Contents / Introduction

Contents

Contents

Introduction

Applications

Type Designation

Multi-turn Actuators

Design Principle

6-7

Functions
Open-Close Duty
Regulating Duty
Limit Switching
Torque Switching

8
8
8
9
10

Control Equipment
Micro Switches
Reduction Gear Unit
Position Indicators
Intermediate Switch
Manual Operation
Top Bevel Gear Set
Space Heater
Motors

11
11
12
12
13
13
13
13
14-15

Actuators for Regulating Duty


Actuator Types
Auma Norm Actuators
Auma Integral Starter Actuators
Control Versions
Auma Compact
Auma e-pac

16-20
21
21
21
22
22
23

Interface
Valve Attachment
Output Drives
Electrical Connection
Actuator Gearbox Combination

24
24
24
25
26

Service Conditions
Enclosure Protection
Ambient Temperature
Explosion Proof

27
27
27
28

General
Data Sheets
Technical Data Open-Close Duty
Electrical Data Open-Close Duty
Technical Data Regulating Duty
Electrical Data Regulating Duty
Dimension Sheet, Norm
Dimension Sheet, Compact
Dimension Sheet, E-pac
Output Drives
Linear Thrust Unit
Terminal Plan (Norm)
Wiring Diagram (Integral Starter)
Legend - Integral Starter

29
30-31
32-33
34
35
36
37
38
39
40
41
42
43

Introduction
In the course of ever increasing demand for
automation in all sectors of industries, electric
actuators for process control and regulation
have become more and more important. For
more than 30 years, Auma concentrates on
design, development and manufacturing of
electric actuators. During this period, Auma
has acquired a know-how in this field that can
hardly be surpassed. Auma today is one of the
leading manufacturers of electric actuators in
the world.
Auma India (Ltd.,) is now a subsidiary of
Auma Werner Riester Gmbh & Co. KG,
Germany manufacturing electric actuators
under brand name
. Auma (India) Ltd.,
started its operations in the year 1985 with HQ
and sophisticated manufacturing base at
Bangalore.
Sales support and after sales service are
provided by network consisting of regional
offices & service centers.

Applications
Auma multi-turn actuators of the type range SA
can be used wherever the automation of the
valve is required. The adoption to the
requirements of nearly every valve automation
task is possible. This is on account of :
An extermely wide torque range
Various combination possibilities with
Auma Valve Gear boxes. Thereby the torque
range can be further extended and / or the
multiturn actuator can be converted into
part turn, lever or linear actuator.
A large variety of versions, whether for open
or closed loop control, explosion proof
applications, a suitable version is available.
Energy
Power Plants
Air Pollution Control
District Heating
Pipelines

Water / Waste Water


Water Works
Water Pipelines
Sewage Treatment
Pump Stations
Locks / Dams

Chemical Industry
Petro-chemical
Chemical
Pharmaceutical

Others
Air Conditioning
Steel Mills
Ship Building
Cement Plants
Food Industry

Type Designation

Auma
Norm

OPEN-CLOSE Duty

Model : SA

Regulating Duty

Model : SAR

Auma
Compact
Actuator
Types

OPEN-CLOSE Duty Model :SA Compact


Regulating Duty

Model : SAR Compact

Auma
Integral Starter
Auma
e-pac

Regulating Duty

Model : SAR e-pac

Expl. Proof OPEN-CLOSE Duty Model :SAEx


Norm
Regulating Duty
Model : SAREx

Auma
Flame Proof /
Explosion Proof

Torque Ratings

OPEN-CLOSE Duty Model :SA e-pac

Expl. Proof OPEN-CLOSE Duty Model :SACEx


Compact Regulating Duty
Model : SARCEx
Output Drives

3 m kg
6 m kg
12 m kg
15 m kg
25 m kg
30 m kg
50 m kg
60 m kg
100 m kg

A Stem nut
B Plug Sleeve
C Dog Coupling
D Stub Shaft
E Bore with Keyway

4 rpm
5.6 rpm
8 rpm
11 rpm
16 rpm
22 rpm
32 rpm
45 rpm
63 rpm
90 rpm
125 rpm
180 rpm

Output Speed

Type Designation : Example


SA
Model
Torque Rating

12

22
Output Speed in RPM
Output Drive

Multi-turn Actuators

Multi-turn Actuator SA3 - SA100


Torque range 3 m kg to 100 m kg
Output speed 4 rpm to 180 rpm

Multi-turn Actuator
Integral Starter - Compact

Multi-turn Actuator
Integral Starter - e pac

Multi-turn Actuator
Flame Proof / Explosion Proof
5

Design Principle

Manual Operation

Motor
Change Gears

Terminal
Compartment

Reduction Gearing

Valve Attachment

Switch Compartment

Design Principle
Motor

Terminal Compartment

Especially high starting torque is frequently


required to unseat valves from end positions.
The motors developed by Auma fulfil this
basic requirement.

All electrical connections are terminated inside


the terminal compartment. Screw type terminals
are provided for easy connections. Multi-pin
plug-socket connector can be provided for ease
of connections & maintenance.

Change Gears

Valve Attachment

Auma actuators are driven by special


combination of gears which are outside the
grease filled housing & require no lubrication.
If required, output speed can be easily altered
by changing the gear pair and / or motor at
site.

The mounting flange is according to ISO 5210 /


DIN 3210. Various output drives are available for
for adaption to various types of valves.

Reduction Gearing

Manual Operation

A well proved principle of worm gearing is


used to reduce the motor speed to required
output speed of actuator. Self-locking feature
is achieved by worm gearing upto 90 output
rpm. Worm shaft and output shaft with worm
wheel run in ample sized bearings. The sliding
worm is positioned between two sets of
springs on worm shaft. The worm moves
axially in relation to thrust which is the
measure for torque. Via lever & gears the
torque is transmitted to control unit.

For commissioning or in an emergency, actuator


can be operated with hand wheel. When starting
the motor, the manual drive is automatically
disengaged.

Switch Compartment
Depending upon type of valve, the actuator
must be switched off at end positions by limit
switch or torque switch. For this purpose,
independent limit switching or torque
switching devices are provided in the switch
compartment. The switching devices are easily
accessible for any setting at site.

Functions
Open Close Duty
The characteristic feature of this actuator is
open loop. The normal valve positions in
OPEN-CLOSE Duty are end positions OPEN
and CLOSED. After receiving command, the
actuator operates the valve to one of the end
positions or if necessary to a preset
intermediate position. The valves are operated
relatively seldom, the time intervals can span
between a few minutes to several months.
Auma multi-turn actuators type SA for open
close service are rated for short time duty
S2-15min.
Typical Characteristics of
OPEN-CLOSE DUTY
Regulating / Modulating Duty
The characteristic feature of this actuator is
closed loop in which input command signal to
actuator is directly influenced by the flow
through the valve. Regulating / Modulating
duty actuator SAR operates between two set
bands between open-close positions depending
upon actual valve position and feedback signal.
The motors of these actuators are rated for
intermittent duty S4-25%. The mechanical
components and motor are designed to withstand
a large number of operations required for
modulating applications.

Typical Characteristics of
Regulating / Modulating Duty
Pemissible number of starts-stops depends upon
actuator size & speed. The details are available
in Data Sheets.

Short Time and Intermittent Duty IS 12824


Short time Duty S2

Intermittent Duty S4

Operation at constant load during a given


time, less than that required to reach thermal
equilibrium, followed by a rest and deenergized period of sufficient duration to reestablish machine temperatures within 2oC.

A sequence of identical duty cycles, each cycle


including a significant period of starting, a period
of operation at constant load and a rest and deenergized period. These periods being too short
to attain thermal equilibrium during one duty
cycle.

The duration of short time is limited to 15, 30


or 60 min.

The relative on time at S4-25% is limited to


25% of the cycle time.

Functions
Limit Switching
The limit switching enables to switch off the
actuator when reaching defined valve
position, usually end positions. The valve
travel is measured by mechanical counter gear
mechanism which when reaching the set

switching points operate the electrical limit


switches by cams. The setting accuracy is 1/10 of
a turn of actuator output shaft.
In limit switching, two train counter gear and
four train counter gear versions are available :

Two Train Counter Gear


For Two train counter gear, two limit switches,
one for each direction of travel having 1 NO
+ 1 NC or 2 NO + 2 NC contacts are provided.
The number of spindle turns can be set
between 1 and 480 or 1 and 4800.

Two Train Counter Gear


Four Train Counter Gear
If limit switching is required at two end
positions only, two train counter gear is used.
However, if two additional intermediate
switching positions are desired, Four Train
Counter Gear is required. This limit switching
has 4 counter gears and 4 micro switches. Two
counter gears are used to switch off at end
positions as in Two Train Counter Gear. The
other two are available for setting any desired
intermediate positions between end positions.
After cam actuation, the switches remain
actuated till reaching end of valve travel.
Examples of such application are :

The accuracy of setting is 1/10 of a turn of


actuator output shaft. For four train counter
gear, 4 limit switches of 1 NO + 1 NC or 2 NO
+ 2 NC contacts are provided.

To stop at intermediate position


Sequence control, that is to start
another equipment like pump or bypass
valve actuator after certain travel
of valve.
Four Train Counter Gear

Functions
Torque Switching
The torque switching enables to switch off the
actuator when pre-determined torque is
reached instead of a defined position. The
torque switching works on principle of sliding
worm.
Axial displacement of worm proportional to
thrust is transmitted to torque switches.
Torque switches operate in closing & opening
directions. The required tripping torque can be
easily set on the graduated dial. If limit switch
cut off is selected prior to torque switch, then
torque switch serves as overload protection.
For tight seating of certain valves, the actuator
must be operated to end position CLOSED
with defined force. Such operation can be
carried out by torque seating. Limit seating is
commonly used in the end position OPEN.

Running Indication
Blinker switch is provided in the actuator and
can be used as running indicator.

10

Torque Switching
When torque seating is used at end position,
limit switches can be used for signalization.
Therefore actuator controls can differentiate
whether actuator was switched off by torque
switch or by limit switch. Micro switches of
torque switching are provided with 1 NO + 1 NC
or 2 NO + 2 NC contacts for both open & close
directions.

Control Equipment
Micro Switches
With the help of micro switches, mechanical
parameters such as travel & torque are
converted into electrical signals for actuator
control. There are four switches in the basic
version :
One limit switch each for the end
positions OPEN and CLOSE
One torque switch each for the
directions OPEN and CLOSE.

Limit switches are tripped when an end position


is reached and torque switches are tripped when
the set tripping torque is exceeded.
The micro switches are sealed to enclosure
protection class IP66, as per IS 13947. The micro
switches have double break change over
potential free contacts. The circuit is interrupted
simultaneously at two points. The basic versions
of the switch contacts are of silver. For low
current ratings, micro switches with gold plated
contacts are available.

Single and Tandem Micro Switches


Limit and Torque Switches are available in
single or tandem versions.

Switching another circuit also with


different voltage & current
Safety function, to operate with single
switch
Multiplying the available contacts,
example for signalization.
For such applications, a relay is recommended
since there may be small differences in tripping
points of tandem switches.

Single Micro Switch

Limit or Torque Switches in tandem version


have additional switching contacts. These
contacts can be wired for following applications :

Tandem Micro Switch

Micro Switch Ratings


Type of Switch

Limit and
Torque

Blinker

Type of
Current

Rating in Amp at
75 V 125 V 250 V
30 V

AC, cos O = 0.8


Inductive

DC inductive

0.2

0.1

DC resistive

0.5

0.25

AC, cos O = 0.8


Inductive

Approx. Electrical
contact rating
500,000 cycles at
250 V AC, 5A
50,000 cycles at
250 V DC, 0.1A
50,000 cycles at
250 V DC, 0.25A

11

Control Equipment
Reduction Gear Unit
A reduction gear unit (RGU) in the actuator is
used for mechanical position indication,
remote position indication & for operation of
intermediate switches. The output shaft of the
actuator drives final output shaft of RGU
through a series of reduction gears and final
o
shaft turns by approximately 270 while
actuator output shaft performs full number of
turns as set on two train or four train counter
gear unit. The reduction gear ratio needed for
each particular case is fitted at works if the
ratio is known. For this purpose fixed RGU
is supplied. If the ratio needs to be altered

at site, variable ratio RGU is available which


allows simple modification at site depending
upon number of turns of output shaft for full
stroke of valve.

Reduction Gear Unit (RGU)


Position Indicators
Mechanical Position Indicator
The position of the valve is indicated
continuously by adjustable discs having
symbols for OPEN and CLOSE. The discs can
be seen through an indicator glass on switch
compartment cover. The open-close discs can
be set to coincide with limit switching. The
mechanical position indicator requires
reduction gear unit for operation.
Remote Position Indicator
The position of the valve can be transmitted as
a continuous signal for remote indication. A
potentiometer mounted on RGU is used for
this purpose. A power supply unit provides
necessary voltage to the potentiometer. The
o
potentiometer rotates through 270 for one full
stroke of valve & output signal from
potentiometer is proportional to valve travel.
Thus the actual position of the valve can be

Mechanical Position Indicator


read off continuously on position meter
calibrated & mounted on control panel.
Technical Data
Std: 220 ohms, 3W, Linearity + 3%
Optional : 100, 560, 1000 ohms,
Potentiometer 3W, Linearity + 3%
Precision : 200, 500, 1000 ohms,
1W, Linearity + 0.5%
Power
PS01, input 220V, 50Hz, output
Supply Unit 24V DC
Position
0 - 100% in various sizes
Meter
Digital Remote Position Indicator
Actual position display can be provided by
digital remote position indicator, which
displays open position in percentage.

Remote Position Indicator


12

Control Equipment
Intermediate Switches
With this limit switching, additional switching
points can be set for each direction of rotation.
The switching can be set between 25 and 75%
of valve travel in each direction. The switch
sub assembly consisting of 2 or 4 cam switches
is mounted on output shaft of RGU. Each
micro switch has 1 NO + 1 NC contact.
Intermediate Switches
Manual Operation
For commissioning or in an emergency when
there is no power supply, actuator can be
operated by hand wheel. The manual drive is
engaged by means of a lever. When motor
starts running, the manual drive gets
disengaged immediately & hand wheel does
not rotate during power operation.
In manual operation, hammer blow can be
effected with hand wheel. The hammer blow
makes it possible to open a jammed or rarely
operated valve.

Top Bevel Gear Set


Manual effort on hand wheel can be further
reduced by using a side mounted hand wheel
instead of standard hand wheel. Reduction
ratios available are
SA3 / 6 / 12 / 15
2:1
SA25 / 30 / 50 / 60
3:1
SA 100
4:1
Instead of hand wheel, a chain pulley can be
provided for actuators mounted in inaccessible
zones.
Top Bevel Gear Set
Space Heater
Condensation in the actuator is possible due to
wide fluctuation of the ambient temperature.
The heater integrated in the control unit
prevents the water condensation. The heater is
rated for continuous duty. This may be
continuously energized or when the actuator
is not operating.

Technical Data
Volts, AC
Resistance
ohms
Rating
Watts

230

230

110

110

5K

2.7K

1.2K

0.6K

10

20

10

20

13

Control Equipment
Motors
As a standard, Auma multi turn actuators are
equipped with 3 phase induction motors.
Auma motors are class F insulated and
withstand winding temperature upto 140o C.

Single Phase AC Motors


Auma actuators can be supplied with single
phase AC motor. The required capacitor is fitted
in the terminal compartment cover.

The motors are used for short time duty (S2-15


min or S4-25% as per IS 12824) and provide
approximately three times rated torque for
short duration. The size of the motor is smaller
compared to continuous duty motor S1 of
same output power. This results in reduced
inertia of the rotor and therefore less
overshoot after switching off of motor. Auma
motors are designed for enclosure protection
class IP 68 when mounted on the actuator. All
motor cables are brought to terminal
compartment cover from inside of the actuator
thus avoiding terminal box.

DC Motors
Auma actuators are also available with DC
motors. These motors operate on 24 V, 110 V or
220 V DC supply.
AC Motors with Other Voltages and
Frequency
Three phase induction motors are available in
wide range of operating voltages from 220 V to
560 V and operating frequency of 50 or 60 Hz.

Technical Data

Voltages

Permissible Variation
in Voltage

3 ph AC Motor

1 ph AC Motor

50/60 Hz : 220 V, 380 V


400 V, 415 V
440 V, 460 V
480 V, 500 V
550 V

50/60 Hz :
220 V - 240 V
110 V - 220 V

+ 10%

+ 10%

Mounting

C Type Flange, B14, IS 2223

Enclosure Protection

IP 67 or IP 68 after mounting

Type of Cooling

Surface Cooled

Insulation Class

F Class, IS 325 (max. temp. rise 140 C)

Starting

Direct on line

Type of Duty

S2-15 min. or S4-25 % IS 12824

Direction of Rotation

Clockwise and anticlockwise

Motor Protection

3 thermo switches

14

DC Motor
220 V
110 V
48 V
24 V
+ 10%

2 thermo switches

4 thermo switches

Control Equipment
Motor Protection
Motor winding may get overheated if the
actuator is run beyond rated duty or if the
rotor is stalled for considerably longer time or
if too high ambient temperature is
encountered. In order to protect the motor
against over heating, thermo switches are
embedded in the windings of three phase,
single phase AC motors and DC motors. When
integrated into the control circuits, they will
protect the motor against damage due to
excessive winding temperature.

Technical Data
AC Voltage

Switch Rating

250 V AC
Cos O = 1
250 V AC
Cos O = 0.6

2.5 A
1.6 A

Tripping Temp 140o C


Reset Temp 90 - 110o C

The thermo switches interrupt the control


circuit as soon as winding temperature of
o
140 C is exceeded. After cooling down to a
o
temperature of approx. 110 C, the actuator can
be switched on once again. PTC thermistors
can also be provided for motor protection.

Note : The motor protection device must be


integrated into the controls, otherwise warranty
for motor is not valid.

Output Speeds
With large range of available output speeds,
almost every required operating time can be
achieved with Auma actuators.
The actuator output speed is determined by
the motor speed, change gears and reduction
gear ratio of worm / worm wheel.
The output speeds are available from 4 - 180
rpm in geometric progression of 1: 1.4.
During trial run, if found necessary, the
output speed can be easily changed by

exchanging the change wheels and or motor at


site. The grease filled housing need not be
opened for this purpose. The torque switch
setting & limit switch setting remains the same.
For actuators with output drive A (Stem nut),
max. permissible stem velocity must be
observed:
- for gate valves max. 500 mm/min
- for globe valves max. 250 mm/min
For higher velocities it is recommended to use
spring loaded stem nut type AF (special design).

Self Locking
Auma multi turn actuators SA/SAR3 to
SA/SAR100 are self locking (see note below)
with exception of output speeds 125 & 180
rpm. Actuators with 125 & 180 rpm are having
double start worm drive. After torque switch is
tripped, the sliding worm may move back to
initial position by the action of torque
measuring springs. This allows torque switch
to be released. If control system provides
continuous signal, this results in hunting of
motor. This can be avoided by the use of
auxiliary relay.

Note on Self Locking :


Self-locking gearing does not ensure safe
stopping after an operation. If this is required,
separate locking arrangement must be provided.

15

Actuators for Regulating Duty


Description of Regulating Duty
Auma actuators of type SAR are suitable for
Regulating duty / Modulating duty. SAR
actuator operates between two set bands in
closed loop and the motor is started, stopped
& reversed at short intervals to correct the
deviation from the set value. SAR actuators
differ from SA actuators in several respects :
- 4 pole motors are used to reduce overshoot
- Worm with high quality finish on flanks for
better efficiency
- Disc springs on worm shaft are pre
compressed to reduce dead band when
reversing.
While selecting Auma actuators for regulating
duty applications, following points should be
noted :

Max. No. of starts


1200 cycles / hour with motor power upto
0.55 kW & 600 cycles / hour with motor
power above 0.55 kW.
Output speed of actuator max. 45 rpm.
Torque for regulating duty should not exceed
50% of max. torque of actuator.
Max. torque of actuator can be used for
seating & unseating of the valve.
For reversing service, duration of impulse
should be minimum of 50 ms.
Electronic position transducer or precision
potentiometer should be used for remote
position indication.
The motor should be short time duty
class S4 - 25%.
The SAR actuator basically consists of
control units as explained in following
diagram.

Principle of Operation

SAR

Regulating duty actuator

CU01

: Electronic positioner

MSAR

Sensor for actuator, i.e.


position transmitter at actuator
(potentiometer or inductive
LVDT)

: Regulating valve

: Sensor for regulating valve

MU

: Signal converter for sensor

Signal converter for SAR i.e.


Electronic position transducer
(RWG 1001/RWG 2002) or
inductive position transmitter
(IWG 1002/ IWG 1003).

SE

: Setting nominal value

: Reference input

XR

: Input value at controller

YR

: Output value at electronic


positioner

MUSAR :

16

Actuators for Regulating Duty


Description of Electronic Units
Sensor for Actuator

Technical Data

A potentiometer is used as sensor for actuator.


Single turn wire wound potentiometer with
4.7 k ohms with linearity of + 0.5 % is available
for this purpose. It is available in single or
tandem version.

Resistance

4.7 k ohms + 0.5 %

Power rating

3 Watt at 40 C

Angle of rotation

275o + 5o

Linearity

+ 0.5%

Electronic position transducer RWG 1001


This device is a signal converter for the
transformation of resistance value into
proportionate current signal. It can also be
placed in the actuator where the position
determined by the potentiometer is converted
into 4-20 mA current signal.
As position transmitter, preferably a
potentiometer of 4.7 k ohm should be used so
that the reference voltage source is not over
loaded. This device requires 24V DC power
supply regulated within + 15%. Auma power
supply unit PS01 is recommended for this
purpose. RWG 1001 is a 3 wire system and is
having linearity of 0.05 %.
Electronic position transducer RWG 2002
This is basically same as RWG 1001, however
with 2 wire system. The linearity is less than 1%.

RWG 2002

RWG 1001
Technical Data - RWG 1001
Configuration
3 Wire
24V DC
Supply Voltage
min. 18, max. 33V
0-20 mA
Output Current
(4-20 mA)
Input resistance
150 k ohms
Displacement of zero
+ 25%
position, max.
Displacement of end
from 50 to 100%
position, max.
Influence of supply
Max. 0.2%
voltage variation
Temp. drift
0.2% 10o C
Linearity not considering
0.05%
potentiometer
Technical Data - RWG 2002
Configuration
2 Wire
24V DC
Supply Voltage
min. 18, max. 33V
Output Current
4-20 mA
Input resistance
150 k ohms
Displacement of zero
+ 25%
position, max.
Displacement of end
from 60 to 100%
position, max.
Influence of supply
Max. 0.15%
voltage variation
Linearity not considering
< 1%
potentiometer
17

Actuators for Regulating Duty


Description of Electronic Units
Dual Output Position Transmitter RWG 2002 DG :
It is a signal converter device for the
transformation of resistance value into
proportionate galvanically isolated two current
outputs. This device requires 24 V DC power
supply regulated within + 10%. Auma power
supply unit PS01 is recommended for
this purpose.

Technical Data - RWG 2002 DG


24V DC
Supply Voltage
+ 10% regulated
Output 1 (Isolated)
0/4-20 mA
Output 2 (Isolated)
0/4-20 mA
Current Drawn
100 mA
Adjustability of Span
+ 50%
Adjustability of Zero
+ 25%
Change in Output due to
< 0.2%
Input Supply Variation
Operating Temperature
o
o
- 20 C to + 80 C
Range
Linearity Error for both
< 1%
Outputs

Inductive Position Transmitter IWG 1002


When using Auma actuators for regulating duty
with demand of high accuracy, an inductive
position transmitter can be fitted to give precise
read out of position.
The output signal is used as feed back to
electronic positioner or for position indicator.
The system consists of two parts, a linear
variable differential transformer (LVDT) and
an electronic unit. The smallest change of
magnetic core in the measuring coil is
transformed into proportional signal. The
transmitter has no moving contacts. This device
requires 24 V DC power supply regulated
within + 15%. Auma power supply
unit PS01 is recommended for this purpose.
The linearity of the unit is less than 0.3%.

IWG 1002
Technical Data - IWG 1002
Configuration
2 Wire
24V DC
Supply Voltage
+ 15% regulated
Output Current
4-20 mA
Resistance max.
600 ohms
Displacement of zero
position, max.

+ 25%

Displacement of end
position, max.

60 to 100%

Temp. drift
Linearity (not
considering LVDT)
18

0.4% / 10o C
< 0.3%

Actuators for Regulating Duty


Description of Electronic Units
Inductive position transmitter IWG 1003
IWG 1003 is similar to IWG 1002 however with
3 wire system.

Technical Data - IWG 1003


Configuration
3 Wire
24V DC
Supply Voltage
+ 15% regulated
Output Current
0 / 4-20 mA
Resistance max.

IWG 1003

Displacement of zero
position, max.
Displacement of end
position, max.
Temp. drift
Linearity (not
considering LVDT)

600 ohms
+ 25%
60 to 100%
o

0.4% / 10 C
< 0.3%

Electronic Positioner CU01


The electronic positioner CU01 is designed as a
three level positioner for regulating of actuator.
By comparing two input signals (reference
signal W & regulating signal X), the positioner
determines the difference. In case this exceeds a
certain value, the actuator is switched on by
relays. The direction of rotation (opening or

closing) depends upon the plus or minus sign of


the deviation. Thus the regulating signal
generated by potentiometer or LVDT changes &
when the regulating signal & reference signal
become equal, the actuator stops as long as no
new correction is required.

Technical Data
Input WE1
XE2
Time delay
Adjustment of zero
point
Adjustment of end
position
Sensitivity (dead
band)
Relay output (max.
resistive load

0-20 mA (4-20 mA)


0-20 mA (4-20 mA)
or 0-Uref
0.5-15 secs.
0 - 20%
60 to 100%
1% - 2.5%
230V, 10A

CU 01

19

Actuators for Regulating Duty


Description of Electronic Units
Signal Isolator
Auma signal isolators are available in various
versions :
Power supply conditions :
230V AC, 110V AC or 24V DC
Various input signals :
4-20 mA or 1-5 V

Various output signals :


4-20 mA single or dual or 4-20 mA & 1-5V
Isolation is provided between input and output
and between two outputs.
Technical Data
Power Supply
Input
Output
Accuracy
Zero & span
adjustment

230V AC + 15%
110V AC + 15%
24V DC + 1V
4-20 mA
1-5V
4-20 mA single
4-20 mA dual
4-20 mA & 1-5 V
+ 0.1% of output span
+ 2% min. at zero
+ 10% min. at span

Signal Isolator

Power supply unit PS01


This unit gives 24V DC power supply for
regulating system (example : for CU01) & for
remote position indication (example : by a
voltmeter suitably calibrated). There are two
versions available:
Version I : For regulating application with
CU01 :
The output voltage Uo & Uc require no trimming
potentiometer. The voltage Uc is diverted from
voltage Uo, thus Uc can serve as common
reference potential for whole regulating system.
This version is suitable for IWG 1003 or
RWG 1001.
Supply voltage to PS01 is 220V or 110V +
15%, 50 Hz
The maximum output voltage is
Uo = 24V + 1 V DC
Uc = 5.5V + 0.5V DC

Version I
20

Version II : For remote position indication with


potentiometer 220 ohms as position transmitter :
In this two additional potentiometers P1 and P2
are provided for positions zero and maximum.

Version II
Technical Data - PS01
Supply voltage and
frequency

220V or 115V (+ 15%)


50 Hz or 60 Hz

Power drawn

9 VA

Output voltage
max.

24V +1V DC

Mounting

Snap on type for DIN


rail 46277

Actuator Types
Auma Norm Actuators
This actuator offers a complete actuator type SA
with electric motor, torque switch for open close direction, limit switches for both end
positions & blinker switch for running
indication. The required reversing contactor
should be installed separately & wired to the
motor. For signalization of the switching and to
trip the contactors over micro switches, control
wires are required from actuator terminal
compartment cover to reversing contactor
installed separately.
Auma Norm
Auma Integral Starter Actuators
The purpose of offering Integral motor controls
for the actuator is to enable the customer to save
high installation costs for external controls.
Actuators with integral controls include control
& switching elements and are supplied
ready for use.
All electrical components such as limit, torque,
thermo switches, all monitoring elements &
position transmitter are integrated into modern
controls.This results in following simplification.
- No extensive wiring in the external control
cabinet

- Several actuators can be connected to common


supply cable using isolating switch for each
actuator.
- Actuator signals are processed in the controls,
only feed back to process control system is
necessary.
- Integral starter housing can be easily
exchanged due to multi pin plug connector
between actuator & integral starter unit.
- Actuator can be operated from Local or
Remote position by means of selector switch
on the integral starter unit.

Auma Integral Starter

21

Actuator Types
Control Versions of Integral Starter Units
Auma Compact
This is a simpler version of Integral Starter Unit
with selector switch & push buttons. The
selector switch has 3 positions :
LOCAL :
The actuator can be operated locally i.e. at the
actuator by push buttons OPEN-OFF-CLOSE.
The running direction is indicated by LEDs.
REMOTE :
The actuator can be operated from remote
control station. The running direction is
indicated by LEDs on the actuator.
OFF :
The actuator cannot be operated with local
controls or from remote.

Auma compact is available as Norm or


Regulating duty actuator. Depending upon Norm
or Regulating duty, following features /
optionals are available :
Reversing contactors
Selector switch
Push buttons & indicating lamps
Thermal overload relay
Power supply unit PS01 for 24 V DC output
Electronic positioner CU01
Electronic position transducer RWG / IWG
Phase discriminator
Signal isolator
DC relay for remote operation
Remote annunciation relay for supply
indication
Multi pin connector can be provided between
actuator and compact and between compact &
terminals for customer connections.

The selector switch can be locked in any position


with pad lock. The compact unit is completely
wired with reversing contactors and no
additional control box is required.

Auma Compact

22

Actuator Types
Control Versions of Integral Starter Units
Auma e-pac
The electronic version of Auma India Integral
Starter e-pac incorporates sophisticated
electronic controls with field programming
feature. E-pac is modular in construction and
consists of Power Supply Module, Relay
Module & Programmable Control Module.

Programmable Control Logic Module consists


of
Inching & Non-inching in local mode by dip
switches
Inching & Non-inching in remote mode by dip
switches
Limit switch seating or Torque seating by dip
switches

Power Supply Module consists of


24 V DC, 150 mA source
Reversing contactors electrically and
mechanically interlocked
Selector switch LOCAL-OFF-REMOTE,
lockable & potential free contacts for localoff & remote
Push buttons OPEN-STOP-CLOSE for
local controls
Single phase supply for space heater 10W

Wide varieties of versions of e-pac & optional


features make the actuator controls adaptable to
any field situation. Versions & optionals
available are :
Emergency shut down (ESD)
2 wire make-break
Timer board to run the actuator in ON-OFF
steps
Open-Close inhibit
Negative switching
Remote control & local stop
Electronic positioner for regulating duty, with
or without isolator
Single phase protection
Automatic phase correction
Remote annunciation relays
Thermal overload relay
Positioner with PID features
Wall mountable e-pac

Relay Module consists of


Monitor relay for collective fault
signals (Thermo switch trip, torque switch
trip in mid travel) with potential free contacts
Local status annunciation (Green) & fault
annunciation (Red) by LEDs

For detailed literature, refer separate catalogue.

Auma e-pac
23

Interface
Valve Attachment
Valve attachment is according to ISO 5210 or DIN 3210

Flange Sizes
Actuator size
SA/SAR
Max. Torque
Nm

12

15

25

30

50

30

60

120

150 250

300

500 600 1000

ISO 5210

F10

F10 F10

F10 F14

F14

F14 F14 F16

DIN 3210

G0

G0

G0

G 12

G 12

G 12

G0

60

G 12

100

G3

Output Drives
Various output drive types according to ISO
5210 / DIN 3210 are available in order to
adapt the actuators to different types of valves.
Special sizes can be supplied on request.

Output Drive Type D


Stub Shaft :

Output Drive Type A

The shaft with key engages with bore and


keyway of mating part.

Stem nut :

Output Drive Type E

The output drive has stem nut for rising or non


rotating valve stem. The mounting flange
together with stem nut and thrust bearings form
one assembly which is suitable for accepting
thrust loads.

Bore with Keyway :

Output Drive Type B

Linear Thrust Unit (LTU)

Plug Sleeve :

With the linear thrust unit, the rotary movement


of the actuator output shaft is converted into an
axial movement. Thus the multiturn actuator
becomes linear actuator. Different stroke lengths
can be provided.

Plug sleeve has bore and keyway and is designed


for transmission of torque.

This type is mainly used for connecting to a gear


box, example Auma Gear Box type GS
(worm / worm wheel) or GK (Bevel gear box).

Output Drive Type C


Dog Coupling :
This is similar to type B, however with dog
coupling for torque transmission.

24

Technical Data
Linear Thrust
Unit

Tr.
Thread

LTU 6
LTU 12
LTU 25
LTU 50

24 x 5
32 x 6
40 x 7
50 x 8

Max.
thrust
kN
20
35
63
100

Stroke
length
mm
50 & 100
60 & 120
80 & 160
80 & 160

Interface
Electrical Connection
Terminals
Version I :

Screw type terminals are used for electrical


connection as standard. Stud type terminals can
be provided for power connections. Terminals
are DIN rail mountable and are available as
single or double decker versions also.

32 x 2 = 64 pins for control


3 + 1 = 4 pins for power
Version II :

Plug socket connector


50 pin circular connector for control
6 + 1 = 7 pins for power

The actuators can also be equipped with plug


socket connectors in two versions.
Electrical Connection for Integral Starter Versions
Between actuator and compact or e-pac :
64 pin connector with 3+1 pins for power
connection or 50 pin circular connector with
6+1 pins for power connection. This simplifies
trouble shooting at site.
From compact or e-pac to customer connections:
Screw type terminals or 64 pin connector with
3+1 pins for power connection or 50 pin circular
connector with 6+1 pins for power connection.
Technical Data

Screw type terminals


Power

Screw type terminals


Terminals max.
Voltage max.
Current max.

3
750 V
34 A

Type of Connection

Scr or stud

4 sq mm
Cross section max.
Plug socket connector 32 x 2 & 3 + 1

Current max.
Type of connections
for customer use
Cross sec. max.

Controls

1
64
500 V
25 A
Scr or
Scr
stud
4 sq mm 2.5 sq mm

64

750 V
25 A

500 V
16 A

Screws

Screws

Screws

6 sq mm

6 sq mm 2.5 sq mm

No. of contacts
Voltage max.

Earth

Multi-pin Connector

Plug socket connector, circular


No. of contacts
Voltage max.
Current max.
Type of connections
for customer use
Cross sec. max.

6
(3 used)

50

750 V
25 A

250 V
16 A

Screws

Screws

Screws

6 sq mm

Circular Connector

6 sq mm 2.5 sq mm
25

Interface
Threads for Cable Glands
As standard, Auma actuators are supplied with
2 cable glands with British Conduit threads
''
111/
4 BSC. The cable glands are directly tightened
on the threads provided in cable entry cover. At
the time of despatch, the cable entry opening in
the cable gland is sealed with aluminium shim
& neoprene rubber sheet to prevent ingress of
dust & water.

3 '' , 1'' can be


Additional cable glands of sizes 3/4''
4
provided. For additional protection under
extreme conditions for weather proof & water
proof applications, double compression cable
glands in various sizes can be supplied. NTP &
PG threads can also be provided.

Stem Protection Tube


To protect rising valve stem, a protection tube
can be fitted to the hand wheel hub. Internal
threads are provided in the hand wheel hub

as a standard. If protection tube is not required,


the bore of the hand wheel hub is closed with lid.

Actuator - Gear box Combinations


Combination with Worm Gear boxes
In combination with worm gear box of type
GS40.2 to GS500, a multiturn actuator is
converted into part turn actuator usually for 90o
movement. This is an ideal solution for large part
turn valves with high torque requirements. The
torque range goes upto 250000 Nm.
Combination with Bevel Gear boxes
By combining multiturn actuators with Bevel
gear boxes GK10.1 to GK35.1, the torque speed
ranges are considerably extended. Output
torques upto 8000 Nm and thrust load upto
820 KN are possible.

Combination with Lever Gear boxes


Louvers, dampers or valves which are operated
via lever arrangement require lever gear boxes.
For such application multiturn actuator is
combined with lever operated Gear box type
GF40 to GF315. The torque range goes
upto 63000 Nm.

26

GEAR OPERATORS

Service Conditions
Enclosure Protection
Auma actuators conform to enclosure protection
IP67 as per IS 13947 (Part I) : 1993, Appendix C.
Auma actuators are also available with improved
enclosure protection IP68. The definition of
IP67 & IP68 as per standard is as follows :
IP : Ingress Protection
First numeral 6 : Dust tight, prevents ingress
of dust.
Second numeral 7 : Protected against the effects
of immersion. Test is made by completely
immersing the equipment in water so that :
Surface of water is atleast 150 mm above
highest point of equipment.
Ambient Temperature
Type
SA
SAR
SAEx
SAREx
SACEx
SARCEx

Under above conditions, ingress of water in


harmful quantity shall not be possible.
Second numeral 8 : Test conditions as above,
however no ingress of water is permitted.

Life Time
Temp.
Range

Actuator Type
Standard
Multi-turn actuator
Multi-turn
Actuator for
Regulating Duty
Explosion Proof
actuators, standard
compact &
regulating duty

The lowest point of equipment is atleast 1 m


below the surface of water
Duration of test is 30 min.

Auma multi-turn actuators meet the following


requirements of operating cycles at 30 turns per
stroke of close - open - close.

SA3 to SA100
15000 Cycles
SAR6 to SAR100 15000 Cycles

-20 to +80 C
-20 to +60 C

-20 to +40 C

Painting
Type of paint
Standard colour
Primer thickness
Paint thickness

Epoxy
DA grey IS 5
40 microns min.
75 microns min.

Any other type & colour of paint can be provided


on request.

27

Service Conditions
Explosion Proof / Flame Proof Actuators
For installation of actuators in potentially
hazardous or explosive areas, special protective
measures are required. These are specified in
Indian Standard IS 2148-1981 ''Specifications
for Flame Proof Enclosures of Electrical
Apparatus''. Auma India actuators developed for
this purpose are suitable for group II gases and in
application other than coal mines. The
enclosures of explosion proof / flame proof
actuators are designed in consideration of
clauses specified in IS 2148-1981 & the
actuators have been tested and certified by
CMRI, Dhanbad.

Necessary approvals from statutory authorities


have been obtained.
Actuator Models
Actual Type

Model

Explosion Proof
Norm
Open-Close Duty

SAEx3/6/12/15
SAEx25/30/50/60
SAEx100

Explosion Proof
Norm
Regulating Duty

SAREx6/12/15
SAREx25/30/50/60
SAREx100

Explosion Proof
Compact
Open-Close Duty

SACEx3/6/12/15
SACEx25/30/50/60
SACEx100

Explosion Proof
Compact
Regulating Duty

SARCEx6/12/15
SARCEx25/30/50/60
SARCEx100

For details please refer separate catalogue.

EN ISO 9001
Certificate : 041005262

28

SAEx3
SAREx6

SAEx100
- SAREx100

SACEx3
SARCEx6

- SACEx100
- SARCEx100

General
Mounting Position

Functional Tests

Auma actuators also with integral controls can


be operated without restriction in any mounting
position.

After assembly, all actuators are thoroughly


tested and torque switches are calibrated. Final
inspection record is provided to the customer.

Test Certificates
Auma actuators and critical components of
actuators have been tested & guaranteed for
performance. Some of the Type test certificates
available are listed.
Endurance Test as per GDCD Standard
Damp Heat Cycle Test as per IS 9000
Vibration Test as per IS 12075
Noise Test as per IS 12065
Enclosure Protection Test as per IS 13947
Tests on Micro Switches
Motor Performance Tests

29

Technical Data

SA3-SA100

Open-Close duty
1)

Type
Min.Nm Max.Nm

20

30

20

60

55

30

120

110

50

150

60

250

Valve
Stem dia.
Mounting Output drive
Flange
Type-A
Output Speed Standard
DIN:3210
(Special
2)
ISO:5210) Max.
1/min
mm

Auma India
Actuator Type

Tripping Torque
both directions

SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA

3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
12
12
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
15
15
15
15
25
25
25
25
25
25
25
25
25
25
25
25

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

11
16
22
32
45
63
90
1253)
1803)
4
5.6
8
11
16
22
32
45
63
90
125
1803)
4 3)
5.6
8
11
16
22
32
45
63
90
125
180
4 3)
5.6 3)
8
11
16
22
32
45
63
4
5.6
8
11
16
22
32
45
63
90
125
180

Permissible
Thrust for
Type-A

Max.

kN

Revolutions
for
Full stroke

Hand
wheel
Dia.
Std.

Hand wheel
Ratio
Std.

With bevel
gear set

Min. / Max.

Weight
Auma India Norm
Std.

With bevel
gear set

Kgs.

Kgs.

G0
(F10)

26

25

1-480
or
1-4800

250

1:1

2:1

39

45

G0
(F10)

26

40

1-480
or
1-4800

250

1:1

2:1

39

45

G0
(F10)

38

60

1-480
or
1-4800

250

1:1

2:1

39

45

G0
(F10)

38

60

1-480
or
1-4800

250

1:1

2:1

39

45

G 12
(F14)

52

120

1-480
or
1-4800

360

1:1

3:1

72

88

3)

220
1) Infinitely adjustable
2) At 50 Hz

3)

3) Non self locking

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

30

Technical Data

SA3-SA100

Open-Close duty
1)

Valve
Stem dia.
Mounting Output drive
Flange
Type-A
Output Speed Standard
DIN:3210
(Special
2)
ISO:5210)
1/min

Auma India
Actuator Type

Tripping Torque
both directions

Type
Min.
Nm.

100

Max.
Nm.

300

264

100

500

450

100

600

540

200

1000

SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA

30
30
30
30
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
50
50
50
50
60
60
60
60
60
60
60
60
60
60
60
60
100
100
100
100
100
100
100
100
100
100
100
100

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

4
5.6
8
11
16
22
32
45
63
90
125 3)
180
3)
4
5.6
8
11
16
22
32
45
63
90
125
1803)
4 3)
5.6
8
11
16
22
32
45
63
90
125
180
4 3)
5.6 3)
8
11
16
22
32
45
63
90
125
180

Permissible
Thrust for
Type-A
Max.
kN

Revolutions
for
Full stroke

Hand
wheel
Dia.
Std.

Hand wheel
Ratio
Std.

With bevel
gear set

Weight
Auma India Norm
Std.

With bevel
gear set

Kgs.

Min. / Max.

Kgs.

G 12
(F14)

52

120

1-480
or
1-4800

360

1:1

3:1

72

88

G 12
(F14)

52

160

1-480
or
1-4800

640

1:1

3:1

75

92

G 12
(F14)

52

160

1-480
or
1-4800

640

1:1

3:1

75

92

G3
(F16)

65

190

1-480
or
1-4800

800

1:1

4:1

107

128

3)

900

3)

Enclosure : IP67 - IS:13947


Actuators are rated for short time duty S2-15min, based on 40o C ambient temperature. The nominal current
is based on an average load of approximately 35% of max. torque. The max. torque can be utilised for a short
time (e.g. to seat or unseat a valve) and the current can rise to max. value. Refer corresponding column for
current at max. torque in Electrical Data.

1) Infinitely adjustable

2) At 50 Hz

3) Non self locking

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

31

Electrical Data

SA3-SA100

Open-Close duty
Auma India
Actuator Type
Torque
Max.

Type

Output Speed
at 50 Hz
1/min

Nm

30

60

55

120

110

150

250

SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA

Three phase Squirrel cage AC Motor 415V, 50 Hz

3
3
3
3
3
3
3
3
3
6
6
6
6
6
6
6
6
6
6
6
6
12
12
12
12
12
12
12
12
12
12
12
12
15
15
15
15
15
15
15
15
15
25
25
25
25
25
25
25
25
25
25
25
25

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
4
5.6
8
11
16
22
32
45
63
90
125
180

Nominal
Output
KW

Speed
1/min

Size

Nominal
Current
A

Current at
Max. Torque
1) A

Starting
Current
A

Power
Factor
Cos o

Full load
Efficiency
(%)

0.06
0.06
0.06
0.12
0.18
0.18
0.37
0.37
0.37
0.06
0.06
0.06
0.12
0.12
0.12
0.18
0.37
0.37
0.55
0.55
0.55
0.06
0.12
0.12
0.12
0.25
0.25
0.37
0.55
1.1
1.1
1.1
1.1
0.06
0.12
0.12
0.25
0.25
0.37
0.55
1.1
1.1
0.12
0.25
0.55
0.55
0.55
0.55
1.1
1.1
2.2
2.2
2.2
2.2

1400
1400
1400
1400
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800

71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
90
90
90
90

0.3
0.3
0.3
0.5
0.6
0.6
1.0
1.0
1.0
0.3
0.3
0.3
0.5
0.5
0.5
0.6
1.0
1.0
1.8
1.8
1.8
0.3
0.5
0.5
0.5
1.4
1.4
1.0
1.8
2.9
2.9
2.9
2.9
0.3
0.5
0.5
1.4
1.4
1.0
1.8
2.9
2.9
0.5
1.4
2.8
2.8
2.8
2.8
2.9
2.9
4.6
4.6
4.6
4.6

0.30
0.38
0.50
0.62
0.84
1.16
1.62
1.40
2.05
0.25
0.30
0.38
0.45
0.62
0.90
1.18
1.62
2.34
3.08
2.45
3.52
0.38
0.46
0.62
0.90
1.45
1.80
2.42
3.08
4.58
6.50
5.10
7.50
0.45
0.55
0.83
1.36
1.66
2.00
2.75
4.26
5.67
0.65
1.29
1.64
1.92
2.60
3.58
4.75
6.58
8.44
12.5
8.95
13.6

1.2
1.2
1.2
2.3
3.3
3.3
5.5
5.5
5.5
1.2
1.2
1.2
2.3
2.3
2.3
3.3
5.5
5.5
9.0
9.0
9.0
1.2
2.3
2.3
2.3
4.6
4.6
5.5
9.0
16.0
16.0
16.0
16.0
1.2
2.3
2.3
4.6
4.6
5.5
9.0
16.0
16.0
2.3
4.6
12.0
12.0
12.0
12.0
16.0
16.0
40.0
40.0
40.0
40.0

0.6
0.6
0.6
0.6
0.7
0.7
0.76
0.76
0.76
0.6
0.6
0.6
0.6
0.6
0.6
0.7
0.76
0.76
0.62
0.62
0.62
0.6
0.6
0.6
0.6
0.5
0.5
0.76
0.62
0.72
0.72
0.72
0.72
0.6
0.6
0.6
0.5
0.5
0.76
0.62
0.72
0.72
0.6
0.5
0.51
0.51
0.51
0.51
0.72
0.72
0.83
0.83
0.83
0.83

46
46
46
55
60
60
68
68
68
46
46
46
55
55
55
60
68
68
70
70
70
46
55
55
55
50
50
68
70
72
72
72
72
46
55
55
50
50
68
70
72
72
55
50
60
60
60
60
72
72
80
80
80
80

220
1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

32

Electrical Data

SA3-SA100

Open-Close duty
Auma India
Actuator Type
Torque
Max.

Type

Nm

300

264

500

450

600

540

1000

SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA

30
30
30
30
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
50
50
50
50
60
60
60
60
60
60
60
60
60
60
60
60
100
100
100
100
100
100
100
100
100
100
100
100

Three phase Squirrel cage AC Motor 415V, 50 Hz

Output Speed
at 50 Hz
1/min

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

4
5.6
8
11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
90
125
180
4
5.6
8
11
16
22
32
45
63
90
125
180

Nominal
Output
KW

Speed
1/min

Size

Nominal
Current
A

Current at
Max. Torque
1) A

Starting
Current
A

Power
Factor
Cos o

Full load
Efficiency
(%)

0.12
0.25
0.55
0.55
0.55
1.1
1.1
1.25
2.2
2.5
2.5
4.0
0.25
0.55
0.55
0.55
1.1
1.1
2.2
2.2
4.0
4.0
5.0
5.0
0.25
0.55
0.55
0.55
1.1
2.2
2.2
4.0
4.0
5.0
5.0
5.0
0.55
0.55
0.75
1.1
2.2
2.2
4.0
4.0
7.5
7.5
7.5
7.5

1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800
1400
1400
1400
1400
1400
1400
2800
2800
2800
2800
2800
2800

71
71
71
71
71
90
71
90
90
90
90
90
71
71
71
71
90
90
90
90
90
90
112
112
71
71
71
71
90
90
90
90
90
112
112
112
71
71
90
90
90
90
90
90
112
112
112
112

0.5
1.4
2.8
2.8
2.8
3.7
2.9
2.7
4.6
5.3
5.3
10.2
1.4
2.8
2.8
2.8
3.7
3.7
4.6
4.6
10.2
10.2
9.9
9.9
1.4
2.8
2.8
2.8
3.7
6.9
4.6
10.2
10.2
9.9
9.9
9.9
2.8
2.8
2.0
3.7
6.9
6.9
10.2
10.2
15.6
15.6
15.6
15.6

0.82
1.39
1.77
2.20
3.08
3.95
5.72
8.65
10.0
15.5
11.5
16.5
1.48
1.95
2.60
3.58
4.80
6.65
8.52
12.5
17.1
26.0
18.2
28.5
1.67
2.2
3.08
5.15
5.75
7.92
10.04
15.05
21.08
31.08
22.5
35.5
2.55
3.85
4.65
6.65
9.06
12.5
17.5
26.0
40.0
60.0
44.6
68.0

2.3
4.6
12.0
12.0
12.0
25.0
16.0
22.0
40.0
40.0
40.0
65.0
4.6
12.0
12.0
12.0
25.0
25.0
40.0
40.0
65.0
65.0
80.0
80.0
4.6
12.0
12.0
12.0
25.0
40.0
40.0
65.0
65.0
80.0
80.0
80.0
12.0
12.0
12.0
25.0
40.0
40.0
65.0
65.0
116.0
116.0
116.0
116.0

0.6
0.5
0.51
0.51
0.51
0.58
0.72
0.81
0.83
0.83
0.83
0.7
0.5
0.51
0.51
0.51
0.58
0.58
0.83
0.83
0.7
0.7
0.86
0.86
0.55
0.51
0.51
0.51
0.58
0.63
0.83
0.7
0.7
0.86
0.86
0.86
0.51
0.51
0.72
0.58
0.63
0.63
0.7
0.7
0.78
0.78
0.78
0.78

55
50
60
60
60
72
72
79
80
79
79
78
50
60
60
60
72
72
80
80
78
78
88
50
50
60
60
60
72
72
80
78
78
88
88
88
60
60
75
72
72
72
78
78
86
86
86
86

900

Permissible voltage variation : + 10%, Permissible frequency variation : + 5%, Permissible combined variation : 10%
if voltage drops below there will be reduction of nominal output.
Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our
warranty is void if those thermoswitches are not connected in control circuit.
Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.

1) Current at max. torque. We recommend to select switch gear and cables suitable for those values.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

33

Technical Data

SAR6-SAR100

Regulating duty
1)
ReguAuma India
Tripping
lating
Actuator Type
Torque
in both Torque
Type
Output Speed
directions
2)

Min. Max. Max.


Nm Nm Nm

30

60

30

60 120 60

60 150 75

120 250 120

150 300 150

250 500 250

300 600 300

1/min

SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR

6
6
6
6
6
6
6
6
12
12
12
12
12
12
12
12
15
15
15
15
15
15
15
25
25
25
25
25
25
25
25
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
60
60
60
60
60
60
100
100
100
100
100
100

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
16
22
32
4
5.6
8
11
16
22

No. of
starts

Max.
c/h

Valve
Mounting
Flange
Standard
DIN:3210
(Special
ISO:5210)

Stem dia.
Output drive
Type-A

Max. mm

Permissible
Thrust for
Type-A

Max.

Hand
wheel
Dia.
Std.

Hand wheel
Ratio

Weight
Auma India Norm

Std. With bevel


gear set

Std. With bevel


gear set

kN

Kgs.

Kgs.

1200

G0
(F10)

26

40

250

1:1

2:1

39

45

1200

G0
(F10)

38

60

250

1:1

2:1

39

45

G0
(F10)

38

60

250

1:1

2:1

39

45

G 12
(F14)

52

120

360

1:1

3:1

72

88

G 12
(F14)

52

120

360

1:1

3:1

72

88

G 12
(F14)

52

160

640

1:1

3:1

75

92

G 12
(F14)

52

160

640

1:1

3:1

75

92

G3
(F16)

65

190

800

1:1

4:1

107

128

900

1200

1200
900
600

1200

600
1200
900
600
1200
600
1200
900

500 1000 500


600

Enclosure : IP67 - IS:13947


Actuators are rated for Intermittent duty S - 25% ED, based on 40o C ambient temperature. The nominal current is based on an
average load of approximately 35% of max. torque. The max. torque can be utilised for a short time (e.g. to seat or unseat
a valve) and the current can rise to max. value. Refer corresponding column for current at max. torque in Electrical Data.

1) Infinitely adjustable

2) At 50 Hz

We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

34

Electrical Data

SAR6-SAR100

Regulating duty
Auma India
Actuator Type

Regulating Torque
Type
Max.
Nm

30

60

75

125

150

250

300

SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR
SAR

Output Speed
at 50 Hz
1/min

6
6
6
6
6
6
6
6
12
12
12
12
12
12
12
12
15
15
15
15
15
15
15
25
25
25
25
25
25
25
25
30
30
30
30
30
30
30
30
50
50
50
50
50
50
50
50
60
60
60
60
60
60
100
100
100
100
100
100

.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....
.....

4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
11
16
22
32
45
4
5.6
8
16
22
32
4
5.6
8
11
16
22

Three phase Squirrel cage AC Motor 415V, 50 Hz


Nominal
Output
KW

Speed
1/min

Size

Nominal
Current
A

Current at
Max. Torque
1) A

Starting
Current
A

Power
Factor
Cos o

0.06
0.06
0.06
0.12
0.12
0.12
0.25
0.25
0.06
0.12
0.12
0.12
0.25
0.25
0.55
0.55
0.06
0.12
0.12
0.25
0.25
0.55
0.55
0.12
0.25
0.25
0.55
0.55
0.55
1.1
1.1
0.12
0.25
0.25
0.55
0.55
1.1
1.1
2.2
0.25
0.55
0.55
0.55
1.1
1.1
2.2
2.2
0.25
0.55
0.55
1.1
2.2
2.2
0.55
0.55
0.75
1.1
2.2
2.2

1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400
1400

71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
71
90
90
71
71
71
71
71
90
90
90
71
71
71
71
90
90
90
90
71
71
71
90
90
90
71
71
90
90
90
90

0.3
0.3
0.3
0.5
0.5
0.5
1.4
1.4
0.3
0.5
0.5
0.5
1.4
1.4
2.8
2.8
0.3
0.5
0.5
1.4
1.4
2.8
2.8
0.5
1.4
1.4
2.8
2.8
2.8
3.7
3.7
0.5
1.4
1.4
2.8
2.8
3.7
3.7
6.9
1.4
2.8
2.8
2.8
3.7
3.7
6.9
6.9
1.4
2.8
2.8
3.7
6.9
6.9
2.8
2.8
2.0
3.7
6.9
6.9

0.25
0.30
0.38
0.45
0.62
0.90
1.45
1.86
0.38
0.46
0.62
0.90
1.45
1.80
2.52
3.52
0.45
0.55
0.83
1.36
1.66
2.20
3.08
0.65
1.29
1.64
1.92
2.60
3.58
4.80
6.67
0.82
1.39
1.77
2.20
3.08
3.95
5.75
8.0
1.48
1.95
2.60
3.58
4.80
6.65
9.06
13.4
1.67
2.2
3.08
5.75
7.92
11.1
2.55
3.85
4.65
6.65
9.06
12.5

1.2
1.2
1.2
2.3
2.3
2.3
4.6
4.6
1.2
2.3
2.3
2.3
4.6
4.6
12.0
12.0
1.2
2.3
2.3
4.6
4.6
12.0
12.0
2.3
4.6
4.6
12.0
12.0
12.0
25.0
25.0
2.3
4.6
4.6
12.0
12.0
25.0
25.0
40.0
4.6
12.0
12.0
12.0
25.0
25.0
40.0
40.0
4.6
12.0
12.0
25.0
40.0
40.0
12.0
12.0
12.0
25.0
40.0
40.0

0.6
0.6
0.6
0.6
0.6
0.6
0.5
0.5
0.6
0.6
0.6
0.6
0.5
0.5
0.51
0.51
0.6
0.6
0.6
0.5
0.5
0.51
0.51
0.6
0.5
0.5
0.51
0.51
0.51
0.58
0.58
0.6
0.5
0.5
0.51
0.51
0.58
0.58
0.63
0.5
0.51
0.51
0.51
0.58
0.58
0.63
0.63
0.5
0.51
0.51
0.58
0.63
0.63
0.51
0.51
0.72
0.58
0.63
0.63

Full load
Efficiency
(%)

46
46
46
55
55
55
50
50
46
55
55
55
50
50
60
60
46
55
55
50
50
60
60
55
50
50
60
60
60
72
72
55
50
50
60
60
72
72
72
50
60
60
60
72
72
72
72
50
60
60
72
72
72
60
60
75
72
72
72

500

Permissible voltage variation : + 10%, Permissible frequency variation : + 5%, Permissible combined variation : 10%
if voltage drops below there will be reduction of nominal output.
Auma motors are provided with 3 thermoswitches one in each winding connected in series to protect windings. Our
warranty is void if those thermoswitches are not connected in control circuit.
Motor data are approximate. Due to usual manufacturing tolerances there may be deviations from the values given.
1) Current at Max. torque. We recommend to select switch gear and cables suitable for those values.
We reserve the right to alter data according to improvements made. Previous data sheets become invalid with the issue of this data sheet.

35

SA3-SA100
SAR6-SAR100

Norm actuator

Dimensions
A
B
C
D
D1
D2
E
J
L max.
LL min.
M min.
N
O
P
Q min
R (Conduit th)
S
Y
d
g (TYPE - A)
g1 (TYPE - B & C)
g2 ( TYPE - D & E)
DIN 3210 Designation

SA3 & SA6


SAR6

SA12 & SA15


SAR12 & SAR15

SA25 & SA30


SAR25 & SAR30

SA50 & SA60


SAR50 & SAR60

SA100
SAR100

215
257
210
250
110 - 125
42 x 3.3
195
185
175-230
35
80
110
96
142
65
2x1
BSC
1
255 4 ''

215
257
235
250
110 - 125
60 x 3.7
195
185
175-230
35
80
110
96
142
65
2x1
BSC
1
255 4 ''

245
282
275
360
110 - 160
76 x 3.7
255
210
175-280
45
80
170
96
167
65
2x1
BSC
1
255 4 ''

245
282
275
640
125 - 160
76 x 3.7
255
210
210-280
45
80
170
96
167
65
2x1
BSC
1
255 4 ''

275
307
380
800
125 - 200
89 x 4.1
255
230
210-305
60
80
210
96
192
65
2x1
BSC
1
255 4 ''

182
125
35
50
15
G0

185
125
37
50
15
G0

250
175
51
65
22
G

250
175
51
65
22
G

306
210
69
80
30
G3

We reserve the right to alter data, dimensions and weights according to improvement made.
Figures and diagrams are not binding.

36

(all dimensions are in mm)

SA3-SA100
SAR6-SAR100

Integral starter compact actuator

Dimensions

SA3 & SA6


SAR6

SA12 & SA15


SAR12 & SAR15

SA25 & SA30


SAR25 & SAR30

SA50 & SA60


SAR50 & SAR60

SA100
SAR100

A
B
C
D
D1
D2
E
J
K
L max.
LL min.
M min.
N
O
P
Q min
R (Conduit th)
S
V
W
d
g (TYPE - A)
g1 (TYPE - B & C)
g2 ( TYPE - D & E)
DIN 3210 Designation

215
430
210
250
110 - 125
42 x 3.3
195
185
342
340
35
80
227
96
315
65
2x1
BSC
25514 ''
160
185
125
35
50
15
G0

215
430
235
250
110 - 125
60 x 3.7
195
185
342
340
35
80
227
96
315
65
2x1
BSC
25514 ''
160
185
125
37
50
15
G0

245
451
275
360
110 - 160
76 x 3.7
255
210
342
450
45
80
227
96
340
65
2x1
BSC
25514 ''
160
185
175
51
65
22
G

245
451
275
640
125 - 160
76 x 3.7
255
210
342
450
45
80
227
96
340
65
2x1
BSC
25514 ''
160
185
175
51
65
22
G

275
467
380
800
125 - 200
89 x 4.1
255
230
342
515
60
80
227
96
365
65
2x1
BSC
25514 ''
160
185
210
69
80
30
G3

1
2

We reserve the right to alter data, dimensions and weights according to improvement made.
Figures and diagrams are not binding.

1
2

(all dimensions are in mm)

37

SA3-SA100
SAR6-SAR100

Integral starter epac actuator

e-pac

e-pac

e-pac

Dimensions
A
B
C
D
D1
D2
E
J
K
L max
LL min.
M min.
N
O
P
Q min
R (Conduit th)
S
V
W
Z (For ON-OFF Duty)
Z1 (For Regulating Duty)
d
g (TYPE - A)
g1 (TYPE - B & C)
g2 ( TYPE - D & E)
DIN 3210 Designation

SA3 & SA6


SAR6

SA12 & SA15


SAR12 & SAR15

SA25 & SA30


SAR25 & SAR30

SA50 & SA60


SAR50 & SAR60

SA100
SAR100

215
278.5
210
250
110 - 125
42 x 3.3
195
185
256
340
35
80
240.5
96
400.5
65
2x1
BSC
25514 ''
185
175
121
202
125
35
50
15
G0

215
278.5
235
250
110 - 125
60 x 3.7
195
185
256
340
35
80
240.5
96
400.5
65
2x1
BSC
25514 ''
185
175
121
202
125
37
50
15
G0

245
303.5
275
360
110 - 160
76 x 3.7
255
210
256
450
45
80
240.5
96
425.5
65
2x1
BSC
25514 ''
185
175
121
202
175
51
65
22
G

245
303.5
325
640
125 - 160
76 x 3.7
255
210
256
450
45
80
240.5
96
425.5
65
2x1
BSC
25514 ''
185
175
121
202
175
51
65
22
G

275
329.5
380
800
125 - 200
89 x 4.1
255
230
256
515
60
80
240.5
96
451.5
65
2x1
BSC
25514 ''
185
175
121
202
210
69
80
30
G3

1
2

We reserve the right to alter data, dimensions and weights according to improvement made.
Figures and diagrams are not binding.

38

1
2

(all dimensions are in mm)

SA3-SA100
SAR6-SAR100

Output drives according to DIN 3210


SA3/
SA6

SAR 6

SA12/
SA15

SAR12/
SAR15

SA25/
SA30

SAR25/
SAR30

SA50/
SA60

SAR50/
SAR60

39

SA100/
SAR100

SA6-SA100
with
LTU6-LTU100

Linear Thrust Unit for control valves

For all other dimensions of actuator, please refer separate data sheet

Dimensions
Stroke (L) mm
Thrust max. kN

LTU6
SA / SAR6
50
100
20

LTU12
SA / SAR12
60
120
35

LTU25
SA / SAR25
80
160
63

LTU50
SA / SAR50
80
160
100

10

18

31.5

50

Thrust max. kN
for Regulating
Stem thread, LH
A

Tr. 24x5
150

200

Tr. 32x6
155

215

Tr. 40x7
219

299

Tr. 50x8
219

299

60

70

101

101

25

30

55

55

70

70

100

100

125

125

175

175

F
G
H
J
K

40

(all dimensions are in mm)

15

15

16

16

M10

M10

M16

M16

102

102

140

140

M16x1.5

M20x1.5

M36x3

M36x3

LTU100
SA / SAR100

Terminal plan - Norm actuator

DSR

Torque switch, closing, clockwise rotation

DOL

Torque switch, opening, anti-clockwise rotation

WSR

Limit switch, closing, clockwise rotation


Limit switch, opening, anti-clockwise rotation

WOL
DSR1
DOL1

}
}

Torque switch in tandem operation


with DSR/DOL

WSR1
WOL1

Limit switch in tandem operation


with WSR/WOL

Th

Thermo switch

b1

Push button for stop

b2

Push button for close

b3

Push button for open

C1

Contactor-close

C2

Contactor-open

e4

Thermal overload relay

e5

Control fuse

h1

Indicator lamp-close

h2

Indicator lamp-open

h3

Indicator lamp-trouble

Motor (3Phase AC) 415V, 3 , 50Hz

a1

Main switch

SH

Space heater

b4

Selector switch

Neutral

Earth

R,S,T(L1,L2,L3)
e1-e3

Phases
Main fuse

Auto

Manual

41

Wiring diagram - Integral starter, epac

42

Th

RL1

RL2

RL3

C8M-C8F

C15M-C15F

DSR

DOL

WSR

WOL

DSR1/DOL1

WSR1/WOL1

F,G

R,Y,B

A,B,C

L 1-27

SH

K2

Space heater

Terminals for customer's connections

Motor terminals

Main supply 415V, 3o, 50Hz, AC Supply

and Integral starter(epac)

Plug in type terminals between basic actuator(Norm)

Limit switch in tandem operation with WSR/WOL

Torque switch in tandem operation with DSR/DOL

Open limit switch

Close limit switch

Open torque switch

Close torque switch

Motor 3Ph, 415V, 50Hz.

24 Pin Rack & panel Male-Female connector

64 Pin Male-Female connector

24V DC Relay for FAULT Annunciation

24V DC Relay for CLOSE Contactor

24V DC Relay for OPEN Contactor

Thermoswitch

Close Contactor

Open Contactor

Potential free contact Local-Off-Remote

Collective fault indication for


- Thermoswitch trip
- Torque switch trip

K1

Info-B

Info-A

Limit switch close

Status

43

4
5

Switch
No

Limit switch close bypass


(Closing by torque switch Close)
(Torque Seating)

Inching operation in Remote


mode (non self retaining)

Timer board operation enabled

Inching operation in Local mode


(non self retaining)

Switch position
OFF

Description

Single phasing

Fault indication

Limit Seating

Non-Inching operation in Remote mode


(self retaining)

Inhibit Close direction

Inhibit Open direction

Timer board operation disenabled

Emergency shut down to Close

Emergency shut down to Open

Applicable

Applicable

Not-Applicable

Not-Applicable

Not-Applicable

Not-Applicable

Not-Applicable

Applicable

Remarks

Thermal overload relay trip

Thermoswitch trip

Torque switch close

Torque switch open

Switch position
ON

Fault

Fault

Fault

Fault

Fault

Fault

Symbol Type

Non-inching operation in Local mode


(self retaining)

24V DC For Customer's use

23V Internal power supply

11V Internal power supply

Actuator in remote mode

Dip switch particulars:-

Status

Status

Status

Status

Actuator in local mode

Limit switch open

Status

Status

Actuator in Close direction

Actuator in open direction

Description

Status

Status

Symbol Type

Display board legend:-

Legend - Integral starter, epac

automates valves

auma india norm


SA3 - SA100
SAR6 - SAR100
Output torque from 30 to 1000 Nm

Worm Gear Boxes


GS 40.2-GS 125.2
Output torque from 300 to 5600 Nm

auma india e-pac


SA3 - SA100
SAR6 - SAR100
Output torque from 30 to 1000 Nm

Bevel Gear Boxes


GK 10.2-GK 35.1
Output torque from 120 to 8000 Nm

Worm Gear Boxes


GS 160-GS 500
Output torque from 8000 to 360000 Nm

Head Office and Works


AUMA (INDIA) LIMITED
Plot No. 39-B, II Phase
Peenya Industrial Area
Bangalore - 560 058.
: 080-8394365
Ph
080-8394366
080-8392808
: 080-8392809
Fax
E-mail : info@auma.co.in

Worm Gear Boxes


GF 40.2-GF 250
Output torque from 300 to 45000 Nm

Spur Gear Boxes


GST 12-GST 1600
Output torque from 120 to 16000 Nm

Branch Office
AUMA (INDIA) LIMITED
8-C, Block B-H,Munirka
NEW DELHI - 110 067.

Branch Office