GEA Cassette-Geko fan coil unit

Data and Facts


12/1998 (GB)

The GEA Cassette-Geko is a recent


addition to GEAs well-established
product lines for central and
decentralized heating, ventilating and
cooling.
Applications include, for example,
airports, banks, bars, boutiques, coffee
houses, commercial premises,
delicatessen shops, exhibition rooms,
fashion houses, fast-food restaurants,
furniture marts, hotels, industrial
premises, insurance company offices,
post offices, public buildings,
restaurants, retail outlets, shopping
centers, shopping malls, show
rooms, stores and supermarkets.
The GEA Cassette-Geko serves the
following functions:
1.
Cooling using chilled water
2.
Heating using hot water
3.
Filtration
4.
Treated air supply
5.
Air distribution to adjacent rooms
The GEA Cassette-Geko has been
developed for integration in suspended
ceilings featuring 600 x 600 mm (single
unit) or 1,200 x 600 mm (double unit)
panels.
The GEA Cassette-Geko is not suitable
for explosive atmospheres, moist
atmospheres, outdoor installation or
high-dust or corrosive atmospheres. Atmospheres containing dust and/or other
materials producing acidic or alkaline reactions when in contact with water may
be the cause of aluminum fin corrosion
especially in the case of units used for
cooling.
For this reason, units must be protected
against this type of material and filters
must be cleaned or replaced after construction. If necessary, copper/copper
heat exchangers or coated fins must be
specified.
The manufacturer and the seller cannot
be held liable for any defect or damage
attributable to applications for which the
GEA Cassette-Geko is not suitable.

Model code

Panel

Control system

(example)

Type
Size
Heat exchanger

GEA Cassette-Geko

Cassette
fan coil unit

G6 . S 1 4 . 0 3 1

G6
S
D

Single unit (600 x 600 mm)


Double unit (1200 x 600 mm)

1
2

Size 1
Size 2

2
4

2-pipe system (3 pipe rows)


4-pipe system (2 + 1 pipe rows)

01
02
03
04
05
06
07

Terminal box for thermostat control


MCE 4 control system
MCB3200 control system
MCE4 control system + extract air sensor
MCB3200 control system + extract air sensor
MCB3200 control system + MCB.UB + supply air sensor
MCB3200 control system + MCB.UB + supply air sensor +
extract air sensor

Bright white panel (RAL 9003)*


pastel turquoise air discharge vanes (similar to RAL 6034)*

Bright white panel (RAL 9003)


Flocked pastel turquoise air discharge vanes (RAL 6034)

Bright white panel (RAL 9003)


Light grey air discharge vanes (RAL 7035)

Bright white panel (RAL 9003)


Flocked light grey air register slats (RAL 7035)

Other colour (panel and unflocked air


discharge vanes only.

*Standard

R
N
T
Q
S
1
2
3
4

Motorized 230 VAC


Motorized 24 VAC*
Thermoelectric 230 VAC
Thermoelectric 24 VAC*
Continuous, 24 VAC, 0-10 V (owner control System only)
T (3 rows), R (1 row)
R (3 rows), T (1 row)
4-pipe
Q (3 rows), N (1 row)
systems only
N (3 rows), Q (1 row)

2
3
8
9

2-way (heating/cooling); 2/4-pipe systems


3-way (heating/cooling); 2/4-pipe systems
2-way (cooling), 3-way (heating); 4-pipe systems
3-way (cooling), 2-way (heating); 4-pipe systems

03
04
06
10
16
25
40

kvs = 0,25 (valve actuators R, N, S)


kvs = 0,40 (valve actuators R, N, S)
kvs = 0,63 (valve actuators R, N, S)
kvs = 1,00 (valve actuators R, N, S)
kvs = 1,60 (valve actuators R, N, S, T, Q)
kvs = 2,50 (valve actuators R, N, S, T, Q)
kvs = 4,00 (valve actuators R, N, S)

03
04
06
10
16
25
40

kvs = 0,25 (valve actuators R, N, S)


kvs = 0,40 (valve actuators R, N, S)
kvs = 0,63 (valve actuators R, N, S)
kvs = 1,00 (valve actuators R, N, S)
kvs = 1,60 (valve actuators R, N, S, T, Q)
kvs = 2,50 (valve actuators R, N, S, T, Q)
kvs = 4,00 (valve actuators R, N, S)

0
1

No isolating valves
Flow and return isolating valves

isolating valves unit


type

kvs - V
(3 rows/2 rows, 2/4-pipes)
kvs - V
(1row, 4 pipes only)

Page

Introduction ..........................................1.1
GEA Cassette-Geko
Unit Model Code ................................1.2
Valve Model Code ..................................2
Units and Control System
Components ..........................................3
Technical Data, Single Unit, Size 1 .......4
Technical Data, Single Unit, Size 2 .......5
Technical Data, Double Unit, Size 1 .....6
Technical Data, Double Unit, Size 2 .....7
Heat Exchanger Pressure Drops ...........8
Capacity Calculations ............................9
Motorized Valves .................................10
Valves with Thermoelectric
Actuators ..............................................11
Treated Air Supply ...............................12
Air Distribution .....................................13
Sound Pressure and Sound
Power Levels .......................................14
NR and NC Numbers ..........................15
Fan coil Unit Noise Data ....................16
Dimensions and Weights ....................17
MCR 3201/3301 Control System .......18
Typical MCR 3201/3301 Installation .19
MCR 3201/MCR 3301
Design Alternatives ......................20-21
MCR 3101 Control System ...................22
Typical MCR 3101 Installation ............23
MCR 3101 Design Alternatives .....24-25
Thermostat and
Fan Control Systems ..........................26
Typical Thermostat Control
System Installation .............................27
Thermostat Control System
Design Alternatives ............................28
Thermostat and Fan Control
System Design Alternatives ..............29
Control System Components .........30-31
Specification text ...........................32-37

VR31610.1S
valve type

Contens

Valve Model Code

valve actuator

Table of Contents

S Single unit (600 x 600 mm)


D Double unit (1200 x 600 mm)
*) Note! provided by others 24 V transformer

Subject to modifications-05/2000

Units and Control System Components


Single unit for heating and cooling (4-pipe system), motorized
three-way valves for continuous control and additional
condensate tray.

Electrical equipment e.g. MCB.UB controller for minimum/


maximum supply air temperature control.

Fig. 3.2

Fig. 3.1
Double unit for heating and cooling (4-pipe system), motorized
three-way valves for continuous control and isolating valves
(no additional* condensate tray).

MCR3201W control unit for heating and cooling for


individual units and groups of units fit for integration with
building control system, maximum user comfort.
White (RAL 9010).
Additional clock and function display unit integrated in MCR3301W
control unit.

*) additional condensate tray as in Fig. 3.1


Fig. 3.3

Fig. 3.4

Valve set, motorized two and four-port valves,


230 VAC or 24 VAC.

MCR 3102W control unit for return air operation


for heating and cooling.
Functions: Valve and fan control.
White.

(four-port

valve

and

isolating

valves

shown)

Fig. 3.5
Valve set, two and four-port valves with thermoelectric
actuators, 230 VAC or 24 VAC.

Fig. 3.6
Thermostat control unit 983.861

(four-port valve and isolating valves shown)


Fig. 3.7

Subject to modifications-05/2000

Fig. 3.8

Single Unit Size 1 Two and four-pipe systems

speed

air flow rate


m3/h
m3/s

1
2
3

340
490
690

row(s)

Technical Data
230 V/50 Hz
power current
W
A

0,094
0,136
0,192

20
25
54

heat exchanger
sound
water connections powerlevel
capacity internal
dB(A)
thread
L

1
2
3

0,19
0,20
0,23

0,8
1,5
2,1

sound pressure level


(see p. 14 for test)

dB(A)

NR

NC

26
35
44

19
29
38

17
27
36

35
44
53

R1 /2"

G6.S12.

model

2-pipe systems, 3 rows


speed

cooling capacity

QK [kW]

1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

heating capacity

2,5
3,3
4,4

tL2 [C]

(heat exchanger)

2 [%r.F.]

11,2
12,0
13,0

p [kPa]

96
94
91

7,3
12,7
20,5

QH [kW]

1
2
3

inlet air = 20 C

1,8
2,5
3,3

speed

warm water 80/60 C

QS [kW]

Q S kW

5,7
7,7
10,1

t L2 [C]

(heat exchanger)

2 % r.F.

p [kPa]

69,7
66,8
63,6

3,1
5,4
8,9
G6.S14.

model

4-pipe systems, 1+2 rows

speed

cooling capacity

Q K [kW]

chilled water 6/12 C

1,9
2,7
3,5

2
3

inlet air = 27 C/ 46 % r. F.

heating capacity

speed

warm water 80/60 C


inlet air = 20 C

1
2
3

QS [kW]
1,5
2,2
2,8

Q S kW

3,7
4,9
6,2

p [kPa]
3,6
6,7
10,9

2 % r.F.

(heat exchanger)

p [kPa]

52,6
49,8
46,6

2,1
3,6
5,5

air inlet tL1 [C], 1 [% r. F.]

watertemperature
[C]

10

15

20

25

air inlet: tL1 [C]

32/40 30/40 27/46 26/50 24/50

32/40 30/40 27/46 26/50 24/50

1,25
-

1,23
-

1,21
1,15
1,10
1,04
0,98

1,00
0,95
0,90
0,84
0,78

0,93
0,88
0,83
0,77
0,71

0,80
0,75
0,83
0,69
0,62
0,57

80/60
70/55
70/50
60/50
60/40
50/40

1,22
1,07
0,99
0,91
0,77
0,70

1,10
0,96
0,89
0,81
0,65
0,59

1,00
0,86
0,78
0,71
0,54
0,49

0,90
0,75
0,67
0,60
0,41
0,38

0,99
0,99

0,85 0,63
0,84 0,63

0,57
0,57

0,45
0,43

40/30

0,48

0,36

0,25

1,21
1,11
1,02
0,90
0,80

0,84 0,66
0,80 0,65

1,00
0,89
0,81
0,71
0,62

0,96
0,87
0,76
0,66
0,57

0,72
0,65
0,75
0,57
0,49
0,44

0,49 0,44
0,49 0,44

0,35
0,33

Qs (sensible)

QK (total)

temperature [C]

chilled water-

(heat exchanger)

Correction factors - heating *)

air inlet: tL1 [C], 1 [% r. F.]

12/18
14/18

92
90
86

tL2 [C]

Correction factors - cooling *)

6/12
7/13
8/12
8/14
10/15
12/16

2 [% r.F.]

13,7
14,1
14,9

QH [kW]

tL2 [C]

*) Note!

Water flow rates


Model
G6. S1..

4-pipe system
1 row
2 rows
min. max.
min. max.
l/h l/h
l/h l/h
160 327
220 501

2-pipe system
3 rows
min. max.
l/h l/h
245 628

The capacities under different design


conditions determined by the above
correction factors are very approximate,
as the correction factors are arithmetic averages for all
models. The exact capacities are available from field and
office staff.

Subject to modifications-05/2000

Single Unit Size 2 Two and four-pipe systems

speed

1
2
3

air flow rate


m3/h
m3/s

230 V/50 Hz
power current
W
A

510
780
1030

72
96
123

0,142
0,217
0,286

row(s)

Technical Data
heat exchanger
sound
water connections powerlevel
dB(A)
capacity internal
L
thread

1
2
3

0,55
0,63
0,68

0,8
1,5
2,1

sound pressure level


(see p. 14 for test)

dB(A)

NR

NC

36
47
55

30
43
49

28
41
47

45
56
64

R1 /2"

G6.S22.

model

2-pipe systems, 3 rows

speed

cooling capacity

speed

heating capacity

inlet air = 20 C

2,6
3,6
4,4

tL2 [C]

(heat exchanger)

2 [% r.F.]

12,1
13,3
14,4

p [kPa]

93
90
86

13,5
24,2
33,5 *)
.

*) Above Vw =794 l/h limit

QH [kW]

t L2 [C]

QS kW

8,0
11,0
13,5

1
2
3

warm water 80/60 C

QS [kW]

3,5
4,8
5,7

1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

QK [kW]

(heat exchanger)

2 % r.F.

p [kPa]

66,5
62,1
58,9

5,7
10,5
15,2
G6.S24.

model

4-pipe systems, 1+2 rows

speed

cooling capacity

QK [kW]
1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

heating capacity

speed

warm water 80/60 C


inlet air = 20 C

1
2
3

QS [kW]

2,8
3,7
4,5

2,2
3,1
3,8

tL2 [C]
14,2
15,4
16,3

QH [kW]

Q S kW

5,0
6,6
7,9

t L2 [C]

0,83 0,68
-

7,1
12,5
17,6

2 % r.F.

(heat exchanger)

p [kPa]
3,8
6,2
8,6

1,00
0,91
0,81
0,72
0,61

0,87
0,76
0,76
0,58

0,74
0,65
0,56
0,50
0,44

0,50
0,50

0,43 0,32
0,45 0,34

32/40 30/40 27/46 26/50 24/50

Qs (sensible)

QK (total)

chilled water-

temperature [C]

12/18
14/18

p [kPa]

49,5
45,3
42,7

air inlet tL1 [C], 1 [% r. F.]

32/40 30/40 27/46 26/50 24/50


-

(heat exchanger)

Correction factors - heating *)

air inlet: tL1 [C], 1 [% r. F.]


-

89
85
82

Correction factors - cooling *)

6/12
7/13
8/12
8/14
10/15
12/16

2 [% r.F.]

0,99 0,85
-

1,00
0,95
0,89
0,83
0,77

watertemperature
[C]

10

15

20

25

air inlet: tL1 [C]

0,94
0,88
0,83
0,77
0,71

0,81
0,74
0,62
0,62
0,56

80/60
70/55
70/50
60/50
60/40
50/40

1,22
1,07
0,99
0,76
0,69

1,11
0,96
0,89
0,66
0,60

1,00
0,86
0,77
0,71
0,55
0,49

0,90
0,75
0,67
0,60
0,43
0,38

0,63 0,55
0,64 0,57

0,41
0,43

40/30

0,48

0,37

0,26

*) Note!

Water flow rates


Model
G6. S2..

4-pipe system
1 row
2 rows
min. max.
min. max.
l/h l/h
l/h l/h
217 401
303 630

Subject to modifications-05/2000

2-pipe system
3 rows
min. max.
l/h l/h
342 794

The capacities under different design


conditions determined by the above
correction factors are very approximate,
as the correction factors are arithmetic averages for all
models. The exact capacities are available from field and
office staff.

Double Unit Size 1 Two and four-pipe systems

speed

1
2
3

air flow rate


m3/s
m3/h

230 V/50 Hz
power current
W
A

600
860
1230

40
50
108

0,167
0,239
0,342

0,38
0,40
0,46

row(s)

Technical Data
heat exchanger
sound
water connections powerlevel
capacity internal
dB(A)
L
thread
1,2
3,0
4,2

1
2
3

sound pressure level


(see p. 14 for test)

dB(A)

NR

NC

29
38
47

23
33
41

21
31
39

38
47
56

R1 /2"

model

G6.D12.

2-pipe systems, 3 rows


speed

cooling capacity

QK [kW]
1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

4,5
6,1
8,1

speed

heating capacity

inlet air = 20 C

3,3
4,5
6,1

tL2 [C]

(heat exchanger)

2 [% r.F.]

10,9
11,7
12,5

p [kPa]

97
95
92

6,1
10,6
17,9

QH [kW]

tL2 [C]

QS kW

10,3
13,9
18,6

1
2
3

warm water 80/60 C

QS [kW]

(heat exchanger)

2 % r.F.

p [kPa]

71,0
68,2
65,0

2,6
4,5
7,6
G6.D14.

model

4-pipe systems, 1+2 rows


speed

cooling capacity

QK [kW]

1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

3,4
4,8
6,4

speed

heating capacity

2,7
3,9
5,2

QH [kW]

Q S kW

Water flow rates


Model
G6. D1..

0,79
0,83 0,66
0,80 0,65

0,97
0,86
0,75
0,67

0,74
0,65
0,75
0,57
0,49

0,63 0,57
0,49 0,45
0,49 0,43

0,43
0,35
0,33

4-pipe system
1 row
2 rows
min. max.
min. max.
l/h l/h
l/h l/h
288 614
394 930

2-pipe system
3 rows
min. max.
l/h l/h
438 1164

Qs (sensible)

32/40 30/40 27/46 26/50 24/50

QK (total)

temperature [C]

chilled water-

12/16
12/18
14/18

32/40 30/40 27/46 26/50 24/50


1,00
0,90
0,80
0,71

2,9
5,5
9,3

2 % r.F.

(heat exchanger)

p [kPa]
1,8
3,0
4,7

Correction factors - heating *)


air inlet tL1 [C], 1 [% r. F.]

1,21
1,11
1,00
0,90

p [kPa]

53,5
50,8
47,6

air inlet: tL1 [C], 1 [% r. F.]


1,34
1,25
1,13

(heat exchanger)

93
91
88

tL2 [C]

Correction factors - cooling *)

6/12
7/13
8/12
8/14
10/15

2 [% r.F.]

13,6
13,8
14,6

6,8
8,9
11,4

tL2 [C]

1
2

warm water 80/60 C


inlet air = 20 C

QS [kW]

1,27
1,23
1,15

1,21
1,16
1,09
1,03

0,97
0,98 0,85
0,97 0,84

1,00
0,94
0,88
0,83

watertemperature
[C]

10

15

20

25

air inlet: tL1 [C]

0,94
0,87
0,81
0,76

0,80
0,75
0,81
0,68
0,62

80/60
70/55
70/50
60/50
60/40

1,21
1,06
0,99
0,91
0,76

1,11
0,96
0,88
0,80
0,65

1,00
0,86
0,78
0,70
0,53

0,89
0,74
0,67
0,60
0,41

0,77 0,70
0,64 0,57
0,63 0,56

0,55
0,46
0,42

50/40
40/30

0,70
0,48

0,59
0,37

0,49
0,25

0,38
-

*) Note!

The capacities under different design


conditions determined by the above
correction factors are very approximate,
as the correction factors are arithmetic averages for all
models. The exact capacities are available from field and
office staff.

Subject to modifications-05/2000

Double Unit Size 2 Two and four-pipe systems

speed

230 V/50 Hz
power current
W
A

air flow rate


m3/s
m3/h

1
2
3

900
1390
1840

0,250
0,386
0,511

144
192
246

row(s)

Technical Data

1,10
1,26
1,36

heat exchanger
sound
water connections powerlevel
capacity internal
dB(A)
L
thread
1,2
3,0
4,2

1
2
3

sound pressure level


(see p. 14 for test)

dB(A)

NR

NC

39
50
58

33
44
52

31
42
50

48
59
67

R1 /2 "

model

G6.D22.

2-pipe systems, 3 rows

speed

cooling capacity

QK [kW]
6,2
8,8
10,5

1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

inlet air = 20 C

tL2 [C]

2 [% r.F.]

11,9
13,0
14,0

94
91
87

tL2 [ C]

QS kW

14,3
20,3
24,8

p [kPa]
11,1
20,7
29,2

QH [kW]

1
2
3

warm water 80/60 C

4,7
6,7
8,2

speed

heating capacity

(heat exchanger)

QS [kW]

(heat exchanger)

2 % r.F.

p [kPa]

67,4
63,5
60,2

4,7
9,0
13,1
G6.D24.

model

4-pipe systems, 1+2 rows

speed

cooling capacity

QK [kW]

1
2
3

chilled water 6/12 C


inlet air = 27 C/ 46 % r. F.

5,0
7,0
8,4

13,9
15,0
15,9

QS kW

9,3
12,4
14,7

t L2 [C] 2 [% r.F.]

t L2 [ C]

Water flow rate


Model
G6. D2..

0,84
-

0,62
0,67 0,49
0,66 0,50

4-pipe system
1 row
2 rows
min. max.
min. max.
l/h l/h
l/h l/h
400 756
548 1174

Subject to modifications-05/2000

0,97
0,87
0,76
0,67

0,74
0,65
0,56
0,50

0,57 0,44
0,43 0,30
0,45 0,33

2-pipe system
3 rows
min. max.
l/h l/h
618 1480

32/40 30/40 27/46 26/50 24/50

Qs (sensible)

QK (total)

temperature [C]

chilled water-

12/16
12/18
14/18

1,00
0,90
0,81
0,71

5,9
11,0
15,4
(heat exchanger)

2 % r.F.

p [kPa]
3,2
5,5
7,6

air inlet tL1 [C], 1 [% r. F.]

32/40 30/40 27/46 26/50 24/50


1,02
-

p [kPa]

Correction factors - heating *)

air inlet: tL1 [C], 1 [% r. F.]


-

(heat exchanger)

50,7
46,5
43,8

Correction factors - cooling *)

6/12
7/13
8/12
8/14
10/15

90
86
83

Q H [kW]

1
2

warm water 80/60 C


inlet air = 20 C

4,0
5,7
7,0

speed

heating capacity

QS [kW]

1,09
-

0,98 0,85
0,83

1,00
0,94
0,89
0,83

watertemperature
[C]

10

15

20

25

air inlet: tL1 [C]

0,93
0,87
0,81
0,76

0,80
0,74
0,67
0,62

80/60
70/55
70/50
60/50
60/40

1,21
1,06
0,99
0,76

1,11
0,96
0,88
0,65

1,00
0,85
0,78
0,71
0,54

0,89
0,75
0,67
0,60
0,42

0,76 0,70
0,62 0,55
0,63 0,56

0,55
0,42
0,42

50/40
40/30

0,70
0,48

0,59
0,37

0,49
0,26

0,38
-

*) Note!

The capacities under different design


conditions determined by the above
correction factors are very approximate,
as the correction factors are arithmetic averages for all
models. The exact capacities are available from field and
office staff.

Heat exchanger pressure drops


3 rows cooling, 2-pipe system
40
35
30

2 rows cooling, 4-pipe system


40
35
30

pressure-drop in kPa
= Model

25

pressure-drop in kPa
= Model

25

20

20

S 12, S 22

5,0
4,5
4,0
3,5
3,0

VW [l/h]

Water flow rate

3 rows heating, 2-pipe system

600
700
800
900
1000

300
350
400
450
500

25
pressure-drop in kPa
= Model

20

S 12, S 22

15

15

10
9,0
8,0
7,0
6,0

10
9,0
8,0
7,0
6,0

Pressure drop[kPa]

5,0
4,5
4,0
3,5
3,0
2,5

pressure-drop in kPa
= Model

S 14, S 24

5,0
4,5
4,0
3,5
3,0

D 14, D 24

2,5

VW [l/h]

Water flow rate

300
350
400
450
500
600
700
800
900
1000

250

200

150

600
700
800
900
1000

250

Water flow rate

300
350
400
450
500

200

150

1,0
0,9
0,8
0,7
0,6

60

1,0
0,9
0,8
0,7
0,6

70
80
90
100

1,5

40
45
50

1,5

60

2,0

D 12, D 22

70
80
90
100

2,0

40
45
50

Pressure drop[kPa]

VW [l/h]

1 row heating, 4-pipe system

25

200

150

Water flow rate

250

1,0
0,9
0,8
0,7
0,6

D 14, D 24

150

1,0
0,9
0,8
0,7
0,6

250

1,5

300
350
400
450
500
600
700
800
900
1000

1,5

200

2,0

60

2,5

2,0

70
80
90
100

2,5

60

D 12, D 22

7,0
6,0

70
80
90
100

5,0
4,5
4,0
3,5
3,0

10
9,0
8,0

40
45
50

Pressure drop[kPa]

10
9,0
8,0
7,0
6,0

20

S 14, S 24

15

40
45
50

Pressure drop [kPa]

15

VW [l/h]

Subject to modifications-05/2000

Capacity calculations
The tables on pages 4 to 7 show heating capacities for 80/60 C water temperatures and an air inlet temperature tA1 = + 20 C and cooling
capacities for 6/12 C water temperatures, an inlet air temperature of tA1 = + 27C and an inlet air humidity of 46 %. The correction factors
given can be used to determine capacities for different conditions.
These conditions and the correction factors are shown by the tables on pages 4 to 7.

cassette fan coil unit


Single unit
Size 1
4-pipe-system

new heating capacity


0,89 (see page 4)
6,2 (see page 4)

new discharge temperature

QH (70/50/+15) =
fH (70/50/+15) =
QH (80/60/+20) =

QH (70/50/+15) = fH (70/50/+15)

new heat exchanger waterside


pressure drop
see page 8, 1 RR

tL2 =

QH (70/50/+15)
VL

cpL (1,0)

5,5 kW 3600
690 m 3/h 1 1,2
VW = 860

+ 15C 24C+ 15 C 39 C

tw
= 237 l/h

p = 4,3 kPa

QK = Cooling capacity, total

QK (8/12/+24/50%) = fK (8/12/+24/50%)

new cooling capacity


0,75 (see page 4)
3,5 (see page 4)

QS (8/12/+24/50%) =
fS (8/12/+24/50%) =
QS (6/12/+27/46%) =

new cooling capacity


0,83 (see page 4)
2,8 (see page 4)

new discharge temperature/humidity


(from Mollier-diagramm)

tL2/ 14 C/87 % r. F.

new water flow rate (cooling)

V W = 860

QK

(8/12+24/50%)

QK (6/12/+27/46%)

= 0,75 3,5 kW = 2,6 kW

QS = Cooling capacity, sensible

QS (8/12/+24/50%) = fS (8/12/+24/50%)
QS

(8/12/+ 24/50%)

V W = 860

Subject to modifications-05/2000

+ tL1

QH (70/50/+15)

=
=
=

new heat exchanger waterside


pressure drop
see page 8, 2 rows

3600

VW = 860 5,5 kW
20 K

Cooling capacity (total) at PKW 8/12C


and t L1= 24C/50% r.F.
QK (8/12/+24/50%)
fK (8/12/+24/50%)
QK (6/12/+27/46%)

QH (80/60/+20)

QH (70/50/+15) = 0,89 6,2 kW = 5,5 kW

tL2 =

new water-flow-rate (heating)

Heating capacity at PWW 70/50 C


and tL1 = + 15 C

G6 . S 1 4.

fan coil unit model:

Example Calculation for a 4-pipe heating and


cooling fan coil unit requiring a heating capacity of
4.5 kW at a water temperature of 70/50 C and an
inlet air temperature of +15 C and a cooling capacity
of 2.0 kW at a water temperature of 8/12 C, an inlet
air temperature of 24 C and a relative humidity of
50 %

QS (6/12/+27/46%)

= 0,83 2,8 kW = 2,3 kW

QK (8/12/+24/50%)
tw

2,6 kW = 560 l/h


4K

p = 13,0 kPa

Motorized valves
Motorized two and four-port valves for
continuous water flow control (3-step
control), connecting cable, plastic motor
casing, red brass valve body, stainless
steel stem and globe.

M
II

III

Technical Data:
rated pressure:
16 bar
maximum ambient temperature:
50C
maximum water flow temperature: 110 C
power:
230 VAC 50/60 Hz
rating:
7 VA
protection:
IP 43
travel time: 120 sec. for 50 Hz (100 sec. for 60 Hz)
maximum glycol content of water:
50 %

union nut not included in supply

Fig. 10.1

Valve data

M
R

kvs
m3/hr

p max*)
kPa

Valve
connection

0,25
0,40
0,63
1,0
1,6
2,5
4,0

400
400
400
400 / 150**
400 / 150**
250 / 180**
250 / 180**

R 1/2"
R 1/2"
R 1/2"
R 1/2"
R 1/2"
R 3/4"
R 3/4"

*) maximum pressure difference for 2 and 4port valves to close


**) for 4-port valves

union nut not included in supply

Fig. 10.2
kvs= 0,25
kvs= 0,63
kvs=1,6
kvs= 0,4
kvs=1,0
kvs=2,5
30

kvs= 4,0

Pressure drop

p [kPa]

20

10
8
6
5

Note:
The maximum pressure drop across the
fully open valve should not exceed 25 kPa
for cooling operation and 15 kPa for heating
operation
Order-Nos.

k vs

3
2

water flow rate V (lw/h)

2000

800
1000

500
600

400

300

200

100

0,25
0,40
0,63
1,0
1,6
2,5
4,0

two-port
valve
935.421
935.422
935.423
935.424
935.425
935.426
935.427

four-port
valve
935.411
935.412
935.413
935.414
935.415
935.416
935.417

Fig. 10.3

10

Subject to modifications-05/2000

Valves with Thermoelectric Actuators


Two and four-port valves with thermoelectric actuators for ON/OFF water flow
control, connecting cable, plastic actuator
housing, red brass valve body and
stainless steel stem.
Technical Data:
rated Pressure:................................... 16 bar
maximum ambienttemperature: ....................................... 50 C
maximum water flow
temperature: ..................................... 110 C

M
II

III

R
V

power:........................... 230 V~/ 50/60 Hz


rating: ................................................... 3 VA
protection: ............................................ IP 43

union nut not included in supply

Fig. 11.1

travel time: ........................... approx. 3 min


maximum glycol content of water: 50%
Valve Data

M
R

ways

kvsm3/hr

pmax*)
kPa

Valve-**)
connection

2
2

1,6
2,5

180
180

R 1/2"
R 3/4"

1,6

50

R 1/2"

2,5

50

R 3/4"

*) maximum pressure difference for


valve to close
**) external thread, flat seal

union nut not included in supply

Fig. 11.2
k vs= 2,5

k vs= 1,6
30

pressure drop

p [kPa]

20

10
8
6
5

Note:

4
3

The maximum pressure drop across the


fully open valve should not exceed 25
kPa for cooling operation and 15 kPa for
heating operation.

1
0,8
0,6
0,5

Order Nos.
valve
connection

0,4

water flow rate V (l/h)

2000

1000

800

500

600

400

300

200

100

0,3

R 1/2 "
R 3/4 "
R 1/2 "
R 3/4"

external
external
external
external

two-port
valve

four-port
valve

935.463
935.464

935.353
935.354

Fig. 11.3

Subject to modifications-05/2000

11

Primary Air Supply

Treated Air Supply:

100

The Cassette-Geko is fitted with inlets for treated air to be


mixed with extract air inside the unit. The single units
feature treated air inlets on three corners ( no inlets on the
fourth corner because of the condensate pump inside the
appliance), while double units are equipped with treated
air inlets on all four corners.

Fig. 12.2

The pressure at the treated air inlets is slightly below


atmospheric pressure. The low pressure should be
disregarded in the design of the treated air system.

Fig. 12.2

Webs
mounting plate
110

75

55

The teated air flow is limited to 20% of the total fan coil
unit air flow at medium speed and 100m3/hr for each
treated air inlet. The height of the treated air inlets
allows the installation of light fixtures in adjacent
suspended ceiling panels. The treated air inlets are
designed for the insertion of standard 110 x 55 mm
rectangular ducts.

air duct

The air ducting is connected quickly and easily.


Follwoing the removal of the blank and the insulation
inside the appliance, the mounting plate is rolled back
and the air duct with ist V-shaped section must be
pushed into the unit (see. Fig. 12.3). The duct is then
fixed to the mounting plate.
Note:
Treated air mixed with the return air must be filtered
and at an appropriate temperature.

Fig. 12.3

12

Subject to modifications-05/2000

Air Distribution

Air Distribution:
Two air outlets are provided on the side walls of the fan
coil unit (see Figs. 12 and 17.4 for location and dimensions)
for connection to separate supply air ducting.
They can be used to supply air from the fan coil unit to
distant areas of a room or even to adjacent rooms using
owner provided ducting (e.g. DN 150 ducting). The air
discharge vanes may be open or closed while air is
supplied to other grilles.

Air flow and air pressure at each air grille are, however,
a function of the number of air outlet used.
Air flow rates as a function of pressure loss in the ownerprovided ducting are depicted in Fig. 13.1 and 13.2 for
the maximum fan speed.

Design:
90
80

T.1- 1
T.1- 2
T.2- 1
T.2- 2

70
60
pressure loss dp [Pa]

Total air flow through the


fan coil unit is not altered
by the number of air flows
through the air discharge
vanes and the external air
outlets is equal to the
design air flow given on
pages 4 to 7.

GEA Cassette-Geko

50
40

30
20
10
0
0

50

100

150

200

250

300

350

450

400

500

air flow rate (m 3/hr)

Fig. 13.1

Note:

GEA Cassette-Geko
120

All air ducting departing


from the fan coil unit
departing feature thermal
insulation to avoid
condensation.

T.1- 1
T.1- 2
T.2- 1
T.2- 2

100

pressure loss dp [Pa]

80

60

40

20

0
0

100

200

300

400

500

600

air flow rate (m /hr)

Fig. 12.2

Subject to modifications-05/2000

13

Sound Pressure and Sound Power Levels


Sound Pressure Level dB(A)

The total sound pressure level for the conference


room is thus given by:
LPges. = LP + 4.5 dB = 32 dB(A) + 4,5 dB
= 36,5 dB(A)

Increase In Sound Level (dB)


Increase in sound level

10
9
8
7
6
5
4,5
4
3
2
1

The predicted sound pressure level therefore satisfies


the minimum requirements given in Fig. 14.1.

Recommended Sound Pressure Levels


Sound-pressure average reverlevel dB(A)
beration time

Residential
(hotel room) night time
residential room day-time
Auditories
TV-studio
Concert-room
opera house
Theatre
Cinema
Lecture room
Reading room
Seminar room
School classroom
Offices
Conference room
Rest room
Office room
Small office room
Open-plan office
Church
Museum
Main hall
IT room
Laboratory
Restaurant
Kitchen
Sales room

Fig. 14.1

*)

According to Fig. 14.2, the increase in level for


three fan coil units is approx. 4.5 dB.

Type of room

The sound pressure levels given in the tables on


pages 4 to 7 and on p. 16 apply for the reverberant
field of a 100 m 3 room and a reverberation time of
0.5 sec.
The sound pressure level at the place of installation
is predicted using the sound power level
expressed in dB(A) and the conversion diagram
given in Fig. 14.4.
Example:
Three model S12 fan coil units are to be installed
in a 20 m x 10 m x 4 m conference room. Fan
operation is to be at speed 2. The resulting sound
power level (see p. 4) is 44 dB(A).
Calculation of Sound Pressure Level:
1. According to Fig. 14.4, the size of the perfectly
absorbing surface is approx. 100 m2 for residential
rooms, offices, hotel rooms and conference rooms
with a volume of 800 m 3
2. The average distance from the fan coil units is
assumed to be 3 m and the directional effect (see
Fig. 14.3) 2. For these conditions, the sound
level difference L = 12 dB, as Fig. 14.4 shows.
3. Accordingly, the A-rated fan coil unit sound
pressure level:
LP = LW - L = 44 dB(A) - 12 dB = 32 dB(A).

35/30
35

30/25
30

0,5
0,5

30
30
30
35
40
40
40
40
40

25
25
25
30
30
35
35
35
35

1,5
2,0
1,5
1,0
1,0
1,0
1,0
1,0
1,0

40
40
40

35
35
35
40
50
35
25
40
35
45
40
55
40
45
40
40 bis 55 **)
45 bis 60 **)
45 bis 60 **)

2
3
4 5 6
8 10
Number of fan coil units

Fig. 14.2

Directional Effects
2

1,0
0,5
0,5
35 0,5
45 0,5
3,0
1,5
1,5
1,5
2,0
1,0
1,5
1,0

Fig. 14.3
Directional effect factor 2
(semi-spherical emission): Unit
suspended in the center of the
ceiling
Directional effect factor 4
(quarter-sphere emission): Unit
adjacent to 2 room surfaces

= minimum requirements
= increased requirements
= depending on use

Directional effect factor 8


(eighth-sphere emission): Unit
adjacent to 3 surfaces

Conversion of sound power level into sound pressure level


0

5
re s

10
12

id e

ie s ,

sw i

c la s

mm

in g

10
poo

sro

a=

ls

om
s
om
s, o
re a
ffic
d in
es
g ro
om
s
n t ia

l ro

15

ra d

io s

tu d

=
=
=

io s

20

0,0

20

0,0

50

0,1
0,1

0,2

0,4

hos

p it a

l ro

co n

om

fe r

grlaorg
ee c
Khiurcr
hcheens
m

s, s

enc

a ll

e ro

ch u

om

s, t

stor

25

30

800 m3

mu

ee

8
4

unit adjacent to two surfaces

unit in center of surface

4 5 6

8 10

15 20

Difference from the sound source [ m ]

30 40

60 70

50
Directional effect factor

ld

35

es

hea

tre

es

ro o

ms

200
500
1000
2000
5000

f ie

unit adjacent to three surfaces

0,5

s ic

rch

100

Absorbation surface [ m2 Sabin ]

to r

fr

Sound level difference L=LW - LP [dB]

fa c

100

200

500

1000 2000

5000 10000

30000

room volume [ m3 ]

Absorption coefficient :
= 1 for a surface which absorbs all incident sound energy. The
above values represent ratios between the sound energy actually
absorbed and the sound energy absorbed by a perfectly absorbing
surface. They are averages.
Perfectly absorbing surface m2 (sabin):
Sabin expresses the size of a surface which would absorb all incident
sound energy. This size is not identical with the total room surface.

Fig. 14.4

14

Subject to modifications-05/2000

NR and NC numbers
NR and NC numbers
ISO Noise Criteria Numbers
If a wide frequency range contains high intensity peaks (as in the
case of the noise emitted by a fan), the dB(A) rating (summation
level) is not sufficient to rate the perceived noise level. For this
reason, rating curves (curves of equal nuisance) accounting for
the frequency composition of the noise are used to classify
disturbance.

90

The ISO NR (noise rating) curves depicted in Fig. 15.2 have


become the international standard for rating noise exposure.
The U.S. are the only country where the NC (noise criteria)
curves of Fig. 15.3 are still used.

60

NR 80
70
70

Sound Pressure Level dB

If an NR or NC number is specified for a room, no octave-band


sound pressure level must be in excess of the sound pressure
level given by the curve.

80

The summation level for all eight octave-bands is always 7 to 10


dB above the NR or NC number. For ventilation systems, the
sound pressure level difference averages 5 dB(A) for the different octave-bands and varies from octave-band to octave-band.

60
50
50

40

40
30
30
NR28

20

20

10

0
63

125

250

500

1000

2000

4000

8000 Hz

ISO Noise Rating Numbers


Example:
Noise emissions are to comply with NR 28 or NC 26.

Fig. 15.2

The base data for the calculation is given in the boxes in the table
on p. 16. To determine the sound pressure level in each octaveband, the sound power levels given for the size 1 single unit for
speed 2 must be tabulated as shown by Fig. 15.1.

The emitted sound pressure level peaks in the 1,000 Hz octave


band at NR 26 or NC 24.
The installation therefore complies with the NR 28 requirement
(as NR 26 is less than NR 28) and the NC 26 requirement (as NC
24 is less than NC 26).

80

70

Sound Pressure Level dB

To obtain the sound pressure levels for the different octavebands, the sound level difference of 12 dB determined in
accordance with Fig. 14.4 on p. 14 must be deducted from the
sound power levels in Fig. 15.1. The octave-band sound pressure
levels obtained are entered into Fig. 15.2 (NR) or Fig. 15.3 (NC).

Noise Criteria Numbers


90

NC 70

60
60
50
50
40
40
30

30
NC 26

20

Model p.12
Noise Emission at Speed 2

20
NR 21
10

63

125

250

45

46

47

12

12

12

33

34

35

500 1000 2000 4000 8000 (Hz)


41

38

34

25

19

[dB]

12 12

12

12

12 [dB]

22

13

0
63

29

26

Fig. 15.1

Subject to modifications-05/2000

125

250

500

1000

2000

4000

8000 Hz

Octave-Band Mean Frequency

[dB]
Fig. 15.3

15

Single

Double

sound power level (dB)

Air flow rate

Speed

Size

Type

Fan coil Unit Noise Data

sound pressure level *)

Octave-band mean frequency (Hz)

no
adjustment

adjustment

no
adjustment

dB

dB(A)

dB

dB(A)

NR

NC

adjustment to

m3/h

63

125

250

500

340

45

37

39

31

28

24

19

19

47

35

38

26

19

17

490

45

46

47

41

38

34

25

19

51

44

42

35

29

27

690

45

56

54

50

47

44

37

27

59

53

50

44

38

36

510

45

47

48

42

39

35

27

19

52

45

43

36

30

28

780

46

59

57

53

51

47

41

32

62

56

53

47

43

41

1030

51

66

64

61

58

55

51

43

70

64

61

55

49

47

600

45

40

42

33

32

29

19

19

48

38

39

29

23

21

860

45

50

50

43

41

38

29

19

54

47

45

38

33

31

1230

50

59

58

53

50

47

41

32

63

56

54

47

41

39

900

45

51

51

45

42

39

31

20

55

48

46

39

33

31

1390

53

62

60

57

53

51

45

37

66

59

57

50

44

42

1840

59

70

67

65

61

58

55

49

73

67

64

58

52

50

1000 2000 4000 8000

* The sound pressure levels apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

16

Subject to modifications-05/2000

Dimensions and Weights


Dimensions

Front view
Single unit

Side view
Single unit

Fig. 17.2

Fig. 17.1

Weights
The weights given below apply to units with empty heat
exchangers including their panels

Front view
Double unit

Type
Single

2-pipe
27 kg

4-pipe
28 kg

Double

53 kg

54 kg

Fig. 17.3

Pipe connections
on rear-side

Side view
double unit

Side View of Heat Exchanger Pipe Connections


*Note: Flow and return piping may differ depending on valving and functionality.
4-pipe system
2-pipe system

Fig. 17.4

all dimensions millimeters

all dimensions millimeters

flow, heating = 1/2"


return, heating = 1/2"
cooling:
* return: Single unit = 1/2"; double unit = 3/4"
* flow: Single unit = 1/2"; double unit = 3/4"

Fig. 17.5

Subject to modifications-05/2000

* return: Single unit = 1/2"; double unit = 3/4"


* flow: Single unit = 1/2"; double unit = 3/4"

Fig. 17.6

17

MCR 3201/3301 Control System


Room and Supply Air Temperature Control
The MCR 3301W and 3201W control units have been designed for
all control functions of the GEA Cassette-Geko. The controllers

themselves are integrated in the terminal box (see Fig. 19.1). The
controller itself is required for each GEA Cassette-Geko.

MCR 3301W and 3201W Functions


2-pipe systems:
Heating only using

hot water

Cooling only using

cold water

Heating or cooling
only using

hot or cold water

4-pipe systems:
Heating and cooling
only using

hot and cold water

MCR 3201W Control Unit (see Fig. 19.2.)

MCR 3301W Control Unit (see Fig. 19.2.)

MCR 3201W control unit for a maximum of 16 fan coil units.

MCR 3301W control unit for a maximum of 16 fan-coil units.

colour: white; other colours and different design upon request.

colour: white; other colours and different design upon request.

Functions and Control Elements (see Fig. 19.1):

Functions and Control Elements (see Fig. 19.1):

room or supply air temperature control (10 to 30 C)

Apart from the MCR 3201W control unit features,


the MCR 3301W control unit is equipped with the
following:
fan speed selector
1-2-3 = manual fan speed selection
A
= automatic fan speed selection

= OFF

3
daytime/night-time operation selector
4
return air operation selector
5 and 6
heating/cooling changeover switch, manual (M)

Apart from the MCR 3201 W control unit features, the MCR
3301 W control unit is equipped with the following:

Multifunctional display unit and push button controls,


menu controlled, modern design
Integrated clock for daytime/night-time operation
according to weekly schedule
Push button for immediate daytime/night-time operation
changeover (automatic return to normal operation at next
programmed changeover time)
Separate room temperature sensor or extract air sensor
required

or
automatic (A)
LED ON display

Terminal Box featuring MCB 3200 Controller


(see Fig. 19.1)
The controller is required for each fan coil unit. The control unit,
the valves, the fans and the condensate pump alarm signal are
tied into the controller.

Valves (see page 10 and 11)


The MCR 3201 and 3301 control systems allow the following
valve functions:
2-pipe system: Continuous (3-position) control or ON/OFF
(2-position) control
4-pipe system: Continuous (3-position) control or ON/OFF
(2-position) control
ChangeoverThermostat,OutdoorTemperatureSensorandClock
(see page . 30 and 31)
Note: Further control options feasible Typical MCR 3201/3301 Control System

18

Subject to modifications-05/2000

Typical MCR 3201/3301 Control System

Control Unit
MCR 3201 W

MCB 3200 Control Unit


and MCB.UB Module

Control Unit
MCR 3301 W

Fig. 19.1

room
temperature sensor
903.411

*
*
*

1st unit

3rd unit

2nd unit

changeover
sensor
903.431

outdoor
temperature sensor
903.451

2
2

extract air sensor 903.381


supply air sensor 903.391

4
3

connection of building control system or DDC


communication unit
MCR 3201 or MCR 3301*)

B 16 A

* MCR 3301 requires extract air sensor or


separate room temperature sensor
230 V / 3 x 1,5 mm2 mains

unit control bus 2 x 2 x 0.6 dia.


(0,6 dia. = 0.28 mm2 )
shielded, twisted pair

*
2

N PE

230 VAC LN PE 50 Hz
mains power for
controller. 16 A
maximum fusing by
owner

peripheral unit* featuring


RS 485 interface for GEA CONTROL bus
floating signal contracts
digital inputs for unit control by
higher level system
analog input for higher level setpoint input
analog output for measured temperature output
to higher level system
*provided upon request

accessory, only if needed


2

low-voltage control line 2 x 0,5 mm

Fig. 19.2

Subject to modifications-05/2000

19

MCR 3201 W / 3301 W Design Alternatives


3-point room temperature control

return air
function

2-PIPE SYSTEM
heating only

cooling only

4-PIPE SYSTEM
heating and
cooling

heating or
cooling

Control Equipment
terminal box featuring
MCB3200 controller

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 4 . 03 _

alternatively:
terminal box featuring
MCB3200 controller plus
extract air temperature
sensor

unit type
G6 . _ _ 2 . 05 _

unit type
G6 . _ _ 2 . 05 _

unit type
G6 . _ _ 2 . 05 _

unit type
G6 . _ _ 4 . 05 _

alternatively:
terminal box featuring
MCB3200 contoller plus
minimum/maximum
supply air temperature
control (MCB.UB unit)
supply air temperature
sensor

unit model
G6 . _ _ 2 . 06 _

unit model
G6 . _ _ 2 . 06 _

unit model
G6 . _ _ 2 . 06 _

unit model
G6 . _ _ 4 . 06 _

alternatively:
terminal box featuring
MCB3200 controller plus
minimum/maximum supply air temperature control (MCB.UB unit)
supply air temperature
sensor
extract air temperature
sensor

unit model
G6 . _ _ 2 . 07 _

unit model
G6 . _ _ 2 . 07 _

unit model
G6 . _ _ 2 . 07 _

unit model
G6 . _ _ 4 . 07 _

230 VAC Valving


motorized (3-position)
4-port valve

valve model
VR3 _ _ . _ _

valve model
VR3 _ _ . _ _

valve model
VR3 _ _ . _ _

valve model
VR3 _ _ _ _ . _ _

alternatively
2-port valve

valve model
VR2 _ _ . _ _

valve model
VR2 _ _ . _ _

Valves (230 V~)

valve model
VR2 _ _ _ _ . _ _

Alternative: Valves (24 V~, to be provided by owner)


24 VAC Valving (transformer to
be provided by owner)
motorized (3-position)
4--port valve

valve model
VN3 _ _ . _ _

valve model
VN3 _ _ . _ _

alternatively
2-port valve

valve model
VN2 _ _ . _ _

valve model
VN2 _ _ . _ _

valve model
VN3 _ _ . _ _

valve model
VN3 _ _ _ _ . _ _
valve model
VN2 _ _ _ _ . _ _

Control Unit (one per group or unit)


control unit including
room temperature sensor*

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

*) Note ! The MCR3301 control unit is not equipped with an integrated room temperature sensor.

Necessary Accessories (one per group or unit)


flow temperature
measurement
measurement of room
temperature if no extract
air temperature sensor is
installed (MCR3301W
control unit only)

20

changeover sensor
903.431
room temperature sensor
903.411

room temperature sensor


903.411

room temperature sensor


903.411

room temperature sensor


903.411

Subject to modifications-05/2000

MCR 3201 W / 3301 W Design Alternatives


2-point room temperature control

return air
function

2-PIPE SYSTEM
cooling only

heating only

4-PIPE SYSTEM
heating or
cooling

heating and
cooling

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 2 . 03 _

unit model
G6 . _ _ 4 . 03 _

alternatively:
terminal box featuring
MCB3200 controller plus
extract air temperature
sensor

unit model
G6 . _ _ 2 . 05 _

unit model
G6 . _ _ 2 . 05 _

unit model
G6 . _ _ 2 . 05 _

unit model
G6 . _ _ 4 . 05 _

thermoelectric actuator
(2-position)
4-port valve

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ _ _ . _ _

alternatively
2-port valve

valve model
VT2 _ _ . _ _

valve model
VT2 _ _ . _ _

terminal box featuring


MCB3200 controller

Control Equipment

230 VAC Valving

valve model
VT2 _ _ _ _ . _ _

24VAC Valving (transformer to be provided by owner)


thermoelectric actuator
(2-position)
4-port valve

valve model
VQ3 _ _ . _ _

valve model
VQ3 _ _ . _ _

alternatively
2-port valve

valve model
VQ2 _ _ . _ _

valve model
VQ2 _ _ . _ _

valve model
VQ3 _ _ . _ _

valve model
VQ3 _ _ _ _ . _ _
valve model
VQ2 _ _ _ _ . _ _

Control Unit (one per group or unit)


control unit including
room temperature sensor*

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

control unit
MCR3201W/3301W

*) Note! The MCR3301 control unit is not equipped with an integrated room temperature sensor.

Necessary Accessories (one per group or unit)


flow temperature
measurement
measurement of room
temperature if no extract
air temperature sensor is
installed (MCR3301W
control unit only)

changeover sensor
903.431
room temperature sensor
903.411

Subject to modifications-05/2000

room temperature sensor


903.411

room temperature sensor


903.411

room temperature sensor


903.411

21

MCR3102W Control System


Room Temperature Control
The MCR3102W control unit (see Fig. 23.1) is used for
the control of

The following may also be connected to the controller:

2-pipe fan coil units for heating only or cooling only


2-pipe fan coil units for heating or cooling and
4-pipe fan coil units for heating and cooling

Changeover sensor, clock or built in control system


output (optional) and outdoor temperature sensor for
temperature adjustment function

connected to cold water and/ or hot water systems

MCR3102W Control Unit (see Fig. 23.1)


MCR3102W control unit for a maximum of
10 fan coil units
colour: white

Valves(see page 10 and 11)


The MCE4 control system allows the following
valve functions:
continuous (3-position) or ON/OFF (2-position)
control of 2-pipe units
ON/OFF (2-position) control of 4-pipe units

Functions and Control Elements (see Fig. 23.1):


1 room temperature control (10 to 30C)
2 fan speed selector
1-2-3 = manual fan speed selection
"auto" = automatic fan speed selection
""
= OFF

Changeover Thermostat, Outdoor Temperature Sensor


and Clock (see page 30 and 31)

3 daytime/night-time operation selector


4 LED ON display
Further Control System Functions and
Controls (not visible):
setpoint limitation (18 to 24C)
night-time temperature reduction adjustment
between 1 and 7 K
automatic changeover between heating and cooling
a) 2-pipe unit as a function of room temperature and
flow temperature (changeover sensor 903.231
required)
b) 4-pipe system with 2 K difference between heating
and cooling
fan ON/OFF and continuous operation settings

Terminal Box featuring MCE4


Controller (see Fig. 23.1)
The controller for valve and fan control is required for
each fan coil unit.
The MCE4 controller features two floating contacts for
"ready" and "condensate pump alarm" signals.

22

Subject to modifications-05/2000

Typical MCR3102W Installation


MCR3102W
Control Unit

MCE4
Controller

Fig. 23.1

1st

2nd

unit

3rd

unit

unit

changeover
sensor
903.431

room
temperature
sensor
903.41
1

extract

air

sensor

903.381

2
4

4
signals

signals

2
2

max.

8
4

1
2

signals

outdoor
temperature
sensor
903.451

B
GEACONT

All
units
serve
the

MCR3102

connected
must
same
function.

A
L

floating
contact
from
clock
or
building
control
system
to
start
daytime
operation.

3
6

PE

10

30

1 2 15

20

25

ut

230
V
AC
L
N
PE
50
Hz
mains
power
for
controller
6
A
maximum
fusing
by
owner

230

low

low

1,5

voltage
voltage

accessory
,

mm

control
control

only

if

mains
line
line

2
4

x
x

0,5
0,5

mm
mm

needed

Fig. 23.2

Subject to modifications-05/2000

23

MCR3102W Design Alternatives


2-point room
temperature control

3-point room temperature control

return air
function

2 PIPE SYSTEM
heating only

cooling only

4-PIPE SYSTEM
heating or
cooling

heating and
cooling

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 4 . 02 _

alternatively:
terminal box as above plus
extract air temperature
sensor

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 4 . 04 _

valve model
VR3 _ _ . _ _

valve model
VR3 _ _ . _ _

valve model
VR3 _ _ . _ _

terminal box featuring MCE4


controller
floating "ready" and
"condensate pump alarn"
contacts

Control Equipment

230 VAC Valving


motorized valve for
continuous (3-position)
control
4-port valve
thermoelectric actuator (2position) for ON/OFF control
4-port valve

alternatively:
2-port valve

valve model
VT3 _ _ _ _ . _ _

valve model
VR2 _ _ . _ _

valve model
VR2 _ _ . _ _

valve model
VT2 _ _ _ _ . _ _

24 VAC Valving (transformer to be provided by owner)


motorized valve for continuous
(3-position) control
4-port valve

valve model
VN3 _ _ . _ _

valve model
VN3 _ _ . _ _

valve model
VN3 _ _ . _ _

thermoelectric actuator(2position) for ON/OFF control


4-port valve

alternatively
2-port valve

valve model
VQ3 _ _ _ _ . _ _

valve model
VN2 _ _ . _ _

valve model
VQ2 _ _ _ _. _ _

valve model
VN2 _ _ . _ _

Control Unit (one per group or unit)


control unit including room
temperature sensor

control unit
MCR3102W

control unit
MCR3102W

control unit
MCR3102W

control unit
MCR3102W

Necessary Accessories (one per group)


flow temperature
measurement

24

changeover sensor
903.431

Subject to modifications-05/2000

MCR3102W Design Alternatives


2-point room temperature control

return air
function

fan control (ON/OFF)

2-PIPE SYSTEM

2-PIPE SYSTEM
heating only

cooling only

heating or
cooling

heating only

cooling only

heating or
cooling

Control Equipment
terminal box featuring
MCE4 controller
floating "ready"
and"condensate pump
alarm" contacts

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

unit model
G6 . _ _ 2 . 02 _

alternatively:
terminal box as above plus
extract air temperature
sensor

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

unit model
G6 . _ _ 2 . 04 _

thermoelectric actuator
2-position)
4-port valve

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

alternatively
2-port valve

valve model
VT2 _ _ . _ _

valve model
VT2 _ _ . _ _

control unit
MCR3102W

control unit
MCR3102W

control unit
MCR3102W

230 VAC Valving

24 VAC Valving (transformer to be provided by owner)


thermoelectric actuator
2-position)
4-port valve

valve model
VQ3 _ _ . _ _

valve model
VQ3 _ _ . _ _

alternatively
2-port valve

valve model
VQ2 _ _ . _ _

valve model
VQ2 _ _ . _ _

valve model
VQ3 _ _ . _ _

Control Unit (one per group or unit)


control unit including
room temperature sensor

control unit
MCR3102W

control unit
MCR3102W

control unit
MCR3102W

Necessary Accessories (one per group)


measurement of flow
temperature

Subject to modifications-05/2000

changeover sensor

changeover sensor

903.431

903.431

25

Thermostat and Fan Control Systems


Room Temperature Control

The thermostat control unit 983.861 (see Fig.27.1) is used


for control of:
2-pipe fan coil units:
2-pipe fan coil units:
2-pipe fan coil units:

4-pipe fan coil units:

for heating only


for cooling only
for heating or cooling
(changeover sensor 902.035
required)
for heating and cooling
(valving required) connected
to cold water and/or hot
water systems

Terminal box for connection of equipment


(fan,valves,etc.),see Fig. 27.2.

Valving (see p.11)


ON/OFF (two position)

Switch 983.860 for Fan Control (no Thermostat)

Thermostat Control Unit 983.860 (see Fig.29.3)

If the thermostat or fan control system are used,


all fan coil units connected must be of the same
size and must serve the same function. The
maximum number of units connected is
four single units or
two double units.
Functions and Control Elements (see Fig.27.1)
1 room temperature control (5 to 30 C)
limitation of temperature range by mechanical stops
feasible
2 ON/OFF switch
3 fan operating mode selector 1-2-3=manual selection
of fan speed

26

Subject to modifications-05/2000

Typical Thermostat Control System Installation

Thermostat Control Unit 983.861

Terminal Box

1
2
3

Fig. 27.1

Fig. 27.2

1st unit

2nd unit

changeover
sensor
902.035

4 x 1,5 mm 2

7 x 1,5 mm

. . . 10 x 1,5 mm 2

3 x 1,5 mm 2

7 . . .12 x 1,5 mm2

maximum number of units connected


single units
= max. 4
double units
= max. 2

B6A
983.861

All units must be of the same size and must


serve the same functions.

N PE

230 VAC L N PE 50 Hz
mains power for control
system
6 A maximum fusing by
owner

230 V / 1,5 mm2 mains power

accessory, only required for heating/ cooling


2-pipe systems
Note: Use 3_way valves!

Abb. 27.3

Subject to modifications-05/2000

27

Thermostat Control System Design Alternatives 983.861


2-point room temperature control
valve control

return air
function

2-PIPE SYSTEM
heating only

cooling only

4-PIPE SYTEM
heating or
cooling

heating and
cooling

unit model
G6 . _ _ 2 . 01 _

unit model
G6 . _ _ 2 . 01 _

unit model
G6 . _ _ 4 . 01 _

thermoelectric actuator
(2-position)
4-port valve

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ . _ _

valve model
VT3 _ _ _ _ . _ _

alternatively:
2-port valve

valve model
VT2 _ _ . _ _

valve model
VT2 _ _ . _ _

unit model
G6 . _ _ 2 . 01 _

Control Equipment
terminal box featuring
terminal strip for fan,
valve and condensate
pump connections

230 VAC Valving

valve model
VT2 _ _ _ _ . _ _

Control Unit (one per group or unit)


control unit for wall
mounting

thermostat control unit


983.861

thermostat control unit


983.861

thermostat control unit


983.861

thermostat control unit


983.861

Necessary Accessories (one per group)


flow temperature
measurement

28

changeover sensor
902.035

Subject to modifications-05/2000

Thermostat and Valve Control System Design Alternatives


2-point room temperature control
Valve Control

return air
function

2-PIPE SYSTEM
cooling only

heating only

4-PIPE SYTEM
heating or
cooling

unit model
G6 . _ _ 2 . 01 _

thermostat control unit


983.861

thermostat control unit


983.861

unit model
G6 . _ _ 2 . 01 _

heating and
cooling

Control Equipment
terminal box featuring
terminal strip for fan
and condensate pump
connections

unit model
G6 . _ _ 2 . 01 _

Control Unit (one per group or unit)


control unit for wall
mounting

thermostat control unit


983.861

Necessary Accessories (one per group)


flow temperature
measurement

changeover sensor
902.035

Switch 983.860 for Owner-Provided Control System


Control Equipment
terminal box featuring
terminal strip for fan
and condensate pump
conections

unit model
G6 . _ _ 2 . 01 _

unit model
G6 . _ _ 2 . 01 _

unit model
G6 . _ _ 2 . 01 _

switch
983.860

switch
983.860

Control Unit (one per group or unit)


switch for wall mounting

switch
983.860

Subject to modifications-05/2000

29

Control System Components

84

22

Room temperature sensor 903.411 (see


Fig. 30.1) replace:
the room temperature sensor integrated
in the MCR control unit. The additional
sensor is required if the control unit is
located at a point not suitable for temperature control and if no extract air temperature sensor is installed.
Description:
Thermistor sensor mounted in white
plastic housing (RAL 9010). Bottom cable
is entry.
Resistance at 25 C = 1,6 k

Fig. 30.1

50
37,5

Outdoor temperature sensor 903.451


(see. 30.2) for units used for cooling to
increase room temperature as a function
of outdoor temperature.

65

Description:
Thermistor sensor mounted in impactresistant white plastic housing (RAL
3010) for wall mounting PG type cable
inlet. Protected to IP 54
Resistance at 25 C = 1,6 k

PG 11

Fig. 30.2

Rubber-sleeved temperature sensor


(see Fig. 30.3) for extract air 903.381)
or supply air (903.391) temperature measurement.

1,5 m

4,1

100

Thermistor sensor cast into stainless steel


sleeve with 1,5 m cable to be mounted by
rubber sleeve.
Protected to IP 43
Resistance at 25 C = 1,6 k

Fig. 30.3

Changeover sensor 903.431 (see Fig. 30.4)

30

30

60

for MCR 3102 and MCR 3201/MCR 3301


control system for changeover between
heating and cooling mode (necessary for
2-pipe units)
Sensor fitted to flow pipe by means of
strap. Impact resistant white plastic housing (RAL 9010)
Protected to IP 43
Resistance at 25 C = 1,6 k
(use 3-way valves only).

Fig. 30.4

30

Subject to modifications-05/2000

Control System Components

90

90

Changeover thermostat 902.035 (see Fig.


31.1) for changeover between heating and
cooling mode (for thermostat control system 983.861 only)

90

Thermostat accommodated in wallmounting housing 1 m extension fitted to


flow pipe.
switching contact: + 17 C ON
+ 27 C OFF
(use 3-way valves only).

Fig. 31.1

66

72

100

45
34

43

24

Digital clock 902.070 (see Fig. 31.2), 3


programs, daily and weekly programs,
weekly grouping, 1 switching
channel,summer and winter time setting,
special programs for vacation periods or
bank holidays (same operation mode for
a defined number of days)
230 VAC 50 to 60 Hz mains power 1
floating type change over contact 16 A/
250 V(ohmic)
66,4 x 66,4 cutout

Fig. 31.2

MCX.BE base unit, MCX.NT power


supply unit,MCX.EE extension units
(see Fig.31.3)
Interface module for connecting the MCR
3201/3301 controller to external control
system (digital and analog signals).

230V mains

power
pack
1

MCX.NT power supply unit

connect
terminals of
same
numbers

X1

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

OFF

OFF

H200

H201

H202

R201

9
78 AB

23456

CD EF

01

23 456

CDEF

01

Modes of operation:

S403 S400

S401 S402
9
78 AB

16
2

15

X603

X605

1 2

OFF

X19 X20

X2
1

A1 B1 RG RG

A2 B2 RG RG

X601

X16
AA AA AE AE AE AE
01 02 01 02 03 04

DE
01

DE DE
02 03

X602
DA DA DA DA DA DA
02 03 04 05 11 12

DE DE DA
04 05 01

+24V GND
GND GND GND GND GND GND

Serien Nr.

DE4
DE3
DE2
DE1

+24V

VCC

DA3
DA4

DE1

DE2

DE3

DE4

DA2

DA4

DA3
14

14

14

11

11

11
K2

K3

12

12

DA1
14

11
K1

12

12

DE1

DE2

DE3

DE4

D 05 - D 08

K4

DA1
DA2

GND

DE4
DE3
DE2
DE1

+24V

VCC

GND

DA3
DA4

11

DA1
DA2
DA2

DA4

DA1

DA3

14

11
K3

K4

12

14

14

14

11

11
K2

K1

12

12

DE1

DE3

12

GND

DE4
DE3
DE2
DE1
DE2

DE4

DA1
DA2

DA3
DA4

11

DA2

DA4
14
K4

12

DA1

DA3
14

14

11
K3

14

11

11
K2

+24V

15

VCC

16

K1

15

12

16

12

12

D 09 - D 12

group operation: for connection of one


group of a maximum or 16 fan coil
units to one MCX.BE module
multiplex operation: for the connection
of a maximum of 90 fan coil units to
one MCX.BE module depending on
system configuration (PLC or DDC and
RS 485 repeater required)
The MCX.BE unit must be integrated
by the owner in a control cabinet.

MCX.EE

15

MCX.EE

GND GND GND GND GND GND

+U INT +U INT +U INT +U INT +U INT GND

16

MCX.EE

16
2
16

S4

MCX.BE
base unit

15

15

X604

D 01 - D 04

MCX.EE extension units

Fig. 31.3

Subject to modifications-05/2000

31

Specification text
item
No. unit

price

total price

GEA Cassette-Geko fan coil unit


Convenience fan coil unit for installation in suspended ceiling featuring
600 x 600 mm panels (single unit)
600 x 1200 mm (double unit)
Construction:
Self-supporting galvanized steel plate structure, cellular polyethylene sound and
thermal insulation material, fire-retardant rating B2 to DIN 4102
Heat Exchanger:
Copper tubing with aluminium fans, 16 bar maximum operating pressure, vent and
drain valves
hot water heating fluid, 80 C maximum flow temperature
cold water cooling fluid, 6 C minimum flow temperature, 50% maximum glycol
content
Internal thread connections:
R " for 2 and 4-pipe single units
R " for 4-pipe double unit heating circuit (1 row)
R " for 2-pipe double unit and 4-pipe double unit cooling circuit (2 rows)
Heat exchanger alternatives:

2-pipe system (3 rows)

4-pipe system (2+1 rows)

Radial Flow Fan:


Radial flow fan, suction-type, low noise, no maintenance ball bearings, three-speed
external rotor motor, 230 VAC /50 Hz

6-pole for size 1

4-pole for size 2

Protected to IP 54, fire-retardant rating B2 to DIN 4102, insulation class 1, integrated


thermal contact for motor protection, wired to terminal strip
Condensate Trays:
Polystyrene foam main condensate tray with integrated fan air passage, fire-retardant
rating B2 to DIN 4102.
Extra condensate tray (not assembled) to collect condensation from valves.
Filter:
Synthetic filter medium, washable, filter class G1 (EN 779), easy replacement.
Condensate pump:
Integrated condensate pump
1.5 m maximum head
rated 27 W
two-stage float switch wired to terminal strip

32

Subject to modifications-05/2000

Specification text
item
No. unit

price

total price

Electrical Equipment
Base terminal box for connection of fan motors, condensate pumps and valve actuators and
GEA switch 983 ... owner control system

Optional control system:


GEA MCE4 controller

or

3-speed fan control


2-step or 3-step valve control for 2-pipe units
2-step valve control for 4-pipe units
ready and condensate pump alarm floating contacts
MCR 3102W control unit (separate accessory)

GEA MCE4 controller, as above, plus:


extract air temperature sensor
or

GEA MCB3200 controller:


RS 485 interface for connection to GEA bus

3-speed fan control


2 or 3-step valve control
condensate pump alarm output to MCR3201W control unit (separate accessory)
interface for MCX.BE communication module (separate accessory) to tie in control
system with GEA bus across digital and analog interfaces and/or to connect several fancoil unit groups to one cable
MCR3201W / MCR3301W control unit (separate accessory)
or

GEA MCB3200 controller, as above, plus:

extract air temperature sensor

or

GEA MCB3200 controller, as above, plus:


MCX.UB system for minimum supply air temperature limitation in the cooling
mode and maximum supply air temperature limitation in the heating mode
supply air temperature sensor
or

GEA MCB3200 controller, as above, plus:


MCX.UB system for minimum supply air temperature limitation in the cooling
mode and maximum supply air temperature limitation in the heating mode
supply air temperature sensor
extract air temperature sensor

Subject to modifications-05/2000

33

Specification text
item
No. unit

price

total price

Panel:
Varnished polystyrene bright white (RAL 9003) frame and intake grille and air register
for:

normal applications (minimum cold water flow temperature of 6 C, maximum inlet


air temperature and inlet air humidity of tA1 = 32 C/RH = 52 %) from translucent
polycarbonate, colour

pastel turquoise (RAL 6034)

light grey (RAL 7035)

wide temperature range applications (minimum cold water flow temperature of 6

C, maximum air inlet temperature and air intake humidity of tA1 = 32 C/RH = 52 %)
from polycarbonate, flocked with textile particles to avoid condensation, colour

pastel turquoise (RAL 6034)

light grey (RAL 7035)

Fire-retardant rating B2 to DIN 4102, other colours upon request


Technical data:
speed
air flow rate
mains power
motor rating
current input

1
/
2
/
3
........................../............................/.......................
........................../............................/.......................
........................../............................/.......................
........................../............................/.......................

cooling
inlet air temperature
relative humidity of inlet air
outlet air temperature ........................../............................/.......................
........................../............................/.......................
relative humidity of outlet
air
condensate production ........................../............................/.......................
cooling water (PKW)
........................../............................/.......................
inlet temperature
........................../............................/.......................
outlet temperature
........................../............................/.......................
flow rate
........................../............................/.......................
pressure drop across heat exchanger (WT)
/.......................
cooling capacity
........................../............................/.......................
-total
........................../............................/.......................
........................../............................/.......................
-sensible
........................../............................/.......................
heating
........................../............................/.......................
inlet air temperature
........................../............................/.......................
outlet air temperatue
........................../............................/.......................
heating water (PWW) ........................../............................/.......................
inlet temperature
........................../............................/.......................
outlet temperature
........................../............................/.......................
flow rate
........................../............................/.......................
pressure drop across heat exchanger (WT)
/.......................
........................../............................/.......................
heating capacity
........................../............................/.......................
........................../............................/.......................
noise data
........................../............................/.......................
sound power level
........................../............................/.......................
sound pressure level
........................../............................/.......................
........................../............................/.......................

m3/h
V/Hz
W
A

C
% r.F.
C
% r.F.
l/h
C
C
kg/h
kPa
kW
kW

C
C
C
C
kg/h
kPa
kW

dB(A)
dB(A)

*100 m3 room reverberant field and 0.5 sec. reverberation time

34

Subject to modifications-05/2000

Specification text
item
No. unit

price

Dimensions/weight
cutout
LxB

________________ mm

panel
LxB
height
weight
Manufacturer:
Order-No.:

total price

________________ mm
________________ mm
________________ kg
GEA Happel Klimatechnik
_________________________

GEA Valving
Valving including tubing for water flow control for:
fan coil unit type:
Single unit
heat exchanger system:
2-pipe system

Double unit
4-pipe system
heating
cooling
3-way valve

alternatively:

2-way valve

Valve actuator, alternatively:

3-position actuator (motor)


power 230 V/50 Hz
power 24 V/50 Hz
valve size DN _____ kvs ________
2-position actuator
(thermoelectric actuator)
power 230 V/50 Hz
power 24 V/50 Hz
Valve size DN _____ k vs ________
radiator valve to preset waterflow

Including, upon request:


Manufacturer:
Order-No.:

GEA Happel Klimatechnik


_________________________

Spare Filter
Spare filter, class G1 (EN 779)
1 set of 4 filters
Manufacturer:
Order No.:

Subject to modifications-05/2000

GEA Happel Klimatechnik


ZK0111

35

Specification text
item
No. unit

price

total price

Control unit
GEA MCR 3201W control unit for room or supply air temperature control with the
following features:
return air and return air/treated air functions
water and/or water plus electric heating functions
electric heating only functions
water cooling functions
3-speed fan control, manual or automatic (as required for temperature control)
night-time temperature reduction by switch or external clock
night-time temperature setting function using incorporated potentiometer
electronic setpoint range limitation
sliding heating/cooling mode changeover for 2-pipe system
automatic heating/cooling mode changeover for 4-pipe system, 2 K differential
integrated room temperature sensor
room temperature adjustment as a function of outdoor temperature
LED status display
minimum/maximum supply air temperature limitation (additional module
required)
ready for interfacing with building control system, DDC or PC (additional
module required)
colour
panel and switch:
pure white (similar RAL)
housing and mobile cover: pure white (similar RAL)
width: 140
mm
height:
80
mm
depth: 36
mm
Manufacturer:
GEA Happel Klimatechnik
Order-Nr. MCR 3201W
Dimensiones:

GEA MCR 3301W control unit


for room or supply air temperature control with the following features:
modern design featuring multifunctional display unit and push button control,
menu-driven
integrated clock for daytime/night-time operation
return air and return air/treated air functions
water and/or water plus electric heating functions
electric heating only functions
water or refrigerant cooling functions
3-speed fan control, manual or automatic (as required for temperature control)
night-time temperature reduction by push button or clock, temperature
programmable
push button for immediate changeover between daytime and night-time
operation (automatic return to normal operation at the next programmed
changeover time)
fast ventilation function (units using treated air)
(room ventilation for a maximum of 1 hour minimizing energy consumption)
electronic setpoint range limitation
sliding heating/cooling mode changeover for 2-pipe system
automatic heating/cooling mode changeover for 4-pipe system, 2 K differential
external room temperature or extract air temperature sensor required
room temperature adjustment as a function of outdoor temperature
LED status display
minimum/maximum supply air temperature limitation (additional module required)
ready for interfacing with building control system, DDC or PC (additional module
required)

36

Subject to modifications-05/2000

Specification text
item
No. unit

price

colour
panel and switch
housing and mobile cover

Dimensions

Width:
Height:
Depth:

total price

pure white
pure white

140
80
36

mm
mm
mm

Manufacturer:
Order-Nr.

GEA Happel Klimatechnik


MCR 3301W

GEA MCR3102W control unit


for room temperature control with the following features:
return air operation
water heating functions
water cooling functions
3-speed fan control, manual or automatic (as required for temperature control)
valve control, 2-step or 3-step, 2-pipe system
valve control, 2-step, 4-pipe system
night-time temperature reduction by switch or external clock
electronic setpoint range limitation
sliding heating/cooling mode changeover for 2-pipe system
automatic heating/cooling mode changeover for 4-pipe system, 2 K differential
integrated room temperature sensor
room temperature adjustment as a function of outdoor temperature
LED status display
colour: white

DimensionsWidth:
160
depth:
Heigth:
Manufacturer:
Order-Nr.

mm
80
30

mm
mm

GEA Happel Klimatechnik


MCR 3102W

Other controls
Electromechanical switch
Switch accommodated in wall-mounted housing
0-1 switch for ON/OFF
1-2-3 switch for fan speeds
Order-Nr.
983.860

GEA Thermostat-switch

as switch 983.860,
with 5 C .. 30 C
Best.-Nr.
983.861

Subject to modifications-05/2000

37

GEA
Klimatechnik GmbH
A-4673 Gaspoltshofen
GEA Happel Belgium N.V.
B-1130 Brussels
GEA Happel Ltd.
Kent TN8 6HF
GB-Edenbridge
GEA Happel France sarl
F-59223 Roncq
GEA Happel
Nederland B.V.
NL-2909 LL
Capelle a/d IJssel

GEA Klimateknik ApS


DK-2400 Kbenhavn NV
GEA-Bro West
A-6020 Innsbruck
GEA Klimatechnika Kft
H-1022 Budapest
GEA Thermtec
Schweiz AG
CH-3065 Bolligen-Station
GEA LVZ, a.s.
CZ-46120 Liberec
GEA Klimatizace spol. s r.o.
CZ-46312 Liberec
GEA-Klima-rashladna
tehnika d.o.o.
HR-10000 Zagreb
GEA Klimatizcia s.r.o.
SK-82104 Bratislava

GEA
Klimatyzacja Sp. z o.o.
PL-54610 Wroclaw
GEA Kondicioner
Moskva
Moskva

GEA PT Baltic Ltd.


LT-2009 Vilnius
GEA PT Baltic Ltd.
LT-2009 Vilnius

23 GEA Klimatehnika YU

YU-11070 Novi Beograd

GEA Klimatizacija
Ukraina
Kyjiv

24 GEA EXOS

ISISAN
TR-80700 Balmumcu
Istanbul

25 GEA

GEA
Klimatizacijska Tehnika
SL-1000 Ljubljana

26 Nnio, Lda.

Luftbehandling AB
S-30245 Halmstad
Climatizacin Espaa
E-08870 Sitges, Barcelona
P-1269-090 Lisboa

GEA PT Baltic Ltd.


LT-2009 Vilnius

27 EVISS Ltd.

GEA PT Baltic Ltd.


LT-2009 Vilnius

28 Oy Teknocalor AB

BG-7000 Rousse
FIN-01300 Vantaa

GEA Happel Ltd. Enterprise Way GB-Edenbridge Kent TN8 6HF phone: (+ 44) 0 17 32/86 07 00 fax: (+ 44) 0 17 32/86 28 28
GEA Happel Klimatechnik GmbH Sdstr. 48 D-44625 Herne phone: (+ 49) 0 23 25/4 68-00 fax: (+ 49) 0 23 25/4 68-2 22
GEA Klimatechnik GmbH Obeltshamer Strae 12 A-4673 Gaspoltshofen phone: (+43) 07735/8000-0 fax: (+43) 07735/8000-110

Nr. 313 092 (GB) 4.000 05/2000


subject to modifications

GEA-Happel
Klimatechnik GmbH
D-44625 Herne