You are on page 1of 40

Packaged Units

PCY Series
PCY036 - PCY360
3 TR thru 30 TR
10 kW thru 105 kW

R-407c

INDEX
Contents

Page

Model decoding ......................................................................................................................................... 2


Blower drive options .................................................................................................................................. 3
Standard specifications/options/accessories .......................................................................................... 3-6
Physical data ......................................................................................................................................... 7-8
Selection procedure .................................................................................................................................. 9
Cooling capacities ............................................................................................................................... 10-14
Electrical data ..................................................................................................................................... 15-20
Fan performance data .........................................................................................................................21-25
Sound level data ................................................................................................................................. 26-32
Pressure drop/blower motor efficiency .................................................................................................... 33
Unit dimensions .................................................................................................................................. 34-36
Controls and sequence of operation ........................................................................................................ 37
Typical schematic wiring diagram ....................................................................................................... 38-39

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

MODEL DECODING
MODELS: PCY036 - PCY060 (DIRECT DRIVE MOTOR)
4, 5 & 6
7
NOMINAL ELECTRICAL
COOLING
SUPPLY
CAPACITY
( V-Ph-Hz )
(MBH)

1, 2 & 3
BASIC

PCY

036

PACKAGED
UNIT
(R-407c)

C : 208/230-1-60*
H : 208/230-3-60

048
060

M : 380-3-60
(4 WIRE)

8
BLOWER
MOTOR

9
DRIVE
OPTIONS

10
HEATER OPTIONS
(kW/STAGE)

U : 0.5 HP ODP N : DIRECT N : NO HEATER


DRIVE
(DIRECT DRIVE)
A : 5/1
W : 0.75 HP ODP
(DIRECT DRIVE)

C : 7.5 /1
D : 10 /2**

F : 460-3-60

NOTE:

*
**
***

11
EVAPORATOR
COIL

12
CONDENSER
COIL

J : ALUMINUM FIN J : ALUMINUM FIN

N : STANDARD UNIT

K : COATED
K : COATED
ALUMINUM FIN
ALUMINUM FIN
L : COPPER FIN

L : COPPER FIN

M : ALUMINUM
FINS WITH
RTC.

M : ALUMINUM
FINS WITH
RTC.

N : COPPER FINS
WITH RTC.

N : COPPER FINS
WITH RTC.

14
ELECTRICAL
OPTIONS

13
ACCESSORIES

N
I
U
V

: STD. UNIT
: ANTI-ICE
: UVM
: VOLT FREE
CONTACTS***

15
FILTER OPTIONS

A : 1" THICK
ALUMINUM

16
THERMOSTAT
OPTION

S : UNIT WITH
THERMOSTAT
D : UNIT WITHOUT
THERMOSTAT

K : ADJ. PRESSURE
SWITCH
A :I & U
B :I&V
C :U&V
D : I, U & V
E : I, U & K
F : I, V & K
G : U, V & K
H : I, U, V & K
J :I&K
L :V&K
M :U&K

Applicable for PCY036 & PCY048 models only.


Applicable for PCY060 model only.
Volt free contact option is available as: A) Unit ON/TRIP indication, B) Compressor RUN/TRIP indication, C) Blower motor RUN/TRIP indication.

MODELS: PCY075 - PCY360 (BELT DRIVEN MOTOR)


1, 2 & 3
BASIC

PCY
PACKAGED
UNIT
(R-407c)

4, 5 & 6
7
NOMINAL ELECTRICAL
COOLING
SUPPLY
CAPACITY
( V-Ph-Hz )
(MBH)
075

090
100

H : 208/230-3-60
M : 380-3-60
(4 WIRE)
F : 460-3-60

8
BLOWER
MOTOR

R : 1.5 HP ODP
Z : 2 HP ODP

9
DRIVE
OPTIONS

J : ALT. I
K : ALT. II

Z : 2 HP ODP
E : 3 HP ODP

10
HEATER OPTIONS
(kW/STAGE)

11
EVAPORATOR
COIL

12
CONDENSER
COIL

13
PDS
OPTION

N : NO HEATER

J : ALUMINUM FIN J : ALUMINUM FIN N : NO PDS

B : 6/1

P : STD. UNIT
K : COATED
K : COATED
WITH PDS
ALUMINUM FIN
ALUMINUM FIN

C : 7.5/1
D : 10/2
E : 12/2

L : COPPER FIN

L : COPPER FIN

M : ALUMINUM
FINS WITH
RTC.

M : ALUMINUM
FINS WITH
RTC.

120

E : 3 HP ODP

150

E : 3 HP ODP
G : 5 HP ODP

G : 20/2 (For PCY090 -150) N : COPPER FINS


WITH RTC.
H : 25/2 (For PCY090 -150)

180
210

G : 5 HP ODP
J : 7.5 HP ODP

N : NO HEATER

240

J : 7.5 HP ODP

300

J : 7.5 HP ODP
L : 10 HP ODP

360

L : 10 HP ODP
M : 15 HP ODP

F : 15/2

F : 15/2
G : 20/2
H : 25/2
J : 30/2
K : 35/2
L : 40/2 (For PCY240 -360)

N : COPPER FINS
WITH RTC.

S : SIGHT
GLASS
G: P&S

14
ELECTRICAL
OPTIONS

N : STD. UNIT
I : ANTI-ICE

15
ACCESSORIES

N : STANDARD UNIT

C : STD. UNIT WITH


U : UVM
FRESH AIR HOOD
& MANUAL
V : VOLT FREE
DAMPER
CONTACTS*
K :ADJ.
PRESSURE
SWITCH
A :I & U
B :I&V
C :U&V
D : I, U & V
E : I, U & K
F
G
H
J
L
M

: I, V & K
: U, V & K
: I, U, V & K
:I&K
:V&K
:U&K

NOTE: * Volt free contact option is available as: A) Unit ON/TRIP indication, B) Compressor RUN/TRIP indication, C) Blower motor RUN/TRIP indication.

A : ECONOMIZER
B : ECONOMIZER
WITH ENTHALPY
SENSOR

16
FILTER
OPTIONS

17
THERMOSTAT
OPTION

A : 1" THICK
S : UNIT WITH
THERMOSTAT
ALUMINUM
D : UNIT
B : 2" THICK
ALUMINUM
WITHOUT
THERMOSTAT

BLOWER DRIVE OPTIONS


MOTOR
MODEL
NUMBER
PCY075
PCY090
PCY100
PCY120
PCY150
PCY180
PCY210
PCY240
PCY300

PCY360

OPTION

BLOWER

HP (kW)

RPM

1.5 (1.1)
2 (1.5)
2 (1.5)
3 (2.2)
2 (1.5)
3 (2.2)

PULLEY
PITCH DIA.
(INCH)
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
2.7 - 3.7
3.1 - 4.1
3.7 - 4.7

938
1270
938
1270
938
1270
938
1270
763
956

PULLEY
PITCH DIA.
(INCH)
6.9
5.1
6.9
5.1
6.9
5.1
6.9
5.1
9.4
8.6

SPEED RANGE (RPM)


MINIMUM MAXIMUM
685
927
685
927
685
927
685
927
577
752

APPROX. SPEED
CHANGE PER
PULLEY TURN
(RPM)
42
57
42
57
42
57
42
57
31
39

5 (3.7)

1750
1750
1750
1750
1750
1750
1750
1750
1750
1750

ALT. I

5 (3.7)

1750

3.7 - 4.7

689

875

9.4

31

ALT. II

7.5 (5.6)

1750

4.3 - 5.5

836

1070

39

ALT. I

5 (3.7)

1750

3.7 - 4.7

589

748

11

27

ALT. II

7.5 (5.6)

1750

3.7 - 4.7

719

914

33

1750

4.3 - 5.5

684

875

11

32

1750

4.3 - 5.5

801

1024

9.4

37

ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II
ALT. I
ALT. II

ALT. I
ALT. II

3 (2.2)
3 (2.2)

7.5 (5.6)

ALT. I

7.5 (5.6)

1750

4.3 - 5.5

684

875

11

32

ALT. II

10 (7.5)

1750

4.3 - 5.5

801

1024

9.4

37

ALT. I

10 (7.5)

1750

4.3 - 5.5

684

875

11

32

ALT. II

15 (11.2)

1750

4.3 - 5.5

801

1024

9.4

37

STANDARD SPECIFICATIONS
A. General
Packaged cooling or combination heating and cooling units suitable for mounting on the roof or ground. The packaged unit
consists of scroll compressors, cooling coil, condenser coil, control wiring and interconnecting piping - all factory assembled and mounted on heavy gauge G-90 galvanized steel sheet press formed base, ready for field connection to utilities
and ducts. The packaged unit is of rigid construction with holes provided in the base rails for overhead rigging. The unit is
provided with an integral weather resistant control panel.
These units are rated, tested and certified in accordance with AHRI standards 210/240 and AHRI 340/360.

B. Unit Enclosure
Panels are of heavy gauge, G-90 galvanized steel sheet with removable access panels, completely weatherized for outdoor
installation and properly reinforced and brazed. Panels and access doors are provided for inspection and access for all
internal parts. Enclosures are provided with adequately reinforced points of support for setting the unit. Steel sheet panels
are zinc-coated and galvanized by the hot dip process of lock forming quality conforming to ASTM A 653 commercial
weight G-90, followed by baked on electrostatic polyester dry powder coat paint, on all external panels.

C. Compressor
Compressors are hermetic scroll for all models. They are provided with all the standard controls and accessories necessary
for safe operation. These are equipped with internal motor protector, factory installed crank case heater and rubber vibration
isolator for quiet and efficient operation.

D. Air Cooled Condensing Section


1. The air-cooled condensing section is enclosed within the unit housing and consists of condenser coil, fan(s), electric
motor(s) and inherently protected compressor(s). Inner grooved copper tubes with wall thickness of 0.0175 inches
(0.445 mm), mechanically bonded to enhanced aluminum fins are standard for all condenser coils. Return bends have
0.022 inch thickness (0.56 mm). As an option, corrugated copper fins or enhanced coated aluminum fins may
be provided. Tube support sheets are galvanized steel, formed to provide structural strength.
2. Fans are propeller type, direct driven, upward discharge and provided with fan grille mounted on the casing.
3. Motors are totally enclosed air-over type with class 'F' insulation & IP55 ratings. Inherent thermal protection is automatic
reset type.
3

E. Evaporator Coil Section


1. All cooling coils are of enhanced louvered fins and inner grooved copper tubes with wall thickness of 0.0175 inches
(0.445mm), mechanically bonded to aluminum fins . Return bend has 0.022 inch thickness (0.56 mm). As option,
enhanced coated aluminum fins or corrugated copper fins may be provided. Tube support sheets are galvanized steel, formed to provide structural strength.
2. Drain Pan: An insulated drain Pan made of G-90 galvanized steel is provided.
3. Insulation: Insulation is supplied in adequate density and thickness for all units to prevent condensation from forming
on the unit casing. Insulation meets the requirements of NFPA 90A and is protected against deterioration and erosion
from air currents.

F. Evaporator Fan
PCY036 - PCY060: Evaporator fan is of a centrifugal forward-curved blade design and sized to meet system airflow/
pressure using direct drive motors. These fans are statically / dynamically balanced in the fan housing during final assembly. Fan motors have ball bearings and conform to NEMA MG standards. Motor starters are magnetic contactor, acrossthe-line type.
PCY075 - PCY360: Evaporator fan is of centrifugal forward-curved blade design capable of handling total required CFM and
static pressure in the low and the medium ranges. Casings are made of galvanized steel. Blower motors are of the open drip
proof type (totally enclosed types are optional) and conform to NEMA MG standards. Fan drive is through adjustable
pitch pulleys and belt driven. Blower motor is mounted on adjustable base and secured by locking device. Fan wheels
shafts and bearing are selected to operate at 25% below first critical speed. Pillow block bearings are selected for at
200,000 hours average life at design operating conditions. Shaft is turned, ground and polished from solid steel. Fans and
pulleys are keyed to shaft and designed for continuous operation at maximum motor horse power and fan speed. All rotating
components and assemblies are statically and dynamically balanced and every unit is vibration tested before shipment
from the factory.

G. Microprocessor Controller
These Packaged units are provided with a microprocessor control board incorporating the following features:

BALANCE LOADING OF COMPRESSORS: The units electronic control automatically operates lead/lag sequence
of compressors. This is to load the compressors evenly over long periods of operation. If required however, compressor-1 can also be set to always lead. In this case, compressor-1 always starts first and stops last. (Selectable through
dip switch setting on control board).

PUMP DOWN FUNCTION: In units equipped with pump down system, the controller provides the time delay between
solenoids opening and compressor starting to equalize the pressure in the system necessary for compressor to startup. (Selectable through dip switch setting on control board).

COMPRESSOR ANTI-RECYCLING PROTECTION: The controller has a built-in 3 minutes minimum off timer for
compressor. This is for compressor protection in case of accidental manual re-set or immediate re-cycling of thermostat due to load demand.

COMPRESSOR LOCK-OUT FUNCTION: If any of the units safety control trips due to abnormal conditions, the
electronic controls locks out the compressor after a pre-determined timing preventing a re-start unless attended by a
qualified service technician. The unit can be re-started through thermostat re-set after ensuring safe system conditions.

FAULT DIAGNOSTICS: In case of system fault, LEDs on the board emits a flashing signal indicating where the fault
is. This is to guide the service technician in identifying the fault.

DIGITAL I/Os: The units control board is compatible to operate with a DDC controller or any standard 24V a.c.
thermostat commercially available.

SEQUENTIAL CONTROL: With input signals from the thermostat, the motors in the equipment is started in sequential order: supply fan condenser fan compressor; at a pre-determined timings.

OPTIONS AND ACCESSORIES


A. Electric Heaters
Electric heaters are of the resistance open coil type and conform to the requirements of UL 573 or equivalent. Electrical
characteristics, kW capacities and number of stages are as indicated. Airflow switches, fusible links and overheat limit
thermostats are provided to shut-off power in case of airflow failure/overheat. Electric heater kit is installed as an externally mounted kit at the supply opening.

B. UV FlowTM Light Emitters:


The damp & dark environment inside the unit could contribute for the growth and development of hazardous bacteria and
TM
fungi. The UV flow concept uses emitter of Ultra Violet to simulate the effect of healthy sun radiation. This will inhibit the
TM
growth of these microorganism reducing in this manner mold related allergies and diseases. Breath safely with UV flow .
TM

To order UV flow use the kit number in tables below:


MODEL No. PCY036/048/060
KIT PART No.

700-391-30

PCY075

PCY090

PCY100

700-391-23

700-391-24

700-391-25

PCY120/150 PCY180/210 PCY240/300


700-391-26

700-391-27

700-391-28

PCY360
700-391-31

C. Economizer
This can be provided as an option to be ordered separately if required for horizontal discharge units only. Economizer
utilizes cool outside air to satisfy cooling load to minimize energy consumption by maintaining poise between outside air
intake and compressor operation when required as per load demand.
The Economizer is operative either by a dry bulb Outdoor Air Thermostat (OAT) or a Solid State Enthalpy Controller (EC) to
sense the outdoor air temperature. The unit is equipped with an electronic control board, the PsychroTroll with a
sensitive feedback system carefully modulating the damper to allow correct percentage of fresh air and return air. The
PsychroTroll is designed to match with a separate Zamil electronic controller & thermostat.

D. Electronic Thermostat
General information: Electronic thermostat shall control one or two stage heating and cooling applications. The thermostat normally displays room temperature and mode of operation.
The temperature can be set by up/down buttons for both cooling and heating cycles. The thermostat also allows you to
select continuous fan operation, or have the fan on intermittent operation with the equipment.
The thermostat is best located about 1500 mm (5 Ft.) above floor level, on a partition wall (not an outside wall), and
should not be exposed to direct light from lamps, sun etc. It should be in return air stream, away from supply air registers/
diffusers.

Single/dual stage - Cooling & heating.


Low voltage control - 24 VAC (nominal).
Room temperature display - in C or F.
Mode of operation - FAN/COOL/HEAT/AUTO.
Fan mode - ON: Continuous fan operation; AUTO: Fan operates ON/OFF with compressor.
Heating & cooling setpoint is permissible.
Temperature set button - Up for increasing & down for decreasing temperature.
Built-in compressor fault & clogged filter indication led lights.
Remote sensing function as an option. Duct sensor is provided with the thermostat.
0

TYPICAL THERMOSTAT
Part No.

Heating Cooling Selector Switch Positions


Stages Stages Mode Switch Fan Switch

800-652-64

1&2

OFF-HEAT/COOL

ON - AUTO

800-652-66

1&2

OFF-HEAT/COOL

ON - AUTO

E. Under Voltage Monitors (UVM)


UVM combines voltage monitoring, phase loss, reversal and imbalance. When the voltage drops below safe limits, the
control relays turn off the equipment. When the device sensed such faults, it will cut-off the supply in the control circuit
thereby cutting off power to the motors. The voltage monitor will re-set automatically when power is brought back to its
normal conditions.
LINE VOLTAGE
RANGE

TRIP & RE-SET VOLTAGE (% OF SET POINT)


UNDER VOLTAGE

190 - 480 VAC

OVER VOLTAGE

PHASE IMBALANCE

TRIP

RE-SET

TRIP

RE-SET

TRIP

RE-SET

90%

93%

110%

107%

6%

4.5%

STANDARD FEATURES/OPTIONS/ACCESSORIES
STANDARD
FEATURES

DESCRIPTION
Horizontal discharge
Compressor crankcase heaters
Evaporator fanbelt driven(1)
Evaporator fan motor ODP type (TEFC type optional)(2)
Condenser fan direct drive, propeller type
Condenser fan motor totally enclosed air-over type
Electric heaters
Filter drier
Filter, aluminum
Bag filter*
Compressor overload protection
Low pressure switch
High pressure switch
Cooling & heating thermostat
Condenser fan guard
Condenser coil guard
Manual outside air damper(3)
Economizer
Enthalpy sensor
NOTES:
(1) Direct drive motors for PCY036 to PCY060.
(2) TEFC motors are available for PCY075 to PCY360.

(3) Manual outside air damper is available for PCY075 to PCY360.


* Unit specific - Check with factory.

OPTION
(FACTORY
INSTALLED)

ACCESSORY
(FIELD
INSTALLED)

PHYSICAL DATA
(DIRECT DRIVE MOTOR)
MODEL NUMBER

PCY036

PCY048

PCY060

NOMINAL CAPACITY, TONS (kW)

3 (10.5)

4.3 (15)

5 (17.5)

Quantity

Oil (oz)

42

46

66

COMPRESSOR

CONDENSER FAN

Refrigerant

R-407c

Type/Drive

Propeller/Direct

Quantity Diameter (inch)


Nominal CFM (L/S)
Motor HP RPM
CONDENSER COIL

1 26

1 26

3000 (1415)

5000 (2360)

5000 (2360)

1/3 1075

1/3 850

1/3 850

Inner Grooved Tubes and Enhanced Fins

Type
Tube dia. - Rows - Fins per inch
Total face area, Sq. ft. (Sq. m.)

EVAPORATOR BLOWER

1 24

3/8-2-16

3/8-2-16

3/8-2-16

11.55 (1.1)

16 (1.5)

16 (1.5)

Type

Centrifugal

Size (inch)

10 x 8

Drive type

Motor HP (Standard)

1000 (472)

1500 (708)

1650 (779)

0.5

0.75

0.75

Type

Inner Grooved Tubes and Enhanced Fins

Tube dia. - Rows - Fins per inch

3/8-3-14

Total face area, Sq. ft. (Sq. m.)


HIGH PRESSURE
SWITCH

5.4 (0.5)

3/8-3-14

3/8-3-14

6 (0.56)

6 (0.56)

Open

470 10 PSIG

Close

360 15 PSIG

LOW PRESSURE
SWITCH

Open

25 5 PSIG

Close

50 5 PSIG

RETURN AIR FILTERS

Quantity
Size (inch)

SHIPPING WEIGHT

10 x 10

Direct Drive

Nominal CFM (L/S)

EVAPORATOR COIL

10 x 10

Kgs.

16 x 25

16.5 x 18-3/8

16.5 x 18-3/8

213

328

328

NOTE: Direct drive motors have single speed connection only. Factory set at medium speed.

PHYSICAL DATA
MODEL NUMBER

PCY075 PCY090 PCY100 PCY120 PCY150 PCY180 PCY210 PCY240 PCY300 PCY360

NOMINAL CAPACITY, TONS (kW)

6.1(21.5)

7.3(25.8)

8.5(30)

10(35.4)

Quantity

Oil (oz)

60

42 x 2

42 x 2

66 x 2

60 x 2

COMPRESSOR

CONDENSER FAN

R-407c

Type/Drive

Propeller/Direct

Nominal CFM (L/S)

1 26

2 26

6600 (3117)

6000 (2834)

Motor HP RPM

11000 (5190)

3/8-2-16
16 (1.5)

20 (1.86)

12 x 12

Motor HP - Std. / Alt

1.5/2

30 (2.78)

2/3

2/3

3/5

5/7.5

56/184T

38 (3.53)

48 (4)

18 x 18

20 x 18

5/7.5

184T/213T

7.5

7.5/10

213T/215T

9600(4535)

10/15
215T/254T
610-990

Inner Grooved Tubes and Enhanced Fins


3/8-3-14
9 (0.84)

10 (0.93)

3/8-4-14
12.5 (1.16) 12.5 (1.16)

3/8-3-14
16 (1.5)

470 10 PSIG

Close

360 15 PSIG

LOW PRESSURE
SWITCH

Open

25 5 PSIG

Close

50 5 PSIG

RETURN AIR
FILTERS

Qty.

4
16-1/2 x 18-3/8

344

441

3/8-4-14

22 (2.04)

27 (2.5)

18 x 24

18 x 18 (1)
18 x 24 (3)
24 x 24 (2)

12 x 24 (2)
24 x 24 (6)

445

3/8-4-14

19.5 (1.81) 22 (2.04)

Open

SHIPPING WEIGHT Kgs.

2.7 1100

650-1270 600-1160 630-1210 650-1220 540-1075 600-1110 530-1020 570-1030 610-1020

Type

Size (inch)

2 32

16000 (7558)

2400(1134) 2700(1275) 3200(1511) 3800(1795) 4800(2267) 5800(2740) 6000(2834) 8000(3779)

56/56

Tube dia. - Rows - Fins per inch

HIGH PRESSURE
SWITCH

2 32

110 x 2

Belt
1900(897)

Total face area, Sq. ft. (Sq. m.)

2 30

15000 (7080)

15 x 15

Motor Frame (NEMA) Std./Alt.

EVAPORATOR COIL

Centrifugal

Nominal CFM (L/S)

Factory setting full turns open

2 30

1.5 1140

Drive type

Fan RPM range

3/8-3-16 3/8-2-14 3/8-3-14 3/8-2-14 3/8-3-14 3/8-3-14 3/8-3-14

Type
Size (inch)

Inner Grooved Tubes and Enhanced Fins

Tube dia. - Rows - Fins per inch


Total face area, Sq. ft. (Sq. m.)

2 26

3/4 1140

CONDENSER COIL Type

60 & 85 110 x 2 110 x 2 110 x 2

Refrigerant

Qty. Diameter (inch)

EVAPORATOR
BLOWER

12(42.3) 14.8(51.9) 17.3(60.6) 20.8(73.2) 24.8(87.2) 29.9(105.1)

450

800

840

975

1025

1076

27 (2.5)

1325

SELECTION PROCEDURE
1. Determine cooling and heating capacity requirements at design conditions
Data:
Condenser entering air temperature
Evaporator entering air temperature
Evaporator airflow
Required cooling capacity
Sensible heat capacity
Required heating capacity
External static pressure
Power supply (V-Ph-Hz)

: 950F
: 800F DB / 670F WB
: 6000 CFM
: 225,000 BTUH
: 148,000 BTUH
: 20 kW
: 1.23 INCH WG.
: 230-3-60

2. Unit selection based on required cooling capacity


Enter cooling capacity performance data at condenser entering air temp. at 950F and evaporator entering air temp. 800F DB,
670F WB, 6000 CFM airflow. The PCY240 unit will give 249,710 BTUH cooling capacity (gross) and 169,980 BTUH sensible
heat capacity (gross).

3. Electric heater selection


Heating capacity required =20 kW.
Enter electric heating table for PCY240 at 230-3-60 power supply.
20 kW heater at 230 volts satisfies the required heating.

4. Determine fan speed and power requirements at design conditions


Before entering the fan performance tables, calculate the summation of external static pressure for the required components as follows.
External static pressure
Electric heater

: 1.23 INCH WG.


: 0.17 INCH WG.
1.4 INCH WG.

Enter fan performance table for PCY240 model. For 6000 CFM and external static pressure of 1.4 INCH WG, it require 878 RPM
and 3.49 brake horse power (BHP) wherein the standard motor will meet job requirements.

5. Determine input power to motor


Use fan motor efficiency table.
BHP x 746 watts
Blower motor watts =
=
Motor efficiency

3.49 x 746
0.81

= 3214 watts.

6. Determine net capacities


Above capacities are gross and do not include blower motor heat gain.
Determine net capacities as follows:
Net cooling capacity
= Gross cooling capacity blower motor heat
= 249,710 (3214 WATTS x 3.413 BTUH/WATTS) = 238,741 BTUH
Net sensible capacity = 169,980 (3214 WATTS x 3.413 BTUH/WATTS) = 159,011 BTUH

7. Altitude correction factors for cooling capacity


ALTITUDE, FT.

2000

4000

6000

8000 10000

Total capacity

0.98

0.96

0.93

0.90

0.88

Sensible capacity

0.93

0.86

0.80

0.75

0.70

FACTOR

COOLING CAPACITIES
Model No.: PCY036
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

750/0.078
62
33.09
25.87
3.14
31.36
24.99
3.37
29.52
24.12
3.61
27.02
23.25
3.79
25.06
22.37
4.03

67
36.01
21.85
3.17
34.08
21.06
3.51
32.07
20.19
3.67
29.37
19.31
3.82
27.29
18.44
4.16

72
39.15
18.18
3.19
37.00
17.31
3.54
34.77
16.44
3.75
31.78
15.56
3.84
29.43
14.69
4.26

EVAPORATOR AIRFLOW, CFM/DR


875/0.087
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
34.16
37.13
40.22
27.88
23.33
19.06
3.15
3.18
3.19
32.32
35.09
37.92
27.01
22.46
18.18
3.49
3.52
3.55
30.36
32.99
35.58
26.13
21.58
17.31
3.67
3.76
3.89
27.78
30.14
32.47
25.26
20.71
16.44
3.80
3.83
3.85
25.73
27.95
30.00
24.39
19.84
15.56
4.08
4.17
4.25

1000/0.096
62
35.06
29.89
3.16
33.12
29.01
3.50
31.10
28.14
3.74
28.40
27.27
3.80
26.30
25.26
4.20

67
38.06
24.74
3.18
35.92
23.86
3.54
33.70
22.99
3.86
30.77
22.12
3.84
28.45
21.24
4.28

72
41.01
19.84
3.20
38.65
18.96
3.56
36.19
18.09
3.95
32.98
17.21
3.86
30.40
16.34
4.29

Model No.: PCY048


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1350/0.1
62
48.25
41.17
4.74
46.05
40.20
4.82
43.52
39.05
5.15
40.75
37.81
5.43
37.63
36.40
5.61

67
52.60
34.19
4.76
50.19
33.22
4.99
47.48
32.16
5.25
44.44
30.92
5.54
41.02
29.60
5.73

72
57.33
27.74
4.79
54.57
26.77
5.02
51.49
25.62
5.31
47.94
24.39
5.73
43.97
22.97
5.85

EVAPORATOR AIRFLOW, CFM/DR


1500/0.111
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
49.26
53.70
58.34
43.56
35.96
28.80
4.75
4.83
5.08
47.00
51.21
55.51
42.59
34.99
27.74
4.92
5.09
5.16
44.38
48.36
52.20
41.44
33.84
26.59
5.24
5.36
5.42
41.52
45.16
48.50
40.20
32.60
25.36
5.54
5.64
5.84
38.31
41.61
44.38
36.40
31.27
23.94
5.77
5.87
5.97

1650/0.119
62
50.19
45.94
4.85
47.83
44.88
4.97
45.15
43.74
5.33
42.19
40.11
5.64
38.93
37.02
5.84

67
54.63
37.64
4.98
52.02
36.58
5.17
49.09
35.52
5.45
45.83
34.28
5.73
42.12
32.87
5.96

72
59.24
29.86
5.15
56.20
28.72
5.25
52.82
27.57
5.53
49.00
26.32
5.94
44.66
24.82
6.06

Model No.: PCY060


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1450/0.1
62
56.43
47.21
5.28
53.44
45.76
5.57
50.33
44.32
5.92
47.17
42.87
6.33
43.82
41.33
6.58

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
61.25
39.53
5.31
58.10
38.18
5.62
54.78
36.74
5.97
51.33
35.29
6.38
47.62
33.85
6.78

72
66.71
32.40
5.36
63.29
31.05
5.66
59.59
29.60
6.01
55.60
28.16
6.42
51.27
26.63
6.87

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


1650/0.119
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
57.93
62.91
68.38
50.45
41.88
33.85
5.29
5.32
5.37
54.85
59.59
64.76
49.01
40.43
32.49
5.58
5.63
5.67
51.63
56.20
60.86
47.57
39.08
31.05
5.93
5.99
6.02
48.36
52.55
56.66
46.12
37.64
29.52
6.39
6.49
6.57
44.83
48.56
51.99
43.50
36.10
27.89
6.68
6.85
6.98
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

1875/0.132
62
59.43
54.06
5.30
56.22
52.62
5.59
52.87
51.08
5.95
49.45
48.01
6.48
45.80
44.40
6.79

72
69.97
35.38
5.38
66.15
34.03
5.68
62.02
32.59
6.03
57.53
31.05
6.65
52.67
29.34
7.11

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input at 0.15 ESP for PCY036/PCY048 & 0.2 ESP for PCY060.

10

67
64.46
44.40
5.34
61.05
43.05
5.64
57.49
41.61
6.00
53.63
40.17
6.58
49.42
38.45
6.94

COOLING CAPACITIES
Model No.: PCY075
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1500/0.09
62
67.83
55.11
6.18
64.27
53.32
6.74
60.72
51.54
7.26
57.16
49.85
7.93
53.53
48.16
8.67

67
73.66
46.65
6.26
69.69
44.86
6.83
66.21
43.26
7.36
62.36
41.57
8.05
58.21
39.79
8.79

72
80.35
38.85
6.36
76.40
37.15
6.95
72.21
35.55
7.50
67.78
33.76
8.23
62.91
31.88
8.86

EVAPORATOR AIRFLOW, CFM/DR


1900/0.11
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
71.31
77.13
84.24
62.07
51.44
41.86
6.22
6.31
6.44
67.50
73.50
79.85
60.29
49.94
40.25
6.79
6.90
7.00
63.77
69.41
75.23
58.50
48.25
38.47
7.44
7.55
7.63
59.88
65.15
70.16
56.72
46.46
36.58
8.19
8.29
8.35
55.92
60.59
64.70
55.02
44.68
34.61
9.03
9.12
9.15

2400/0.131
62
74.55
70.35
6.27
70.52
68.47
6.84
66.50
65.27
7.49
62.38
61.23
8.24
58.05
56.99
9.07

67
80.92
57.56
6.37
76.62
55.77
6.95
72.22
54.08
7.60
67.54
52.29
8.32
62.45
50.32
9.14

72
87.74
45.62
6.51
82.79
43.82
7.05
77.54
41.94
7.65
71.91
39.98
8.42
61.27
37.91
9.23

Model No.: PCY090


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

1900/0.09
62
81.01
67.17
7.83
76.82
65.08
8.62
72.48
62.99
9.18
67.82
60.80
9.95
62.93
58.52
10.73

67
88.22
56.53
7.88
83.82
54.53
8.69
79.11
52.54
9.34
74.16
50.45
10.16
68.89
48.26
10.87

72
96.45
46.74
7.95
91.61
44.84
8.77
86.38
42.75
9.40
80.91
40.66
10.34
75.05
38.48
10.99

EVAPORATOR AIRFLOW, CFM/DR


2400/0.108
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
85.18
92.78
100.93
75.81
62.80
50.54
7.85
7.91
8.00
80.68
87.91
95.59
73.72
60.80
48.55
8.65
8.73
8.79
76.00
82.86
89.87
71.63
58.71
46.46
9.58
9.66
9.71
71.01
77.40
83.95
69.35
56.53
44.37
10.45
10.51
10.55
65.73
71.74
77.45
64.13
54.25
42.09
11.04
11.35
11.59

3000/0.128
62
88.88
85.60
7.88
84.15
83.60
8.68
79.17
77.24
9.62
73.81
72.01
10.48
68.31
66.69
11.35

67
96.75
69.92
7.95
91.54
67.83
8.77
86.09
65.74
9.68
80.25
63.46
10.53
74.17
61.18
11.51

72
104.70
54.91
8.04
98.90
52.82
8.82
92.73
50.73
9.72
86.21
48.45
10.68
79.30
46.17
11.85

Model No.: PCY100


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2200/0.09
62
94.85
78.28
8.96
90.27
76.00
9.59
85.22
73.63
9.72
79.52
70.87
10.33
73.28
68.02
10.93

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
103.33
65.93
9.03
98.49
63.75
9.89
93.00
61.47
10.11
86.80
58.81
10.58
79.93
55.96
11.23

72
112.91
54.53
9.07
107.37
52.25
10.03
101.19
49.88
10.51
94.20
47.22
10.76
86.20
44.27
11.52

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


2700/0.109
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
99.05
107.86
117.39
87.02
72.20
58.33
8.99
9.06
9.09
94.21
102.59
111.37
84.74
70.02
56.05
9.82
10.00
10.08
88.69
96.65
104.46
82.18
67.55
53.58
10.41
10.70
10.92
82.71
90.03
96.77
79.61
64.89
50.83
10.56
10.80
11.13
76.06
82.64
88.07
73.91
62.04
47.69
11.44
11.65
11.94
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

3400/0.13
62
103.59
98.71
9.02
98.35
96.43
9.96
92.53
89.97
11.00
86.00
83.60
11.11
78.90
76.67
11.58

72
121.71
63.37
9.09
114.98
60.99
10.35
107.39
58.33
11.12
98.97
55.48
11.58
89.29
52.25
12.22

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input based on nominal CFM & 0.25 ESP.

11

67
112.53
80.56
9.07
106.88
78.38
10.17
100.38
75.81
11.08
93.05
72.96
11.33
84.99
69.92
11.91

COOLING CAPACITIES
Model No.: PCY120
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

2600/0.092
62
112.86
95.09
10.18
106.71
91.98
11.24
100.34
88.79
11.91
95.56
87.22
12.64
88.32
83.76
13.50

67
122.35
80.04
10.35
115.92
77.12
11.44
108.97
74.01
12.18
103.65
72.15
12.80
95.60
68.70
13.83

72
133.10
66.22
10.54
125.88
63.20
11.65
117.93
60.00
12.55
111.58
57.76
12.89
102.11
54.11
14.23

EVAPORATOR AIRFLOW, CFM/DR


3200/0.105
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
117.98
127.99
138.55
105.90
87.94
70.92
10.26
10.45
10.66
111.43
120.83
130.42
102.70
84.74
67.72
11.33
11.53
11.74
104.63
113.29
121.79
99.50
81.54
64.51
12.60
12.81
12.96
99.41
107.37
114.53
98.06
79.83
62.18
12.71
12.85
12.92
91.68
98.51
104.04
91.83
76.18
58.34
13.99
14.19
14.60

4000/0.124
62
123.24
119.82
10.35
116.34
116.72
11.43
108.96
109.10
12.69
103.14
103.25
12.78
94.79
94.90
14.23

67
133.32
97.72
10.54
125.65
94.61
11.64
117.36
91.23
12.89
110.76
89.52
12.89
101.16
85.78
14.68

72
143.50
76.84
10.77
134.45
73.55
11.82
124.77
70.07
12.97
116.45
67.65
12.94
105.11
63.71
15.17

Model No.: PCY150


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3000/0.098
62
135.46
112.63
11.78
127.71
108.77
12.86
119.68
105.00
13.76
111.13
101.04
14.88
102.03
96.98
16.25

67
146.35
94.13
12.01
138.24
90.67
13.10
129.73
87.01
14.06
120.54
83.15
15.36
110.97
79.29
16.51

72
159.14
77.25
12.27
150.55
73.90
13.35
141.28
70.34
14.36
131.48
66.68
15.62
121.18
62.92
17.07

EVAPORATOR AIRFLOW, CFM/DR


3800/0.119
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
141.60
153.20
166.55
127.06
104.60
83.87
11.89
12.14
12.43
133.47
144.43
157.17
123.30
101.04
80.41
12.98
13.23
13.47
124.83
135.33
146.96
119.44
97.38
76.75
14.22
14.45
14.62
115.69
125.55
136.90
112.63
93.52
73.19
15.60
15.82
15.96
106.04
115.27
125.84
103.27
89.45
69.32
17.13
17.35
17.55

4800/0.143
62
147.41
144.34
12.01
138.86
135.19
13.09
129.67
126.25
14.32
120.03
116.90
15.70
109.76
106.84
17.21

67
159.45
117.00
12.28
150.29
113.44
13.34
140.50
109.68
14.54
129.86
105.72
15.89
119.42
101.85
17.42

72
173.57
91.89
12.58
163.61
88.33
13.55
153.03
84.78
14.67
142.02
81.02
16.00
130.39
77.15
17.62

Model No.: PCY180


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

3800/0.135
62
166.38
138.57
15.82
157.49
134.11
17.17
147.80
129.36
18.07
137.64
124.52
19.70
126.85
119.48
20.96

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
178.96
115.89
16.07
169.49
111.63
17.45
159.22
107.17
18.44
148.63
102.62
20.00
137.73
98.06
21.27

72
194.26
95.45
16.34
183.74
91.18
17.75
172.91
86.92
18.75
161.76
82.56
20.31
150.45
78.39
21.59

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


4800/0.177
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
173.86
187.35
203.33
155.62
128.30
103.20
15.96
16.21
16.51
164.24
176.97
191.83
151.07
123.94
98.84
17.32
17.61
17.91
154.01
165.99
180.32
146.41
119.38
94.67
18.87
19.18
19.51
143.18
154.83
168.42
141.47
114.83
90.31
20.62
20.95
21.29
131.95
143.45
156.51
130.72
110.37
86.05
21.49
21.81
22.16
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

6000/0.22
62
180.73
175.29
16.07
170.46
170.73
17.43
159.68
158.14
19.00
148.14
146.71
20.76
136.61
135.27
22.69

72
211.51
112.21
16.66
199.36
107.85
18.07
187.22
103.68
19.66
174.57
99.23
21.44
162.17
94.96
23.40

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input based on nominal CFM & 0.35 ESP.

12

67
195.03
142.54
16.35
183.81
138.08
17.75
172.33
133.53
19.32
160.36
128.88
21.09
148.40
124.33
23.05

COOLING CAPACITIES
Model No.: PCY210
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

4800/0.099
62
197.63
170.15
17.63
185.70
164.34
19.26
173.36
158.53
19.95
160.62
152.62
21.04
147.27
146.61
22.22

67
212.54
141.08
18.00
199.87
135.57
19.67
186.98
130.14
20.34
173.50
124.61
21.42
159.00
118.70
23.04

72
229.52
114.34
18.39
216.51
109.20
20.10
202.91
104.07
20.77
188.31
98.65
21.73
172.30
92.83
23.68

EVAPORATOR AIRFLOW, CFM/DR


5800/0.117
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
204.35
219.85
237.21
187.99
153.98
122.28
17.78
18.16
18.56
191.89
206.72
223.91
182.27
148.55
117.34
19.41
19.84
20.29
178.92
193.11
209.64
176.45
143.02
112.21
20.88
21.32
21.75
165.47
178.75
194.17
162.50
137.30
106.69
21.17
21.54
21.81
151.55
163.67
177.00
148.84
131.49
100.78
23.30
23.55
24.28

7000/0.136
62
210.64
208.82
17.91
197.65
194.09
19.56
184.08
180.72
21.45
169.93
166.86
21.30
155.47
152.62
24.09

67
226.59
168.80
18.32
212.79
163.37
20.00
198.71
157.85
21.89
183.74
152.13
21.64
167.88
146.32
24.62

72
244.26
131.59
18.72
230.54
126.75
20.46
215.96
121.61
22.32
199.62
115.99
21.87
181.22
109.89
25.50

Model No.: PCY240


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

5000/0.084
62
237.86
194.85
21.56
223.27
187.61
23.47
208.04
180.15
24.92
191.70
172.50
25.62
174.03
164.45
27.61

67
255.77
163.03
21.92
240.82
156.39
23.84
224.57
149.34
25.31
207.21
142.09
25.99
188.09
134.13
27.99

72
277.23
134.24
22.33
261.29
127.78
24.28
244.03
121.14
25.76
225.02
113.90
26.47
204.27
106.24
28.51

EVAPORATOR AIRFLOW, CFM/DR


6000/0.095
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
246.47
265.26
287.86
213.48
176.53
142.89
21.72
22.11
22.52
231.37
249.71
271.08
206.33
169.98
136.55
23.61
24.03
24.49
215.20
232.57
252.46
198.88
162.93
129.60
25.81
26.25
26.77
197.97
214.10
232.28
191.13
155.48
122.25
25.74
26.16
26.69
179.42
193.80
210.51
174.71
147.42
114.60
28.28
28.72
29.32

7500/0.112
62
256.74
240.78
21.91
240.83
233.73
23.80
223.61
217.71
26.01
205.07
199.59
25.90
185.52
180.56
28.43

67
276.86
196.37
22.31
260.06
189.72
24.25
241.60
182.37
26.47
221.81
174.71
26.37
200.40
166.66
28.93

72
300.50
155.48
22.74
282.48
149.04
24.74
262.48
141.99
27.05
240.86
134.54
26.97
217.60
126.68
29.62

Model No.: PCY300


CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

7000/0.099
62
288.91
251.24
24.61
270.81
242.96
26.55
252.07
234.57
28.70
236.84
232.26
29.26
217.42
210.43
31.62

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
309.95
206.50
25.92
290.99
198.74
27.88
272.01
191.18
30.02
257.56
188.92
30.56
238.58
181.46
33.10

72
334.38
165.39
27.53
315.53
158.45
29.39
296.67
151.72
31.55
283.09
149.20
32.22
264.22
142.59
35.22

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


8000/0.117
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
295.47
317.12
341.97
269.99
219.97
173.78
25.55
27.16
27.67
276.63
297.64
322.97
261.49
212.30
167.05
27.55
29.15
29.46
257.42
278.17
303.98
246.58
204.64
160.42
29.72
31.35
31.60
242.10
263.69
290.43
234.28
202.98
158.36
30.30
31.93
33.03
222.55
244.23
271.10
215.33
195.52
151.75
32.73
34.62
35.46
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

9600/0.135
62
304.03
291.22
26.81
284.53
272.58
28.85
264.59
253.42
31.10
249.01
240.99
31.67
228.72
221.29
34.21

72
352.06
187.03
29.79
333.20
180.61
31.58
313.91
173.98
33.87
300.32
172.52
34.74
280.70
166.13
38.31

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input based on nominal CFM & 0.4 ESP.

13

67
326.31
240.89
28.18
306.47
233.33
30.16
286.62
225.87
32.40
271.99
224.91
33.02
252.25
217.67
35.89

COOLING CAPACITIES
Model No.: PCY360
CONDENSER
ENTERING AIR
TEMP. (0F)
85

95

105

115

125

TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW
TC
SC
kW

8200/0.054
62
346.89
274.67
32.03
324.93
265.07
34.61
302.59
255.66
37.48
301.98
253.18
40.61
276.22
235.07
44.00

TC Total Capacity (1000 Btuh) Gross


SC Sensible Heat Capacity (1000 Btuh) Gross

67
371.05
226.39
32.89
348.47
217.64
35.48
325.13
208.81
38.33
324.50
205.32
41.41
294.85
195.14
44.70

72
401.33
182.76
33.85
377.76
174.59
36.40
352.36
165.95
39.18
349.72
160.89
42.13
311.08
149.04
45.26

kW Total unit power input


DR Wet Bulb depression ratio

EVAPORATOR AIRFLOW, CFM/DR


9600/0.066
EVAPORATOR ENTERING AIR, WBE (0F)
62
67
72
356.44
381.95
413.80
298.15
243.40
193.79
32.33
33.22
34.25
333.78
358.53
389.25
288.64
234.75
185.61
34.90
35.80
36.74
310.69
334.26
362.09
279.33
225.92
176.68
37.75
38.61
39.45
309.71
332.54
357.66
263.55
222.64
171.55
40.86
41.65
42.35
282.37
300.17
314.30
240.35
211.88
158.63
44.20
44.88
45.37
DBE Dry Bulb Temp. (0F) of Air Entering Coil
WBE Wet Bulb Temp. (0F) of Air Entering Coil

11250/0.078
62
366.13
325.42
32.63
342.63
306.31
35.18
318.13
284.45
38.01
317.08
269.81
41.09
288.36
245.44
44.39

72
426.34
206.62
34.64
400.57
198.26
37.06
371.78
189.13
39.70
365.59
183.98
42.53
316.95
169.89
45.46

DBL Dry Bulb Temp. (0F) of Air Leaving Coil


WBL Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES: 1. Direct interpolation is permissible Do not extrapolate.


2. Capacities above are based on DBE = 800F. For higher or lower DBE, add following Correction Factor to Sensible Capacity = 1.08 x CFM (1 DR) (DBE 80).
3. To calculate leaving conditions, follow this procedure: DBL = DBE (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL [DR (DBE WBE)].
4. Total unit power input based on nominal CFM & 0.45 ESP.

14

67
392.73
263.08
33.56
368.34
254.24
36.10
342.94
245.39
38.88
340.22
242.41
41.87
303.14
214.23
44.92

ELECTRICAL DATA
MODEL No.: PCY036
POWER
SUPPLY
(V-Ph-Hz)

VOLTAGE
RANGE
MIN.

230-1-60

230-3-60

380-3-60
(4 WIRE)

460-3-60

207

207

342

414

MAX.

253

253

418

506

FM

FLA

1.6

1.6

1.6

0.8

MODEL No.: PCY048


COMPRESSOR

BLOWER
MOTOR

ELECTRIC
HEATER

RLA

HP

kW

21.4

13.6

6.9

6.4

LRA

112

93

46

48

0.5

0.5

0.5

0.5

FLA

1.8

1.8

1.8

0.9

MCA MOCP

FLA

VOLTAGE
RANGE
MIN.

230-3-60

380-3-60
(4 WIRE)

460-3-60

207

342

414

MAX.

253

418

506

1.3

10.7

10

64

63

0.75

0.75

4.2

2.8

- Fan Motor

HP

- Horse Power

FLA

- Full Load Amps

RLA

- Rated Load Amps

LRA

- Locked Rotor Amps

MCA MOCP

FLA

38.2

60

21.7

38.2

60

7.5

32.6

43

50

7.5

32.6

46

60

10*

43.5

56.6

60

10*

43.5

59.6

70

20.4

35

29.2

45

12.6

20.4

35

12.6

29.2

45

7.5

18.8

25.8

35

7.5

18.8

29.2

45

10*

25.1

33.6

35

10*

25.1

36.7

45

230-1-60

230-3-60

207

207

253

253

3.6

3.6

24.3

17.1

137

114

0.75

0.75

4.2

4.2

12

20

19.4

30

7.6

12

20

7.6

19.4

30

7.5

11.4

16.5

20

7.5

11.4

19.5

30

10*

15.2

21.2

25

10*

15.2

24.3

30

380-3-60
(4 WIRE)

342

418

3.6

9.3

54

0.75

4.2

9.7

15

14

20

6.3

9.7

15

6.3

14

20

7.5

9.4

12.9

15

10*

12.6

16.8

20

460-3-60

MCA MOCP

FLA

33.7

50

12.6

33.7

50

7.5

18.8

33.7

50

10*

25.1

36.6

50

21.2

30

7.6

21.2

30

7.5

11.4

21.2

30

10*

15.2

24.3

30

16.6

30

6.3

16.6

30

7.5

9.4

16.6

30

10*

12.6

19.2

30

LEGEND:
FM

kW

FLA

50

kW

3.6

HP

LRA

50

HP

4.2

RLA

30.1

RLA

0.75

FLA

30.1

FLA

128

ELECTRIC
HEATER

ELECTRIC
HEATER

20.7

BLOWER
MOTOR

21.7

BLOWER
MOTOR

3.6

COMPRESSOR

COMPRESSOR

FLA

MAX.

FM

FM

LRA

VOLTAGE
RANGE
MIN.

MODEL No.: PCY060


POWER
SUPPLY
(V-Ph-Hz)

POWER
SUPPLY
(V-Ph-Hz)

MCA - Minimum Circuit Amps


MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

15

414

506

1.3

7.9

58

0.75

2.8

7.5

9.4

15.3

20

10*

12.6

19.2

25

ELECTRICAL DATA
MODELS: PCY075 & PCY090
MODEL NUMBER

DESCRIPTION

PCY075

VOLTAGE
RANGE

POWER SUPPLY
(V-Ph-Hz)

Min.

Max.

FM

COMPRESSOR

FLA

RLA LRA HP FLA Nom. kW

PCY090

ELECTRIC
HEATER

BM

1.5 4 . 3

MOCP

30.2

50

5/6

RLA LRA HP FLA

5/6

12.6/15.1 30.2/30.2

50/50

7.5/10

18.8/25.1 30.2/36.8

50/50

(STD)

207

253

2.6

25.1/30.1 36.8/43.1

50/50

5.7

7.5/10

18.8/25.1 31.6/38.5

50/50

3.3

25.1/30.1 38.5/44.8
37.7

54.2

50/50
60

414

506

1.9

10

FLA

- Full Load Amps

RLA

- Rated Load Amps

LRA

- Locked Rotor Amps

60/80

25*/30*

62.8/75.3 89.0/104.7 100/110

25.8

35

7.6/9.1

25.8/25.8

35/35

11.4/15.2 17.6/22.3

30/30

7.5/10

15.2/18.2 22.3/26.1

3.3

30/30

15*

22.8

31.8

35

18.3

30

5/6

7.6/9.1

18.3/18.3

30/30

11.4/15.2 18.4/23.1

30/30

7.5/10

15.2/18.2 23.1/27.0

9.3

54

4.9

30/30

7.5/10

11.4/15.2 25.8/25.8

35/35

10*/12*

15.2/18.2 25.8/26.9

35/35

15*/20*

22.8/30.4 32.6/42.1

35/45

25*/30*

38/45.6

51.7/61.2

27.4

60/70
40

5/6

7.6/9.1

27.4/27.4

40/40

7.5/10

11.4/15.2 27.4/27.4

40/40

10*/12*

15.2/18.2 27.4/28.9

40/40

15*/20*

22.8/30.4 34.6/44.1

40/50

15*

22.8

32.7

35

25*/30*

38/45.6

53.7/63.2

16.6

30

19.3

25

5/6

6.3/7.5

16.6/16.6

30/30

5/6

6.3/7.5

19.3/19.3

25/25

7.5/10

9.4/12.6

16.6/18.5

30/30

12.6/15.1 18.5/21.6

(STD)

30/30

60/70

7.5/10

9.4/12.6

19.3/19.5

25/25

10*/12*

12.6/15.1 19.5/22.6

25/25

15*/20*

18.8/25.1 27.3/35.2

30/40

25*/30*

31.4/37.7 43.0/50.9

45/60

15*

18.8

26.3

30

17.4

30

21.0

30

5/6

6.3/7.5

17.4/17.4

30/30

5/6

6.3/7.5

21.0/21.0

30/30

7.5/10

9.4/12.6

17.4/19.5

30/30

6.4

48

3
(ALT.)

12.6/15.1 19.5/22.6
18.8

LEGEND:

- Horse Power

37.7/50.2 57.6/73.3

5/6

15*

HP

60/60

15*/20*

30

10*/12*

- Fan Motor

60/60

30/30

(ALT.)

FM

18.8/25.1 43.2/43.2
25.1/30.1 43.2/48.2

17.6

10*/12*

7.5/10
10*/12*

17.6/17.6

75

60
60/60

10*/12*

460-3-60

43.2

7.6/9.1

(ALT.)

1.5 2 . 2

12.6/15.1 43.2/43.2

(ALT.)

(STD)

90/110

5/6

10*/12*

8.4

(STD)

10.7 70

62.8/75.3 85.7/101.4

(STD)

1.6

60/80

25*/30*
5/6

15*

418

37.7/50.2 54.3/70.0

50

10*/12*

342

50/50

15*/20*

31.6

(ALT.)

1.5 2 . 6

50/50

50/50

50
50/50

18.8/25.1 40.5/40.5

12.6/15.1 31.6/31.6

40.5

25.1/30.1 40.5/44.8

60

5/6

12.6/15.1 40.5/40.5

7.5/10

52.5

14.3 93

MOCP

10*/12*

37.7

18.6 156

MCA

FLA

15*

(ALT.)

380-3-60 (4 WIRE)

5.7

(STD)

10*/12*
230-3-60

ELECTRIC
HEATER

BM

MCA

FLA

COMPRESSOR
(each)

MCA - Minimum Circuit Amps


MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

16

27.3

30/30
30

4.7

7.5/10

9.4/12.6

21.0/21.6

30/30

10*/12*

12.6/15.1 21.6/24.7

30/30

15*/20*

18.8/25.1 29.4/37.3

35/40

25*/30*

31.4/37.7 45.1/53.0

50/60

ELECTRICAL DATA
MODELS: PCY100 & PCY120
MODEL NUMBER

DESCRIPTION

PCY100

VOLTAGE
RANGE

POWER SUPPLY
(V-Ph-Hz)

Min.

Max.

FM

COMPRESSOR
(each)

FLA

RLA LRA HP FLA Nom. kW

ELECTRIC
HEATER

BM

5.7

(STD)

230-3-60

207

253

2.6

17.1 114

8.4

(ALT.)

3.3

(STD)

380-3-60 (4 WIRE)

342

418

1.6

9.3

54

4.9

(ALT.)

(STD)

460-3-60

414

506

1.9

7.9

58

3
(ALT.)

4.7

- Fan Motor

HP

- Horse Power

FLA

- Full Load Amps

RLA

- Rated Load Amps

LRA

- Locked Rotor Amps

MOCP

FLA
46.8

60

5/6

12.6/15.1

46.8/46.8

60/60

7.5/10

18.8/25.1

46.8/46.8

60/60

10*/12*

25.1/30.1

46.8/46.8

60/60

15*/20*

37.7/50.2

54.2/69.9

60/80

25*/30*

62.8/75.3 85.7/101.4

90/110

49.5

70

5/6

12.6/15.1

49.5/49.5

70/70

7.5/10

18.8/25.1

49.5/49.5

70/70

10*/12*

25.1/30.1

49.5/49.5

70/70

15*/20*

37.7/50.2

57.6/73.3

70/80

25*/30*

62.8/75.3 89.0/104.7 100/110


-

25.8

35

5/6

7.6/9.1

25.8/25.8

35/35

7.5/10

11.4/15.2

25.8/25.8

35/35

10*/12*

15.2/18.2

25.8/26.9

35/35

15*/20*

22.8/30.4

32.6/42.1

35/45

25*/30*

38/45.6

51.7/61.2

60/70

27.4

40

5/6

7.6/9.1

27.4/27.4

40/40

7.5/10

11.4/15.2

27.4/27.4

40/40

10*/12*

15.2/18.2

27.4/28.9

40/40

15*/20*

22.8/30.4

34.6/44.1

40/50

25*/30*

38/45.6

53.7/63.2

60/70

22.7

30

5/6

6.3/7.5

22.7/22.7

30/30

7.5/10

9.4/12.6

22.7/22.7

30/30

10*/12*

12.6/15.1

22.7/22.7

30/30

15*/20*

18.8/25.1

27.3/35.2

30/40

25*/30*

31.4/37.7

43.0/50.9

50/60

24.4

30

5/6

6.3/7.5

24.4/24.4

30/30

7.5/10

9.4/12.6

24.4/24.4

30/30

10*/12*

12.6/15.1

24.4/24.7

30/30

15*/20*

18.8/25.1

29.5/37.3

35/40

25*/30*

31.4/37.7

45.1/53.0

50/60

MCA - Minimum Circuit Amps


MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

17

BM

ELECTRIC
HEATER

RLA LRA HP FLA Nom. kW

LEGEND:
FM

MCA

PCY120
COMPRESSOR
(each)

20.7 128

63

3
(STD)

57.6

80

FLA
-

5/6

12.6/15.1 57.6/57.6

80/80

7.5/10

18.8/25.1 57.6/57.6

80/80

10*/12*

25.1/30.1 57.6/57.6

80/80

15*/20*

37.7/50.2 57.6/73.3

80/80

25*/30*

62.8/75.3 89.0/104.7 100/110

30.6

40

5/6

7.6/9.1

30.6/30.6

40/40

7.5/10

11.4/15.2 30.6/30.6

40/40

10*/12*

15.2/18.2 30.6/30.6

40/40

15*/20*

22.8/30.4 34.6/44.1

40/50

4.9

(STD)

10

MOCP

8.4

(STD)

10.7 64

MCA

25*/30*

38/45.6

53.7/63.2

60/70

29.1

40

5/6

6.3/7.5

29.1/29.1

40/40

7.5/10

9.4/12.6

29.1/29.1

40/40

10*/12*

12.6/15.1 29.1/29.1

40/40

15*/20*

18.8/25.1 29.5/37.3

40/40

25*/30*

31.4/37.7 45.1/53.0

50/60

4.7

ELECTRICAL DATA
MODELS: PCY150 & PCY180
MODEL NUMBER

DESCRIPTION

PCY150

VOLTAGE
RANGE

POWER SUPPLY
(V-Ph-Hz)

Min.

FM
(each)

Max.

FLA

COMPRESSOR
(each)

BM

ELECTRIC
HEATER

RLA LRA HP FLA Nom. kW

5/6
3

8.4

230-3-60

207

253

2.6

18.6 156

14.7

4.9

(STD)

380-3-60 (4 WIRE)

342

418

1.6

10.7 70

8.5

(ALT.)

4.7

(STD)

460-3-60

414

506

1.9

10

75

5
(ALT.)

7.8

- Fan Motor

HP

- Horse Power

FLA

- Full Load Amps

RLA

- Rated Load Amps

LRA

- Locked Rotor Amps

70

18.8/25.1 52.8/52.8

70/70
70/70

15*/20*

37.7/50.2 57.6/73.3

70/80

25*/30*

62.8/75.3 89.0/104.0 100/110


59.1

80

12.6/15.1 59.1/59.1

80/80

7.5/10

18.8/25.1 59.1/59.1

80/80

10*/12*

25.1/30.1 59.1/59.1

80/80

15*/20*

37.7/50.2 65.5/81.2

80/90

25*/30*

62.8/75.3 96.9/112.6 100/125

30.6

40

5/6

7.6/9.1

30.6/30.6

40/40

7.5/10

11.4/15.2 30.6/30.6

40/40

10*/12*

15.2/18.2 30.6/30.6

40/40

15*/20*

22.8/30.4 34.6/44.1

40/50

25*/30*

38/45.6

53.7/63.2

60/70

34.2

45

5/6

7.6/9.1

34.2/34.2

45/45

7.5/10

11.4/15.2 34.2/34.2

45/45

10*/12*

15.2/18.2 34.2/34.2

45/45

15*/20*

22.8/30.4 39.1/48.6

45/50

25*/30*

38/45.6

58.1/67.7

60/70

29.1

40

5/6

6.3/7.5

29.1/29.1

40/40

7.5/10

9.4/12.6

29.1/29.1

40/40

10*/12*

12.6/15.1 29.1/29.1

40/40

15*/20*

18.8/25.1 29.5/37.3

40/40

25*/30*

31.4/37.7 45.1/53.0

50/60

32.2

40

5/6

6.3/7.5

32.2/32.2

40/40

7.5/10

9.4/12.6

32.2/32.2

40/40

10*/12*

12.6/15.1 32.2/32.2

40/40

15*/20*

18.8/25.1 33.3/41.2

40/45

25*/30*

31.4/37.7 49.0/56.9

60/70

MCA - Minimum Circuit Amps


MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

18

ELECTRIC
HEATER

MCA

MOCP

83.9

110

FLA
-

70/70

25.1/30.1 52.8/52.8

BM

RLA LRA HP FLA Nom. kW

7.5/10

LEGEND:
FM

52.8

10*/12*

5/6
5

MOCP

12.6/15.1 52.8/52.8

(ALT.)

MCA

FLA

(STD)

PCY180
COMPRESSOR
(each)

10*/12*

25.1/30.1 83.9/83.9

110/110

15*/20*

37.7/50.2 83.9/83.9

110/110

25*/30*

62.8/75.3 95.5/111.2

110/125

13.6

(STD)

25 164
&
&
32.1 195

91.9

125

10*/12*

25.1/30.1 91.9/91.9

125/125

15*/20*

37.7/50.2 91.9/91.9

125/125

25*/30*

62.8/75.3 105.5/121.2 125/125

7.5 21.6
(ALT.)

42.4

60

10*/12*

15.2/18.2 42.4/42.4

60/60

15*/20*

22.8/30.4 42.4/48.5

60/60

8.4

(STD)

12.1 100
&
&
15 123

25*/30*

38/45.6

58.0/67.5

60/70

46

60

10*/12*

15.2/18.2 46.1/46.1

60/60

15*/20*

22.8/30.4 46.1/53.1

60/60

7.5 12.1
(ALT.)

25*/30*

38/45.6

62.7/72.2

70/80

41.2

60

10*/12*

12.6/15.1 41.2/41.2

60/60

15*/20*

18.8/25.1 41.2/41.2

60/60

25*/30*

31.4/37.7 47.9/55.7

60/60

6.9

(STD)

12.1 95
&
&
14.7 100

7.5
(ALT.)

45.1

60

10*/12*

12.6/15.1 45.1/45.1

60/60

15*/20*

18.8/25.1 45.1/45.1

60/60

25*/30*

31.4/37.7 52.8/60.6

60/70

10.8

ELECTRICAL DATA
MODELS: PCY210 & PCY240
MODEL NUMBER

DESCRIPTION

PCY210

VOLTAGE
RANGE

POWER SUPPLY
(V-Ph-Hz)

Min.

FM
(each)

Max.

FLA

COMPRESSOR
(each)

BM

PCY240

ELECTRIC
HEATER

RLA LRA HP FLA Nom. kW

MCA

MOCP

99.6

130

FLA

COMPRESSOR
(each)

BM

ELECTRIC
HEATER

RLA LRA HP FLA Nom. kW


-

207

253

5.2

25.1/30.1 99.6/99.6

130/130

15*/20*

37.7/50.2 99.6/99.6

130/130

25*/30*

62.8/75.3 99.6/111.2

130/130
41.4 239 7.5 21.6

33.6 225
-

107.6

140

10*/12*

25.1/30.1 107.6/107.6 140/140

15*/20*

37.7/50.2 107.6/107.6 140/140

25*/30*

62.8/75.3 107.6/121.2 140/140

418

56.2

25.1/30.1 125.1/125.1 170/170

15*/20*

37.7/50.2 125.1/125.1 170/170

25*/30*

62.8/75.3 125.1/125.1 170/170

35*/40* 87.9/100.4 136.9/152.7 170/170

80

10*/12*

15.2/18.2 56.2/56.2

80/80

15*/20*

22.8/30.4 56.2/56.2

80/80

25*/30*

38/45.6

58.0/67.5

80/80

59.9

80

21.2 145 7.5 12.1

18.6 140

506

2.9

10*/12*

15.2/18.2 59.9/59.9

80/80

15*/20*

22.8/30.4 59.9/59.9

80/80

25*/30*

38/45.6

62.7/72.2

80/80

51.6

70

10*/12*

12.6/15.1 51.6/51.6

70/70

15*/20*

18.8/25.1 51.6/51.6

70/70

25*/30*

31.4/37.7 51.6/55.7

70/70

15.2/18.2 65.8/65.8

90/90

15*/20*

22.8/30.4 65.8/65.8

90/90

25*/30*

35*/40*

18 125 7.5 10.8

17.3 114
-

7.5
(ALT.)

- Fan Motor

HP

- Horse Power

FLA

- Full Load Amps

RLA

- Rated Load Amps

LRA

- Locked Rotor Amps

55.5

70

10*/12*

12.6/15.1 55.5/55.5

70/70

15*/20*

18.8/25.1 55.5/55.5

70/70

25*/30*

31.4/37.7 55.5/60.6

70/70

10.8

LEGEND:
FM

90

38/45.6

65.8/72.2

90/90

53.2/60.8 81.7/91.2

90/100

57.1

80

6.9

(STD)

414

65.8

10*/12*

460-3-60

(STD)

7.5 12.1
(ALT.)

170

8.4

(STD)

342

10*/12*

380-3-60 (4 WIRE)

125.1

FLA

(STD)

7.5 21.6
(ALT.)

MOCP

13.6

(STD)

230-3-60

10*/12*

MCA

MCA - Minimum Circuit Amps


MOCP - Maximum Over Current Protection

* Combination of 2 heater modules

19

(STD)

10*/12*

12.6/15.1 57.1/57.1

80/80

15*/20*

18.8/25.1 57.1/57.1

80/80

25*/30*

31.4/37.7 57.1/60.6

80/80

35*/40*

43.9/50.2 68.5/76.3

80/80

ELECTRICAL DATA
MODELS: PCY300 & PCY360
MODEL NUMBER

DESCRIPTION

POWER
SUPPLY
(V-Ph-Hz)

PCY300

VOLTAGE
RANGE
Min.

FM
(each)

Max.

FLA

COMPRESSOR
(each)

BM

ELECTRIC
HEATER

RLA LRA HP FLA Nom. kW


-

7.5 21.6
(STD)

230-3-60

207

253

6.8

3.9

28

506

3.8

BM

- Blower Motor

FM

- Fan Motor (Condenser)

RLA

- Rated Load Amps

FLA

- Full Load Amps

LRA

- Locked Rotor Amps

MCA

- Minimum Circuit Amps

MOCP

162.6

220

FLA
-

15*/20*

37.7/50.2 141.2/141.2 190/190

25*/30*

62.8/75.3 141.2/141.2 190/190

25*/30*

62.8/75.3 162.6/162.6 220/220

35*/40*

87.9/100.4 141.2/152.7 190/190

35*/40*

87.9/100.4 162.6/162.6 220/220

10
(STD

28

10*/12*

25.1/30.1 162.6/162.6 220/220

15*/20*

37.7/50.2 162.6/162.6 220/220

147.6

200

175.2

230

10*/12*

25.1/30.1 147.6/147.6 200/200

15*/20*

37.7/50.2 147.6/147.6 200/200

25*/30*

62.8/75.3 147.6/147.6 200/200

25*/30*

62.8/75.3 175.2/175.2 230/230

35*/40*

87.9/100.4 147.6/160.7 200/200

35*/40*

87.9/100.4 175.2/176.4 230/230

15
(ALT.)

40.6

10*/12*

25.1/30.1 175.2/175.2 230/230

15*/20*

37.7/50.2 175.2/175.2 230/230

74.8

100

10*/12*

15.2/18.2

74.8/74.8

100/100

10*/12*

15.2/18.2 100.2/100.2 130/130

15*/20*

22.8/30.4

74.8/74.8

100/100

15*/20*

22.8/30.4 100.2/100.2 130/130

25*/30*

38/45.6

74.8/74.8

100/100

25*/30*

35*/40*

53.2/60.8

81.7/91.2

100/100

35*/40*

80.2

100

10*/12*

15.2/18.2

80.2/80.2

100/100

10*/12*

15.2/18.2 107.2/107.2 140/140

15*/20*

22.8/30.4

80.2/80.3

100/100

15*/20*

22.8/30.4 107.2/107.2 140/140

25*/30*

38/45.6

80.2/80.4

100/100

25*/30*

35*/40*

53.2/60.8

88.4/97.9

100/1100

35*/40*

1 0 17.5
(STD)

38/45.6

100.2

130

100.2/100.2 130/130

53.2/60.8 100.2/100.2 130/130

15
(ALT.)

24.5

38/45.6

107.2

140

107.2/107.2 140/140

53.2/60.8 107.2/107.2 140/140

65

90

85.1

120

10*/12*

12.6/15.1

65.0/65.0

90/90

10*/12*

12.6/15.1

85.1/85.1

120/120

15*/20*

18.8/25.1

65.0/65.0

90/90

15*/20*

18.8/25.1

85.1/85.1

120/120

25*/30*

31.4/37.7

65.0/65.0

90/90

25*/30*

31.4/37.7

85.1/85.1

120/120

35*/40*

43.9/50.2

68.5/76.3

90/90

35*/40*

43.9/50.2

85.1/85.1

120/120

68.2

90

91.4

120

10*/12*

12.6/15.1

68.2/68.2

90/90

10*/12*

12.6/15.1

91.4/91.4

120/120

15*/20*

18.8/25.1

68.2/68.2

90/90

15*/20*

18.8/25.1

91.4/91.4

120/120

25*/30*

31.4/37.7

68.2/68.2

90/90

25*/30*

31.4/37.7

91.4/91.4

120/120

35*/40*

43.9/50.2

72.5/80.3

90/90

35*/40*

43.9/50.2

91.4/91.4

120/120

10
(STD)

14

28.2 173

14

MOCP - Maximum Over Current Protection

*Combination of heater

MCA

25.1/30.1 141.2/141.2 190/190

LEGEND:
- Horse Power

RLA LRA HP FLA Nom. kW

20.7 125

10
(ALT.)

HP

190

ELECTRIC
HEATER

33.3 196

7.5 10.8
(STD)

414

24.4 145

1 0 17.5
(ALT.)

460-3-60

141.2

FLA

BM

53.8 340

7.5 12.1
(STD)

418

MOCP

47.1 245

10
(ALT.)

342

MCA

10*/12*

380-3-60 (4 WIRE)

PCY360
COMPRESSOR
(each)

modules

20

1 5 20.3
(ALT.)

FAN PERFORMANCE DATA


(DIRECT DRIVE MOTOR)
Model No.: PCY036
EXTERNAL STATIC PRESSURE (inch wg.)

BLOWER MOTOR
SPEED
0.1

0.2

0.3

0.4

0.5

0.6

CFM

1200

1125

1050

950

875

770

BHP

0.44

0.43

0.43

0.42

0.41

0.40

CFM

1050

950

875

840

810

780

BHP

0.36

0.35

0.35

0.34

0.34

0.33

CFM

900

850

800

750

710

650

BHP

0.3

0.29

0.29

0.28

0.28

0.27

HIGH

MEDIUM

LOW

Model No.: PCY048


EXTERNAL STATIC PRESSURE (inch wg.)

BLOWER MOTOR
SPEED
0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

1875

1830

1750

1680

1650

1590

1500

1410

1280

1200

BHP

0.95

0.93

0.90

0.85

0.82

0.78

0.73

0.70

0.65

0.60

CFM

1685

1590

1550

1525

1500

1450

1380

1300

1225

1130

BHP

0.88

0.85

0.83

0.80

0.78

0.76

0.75

0.71

0.70

0.69

CFM

1540

1475

1450

1410

1370

1320

1250

1200

1110

1025

BHP

0.78

0.75

0.71

0.68

0.65

0.62

0.60

0.59

0.57

0.55

HIGH

MEDIUM

LOW

Model No.: PCY060


EXTERNAL STATIC PRESSURE (inch wg.)

BLOWER MOTOR
SPEED
0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

2005

1980

1860

1840

1710

1650

1570

1490

1370

1265

BHP

0.98

0.97

0.95

0.93

0.91

0.91

0.89

0.87

0.82

0.80

CFM

1900

1860

1780

1710

1660

1590

1500

1415

1310

1202

BHP

0.93

0.91

0.88

0.81

0.79

0.75

0.71

0.67

0.62

0.59

CFM

1710

1640

1590

1570

1520

1465

1380

1290

1220

1150

BHP

0.82

0.80

0.78

0.73

0.71

0.69

0.69

0.61

0.58

0.54

HIGH

MEDIUM

LOW

NOTES: 1. Values include losses for dry coil, 1" thick filters & unit casing.
2. Direct drive motors have single speed connection only. Factory set at medium speed. Thermostats are also single speed type only. Refer
to the unit wiring diagram for connecting to other motor speeds.

21

FAN PERFORMANCE DATA


Model No.: PCY075
External Static Pressure (inch wg.)

Airflow,
CFM (L/S)

0.2

0.4

RPM

BHP

1500 (708)

654*

0.44*

1600 (755)

672*

0.46*

1800 (849)

690

0.6

0.8

1.0

1.2

1.4

1.6

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

731

0.45

822

0.49

917

0.55

993

0.67

1066

0.77

1135

0.87

1192

755

0.49

846

0.54

934

0.64

1011

0.76

1082

0.86

1150

0.99

1208

1.28

0.49

780

0.54

870

0.59

954

0.74

1030

0.85

1098

0.95

1166

1.11

1223

1.35
1.41

RPM

BHP

II

1.22

2000 (944)

710

0.53

808

0.61

892

0.65

972

0.85

1048

0.93

1114

1.04

1181

1.24

1239

2200 (1038)

736

0.59

830

0.69

914

0.78

990

0.98

1064

1.02

1130

1.18

1195

1.38

1255

1.54

2400 (1133)

766

0.65

852

0.78

933

0.91

1008

1.05

1079

1.19

1146

1.34

1210

1.50

1270*

1.66*

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 1.5 HP motor to be used for the unshaded portion.
3. Alt. 2 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY090


Airflow,
CFM (L/S)
1900 (897)
2000 (944)
2200 (1038)
2400 (1133)
2600 (1227)
2800 (1321)
3000 (1416)

0.2
RPM BHP

0.4
RPM BHP

610*
622*
635*
648*
661*
674*
690

670*
681*
693
705
714
725
737

0.58*
0.61*
0.64*
0.67*
0.70*
0.74*
0.78

0.59*
0.63*
0.68
0.73
0.78
0.82
0.93

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP
734
744
754
765
776
788
800

0.61
0.67
0.74
0.81
0.89
0.96
1.08

821
827
832
838
843
849
854

0.84
0.89
0.95
1.01
1.07
1.12
1.17

875
881
888
895
902
906
910

0.91
0.97
1.04
1.11
1.19
1.29
1.39

948
951
954
957
960
962
964

1.02
1.09
1.17
1.25
1.34
1.43
1.54

1.4
1.6
RPM BHP RPM BHP

1.8
2.0
RPM BHP RPM BHP

1000
1002
1005
1008
1011
1013
1015

1100
1103
1107
1110
1113
1115
1117

1.06
1.16
1.27
1.38
1.49
1.59
1.71

1050
1053
1056
1059
1062
1065
1067

1.18
1.28
1.39
1.51
1.63
1.76
1.89

1.26
1.39
1.52
1.66
1.80
1.94
2.11

II

1143
1146
1149
1153
1158
1161
1163

1.41
1.54
1.67
1.81
1.95
2.11
2.15

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 2 HP motor to be used for the unshaded portion.
3. Alt. 3 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY100


Airflow,
CFM (L/S)
2200 (1038)
2400 (1133)
2600 (1227)
2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)

0.2
RPM BHP
635*
641*
649*
656*
668*
680*
699

0.64*
0.66*
0.68*
0.69*
0.72*
0.81*
0.92

0.4
RPM BHP
719
723
728
733
745
753
768

0.73
0.78
0.83
0.88
0.95
1.01
1.13

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP
768
778
788
798
810
822
834

0.69
0.78
0.88
0.99
1.10
1.22
1.35

837
846
855
865
875
886
897

0.86
0.96
1.07
1.19
1.31
1.44
1.57

893
902
911
920
929
938
946

1.01
1.1
1.2
1.31
1.42
1.56
1.71

960
969
979
989
999
1006
1013

1.08
1.19
1.3
1.42
1.55
1.69
1.85

1.4
1.6
RPM BHP RPM BHP
1023
1030
1037
1045
1053
1061
1068

1.37
1.47
1.57
1.68
1.79
1.93
2.10

1086
1090
1095
1102
1109
1114
1120

1.8
2.0
RPM BHP RPM BHP

II

1.79
1.85
1.9
1.96
2.05
2.17
2.30

1136
1141
1147
1153
1159
1165
1170

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 2 HP motor to be used for the unshaded portion.
3. Alt. 3 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

22

2.11
2.14
2.19
2.24
2.29
2.35
2.41

1170
1177
1185
1193
1201
1210
1213

2.21
2.25
2.31
2.38
2.45
2.51
2.55

FAN PERFORMANCE DATA


Model No.: PCY120
Airflow,
CFM (L/S)
2600 (1227)
2800 (1321)
3000 (1416)
3200 (1510)
3400 (1605)
3600 (1699)
3800 (1793)
4000 (1888)

0.2
RPM BHP
649*
656*
665*
685*
699
719
733
749

0.67*
0.69*
0.72*
0.82*
0.93
1.06
1.17
1.31

0.4
RPM BHP
728
733
745
755
770
783
797
812

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP

0.83
0.88
0.95
1.01
1.14
1.25
1.39
1.54

788
798
810
824
835
847
859
872

0.88
0.99
1.10
1.20
1.31
1.45
1.63
1.78

855
865
875
885
894
906
918
929

1.07
1.19
1.31
1.41
1.55
1.71
1.87
2.03

911
920
929
939
945
956
965
974

1.2
1.31
1.42
1.52
1.69
1.84
2.01
2.19

979
989
999
1002
1011
1021
1029
1037

1.4
1.6
RPM BHP RPM BHP

II

1.3
1.42
1.55
1.68
1.83
1.99
2.18
2.36

1037
1045
1053
1058
1066
1072
1081
1088

1.57
1.68
1.79
1.91
2.06
2.22
2.35
2.46

1095
1105
1109
1112
1118
1125
1131
1137

1.9
1.96
2.05
2.12
2.24
2.38
2.48
2.54

1.8
2.0
RPM BHP RPM BHP
1147
1153
1159
1164
1169
1175
1180
1185

2.19
2.24
2.29
2.41
2.49
2.56
2.61
2.70

1181
1183
1184
1185
1199
1209
1215
1220

2.31
2.38
2.45
2.57
2.61
2.68
2.75
2.82

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 3 HP motor to be used.
3. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY150


Airflow,
CFM (L/S)

0.2
RPM BHP

0.4
RPM BHP

3000 (1416)
3200 (1510)
3400 (1605)
3600 (1699)
3800 (1793)
4000 (1888)

541*
548*
556*
564*
570*
577

0.64*
0.69*
0.75*
0.82*
0.9*
0.98

596
605
615
625
635
645

4200 (1982)

592

1.06

4400 (2076)

612

1.18

4600 (2170)

630

4800 (2265)

652

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP

1.4
1.6
RPM BHP RPM BHP
928
931
936
941
946
950

II

1.8
2.0
RPM BHP RPM BHP

0.82
0.89
0.94
1.02
1.10
1.18

662
668
675
682
690
698

0.93
1.01
1.10
1.20
1.30
1.42

705
712
718
724
730
735

1.13
1.22
1.31
1.41
1.52
1.63

710
719
729
741
753
768

1.25
1.32
1.41
1.50
1.60
1.67

805
810
818
826
834
842

1.48
1.56
1.65
1.75
1.85
1.95

881
885
890
895
901
905

1.75
1.79
1.84
1.90
1.95
2.01

1.79
1.85
1.93
2.02
2.12
2.22

984*
989*
996*
1002*
1008*
1013*

1.81*
1.92*
2.05*
2.20*
2.40*
2.60*

1048*
1051*
1054*
1058*
1062*
1065*

2.04*
2.16*
2.30*
2.45*
2.65*
2.85*

654

1.27

706

1.53

742

1.74

780

1.79

851

2.11

910

2.12

670

1.39

713

1.65

749

1.89

794

1.95

860

2.26

915

2.24

955

2.38

1017* 2.76* 1067* 3.03*

959*

2.56* 1021* 2.90* 1069* 3.18*

1.32

692

1.54

720

1.80

756

2.03

810

2.11

871

2.41

922

2.39

965*

2.74* 1026* 3.05* 1072* 3.35*

1.47

711

1.69

728

1.93

763

2.18

826

2.25

880

2.53

928

2.57

970*

2.92* 1032* 3.22* 1075* 3.54*

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 3 HP motor to be used for the unshaded portion.
3. Alt. 5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY180


Airflow,
CFM (L/S)
3800 (1793)
4000 (1888)
4200 (1982)
4400 (2076)
4600 (2170)
4800 (2265)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)

0.2
RPM BHP

0.4
RPM BHP

601*
609*
618*
628*
638*
648*
658*
669*
682*
696
709
725

651*
658*
667*
676*
686*
696
705
716
729
743
759
774

1.02*
1.12*
1.24*
1.34*
1.45*
1.55*
1.64*
1.74*
1.86*
2.02
2.21
2.42

1.28*
1.35*
1.44*
1.52*
1.61*
1.71
1.80
1.92
2.08
2.26
2.46
2.68

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
1.4
1.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

699
708
717
726
736
746
756
765
777
791
805
826

1.81
1.85
1.91
1.98
2.05
2.12
2.25
2.48
2.61
2.75
2.90
3.00

751
758
766
774
784
792
802
811
822
833
845
857

1.85
1.92
1.99
2.05
2.12
2.19
2.35
2.54
2.68
2.82
3.01
3.30

805
810
818
825
832
841
850
859
869
880
892
901

1.95
2.00
2.08
2.13
2.18
2.25
2.40
2.62
2.81
3.04
3.30
3.60

859
864
871
877
882
888
895
903
911
919
927
935

2.35
2.42
2.51
2.61
2.70
2.80
2.91
3.06
3.24
3.42
3.62
3.80

899
905
910
915
922
928
934
942
951
962
973
982

2.45
2.54
2.62
2.71
2.80
2.89
3.01
3.15
3.34
3.54
3.80
4.20

961
969
975
982
990
994
1001
1008
1015
1023
1031
1039

2.76
2.84
2.94
3.05
3.15
3.28
3.54
3.72
3.89
4.09
4.28
4.60

1.8
RPM BHP

2. Standard 5 HP motor to be used for the unshaded portion.


3. Alt. 7.5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

23

II

995
2.78
1005 2.85
1015 2.98
1021 3.15
1027 3.30
1033 3.45
1039 3.65
1046 3.84
1052 3.96
1059 4.19
1067 4.46
1074* 4.92*

Notes: 1. Values include losses for filters, unit casing and wet coils.

2.0
RPM BHP
1035
1042
1050
1059
1065
1070*
1076*
1082*
1088*
1094*
1103*
1109*

3.01
3.11
3.20
3.35
3.50
3.65*
3.81*
3.96*
4.15*
4.45*
4.81*
5.28*

FAN PERFORMANCE DATA


Model No.: PCY210
Airflow,
CFM (L/S)
4800 (2265)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
6800 (3209)
7000 (3303)

0.2
RPM BHP

0.4
RPM BHP

527*
534*
542*
550*
559*
568*
577*
589
595
605
614
623

545*
550*
557*
564*
572*
578*
586
642
649
657
665
673

1.55*
1.59*
1.65*
1.73*
1.81*
1.91*
2.03*
2.15
2.27
2.39
2.52
2.66

1.56*
1.62*
1.71*
1.81*
1.91*
2.01*
2.13
2.25
2.24
2.51
2.64
2.78

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
1.4
1.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

653
658
663
669
675
682
689
695
701
708
715
721

1.69
1.76
1.84
1.93
2.02
2.12
2.24
2.36
2.5
2.64
2.78
2.93

707
712
717
723
729
735
741
746
751
757
763
768

1.80
1.87
1.95
2.03
2.12
2.24
2.36
2.49
2.63
2.78
2.93
3.09

761
765
770
775
780
785
790
795
799
804
809
814

1.98
2.08
2.18
2.29
2.40
2.52
2.68
2.83
2.98
3.13
3.29
3.46

806
811
816
822
827
832
837
841
845
850
854
858

2.51
2.55
2.63
2.72
2.81
2.91
3.02
3.17
3.33
3.49
3.66
3.83

II

851
855
861
867
872
877
882
886
889
893
897
900

2.65
2.71
2.79
2.83
2.92
2.97
3.12
3.28
3.44
3.61
3.79
3.97

912
914
917*
919*
921*
923*
926*
928*
931*
935*
938*
941*

2.74
2.82
2.92*
3.03*
3.13*
3.26*
3.48*
3.64*
3.81*
3.99*
4.17*
4.36*

1.8
RPM BHP

2.0
RPM BHP

955*
957*
959*
961*
963*
965*
967*
969*
972*
975*
978*
981*

991*
993*
996*
999*
1001*
1004*
1006*
1009*
1011*
1014*
1016*
1019*

3.14*
3.24*
3.36*
3.46*
3.58*
3.70*
3.84*
4.01*
4.19*
4.38*
4.57*
4.76*

3.63*
3.72*
3.84*
3.93*
4.02*
4.12*
4.22*
4.39*
4.58*
4.77*
4.97*
5.17*

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 5 HP motor to be used for the unshaded portion.
3. Alt. 7.5 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY240


Airflow,
CFM (L/S)
5000 (2360)
5200 (2454)
5400 (2548)
5600 (2643)
5800 (2737)
6000 (2832)
6200 (2926)
6400 (3020)
6600 (3115)
6800 (3209)
7000 (3303)
7200 (3398)
7400 (3492)
7500 (3542)

0.2
RPM BHP

0.4
RPM BHP

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP

569*
575*
580*
586*
592*
598*
604*
610*
616*
622*
629*
636*
644*
652*

627*
631*
635*
640*
645*
650*
655*
660*
666*
673*
679*
686
693
700

663*
668*
673*
679*
685
691
697
703
710
717
723
729
736
743

2.04*
2.09*
2.13*
2.18*
2.23*
2.28*
2.34*
2.42*
2.51*
2.60*
2.71*
2.82*
2.94*
3.09*

2.41*
2.46*
2.50*
2.55*
2.61*
2.68*
2.75*
2.82*
2.91*
2.99*
3.08*
3.18
3.29
3.40

2.49*
2.53*
2.58*
2.63*
2.69
2.75
2.83
2.89
2.97
3.06
3.16
3.27
3.39
3.51

713
716
720
725
730
735
740
746
753
759
766
773
780
786

2.58
2.61
2.66
2.72
2.78
2.84
2.91
2.99
3.08
3.19
3.31
3.44
3.58
3.74

760
764
769
773
778
783
788
793
798
805
811
817
823
829

2.79
2.83
2.88
2.93
2.99
3.05
3.13
3.22
3.37
3.49
3.62
3.76
3.91
4.05

808
812
818
823
828
833
838
842
846
850
855
860
865
870

3.21
3.24
3.28
3.33
3.39
3.45
3.51
3.58
3.68
3.79
3.91
4.05
4.23
4.41

1.4
1.6
RPM BHP RPM BHP
858
862
866
870
874
878
881
885
889
893
897
901
906
911

3.16
3.21
3.26
3.33
3.42
3.49
3.57
3.71
3.85
3.97
4.11
4.26
4.42
4.59

892
898
905
910
915
920
925
929
933
936
940
944
948
952

3.69
3.74
3.80
3.86
3.92
3.99
4.08
4.17
4.29
4.41
4.54
4.68
4.84
5.02

1.8
2.0
RPM BHP RPM BHP

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

24

II

935
941
946
950
954
958
962
965
968
972
976
981
985
989

3.81
3.88
3.93
3.99
4.06
4.12
4.18
4.32
4.48
4.64
4.82
5.01
5.19
5.39

968
973
979
984
991
996
1001
1005
1008
1011
1014
1018
1022
1026*

3.81
3.89
3.98
4.08
4.18
4.31
4.44
4.60
4.78
4.96
5.16
5.36
5.58
5.80*

FAN PERFORMANCE DATA


Model No.: PCY300
Airflow,
CFM (L/S)
7000 (3303)
7200 (3398)
7400 (3492)
7600 (3587)
7800 (3681)
8000 (3775)
8200 (3870)
8400 (3964)
8600 (4058)
8800 (4152)
9000 (4247)
9200 (4341)
9400 (4436)
9600 (4530)

0.2
RPM BHP

0.4
RPM BHP

608*
613*
618*
624*
630*
637*
645*
655*
663*
672*
681*
689
698
707

644*
649*
655*
662*
670*
678*
686
695
703
711
719
727
735
742

3.02*
3.10*
3.20*
3.32*
3.45*
3.60*
3.79*
3.98*
4.18*
4.38*
4.60*
4.73
4.84
5.05

3.21*
3.29*
3.40*
3.50*
3.61*
3.73*
3.89
4.15
4.35
4.56
4.80
4.95
5.09
5.41

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP
688
693
699
706
712
719
726
733
741
748
755
764
772
778

3.29
3.38
3.51
3.64
3.80
3.97
4.17
4.38
4.60
4.82
5.05
5.17
5.32
5.57

730
735
742
748
754
760
766
772
779
785
791
798
806
812

3.50
3.61
3.71
3.85
4.01
4.18
4.37
4.61
4.83
5.04
5.28
5.52
5.80
6.05

770
775
781
787
793
799
805
810
816
822
827
831
838
846

3.85
3.98
4.11
4.25
4.41
4.60
4.81
5.04
5.27
5.50
5.76
6.00
6.26
6.54

816
821
825
830
835
838
843
847
853
858
864
869
875
881

4.24
4.36
4.51
4.65
4.82
5.02
5.25
5.46
5.69
5.95
6.19
6.45
6.72
6.99

1.4
1.6
RPM BHP RPM BHP
859
862
866
870
874
878
882
886
891
895
899
905
910
915

4.41
4.53
4.69
4.84
5.01
5.19
5.38
5.68
5.89
6.15
6.39
6.68
6.95
7.25

891
895
899
905
910
915
920
924
929
934
938
942
947
951

4.61
4.85
5.02
5.16
5.35
5.59
5.85
6.10
6.35
6.61
6.88
7.15
7.44
7.73

1.8
2.0
RPM BHP RPM BHP

II

926
931
935
940
945
950
955
959
964
968
973
978
982
987

5.28
5.41
5.55
5.69
5.85
6.05
6.31
6.55
6.81
7.11
7.37
7.65
7.92
8.25

965
969
973
977
981
985
988
992
996
999
1003
1007
1012
1016

5.71
5.84
5.99
6.13
6.31
6.51
6.76
6.98
7.29
7.55
7.86
8.16
8.45
8.79

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 7.5 HP motor to be used for the unshaded portion.
3. Alt. 10 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

Model No.: PCY360


Airflow,
CFM (L/S)
8200 (3870)
8400 (3964)
8600 (4058)
8800 (4152)
9000 (4247)
9200 (4341)
9400 (4436)
9600 (4530)
9800 (4624)
10000 (4719)
10200 (4813)
10400 (4907)
10600 (5002)
10800 (5096)
11000 (5191)
11250 (5286)

0.2
RPM BHP

0.4
RPM BHP

External Static Pressure (inch wg.)


0.6
0.8
1.0
1.2
RPM BHP RPM BHP RPM BHP RPM BHP

610*
615*
620*
625*
630*
635*
640*
645*
655*
665*
675*
685
695
705
715
725

605*
615*
625*
635*
645*
655*
665*
675*
684*
695
705
715
725
735
745
755

635*
645*
655*
665*
675*
685
695
705
715
725
735
745
755
765
775
785

4.20*
4.35*
4.50*
4.65*
4.80*
5.00*
5.20*
5.40*
5.60*
5.80*
6.00*
6.20
6.40
6.60
6.80
7.00

4.51*
4.65*
4.80*
4.95*
5.10*
5.30*
5.50*
5.70*
5.90*
6.10
6.30
6.50
6.70
6.90
7.10
7.30

4.90*
5.05*
5.20*
5.35*
5.50*
5.70
5.90
6.10
6.30
6.50
6.70
6.90
7.10
7.30
7.50
7.70

660*
670*
680*
690
700
710
720
730
740
750
760
770
780
790
800
810

5.31*
5.45*
5.60*
5.75
5.90
6.10
6.30
6.50
6.70
6.90
7.10
7.30
7.50
7.70
7.90
8.10

690
700
710
720
730
740
750
760
770
780
790
800
810
820
830
840

5.80
5.95
6.10
6.25
6.40
6.60
6.80
7.00
7.20
7.40
7.60
7.80
8.00
8.20
8.40
8.60

720
730
740
750
760
770
780
790
800
810
820
830
840
850
860
870

6.20
6.35
6.50
6.65
6.80
7.00
7.20
7.40
7.60
7.80
8.00
8.20
8.40
8.60
8.80
9.00

1.4
1.6
RPM BHP RPM BHP
750
765
775
785
795
805
815
825
835
845
855
865
875
885
895
905

6.71
6.85
7.00
7.15
7.30
7.50
7.70
7.90
8.10
8.30
8.50
8.70
8.90
9.10
9.30
9.50

780
790
800
810
820
830
840
850
860
870
880
890
900
910
920
930

7.20
7.35
7.50
7.65
7.80
8.00
8.20
8.40
8.60
8.80
9.00
9.20
9.40
9.60
9.80
10.00

1.8
2.0
RPM BHP RPM BHP
810
820
830
840
850
860
870
880
890
900
910
920
930
940
950
960

Notes: 1. Values include losses for filters, unit casing and wet coils.
2. Standard 10 HP motor to be used for the unshaded portion.
3. Alt. 15 HP motor to be used for the shaded portion.
4. Bordered regions indicate alternative drives I & II.

* For bold figures, consult your nearest Zamil representative for proper selection of drives. Drives shall be field supplied & installed.

25

7.60
7.75
7.90
8.05
8.20
8.40
8.60
8.80
9.00
9.20
9.40
9.60
9.80
10.00
10.20
10.40

II

840
850
860
870
880
890
900
910
920
930
940
950
960
970
980
990

8.00
8.20
8.40
8.60
8.80
9.00
9.20
9.40
9.60
9.80
10.00
10.20
10.40
10.60
10.80
11.00

SOUND LEVEL DATA


To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP (see step 4 & table below).
2. Read dBA level from respective graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from sound power factor table and add dBA level to each values in the row to obtain
Sound Power Level (dB re 10-12 watts).
4. Calculate TSP (Total Static Pressure) as follows:
TSP = ISP + ESP
ESP (External Static Pressure) from Job Specification.
ISP (Internal Static Pressure) Calculate from table below.
FACE VELOCITY

INTERNAL STATIC PRESSURE (inch wg.)

(FPM)
2 ROW

3 ROW

4 ROW

200

0.42

0.44

0.47

300

0.67

0.73

0.78

400

0.88

0.95

1.05

450

1.02

1.13

1.23

500

1.16

1.29

1.49

NOTE:
Pressure drop across filter, coil and casing are included in ISP.

26

SOUND LEVEL DATA


MODEL: PCY036

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

493-887 RPM

7.5

+ 0.5

+ 7.5

+ 10.5

+ 5.5

+2

6.5

887-1750 RPM

+ 0.5

+7

+7

+8

+ 1.5

1.5

6.5

1750-2500 RPM

+ 0.5

+7

+7

+5

+ 4.5

1.5

6.5

To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12 watts).

27

SOUND LEVEL DATA


MODELS: PCY048 - PCY060

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

493-887 RPM

7.5

+ 0.5

+ 7.5

+ 10.5

+ 5.5

+2

6.5

887-1750 RPM

+ 0.5

+7

+7

+8

+ 1.5

1.5

6.5

1750-2500 RPM

+ 0.5

+7

+7

+5

+ 4.5

1.5

6.5

1. To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite to the center of blower inlet:
a) From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
b) Read Sound Pressure dBA level from above graph at operating BHP & SE(%).
2. To obtain Sound Power Level (dB re 10-12 watts), knowing RPM, select proper row from above table and add Sound
Pressure dBA level to each values in the row.

28

SOUND LEVEL DATA


MODEL: PCY075

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

251-495 RPM

+2

+ 11.5

+8

+ 5.5

+2

6.5

495-990 RPM

6.5

+ 1.5

+8

+ 10.5

+5

+ 1.5

1.5

990-1953 RPM

+ 1.5

+8

+7

+8

+ 1.5

7.5

1953-2050 RPM

+ 1.5

+8

+7

+5

+ 4.5

7.5

To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12 watts).

29

SOUND LEVEL DATA


MODELS: PCY090 - PCY180

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

211-417 RPM

4.5

+3

+ 12

+8

+5

+2

1.5

417-835 RPM

5.5

+ 2.5

+ 8.5

+ 10.5

+ 4.5

+ 1.5

7.5

835-1647 RPM

5.5

+ 2.5

+8

+7

+7

+1

2.5

7.5

To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12 watts).

30

SOUND LEVEL DATA


MODELS: PCY210 - PCY240

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

255-443 RPM

3.5

+4

+ 12.5

+8

+ 4.5

+ 1.5

7.5

443-887 RPM

+ 3.5

+9

+ 10

+4

+1

2.5

887-1750 RPM

+ 3.5

+ 8.5

+7

+7

+ 0.5

To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12 watts).

31

SOUND LEVEL DATA


MODELS: PCY300 - PCY360

SOUND POWER FACTOR TABLE


VALUES GIVE TO SOUND POWER
Octave Band
Center Frequency Hz

63

125

250

500

1000

2000

4000

8000

267-507 RPM

+ 4.5

+ 12.5

+ 7.5

+ 4.5

+ 1.5

7.5

507-1014 RPM

3.5

+ 3.5

+9

+ 10

+4

+ 0.5

2.5

1014-2000 RPM

+ 3.5

+ 8.5

+7

+ 6.5

+ 0.5

To obtain Sound Pressure Level measured 5 ft. (1.6 m) directly opposite to the center of blower inlet:
1. From performance table at operating conditions, find BHP, RPM & Static Efficiency (SE).
SE= (CFM x TSP)/6362 x BHP
2. Read dBA level from above graph at operating BHP & SE(%).
3. Knowing RPM, select proper row from above table and add dBA level to each values in the row to obtain Sound Power
Level (dB re 10-12 watts).

32

STATIC PRESSURE DROP (inch wg.)


MODELS: PCY036 - PCY060
CFM

COMPONENT

900
0.12
0.19

1 HEATER MODULE
2 HEATER MODULE

1200
0.12
0.19

1400
0.12
0.19

1600
0.13
0.20

1800
0.14
0.21

2000
0.15
0.21

MODELS: PCY075 - PCY090


COMPONENT
1 HEATER MODULE
2 HEATER MODULE

CFM
1600
0.11
0.18

1800
0.12
0.19

2000
0.13
0.19

2200
0.13
0.19

2400
0.14
0.20

2600
0.15
0.20

3000
0.16
0.21

3200
0.16
0.21

3400
0.17
0.22

3600
0.18
0.23

3800
0.18
0.23

MODELS: PCY100 - PCY150


CFM
COMPONENT
1 HEATER MODULE
2 HEATER MODULE

2600
0.04
0.06

2800
0.04
0.06

3000
0.05
0.07

3400
0.08
0.10

3800
0.10
0.12

4000
0.11
0.14

4200
0.12
0.15

4800
0.14
0.18

5200
0.16
0.20

5800
0.18
0.22

MODELS: PCY180 - PCY210


COMPONENT
1 HEATER MODULE
2 HEATER MODULE

CFM
4800
0.08
0.14

5200
0.08
0.14

5600
0.08
0.14

6000
0.08
0.14

6200
0.08
0.14

6800
0.09
0.16

7000
0.10
0.16

7400
0.10
0.16

7600
0.10
0.16

7800
0.11
0.17

8200
0.11
0.17

9600
0.11
0.20

10200
0.12
0.21

10800
0.13
0.22

11400
0.14
0.23

12000
0.15
0.24

MODELS: PCY240 - PCY360


COMPONENT
1 HEATER MODULE
2 HEATER MODULE

CFM
6000
0.05
0.14

6600
0.06
0.15

7200
0.07
0.16

7800
0.08
0.17

8400
0.09
0.18

9000
0.10
0.19

BLOWER MOTOR EFFICIENCY


MOTOR HP

0.75

1.0

1.5

2.0

3.0

5.0

7.5

10.0

EFFICIENCY (%)

0.81

0.81

0.80

0.81

0.81

0.80

0.81

0.80

NOTE: Convert BHP to watts using following formula


746 x BHP
Watts =
Motor Efficiency

33

UNIT DIMENSIONS
PCY036

24
[0.94]

NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).

34

UNIT DIMENSIONS
PCY048 - PCY120

COMPRESSOR / CONTROLS
ACCESS PANEL

ACCESS PANEL
FOR BLOWER & MOTOR

CONTROL COMPARTMENT
CONDENSER COIL

CONDENSATE DRAIN OUTLET


3/4" NPT

AIR IN

(OPTIONAL)
FRESH AIR OPENING/HOOD

AIR IN

SUPPLY AIR

RETURN AIR

TOP VIEW

AIR OUT

FILTER

RETURN AIR
OPENING

ACCESS
PANEL

SUPPLY AIR
OPENING

CONDENSER COIL

CONDENSER COIL
POWER SUPPLY CONN

132
[5.21]

DRAIN OUTLET

12.7 ( 0.5) MOUNTING HOLES


(2 EACH SIDE)

SIDE VIEW

FRONT VIEW

SIDE VIEW

DIMENSIONS
MODEL
A

PCY048 - PCY075

2080(81.89)

1162(45.75)

1034(40.71)

PCY090 - PCY120

2212(87.1)

1408(55.43)

1085(42.72)

1114(43.86) 308(12.15) 550(21.64) 798(31.4) 300(11.81) 251(9.87) 396(15.59) 152(5.98) 175(6.88)


1372(54)

255(10.03) 707(27.84) 790(31.1) 367(14.46) 190(7.48) 476(18.74) 150(5.91) 145(5.71)

NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).

35

24(0.94)

171(6.73) 1775(69.88)

48(1.89)

200(7.87) 1907(75.08)

UNIT DIMENSIONS
PCY150 - PCY360

ACCESS PANEL
FOR BLOWER & MOTOR

CONTROLS
ACCESS PANEL

CONDENSER COIL

CONTROL COMPARTMENT

CONDENSATE DRAIN OUTLET


3/4" NPT

A\IR IN

POWER INLET

(OPTIONAL)
FRESH AIR OPENING/HOOD

A\IR IN

CONDENSER COIL
AIR IN

SUPPLY AIR

RETURN AIR

TOP VIEW

AIR OUT

N
CONTROL BOX
ACCESS PANEL

FILTER
ACCESS PANEL

RETURN AIR OPENING

DRAIN OUTLET
144
[5.67]

233
[9.17]

SUPPLY AIR
OPENING

CONDENSER COIL

COMPRESSOR
ACCESS PANEL

POWER INLET
D

SIDE VIEW

G
16 x 25mm
MOUNTING SLOT (3EACH SIDE)
MOUNTING SLOT (4EACH SIDE FOR PQH360)
PCY360)

SIDE VIEW

FRONT VIEW

DIMENSIONS
MODEL
A

PCY150 - PCY180 2794(110)

1778(70) 1266(49.83) 1715(67.52) 1737(68.37) 197(7.75) 817(32.17) 720(28.35) 1200(47.25)

83(3.27)

194(7.64)

171(6.73)

PCY210 - PCY240 3048(120)

2135(84)

84(3.31) 1050(41.34) 666(26.22) 289(11.38)

194(7.64)

PCY300 - PCY360 3683(145)

2184(86) 1446(56.94) 2125(83.66) 2184(86)

97(3.83) 1000(39.37) 680(26.77)

372(14.65) 1125(44.29)

1446(56.94) 2075(81.7) 2152(84.72) 324(12.76) 915(36.02) 740(29.13) 1200(47.25)


42(1.65)

938(36.93) 527(20.75)

NOTE:
1. All dimensions are in mm (dimensions in brackets are in inches).

36

912(35.9) 666(26.22)

254(10)

CONTROLS & SEQUENCE OF OPERATION


Scroll compressors are designed to operate in single direction only. Hence, care has to be taken to ensure correct rotation
when the system is operated. Verification of correct rotation is by observing that the suction pressure drops and discharge
pressure rises when compressor run. Reverse rotation results in abnormal sound, as well as, substantially low current draw
and by interchanging power supply wire L1 & L3 will correct this problem.
The operation of the air conditioning unit is controlled by a 24VAC electronic control board.
GENERAL
The thermostat normally displays room temperature and mode of operation. The five buttons on the front of the unit allow
complete control of the thermostat. The thermostat also allows to select continuous fan operation (useful when using an air
cleaner) or have the fan come on with the compressor.
SWITCH FUNCTION
- On/Off Key
: Switch the system On or Off.
- Up Key
: To increases the set temperature.
- Down Key
: To decreases the set temperature.
- Mode Key
: Changes the mode to Fan, Cool, Heat or Auto.
- Fan Key
: Changes the Fan Operation to Auto or Continuous.
- C/F selection : By pressing Mode & UP key together, toggles between C to F or vice versa.
USER CONTROLS
Mode:
Select the desired mode of operation by pressing of the mode button:
O
T
U
A

T
A
E
H

L
O
O
C

N
A
F

Fan:

In this mode of operation, the compressor will be in inactive state. Display shows room temperature. Fan will be running.

Cool:
In this mode of operation, the compressor will be ON after a delay depending on the differential of room temperature & Set temperature.
Heat:

In this mode of operation, Fan is ON.

Auto:
In auto mode, thermostat provide automatic changeover from heating to cooling mode & vice versa. Thermostat
automatically switches to maintain the desired temperature.
DIP SWITCH OPTIONS AND FUNCTIONS
There are 4 small DIP (Dual in line package) switches on the back of the circuit board which must be configured by the
installer.
HOOK-UP WIRING DIAGRAM
( THERMOSTAT CONTROLLER TO PACKAGED UNIT )

DIP SWITCH SELECTION


SWITCH

ON

OFF

N. A.

N. A.

N. A.

THERMOSTAT
(ZAC P/N 80065261)

Y2

NOTE: OPTIONAL CONNECTION :


IF REMOTE TEMPERATURE SENSING
FUNCTION IS REQUIRED.

INDOOR SENSOR REMOTE SENSOR

SENSOR

PACU CONTROL PANEL

Note:
Keep DIP SWITCH 1, 2 & 3 in OFF
position only.

W1
Y1
REMOTE
SENSOR

G
24V(R)

COMPRESSOR FAULT SIGNAL


(VOLT-FREE CONTACT)

ATB

COMP 1

24V(C)
FAULT 1

( OPTIONAL CONNECTION )

FAULT 2

COMP 2
(COMMON)

LVTB
R
C
G
Y1
Y2

LEGEND:
ATB
LVTB

AUXILIARY TERMINAL BLOCK


LOW VOLTAGE TERMINAL BLOCK

37

24V ac
SUPPLY FAN CONTROL
STG1 COOLING
STG2 COOLING

W1

STG1 HEATER

W2

STG2 HEATER

W2

TYPICAL SCHEMATIC WIRING DIAGRAM


REFER TO UNIT
NAMEPLATE
FOR
POWER
SUPPLY

TO HVTB
L1
ATB (UVM)
JP1 1A
1

(SD)
JP2

TO NTB/HVTB
N/L2

230VAC

ATB

1B
PLEASE REFER TO FAN MOTOR CONTROL
CONNECTION FOR OLR, LOW AMBIENT AND T.O.P
FMC

HC2

SEE OPTIONAL VFC CONNECTION

AFS

28

HC1
BMC

19

(SEE NOTE 3)
OLR-1

PDS2
PDS1

(SEE NOTE 3)

TO ATB
CC2

3A

3B

4A

4B

14

29

30

41B

41A

12

CC1

THERMOSTAT / DDC CONTROLLER

LOCK2(RED)

LOCK1(RED)

PRI

SYSTEM2(ORG)

COMP1

COMP2

P1

P2

INFAN

HEATER1

HEATER2

X1

X2

OUTFAN1

OUTFAN2

LIVE

NEUTRAL

(by others)

LVTB
R

ECB

Y1

Y1

Y2

Y2

W1

W1

W2

W2

R
24Vac

BM CONTROL

STG1 COOLING

Y1

STG2 COOLING

Y2

STG1 HEATING

W1

STG2 HEATING

W2

SYSTEM1(YEL)
ON/OFF

FUSE

(ON/OFF)

ANS

P3_##

HP1

240v

(HP1)

12v-0-12v

HP2

SEC

ON

(HP2)

DIP

DIP SWITCH
POWER(GRN)
J_PROG

LP1

22A

(LP1)

23A

LP2

22B

(LP2)

23B

LPS1

LPS2

NOTE: 1. Refer to next page for legend, notes & wiring diagram for optional items.
2. Refer to unit control box (inside panel) for exact wiring diagram.

38

TYPICAL SCHEMATIC WIRING DIAGRAM


LEGEND
AR
AFS
ATB
BM
BMC
CC
CCA
CB
C. HTR
COMP
ECB
FCS
F
FL
FM
FMC
FR
HC
HPS
HVTB
HTR
JP
L1
L2
L3
LPS
LUG
NTB
O/L
OHT
PDS

AUXILIARY RELAY
AIRFLOW SWITCH
AUXILIARY TERMINAL BLOCK
BLOWER MOTOR
BLOWER MOTOR CONTACTOR
COMPRESSOR CONTACTOR
AUXILIARY CONTACT
CIRCUIT BREAKER
CRANKCASE HEATER
COMPRESSOR
ELECTRONIC CONTROL BOARD
FAN CYCLING SWITCH
FUSE
FUSE LINK
FAN MOTOR (CONDENSER)
FAN MOTOR CONTACTOR
FAULT RELAY
HEATER CONTACTOR
HIGH PRESSURE SWITCH
HIGH VOLTAGE TERMINAL BLOCK
HEATER
JUMPER
LINE 1
LINE 2
LINE 3
LOW PRESSURE SWITCH
LUG GROUND
NEUTRAL TERMINAL BLOCK
OVER LOAD
OVER HEAT THERMOSTAT
PUMP DOWN SOLENOID

SSPS

SOLID STATE PROTECTIVE SYSTEM

SD

SMOKE DETECTOR

TRANS TRANSFORMER
T'STAT THERMOSTAT
UVM

___
+

UNDER VOLTAGE MONITOR


FIELD WIRING
DISCONNECT TAB - 1/4"
SPLICE-CLOSED END
TERMINAL BLOCK OR TERMINATION POINT

NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. ANY WIRE REPLACEMENT SHOULD BE OF 900C OR ITS
EQUIVALENT. USE COPPER CONDUCTOR WIRES ONLY.
3. IF PDS & HEATERS ARE FACTORY INSTALLED, PLEASE
READ BROKEN LINES AS CONTINUOUS LINES.
4 . POWER MUST BE SUPPLIED TO CRANKCASE
HEATER FOR MINIMUM OF 12 HOURS PRIOR TO
SYSTEM START UP.
IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE
HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM.

TO ECB
TO ECB

TO ECB
OUTFAN 1
TO ECB
OUTFAN 2

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE.

TO ECB
OUTFAN 1
TO ECB
OUTFAN 2

5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER


TO BE PROVIDED BY CONSUMER WITH RATING AS RECOMMENDED BY ZAMIL.
6. COMPRESSORS ARE PROVIDED WITH INTERNAL OVERLOAD.
7. IF COMPRESSOR IS SUPPLIED WITH SSPS, CONNECT AS
SHOWN. PLEASE ALLOW 2-3 MINUTES FOR SSPS SWITCH
TO CLOSE, BEFORE STARTING THE UNIT.
8. IF ANY CHANGE IN DIP SWITCH SETTING IS REQUIRED,
TURN OFF POWER FIRST & SET REQUIRED SETTING.
9. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER
SUPPLY ONLY.

39