Air Handling Units

Direct Expansion
BY Series
(Matching with CY series Condensing units)
BY07 thru BY25
6 TR thru 30 TR
20 kW thru 105 kW

Company Business
Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi Arabia
and today is a leading international manufacturer of air conditioning systems and is Number One in the Middle East.
Zamil Air conditioners manufactures both consumer and central air conditioners and has sales operations in over 55
countries in the Middle East, Europe, Africa and Asia.
The companys operations are structured into four Strategic Business Units (SBUs) supporting five in-house product and
service brands as well as a number of international brands under the OEM sales.
The five in-house brands are Classic, Cooline, CoolCare, Clima Tech and Geoclima.
The four SBUs are:
1. Consumer Business Unit supporting Classic, Cooline, GE and OEM brands for consumers.
2. Unitary & Applied Business Unit supporting Zamil, Cooline, GE and OEM brands for commercial and industrial customers.
3. Zamil CoolCare Business Unit providing industrial, electro mechanical contracting services, HVAC maintenance,
retrofit & operation services and parts.
4. Geoclima srl is an independent business supporting other SBUs for their requirements of chillers & double skin AHUs.
The first three SBUs - Consumer Products, Unitary & Applied Products and CoolCare direct their business operations
from the corporate headquarters in Dammam, Saudi Arabia.
Geoclima has its engineering & production operations located at Monfalcone, Italy and has a design center in Austria.
All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at
its best and achieve the corporate goals of maximizing customer satisfaction.
Factories and Productions
Zamil Air Conditioners has two manufacturing plants in Dammam, Saudi Arabia and has one specialty production facility
in Italy operated by Geoclima.
The company can produce up to 550,000 Room Air Conditioners, 300,000 Mini-Split systems and 50,000 Central Air
Conditioning systems per year.
Quality & Product Certificates
The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization)
Certificate for Room Air Conditioners. ZACs products are also certified with:
1. CE (Council of European Community)
2. UL (Underwriters Laboratory)
3. Eurovent (Certified Performance)
4. ETL (Test Facilities)
5. SASO (Saudi Arabian Standards Organization)
6. ISO 9001:2008 (International Organization for Standardization)
7. ASME (American Quality of Mechanical Engineers)
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed
bin Fahd Al Saud Award for Factory Safety.
Our Products
In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufacturers a host of residential, commercial and industrial air conditioners. This broad range extends from the
Concealed Units up to 5 TR, the Ducted Splits up to 30 TR, the Packaged Units up to 95 TR, the Single and Double Skin
Air Handling Units up to 138,316 CFM and the Water Chillers up to 500 TR cooling capacity.

INDEX
Contents

Page

Outstanding features ................................................................................................................................ 2


Model decoding ........................................................................................................................................ 3
Blower drive options ................................................................................................................................. 4
Standard specifications ......................................................................................................................... 4-5
Options and accessories ....................................................................................................................... 5-6
Physical data ............................................................................................................................................ 7
Cooling capacities ............................................................................................................................... 8-14
Fan performance data ....................................................................................................................... 15-16
Electrical data .................................................................................................................................... 17-19
Dimensions, indoor units ................................................................................................................... 20-23
Dimensions, heater box .......................................................................................................................... 24
Dimensions, outdoor units ................................................................................................................. 25-27
Typical schematic wiring diagram ...................................................................................................... 28-31
Controls and sequence of operation ....................................................................................................... 32
Installation instructions ........................................................................................................................... 33

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

OUTSTANDING FEATURES
* HIGH EER (ENERGY EFFICIENCY RATIO)
* INDEPENDENT HORIZONTAL OR VERTICAL AIR DISCHARGE UNITS
* LOW CEILING HEIGHT REQUIREMENTS
* MICROPROCESSOR BASED CONTROLS
* ONE SIDE TOTAL SERVICE ACCESSIBILITY
* SINGLE POINT POWER ENTRY
* UV FLOW LIGHT EMITTERS FOR ENHANCED IAQ (INDOOR AIR QUALITY)
* NUMBERED CODED WIRES
* INSULATED DRAIN PAN
* FACTORY INSTALLED OPTIONS UPON REQUEST
* SMALL FOOTPRINT
* LIGHT WEIGHT
* PRE-PAINTED CABINETS WITH FIBERGLASS INSULATION
* LARGE CHOICE OF HEATERS; FACTORY OR FIELD INSTALLATION
* STANDARD OR OPTIONAL MOTORS; FACTORY OR FIELD INSTALLATION
* ALUMINUM OR SYNTHETIC FILTERS
* UL LISTED MAJOR COMPONENTS

25

18

14

10

07

V : VERTICAL

H : HORIZONTAL

F : 460-3-60

M : 380-3-60
(4 WIRE)

D : DUAL

FOR BY18 - BY25

D : DUAL

S : SINGLE

H : 208/230-3-60 FOR BY07 - BY14

3&4
7
5
6
FACE AREA ARRANGEMENT ELECTRICAL REFRIGERATION
(SQ. FT.)
CIRCUIT
SUPPLY
(V-Ph-Hz)

NOTE: * Blower motor RUN/TRIP indication.

AIR
HANDLING
UNIT

BY

1& 2
BASIC

MODELS: BY07 - BY25

C : COOL ONLY

8
MODE

L : 10 HP ODP

J : 7.5 HP ODP

FOR BY25

J : 7.5 HP ODP

G : 5 HP ODP

FOR BY14/18

E : 3 HP ODP

D : 2 HP ODP

FOR BY10

E : 3 HP ODP

D : 2 HP ODP

FOR BY07

9
BLOWER
MOTOR

K : ALT. II

J : ALT. I

10
DRIVE
OPTIONS
12
EVAPORATOR
COIL

: 5/1
: 6/1
: 7.5 /1
: 10 /2
: 12/2
: 15 /2
: 20 /2
: 25/2
: 30/2

FOR BY18 -BY25


N : NO HEATER
E : 12/2
F : 15 /2
G : 20 /2
H : 25/2
J : 30/2
K : 35/2
L : 40/2

A
B
C
D
E
F
G
H
J
C : COPPER FIN

B : COATED
ALUMINUM
FIN

FOR BY07 -BY14 A : ALUMINUM


FIN
N : NO HEATER

11
HEATER
OPTIONS
(kW/STAGE)

MODEL DECODING

D : 2"SYNTHETIC

B : 2" ALUMINUM

N : NO FILTER

FOR BY25

C : 1" SYNTHETIC
D : 2"SYNTHETIC

A : 1" ALUMINUM
B : 2" ALUMINUM

N : NO FILTER

FOR BY10, 14 & 18

FOR BY07
N : NO FILTER
E : 1/2" ALUMINUM
F : 1/2" SYNTHETIC
A : 1" ALUMINUM
C : 1" SYNTHETIC

13
FILTER

V : VOLT FREE
CONTACTS

N : NO OPTION

14
OTHER OPTIONS

D : UNIT WITHOUT
THERMOSTAT

S : UNIT WITH
THERMOSTAT

15
THERMOSTAT
OPTION

BLOWER DRIVE OPTIONS


MOTOR
MODEL
NUMBER

BY07
BY10
BY14
BY18
BY25

OPTION
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II

HP

RPM

2
3
2
3
5

1750
1750
1750
1750
1750
1750
1750
1750
1750
1750

7.5
5
7.5
7.5
10

BLOWER
PULLEY
PITCH DIA.
(INCH)
2.7 - 3.7
2.7 - 3.7
3.1 - 4.1
3.1 - 4.1
3.7 - 4.7
4.3 - 5.5
3.7 - 4.7
4.3 - 5.5
4.3 - 5.5
4.3 - 5.5

SPEED RANGE (RPM)


MINIMUM

MAXIMUM

893
964
733
875
809
940
809
875
685
800

1156
1321
970
1157
1028
1203
1028
1120
880
1023

PULLEY
PITCH DIA.
(INCH)
5.6
4.9
7.4
6.2
8.0
8.0
8.0
8.6
11
9.4

APPROX. SPEED
CHANGE PER
PULLEY
TURN (RPM)
62
71
40
47
37
44
37
40
38
44

STANDARD SPECIFICATIONS
A. General
These Zamil Air Handling Units are factory fabricated and assembled, consisting of forward-curved fan section with
blower motor, DX coil, electric heaters (optional), filters & electrical control box and are suitable for indoor applications.
The unit is ready to operate when piped to a suitable condensing unit, connected to power/controls and air ducts or
plenums.
They should be ordered separately as horizontal air discharge or vertical air discharge units as per application requirements.

B. Unit Enclosure
Casing Panels are of heavy gauge (G-90) galvanized steel. Removable access panels are provided for inspection and
access to all internal parts. These panels are insulated with 1/2" thick fiberglass insulation to prevent condensation from
forming on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and
errosion from air currents. Steel sheet is zinc-coated, galvanized by the hot dip process of lock forming quality conforming to ASTM A 653 commercial weight G-90, followed by baked-on electrostatic polyester dry powder coat.

C. Coils
Coils are of the enhanced louvered fin-and-tube type, constructed of copper tubes, mechanically bonded to aluminum
fins. As an option, corrugated copper or enhanced coated aluminum fins may be provided. End plates and tube support
sheets are 18 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at
not less than 300 psi (2070 kPa) air pressure. Coils conform to ARI 410.

D. Drain Pans
Drain pans provided under cooling coil section are made of G-90 galvanized steel with mastic coated liner for additional
corrosion protection. Drain outlets of 3/4" NPT is provided for field connection.

E. Evaporator Fan
Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/pressure. Fan motor is
mounted on an adjustable base and secured by a locking device. Fan drive is through adjustable motor pitch pulley and
belt-driven. Fan shafts are designed to operate at less than 2/3rds of the first critical speed when the unit comes up to
rated revolutions per minute (RPM). Units have sealed, permanently lubricated ball or sleeve fan bearing and are statically / dynamically balanced in the fan housing during final assembly. Fan motors are of the open drip-proof type (totally
enclosed types are optional) and conform to NEMA MG-1 & MG-2. Motor starters are magnetic contactor, across-theline type.

F. Microprocessor Control
These air handling units are provided with a microprocessor control board incorporating the following features:
-

BALANCE LOADING OF COMPRESSORS: The units electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable through
dip switch setting on control board).

PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoids opening and compressor starting to equalize the pressure in the system necessary for compressor to startup. (Selectable through dip switch setting on control board).

COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load demand.

COMPRESSOR LOCK-OUT FUNCTION: If any of the units safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

FAULT DIAGNOSTICS: In case of system fault, LEDs on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.

DIGITAL I/Os: The units control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.

SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential order: supply fan condenser fan compressor; at a pre-determined timings.

G. Control Panel
A complete factory-wired control panel is provided to ensure safe and proper operation.

OPTIONS AND ACCESSORIES


A. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Thermal cut-outs, fusible links and airflow switches
are provided to shut-off power to heaters in case of airflow failure.

B. Filters
Filters are easily accessible through the filter access panel. Filters may be synthetic or permanent washable aluminum
type (refer to model decoding for details). As an accessory, bag filter section can be provided for belt driven units.

C. Discharge Air Plenum & Return Air Grille


As an accessory, discharge air plenum with return air grilles can be provided on vertical units.

D. UV Flow Light Emitters


The damp & dark environment inside the AHU is ideal for the growth and development of hazardous bacteria & fungi. The
UV flow concept uses emitters of Ultra Violet light to simulate the effect of healthy sun radiation. This will inhibit the growth
of these microorganisms reducing in this manner mold related allergies and diseases. Breath safely with UV flow.
To order the UV flow use the kit numbers in the table below.
MODEL NUMBER
KIT PART NUMBER

BY07

BY10

BY14

BY18

BY25

700-391-18

700-391-19

700-391-20

700-391-21

700-391-22

E. Electronic Thermostat
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermostat normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and
should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/
diffusers.

Single/dual stage - Cooling & heating.


Low voltage control - 24 VAC (nominal).
Room temperature display - in C or F.
Mode of operation - FAN/COOL/HEAT/AUTO.
Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
Heating & cooling setpoint is permissible.
Temperature set button - Up for increasing & down for decreasing temperature.
Built-in compressor fault & clogged filter indication led lights.
Remote sensing function as an option. Duct sensor is provided with the thermostat.
0

TYPICAL THERMOSTAT
Part No.
800-652-61

Heating Cooling Selector Switch Positions


Stages Stages Mode Switch Fan Switch
1&2

1&2

OFF-HEAT/COOL

ON - AUTO

PHYSICAL DATA
MODEL NUMBER

BY07

BY10

BY14

EVAPORATOR BLOWER Type


Nominal airflow CFM (L/S)

BY25

Centrifugal
2800 (1321)

4600 (2171)

5500 (2596)

7000 (3303)

9000 (4247)

Motor HP (Std/Alt)

2/3

3/2

5/7.5

5/7.5

7.5/10

Drive type

Belt

Belt

Belt

Belt

Belt

12x12

15x15

15x15

15x12

18x18

Blower size
Quantity
EVAPORATOR COIL

BY18

Corrugated Fin & Tube

Type
Tube dia. - Rows - FPI
Face area, Sq. ft. (Sq. m.)

3/8 - 3 - 14

3/8 - 4 - 14

3/8 - 4 - 14

3/8 - 4 - 14

3/8 - 4 - 14

7 (0.65)

10 (0.93)

14 (1.3)

17.4 (1.62)

25 (2.32)

1-1/8

1-3/8

1-3/8

REFRIGERANT LINES
SINGLE COMPRESSOR

Suction line size O.D. (inch)


Liquid line size O.D. (inch)

5/8

5/8

5/8

REFRIGERANT LINES
DUAL COMPRESSOR

Suction line size O.D. (inch)

7/8

7/8

1-1/8

1-3/8

1-3/8

Liquid line size O.D. (inch)

1/2

1/2

5/8

5/8

7/8

RETURN AIR FILTER

Size (inch)

20 x 20 x 1/2

18 x 24 x 1

20 x 24 x 1

20 x 24 x 1

20 x 24 x 2

165

225

300

340

420

Quantity
SHIPPING WEIGHT

kg. (approx.)

COOLING CAPACITIES
(Single compressor units)
BY07 INDOOR UNIT WITH CY075 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1900/0.102
62
68.38
61.94
6.55
65.49
60.59
7.21
62.34
59.15
7.94
59.03
57.63
8.66
55.63
54.52
9.38

67
74.46
51.99
6.74
71.41
50.71
7.41
68.12
49.34
8.14
64.66
47.91
8.88
61.12
46.47
9.61

72
80.91
41.85
6.88
77.72
40.64
7.57
74.28
39.35
8.32
70.68
38.01
9.09
67.07
36.71
9.85

EVAPORATOR AIRFLOW, CFM/DR


2400/0.126
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
71.74
78.24
85.14
70.48
58.38
46.06
6.83
7
7.14
68.6
74.91
81.72
67.23
57.03
44.83
7.49
7.66
7.83
65.25
71.38
78
63.95
55.63
43.5
8.21
8.4
8.59
61.7
67.73
74.17
60.47
54.21
42.14
8.93
9.13
9.35
58.14
63.99
70.24
56.98
52.76
40.77
9.63
9.86
10.14

2900/0.148
62
74.17
72.69
7.33
70.89
69.47
7.98
67.22
65.88
8.7
63.56
62.29
9.42
59.9
58.7
10.12

67
80.84
64.18
7.49
77.45
62.89
8.15
73.67
61.42
8.89
69.9
60.01
9.62
65.88
58.44
10.36

72
88.13
49.84
7.64
84.5
48.58
8.32
80.63
47.24
9.09
76.63
45.87
9.87
72.63
44.54
10.66

BY07 INDOOR UNIT WITH CY090 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2250/0.118
62
74.41
69.27
7.79
70.98
67.71
8.67
67.35
66.08
9.58
63.63
62.35
10.47
59.8
58.61
11.34

67
81.45
57.95
8.02
77.94
56.54
8.89
74.13
54.99
9.79
70.23
53.42
10.68
66.23
51.85
11.55

72
89.03
46.47
8.23
85.25
45.07
9.1
81.27
43.62
10
77.3
42.2
10.91
73.03
40.67
11.81

EVAPORATOR AIRFLOW, CFM/DR


2800/0.144
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
77.72
85.21
93.05
76.16
64.68
50.79
8.33
8.53
8.74
74.06
81.33
89.07
72.58
63.13
49.38
9.18
9.39
9.61
70.27
77.32
84.97
68.87
61.57
47.96
10.08
10.28
10.52
66.25
73.2
80.62
64.92
59.98
46.45
10.95
11.16
11.42
62.22
68.95
76.16
60.98
58.36
44.91
11.82
12.03
12.33

3350/0.168
62
80.14
78.53
8.82
76.34
74.82
9.67
72.25
70.81
10.55
68.17
66.8
11.42
63.93
62.66
12.29

67
87.86
70.74
9.02
83.8
69.16
9.87
79.73
67.67
10.76
75.37
66.01
11.64
71.02
64.43
12.51

72
96.17
54.78
9.24
91.98
53.35
10.11
87.65
51.88
11.01
83.17
50.38
11.92
78.55
48.84
12.84

BY10 INDOOR UNIT WITH CY100 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2800/0.05
62
93.7
84.45
8.88
90.53
83.14
9.72
86.75
81.54
10.64
82.96
77.99
11.57
78.57
73.86
12.61

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
101.72
69.89
9.09
98.45
68.66
9.92
94.68
67.26
10.85
90.68
65.75
11.81
86.31
64.17
12.87

72
110.43
55.2
9.34
106.93
54.01
10.16
103.07
52.71
11.14
99.09
51.38
12.14
94.62
49.9
13.27

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


3400/0.066
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
97.19
105.68
114.75
91.35
77.72
60.21
9.11
9.32
9.62
93.78
102.15
111.09
88.15
76.41
59.02
9.94
10.14
10.43
89.93
98.17
106.98
84.53
74.97
57.68
10.85
11.08
11.42
85.78
94.04
102.88
80.63
73.49
56.36
11.78
12.04
12.44
81.33
89.47
98.19
76.45
71.88
54.86
12.81
13.11
13.59
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

4000/0.076
62
99.69
93.71
9.49
96.21
90.44
10.3
92.2
86.67
11.22
88.02
82.74
12.15
83.31
78.31
13.18

72
118.1
65.01
10.05
114.14
63.74
10.86
110
62.44
11.85
105.69
61.08
12.89
100.86
59.56
14.06

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

67
108.38
85.01
9.72
104.74
83.72
10.53
100.75
82.36
11.46
96.42
80.8
12.43
91.73
79.2
13.51

COOLING CAPACITIES
(Single compressor units)
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3200/0.059
62
112.8
106.89
11.14
104.71
101.14
11.88
96.63
91.8
12.58
91.61
87.03
13.25
85.33
81.07
14.04

67
122.36
88.89
11.44
113.62
83.56
12.18
105.02
76.15
12.87
99.75
74.19
13.56
93.09
71.74
14.35

72
132.41
70.55
11.76
123.17
65.79
12.52
113.93
59.36
13.24
108.41
57.52
13.96
101.38
55.21
14.8

EVAPORATOR AIRFLOW, CFM/DR


4000/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
117.12
127.11
137.76
114.78
99.61
77.42
11.62
11.92
12.29
108.58
118.09
128.1
106.41
94.18
72.55
12.34
12.65
13.06
100.04
108.9
118.45
95.04
86.1
65.79
13.03
13.35
13.8
94.81
103.35
112.59
90.07
84.12
63.91
13.7
14.03
14.51
88.37
96.42
105.17
83.95
81.68
61.56
14.48
14.83
15.36

4800/0.092
62
120.05
117.65
12.25
111.48
109.25
12.98
102.69
97.56
13.66
97.05
92.19
14.33
90.35
85.84
15.11

67
130.47
109.78
12.57
121.11
104.12
13.3
111.75
95.63
14
105.92
93.56
14.68
98.84
91.19
15.48

72
141.72
83.96
12.98
131.79
79
13.77
121.66
71.82
14.5
115.66
69.98
15.23
108
67.62
16.09

BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.076
62
130.72
121.42
13.6
125.32
119.09
14.91
119.22
115.64
16.35
113.64
110.23
17.63
107.89
104.65
18.9

67
141.5
100.28
13.95
135.95
98.14
15.27
129.71
95.74
16.73
123.99
93.55
18.03
118.27
91.39
19.32

72
152.59
78.76
14.33
146.9
76.77
15.68
140.69
74.65
17.17
135
72.7
18.52
129.48
70.85
19.87

EVAPORATOR AIRFLOW, CFM/DR


4600/0.088
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
133.69
144.78
156.04
129.68
107.7
83.43
14.07
14.42
14.82
128.08
139
150.29
124.24
105.5
81.48
15.37
15.73
16.17
121.86
132.62
143.95
118.21
103.13
79.37
16.8
17.18
17.67
116.05
126.83
138.2
112.57
101
77.45
18.08
18.48
19.02
110.24
121.05
132.45
106.93
98.89
75.55
19.34
19.77
20.38

5000/0.095
62
135.29
131.24
14.43
129.63
125.74
15.73
123.31
119.61
17.15
117.43
113.91
18.43
111.55
108.2
19.69

67
146.53
112.45
14.78
140.68
110.26
16.09
134.18
107.86
17.54
128.32
105.74
18.84
122.47
103.63
20.13

72
157.97
86.44
15.2
152.16
84.5
16.55
145.69
82.36
18.05
139.87
80.45
19.41
134.27
78.67
20.77

BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.050
62
141.18
132.88
13.72
135.25
130.17
15.04
128.63
127.21
16.49
122.53
120.08
17.79
116.43
114.1
19.07

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
152.95
110.4
14.07
146.88
107.9
15.41
140.12
105.14
16.89
133.87
102.58
18.21
127.8
100.19
19.52

72
164.83
87.29
14.51
158.79
85.06
15.89
152.07
82.6
17.41
146.03
80.42
18.79
140
78.24
20.18

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


4800/0.062
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
145.99
157.94
170.28
143.07
121.29
94.24
14.23
14.6
15.1
139.71
151.7
164.07
136.92
118.83
92.04
15.54
15.93
16.48
132.81
144.62
157.24
130.15
116.02
89.65
16.99
17.41
18.03
126.33
138.38
151.03
123.8
113.62
87.47
18.28
18.73
19.42
120.05
131.93
145.03
117.65
111.07
85.42
19.57
20.05
20.82
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

5800/0.076
62
149.86
146.87
15.12
143.55
140.68
16.42
136.47
133.74
17.86
129.9
127.3
19.15
123.33
120.86
20.43

72
175.25
102.5
16.09
168.75
100.23
17.48
161.75
97.85
19.03
155.5
95.74
20.44
149.5
93.79
21.85

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

67
162.43
134.31
15.52
155.9
131.77
16.85
148.6
128.95
18.32
142.32
126.67
19.65
135.78
124.17
20.98

COOLING CAPACITIES
(Dual compressor units)
BY07 INDOOR UNIT WITH CY075 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1900/0.102
62
67.64
63.67
6.6
64
61.92
6.89
60.68
60.38
7.15
56.79
55.66
7.47
53.23
52.17
7.78

67
74.3
53.69
6.96
70.51
52.03
7.3
67.05
50.56
7.6
63.01
48.85
7.98
59.31
47.3
8.34

72
81.32
43.44
7.3
77.39
41.9
7.69
73.79
40.5
8.05
69.61
38.91
8.48
65.76
37.47
8.9

EVAPORATOR AIRFLOW, CFM/DR


2400/0.126
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
71.22
78.24
85.76
69.79
60.37
47.87
6.96
7.31
7.65
67.24
74.18
81.52
65.9
58.68
46.28
7.27
7.67
8.06
63.69
70.44
77.69
62.41
57.14
44.88
7.53
7.99
8.43
59.5
66.17
73.14
58.31
55.43
43.2
7.87
8.38
8.88
55.74
62.22
69.1
54.62
53.84
41.76
8.19
8.75
9.31

2900/0.148
62
73.67
72.2
7.51
69.63
68.23
7.82
65.83
64.52
8.11
61.54
60.31
8.45
57.49
56.34
8.78

67
80.97
66.41
7.87
76.82
64.79
8.23
72.92
63.25
8.56
68.39
61.46
8.96
64.24
59.82
9.34

72
88.88
51.82
8.21
84.5
50.26
8.63
80.38
48.77
9.01
75.75
47.15
9.47
71.38
45.6
9.92

BY07 INDOOR UNIT WITH CY090 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2250/0.118
62
77.25
74.76
8.29
73.43
72.88
8.61
69.51
68.12
8.96
65.39
64.08
9.33
60.69
59.47
9.77

67
84.77
62.82
8.75
80.86
61.12
9.11
76.77
59.35
9.5
72.47
57.5
9.92
67.5
55.42
10.41

72
93.01
50.77
9.22
88.93
49.17
9.63
84.57
47.45
10.08
80.11
45.73
10.54
74.87
43.75
11.1

EVAPORATOR AIRFLOW, CFM/DR


2800/0.144
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
80.64
88.73
97.52
79.03
69.94
55.47
8.91
9.36
9.85
76.62
84.49
93.17
75.09
68.14
53.84
9.24
9.74
10.28
72.47
80.12
88.59
71.02
66.32
52.12
9.59
10.14
10.73
68.2
75.62
83.76
66.84
64.49
50.32
9.97
10.56
11.21
63.08
70.28
78.21
61.81
62.31
48.31
10.41
11.07
11.78

3350/0.168
62
83.2
81.54
9.46
78.97
77.39
9.8
74.59
73.1
10.16
70.21
68.81
10.54
64.81
63.51
10.99

67
91.64
76.43
9.93
87.28
74.67
10.31
82.64
72.76
10.72
77.99
70.94
11.15
72.47
68.78
11.66

72
100.93
59.75
10.43
96.31
58.06
10.87
91.55
56.34
11.33
86.49
54.5
11.82
80.57
52.39
12.39

BY10 INDOOR UNIT WITH CY100 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2800/0.05
62
96.14
87.31
9.3
91.26
85.2
9.83
86.5
83.04
10.35
81.5
78.24
10.89
76.37
73.32
11.46

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
105.61
72.9
9.78
100.51
70.92
10.37
95.41
68.96
10.95
90.19
66.99
11.57
84.73
64.94
12.22

72
115.62
58.2
10.26
110.19
56.28
10.92
104.88
54.46
11.59
99.21
52.5
12.29
93.41
50.54
13.03

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


3400/0.066
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
100.3
110.11
120.61
96.28
80.99
63.47
9.63
10.11
10.61
95.11
104.8
114.9
91.31
79.05
61.54
10.17
10.71
11.3
89.93
99.35
109.18
86.33
77.02
59.64
10.7
11.32
11.99
84.59
93.75
103.17
81.21
74.96
57.64
11.26
11.95
12.71
79.11
88
97.16
75.95
72.89
55.72
11.84
12.61
13.45
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

4000/0.076
62
103.18
99.05
10.08
97.78
93.87
10.62
92.37
88.68
11.17
86.8
83.33
11.73
81.22
77.97
12.31

72
124.31
68.41
11.08
118.45
66.5
11.79
112.41
64.55
12.49
106.21
62.56
13.22
99.83
60.54
13.98

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC= 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

10

67
113.41
88.66
10.56
107.86
86.69
11.18
102.14
84.6
11.8
96.24
82.47
12.44
90.35
80.45
13.11

COOLING CAPACITIES
(Dual compressor units)
BY10 INDOOR UNIT WITH CY120 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3200/0.059
62
114.47
105.56
11.43
108.48
102.83
11.98
102.34
100.13
12.52
96.63
96.63
13.04
90.07
88.27
13.67

67
125.97
88.62
12
119.86
86.12
12.66
113.48
83.53
13.3
107.51
81.11
13.92
100.72
78.45
14.67

72
138.9
71.58
12.59
132.55
69.21
13.37
125.93
66.79
14.14
119.86
64.61
14.88
112.69
62.06
15.79

EVAPORATOR AIRFLOW, CFM/DR


4000/0.076
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
119.74
132.31
146.38
117.34
99.74
78.98
12.01
12.6
13.21
113.46
125.72
139.66
111.19
97.12
76.6
12.59
13.29
14.04
106.84
118.96
132.59
104.7
94.51
74.13
13.16
13.96
14.86
100.74
112.72
126.03
98.73
92.12
71.87
13.7
14.61
15.64
93.77
105.43
118.28
91.89
89.37
69.21
14.35
15.4
16.59

4800/0.092
62
123.61
121.14
12.73
116.92
114.58
13.33
110.01
107.81
13.91
103.95
101.87
14.47
96.63
94.69
15.12

67
136.72
109.99
13.32
130.06
107.51
14.04
122.98
104.87
14.74
116.32
102.33
15.41
108.83
99.64
16.22

72
151.86
85.79
13.95
144.83
83.38
14.83
137.38
80.86
15.67
130.34
78.47
16.48
122.28
75.8
17.45

BY10 INDOOR UNIT WITH CY150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.076
62
131.07
121.55
14.08
124.62
118.74
15.52
118.17
114.62
16.95
111.37
108.03
18.38
105.1
101.95
19.64

67
143.06
100.91
14.41
136.3
98.25
15.88
129.54
95.68
17.35
122.43
92.97
18.81
116.01
90.58
20.12

72
155.86
79.91
14.73
148.97
77.51
16.26
141.72
74.99
17.79
134.48
72.55
19.34
127.76
70.28
20.74

EVAPORATOR AIRFLOW, CFM/DR


4600/0.088
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
134.29
146.58
160.01
130.26
108.33
84.78
14.54
14.86
15.2
127.68
139.79
152.87
123.85
105.81
82.37
15.98
16.33
16.74
120.86
132.62
145.34
117.24
103.1
79.81
17.4
17.8
18.28
113.85
125.44
137.8
110.43
100.5
77.32
18.83
19.27
19.85
107.43
118.66
130.86
104.21
97.97
75.05
20.09
20.59
21.26

5000/0.095
62
136.17
132.08
14.9
129.41
125.53
16.33
122.44
118.77
17.75
115.25
111.79
19.18
108.71
105.45
20.44

67
148.7
113.24
15.22
141.76
110.7
16.68
134.39
107.93
18.15
127.02
105.28
19.63
120.3
102.89
20.95

72
162.28
87.87
15.56
154.96
85.42
17.1
147.41
82.93
18.65
139.66
80.39
20.23
132.54
78.08
21.65

BY14 INDOOR UNIT WITH CY150 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4000/0.05
62
136.47
125.59
14.32
129.67
122.62
15.8
122.7
119.02
17.26
115.56
112.09
18.73
109.11
105.83
20.02

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
149.13
104.51
14.64
142.02
101.7
16.15
134.74
98.86
17.67
127.28
96.01
19.19
120.52
93.47
20.54

72
162.76
83.1
15
155.34
80.47
16.59
147.76
77.82
18.18
140
75.15
19.8
132.93
72.76
21.27

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


4800/0.062
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
141.39
154.82
169.24
137.14
115.31
90.16
14.82
15.14
15.54
134.27
147.33
161.59
130.25
112.45
87.58
16.29
16.66
17.15
126.95
139.63
153.52
123.15
109.55
84.84
17.75
18.18
18.77
119.42
131.93
145.24
115.84
106.76
82.07
19.22
19.71
20.43
112.52
124.65
137.79
109.15
104.03
79.63
20.52
21.08
21.92
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

5800/0.076
62
145.82
141.45
15.7
138.49
134.34
17.16
130.66
126.74
18.63
122.82
119.14
20.09
115.75
112.27
21.4

72
175.25
98.44
16.48
167
95.7
18.1
158.75
93.04
19.75
150
90.17
21.43
142.25
87.72
22.97

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.3 ESP.

11

67
159.92
128.04
16.03
152.12
125.19
17.55
144.08
122.24
19.09
136.03
119.43
20.63
128.49
116.7
22.02

COOLING CAPACITIES
(Dual compressor units)
BY14 INDOOR UNIT WITH CY180 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4400/0.056
62
167.37
148.38
15.98
160.47
145.18
17.54
152.99
141.81
19.27
145.32
138.4
20.96
137.46
134.94
22.64

67
182.36
124.49
16.38
175.3
121.57
17.94
167.48
118.35
19.66
159.66
115.22
21.37
151.46
111.91
23.07

72
198.38
100.23
16.77
190.98
97.46
18.35
183.02
94.53
20.12
174.86
91.56
21.88
166.71
88.66
23.65

EVAPORATOR AIRFLOW, CFM/DR


5500/0.073
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
174.95
190.75
207.91
168.42
139.28
109.92
16.88
17.26
17.69
167.52
183.36
200.09
165.1
136.42
107.15
18.42
18.8
19.27
159.61
175.01
191.55
158.01
133.12
104.14
20.12
20.52
21.04
151.46
166.67
183.02
149.95
129.91
101.2
21.81
22.22
22.83
143.31
158.09
174.25
141.88
126.61
98.19
23.46
23.92
24.63

6600/0.088
62
180.31
178.51
18.16
172.55
170.82
19.68
164.5
162.85
21.37
155.87
154.31
23.04
147.24
145.77
24.69

67
196.86
153.29
18.53
189.13
150.41
20.07
180.55
147.16
21.78
171.68
143.77
23.49
162.81
140.48
25.19

72
214.78
118.92
19.01
206.53
116.08
20.59
197.72
113.09
22.38
188.9
110.17
24.18
179.79
107.15
26

BY18 INDOOR UNIT WITH CY180 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5050/0.052
62
176.47
163.61
16.72
168.99
160.21
18.34
161.07
156.79
20.14
152.71
151.18
21.92
144.35
142.91
23.68

67
192.66
136.38
17.13
185
133.27
18.75
176.68
129.94
20.57
168.14
126.55
22.37
159.6
123.25
24.17

72
209.84
108.63
17.59
202
105.79
19.26
193.29
102.63
21.14
184.59
99.54
23.03
175.88
96.51
24.95

EVAPORATOR AIRFLOW, CFM/DR


6300/0.067
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
183.92
201.29
219.69
182.08
153.4
119.75
17.44
17.85
18.39
176.24
193.1
211.27
174.47
150.21
116.83
19.04
19.47
20.06
167.73
184.36
202.03
166.05
146.89
113.62
20.81
21.28
21.97
158.94
175.34
192.8
157.35
143.44
110.47
22.58
23.09
23.9
150.16
166.33
183.57
148.66
140.1
107.38
24.33
24.9
25.85

7550/0.082
62
189.49
187.6
18.38
181.27
179.45
19.96
172.38
170.66
21.73
163.5
161.87
23.49
154.29
152.75
25.23

67
207.19
169.31
18.81
198.68
166.1
20.43
189.51
162.68
22.24
180.35
159.36
24.06
170.86
155.86
25.88

72
226.5
129.96
19.42
217.71
127.02
21.1
208.28
123.87
23.03
198.84
120.79
24.98
189.08
117.58
26.98

BY18 INDOOR UNIT WITH CY220 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5050/0.054
62
201.12
176.71
20.12
193.86
173.3
22.01
186.38
169.81
23.89
178.68
166.24
25.76
170.09
162.39
27.8

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
217.84
148.27
20.64
210.39
145.15
22.55
202.51
141.82
24.43
194.63
138.58
26.3
185.43
134.77
28.37

72
235.74
119.48
21.14
227.69
116.4
23.08
219.63
113.38
25.01
211.36
110.3
26.93
201.78
106.76
29.06

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


6300/0.069
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
210
227.78
246.84
199.83
165.44
130.66
20.89
21.39
21.94
202.31
219.59
238.15
196.46
162.12
127.49
22.76
23.27
23.88
194.35
211.4
229.46
192.94
158.9
124.38
24.61
25.15
25.81
186.12
202.93
220.77
182.4
155.56
121.34
26.46
27.01
27.75
177.06
193.37
210.72
173.52
151.86
117.82
28.49
29.07
29.92
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

7550/0.085
62
216.47
212.14
21.82
208.24
204.08
23.69
200.02
196.02
25.53
191.46
187.63
27.35
181.92
178.29
29.37

72
254.49
140.9
22.94
245.7
137.87
24.88
236.59
134.72
26.82
227.48
131.65
28.78
216.74
127.96
30.97

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

12

67
235.01
181.79
22.32
226.17
178.24
24.2
217.66
175.04
26.07
208.83
171.68
27.94
198.68
167.8
30.01

COOLING CAPACITIES
(Dual compressor units)
BY18 INDOOR UNIT WITH CY240 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5600/0.061
62
221.8
188.82
21.87
214.24
185.37
23.87
206.19
181.79
26.1
197.89
178.1
28.29
188.37
173.88
30.69

67
240.1
158.41
22.51
232.09
155.11
24.49
223.84
151.81
26.69
215.1
148.26
28.86
205.39
144.41
31.22

72
259.48
127.52
23.08
251.03
124.39
25.06
242.34
121.22
27.26
233.41
117.99
29.43
223.28
114.37
31.83

EVAPORATOR AIRFLOW, CFM/DR


7000/0.078
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
231.81
250.97
271.25
213.75
176.76
139.28
22.83
23.42
24.02
223.57
242.47
262.5
210.14
173.46
136.25
24.8
25.37
25.99
215.03
233.37
253.15
206.56
169.9
132.99
26.98
27.53
28.18
206.19
224.26
243.79
200
166.42
129.79
29.13
29.67
30.35
196.12
213.95
232.93
190.24
162.52
126.07
31.48
32.01
32.75

8400/0.094
62
238.64
231.48
24.01
230.22
223.32
25.75
221.07
214.44
27.85
211.92
205.56
29.9
201.67
195.62
32.25

67
258.55
193.93
24.48
249.45
190.44
26.37
240.35
187.14
28.46
230.88
183.65
30.58
219.95
179.56
32.85

72
279.88
150.34
25.24
270.47
147.14
27.2
260.69
143.85
29.39
250.91
140.62
31.56
240.05
137.11
33.99

BY25 INDOOR UNIT WITH CY240 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

6000/0.041
62
228.24
195.68
22.42
220.39
192.32
24.38
211.76
188.54
26.56
203.14
184.87
28.7
193.2
180.61
31.05

67
247.37
163.58
23
238.79
160.12
24.95
229.94
156.65
27.11
221.1
153.26
29.25
210.95
149.37
31.59

72
267.41
130.77
23.62
258.62
127.63
25.58
249.57
124.45
27.77
240.26
121.2
29.94
229.66
117.53
32.36

EVAPORATOR AIRFLOW, CFM/DR


7500/0.054
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
239.54
259.47
281.25
223.35
183.85
144.21
23.09
23.66
24.39
230.72
250.69
271.88
219.18
180.62
141.03
25.01
25.59
26.35
221.57
240.93
261.85
210.49
176.85
137.61
27.15
27.72
28.54
212.42
231.5
252.16
201.8
173.41
134.43
29.25
29.83
30.73
201.96
220.77
240.84
191.86
169.51
130.69
31.57
32.16
33.18

9000/0.067
62
247.06
234.71
23.95
238.04
226.14
25.85
228.24
216.82
27.95
218.82
207.88
30.05
207.84
197.45
32.34

67
268.05
203.1
24.54
258.68
199.73
26.45
248.54
195.94
28.57
238.79
192.55
30.68
227.47
188.51
33.01

72
290.56
156.42
25.38
280.86
153.27
27.36
270.78
150.02
29.55
260.3
146.63
31.77
248.66
142.95
34.24

BY25 INDOOR UNIT WITH CY300 OUTDOOR UNIT


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125
`

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

7200/0.052
62
275.76
246.81
26.05
264.78
241.71
28.39
252.24
235.98
31.2
240.63
230.7
33.71
229.02
225.57
36.19

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
298.09
206.13
26.75
286.86
201.43
29.1
274.06
196.17
31.94
262.2
191.29
34.47
250.65
186.71
36.99

72
321.21
164.71
27.47
309.72
160.37
29.87
297
155.69
32.78
285.21
151.34
35.39
273.72
147.21
38.02

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


9000/0.067
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
287.45
310.97
334.78
279.95
230.66
180.24
27.03
27.71
28.55
275.69
298.87
323.15
274.69
225.75
176.12
29.35
30.05
30.95
262.75
285.61
309.57
262.75
220.63
171.3
32.12
32.87
33.88
250.59
273.12
297.54
250.59
215.66
167.1
34.61
35.4
36.51
238.04
261.03
285.52
233.28
211.06
162.92
37.07
37.91
39.16
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

10800/0.082
62
295.53
289.62
28.38
283.76
278.09
30.68
269.65
264.25
33.45
257.41
252.26
35.91
244.71
239.81
38.36

72
344.02
194.65
30.03
332.38
190.73
32.44
318.41
185.92
35.38
306.31
181.87
38.04
294.21
177.83
40.72

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

13

67
319.32
253.39
29.09
307.14
248.71
31.42
293.57
243.7
34.24
280.92
238.89
36.76
268.28
234.12
39.29

COOLING CAPACITIES
(Dual compressor units)
BY25 INDOOR UNIT WITH CY360 OUTDOOR UNIT
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

9000/0.065
62
334.9
304.4
35.79
321.57
298.38
38.58
305.49
290.83
41.69
289.8
283.9
44.74
273.33
267.87
47.74

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
364.81
255.21
36.73
350.77
249.32
39.51
334.38
242.41
42.59
318.38
235.95
45.64
301.99
229.35
48.66

72
396.08
204.79
37.61
381.72
199.36
40.42
365.43
193.28
43.56
348.75
187.09
46.7
332.46
181.21
49.85

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


10500/0.079
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
344.97
375.54
407.78
331.8
275.15
217.53
36.92
37.83
38.74
330.78
360.98
393.3
325.48
269.25
212.3
39.7
40.58
41.54
314.31
344.59
376.55
308.03
262.75
206.27
42.76
43.65
44.7
297.84
327.75
359.35
291.89
256.06
200.09
45.78
46.69
47.87
280.92
310.9
342.61
275.3
249.51
194.25
48.76
49.71
51.05
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

12000/0.092
62
352.94
345.88
38.21
338.3
331.53
40.96
321.57
315.14
44
304.31
298.23
47
287.06
281.32
49.97

72
417.41
229.85
40.05
402.41
224.57
42.87
385.34
218.6
46.04
367.76
212.44
49.23
350.69
206.66
52.44

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to SC = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM);
WBL = DBL [DR (DBE WBE)].
4. Total unit power input includes blower motor watts at nominal CFM & 0.4 ESP.

14

67
383.93
294.2
39.09
369.36
288.61
41.84
352.2
281.85
44.9
335.03
275.23
47.94
317.86
268.75
50.96

FAN PERFORMANCE DATA


BELT DRIVEN MOTORS
MODEL No.: BY07
Airflow,
CFM (L/S)

0.2

0.4

External Static Pressure (inch wg.)


0.8
1.0

0.6

RPM

BHP

RPM

1800 (849)

820*

0.62*

900

2000 (944)

824*

0.7*

905

2200 (1038)

853

0.81

2400 (1133)

950

2600 (1227)

968

2800 (1321)

1054

1.4

1106

1.5

1160

1.61

3000 (1416)

1066

1.55

1133

1.7

1180

1.82

3200 (1510)

1091

1.75

1157

1.91

1202

2.02

1255

3400 (1605)

1116

1.96

1171

2.1

1228

2.3

1276

1.2

1.4

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

0.71

965

0.82

1020

0.88

1102

1.03

1145

1.14

1220

1.26

0.79

970

0.91

1026

1.0

1107

1.12

1152

1.25

1225

1.35

927

0.91

986

1.02

1041

1.13

1111

1.25

1160

1.36

1237

1.48

0.94

1004

1.05

1059

1.21

1132

1.27

1155

1.38

1244

1.5

1297

1.65

1.1

1032

1.22

1086

1.33

1150

1.45

1194

1.57

1250

1.69

1305

1.82

1216

1.76

1261

1.88

1323

2.02

1380*

2.2*

1234

1.94

1276

2.09

1334*

2.23*

1400*

2.3*

2.2

1307

2.33

1359*

2.47*

2.45

1329

2.6

1368*

2.73*

II

NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY10


Airflow,
CFM (L/S)

External Static Pressure (inch wg.)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)
3600 (1699)
3800 (1793)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)

610
625
636
660
675
700
727
772
791
840

0.62
0.69
0.77
0.88
1.0
1.13
1.28
1.41
1.58
1.79

710
720
734
746
760
778
790
843
864
890

0.75
0.80
0.92
1.01
1.16
1.3
1.45
1.62
1.79
1.96

745
760
780
805
820
840
865
880
887
931

0.87
0.95
1.06
1.18
1.32
1.43
1.62
1.78
1.94
2.2

4800 (2265)

857

1.95

906

2.17

947

2.4

5000 (2360)

876

2.15

920

2.38

961

2.6

760
810
820
833
848
868
882
921
934
975

0.95
1.12
1.26
1.34
1.48
1.63
1.8
1.96
2.14
2.38

850
865
870
881
900
913
926
968
979
1017

1.2
1.25
1.38
1.5
1.66
1.8
1.96
2.16
2.34
2.59

988

2.57

1035

2.76

1005

2.76

905
915
925
939
950
966
980
1011
1024
1058

1.32
1.4
1.51
1.67
1.82
2.0
2.18
2.36
2.54
2.77

965
970
978
983
995
1006
1023
1054
1067

1.5
1.6
1.73
1.84
1.98
2.18
2.4
2.56
2.77

1000
1013
1023
1033
1043
1056
1066
1096

BHP
2.25
2.43
2.58
2.75
2.91
3.11
3.34
3.64
3.83
4.13
4.35
4.66
4.92
5.2

RPM
992
1002
1010
1053
1065
1068
1070
1098
1106
1114
1123
1133
1150
1161

1.6
1.75
1.86
2.02
2.21
2.39
2.6
2.76

1054
1065
1073
1083
1090
1100
1108

BHP
2.4
2.6
2.78
2.93
3.14
3.37
3.59
3.88
4.14
4.37
4.59
4.85
5.2
5.51

RPM
1075
1080
1093
1100
1107
1113
1119
1133
1139
1150
1157
1167
1183
1194

1.8
2.0
2.1
2.25
2.41
2.58
2.77

1100
1115
1122
1128
1131
1143

2.0
2.15
2.28
2.44
2.6
2.78

II

NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. 2 HP motor and alternative drive I to be used for the unshaded portion.
3. 3 HP motor and alternative drive II to be used for the shaded portion.

MODEL No.: BY14


Airflow,
CFM (L/S)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)
4800 (2265)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)

0.2
RPM
694*
705*
719*
735*
748*
761*
778
800
808
826
837
850
879
894

BHP
1.21*
1.33*
1.43*
1.57*
1.72*
1.87*
2.06
2.31
2.46
2.68
2.90
3.12
3.41
3.76

0.4
RPM
743*
761*
774
787
800
812
823
846
858
869
885
900
920
933

BHP
1.3*
1.45*
1.6
1.75
1.92
2.09
2.27
2.5
2.7
2.9
3.12
3.41
3.70
4.0

0.6
RPM
797
811
823
835
846
862
873
894
903
917
927
940
962
973

BHP
1.52
1.67
1.8
1.95
2.09
2.30
2.48
2.72
2.90
3.12
3.37
3.65
3.96
4.24

0.8
RPM
845
857
869
885
897
904
917
934
945
955
965
980
1000
1013

External Static Pressure (inch wg.)


1.0
1.2
1.4

BHP
1.66
1.81
1.97
2.17
2.35
2.52
2.70
2.94
3.12
3.4
3.64
3.92
4.2
4.44

RPM
890
903
918
929
935
948
959
979
987
1000
1009
1021
1040
1050

BHP
1.83
2.0
2.17
2.34
2.52
2.70
2.91
3.15
3.38
3.65
3.9
4.17
4.45
4.68

RPM
937
951
963
971
979
989
1001
1019
1028
1041
1047
1061
1078
1091

BHP
2.03
2.19
2.33
2.55
2.72
2.91
3.11
3.38
3.65
3.9
4.13
4.38
4.69
4.92

RPM
975
992
1006
1013
1023
1032
1038
1056
1063
1078
1088
1100
1114
1125

1.6

1.8

NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

15

2.0
BHP
2.64
2.82
2.97
3.17
3.4
3.6
3.85
4.10
4.35
4.6
4.85
5.1
5.45
5.8

RPM
1102
1110
1133
1138
1144
1150
1159
1171
1176
1186
1194
1205
1218
1229

II

BHP
2.85
3.05
3.2
3.41
3.62
3.86
4.08
4.36
4.57
4.78
5.05
5.4
5.76
6.08

FAN PERFORMANCE DATA


BELT DRIVEN MOTORS
MODEL No.: BY18
Airflow,
CFM (L/S)

External Static Pressure (inch wg.)


0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
6800 (3209)
7000 (3303)
7200 (3398)
7400 (3492)
7600 (3587)
7800 (3681)
8000 (3775)
8200 (3870)
8400 (3964)

715*
718*
721*
725*
729*
733*
738*
745*
753*
761*
772*
777*
794*
805
820
830
867
890

1.33*
1.42*
1.53*
1.68*
1.81*
1.9*
2.03*
2.15*
2.38*
2.5*
2.69*
2.84*
2.96*
3.18
3.36
3.59
3.77
4.05

731*
737*
750*
756*
762*
775*
788*
795*
800*
810
820
830
845
850
870
880
890
904

1.56*
1.68*
1.81*
1.92*
2.03*
2.14*
2.35*
2.5*
2.64*
2.78
2.92
3.08
3.3
3.5
3.69
3.86
4.1
4.42

787*
793*
802*
807
816
833
839
850
855
863
875
880
890
900
909
922
936
945

1.82*
1.96*
2.07*
2.21
2.35
2.42
2.57
2.71
2.92
3.08
3.33
3.41
3.62
3.83
4.1
4.25
4.5
4.75

850
856
860
866
872
877
888
900
905
910
918
927
936
941
954
963
972
986

2.07
2.26
2.35
2.5
2.64
2.78
2.92
3.08
3.25
3.41
3.58
3.75
3.95
4.2
4.5
4.65
4.9
5.1

902
905
911
916
921
930
935
940
950
960
967
976
985
990
1002
1008
1016
1025

2.4
2.53
2.66
2.79
2.9
3.02
3.24
3.41
3.58
3.75
3.95
4.14
4.4
4.57
4.9
5.05
5.25
5.45

955
961
966
968
970
980
985
990
1000
1004
1012
1017
1021
1026
1041
1046
1054
1066

2.66
2.83
2.96
3.07
3.23
3.4
3.56
3.72
3.88
4.14
4.28
4.47
4.68
4.85
5.14
5.33
5.56
5.85

1005
1010
1012
1015
1020
1025
1030
1036
1045
1050
1054
1059
1065
1069
1083
1087
1100
1107

2.96
3.15
3.23
3.38
3.53
3.69
3.84
4.04
4.23
4.47
4.66
4.85
5.09
5.23
5.47
5.75
6
6.24

1057
1060
1062
1065
1066
1070
1080
1082
1083
1090
1095
1100
1108
1112
1125
1128
1132
1140

3.3
3.46
3.57
3.73
3.84
4.0
4.27
4.45
4.6
4.83
5.04
5.19
5.47
5.66
5.9
6.12
6.36
6.72

1104
1107
1109
1110
1113
1118
1120
1126
1127
1134
1135
1141*
1150*
1154*
1158*
1164*
1172*

3.6
3.76
3.88
4.07
4.18
4.4
4.63
4.82
5
5.16
5.39
5.58*
5.8*
6*
6.36*
6.6*
6.84*

II

1153*
1155*
1157*
1158*
1159*
1162*
1163*
1165*
1170*
1175*
1179*
1183*
1185*
1193*
1200*

3.88*
4.04*
4.27*
4.4*
4.59*
4.72*
4.95*
5.09*
5.3*
5.51*
5.72*
5.95*
6.12*
6.42*
6.78*

NOTES : 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor and alternative drive I to be used for the unshaded portion.
3. Alt. 7.5 HP motor and alternative drive II to be used for the shaded portion.
* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

MODEL No.: BY25


Airflow,
CFM (L/S)
6000 (2832)
6400 (3020)
6800 (3209)
7200 (3398)
7600 (3587)
8000 (3775)
8400 (3964)
8800 (4152)
9200 (4341)
9600 (4530)
10000 (4719)
10400 (4907)
10800 (5096)
11200 (5286)
11600 (5474)
12000 (5663)

0.4
RPM BHP
700
706
716
722
732
740
751
759
770
779
790
801
809
821
852
870

2.6
2.8
3.05
3.24
3.4
3.6
3.9
4.2
4.5
4.9
5.2
5.55
5.9
6.4
6.8
7.2

0.6
RPM

BHP

762
764
766
768
770
772
778
784
790
796
806
813
825
856
872
885

3.12
3.3
3.5
3.7
3.82
4.0
4.35
4.65
5.0
5.35
5.67
6.1
6.5
6.9
7.3
7.8

0.8
RPM BHP

812
813
814
815
816
818
821
824
828
832
838
849
870
876
885
892

3.6
3.78
4.0
4.19
4.35
4.56
4.85
5.16
5.5
5.84
6.15
6.6
7.0
7.4
7.9
8.5

External Static Pressure (inch wg.)


1.0
1.2
1.4
RPM BHP RPM BHP RPM BHP
847
848
849
850
851
852
853
857
862
870
878
890
898
906
914
925

4.0
4.22
4.42
4.64
4.88
5.18
5.5
5.81
6.14
6.45
6.7
7.1
7.5
7.95
8.45
9.0

870
871
872
873
874
875
876
878
880
900
915
920
928
936
944
952

4.5
4.73
4.96
5.2
5.45
5.65
5.97
6.3
6.75
7.1
7.4
7.85
8.3
8.7
9.15
9.6

940
942
944
945
947
948
949
951
953
955
957
965
973
981
989
996

5.0
5.23
5.45
5.68
5.9
6.12
6.48
6.8
7.15
7.6
8.06
8.4
8.8
9.25
9.6
10.1

1.6
RPM BHP

1.8
RPM BHP

2.0
RPM BHP

980
981
982
983
985
986
988
990
992
994
996
1003
1009
1014

1010
1011
1013
1014
1016
1018
1019
1020
1021
1022
1023
1034*

1059*
1060*
1062*
1063*
1064*
1065*
1066*
1067*
1068*
1069*
1070*

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.
NOTES: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.

16

5.46
5.71
5.97
6.23
6.5
6.8
7.2
7.6
8.0
8.35
8.71
9.1
9.5
9.9

6.0
6.3
6.6
6.95
7.25
7.5
7.8
8.1
8.45
8.75
9.25
9.7*

II

6.6*
6.92*
7.22*
7.51*
7.78*
8.05*
8.35*
8.65*
9.0*
9.45*
9.8*

ELECTRICAL DATA
MODEL No.: BY07
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

MAX.

MODEL No.: BY10

BLOWER
MOTOR
HP

FLA

2
(STD.)

208/230-3-60

187

253
3
(ALT.)

2
(STD.)

380-3-60
(4 WIRE)

342

6.6

8.8

418
3
5.14
(ALT.)

2
(STD.)

460-3-60

414

3.5

506
3
(ALT.)

4.1

POWER
SUPPLY
(V-Ph-Hz)

ELECTRIC HEATER
MCA
kW

MOCP

MIN.

FLA

MAX.

BLOWER
MOTOR
HP

FLA

Horse Power

MCA

Minimum Circuit Amps

MCA
kW

MOCP

FLA

8.3

15

8.3

15

12.6

24

25

12.6

24

25
30/35

6/7.5

15.1/18.8

27.1/31.8

30/35

10*/12*

25.1/30.1

39.6/45.9

40/50

15*/20*

37.7/50.2

55.4/71

60/80

25*/30*

62.8/75.3 86.8/102.4

2
(ALT.)

6.6

90/110

11

20

12.6

26.8

30

6/7.5

15.1/18.8

29.9/34.5

35/35

10*/12*

25.1/30.1

42.4/48.6

45/50

15*/20*

37.7/50.2

58.1/73.8

60/80

25*/30*

62.8/75.3 89.5/105.1 90/110

208/230-3-60

187

253

3
(STD.)

8.8

6/7.5

15.1/18.8

27.1/31.8

10*/12*

25.1/30.1

39.6/45.9

40/50

15*/20*

37.7/50.2

55.4/71

60/80

25*/30*

62.8/75.3 86.8/102.4 90/110

11

20

12.6

26.8

30

6/7.5

15.1/18.8

29.9/34.5

35/35

10*/12*

25.1/30.1

42.4/48.6

45/50

58.1/73.8

60/80

15

15*/20*

37.7/50.2

7.6

14.5

15

25*/30*

62.8/75.3 89.5/105.1 90/110

6/7.5

9.1/11.4

16.4/19.3

20/20

10*/12*

15.2/18.2

24/27.8

25/30

15*/20*

22.8/30.4

33.5/43

35/45

25*/30*

38/45.6

52.5/62

60/70

6.4

15

7.6

15.9

20

6/7.5

9.1/11.4

17.8/20.7

20/25

10*/12*

15.2/18.2

25.4/29.2

30/30

15*/20*

22.8/30.4

34.9/44.4

40/45

25*/30*

38/45.6

53.9/63.4

60/70

4.4

15

2
(ALT.)

380-3-60
(4 WIRE)

342

418

15

7.6

14.5

15

6/7.5

9.1/11.4

16.4/19.3

20/20

10*/12*

15.2/18.2

24/27.8

25/30

15*/20*

22.8/30.4

33.5/43

35/45

25*/30*

38/45.6

52.5/62

60/70

6.4

15

7.6

15.9

20

6.3

12.3

15

6/7.5

7.5/9.4

13.8/16.1

15/20

10*/12*

12.6/15.1

20.1/23.3

25/25

15*/20*

18.8/25.1

27.9/35.8

30/40

25*/30*

31.4/37.7

43.6/51.5

45/60

5.1

15

6.3

13

15

4.4

15

6/7.5

7.5/9.4

14.5/16.9

15/20

6.3

12.3

15

10*/12*

12.6/15.1

20.9/24

25/25

15*/20*

18.8/25.1

28.6/36.5

30/40

25*/30*

31.4/37.7

44.4/52.3

45/60

3
5.14
(STD.)

2
(ALT.)

460-3-60

414

3.5

506

Full Load Amps

HP

ELECTRIC HEATER

LEGEND
FLA

VOLTAGE
RANGE

3
(STD.)

MOCP Maximum Over Current Protection

* Combination of 2 heater modules

17

4.1

6/7.5

9.1/11.4

17.8/20.7

20/25

10*/12*

15.2/18.2

25.4/29.2

30/30

15*/20*

22.8/30.4

34.9/44.4

40/45

25*/30*

38/45.6

53.9/63.4

60/70

6/7.5

7.5/9.4

13.8/16.1

15/20

10*/12*

12.6/15.1

20.1/23.3

25/25

15*/20*

18.8/25.1

27.9/35.8

30/40

25*/30*

31.4/37.7

43.6/51.5

45/60

5.1

15

6.3

13

15

6/7.5

7.5/9.4

14.5/16.9

15/20

10*/12*

12.6/15.1

20.9/24

25/25

15*/20*

18.8/25.1

28.6/36.5

30/40

25*/30*

31.4/37.7

44.4/52.3

45/60

ELECTRICAL DATA
MODEL No.: BY14
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

MAX.

MODEL No.: BY18

BLOWER
MOTOR
HP

FLA

5
13.8
(STD.)

208/230-3-60

187

kW

MIN.

6.9

Full Load Amps

HP

Horse Power

MCA

Minimum Circuit Amps

MCA
kW

MOCP

FLA

17.3

30

17.3

30

33

40

12.6

33

40
45/45

15.1/18.8

36.1/40.8

45/45

25.1/30.1

48.6/54.9

50/60

15*/20*

37.7/50.2

64.4/80

70/90

25*/30*

62.8/75.3 95.8/111.4 100/125

5
13.8
(STD.)

187

253

6/7.5

15.1/18.8

36.1/40.8

10*/12*

25.1/30.1

48.6/54.9

50/60

15*/20*

37.7/50.2

64.4/80

70/90

25*/30*

62.8/75.3 95.8/111.4 100/125

35*/40*

87.9/100.4 127.1/142.8 150/150

24.4

40

24.4

40

12.6

40.1

50

12.6

40.1

50

6/7.5

15.1/18.8

43.3/47.9

50/60

10*/12*

25.1/30.1

55.8/62

60/70

15*/20*

37.7/50.2

71.5/87.1

80/90

25*/30*

62.8/75.3 102.9/118.5 110/125

11.3

20

7.6

20.8

25

6/7.5

9.1/11.4

22.6/25.5

25/30

10*/12*

15.2/18.2

30.3/34

35/35

15*/20*

22.8/30.4

39.8/49.3

45/50

25*/30*

38/45.6

58.8/68.3

60/70

15.6

7.6

25.1

35

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

15*/20*

22.8/30.4

44.1/53.6

25*/30*

38/45.6

63.1/72.6
8.6

380-3-60
(4 WIRE)

342

418

7.5
12.5
(ALT.)

6/7.5

15.1/18.8

43.3/47.9

50/60

10*/12*

25.1/30.1

55.8/62

60/70

15*/20*

37.7/50.2

71.5/87.1

80/90

25*/30*

62.8/75.3 102.9/118.5 110/125

35*/40*

87.9/100.4 134.3/149.9 150/175

11.3

20

7.6

20.8

25

6/7.5

9.1/11.4

22.6/25.5

25/30

10*/12*

15.2/18.2

30.3/34

35/35

15*/20*

22.8/30.4

39.8/49.3

45/50

25*/30*

38/45.6

58.8/68.3

60/70

35*/40*

53.2/60.8

77.8/87.3

80/90

15.6

25

7.6

25.1

35

6/7.5

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

15*/20*

22.8/30.4

44.1/53.6

50/60

50/60

25*/30*

38/45.6

63.1/72.6

70/80

70/80

35*/40*

53.2/60.8

82.1/91.6

90/100

8.6

15

6.3

16.5

20
20/25

15

6.3

16.5

20

6/7.5

7.5/9.4

18/20.4

20/25

10*/12*

12.6/15.1

24.4/27.5

15*/20*

18.8/25.1

25*/30*

31.4/37.7

5
(STD.)

25

6/7.5

7.5
19.5
(ALT.)

6/7.5

7.5/9.4

18/20.4

10*/12*

12.6/15.1

24.4/27.5

30/30

30/30

15*/20*

18.8/25.1

32.1/40

35/45

32.1/40

35/45

25*/30*

31.4/37.7

47.9/55.8

50/60

47.9/55.8

50/60

35*/40*

43.9/50.2

63.5/71.4

70/80

12.2

20

6.3

20.1

25

12.2

5
(STD.)

460-3-60

414

6.9

506

20

6.3

20.1

25

6/7.5

7.5/9.4

21.6/23.9

25/30

10*/12*

12.6/15.1

27.9/31.1

30/35

15*/20*

18.8/25.1

35.7/43.6

40/45

25*/30*

31.4/37.7

51.4/59.3

60/70

7.5
9.75
(ALT.)

LEGEND
FLA

FLA

7.5
9.75
(ALT.)

HP

ELECTRIC HEATER

12.6

6/7.5

506

MAX.

BLOWER
MOTOR

5
(STD.)

VOLTAGE
RANGE

414

FLA

10*/12*

418

7.5
12.5
(ALT.)

460-3-60

MOCP

208/230-3-60

5
(STD.)

342

MCA

253

7.5
19.5
(ALT.)

380-3-60
(4 WIRE)

POWER
SUPPLY
(V-Ph-Hz)

ELECTRIC HEATER

MOCP Maximum Over Current Protection

* Combination of 2 heater modules

18

6/7.5

7.5/9.4

21.6/23.9

25/30

10*/12*

12.6/15.1

27.9/31.1

30/35

15*/20*

18.8/25.1

35.7/43.6

40/45

25*/30*

31.4/37.7

51.4/59.3

60/70

35*/40*

43.9/50.2

67.1/74.9

70/80

ELECTRICAL DATA
MODEL No.: BY25
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

MAX.

BLOWER
MOTOR
HP

187

253

10
26.1
(ALT.)

7.5
12.5
(STD.)

380-3-60
(4 WIRE)

342

418

10
(ALT.)

414

506

10
(ALT.)

kW

25.5

45

12.6

41.2

50

6/7.5

15.1/18.8

44.3/49

60/60

25.1/30.1

56.9/63.2

70/70

15*/20*

37.7/50.2

72.6/88.3

80/90

25*/30*

62.8/75.3 103.9/119.6 110/125

35*/40*

87.9/100.4 135.3/151 150/175

32.6

50

12.6

48.3

70

6/7.5

15.1/18.8

51.5/56.2

70/70

10*/12*

25.1/30.1

64/70.3

80/80

15*/20*

37.7/50.2

79.7/95.4

90/100

25*/30*

62.8/75.3 111.1/126.8 125/150

35*/40*

87.9/100.4 142.4/158.1 150/175

15.6

25

7.6

25.1

35

6/7.5

9.1/11.4

27/29.9

35/35

10*/12*

15.2/18.2

34.6/38.4

40/45

15*/20*

22.8/30.4

44.1/53.6

50/60

25*/30*

38/45.6

63.1/72.6

70/80

35*/40*

53.2/60.8

82.1/91.6

90/100

20

35

7.6

29.5

40

6/7.5

9.1/11.4

31.4/34.2

45/45

10*/12*

15.2/18.2

39/42.8

50/50

15*/20*

22.8/30.4

48.5/58

50/60

25*/30*

38/45.6

67.5/77

70/80

35*/40*

53.2/60.8

86.5/96

90/100

12.8

20

6.3

20.6

25

6/7.5

7.5/9.4

22.2/24.5

30/30

10*/12*

12.6/15.1

28.4/31.6

35/35

15*/20*

18.8/25.1

36.3/44.1

40/45

25*/30*

31.4/37.7

52/59.8

60/60

35*/40*

43.9/50.2

67.7/75.5

70/80

16.3

25

6.3

24.1

35

13

6/7.5

7.5/9.4

25.7/28

35/35

10*/12*

12.6/15.1

31.9/35.1

40/40

15*/20*

18.8/25.1

39.8/47.6

45/50

25*/30*

31.4/37.7

55.5/63.3

60/70

35*/40*

43.9/50.2

71.2/79

80/80

LEGEND
FLA

Full Load Amps

HP

Horse Power

MCA

Minimum Circuit Amps

MOCP

FLA

10*/12*

16

7.5
10.2
(STD.)

460-3-60

MCA

FLA

7.5
20.4
(STD.)

208/230-3-60

ELECTRIC HEATER

MOCP Maximum Over Current Protection

* Combination of 2 heater modules

19

DIMENSIONS
BY07 - BY14 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL

BY07

1360(53.5) 1100(43.31) 600(23.62)

BY10

1490(58.7) 1400(55.12) 675(26.57)

BY14

1625(64)

1600(63)

705(27.75)

813(32)

182(7.16) 406(15.98)

66(2.6)

995(39.17) 550(21.65) 378(14.88) 721(28.38) 123(4.84)

813(32)

332(13.1) 406(15.98)

42(1.65)

1321(52)

187(7.36) 406(15.98)

55(2.16) 1495(58.86) 655(25.8) 471(18.54) 791(31.14) 153(6.02)

1295(51)

625(24.61) 378(14.88) 721(28.38)

20

198(7.8)

DIMENSIONS
BY07 - BY14 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL

BY07

1360(53.5) 1100(43.31) 600(23.62)

BY10

1490(58.7) 1400(55.12) 675(26.57)

BY14

1625(64)

1600(63)

705(27.75)

813(32)

213(8.4)

406(15.98)

85(3.34)

991(39)

504(19.83) 302(11.87) 697(27.53) 110(4.33)

813(32)

365(14.38) 406(15.98)

35(1.38) 1299(51.15) 607(23.91) 338(13.29) 732(28.81) 123(4.84)

1321(52)

224(8.82) 406(15.98)

49(1.92) 1497(58.95) 607(23.91) 370(14.59) 929(36.56) 110(4.33)

21

DIMENSIONS
BY18 - BY25 (HORIZONTAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY18
BY25

A
1625(64)

2070(81.5) 705(27.75)

1825(71.85) 2362(93)

840(33.1)

1575(62)

382(15.04) 483(19.02)

35(1.38)

1965(77.36) 655(25.79) 471(18.54) 791(31.14)

1575(62)

590(23.23) 483(19.02)

50(1.97)

2257(88.86) 790(31.1)

22

503(19.8)

M
153(6.02)

913(35.94) 288(11.34)

DIMENSIONS
BY18 - BY25 (VERTICAL DISCHARGE)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).


DIMENSIONS
MODEL
BY18
BY25

A
1625(64)

2070(81.5) 705(27.75)

1825(71.85) 2362(93)

840(33.1)

1575(62)

422(16.61) 483(19.02)

46(1.81)

1969(77.52) 596(23.46) 354(13.94) 878(34.57)

110(4.33)

1575(62)

625(24.61) 483(19.02)

74(2.91)

2217(87.28) 596(23.46) 704(27.72) 878(34.57)

110(4.33)

23

DIMENSIONS - HEATER BOX


BY07 - BY14

412

(1 6

.2")

205 (8.1")

P
) TY
(1"
4
.
25

DIMENSIONS
MODEL

HEATER ACCESS COVER

BY07

818 (32.2)

BY10

818 (32.2)

BY14

1326(52.2)

HEATER CONTROLS MTG


COVER
HEATER CONTROLS MTG
PLATE

BY18 - BY25

(1
492

")
9.4

P
TY

205 (8.1")

")
4 (1
25.

1581 (6
2.3")

HEATER ACCESS COVER


(BOTH SIDES)

HEATER CONTROLS MTG


COVER
HEATER CONTROLS MTG
PLATE

NOTES:

1. All dimensions are in mm (dimensions in brackets are in inches).


2. Heater box is an optional feature.

24

DIMENSIONS

1016 [40"]

1061 [41.771"]

MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY075 - CY120

571 [22.480"]

190 [7.480"]

115 [4.527"]

1123 [44.212"]

1161 [45.708"]

966 [38.031"]

82 [3.228"]

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Dual system units will have 2 set of service valves.
3. Allow 32" (812 mm) clearance to service end of the unit, 24" (610 mm) on remaining sides and 48" (1219 mm) between units for
proper airflow.

25

DIMENSIONS
MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY150 - CY300

MODEL NUMBER

CY150 - CY220

1900 (74.8)

1120 (44.09)

1145 (45.07)

1071 (42.16)

150 (5.9)

800 (31.5)

800 (31.5)

CY240 - CY300

2200 (86.61)

1225 (48.23)

1300 (51.18)

1179 (46.41)

300 (11.81)

800 (31.5)

800 (31.5)

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Single system units will have 1 set of service valves.
3. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

26

DIMENSIONS

195 [7.677"]

MATCHING CONDENSING (OUTDOOR) UNIT, MODEL No.: CY360

NOTES:
1. All dimensions are in mm, (dimensions in brackets are in inches).
2. Allow 32" (812 mm) clearance to service end of the unit, 48" (1219 mm) on remaining sides for proper airflow.

27

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with single compressor units)
HVTB OR BMC
L1

REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY

L2
L3

LUG

70

69

68

BMC

BM
TO CONDENSING UNIT ATB

HC2

AFS
NC

28

HC1

C
NO

230V

BMC
TO CONDENSING UNIT ATB

LOCK2(RED)

SYSTEM1(YEL)

29

30

PRI

ECB

LOCK1(RED)

SYSTEM2(ORG)
FUSE

TRANS

P3_##

DIP

POWER(GRN)

W2 W1 Y1 G

TO CONDENSING UNIT ATB

J_PROG

THERMOSTAT / DDC CONTROLLER


(by others)

LVTB
R
C
G
Y1
W1
W2

CONNECTION APPLICABLE FOR 1PH BM

R
24Vac

BM CONTROL

STG1 COOLING

Y1

STG1 HEATING

W1

STG2 HEATING

W2

APPLICABLE FOR BM WITH


EXTERNAL OLR (OPTION)

L3

L2

L1

TO HVTB

BMC

70

69

OLR
68

SEC

ON

DIP SWITCH

BM

LVTB
18 OLR 19
G

BM

BMC

ATB
2

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

28

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with single compressor units)

LEGEND

ECB DIP SWITCH SETTINGS & LED INDICATORS

OFF= WITHOUT PUMP DOWN

ON= WITH PUMP DOWN OPTION

on-board programming function (always set to on)

TO HVTB

HC1

29

28

HEATER TYPES

H1

H2

OHT
(#1)
H3

FL

FL
OHT
(#2)

FL

OHT
FL

FL
FL
OHT

F11
F12
F13

F17
F18
F19

HEATER OPTION-2

STG
1

I STG
5 K.W

71A
72A
73A
T1F
T2F
T3F

HEATER2

HEATER3

HEATER4

28
HC1

(SEE TABLE)

HC2

30

28

28

(SEE TABLE)

HEATER OPTION-3

II STG

AI
AFS
ATB
AR
BM
BMC
CAP
ECB
FL
HC
HVTB
HTR
L1
L2
L3
LVTB
LUG
MOHT
NTB
OHT
OLR

ANTI ICE THERMOSTAT


AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
AUXILIARY RELAY
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
CAPACITOR
ELECTRONIC CONTROL BOARD
FUSE LINK
HEATER CONTACTOR
HIGH VOLTAGE TERMINAL BLOCK
HEATER
LINE 1
LINE 2
LINE 3
LOW VOLTAGE TERMINAL BLOCK
LUG GROUND
MANUAL RESET OHT
NEUTRAL TERMINAL BLOCK
OVERHEAT THERMOSTAT
OVER LOAD RELAY

SM
VFC

SYSTEMIZER
VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT

___

OPTIONS

1) ANTI ICE OPTION

COMP

6 K.W

6 K.W

7.5 K.W

7.5 K.W

10 K.W

5 K.W

12 K.W

6 K.W

6 K.W

15 K.W

7.5 K.W

7.5 K.W

AI-1

21A

23A

LPS

10 K.W

10 K.W

25 K.W

12.5 K.W

12.5 K.W

30 K.W

15 K.W

15 K.W

35 K.W

*
*

7.5+10 K.W

7.5+10 K.W

2*10 K.W

2*10 K.W

NOTES: HTR-35 & 40KW IS APPLICABLE FOR


BY 18 MODEL ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODEL
USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
THERMOSTAT CONTROL VOLTAGE - 24VAC.

5 K.W

20 K.W

40 K.W
H4

OPT#
2

HC2

HEATER1

HC3

HEATER DATA TABLE


HTR
5 K.W

OHT

30

HEATER DATA TABLE

OHT
FL

OHT

28

29

(SEE TABLE)

HEATER OPTION-1

L1 L2 L3

T1H
T2H
T3H

T1F
T2F
T3F
HC1

29

OHT
FL

HEATER3

28

HC4

HC2

TO HVTB

HC1

HC3

HEATER1

HEATER4
HC3

S4

L1 L2 L3

74A
75A
76A

74B
75B
76B

HEATER3
30

HC1

HC4
T1I
T2I
T3I

T1H
T2H
T3H

T1G
T2G
T3G

T1F
T2F
T3F

HEATER2

HEATER1

HC3

HC2

71A F11
72A F12
73A F13

F17
F18
F19
74A
75A
76A

F14
F15
F16
71B
72B
73B

F11
F12
F13
71A
72A
73A
HC1

S3

TO HVTB
L1 L2 L3

L1 L2 L3

L1 L2 L3

F20
F21
F22

L1 L2 L3

S2

note:
Set dip switch # 3 according to unit's option
(pump down or no pump down)

TO HVTB
L1 L2 L3

S1

T1I
T2I
T3I

S3
S4

DIP SWITCH #
ON
OFF

F17
F18
F19

ON= COMPRESSOR 1 LEAD

74A
75A
76A

ON= TEST MODE ENABLE

LOAD BALANCE
OFF= (Comp1&2 Auto Lead Lag)

T1H
T2H
T3H

OFF=TEST MODE DISABLE

S2

T1G
T2G
T3G

S1

L1 L2 L3

LED INDICATORS
Green power on/off indicator
Red
system lock-out due to system fault
system 1 fault diagnostic
Yellow blinking slow - LPS1/ HPS1/ SSPS1/
OLR1/CB1 ckt fault
system 2 fault diagnostic
Orange blinking slow - LPS2/ HPS2/ SSPS2/
OLR2/ CB2 ckt fault

FACTORY SETTINGS OF DIP SWITCHES

DIP SWITCH FUCTIONS

CONNECTION APPLICABLE FOR ANTI ICE

2. ANY WIRE REPLACEMENT SHOULD BE OF THE


900C OR ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.

2) VFC OPTION FOR BM RUN &TRIP INDICATION

48

48A

BMCA-1A

49

3. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT


CYCLE PROTECTION FOR COMPRESSOR IS AVAILABLE IN ZAMIL ELECTRONIC THERMOSTAT.

BM ON
51A

51

*
*

BMCA-2A

52

5. FUSED DISCONNECT SWITCH OR CIRCUIT


BREAKER TO BE PROVIDED BY CONSUMER WITH
RATING AS RECOMMENDED BY ZAMIL.

BM TRIP
BM TRIP CONNECTION FOR BM WITH OLR

OLR-2

51

BM TRIP

29

4. IF HEATERS ARE FACTORY INSTALLED, PLEASE


READ BROKEN LINES AS CONTINUOUS LINES.

52

6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.
7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE
BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
UNITS WITH 380 VOLT.

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with dual compressor units)
APPLICABLE FOR 1PH BM

TO HVTB

L2

69

L3

70

BM

L3

68
L2

BMC

L1

REFER TO UNIT
NAMEPLATE FOR
POWER SUPPLY

L1

HVTB

APPLICABLE FOR BM WITH EXTERNAL OLR

BMC
OLR

70

69

68

LUG

BM

LVTB
18
G

OLR 19

BMC

ATB
2

TO CU ATB
HC2
HC1

28

NC
C
NO

BMC
TO CONDENSING UNIT ATB

3B

3A
COMP1

4A
P1

COMP2

4B
P2

29

30

14
INFAN

ECB

LOCK1(RED)
SYSTEM1(YEL)

29

30

PRI

HEATER1

41A
X1

LOCK2(RED)
SYSTEM2(ORG)

HEATER2

41B
X2

OUTFAN1

OUTFAN2

TO CU ATB

NEUTRAL

LIVE

230V

FUSE

(HP1)

12v-0-12v

HP2
(HP2)
SEC

TRANS

HP1
240v

DIP SWITCH
POWER(GRN)
J_PROG

LP1

26A

(LP1)

23A

LP2

22B

(LP2)

23B

13
14

TO CONDENSING UNIT ATB

15
16

THERMOSTAT / DDC CONTROLLER


LVTB

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

30

TYPICAL SCHEMATIC WIRING DIAGRAM


(Matching with dual compressor units)
LEGEND

ECB DIP SWITCH SETTINGS & LED INDICATORS

S1

OFF=TEST MODE DISABLE

S2

OFF=

LED INDICATORS

FACTORY SETTINGS OF DIP SWITCHES

DIP SWITCH FUCTIONS


ON= TEST MODE ENABLE

LOAD BALANCE
(Comp1&2 Auto Lead Lag)

DIP SWITCH #

S1

S2

S3

Green

power on/off indicator

Red

system lock-out due to system fault

Yellow

blinking slow - LPS1/ HPS1/ SSPS1/

S4

system 1 fault diagnostic

ON
OFF

ON= COMPRESSOR 1 LEAD

OLR1/CB1 ckt fault


note:
Set dip switch # 3 according to unit's option
(pump down or no pump down)

TO HVTB

HC1

29

28

HC1

HEATER TYPES

H1

HTR

OHT

H2

OHT
(#1)
H3

FL

FL
OHT
(#2)

FL

OHT
FL

FL
FL
OHT

HEATER OPTION-2

STG

I STG
5 K.W

F11
F12
F13
71A
72A
73A
T1F
T2F
T3F

T1I
T2I
T3I

HEATER3

HEATER4

28
HC1

(SEE TABLE)

HC2

30

28

28

(SEE TABLE)

HEATER OPTION-3

II STG

6 K.W

6 K.W

7.5 K.W

7.5 K.W

10 K.W

5 K.W

5 K.W

12 K.W

6 K.W

6 K.W

15 K.W

7.5 K.W

7.5 K.W

20 K.W

10 K.W

10 K.W

25 K.W

12.5 K.W

12.5 K.W

30 K.W

15 K.W

15 K.W

35 K.W

*
*

7.5+10 K.W

7.5+10 K.W

2*10 K.W

2*10 K.W

COMP1
AI-1

NOTES: HTR-35 & 40KW IS APPLICABLE FOR


BY 18 & 25 MODELS ONLY.
USE OPTION 1 FOR 230V-3PH UNIT MODEL
USE OPTION 3 FOR 380V/460V-3PH UNIT MODEL

1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.


THERMOSTAT CONTROL VOLTAGE - 24VAC.

COMP2

AI-2

21B

23B

LPS2

48A

4. A 3 TO 4 MINUTE (APPROX.) BUILT-IN SHORT


CYCLE PROTECTION FOR COMPRESSOR IS AVAILABLE IN ZAMIL ELECTRONIC THERMOSTAT.

49

BM ON
51

51A

52

BM TRIP CONNECTION FOR BM WITH OLR

51

BM TRIP

31

5. FUSED DISCONNECT SWITCH OR CIRCUIT


BREAKER TO BE PROVIDED BY CONSUMER WITH
RATING AS RECOMMENDED BY ZAMIL.
6. FOR ANY SAFETY TRIP OF COMP. (FAULT), VOLTAGE ACROSS TERMINAL X1, X2 & 2 IS 230 VAC.

BM TRIP

OLR-2

2. ANY WIRE REPLACEMENT SHOULD BE OF THE


900C OR ITS EQUIVALENT.
USE COPPER CONDUCTOR WIRES ONLY.
3. IF HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.

2) VFC OPTION FOR BM RUN &TRIP INDICATION

*
*

LEAD LAG SWITCH


MANUAL RESET OHT
NEUTRAL TERMINAL BLOCK
OVERHEAT THERMOSTAT
OVER LOAD RELAY
SYSTEMIZER
VOLT FREE CONTACT
FIELD WIRING
DISCONNECT TAB - 1/4"
FL OR MOHT

NOTES

23A

LPS1

48

LLS
MOHT
NTB
OHT
OLR
SM
VFC
+

1) ANTI ICE OPTION

21A

ANTI ICE THERMOSTAT


AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
AUXILIARY RELAY
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
ELECTRONIC CONTROL BOARD
FUSE LINK
HEATER CONTACTOR
HIGH VOLTAGE TERMINAL BLOCK
HEATER
LINE 1
LINE 2
LINE 3
LOW VOLTAGE TERMINAL BLOCK
LUG GROUND

___

OPTIONS

40 K.W
H4

OPT#

HEATER2

HEATER1

HC3

HEATER DATA TABLE


5 K.W

OHT

30

HEATER DATA TABLE

OHT
FL

FL

28

29

(SEE TABLE)

HEATER OPTION-1

OHT

F17
F18
F19

28
29

HC2

T1H
T2H
T3H

T1I
T2I
T3I
HC3

HEATER3

HC4

HC2

L1 L2 L3

HC1

HC3

HEATER1

HEATER4

TO HVTB

L1 L2 L3

74A
75A
76A

74B
75B
76B

HC1

HC4

HEATER3
30

71A F11
72A F12
73A F13

F20
F21
F22

F17
F18
F19
T1H
T2H
T3H

T1G
T2G
T3G

T1F
T2F
T3F

HEATER2

HEATER1

HC3

HC2

TO HVTB
L1 L2 L3

T1F
T2F
T3F

HC1

L1 L2 L3

L1 L2 L3

74A
75A
76A

F14
F15
F16
71B
72B
73B

71A
72A
73A

F11
F12
F13

L1 L2 L3

blinking slow - LPS2/ HPS2/ SSPS2/


OLR2/ CB2 ckt fault

F17
F18
F19

TO HVTB
L1 L2 L3

L1 L2 L3

system 2 fault diagnostic


Orange

T1H
T2H
T3H

on-board programming function (always set to on)

T1G
T2G
T3G

OFF= WITHOUT PUMP DOWN

74A
75A
76A

ON= WITH PUMP DOWN OPTION

S3
S4

AI
AFS
ATB
AR
BM
BMC
ECB
FL
HC
HVTB
HTR
L1
L2
L3
LVTB
LUG

52

7. NTB IS APPLICABLE FOR UNITS WITH 1 PHASE


BLOWER MOTOR ONLY. ALSO APPLICABLE FOR
UNITS WITH 380 VOLT.

CONTROLS & SEQUENCE OF OPERATION


Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct
rotation when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and
discharge pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low
current draw and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit
allow complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when
using an air cleaner) or have the fan come on with the compressor.
SWITCH FUNCTION
- On/Off Key
: Switch the system On or Off.
- Up Key
: To increases the set temperature.
- Down Key
: To decreases the set temperature.
- Mode Key
: Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key
: Changes the Fan Operation to Auto or Continuous.
- C/F selection : By pressing Mode & UP key together, toggles between C to F or vice versa.
USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:
O
T
U
A

T
A
E
H

L
O
O
C

N
A
F

In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Fan:

Cool:
In this mode of operation, the compressor will be ON after a delay depending on the differential of room
temperature & Set temperature.
In this mode of operation, Fan is ON.

Heat:

Auto:
In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Thermostat automatically switches to maintain the desired temperature.
DIP SWITCH OPTIONS AND FUNCTIONS
There are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by
the installer.
HOOK-UP WIRING DIAGRAM
DIP SWITCH SELECTION
( THERMOSTAT CONTROLLER TO AIR HANDLING UNIT )
SWITCH

ON

OFF

N. A.

N. A.

N. A.

3
4

THERMOSTAT
(ZAC P/N 80065261)

Y2

NOTE: OPTIONAL CONNECTION :


IF REMOTE TEMPERATURE SENSING
FUNCTION IS REQUIRED.

INDOOR SENSOR REMOTE SENSOR

W1
Y1

SENSOR

Note:
Keep DIP SWITCH 1, 2 & 3 in OFF
position only.

REMOTE
SENSOR

ACCU CONTROL PANEL

G
24V(R)

COMPRESSOR FAULT SIGNAL


(VOLT-FREE CONTACT)

ATB

24V(C)
FAULT 1

COMP 1
( OPTIONAL CONNECTION )

FAULT 2

COMP 2
(COMMON)

AHU CONTROL PANEL


LVTB
R

24V ac

C
G
Y1
Y2

LEGEND:
ATB
LVTB

AUXILIARY TERMINAL BLOCK


LOW VOLTAGE TERMINAL BLOCK

32

SUPPLY FAN CONTROL


STG1 COOLING
STG2 COOLING

W1

STG1 HEATER

W2

STG2 HEATER

W2

INSTALLATION INSTRUCTIONS
A. GENERAL
Blower units are shipped completely wired. Only external power, interconnecting control wiring between outdoor and
indoor units and refrigerant pipe connections are needed to complete the installation. For detailed instructions/informations, please refer to corresponding IOM manual.

B. UNIT LOCATION & ACCESS SPACE


The placement of the unit in relationship to the building is very important. A minimum of 36 inches clearance must be
kept on the service access side and return air side.
When making tubing connections, be sure to provide clearance for electrical connections.

C. TUBING INSTALLATION
Do not remove plugs from the compression fittings until tubing has been run and is ready for connection.
a. Make sure the tubing is round, without dent or burrs.
b. Cut tubing to the length required with a tube cutter carefully. Do not use a hacksaw.
c. Remove burr from inside and outside using file or deburring tool.
NOTE: Always use a gear type tube bender when making bends in suction line.
When installing tubing through walls or along side of any structural members, be sure the tubing is isolated from these
members or walls to avoid any transmission of vibration that may occur, while unit is running.

ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply will result in damage to the unit.
NOTE: Use copper wires of proper rating for all field wiring.
Warning
Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.
B) Ground & power wires
Connect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.
C) Control wiring between outdoor & indoor unit
Use 16 gauge color-coded wire between the indoor and outdoor units (control wiring).

STEP 2: START-UP
Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging method details.

STEP 3: SEQUENCE OF OPERATION


With power supplied to indoor and outdoor units, the unit starts responding to the thermostat mode requirement.
Cooling mode: When thermostat calls for cooling, the blower motor in the indoor unit is switched on. The compressor
contactor is energized to start the compressor and condenser fan.
As the conditioned space approaches the thermostat cooling set point, the unit cycles off.
Heating mode: When thermostat calls for heating, the blower motor in the indoor unit is switched on. The contactor for
electric heater is switched on to energize the heaters. If the room temperature is not satisfied and there are two heaters
installed, the second heater also will be energized.
Once, the conditioned space approaches the desired temperature set point, the heating stages cycles off.
Fan mode: In this mode the indoor unit blower motor is switched on alone.

33

PL-AP-BY2-10-2M-E