description

5.2
cont.
5.3

Unit Speed

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

? ? ? Red

IND1_12 =1

Communication error

String (5)

PRES_A(1-5)

Unit of measured Speed

E SP1 Spd Black

INTWB11 = 1 and
BOOL_E = 1

NLS (E SP1 Spd)

E SP2 Spd Black

INTWB_12 = 1 and
BOOL_E = 1

NLS (E SP2 Spd)

SP1 Speed Black

INTWB_11 = 1 and
BOOL_E = 0

NLS (SP1 Speed )

SP2 Speed Black

INTWB_12 = 1 and
BOOL_E = 0

NLS (SP 2 Speed )

ESP1, Black

REAL_D
(help drive object) and
(BOOL_E = 1 and
INTWB11= 1)

External set point value for


speed unit

ESP2, Black

REAL_D and
(BOOL_E = 1
INTWB12=1)

Set point value for speed %

SP1, Black

REAL_PARAM
(help drive object) and
(BOOL_E = 0 and
INTWB11=1)

Set point value for speed unit

SP2, Black

REAL_PARAM and
(BOOL_E = 0 and
INTWB12=1)

Set Point value for speed %

String (5) Black

(INTWB_11 = 1 and
BOOL_E = 1)
or
(INTWB_11 = 1 and
BOOL_E = 0)

unit

Black
6.1

6.2

6.3

Headline Set Point


Speed

SetPoint speed value

Unit SetPoint Speed

PRES_A(1-5)

% Black

104

(INTWB_12 = 1 and
BOOL_E =1)
or
(INTWB12 = 1 and
BOOL_E = 0) and

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

7.1

Headline Current

Black

INTWB_01 = 1

NLS (Current)

7.2

Current value

Value string, Black

REAL_RES

Numeric presentation of
Current

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

7.3

Current Unit

% Black

8.1

Headline Torque

Black

INTWB_02 = 1

NLS (Torque)

8.2

Torque value

Black

REAL_A

Numeric presentation of
Torque

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

8.3

Torque Unit

% Black

9.1

Headline External Set


Point Torque/
Set Point Torque/
PID

E SP Torq Black

Unit of current

Unit of Torque
INTWB_14 = 1 and
BOOL_E = 1

Head line of External Set


Point Torque
NLS (E SP Torque)

SP Torque Black

INTWB_14 = 1 and
BOOL_E = 0

Head line of External Set


Point Torque
NLS (SP Torque)

E SP PID Black

INTWB_13 = 1 and
BOOL_E = 1

Head line of External Set


Point PID
NLS (E SP PID)

SP PID Black

INTWB_13 = 1 and
BOOL_E = 0

Head line of External Set


Point PID
NLS (SP PID)

9.2

External Set Point


Torque/
Set Point Torque/
PID

E SP Torque Black

REAL_E and
(BOOL_E = 1 and
INTWB14= 1)

SP Torque, Black

REAL_PARAM and

External set point value for


torque

Set point value for torque

(BOOL_E = 0
INTWB14=1)

3BSE 021 945R401

105

DRICONE, Engineered drive

No

Description

9.2
cont.

Section 3, Faceplates and Graphic Elements

Presentation
E SP PID, Black

Condition

Remarks

REAL_E and

External set point value for


PID

(BOOL_E = 1 and
INTWB13= 1)
SP PID, Black

REAL_PARAM and

Set Point value for PID

(BOOL_E = 0 and
INTWB13=1)
9.3

10.1

10.2

Unit External Set Point


Torque/ Set Point
Torque / PID

String (5)

Baragraph text

Unit of External Set Point


Torque or Set Point Torque or
PID

Current, Black

INTWB_01 = 1

NLS (Current) Current

Torque, Black

INTWB_02 = 1

NLS (Torque) Torque

INTWB_01 = 1 or

Bar graph Visible

Black

Motor Current

INTWB_02 = 1
10.3

Motor Current

Bar graph +, Magenta

INTWB_02 = 1 and

Motor torque value

REAL_A
REAL_A_MIN to
REAL_A_MAX
Bar graph +/-, Magenta

INTWB_02 = 1 and

Motor torque value

REAL_A_MIN<0
REAL_A
-REAL_A_MAX to
REAL_A_MAX
Bar graph +, Brown

INTWB_01 = 1 and

Motor current value

REAL_RES
REAL_RES_MIN to
REAL_RES_MAX
Bar graph +/-, Brown

INTWB_01 = 1 and

Motor current value

REAL_RES_MIN<0
REAL_RES
-REAL_RES_MAX to
REAL_RES_MAX
10.4

Hi Load Indication

at 100%

INTWB_01 = 1 and

Limit Visible for current only

REAL_RES_HILIM>0.02

106

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

10.4
cont.

DRICONE, Engineered drive

Presentation

Condition

Remarks

Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_HILIM

Above high load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_HILIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_HILIM

Red
Unfilled, Grey
10.5

Normal Load Limit


Indication
Normal Load Limit
Indication

Arrow (polygon)

Alarm blocked

The value of current has


passed the high load limit.
Not high load

REAL_RES_LOLIM>0.02

Limit Visible

at REAL_RES_LOLIM

Upper limit of normal load

REAL_RES_MIN to
REAL_RES_MAX
Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_LOLIM

Above normal load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_LOLIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_LOLIM

Grey
Unfilled, Grey
11

Blocking Interlock text

3BSE 021 945R401

Alarm blocked

The value of current has


passed the normal load limit.
Normal

Interlock text Red

ACT_PRES_TEXT

Get the actual interlock text


from the database. Valid for
interlocks IC, IB1-IB4

Interlock text Yellow

ACT_PRES_TEXT

Get the actual interlock text


from the database. Valid for
interlock IA

107

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

3.6.1.2 Block

Presentation:

Behavior:
No

Description

Override Interlock

108

Block Alarm

Block Printout

Default Presentation

Condition

Remarks
IND2_15 Indicates current
status

Yellow

Blocked

Override pressed

MORD_04 = 1

Normal pressed

MORD_05 = 1

Block Alarm Black

Yellow

Blocked

Block pressed

ALARM_BLK = 1

Deblock pressed

ALARM_BLK = 0

Block Alarm Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.2 Displays
3.6.2.1 Object Display

Presentation:
9

10

11

1
2

12
13
14
15

3
4
5
6
7
8

16
17
18
19
20
21

40

22

41
23
24

42

25

43
44
45

26
27
28
29

46

35-39

30-34

Behavior:
No

Description

Presentation

Condition

Remarks

Select Frame

White

SELECTED = 1

Object select frame

Grey

3BSE 021 945R401

109

DRICONE, Engineered drive

No

Description

Header

Presentation

Red flashing

Section 3, Faceplates and Graphic Elements

Condition

Remarks

NAME and DESCR

Object name and description

AU_IND1_11 = 1 or

Unacknowledged alarm

AU_IND1_07 = 1 or
AU_IND1_09 = 1 or
AU_IND1_12 = 1
Red

IND1_11 = 1 or

Fault

IND1_07 = 1 or

Alarm

IND1_09 = 1 or

Limit

IND1_12 = 1

Communication error

Green
3.1

3.2

4.1

4.2

5.1

5.2

110

Range Max Speed

Range Min Speed

Range Max Current

Range Min Current

Range Max Torque

Range Min Torque

Trim Curve Speed

Trim Curve Current

Trim Curve Torque

Normal

Green

REAL_C_MAX

INTWB_00 = 1

Green

REAL_C_MIN

INTWB_00 = 1

Brown

REAL_RES_MAX

INTWB_01 = 1

Brown

REAL_RES_MIN

INTWB_01 = 1

Magenta

REAL_A_MAX

INTWB_02 = 1

Magenta

REAL_A_MIN

INTWB_02 = 1

Limit visible

Green

REAL_C

Trim curve for speed

INTWB_00 = 1

Trim curve visible

Brown

REAL_RES

Trim curve for current

INTWB_01 = 1

Trim curve visible

Magenta

REAL_A

Trim curve for Torque

INTWB_02 = 1

Trim curve visible

Limit visible

Limit visible

Limit visible

Limit visible

Limit visible

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

9.1

Bar graph Speed

Green

REAL_C

Speed bar graph

INTWB_00 = 1 and

Bar graph when speed min


value is positive.

Bar graph +

REAL_C
REAL_C_MIN to
REAL_C_MAX
Bar graph +/-

INTWB_00 = 1 and
REAL_C_MIN<0

Bar graph when speed min


value is negative.

REAL_C
-REAL_C_MAX to
REAL_C_MAX
10.1

Bar graph Current

Brown
Bar graph +

REAL_RES

Current bar graph

INTWB_01 = 1 and

Bar graph when current min


value is positive.

REAL_RES
REAL_RES_MIN to
REAL_RES_MAX
Bar graph +/-

INTWB_01 = 1 and
REAL_RES_MIN<0

Bar graph when current min


value is negative.

REAL_RES
-REAL_RES_MAX to
REAL_RES_MAX
10.2

Hi Load Indication

at 100%

INTWB_01 = 1

Limit Indication

Filled

ALARM_BLK=1 and

High load, Alarm blocked

Yellow

REAL_RES >
REAL_RES_HILIM
or
ALARM_PERIOD_BLK=1
and
REAL_RES >
REAL_RES_HILIM

Unfilled
Yellow

ALARM_PERIOD_BLK=1
or

Alarm blocked

ALARM_BLK = 1
Filled
Red
Unfilled, Grey

3BSE 021 945R401

REAL_RES >
REAL_RES_HILIM

The value of current has


passed the high load limit.
Not high load

111

DRICONE, Engineered drive

No

Description

10.3

Normal Load Limit


Indication

Section 3, Faceplates and Graphic Elements

Presentation

Arrow (polygon)

Condition

Remarks

INTWB_01 = 1

Limit Visible for current only

at REAL_RES_LOLIM

Upper limit of normal load

REAL_RES_MIN to
REAL_RES_MAX
Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_LOLIM

Above normal load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_LOLIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_LOLIM

Grey
Unfilled, Grey
11.1

Bar graph Torque

Magenta
Bar graph +

Alarm blocked

The value of current has


passed the normal load limit.
Normal

REAL_A

Torque bar graph

INTWB_02 = 1 and

Bar graph when torque min


value is positive.

REAL_A
REAL_A_MIN to
REAL_A_MAX
Bar graph +/-

INTWB_02 = 1 and
REAL_A_MIN<0

Bar graph when torque min


value is negative.

REAL_A
-REAL_A_MAX to
REAL_A_MAX
12

ALARMS

12.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_IND1_11 = 1

Unacknowledged alarm

Red

IND1_11 = 1

Alarm

12.3

112

Warning Indication

Alarms

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

12.4

Alarm 1 Text

Fault

DRICONE, Engineered drive

Condition

Remarks
NLS (Fault)

Red

IND1_11 = 1 or
AU_IND1_11 = 1

Grey

13.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

13.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_IND1_09 = 1

Unacknowledged alarm

Red

IND1_09 = 1

Alarm

13.3

13.4

Warning Indication

Alarm 2 Text

At Limit

NLS (At Limit)

Red

IND1_09 = 1 or
AU_IND1_09 = 1

Grey

14.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

14.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_IND1_07 = 1

Unacknowledged alarm

Red

IND1_07 = 1

Alarm

14.3

14.4

Warning Indication

Alarm 3 Text

Alarm

NLS (Alarm)

Red

IND1_07 = 1 or
AU_IND1_07 = 1

Grey

15.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

15.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_PERIOD_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_IND1_12 = 1

Unacknowledged alarm

Red

IND1_12 = 1

Alarm

15.3

Warning Indication

3BSE 021 945R401

113

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

15.4

Alarm 4 Text

Comm. error

Condition

Remarks
NLS (Comm. error)

Red

IND1_12 = 1 or
AU_IND1_12 = 1

Grey

16

INTERLOCKS

Interlocks

16

STATUS

Status

16.1

IC1 Active

16.2

IC1 Text

17.1

IB2 Blocked

17.2

IB2 Active

17.3

IB2 Text

18.1

IB4 Block Indication

Yellow

IND2_08 = 1

Safety Interlock IC1 active

Green

I2_08TXT

Safety Interlock IC1 text from


database

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

Yellow

IND2_11 = 1

Interlock IB2 active

Green

I2_11TXT

Interlock IB2 text from


database

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

X Yellow

IND2_13 = 1 and
IND2_02 = 1 and
BOOL_F = 1

Pending interlock, will be set


when not running.

(IND2_13 = 1 and
BOOL_F = 0)
or
(IND2_13 = 1 and
IND2_02 = 0 and
BOOL_F = 1)

Interlock IB4 active

18.2

IB4 Active

18.3

IB4 Text

Green

I2_13TXT

Interlock IB4 text from


database

19.1

IB1 Blocked

BX Red

IND1_15 = 1

Override Interlock and


Interlock IB1 active

BX Yellow

(BOOL_C = 1 or
IND2_15=1) and
IND1_15=0

Jog mode. Interlock blocked

Yellow

IND2_10 = 1 and
IND2_15 = 0

Interlock IB1 active

19.2

114

IB1 Active

Yellow

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

19.3

IB1 Text

Green

I2_10TXT

Interlock IB1 text from


database

20.1

IB3 Blocked

BX Red

IND1_15 = 1

Override Interlock and


Interlock IB3 active

BX Yellow

(BOOL_C = 1 or
IND2_15=1) and
IND1_15=0

Jog mode. Interlock blocked

X Yellow

IND2_12 = 1 and
IND2_02 = 1and
BOOL_F = 1and
IND2_15 = 0

Pending interlock, will be set


when not running.

(IND2_12 = 1 and
BOOL_F = 0 and
IND2_15 = 0 and)
or
(IND2_12 = 1 and
IND2_02 = 0 and
BOOL_F = 1and
IND2_15 = 0)

Interlock IB3 active

20.2

IB3 Active

20.3

IB3 Text

Green

I2_12TXT

Interlock IB3 text from


database

21.1

IA Blocked

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

21.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

21.3

IA Text

Green

I2_14TXT

Interlock IA text from


database

22

Blocking Interlock

Grey

22.1

Blocking Interlock Text Green

ACT_PRES_TEXT

23.1

Ready Run Indication

IND2_01 = 1

23.2

Ready Run Text

24.1

Not at reference
Indication

24.2

Not at reference Text

25.1

Repeat Fail Blocked


Indication

3BSE 021 945R401

Yellow

Blocking Interlock

Green

Ready Run

Grey

NLS (Ready Run)

Green

Not at Setpoint
Yellow

The Interlock that is active.

IND2_02 = 1 and
IND2_07 = 0
Grey

NLS (Not at Setpoint)


REPEAT_BLK = 1

115

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

25.2

Repeat Fail Blocked


Text

Repeat Fail Blk

Remarks
NLS (Repeat Fail Blk)

Yellow

REPEAT_BLK = 1

Grey

26

Nominal Values

26.1

Nom. Speed Text

Nom. Speed

26.2

Nom. Speed Value

Green

26.3

Nom. Speed Unit

rpm Grey

27.1

Nom. Power Text

Power Grey

INTWA_00 = 1

27.2

Nom. Power Value

Green

REAL_E from MMCX help


object

27.3

Nom. Power Unit

kW Grey

28.1

Nom. Current Text

Current

28.2

Nom. Current Value

Green

28.3

Nom. Current Unit

A Grey

29.1

Nom. Torque Text

Torque

29.2

Nom. Torque Value

Green

29.3

Nom. Torque Unit

Nm Grey

Unit Nm

30

MotorStatus Text

Motor Status Grey

Run

116

Nominal values
Grey

NLS (Speed) Nominal Speed


of drive
INTL_RES
Unit rpm
NLS (Power) Nominal Power
of drive

Unit kW
Grey

INTWA_00 = 1

NLS (Current) Nominal


Current of motor

REAL_E_MIN from MMCX


help object
Unit Ampere
Grey

INTWA_00 = 1

NLS (Torque) Nominal Torque


of motor

REAL_E_MAX from MMCX


help object

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

31.1

MotorStatus

Light brown

DRICONE, Engineered drive

Condition

Remarks

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

IND2_02 = 1

Drive running

IND2_01 = 1

Drive ready to start

Green

Green

Green

Green
Ready Run
Medium Green (K5)
(Centre part)

IND2_02 =1

Running

IND2_02 = 1 and

Forward

Medium Green (K5), Light


green (L5), Dark green
(M5), Black (K16) (Centre
part background)
31.2

Direction Indication
speed value positive

IND2_02 = 1 and

Reverse

speed value negative

IND2_01 = 1
Green

3BSE 021 945R401

Run permitted

117

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

32.1

Torque Text

Torque

INTWB_02 = 1

NLS (Torque)

32.2

Torque Value

Magenta

REAL_A

Torque value

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

INTWB_14 = 1 and
BOOL_E = 0

NLS (SP Torque)

Grey

32.3

Torque Unit

% Magenta

33.1

SP Torque Text

SP Torque

33.2

SP Torque Value

Cyan

REAL_PARAM and
BOOL_E = 0

Set point torque value

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Torque


setpoint is selected

% Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP Torque


setpoint is selected

INTWB_13 = 1 and
BOOL_E = 0

NLS (SP PID)

33.3

33.4

33.5

SP Torque Unit

Grey

SP PID Text

SP PID

SP PID Value

Cyan

REAL_PARAM and
BOOL_E = 0

Set point PID value

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP PID setpoint is


selected

% Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP PID setpoint is


selected

SP PID Unit

Grey

34.1

E Sp Torque Text

E SP Torque Grey

INTWB_14 = 1 and
BOOL_E = 1

NLS (E SP Torque)

34.2

E Sp Torque Value

Cyan

REAL_E and BOOL_E = 1

External Set point torque


value, value from PC-program

Grey

REAL_E and BOOL_E = 0

When the SP Torque setpoint


is selected

118

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

34.3

E Sp Torque Unit

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP Torque setpoint


is selected

INTWB_13 = 1 and
BOOL_E = 1

NLS (E SP PID)

34.4

E Sp PID Text

E SP PID

34.5

E Sp PID Value

Cyan

REAL_E and BOOL_E = 1

External Set point PID value,


value from PC-program

Grey

REAL_E and BOOL_E = 0

When the SP PID setpoint is


selected

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP PID setpoint is


selected

INTWB_00 = 1

NLS (Speed)

34.6

E Sp PID Unit

Grey

35.1

Speed Text

Speed

35.2

Speed Value

Green

REAL_C

Motor speed

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

PRES_A (1-5)

Unit of speed from MMCX


database.

INTWB_11 = 1 and
BOOL_E = 0

NLS (SP Speed)

REAL_PARAM and
BOOL_E = 0

Motor speed

Grey

35.3

Speed Unit

Green

36.1

SP1 Speed Text

SP1 Speed

36.2

SP1 Speed Value

Cyan

Grey

from drive help object


Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Spd setpoint


is selected

from drive help object


36.3

36.4

SP1 Speed Unit

SP2 Speed Text

3BSE 021 945R401

Unit

Cyan

PRES_A (1-5) and


BOOL_E = 0

Unit of SP Speed from MMCX


database.

Unit Grey

PRES_A (1-5) and


BOOL_E = 1

When the E SP Spd setpoint


is selected

INTWB_12 = 1 and
BOOL_E = 0

NLS (SP Speed)

SP2 Speed

Grey

119

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

36.5

SP2 Speed Value

Cyan

REAL_PARAM and
BOOL_E = 0

Motor speed

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Spd setpoint


is selected

Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP Spd setpoint


is selected

INTWB_11 = 1 and
BOOL_E = 1

NLS (E SP Spd)

REAL_D and
BOOL_E = 1

External Set point speed


value, value from PC-program

36.6

SP2 Speed Unit

37.1

E SP1 Spd Text

E SP1 Spd

37.2

E SP1 Spd Value

Cyan

Grey

from drive help object


Grey

REAL_D and
BOOL_E = 0

When the SP Speed setpoint


is selected

from drive help object


37.3

E SP1 Spd Unit

Unit Cyan

PRES_A (1-5) and


BOOL_E = 1

Unit of SP Speed from MMCX


database.

Unit Grey

PRES_A (1-5) and


BOOL_E = 0

When the SP Speed setpoint


is selected

INTWB_12 = 1 and
BOOL_E = 1

NLS (E SP Spd)

37.4

E SP2 Spd Text

E SP2 Spd

37.5

E SP2 Spd Value

Cyan

REAL_D and
BOOL_E = 1

External Set point speed


value, value from PC-program

Grey

REAL_D and
BOOL_E = 0

When the SP Speed setpoint


is selected

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP Speed setpoint


is selected

37.6

120

E SP2 Spd Unit

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

38.1

Current Text

CURRENT

INTWB_01 = 1

NLS (Current)

38.2

Current Value

Brown

REAL_RES

Current

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

% of nominal current

PRES_B and
INTWB_03 = 1

Free text from MMCX


database element, max 10
characters

Grey

38.3

Current Unit

% Brown

39.1

Value Text

Value

39.2

Value Value

Light Yellow

REAL_B

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

Light Yellow

PRES_A [6..10]

Free text, max 5 characters.

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central Controlled from


operators place or by group
start or other PC-program

Green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

NLS (Central)

Grey

39.3

Value Unit

40.1

Central Indication

40.2

Central Text

41.1

41.2

42.1

Green

Central

Local Indication

Local Text

Jog Indication

3BSE 021 945R401

Grey

Green

BOOL_D = 1 and
IND2_09 = 1

Local
Controlled from local panel

Local
Green

BOOL_D = 1 and
IND2_09 = 1

Grey

Yellow

BOOL_C = 1 and
IND2_09 = 1

Jog
Jog running from motor
location

121

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

42.2

Test Text

Jog

43.1

Condition

Remarks

Yellow

BOOL_C = 1 and
IND2_09 = 1

NLS (Jog)

Grey

Drive local Indication

Yellow

IND2_09 = 0

Local
Controlled from local drive
panel

43.2

44.1

44.2

45.1

45.2

46.1

46.2

122

Drivel ocal Text

Drive local
Yellow

IND2_09 = 0

Grey

Out of Service
Indication
Out of Service Text

Light brown

Out of service
Light brown

IND2_00 = 0

Grey

Green

BOOL_A = 1 and
BOOL_B = 0 and
IND2_09 = 1

NLS (Out of service)

Manual mode.
Startorder affects the motor
directly

Man Grey
Green

BOOL_A = 1 and
BOOL_B = 0 and
IND2_09 = 1

Grey

Auto Indication

Auto Text

Out of service
No control possible

Man Indication

Man Text

IND2_00 = 0

NLS (Drive local)

Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

Auto mode.
Process conditions control
start/stop of motor

Auto
Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.2.2 Diagnostic Fault Display

Data Base Element MMCX is to be named by the main Data Base Element + suffix
<.FL>
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.FL
Presentation:

1
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Behavior:
No

Description

Presentation

Header

FAULTS Grey

2.1

Short Circuit
Fault

Red flashing

Short Circuit
Fault

Red

2.2

3BSE 021 945R401

Condition

Remarks
Faults title

AU_IND1_00 = 1

Unacknowledged Alarm
Short Circuit Fault

IND1_00 = 1

Short Circuit Fault

123

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

2.3

Short Circuit Text


Fault

Short Circuit

AU_IND1_00 = 1 or

NLS (Short Circuit) fault

Red

IND1_00 = 1

Short Circuit Text


Normal

Short Circuit

IND1_00 = 0

NLS (Short Circuit) normal

AU_IND1_01 = 1

Unacknowledged Alarm

2.4

3.1

Grey

Over Current
Fault

Red flashing

3.2

Over Current
Fault

Red

3.3

Over Current Text


Fault
Over Current Text
Normal

3.4

4.1

Over Current Fault


IND1_01 = 1

Over Current Fault

Over Current

AU_IND1_01 = 1 or

NLS (Over Current) fault.

Red

IND1_01 = 1

Over Current

IND1_01 = 0

NLS (Over Current) normal

AU_IND1_02 = 1

Unacknowledged Alarm

Grey

DC Over Voltage
Fault

Red flashing

4.2

DC Over Voltage
Fault

Red

4.3

DC Over Voltage Text


Fault
DC Over Voltage Text
Normal

4.4

5.1

DC Over Voltage Fault


IND1_02 = 1

DC Over Voltage Fault

DC Over Voltage

AU_IND1_02 = 1 or

NLS (DC Over Voltage) fault.

Red

IND1_02 = 1

DC Over Voltage

IND1_02 = 0

NLS (DC Over Voltage)


normal

AU_IND1_03 = 1

Unacknowledged Alarm

Grey

Power Plate Over Temp


Fault

Red flashing

5.2

Power Plate Over Temp


Fault

Red

5.3

Power Plate Over Temp


Text
Fault

Power Plate Over


Temp

Power Plate Over Temp


Text
Normal

Power Plate Over


Temp

5.4

124

Power Plate Over Temp


IND1_03 = 1

Power Plate Over Temp

AU_IND1_03 = 1 or

NLS (Power Plate Over


Temp) fault.

IND1_03 = 1

Red
IND1_03 = 0

NLS (Power Plate Over


Temp) normal

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

6.1

Earth Fault
Fault

Red flashing

6.2

Earth Fault
Fault

Red

6.3

Earth Fault Text


Fault
Earth Fault Text
Normal

6.4

7.1

Presentation

AU_IND1_04 = 1 or

NLS (Earth Fault) fault.

Red

IND1_04 = 1

Earth Fault

IND1_04 = 0

NLS (Earth Fault) normal

AU_IND1_05 = 1

Unacknowledged Alarm

Grey

Red

7.3

Motor Over Temperature


Text
Fault

Motor Over
Temperature

Motor Over Temperature


Text
Normal

Motor Over
Temperature

Motor Over Temperature Fault


IND1_05 = 1

Motor Over Temperature Fault

AU_IND1_05 = 1 or

NLS (Motor Over


Temperature) fault.

IND1_05 = 1

Red
IND1_05 = 0

NLS (Motor Over


Temperature) normal

AU_IND1_06 = 1

Unacknowledged Alarm

Grey

Motor Overload
Fault

Red flashing

8.2

Motor Overload
Fault

Red

8.3

Motor Overload Text


Fault
Motor Overload Text
Normal

Motor Overload Fault


IND1_06 = 1

Motor Overload Fault

Motor Overload

AU_IND1_06 = 1 or

NLS (Motor Overload) fault.

Red

IND1_06 = 1

Motor Overload

IND1_06 = 0

NLS (Motor Overload) normal

AU_IND1_07 = 1

Unacknowledged Alarm

Grey

System Fault
Fault

Red flashing

9.2

System Fault
Fault

Red

9.3

System Fault Text


Fault

3BSE 021 945R401

Unacknowledged Alarm

Earth Fault

Motor Over Temperature


Fault

9.1

AU_IND1_04 = 1

Earth Fault

7.2

8.4

Remarks

IND1_04 = 1

Red flashing

8.1

Condition

Earth Fault

Motor Over Temperature


Fault

7.4

DRICONE, Engineered drive

System Fault
IND1_07 = 1

System Fault

System Fault

AU_IND1_07 = 1 or

NLS (System Fault) fault.

Red

IND1_07 = 1

125

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

9.4

System Fault Text


Normal

System Fault

IND1_07 = 0

NLS (System Fault) normal

AU_IND1_08 = 1

Unacknowledged Alarm

10.1

Grey

Underload
Fault

Red flashing

10.2

Underload
Fault

Red

10.3

Underload Text
Fault
Underload Text
Normal

10.4

11.1

Underload Fault
IND1_08 = 1

Underload Fault

Underload

AU_IND1_08 = 1 or

NLS (Underload) fault.

Red

IND1_08 = 1

Underload

IND1_08 = 0

NLS (Underload) normal

AU_IND1_09 = 1

Unacknowledged Alarm

Grey

Over Speed
Fault

Red flashing

11.2

Over Speed
Fault

Red

11.3

Over Speed Text


Fault
Over Speed Text
Normal

11.4

12.1

Over Speed Fault


IND1_09 = 1

Over Speed Fault

Over Speed

AU_IND1_09 = 1 or

NLS (Over Speed) fault.

Red

IND1_09 = 1

Over Speed

IND1_09 = 0

NLS (Over Speed) normal

AU_IND1_10 = 1

Unacknowledged Alarm

Grey

Fault 10
Fault

Red flashing

12.2

Fault 10
Fault

Red

12.3

Fault 10 Text
Fault
Fault 10 Text
Normal

12.4

13.1

13.2

126

Fault 10 Fault
IND1_10 = 1

Fault 10 Fault

Fault 10

AU_IND1_10 = 1 or

NLS (Fault 10) fault

Red

IND1_10 = 1

Fault 10

IND1_10 = 0

NLS (Fault 10) normal

AU_IND1_11 = 1

Unacknowledged Alarm

Grey

Master/Follower Link
Fault

Red flashing

Master/Follower Link
Fault

Red

Master/Follower Link Fault


IND1_11 = 1

Master/Follower Link Fault

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

13.3

Master/Follower Link Text


Fault

Master/Follower Link

AU_IND1_11 = 1 or

Red

IND1_11 = 1

NLS (Master/Follower Link)


fault.

Master/Follower Link Text


Normal

Master/Follower Link

IND1_11 = 0

NLS (Master/Follower Link)


normal

AU_IND1_12 = 1

Unacknowledged Alarm

13.4

14.1

Grey

Short Circuit INT1


Fault

Red flashing

14.2

Short Circuit INT1


Fault

Red

14.3

Short Circuit INT1 Text


Fault
Short Circuit INT1 Text
Normal

14.4

15.1

Short Circuit INT1 Fault


IND1_12 = 1

Short Circuit INT1 Fault

Short Circuit INT1

AU_IND1_12 = 1 or

NLS (Short Circuit INT1) fault.

Red

IND1_12 = 1

Short Circuit INT1

IND1_12= 0

NLS (Short Circuit INT1)


normal

AU_IND1_13 = 1

Unacknowledged Alarm

Grey

Short Circuit INT2


Fault

Red flashing

15.2

Short Circuit INT2


Fault

Red

15.3

Short Circuit INT2 Text


Fault
Short Circuit INT2 Text
Normal

15.4

16.1

Short Circuit INT2 Fault


IND1_13 = 1

Short Circuit INT2 Fault

Short Circuit INT2

AU_IND1_13 = 1 or

NLS (Short Circuit INT2) fault.

Red

IND1_13 = 1

Short Circuit INT2

IND1_13 = 0

NLS (Short Circuit INT2)


normal

AU_IND1_14 = 1

Unacknowledged Alarm

Grey

Short Circuit INT3


Fault

Red flashing

16.2

Short Circuit INT3


Fault

Red

16.3

Short Circuit INT3 Text


Fault
Short Circuit INT3 Text
Normal

16.4

17.1

Short Circuit INT4


Fault

3BSE 021 945R401

Short Circuit INT3 Fault


IND1_14 = 1

Short Circuit INT3 Fault

Short Circuit INT3

AU_IND1_14 = 1 or

NLS (Short Circuit INT3) fault

Red

IND1_14 = 1

Short Circuit INT3

IND1_14 = 0

NLS (Short Circuit INT3)


normal

AU_IND1_15 = 1

Unacknowledged Alarm

Grey
Red flashing

Short Circuit INT4 Fault

127

DRICONE, Engineered drive

No

Description

17.2

Short Circuit INT4


Fault

17.3

Short Circuit INT4 Text


Fault
Short Circuit INT4 Text
Normal

17.4

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Red

IND1_15 = 1

Short Circuit INT4 Fault

Short Circuit INT4

AU_IND1_15 = 1 or

NLS (Short Circuit INT4) fault.

Red

IND1_15 = 1

Short Circuit INT4

IND1_15 = 0

NLS (Short Circuit INT4)


normal

AU_IND2_00 = 1

Unacknowledged Alarm

Grey

Supply Phase
Fault

Red flashing

18.2

Supply Phase
Fault

Red

18.3

Supply Phase Text


Fault
Supply Phase Text
Normal

18.1

18.4

19.1

Supply Phase Fault


IND2_00 = 1

Supply Phase Fault

Supply Phase

AU_IND2_00 = 1 or

NLS (Supply Phase) Fault.

Red

IND2_00 = 1

Supply Phase

IND2_00 = 0

NLS (Supply Phase) normal

AU_IND2_01 = 1

Unacknowledged Alarm

Grey

No Motor Data Given


Fault

Red flashing

19.2

No Motor Data Given


Fault

Red

19.3

No Motor Data Given


Text Fault
No Motor Data Given
Text Normal

19.4

20.1

No Motor Data Given Fault


IND2_01 = 1

No Motor Data Given Fault

No Motor Data Given

AU_IND2_01 = 1 or

Red

IND2_01 = 1

NLS (No Motor Data Given)


Fault

No Motor Data Given

IND2_01 = 0

NLS (No Motor Data Given)


normal

AU_IND2_02 = 1

Unacknowledged Alarm

Grey

DC Under Voltage
Fault

Red flashing

20.2

DC Under Voltage
Fault

Red

20.3

DC Under Voltage Text


Fault
DC Under Voltage Text
Normal

20.4

128

DC Under Voltage Fault


IND2_02 = 1

DC Under Voltage Fault

DC Under Voltage

AU_IND2_02 = 1 or

Red

IND2_02 = 1

NLS (DC Under Voltage)


Fault.

DC Under Voltage

IND2_02 = 0

Grey

NLS (DC Under Voltage)


normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

21.1

Cable Temperature
Fault

Red flashing

21.2

Cable Temperature
Fault

Red

21.3

Cable Temperature Text


Fault
Cable Temperature Text
Normal

21.4

22.1

22.2

22.3

22.4

23.1

Presentation

Remarks

AU_IND2_03 = 1

Unacknowledged Alarm

IND2_03 = 1

Cable Temperature Fault

Cable Temperature

AU_IND2_03 = 1 or

Red

IND2_03 = 1

NLS (Cable Temperature)


Fault.

Cable Temperature

IND2_03 = 0

NLS (Cable Temperature)


normal

AU_IND2_04 = 1

Unacknowledged Alarm

Grey

Run Disabled
Fault

Red flashing

Run Disabled
Fault

Red

Run Disabled
IND2_04 = 1

Run Disabled
Fault

Run Disabled Text


Fault

Run Disabled

AU_IND2_04 = 1 or

Red

IND2_024= 1

Run Disabled Text


Normal

Run Disabled

IND2_04= 0

NLS (Run Disabled) normal

AU_IND2_05 = 1

Unacknowledged Alarm

23.2

Encoder Error
Fault

Red

23.3

Encoder Error Text


Fault
Encoder Error Text
Normal

Encoder Error Fault


IND2_05 = 1

Encoder Error Fault

Encoder Error

AU_IND2_05 = 1 or

NLS (Encoder Error) Fault.

Red

IND2_05 = 1

Encoder Error

IND2_05 = 0

NLS (Encoder Error) normal

AU_IND2_06 = 1

Unacknowledged Alarm

Grey

I/O Link Channel 1


Fault

Red flashing

24.2

I/O Link Channel 1


Fault

Red

24.3

I/O Link Channel 1 Text


Fault

3BSE 021 945R401

NLS (Run Disabled) Fault.

Grey
Red flashing

24.1

Condition

Cable Temperature Fault

Encoder Error
Fault

23.4

DRICONE, Engineered drive

I/O Link Channel 1 Fault


IND2_06 = 1

I/O Link Channel 1 Fault

I/O Link Channel 1

AU_IND2_06 = 1 or

Red

IND2_06 = 1

NLS (I/O Link Channel 1)


Fault

129

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

24.4

I/O Link Channel 1Text


Normal

I/O Link Channel 1

IND2_06 = 0

NLS (I/O Link Channel 1)


normal

AU_IND2_07 = 1

Unacknowledged Alarm

25.1

Grey

Cabinet Over Temperature


Fault

Red flashing

25.2

Cabinet Over Temperature


Fault

Red

25.3

Cabinet Over Temperature


Text
Fault

Cabinet Over
Temperature

Cabinet Over Temperature


Text
Normal

Cabinet Over
Temperature

25.4

26.1

Cabinet Over Temperature


Fault
Cabinet Over Temperature
Fault

AU_IND2_07 = 1 or

NLS (Cabinet Over


Temperature) Fault

IND2_07 = 1

Red
IND2_07 = 0

NLS (Cabinet Over


Temperature) normal

AU_IND2_08 = 1

Unacknowledged Alarm

Grey

Fault 18
Fault

Red flashing

26.2

Fault 18
Fault

Red

26.3

Fault 18 Text
Fault
Fault 18 Text
Normal

26.4

IND2_07 = 1

Fault 18 Fault
IND2_08 = 1

Fault 18 Fault

Fault 18

AU_IND2_08 = 1 or

NLS (Fault 18) Fault

Red

IND2_08 = 1

Fault 18

IND2_08 = 0

NLS (Fault 18) normal

Grey

27.1

Over Switching Frequency


Fault

Red flashing

AU_IND2_09 = 1

Over Switching Frequency


Fault

27.2

Over Switching Frequency


Fault

Red

IND2_09 = 1

Unacknowledged Alarm

27.3

27.4

130

Over Switching Frequency


Fault

Over Switching
Frequency Text
Fault

Over Switching
Frequency

Over Switching
Frequency Text
Normal

Over Switching
Frequency

AU_IND2_09 = 1 or
IND2_09 = 1

NLS (Over Switching


Frequency) Fault.

Red
IND2_09 = 0

NLS (Over Switching


Frequency) normal

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

28.1

Al Below Min. Level


Fault

Red flashing

28.2

Al Below Min. Level


Fault

Red

28.3

Al Below Min. Level Text


Fault
Al Below Min. Level Text
Normal

28.4

29.1

Presentation

AU_IND2_10 = 1 or

Red

IND2_10 = 1

NLS (Al Below Min. Level)


Fault

Al Below Min. Level

IND2_10 = 0

NLS (Al Below Min. Level)


normal

AU_IND2_11 = 1

Unacknowledged Alarm

Grey

Red

29.3

PPCC Link Text


Fault
PPCC Link Text
Normal

PPCC Link Fault


IND2_11 = 1

PPCC Link Fault

PPCC Link

AU_IND2_11 = 1 or

NLS (PPCC Link) Fault.

Red

IND2_11 = 1

PPCC Link

IND2_11 = 0

NLS (PPCC Link) normal

AU_IND2_12 = 1

Unacknowledged Alarm

Grey

Communication Channel 0
Fault

Red flashing

30.2

Communication Channel 0
Fault

Red

30.3

Communication Channel 0
Text
Fault

Communication
Channel 0

Communication Channel 0
Text
Normal

Communication
Channel 0

31.2

Communication Channel 0
Fault
IND2_12 = 1

Communication Channel 0
Fault

AU_IND2_12 = 1 or

NLS (Communication
Channel 0) Fault.

IND2_12 = 1

Red
IND2_12 = 0

NLS (Communication
Channel 0) normal

AU_IND2_13 = 1

Unacknowledged Alarm

Grey

Panel Loss
Fault

Red flashing

Panel Loss
Fault

Red

3BSE 021 945R401

Unacknowledged Alarm

Al Below Min. Level

PPCC Link
Fault

31.1

AU_IND2_10 = 1

Al Below Min. Level Fault

29.2

30.4

Remarks

IND2_10 = 1

Red flashing

30.1

Condition

Al Below Min. Level Fault

PPCC Link
Fault

29.4

DRICONE, Engineered drive

Panel Loss Fault


IND2_13 = 1

Panel Loss Fault

131

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

31.3

Panel Loss Text


Fault

Panel Loss

AU_IND2_13 = 1 or

NLS (Panel Loss) Fault.

Red

IND2_13 = 1

Panel Loss Text


Normal

Panel Loss

IND2_13 = 0

NLS (Panel Loss) normal

AU_IND2_14 = 1

Unacknowledged Alarm

31.4

32.1

Grey

Motor Stalled
Fault

Red flashing

32.2

Motor Stalled
Fault

Red

32.3

Motor Stalled Text


Fault
Motor Stalled Text
Normal

32.4

33.1

Motor Stalled Fault


IND2_14 = 1

Motor Stalled Fault

Motor Stalled

AU_IND2_14 = 1 or

NLS (Motor Stalled) Fault.

Red

IND2_14 = 1

Motor Stalled

IND2_14 = 0

NLS (Motor Stalled) normal

AU_IND2_15 = 1

Unacknowledged Alarm

Grey

Motor Phase Missing


Fault

Red flashing

33.2

Motor Phase Missing


Fault

Red

33.3

Motor Phase Missing Text


Fault
Motor Phase Missing Text
Normal

33.4

132

Motor Phase Missing Fault


IND2_15 = 1

Motor Phase Missing Fault

Motor Phase Missing

AU_IND2_15 = 1 or

Red

IND2_15 = 1

NLS (Motor Phase Missing)


Fault.

Motor Phase Missing

IND2_15 = 0

Grey

NLS (Motor Phase Missing)


normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.2.3 Diagnostic Alarm Display

Data Base Element MMCX is to be named by the main Data Base Element + suffix
<.AL>
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.AL
Presentation:

1
15
16
17
18
19
20
21
22
23
24
25
26

2
3
4
5
6
7
8
9
10
11
12
13

27

14

Behavior:
No

Description

Presentation

Header

ALARMS Grey

2.1

Prevent Start
Alarm

Red flashing

Prevent Start
Alarm

Red

2.2

3BSE 021 945R401

Condition

Remarks
Alarms title.

AU_IND1_00 = 1

Unacknowledged Alarm
Prevent Start Alarm

IND1_00 = 1

Prevent Start Alarm

133

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

2.3

Prevent Start Text


Alarm

Prevent Start

AU_IND1_00 = 1 or

NLS (Prevent Start) alarm.

Red

IND1_00 = 1

Prevent Start Text


Normal

Prevent Start

IND1_00 = 0

NLS (Prevent Start) normal

AU_IND1_01 = 1

Unacknowledged Alarm

2.4

3.1

Grey

Emergency Stop
Alarm

Red flashing

3.2

Emergency Stop
Alarm

Red

3.3

Emergency Stop Text


Alarm
Emergency Stop Text
Normal

3.4

4.1

Emergency Stop Alarm


IND1_01 = 1

Emergency Stop Alarm

Emergency Stop

AU_IND1_01 = 1 or

NLS (Emergency Stop) alarm.

Red

IND1_01 = 1

Emergency Stop

IND1_01 = 0

NLS (Emergency Stop)


normal

AU_IND1_02 = 1

Unacknowledged Alarm

Grey

Motor Temperature
Alarm

Red flashing

4.2

Motor Temperature
Alarm

Red

4.3

Motor Temperature Text


Alarm
Motor Temperature Text
Normal

4.4

5.1

Motor Temperature Alarm


IND1_02 = 1

Motor Temperature Alarm

Motor Temperature

AU_IND1_02 = 1 or

Red

IND1_02 = 1

NLS (Motor Temperature)


alarm.

Motor Temperature

IND1_02 = 0

NLS (Motor Temperature)


normal

AU_IND1_03 = 1

Unacknowledged Alarm

Grey

Motor Overload
Alarm

Red flashing

5.2

Motor Overload
Alarm

Red

5.3

Motor Overload Text


Alarm
Motor Overload Text
Normal

5.4

6.1

134

Power Plate Over Temp


Alarm

Motor Overload Alarm


IND1_03 = 1

Motor Overload Alarm

Motor Overload

AU_IND1_03 = 1 or

NLS (Motor Overload) alarm.

Red

IND1_03 = 1

Motor Overload

IND1_03 = 0

NLS (Motor Overload) normal

AU_IND1_04 = 1

Unacknowledged Alarm

Grey
Red flashing

Power Plate Over Temp Alarm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

6.2

Power Plate Over Temp


Alarm

6.3

Power Plate Over Temp


Text
Alarm

Power Plate Over


Temp

Power Plate Over Temp


Text
Normal

Power Plate Over


Temp

6.4

7.1

Presentation

Condition

Remarks

Red

IND1_04 = 1

Power Plate Over Temp Alarm

AU_IND1_04 = 1 or

NLS (Power Plate Over Temp)


alarm.

7.2

Encoder
Alarm

Red

7.3

Encoder Text
Alarm
Encoder Text
Normal

Encoder

AU_IND1_05 = 1 or

NLS (Encoder) alarm.

Red

IND1_05 = 1

Encoder

IND1_05 = 0

NLS (Encoder) normal

AU_IND1_06 = 1

Unacknowledged Alarm

Grey

Temperature
Measurement
Alarm

Red

8.3

Temperature
Measurement Text
Alarm

Temperature
Measurement

Temperature
Measurement Text
Normal

Temperature
Measurement

Temperature Measurement
Alarm
IND1_06 = 1

Temperature Measurement
Alarm

AU_IND1_06 = 1 or

NLS (Temperature
Measurement) alarm.

IND1_06 = 1

Red
IND1_06 = 0

NLS (Temperature
Measurement) normal

AU_IND1_07 = 1

Unacknowledged Alarm

Grey

Digital I/O
Alarm

Red flashing

Digital I/O
Alarm

Red

3BSE 021 945R401

Unacknowledged Alarm

Encoder Alarm

8.2

9.2

AU_IND1_05 = 1

IND1_05 = 1

Red flashing

9.1

NLS (Power Plate Over Temp)


normal

Encoder Alarm

Temperature
Measurement
Alarm

8.4

IND1_04 = 0

Grey
Red flashing

8.1

IND1_04 = 1

Red

Encoder
Alarm

7.4

DRICONE, Engineered drive

Digital I/O Alarm


IND1_07 = 1

Digital I/O Alarm

135

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

9.3

Digital I/O Text


Alarm

Digital I/O

AU_IND1_07 = 1 or

NLS (Digital I/O) alarm.

Red

IND1_07 = 1

Digital I/O Text


Normal

Digital I/O

IND1_07 = 0

NLS (Digital I/O) normal

AU_IND1_08 = 1

Unacknowledged Alarm

9.4

10.1

Grey

Analog I/O
Alarm

Red flashing

10.2

Analog I/O
Alarm

Red

10.3

Analog I/O Text


Alarm
Analog I/O Text
Normal

10.4

11.1

Analog I/O Alarm


IND1_08 = 1

Analog I/O Alarm

Analog I/O

AU_IND1_08 = 1 or

NLS (Analog I/O) alarm.

Red

IND1_08 = 1

Analog I/O

IND1_08 = 0

NLS (Analog I/O) normal

AU_IND1_09 = 1

Unacknowledged Alarm

Grey

External Digital I/O


Alarm

Red flashing

11.2

External Digital I/O


Alarm

Red

11.3

External Digital I/O Text


Alarm
External Digital I/O Text
Normal

11.4

12.1

External Digital I/O Alarm


IND1_09 = 1

External Digital I/O Alarm

External Digital I/O

AU_IND1_09 = 1 or

Red

IND1_09 = 1

NLS (External Digital I/O)


alarm.

External Digital I/O

IND1_09 = 0

NLS (External Digital I/O)


normal

AU_IND1_10 = 1

Unacknowledged Alarm

Grey

External Analog I/O


Alarm

Red flashing

12.2

External Analog I/O


Alarm

Red

12.3

External Analog I/O Text


Alarm
External Analog I/O Text
Normal

12.4

13.1

136

Master Follower Link


Alarm

External Analog I/O Alarm


IND1_10 = 1

External Analog I/O Alarm

External Analog I/O

AU_IND1_10 = 1 or

Red

IND1_10 = 1

NLS (External Analog I/O)


alarm.

External Analog I/O

IND1_10 = 0

NLS (External Analog I/O)


normal

AU_IND1_11 = 1

Unacknowledged Alarm

Grey
Red flashing

Master Follower Link Alarm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

13.2

Master Follower Link


Alarm

13.3

Master Follower Link


Text
Alarm
Master Follower Link
Text
Normal

13.4

14.1

Presentation

Condition

Remarks

Red

IND1_11 = 1

Master Follower Link Alarm

Master/Follower Link

AU_IND1_11 = 1 or

Red

IND1_11 = 1

NLS (Master Follower Link)


alarm.

Master/Follower Link

IND1_11 = 0

NLS (Master Follower Link)


normal

AU_IND1_14 = 1

Unacknowledged Alarm

Grey

Earth Fault
Fault

Red flashing

14.2

Earth Fault
Fault

Red

14.3

Earth Fault
Fault
Earth Fault
Normal

14.4

15.1

Earth Fault
IND1_14 = 1

Earth Fault

Earth Fault

AU_IND1_14 = 1 or

NLS (Earth Fault) fault.

Red

IND1_14 = 1

Earth Fault

IND1_14 = 0

NLS (Earth Fault) normal

AU_IND2_00 = 1

Unacknowledged Alarm

Grey

Motor Fan
Fault

Red flashing

15.2

Motor Fan
Fault

Red

15.3

Motor Fan Text


Fault
Motor Fan Text
Normal

15.4

16.1

Motor Fan
IND2_00 = 1

Motor Fan

Motor Fan

AU_IND2_00 = 1 or

NLS (Motor Fan) fault.

Red

IND2_00 = 1

Motor Fan

IND2_00 = 0

NLS (Motor Fan) normal

AU_IND2_01 = 1

Unacknowledged Alarm

Grey

Underload
Fault

Red flashing

16.2

Underload
Fault

Red

16.3

Underload Text
Fault
Underload Text
Normal

16.4

3BSE 021 945R401

DRICONE, Engineered drive

Underload Fault
IND2_01 = 1

Underload Fault

Underload

AU_IND2_01 = 1 or

NLS (Underload) fault.

Red

IND2_01 = 1

Underload

IND2_01 = 0

NLS (Underload) normal

Grey

137

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

17.1

Alarm 2
Fault

Red flashing

17.2

Alarm 2
Fault

Red

17.3

Alarm 2 Text
Fault
Alarm 2 Text
Normal

17.4

18.1

Presentation

Alarm 2

AU_IND2_02 = 1 or

NLS (Alarm 2) fault.

Red

IND2_02 = 1

Alarm 2

IND2_02 = 0

NLS (Alarm 2) normal

AU_IND2_03 = 1

Unacknowledged Alarm

Grey

Cable Temperature
Fault

Red

18.3

Cable Temperature Text


Fault
Cable Temperature Text
Normal

Cable Tempertaure Fault


IND2_03 = 1

Cable Tempertaure Fault

Cable Temperature

AU_IND2_03 = 1 or

Red

IND2_03 = 1

NLS (Cable Tempertaure)


fault.

Cable Temperature

IND2_03 = 0

NLS (Cable Tempertaure)


normal

AU_IND2_04 = 1

Unacknowledged Alarm

Grey

Alarm 4
Fault

Red flashing

19.2

Alarm 4
Fault

Red

19.3

Alarm 4 Text
Fault
Alarm 4 Text
Normal

20.1

Alarm 4 Fault
IND2_04 = 1

Alarm 4 Fault

Alarm 4

AU_IND2_04 = 1 or

NLS (Alarm 4) fault.

Red

IND2_04 = 1

Alarm 4

IND2_04 = 0

NLS (Alarm 4) normal

AU_IND2_05 = 1

Unacknowledged Alarm

Grey

Alarm 5
Fault

Red flashing

20.2

Alarm 5
Fault

Red

20.3

Alarm 5 Text
Fault

138

Unacknowledged Alarm

Alarm 2 Fault

18.2

19.4

AU_IND2_02 = 1

IND2_02 = 1

Red flashing

19.1

Remarks
Alarm 2 Fault

Cable Temperature
Fault

18.4

Condition

Alarm 5 Fault
IND2_05 = 1

Alarm 5 Fault

Alarm 5

AU_IND2_05 = 1 or

NLS (Alarm 5) fault.

Red

IND2_05 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

20.4

Alarm 5 Text
Normal

Alarm 5

IND2_05 = 0

NLS (Alarm 5) normal

AU_IND2_06 = 1

Unacknowledged Alarm

21.1

Grey

Alarm 6
Fault

Red flashing

21.2

Alarm 6
Fault

Red

21.3

Alarm 6 Text
Fault
Alarm 6 Text
Normal

21.4

22.1

Alarm 6 Fault
IND2_06 = 1

Alarm 6 Fault

Alarm 6

AU_IND2_06 = 1 or

NLS (Alarm 6) fault.

Red

IND2_06 = 1

Alarm 6

IND2_06 = 0

NLS (Alarm 6) normal

AU_IND2_07 = 1

Unacknowledged Alarm

Grey

Power Failure File


Fault

Red flashing

22.2

Power Failure File


Fault

Red

22.3

Power Failure File Text


Fault
Power Failure File Text
Normal

22.4

23.1

Power Failure File Fault


IND2_07 = 1

Power Failure File Fault

Power Failure File

AU_IND2_07 = 1 or

NLS (Power Failure File) fault.

Red

IND2_07 = 1

Power Failure File

IND2_07 = 0

NLS (Power Failure File)


normal

AU_IND2_08 = 1

Unacknowledged Alarm

Grey

Power Down File


Fault

Red flashing

23.2

Power Down File


Fault

Red

23.3

Power Down File Text


Fault
Power Down File Text
Normal

23.4

24.1

24.2

Power Down File Fault


IND2_08 = 1

Power Down File Fault

Power Down File

AU_IND2_08 = 1 or

NLS (Power Down File) fault.

Red

IND2_08 = 1

Power Down File

IND2_08 = 0

NLS (Power Down File)


normal

AU_IND2_09 = 1

Unacknowledged Alarm

Grey

Motor Stalling
Fault

Red flashing

Motor Stalling
Fault

Red

3BSE 021 945R401

Motor Stalling Fault


IND2_09 = 1

Motor Stalling Fault

139

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

24.3

Motor Stalling Text


Fault

Motor Stalling

AU_IND2_09 = 1 or

NLS (Motor Stalling) fault.

Red

IND2_09 = 1

Motor Stalling Text


Normal

Motor Stalling

IND2_09 = 0

NLS (Motor Stalling) normal

AU_IND2_10 = 1

Unacknowledged Alarm

24.4

25.1

Grey

Al Below Min. Level


Fault

Red flashing

25.2

Al Below Min. Level


Fault

Red

25.3

Al Below Min. Level Text


Fault

Al Below Min. Level Fault


IND2_10 = 1

Al Below Min. Level Fault

Al Below Min. Level

AU_IND2_10 = 1 or

Red

IND2_10 = 1

NLS (Al Below Min. Level)


fault.

25.4

Al Below Min. Level Text Al Below


Normal
Grey

26.1

DDCS Comm Timeout


Ch 0
Fault

Red flashing

26.2

DDCS Comm Timeout


Ch 0
Fault

Red

26.3

DDCS Comm Timeout


Ch 0 Text
Fault

DDCS Comm
Timeout Ch 0

DDCS Comm Timeout


Ch 0 Text
Normal

DDCS Comm
Timeout Ch 0

26.4

27.1

Min. Level

AU_IND2_11 = 1

Unacknowledged Alarm

IND2_11 = 1

DDCS Comm Timeout Ch 0


Fault

AU_IND2_11 = 1 or

NLS (DDCS Comm Timeout


Ch 0) fault.

IND2_11 = 1

Red
IND2_11 = 0

NLS (DDCS Comm Timeout


Ch 0) normal

AU_IND2_13 = 1

Unacknowledged Alarm

Grey
Red flashing

27.2

Panel Loss
Alarm

Red

27.3

Panel Loss Text


Alarm
Panel Loss Text
Normal

140

NLS (Al Below Min. Level)


normal

DDCS Comm Timeout Ch 0


Fault

Panel Loss
Alarm

27.4

IND2_10 = 0

Panel Loss Alarm


IND2_13 = 1

Panel Loss Alarm

Panel Loss

AU_IND2_13 = 1 or

NLS (Panel Loss) alarm.

Red

IND2_13 = 1

Panel Loss

IND2_13 = 0

NLS (Panel Loss) normal

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.2.4 Status and Limit Display

The status information to this diagnostic display comes from the main Data Base
Element.Limits information is found in the faults Data Base Element MMCX +
suffix <.FL>
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.FL
Presentation:

1
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

Behavior:
No

Description

Presentation

Header

STATUS and LIMITS

Condition

Remarks
STATUS and LIMITS title.

Grey
2.1

Out of Window
Status

3BSE 021 945R401

Red flashing

AU_IND1_01 = 1

Unacknowledged alarm
Out of Window Status

141

DRICONE, Engineered drive

No

Description

2.2

Out of Window
Status

2.3

Out of Window
Status
Out of Window
Normal

2.4

3.1

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Red

IND1_01 = 1

Out of Window Status

Out of Window

AU_IND1_01 = 1 or

NLS (Out of Window) Status.

Red

IND1_01 = 1

Out of Window

IND1_01 = 0

NLS (Out of Window) normal

AU_IND1_02 = 1

Unacknowledged alarm

Grey

Emergency Stop Coast


Status

Red flashing

3.2

Emergency Stop Coast


Status

Red

3.3

Emergency Stop Coast


Text
Status

Emergency Stop
Coast

Emergency Stop Coast


Text
Normal

Emergency Stop
Coast

3.4

4.1

Emergency Stop Coast Status

4.2

Run Disabled
Status

Red

4.3

Run Disabled Text


Status
Run Disabled Text
Normal

IND1_02 = 0

NLS (Emergency Stop Coast)


normal

AU_IND1_04 = 1

Unacknowledged alarm

IND1_04 = 1

Run Disabled Status

Run Disabled

AU_IND1_04 = 1 or

NLS (Run Disabled) Status.

Red

IND1_04 = 1

Run Disabled

IND1_04 = 0

NLS (Run Disabled) normal

AU_IND1_06 = 1

Unacknowledged alarm

Grey
Red flashing

5.2

First Start Not Done


Status

Red

5.3

First Start Not Done Text


Status

142

NLS (Emergency Stop Coast)


Status.

IND1_02 = 1

Run Disabled Status

First Start Not Done


Status

5.4

AU_IND1_02 = 1 or

Grey
Red flashing

5.1

Emergency Stop Coast Status

Red

Run Disabled
Status

4.4

IND1_02 = 1

First Start Not Done Status


IND1_06 = 1

First Start Not Done Status

First Start Not Done

AU_IND1_06 = 1 or

Red

IND1_06 = 1

NLS (First Start Not Done)


Status.

First Start Not Done Text First


Normal
Grey

Start Not Done

IND1_06 = 0

NLS (First Start Not Done)


normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

6.1

Start Inhibition
Status

Red flashing

6.2

Start Inhibition
Status

Red

6.3

Start Inhibition Text


Status
Start Inhibition Text
Normal

6.4

Presentation

AU_IND1_08 = 1 or

NLS (Start Inhibition) Status.

Red

IND1_08 = 1

Start Inhibition

IND1_08 = 0

NLS (Start Inhibition) normal

IND2_00 = 1

Ready To Switch On Status

IND2_00 = 1

NLS (Ready To Switch On)


Status.

IND2_00 = 0

NLS (Ready To Switch On)


normal

IND2_01 = 1

Ready Run Status

IND2_01 = 1

NLS (Ready Run) Status.

IND2_01 = 0

NLS (Ready Run) normal

IND2_04 = 1

Emergency Coast Stop Status

IND2_04 = 1

NLS (Emergency Coast Stop)


Status.

IND2_04 = 0

NLS (Emergency Coast Stop)


normal

IND2_05 = 1

Fast Emergency Stop Status

Grey

Ready To Switch On

Ready To Switch On
Text
Normal

Ready To Switch On

Green

Green

Grey

8.1

Ready Run
Status

8.2

Ready Run Text


Status

Ready Run

Ready Run Text


Normal

Ready Run

Green

Green

Grey

9.1

Emergency Coast Stop


Status

9.2

Emergency Coast Stop


Text
Status

Emergency Coast
Stop

Emergency Coast Stop


Text
Normal

Emergency Coast
Stop

Fast Emergency Stop


Status

3BSE 021 945R401

Unacknowledged alarm

Start Inhibition

Ready To Switch On
Text
Status

10.1

AU_IND1_08 = 1

Start Inhibition Status

7.2

9.3

Remarks

IND1_08 = 1

Ready To Switch On
Status

8.3

Condition

Start Inhibition Status

7.1

7.3

DRICONE, Engineered drive

Red

Red

Grey
Red

143

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

10.2

Fast Emergency Stop


Text
Status

Fast Emergency Stop

IND2_05 = 1

NLS (Fast Emergency Stop)


Status.

Fast Emergency Stop


Text
Normal

Fast Emergency Stop

IND2_05 = 0

NLS (Fast Emergency Stop)


normal

IND2_06 = 1

Switch On Inhibit Status

IND2_06 = 1

NLS (Switch On Inhibit)


Status.

IND2_06 = 0

NLS (Switch On Inhibit)


normal

INTWB_00 = 1

Logg Data Ready Status

INTWB_00 = 1

NLS (Logg Data Ready)


Status.

INTWB_00 = 0

NLS (Logg Data Ready)


normal

INTWB_03 = 1

Motor Magnetized Status

INTWB_03 = 1

NLS (Motor Magnetized)


Status.

INTWB_03 = 0

NLS (Motor Magnetized)


normal

INTWB_05 = 1

Synch Ready Status

INTWB_05 = 1

NLS (Synch Ready) Status.

INTWB_05 = 0

NLS (Synch Ready) normal

INTWB_07 = 1

Identity Run Done Status

10.3

Red

Grey

11.1

Switch On Inhibit
Status

11.2

Switch On Inhibit Text


Status

Switch On Inhibit

Switch On Inhibit Text


Normal

Switch On Inhibit

11.3

Red

Red

Grey

12.1

Logg Data Ready


Status

12.2

Logg Data Ready Text


Status

Logg Data Ready

Logg Data Ready Text


Normal

Logg Data Ready

12.3

Green

Green

Grey

13.1

Motor Magnetized
Status

13.2

Motor Magnetized Text


Status

Motor Magnetized

Motor Magnetized Text


Normal

Motor Magnetized

13.3

Green

Green

Grey

14.1

Synch Ready
Status

14.2

Synch Ready Text


Status

Synch Ready

Synch Ready Text


Normal

Synch Ready

14.3

15.1

144

Identity Run Done


Status

Green

Green

Grey
Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

15.2

Identity Run Done Text


Status

Identity Run Done

INTWB_07 = 1

NLS (Identity Run Done)


Status.

Identity Run Done Text


Normal

Identity Run Done

INTWB_07 = 0

NLS (Identity Run Done)


normal

INTWB_10 = 1

Torque Control Status

INTWB_10 = 1

NLS (Torque Control) Status.

INTWB_10 = 0

NLS (Torque Control) normal

Green

INTWB_11 = 1

Zero Speed Status

INTWB_11 = 1

NLS (Zero Speed) Status.

INTWB_11 = 0

NLS (Zero Speed) normal

INTWA_00 = 1

Torque Motor Limit

15.3

Green

Grey

16.1

Torque Control
Status

16.2

Torque Control Text


Status

Torque Control

Torque Control Text


Normal

Torque Control

16.3

Green

Green

Grey

17.1

Zero Speed
Status

17.2

Zero Speed Text


Status

Zero Speed

Zero Speed Text


Normal

Zero Speed

17.3

18.1

18.2

18.3

19.1

19.2

19.3

20.1

Green

Grey

Torque Motor Limit


Limit

Red

From MMCX.FL.

Torque Motor Limit Text


Limit

Torque Motor Limit

Torque Motor Limit Text


Normal

Torque Motor Limit


Red

INTWA_00 = 0

NLS (Torque Motor Limit)


normal

INTWA_01 = 1

SPC Torque Min Limit


From MMCX.FL.

SPC Torque Min Limit


Limit

SPC Torque Min Limit

SPC Torque Min Limit


Normal

SPC Torque Min Limit

3BSE 021 945R401

NLS (Torque Motor Limit)


Limit.

Grey

SPC Torque Min Limit


Limit

SPC Torque Max Limit


Limit

INTWA_00 = 1

Red

INTWA_01 = 1

NLS (SPC Torque Min Limit)


Limit.

INTWA_01 = 0

NLS (SPC Torque Min Limit)


normal

INTWA_02 = 1

SPC Torque Max Limit

Red

Grey
Red

From MMCX.FL.

145

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

20.2

SPC Torque Max Limit


Text
Limit

SPC Torque Max Limit

INTWA_02 = 1

NLS (SPC Torque Max Limit)


Limit.

SPC Torque Max Limit


Text
Normal

SPC Torque Max Limit

INTWA_02 = 0

NLS (SPC Torque Max Limit)


normal

INTWA_03 = 1

Torque User Current


Limitation

20.3

21.1

21.2

21.3

22.1

22.2

22.3

23.1

23.2

23.3

24.1

146

Red

Grey

Torque User Current


Limit
Limit

Red

From MMCX.FL.

Torque User Current


Limit Text
Limit

Torque User Current


Limit

Torque User Current


Limit Text
Normal

Torque User Current


Limit

NLS (Torque User Current


Limit) Limit.

INTWA_03 = 0

NLS (Torque User Current


Limit) normal

INTWA_04 = 1

Torque Inverter Current Limit

Red

Grey

Torque Inverter Current


Limit
Limit

Red

From MMCX.FL.

Torque Inverter Current


Limit Text
Limit

Torque Inverter
Current Limit

Torque Inverter Current


Limit Text
Normal

Torque Inverter
Current Limit

INTWA_04 = 1

NLS (Torque Inverter Current


Limit) Limit.

INTWA_04 = 0

NLS (Torque Inverter Current


Limit) normal

INTWA_05 = 1

Torque Min Limit

Red

Grey

Torque Min Limit


Limit

Red

From MMCX.FL.

Torque Min Limit Text


Limit

Torque Min Limit

Torque Min Limit Text


Normal

Torque Min Limit

Torque Max Limit


Limit

INTWA_03 = 1

INTWA_05 = 1

NLS (Torque Min Limit) Limit.

INTWA_05 = 0

NLS (Torque Min Limit)


normal

INTWA_06 = 1

Torque Max Limit

Red

Grey
Red

From MMCX.FL.

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

24.2

Torque Max Limit Text


Limit

Torque Max Limit

INTWA_06 = 1

NLS (Torque Max Limit) Limit.

Torque Max Limit Text


Normal

Torque Max Limit

INTWA_06 = 0

NLS (Torque Max Limit)


normal

INTWA_07 = 1

Torque Reference Min Limit

24.3

25.1

25.2

25.3

26.1

26.2

26.3

27.1

27.2

27.3

28.1

28.2

Red

Grey

Torque Reference Min


Limit
Limit

Red

From MMCX.FL.

Torque Reference Min


Limit Text
Limit

Torque Reference Min


Limit

Torque Reference Min


Limit Text
Normal

Torque Reference Min


Limit

INTWA_07 = 0

NLS (Torque Reference Min


Limit) normal

INTWA_08 = 1

Torque Reference Max Limit

Grey
Red

From MMCX.FL.

Torque Reference Max


Limit Text
Limit

Torque Reference Max


Limit

Torque Reference Max


Limit Text
Normal

Torque Reference Max


Limit

INTWA_08 = 1

NLS (Torque Reference Max


Limit) Limit.

INTWA_08 = 0

NLS (Torque Reference Max


Limit) normal

INTWA_09 = 1

Flux Min Limit

Red

Grey

Flux Min Limit


Limit

Red

From MMCX.FL.

Flux Min Limit Text


Limit

Flux Min Limit

Flux Min Limit Text


Normal

Flux Min Limit

INTWA_09 = 1

NLS (Flux Min Limit) Limit.

INTWA_09 = 0

NLS (Flux Min Limit) normal

INTWA_10 = 1

Frequency Min Limit

Red

Grey

Frequency Min Limit


Limit

3BSE 021 945R401

NLS (Torque Reference Min


Limit) Limit.

Red

Torque Reference Max


Limit
Limit

Frequency Min Limit


Text
Limit

INTWA_07 = 1

Red

From MMCX.FL.

Frequency Min Limit


Red

INTWA_10 = 1

NLS (Frequency Min Limit)


Limit.

147

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

28.3

Frequency Min Limit


Text
Normal

Frequency Min Limit

INTWA_10 = 0

NLS (Frequency Min Limit)


normal

INTWA_11 = 1

Frequency Max Limit

29.1

29.2

29.3

30.1

30.2

30.3

31.1

31.2

31.3

32.1

32.2

32.3

148

Grey

Frequency Max Limit


Limit

Red

From MMCX.FL.

Frequency Max Limit


Text
Limit

Frequency Max Limit

Frequency Max Limit


Text
Normal

Frequency Max Limit

INTWA_11 = 1

NLS (Frequency Max Limit)


Limit.

INTWA_11 = 0

NLS (Frequency Max Limit)


normal

INTWA_12 = 1

DC Under Voltage Limit

Red

Grey

DC Under Voltage Limit


Limit

Red

From MMCX.FL.

DC Under Voltage Limit


Text
Limit

DC Under Voltage
Limit

DC Under Voltage Limit


Text
Normal

DC Under Voltage
Limit

INTWA_12 = 1

NLS (DC Under Voltage Limit)


Limit.

INTWA_12 = 0

NLS (DC Under Voltage Limit)


normal

INTWA_13 = 1

DC Over Voltage Limit

Red

Grey

DC Over Voltage Limit


Limit

Red

From MMCX.FL.

DC Over Voltage Limit


Text
Limit

DC Over Voltage Limit

DC Over Voltage Limit


Text
Normal

DC Over Voltage Limit

INTWA_13 = 1

NLS (DC Over Voltage Limit)


Limit.

INTWA_13 = 0

NLS (DC Over Voltage Limit)


normal

INTWA_14 = 1

Torque Limit

Red

Grey

Torque Limit
Limit

Red

From MMCX.FL.

Torque Limit Text


Limit

Torque Limit

Torque Limit Text


Normal

Torque Limit

INTWA_14 = 1

NLS (Torque Limit) Limit.

INTWA_14 = 0

NLS (Torque Limit) normal

Red

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

33.1

Frequency Limit
Limit

33.2

33.3

Presentation
Red

DRICONE, Engineered drive

Condition

Remarks

INTWA_15 = 1

Frequency Limit
From MMCX.FL.

Frequency Limit Text


Limit

Frequency Limit

Frequency Limit Text


Normal

Frequency Limit

INTWA_15 = 1

NLS (Frequency Limit) Limit.

INTWA_15 = 0

NLS (Frequency Limit) normal

Red

Grey

3.6.2.5 Diagnostic Fault Display for DCS

Data Base Element MMCX is to be named by the main Data Base Element + suffix
<.FL>. This display is used when there is a DCS 500 or DCS 600 drive.
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.FL
Presentation:

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16

3BSE 021 945R401

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

149

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Presentation

Header

FAULTS Grey

2.1

Auxiliary
Under Voltage
Fault

Red flashing

2.2

Auxiliary
Under Voltage
Fault

Red

2.3

Auxiliary
Under Voltage Text
Fault

Auxiliary
Under Voltage

Auxiliary
Under Voltage Text
Normal

Auxiliary
Under Voltage

2.4

3.1

AU_IND1_00 = 1

Unacknowledged Alarm

IND1_00 = 1

Auxiliary Under Voltage Fault

AU_IND1_00 = 1 or

NLS (Auxiliary Under Voltage)


fault

IND1_00 = 1

IND1_00 = 0

NLS (Auxiliary Under Voltage)


normal

AU_IND1_01 = 1

Unacknowledged Alarm

Grey

3.2

Over Current
Fault

Red

3.3

Over Current Text


Fault
Over Current Text
Normal

Over Current Fault


IND1_01 = 1

Over Current Fault

Over Current

AU_IND1_01 = 1 or

NLS (Over Current) fault

Red

IND1_01 = 1

Over Current

IND1_01 = 0

NLS (Over Current) normal

AU_IND1_02 = 1

Unacknowledged Alarm

Grey

Armature
Over Voltage
Fault

Red flashing

4.2

Armature
Over Voltage
Fault

Red

4.3

Armature
Over Voltage Text
Fault

150

Faults title

Red

Red flashing

4.1

Remarks

Auxiliary Under Voltage Fault

Over Current
Fault

3.4

Condition

Armature Over Voltage Fault

Armature
Over Voltage

IND1_02 = 1

Armature Over Voltage Fault

AU_IND1_02 = 1 or

NLS (Armature Over Voltage)


fault.

IND1_02 = 1

Red

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

4.4

Armature
Over Voltage Text
Normal

Armature
Over Voltage

IND1_02 = 0

NLS (Armature Over Voltage)


normal

Converter
Over Temperature
Fault

Red flashing

AU_IND1_03 = 1

Unacknowledged Alarm

5.2

Converter
Over Temperature
Fault

Red

5.3

Converter
Over Temperature Text
Fault

Converter
Over Temperature

Converter
Over Temperature Text
Normal

Converter
Over Temperature

5.1

5.4

6.1

Grey

Converter Over Temperature

6.2

Earth Fault
Fault

Red

6.3

Earth Fault Text


Fault
Earth Fault Text
Normal

NLS (Converter Over


Temperature) fault.

IND1_03 = 1

IND1_03 = 0

NLS (Converter Over


Temperature) normal

AU_IND1_04 = 1

Unacknowledged Alarm
Earth Fault

IND1_04 = 1

Earth Fault

Earth Fault

AU_IND1_04 = 1 or

NLS (Earth Fault) fault.

Red

IND1_04 = 1

Earth Fault

IND1_04 = 0

NLS (Earth Fault) normal

AU_IND1_05 = 1

Unacknowledged Alarm

Grey

Motor 1
Over Temperature
Fault

Red flashing

7.2

Motor 1
Over Temperature
Fault

Red

7.3

Motor 1
Over Temperature Text
Fault

3BSE 021 945R401

AU_IND1_03 = 1 or

Grey
Red flashing

7.1

Converter Over Temperature

Red

Earth Fault
Fault

6.4

IND1_03 = 1

Motor 1 Over Temperature


Fault

Motor 1
Over Temperature

IND1_05 = 1

Motor 1 Over Temperature


Fault

AU_IND1_05 = 1 or

NLS (Motor 1 Over


Temperature) fault.

IND1_05 = 1

Red

151

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

7.4

Motor 1
Over Temperature Text
Normal

Motor 1
Over Temperature

IND1_05 = 0

NLS (Motor 1 Over


Temperature) normal

AU_IND1_06 = 1

Unacknowledged Alarm

8.1

Grey

Motor 1 OverLoad
Fault

Red flashing

8.2

Motor 1 OverLoad
Fault

Red

8.3

Motor 1 OverLoad Text


Fault
Motor 1 OverLoad Text
Normal

8.4

Motor 1 OverLoad Fault


IND1_06 = 1

Motor 1 OverLoad Fault

Motor 1 Overload

AU_IND1_06 = 1 or

NLS (Motor 1 OverLoad) fault.

Red

IND1_06 = 1

Motor 1 Overload

IND1_06 = 0

NLS (Motor 1 OverLoad)


normal

AU_IND1_07 = 1

Unacknowledged Alarm

Grey

I/O Board
Not Found
Fault

Red flashing

9.2

I/O Board
Not Found
Fault

Red

9.3

I/O Board
Not Found Text
Fault
I/O Board
Not Found Text
Normal

9.1

9.4

10.1

I/O Board Not Found


IND1_07 = 1

I/O Board Not Found

I/O Board Not Found

AU_IND1_07 = 1 or

Red

IND1_07 = 1

NLS (I/O Board Not Found)


fault.

I/O Board Not Found

IND1_07 = 0

NLS (I/O Board Not Found)


normal

AU_IND1_08 = 1

Unacknowledged Alarm

Grey

Motor 2
Over Temperature
Fault

Red flashing

10.2

Motor 2
Over Temperature
Fault

Red

10.3

Motor 2
Over Temperature Text
Fault

152

Motor 2 Over Temperature


Fault

Motor 2
Over Temperature

IND1_08 = 1

Motor 2 Over Temperature


Fault

AU_IND1_08 = 1 or

NLS (Motor 2 Over


Temperature) fault.

IND1_08 = 1

Red

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

10.4

Motor 2
Over Temperature Text
Normal

Motor 2
Over Temperature

IND1_08 = 0

NLS (Motor 2 Over


Temperature) normal

AU_IND1_09 = 1

Unacknowledged Alarm

11.1

Grey

Motor 2
OverLoad
Fault

Red flashing

11.2

Motor 2
OverLoad
Fault

Red

11.3

Motor 2
OverLoad Text
Fault
Motor 2
OverLoad Text
Normal

11.4

12.1

Motor 2 OverLoad Fault


IND1_09 = 1

Motor 2 OverLoad Fault

Motor 2 Overload

AU_IND1_09 = 1 or

NLS (Motor 2 OverLoad) fault.

Red

IND1_09 = 1

Motor 2 Overload

IND1_09 = 0

NLS (Motor 2 OverLoad)


normal

AU_IND1_11 = 1

Unacknowledged Alarm

Grey

Mains Under Voltage


Fault

Red flashing

12.2

Mains Under Voltage


Fault

Red

12.3

Mains Under Voltage


Text
Fault
Mains Under Voltage
Text
Normal

12.4

13.1

Mains Under Voltage Fault


IND1_11 = 1

Mains Under Voltage Fault

Mains Under Voltage

AU_IND1_11 = 1 or

Red

IND1_11 = 1

NLS (Mains Under Voltage)


fault.

Mains Under Voltage

IND1_11 = 0

NLS (Mains Under Voltage)


normal

AU_IND1_12 = 1

Unacknowledged Alarm

Grey

Mains Over Voltage


Fault

Red flashing

13.2

Mains Over Voltage


Fault

Red

13.3

Mains Over Voltage Text


Fault

Mains Over Voltage Fault


IND1_12 = 1

Mains Over Voltage Fault

Mains Over Voltage

AU_IND1_12 = 1 or

Red

IND1_12 = 1

NLS (Mains Over Voltage)


fault.

13.4

Mains Over Voltage Text Mains


Normal
Grey

14.1

Not In Synchronism
Fault

3BSE 021 945R401

Over Voltage

Red flashing

IND1_12= 0

NLS (Mains Over Voltage)


normal

AU_IND1_13 = 1

Unacknowledged Alarm
Not In Synchronism Fault

153

DRICONE, Engineered drive

No

Description

14.2
14.3

14.4

15.1

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Not In Synchronism
Fault

Red

IND1_13 = 1

Not In Synchronism Fault

Not In Synchronism Text Not


Fault
Red

In Synchronism

AU_IND1_13 = 1 or

NLS (Not In Synchronism)


fault.

Not In Synchronism Text


Normal

IND1_13 = 1

Not In Synchronism
Red flashing

15.2

Field Ex 1
Over Current
Fault

Red

15.3

Field Ex 1
Over Current Text
Fault

Field Ex 1
Over Current

Field Ex 1
Over Current Text
Normal

Field Ex 1
Over Current

16.1

Field Ex 1
Communication Error
Fault

Red

16.3

Field Ex 1
Communication Error
Text
Fault

Field Ex 1
Communication Error

Field Ex 1
Communication Error
Text
Normal

Field Ex 1
Communication Error

154

IND1_14 = 1

Field Ex 1 Over Current Fault

AU_IND1_14 = 1 or

NLS (Field Ex 1 Over Current)


fault.

IND1_14 = 1

IND1_14 = 0

NLS (Field Ex 1 Over Current)


normal

AU_IND1_15 = 1

Unacknowledged Alarm

Grey

16.2

Armature Current Ripple


Fault

Unacknowledged Alarm

Red

Red flashing

17.1

AU_IND1_14 = 1

Field Ex 1 Over Current Fault

Field Ex 1
Communication Error
Fault

16.4

NLS (Not In Synchronism)


normal

Grey

Field Ex 1
Over Current
Fault

15.4

IND1_13 = 0

Field Ex 1 Communication
Error Fault
IND1_15 = 1

Field Ex 1 Communication
Error Fault

AU_IND1_15 = 1 or

NLS (Field Ex 1
Communication Error) fault.

IND1_15 = 1

Red
IND1_15 = 0

NLS (Field Ex 1
Communication Error) normal

AU_IND2_00 = 1

Unacknowledged Alarm

Grey
Red flashing

Armature Current Ripple Fault

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

17.2

Armature Current Ripple


Fault

17.3

Armature Current Ripple


Text
Fault

Armature Current
Ripple

Armature Current Ripple


Text
Normal

Armature Current
Ripple

17.4

18.1

Presentation

Condition

Remarks

Red

IND2_00 = 1

Armature Current Ripple Fault

AU_IND2_00 = 1 or

NLS (Armature Current


Ripple) Fault.

18.2

Field Ex 2
Over Current
Fault

Red

18.3

Field Ex 2
Over Current Text
Fault

Field Ex 2
Over Current

Field Ex 2
Over Current Text
Normal

Field Ex 2
Over Current

19.2

19.3

19.4

NLS (Armature Current


Ripple) normal

AU_IND2_01 = 1

Unacknowledged Alarm
Field Ex2 Over Current Fault

IND2_01 = 1

Field Ex2 Over Current Fault

AU_IND2_01 = 1 or

NLS (Field Ex2 Over Current)


Fault.

IND2_01 = 1

Red
IND2_01 = 0

NLS (Field Ex2 Over Current)


normal

AU_IND2_02 = 1

Unacknowledged Alarm

Grey

Field Ex 2
Communication Error
Fault

Red flashing

Field Ex 2
Communication Error
Fault

Red

Field Ex2
Communication Error
IND2_02 = 1

Field Ex2
Communication Error
Fault

Field Ex 2
Communication Error
Text
Fault

Field Ex 2
Communication Error

Field Ex 2
Communication Error
Text
Normal

Field Ex 2
Communication Error

3BSE 021 945R401

IND2_00 = 0

Grey
Red flashing

19.1

IND2_00 = 1

Red

Field Ex 2
Over Current
Fault

18.4

DRICONE, Engineered drive

AU_IND2_02 = 1 or
IND2_02 = 1

NLS (Field Ex2


Communication Error) Fault.

Red
IND2_02 = 0

NLS (Field Ex2


Communication Error) normal

Grey

155

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

20.1

Phase Sequence
Fault

Red flashing

20.2

Phase Sequence
Fault

Red

20.3

Phase Sequence Text


Fault

Condition

Remarks

AU_IND2_03 = 1

Unacknowledged Alarm
Phase Sequence Fault

IND2_03 = 1

Phase Sequence Fault

Phase Sequence

AU_IND2_03 = 1 or

NLS (Phase Sequence) Fault.

Red

IND2_05 = 1

Phase Sequence Text


Normal

Phase Sequence

IND2_03 = 0

NLS (Phase Sequence)


normal

No Field Acknowledge
Fault

Red flashing

AU_IND2_04 = 1

Unacknowledged Alarm

21.2

No Field Acknowledge
Fault

Red

21.3

No Field
Acknowledge Text
Fault

No Field
Acknowledge

No Field
Acknowledge Text
Normal

No Field
Acknowledge

20.4

21.1

21.4

22.1

Grey

No Field Acknowledge Fault


No Field Acknowledge Fault

AU_IND2_04 = 1 or

NLS (No Field Acknowledge)


Fault.

IND2_04 = 1

Red
IND2_04 = 0

NLS (No Field Acknowledge)


normal

AU_IND2_05 = 1

Unacknowledged Alarm

Grey

Speed Measured
Fault

Red flashing

22.2

Speed Measured
Fault

Red

22.3

Speed Measured Text


Fault
Speed Measured Text
Normal

22.4

IND2_04 = 1

Speed Measured Fault


IND2_05 = 1

Speed Measured Fault

Speed Measured

AU_IND2_05 = 1 or

NLS (Speed Measured) Fault.

Red

IND2_05 = 1

Speed Measured

IND2_05 = 0

NLS (Speed Measured)


normal

Grey

23.1

No External Fan
Acknowledge
Fault

Red flashing

AU_IND2_06 = 1

No External Fan Acknowledge


Fault

23.2

No External Fan
Acknowledge
Fault

Red

IND2_06 = 1

Unacknowledged Alarm

156

No External Fan Acknowledge


Fault

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

23.3

No External Fan
Acknowledge Text
Fault

No External Fan
Acknowledge

AU_IND2_06 = 1 or

NLS (No External Fan


Acknowledge) Fault.

No External Fan
Acknowledge Text
Normal

No External Fan
Acknowledge

No Main Contactor
Acknowledge
Fault

Red flashing

24.2

No Main Contactor
Acknowledge
Fault

Red

24.3

No Main Contactor
Acknowledge Text
Fault

No Main Contactor
Acknowledge

No Main Contactor
Acknowledge Text
Normal

No Main Contactor
Acknowledge

23.4

24.1

24.4

25.1

Red

AU_IND2_7 = 1

Unacknowledged Alarm

IND2_7 = 1

No Main Contactor
Acknowledge Fault

AU_IND2_7 = 1 or

NLS (No Main Contactor


Acknowledge) Fault.

IND2_11 = 1

Red
IND2_7 = 0

NLS (No Main Contactor


Acknowledge) normal

AU_IND2_8 = 1

Unacknowledged Alarm

Grey

25.2

Type Coding
Fault

Red

25.3

Type Coding Text


Fault
Type Coding Text
Normal

Type Coding Fault


IND2_8 = 1

Type Coding Fault

Type Coding

AU_IND2_8 = 1 or

NLS (Type Coding) Fault.

Red

IND2_8 = 1

Type Coding

IND2_8 = 0

NLS (Type Coding) normal

AU_IND2_9 = 1

Unacknowledged Alarm

Grey

Paramater Backup
Fault

Red flashing

26.2

Paramater Backup
Fault

Red

26.3

Paramater Backup Text


Fault

3BSE 021 945R401

NLS (No External Fan


Acknowledge) normal

No Main Contactor
Acknowledge Fault

Red flashing

26.1

IND2_06 = 0

Grey

Type Coding
Fault

25.4

IND2_09 = 1

Paramater Backup Fault


IND2_9 = 1

Paramater Backup Fault

Paramater Backup

AU_IND2_9 = 1 or

Red

IND2_9 = 1

NLS (Paramater Backup)


Fault.

157

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

26.4

Paramater Backup Text


Normal

Paramater Backup

IND2_9 = 0

NLS (Paramater Backup)


normal

AU_IND2_10 = 1

Unacknowledged Alarm

27.1

Grey

No C Fan Acknowledge
Fault

Red flashing

27.2

No C Fan Acknowledge
Fault

Red

27.3

No C Fan Acknowledge
Text
Fault

No C Fan
Acknowledge

No C Fan Acknowledge
Text
Normal

No C Fan
Acknowledge

27.4

28.1

No C Fan Acknowledge Fault

28.2

DDCS Communication
Channel 0
Fault

Red

28.3

DDCS Communication
Channel 0 Text
Fault

DDCS Communication
Channel 0

DDCS Communication
Channel 0 Text
Normal

DDCS Communication
Channel 0

NLS (No C Fan


Acknowledge) Fault.

IND2_10 = 1

IND2_10 = 0

NLS (No C Fan


Acknowledge) normal

AU_IND2_11 = 1

Unacknowledged Alarm
DDCS Communication
Channel 0 Fault

IND2_11 = 1

DDCS Communication
Channel 0 Fault

AU_IND2_11 = 1 or

NLS (DDCS Communication


Channel 0) Fault.

IND2_11 = 1

Red
IND2_11 = 0

NLS (DDCS Communication


Channel 0) normal

AU_IND2_12 = 1

Unacknowledged Alarm

Grey

Field Exciter 1
Not OK
Fault

Red flashing

29.2

Field Exciter 1
Not OK
Fault

Red

29.3

Field Exciter 1
Not OK Text
Fault

158

AU_IND2_10 = 1 or

Grey
Red flashing

29.1

No C Fan Acknowledge Fault

Red

DDCS Communication
Channel 0
Fault

28.4

IND2_10 = 1

Field Exciter 1 Not OK Fault

Field Exciter 1
Not OK

IND2_12 = 1

Field Exciter 1 Not OK Fault

AU_IND2_12 = 1 or

NLS (Field Exciter 1 Not OK)


Fault.

IND2_13 = 1

Red

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

29.4

Field Exciter 1
Not OK Text
Normal

Field Exciter 1
Not OK

IND2_12 = 0

NLS (Field Exciter 1 Not OK)


normal

AU_IND2_13 = 1

Unacknowledged Alarm

30.1

Grey

Field Exciter 2
Not OK
Fault

Red flashing

30.2

Field Exciter 2
Not OK
Fault

Red

30.3

Field Exciter 2
Not OK Text
Fault

Field Exciter 2
Not OK

Field Exciter 2
Not OK Text
Normal

Field Exciter 2
Not OK

30.4

31.1

Field Exciter 2 Not OK Fault


IND2_13 = 1

Field Exciter 2 Not OK Fault

AU_IND2_13 = 1 or

NLS (Field Exciter 2 Not OK)


Fault.

IND2_13 = 1

Red
IND2_13 = 0

NLS (Field Exciter 2 Not OK)


normal

AU_IND2_14 = 1

Unacknowledged Alarm

Grey

Motor Stalled
Fault

Red flashing

31.2

Motor Stalled
Fault

Red

31.3

Motor Stalled Text


Fault

Motor Stalled Fault


IND2_14 = 1

Motor Stalled Fault

Motor Stalled

AU_IND2_14 = 1 or

NLS (Motor Stalled) Fault.

Red

IND2_14 = 1

Motor Stalled Text


Normal

Motor Stalled

IND2_14 = 0

NLS (Motor Stalled) normal

Motor Over Speed


Fault

Red flashing

AU_IND2_15 = 1

Unacknowledged Alarm

32.2

Motor Over Speed


Fault

Red

32.3

Motor Over Speed Text


Fault
Motor Over Speed Text
Normal

31.4

32.1

32.4

3BSE 021 945R401

Grey

Motor Over Speed Fault


IND2_15 = 1

Motor Over Speed Fault

Motor Over Speed

AU_IND2_15 = 1 or

Red

IND2_15 = 1

NLS (Motor Over Speed)


Fault.

Motor Over Speed

IND2_15 = 0

Grey

NLS (Motor Over Speed)


normal

159

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

3.6.2.6 Diagnostic Alarm Display for DCS

Data Base Element MMCX is to be named by the main Data Base Element + suffix
<.AL>. This display is used when there is a DCS 500 orDCS 600 drive.
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.AL.
Presentation:

1
2
3
4
5
6
7

15
16
17
18
19
21

8
9
10
11
12
13
14

Behavior:
No

Description

Presentation

Header

ALARMS Grey

2.1

Start Inhibition
Alarm

Red flashing

Start Inhibition
Alarm

Red

2.2

160

Condition

Remarks
Alarms title.

AU_IND1_00 = 1

Unacknowledged Alarm
Start InhibitionAlarm

IND1_00 = 1

Start InhibitionAlarm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

2.3

Start InhibitionText
Alarm

Start Inhibition

AU_IND1_00 = 1 or

NLS (Start Inhibition) alarm.

Red

IND1_00 = 1

Start InhibitionText
Normal

Start Inhibition

IND1_00 = 0

NLS (Start Inhibition) normal

AU_IND1_01 = 1

Unacknowledged Alarm

2.4

3.1

Grey

Emergency Stop
Alarm

Red flashing

3.2

Emergency Stop
Alarm

Red

3.3

Emergency Stop Text


Alarm
Emergency Stop Text
Normal

3.4

4.1

Emergency Stop Alarm


IND1_01 = 1

Emergency Stop Alarm

Emergency Stop

AU_IND1_01 = 1 or

NLS (Emergency Stop) alarm.

Red

IND1_01 = 1

Emergency Stop

IND1_01 = 0

NLS (Emergency Stop)


normal

AU_IND1_02 = 1

Unacknowledged Alarm

Grey

Temperature Alarm
Motor 1
Alarm

Red flashing

4.2

Temperature Alarm
Motor 1
Alarm

Red

4.3

Temperature Alarm
Motor 1 Text
Alarm

Temperature Alarm
Motor 1

Temperature Alarm
Motor 1 Text
Normal

Temperature Alarm
Motor 1

4.4

5.1

Temperature Alarm Motor 1


Alarm
Temperature Alarm Motor 1
Alarm

AU_IND1_02 = 1 or

NLS (Temperature Alarm


Motor 1) alarm.

IND1_02 = 1

Red
IND1_02 = 0

NLS (Temperature Alarm


Motor 1) normal

AU_IND1_03 = 1

Unacknowledged Alarm

Grey

Overload Alarm Motor 1


Alarm

Red flashing

5.2

Overload Alarm Motor 1


Alarm

Red

5.3

Overload Alarm Motor 1


Text
Alarm

3BSE 021 945R401

IND1_02 = 1

Overload Alarm Motor 1 Alarm

Overload Alarm
Motor 1

IND1_03 = 1

Overload Alarm Motor 1 Alarm

AU_IND1_03 = 1 or

NLS (Overload Alarm Motor 1)


alarm.

IND1_03 = 1

Red

161

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

5.4

Overload Alarm Motor 1


Text
Normal

Overload Alarm
Motor 1

IND1_03 = 0

NLS (Overload Alarm Motor 1)


normal

AU_IND1_04 = 1

Unacknowledged Alarm

6.1

Grey

Over Temperature
Converter
Alarm

Red flashing

6.2

Over Temperature
Converter
Alarm

Red

6.3

Over Temperature
Converter Text
Alarm

Over Temperature
Converter

Over Temperature
Converter Text
Normal

Over Temperature
Converter

6.4

7.1

Over Temperature Converter


Alarm

7.2

Current Register
Blocked
Alarm

Red

7.3

Current Register
Blocked Text
Alarm

Current Register
Blocked

Current Register
Blocked Text
Normal

Current Register
Blocked

NLS (Over Temperature


Converter) alarm.

IND1_04 = 1

IND1_04 = 0

NLS (Over Temperature


Converter) normal

AU_IND1_05 = 1

Unacknowledged Alarm
Current Register Blocked
Alarm

IND1_05 = 1

Current Register Blocked


Alarm

AU_IND1_05 = 1 or

NLS (Current Register


Blocked) alarm.

IND1_05 = 1

Red
IND1_05 = 0

NLS (Current Register


Blocked) normal

AU_IND1_07 = 1

Unacknowledged Alarm

Grey

RAM Backup Failed


Alarm

Red flashing

8.2

RAM Backup Failed


Alarm

Red

8.3

RAM Backup Failed Text


Alarm

162

AU_IND1_04 = 1 or

Grey
Red flashing

8.1

Over Temperature Converter


Alarm

Red

Current Register
Blocked
Alarm

7.4

IND1_04 = 1

RAM Backup Failed Alarm


IND1_07 = 1

RAM Backup Failed Alarm

RAM Backup Failed

AU_IND1_07 = 1 or

Red

IND1_07 = 1

NLS (RAM Backup Failed)


alarm.

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

8.4

RAM Backup Failed Text RAM


Normal
Grey

9.1

Temperature Alarm
Motor 2
Alarm

Red flashing

9.2

Temperature Alarm
Motor 2
Alarm

Red

9.3

Temperature Alarm
Motor 2 Text
Alarm

Temperature Alarm
Motor 2

Temperature Alarm
Motor 2 Text
Normal

Temperature Alarm
Motor 2

9.4

10.1

Presentation

Backup Failed

Overload Alarm Motor 2


Alarm

Red

10.3

Overload Alarm Motor 2


Text
Alarm

Overload Alarm
Motor 2

Overload Alarm Motor 2


Text
Normal

Overload Alarm
Motor 2

NLS (RAM Backup Failed)


normal

AU_IND1_08 = 1

Unacknowledged Alarm

IND1_08 = 1

Temperature Alarm Motor 2


Alarm

AU_IND1_08 = 1 or

NLS (Temperature Alarm


Motor 2) alarm.

IND1_08 = 1

IND1_08 = 0

NLS (Temperature Alarm


Motor 2) normal

AU_IND1_09 = 1

Unacknowledged Alarm
Overload Alarm Motor 2 Alarm

IND1_09 = 1

Overload Alarm Motor 2 Alarm

AU_IND1_09 = 1 or

NLS (Overload Alarm Motor 2)


alarm.

IND1_09 = 1

Red
IND1_09 = 0

NLS (Overload Alarm Motor 2)


normal

AU_IND1_10 = 1

Unacknowledged Alarm

Grey

Mains Under Voltage


Alarm

Red flashing

11.2

Mains Under Voltage


Alarm

Red

11.3

Mains Under Voltage


Text
Alarm
Mains Under Voltage
Text
Normal

3BSE 021 945R401

IND1_07 = 0

Grey

10.2

11.4

Remarks

Red

Red flashing

11.1

Condition

Temperature Alarm Motor 2


Alarm

Overload Alarm Motor 2


Alarm

10.4

DRICONE, Engineered drive

Mains Under Voltage Alarm


IND1_10 = 1

Mains Under Voltage Alarm

Mains Under Voltage

AU_IND1_10 = 1 or

Red

IND1_10 = 1

NLS (Mains Under Voltage)


alarm.

Mains Under Voltage

IND1_10 = 0

Grey

NLS (Mains Under Voltage)


normal

163

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

12.1

Converter Fan
Acknowledged
Alarm

Red flashing

12.2

Converter Fan
Acknowledged
Alarm

Red

12.3

Converter Fan
Acknowledged Text
Alarm

Converter Fan
Acknowledged

Converter Fan
Acknowledged Text
Normal

Converter Fan
Acknowledged

12.4

Presentation

Armature Current
Device
Alarm

Red

13.3

Armature Current
Device Text
Alarm

Armature Current
Device

Armature Current
Device Text
Normal

Armature Current
Device

IND1_12 = 1

Converter Fan Acknowledged


Alarm

AU_IND1_12 = 1 or

NLS (Converter Fan


Acknowledged) alarm.

IND1_12 = 1

IND1_12 = 0

NLS (Converter Fan


Acknowledged) normal

AU_IND1_13 = 1

Unacknowledged Alarm
Armature Current Device
Alarm

IND1_13 = 1

Armature Current Device


Alarm

AU_IND1_13 = 1 or

NLS (Armature Current


Device) alarm.

IND1_13 = 1

Red
IND1_13 = 0

NLS (Armature Current


Device) normal

AU_IND1_15 = 1

Unacknowledged Alarm

Grey

External Fan
Acknowledged
Fault

Red flashing

14.2

External Fan
Acknowledged
Fault

Red

14.3

External Fan
Acknowledged
Fault

164

Unacknowledged Alarm

Grey

13.2

14.1

AU_IND1_12 = 1

Red

Red flashing

13.4

Remarks
Converter Fan Acknowledged
Alarm

Armature Current
Device
Alarm

13.1

Condition

External Fan Acknowledged

External Fan
Acknowledged

IND1_15 = 1

External Fan Acknowledged

AU_IND1_15 = 1 or

NLS (External Fan


Acknowledged) fault.

IND1_15 = 1

Red

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

No

Description

Presentation

Condition

Remarks

14.4

External Fan
Acknowledged
Normal

External Fan
Acknowledged

IND1_15 = 0

NLS (External Fan


Acknowledged) normal

AU_IND2_00 = 1

Unacknowledged Alarm

15.1

Grey

Panel Loss
Fault

Red flashing

15.2

Panel Loss
Fault

Red

15.3

Panel Loss Text


Fault
Panel Loss Text
Normal

15.4

16.1

Panel Loss
IND2_00 = 1

Panel Loss

Panel Loss

AU_IND2_00 = 1 or

NLS (Panel Loss) fault.

Red

IND2_00 = 1

Panel Loss

IND2_00 = 0

NLS (Panel Loss) normal

AU_IND2_01 = 1

Unacknowledged Alarm

Grey

Type Code Changed


Fault

Red flashing

16.2

Type Code Changed


Fault

Red

16.3

Type Code Changed


Text
Fault
Type Code Changed
Text
Normal

16.4

17.1

Type Code Changed Fault


IND2_01 = 1

Type Code Changed Fault

Type Code Changed

AU_IND2_01 = 1 or

Red

IND2_01 = 1

NLS (Type Code Changed)


fault.

Type Code Changed

IND2_01 = 0

NLS (Type Code Changed)


normal

AU_IND2_02 = 1

Unacknowledged Alarm

Grey

Init Values Read, S2


Fault

Red flashing

17.2

Init Values Read, S2


Fault

Red

17.3

Init Values Read, S2 Text


Fault

Init Values Read, S2 Fault


IND2_02 = 1

Init Values Read, S2 Fault

Init Values Read, S2

AU_IND2_02 = 1 or

Red

IND2_02 = 1

NLS (Init Values Read, S2)


fault.

17.4

Init Values Read, S2 Text Init Values


Normal
Grey

18.1

Param Set 2 Missing


Fault

Red flashing

Param Set 2 Missing


Fault

Red

18.2

3BSE 021 945R401

Read, S2

IND2_02 = 0

NLS (Init Values Read, S2)


normal

AU_IND2_03 = 1

Unacknowledged Alarm
Param Set 2 Missing Fault

IND2_03 = 1

Param Set 2 Missing Fault

165

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

18.3

Param Set 2 Missing


Text
Fault

Param Set 2 Missing

AU_IND2_03 = 1 or

Red

IND2_03 = 1

NLS (Param Set 2 Missing)


fault.

Param Set 2 Missing


Text
Normal

Param Set 2 Missing

IND2_03 = 0

NLS (Param Set 2 Missing)


normal

AU_IND2_04 = 1

Unacknowledged Alarm

18.4

19.1

Grey

Backup Not Allowed


Fault

Red flashing

19.2

Backup Not Allowed


Fault

Red

19.3

Backup Not Allowed


Text
Fault
Backup Not Allowed
Text
Normal

19.4

20.1

Backup Not Allowed Fault


IND2_04 = 1

Backup Not Allowed Fault

Backup Not Allowed

AU_IND2_04 = 1 or

Red

IND2_04 = 1

NLS (Backup Not Allowed)


fault.

Backup Not Allowed

IND2_04 = 0

NLS (Backup Not Allowed)


normal

AU_IND2_05 = 1

Unacknowledged Alarm

Grey

Write Backup
Fault

Red flashing

20.2

Write Backup
Fault

Red

20.3

Write Backup Text


Fault
Write Backup Text
Normal

20.4

166

Write Backup Fault


IND2_05 = 1

Write Backup Fault

Write Backup

AU_IND2_05 = 1 or

NLS (Write Backup) fault.

Red

IND2_05 = 1

Write Backup

IND2_05 = 0

NLS (Write Backup) normal

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONE, Engineered drive

3.6.3 Graphic Element


3.6.3.1 Motor01

Presentation:

Behavior:
No

Description

Presentation

Condition

Remarks

SelectFrame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Black

3BSE 021 945R401

167

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

PointOfControl - Visible

ModeVisible = true

O Yellow

IND2_00= 0

Out of service

D Yellow

IND2_09= 0

Drive Local Control

J Yellow

BOOL_C = 1 and
IND2_09 = 1

Jog Control

L Green

BOOL_D = 1 and
IND2_09 = 1

Local Control

A Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

NLS (Auto)

BOOL_A = 1 and

NLS (Man)

ManModeVisible = true

M Green

BOOL_B = 0 and
IND2_09 = 1
ManModeVisible = false
Control point

C Green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central Control

Point OfControlVisible =
false

Control point not visible

Direction Indication

DirectionVisible = true
Green

IND2_02 = 1 and

Forward

speed value positive

Green

IND2_02 = 1 and

Reverse

speed value negative

168

Green

IND2_01 = 1

Run permitted

DirectionVisible = false

Direction is invisible

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

DriveStatus

Light brown

shape

DRICONE, Engineered drive

Condition

Remarks

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

IND2_01 = 1

Drive ready to start

Green

Green

Green
Ready Run
Green

Red flashing

IND2_02 = 1

Drive running

AU_IND1_09 = 1 or

Unacknowledged alarm

AU_IND1_10 = 1 or
AU_IND1_11 = 1 or
AU_IND1_12 = 1
Red

Green

IND1_09 = 1 or

Fault

IND1_10 = 1 or

Warning

IND1_11 = 1 or

Limit

IND1_12 = 1

Communication error

The conditions are in priority order. Underlined parameters are configurable.

3BSE 021 945R401

169

DRICONE, Engineered drive

Section 3, Faceplates and Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default)

Remarks

PointOfControlVisible

2. Control Point

true, false

Show point of control or not.

ManModeVisible

2. Control Point

true, false

True = show M when manual


mode. False = show C when
manual mode.

DirectionVisible

3. Direction

true, false

Show Direction or not.

170

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

3.7 DRICONS, Standard drive


3.7.1 Faceplate
Presentation:

3BSE 021 945R401

171

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

172

Default Presentation

Condition

M Dark green

BOOL_A = 1 and
BOOL_B = 0 and
IND2_09 = 1

A Dark green

BOOL_A = 0 and
BOOL_B = 1 and
IND2_09 = 1

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Default Presentation

Condition

Remarks

3.2

Control point

O Light brown

IND2_00 = 0

Out of service.

D Yellow

IND2_09 = 0

Drive local

J Yellow

IND2_09 = 1 and
BOOL_C = 1

Jog running from motor


place

L Dark green

IND2_09 = 1 and
BOOL_D = 1

Local controlled from


local panel

C Dark green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central controlled from


operators panel

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Interlock indications

X Yellow

(IND2_12 = 1 and IND2_02 = 1


and BOOL_F = 1
and IND2_15 = 0)

B- Interlock 3

or

B - Interlock 4

(IND2_13 = 1 and IND2_02 = 1


and BOOL_F = 1)

X Green

3BSE 021 945R401

(IND2_08 = 1) or
(IND2_10 = 1 and IND2_15 = 0 )
or
IND2_11 = 1
or
(IND2_12 = 1 and BOOL_F = 0
and IND2_15 = 0 )
or
(IND2_12 = 1 and IND2_02 = 0
and BOOL_F = 1
and IND2_15 = 0)
or
(IND2_13 = 1 and BOOL_F = 0)
or
(IND2_13 = 1 and IND2_02 = 0
and BOOL_F = 1)
or
IND2_14 = 1

C - interlock

BX Red

IND1_15 = 1

Override Interlock and


Interlock active

BX Yellow

(BOOL_C = 1 or IND2_15 = 1)
and IND1_15=0

Override Interlock and


Interlock active

B - Interlock 1
B - Interlock 2
B- Interlock 3

B - Interlock 4

IA- Interlock

173

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Aspect links

Diagnostic Display

position 0, 0, 7

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

174

Remarks

Start

Start motor

Set MORD_02 = 1

Stop

Stop motor

Set MORD_03 = 1

Man

Set to Man Mode

Set MORD_14 = 1

Auto

Set to Auto Mode

Set MORD_15 = 1

Cen

Set to Central Control

Set MORD_10 = 1

Loc

Set to Local Control

Set MORD_11 = 1

Jog

Set to Jog Control

Set MORD_12 = 1

OoS

Set to Out of Service


Control

Set MORD_13 = 1

O SP

Set use of operator


setpoint

Set MORD_06 = 1

E SP

Set use of external setpoint

Set MORD_07 = 1

ResF

Reset Drive fault

Set MORD_08 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

3.7.1.1 Control and Reduced Control

Presentation:
2

4
5
6
7
8
9
10
11

3BSE 021 945R401

11

175

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Presentation

Motor Status

Light brown

Condition

Remarks

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

IND2_02 = 1

Drive running

IND2_01 = 1

Drive ready to start

Green

Green

Green

Green
Ready Run

Running mode
Indication

Medium Green
(Centre part)

IND2_02=1

Medium Green, Light


green, Dark green, Black
(Centre part background)

All others except out of


service.
IND2_02 = 1 and

Running

Forward

speed value positive

IND2_02 = 1 and

Reverse

speed value negative

176

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

DRICONS, Standard drive

Condition

Remarks

IND2_01 = 1

Run permitted

Comm Err Red Flash

AU_IND1_12 = 1

NLS (Communication Error)


unacknowledged fault

Comm Err Red

IND1_12 = 1

NLS (Communication Error)

Fault Red Flash

AU_IND1_11 = 1

NLS (Fault)
unacknowledged fault

Fault Red

IND1_11 = 1

NLS (Fault)

Warning Red Flash

AU_IND1_10 = 1

NLS (Warning)
unacknowledged warning

Warning Red

IND1_10 = 1

NLS (Warning)

At Limit Red Flash

AU_IND1_09 = 1

NLS (Limit)
unacknowledged limit

At Limit Red

IND1_09 = 1

NLS (Limit)

Not At Setpoint

IND2_02 = 1 and

Green

IND2_07 = 0

NLS (Actual value at not


reference)

IND2_01 = 1 and

NLS (Ready Run)

2 cont.

Green
3

Warning text

Information text

Ready Run Green

ind2_02 = 0

Ready Green

IND2_00 = 1 and

NLS (Ready

IND2_02 = 0
5.1

Headline Speed

Speed Black

INTWB_00 = 1

NLS (Speed)

5.2

Speed value

Black

REAL_C

Numeric presentation of
speed value 1

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

String (5)

PRES_A(1-5)

Unit of measured Speed

5.3

Unit Speed

Black

3BSE 021 945R401

177

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

6.1

Headline Set Point


Speed

E SP1 Spd Black

Condition

Remarks

INTWB11 = 1 and

NLS (E SP1 Spd)

BOOL_E = 1

E SP2 Spd Black

INTWB_12 = 1 and

NLS (E SP2 Spd)

BOOL_E = 1

SP1 Speed Black

INTWB_11 = 1 and

NLS (SP1 Speed )

BOOL_E = 0

SP2 Speed Black

INTWB_12 = 1 and

NLS (SP 2 Speed )

BOOL_E = 0
6.2

SetPoint speed value

ESP1, Black

REAL_D (help drive


object) and

External set point value for


speed unit

(BOOL_E = 1 and
INTWB11= 1)
ESP2, Black

REAL_D and

Set point value for speed %

(BOOL_E = 1
INTWB12=1)
SP1, Black

SP2, Black

REAL_PARAM (help drive Set point value for speed


object) and (BOOL_E = 0 unit
and INTWB11=1)
REAL_PARAM and

Set Point value for speed %

(BOOL_E = 0 and
INTWB12=1)
6.3

Unit SetPoint Speed

String (5) Black

(INTWB_11 = 1 and
BOOL_E = 1)

unit

or
(INTWB_11 = 1 and
BOOL_E = 0)
PRES_A(1-5)

% Black

(INTWB_12 = 1 and
BOOL_E =1)

or
(INTWB12 = 1 and
BOOL_E = 0) and
7.1

178

Headline Current

Black

INTWB_01 = 1

NLS (Current)

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

7.2

Current value

Value string, Black

REAL_RES

Numeric presentation of
Current

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

7.3

Current Unit

% Black

8.1

Headline Torque

Black

INTWB_02 = 1

NLS (Torque)

8.2

Torque value

Black

REAL_A

Numeric presentation of
Torque

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

8.3

Torque Unit

% Black

9.1

Headline External Set


Point Torque/ Set Point
Torque/
PID

E SP Torq Black

Unit of current

Unit of Torque
INTWB_14 = 1 and
BOOL_E = 1

Head line of External Set


Point Torque
NLS (E SP Torque)

SP Torque Black

INTWB_14 = 1 and
BOOL_E = 0

Head line of External Set


Point Torque
NLS (SP Torque)

E SP PID Black

INTWB_13 = 1 and
BOOL_E = 1

Head line of External Set


Point PID
NLS (E SP PID)

SP PID Black

INTWB_13 = 1 and
BOOL_E = 0

Head line of External Set


Point PID
NLS (SP PID)

3BSE 021 945R401

179

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

9.2

External Set Point


Torque/ Set Point
Torque / PID/

E SP Torque Black

Condition

Remarks

REAL_E and

External set point value for


torque

(BOOL_E = 1 and
INTWB14= 1)
SP Torque, Black

REAL_PARAM and

Set point value for torque

(BOOL_E = 0
INTWB14=1)
E SP PID, Black

REAL_E and
(BOOL_E = 1 and
INTWB13= 1)

SP PID, Black

REAL_PARAM and

External set point value for


PID

Set Point value for PID

(BOOL_E = 0 and
INTWB13=1)
9.3

10.1

10.2

Unit External Set Point


Torque/ Set Point
Torque / PID

String (5)

Unit of External Set Point


Torque or Set Point Torque
or PID

Baragraph text

Current, Black

INTWB_01 = 1

NLS (Current) Current

Torque, Black

INTWB_02 = 1

NLS (Torque) Torque

INTWB_01 = 1 or

Bar graph Visible

Black

Motor Current

INTWB_02 = 1
10.3

180

Motor Current

Bar graph +, Magenta

INTWB_02 = 1 and
REAL_A
REAL_A_MIN to
REAL_A_MAX

Motor torque value

Bar graph +/-, Magenta

INTWB_02 = 1 and
REAL_A_MIN<0
REAL_A
-REAL_A_MAX to
REAL_A_MAX

Motor torque value

Bar graph +, Brown

INTWB_01 = 1 and
REAL_RES
REAL_RES_MIN to
REAL_RES_MAX

Motor current value

Bar graph +/-, Brown

INTWB_01 = 1 and
REAL_RES_MIN<0
REAL_RES
-REAL_RES_MAX to
REAL_RES_MAX

Motor current value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

10.4

Hi Load Indication

at 100%

INTWB_01 = 1 and

Limit Visible for current only.

REAL_RES_HILIM>0.02
Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_HILIM

Above high load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_HILIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_HILIM

Red
Unfilled, Grey
10.5

Normal Load Limit


Indication

Arrow (polygon)

Alarm blocked

The value of current has


passed the high load limit.
Not high load

REAL_RES_LOLIM>0.02

Limit Visible

at REAL_RES_LOLIM

Upper limit of normal load

REAL_RES_MIN to
REAL_RES_MAX
Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_LOLIM

Above normal load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_LOLIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_LOLIM

Grey
Unfilled, Grey

3BSE 021 945R401

Alarm blocked

The value of current has


passed the normal load
limit.
Normal

181

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

11

Blocking Interlock text

Interlock text Red

ACT_PRES_TEXT

Get the actual interlock text


from the database. Valid for
interlocks IC, IB1-IB4,

Interlock text Yellow

ACT_PRES_TEXT

Get the actual interlock text


from the database. Valid for
interlock IA

Condition

Remarks

3.7.1.2 Block

Presentation:

Behavior:
No

Description

Override Interlock

Block Alarm

Default Presentation

IND2_15 Indicates current


status

Yellow

Blocked

Override pressed

MORD_04 = 1

Normal pressed

MORD_05 = 1

Block Alarm Black

Yellow

182

Blocked

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.
3

Block Printout

DRICONS, Standard drive

Default Presentation

Condition

Block pressed

ALARM_BLK = 1

Deblock pressed

ALARM_BLK = 0

Remarks

Block Alarm Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

3.7.2 Displays
3.7.2.1 Object Display

Presentation:
9

1
2

10

11

12
13
14
15

3
4
5
6
7
8

16
17
18
19
20
21

40

22

41
23
24

42

25

43
44
45

26
27
28
29

46

35-39

3BSE 021 945R401

30-34

183

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Presentation

Condition

Remarks

Select Frame

White

SELECTED = 1

Object select frame

Grey

Header
Red flashing

NAME and DESCR

Object name and description

AU_IND1_11 = 1 or

Unacknowledged alarm

AU_IND1_10 = 1 or
AU_IND1_09 = 1 or
AU_IND1_12 = 1
Red

IND1_11 = 1 or

Fault

IND1_10 = 1 or

Warning

IND1_09 = 1 or

Limit

IND1_12 = 1

Communication error

Green
3.1

3.2

4.1

4.2

5.1

5.2

184

Range Max Speed

Range Min Speed

Range Max Current

Range Min Current

Range Max Torque

Range Min Torque

Trim Curve Speed

Normal

Green

REAL_C_MAX

INTWB_00 = 1

Green

REAL_C_MIN

INTWB_00 = 1

Brown

REAL_RES_MAX

INTWB_01 = 1

Brown

REAL_RES_MIN

INTWB_01 = 1

Magenta

REAL_A_MAX

INTWB_02 = 1

Magenta

REAL_A_MIN

INTWB_02 = 1

Limit visible

Green

REAL_C

Trim curve for speed

INTWB_00 = 1

Trim curve visible

Limit visible

Limit visible

Limit visible

Limit visible

Limit visible

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

Trim Curve Current

Brown

REAL_RES

Trim curve for current

INTWB_01 = 1

Trim curve visible

Magenta

REAL_A

Trim curve for Torque

INTWB_02 = 1

Trim Curve visible

Green

REAL_C

Speed bar graph

INTWB_00 = 1 and

Bar graph when speed min


value is positive.

9.1

Trim Curve Torque

Bar graph Speed

Bar graph +

REAL_C
REAL_C_MIN to
REAL_C_MAX
Bar graph +/-

INTWB_00 = 1 and
REAL_C_MIN<0

Bar graph when speed min


value is negative.

REAL_C
-REAL_C_MAX to
REAL_C_MAX
10.1

Bar graph Current

Brown
Bar graph +

REAL_RES

Current bar graph

INTWB_01 = 1 and

Bar graph when current min


value is positive.

REAL_RES
REAL_RES_MIN to
REAL_RES_MAX
Bar graph +/-

INTWB_01 = 1 and
REAL_RES_MIN<0

Bar graph when current min


value is negative.

REAL_RES
-REAL_RES_MAX to
REAL_RES_MAX

3BSE 021 945R401

185

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

10.2

Hi Load Indication

at 100%

INTWB_01 = 1

Limit Indication

Filled

ALARM_BLK=1 and

High load, Alarm blocked

Yellow

REAL_RES >
REAL_RES_HILIM
or
ALARM_PERIOD_BLK=1
and
REAL_RES >
REAL_RES_HILIM

Unfilled
Yellow

ALARM_PERIOD_BLK=1
or

Alarm blocked

ALARM_BLK = 1
Filled
Red

REAL_RES >
REAL_RES_HILIM

Unfilled, Grey
10.3

Normal Load Limit


Indication

Arrow (polygon)

The value of current has


passed the high load limit.
Not high load

INTWB_01 = 1

Limit Visible for current only

at REAL_RES_LOLIM

Upper limit of normal load

REAL_RES_MIN to
REAL_RES_MAX
Filled

AL_BLK=1 and

Yellow

REAL_RES >
REAL_RES_LOLIM

Above normal load, Alarm


blocked

or
AL_P_BLK=1 and
REAL_RES >
REAL_RES_LOLIM
Unfilled

AL_P_BLK=1 or

Yellow

AL_BLK = 1

Filled

REAL_RES >
REAL_RES_LOLIM

Grey
Unfilled, Grey

186

Alarm blocked

The value of current has


passed the normal load limit.
Normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

11.1

Bar graph Torque

Magenta

REAL_A

Torque bar graph

INTWB_02 = 1 and

Bar graph when torque min


value is positive.

Bar graph +

REAL_A
REAL_A_MIN to
REAL_A_MAX
Bar graph +/-

INTWB_02 = 1 and
REAL_A_MIN<0

Bar graph when torque min


value is negative.

REAL_A
-REAL_A_MAX to
REAL_A_MAX
12

ALARMS

12.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK =
1

Alarm blocked by PC-program

Red flashing

AU_IND1_11 = 1

Unacknowledged alarm

Red

IND1_11 = 1

Alarm

12.3

12.4

Alarms

Warning Indication

Alarm 1 Text

Fault

NLS (Fault)

Red

IND1_11 = 1 or
AU_IND1_11 = 1

Grey

13.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

13.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK =
1

Alarm blocked by PC-program

Red flashing

AU_IND1_09 = 1

Unacknowledged alarm

Red

IND1_09 = 1

Alarm

13.3

13.4

Warning Indication

Alarm 2 Text

3BSE 021 945R401

At Limit

NLS (At Limit)

Red

IND1_09 = 1 or
AU_IND1_09 = 1

Grey

187

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

14.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

14.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

ALARM_PERIOD_BLK =
1

Alarm blocked by PC-program

Red flashing

AU_IND1_10 = 1

Unacknowledged alarm

Red

IND1_10 = 1

Alarm

14.3

14.4

Warning Indication

Alarm 3 Text

Warning

NLS (Warning)

Red

IND1_10 = 1 or
AU_IND1_10 = 1

Grey

15.1

Printout Blocked

P Yellow

PRINT_BLK = 1

Printout blocked

15.2

Alarm Blocked

B Yellow

ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_PERIOD_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_IND1_12 = 1

Unacknowledged alarm

Red

IND1_12 = 1

Alarm

15.3

15.4

Warning Indication

Alarm 4 Text

Comm. error

NLS (Comm. error)

Red

IND1_12 = 1 or
AU_IND1_12 = 1

Grey

16

INTERLOCKS

Interlocks

16

STATUS

Status

16.1

IC1 Active

16.2

IC1 Text

17.1

IB2 Blocked

17.2

IB2 Active

17.3

IB2 Text

188

Yellow

IND2_08 = 1

Safety Interlock IC1 active

Green

I2_08TXT

Safety Interlock IC1 text from


database

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

Yellow

IND2_11 = 1

Interlock IB2 active

I2_11TXT

Interlock IB2 text from


database

Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

18.1

IB4 Block Indication

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

X Yellow

IND2_13 = 1 and IND2_02 Pending interlock, will be set


=1
when not running.
and BOOL_F = 1

18.2

IB4 Active

Yellow

(IND2_13 = 1 and
BOOL_F = 0)

Interlock IB4 active

or
(IND2_13 = 1 and
IND2_02 = 0
and BOOL_F = 1)
18.3

IB4 Text

Green

I2_13TXT

Interlock IB4 text from


database

19.1

IB1 Blocked

BX Red

IND1_15 = 1

Override Interlock and


Interlock IB1 active

BX Yellow

(BOOL_C = 1 or
IND2_15=1) and
IND1_15=0

Jog mode. Interlock blocked

19.2

IB1 Active

19.3

IB1 Text

Green

I2_10TXT

Interlock IB1 text from


database

20.1

IB3 Blocked

BX Red

IND1_15 = 1

Override Interlock and


Interlock IB3 active

BX Yellow

(BOOL_C = 1 or
IND2_15=1) and
IND1_15=0

Jog mode. Interlock blocked

X Yellow

IND2_12 = 1 and IND2_02 Pending interlock, will be set


=1
when not running.
and BOOL_F = 1
and IND2_15 = 0

3BSE 021 945R401

Yellow

IND2_10 = 1 and IND2_15 Interlock IB1 active


=0

189

DRICONS, Standard drive

No

Description

20.2

IB3 Active

Section 3, Faceplates and Graphic Elements

Presentation
Yellow

Condition

Remarks

(IND2_12 = 1 and
BOOL_F = 0 and IND2_15
= 0 and)

Interlock IB3 active

or
(IND2_12 = 1 and
IND2_02 = 0 and BOOL_F
=1
and IND2_15 = 0)
20.3

IB3 Text

Green

I2_12TXT

Interlock IB3 text from


database

21.1

IA Blocked

BX Yellow

BOOL_C = 1

Jog mode. Interlock blocked

21.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

21.3

IA Text

Green

I2_14TXT

Interlock IA text from


database

22

Blocking Interlock

Grey

22.1

Blocking Interlock Text

Green

23.1

Ready Run Indication

23.2

Ready Run Text

24.1

Not at reference
Indication

24.2

Not at reference Text

25.1

Repeat Fail Blocked


Indication

25.2

Repeat Fail Blocked


Text

Blocking Interlock
ACT_PRES_TEXT

Green

Ready Run

IND2_01 = 1
Grey

Green

NLS (Ready Run)


IND2_02 = 1 and IND2_07
=0

Not at Setpoint Grey


Yellow

NLS (Not at Setpoint)


REPEAT_BLK = 1

Repeat Fail Blk

NLS (Repeat Fail Blk)

Yellow

REPEAT_BLK = 1

Grey

26

Nominal Values

26.1

Nom. Speed Text

Nom. Speed Grey

26.2

Nom. Speed Value

Green

26.3

Nom. Speed Unit

rpm Grey

190

The Interlock that is active.

Nominal values
NLS (Speed) Nominal Speed
of drive
INTL_RES
Unit rpm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

27.1

Nom. Power Text

Power Grey

INTWA_00 = 1

NLS (Power) Nominal Power


of drive

27.2

Nom. Power Value

Green

REAL_E from MMCX help


object

27.3

Nom. Power Unit

kW Grey

28.1

Nom. Current Text

Current

28.2

Nom. Current Value

Green

28.3

Nom. Current Unit

A Grey

29.1

Nom. Torque Text

Torque Grey

INTWA_00 = 1

29.2

Nom. Torque Value

Green

REAL_E_MAX from
MMCX help object

29.3

Nom. Torque Unit

Nm Grey

Unit Nm

30

MotorStatus Text

Motor Status Grey

Run

31.1

MotorStatus

Light brown

Unit kW
Grey

INTWA_00 = 1
REAL_E_MIN from MMCX
help object

Unit Ampere
NLS (Torque) Nominal Torque
of motor

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

IND2_02 = 1

Drive running

Green

Green

NLS (Current) Nominal


Current of motor

Green

3BSE 021 945R401

191

DRICONS, Standard drive

No

Description

31.1
cont.

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

IND2_01 = 1

Drive ready to start

Green
Ready Run
Medium Green
(Centre part)

IND2_02 =1

Running

IND2_02 = 1 and

Forward

Medium Green, Light


green, Dark green, Black
(Centre part background)
31.2

Direction Indication
speed value positive

IND2_02 = 1 and

Reverse

speed value negative

IND2_01 = 1
Green

Run permitted

32.1

Torque Text

Torque Grey

INTWB_02 = 1

NLS (Torque)

32.2

Torque Value

Magenta

REAL_A

Torque value

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

INTWB_14 = 1 and
BOOL_E = 0

NLS (SP Torque)

32.3

Torque Unit

% Magenta

33.1

SP Torque Text

SP Torque

33.2

SP Torque Value

Cyan

REAL_PARAM and
BOOL_E = 0

Set point torque value

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Torque


setpoint is selected

% Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP Torque


setpoint is selected

33.3

192

SP Torque Unit

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

33.4

SP PID Text

SP PID

INTWB_13 = 1 and
BOOL_E = 0

NLS (SP PID)

33.4

SP PID Value

Cyan

REAL_PARAM and
BOOL_E = 0

Set point PID value

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP PID setpoint is


selected

% Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP PID setpoint is


selected
NLS (E SP Torque)

33.5

SP PID Unit

Grey

34.1

E Sp Torque Text

E SP Torque Grey

INTWB_14 = 1 and
BOOL_E = 1

34.2

E Sp Torque Value

Cyan

REAL_E and BOOL_E = 1 External Set point torque


value, value from PC-program

Grey

REAL_E and BOOL_E = 0 When the SP Torque setpoint


is selected

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP Torque setpoint


is selected

INTWB_13 = 1 and
BOOL_E = 1

NLS (E SP PID)

34.3

E Sp Torque Unit

34.4

E Sp PID Text

E SP PID

34.5

E Sp PID Value

Cyan

REAL_E and BOOL_E = 1 External Set point PID value,


value from PC-program

Grey

REAL_E and BOOL_E = 0 When the SP PID setpoint is


selected

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP PID setpoint is


selected

INTWB_00 = 1

NLS (Speed)

34.6

E Sp PID Unit

Grey

35.1

Speed Text

Speed

35.2

Speed Value

Green

REAL_C

Motor speed

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

3BSE 021 945R401

Grey

193

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

35.3

Speed Unit

Green

PRES_A (1-5)

Unit of speed from MMCX


database.

36.1

SP1 Speed Text

SP1 Speed

INTWB_11 = 1 and
BOOL_E = 0

NLS (SP Speed)

36.2

SP1 Speed Value

Cyan

REAL_PARAM and
BOOL_E = 0

Motor speed

Grey

from drive help object


Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Spd setpoint


is selected

from drive help object


36.3

SP1 Speed Unit

Unit

Cyan

PRES_A (1-5) and


BOOL_E = 0

Unit of SP Speed from MMCX


database.

Unit Grey

PRES_A (1-5) and


BOOL_E = 1

When the E SP Spd setpoint


is selected

INTWB_12 = 1 and
BOOL_E = 0

NLS (SP Speed)

36.4

SP2 Speed Text

SP2 Speed

36.5

SP2 Speed Value

Cyan

REAL_PARAM and
BOOL_E = 0

Motor speed

Grey

REAL_PARAM and
BOOL_E = 1

When the E SP Spd setpoint


is selected

Cyan

BOOL_E = 0

% Grey

BOOL_E = 1

When the E SP Spd setpoint


is selected

INTWB_11 = 1 and
BOOL_E = 1

NLS (E SP Spd)

36.6

SP2 Speed Unit

Grey

37.1

E SP1 Spd Text

E SP1 Spd

37.2

E SP1 Spd Value

Cyan

REAL_D and BOOL_E = 1 External Set point speed


value, value from PC-program
from drive help object

Grey

REAL_D and BOOL_E = 0 When the SP Speed setpoint


is selected
from drive help object

Unit Cyan

PRES_A (1-5) and


BOOL_E = 1

Unit of SP Speed from MMCX


database.

Unit Grey

PRES_A (1-5) and


BOOL_E = 0

When the SP Speed setpoint


is selected

37.3

194

E SP1 Spd Unit

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

37.4

E SP2 Spd Text

E SP2 Spd

INTWB_12 = 1 and
BOOL_E = 1

NLS (E SP Spd)

37.5

E SP2 Spd Value

Cyan

REAL_D and BOOL_E = 1 External Set point speed


value, value from PC-program

Grey

REAL_D and BOOL_E = 0 When the SP Speed setpoint


is selected

% Cyan

BOOL_E = 1

% Grey

BOOL_E = 0

When the SP Speed setpoint


is selected

37.6

E SP2 Spd Unit

Grey

38.1

Current Text

CURRENT Grey

INTWB_01 = 1

NLS (Current)

38.2

Current Value

Brown

REAL_RES

Current

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

% of nominal current

38.3

Current Unit

% Brown

39.1

Value Text

Value Grey

39.2

Value Value

39.3

Value Unit

40.1

Central Indication

3BSE 021 945R401

INTWB_03 = 1,Frequency

NLS (Frequency)

INTWB_04 =1, Power

NLS (Power)

INTWB_05 = 1, Outputv

NLS (Outputv)

INTWB_06 = 1, PRES_B

Free text from MMCX db


element, max 10 characters

INTWB_07 = 1, Ref

NLS (Ref)

INTWB_08 = 1, Con dev

NLS (Con dev)

INTWB_09 = 1, Act 1

NLS (Act 1)

INTWB_10 = 1, Act 2

NLS (Act 2)

Light Yellow

REAL_B

Red Flash

AU_IND1_12 =1

Communication error
Unacknowledged

? ? ? Red

IND1_12 =1

Communication error

Light Yellow

PRES_A [6..10]

Free text, max 5 characters.

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central Controlled
from operators place or by
group start or other PCprogram

Green

195

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

40.2

Central Text

Central

41.1

41.2

42.1

42.2

43.1

Condition

Remarks

Green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

NLS (Central)

Grey

Local Indication

Local Text

Green

Local
Controlled from local panel

Local
Green

BOOL_D = 1 and
IND2_09 = 1

Grey

Jog Indication

Test Text

BOOL_D = 1 and
IND2_09 = 1

Yellow

BOOL_C = 1 and
IND2_09 = 1

Jog

Yellow

BOOL_C = 1 and
IND2_09 = 1

NLS (Jog)

Grey

Jog running from motor


location

Jog

Drive local Indication

Yellow

IND2_09 = 0

Local
Controlled from local drive
panel

43.2

44.1

44.2

196

Drivel ocal Text

Drive local
Yellow

IND2_09 = 0

Grey

Out of Service
Indication
Out of Service Text

Light brown

IND2_00 = 0

NLS (Drive local)

Out of service
No control possible

Out of service
Light brown

IND2_00 = 0

Grey

NLS (Out of service)

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

45.1

Man Indication

Presentation
Green

DRICONS, Standard drive

Condition

Remarks

BOOL_A = 1 and

Manual mode. Startorder


affects the motor directly

BOOL_B = 0 and
IND2_09 = 1
45.2

Man Text

Man Grey
Green

BOOL_A = 1 and
BOOL_B = 0 and
IND2_09 = 1

Grey
46.1

Auto Indication

46.2

Auto Text

3BSE 021 945R401

Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

Auto mode. Process


conditions control start/stop of
motor

Auto
Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

Grey

197

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

3.7.2.2 Diagnostic Display

Data Base Element MMCX is to be named by the main Data Base Element + suffix
<.FL>
Example: The main MMCX has the name 313-552A. The MMCX for the fault
overlap display must have the name 313-552A.FL
Presentation:

18

19

20

21

22

23

24

25

10

26

11

27

12

28

13

29

14

30

15

31

16

32

17

33

Behavior:
No

Description

Presentation

1.1

Header

Diagnostic Grey

Diagnostic title.

1.2

Sub header

Fault and Alarm Grey

Fault and Alarm title.

2.1

Short Circuit
Fault

198

Red flashing

Condition

AU_IND1_00 = 1

Remarks

Unacknowledged Alarm Short


Circuit Fault

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

2.2

Short Circuit
Fault

Red

IND1_00 = 1

Short Circuit Fault

2.3

Short Circuit Text


Fault

Short Circuit

AU_IND1_00 = 1 or

NLS (Short Circuit) fault.

Red

IND1_00 = 1

Short Circuit Text


Normal

Short Circuit

IND1_00 = 0

NLS (Short Circuit) normal

AU_IND1_01 = 1

Unacknowledged Alarm

2.4

3.1

Grey

Over Current
Fault

Red flashing

3.2

Over Current
Fault

Red

3.3

Over Current Text


Fault
Over Current Text
Normal

3.4

4.1

Over Current Fault


IND1_01 = 1

Over Current Fault

Over Current

AU_IND1_01 = 1 or

NLS (Over Current) fault.

Red

IND1_01 = 1

Over Current

IND1_01 = 0

NLS (Over Current) normal

AU_IND1_02 = 1

Unacknowledged Alarm

Grey

DC Over Voltage
Fault

Red flashing

4.2

DC Over Voltage
Fault

Red

4.3

DC Over Voltage Text


Fault
DC Over Voltage Text
Normal

4.4

5.1

DC Over Voltage Fault


IND1_02 = 1

DC Over Voltage Fault

DC Over Voltage

AU_IND1_02 = 1 or

NLS (DC Over Voltage) fault.

Red

IND1_02 = 1

DC Over Voltage

IND1_02 = 0

NLS (DC Over Voltage)


normal

AU_IND1_03 = 1

Unacknowledged Alarm

Grey

Power Plate Over Temp


Fault

Red flashing

5.2

Power Plate Over Temp


Fault

Red

5.3

Power Plate Over Temp


Text
Fault

Power Plate
Temperature

Power Plate Over Temp


Text
Normal

Power Plate
Temperature

5.4

3BSE 021 945R401

Power Plate Over Temp


IND1_03 = 1

Power Plate Over Temp

AU_IND1_03 = 1 or

NLS (Power Plate Over


Temp) fault.

IND1_03 = 1

Red
IND1_03 = 0

NLS (Power Plate Over


Temp) normal

Grey

199

DRICONS, Standard drive

No

Description

6.1

Earth Fault
Fault

6.2

Earth Fault
Fault

6.3

Earth Fault Text


Fault
Earth Fault Text
Normal

6.4

7.1

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Red flashing

AU_IND1_04 = 1

Unacknowledged Alarm Earth


Fault Fault

Red

IND1_04 = 1

Earth Fault Fault

Earth Fault

AU_IND1_04 = 1 or

NLS (Earth Fault) fault.

Red

IND1_04 = 1

Earth Fault

IND1_04 = 0

NLS (Earth Fault) normal

AU_IND1_05 = 1

Unacknowledged Alarm

Grey

Motor Over Temperature


Fault

Red flashing

7.2

Motor Over Temperature


Fault

Red

7.3

Motor Over Temperature


Text
Fault

Motor Over
Temperature

Motor Over Temperature


Text
Normal

Motor Over
Temperature

7.4

8.1

Motor Over Temperature Fault

8.2

Motor Overload
Fault

Red

8.3

Motor Overload Text


Fault
Motor Overload Text
Normal

NLS (Motor Over


Temperature) fault.

IND1_05 = 1

IND1_05 = 0

NLS (Motor Over


Temperature) normal

AU_IND1_06 = 1

Unacknowledged Alarm
Motor Overload Fault

IND1_06 = 1

Motor Overload Fault

Motor Overload

AU_IND1_06 = 1 or

NLS (Motor Overload) fault.

Red

IND1_06 = 1

Motor Overload

IND1_06 = 0

NLS (Motor Overload) normal

AU_IND1_07 = 1

Unacknowledged Alarm

Grey

System Fault
Fault

Red flashing

9.2

System Fault
Fault

Red

9.3

System Fault Text


Fault

200

AU_IND1_05 = 1 or

Grey
Red flashing

9.1

Motor Over Temperature Fault

Red

Motor Overload
Fault

8.4

IND1_05 = 1

System Fault Fault


IND1_07 = 1

System Fault Fault

System Fault

AU_IND1_07 = 1 or

NLS (System Fault) fault.

Red

IND1_07 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

9.4

System Fault Text


Normal

System Fault

IND1_07 = 0

NLS (System Fault) normal

Grey

10.1

Underload
Fault

Red flashing

AU_IND1_08 = 1

Unacknowledged Alarm
Underload Fault

10.2

Underload
Fault

Red

IND1_08 = 1

Underload Fault

10.3

Underload Text
Fault

Underload

AU_IND1_08 = 1 or

NLS (Underload) fault.

Red

IND1_08 = 1

Underload Text
Normal

Underload

IND1_08 = 0

NLS (Underload) normal

AU_IND1_09 = 1

Unacknowledged Alarm

10.4

11.1

Grey

Over Speed
Fault

Red flashing

11.2

Over Speed
Fault

Red

11.3

Over Speed Text


Fault
Over Speed Text
Normal

11.4

12.1

Over Speed Fault


IND1_09 = 1

Over Speed Fault

Over Speed

AU_IND1_09 = 1 or

NLS (Over Speed) fault.

Red

IND1_09 = 1

Over Speed

IND1_09 = 0

NLS (Over Speed) normal

AU_IND1_10 = 1

Unacknowledged Alarm

Grey

Fault 10
Fault

Red flashing

12.2

Fault 10
Fault

Red

12.3

Fault 10 Text
Fault

Fault 10 Red

12.4

Fault 10 Text
Normal

Fault 10

13.1

Fault 11
Fault

Red flashing

13.2

Fault 11
Fault

Red

13.3

Fault 11 Text
Fault

3BSE 021 945R401

Fault10 Fault
IND1_10 = 1

Fault10 Fault

AU_IND1_10 = 1 or

NLS (Fault10) fault.

IND1_10 = 1
Grey

IND1_10 = 0

NLS (Fault10) normal

AU_IND1_11 = 1

Unacknowledged Alarm
Fault11 Fault

Fault 11

Red

IND1_11 = 1

Fault11 Fault

AU_IND1_11 = 1 or

NLS (Fault11) fault.

IND1_11 = 1

201

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

13.4

Fault 11 Text
Normal

Fault 11

IND1_11 = 0

NLS (Fault11) normal

14.1

Fault 12
Fault

Red flashing

AU_IND1_12 = 1

Unacknowledged Alarm
Fault12 Fault

14.2

Fault 12
Fault

Red

IND1_12 = 1

Fault12 Fault

14.3

Fault 12 Text
Fault

Fault 12

AU_IND1_12 = 1 or

NLS (Fault12) fault.

14.4

Fault 12 Text
Normal

Fault 12

15.1

Fault 13
Fault

15.2

Fault 13
Fault

15.3

Fault 13 Text
Fault

Fault 13

15.4

Fault 13 Text
Normal

Fault 13

16.1

Fault 14
Fault

16.2

Fault 14
Fault

16.3

Fault 14 Text
Fault

Fault 14

16.4

Fault 14 Text
Normal

Fault 14

17.1

Fault 15
Fault

17.2

Fault 15
Fault

17.3

Fault 15 Text
Fault

Fault 15

Fault 15 Text
Normal

Fault 15

17.4

202

Grey

Red

IND1_12 = 1
Grey

IND1_12= 0

NLS (Fault12) normal

Red flashing

AU_IND1_13 = 1

Unacknowledged Alarm
Fault13 Fault

Red

IND1_13 = 1

Fault13 Fault

AU_IND1_13 = 1 or

NLS (Fault13) fault.

Red

IND1_13 = 1
Grey

IND1_13 = 0

NLS (Fault13) normal

Red flashing

AU_IND1_14 = 1

Unacknowledged Alarm
Fault14 Fault

Red

IND1_14 = 1

Fault14 Fault

AU_IND1_14 = 1 or

NLS (Fault14) fault.

Red

IND1_14 = 1
Grey

IND1_14 = 0

NLS (Fault14) normal

Red flashing

AU_IND1_15 = 1

Unacknowledged Alarm
Fault15 Fault

Red

IND1_15 = 1

Fault15 Fault

AU_IND1_15 = 1 or

NLS (Fault15) fault.

Red

IND1_15 = 1
Grey

IND1_15 = 0

NLS (Fault15) normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

18.1

Start Inhibition
Alarm

Red flashing

18.2

Start Inhibition
Alarm

Red

18.3

Start Inhibition Text


Alarm
Start Inhibition Text
Normal

18.4

19.1

Presentation

AU_IND2_00 = 1 or

NLS (Start Inhibition) alarm.

Red

IND2_00 = 1

Start Inhibition

IND2_00 = 0

NLS (Start Inhibition) normal

AU_IND2_01 = 1

Unacknowledged Alarm

Grey

Red

19.3

Alarm 1 Text
Alarm
Alarm 1 Text
Normal

Alarm1 Alarm
IND2_01 = 1

Alarm1 Alarm

Alarm 1

AU_IND2_01 = 1 or

NLS (Alarm1) alarm.

Red

IND2_01 = 1

Alarm 1

IND2_01 = 0

NLS (Alarm1) normal

AU_IND2_02 = 1

Unacknowledged Alarm

Grey

Alarm 2
Alarm

Red flashing

20.2

Alarm 2
Alarm

Red

20.3

Alarm 2 Text
Alarm
Alarm 2 Text
Normal

Alarm2 Alarm
IND2_02 = 1

Alarm2 Alarm

Alarm 2

AU_IND2_02 = 1 or

NLS (Alarm2) alarm.

Red

IND2_02 = 1

Alarm 2

IND2_02 = 0

NLS (Alarm2) normal

AU_IND2_03 = 1

Unacknowledged Alarm

Grey

Motor Overload
Alarm

Red flashing

21.2

Motor Overload
Alarm

Red

21.3

Motor Overload Text


Alarm

3BSE 021 945R401

Unacknowledged Alarm

Start Inhibition

Alarm 1
Alarm

21.1

AU_IND2_00 = 1

Start Inhibition Alarm

19.2

20.4

Remarks

IND2_00 = 1

Red flashing

20.1

Condition

Start Inhibition Alarm

Alarm 1
Alarm

19.4

DRICONS, Standard drive

Motor Overload Alarm


IND2_03 = 1

Motor Overload Alarm

Motor Overload

AU_IND2_03 = 1 or

NLS (Motor Overload) alarm.

Red

IND2_03 = 1

203

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

21.4

Motor Overload Text


Normal

Motor Overload

IND2_03 = 0

NLS (Motor Overload) normal

Grey

22.1

Power Plate
Temperature
Alarm

Red flashing

AU_IND2_04 = 1

Unacknowledged Alarm
Power Plate Temperature
Alarm

22.2

Power Plate
Temperature
Alarm

Red

IND2_04 = 1

Power Plate Temperature


Alarm

22.3

Power Plate
Temperature Text
Alarm

Power Plate
Temperature

AU_IND2_04 = 1 or

NLS (Power Plate


Temperature) alarm.

Power Plate
Temperature Text
Normal

Power Plate
Temperature

22.4

IND2_04 = 1

Red
IND2_04 = 0

NLS (Power Plate


Temperature) normal

Grey

23.1

Encoder
Alarm

Red flashing

AU_IND2_05 = 1

Unacknowledged Alarm
Encoder Alarm

23.2

Encoder
Alarm

Red

IND2_05 = 1

Encoder Alarm

23.3

Encoder Text
Alarm

Encoder

AU_IND2_05 = 1 or

NLS (Encoder) alarm.

Red

IND2_05 = 1

Encoder Text
Normal

Encoder

IND2_05 = 0

NLS (Encoder) normal

AU_IND2_06 = 1

Unacknowledged Alarm

23.4

24.1

Grey

Alarm 6
Alarm

Red flashing

24.2

Alarm 6
Alarm

Red

24.3

Alarm 6 Text
Alarm
Alarm 6 Text
Normal

24.4

25.1

204

Alarm 7
Alarm

Alarm6 Alarm
IND2_06 = 1

Alarm6 Alarm

Alarm 6

AU_IND2_06 = 1 or

NLS (Alarm6) alarm.

Red

IND2_06 = 1

Alarm 6

IND2_06 = 0

NLS (Alarm6) normal

AU_IND2_07 = 1

Unacknowledged Alarm

Grey
Red flashing

Alarm7 Alarm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

25.2

Alarm 7
Alarm

25.3

Alarm 7 Text
Alarm
Alarm 7 Text
Normal

25.4

26.1

Presentation

Condition

Remarks

Red

IND2_07 = 1

Alarm7 Alarm

Alarm 7

AU_IND2_07 = 1 or

NLS (Alarm7) alarm.

Red

IND2_07 = 1

Alarm 7

IND2_07 = 0

NLS (Alarm7) normal

AU_IND2_08 = 1

Unacknowledged Alarm

Grey

Alarm 8
Alarm

Red flashing

26.2

Alarm 8
Alarm

Red

26.3

Alarm 8 Text
Alarm
Alarm 8 Text
Normal

26.4

27.1

Alarm8 Alarm
IND2_08 = 1

Alarm8 Alarm

Alarm 8

AU_IND2_08 = 1 or

NLS (Alarm8) alarm.

Red

IND2_08 = 1

Alarm 8

IND2_08 = 0

NLS (Alarm8) normal

AU_IND2_09 = 1

Unacknowledged Alarm

Grey

Alarm 9
Alarm

Red flashing

27.2

Alarm 9
Alarm

Red

27.3

Alarm 9 Text
Alarm
Alarm 9 Text
Normal

27.4

28.1

Alarm9 Alarm
IND2_09 = 1

Alarm9 Alarm

Alarm 9

AU_IND2_09 = 1 or

NLS (Alarm9) alarm.

Red

IND2_09 = 1

Alarm 9

IND2_09 = 0

NLS (Alarm9) normal

AU_IND2_10 = 1

Unacknowledged Alarm

Grey

Alarm 10
Alarm

Red flashing

28.2

Alarm 10
Alarm

Red

28.3

Alarm 10 Text
Alarm
Alarm 10 Text
Normal

28.4

3BSE 021 945R401

DRICONS, Standard drive

Alarm10 Alarm
IND2_10 = 1

Alarm10 Alarm

Alarm 10

AU_IND2_10 = 1 or

NLS (Alarm10) alarm.

Red

IND2_10 = 1

Alarm 10

IND2_10 = 0

NLS (Alarm10) normal

Grey

205

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

29.1

Alarm 11
Alarm

Red flashing

29.2

Alarm 11
Alarm

Red

29.3

Alarm 11 Text
Alarm
Alarm 11 Text
Normal

29.4

Presentation

Condition

Remarks

AU_IND2_11 = 1

Unacknowledged Alarm
Alarm11 Alarm

IND2_11 = 1

Alarm11 Alarm

Alarm 11

AU_IND2_11 = 1 or

NLS (Alarm11) alarm.

Red

IND2_11 = 1

Alarm 11

IND2_11 = 0

NLS (Alarm11) normal

Grey

30.1

Communications
Channel 0
Alarm

Red flashing

AU_IND2_12 = 1

Unacknowledged Alarm
Communications Channel 0
Alarm

30.2

Communications
Channel 0
Alarm

Red

IND2_12 = 1

Communications Channel 0
Alarm

30.3

Communications
Channel 0 Text
Alarm

Communications
Channel 0

AU_IND2_12 = 1 or

NLS (Communications
Channel 0) alarm.

Communications
Channel 0 Text
Normal

Communications
Channel 0

30.4

IND2_12 = 1

Red
IND2_12 = 0

NLS (Communications
Channel 0) normal

Grey

31.1

Thermistor
Alarm

Red flashing

AU_IND2_13 = 1

Unacknowledged Alarm
Thermistor Alarm

31.2

Thermistor
Alarm

Red

IND2_13 = 1

Thermistor Alarm

31.3

Thermistor Text
Alarm

Thermistor

AU_IND2_13 = 1 or

NLS (Thermistor) alarm.

Red

IND2_13 = 1

Thermistor Text
Normal

Thermistor

IND2_13 = 0

NLS (Thermistor) normal

31.4

Grey

32.1

Earth Fault
Alarm

Red flashing

AU_IND2_14 = 1

Unacknowledged Alarm Earth


Fault Alarm

32.2

Earth Fault
Alarm

Red

IND2_14 = 1

Earth Fault Alarm

206

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

DRICONS, Standard drive

No

Description

Presentation

Condition

Remarks

32.3

Earth Fault Text


Alarm

Earth Fault

AU_IND2_14 = 1 or

NLS (Earth Fault) alarm.

Red

IND2_14 = 1

Earth Fault Text


Normal

Earth Fault

IND2_14 = 0

NLS (Earth Fault) normal

AU_IND2_15 = 1

Unacknowledged Alarm

32.4

33.1

Grey

Alarm 15
Alarm

Red flashing

33.2

Alarm 15
Alarm

Red

33.3

Alarm 15 Text
Alarm
Alarm 15 Text
Normal

33.4

Alarm15 Alarm
IND2_15 = 1

Alarm15 Alarm

Alarm 15

AU_IND2_15 = 1 or

NLS (Alarm15) alarm.

Red

IND2_15 = 1

Alarm 15

IND2_15 = 0

NLS (Alarm15) normal

Grey

3.7.3 Graphic Element


3.7.3.1 Motor01

Presentation:

3BSE 021 945R401

207

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Presentation

Condition

Remarks

SelectFrame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Black

PointOfControl - Visible

ModeVisible = true

O Yellow

IND2_00= 0

Out of service

D Yellow

IND2_09= 0

Drive Local Control

J Yellow

BOOL_C = 1 and
IND2_09 = 1

Jog Control

L Green

BOOL_D = 1 and
IND2_09 = 1

Local Control

A Green

BOOL_B = 1 and
BOOL_A = 0 and
IND2_09 = 1

NLS (Auto)

BOOL_A = 1 and

NLS (Man)

ManModeVisible = true

M Green

BOOL_B = 0 and
IND2_09 = 1
ManModeVisible = false

208

C Green

IND2_09 = 1 and
BOOL_C = 0 and
BOOL_D = 0

Central Control

Point OfControlVisible =
false

Control point not visible

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Direction Indication

Presentation

DRICONS, Standard drive

Condition

Remarks

DirectionVisible = true
Green

IND2_02 = 1 and

Forward

speed value positive

Green

IND2_02 = 1 and

Reverse

speed value negative

DriveStatus

Green

IND2_01 = 1

Run permitted

DirectionVisible = false

Direction is invisible

IND2_00 = 0

Out of service

IND2_01 = 0 or

Not Ready for Start


Not Ready Run

IND2_08 = 1 or

C - interlock

IND2_10 = 1 or

B - Interlock 1

IND2_11 = 1 or

B - Interlock 2

IND2_12 = 1 or

B- Interlock 3

IND2_13 = 1 or

B - Interlock 4

IND2_14 = 1

A - Interlock

Light brown

shape

Green

Green

3BSE 021 945R401

209

DRICONS, Standard drive

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

4
cont.

DriveStatus

Green

Condition

Remarks

IND2_01 = 1

Drive ready to start


Ready Run

Green

Red flashing

IND2_02 = 1

Drive running

AU_IND1_09 = 1 or

Unacknowledged alarm

AU_IND1_10 = 1 or
AU_IND1_11 = 1 or
AU_IND1_12 = 1
Red

Green

IND1_09 = 1 or

Fault

IND1_10 = 1 or

Warning

IND1_11 = 1 or

Limit

IND1_12 = 1

Communication error

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default)

Remarks

PointOfControlVisible

2. Control Point

true, false

Show point of control or not.

ManModeVisible

2. Control Point

true, false

True = show M when manual


mode. False = show C when
manual mode.

DirectionVisible

3. Direction

true, false

Show Direction or not.

210

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

3.8 GENBIN, Binary Object


3.8.1 Faceplate
Presentation:

3BSE 021 945R401

211

GENBIN, Binary Object

Section 3, Faceplates and Graphic Elements

2
1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

212

Control point

Default Presentation

Condition

M Dark green

MAN = 1

A Dark green

AUTO = 1

B Dark green

BLK = 1

S Dark green

STBY = 1

C Dark green

CEN = 1

L Dark green

LOC = 1

R Dark green

REM = 1

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

No

Description

Default Presentation

Condition

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Signal error

Q Red

ALSIGNE = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Remarks

On

set to open order

Set MORD_08 = 1

Off

set to open order

Set MORD_09 = 1

Man

Set to Man Mode

Set MORD_04 = 1

Auto

Set to Auto Mode

Set MORD_05 = 1

Stb

Set to Standby Mode

Set MORD_07 = 1

Blk

Set to Blocked Mode

Set MORD_06 = 1

Cen

Set to Central control

Set MORD_01 = 1

Loc

Set to Local control

Set MORD_02 = 1

Rem

Set to Remote control

Set MORD_03 = 1

3BSE 021 945R401

213

GENBIN, Binary Object

Section 3, Faceplates and Graphic Elements

3.8.1.1 Control and ReducedControl

Presentation:
2

3
4

Behavior:
No

Description

1.1

Range Max

Default Presentation Condition


MAX
Black

1.2

Range Min

214

Range Max of the MV


value

MIN

Black

Remarks

Range Min of the MV value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2.1

Measured Value
Bargraph

2.2

2.3

2.4

Default Presentation Condition


MV
Green

High Limit 2

Remarks
Object measured value

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

ALLIMH2 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH2 = 1 and AU_ST_04


=1

Unfilled Red flashing

AU_ST_04 = 1

Filled Red

ALLIMH2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

ALLIMH1 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH1 = 1 and AU_ST_05


=1

Unfilled Red flashing

AU_ST_05 = 1

Filled Red

ALLIMH1 = 1

Unfilled Grey

Low Limit 1

3BSE 021 945R401

GENBIN, Binary Object

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

ALLIML1 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

215

GENBIN, Binary Object

No

Description

2.4
cont.

2.5

Section 3, Faceplates and Graphic Elements

Default Presentation Condition


Filled Red flashing

ALLIML1 = 1 and AU_ST_06


=1

Unfilled Red flashing

AU_ST_06 = 1

Filled Red

ALLIML1 = 1

Unfilled Grey

Low Limit 2

Remarks

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

ALLIML2 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML2 = 1 and AU_ST_07


=1

Filled Red

ALLIML2 = 1

Unfilled Grey

Unfilled Red flashing

AU_ST_07 = 1

Measured Value

3.1

MV

MV Black

3.2

MV Value

X X X Red

MV is Bad

No contact with controller

? ? ? Red

ALSIGNE = 1

Signal error

Black

MV

Measured value

UNIT

Measured unit

3.3

The MV object value

MV Unit
Black

216

Status Indication

Text in front of the value

Status - Square indication

Unfilled Green Flashing

INDONOP = 1 and INDCH = 1 Off

Unfilled Green

INDONOP = 0 and INDCH = 0 Off

Filled Green Flashing

INDONOP = 0 and INDCH = 1 On

Filled Green

INDONOP = 1 and INDCH = 0 On

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

3.8.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Block Alarm

Block Alarm Black

Block Printout

Block Event

Yellow

Blocked

Block pressed

AL_BLK = 1

Deblock pressed

AL_BLK = 0

Remarks

Block Printout Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

Block Event Black

Yellow

3BSE 021 945R401

Condition

Blocked

217

GENBIN, Binary Object

No

Description

3
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Block pressed

EVENT_BLK = 1

Deblock pressed

EVENT_BLK = 0

Remarks

3.8.1.3 Limits

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

H2

H1

L1 Black
Black

218

Remarks

H1 Black
Black

Condition

L1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

No

Description

Default Presentation

L2

L2 Black
Black

Condition

Remarks

L2

3.8.2 Object Display


Presentation:
2

43

8
9
10
11

12

13
14
15

16
17
24

18
19
20

25
26
27

21

28-30

3BSE 021 945R401

22

23

219

GENBIN, Binary Object

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object name and


description

Red flashing

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unacknowledged signal
error
UnAck alarm feedback
error
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

Red

ALSIGNE = 1 or
ALFBE = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm feedback error
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

Range Max
Green
Range Min

PROC_SEC

Process section
Text in front of the value

CLASS

Object class

MAX

Range Max of the MV


value

MIN

Green

220

Text in front of the value

Range Min of the MV value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Measure Value Trim


Curve

Default Presentation

Green

Status Indication

7.2

7.3

Measured Value
Bargraph

Remarks

MV

Object value - Trim curve

Green

Status indication - On / Off

MV

High Limit 2

Object value - Bargraph

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

ALLIMH2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH2 = 1 and
AU_ST_04 = 1

Unfilled Red flashing

AU_ST_04 = 1

Filled Red

ALLIMH2 = 1

Unfilled Grey

High Limit 1

3BSE 021 945R401

Condition

INDONOP
Green

7.1

GENBIN, Binary Object

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

ALLIMH1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH1 = 1 and
AU_ST_05 = 1

Unfilled Red flashing

AU_ST_05 = 1

Filled Red

ALLIMH1 = 1

Unfilled Grey

221

GENBIN, Binary Object

No

Description

7.4

Low Limit 1

7.5

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

ALLIML1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML1 = 1 and
AU_ST_06 = 1

Unfilled Red flashing

AU_ST_06 = 1

Filled Red

ALLIML1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

ALLIML2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML2 = 1 and
AU_ST_07 = 1

Unfilled Red flashing

AU_ST_07 = 1

Filled Red

ALLIML2 = 1

Unfilled Grey

ALARM LIMITS for MV

8.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

8.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALLIMH2 = 1 and
AU_ST_04 = 1

Alarm High limit 2

Red

ALLIMH2 = 1

8.3

8.4

222

Alarm Indication

H2 Text

Alarm limits for MV

H2 Grey

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

8.5

H2 Value

Default Presentation

GENBIN, Binary Object

Condition

Remarks

MVH2

High limit 2 value

Green

9.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

9.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALLIMH1 = 1 and
AU_ST_05 = 1

Warning High limit 1

Red

ALLIMH1 = 1

9.3

Warning Indication

9.4

H1 Text

9.5

H1 Value

H1

Grey

Text in front of the value


MVH1

Green

High limit 1 value

10.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

10.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALLIML1 = 1 and
AU_ST_06 = 1

Warning Low limit 1

Red

ALLIML1 = 1

10.3

Warning Indication

10.4

L1 Text

10.5

L1 Value

L1 Grey

Text in front of the value


MVL1

Green

Low limit1 value

11.1

Printout Blocked

P Yellow

PR_BLK

Printout blocked

11.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALLIML2 = 1 and
AU_ST_07 = 1

Alarm Low limit 2

Red

ALLIML2 = 1

11.3

11.4

Alarm Indication

L2 Text

3BSE 021 945R401

L2 Grey

Text in front of the value

223

GENBIN, Binary Object

No

Description

11.5

L2 Value

Section 3, Faceplates and Graphic Elements

Default Presentation

Green
12

INTERLOCKS

12.1

Mode Interlock Indication

12.2

Mode Interlock Text

13.1

Process Interlock
Indication

13.2

Process Interlock Text

14.1

Switchgear Interlock
Indication

14.2

Switchgear Interlock Text

15.1

Emergency Trip Interlock


Indication

15.2

Emergency Trip Interlock


Text

16

STATUS

16.1

Alarm Period Block


Indication

16.2

Alarm Period Block Text

224

Condition

Remarks

MVL2

Low limit 2 value

Interlocks

Yellow

INTMODE = 1

Mode

Mode interlock text

Yellow

INTMODE = 1

Grey

Yellow

INTPROC = 1

Process
INTPROC = 1

Grey

INTSWGR = 1

Switchgear

Switchgear interlock
indication
Switchgear interlock text

Yellow

INTSWGR = 1

Grey

Yellow

Process interlock
indication
Process interlock text

Yellow

Yellow

Mode interlock indication

INTEMTP = 1

Emergency Trip

Emergency Trip interlock


indication
Emergency Trip interlock
text

Yellow

INTEMTP = 1

Grey

Status
Yellow

AUTO_BLK = 1

Alarm Period Blk

Alarm block by PCprogram


Alarm period block text

Yellow

AUTO_BLK = 1

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

17.1

Repeat Fail Block


Indication

17.2

Repeat Fail Block Text

18.1

Event Indication

18.2

Event Text

19.1

19.2

20.1

20.2

Default Presentation
Yellow

21

PARAMETER

21.1

Implemented Indication

21.2

Implemented Text

22

Measured Value

22.1

MV

3BSE 021 945R401

Remarks

RP_BLK = 1

Repeat fail block indication


Repeat fail block text

Yellow

RP_BLK = 1

Grey

Yellow

Event

EV_BLK = 1

Yellow

Event indication
Event text

Yellow

EV_BLK = 1

Grey

Red Flashing

AU_ST_00 = 1

Red

ALSIGNE = 1

Signal Error

Signal error indication

Signal error text

Red

AU_ST_00 = 1 or
ALSIGNE = 1

Grey

Feed Back Error


Indication
Feed Back Error Text

Condition

Repeat Fail Blk

Signal Error Indication

Signal Error Text

GENBIN, Binary Object

Red Flashing

AU_ST_01 = 1

Red

ALFBE = 1

Feed Back Error

Feed back error indication

Feed back error text

Red

AU_ST_01 = 1 or ALFBE =
1

Grey

Parameter
Green

Implemented Grey

IMPLEMENTED = 1

Implemented indication
Implemented text
The MV object value

MV Grey

Text in front of the value

225

GENBIN, Binary Object

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

22.2

MV Value

X X X Red

MV is Bad

No contact with controller

? ? ? Red

ALSIGNE = 1

Signal error

MV

Measured value

Green
22.3

MV Unit

UNIT
Green

23

Man Indication

24.2

Man Text

25.1

Auto Indication

25.2

Auto Text

26.1

Blocked Indication

26.2

Blocked Text

27.1

Stand By Indication

27.2

Stand By Text

226

Central Control
Indication

Measured unit

Status Indication

24.1

28.1

Status - Square indication


Unfilled Green Flashing

INDONOP = 1 and INDCH


=1

Off

Unfilled Green

INDONOP = 0 and INDCH


=0

Off

Filled Green Flashing

INDONOP = 0 and INDCH


=1

On

Filled Green

INDONOP = 1 and INDCH


=0

On

MAN = 1

Manual mode

Man Green

MAN = 1

Man text

Grey

Green

Green

AUTO = 1

Auto mode

Auto Green

AUTO = 1

Auto text

Grey

Green

BLK = 1

Blocked mode

Blocked Green

BLK = 1

Blocked text

Grey

Green

STBY = 1

Stand by mode

Stand By Green

STBY = 1

Stand by text

Grey

Green

CEN = 1

Central control indication

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

No

Description

Default Presentation

Condition

Remarks

28.2

Central Control Text

Central Green

CEN = 1

Central control text

Grey

29.1

Local Control Indication

29.2

Local Control Text

30.1

Remote Control
Indication

30.2

Remote Control Text

3BSE 021 945R401

Green

LOC = 1

Local control indication

Local Green

LOC = 1

Local control text

Grey

Green

REM = 1

Remote control indication

Remote Green

REM = 1

Remote control text

Grey

227

GENBIN, Binary Object

Section 3, Faceplates and Graphic Elements

3.8.3 Graphic Element


3.8.3.1 Numeric

Presentation:

1
2

3
5

228

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

MV

Object value

ALSIGNE = 1 and
AU_ST_00 =1

Unacknowledged signal
error

AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck alarm feedback


error
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

ALSIGNE = 1

Signal error

Red

ALFBE = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Alarm feedback error


Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green

Invisible
2

Measured Value

???

Red flashing

Red flashing

???

Red

Mode

Object mode

M Green

MAN = 1

Manual mode

A Green

AUTO = 1

Auto mode

B Green

BLK = 1

Blocked mode

S Green

STBY = 1

Standby mode

Operator Position

Object mode

C Green

CEN = 1

Central position

L Green

LOC = 1

Local position

R Green

REM = 1

Remote position

3BSE 021 945R401

Operator position is
invisible

229

GENBIN, Binary Object

No

Description

Interlocks

Unit

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks
Object interlock

X Yellow

INTMODE = 1 or
INTPROC = 1 or
INTSWGR = 1 or
INTEMTP = 1

Green

UNIT

Interlock mode
Interlock process
Interlock switchgear
Interlock emergency trip

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

3, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

230

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENBIN, Binary Object

3.8.3.2 IndicatorBox01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Black

INDONOP = 1 and INDCH


=1
INDONOP = 0 and INDCH
=0

Off

Red flashing

AU_ST_00 = 1 or

Unacknowledged signal
error
UnAck alarm feedback
error
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

Invisible
2

Symbol Center Color

AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

3BSE 021 945R401

231

GENBIN, Binary Object

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red

ALSIGNE = 1 or
ALFBE = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm feedback error
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green flashing

INDCH = 1 and INDONOP


=0

Green

Interlocks

On
Object interlock

X Yellow

INTMODE = 1 or
INTPROC = 1 or
INTSWGR = 1 or
INTEMTP = 1

Interlock mode
Interlock process
Interlock switchgear
Interlock emergency trip

Label

User defined Label

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

3, (0...5)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Label

3. Interlock

Any character

232

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

3.9 GENCON, PI Controller


3.9.1 Faceplate
Presentation:

3BSE 021 945R401

233

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

1
3

234

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

Default Presentation

Condition

M Dark Green

MAN = 1

A Dark Green

AUTO = 1

MFd Dark Green

MANF = 1

E1 Dark Green

E1 = 1

E2 Dark Green

E2 = 1

3.2

Print Blk

P Yellow

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Increase output
with 0,5 unit

MAN = 1

Increase setpoint
with 0,5 unit

AUTO = 1

Decrease output
with 0,5 unit

MAN = 1

Decrease setpoint
with 0,5 unit

AUTO = 1

Incr

Decr

Remarks

Man

Set to Man Mode

Set MORD_03 = 1

Auto

Set to Auto Mode

Set MORD_04 = 1

MFd

Set to Man Force Mode

Set MORD_02 = 1

E1

Set to E1 Mode

Set MORD_05 = 1

E2

Set to E2 Mode

Set MORD_06 = 1

3BSE 021 945R401

235

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

3.9.1.1 Control and ReducedControl

Presentation:
2

6
7
8

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Range Max

Black

MAX

Range Max of the MV


value

1.2

Range Min

Black

MIN

Range Min of the MV value

2.1

Measured Value
Bargraph

MV

Object measured value

236

Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2.2

High Limit 2

2.3

2.4

Default Presentation

Condition

Remarks

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

ALLIMH2 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH2 = 1 and AU_ST_04 = 1

Unfilled Red flashing

AU_ST_04 = 1

Filled Red

ALLIMH2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

ALLIMH1 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH1 = 1 and AU_ST_05 = 1

Unfilled Red flashing

AU_ST_05 = 1

Filled Red

ALLIMH1 = 1

Unfilled Grey

Low Limit 1

3BSE 021 945R401

GENCON, PI Controller

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

ALLIML1 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML1 = 1 and AU_ST_06 = 1

Unfilled Red flashing

AU_ST_06 = 1

Filled Red

ALLIML1 = 1

Unfilled Grey

237

GENCON, PI Controller

No

Description

2.5

Low Limit 2

3.1

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

ALLIML2 = 1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML2 = 1 and AU_ST_07 = 1

Unfilled Red flashing

AU_ST_07 = 1

Filled Red

ALLIML2 = 1

Unfilled Grey

SP Value

SP
Cyan

3.2

3.3

4.1

4.2

238

High SP Limit

Object setpoint value

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

LIMSPH = 1

Limitation line and mesh

Grey

Low SP Limit

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

LIMSPL = 1

Limitation line and mesh

Grey

OUT Value

OUT

Object output value

INDON = 1 or ONOFCTRL = 1

Invisible

Magenta

High OUT Limit

OUTPH

Upper warning limit output

INDON = 1 or ONOFCTRL = 1

Invisible

OUTPH > 100%

Invisible

Yellow

LIMOPH = 1

Limitation line and mesh

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

4.3

Low OUT Limit

Measured Value

5.1

MV Value

Default Presentation

Condition

Remarks

OUTPL

Lower warning limit output

INDON = 1 or
ONOFCTRL = 1

Invisible

OUTPL < 0%

Invisible

Yellow

LIMOPL = 1

Limitation line and mesh

Grey

The MV object value

???

Red

Black
5.2

MV Unit
Black

Setpoint Value

6.1

SP Value

7.1

OUT Value

7.2

OUT Unit

7.3

Status Indication

MV

Measured value

UNIT

Measured unit

Setpoint unit

The OUT object value


OUT

Black

INDON = 0 and ONOFCTRL = 0

% Black

INDON = 0 and ONOFCTRL = 0

Output value

Output unit
Status - Square indication

Filled Green

INDON = 1

On

Unfilled Green

INDON = 0 and ONOFCTRL = 1

Off

Warning Indication
Deviation

3BSE 021 945R401

Setpoint value

UNIT

Black
Output Value

Signal error

SP

SP Unit

ALAI = 1

The SP object value

Black
6.2

GENCON, PI Controller

Warning indication
Deviation

DEV Red

ALDEV = 1

ALDEV = 0

Invisible

239

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

3.9.1.2 Limits

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

L2

MVH1

MVL1

L2 Black
Black

240

MVH2

L1 Black
Black

Remarks

H1 Black
Black

Condition

MVL2

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

Presentation:

1
2

3
4

Behavior:
No

Description

Default Presentation

Condition

SP H

SPH Black

SETPH

SP L

SPL Black

SETPL

OUT H

OUT H Black

OUTPH

OUT L

OUT L Black

OUTPL

3BSE 021 945R401

Remarks

241

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

3.9.1.3 Block

Presentation:

Behavior::
No

Description

Default Presentation

Block Alarm

Block Alarm Black

242

Condition

Yellow

Blocked

Block pressed

AL_BLK = 1

Deblock pressed

AL_BLK = 0

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

3.9.2 Object Display


Presentation:
2

10
11
12
13

1
5

14

15
16
17
18
22
23
24
25
26

19-21

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

3BSE 021 945R401

NAME and DESCR

Object name and


description

243

GENCON, PI Controller

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red flashing

AU_ST_00 = 1 or
AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unacknowledged signal
error
UnAck alarm Deviation
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

Red

ALAI = 1 or
ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

5.1

Range MV Max
Green

5.2

Range OUT Max

5.3

Range MV Min

Range OUT Min

Measure Value Trim


Curve
Setpoint Value Trim
Curve

CLASS

Object class

MAX

Range Max of the MV


value

Range Max of the OUT


value

Range Min of the OUT


value
MV

Object setpoint value

OUT

Magenta

Object measure value

SP

Cyan

Range Min of the MV value

0 Magenta

Green

Process section
Text in front of the value

MIN

Output Value Trim Curve

244

PROC_SEC

100 Magenta

Green
5.4

Text in front of the value

Object output value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.1

Measured Value
Bargraph

7.2

7.3

7.4

Default Presentation

Green

High Limit 2

Condition

Remarks

MV

Object value - Bargraph

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

ALLIMH2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH2 = 1 and
AU_ST_04 = 1

Unfilled Red flashing

AU_ST_04 = 1

Filled Red

ALLIMH2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

ALLIMH1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH1 = 1 and
AU_ST_05 = 1

Unfilled Red flashing

AU_ST_05 = 1

Filled Red

ALLIMH1 = 1

Unfilled Grey

Low Limit 1

3BSE 021 945R401

GENCON, PI Controller

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

ALLIML1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML1 = 1 and
AU_ST_06 = 1

Unfilled Red flashing

AU_ST_06 = 1

245

GENCON, PI Controller

No

Description

7.4
cont.
7.5

8.1

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Filled Red

ALLIML1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

ALLIML2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML2 = 1 and
AU_ST_07 = 1

Unfilled Red flashing

AU_ST_07 = 1

Filled Red

ALLIML2 = 1

Unfilled Grey

SP Value

SP
Cyan

8.2

8.3

9.1

9.2

246

High SP Limit

Object setpoint value

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

LIMSPH = 1

Limitation line and mesh

Grey

Low SP Limit

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

LIMSPL = 1

Limitation line and mesh

Grey

OUT Value

High OUT Limit

Remarks

OUT

Object output value

INDON = 1 or
ONOFCTRL = 1

Invisible

Magenta

OUTPH

Upper warning limit output

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

9.2
cont.

9.3

GENCON, PI Controller

Default Presentation

Condition

Remarks

INDON = 1 or
ONOFCTRL = 1

Invisible

OUTPH > 100%

Invisible

Yellow

LIMOPH = 1

Limitation line and mesh

Grey

Low OUT Limit

OUTPL

Lower warning limit output

INDON = 1 or
ONOFCTRL = 1

Invisible

OUTPL < 0%

Invisible

Yellow

LIMOPL = 1

Limitation line and mesh

Grey

10

ALARM LIMITS for MV

10.1

MV Text

MV Grey

10.2

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

10.3

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Be Yellow

EV_BLK = 1

Event blocked

Red flashing

ALLIMH2 = 1 and
AU_ST_04 = 1

Alarm High limit 2

Red

ALLIMH2 = 1

10.4

Alarm Indication

10.5

H2 Text

10.6

H2 Value

Alarm limits for MV


Text in front of the line

H2 Grey

Text in front of the value


MVH2

Green

High limit 2 value

11.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

11.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Be Yellow

EV_BLK = 1

Event blocked

3BSE 021 945R401

247

GENCON, PI Controller

No

Description

11.3

Warning Indication

11.4

H1 Text

11.5

H1 Value

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red flashing

ALLIMH1 = 1 and
AU_ST_05 = 1

Warning High limit 1

Red

ALLIMH1 = 1

H1 Grey

Text in front of the value


MVH1

Green

High limit 1 value

12.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Be Yellow

EV_BLK = 1

Event blocked

Red flashing

ALLIML1 = 1 and
AU_ST_06 = 1

Warning Low limit 1

Red

ALLIML1 = 1

12.3

Warning Indication

12.4

L1 Text

12.5

L1 Value

L1 Grey

Text in front of the value


MVL1

Green

Low limit1 value

13.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

13.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Be Yellow

EV_BLK = 1

Event blocked

Red flashing

ALLIML2 = 1 and
AU_ST_07 = 1

Alarm Low limit 2

Red

ALLIML2 = 1

13.3

Alarm Indication

13.4

L2 Text

13.5

L2 Value

L2 Grey
MVL2
Green

14.1

248

DEV Text

Text in front of the value

DEV Grey

Low limit 2 value

Text in front of the line

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

No

Description

Default Presentation

Condition

Remarks

14.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Be Yellow

EV_BLK = 1

Event blocked

14.3

Alarm Indication

14.4

Out of range Text

15

LIMITATIONS for SP

15.1

SP Text

15.2

Warning Indication

15.3

H Text

15.4

H Value

Red flashing

ALDEV = 1 and AU_ST_03


=1

Red

ALDEV = 1

Out of range Grey


Limitations for SP

SP Grey
Yellow

Warning Indication

16.2

L Text

16.3

L Value

Yellow

LIMITATIONS for OUT

17.1

OUT Text

17.2

Warning Indication

17.3

H Text

17.4

H Value

Warning Indication

18.2

L Text

18.3

L Value

LIMSPL = 1

Warning Setpoint Low


Text in front of the value

SETPL

Setpoint Low value

Limitations for OUT

OUT Grey
Yellow

Text in front of the line


LIMOPH = 1

H Grey

Yellow

Warning Output High


Text in front of the value

OUTPH

Output High value

LIMOPL = 1

L Grey

Warning Output Low


Text in front of the value

OUTPL
Magenta

3BSE 021 945R401

Setpoint High value

L Grey

Magenta
18.1

Warning Setpoint High


Text in front of the value

SETPH

Cyan
17

LIMSPH = 1

H Grey

Cyan
16.1

Text in front of the line

Output Low value

249

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

No

Description

19

Measured Value

19.1

MV

MV Grey

19.2

MV Value

? ? ? Red

ALAI = 1

Signal error

Green

MV

Measured value

UNIT

Measured unit

19.3

Default Presentation

Green
Setpoint Value

20.1

SP

20.2

SP Value

21.1

OUT

21.2

OUT Value

21.3

OUT Unit

21.4

Status Indication

22.1

Balance indication

22.2

Balance Text

23.1

250

Man indication

Text in front of the value


SP

Setpoint value

UNIT

Cyan
Output Value

SP Grey

SP Unit

21

Text in front of the value

The SP object value

Cyan
20.3

Remarks
The MV object value

MV Unit

20

Condition

Setpoint unit

The OUT object value

OUT Grey

Text in front of the value


OUT

Magenta

INDON = 0 and
ONOFCTRL = 0

% Magenta

INDON = 0 and
ONOFCTRL = 0

Output value

Output unit
Status - Square indication

Filled Green

INDON = 1

On

Unfilled Green

INDON = 0 and
ONOFCTRL = 1

Off

BAL = 1

Balance mode

Green filled

Bal

Text behind the indication

Green

BAL = 1

Grey

Green filled

MANF = 1 or MAN = 1

Balance mode

Manual mode

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

23.2

Man Text

Man

23.3

Forced Text

23.4

Man Out Text

23.5

Man Out Value

24.1

Auto indication

24.2

Auto Text

24.3

Auto Setpoint Text

24.4

Auto Setpoint Value

25.1

E1 indication

25.2

E1 Text

26.1

E2 indication

26.2

E2 Text

3BSE 021 945R401

GENCON, PI Controller

Condition

Remarks
Text behind the indication

Green

MANF = 1 or MAN = 1

Grey

Forced Green

MANF = 1

invisible

MANF = 0

OUT Grey

Manual mode

Manual Forced mode

Text in front of the value


MANOUT

Man Out value

Magenta

MANF = 1 or MAN = 1

Manual mode

Grey

Green filled

AUTO = 1

Auto

Auto mode
Text behind the indication

Green

AUTO = 1

Grey

SP Grey

Auto mode

Text in front of the value


SETP

Auto Setpoint value

Cyan

AUTO = 1

Auto mode

Grey

Green filled

E1 = 1

E1

E1 mode
Text behind the indication

Green

E1 = 1

Grey

Green filled

E2 = 1

E2

E1 mode

E2 mode
Text behind the indication

Green

E2 = 1

Grey

E2 mode

251

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

3.9.3 Graphic Element


3.9.3.1 Numeric

Presentation:

1
2

252

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

MV

Object value

? ? ? Red flashing

ALAI = 1 and AU_ST_00 =


1

Unacknowledged signal
error

Red flashing

AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck alarm Deviation


UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

? ? ? Red

ALAI = 1

Signal error

Red

ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green

Green

UNIT

Invisible
2

Measured Value

Unit

Mode

Object mode

Bal Green

BAL = 1

Balanced mode

M Fd Green

MANF = 1

Manual Forced mode

M Green

MAN = 1

Manual mode

A Green

AUTO = 1

Auto mode

E1 Green

E1 = 1

E1 mode

E2 Green

E2 = 1

E2 mode

Mode is invisible

The conditions are in priority order. Underlined parameters are configurable.

3BSE 021 945R401

253

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible
2

Setpoint Value

SP
Red flashing

AU_ST_00 = 1 or
AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

254

Unacknowledged signal
error
UnAck alarm Deviation
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.

GENCON, PI Controller

Default Presentation

Condition

Remarks

Red

ALAI = 1 or
ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Green

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

255

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

OP

Object value

AU_ST_00 = 1 or

Unacknowledged signal
error
UnAck alarm Deviation
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

Invisible
2

Output Value
Red flashing

AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

256

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.

GENCON, PI Controller

Default Presentation

Condition

Remarks

Red

ALAI = 1 or
ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

Magenta

% Green

Unit

Object unit

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

257

GENCON, PI Controller

Section 3, Faceplates and Graphic Elements

3.9.3.2 Bargraph

Presentation:

1
4
5

2
3

6
7

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

ALAI = 1 and AU_ST_00 =


1

Unacknowledged signal
error

? Red

ALAI = 1

Signal error

MV

Object value

ALAI = 1

Invisible - I/O Error

Measured Value
-

258

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3
cont.

GENCON, PI Controller

Default Presentation

Condition

Remarks

Red flashing

AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck alarm Deviation


UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

Red

ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

ALLIMH2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH2 = 1 and
AU_ST_04 = 1

Unfilled Red flashing

AU_ST_04 = 1

Filled Red

ALLIMH2 = 1

Unfilled Grey

Green
4

High Limit 2

High Limit 1

3BSE 021 945R401

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

ALLIMH1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIMH1 = 1 and
AU_ST_05 = 1

Unfilled Red flashing

AU_ST_05 = 1

Filled Red

ALLIMH1 = 1

Unfilled Grey

259

GENCON, PI Controller

No

Description

Low Limit 1

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

ALLIML1 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML1 = 1 and
AU_ST_06 = 1

Unfilled Red flashing

AU_ST_06 = 1

Filled Red

ALLIML1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

ALLIML2 = 1 and AL_BLK


=1

Unfilled Yellow

AL_BLK = 1

Filled Red flashing

ALLIML2 = 1 and
AU_ST_07 = 1

Unfilled Red flashing

AU_ST_07 = 1

Filled Red

ALLIML2 = 1

Unfilled Grey

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

260

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Black

SELECTED = 0

1.2

Top Left Edge

Light Grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark Grey

Three Dimensions effect

Setpoint Value

3BSE 021 945R401

SP

Object setpoint value

261

GENCON, PI Controller

No

Section 3, Faceplates and Graphic Elements

Description

2
cont.

Default Presentation

Condition

Remarks

Red flashing

AU_ST_00 = 1 or
AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unacknowledged signal
error
UnAck alarm Deviation
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

ALAI = 1 or
ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

LIMSPH = 1

Limitation line and mesh

Grey

Red

Cyan
3

High SP Limit

Low SP Limit

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

LIMSPL = 1

Limitation line and mesh

Grey

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

262

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENCON, PI Controller

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Output Value

3BSE 021 945R401

OUT

Object output value

263

GENCON, PI Controller

No

Section 3, Faceplates and Graphic Elements

Description

2
cont.

Default Presentation

Condition

Remarks

Red flashing

AU_ST_00 = 1 or
AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unacknowledged signal
error
UnAck alarm Deviation
UnAck alarm high limit 2
UnAck alarm high limit 1
UnAck alarm low limit 1
UnAck alarm low limit 2

ALAI = 1 or
ALDEV = 1 or
ALLIMH2 = 1 or
ALLIMH1 = 1 or
ALLIML1 = 1 or
ALLIML2 = 1

Signal error
Alarm Deviation
Alarm high limit 2
Alarm high limit 1
Alarm low limit 1
Alarm low limit 2

OUTPH

Upper warning limit output

OUTPH > 100%

Invisible if OUTPH >

Yellow

LIMOPH = 1

Limitation line and mesh

Grey

Red

Magenta
3

High OUT Limit

Low OUT Limit

OUTPL

Lower warning limit output

OUTPL < 0%

Invisible if OUTPL <

Yellow

LIMOPL = 1

Limitation line and mesh

Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

264

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

3.10 GENUSD, User Defined Object


3.10.1 Faceplate
Presentation:

3BSE 021 945R401

265

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

2
1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

3.3

266

Control Point

Signal Error

Default Presentation

Condition

M Dark green

MAN = 1

A Dark green

AUTO = 1

B Dark green

BLK = 1

S Dark green

STBY = 1

M1 Dark green

M1 = 1

M2 Dark green

M2 = 1

M3 Dark green

M3 = 1

Q1 Red

ALQ1 = 1

Q2 Red

ALQ2 = 1

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

No

Description

Default Presentation

Condition

3.4

Print Blk

P Yellow

PRINT_BLK

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Incr

Remarks

Increase setpoint2
with 1 unit
Increase setpoint
with 0,5%

Decr

Decrease setoint2
with 1 unit
Decrease setpoint
with 0,5%

Man

Set to Man Mode

Set MORD_04 = 1

Auto

Set to Auto Mode

Set MORD_05 = 1

Blk

Set to Blocked Mode

Set MORD_06 = 1

Stb

Set to Standby Mode

Set MORD_07 = 1

M1

Set to M1 Mode

Set MORD_01 = 1

M2

Set to M2 Mode

Set MORD_02 = 1

M3

Set to M3 Mode

Set MORD_03 = 1

C1

Set to C1 Mode

Set MORD_09 = 1

C2

Set to C2 Mode

Set MORD_10 = 1

C3

Set to C3 Mode

Set MORD_11 = 1

C4

Set to C4 Mode

Set MORD_12 = 1

C5

Set to C5 Mode

Set MORD_13 = 1

C6

Set to C6 Mode

Set MORD_14 = 1

C7

Set to C7 Mode

Set MORD_15 = 1

C8

Set to C8 Mode

Set MORD_16 = 1

3BSE 021 945R401

267

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

3.10.1.1 Control and ReducedControl

Presentation:
2

4
5
6
7

4
8
5

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Range Max

Green

MAX

Range Max of the MV


value

1.2

Range Min

Green

MIN

Range Min of the MV value

2.1

Measured Value
Bargraph

MV

Object measured value

268

Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2.2

High Limit 2

2.3

2.4

2.5

3.1

Default Presentation

Condition

Remarks

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV > MVH2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH2

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV > MVH1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV < MVL1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV < MVL2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL2

Unfilled Grey

SP Value

SP
Cyan

3BSE 021 945R401

GENUSD, User Defined Object

Object setpoint value

269

GENUSD, User Defined Object

No

Description

3.2

High SP Limit

3.3

Default Presentation

Condition

Remarks

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

SP > SETPH

Limitation line and mesh

Grey

Low SP Limit

Measured Value

4.1

MV Value

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

SP < SETPL

Limitation line and mesh

Grey

The MV object value


MV

Black
4.2

MV Unit

Setpoint Value

5.1

SP Value

Measured value

UNIT

Black
5

Section 3, Faceplates and Graphic Elements

Measured unit

The SP object value


SP

Black

Setpoint value

5.2

SP Unit

UNIT

Setpoint unit

Mesured2 Value

The MV2 object value

6.1

MV2 Value

Black

MV2

Measured2 Value

6.2

MV2 Unit

% Black

Setpoint 2 Value

7.1

SP2 Value

Black

7.2

SP2 Unit

% Black

Status Indication

270

Measured2 Unit

SP2

The setpoint 2 value


The setpoint 2 Unit
Status - Square indication

Filled Green

IND1 = 1

On

Unfilled Green

IND1 = 0 and IND2 =1

Off

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

3.10.1.2 Limits and Block

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

L2

MVH1

MVL1

L2 Black
Black

3BSE 021 945R401

MVH2

L1 Black
Black

Remarks

H1 Black
Black

Condition

MVL2

271

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

3
4

Behavior:
No

Description

Default Presentation

SP H

SP H Black
Black

SP L

SP2 H

SP2 L

SETPL

SETP2H

SP2 L Black
Black

272

SETPH

SP2 H Black
Black

Remarks

SP L Black
Black

Condition

SETP2L

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

Presentation:

Behavior:
No

Description

Default Presentation

Block Alarm

Block Alarm Black

Block Printout

Block Event

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

AL_BLK = 1

Deblock pressed

AL_BLK = 0

Remarks

Block Printout Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

Block Event Black

Yellow

Blocked

Block pressed

EVENT_BLK = 1

Deblock pressed

EVENT_BLK = 0

273

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

3.10.2 Object Display


Presentation:
2

3 4

10

12-19









20-25

11

19
26
27
28

33-36

29-32

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Black

SELECTED = 0

274

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Header

Default Presentation

GENUSD, User Defined Object

Condition

Remarks

NAME and DESCR

Object name and


description

AU_ST_00 = 1 or

AU_ST_02 = 1 or
AU_ST_03 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unacknowledged sign.
error 1
Unacknowledged sign.
error 2
Unacknowledged alarm 1
Unacknowledged alarm 2
Unacknowledged alarm 3
Unacknowledged alarm 4
Unacknowledged alarm 5
Unacknowledged alarm 6

Red

ALQ1 = 1 or
ALQ2 = 1 or
ALF1 = 1 or
ALF2 = 1 or
ALF3 = 1 or
ALF4 = 1 or
ALF5 = 1 or
ALF6 = 1

Signal error 1
Signal error 2
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6

Green

Normal

Red flashing

AU_ST_01 = 1 or

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

5.1

Range MV Max
Green

5.2

Range MV Min

Text in front of the value


PROC_SEC

Process section
Text in front of the value

CLASS

Object class

MAX

Range Max of the MV


value

MIN

Range Min of the MV value

Green

Measure Value Trim


Curve

Green

MV

Object measure value

Setpoint Value Trim


Curve

Cyan

SP

Object setpoint value

3BSE 021 945R401

275

GENUSD, User Defined Object

No

Description

7.1

Measured Value
Bargraph

7.2

7.3

7.4

7.5

276

Default Presentation

Green

High Limit 2

Section 3, Faceplates and Graphic Elements

Condition

Remarks

MV

Object value

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV > MVH2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH2

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV > MVH1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV < MVL1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV < MVL2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL2

Unfilled Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

8.1

SP Value

Default Presentation

Cyan
8.2

8.3

High SP Limit

GENUSD, User Defined Object

Condition

Remarks

SP

Object setpoint value

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

SP > SETPH

Limitation line and mesh

Grey

Low SP Limit

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

SP < SETPL

Limitation line and mesh

Grey

LIMITATIONS for MV

Alarm limits for MV

9.1

MV Text

MV Grey

Text in front of the line

9.2

H2 Text

H2 Grey

Text in front of the value

9.3

H2 Value

MVH2
Green

9.4

H1 Text

9.5

H1 Value

9.6

L1 Text

9.7

L1 Value

L2 Text

9.9

L2 Value

LIMITATIONS for SP

10.1

SP Text

3BSE 021 945R401

High limit 1 value

L1 Grey

Text in front of the value


MVL1

Low limit 1 value

L2 Grey

Text in front of the value


MVL2

Green
10

Text in front of the value


MVH1

Green
9.8

H1 Grey

Green

High limit 2 value

Low limit 2 value

Limitations for SP

SP Grey

Text in front of the line

277

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

10.2

H Text

H Grey

10.3

H Value

L Text

10.5

L Value

Setpoint High value

L Grey

Text in front of the value


SETPL

Cyan

Remarks
Text in front of the value

SETPH
Cyan

10.4

Condition

Setpoint Low value

11

LIMITATIONS for SP2

Limitations for SP2

11.1

SP2 Text

SP2 Grey

Text in front of the line

11.2

H Text

H Grey

Text in front of the value

11.3

H Value

SETP2H
Magenta

11.4

L Text

11.5

L Value

L Grey

Text in front of the value


SETP2L

Magenta

Setpoint High 2 value

Setpoint Low 2 value

12

ALARMS

12.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALQ1 = 1 and AU_ST_00 =1

Signal error 1

Red

ALQ1 = 1

12.3

12.4

13.1

278

Alarms

Alarm Indication

User defined text

Printout Blocked

Q1: Optional text

User defined text

Red

ALQ1 = 1 or
AU_ST_00 =1

Grey

P Yellow

PR_BLK = 1

Alarm or
Unacknowledged alarm

Printout blocked

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

No

Description

Default Presentation

Condition

Remarks

13.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALQ2 = 1 and AU_ST_01 =1

Signal error 2

Red

ALQ2 = 1

13.3

13.4

Alarm Indication

User defined text

Q2: Optional text

User defined text

Red

ALQ2 = 1 or
AU_ST_01 =1

Grey

Alarm or
Unacknowledged alarm

14.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

14.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF1 = 1 and AU_ST_02 =1

Alarm 1

Red

ALF1 = 1

14.3

14.4

Alarm Indication

User defined text

K1: Optional text

User defined text

Red

ALF1 = 1 or
AU_ST_02 =1

Grey

Alarm or
Unacknowledged alarm

15.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

15.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF2 = 1 and AU_ST_03 =1

Alarm 2

Red

ALF2 = 1

15.3

15.4

Alarm Indication

User defined text

3BSE 021 945R401

K2: Optional text

User defined text

Red

ALF2 = 1 or
AU_ST_03 =1

Grey

Alarm or
Unacknowledged alarm

279

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

16.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

16.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF3 = 1 and AU_ST_04 =1

Alarm 3

Red

ALF3 = 1

16.3

16.4

Alarm Indication

User defined text

K3: Optional text

User defined text

Red

ALF3 = 1 or
AU_ST_04 =1

Grey

Alarm or
Unacknowledged alarm

17.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

17.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF4 = 1 and AU_ST_05 =1

Alarm 4

Red

ALF4 = 1

17.3

17.4

Alarm Indication

User defined text

K4: Optional text

User defined text

Red

ALF4 = 1 or
AU_ST_05 = 1

Grey

Alarm or
Unacknowledged alarm

18.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

18.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF5 = 1 and AU_ST_06 =1

Alarm 5

Red

ALF5 = 1

18.3

280

Alarm Indication

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

18.4

User defined text

K5: Optional text

GENUSD, User Defined Object

Condition

Remarks
User defined text

Red

ALF5 = 1 or
AU_ST_06 = 1

Grey

Alarm or
Unacknowledged alarm

19.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

19.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AUTO_BLK = 1

Alarm blocked by PCprogram

Red flashing

ALF6 = 1 and AU_ST_07 =1

Alarm 6

Red

ALF6 = 1

19.3

19.4

Alarm Indication

User defined text

20

INTERLOCKS

20.1

Interlock Indication

20.2

User defined text

21.1

Interlock Indication

21.2

User defined text

22.1

Interlock Indication

22.2

User defined text

23.1

Interlock Indication

3BSE 021 945R401

K6: Optional text

User defined text

Red

ALF6 = 1 or
AU_ST_07 = 1

Grey

Alarm or
Unacknowledged alarm

Interlocks
Yellow

INTLU1 = 1

U1: Optional text

User defined text

Yellow

INTLU1 = 1

Grey

Yellow

INTLU2 = 1

U2: Optional text


INTLU2 = 1

Grey

INTLU3 = 1

U3: Optional text

Interlock 2

Interlocked

Interlock 3
User defined text

Yellow

INTLU3 = 1

Grey

Yellow

Interlocked

User defined text

Yellow

Yellow

Interlock 1

INTLU4 = 1

Interlocked

Interlock 4

281

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

23.2

User defined text

U4: Optional text

24.1

Interlock Indication

24.2

User defined text

25.1

Interlock Indication

25.2

User defined text

26

STATUS & BLOCKING

26.1

Implemented Indication

26.2

Implemented text

Condition

User defined text

Yellow

INTLU4 = 1

Grey

Yellow

INTLU5 = 1

U5: Optional text

Interlocked

Interlock 5
User defined text

Yellow

INTLU5 = 1

Grey

Yellow

Remarks

INTLU6 = 1

U6: Optional text

Interlocked

Interlock 6
User defined text

Yellow

INTLU6 = 1

Grey

Interlocked

Status and Blocking


Green

ACT = 1

Implemented

Implemented
Implemented text

Grey
27.1

Repeat Fail Block


Indication

27.2

Repeat Fail Block text

28.1

Event Block Indication

28.2

Event Block text

29

Measured Value

29.1

MV

282

Yellow

RP_BLK = 1

Repeat Fail Blk

Repeat Fail Block text

Yellow

RP_BLK = 1

Grey

Yellow

Repeat Fail Block

EV_BLK = 1

Event Block

Event Block
Event Block text

Yellow

EV_BLK = 1

Grey

The MV object value

MV Grey

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

29.2

MV Value

Default Presentation

Green
29.3

MV Unit

Setpoint Value

30.1

SP

30.2

SP Value

31.1

MV2 Text

31.2

MV2 Value

32.1

SP2 Text

32.2

SP2 Value

Text in front of the value


Setpoint value

Setpoint unit

Text in front of the value


MV2

Measured 2 value

UNIT2

Measured 2 unit

The SP2 object value

SP2 Grey

Text in front of the value


SETP2

Cyan
32.3

MV2 Grey

Green
Setpoint 2 Value

Measured unit

The MV2 object value

MV2 Unit

32

UNIT

Green
31.3

Measured value

SP

Cyan
Measured 2 Value

MV

SP Grey

SP Unit

31

Remarks

The SP object value

Cyan
30.3

Condition

UNIT
Green

30

GENUSD, User Defined Object

SP2 Unit

UNIT2

Cyan

Setpoint 2 value

Setpoint 2 unit

33.1

I1 Text

I1 Grey

33.2

I1 Indication

Filled Green

IND1 = 1

On - Square indication

Unfilled Green

IND1 = 0

Off - Square indication

34.1

I2 Text

3BSE 021 945R401

I2 Grey

I1-text

I2-text

283

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

34.2

I2 Indication

Filled Green

IND2 = 1

On - Square indication

Unfilled Green

IND2 = 0

Off - Square indication

35.1

I3 Text

I3 Grey

35.2

I3 Indication

Filled Green

IND3 = 1

On - Square indication

Unfilled Green

IND3 = 0

Off - Square indication

I3-text

36.1

I4 Text

I4 Grey

36.2

I4 Indication

Filled Green

IND4 = 1

On - Square indication

Unfilled Green

IND4 = 0

Off - Square indication

M1 = 1

Operator position
indication

37.1

M1 Indication

37.2

User defined text

38.1

M2 Indication

38.2

User defined text

39.1

M3 Indication

39.2

User defined text

40.1

Man Indication

40.2

Man text

41.1

284

Auto Indication

Green

I4-text

M1: Opt. text

User defined text

Green

M1 = 1

Grey

Green

M2 = 1

M2: Opt. text

User defined text

Green

M2 = 1

Grey

Green

M3 = 1

M3: Opt. text


M3 = 1

Grey

MAN = 1

Man

Manual mode
Man text

Green

MAN = 1

Grey

Green

Operator position
indication
User defined text

Green

Green

Operator position
indication

AUTO = 1

Auto mode

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

41.2

Auto text

Auto

42.1

Blocked Indication

42.2

Blocked text

43.1

Stand By indication

43.2

Stand By text

3BSE 021 945R401

GENUSD, User Defined Object

Condition

Auto text

Green

AUTO = 1

Grey

Green

BLK = 1

Blocked

Blocked mode
Blocked text

Green

BLK = 1

Grey

Green filled

Remarks

STBY = 1

Stand By

Stand By mode
Stand By text

Green

STBY = 1

Grey

285

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

3.10.3 Graphic Element


3.10.3.1 Numeric

Presentation:

1
2

5
6

286

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

ALARM_BK = 1

Alarm blocked by operator

MV

Object setpoint value

Red flashing

AU_ST_00 =1 or
AU_ST_01 =1 or
AU_ST_02 =1 or
AU_ST_03 =1 or
AU_ST_04 =1 or
AU_ST_05 =1 or
AU_ST_06 =1 or
AU_ST_07 =1

Unacknowledged alarm

Red

ALQ1 = 1 or ALQ2 = 1 or
ALF1 = 1 or ALF2 = 1 or
ALF3 = 1 or ALF4 = 1 or
ALF5 = 1 or ALF6 = 1

Alarm

Green

Invisible
2

Measured Value

Unit

Object unit
Green

UNIT

Control Point

Object mode

M1 Magenta

M1 = 1

Operator position M1

M2 Magenta

M2 = 1

Operator position M2

M3 Magenta

M3 = 1

Operator position M3

3BSE 021 945R401

Operator position is
invisible

287

GENUSD, User Defined Object

No

Description

Mode

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks
Object mode

M Green

MAN = 1

Manual mode

A Green

AUTO = 1

Auto mode

B Green

BLK = 1

Blocked mode

S Green

STBY = 1

Standby mode

Mode is invisible

Interlocks

Object interlock

X Yellow

Interlock 1
Interlock 2
Interlock 3
Interlock 4
Interlock 5
Interlock 6

INTLU1 = 1 or
INTLU2 = 1 or
INTLU3 = 1 or
INTLU4 = 1 or
INTLU5 = 1 or
INTLU6 = 1

Interlock is invisible

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

1
2

288

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

ALARM_BK = 1

Alarm blocked by operator

SP

Object setpoint value

Red flashing

AU_ST_00 =1 or
AU_ST_01 =1 or
AU_ST_02 =1 or
AU_ST_03 =1 or
AU_ST_04 =1 or
AU_ST_05 =1 or
AU_ST_06 =1 or
AU_ST_07 =1

Unacknowledged alarm

Red

ALQ1 = 1 or ALQ2 = 1 or
ALF1 = 1 or ALF2 = 1 or
ALF3 = 1 or ALF4 = 1 or
ALF5 = 1 or ALF6 = 1

Alarm

Cyan

Invisible
2

Setpoint Value

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

289

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

ALARM_BK = 1

Alarm blocked by operator

Invisible

290

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

MV2 Value

Default Presentation

GENUSD, User Defined Object

Condition

Remarks

MV2

Measured 2 value

Red flashing

AU_ST_00 =1 or
AU_ST_01 =1 or
AU_ST_02 =1 or
AU_ST_03 =1 or
AU_ST_04 =1 or
AU_ST_05 =1 or
AU_ST_06 =1 or
AU_ST_07 =1

Unacknowledged alarm

Red

ALQ1 = 1 or ALQ2 = 1 or
ALF1 = 1 or ALF2 = 1 or
ALF3 = 1 or ALF4 = 1 or
ALF5 = 1 or ALF6 = 1

Alarm

Cyan

Unit

Object unit
Green

UNIT2

Measured 2 unit

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

291

GENUSD, User Defined Object

Section 3, Faceplates and Graphic Elements

3.10.3.2 Bargraph

Presentation:

1
3
4

5
6

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Measured Value

292

MV

Object value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.

Default Presentation

Condition

Remarks

Red flashing

AU_ST_00 =1 or AU_ST_01
=1 or AU_ST_02 =1 or
AU_ST_03 =1 or AU_ST_04
=1 or AU_ST_05 =1 or
AU_ST_06 =1 or AU_ST_07
=1

Unacknowledged alarm

Red

ALQ1 = 1 or ALQ2 = 1 or
ALF1 = 1 or ALF2 = 1 or
ALF3 = 1 or ALF4 = 1 or
ALF5 = 1 or ALF6 = 1

Alarm

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV > MVH2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH2

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV > MVH1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV > MVH1

Unfilled Grey

Low Limit 1

3BSE 021 945R401

GENUSD, User Defined Object

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV < MVL1 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL1

Unfilled Grey

293

GENUSD, User Defined Object

No

Description

Low Limit 2

Default Presentation

Section 3, Faceplates and Graphic Elements

Condition

Remarks

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV < MVL2 and AL_BLK = 1

Unfilled Yellow

AL_BLK = 1

Filled Red

MV < MVL2

Unfilled Grey

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

294

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GENUSD, User Defined Object

Presentation:

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Setpoint Value

3BSE 021 945R401

SP

Object setpoint value

295

GENUSD, User Defined Object

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red flashing

AU_ST_00 =1 or
AU_ST_01 =1 or
AU_ST_02 =1 or
AU_ST_03 =1 or
AU_ST_04 =1 or
AU_ST_05 =1 or
AU_ST_06 =1 or
AU_ST_07 =1

Unacknowledged alarm

Red

ALQ1 = 1 or ALQ2 = 1 or
ALF1 = 1 or ALF2 = 1 or
ALF3 = 1 or ALF4 = 1 or
ALF5 = 1 or ALF6 = 1

Alarm

SETPH

Upper warning limit


setpoint

SETPH > MAX

Invisible

Yellow

SP > SETPH

Limitation line and mesh

Grey

Cyan
3

High SP Limit

Low SP Limit

SETPL

Lower warning limit


setpoint

SETPL < MIN

Invisible

Yellow

SP < SETPL

Limitation line and mesh

Grey

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

296

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP ALARM, Group Alarm

3.11 GROUP ALARM, Group Alarm


3.11.1 Faceplate
Presentation:

3BSE 021 945R401

297

GROUP ALARM, Group Alarm

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Alarm and Block


Indicator

Default Presentation

Condition

Remarks

DISTURB=1

Alarm

AL_UNACK=1

Unacknowledged alarm
Click icon to acknowledge

298

AL_BLK=1 or

Alarm block

AL_P_BLK=1

Alarm Period Block

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

1
cont.

GROUP ALARM, Group Alarm

Condition

Remarks

RP_F_BLK=1

Repeat Fail Block

Name and Description

Status Field

3.1

Print Blk

P Yellow

PRINT_BLK=1

Printout blocked

Aspect Links

Alarm List

position 0,0,8

Alarm List

Event List

position 0,0,9

Event List

Object Display

position 5,5,10

Object Display

Object Type Help

position 0, 0, 12

3BSE 021 945R401

299

GROUP ALARM, Group Alarm

Section 3, Faceplates and Graphic Elements

3.11.1.1 Control and Reduced Control

Presentation:

1
2
3
4
5

1
2

Behavior:
No

Description

Default Presentation

1.1

No. of Alarms Text

No of Alarms: Black

1.2

No. of Alarms Value

Red

DST_CNT > 0

Green

DST_CNT = 0

2.1

Reason Text

2.2

Reason Value

300

Condition

Remarks
Dist Counter

Reason: Black
Alarm Green

REASON=0

Unack Green

REASON=1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Member Status

MEMBER STATUS black

4.1

Prevent Event
Indication

4.2

Prevent Event Text

Prevent Event: Black

4.3

Prevent Event Handling

Op Yellow

Yellow

Pgm Yellow
Ext Yellow
5.1

Block Control
Indication

5.2

Block Control Text

Green

GROUP ALARM, Group Alarm

Condition

Remarks
status

PREV_OP=1 or
PREV_PGM=1 or
PREV_EXT=1

PREV_OP=1
PREV_PGM=1
PREV_EXT=1
BLK_CTRL=1

Block Control Black

3.11.1.2 Block

Presentation:

3BSE 021 945R401

301

GROUP ALARM, Group Alarm

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Block Alarm

Block Alarm Black

302

Block Printout

Block Obj Alarm

Block ObjPrint

Condition

Yellow

Blocked

Block pressed

AL_BLK=1

Deblock pressed

AL_BLK=0

Remarks

Block Alarm Black

Yellow

Blocked

Block pressed

PR_BLK=1

Deblock pressed

PR_BLK=0

Block Alarm Black

Object alarm block

Yellow

Blocked

Block pressed

M_AL_BLK=1

Deblock pressed

M_AL_BLK=0

Block Alarm Black

Object printout block

Yellow

Blocked

Block pressed

M_PR_BLK=1

Deblock pressed

M_PR_BLK=0

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP ALARM, Group Alarm

3.11.2 Object Display


Presentation:
2

6
7
8
9
10
11
12

13
14
15
16
17
18
19
20
21
22
23
24

25
26

27, 28, 29,30

Behavior:
No

Description

Default Presentation

Condition

Remarks

Select Frame

White

SELECTED=1

Object select frame

Invisible

Header
Red flashing

3BSE 021 945R401

NAME and DESCR

Object name and description

AL_UNACK=1

Unacknowledged

303

GROUP ALARM, Group Alarm

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red

DISTURB=1

Alarm

Green

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

5.1

Member Name

Text in front of value


PROC_SEC

Text in front of value


CLASS

5.3

Action Status

Member Status

GROUP STATUS

6.1

Disturb Indication

6.2

7.1

304

Disturbance Text

Alarm block Indication

Object class

GRPMEMB:OBJECT
Yellow

GRPMEMB:BLOCKED = 1

Red

GRPMEMB:DISTURB = 1

Green

Invisible
5.2

Process Section

Error

Al Grey

GRPMEMB:ACTION = 0

Bc Grey

GRPMEMB: ACTION = 1

Ac Grey

GRPMEMB: ACTION = 2

No Grey

GRPMEMB: ACTION = 3

Other values

* Yellow

GRPMEMB: F_Upx =1

B Yellow

GRPMEMB: BLOCKED =1

F Red

GRPMEMB: DISTURB =1

Invisible

Group Status

Red flashing
Red

AL_UNACK=1

Unacknowledged

DISTURB=1

Alarm

Disturbance

Text behind indication

Red

AL_UNACK=1 or
DISTURB=1

Grey

Yellow

AL_BLK=1

Alarm blocked by operator

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.2

Alarm Block Text

8.1

Printout block
Indication

8.2

Printout Block Text

Default Presentation

AL_BLK=1

Grey

Yellow

PR_BLK=1

Yellow

PR_BLK=1

Grey

Yellow

P_AL_BLK=1

Alarm Period Block Text Alarm Period Block


Yellow

10.2

Repeat Fail Block Text

11.1

Second Fail Block


Indication

11.2

Second Fail Block Text

Text behind indication


-

Yellow flashing

RP_F_BLK=1

RP_F_BLK=1

Grey

Yellow

SC_F_BLK=1

SC_F_BLK=1

Grey

12.1

No. of Alarms Text

No of Alarms: Black

12.2

No. of Alarms Value

Red

DST_CNT > 0

Green

DST_CNT = 0

Implemented Indication

Green

13.2

Implemented Text

Implemented Grey

14.1

Group member
Indication

14.2

Group member Text

Second Fail Block


Text behind indication

Second Fail Block


Yellow

13.1

Repeat Fail Block


Text behind indication

Alarm Block
Yellow

GROUP PARAMETERS

Alarm blocked by PCprogram

P_AL_BLK=

Grey

13

Print block
Text behind indication

Print Block

9.2

Remarks
Text behind indication

Alarm Block

Alarm period block


Indication

Repeat Fail Block


Indication

Condition

Yellow

9.1

10.1

GROUP ALARM, Group Alarm

Dist Counter

Group Parameters

Green
Group member

ACT=1

Implemented
Text behind indication

GRP_MEMB=1

Group member
Text behind indication

Grey

3BSE 021 945R401

305

GROUP ALARM, Group Alarm

No

Description

Default Presentation

15.1

Reason Text

Reason: Grey

15.2

Reason Value

Section 3, Faceplates and Graphic Elements

Condition

Alarm Green

REASON=0

Unack Green

REASON=1

Green

RP_F_CTL=1

16.1

Repeat Fail Control


Indication

16.2

Repeat Fail Control Text Repeat Fail Control

Remarks

Repeat Fail Control


Text behind indication

Grey
17.1

Second Fail Control


Indication

17.2

Second Fail Control


Text

Green
Second Fail Control

GROUP MEMBER
STATUS

18.1

Prevent Event
Indication

18.2

Prevent Event Text

Prevent Event: Grey

18.3

Prevent Event Handling

Op Yellow

Yellow

Ext Yellow

19.2

Alarm Period Block


Text

Text behind indication

Group Member Status

Pgm Yellow

Alarm Period Block


Indication

Second Fail Control

Grey

18

19.1

SC_F_CTL=1

Yellow

PREV_OP=1 or
PREV_PGM=1 or
PREV_EXT=1

PREV_OP=1
PREV_PGM=1
PREV_EXT=1
M_AL_P_B=1

Alarm Period Block


Yellow

Text behind indication


M_AL_P_B=1

Grey
20.1

Alarm Block Indication

20.2

Alarm Block Text

Yellow

M_AL_BLK=1

Alarm Block
Yellow

Text behind indication


M_AL_BLK=1

Grey
21.1

306

Printout Block
Indication

Yellow

M_PR_BLK=1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

21.2

Printout Block Text

Print Block
Yellow

GROUP ALARM, Group Alarm

Condition

Remarks
Text behind indication

M_PR_BLK=1

Grey
22.1

First Up Indication

22.2

First Up Text

Yellow

M_AL_P_B=1

First Up
Yellow

Text behind indication


M_AL_P_B=1

Grey
23

GROUP MEMBER
PARAMETERS

Group Member Parameters

23.1

Deblk Delay Text

Delblk Delay: Grey

23.2

Deblk Delay Value

Green

DBLK_D_T

24.1

First Up Control
Indication

Green

F_UP_CTL=1

24.2

First Up Control Text

25.1

Block Control
Indication

25.2

Block Control Text

First Up Control Grey

Green

Value

Text behind indication


BLK_CTL=1

Block Control

Text behind indication

Grey
26.1

Page Browser Button

Next Page Black

Click for cyclical page


browsing: 1,2,3,1,2,3

26.2

Page numbering

Page: Grey

Group members were


displayed in 3 pages

1(3) Grey

1(3), 2(3) or 3(3)

27

ACKNOWLEDGE
CONTROL

27.1

Group Auto
Acknowledge ind.

27.2

Group Auto
Acknowledge Text

Group Member Parameters

Green

G_A_ACK=1

Group Auto
Acknowledge
Grey

28.1

Member Auto
Acknowledge ind.

3BSE 021 945R401

Green

M_A_ACK=1

307

GROUP ALARM, Group Alarm

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

28.2

Member Auto
Acknowledge Text

Member Auto
Acknowledge

Condition

Remarks

Grey
29.1

Alarm Indicator Text

Alarm Indicator
Grey

29.2

Alarm Indicator Name

30.1

Unack Indicator text

Green

DST_NAME

Unack indicator
Grey

30.2

Unack Indicator Name

Green

UNACK_NAME

3.11.3 Graphic Element


Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Select Frame

White

SELECTED=1

Object select frame

Dotted Yellow

AL_BLK=1

Alarm Blocked by operator

Dotted Yellow

SC_F_BLK=1

Second Fail Blocked

Invisible
2

308

Symbol Center Color

No. of Alarms

3D display object
Red flashing

AL_UNACK=1

Unacknowledged alarm

Red

DISTURB=1

Alarm

Green

No. of alarms

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3
cont.

3BSE 021 945R401

GROUP ALARM, Group Alarm

Default Presentation

Condition

Black

DST_CNT>0 and
VisNoOfAlarms = true

VisNoOfAlarms = false

Remarks

invisible

309

GROUP, Group Control

Section 3, Faceplates and Graphic Elements

3.12 GROUP, Group Control


3.12.1 Faceplate
Presentation:

310

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP, Group Control

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

Control point

3BSE 021 945R401

Default Presentation

Condition

M Dark green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

A Dark green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

S Dark green

IND2_04 = 1

Remarks

Sequence controller from


groupstart

311

GROUP, Group Control

No

Description

3.2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

C Dark green

IND2_04 = 0 and
IND2_03 = 0 and
IND2_02 = 0 and
IND2_01 = 0

Control controlled from


operators panel

L Dark green

IND2_01 = 1

Local controlled from local


panel

T Yellow

IND2_2 = 1

Test, jog running from


motor place

O Kakhi

IND2_3 = 1

Out of service. No control


possible.

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Interlock Indication

X Dark green

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11 = 1 or
(IND2_13 = 1 and
IND1_12 = 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

Safety interlock or
Operator interlock

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Object Type Help

position 0, 0, 12

312

Aspect links

Start

Start motor

Set MORD_10 = 1

Stop

Stop motor

Set MORD_11 = 1

Man

Set to Man Mode

Set MORD_05 = 1

Auto

Set to Auto Mode

Set MORD_04 = 1

Seq

Set to Sequence Control

Set MORD_15 = 1

Cen

Set to Central Control

Set MORD_03 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP, Group Control

No

Description

Default Presentation

Condition

Remarks

5
cont.

Loc

Set to Local Control

Set MORD_00 = 1

Test

Set to Test Control

Set MORD_01 = 1

OoS

Set to Out of Service


Control

Set MORD_02 = 1

Hold

Stop the stepping

Set MORD_09 = 1

IHold

Instant stop of the stepping

Set MORD_12 = 1

3.12.1.1 Control and ReducedControl

Presentation:

2
4
5

3BSE 021 945R401

4
5

313

GROUP, Group Control

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Error 1

TO Seq Red flashing

AU_IND1_00 = 1

Time Out Seq. Unack


alarm

TO Step Red flashing

AU_IND1_01 = 1

Time Out Step Unack


alarm

TO Seq Red

IND1_00 = 1

Time Out Sequence alarm

TO Step Red

IND1_01 = 1

Time Out Step alarm

Fault 3 Red flashing

AU_IND1_02 = 1

Unack alarm fault 3

Fault 4 Red flashing

AU_IND1_03 = 1

Unack alarm fault 4

Fault 5 Red flashing

AU_IND1_04 = 1

Unack alarm fault 5

Fault 3 Red

IND1_02 = 1

Alarm fault 3

Fault 4 Red

IND1_03 = 1

Alarm fault 4

Fault 5 Red

IND1_04 = 1

Alarm fault 5

IND2_06 = 0

Not Ready for Start

IND1_15 = 1

Hold

IND1_12 = 1 or

Run or

IND1_13 = 1

Sequence in progress

IND2_06 = 1

Ready to start

IND2_14 = 1 and

A-Interlock

Error 2

Status

IND2_06 = 1
Grey

IND2_03 = 1

Out of service

Green flashing

IND1_13 = 1

Sequence in Progress

Green

4.1

Active Step Text

Active Step Grey

4.2

Active Step Value

Green

Act Pres Text

314

Active Step text


INTL_RES
ACT_PRES_TEXT

Actual interlock text

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

5
cont.

GROUP, Group Control

Default Presentation

Condition

Remarks

Red

IND2_06 = 0

Not ready for start

Yellow

IND2_06 = 1

Ready for start

Condition

Remarks

3.12.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Override Interlock

Override Interlock Black

Block Alarm

3BSE 021 945R401

IND2_00 Indicates current


status

Yellow

Blocked

Override pressed

MORD_06 = 1

Normal pressed

MORD_07 = 0

Block Alarm Black

Yellow

Blocked

Block pressed

AL_BLK = 1

315

GROUP, Group Control

No

Description

2
cont.
3

Block Printout

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Deblock pressed

AL_BLK = 0

Remarks

Block Printout Black

Yellow

Blocked

Block pressed

PR_BLK = 1

Deblock pressed

PR_BLK = 0

3.12.2 Object Display


Presentation:

1
3
4
5
6
7

8
9
10
11
28

12
13

27

14
15
16
17
18

26

21-25

316

19-20

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP, Group Control

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

Normal

ALARMS

3.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

3.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_00 = 1

Unacknowledged alarm

Red

IND1_00 = 1

Alarm

TO Seq

TXT_BLK_00 = 0

Time Out Sequence

Red

IND1_00 = 1 or AU_IND1_00
=1

Grey

3.3

3.4

Alarms

Warning Indication

Alarm 1 Text

4.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

4.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_01 = 1

Unacknowledged alarm

Red

IND1_01 = 1

Alarm

TO Step

TXT_BLK_01 = 0

Time Out Step

Red

IND1_01 = 1 or AU_IND1_01
=1

Grey

4.3

4.4

Warning Indication

Alarm 2 Text

3BSE 021 945R401

317

GROUP, Group Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

5.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

5.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_02 = 1

Unacknowledged alarm

Red

IND1_02 = 1

Alarm

Fault 3

TXT_BLK_02 = 0

Error text for fault 3

Red

IND1_02 = 1 or AU_IND1_02
=1

Grey

5.3

5.4

Warning Indication

Alarm 3 Text

6.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

6.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_03 = 1

Unacknowledged alarm

Red

IND1_03 = 1

Alarm

Fault 4

TXT_BLK_03 = 0

Error text for fault 4

Red

IND1_03 = 1 or AU_IND1_03
=1

Grey

6.3

6.4

Warning Indication

Alarm 4 Text

7.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

7.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_04 = 1

Unacknowledged alarm

Red

IND1_04 = 1

Alarm

7.3

318

Warning Indication

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

GROUP, Group Control

No

Description

Default Presentation

Condition

Remarks

7.4

Alarm 5 Text

Fault 5

TXT_BLK_04 = 0

Error text for fault 5

Red

IND1_04 = 1 or AU_IND1_04
=1

Grey

INTERLOCKS

Interlocks

8.1

IC1 Active

8.2

IC1 Text

9.1

IC2 Active

9.2

IC2 Text

C-Interlock 2 Grey

10.1

IB2 Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

10.2

IB2 Active

Yellow

IND2_11 = 1

Interlock IB2 active

10.3

IB2 Text

Green

IB2_TXT

Interlock text IB2

11.1

IB4 Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

11.2

IB4 Active

Yellow

IND2_13 = 1

Interlock IB4 active

11.3

IB4 Text

Green

IB4_TXT

Interlock IB4 text

12.1

IB1 Blocked

BX Red

IND2_15 = 1 and
Override Interlock and
(IND2_00 = 1 or IND2_02 = 1) Interlock IB1 active

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock


blocked

IND2_10 = 1

Interlock IB1 active


Interlock IB1 text

Yellow

IND2_08 = 1

C-Interlock 1 Grey
Yellow

Safety Interlock IC1


IND2_09 = 1

Safety Interlock IC2 active


Safety Interlock IC2

12.2

IB1 Active

12.3

IB1 Text

Green

IB1_TXT

13.1

IB3 Blocked

BX Red

IND2_15 = 1 and
Override Interlock and
(IND2_00 = 1 or IND2_02 = 1) Interlock IB3 active

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock


blocked

IND2_12 = 1

Interlock IB3 active

IB3_TXT

Interlock IB3

13.2

IB3 Active

13.3

IB3 Text

3BSE 021 945R401

Yellow

Safety Interlock IC1 active

Yellow
Green

319

GROUP, Group Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

14.1

IA Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

14.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

14.3

IA Text

IA_TXT

Interlock IA text

15

STATUS

15.1

Implemented Indication

15.2

Implemented Text

16.1

Repeat Fail Blocked


Indication

16.2

Repeat Fail Blocked


Text

17

INFO

17.1

X1 Indication

17.2

X1 Text

18.1

X2 Indication

Green

Status
Green

Implemented Grey
Yellow

Implemented
REPEAT_BLK = 1

Repeat Fail Blk

The motor can be


controlled
Repeat Fail Blocked

Yellow

REPEAT_BLK = 1

Grey

Info
Red flashing

AU_IND1_07 = 1

Unack external alarm X1

Red

IND1_07 = 1

External alarm

Green

X1_TXT

Red flashing

AU_IND1_11 = 1

Unack external alarm X2

Red

IND1_11 = 1

External alarm

18.2

X2Text

Green

19.1

Run

Run Grey

320

ACT = 1

X2_TXT
Run

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

19.2

Status

Default Presentation

GROUP, Group Control

Condition

Remarks

IND2_06 = 0

Not Ready for Start

IND1_15 = 1

Hold

IND1_12 = 1 or

Run or

IND1_13 = 1

Sequence in progress

IND2_06 = 1

Ready to start

IND2_14 = 1 and

A-Interlock

IND2_06 = 1
Grey

IND2_03 = 1

Out of service

Green flashing

IND1_13 = 1

Sequence in Progress

Green

20.1

Active Step

Active Step Grey

20.2

Active Step Value

Green

21.1

Sequence Indication

21.2

Sequence Text

22.1

Central Indication

22.2

Central Text

3BSE 021 945R401

Green

INTL_RES

Value of current step

IND2_04 = 1

Sequence Controlled from


groupstart

Sequence
Green

IND2_04 = 1

Grey

Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central Controlled from


operators place

Central
Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Grey

321

GROUP, Group Control

No

Description

23.1

Local Indication

Section 3, Faceplates and Graphic Elements

Default Presentation
Green

Condition

Remarks

IND2_01 = 1

Local
Controlled from local
panel

23.2

24.1

Local Text

Local
Green

IND2_01 = 1

Grey

Test Indication

Yellow

IND2_02 = 1

Test
Jog running from motor
place

24.2

25.1

25.2

26.1

Test Text

Test
Yellow

IND2_02 = 1

Grey

Out of Service
Indication
Out of Service Text

Blocking Interlock Text

Yellow

IND2_03 = 1

Out of service
No control possible

Out of Service
Yellow

IND2_03 = 1

Grey

Blocking Interlock:

Blocking Interlock text

Grey
26.2

Act Pres Text

27.1

Auto Indication

27.2

Auto Text

322

ACT_PRES_TEXT

Actual interlock text

Red

IND2_06 = 0

Not ready for start

Yellow

IND2_06 = 1

Ready for start

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode. Process


conditions control
start/stop of motor

Green

Auto
Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

28.1

Man Indication

28.2

Man Text

Default Presentation
Green

GROUP, Group Control

Condition

Remarks

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode. Start order


affects the motor directly

Man Grey
Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Grey

3.12.3 Graphic Element


3.12.3.1 Indicator01

Presentation:

1
4

2
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

3BSE 021 945R401

323

GROUP, Group Control

No

Description

Mode

Section 3, Faceplates and Graphic Elements

Default Presentation

Remarks

ModeVisible = true

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

M Green

ManModeVisible = true
and
IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

ModeVisible = false

Mode is invisible

PointofControlVisible =
true

Control point

Status

Condition

S Green

IND2_04 = 1

Sequence Control

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central Control

L Green

IND2_01 = 1

Local Control

T Green

IND2_02 = 1

Test Control

O Green

IND2_03 = 1

Out of Servive Control

PointofControlVisible =
false

Control point is invisible

IND2_06 = 0

Not Ready for Start

Shape

324

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

GROUP, Group Control

Default Presentation

Condition

Remarks

IND1_15 = 1

Hold

IND1_12 = 1 or

Run or

IND1_13 = 1

Sequence in progress

IND2_06 = 1

Ready to start

IND2_14 = 1 and
IND2_06 = 1 and
IND2_02 = 0

A-Interlock

Grey

IND2_03 = 1

Out of Service

Red flashing

AU_IND = 1

Alarm Unack

Red

IND1_DIST = 1

Error

Green flashing

IND1_13 = 1

Start/Stop in progress

Green

4
cont.

color

3.12.3.2 ObjectLine01

Presentation:
1

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

3BSE 021 945R401

325

GROUP, Group Control

No

Description

Header

4.1

4.2

326

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

Normal

IND2_06 = 0

Not Ready for Start

IND1_15 = 1

Hold

IND1_12 = 1 or

Run or

IND1_13 = 1

Sequence in progress

IND2_06 = 1

Ready to start

IND2_14 = 1 and
IND2_06 = 1 and
IND2_02 = 0

A-Interlock

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_13 = 1

Sequence in Progress

Green

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto start

O Yellow

IND2_03 = 1

Out of Service

T Yellow

IND2_02 = 1

Test

L Green

IND2_01 = 1

Local

S Green

IND2_04 = 1

Sequence

Status

Mode

Point Of Control

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

4.2
cont.

4.3

Interlock Indication

GROUP, Group Control

Default Presentation

Condition

Remarks

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central

X Green

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11 = 1 or
(IND2_13 = 1 and
IND1_12 = 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

Safety interlock or
Operator interlock

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

4.4

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

4.5

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

IND1_08 = 1

Collective fault indication

4.6

Fault Indication

F Red

5.1

Active Step Text

Active Step Grey

5.2

Active Step value

Green

INTL_RES

Error 1

TO Seq Red flashing

AU_IND1_00 = 1

Time Out Seq. Unack


alarm

TO Step Red flashing

AU_IND1_01 = 1

Time Out Step Unack


alarm

TO Seq Red

IND1_00 = 1

Time Out Sequence alarm

TO Step Red

IND1_01 = 1

Time Out Step alarm

Fault 3 Red flashing

AU_IND1_02 = 1

Unack alarm fault 3

Fault 4 Red flashing

AU_IND1_03 = 1

Unack alarm fault 4

Fault 5 Red flashing

AU_IND1_04 = 1

Unack alarm fault 5

Fault 3 Red

IND1_02 = 1

Alarm fault 3

Error 2

3BSE 021 945R401

Active Step text

327

GROUP, Group Control

No

Description

7
cont.
8

328

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Fault 4 Red

IND1_03 = 1

Alarm fault 4

Fault 5 Red

IND1_04 = 1

Alarm fault 5

ACT_PRES_TEXT

Actual interlock text

Red

IND2_06 = 0

Not ready for start

Yellow

IND2_06 = 1

Ready for start

Act Pres Text

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

AC 400 Local Devices

3.13 AC 400 Local Devices


3.13.1 Display
Presentation:
6

10

11

14

15

16
17

12

3BSE 021 945R401

13

329

AC 400 Local Devices

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default presentation

Controller power supply Grey


header

1.1

24V supply indication

Condition

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

Battry voltage
indication

Green filled

Implemented = 1

Red crossed

Error = 1

Battry voltage name

Grey

Implemented = 1

Red

Error = 1

Battry backup supply


indication

Green filled

Implemented = 1

Red crossed

Error = 1

Battry backup supply


name

Grey

Implemented = 1

Red

Error = 1

I/O power supply


header

Grey

4.1

I/O 24V supply


indication

Green filled

Implemented = 1

Red crossed

Error = 1

I/O 24V supply name

Grey

Implemented = 1

Red

Error = 1

Green filled

Implemented = 1

Red crossed

Error = 1

1.2

2.1

2.2

3.1

3.2

3.3

3.4

4.2

5.1

330

24V supply name

Regulator indication

Regulator name

I/O regulator indication

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

AC 400 Local Devices

No

Description

Default presentation

Condition

5.2

I/O regulator name

Grey

Implemented = 1

Red

Error = 1

Controller header

Grey

6.1

Processor module
indication

Green filled

Implemented = 1

Green empty

Standby = 1

Yellow crossed

Warning = 1

Red crossed

Error = 1

Grey

Implemented = 1

Grey

Standby = 1

Grey

Warning = 1

Red

Error = 1

6.2

7.1

7.2

8.1

8.2

Processor module
name

Program card indication Green filled

Program card name

Free pgm card & M500


indication

Free pgm card & M500


name

Implemented = 1

Yellow crossed

Warning = 1

Red crossed

Error = 1

Grey

Implemented = 1

Grey

Warning = 1

Red

Error = 1

Green filled

Implemented = 1

Yellow crossed

Warning = 1

Red crossed

Error = 1

Grey

Implemented = 1

Grey

Warning = 1

Red

Error = 1

Subrack fan header

Grey

9.1

Fan indication

Green filled

Implemented = 1

Red crossed

Error = 1

3BSE 021 945R401

Remarks

331

AC 400 Local Devices

Section 3, Faceplates and Graphic Elements

No

Description

Default presentation

Condition

9.2

Fan name

Grey

Implemented = 1

Red

Error = 1

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

10.1

I/O fan indication

I/O fan name

11

S100 I/O bus extention


header

Grey

11.1

S100 I/O bus extention


indication

Green filled

Implemented = 1

Red crossed

Error = 1

S100 I/O bus extention


name

Grey

Implemented = 1

Red

Error = 1

12

Additional header

Grey

12.1

User defined
supervision indication

Green filled

Implemented = 1

Red crossed

Error = 1

User defined
supervision name

Grey

Implemented = 1

Red

Error = 1

PC triggered
supervision indication

Green filled

Implemented = 1

Red crossed

Error = 1

PC triggered
supervision name

Grey

Implemented = 1

Red

Error = 1

14

Terminal header

Grey

14.1

Terminal indication

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

11.2

12.2

13.1

13.2

14.2

332

Terminal name

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

AC 400 Local Devices

No

Description

Default presentation

15

Printer header

Grey

15.1

Printer indication

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

15.2

Printer name

Condition

16

External
communication

Grey

16.1

XCom indication

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

Green filled

Implemented = 1

Red crossed

Error = 1

Grey

Implemented = 1

Red

Error = 1

16.2

17.1

17.2

XCom name

RSCom indication

RSCcom name

3BSE 021 945R401

Remarks

333

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

3.14 MANSTN, Manual Station


3.14.1 Faceplate
Presentation:

334

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

2
1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

Print Blk

3BSE 021 945R401

Default Presentation

Condition

M Dark green

MAN = 1

E1 Dark green

E1 = 1

P Yellow

PRINT_F1_BLK or
PRINT_F2_BLK

Remarks

335

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Incr

Increase output
with 0,5 unit

MAN = 1

Decr

Decrease output
with 0,5 unit

MAN = 1

Man

Set to Man Mode

Set MMI_MAN = 1

E1

Set to E1 Mode

Set MMI_E1 = 1

Remarks

3.14.1.1 Control and ReducedControl

Presentation:
2

6
7
8
4
5

336

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

Behavior:
No

Description

Default Presentation

Condition

Remarks

Ranges

1.1

MV Range Max

Black

MAX

Range Max of the MV


value

1.2

MV Range Min

Black

MIN

Range Min of the MV value

2.1

Direction

Incr Black

MV_DIR = INCREASING

Increase

Decr Black

MV_DIR = DECREASING

Decrease

MV

Object value

2.2

2.3

Measured Value
Bargraph

Green

High Limit 2

3BSE 021 945R401

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

337

MANSTN, Manual Station

No

Description

2.4

High Limit 1

2.5

338

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2.6

Low Limit 2

Default Presentation

MANSTN, Manual Station

Condition

Remarks

MVL2

Alarm Low limit

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

3.1

OUT Range Max

100.0 Black

Range Max of OUT is


100.0%

3.2

OUT Range Min

0 Black

Range Min of OUT is 0.0%

Output Limitations

4.1

OUT Value Bargraph

Mesh and limitations lines


POUT
Magenta

4.2

4.3

4.4

High Limitation

3BSE 021 945R401

OUTPH

Upper warning limit output

OUTPH > PO_MAX

Invisible

Yellow

OUT=HL = 1

Grey

Low Limitation

Actuator position

Object value

OUTPL

Lower warning limit output

OUTPL < PO_MIN

Invisible

Yellow

OUT=LL = 1

Grey

Op Black

ACT_DIR = OPENING

Actuator open

Cl Black

ACT_DIR = CLOSING

Actuator closed

339

MANSTN, Manual Station

No

Description

Actuator Value
Bargraph

Section 3, Faceplates and Graphic Elements

Default Presentation

Blue

Condition

Remarks

ACTPOS

Actuator value

CTRL = ON-OFF

Measured Value

The MV object value

6.1

MV

MV Black

6.2

MV Value

XXX Red

MV is Bad

No connect with controller

? ? ? Red

ERR =1

Signal error

Black

MV

Measured value

Black

UNIT

Measured unit

Text in front of the value

6.3

MV Unit

Output Value

7.1

OUT

OUT Black

7.2

OUT Value

Black

POUT

Output value

7.3

OUT Unit

Black

PO_UNIT

Output unit

Actuator Value

8.1

ACT

8.2

ACT Value

The OUT object value

The ACT object value

ACT Black

Black
8.3

CTRL = ON-OFF

Text in front of the value

ACTPOS

Actuator value

CTRL = ON-OFF

ACT Unit

Actuator unit

% Black

340

Text in front of the value

CTRL = ON-OFF

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

3.14.1.2 Limits

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

L2

MVH1

MVL1

L2 Black
Black

3BSE 021 945R401

MVH2

L1 Black
Black

Remarks

H1 Black
Black

Condition

MVL2

341

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

Behavior:
No

Description

Default Presentation

OUT H

OUT H Black
Black

OUT L

Remarks

OUTPH

OUT L Black
Black

342

Condition

OUTPL

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

3.14.1.3 Block

Presentation:

3
4

Behavior:
No

Description

Default Presentation

Block Alarm 1

Block Alarm L1/H1 Black

Block Alarm 2

Block Printout 1

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

AL_F1_BLK = 1

Deblock pressed

AL_F1_BLK = 0

Remarks

Block Alarm L2/H2 Black

Yellow

Blocked

Block pressed

AL_F2_BLK = 1

Deblock pressed

AL_F2_BLK= 0

Block Printout L1/H1


Black

Yellow

Blocked

Block pressed

PRINT_F1_BLK = 1

Deblock pressed

PRINT_F1_BLK = 0

343

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Block Printout 2

Block Printout L2/H2


Black

344

Condition

Yellow

Blocked

Block pressed

PRINT_F2_BLK = 1

Deblock pressed

PRINT_F2_BLK = 0

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

3.14.2 Object Display


Presentation:
2

3 4

10
11
12
13

1
5

6
14
15

19
20

16-18

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Grey

SELECTED = 0

static

NAME and DESCR

Object name and


description

AL_UNACK = 1

Unacknowledged High
Alarm

Header
Red flashing

3BSE 021 945R401

345

MANSTN, Manual Station

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red

DISTURB = 1

High Alarm Text

Green

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

Ranges

MAX

MV Range Min

Green

MIN

OUT Range Max

Magenta

PO_MAX

OUT Range Min

Magenta

PO_MIN

ACT Range Max

100 Blue

ACT Range Min

0 Blue
MV
Green

Direction

Measured Value
Bargraph

MV value - Trim curve

AUT value - Trim curve

ACTPOS

ACT value - Trim curve

Blue

CTRL = ON-OFF

Incr Green

MV_DIR = INCREASING

Increase

Decr Green

MV_DIR = DECREASING

Decrease

MV

Object value

Symbol 2 Normal

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Green

High Limit 2
-

346

Object class

POUT

Output Value Trim Curve

7.3

CLASS

Green

Measure Value Trim


Curve

Process section
Text in front of the value

MV Range Max

Magenta

7.2

PROC_SEC

The actuator ranges are


omitted since they always
range from 0-100%.

Output Value Trim Curve

7.1

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.3
cont.

MANSTN, Manual Station

Default Presentation

Condition

Remarks

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Logical color

AL_F2_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

7.4

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

High Alarm Symbol

Unfilled Grey

Limit

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Logical color

AL_F1_BLK = 1

Logical color

High Limit 1

Unfilled Yellow

blocked Symbol

blocked Symbol

7.5

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Logical color

AL_F1_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

3BSE 021 945R401

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

347

MANSTN, Manual Station

No

Description

7.5
cont.
7.6

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Unfilled Grey

Low Limit 2

Remarks

MVL2

Alarm Low limit

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Logical color

AL_F2_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

8.1

8.2

Open or Closed

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Op Green

ACT_DIR = OPENING

Cl Green

ACT_DIR = CLOSING

OUT Value Bargraph

POUT
Magenta

8.3

8.4

High Limitation

348

Upper warning limit output

OUTPH > PO_MAX

Invisible

Yellow

OUT=HL = 1

High Limitation

Grey

Low Limitation

OUTPL

Lower warning limit output

OUTPL < PO_MIN

Invisible

Yellow

OUT=LL = 1

Low Limitation

Grey

Actuator Value Bargraph

ALARM LIMITS for MV

Object output value

OUTPH

ACTPOS
Blue

10

Open or close information

Object actuator value

CTRL = ON-OFF
Alarm limits for MV

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

No

Description

Default Presentation

Condition

Remarks

10.1

Printout Blocked

P Yellow

PRINT_F2_BLK = 1

Printout Blocked.

10.2

Alarm Blocked

B Yellow

AL_F2_BLK =1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK =1

Alarm blocked by PCprogram

Red flashing

AU_MV>H2 =1

Alarm High limit 2

Red

MV>H2 = 1

10.3

Alarm Indication

10.4

H2 Text

10.5

H2 Value

H2 Grey

Text in front of the value


MVH2

Green

High limit 2 value

11.1

Printout Blocked

P Yellow

PRINT_F1_BLK = 1

Printout Blocked

11.2

Alarm Blocked

B Yellow

AL_F1_BLK =1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK =1

Alarm blocked by PCprogram

Red flashing

AU_MV>H1 =1

Warning High limit 1

Red

MV>H1 = 1

11.3

Alarm Indication

11.4

H1 Text

11.5

H1 Value

H1 Grey

Text in front of the value


MVH1

Green

High limit 1 value

12.1

Printout Blocked

P Yellow

PRINT_F1_BLK = 1

Printout Blocked

12.2

Alarm Blocked

B Yellow

AL_F1_BLK =1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK =1

Alarm blocked by PCprogram

Red flashing

AU_MV<L1 =1

Warning Low limit 1

Red

MV<L1 = 1

12.3

Alarm Indication

12.4

L1 Text

12.5

L1 Value

13.1

Printout Blocked

3BSE 021 945R401

L1 Grey

Text in front of the value


MVL1

Green

P Yellow

PRINT_F2_BLK = 1

Low limit1 value

Printout Blocked

349

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

13.2

Alarm Blocked

B Yellow

AL_F2_BLK =1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK =1

Alarm blocked by PCprogram

Red flashing

AU_MV<L2 =1

Alarm Low limit 2

Red

MV<L2 = 1

13.3

Alarm Indication

13.4

L2 Text

13.5

L2 Value

L2 Grey
MVL2
Green

14

LIMITATIONS for OUT

14.1

OUT Text

14.2

Warning Indication

14.3

H Text

14.4

H Value

Warning Indication

15.2

L Text

15.3

L Value

OUT Grey
Yellow

Text in front of the line


OUT=HL = 1

H Grey

Yellow

OUT=LL = 1

MV Grey

16.2

MV Value

? ? ? Red

Green
MV Unit

Warning Output Low


Text in front of the value

OUTPL

MV Text

Output High value

L Grey

16.1

Warning Output High


Text in front of the value

OUTPH

Magenta

16.3

Low limit 2 value

Limitations for OUT

Magenta
15.1

Text in front of the value

Output Low value

Text in front of the value


ERR = 1

Signal error

MV

Measured value

UNIT

Measured unit

17.1

OUT Text

17.2

OUT Value

OUT Grey
POUT
Magenta

350

Text in front of the value


Output value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

17.3

OUT Unit

Default Presentation

Magenta
18

Actuator Value

18.1

ACT

18.2

ACT Value

ACT Grey

Remarks

PO_UNIT

Output unit

CTRL = ON-OFF

Text in front of the value

ACTPOS

Actuator value

CTRL = ON-OFF

ACT Unit

Actuator unit

%
19.1

Man indication

19.2

Man Text

19.3

Man Out Text

19.4

Man Out Value

20.1

E1 indication

20.2

E1 Text

20.3

Condition

The ACT object value

Blue
18.3

MANSTN, Manual Station

Blue
Green

MAN = 1

Man

Manual mode
Text behind the indication

Green

MAN = 1

Grey

OUT Grey

Text in front of the value


MANOUT

Man Out value

Magenta

MAN = 1

Manual mode

Grey

Green

E1 = 1

E1 Grey

E1 mode
Text behind the indication

Green

E1 = 1

Grey

E1 Name

3BSE 021 945R401

CTRL = ON-OFF

E1NAME
Green

E1 = 1

Grey

User text behind the text


E1

351

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

3.14.3 Graphic Element


3.14.3.1 Numeric, Mode and Unit

Presentation:

1
2

352

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

MV

Object value

MV is Bad

No contact with controller

ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

ERR =1

Signal error

Red

DISTURB =1

Alarm

Green

Invisible
2

Measured Value

X X X Red
? ? ? Red flashing

Unit

Object unit
Green

UNIT

Mode

Object mode

M Green

MAN = 1

E1 Green

E1 = 1

E1 mode
Mode is invisible

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

353

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

POUT

Object ratio value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Magenta

Invisible
2

Output Value

Unit

Object unit

% Green
The conditions are in priority order. Underlined parameters are configurable.

354

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MANSTN, Manual Station

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3.14.3.2 Bargraph

Presentation:

1
4
5

6
7

3BSE 021 945R401

355

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

? Red

ERR = 1

Signal error

MV

Object value

ERR = 1

Invisible - I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Green

356

MV Value

High Limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

5
cont.

MANSTN, Manual Station

Default Presentation

Condition

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

The conditions are in priority order. Underlined parameters are configurable.

3BSE 021 945R401

357

MANSTN, Manual Station

Section 3, Faceplates and Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

358

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Out Value

Default Presentation

MANSTN, Manual Station

Condition

Remarks

POUT

Object output value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

ERR = 1 or
DISTURB =1

Alarm

Magenta

High Limitation

OUTPH

Upper warning limit output

OUTPH > PO_MAX

Invisible

Yellow

OUT=HL = 1

Grey

Low Limitation

OUTPL

Lower warning limit output

OUTPL < PO_MIN

Invisible

Yellow

OUT=LL = 1

Grey

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

3BSE 021 945R401

359

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

3.15 MOTCON, Motor Control


3.15.1 Faceplate
Presentation:

360

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

2
1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

Control point

3BSE 021 945R401

Default Presentation

Condition

M Dark green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

A Dark green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

S Dark green

IND2_04 = 1

Remarks

Sequence controller from


groupstart

361

MOTCON, Motor Control

No

Description

3.2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

C Dark green

IND2_04 = 0 and
IND2_03 = 0 and
IND2_02 = 0 and
IND2_01 = 0

Control controlled from


operators panel

L Dark green

IND2_01 = 1

Local controlled from local


panel

T Yellow

IND2_2 = 1

Test, jog controlled from


motor place

O Kakhi

IND2_3 = 1

Out of service. No control


possible.

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Interlock Indication

X Dark green

IND2_08 = 1 or
Safety interlock or
IND2_09 = 1 or
Operator interlock
IND2_13 = 1 or
(IND2_11 = 1 and IND1_12
= 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

362

Aspect links

Start

Start motor

Set MORD_10 = 1

Stop

Stop motor

Set MORD_11 = 1

Man

Set to Man Mode

Set MORD_05 = 1

Auto

Set to Auto Mode

Set MORD_04 = 1

Seq

Set to Sequence Control

Set MORD_15 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

No

Description

Default Presentation

5
cont.

Cen

Set to Central Control

Set MORD_03 = 1

Loc

Set to Local Control

Set MORD_00 = 1

Test

Set to Test Control

Set MORD_01 = 1

OoS

Set to Out of Service


Control

Set MORD_02 = 1

Ord1

Set Order 1

Set MORD_12 = 1

Ord2

Set Order 2

Set MORD_13 = 1

Ord3

Set Order 3

Set MORD_14 = 1

R/L

Set direction to Reverse/


Low

Set MORD_09 = 1

F/H

Set direction to Forward/


High

Set MORD_08 = 1

3BSE 021 945R401

Condition

Remarks

363

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

3.15.1.1 Control and ReducedControl

Presentation:

4
1
5

6
2
3

Behavior:
No

Description

Motor Status

Default Presentation

Condition

Remarks

IND2_07 = 0

Not Ready for Start


Error or interlocks prevent
the start

IND2_14 = 1 and
IND2_07 = 1

364

A-Interlock

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

1
cont.

MOTCON, Motor Control

Condition

Remarks

IND1_12 = 1 or
IND1_15 = 1

Run
Direction Change

IND2_06 = 1

2.1

2.2

Bargraph

Limit Indication

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

Green

REAL_RES

Motor current value

REAL_RES_HILIM <= 0.1

Bargraph invisible

at 100%

3BSE 021 945R401

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

Grey

REAL_RES_HILIM <= 0.1

Limit Indication invisible

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

CVO Red flashing

AU_IND1_00 = 1

Control voltage unack.


error

BIM Red flashing

AU_IND1_01 = 1

Bimetal Relay unack. error

LSTOP Red flashing

AU_IND1_02 = 1

Local stop unack. error

SMON Red flashing

AU_IND1_03 = 1

Safety monitor unack. error

CVO Red

IND1_00 = 1

Control voltage error

Act Pres Text

Error 1

Start Ready Auto. The


motor starts when the
process conditions are
satisfied

365

MOTCON, Motor Control

No

Description

4
cont.

Direction Indication

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

BIM Red

IND1_01 = 1

Bimetal Relay

LSTOP Red

IND1_02 = 1

Local stop

SMON Red

IND1_03 = 1

Safety monitor

IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

MCERR Red flashing

AU_IND1_04 = 1

Motor Current unack error

MONL Red flashing

AU_IND1_05 = 1

Monitor low unack error

MONH Red flashing

AU_IND1_06 = 1

Monitor high unack error

MCERR Red

IND1_04 = 1

MotorCurrent error

MONL Red

IND1_05 = 1

Monitor low error

MONH Red

IND1_06 = 1

Monitor high error

Green

Green

366

Error 2

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

3.15.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Override Interlock

Override Interlock Black

Block Alarm

Block Printout

3BSE 021 945R401

Condition

Remarks
IND2_00 Indicates current
status

Yellow

Blocked

Block pressed

MORD_06 = 1

Deblock pressed

MORD_07 = 1

Block Alarm Black

Yellow

Blocked

Block pressed

ALARM_BLK = 1

Deblock pressed

ALARM_BLK = 0

Block Printout Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

367

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

3.15.2 Object Display


Presentation:
2

1
6
7
8
9
10
11
12




13
14
15
16


34

17
18
19
20
21
22
23

33

28-32

24-27

Behavior:
No

Description

Default Presentation Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object name and description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

368

Normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

No

Description

Default Presentation Condition

3.1

Range Max

Green

REAL_RES_MAX

REAL_RES_HILIM <= 0.1

Green

REAL_RES_MIN

REAL_RES_HILIM <= 0.1

Limit invisible

Green

REAL_RES

Motor current

REAL_RES_HILIM <= 0.1

Trim Curve invisible

Green

REAL_RES

Motor current

REAL_RES_HILIM <= 0.1

Bargraph invisible

3.2

5.1

5.2

Range Min

Trim Curve

Bargraph

Limit Indication

at 100%

Remarks

Limit invisible

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

REAL_RES_HILIM <= 0.1

Limit Indication invisible

Grey
6

ALARMS

6.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

6.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_00 = 1

Unacknowledged alarm

Red

IND1_00 = 1

Alarm

Control Voltage

TXT_BLK_00 = 0

Monitoring of Control
Voltage

Red

IND1_00 = 1 or AU_IND1_00
=1

Grey

6.3

6.4

Alarms

Warning Indication

Alarm 1 Text

3BSE 021 945R401

369

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation Condition

Remarks

7.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

7.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_01 = 1

Unacknowledged alarm

Red

IND1_01 = 1

Alarm

Bimetal Relay

TXT_BLK_01 = 0

Monitoring of Bimetal Relay

Red

IND1_01 = 1 or AU_IND1_01
=1

Grey

7.3

7.4

Warning Indication

Alarm 2 Text

8.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

8.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_02 = 1

Unacknowledged alarm

Red

IND1_02 = 1

Alarm

Local Stop

TXT_BLK_02 = 0

Monitoring of Local Stop

Red

IND1_02 = 1 or AU_IND1_02
=1

Grey

8.3

8.4

Warning Indication

Alarm 3 Text

9.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

9.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_03 = 1

Unacknowledged alarm

Red

IND1_03 = 1

Alarm

TXT_BLK_03 = 0

Monitoring of Safety Monitor

9.3

9.4

370

Warning Indication

Alarm 4 Text

Safety Monitor

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

9.4
cont.

MOTCON, Motor Control

Default Presentation Condition


Red

IND1_03 = 1 or AU_IND1_03
=1

Grey

Remarks

10.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

10.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_04 = 1

Unacknowledged alarm

Red

IND1_04 = 1

Alarm

Main Contactor

TXT_BLK_04 = 0

Monitoring of Main Contactor

Red

IND1_04 = 1 or AU_IND1_04
=1

Grey

10.3

10.4

Warning Indication

Alarm 5 Text

11.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

11.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_05 = 1

Unacknowledged alarm

Red

IND1_05 = 1

Alarm

Monitor Low

TXT_BLK_05 = 0

Monitoring of Monitor Low

Red

IND1_05 = 1 or AU_IND1_05
=1

Grey

11.3

11.4

Warning Indication

Alarm Text

12.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_06 = 1

Unacknowledged alarm

Red

IND1_06 = 1

Alarm

12.3

Warning Indication

3BSE 021 945R401

371

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation Condition

Remarks

12.4

Alarm Text

Monitor High

TXT_BLK_06 = 0

Monitoring of Monitor High

Red

IND1_06 = 1 or AU_IND1_06
=1

Grey

13

INTERLOCKS

Interlocks

13.1

IC1 Active

13.2

IC1 Text

14.1

IC2 Active

14.2

IC2 Text

C-Interlock 2 Grey

15.1

IB2 Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

15.2

IB2 Active

Yellow

IND2_13 = 1

Interlock IB2 active

15.3

IB2 Text

Green

IB2_TXT

Interlock text IB2

16.1

IB4 Block Indication

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

16.2

IB4 Active

Yellow

IND2_11 = 1

Interlock IB4 active

16.3

IB4 Text

Green

IB4_TXT

Interlock IB4 text

17.1

IB1 Blocked

BX Red

IND2_15 = 1 and
Override Interlock and
(IND2_00 = 1 or IND2_02 = 1) Interlock IB1 active

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock blocked

IND2_12 = 1

Interlock IB1 active


Interlock IB1 text

Yellow

IND2_08 = 1

C-Interlock 1 Grey
Yellow

Yellow

Safety Interlock IC1 active


Safety Interlock IC1

IND2_09 = 1

Safety Interlock IC2 active


Safety Interlock IC2

17.2

IB1 Active

17.3

IB1 Text

Green

IB1_TXT

18.1

IB3 Blocked

BX Red

IND2_15 = 1 and
Override Interlock and
(IND2_00 = 1 or IND2_02 = 1) Interlock IB3 active

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock blocked

IND2_10 = 1

Interlock IB3 active

18.2

IB3 Active

18.3

IB3 Text

Green

IB3_TXT

Interlock IB3

19.1

IA Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

19.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

19.3

IA Text

IA_TXT

Interlock IA text

372

Yellow

Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

20

STATUS

20.1

Implemented Indication

20.2

Implemented Text

21.1

Repeat Fail Blocked


Indication

21.2

Repeat Fail Blocked


Text

22

INFO

22.1

X1 Indication

22.2

X1 Text

23.1

X2 Indication

MOTCON, Motor Control

Default Presentation Condition

Remarks
Status

Green

ACT = 1

Implemented Grey
Yellow

Implemented
REPEAT_BLK = 1

Repeat Fail Block

The motor can be controlled


Repeat Fail Blocked

Yellow

REPEAT_BLK = 1

Grey

Info
Red flashing

AU_IND1_07 = 1

Unack external alarm X1

Red

IND1_07 = 1

External alarm

Green

X1_TXT

Red flashing

AU_IND1_11 = 1

Unack external alarm X2

Red

IND1_11 = 1

External alarm

23.2

X2Text

Green

24.1

Motor Status Text

Run Grey

24.2

Motor Status

X2_TXT
Run
Not Ready for Start
IND2_07 = 0

Error or interlocks prevent


the start

IND2_14 = 1 and

A-Interlock

IND2_07 = 1

3BSE 021 945R401

IND1_12 = 1 or

Run

IND1_15 = 1

Direction Change

373

MOTCON, Motor Control

No

Description

Section 3, Faceplates and Graphic Elements

Default Presentation Condition

24.2
cont.

25.1

Dir/Speed Text

25.2

Direction Indication

Remarks

IND2_06 = 1

Start Ready Auto. The motor


starts when the process
conditions are satisfied

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

Dir/Speed Grey

Green

Direction and speed

IND1_13 = 1

Forwards/High

IND1_14 = 1

Reverse/Low

26.1

Current Text

CURRENT Grey

26.2

Current Value

Green

REAL_RES

Motor current

26.3

Current Unit

% Green

% of nominal current

27.1

Nominal Current Text

Nom. Current Grey

27.2

Nom. Current Value

Green

27.3

Nom. Current Unit

A Green

28.1

Sequence Indication

28.2

Sequence Text

374

Green

Current

Nominal Current of motor


REAL_RES_HILIM
Unit Ampere
IND2_04 = 1

Sequence Controlled from


groupstart

Sequence
Green

IND2_04 = 1

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

29.1

Central Indication

29.2

Central Text

30.1

MOTCON, Motor Control

Default Presentation Condition


Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Remarks
Central Controlled from
operators place

Central
Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Grey

Local Indication

Green

IND2_01 = 1

Local
Controlled from local panel

30.2

31.1

Local Text

Local
Green

IND2_01 = 1

Grey

Test Indication

Yellow

IND2_02 = 1

Test
Jog running from motor
place

31.2

32.1

32.2

33.1

Test Text

Test
Yellow

IND2_02 = 1

Grey

Out of Service
Indication
Out of Service Text

Blocking Interlock Text

Yellow

IND2_03 = 1

Out of service
No control possible

Out of Service
Yellow

IND2_03 = 1

Grey

Blocking Service:

Blocking Interlock text

Grey
33.2

Actual Interlock Text

3BSE 021 945R401

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

375

MOTCON, Motor Control

No

Description

34.1

Auto Indication

34.2

Auto Text

35.1

Man Indication

35.2

Man Text

376

Section 3, Faceplates and Graphic Elements

Default Presentation Condition


Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Remarks
Auto mode. Process
conditions control start/stop
of motor

Auto
Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Grey

Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode. Start order


affects the motor directly

Man Grey
Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

3.15.3 Graphic Element


3.15.3.1 BargraphMC01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Limit Indication

at 100%

3BSE 021 945R401

Filled Yellow

AL_BLK = 1 and IND1_10


=1

Alarm blocked

Unfilled Yellow

AL_BLK = 1

Alarm blocked

377

MOTCON, Motor Control

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Filled Red flashing

AU_IND = 1 and IND1_10


=1

Unacknowledged alarm

Unfilled Red flashing

AU_IND = 1

Unacknowledged alarm

Filled Light Red

IND1_10 = 1

High motor current

Grey

Limit

Bargraph

REAL_RES
Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Error

Green

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

Orientation

378

Vertical, Horizontal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCON, Motor Control

3.15.3.2 Motor01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Mode or
Control point

3BSE 021 945R401

ModeIndVis = true

You can configure your


own text instead of using
the figures

* Yellow

IND2_02 = 1 and IND2_03


=0

Test

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

379

MOTCON, Motor Control

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0 and
IND2_14 = 0 and
IND2_07 = 1

Indicates Auto Start


Init Not Performed

M Green

ManModeIndVis = true and Manual mode


IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0
ManModeIndVis = false

S Green

IND2_04 = 1

Sequence Control

L Green

IND2_01 = 1

Local Control

C Green

IND2_01 = 0 and
IND2_04 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Central Control

ModeIndVis = false

Mode or Control point is


invisible

Direction Indication

DirectionVisible = true
Green
IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

DirectionVisible = false

Direction is invisible

Green

380

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Motor Status

Default Presentation

Shape

MOTCON, Motor Control

Condition

Remarks

IND2_07 = 0

Not Ready for Start


Error or interlocks prevent
the start

IND2_14 = 1 and

A-Interlock

IND2_07 = 1

Color

IND1_12 = 1 or

Run

IND1_15 = 1

Direction Change

IND2_06 = 1

Start Ready Auto. The


motor starts when the
process conditions are
satisfied

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Error

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ModeIndVis

2. Mode or Control point

True, False

ManModeIndVis

2. Mode or Control point

True, False

DirectionVisible

3. Direction Indication

True, False

3BSE 021 945R401

381

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

3.15.3.3 ObjectLine01

Presentation:
3

10

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

Header

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

Normal

Motor Status

Not Ready for Start


IND2_07 = 0
IND2_14 = 1 and
IND2_07 = 1
IND1_12 = 1 or
IND1_15 = 1

IND2_06 = 1

382

Error or interlocks prevent


the start

A-Interlock
Run
Direction Change
Start Ready Auto. The
motor starts when the
process conditions are
satisfied

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

3
cont.

Direction Indication

MOTCON, Motor Control

Green
IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

Green

Status Indication

5.1

Mode

5.2

Point Of Control

3BSE 021 945R401

Status Indication

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0

Indicates Auto Start


Init Not Performed

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

O Yellow

IND2_03 = 1

Out of Service

T Yellow

IND2_02 = 1

Test

L Green

IND2_01 = 1

Local

S Green

IND2_04 = 1

Sequence

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central

383

MOTCON, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

5.3

Interlock Indication

X Green

IND2_08 = 1 or
Safety interlock or
IND2_09 = 1 or
Operator interlock
IND2_13 = 1 or
(IND2_11 = 1 and IND1_12
= 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

5.4

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

5.5

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

5.6

Fault Indication

F Red

IND1_08 = 1

Collective fault indication

Bargraph

Green

REAL_RES

Motor current value

REAL_RES_HILIM <= 0.1

Bargraph invisible

384

Limit Indication

Error 1

at 100%

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

Grey

REAL_RES_HILIM <= 0.1

Limit Indication invisible

CVO Red flashing

AU_IND1_00 = 1

Control voltage unack. error

BIM Red flashing

AU_IND1_01 = 1

Bimetal Relay unack. error

LSTOP Red flashing

AU_IND1_02 = 1

Local stop unack. error

SMON Red flashing

AU_IND1_03 = 1

Safety monitor unack. error

CVO Red

IND1_00 = 1

Control voltage error

BIM Red

IND1_01 = 1

Bimetal Relay

LSTOP Red

IND1_02 = 1

Local stop

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

8
cont.
9

10

Error 2

Default Presentation

Condition

Remarks

SMON Red

IND1_03 = 1

Safety monitor

MCERR Red flashing

AU_IND1_04 = 1

Motor Current unack error

MONL Red flashing

AU_IND1_05 = 1

Monitor low unack error

MONH Red flashing

AU_IND1_06 = 1

Monitor high unack error

MCERR Red

IND1_04 = 1

Motor Current error

MONL Red

IND1_05 = 1

Monitor low error

MONH Red

IND1_06 = 1

Monitor high error

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

Act Pres Text

3BSE 021 945R401

MOTCON, Motor Control

385

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

3.16 MOTCONI, Motor Control


3.16.1 Faceplate
Presentation:

386

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

2
1
4

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

Control point

3BSE 021 945R401

Default Presentation

Condition

M Dark green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

A Dark green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

S Dark green

IND2_04 = 1

Remarks

Sequence controller from


groupstart

387

MOTCONI, Motor Control

No

Description

3.2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

C Dark green

IND2_04 = 0 and
IND2_03 = 0 and
IND2_02 = 0 and
IND2_01 = 0

Control controlled from


operators panel

L Dark green

IND2_01 = 1

Local controlled from local


panel

LM Yellow

BOOLH = 1

Local - MCC

T Yellow

IND2_2 = 1

Test, jog controlled from


motor place

O Kakhi

IND2_3 = 1

Out of service. No control


possible.

3.3

Print Blk

P Yellow

PRINT_BLK = 1

3.4

Interlock Indication

X Dark green

IND2_08 = 1 or
Safety interlock or
IND2_09 = 1 or
Operator interlock
IND2_13 = 1 or
(IND2_11 = 1 and IND1_12
= 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

W Yellow

IND1_07 or
BOOLD

Collective Warning
Indication

F Red

IND1_11 or
BOOLE or

Collective Fault Indication



Warnings or Alarms

IND1_08
4

388

Aspect links

Diagnostic Display

position 0, 0, 7

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Object Type Help

position 0, 0, 12

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

No

Description

Default Presentation

Start

Start motor

Set MORD_10 = 1

Stop

Stop motor

Set MORD_11 = 1

Man

Set to Man Mode

Set MORD_05 = 1

Auto

Set to Auto Mode

Set MORD_04 = 1

Seq

Set to Sequence Control

Set MORD_15 = 1

Cen

Set to Central Control

Set MORD_03 = 1

Loc

Set to Local Control

Set MORD_00 = 1

J/T

Set to Jog/Test Control

Set MORD_01 = 1

OoS

Set to Out of Service


Control

Set MORD_02 = 1

Ord1

Set Order 1

Set MORD_12 = 1

Ord2

Set Order 2

Set MORD_13 = 1

Ord3

Set Order 3

Set MORD_14 = 1

R/L

Set direction to Reverse/


Low

Set MORD_09 = 1

F/H

Set direction to Forward/


High

Set MORD_08 = 1

3BSE 021 945R401

Condition

Remarks

389

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

3.16.1.1 Control and ReducedControl

Presentation:

4
1

5
6

2
3
7

Behavior:
No

Description

Motor Status

Default Presentation

Condition

Remarks

IND2_07 = 0

Not Ready for Start


Error or interlocks prevent
the start

IND2_14 = 1 and
IND2_07 = 1

390

A-Interlock

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

1
cont.

MOTCONI, Motor Control

Condition

Remarks

IND1_12 = 1 or
IND1_15 = 1

Run
Direction Change

IND2_06 = 1

2.1

2.2

Bargraph

Limit Indication

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

Green

REAL_RES

Motor current value

REAL_RES_HILIM <= 0.1

Bargraph invisible

at 100%

3BSE 021 945R401

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

Grey

REAL_RES_HILIM <= 0.1

Limit Indication invisible

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

COERR Red flashing

AU_IND1_00 = 1

Communication unack.
error

TRIP Red flashing

AU_IND1_02 = 1

Tripped unack. error

ESTOP Red flashing

AU_IND1_03 = 1

Emergency stop unack.


error

COERR Red

IND1_00 = 1

Communication error

Act Pres Text

Error 1

Start Ready Auto. The


motor starts when the
process conditions are
satisfied

391

MOTCONI, Motor Control

No

Description

4
cont.
5

Direction Indication

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

TRIP Red

IND1_02 = 1

Tripped error

ESTOP Red

IND1_03 = 1

Emergency stop error

IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

MCERR Red flashing

AU_IND1_04 = 1

Main Contactor unack


error

MONL Red flashing

AU_IND1_05 = 1

Monitor low unack error

MONH Red flashing

AU_IND1_06 = 1

Monitor high unack error

MCERR Red

IND1_04 = 1

Main Contactor error

MONL Red

IND1_05 = 1

Monitor low error

MONH Red

IND1_06 = 1

Monitor high error

BOOLG = 1

MCC Status

Green

Green

Error 2

MCC Status

7.1

Warnings

Warnings Text

7.2

Alarms

Alarms Text

392

Acknowledge Warnings
and Alarms

Yellow flashing
Yellow

BOOLD = 1
IND1_07 = 1

Warnings Grey

BOOLG = 1

Yellow

BOOLD = 1 or
IND1_07 = 1

Red flashing
Red

BOOLE = 1
IND1_11 = 1

Alarms Grey

BOOLG = 1

Red

BOOLE = 1 or
IND1_11 = 1

Acknowledge

BOOLD = 1 or
BOOLE = 1 or
IND1_07 = 1 or
IND1_11 = 1

Acknowledge main object


and the Alarm and
Warning objects

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

3.16.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Override Interlock

Override Interlock Black

Block Alarm

Block Printout

3BSE 021 945R401

Condition

Remarks
IND2_00 Indicates current
status

Yellow

Blocked

Block pressed

MORD_06 = 1

Deblock pressed

MORD_07 = 1

Block Alarm Black

Yellow

Blocked

Block pressed

ALARM_BLK = 1

Deblock pressed

ALARM_BLK = 0

Block Printout Black

Yellow

Blocked

Block pressed

PRINT_BLK = 1

Deblock pressed

PRINT_BLK = 0

393

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

3.16.2 Displays
3.16.2.1 Object Display View 1

Presentation:
2

38, 39

37
6

8
9
10
11
12

3
4

13
14
15
16
17
18

36
35

19
20
21
22
23
24

34
29-33

25-27

28

Behavior
No

Description

Presentation

Condition

Remarks

SelectFrame

White

SELECTED = 1

Object select frame

Black

394

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Header

Presentation

MOTCONI, Motor Control

Condition

Remarks

NAME and DESCR

Object name and description

Red flashing

AU_IND = 1 OR
BOOLE = 1

Unacknowledged alarm

Red

IND1_DIST = 1 OR

Alarm

IND1_11 = 1
Yellow flashing

BOOLD = 1

Unacknowledged warning

Yellow

IND1_07 = 1

Warning

Green
3.1

3.2

5.1

5.2

Range Max

Range Min

Trim Curve

Bargraph

Limit Indication

Normal

Green

REALRES_MAX

REALRES_HILIM <= 0.1

Green

REALRES_MIN

REALRES_HILIM <= 0.1

Limit invisible

Green

REALRES

Motor current

REALRES_HILIM <= 0.1

Trim Curve invisible

Green

REALRES

Motor current

REALRES_HILIM <= 0.1

Bargraph invisible

at 100%

Limit invisible

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

REALRES_HILIM <= 0.1

Limit Indication invisible

Grey
6

ALARMS

6.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

6.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_00 = 1

Unacknowledged alarm

Red

IND1_00 = 1

Alarm

6.3

Warning Indication

3BSE 021 945R401

Alarms

395

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

6.4

Alarm 1 Text

Comm. Error

TXT_BLK_00 = 0

Monitoring of
Communication Error

Red

IND1_00 = 1 or AU_IND1_00
=1

Grey

8.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

8.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_02 = 1

Unacknowledged alarm

Red

IND1_02 = 1

Alarm

Local Stop

TXT_BLK_02 = 0

Monitoring of Local Stop

Red

IND1_02 = 1 or AU_IND1_02
=1

Grey

8.3

8.4

Warning Indication

Alarm 3 Text

10.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

10.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_04 = 1

Unacknowledged alarm

Red

IND1_04 = 1

Alarm

Main Contactor

TXT_BLK_04 = 0

Monitoring of Main Contactor

Red

IND1_04 = 1 or AU_IND1_04
=1

Grey

10.3

10.4

Warning Indication

Alarm 5 Text

11.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

11.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

396

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

11.3

Warning Indication

11.4

Alarm Text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Red flashing

AU_IND1_05 = 1

Unacknowledged alarm

Red

IND1_05 = 1

Alarm

Monitor Low

TXT_BLK_05 = 0

Monitoring of Monitor Low

Red

IND1_05 = 1 or AU_IND1_05
=1

Grey

12.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

12.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_06 = 1

Unacknowledged alarm

Red

IND1_06 = 1

Alarm

Monitor High

TXT_BLK_06 = 0

Monitoring of Monitor High

Red

IND1_06 = 1 or AU_IND1_06
=1

Grey

12.3

12.4

Warning Indication

Alarm Text

13

INTERLOCKS

13.1

IC1 Active

13.2

IC1 Text

14.1

IC2 Active

14.2

IC2 Text

C-Interlock 2 Grey

15.1

IB2 Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

15.2

IB2 Active

Yellow

IND2_13 = 1

Interlock IB2 active

15.3

IB2 Text

Green

IB2_TXT

Interlock text IB2

16.1

IB4 Block Indication

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

16.2

IB4 Active

Yellow

IND2_11 = 1

Interlock IB4 active

16.3

IB4 Text

IB4_TXT

Interlock IB4 text

3BSE 021 945R401

Interlocks
Yellow

IND2_08 = 1

C-Interlock 1 Grey
Yellow

Green

Safety Interlock IC1 active


Safety Interlock IC1

IND2_09 = 1

Safety Interlock IC2 active


Safety Interlock IC2

397

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

17.1

IB1 Blocked

BX Red

IND2_15 = 1 and

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock blocked

IND2_12 = 1

Interlock IB1 active


Interlock IB1 text

Yellow

Remarks

Override Interlock and


(IND2_00 = 1 or IND2_02 = 1) Interlock IB1 active

17.2

IB1 Active

17.3

IB1 Text

Green

IB1_TXT

18.1

IB3 Blocked

BX Red

IND2_15 = 1 and

BX Yellow

IND2_00 = 1 or IND2_02 = 1

Test mode. Interlock blocked

IND2_10 = 1

Interlock IB3 active

18.2

IB3 Active

18.3

IB3 Text

Green

IB3_TXT

Interlock IB3

19.1

IA Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock blocked

19.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

19.3

IA Text

IA_TXT

Interlock IA text

20

STATUS

20.1

Implemented Indication

20.2

Implemented Text

21.1

Repeat Fail Blocked


Indication

Yellow

21.2

Repeat Fail Blocked


Text

Repeat Fail Blk

22

MCC STATUS

22.1

Warnings

Warnings text

398

Yellow

Override Interlock and


(IND2_00 = 1 or IND2_02 = 1) Interlock IB3 active

Green

Status
Green

ACT = 1

Implemented Grey

Implemented
REPEAT_BLK = 1

The motor can be controlled


Repeat Fail Blocked

Yellow

REPEAT_BLK = 1

Grey

BOOLG = 1

MCC status

Yellow flashing

BOOLD = 1

Unack MCU warning

Yellow

IND1_07 = 1

MCU warning

Warnings Green

BOOLG = 1

Displaying warnings

Yellow

BOOLD = 1 or IND1_07 = 1

Warnings

Grey

BOOLG = 0

Whole Field Greyed

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

23.1

Alarms

23.2

24.1

Alarms text

Location text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Red flashing

BOOLE = 1

Unack MCU alarm

Red

IND1_11 = 1

MCU alarm

Alarms Green

BOOLG = 1

Displaying alarms

Red

BOOLE = 1 or IND1_11 = 1

Alarms

Grey

BOOLG = 0

Whole Field Greyed

MCC Location:

MCC Location

Grey
Green
25.1

MotorStatus Text

25.2

MotorStatus

X1-TEXT

Run Grey

Run
Not Ready for Start
IND2_07 = 0

Error or interlocks prevent


the start

IND2_14 = 1 and

A-Interlock

IND2_07 = 1

3BSE 021 945R401

IND1_12 = 1 or

Run

IND1_15 = 1

DirectionChange

IND2_06 = 1

Start Ready Auto. The motor


starts when the process
conditions are satisfied

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

399

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

26.1

Dir/Speed Text

Dir/Speed Grey

26.2

Direction Indication

27.1

Current Text

Condition

Remarks
Direction and speed

IND1_13 = 1

Forwards/High

IND1_14 = 1

Reverse/Low

Green

Current Grey

BOOLA = 1

Motor current

Power Grey

BOOLA = 0 and BOOLC = 1

Motor power (If MCU2)

27.2

Current Value

Green

REALRES

Motor current

27.3

Current Unit

% Green

% of normal current

28.1

Nom. Current Text

Nom.Current Grey

BOOLA = 1

Nominal current of motor

Nom.Power Grey

BOOLA = 0 and BOOLC = 1

nominal power of motor


(if MCU2)

28.2

Nom. Current Value

Green

REALRES_HILIM

28.3

Nom. Current Unit

Green

X2-TEXT

Unit for current or power

29.1

Sequence Indication

IND2_04 = 1

Sequence Controlled
from groupstart

29.2

Sequence Text

30.1

Central Indication

30.2

Central Text

400

Green
Sequence
Green

IND2_04 = 1

Grey

Green

IND2_01 = 0 and
Central Controlled
IND2_02 = 0 and
from operators place
IND2_03 = 0 and
IND2_04 = 0 and BOOLH = 0

Central
Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0 and BOOLH = 0

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

31.1

Local Indication

MOTCONI, Motor Control

Presentation

Condition

Remarks

Green

IND2_01 = 1

Local
Controlled from local panel

31.2

31.3

32.1

Local Text

Local Text

Local
Green

IND2_01 = 1

Grey

Local - MCC

MCU controlled by an other


LON station. (No Control
Access)

Yellow

BOOLH = 1

Grey

Test Indication

Yellow

IND2_02 = 1

Test
Jog running from motor
place

32.2

33.1

Test Text

Jog/Test
Yellow

IND2_02 = 1

Grey

Out of Service Indication

Kakhi

IND2_03 = 1

Out of service
No control possible

33.2

Out of Service Text

34.1

Blocking Interlock Text

34.2

Actual Interlock Text

35.1

Auto Indication

3BSE 021 945R401

Out of Service
Kakhi

IND2_03 = 1

Grey

Blocking
Interlock: Grey

Blocking Interlock text


ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode. Process


conditions control start/stop
of motor

Green

401

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

35.2

Auto Text

Auto

36.1

Man Indication

36.2

Man Text

Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Grey

Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Remarks

Manual mode. Startorder


affects the motor directly

Man Grey
Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Grey

37

TOGGLE

38

SECTION

38.1

Section Text

Section Grey

38.2

Section Value

Green

39

CLASS

39.1

Class Text

Class Grey

39.2

Class Value

Green

402

Condition

White/black

Toggle between Object


Display View 1 and View 2
If available from AC 400
series
Text in front of the value
PROC_SEC

Process section
If available from AC 400
series
Text in front of the value

CLASS

Object class

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

3.16.2.2 Object Display View 2

Presentation:

1
2
3
4

6
7
8
9

Behavior:
No

Description

Presentation

TOGGLE

White/black

DIAGNOSTICS

2.1

TOL Capacity text

Condition

Remarks
Toggle between MOTIOB01
and MOTIOB02

BOOLF = 1
BOOLF = 0

TOL Capacity

Diagnostics
Diagnostics field invisible
Thermal overload capacity

Grey
TOL Capacity value

3BSE 021 945R401

Green

REALE

Thermal overload capacity

403

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

2.2

TOL Capacity bargraph

Green

REALE

Thermal overload capacity

REALE <= 0.1

Bargraph invisible

Time TOL trip

BOOLB = 1

Time to thermal overload trip

BOOLB = 0

Time to thermal overload


reset

3.1

Time to TOL trip text

Grey
Time to TOL reset text

Time TOL reset


Grey

4.1

Time to TOL trip/reset


value in Seconds

Green

REALA

Time to thermal overload


trip/reset

Cosphi text

Cosphi

BOOLC = 1

Cosphi

Cosphi value

Green

REALC

Cosphi

BOOLF = 1
BOOLF = 0

Maintenance
Maintenance field invisible

MAINTENANCE

5.1

Contactor switch cycles


text

5.2

Contactor switch
cycles Grey

Contactor switch cycles Green


value

REALD

Contactor switch cycles

Contactor switch cycles Green


bargraph

REALD

Thermal overload capacity

REALD <= 0.1

Bargraph invisible

6.1

6.2

Run hours text

Run hours Grey

Run hours value

Green

REALB

Cumulated run hours

Run hours bargraph

Green

REALB

Cumulated run hours

REALB <= 0.1

Bargraph invisible

MCC STATUS

7.1

Warnings

Warnings text

7.2

404

Contactor switch cycles

Cumulated run hours

Info
Yellow flashing

BOOLD = 1

Unack MCU warning

Yellow

IND1_07 = 1

MCU warning

Warnings Green

BOOLG = 1

Displaying warnings

Yellow

BOOLD = 1 or IND1_07 = 1

Warnings

Grey

BOOLG = 0

Whole Field Greyed

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

8.1

Alarms

Alarms text

8.2
9

Location text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Red flashing

BOOLE = 1

Unack MCU alarm

Red

IND1_11 = 1

MCU alarm

Alarms Green

BOOLG = 1

Displaying alarms

Red

BOOLE = 1 or IND1_11 = 1

Alarms

Grey

BOOLG = 0

Whole Field Greyed

MCC Location:

MCC Location

Grey
Green

3BSE 021 945R401

X1-TEXT

405

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

3.16.2.3 Diagnostic Display

Presentation:
2
1

3-17

18-31

32-46

47-61

Remark: 12, 16, 23-31, 41, 52-61 not available for MCU1(BOOLC = 0)
Behavior:
No

Description

Presentation

Condition

Remarks

Frame

Black

No selection of frame
Remains on the main dialog.

Header

NAME and DESCR

Object name and description

406

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

MOTCONI, Motor Control

Condition

Remarks

WARNINGS
3.1

Thermal overload
warning

Yellow flashing

AU_IND1_00 = 1

Unacknowledged warning

3.2

Thermal overload
warning

Yellow

IND1_00 = 1

warning

3.3

Thermal overload text

AU_IND1_00 = 1 or
IND1_00 = 1

Thermal overload

Yellow

Thermal overload

IND1_00 = 0

Thermal overload

3.4

Thermal overload text

Thermal overload

Grey
4.1

Phase loss L1 warning

Yellow flashing

AU_IND1_01 = 1

Unacknowledged warning

4.2

Phase loss L1 warning

Yellow

IND1_01 = 1

warning

4.3

Phase loss L1 text

AU_IND1_01 = 1 or
IND1_01 = 1

Phase loss L1

Yellow

Phase loss L1

IND1_01 = 0

Phase loss L1

4.4

Phase loss L1 text

Phase loss L1

Grey
5.1

Phase loss L2 warning

Yellow flashing

AU_IND1_02 = 1

Unacknowledged warning

5.2

Phase loss L2 warning

Yellow

IND1_02 = 1

warning

5.3

Phase loss L2 text

AU_IND1_02 = 1 or
IND1_02 = 1

Phase loss L2

Yellow

Phase loss L2

IND1_02 = 0

Phase loss L2

5.4

Phase loss L2 text

Phase loss L2

Grey
6.1

Phase loss L3 warning

Yellow flashing

AU_IND1_03 = 1

Unacknowledged warning

6.2

Phase loss L3 warning

Yellow

IND1_03 = 1

warning

6.3

Phase loss L3 text

AU_IND1_03 = 1 or
IND1_03 = 1

Phase loss L3

Yellow

Phase loss L3

IND1_03 = 0

Phase loss L3

6.4

Phase loss L3 text

Phase loss L3

Grey
7.1

Underload warning

Yellow flashing

AU_IND1_04 = 1

Unacknowledged warning

7.2

Underload warning

Yellow

IND1_04 = 1

warning

7.3

Underload text

AU_IND1_04 = 1 or
IND1_04 = 1

Underload

Underload
Yellow

3BSE 021 945R401

407

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

7.4

Underload text

Underload

IND1_04 = 0

Underload

Grey
8.1

Noload warning

Yellow flashing

AU_IND1_05 = 1

Unacknowledged warning

8.2

Noload warning

Yellow

IND1_05 = 1

warning

8.3

Noload text

AU_IND1_05 = 1 or
IND1_05 = 1

Noload

Yellow

Noload

IND1_05 = 0

Noload

8.4

Noload text

Noload

Grey
9.1

Stall warning

Yellow flashing

AU_IND1_06 = 1

Unacknowledged warning

9.2

Stall warning

Yellow

IND1_06 = 1

warning

9.3

Stall text

AU_IND1_06 = 1 or
IND1_06 = 1

Stall

Yellow

Stall

IND1_06 = 0

Stall

9.4

Stall text

Stall

Grey
10.1

Feedback CFA warning

Yellow flashing

AU_IND1_07 = 1

Unacknowledged warning

10.2

Feedback CFA warning

Yellow

IND1_07 = 1

warning

10.3

Feedback CFA text

AU_IND1_07 = 1 or
IND1_07 = 1

Feedback CFA

Yellow

Feedback CFA

IND1_07 = 0

Feedback CFA

10.4

Feedback CFA text

Feedback CFA

Grey
11.1

Feedback CFB warning

Yellow flashing

AU_IND1_08 = 1

Unacknowledged warning

11.2

Feedback CFB warning

Yellow

IND1_08 = 1

warning

11.3

Feedback CFB text

AU_IND1_08 = 1 or
IND1_08 = 1

Feedback CFB

Yellow

Feedback CFB

IND1_08 = 0

Feedback CFB

11.4

Feedback CFB text

Feedback CFB

Grey
12.1

Feedback CFC warning

Yellow flashing

AU_IND1_09 = 1

Unacknowledged warning

12.2

Feedback CFC warning

Yellow

IND1_09 = 1

warning

12.3

Feedback CFC text

AU_IND1_09 = 1 or
IND1_09 = 1

Feedback CFC

Yellow

Feedback CFC

IND1_09 = 0

Feedback CFC

12.4

Feedback CFC text

Feedback CFC

Grey

408

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

13.1

Overload warning

13.2

Overload warning

13.3

Overload text

13.4

Overload text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Yellow flashing

AU_IND2_03 = 1

Unacknowledged warning

Yellow

IND2_03 = 1

warning

AU_IND2_03 = 1 or
IND2_03 = 1

Overload

Yellow

Overload

IND2_03 = 0

Overload

Overload

Grey
14.1

Maintenance A warning

Yellow flashing

AU_IND2_04 = 1

Unacknowledged warning

14.2

Maintenance A warning

Yellow

IND2_04 = 1

warning

14.3

Maintenance A text

AU_IND2_04 = 1 or
IND2_04 = 1

Maintenance A

Yellow

Maintenance A

IND2_04 = 0

Maintenance A

14.4

Maintenance A text

Maintenance A

Grey
15.1

Maintenance B warning

Yellow flashing

AU_IND2_05 = 1

Unacknowledged warning

15.2

Maintenance B warning

Yellow

IND2_05 = 1

warning

15.3

Maintenance B text

AU_IND2_05 = 1 or
IND2_05 = 1

Maintenance B

Yellow

Maintenance B

IND2_05 = 0

Maintenance B

15.4

Maintenance B text

Maintenance B

Grey
16.1

Maintenance C warning

Yellow flashing

AU_IND2_06 = 1

Unacknowledged warning

16.2

Maintenance C warning

Yellow

IND2_06 = 1

warning

16.3

Maintenance C text

AU_IND2_06 = 1 or
IND2_06 = 1

Maintenance C

Yellow

Maintenance C

IND2_06 = 0

Maintenance C

16.4

Maintenance C text

Maintenance C

Grey
17.1

Maintenance motor
warning

Yellow flashing

AU_IND2_07 = 1

Unacknowledged warning

17.2

Maintenance motor
warning

Yellow

IND2_07 = 1

warning

17.3

Maintenance motor text

AU_IND2_07 = 1 or
IND2_07 = 1

Maintenance motor

Yellow

Maintenance motor

IND2_07 = 0

Maintenance motor

17.4

Maintenance motor text

Maintenance motor

Grey

3BSE 021 945R401

409

MOTCONI, Motor Control

No

Description

18.1

Fail-safe activated
warning

18.2

Fail-safe activated
warning

18.3

Fail-safe activated text

18.4

Fail-safe activated text

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Yellow flashing

AU_IND2_08 = 1

Unacknowledged warning

Yellow

IND2_08 = 1

warning

AU_IND2_08 = 1 or
IND2_08 = 1

Fail-safe activated

Yellow

Failsafe activated

IND2_08 = 0

Fail-safe activated

Failsafe activated

Grey
19.1

Ext. ROM not present


warning

Yellow flashing

AU_IND2_09 = 1

Unacknowledged warning

19.2

Ext. ROM not present


warning

Yellow

IND2_09 = 1

warning

19.3

Ext. ROM not present


text

Ext. ROM not


present Yellow

AU_IND2_09 = 1 or
IND2_09 = 1

External Memory not present

19.4

Ext. ROM not present


text

Ext. ROM not


present Gray

IND2_09 = 0

External Memory not present

20.1

Ext. ROM write fail


warning

Yellow flashing

AU_IND2_10 = 1

Unacknowledged warning

20.2

Ext. ROM write fail


warning

Yellow

IND2_10 = 1

warning

20.3

Ext. ROM write fail text

AU_IND2_10 = 1 or
IND2_10 = 1

External Memory write fail

Yellow

Ext. ROM write fail

IND2_10 = 0

External Memory write fail

20.4

Ext. ROM write fail text

Ext. ROM write fail

Gray
21.1

Ext. ROM read fail


warning

Yellow flashing

AU_IND2_11 = 1

Unacknowledged warning

21.2

Ext. ROM read fail


warning

Yellow

IND2_11 = 1

warning

21.3

Ext. ROM read fail text

AU_IND2_11 = 1 or
IND2_11 = 1

External Memory read fail

Yellow

Ext. ROM read fail

IND2_11 = 0

External Memory read fail

21.4

Ext. ROM read fail text

Ext. ROM read fail

Gray

410

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

22.1

Drawer location
warning

22.2

Drawer location
warning

22.3

Drawer location text

22.4

Drawer location text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Yellow flashing

AU_IND2_12 = 1

Unacknowledged warning

Yellow

IND2_12 = 1

warning

AU_IND2_12 = 1 or
IND2_12 = 1

Drawer location

Yellow

Drawer location

IND2_12 = 0

Drawer location

Drawer location

Grey
23.1

Earth fault warning

Yellow flashing

AU_IND1_10 = 1

Unacknowledged warning

23.2

Earth fault warning

Yellow

IND1_10 = 1

warning

23.3

Earth fault text

AU_IND1_10 = 1 or
IND1_10 = 1

Earth fault

Yellow

Earth fault

IND1_10 = 0

Earth fault

23.4

Earth fault text

Earth fault

Grey
24.1

Unbalance warning

Yellow flashing

AU_IND1_11 = 1

Unacknowledged warning

24.2

Unbalance warning

Yellow

IND1_11 = 1

warning

24.3

Unbalance text

AU_IND1_11 = 1 or
IND1_11 = 1

Unbalance

Yellow

Unbalance

IND1_11 = 0

Unbalance

24.4

Unbalance text

Unbalance

Grey
25.1

Cosphi warning

Yellow flashing

AU_IND1_12 = 1

Unacknowledged warning

25.2

Cosphi warning

Yellow

IND1_12 = 1

warning

25.3

Cosphi text

AU_IND1_12 = 1 or
IND1_12 = 1

Cosphi

Yellow

Cosphi

IND1_12 = 0

Cosphi

25.4

Cosphi text

Cosphi

Grey
26.1

Rotation warning

Yellow flashing

AU_IND1_13 = 1

Unacknowledged warning

26.2

Rotation warning

Yellow

IND1_13 = 1

warning

26.3

Rotation text

AU_IND1_13 = 1 or
IND1_13 = 1

Rotation

Yellow

Rotation

IND1_13 = 0

Rotation

26.4

Rotation text

Rotation

Grey

3BSE 021 945R401

411

MOTCONI, Motor Control

No

Description

27.1

PTC temperature
warning

27.2

PTC temperature
warning

27.3

PTC temperature text

27.4

PTC temperature text

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Yellow flashing

AU_IND1_14 = 1

Unacknowledged warning

Yellow

IND1_14 = 1

warning

AU_IND1_14 = 1 or
IND1_14 = 1

PTC temperature

Yellow

PTC temperature

IND1_14 = 0

PTC temperature

PTC temperature

Grey
28.1

Undervoltage warning

Yellow flashing

AU_IND1_15 = 1

Unacknowledged warning

28.2

Undervoltage warning

Yellow

IND1_15 = 1

warning

28.3

Undervoltage text

AU_IND1_15 = 1 or
IND1_15 = 1

Undervoltage

Yellow

Undervoltage

IND1_15 = 0

Undervoltage

28.4

Undervoltage text

Undervoltage

Grey
29.1

Start limitation warning

Yellow flashing

AU_IND2_00 = 1

Unacknowledged warning

29.2

Start limitation warning

Yellow

IND2_00 = 1

warning

29.3

Start limitation text

AU_IND2_00 = 1 or
IND2_00 = 1

Start limitation

Yellow

Start limitation

IND2_00 = 0

Start limitation

29.4

Start limitation text

Start limitation

Grey
30.1

Auto reclosure warning

Yellow flashing

AU_IND2_01 = 1

Unacknowledged warning

30.2

Auto reclosure warning

Yellow

IND2_01 = 1

warning

30.3

Auto reclosure text

AU_IND2_01 = 1 or
IND2_01 = 1

Auto reclosure

Yellow

Auto reclosure

IND2_01 = 0

Auto reclosure

30.4

Auto reclosure text

Auto reclosure

Grey
31.1

MCU temperature
warning

Yellow flashing

AU_IND2_02 = 1

Unacknowledged warning

31.2

MCU temperature
warning

Yellow

IND2_02 = 1

warning

31.3

MCU temperature text

AU_IND2_02 = 1 or
IND2_02 = 1

MCU temperature

MCU temperature
Yellow

412

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

No

Description

Presentation

Condition

Remarks

31.4

MCU temperature text

MCU temperature

IND2_02 = 0

MCU temperature

Grey
ALARMS
32.1

Thermal overload alarm

Red flashing

AU_IND1_00 = 1

Unacknowledged alarm

32.2

Thermal overload alarm

Red

IND1_00 = 1

alarm

32.3

Thermal overload text

AU_IND1_00 = 1 or
IND1_00 = 1

Thermal overload

Red

Thermal overload

IND1_00 = 0

Thermal overload

32.4

Thermal overload text

Thermal overload

Grey
33.1

Phase loss L1 alarm

Red flashing

AU_IND1_01 = 1

Unacknowledged alarm

33.2

Phase loss L1 alarm

Red

IND1_01 = 1

alarm

33.3

Phase loss L1 text

AU_IND1_01 = 1 or
IND1_01 = 1

Phase loss L1

Red

Phase loss L1

IND1_01 = 0

Phase loss L1

33.4

Phase loss L1 text

Phase loss L1

Grey
34.1

Phase loss L2 alarm

Red flashing

AU_IND1_02 = 1

Unacknowledged alarm

34.2

Phase loss L2 alarm

Red

IND1_02 = 1

alarm

34.3

Phase loss L2 text

AU_IND1_02 = 1 or
IND1_02 = 1

Phase loss L2

Red

Phase loss L2

IND1_02 = 0

Phase loss L2

34.4

Phase loss L2 text

Phase loss L2

Grey
35.1

Phase loss L3 alarm

Red flashing

AU_IND1_03 = 1

Unacknowledged alarm

35.2

Phase loss L3 alarm

Red

IND1_03 = 1

alarm

35.3

Phase loss L3 text

AU_IND1_03 = 1 or
IND1_03 = 1

Phase loss L3

Red

Phase loss L3

IND1_03 = 0

Phase loss L3

35.4

Phase loss L3 text

Phase loss L3

Grey
36.1

Underload alarm

Red flashing

AU_IND1_04 = 1

Unacknowledged alarm

36.2

Underload alarm

Red

IND1_04 = 1

alarm

36.3

Underload text

AU_IND1_04 = 1 or
IND1_04 = 1

Underload

Underload
Red

3BSE 021 945R401

413

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

36.4

Underload text

Underload

IND1_04 = 0

Underload

Grey
37.1

Noload alarm

Red flashing

AU_IND1_05 = 1

Unacknowledged alarm

37.2

Noload alarm

Red

IND1_05 = 1

alarm

37.3

Noload text

AU_IND1_05 = 1 or
IND1_05 = 1

Noload

Red

Noload

IND1_05 = 0

Noload

37.4

Noload text

Noload

Grey
38.1

Stall alarm

Red flashing

AU_IND1_06 = 1

Unacknowledged alarm

38.2

Stall alarm

Red

IND1_06 = 1

alarm

38.3

Stall text

AU_IND1_06 = 1 or
IND1_06 = 1

Stall

Red

Stall

IND1_06 = 0

Stall

38.4

Stall text

Stall

Grey
39.1

Feedback CFA alarm

Red flashing

AU_IND1_07 = 1

Unacknowledged alarm

39.2

Feedback CFA alarm

Red

IND1_07 = 1

alarm

39.3

Feedback CFA text

AU_IND1_07 = 1 or
IND1_07 = 1

Feedback CFA

Red

Feedback CFA

IND1_07 = 0

Feedback CFA

39.4

Feedback CFA text

Feedback CFA

Grey
40.1

Feedback CFB alarm

Red flashing

AU_IND1_08 = 1

Unacknowledged alarm

40.2

Feedback CFB alarm

Red

IND1_08 = 1

alarm

40.3

Feedback CFB text

AU_IND1_08 = 1 or
IND1_08 = 1

Feedback CFB

Red

Feedback CFB

IND1_08 = 0

Feedback CFB

40.4

Feedback CFB text

Feedback CFB

Grey
41.1

Feedback CFC alarm

Red flashing

AU_IND1_09 = 1

Unacknowledged alarm

41.2

Feedback CFC alarm

Red

IND1_09 = 1

alarm

41.3

Feedback CFC text

AU_IND1_09 = 1 or
IND1_09 = 1

Feedback CFC

Red

Feedback CFC

IND1_09 = 0

Feedback CFC

41.4

Feedback CFC text

Feedback CFC

Grey

414

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

42.1

Parameter failure alarm

42.2

Parameter failure alarm

42.3

Parameter failure text

42.4

Parameter failure text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Red flashing

AU_IND2_04 = 1

Unacknowledged alarm

Red

IND2_04 = 1

alarm

AU_IND2_04 = 1 or
IND2_04 = 1

Parametering failure

Red

Parametering failure

IND2_04 = 0

Parametering failure

Parametering failure

Grey
43.1

External trip alarm

Red flashing

AU_IND3_05 = 1

Unacknowledged alarm

43.2

External trip alarm

Red

IND3_05 = 1

alarm

43.3

External trip text

AU_IND2_05 = 1 or
IND2_05 = 1

External trip

Red

External trip

IND2_05 = 0

External trip

43.4

External trip text

External trip

Grey
44.1

Testmode failure trip


alarm

Red flashing

AU_IND2_06 = 1

Unacknowledged alarm

44.2

Testmode failure trip


alarm

Red

IND2_06 = 1

alarm

44.3

Testmode failure trip


text

Testmode failure trip

AU_IND2_06 = 1 or
IND2_06 = 1

Testmode failure trip

Red

Testmode failure trip


text

Testmode failure trip

IND2_06 = 0

Testmode failure trip

44.4

Grey

45.1

EM-stop alarm

Red flashing

AU_IND2_07 = 1

Unacknowledged alarm

45.2

EM-stop alarm

Red

IND2_07 = 1

alarm

45.3

EM-stop text

AU_IND2_07 = 1 or
IND2_07 = 1

EM-stop

Red

EM-stop

IND2_07 = 0

EM-stop

45.4

EM-stop text

EM-stop

Grey
46.1

Internal fault alarm

Red flashing

AU_IND2_08 = 1

Unacknowledged alarm

46.2

Internal fault alarm

Red

IND2_08 = 1

alarm

46.3

Internal fault text

AU_IND2_08 = 1 or
IND2_08 = 1

Internal fault

Red

Internal fault

IND2_08 = 0

Internal fault

46.4

Internal fault text

Internal fault

Grey

3BSE 021 945R401

415

MOTCONI, Motor Control

No

Description

47.1

External fault alarm

47.2

External fault alarm

47.3

External fault text

47.4

External fault text

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Red flashing

AU_IND2_09 = 1

Unacknowledged alarm

Red

IND2_09 = 1

alarm

AU_IND2_09 = 1 or
IND2_09 = 1

External fault

Red

External trip cmd

IND2_09 = 0

External fault

External trip cmd

Grey
48.1

Main switch OFF alarm

Red flashing

AU_IND2_10 = 1

Unacknowledged alarm

48.2

Main switch OFF alarm

Red

IND2_10 = 1

alarm

48.3

Main switch OFF text

AU_IND2_10 = 1 or
IND2_10 = 1

Main switch OFF

Red

Main Switch OFF

IND2_10 = 0

Main switch OFF

48.4

Main switch OFF text

Main Switch OFF

Grey
49.1

Startup inhibit alarm

Red flashing

AU_IND2_11 = 1

Unacknowledged alarm

49.2

Startup inhibit alarm

Red

IND2_11 = 1

alarm

49.3

Startup inhibit text

Startup inhibit Red

AU_IND2_11 = 1 or
IND2_11 = 1

Startup inhibit

49.4

Startup inhibit text

Startup inhibit Grey

IND2_11 = 0

Startup inhibit

50.1

MCB trip alarm

Red flashing

AU_IND2_12 = 1

Unacknowledged alarm

50.2

MCB trip alarm

Red

IND2_12 = 1

alarm

50.3

MCB trip text

MCB trip Red

AU_IND2_12 = 1 or
IND2_12 = 1

MCB trip

50.4

MCB trip text

MCB trip Grey

IND2_12 = 0

MCB trip

51.1

Motor still running


alarm

Red flashing

AU_IND2_13 = 1

Unacknowledged alarm

51.2

Motor still running


alarm

Red

IND2_13 = 1

alarm

51.3

Motor still running text

AU_IND2_13 = 1 or
IND2_13 = 1

Motor still running

Red

Motor still running

IND2_13 = 0

Motor still running

51.4

Motor still running text

Motor still running

Grey

416

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

52.1

Earth fault alarm

52.2

Earth fault alarm

52.3

Earth fault text

52.4

Earth fault text

Presentation

MOTCONI, Motor Control

Condition

Remarks

Red flashing

AU_IND1_10 = 1

Unacknowledged alarm

Red

IND1_10 = 1

alarm

AU_IND1_10 = 1 or
IND1_10 = 1

Earth fault

Red

Earth fault

IND1_10 = 0

Earth fault

Earth fault

Grey
53.1

Unbalance alarm

Red flashing

AU_IND1_11 = 1

Unacknowledged alarm

53.2

Unbalance alarm

Red

IND1_11 = 1

alarm

53.3

Unbalance text

AU_IND1_11 = 1 or
IND1_11 = 1

Unbalance

Red

Unbalance

IND1_11 = 0

Unbalance

53.4

Unbalance text

Unbalance

Grey
54.1

Cosphi alarm

Red flashing

AU_IND1_12 = 1

Unacknowledged alarm

54.2

Cosphi alarm

Red

IND1_12 = 1

alarm

54.3

Cosphi text

AU_IND1_12 = 1 or
IND1_12 = 1

Cosphi

Red

Cosphi

IND1_12 = 0

Cosphi

54.4

Cosphi text

Cosphi

Grey
55.1

Rotation alarm

Red flashing

AU_IND1_13 = 1

Unacknowledged alarm

55.2

Rotation alarm

Red

IND1_13 = 1

alarm

55.3

Rotation text

AU_IND1_13 = 1 or
IND1_13 = 1

Rotation

Red

Rotation

IND1_13 = 0

Rotation

55.4

Rotation text

Rotation

Grey
56.1

PTC temperature alarm

Red flashing

AU_IND1_14 = 1

Unacknowledged alarm

56.2

PTC temperature alarm

Red

IND1_14 = 1

alarm

56.3

PTC temperature text

AU_IND1_14 = 1 or
IND1_14 = 1

PTC temperature

Red

PTC temperature

IND1_14 = 0

PTC temperature

56.4

PTC temperature text

PTC temperature

Grey

3BSE 021 945R401

417

MOTCONI, Motor Control

No

Description

57.1

Undervoltage alarm

57.2

Undervoltage alarm

57.3

Undervoltage text

57.4

Undervoltage text

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

Red flashing

AU_IND1_15 = 1

Unacknowledged alarm

Red

IND1_15 = 1

alarm

AU_IND1_15 = 1 or
IND1_15 = 1

Undervoltage

Red

Undervoltage

IND1_15 = 0

Undervoltage

Undervoltage

Grey
58.1

Start limitation alarm

Red flashing

AU_IND2_00 = 1

Unacknowledged alarm

58.2

Start limitation alarm

Red

IND2_00 = 1

alarm

58.3

Start limitation text

AU_IND2_00 = 1 or
IND2_00 = 1

Start limitation

Red

Start limitation

IND2_00 = 0

Start limitation

58.4

Start limitation text

Start limitation

Grey
59.1

PTC short circuit alarm

Red flashing

AU_IND2_01 = 1

Unacknowledged alarm

59.2

PTC short circuit alarm

Red

IND2_01 = 1

alarm

59.3

PTC short circuit text

AU_IND2_01 = 1 or
IND2_01 = 1

PTC short circuit

Red

PTC short circuit

IND2_01 = 0

PTC short circuit

59.4

PTC short circuit text

PTC short circuit

Grey
60.1

PTC open circuit alarm

Red flashing

AU_IND2_02 = 1

Unacknowledged alarm

60.2

PTC open circuit alarm

Red

IND2_02 = 1

alarm

60.3

PTC open circuit text

AU_IND2_02 = 1 or
IND2_02 = 1

PTC open circuit

Red

PTC open circuit

IND2_02 = 0

PTC open circuit

60.4

PTC open circuit text

PTC open circuit

Grey
61.1

Torque trip alarm

Red flashing

AU_IND2_03 = 1

Unacknowledged alarm

61.2

Torque trip alarm

Red

IND2_03 = 1

alarm

61.3

Torque trip text

AU_IND2_03 = 1 or
IND2_03 = 1

Torque trip

Red

Torque trip

IND2_03 = 0

Torque trip

61.4

Torque trip text

Torque trip

Grey

418

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

3.16.3 Graphic Element


3.16.3.1 BargraphMC01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Limit Indication

at 100%

3BSE 021 945R401

Filled Yellow

AL_BLK = 1 and IND1_10


=1

Alarm blocked

Unfilled Yellow

AL_BLK = 1

Alarm blocked

419

MOTCONI, Motor Control

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Filled Red flashing

AU_IND = 1 and IND1_10


=1

Unacknowledged alarm

Unfilled Red flashing

AU_IND = 1

Unacknowledged alarm

Filled Light Red

IND1_10 = 1

High motor current

Grey

Limit

Bargraph

REALRES
Red flashing

AU_IND = 1 or BOOLE = 1 Unacknowledged alarm

Red

IND1_DIST = 1 or
IND1_11 = 1

Error

Yellow flashing

BOOLD = 1

Unacknowledge warning

Yellow

IND1_07 = 1

Warning

Green

NormalColor

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

3, (1..4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

Orientation

420

Vertical, Horizontal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

3.16.3.2 Motor01

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Mode or
Control point

3BSE 021 945R401

ModeIndVis = true

You can configure your


own text instead of using
the figures

* Yellow

IND2_02 = 1 and IND2_03


=0

Test

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

421

MOTCONI, Motor Control

No

Description

2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0 and
IND2_14 = 0 and
IND2_07 = 1

Indicates Auto Start


Init Not Performed

M Green

ManModeIndVis = true and Manual mode


IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0
ManModeIndVis = false

S Green

IND2_04 = 1

Sequence Control

L Green

IND2_01 = 1

Local Control

LM Yellow

BOOLH = 1

Local - MCC

C Green

IND2_01 = 0 and
IND2_04 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Central Control

ModeIndVis = false

Mode or Control point is


invisible

Direction Indication

DirectionVisible = true
Green
IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

DirectionVisible = false

Direction is invisible

Green

422

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Motor Status

Default Presentation

Shape

MOTCONI, Motor Control

Condition

Remarks

IND2_07 = 0

Not Ready for Start


Error or interlocks prevent
the start

IND2_14 = 1 and

A-Interlock

IND2_07 = 1

Color

IND1_12 = 1 or

Run

IND1_15 = 1

Direction Change

IND2_06 = 1

Start Ready Auto. The


motor starts when the
process conditions are
satisfied

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Error

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

The conditions are in priority order. Underlined parameters are configurable.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ModeIndVis

2. Mode or Control point

True, False

ManModeIndVis

2. Mode or Control point

True, False

DirectionVisible

3. Direction Indication

True, False

3BSE 021 945R401

423

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

3.16.3.3 ObjectLine01

Presentation:
1

10

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

424

Header

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1 or BOOLE = 1 Unacknowledged alarm

Red

IND1_DIST = 1 or
IND1_11 = 1

Alarm

Yellow flashing

BOOLD = 1

Acknowledge warning

Yellow

IND1_07 = 1

Warning

Green

Normal

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Motor Status

Default Presentation

MOTCONI, Motor Control

Condition

Not Ready for Start


IND2_07 = 0

Error or interlocks prevent

IND2_14 = 1 and
IND2_07 = 1

A-Interlock

IND1_12 = 1 or
IND1_15 = 1

Direction Indication

Remarks

Run
Direction Change

IND2_06 = 1

Start Ready Auto. The


motor starts when the
process conditions are
satisfied

IND1_12 = 0

Motor ready to start

Grey

IND2_03 = 1

Out of service

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

Green
IND1_13 = 1

Forward/High

IND1_14 = 1

Reverse/Low

Green

Status Indication

5.1

Mode

3BSE 021 945R401

Status Indication

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0

Indicates Auto Start


Init Not Performed

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

425

MOTCONI, Motor Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

5.2

Point Of Control

O Yellow

IND2_03 = 1

Out of Service

T Yellow

IND2_02 = 1

Test

LM Yellow

BOOLH = 1

Local - MCC

L Green

IND2_01 = 1

Local

S Green

IND2_04 = 1

Sequence

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central

X Green

Safety interlock or
IND2_08 = 1 or
IND2_09 = 1 or
Operator interlock
IND2_13 = 1 or
(IND2_11 = 1 and IND1_12
= 0) or
(IND2_00 = 0 and
(IND2_12 = 1 or
(IND2_10 = 1 and
IND1_12 = 0)))

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

5.3

Interlock Indication

5.4

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

5.5

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

W Yellow

IND1_07 or BOOLD

Collective Warning
indication

F Red

IND1_11 or BOOLE or
IND1_08

Collective Fault Indication

5.6

426

Warnings or Alarms

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

MOTCONI, Motor Control

No

Description

Default Presentation

Condition

Remarks

Bargraph

Green

REAL_RES

Motor current value

REAL_RES_HILIM <= 0.1

Bargraph invisible

Limit Indication

Error 1

Error 2

3BSE 021 945R401

at 100%

Limit Indication

Yellow

AL_BLK = 1

Alarm blocked by operator

Red

IND1_10 = 1

High motor current

Grey

REAL_RES_HILIM <= 0.1

Limit Indication invisible

COERR Red flashing

AU_IND1_00 = 1

Communication unack. error

TRIP Red flashing

AU_IND1_02 = 1

Tripped unack. error

ESTOP Red flashing

AU_IND1_03 = 1

Emergency stop unack.


error

COERR Red

IND1_00 = 1

Communication error

TRIP Red

IND1_02 = 1

Tripped error

ESTOP Red

IND1_03 = 1

Emergency stop error

MCERR Red flashing

AU_IND1_04 = 1

Main Contactor unack error

MONL Red flashing

AU_IND1_05 = 1

Monitor low unack error

MONH Red flashing

AU_IND1_06 = 1

Monitor high unack error

MCERR Red

IND1_04 = 1

Main Contactor error

MONL Red

IND1_05 = 1

Monitor low error

MONH Red

IND1_06 = 1

Monitor high error

427

MOTCONI, Motor Control

No

Description

10

Act Pres Text

428

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

3.17 PIDCONA, Adaptive PID Ctrl


3.17.1 Faceplate
Presentation:

3BSE 021 945R401

429

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

430

Default Presentation

Condition

Remarks

BaLo Dark green

LOCAL = 1

Bal Local mode

Bal Dark green

BAL = 1

Bal mode

MCp Dark green

CLAMP = 1

Man Clamped mode

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Default Presentation

Condition

Remarks

3.1
cont.

Mode

MFd Dark green

MANFD = 1

Man Forced mode

M AT Dark green

MAN = 1 and
ATENBL = 1

Man mode and Autotuning

M Dark green

MAN = 1

Man mode

A AT Dark green

AUTO = 1 and
ATENBL = 1

Auto mode and Autotuning

A Ad Dark green

AUTO = 1 and
ADAPON = 1

Auto mode and Adaptation

A Dark green

AUTO = 1

Auto mode

E1 AT Dark green

E1 = 1 and
ATENBL = 1

E1 mode and Autotuning

E1 Ad Dark green

E1 = 1 and
ADAPON = 1

E1 mode and Adaptation

E1 Dark green

E1 = 1

E1 mode

E2 AT Dark green

E2 = 1 and
ATENBL = 1

E2 mode and Autotuning

E2 Ad Dark green

E2 = 1 and
ADAPON = 1

E2 mode and Adaptation

E2 Dark green

E2 = 1

E2 mode

E3 AT Dark green

E3 = 1 and
ATENBL = 1

E3 mode and Autotuning

E3 Dark green

E3 = 1

E3 mode

3.2

Print Blk

P Yellow

PRINT_F1_BLK = 1 or
PRINT_F2_BLK = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

3BSE 021 945R401

431

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Incr

Increase output
with 0,5 unit

MAN = 1

Increase setpoint
with 0,5 unit

AUTO = 1

Decrease output
with 0,5 unit

MAN = 1

Decrease setpoint
with 0,5 unit

AUTO = 1

Decr

432

Remarks

Man

Set to Man Mode

Set MMI_MAN = 1

Auto

Set to Auto Mode

Set MMI_AUTO = 1

MFd

Set to Man Force Mode

Set MANFD = 1

E1

Set to E1 Mode

Set MMI_E1 = 1

E2

Set to E2 Mode

Set MMI_E2 = 1

E3

Set to E3 Mode

Set MMI_E3 = 1

sTun.

Start Autotuning

Set START_TUNE = 1

cTun.

Continue Autotuning

Set CONT-TUNE = 1

Verif.

Try to Verify Setting

Set VERIFY_REQUEST = 1

A&S

Accept Autotuning and


Save present parameters

Set SAVE_REQUEST = 1

S&R

Store Autotuning and


Restore present

Set RESTORE_REQUEST = 1

Retr.

Retrieve Aborted Setting

Set RETRIEVE = 1

Save

Save present parameters

Set SAVE_REQUEST = 1

Rest.

Restore present
parameters

Set RESTORE_REQUEST = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

3.17.1.1 Control and ReducedControl

Presentation:
3

7
8
9
10

5
6

7
8

3BSE 021 945R401

9
10

433

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

MV Range Max

Black

MAX

Range Max of the MV and


SP value

1.2

MV Range Min

Black

MIN

Range Min of the MV and


SP value

2.1

OUT Range Max

Black

OUTMAX

Range Max of OUT and


ACT value

2.2

OUT Range Min

Black

OUTMIN

Range Min of OUT and


ACT value

3.1

Direction

Incr Black

REVACT = 1

Increase of measured
value

Decr Black

REVACT = 0

Decrease of measured
value

MV

Measured Value

3.2

3.3

3.4

434

Measured Value
Bargraph

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3.4
cont.

3.5

3.6

Default Presentation

Condition

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

SP Value Bargraph

4.2

High SP Limit

3BSE 021 945R401

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

4.1

PIDCONA, Adaptive PID Ctrl

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Cyan

SETP

Setpoint value

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

435

PIDCONA, Adaptive PID Ctrl

No

Description

4.3

Low SP Limit

5.1

5.2

Opening or Closing

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

SETPL

Lower setpoint limit

Yellow

SP=LL = 1

Limitation line and mesh

Grey

Op Black

ACT_DIR = OPENING

Actuator position opening

Cl Black

ACT_DIR = CLOSING

Actuator position closing

OUT

Output value

OUT Value Bargraph


Magenta

5.3

5.4

HIgh OUT Limit

OUTPH

Upper limit output

OUTPH > OUTMAX or


(EOHL > OUTMAX and
EOLIM = 1)

Invisible

Yellow

OUT=HL = 1

Limitation line and mesh

Grey

Low OUT Limit

OUTPL

Lower limit output

OUTPL < OUTMIN or


(EOLL < OUTMIN and
EOLIM = 1)

Invisible

Yellow

OUT=LL = 1

Limitation line and mesh

Grey

ACT Value Bargraph

ACTPOS
Blue

Actuator value

SHOW_ACT = 1

7.1

MV Text

MV Black

7.2

MV Value

X X X Red

MV is Bad

No contact with controller

? ? ? Red

AI_ERR = 1

Signal error

MV

Measured value

Black
7.3

MV Unit

UNIT

Black

436

Text in front of the value

Measured unit

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

8.1

SP Text

SP Black

8.2

SP Value

SP Unit

OUT Text

9.2

OUT Value

Remarks
Text in front of the value
Setpoint value

UNIT

Black
9.1

Condition

SETP
Black

8.3

PIDCONA, Adaptive PID Ctrl

Setpoint unit

OUT Black

Text in front of the value


OUT

Black

Output value

9.3

OUT Unit

Black

OUTUNIT

Output unit

9.4

External OUT Limitation


Indication

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

OUT limited by external


limitation

10.1

ACT Text

ACT Black

SHOW_ACT = 1

Text in front of the value

10.2

ACT Value

ACTPOS

Actuator value

Black
10.3

ACT Unit

Black

SHOW_ACT = 1
OUTUNIT

Actuator unit

SHOW_ACT = 1

3BSE 021 945R401

437

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

3.17.1.2 Limits

Presentation:

1
2
3
4
5
6

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

L2

DEV H

DEV L

MVL2

DEVH

DEV L Black
Black

438

MVL1

DEV H Black
Black

MVH1

L2 Black
Black

MVH2

L1 Black
Black

Remarks

H1 Black
Black

Condition

DEVL

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

Presentation:

1
2

3
4

Behavior:
No

Description

Default Presentation

SP H

SP H Black
Black

SP L

OUT H

OUT L

SPL

OUTPH

OUT L Black
Black

3BSE 021 945R401

SPH

OUT H Black
Black

Remarks

SP L Black
Black

Condition

OUTPL

439

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

3.17.1.3 Block

Presentation:

1
2

3
4

Behavior:
No

Description

Default Presentation

Block Alarm 1

Block Alarm L1/H1 Black

440

Block Alarm 2

Block Printout 1

Condition

Yellow

Blocked

Block pressed

AL_F1_BLK = 1

Deblock pressed

AL_F1_BLK = 0

Remarks

Block Alarm L2/H2 Black

Yellow

Blocked

Block pressed

AL_F2_BLK = 1

Deblock pressed

AL_F2_BLK= 0

Block Printout L1/H1


Black

Yellow

Blocked

Block pressed

PRINT_F1_BLK = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3
cont.
4

Block Printout 2

PIDCONA, Adaptive PID Ctrl

Default Presentation

Condition

Deblock pressed

PRINT_F1_BLK = 0

Remarks

Block Printout L2/H2


Black

Yellow

Blocked

Block pressed

PRINT_F2_BLK = 1

Deblock pressed

PRINT_F2_BLK = 0

3.17.1.4 Parameters

Presentation:

1
2
3
4
5
6
7

Behavior:
No

Description

Default Presentation

Adaptation Enable

Adaptation Enable Black

2.1

Gain

3BSE 021 945R401

Condition

Yellow

Blocked

Enable pressed

ADAPENBL = 1

Off pressed

ADAPENBL = 0

Gain Black

Remarks

Gain

441

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

2.2

Value

Black

GAIN

3.1

TI

TI Black

3.2

Value

Black

3.3

Unit

s Black

4.1

TD

TD Black

4.2

Value

Black

4.3

Unit

s Black

5.1

BETA

BETA Black

5.2

Value

Black

6.1

TS

TS Black

6.2

Value

Black

6.3

Unit

s Black

7.1

DZ

DZ Black

7.2

Value

Black

DZ, CTRL = ON - OFF

7.3

Unit

% Black

DZ, CTRL = ON - OFF

442

Remarks

Integration time
TI

Derivation time
TD

Setpoint factor BETA


BETA
Sampling time
TS

Dead zone

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

3.17.1.5 Response Setup

Presentation:

1
2
3
4
5

Behavior:
No

Description

Default Presentation

Condition

Extra Damped

Extra Damped pressed

RESPTYPE = 1

Remarks

Extra Damped unpressed


2

Damped

Damped pressed

RESPTYPE = 2

Damped unpressed
3

Normal

Normal pressed

RESPTYPE = 3

Normal unpressed
4

Fast

Fast pressed

RESPTYPE = 4

Fast unpressed
5

Extra Fast

Extra Fast pressed

RESPTYPE = 5

Extra Fast unpressed

3BSE 021 945R401

443

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

3.17.1.6 Extended Setup

Presentation:

1
2

3
4

Behavior:
No

Description

Excitation Level Output


Value

1.1

OUT

OUT Black

1.2

OUT Value

Black

EXCLOUT

Output value

1.3

OUT Unit

Black

OUTUNIT

Output unit

Excitation Level Setpoint


Value

2.1

SP

SP Black

2.2

SP Value

Black

EXCLSP

Setpoint value

2.3

SP Unit

Black

UNIT

Setpoint unit

3.1

Frequency Text

Frequency Black

3.2

Value

Black

3.3

444

Unit

Default Presentation

Condition

Remarks
The Excitation level OUT
object value
Text in front of the value

The Excitation level SP


object value
Text in front of the value

Design frequency limit


FREQLIM

Text in front of the value

None Black

Infinite frequency limit

Rad/s Black

Unit

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Default Presentation

Condition

4.1

Unlimited

Unlimited pressed

FREQ_UNLIMITED = 1

Unlimited unpressed

FREQ_UNLIMITED = 0

4.2

Remarks

3.17.2 Object Display


Presentation:
8

10 11 12

3-4

1
2

13
14
15
16

17
18
7
19
20
21
22

23
24
25
26

40
41
42
43
44
45
46

27
28
29
30
31
32
33
34

47
48

49 - 50

35 - 39

Behavior:
No

Description

Presentation

Condition

Remarks

SelectFrame

White

SELECTED = 1

Object select frame

Grey

3BSE 021 945R401

445

PIDCONA, Adaptive PID Ctrl

No

Description

Header

Section

Presentation

Condition

Remarks

NAME and DESCR

Object name and description

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Green

Normal

Section Grey
Green

Class

MV Range Max
Green
OUT Range Max

MV Range Min

OUT Range Min

Measured Value Trim


Curve
Setpoint Value Trim
Curve
Output Value Trim
Curve

446

CLASS

Object class

MAX

Range Max of MV and SP


values

Range Max of OUT and ACT


values

Range Min of MV and SP


values

OUTMIN

Magenta

Process section
Text in front of the value

MIN
Green

PROC_SEC

OUTMAX
Magenta

Text in front of the value

Class Grey
Green

Section 3, Faceplates and Graphic Elements

Range Min of OUT and ACT


values

MV

Green

SETP

Cyan

OUT

Magenta

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

Condition

Remarks

8.1

Direction

Incr Green

REVACT = 1

Increase. When measured


value is increasing, it is
counteracted with decreasing
output.

Decr Green

REVACT = 0

Decrease. When measured


value is decreasing, output
also decreasing.

MV

Measured Value

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

8.2

8.3

8.4

Measured Value
Bargraph

Green

High Limit 2

High Limit 1

3BSE 021 945R401

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

447

PIDCONA, Adaptive PID Ctrl

No

Description

8.5

Low Limit 1

8.6

9.1

9.2

448

Presentation

Section 3, Faceplates and Graphic Elements

Condition

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Working SP Value
Bargraph

If AUTO = 1 or E1 = 1 or
E2 = 1 or
ATENBL =1

Current Setpoint value

Cyan

Then
WSP

Working Setpoint value

Cyan

else
SETP

Auto Setpoint value

SETP

Auto Setpoint value

AUTOSP Value
Cyan

If SETP > WSP

Black

If SETP < WSP

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

9.3

High SP Limit

9.4

10.1

10.2

Presentation

Condition

Remarks

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

Opening or Closing

SETPL

Lower setpoint limit

Yellow

SP=LL = 1

Limitation line and mesh

Grey

Op Magenta

ACT_DIR = OPENING

Opening. When output is


increasing the valve is
opening.

Cl Magenta

ACT_DIR = CLOSING

Closing. When output is


increasing the valve is closing.

OUT

Output value

OUT Value Bargraph


Magenta

10.3

10.4

11

HIgh OUT Limit

Upper limit output

OUTPH > OUTMAX or


(EOHL > OUTMAX and
EOLIM = 1)

Invisible

Yellow

OUT=HL = 1

Limitation line and mesh

Grey

Low OUT Limit

OUTPL

Lower limit output

OUTPL < OUTMIN or


(EOLL < OUTMIN and
EOLIM = 1)

Invisible

Yellow

OUT=LL = 1

Limitation line and mesh

Grey

ACT Value Bargraph

Gain Scheduling
Bargraph

3BSE 021 945R401

OUTPH

ACTPOS
Blue

12.1

PIDCONA, Adaptive PID Ctrl

SHOW_ACT = 1
SCHEDIN

Brown

Actuator position.

Gain scheduling value in.


Gain scheduling enabled.

449

PIDCONA, Adaptive PID Ctrl

No

Description

12.2

Zone limit between


zone 4 and 5

12.3

12.4

12.5

Zone limit between


zone 3 and 4
Zone limit between
zone 2 and 3
Zone limit between
zone 1 and 2

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

ZLIM45
Grey

Gain scheduling enabled.


ZLIM34

Grey

Gain scheduling enabled.


ZLIM23

Grey

Gain scheduling enabled.


ZLIM12

Grey

Gain scheduling enabled.

13

ALARM LIMITS

13.1

MV Text

MV Grey

13.2

Printout blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked.

13.3

Alarm blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator.

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_MV>H2 = 1

Unacknowledged alarm.

Red

MV>H2 = 1

Alarm.

13.4

Alarm Indication

Alarm limits
Text in front of the line

13.5

H2 Text

H2 Grey

13.6

H2 Value

Green

MVH2

High limit 2 value

14.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

14.2

Alarm blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator.

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_MV>H1 = 1

Unacknowledged alarm.

Red

MV>H1 = 1

Alarm.

14.3

Alarm Indication

Text in front of the value

14.4

H1 Text

H1 Grey

14.5

H1 Value

Green

MVH1

High limit 1 value

15.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked.

15.2

Alarm blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator.

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PC-program

450

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

15.3

Alarm Indication

Presentation

PIDCONA, Adaptive PID Ctrl

Condition

Remarks

Red flashing

AU_MV<L1 = 1

Unacknowledged alarm.

Red

MV<L1 = 1

Alarm.

15.4

L1 Text

L1 Grey

15.5

L1 Value

Green

MVL1

Low limit 1 value

16.1

Printout blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked.

16.2

Alarm blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator.

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_MV<L2 = 1

Unacknowledged alarm.

Red

MV<L2 = 1

Alarm.

16.3

Alarm Indication

16.4

L2 Text

L2 Grey

16.5

L2 Value

Green

17.1

DEV

DEV Grey

17.2

Printout blocked

17.3

Alarm blocked

17.4

Alarm Indication

Text in front of the value

Text in front of the value


MVL2

Low limit 2 value

P Yellow

PRINT_F1_BLK = 1

Printout blocked.

B Yellow

AL_F1_BLK =1

Alarm block by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_DEV>H1 = 1

Unacknowledged alarm.

Red

DEV>H1 = 1

Alarm.

17.5

H Text

H1 Grey

17.6

Value

Cream

DEVH1

18.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked.

18.2

Alarm blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PC-program

Red flashing

AU_DEV<L1 = 1

Unacknowledged alarm.

Red

DEV<L1 = 1

Alarm.

18.3

Alarm Indication

18.4

L Text

L1 Grey

18.5

L Value

Cream

3BSE 021 945R401

Text in front of the value

Text in front of the value


DEVL1

451

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

19

LIMITATIONS

19.1

SP Text

19.2

Warning Indication

19.3

H Text

H Grey

19.4

H Value

Cyan

20.1

Warning Indication

20.2

L Text

L Grey

20.3

L Value

Cyan

21.1

OUT Text

OUT Grey

21.2

Warning Indication

21.3

H Text

H Grey

21.4

H Value

Grey

OUTPH, EOLIM = 1

Magenta

OUTPH, EOLIM = 0

Magenta

EOLIM = 1

Grey

21.5

External H value

Presentation

Condition

Limitations

SP Grey
Yellow

Yellow

Yellow

SP=HL = 1

Setpoint is equal to high


setpoint limit
High limit setpoint

SETPH
SP=LL = 1

Setpoint is equal to low


setpoint limit
Low limit setpoint

SETPL
Output
OUT=HL = 1

Output is equal to output high


limit
Output high limit.

Warning Indication

22.2

L Text

L Grey

22.3

L Value

Grey

OUTPL, EOLIM = 1

Magenta

OUTPL, EOLIM = 0

Magenta

EOLIM = 1

Grey

External L Value

Yellow

Setpoint

22.1

22.4

Remarks

OUT=LL = 1

Output high limit value.

External output high limit


value

Output is equal to low output


limit
Output low limit.
Output low limit value.

External output low limit value.

23

PARAMETERS

23.1

P Green

GAIN > 0

Gain active

23.2

I Green

GAIN > 0 and


TI > 0

Integration active

452

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

Condition

Remarks

23.3

D Green

GAIN > 0 and


TD > 0

Derivation active

23.4

Zone Text

Zone Green

GSENBL = 1

Gain scheduling active

23.5

Zone Value

Green

GSENBL = 1

Gain scheduling zone

24.1

Present Text

Present Grey

24.2

Text

24.3

Saved Text

24.4

Text

PRESENT_OBT = 0

Default setting. Invisible.

(M) Green

PRESENT_OBT = 1

Manual setting

(A) Green

PRESENT_OBT = 2

Autotuned setting

Saved Grey

Saved parameters
SAVED_OBT = 0

Default setting. Invisible.

(M) Green

SAVED_OBT = 1

Manual setting

(A) Green

SAVED_OBT = 2

Autotuned setting

25.1

Gain Text

Gain Grey

25.2

Present Gain Value

Green

25.3

Saved Gain Value

Green

26.1

TI Text

TI Grey

26.2

Present TI Value

Green

26.4

Unit

s Green

26.5

Saved TI Value

Green

26.5

Unit

s Green

27.1

TD Text

TD Grey

27.2

Present TD Value

Green

27.3

Unit

s Green

27.4

Saved TD Value

Green

27.5

Unit

s Green

28.1

BETA Text

BETA Grey

28.2

Present BETA Value

Green

3BSE 021 945R401

Present parameters

Gain

Integration time
TI

Derivation time
TD

Setpoint factor BETA


BETA

453

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

28.3

Saved BETA Value

Green

29.1

Alarm Indication

Red flashing

INV_TSAMP = 1

Unacknowledged TS alarm.

Red

INV_TSAMP = 1

TS Alarm. There is one or


more invalid sample rates.

29.2

TS Text

TS Grey

29.3

Present TS Value

Green

29.4

Unit

s Green

29.5

Saved TS Value

Green

29.6

Unit

s Green

30.1

DZ Text

DZ Grey

30.2

Value

Green

30.3

Unit

% Green

31.1

Response Text

Response Grey

31.2

Response Type Text

Extra Damped

Sampling time
TS

Deadzone
DZ

Damped
Normal

Green

Green

Green

RESPTYPE = EXTRA
DAMPED
RESPTYPE = DAMPED
RESPTYPE = NORMAL

Fast Green

RESPTYPE = FAST

Extra Fast Green

RESPTYPE = EXTRA
FAST

32.1

Freq Limit Text

Freq Limit Grey

32.2

Value

Green

None Green
32.3

Unit

Rad/s Green

33.1

Frequency Text

Frequency Grey

33.2

Value

Green

33.3

Unit

Rad/s Green

454

Response type

Design frequency limit


FREQLIM
Infinite frequency limit.

Design frequency. Shown only


when an autotuned setting
exist.

Design frequency unit.

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

34.1

Zone Info Text

Zone Info Grey

34.2

Text

- - Green

ZONE1_OBT = 0

Default

M-

Green

ZONE1_OBT = 1

Manual setting

A - Green

ZONE1_OBT = 2

Autotuned setting

-V

Green

ZONE1_OBT = 4

The zone has been visited


during autotuning

MV Green

ZONE1_OBT = 5

Manual setting and the zone


has been visited during
autotuning

AV Green

ZONE1_OBT = 6

Autotuned setting and the


zone has been visited during
autotuning

- - Green

ZONE2_OBT = 0

Default

M-

Green

ZONE2_OBT = 1

Manual setting

A - Green

ZONE2_OBT = 2

Autotuned setting

-V

Green

ZONE2_OBT = 4

The zone has been visited


during autotuning

MV Green

ZONE2_OBT = 5

Manual setting and the zone


has been visited during
autotuning

AV Green

ZONE2_OBT = 6

Autotuned setting and the


zone has been visited during
autotuning

34.3

Text

3BSE 021 945R401

Condition

Remarks
Gain scheduling zone
information

455

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

34.4

Text

- - Green

ZONE3_OBT = 0

Default

M - Green

ZONE3_OBT = 1

Manual setting

A-

Green

ZONE3_OBT = 2

Autotuned setting

-V

Green

ZONE3_OBT = 4

The zone has been visited


during autotuning

MV Green

ZONE3_OBT = 5

Manual setting and the zone


has been visited during
autotuning

AV Green

ZONE3_OBT = 6

Autotuned setting and the


zone has been visited during
autotuning

- - Green

ZONE4_OBT = 0

Default

M - Green

ZONE4_OBT = 1

Manual setting

A-

Green

ZONE4_OBT = 2

Autotuned setting

-V

Green

ZONE4_OBT = 4

The zone has been visited


during autotuning

MV Green

ZONE4_OBT = 5

Manual setting and the zone


has been visited during visit
autotuning

AV Green

ZONE4_OBT = 6

Autotuned setting and the


zone has been visited during
autotuning

- - Green

ZONE5_OBT = 0

Default

M - Green

ZONE5_OBT = 1

Manual setting

A-

Green

ZONE5_OBT = 2

Autotuned setting

-V

Green

ZONE5_OBT = 4

The zone has been visited


during autotuning

MV Green

ZONE5_OBT = 5

Manual setting and the zone


has been visited during visit
autotuning

AV Green

ZONE5_OBT = 6

Autotuned setting and the


zone has been visited during
autotuning

34.5

34.6

456

Text

Text

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

35.1

MV Text

MV Grey

35.2

MV Value

? ? ? Red

Green
35.3

36.2

Current SP Value

36.3

37.2

OUT Value

MV

Measured value

Measured unit

Text in front of the value


If AUTO = 1 or E1 = 1 or
E2 = 1 or
ATENBL =1

Current Setpoint value

Cyan

Then
WSP

Working Setpoint value

Cyan

else
SETP

Auto Setpoint value

UNIT

Setpoint unit

OUT Grey

Text in front of the value


OUT

Magenta
37.3

Signal error

SP Grey

Cyan
OUT Text

AI_ERR

SP Unit

37.1

Remarks
Text in front of the value

UNIT
Green

SP Text

Condition

MV Unit

36.1

PIDCONA, Adaptive PID Ctrl

OUT Unit

Output value

OUTUNIT

Magenta

Output unit

37.4

External OUT
Limitation Indication

X Yellow

(OUT=HL = 1 or
OUT=LL= 1) and
EOLIM = 1

OUT limited by external


limitation

38.1

ACT Text

ACT Grey

SHOW_ACT = 1

Actuator position

38.2

ACT Value

ACTPOS

Actuator value

Blue
38.2

SHOW_ACT = 1

ACT Unit

OUTUNIT
Blue

39.1

DEV Text

3BSE 021 945R401

DEV

Actuator unit

SHOW_ACT = 1
Grey

Text in front of the value

457

PIDCONA, Adaptive PID Ctrl

No

Description

39.2

DEV Value

Section 3, Faceplates and Graphic Elements

Presentation

Condition

Remarks

DEV

Deviation value.
DEV = MV - SP

Cream
39.3

DEV Unit

40.1

Bal Indicator

40.2

Bal Mode

40.3
41.1

41.2

Man Mode

41.4

Out Text

41.5

Man Out Value

42.2

Auto Mode

SP Text

42.4

Auto Setpoint Value

Deviation unit
BAL = 1

Balance control mode

Bal Green

BAL = 1

Bal Grey

Local Green

LOCAL = 1

Balance Local control mode

Grey

MAN = 1 and
ATENBL = 1

When autotuning is finished


manual control mode is
resumed

Green

MAN = 1

Manual control mode

Man Green

MAN = 1

Man Grey

Clamped Green

CLAMP = 1

Man Clamped control mode

Forced Green

MANFD = 1

Man Forced control mode

OUT Grey

Text in front of the value


MANOUT

Man Out value

Magenta

MAN = 1

Manual mode

Grey

Auto Indicator

42.3

458

Green filled

Man Indicator

41.3

42.1

% Cream

Grey

AUTO = 1 and
ATENBL = 1

Green

AUTO = 1

Auto Green

AUTO = 1

Auto Grey

SP Grey

When autotuning is finished


control mode auto is resumed

Auto control mode

Text in front of the value


SETP

Auto Setpoint value

Cyan

AUTO = 1

Auto mode

Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

Condition

Remarks

43.1

E1 Indicator

Grey

E1 = 1 and
ATENBL = 1

When autotuning is finished


control mode E1 is resumed

Green

E1 =1

43.2

43.3

E1 Mode

SP Text

43.5

E1 Setpoint Value

44.2

44.3

E1 Grey

E1NAME

Green

E1 = 1

Grey

SP Grey

E2 Mode

44.5

E2 Setpoint Value

E3 Mode Indicator

3BSE 021 945R401

User text behind the text E1

Text in front of the value


E1 control mode setpoint

Green

E1 = 1

E1 mode

Grey

Grey

E2 = 1 and
ATENBL = 1

Green

E2 = 1

E2 Green

E2 = 1

E2 Grey

E2 Name

SP Text

Text behind the indication

EXTREF1

E1 Mode Indicator

44.4

45.1

E1 =1

E1 Name

43.4

44.1

E1 Green

When autotuning is finished


control mode E2 is resumed

E2 control mode

E2NAME
Green

E2 = 1

Grey

SP Grey

Text in front of the value


EXTREF2

E2 control mode setpoint

Green

E2 = 1

E2 mode

Grey

Grey

E3 = 1 and
ATENBL = 1

Green

E3 = 1

When autotuning is finished


control mode E3 is resumed

459

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

No

Description

Presentation

Condition

Remarks

45.2

E3 Mode

E3 Green

E3 = 1

External 3 control mode

E3 Grey

45.3

E3 Name

45.4

OUT Text

45.5

E3 Output Value

46.1

E3NAME
Green

E2 = 1

Grey

OUT

Grey

Text in front of the value


EXTREF3

E3 control mode output

Green

E3 = 1

E3 mode

Grey

Autotuning Alarm
Indicator

Red flashing

46.2

Autotuning Indicator

Green

46.3

Autotuning

AL_F5_UNACK = 1

Red

Autotuning Green

Unacknowledged alarm
Alarm

ATENBL = 1

Autotuning active

ATENBL = 1

Autotuning active.

Autotuning Grey
46.4

460

Text

Off Grey

Autotuning failed or stopped.

Done Grey

Autotuning was successful.

Listen Phase Green

ATENBL = 1

Check process value


variation.

Relay Phase Green

ATENBL = 1

Relay feedback with sample


rate selection and design
calculations.

Excite Phase Green

ATENBL = 1

Adaptive control with setpoint


excitation.

Verify Phase Green

ATENBL = 1

Verify setting with a setpoint


step.

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

Condition

46.5

Text

Aborted by PC Green

Autotuning aborted by PCinput LOCALFL, LOCAL,


BALIN, CLAMP, ATENBL or
command Man Forced or AI
error.

Failed

Autotuning failed.

Green

Remarks

Verify Uncertain Green

The response of the step


outside bounds but not
rejected and the design is
considered uncertain.

Verify OK

The response of the step


within bound of the design.

Green

46.6

Text

Low Excitation Green

Excitation level too low.

47.1

Text

Step Green

Number of listen steps.

OUT Step
SP Step

Green

Number of output steps from


the beginning of relay phase.

Green

Number of setpoint steps from


the beginning of excitation
phase.

47.2

Counter

Green

Counter value.

47.3

Text

Outside Start Zone

Zone has changed during


autotuning with gain
scheduling. Text only visible
during autotuning.

Green

48.1

48.2

Adaptation Alarm
Indicator

Red flashing

Adaptation Indicator

Green

AL_F5_UNACK = 1

Red

Alarm.
ADAPON = 1

Yellow

48.3

Adaptation

Adaptation Green

Unacknowledged alarm.

Adaptation active.
1. Adaptation blocked by PC
program or
2. Not mode Auto, E1 or E2 or
3. No autotuned setting exist.

ADAPON = 1

Adaptation active.

Adaptation Grey
48.4

Text

3BSE 021 945R401

Failed Green

Alarm text.

461

PIDCONA, Adaptive PID Ctrl

No

Description

Presentation

49

Text

timeout
(CONTINUE restarts
counter)

Section 3, Faceplates and Graphic Elements

Condition

Remarks
The setpoint step counter has
reach max number of steps
- 2.

Green

timeout
(ABORTS if Verify
fails)

The setpoint step counter has


reach max number of steps
- 2.

Green
50

Text

CONTINUE,
ACCEPT or STOP ?
Green

462

AT_ALERT = 1

Question to the operator.


Continue tune, accept and
save setting or stop
autotuning and restore setting.

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

3.17.3 Graphic Element


3.17.3.1 Numeric, Mode and Unit

Presentation:

1
2

3BSE 021 945R401

463

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

MV

Object value

? ? ? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

AI_ERR = 1

Signal error

Red

DISTURB = 1

Alarm

Green

Invisible
2

Measured Value

Unit

Object unit
Green

464

UNIT

Mode

Object mode

BaLo Green

LOCAL = 1

Bal Local mode

Bal Green

BAL = 1

Bal mode

MCp Green

CLAMP = 1

Man Clamped mode

MFd Green

MANFD = 1

Man Forced mode

M AT Green

MAN = 1 and
ATENBL = 1

Man mode and Autotuning

M Green

MAN = 1

Man mode

A AT Green

AUTO = 1 and
ATENBL = 1

Auto mode and Autotuning

A Ad Green

AUTO = 1 and
ADAPON = 1

Auto mode and Adaptation

A Green

AUTO = 1

Auto mode

E1 AT Green

E1 = 1 and
ATENBL = 1

E1 mode and Autotuning

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

4
cont.

PIDCONA, Adaptive PID Ctrl

Default Presentation

Condition

Remarks

E1 Ad Green

E1 = 1 and
ADAPON = 1

E1 mode and Adaptation

E1 Green

E1 = 1

E1 mode

E2 AT Green

E2 = 1 and
ATENBL = 1

E2 mode and Autotuning

E2 Ad Green

E2 = 1 and
ADAPON = 1

E2 mode and Adaptation

E2 Green

E2 = 1

E2 mode

E3 AT Green

E3 = 1 and
ATENBL = 1

E3 mode and Autotuning

E3 Green

E3 = 1

E3 mode

External OUT Limitation

External output limitation

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

External output limitation

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

3BSE 021 945R401

465

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

SETP

Setpoint value

Invisible
2

Setpoint Value
Red flashing

AL_UNACK = 1

Red

DISTURB = 1

Cyan

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

1
2

466

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

OUT

Output value

Invisible
2

Output Value
Red flashing

AL_UNACK = 1

Red

DISTURB = 1

Magenta

Unit

OUTUNIT
Green

Object unit

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

467

PIDCONA, Adaptive PID Ctrl

Section 3, Faceplates and Graphic Elements

3.17.3.2 Bargraph

Presentation:

1
4

6
7

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

AI_ERR = 1

AI error alarm

468

Red

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

MV Value

Default Presentation

Condition

Remarks

MV

Object value

AI_ERR = 1

Invisible - I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB =1

Alarm

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 > MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

Low Limit 1

3BSE 021 945R401

PIDCONA, Adaptive PID Ctrl

MVH1

Warning High limit 1

MVH1 > MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

MVL1

Warning Low limit 1

469

PIDCONA, Adaptive PID Ctrl

No

Description

6
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVL1 < MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 < MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

470

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Setpoint Value

3BSE 021 945R401

SETP

Object setpoint value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Cyan

471

PIDCONA, Adaptive PID Ctrl

No

Description

High SP Limit

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

SETPL

Lower limit setpoint

Yellow

SP=LL = 1

Limitation line and mesh

Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

472

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCONA, Adaptive PID Ctrl

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Setpoint Value

3BSE 021 945R401

OUT

Object setpoint value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Cyan

473

PIDCONA, Adaptive PID Ctrl

No

Description

High SP Limit

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

OUTPH

Upper limit setpoint

Yellow

OUT=HL = 1

Limitation line and mesh

Grey

Low SP Limit

OUTPL

Lower limit setpoint

Yellow

OUT=LL = 1

Limitation line and mesh

Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

474

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

3.18 PIDCON, PID Controller


3.18.1 Faceplate
Presentation:

3BSE 021 945R401

475

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

476

Default Presentation

Condition

BaLo Dark green

LOCAL = 1

Bal Dark green

BAL = 1

MCp Dark green

CLAMPED = 1

MFd Dark green

MANFD = 1

M Dark green

MAN = 1

A Dark green

AUTO = 1

E1 Dark green

E1 = 1

Remarks

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3.1
cont.

PIDCON, PID Controller

Default Presentation

Condition

E2 Dark green

E2 = 1

E3 Dark green

E3 = 1

3.2

Print Blk

P Yellow

PRINT_F1_BLK = 1 or
PRINT_F2_BLK = 1

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0 , 12

Increase output
with 0,5 unit

MAN = 1

Increase setpoint
with 0,5 unit

AUTO = 1

Decrease output
with 0,5 unit

MAN = 1

Decrease setpoint
with 0,5 unit

AUTO = 1

Incr

Decr

Remarks

Man

Set to Man Mode

Set MMI_MAN = 1

Auto

Set to Auto Mode

Set MMI_AUTO = 1

MFd

Set to Man Force Mode

Set MANFD = 1

E1

Set to E1 Mode

Set MMI_E1 = 1

E2

Set to E2 Mode

Set MMI_E2 = 1

E3

Set to E3 Mode

Set MMI_E3 = 1

3BSE 021 945R401

477

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

3.18.1.1 Control and ReducedControl

Presentation:
3

7
8
9
10

5
6

9
10

7
8

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

MV Range Max

Black

MAX

Range Max of the MV and


SP value

1.2

MV Range Min

Black

MIN

Range Min of the MV and


SP value

478

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

No

Description

Default Presentation

2.1

OUT Range Max

100.0 Black

Range Max of OUT is


100.0%

2.2

OUT Range Min

0.0 Black

Range Min of OUT is 0.0%

3.1

Direction

Incr Green

MV_DIR = INCREASING

Increase of measured
value

Decr Green

MV_DIR = DECREASING

Decrease of measured
value

MV

Measured Value

3.2

3.3

3.4

3.5

Measured Value
Bargraph

Green

High Limit 2

3BSE 021 945R401

Remarks

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

Low Limit 1

Condition

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

MVL1

Warning Low limit 1

479

PIDCON, PID Controller

No

Description

3.5
cont.

3.6

SP Value Bargraph

4.2

High SP Limit

5.1

5.2

480

Default Presentation

Condition

Remarks

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and AL_F1_BLK


=1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and AU_MV<L1


=1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

4.1

4.3

Section 3, Faceplates and Graphic Elements

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and AL_F2_BLK


=1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and AU_MV<L2


=1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Cyan

SETP

Setpoint value

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

Opening or Closing

OUT Value Bargraph

SETPL

Lower setpoint limit

Yellow

SP=LL = 1

Limitation line and mesh

Grey

Op Magenta

ACT_DIR = OPENING

Actuator position opening

Cl Magenta

ACT_DIR = CLOSING

Actuator position closing

POUT

Output value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

5.2
cont.
5.3

5.4

PIDCON, PID Controller

Default Presentation

Condition

Magenta

HIgh OUT Limit

Remarks

OUTPH

Upper limit output

OUTPH > 100 or


(EOHL > 100 and EOLIM =
1)

Invisible

Yellow

OUT=HL = 1

Limitation line and mesh

Grey

Low OUT Limit

OUTPL

Lower limit output

OUTPL < 0 or
(EOLL < 0 and EOLIM = 1)

Invisible

Yellow

OUT=LL = 1

Limitation line and mesh

Grey

ACT Value Bargraph

ACTPOS
Blue

Actuator value

CTRL = ON-OFF

7.1

MV Text

MV Black

7.2

MV Value

X X X Red

MV is Bad

No contact with controller

? ? ? Red

AI_ERR = 1

Signal error

MV

Measured value

Black
7.3

MV Unit

SP Text

8.2

SP Value

OUT Text

9.2

OUT Value

3BSE 021 945R401

Setpoint value

UNIT

Black
9.1

Text in front of the value


SETP

SP Unit

Measured unit

SP Black

Black
8.3

UNIT

Black
8.1

Text in front of the value

Setpoint unit

OUT Black

Text in front of the value


POUT

Output value

481

PIDCON, PID Controller

No

Description

9.2
cont.

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Black

Remarks

9.3

OUT Unit

% Black

9.4

External OUT Limitation


Indication

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

OUT limited by external


limitation

10.1

ACT Text

ACT Black

CTRL = ON-OFF

Text in front of the value

10.2

ACT Value

ACTPOS

Actuator value

10.3

ACT Unit

Output unit

Black

CTRL = ON-OFF

% Black

CTRL = ON-OFF

Actuator unit

3.18.1.2 Limits

Presentation:

1
2
3
4

5
6

482

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

MVL1

MVL2

DEV H Black

DEV H

Black
6

MVH1

L2 Black

L2

Black
5

MVH2

L1 Black

L1

Black
4

Remarks

H1 Black

H1

Black
3

Condition

DEVH

DEV L Black

DEV L

Black

DEVL

Presentation:

1
2

3
4

3BSE 021 945R401

483

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

SP H

SP H Black
Black

SPH

SPL

OUT H Black

OUT H

Black
4

Remarks

SP L Black

SP L

Black
3

Condition

OUTH

OUT L Black

OUT L

Black

OUTL

3.18.1.3 Block

Presentation:

1
2

3
4

484

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Block Alarm 1

Block Alarm L1/H1 Black

Block Alarm 2

Block Printout 1

Block Printout 2

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

AL_F1_BLK = 1

Deblock pressed

AL_F1_BLK = 0

Remarks

Block Alarm L2/H2 Black

Yellow

Blocked

Block pressed

AL_F2_BLK = 1

Deblock pressed

AL_F2_BLK= 0

Block Printout L1/H1


Black

Yellow

Blocked

Block pressed

PRINT_F1_BLK = 1

Deblock pressed

PRINT_F1_BLK = 0

Block Printout L2/H2


Black

Yellow

Blocked

Block pressed

PRINT_F2_BLK = 1

Deblock pressed

PRINT_F2_BLK = 0

485

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

3.18.1.4 Parameters

Presentation:

1
2
3
4
5
6
7

Behavior:
No

Description

Default Presentation

Block Integration

Block I Black

Block Deviation

Yellow

Blocked

Block pressed

BLK_I = 1

Deblock pressed

BLK_I = 0

Remarks

Block D Black

Yellow

Blocked

Block pressed

BLK_D = 1

Deblocked pressed

BLK_D = 0

3.1

Gain

Gain Black

3.2

Value

Black

486

Condition

Gain
GAIN

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

No

Description

Default Presentation

4.1

TI

TI Black

4.2

Value

Black

4.3

Unit

s Black

5.1

TD

TD Black

5.2

Value

Black

5.3

Unit

s Black

6.1

TF

TF Black

6.2

Value

Black

6.3

Unit

s Black

7.1

DZ

DZ Black

7.2

Value

Black

DZ, CTRL = ON - OFF

7.3

Unit

% Black

DZ, CTRL = ON - OFF

3BSE 021 945R401

Condition

Remarks
Integration time

TI

Derivation time
TD

Filter Time
TF

Dead zone

487

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

3.18.2 Object Display


Presentation:
2

9 10

3 4

11
12
13
14
15
16

17
18
19
20

21
22
23
24
25
26
27

33
34
35
36
37
38

28-32

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header
Red flashing

488

NAME and DESCR

Object name and


description

AL_UNACK = 1

Unacknowledged alarm

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.
3

Section

Default Presentation

Condition

Remarks

Red

DISTURB = 1

Alarm

Green

Normal

Section Grey
Green

Class

Text in front of the value


PROC_SEC

Class Grey
Green

PIDCON, PID Controller

MV Range Max
Green

Text in front of the value


CLASS

Object class

MAX

Range Max of the MV and


SP value

OUT Range Max

Range Max of OUT is


100.0%

100.0 Magenta
6

MV Range Min

MIN

Green

7.2

7.3

Direction

Measured Value
Bargraph

Range Min of OUT is 0.0%

0.0 Magenta

Incr Green

MV_DIR = INCREASING

Increase of measured
value

Decr Green

MV_DIR = DECREASING

Decrease of measured
value

MV

Measured Value

Green

High Limit 2

3BSE 021 945R401

Range Min of the MV and


SP value

OUT Range Min

7.1

Process section

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

489

PIDCON, PID Controller

No

Description

7.3
cont.

7.4

7.5

7.6

490

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

Remarks

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.6
cont.

8.1

SP Value Bargraph

8.2

High SP Limit

8.3

9.1

9.2

Default Presentation

Condition

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Cyan

SETP

Setpoint value

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

Opening or Closing

9.4

10

Lower setpoint limit

Yellow

SP=LL = 1

Limitation line and mesh

Grey

Op Magenta

ACT_DIR = OPENING

Actuator position opening

Cl Magenta

ACT_DIR = CLOSING

Actuator position closing

POUT

Output value

OUT Value Bargraph

HIgh OUT Limit

Upper limit output

OUTPH > 100 or


(EOHL > 100 and EOLIM =
1)

Invisible

Yellow

OUT=HL = 1

Limitation line and mesh

Grey

Low OUT Limit

OUTPL

3BSE 021 945R401

Lower limit output

OUTPL < 0 or
Invisible
(EOLL < 0 and EOLIM = 1)

Yellow

OUT=LL = 1

Grey

ACT Value Bargraph

ALARM LIMITS

OUTPH

ACTPOS
Blue

11

Remarks

SETPL

Magenta
9.3

PIDCON, PID Controller

Limitation line and mesh

Actuator value

CTRL = ON-OFF
Alarm limits

491

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

11.1

MV Text

MV Grey

11.2

Printout blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked

11.3

Alarm blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV>H2 = 1

Unacknowledged alarm

Red

MV>H2 = 1

Alarm

11.4

Alarm Indication

Condition

Remarks
Text in front of the line

11.5

H2 Text

H2 Grey

11.6

H2 Value

Green

MVH2

High limit 2 value

12.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

12.2

Alarm blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV>H1 = 1

Unacknowledged alarm

Red

MV>H1 = 1

Alarm

12.3

Alarm Indication

Text in front of the value

12.4

H1 Text

H1 Grey

12.5

H1 Value

Green

MVH1

High limit 1 value

13.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

13.2

Alarm blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV<L1 = 1

Unacknowledged alarm

Red

MV<L1 = 1

Alarm

13.3

Alarm Indication

Text in front of the value

13.4

L1 Text

L1 Grey

13.5

L1 Value

Green

MVL1

Low limit 1 value

14.1

Printout blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked

14.2

Alarm blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PCprogram

492

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

14.3

Alarm Indication

Default Presentation

Condition

Remarks

Red flashing

AU_MV<L2 = 1

Unacknowledged alarm

Red

MV<L2 = 1

Alarm

14.4

L2 Text

L2 Grey

14.5

L2 Value

Green

15.1

DEV

DEV Grey

15.2

Printout blocked

15.3

Alarm blocked

15.4

Alarm Indication

PIDCON, PID Controller

Text in front of the value


MVL2

Low limit 2 value

P Yellow

PRINT_F1_BLK = 1

Printout blocked

B Yellow

AL_F1_BLK =1

Alarm block by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_DEV>H1 = 1

Unacknowledged alarm

Red

DEV>H1 = 1

Alarm

15.5

H Text

H Grey

15.6

H Value

Cream

DEVH1

16.1

Printout blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

16.2

Alarm blocked

B Yellow

AL_F1_BLK =1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_DEV<L1 = 1

Unacknowledged alarm

Red

DEV<L1 = 1

Alarm

16.3

Alarm Indication

16.4

L Text

L Grey

16.5

L Value

Cream

17

LIMITATIONS

17.1

SP Text

17.2

Warning Indication

17.3

H Text

H Grey

17.4

H Value

Cyan

18.1

Warning Indication

18.2

L Text

3BSE 021 945R401

Text in front of the value

Text in front of the value


DEVL1
Limitations

SP Grey
Yellow

Yellow

L Grey

Setpoint
SP=HL = 1
High limit setpoint
SETPH
SP=LL = 1
Low limit setpoint

493

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

18.3

L Value

Cyan

SETPL

19.1

OUT Text

OUT Grey

19.2

Warning Indication

19.3

H Text

H Grey

19.4

H Value

Grey

OUTPH, EOLIM = 1

Magenta

OUTPH, EOLIM = 0

Magenta

EOLIM = 1

19.5

External H value

Yellow

Remarks

Text in front of the line


OUT_HL = 1
High limit output
Output High value

External Output High value

Grey
20.1

Warning

20.2

L Text

L Grey

20.3

L Value

Grey

OUTPL, EOLIM = 1

Magenta

OUTPL, EOLIM = 0

Magenta

EOLIM = 1

Grey

20.4

External L Value

Yellow

OUT_EQ_LL = 1
Low limit output
Output Low value

External Output Low value

21

PARAMETERS

Grey

21.1

P Green

21.2

I Green

BLK_I = 0 and
EINTBE = 0

Integration active

21.3

D Green

BLK_D = 0 and
EDERBE = 0

Derivation active

22.1

Gain

Gain Grey

22.2

Value

Grey

EGAINE = 1

Green

GAIN
EGAINE = 1

Gain active

Gain

22.3

External Value

Green

23.1

TI

TI Grey

23.2

Value

Grey

ETIE = 1

Green

TI

23.3

494

Unit

Value changed by operator

Integration time
Value changed by operator

s Green

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

No

Description

Default Presentation

Condition

23.4

External Value

Green

ETIE = 1

23.5

External Unit

s Green

ETIE = 1

24.1

TD

TD Grey

24.2

Value

Grey

ETDE = 1

Green

TD

Derivation time

24.3

Unit

s Green

24.4

External Value

Green

ETDE = 1

24.5

External Unit

s Green

ETDE = 1

25.1

TF

TF Grey

25.2

Value

Grey

ETFE = 1

Green

TF

Unit

s Green

25.4

External Value

Green

ETFE = 1

25.5

External Unit

s Green

ETFE = 1

26.1

TS

TS Grey

26.2

Value

Green

26.3

Unit

s Green

27.1

DZ

DZ Grey

27.2

Value

Green

DZ, CTRL = ON-OFF

27.3

Unit

% Green

DZ, CTRL = ON-OFF

28.1

MV Text

MV Grey

28.2

MV Value

? ? ? Red

28.3

MV Unit

29.1

SP Text

3BSE 021 945R401

SP Grey

Value changed by operator

Sampling time
TS

Dead zone

Text in front of the value


AI_ERR = 1

Signal error

MV

Measured value

UNIT

Green

Value changed by operator

Filter Time

25.3

Green

Remarks

Measured unit

Text in front of the value

495

PIDCON, PID Controller

No

Description

29.2

SP Value

Section 3, Faceplates and Graphic Elements

Default Presentation

Cyan
29.3

SP Unit

OUT Text

30.2

OUT Value

Remarks

SETP

Setpoint value

UNIT

Cyan
30.1

Condition

OUT Grey

Text in front of the value


POUT

Magenta

Setpoint unit

Output value

30.3

OUT Unit

% Magenta

30.4

External OUT Limitation


Indication

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

OUT limited by external


limitation

31.1

ACT Text

ACT Grey

CTRL = ON-OFF

Text in front of the value

31.2

ACT Value

ACTPOS

Actuator value

Blue

CTRL = ON-OFF
CTRL = ON-OFF

31.3

ACT Unit

% Blue

32.1

DEV Text

DEV Grey

32.2

DEV Value

DEV Unit

33.1

Bal indication

33.2

Bal Mode

33.3
34.1

Man indication

34.2

Man Mode

34.3

496

Deviation value

% Cream
Green filled

Actuator unit
Text in front of the value

DEV
Cream

32.3

Output unit

Deviation unit
BAL = 1

Bal control mode

Bal Green

BAL = 1

Text behind the indication

Bal Grey

Local Green

LOCAL = 1

Bal Local control mode

MAN = 1

Man control mode

Man Green

MAN = 1

Text behind the indication

Man Grey

Clamped Green

CLAMP = 1

Man Clamp control mode

Forced Green

MANFD = 1

Man Forced control mode

Green filled

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

34.4

Man Out Text

OUT Grey

34.5

Man Out Value

35.1

Auto indication

35.2

Auto Mode

35.3

Auto Setpoint Text

35.4

Auto Setpoint Value

36.1

E1 indication

36.2

E1 Mode

36.2

E2 indication

37.2

E2 Mode

37.2

E3 indication

38.2

E3 Mode

3BSE 021 945R401

Remarks
Text in front of the value
Man Out value

Magenta

MAN = 1

Manual mode

Grey

Green filled

AUTO = 1

Auto control mode

Auto Green

AUTO = 1

Text behind the indication

Auto Grey

SP Grey

Text in front of the value


AUTOSP

Auto Setpoint value

Cyan

AUTO =1

Auto mode

Grey

Green filled

E1 = 1

E1 control mode

E1 Green

E1 = 1

Text behind the indication

E1 Grey

E1NAME

Green

E1 = 1

Grey

Green filled

User text behind the text


E1

E2 = 1

E2 control mode

E2 Green

E2 = 1

Text behind the indication

E2 Grey

E2 Name

38.1

Condition

MAN_OUT

E1 Name

37.1

PIDCON, PID Controller

E2NAME
Green

E2 = 1

Grey

Green filled

User text behind the text


E2

E3 = 1

E3 control mode

E3 Green

E3 = 1

Text behind the indication

E3 Grey

497

PIDCON, PID Controller

No

Description

38.3

E3 Name

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

E3NAME

User text behind the text


E3

Green

E3 = 1

Grey

3.18.3 Graphic Element


3.18.3.1 Numeric, Mode and Unit

Presentation:

1
2

498

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

MV

Object value

? ? ? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

AI_ERR = 1

Signal error

Red

DISTURB = 1

Alarm

Green

Invisible
2

Measured Value

Unit

Object unit
Green

UNIT

Mode

Object mode

BaLo Green

LOCAL = 1

Bal Local mode

Bal Green

BAL = 1

Bal mode

MCp Green

CLAMPED = 1

Man Clamped mode

MFd Green

MANFD = 1

Man Forced mode

M Green

MAN = 1

Man mode

A Green

AUTO = 1

Auto mode

E1 Green

E1 = 1

E1 mode

E2 Green

E2 = 1

E2 mode

E3 Green

E3 = 1

E3 mode

3BSE 021 945R401

Mode is invisible

499

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

External OUT Limitation

Condition

Remarks
External output limitation

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

External output limitation

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

500

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

SETP

Setpoint value

Invisible
2

Setpoint Value
Red flashing

AL_UNACK = 1

Red

DISTURB = 1

Cyan

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

1
2

3BSE 021 945R401

501

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

OUT

Output value

Invisible
2

Output Value
Red flashing

AL_UNACK = 1

Red

DISTURB = 1

Magenta

Unit

Object unit

% Green

The conditions are in priority order.

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

502

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

PIDCON, PID Controller

3.18.3.2 Bargraph

Presentation:

1
4

6
7

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

AI_ERR = 1

AI error alarm

3BSE 021 945R401

Red

503

PIDCON, PID Controller

No

Description

MV Value

504

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MV

Object value

AI_ERR = 1

Invisible - I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB =1

Alarm

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 > MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

Low Limit 1

MVH1

Warning High limit 1

MVH1 > MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

MVL1

Warning Low limit 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

6
cont.

PIDCON, PID Controller

Default Presentation

Condition

Remarks

MVL1 < MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Unfilled Yellow

AL_F1_BLK = 1

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 < MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Unfilled Yellow

AL_F2_BLK = 1

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

3BSE 021 945R401

505

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Setpoint Value

506

SETP

Object setpoint value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Cyan

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

High SP Limit

Default Presentation

PIDCON, PID Controller

Condition

Remarks

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

SETPH

Lower limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...4)

FrameStyle

1. Lock Frame

Raised, Flat, Sunken

3BSE 021 945R401

507

PIDCON, PID Controller

Section 3, Faceplates and Graphic Elements

Presentation:

1
3

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

Setpoint Value

508

SETP

Object setpoint value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Cyan

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

High SP Limit

Default Presentation

PIDCON, PID Controller

Condition

Remarks

SETPH

Upper limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Low SP Limit

SETPH

Lower limit setpoint

Yellow

SP=HL = 1

Limitation line and mesh

Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

509

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

3.19 RATSTN, Ratio Station


3.19.1 Faceplate
Presentation:

510

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

1
4

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

Default Presentation

Condition

M Dark green

MAN = 1

A Dark green

AUTO = 1

E1 Dark green

E1 = 1

3.2

Print Blk

P Yellow

PRINT_F1_BLK or
PRINT_F2_BLK

Aspect links

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

3BSE 021 945R401

Remarks

511

RATSTN, Ratio Station

No

Description

4
cont.
5

Incr

Decr

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Object Type Help

position 0, 0, 12

Increase output
with 0,5 unit

MAN = 1

Increase ratio with 0,5 unit

AUTO = 1

Decrease output
with 0,5 unit

MAN = 1

Remarks

Decrease ratio with 0,5 unit AUTO = 1

512

Man

Set to Man Mode

Set MMI_MAN = 1

Auto

Set to Auto Mode

Set MMI_AUTO = 1

E1

Set to E1 Mode

Set MMI_E1 = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

3.19.1.1 Control and ReducedControl

Presentation:
2

3
4

5
6

7-8

3
4

3BSE 021 945R401

5
6

513

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Range Max

Black

MAX

Range Max of the MV


value

1.2

Range Min

Black

MIN

Range Min of the MV value

2.1

Measured Value
Bargraph

MV

Object value

2.2

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Logical color

AL_F2_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

2.3

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Logical color

AL_F1_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

514

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2.4

Low Limit 1

Default Presentation

RATSTN, Ratio Station

Condition

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Logical color

AL_F1_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

2.5

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Logical color

AL_F2_BLK = 1

Logical color

Unfilled Yellow

blocked Symbol

blocked Symbol

Measured Value

3.1

MV Value

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

The MV object value

? ? ? Red

Black
3.2

MV Unit

Ratio Value

3BSE 021 945R401

AI Error

MV

Measured value

UNIT

Black
4

AI_ERR = 1

Measured unit

The RAT object value

515

RATSTN, Ratio Station

No

Description

4.1

RAT Value

Section 3, Faceplates and Graphic Elements

Default Presentation

Black
4.2

RAT Unit

Output Value

5.1

OUT Value

6.1

BIAS Value

6.2

516

BIAS Unit

Warning Indication Ratio

Warning Indication
Output

Ratio unit

Output value

PO_UNIT

Black
BIAS Value

Ratio value

POUT

OUT Unit

RATIO

The OUT object value

Black
5.2

Remarks

R_UNIT
Black

Condition

Output unit

The BIAS object value


PARAM9
EBIAS = 1

External Bias value

Black

BIAS
EBIAS = 0

Bias value

Black

Ext Black

EBIAS = 1

External Bias

PO_UNIT
EBIAS = 0

Bias unit

Black

RAT=H Yellow

RATIO=HL = 1

Warning for Ratio

RAT=L Yellow

RATIO=LL = 1

OUT=H Yellow

OUT=HL = 1

OUT=L Yellow

OUT=LL =1

Warning for Output

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

3.19.1.2 Limits

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

H2

H2 Black
Black

H1

L1

L2

MVH1

MVL1

L2 Black
Black

3BSE 021 945R401

MVH2

L1 Black
Black

Remarks

H1 Black
Black

Condition

MVL2

517

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

4
5

Behavior:
No

Description

Default Presentation

RAT H

RAT H Black
Black

RAT L

PVUC

PVUG

RATIOL

OUTPH

OUT L Black
Black

518

RATIOH

OUT H Black
Black

Remarks

RAT L Black
Black

"

Condition

OUTPL

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

3.19.1.3 Block

Presentation:

1
2

3
4

Behavior:
No

Description

Default Presentation

Block Alarm 1

Block Alarm L1/H1 Black

Block Alarm 2

Block Printout 1

3BSE 021 945R401

Condition

Yellow

Blocked

Block pressed

AL_F1_BLK = 1

Deblock pressed

AL_F1_BLK = 0

Remarks

Block Alarm L2/H2 Black

Yellow

Blocked

Block pressed

AL_F2_BLK = 1

Deblock pressed

AL_F2_BLK= 0

Block Printout L1/H1


Black

Yellow

Blocked

Block pressed

PRINT_F1_BLK = 1

Deblock pressed

PRINT_F1_BLK = 0

519

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Block Printout 2

Block Printout L2/H2


Black

Condition

Yellow

Blocked

Block pressed

PRINT_F2_BLK = 1

Deblock pressed

PRINT_F2_BLK = 0

Remarks

3.19.2 Object Display


Presentation:
2

34

8
9
10
11

1
5
6

12
13
14
15

20

21
22

16-19

520

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object name and


description

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Green

Normal

3.1

Section Text

Section Grey

3.2

Section Value

Green

4.1

Class Text

Class Grey

4.2

Class Value

Green

Range Max
Green
Range Min

7.1

Measure Value Trim


Curve
Measured Value
Bargraph

3BSE 021 945R401

PROC_SEC

CLASS

Object class

MAX

Range Max of the MV


value

Object value - Trim curve

MV

Green

Range Min of the MV value

MV

Green

Process section
Text in front of the value

MIN
Green

Text in front of the value

Object value - Bargraph

521

RATSTN, Ratio Station

No

Description

7.2

High Limit 2

7.3

522

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.4

Low Limit 1

7.5

Default Presentation

RATSTN, Ratio Station

Condition

Remarks

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

ALARM LIMITS for MV

8.1

MV Text

MV Grey

8.2

Printout Blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked

8.3

Alarm Blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV>H2 = 1

Alarm High limit 2

Red

MV> H2 = 1

8.4

Alarm Indication

3BSE 021 945R401

Alarm limits for MV


Text in front of the line

523

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

8.5

H2 Text

H2 Grey

8.6

H2 Value

Condition

Remarks
Text in front of the value

MVH2
Green

High limit 2 value

9.1

Printout Blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

9.2

Alarm Blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV>H1 = 1

Warning High limit 1

Red

MV> H1 = 1

9.3

Warning Indication

9.4

H1 Text

9.5

H1 Value

H1 Grey

Text in front of the value


MVH1

Green

High limit 1 value

10.1

Printout Blocked

P Yellow

PRINT_F1_BLK = 1

Printout blocked

10.2

Alarm Blocked

B Yellow

AL_F1_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F1_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV<L1 = 1

Warning Low limit 1

Red

MV<L1 = 1

10.3

Warning Indication

10.4

L1 Text

10.5

L1 Value

L1 Grey

Text in front of the value


MVL1

Green

Low limit 1 value

11.1

Printout Blocked

P Yellow

PRINT_F2_BLK = 1

Printout blocked

11.2

Alarm Blocked

B Yellow

AL_F2_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_F2_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_MV<L2 = 1

Alarm Low limit 2

Red

MV<L2 = 1

11.3

11.4

524

Alarm Indication

L2 Text

L2 Grey

Text in front of the value

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

11.5

L2 Value

Default Presentation

Green
12

LIMITATIONS for RAT

12.1

RAT Text

12.2

Warning Indication

12.3

H Text

12.4

H Value

Warning Indication

13.2

L Text

13.3

L Value

LIMITATIONS for OUT

14.1

OUT Text

14.2

Warning Indication

14.3

H Text

14.4

H Value

14.5

Yellow

Warning Indication

15.2

L Text

15.3

L Value

3BSE 021 945R401

MVL2

Low limit 2 value

Text in front of the line


RATIO=HL = 1

H Grey

Yellow

Warning Ratio High


Text in front of the value

RATIOH

Ratio High value

RATIO=LL = 1

L Grey

Warning Ratio Low


Text in front of the value

RATIOL

Ratio Low value

Limitations for OUT

OUT Grey
Yellow

Text in front of the line


OUT=HL = 1

H Grey

Grey

EOLIM = 1

Magenta

EOHL

Magenta

EOLIM = 1

Grey

Yellow

Warning Output High


Text in front of the value

OUTPH

External H value

15.1

Remarks

RAT Grey

Cyan
14

Condition

Limitations for RAT

Cyan
13.1

RATSTN, Ratio Station

OUT=LL = 1

L Grey

Output High value

External Output High value

Warning Output Low


Text in front of the value

OUTPL
Grey

EOLIM = 1

Magenta

Output Low value

525

RATSTN, Ratio Station

No

Description

15.4

External L Value

Section 3, Faceplates and Graphic Elements

Default Presentation

16.2

MV Value

? ? ? Red

Green
MV Unit

RAT Value

18.2

OUT Value

OUT Unit

Text in front of the value

Text in front of the value

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

BIAS Text

BIAS Grey

19.2

BIAS Value

Output value

19.1

Ratio unit

Magenta

X Yellow

Ratio value

PO_UNIT

External OUT Limitation

Measured unit

POUT

18.4

526

Measured value

OUT Grey

Magenta
18.3

MV

R_UNIT
Cyan

OUT Text

AI Error

RATIO

RAT Unit

18.1

AI_ERR = 1

RAT Grey

Cyan
17.3

Text in front of the value

UNIT
Green

17.2

External Output Low value

Grey

MV Grey

RAT Text

EOLL
EOLIM = 1

MV Text

17.1

Remarks

Magenta

16.1

16.3

Condition

Output unit

OUT limited by external


limitation
Text in front of the value

PARAM9
EBIAS = 1

External Bias value

Blue

BIAS
EBIAS = 0

Bias value

Blue

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

No

Description

Default Presentation

Condition

Remarks

19.3

BIAS Unit

Ext Blue

EBIAS = 1

External Bias

PO_UNIT
EBIAS = 0

Bias unit

Blue

MAN = 1

Manual mode

Man Green

MAN = 1

Text behind the indication

Man Grey

20.1

Man indication

20.2

Man Text

20.3

Man Out Text

20.4

Man Out Value

21.1

Auto indication

21.2

Auto Text

21.3

Auto Ratio Text

21.4

Auto Ratio Value

22.1

E1 indication

22.2

E1 Text

22.3

Green filled

OUT Grey
MANOUT

Man Out value

Magenta

MAN = 1

Manual mode

Grey

Green filled

AUTO = 1

Auto mode

Auto Green

AUTO = 1

Text behind the indication

Auto Grey

RAT Grey

Text in front of the value


RATIOREF

Auto Ratio value

Cyan

AUTO = 1

Auto mode

Grey

Green filled

E1 = 1

E1 mode

E1 Green

E1 = 1

Text behind the indication

E1 Grey

E1 Name

3BSE 021 945R401

Text in front of the value

E1NAME
Green

E1 = 1

Grey

User text behind the text


E1

527

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

3.19.3 Graphic Element


3.19.3.1 Numeric, Mode and Unit

Presentation:

1
2

528

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

MV

Object value

? ? ? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

AI_ERR = 1

Signal error

Red

DISTURBANCE = 1

Alarm

Green

Invisible
2

Measured Value

Unit

Object unit
Green

UNIT

Mode

Object mode

M Green

MAN = 1

Manual mode

A Green

AUTO = 1

Auto mode

E1 Green

E1 = 1

E1 mode

External OUT Limitation

External output limitation

X Yellow

(OUT=HL = 1 or OUT=LL=
1) and
EOLIM = 1

External output limitation

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

3BSE 021 945R401

529

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

Presentation:

1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

WRATIO

Object ratio value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Cyan

Invisible
2

Ratio Value

Unit

Object unit
Green

530

R_UNIT

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

Presentation:

1
2

3BSE 021 945R401

531

RATSTN, Ratio Station

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

AL_F1_BLK = 1 or
AL_F2_BLK = 1

Alarm blocked by operator

Logical color FaceplateFg

POUT

Object ratio value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB = 1

Alarm

Magenta

Invisible
Black
2

Output Value

Unit

Object unit
Green

PO_UNIT

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

0, (1..4)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

532

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

RATSTN, Ratio Station

3.19.3.2 BargraphMV01

Presentation:

1
4
5

6
7

Behavior:
No

Description

Default Presentation

Condition

Remarks

1.1

Lock Frame

White

SELECTED = 1

Object frame

Invisible

SELECTED = 0

1.2

Top Left Edge

Light grey

Three Dimensions effect

1.3

Bottom Right Edge

Dark grey

Three Dimensions effect

AI Error

? Red flashing

AI_ERR = 1 and
AL_UNACK = 1

Unacknowledged signal
error

? Red

AI_ERR = 1

Signal error

MV

Object value

AI_ERR = 1

Invisible - I/O Error

Measured Value
-

3BSE 021 945R401

533

RATSTN, Ratio Station

No

Description

3
cont.

534

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Red

DISTURB =1

Alarm

Green

High Limit 2

MVH2

Alarm High limit 2

MVH2 >= MAX

Invisible

Filled Yellow

MV>H2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H2 = 1 and
AU_MV>H2 = 1

Unfilled Red flashing

AU_MV>H2 = 1

Filled Red

MV>H2 = 1

Unfilled Grey

High Limit 1

MVH1

Warning High limit 1

MVH1 >= MAX

Invisible

Filled Yellow

MV>H1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV>H1 = 1 and
AU_MV>H1 = 1

Unfilled Red flashing

AU_MV>H1 = 1

Filled Red

MV>H1 = 1

Unfilled Grey

Low Limit 1

MVL1

Warning Low limit 1

MVL1 <= MIN

Invisible

Filled Yellow

MV<L1 = 1 and
AL_F1_BLK = 1

Logical color
blockedSymbol

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

6
cont.

RATSTN, Ratio Station

Default Presentation

Condition

Remarks

Unfilled Yellow

AL_F1_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L1 = 1 and
AU_MV<L1 = 1

Unfilled Red flashing

AU_MV<L1 = 1

Filled Red

MV<L1 = 1

Unfilled Grey

Low Limit 2

MVL2

Alarm Low limit 2

MVL2 <= MIN

Invisible

Filled Yellow

MV<L2 = 1 and
AL_F2_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_F2_BLK = 1

Logical color
blockedSymbol

Filled Red flashing

MV<L2 = 1 and
AU_MV<L2 = 1

Unfilled Red flashing

AU_MV<L2 = 1

Filled Red

MV<L2 = 1

Unfilled Grey

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Lock Frame

3, (0...5)

FrameStyle

1 Lock Frame

Raised, Flat, Sunken

3BSE 021 945R401

Sunken

535

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

3.20 SEQ, Sequence


3.20.1 Faceplate
Presentation:

536

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

SEQ, Sequence

1
4

Behavior:
No

Description

Default Presentation

Condition

Lock Button

Lock

Name and Description

Name: Name

Remarks

Name: Description
3

Status Field

3.1

Mode

M Un Dark green

MANM= 1 and
UNCOND M= 1

Manual mode

M Dark green

MANM= 1

Manual mode

A Dark green

AUTOM= 1

Auto mode

HOLD Yellow

HOLDM= 1

Hold mode

3.2

Print Blk

P Yellow

TF_PRINT_BLK

Aspect links

Alarm List

position 0, 0, 8

3BSE 021 945R401

537

SEQ, Sequence

No

Description

4
cont.

538

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Object Type Help

position 0, 0, 12

Remarks

Start

Start the Sequence

Set START = 1

Stop

Stop the Sequence

Set START = 0

Man

Set to manual mode

Set MAN = 1

Auto

Set to automatic mode

Set MAN = 0

Hold

Set to hold mode

Set HOLD = 1

Step

Step the Sequence one


step

Set STEP = 1

Res

Reset the Sequence to


initial values

Set RESET = 1

Jump

Jump to step JPOSN_OUT

Set JUMP = 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

SEQ, Sequence

3.20.1.1 Control and ReducedControl

Presentation:

2
3
5

Behavior:
No

Description

Run Status Indication

Default Presentation
Green

Condition

Remarks

INTERLOCK (SEQ_RFS)
= 1 and

Not Ready for Start

RUN = 0
Green

HOLDM= 1

RUN = 1
Green flashing

3BSE 021 945R401

and

Not-Completed

BUSY
(SEQ_COMPLETE)= 1

539

SEQ, Sequence

No

Description

Section 3, Faceplates and Graphic Elements

Default Presentation

1
cont.

Condition

Green

RUN = 1

Green

RUN = 0

M Un Green

MANM = 1 and

Remarks

Manual mode

UNCOND M= 1

M Green

MANM = 1

Manual mode

A Green

AUTOM = 1

Auto mode

HOLD Yellow

HOLDM = 1

Hold mode

POSN : STEPNAME

Current step number and


name

Current Step Number


and Name
Black

POSN <> 0

Information Text

INFTXT
Black

BLANKINF = 0

Information Value

Alarm Text:

Interlock Info Text

Information text

INFVAL

Information value

Black

BLANKINF = 0 and
INFTXT <>

? ? ? Yellow flashing

DI2_RP_F_BLK = 1

Repeat fail block

DI1_AL_BLK = 1 or
DI1_AL_P_BLK = 1

Alarm blocked by operator


or Alarm blocked by PCprogram

Jump Error

Red

TS_POSN_F = 1

Seq. Time

Red

TS_SEQAL = 1

Step Time

Red

TS_STEPAL = 1

Next Step Enabled

NXTCOND = 1

Green

540

CONDTXT1

CONDTXT1 <> and

Yellow

CONDSTA1 = 0

CONDTXT2

CONDTXT2 <> and

Yellow

CONDSTA2 = 0

Condition 1 exists but is


not satisfied
Condition 2 exists but is
not satisfied

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

5
cont.

SEQ, Sequence

Default Presentation

Condition

Remarks

CONDTXT3

CONDTXT3 <> and

Yellow

CONDSTA3 = 0

Condition 3 exists but is


not satisfied

CONDTXT4

CONDTXT4 <> and

Yellow

CONDSTA4 = 0

CONDTXT5

CONDTXT5 <> and

Yellow

CONDSTA5 = 0

CONDTXT6

CONDTXT6 <> and

Yellow

CONDSTA6 = 0

CONDTXT7

CONDTXT7 <> and

Yellow

CONDSTA7 = 0

CONDTXT8

CONDTXT8 <> and

Yellow

CONDSTA8 = 0

Condition 4 exists but is


not satisfied
Condition 5 exists but is
not satisfied
Condition 6 exists but is
not satisfied
Condition 7 exists but is
not satisfied
Condition 8 exists but is
not satisfied

3.20.1.2 Block

Presentation:

1
2
3
4
5

3BSE 021 945R401

541

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

Behavoir:
No

Description

Default Presentation

Block Command

Block Command Black

Block Alarm

Yellow

Blocked

Block pressed

BLOCKED = 1

Deblock pressed

BLOCKED = 0

Block Printout

Block I/P Event

DI1_AL_BLK = 1 and
TF_AL_BLK = 1

Deblock pressed

DI1_AL_BLK = 0 and
TF_AL_BLK = 0

Block Printout Black

Block I/P Printout

DI1_PR_BLK = 1 and
TF_PR_BLK = 1

Deblock pressed

DI1_PR_BLK = 0 and
TF_PR_BLK = 0

Block I/P Event Black


Blocked

Block pressed

PT_AL_BLK = 1 and
SI_AL_BLK = 1

Deblock pressed

PT_AL_BLK = 0 and
SI_AL_BLK = 0

Block I/P Printout Black

Yellow

542

Blocked

Block pressed

Yellow

Blocked

Block pressed

Yellow

Remarks

Block Alarm Black

Yellow

Condition

Blocked

Block pressed

PT_PR_BLK = 1 and
SI_PR_BLK = 1

Deblock pressed

PT_PR_BLK = 0 and
SI_PR_BLK = 0

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

SEQ, Sequence

3.20.1.3 Parameters

Presentation:

1
2
3
4

Behavior:
No

Description

Default Presentation

Manual Mode

Manual Mode Black

Condition

Yellow

Blocked

Unconditional pressed

UNCONDM / UNCOND= 1

Conditional pressed

UNCONDM / UNCOND= 0

Jump pos

Dialog for changing


JPOSN_OUTP, value black

JPOSN_OUTP/JPOSN

No of Turns

Dialog for changing


NO_OF_TURNS_OUTP/

NO_OF_TURNS_OUTP/

Remarks

NO_OF_TURNS

NO_OF_TURNS, value black


4

Interval Time

Dialog for changing


INTERV_TIME_DEL/

INTERV_TIME_DEL/
INTERV_TIME

INTERV_TIME, value black

3BSE 021 945R401

543

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

3.20.2 Object Display


Presentation:
2

3-4

35-40
41-42

5
6

1
21
22

7
8
9
10
11

23
25
26-34

12
13
14
24
15
16

20

19

17-18

43-44

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Khaki

SELECTED = 0

Logical color (static)

NAME and DESCR

Object name and


description

544

Header

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

2
cont.

Default Presentation

Condition

Remarks

Red flashing

DI2_ALARM_UNACK = 1
or
AU_POSN_F = 1 or
AU_SERVUC = 1 or
AU_SEQAL = 1 or
AU_STEPAL = 1

Unacknowledged alarm

Yellow

BLOCKED =1

Command blocked

Red

DI2_DIST = 1

Alarm

Green

Normal

3.1

Section Text

Section Khaki

3.2

Section Value

Green

4.1

Class Text

Class Khaki

4.2

Class Value

Green

Sequence Time Out

5.1

Alarm Blocked

5.2

5.3

Step Time Out

6.1

Alarm Blocked

6.2

6.3

Alarm Indication

Step Time Out Text

3BSE 021 945R401

Text in front of the value


PROC_SEC

Process section
Text in front of the value

CLASS

Object class
Sequence Time Out

B Yellow

TF_ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

TF_ALARM_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_SEQAL = 1

Unacknowledged alarm

Red

TS_SEQAL = 1

Alarm

Alarm Indication

Sequence Time Out Text

SEQ, Sequence

Sequence Time Out

Text for Sequence Time Out

Red

AU_SEQAL = 1 or
TS_SEQAL = 1

Khaki

Step Time Out

B Yellow

TF_ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

TF_ALARM_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_STEPAL = 1

Unacknowledged alarm

Red

TS_STEPAL = 1

Alarm

Step Time Out

Text for Step Time Out

545

SEQ, Sequence

No

Description

6.3
cont.

Jump Error

7.1

Alarm Blocked

7.2

7.3

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Red

AU_STEPAL = 1 or
TS_STEPAL = 1

Khaki

Jump Error

B Yellow

TF_ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

TF_ALARM_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_POSN_F = 1

Unacknowledged alarm

Red

TS_POSN_F = 1

Alarm

Alarm Indication

Jump Error Text

Command Blocking

8.1

Command Block
Indication

8.2

Command Text

Remarks

Jump Error Red

Text for Jump Error

Red

AU_POSN_F = 1 or
TS_POSN_F = 1

Khaki

Command blocking

Yellow

BLOCKED = 1

Command

Command blocked
Text for Command

Yellow

BLOCKED = 1

Khaki

Alarm Blocking

9.1

Printout Blocked

P Yellow

DI1_PRINT_BLK = 1 and
TF_PRINT_BLK = 1

Printout blocked

9.2

Alarm Blocked

B Yellow

TF_ALARM_BLK = 1

Alarm blocked by operator

Bx Yellow

TF_ALARM_P_BLK = 1

Alarm blocked by PCprogram

9.3

Alarm Text

10

Event Blocking

10.1

Printout Blocked

546

Alarm blocking

Alarm Grey

Text for Alarm


Event blocking

P Yellow

PT_PRINT_BLK = 1 and
SI_PRINT_BLK = 1

Printout blocked

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

SEQ, Sequence

No

Description

Default Presentation

Condition

Remarks

10.2

Event Blocked

B Yellow

PT_ALARM_BLK = 1 and
SI_ALARM_BLK = 1

Alarm blocked

10.3

Event Text

Event Grey

11.1

Repeat Fail Block


Indication

11.2

Repeat Fail Block Text

Yellow flashing

Text for REPEAT FAIL


BLOCK

Yellow

DI2_REPEAT_FAIL_BLK =
1

Khaki

SEQUENS TIMES

12.1

Max Sequence Time Text

Max Time Khaki

12.2

Max Sequence Time

Green

12.3

Elapsed Sequence Time


Text

Elapsed Time Khaki

12.4

Elapsed Sequence Time

Green

13

STEP TIMES

13.1

Max Step Time Text

Max Time Khaki

13.2

Max Step Time

Green

13.3

Elapsed Step Time Text

Elapsed Time Khaki

13.4

Elapsed Step Time

Green

14

INTERVAL TIMES

14.1

Max Interval Time Text

Max Time Khaki

14.2

Max Interval Time

Green

14.3

Elapsed Interval Time


Text

Elapsed Time Khaki

14.4

Elapsed Interval Time

Green

SEQUENS TIMES
Max Time Text
SEQTD

Max Sequence Time


Elapsed Time Text

SEQTE

Elapsed Sequence Time


STEP TIMES
Max Time Text

STEPTD

Max Step Time


Elapsed Time Text

STEPTE

Elapsed Step Time


INTERVAL TIMES

NO OF TURNS
Number of Turns Text

DI2_REPEAT_FAIL_BLK = Repeat fail blocked


1

REPEAT FAIL
BLOCK

12

15.1

Text for Event

Max Time Text


INTV_TDO

Max Interval Time


Elapsed Time Text

INTERV_TIME_EL

Elapsed Interval Time


NO OF TURNS

Number of Turns

Number of Turns Text

Khaki

3BSE 021 945R401

547

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

15.2

Number of Turns

Green

NO_OF_TURNS_OUTP

Number of Turns

16.1

Actual Turn Text

Actual Turn Khaki

16.2

Actual Turn

Green

17.1

Jump to Step Text

Jump to Step Khaki

17.2

Jump to Step Value

Actual Turn Text


ACT_TURN

Actual Turn
Jump to Step Text

JPOSN_OUTP
Khaki

MAN = 1

MAN = 0

18.1

Change to Step Text

Change to Step Khaki

18.2

Change to Step Value

Green

19

Run Status Indication

Green

Jump to Step Value

Invisible
Change to Step Text

NEXTSTEP

Change to Step Value

INTERLOCK = 1 and

Not Ready for Start

RUN = 0
Green

HOLD = 1

RUN = 1

and

Not-Completed

BUSY = 1
Green flashing

M Un

Green

RUN = 1

Green

RUN = 0

Green

MANM= 1 and

Manual mode

UNCONDM= 1

Green

MANM= 1

Manual mode

AUTOM= 1

Auto mode

Yellow

HOLDM= 1

Hold mode

Green filled

MANM= 1

Manual mode

Man Green

MANM= 1

Man text behind the


indication

Man Khaki

MANM= 0

Uncond Green

UNCONDM= 1

Green

HOLD
20.1

548

Manual Mode Indication

Manual unconditional mode

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

20.2

Auto mode

Default Presentation

Auto

Condition

Remarks

Green filled

AUTOM= 1

Auto mode

Green

AUTOM = 1

Auto text behind the


indication

Auto Khaki
20.3

21

Hold mode

Yellow filled

AUTOM= 0
HOLDM= 1

Hold mode

Hold Yellow

HOLDM = 1

Hold text behind the


indication

Hold Khaki

HOLDM = 0

Previous Step Text

Previous Step Khaki

PREPOS <> 0

Previous Step Text

Previous Step Box

Filled background Black

PREPOS <> 0

Invisible when PREPOS = 0

PREPOS : PRENAME

Previous step number and


name

Previous Step Number


and
Name
Green
22.1

Information Text

Information Khaki

22.2

Information Box

Filled background Black

22.3

Information Text
Green

22.4

SEQ, Sequence

Information Value

Information Text
BLANKINF = 0 and
INFTXT <>

Invisible when BLANKINF =


1

INFTXT

Information text

BLANKINF = 0 and
INFTXT <>
INFVAL

Green
23.1

Current Step Text

Current Step Khaki

23.2

Current Step Box

Filled background Black

23.3

Current Step Number


and Name
Green

24.1

Next Step Text

Next Step Khaki

24.2

Next Step Box

Filled background Black

3BSE 021 945R401

PREPOS <> 0

Information value

BLANKINF = 0 and
INFTXT <>
Current Step Text
POSN <> 0

Invisible when POSN = 0

POSN : STEPNAME

Current step number and


name

POSN <> 0
Next Step Text
NXTPOS <> 0

Invisible when NXTPOS = 0

549

SEQ, Sequence

No

Description

24.3

Next Step Number and


Name

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

NXTPOS : NXTNAME

Next step number and


name

Green

NXTPOS <> 0

Transitions
Condition Khaki

any CONDTXT# <>

Transitions Condition Text


Invisible when no
CONDTXT#

25.1

Transitions Condition
Text

25.2

Transition Condition Box Filled background Black

any CONDTXT# <>

26.1

Transition Condition 1
Ind.

Green

CONDSTA1 = 0

Green

CONDSTA1 = 1

26.2

Transition Condition 1
Text

CONDTXT1 Green

27.1

Transition Condition 2
Ind.

Green

CONDSTA2 = 0

Green

CONDSTA2 = 1

27.2

Transition Condition 2
Text

CONDTXT2 Green

28.1

Transition Condition 3
Ind.

Green

CONDSTA3 = 0

Green

CONDSTA3 = 1

28.2

Transition Condition 3
Text

CONDTXT3 Green

29.1

Transition Condition 4
Ind.

Green

CONDSTA4 = 0

Green

CONDSTA4 = 1

29.2

Transition Condition 4
Text

CONDTXT4 Green

30.1

Transition Condition 5
Ind.

Green

CONDSTA5 = 0

Green

CONDSTA5 = 1

30.2

Transition Condition 5
Text

CONDTXT5 Green

31.1

Transition Condition 6
Ind.

Green

CONDSTA6 = 0

Green

CONDSTA6 = 1

Transition Condition 6
Text

CONDTXT6 Green

31.2

550

CONDTXT1 <>

CONDTXT2 <>

CONDTXT3 <>

CONDTXT4 <>

CONDTXT5 <>

CONDTXT6 <>

Invisible when no
CONDTXT1

Invisible when no
CONDTXT2

Invisible when no
CONDTXT3

Invisible when no
CONDTXT4

Invisible when no
CONDTXT5

Invisible when no
CONDTXT6

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

32.1

Transition Condition 7
Ind.

Green

CONDSTA7 = 0

Green

CONDSTA7 = 1

32.2

Transition Condition 7
Text

CONDTXT7 Green

33.1

Transition Condition 8
Ind.

Green

CONDSTA8 = 0

Green

CONDSTA8 = 1

33.2

Transition Condition 8
Text

CONDTXT8 Green

34.1

Next Step Enabled


Indication

34.2

Next Step Enabled Text

Default Presentation

SEQ, Sequence

Condition

CONDTXT7 <>

CONDTXT8 <>

Green

NXTCOND = 0

Green

NXTCOND = 1

Next Step Enabled

Remarks

Invisible when no
CONDTXT7

Invisible when no
CONDTXT8

Next Step Enabled Text

Green
34.3

Next Step Enabled Box

Filled background

Next Step Enabled Box

Black
35.1

Activities Text

Activities Khaki

35.2

Activities Box

Filled background Black

36.1

Activity 1 Indication

36.2

Activity 1 Text

37.1

Activity 2 Indication

37.2

Activity 2 Text

38.1

Activity 3 Indication

38.2

Activity 3 Text

39.1

Activity 4 Indication

39.2

Activity 4 Text

3BSE 021 945R401

Activities Text
any ACTTXT# <>

Green

ACTSTA1 = 0

Green

ACTSTA1 = 1

ACTTXT1 Green

ACTTXT1 <>

Green

ACTSTA2 = 0

Green

ACTSTA2 = 1

ACTTXT2 Green

ACTTXT2 <>

Green

ACTSTA3 = 0

Green

ACTSTA3 = 1

ACTTXT3 Green

ACTTXT3 <>

Green

ACTSTA4 = 0

Green

ACTSTA4 = 1

ACTTXT4 Green

ACTTXT4 <>

Invisible when no ACTTXT#

Invisible when no ACTTXT1

Invisible when no ACTTXT2

Invisible when no ACTTXT3

Invisible when no ACTTXT4

551

SEQ, Sequence

No

Description

40.1

All Activities Indication

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Green

ALLACT = 0

Green

ALLACT = 1

Remarks

40.2

All Activities Text

All Activities Grey

All Activities Text

40.3

All Activities Box

Filled Background

All Activities Box

Black
41

Jump Cond and Step


Text

Jump Cond and


Step Khaki

41.1

Jump Condition 1 Box

Filled background

Jump Cond and Step Text


JCTXT1 <>

Hollow when no JCTXT1

Black
41.2

Jump Condition 1
Indication

41.3

Jump Condition 1 Text

41.4

Jump Step 1 Number and


Name

42.1

Jump Condition 2 Box

JCTXT1

Green

JCSTA1 = 0

Green

JCSTA1 = 1

Green

JCTXT1 <>

Invisible when no JCTXT1

JPOS1 : JNAME1

Jump step number and


name

Green

JCTXT1 <> 0

Invisible when no JCTXT1

Filled background

JCTXT2 <>

Hollow when no JCTXT2

Black
42.2

Jump Condition 2
Indication

42.3

Jump Condition 2 Text

42.4

Jump Step 2 Number and


Name

JCTXT2

Green

JCSTA2 = 0

Green

JCSTA2 = 1

Green

Green
43.1

Jump Condition 3 Box

Filled background

JCTXT2 <>

Invisible when no JCTXT2

JPOS2 : JNAME2

Jump step number and


name

JCTXT2 <> 0

Invisible when no JCTXT2

JCTXT3 <>

Hollow when no JCTXT3

Black
43.2

43.3

552

Jump Condition 3
Indication
Jump Condition 3 Text

JCTXT3

Green

JCSTA3 = 0

Green

JCSTA3 = 1

Green

JCTXT3 <>

Invisible when no JCTXT3

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

43.4

Jump Step 3 Number and


Name

44.1

Jump Condition 4 Box

Default Presentation

SEQ, Sequence

Condition

Remarks

JPOS23 : JNAME3

Jump step number and


name

Green

JCTXT3 <> 0

Invisible when no JCTXT3

Filled background

JCTXT4 <>

Hollow when no JCTXT4

Black
44.2

Jump Condition 4
Indication

44.3

Jump Condition 4 Text

44.4

Jump Step 4 Number and


Name

JCTXT4

Green

Green

JCSTA4 = 0

Green

JCSTA4 = 1

Green

JCTXT4 <>

Invisible when no JCTXT4

JPOS4 : JNAME4

Jump step number and


name

JCTXT24 <> 0

Invisible when no JCTXT4

3.20.3 Graphic Element


3.20.3.1 Indicator01

Presentation:

1
2

3BSE 021 945R401

553

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Dotted Yellow

DI1_ALARM_BLK = 1

Alarm blocked by operator

ModeVisible = true

Object mode

M Green

MANM= 1

Manual mode

A Green

AUTOM =1

Auto mode

H Yellow

HOLDM =1

Hold mode

ModeVisible = false

Mode is invisible

Green

INTERLOCK (SEQ_RFS)
= 1 and
RUN = 0

Not Ready for Start

Green

HOLDM= 1

Invisible
2

Mode

Run Status Indication

RUN = 1 and

Not-Completed

BUSY
(SEQ_COMPLETE)= 1

Green flashing
Green

RUN = 1

Green

RUN = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ModeVisible

2. Mode

true, false

554

Mode string is visible

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

SEQ, Sequence

3.20.3.2 CurrentStepNumberName01

Presentation:

Behavior:
No

Description

Current Step Number

Default Presentation

Condition

Remarks
Current Step Number

POSN
Green

Invisible when POSN = 0

POSN <> 0

Current Step Name

Current Step Name


Green

STEPNAME

3BSE 021 945R401

555

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

3.20.3.3 ObjectLine01

Presentation:
1

12

10

11

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Invisible

SELECTED = 0

556

Header

Run Status Indication

NAME and DESCR

Object name and


description

Red flashing

DI2_ALARM_UNACK = 1 or Unacknowledged alarm


AU_POSN_F = 1 or
AU_SERVUC = 1 or
AU_SEQAL = 1 or
AU_STEPAL = 1

Yellow

BLOCKED =1

Command blocked

Red

DI2_DIST = 1

Alarm

Green

Normal

Green

INTERLOCK (SEQ_RFS) =
1 and RUN = 0

Not Ready for Start

Green

HOLDM= 1

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

SEQ, Sequence

Default Presentation

3
cont.

RUN = 1

Green

RUN = 1

Green

RUN = 0

Not-Completed

MAN M= 1 and
UNCONDM= 1

Manual mode

M Green

MANM= 1

Manual mode

A Green

AUTOM= 1

Auto mode

HOLD Yellow

HOLDM= 1

Hold mode

Printout Blocked

P Yellow

TF_PRINT_BLK = 1

Printout blocked

Alarm Blocked

B Yellow

DI1_ALARM_BLK = 1

Alarm blocked by operator

Bx

DI1_ALARM_P_BLK = 1

Alarm blocked by PCprogram

DI2_DIST = 1

Alarm

INFTXT

Information text

BLANKINF = 0

Invisible when BLANKINF


=1

INFVAL

Information value

Khaki

BLANKINF = 0 and INFTXT


<>

Invisible when BLANKINF


=1

? ? ? Yellow flashing

DI2_REPEAT_FAIL_BLK =
1

Repeat fail block

DI1_ALARM_BLK = 1 or
DI1_ALARM_PERIOD_BLK
=1

Alarm blocked by operator


or Alarm blocked by PCprogram

Yellow

F Red

Information Text
Khaki

and

M Un Green

Mode

Fault Indication
6

Remarks

BUSY (SEQ_COMPLETE)=
1

Green flashing

Condition

Information Value

Alarm Text

3BSE 021 945R401

Jump Error

Red

TS_POSN_F = 1

Seq. Time

Red

TS_SEQAL = 1

Step Time

Red

TS_STEPAL = 1

557

SEQ, Sequence

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Interlock Info Text

Next Step Enabled

NXTCOND = 1

Remarks

Green

10

Command Blocked

11

Current Step Name

CONDTXT1
Yellow

CONDTXT1 <> and


CONDSTA1 = 0

Condition 1 exists but is


not satisfied.

CONDTXT2
Yellow

CONDTXT2 <> and


CONDSTA2 = 0

Condition 2 exists but is


not satisfied.

CONDTXT3
Yellow

CONDTXT3 <> and


CONDSTA3 = 0

Condition 3 exists but is


not satisfied

CONDTXT4
Yellow

CONDTXT4 <> and


CONDSTA4 = 0

Condition 4 exists but is


not satisfied

CONDTXT5
Yellow

CONDTXT5 <> and


CONDSTA5 = 0

Condition 5 exists but is


not satisfied

CONDTXT6
Yellow

CONDTXT6 <> and


CONDSTA6 = 0

Condition 6 exists but is


not satisfied

CONDTXT7
Yellow

CONDTXT7 <> and


CONDSTA7 = 0

Condition 7 exists but is


not satisfied

CONDTXT8
Yellow

CONDTXT8 <> and


CONDSTA8 = 0

Condition 8 exists but is


not satisfied

BL Yellow

BLOCKED = 1

Command blocked

STEPNAME

Invisible when POSN = 0

Green
12

Current Step Number

POSN
Green

558

POSN <> 0
Invisible when POSN = 0

POSN <> 0

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

TEXT, Text data

3.21 TEXT, Text data


3.21.1 Faceplate
Presentation:
2

1
3

Behavior:
No

Description

Object lock button

Name and Description

Status Field

3.1

Mode

3BSE 021 945R401

Default Presentation

Condition

M Dark green

MAN = 1

A Dark green

MAN = 0

Remarks

559

TEXT, Text data

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Aspect Links

Object Display

Condition

Remarks

Object Type Help


5

Man

Set to Manual Mode

Set MAN = 1

Auto

Set to Automatic Mode

Set MAN = 0

On

Set VALUE to one

MAN = 1 and ORD_BLK =


0

Set BOOLEAN = 1

Off

Set VALUE to zero

MAN = 1 and ORD_BLK =


0

Set BOOLEAN = 1

3.21.1.1 Control

Presentation:

560

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

TEXT, Text data

Behavior:
No

Description

Value Text

Default Presentation

Condition

Remarks

TEXT

The object Text value

BLANKT = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Black

Value Integer Long

INT_LONG

The object IL value

BLANKIL = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Black

Value Boolean

BOOLEAN

The object Boolean value

BLANKB = 1

Invisible

BOOLEAN =1

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Black

Value real

3BSE 021 945R401

REAL

The object Real value

BLANKR = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Black

561

TEXT, Text data

Section 3, Faceplates and Graphic Elements

3.21.2 ObjectDisplay
Presentation:
1

2
3
4

Behavior:
No

Description

Lock Frame

Header

Mode

562

Default Presentation

Condition

Remarks
Object select frame

White

SELECTED = 1

Only for overlap

Grey

SELECTED = 0

static

Green

NAME

The object name


The object mode

M Green

MAN = 1

Manual mode

A Green

MAN = 0

Auto mode

TEXT

The object Text value

BLANKT = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

Value Text

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Value Integer Long

Default Presentation

Condition

Remarks

INT_LONG

The object IL value

BLANKIL = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

Value Boolean

BOOLEAN

The object Boolean value

BLANKB = 1

Invisible

BOOLEAN =1

BOOLEAN =0

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

Value real

3BSE 021 945R401

TEXT, Text data

REAL

The object Real value

BLANKR = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

563

TEXT, Text data

Section 3, Faceplates and Graphic Elements

3.21.3 Graphic Element


3.21.3.1 SingleLineText01

Presentation:

1
2

3.21.3.2 MultiLineText01

Presentation:
1
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

564

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Value

Default Presentation

TEXT, Text data

Condition

Remarks

TEXT

The object value

BLANKT = 1

Invisible

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

Configuration:.
Parameters

Affects

Options (bold is default) Remarks

Alignment

2. Value

0 = Left, 1 = Right
2 = Center

Alignment of text in field

NumberOfChar

2. Value

72, (1..72)

Number of total character


that the field could contain.

Font

2. Value

10 point

3.21.3.3 NumericString01

Presentation:
1
2

3BSE 021 945R401

565

TEXT, Text data

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

Values

The object values


REAL

DataType = 0

INT_LONG

DataType = 1

BOOLEAN

DataType = 2

No Datatype Green

BLANKx = 1

Red flashing

COLOR2 = 1

Red

COLOR1 = 1

Green

Invisible, x = IL,R, or T *

Configuration:.
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1. Lock Frame

3, (0...5)

FrameStyle

1. Lock Frame

Flat, Raised, Sunken

DataType

2. Value

0 = Real,
1 = Int Long,
2 = Boolean

566

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

VALVECON, Valve Control

3.22 VALVECON, Valve Control


3.22.1 Faceplate
Presentation:

3BSE 021 945R401

567

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

1
3

Behavior:
No

Description

Lock Button

Name and Description

Status Field

3.1

Mode

3.2

568

Control point

Default Presentation

Condition

M Dark green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

A Dark green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

S Dark green

IND2_04 = 1

Remarks

Sequence controller from


groupstart

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3.2
cont.

VALVECON, Valve Control

Default Presentation

Condition

Remarks

C Dark green

IND2_04 = 0 and
IND2_03 = 0 and
IND2_02 = 0 and
IND2_01 = 0

Control controlled from


operators panel

L Dark green

IND2_01 = 1

Local controlled from local


panel

T Yellow

IND2_2 = 1

Test, jog running from


motor place

O Kakhi

IND2_3 = 1

Out of service. No control


possible.

3.3

Print Blk

P Black

PRINT_BLK

3.4

Interlock Indication

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11= 1 or
(IND2_13 = 1 and
IND1_12 = 0) or
(IND2_00 = 0 and
(IND2_10 = 1 or
(IND2_12 = 1 and
IND1_12 = 0)))

Safety interlock or

BX Green

IND2_15 = 1

Override interlocks

BX Yellow

IND2_00 = 1

Override interlock

Alarm List

position 0, 0, 8

Event List

position 0, 0, 9

Object Display

position 5, 5, 10

Trend Display

position 6, 6, 11

Object Type Help

position 0, 0, 12

Aspect links

Green

Operator interlock

Op

Open Value

Set MORD_08 = 1

Cl

Close Value

Set MORD_09 = 1

Man

Set to Man Mode

Set MORD_05 = 1

Auto

Set to Auto Mode

Set MORD_04 = 1

Seq

Set to Sequence Control

Set MORD_10 = 1

Cen

Set to Central Control

Set MORD_03 = 1

3BSE 021 945R401

569

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

Condition

Remarks

5
cont.

Lock

Set to Local Control

Set MORD_00 = 1

Test

Set to Test Control

Set MORD_01 = 1

OoS

Set to Out of Service


Control

Set MORD_02 = 1

3.22.1.1 Control and ReducedControl

Presentation:

1
3
2

Behavior:
No

Description

Default Presentation

Condition

Remarks

Error 1

PEO Red flashing

AU_IND1_02=1

Unack Position Error Open

PEC Red flashing

AU_IND1_03=1

Unack Position Error Close

570

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

1
cont.
2

3.1

Error 2

VALVECON, Valve Control

Default Presentation

Condition

Remarks

PEO Red

IND1_02=1

Position Error Open

PEC Red

IND1_03=1

Position Error Close

Fault 1 Red flashing

AU_IND1_00=1

Unacknowledged Fault 1

Fault 2 Red flashing

AU_IND1_01=1

Unacknowledged Fault 2

Fault 1 Red

IND1_00=1

Fault 1

Fault 2 Red

IND1_01=1

Fault 2

IND2_07 = 0

Not ready for start

Valve Status
Green
(IND1_13 = 1 or
IND1_12 = 1) and
IND1_15 = 1

No limit position

IND1_07 = 1

Limit position

IND1_07 = 0 and
IND1_15 = 0

No limit position

Green

IND2_07 = 1 and
IND2_14 = 1

A-Interlock

Green
Grey

IND2_03 = 1

Out of service

Green

INDI_07 = 1 / PRES_A

User defined text

Green flashing

Green

3.2

Valve Text

INDI_11 = 1 / PRES_B
4

Act Pres Text

3BSE 021 945R401

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

571

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

3.22.1.2 Block

Presentation:

Behavior:
No

Description

Default Presentation

Override Interlock

Override Interlock Black

Block Alarm

Block Printout

Remarks
IND2_00 Indicates current
status

Yellow

Blocked

Overide pressed

MORD_06 = 1

Normal pressed

MORD_07 = 0

Block Alarm Black

Yellow

Blocked

Block pressed

AL_BLK = 1

Deblock pressed

AL_BLK = 0

Block Printout Black

Yellow

572

Condition

Blocked

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

3
cont.

VALVECON, Valve Control

Default Presentation

Condition

Block pressed

PR_BLK = 1

Deblock pressed

PR_BLK = 0

Remarks

3.22.2 Object Display


Presentation:

1
6
7
8
9

2
3
5

10
11
4

12
13

28
27

14
15
16
17
18

26

21-25

3BSE 021 945R401

19-20

573

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Grey

SELECTED = 0

Header

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

Normal

Range Max

Green

User defined text for open


position

Range Min

Green

User defined text for close


position

Trim Curve
ALARMS

Green

Curve shows the valve


position
Alarms

6.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

6.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_00 = 1

Unacknowledged alarm

Red

IND1_00 = 1

Alarm

Fault 1

TXT_BLK_00 = 0

User defined Fault 1

Red

IND1_00 = 1 or
AU_IND1_00 = 1

Grey

6.3

6.4

Warning Indication

Alarm 1 Text

7.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

7.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

574

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

7.3

Warning Indication

7.4

Alarm 2 Text

Default Presentation

VALVECON, Valve Control

Condition

Remarks

Red flashing

AU_IND1_01 = 1

Unacknowledged alarm

Red

IND1_01 = 1

Alarm

Fault 2

TXT_BLK_01 = 0

User defined Fault 2

Red

IND1_01 = 1 or
AU_IND1_01 = 1

Grey

8.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

8.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_02 = 1

Unacknowledged alarm

Red

IND1_02 = 1

Alarm

PEO

TXT_BLK_02 = 0

PEO Position Error Open

Red

IND1_02 = 1 or
AU_IND1_02 = 1

Grey

8.3

8.4

Warning Indication

Alarm 3 Text

9.1

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

9.2

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

Red flashing

AU_IND1_03 = 1

Unacknowledged alarm

Red

IND1_03 = 1

Alarm

PEC

TXT_BLK_03 = 0

PEC Position Error closed

Red

IND1_03 = 1 or
AU_IND1_03 = 1

Grey

9.3

9.4

Warning Indication

Alarm 4 Text

INTERLOCKS
10.1

IC1 Active

10.2

IC1 Text

3BSE 021 945R401

Interlocks
Yellow

C-Interlock 1 Grey

IND2_08 = 1

Safety Interlock IC1 active


Safety Interlock IC1

575

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

11.1

IC2 Active

11.2

IC2 Text

C-Interlock 2 Grey

12.1

IB2 Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

12.2

IB2 Active

Yellow

IND2_11 = 1

Interlock IB2 active

12.3

IB2 Text

Green

IB2_TXT

Interlock text IB2

13.1

IB4 Block Indication

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

13.2

IB4 Active

Yellow

IND2_13 = 1

Interlock IB4 active

13.3

IB4 Text

Green

IB4_TXT

Interlock IB4 text

14.1

IB1 Blocked

BX Red

IND2_15 = 1 and
(IND2_00 = 1 or IND2_02
= 1)

Override Interlock and


Interlock IB1 active

BX Yellow

IND2_00 = 1 or IND2_02 =
1

Test mode. Interlock


blocked

IND2_10 = 1

Interlock IB1 active

Yellow

Yellow

Condition

Remarks

IND2_09 = 1

Safety Interlock IC2 active


Safety Interlock IC2

14.2

IB1 Active

14.3

IB1 Text

Green

IB1_TXT

Interlock IB1 text

15.1

IB3 Blocked

BX Red

IND2_15 = 1 and
(IND2_00 = 1 or IND2_02
= 1)

Override Interlock and


Interlock IB3 active

BX Yellow

IND2_00 = 1 or IND2_02 =
1

Test mode. Interlock


blocked

IND2_12 = 1

Interlock IB3 active

15.2

IB3 Active

Yellow

15.3

IB3 Text

Green

IB3_TXT

Interlock IB3

16.1

IA Blocked

BX Yellow

IND2_02 = 1

Test mode. Interlock


blocked

16.2

IA Active

Yellow

IND2_14 = 1

Interlock IA active

16.3

IA Text

IA_TXT

Interlock IA text

Green

STATUS
17.1

Implemented Indication

17.2

Implemented Text

576

Status
Green

Implemented Grey

ACT = 1
Implemented

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

18.1

Repeat Fail Blocked


Indication

18.2

Repeat Fail Blocked Text

19.1

Default Presentation
Yellow

VALVECON, Valve Control

Condition

Remarks

REPEAT_BLK = 1

The motor can be


controlled

Repeat Fail Blk

Repeat Fail Blocked

Yellow

REPEAT_BLK = 1

Grey

Valve Open Status


IND2_07 = 0

Not ready for start

IND1_12 = 1 and
IND1_15 = 1

Open
No limit position open

IND1_07 = 1

Limit position open

IND1_07 = 0 and
IND1_15 = 0

No limit position open

Green

IND2_07 = 1 and
IND2_14 = 1

A-Interlock

Green
Grey

IND2_03 = 1

Out of service

Green

PRES_A

User defined text

Green

Green flashing

Green

19.2

Valve Open Text

3BSE 021 945R401

577

VALVECON, Valve Control

No

Description

20.1

Valve Close Status

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

IND2_07 = 0

Not ready for start

IND1_13 = 1 and
IND1_15 = 1

Close
No limit position close

IND1_11 = 1

Limit position close

IND1_11 = 0 and
IND1_15 = 0

No limit position close

Green

IND2_07 = 1 and
IND2_14 = 1

A-Interlock

Green
Grey

IND2_03 = 1

Out of service

Green

PRES_B

User defined text

IND2_04 = 1

Sequence Controlled
from groupstart

Green

Green flashing

Green

20.2

Valve Close Text

21.1

Sequence Indication

21.2

Sequence Text

22.1

Central Indication

22.2

Central Text

23.1

578

Local Indication

Green

Sequence
Green

IND2_04 = 1

Grey

Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central Controlled
from operators place

Central
Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Grey

Green

IND2_01 = 1

Local
Controlled from local panel

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

23.2

Local Text

Local

24.1

Test Indication

24.2

Test Text

25.1

Out of Service Indication

25.2

Out of Service Text

26.1

Blocking Interlock Text

VALVECON, Valve Control

Condition

Green

IND2_01 = 1

Grey

Yellow

IND2_02 = 1

Remarks

Test
Jog running from motor
place

Test
Yellow

IND2_02 = 1

Grey

Yellow

IND2_03 = 1

Out of service
No control possible

Out of Service
Yellow

IND2_03 = 1

Grey

Blocking Interlock:

Blocking Interlock text

Grey
26.2

Actual Interlock Text

27.1

Auto Indication

27.2

Auto Text

28.1

Man Indication

3BSE 021 945R401

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07 = 0

Not ready for start

Yellow

IND2_07 = 1

Ready for start

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode. Process


conditions control
start/stop of motor

Green

Auto
Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Grey

Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode. Startorder


affects the motor directly

579

VALVECON, Valve Control

Section 3, Faceplates and Graphic Elements

No

Description

Default Presentation

28.2

Man Text

Man Grey

Condition

Remarks

Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Grey

3.22.3 Graphic Element


3.22.3.1 Valve01

Presentation:

3
2

5
1
6

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

580

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

No

Description

Mode



Default Presentation

Condition

Remarks

ModeVisible = true

* Yellow

IND2_02 = 1 and IND2_03


=0

Test

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

ModeVisible = false

Mode is invisible

Control Point

PointofControlVisible= true

S Green

IND2_04 = 1

Sequence Control

L Green

IND2_01 = 1

Local Control

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central Control

PointofControlVisible =
false

Control point is invisible

Interlock Indication

InterlockVisible = true
-

IND2_03 = 1

Out Of Service - No
indication

XA Yellow

IND2_14 = 1

IA1

IND2_07 = 1

Ready for start

X Yellow

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11= 1 or
(IND2_13 = 1 and IND1_11
= 0) or
(IND2_00 = 0 and
(IND2_10 = 1 or
(IND2_12 = 1 and IND1_11
= 0)))

IC1 or
IC2 or
IB2 or
(IB4 & OPN=0) or

InterlockVisible = false

Interlock is invisible

3BSE 021 945R401

VALVECON, Valve Control

(BlkIntl=0 &
(IB1 or
(IB3 & OPN=0)))

581

VALVECON, Valve Control

No

Description

Actuator Indication

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

ActuatorVisible = true
Grey

IND2_03 = 1

Out Of Service

Red flashing

IND1_09 = 1

Alarm Unack

Red

IND1_08 = 1

Collective fault

Green

ActuatorVisible = false

Actuator is invisible

IND1_15 = 0 and

No intermediate position

IND1_11 = 1

No limit position for open

IND1_15 = 1 and

Intermediate position

IND1_12 = 0

Not open

IND1_15 = 1 and

Intermediate position

IND1_12 = 1

Open

IND1_15 = 0 and

No intermediate position

IND1_07 = 1

Limit position for open

Grey

IND2_03 = 1

Out Of Service

Red flashing

AU_IND = 1

Unacknowledged Alarm

Red

IND1_DIST = 1

Alarm

Green

Valve Status

Black

Green flashing

Green flashing

Green

582

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

VALVECON, Valve Control

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

Horizontal, Vertical

Actuator Visible

true, false

Mode Visible

true, false

Point of Control Visible

true, false

Interlock Visible

true, false

3.22.3.2 ObjectLine01

Presentation:
1

Behavior:
No

Description

Default Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Selected

Invisible

SELECTED = 0

Header

3BSE 021 945R401

NAME and DESCR

Object name and


description

Red flashing

AU_IND = 1

Unacknowledged alarm

Red

IND1_DIST = 1

Alarm

Green

Normal

583

VALVECON, Valve Control

No

Description

Valve Open Status

Section 3, Faceplates and Graphic Elements

Default Presentation

Condition

Remarks

IND2_07 = 0

Not ready for start

IND1_12 = 1 and
IND1_15 = 1

Open
No limit position open

IND1_07 = 1

Limit position for open

Green flashing

IND1_13 = 1 and
IND1_15 = 1

Close
No limit for close

IND1_11 = 0 and
IND1_15 = 0

Limit position for close

Green

IND2_07 = 1 and
IND2_14 = 1

A-Interlock

Green
Grey

IND2_03 = 1

Out of service

Green

Green flashing

Green

Status Indication

4.1

Mode

4.2

584

Point Of Control

Status Indication

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

O Yellow

IND2_03 = 1

Out of Service

T Yellow

IND2_02 = 1

Test

L Green

IND2_01 = 1

Local

S Green

IND2_04 = 1

Sequence

C Green

IND2_01 = 0 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_04 = 0

Central

3BSE 021 945R401

Section 3, Faceplates and Graphic Elements

VALVECON, Valve Control

No

Description

Default Presentation

Condition

Remarks

4.3

Interlock Indication

X Green

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11 = 1 or
(IND2_13 = 1 and
IND1_12 = 0) or
(IND2_00 = 0 and
(IND2_10 = 1 or
(IND2_12 = 1 and
IND1_12 = 0)))

Safety interlock or

BX Red

IND2_15 = 1

Override Interlocks.
Interlock IB1 or IB3 active

BX Yellow

IND2_00 = 1

Override Interlock

Operator interlock

4.4

Printout Blocked

P Yellow

PR_BLK = 1

Printout blocked

4.5

Alarm Blocked

B Yellow

AL_BLK = 1

Alarm blocked by operator

Bx Yellow

AL_P_BLK = 1

Alarm blocked by PCprogram

F Red

IND1_08 = 1

Collective fault indication

PRES_B
IND1_07 = 1

User defined text

OPEN Green

PRES_A
IND1_11 = 1

User defined text

CLOSED Green
PEO Red flashing

AU_IND1_02 = 1

Unack Position Error Open

PEC Red flashing

AU_IND1_03 = 1

Unack Position Error Close

PEO Red

IND1_02 = 1

Position Error Open

PEC Red

IND1_03 = 1

Position Error Close

Fault 1 Red flashing

AU_IND1_00 = 1

Unacknowledged Fault 1

Fault 2 Red flashing

AU_IND1_01 = 1

Unacknowledged Fault 2

Fault 1 Red

IND1_00 = 1

Fault 1

Fault 2 Red

IND1_01 = 1

Fault 2

ACT_PRES_TEXT

Actual interlock text

Red

IND2_07=0

Not ready for start

Yellow

IND2_07=1

Ready for start

4.6

Fault Indication

Valve Open Text


Valve Closed Text

Error 1

Error 2

Act Pres Text

3BSE 021 945R401

585

VALVECON, Valve Control

586

Section 3, Faceplates and Graphic Elements

3BSE 021 945R401

3BSE 021 945R401. Printed in Sweden May 2002


Copyright 2002 by ABB. All Rights Reserved
Registered Trademark of ABB.
Trademark of ABB.

http://www.abb.com/control
Automation Technology Products
Vsters, Sweden
www.abb.com/processautomation
email: processautomation@se.abb.com

Automation Technology Products


Wickliffe, Ohio, USA
www.abb.com/processautomation
email: industrialitsolutions@us.abb.com

Automation Technology Products


Mannheim, Germany
www.abb.de/processautomation
email: marketing.control-prodcts@de.abb.com

You might also like