You are on page 1of 5

OWNER

KANDHKOT FIELD GAS COMPRESSION STATION (KFGCS) PROJECT

Document Title:
Date: 03/06/2008

CONTRACTOR

ELECTRICAL CABLE SIZING

Document No: CAL-00-E-0004

Rev: 1

Class: I

Sheet 1 of 5

ELECTRICAL CABLE SIZING

1
0

Re-Issued for
Construction

03/06/2008

Issued for Construction 22/11/2007

SB

ARS

ShS

ARS

SN

ShS

LiuXG

Issued for Approval

21/09/2007

ARS

SN

ShS

LiuXG

Rev

Description

Date

Prepared

Checked

Approved

CPECC

OWNER

3-PHASE 415V FEEDER LOADS CABLE SELECTION TABLE - 3C+E, 4C+E @ 53C

LOAD RATING (kW)

Current (Amps)

VOLTAGE

9.4100

1.7

727

1165

1733

2891

4528

6985

9483

12509

17266

22313

27474

32117

37543

44866

51450

3.5

364

582

867

1445

2264

3493

4741

6254

8633

11157

13737

16059

18772

22433

25725

5.2

242

388

578

964

1509

2328

3161

4170

5755

7438

9158

10706

12514

14955

17150

7.0

182

291

433

723

1132

1746

2371

3127

4317

5578

6869

8029

9386

11217

12863

8.7

145

233

347

578

906

1397

1897

2502

3453

4463

5495

6423

7509

8973

10290

194

289

482

755

1164

1580

2085

2878

3719

4579

5353

6257

7478

8575

289

453

699

948

1251

1727

2231

2747

3212

3754

4487

5145

2.5

10

16

25

35

50

70

95

120

150

185

240

300

5.8500

3.9100

2.3200

1.4600

0.9270

0.6680

0.4930

0.3420

0.2540

0.1960

0.1590

0.1280

0.0988

0.0799

Resistance @ 90C (Ohms/1000m)

0.087

0.087

0.086

0.084

0.082

0.079

0.078

0.077

0.076

0.073

0.073

0.074

0.074

0.073

0.072

Reactance @50Hz (Ohms/1000m)

25

34

43

59

115

150

180

215

265

315

360

405

460

530

590

Current Rating (A)

22

29

37

51

99

129

155

185

228

271

310

348

396

456

507

Current Post Temperature Derating for 53C

10

14

17

24

46

61

73

87

107

127

146

164

186

214

238

Project Installation Current Rating (A)

10.4

10

17.4

15

26.1

302

466

632

834

1151

1488

1832

2141

2503

2991

3430

20

34.8

226

349

474

625

863

1116

1374

1606

1877

2243

2573

25

43.5

181

279

379

500

691

893

1099

1285

1502

1795

2058

30

52.2

233

316

417

576

744

916

1071

1251

1496

1715

40

69.6

237

313

432

558

687

803

939

1122

1286

50

87.0

345

446

549

642

751

897

1029

60

104.3

288

372

458

535

626

748

858

70

121.7

319

392

459

536

641

735

75

130.4

366

428

501

598

686

80

139.1

343

401

469

561

643

100

173.9

375

449

515

125

217.4

150

260.9

412

MAXIMUM LENGTH OF CABLE RUN (m)

L = maximum permissible cable length (m)

Vd 3 = maximum allowable three phase volt drop (volt)


I = maximum load current (Amp)
Rc = cable resistance at 90 deg C (Ohm/km)
Xc = cable reactance at 50Hz (Ohm/km)
= power angle of the maximum load current

Cable Size (mm2)

Notes:
1. Overcurrent protection shall not exceed current
ratings for the cable.
2. Cables sized for installation on underground
trenches.
3. All cables are stranded copper XLPE insulated
with a maximum conductor operating temperature of
90C.
4. Maximum lengths are calculated for a maximum
voltage drop of 4%.
5. Derating factors for design ambient temperature
(53C) is 0.86 as per Table A.52-15 of IEC 60364-552.
6. Derating factor for installation is 0.47 as per Table
A.52-18 of IEC 60364-5-52.
7. Cable impedance and current carrying capacity
data has been considered from vendor data.
References:
1. Basis of Design - Electrical BOD-00-E-0001

Symbols and abreviations used:

415

2. IEC 60364-52 - Electrical Installation - Wiring


Systems
3. Vendor Catalogues.

8. The figures listed in the above table are the maximum permissible cable length at
the relevant load, and are calculated from :

L=

1000V d 3

3I ( Rc Cos +X c Sin )

3-PHASE 415V MOTOR LOADS SELECTION TABLE (3C+E) @ 53C

LOAD RATING (kW)

Current (Amps)

9.4100

0.25

0.5

1381

2213

3296

5505

8639

13365

18195

24084

33422

43403

53756

63206

74352

89556

103404

0.37

0.8

944

1513

2253

3761

5899

9120

12407

16408

22739

29493

36474

42822

50291

60452

69675

0.55

1.2

635

1018

1515

2530

3969

6135

8347

11038

15297

19841

24537

28808

33832

40668

46872

0.75

1.6

471

755

1124

1876

2942

4544

6178

8163

11298

14636

18073

21188

24844

29804

34292

1.1

2.4

321

515

767

1279

2006

3098

4212

5566

7703

9979

12323

14446

16939

20321

23381

1.5

3.3

238

382

569

949

1487

2295

3118

4117

5690

7362

9078

10628

12442

14897

17112

2.2

4.8

178

284

423

704

1099

1688

2282

2995

4102

5263

6427

7452

8635

10209

11601

6.5

124

198

295

491

769

1184

1606

2114

2911

3753

4608

5372

6261

7454

8521

8.7

105

167

249

413

643

985

1326

1733

2358

3008

3649

4203

4837

5671

6399

5.5

12.0

147

217

359

555

841

1122

1450

1939

2437

2907

3296

3731

4291

4767

7.5

16.4

162

267

413

626

834

1077

1438

1805

2150

2434

2752

3160

3506

11

24.0

317

477

631

808

1067

1327

1563

1752

1961

2227

2448

415

Cable Size (mm2)

2.5

10

16

25

35

50

70

95

120

150

185

240

300

5.8500

3.9100

2.3200

1.4600

0.9270

0.6680

0.4930

0.3420

0.2540

0.1960

0.1590

0.1280

0.0988

0.0799

Resistance @ 90C (Ohms/1000m)

0.087

0.087

0.086

0.084

0.082

0.079

0.078

0.077

0.076

0.073

0.073

0.074

0.074

0.073

0.072

Reactance @50Hz (Ohms/1000m)

25

34

43

59

115

150

180

215

265

315

360

405

460

530

590

Current Rating (A)

22

29

37

51

99

129

155

185

228

271

310

348

396

456

507

Current Post Temperature Derating for 53C

10

14

17

24

46

61

73

87

107

127

146

164

186

214

238

Project Installation Current Rating (A)


Notes:
1. Overcurrent protection shall not exceed current ratings
for the cable.
2. Cables sized for installation on underground trenches.
3. All cables are stranded copper XLPE insulated with a
maximum conductor operating temperature of 90C.
4. Maximum lengths are calculated for a maximum
voltage drop at the load terminals of 15% nominal
voltage under starting conditions and maximum voltage
drop of less than 4% under steady state.
5. Derating factors for design ambient temperature
(53C) is 0.86 as per Table A.52-15 of IEC 60364-5-52.

15

29.3

280

419

552

703

922

1139

1332

1485

1652

1864

2039

18.5

36.1

218

328

433

553

727

902

1059

1183

1321

1495

1639

22

43.0

184

276

364

465

612

758

890

995

1111

1257

1378

30

58.6

213

281

357

467

576

673

749

832

937

1024

37

72.3

236

299

390

479

558

619

685

769

838

45

83.9

267

346

424

491

543

600

671

729

55

102.5

279

342

398

440

487

545

593

75

139.8

298

329

363

405

440

90

167.8

313

347

374

References:
1. Basis of Design - Electrical BOD-00-E-0001

286

308

2. IEC 60364-52 - Electrical Installation - Wiring Systems

110

205.1

132

246.1

150

279.7

185

300.9

L = maximum permissible cable length (m)


Vd 3 = maximum allowable three phase volt drop (volt).
I = maximum load current (Amp)
Rc = cable resistance at 90 deg C (Ohm/km)
Xc = cable reactance at 50Hz (Ohm/km)
= starting power angle of the maximum load current

6. Derating factor for installation is 0.47 as per Table


A.52-18 of IEC 60364-5-52.
7. Cable impedance and current carrying capacity data
has been considered from vendor data.
8. It is assumed that the inrush starting current is 6 times
the full load current of the motor and starting is DOL.

3. Vendor Catalogues.

MAXIMUM LENGTH OF CABLE RUN (m)

Symbols and abreviations used:

VOLTAGE

9. The figures listed in the above table are the maximum permissible cable length at
the relevant load, and are calculated from :

L=

1000V d 3

36I ( Rc Cos +X c Sin )

Page 3 of 5

1-PHASE 240V FEEDER LOADS CABLE SELECTION TABLE - 2C+E, @ 53C

240

Current (Amps)

VOLTAGE

LOAD RATING (kW)

0.04

3.0

211

337

502

837

1311

2023

2746

3623

5001

6463

7957

9302

10874

12995

14902

Notes:

6.0

105

169

251

419

656

1012

1373

1811

2500

3231

3979

4651

5437

6497

7451

12.0

84

126

209

328

506

687

906

1250

1616

1989

2326

2718

3249

3725

1. Overcurrent protection shall not exceed current


ratings for the cable.

100

167

2.5

10

16

25

35

50

70

95

120

150

185

240

300

9.4100

5.8500

3.9100

2.3200

1.4600

0.9270

0.6680

0.4930

0.3420

0.2540

0.1960

0.1590

0.1280

0.0988

0.0799

Resistance @ 90C (Ohms/1000m)

0.087

0.087

0.086

0.084

0.082

0.079

0.078

0.077

0.076

0.073

0.073

0.074

0.074

0.073

0.072

Reactance @50Hz (Ohms/1000m)

25

34

43

59

115

150

180

215

265

315

360

405

460

530

590

Current Rating (A)

22

29

37

51

99

129

155

185

228

271

310

348

396

456

507

Current Post Temperature Derating for 53C

10

14

17

24

46

61

73

87

107

127

146

164

186

214

238

Project Installation Current Rating (A)

15.0

262

405

549

725

1000

1293

1591

1860

2175

2599

2980

10

30.1

131

202

275

362

500

646

796

930

1087

1299

1490

15

45.1

87

135

183

242

333

431

530

620

725

866

993

20

60.1

101

137

181

250

323

398

465

544

650

745

25

75.2

145

200

259

318

372

435

520

596

167

215

265

310

362

433

497

162

199

233

272

325

373

186

217

260

298

181

217

248

186

213

30

90.2

40

120.3

50

150.4

60

180.4

70

210.5

80

240.6

L = maximum permissible cable length (m)


= maximum allowable single phase volt drop (volt)
VI d=1 maximum
load current (Amp)

Rc = cable resistance at 90 deg C (Ohm/km)


Xc = cable reactance at 50Hz (Ohm/km)
= power angle of the maximum load current

Cable Size (mm2)

2. Cables sized for installation on underground


trenches.
3. All cables are stranded copper XLPE insulated
with a maximum conductor operating temperature of
90C.
4. Maximum lengths are calculated for a maximum
voltage drop of 4%.
5. Derating factors for design ambient temperature
(53C) is 0.86 as per Table A.52-15 of IEC 60364-552.
6. Derating factor for installation is 0.47 as per Table
A.52-18 of IEC 60364-5-52.

MAXIMUM LENGTH OF CABLE RUN (m)

Symbols and abreviations used:

Volt Drop

8. The figures listed in the above table are the maximum permissible cable length at
the relevant load, and are calculated from :

L=

1000V d 1

2I ( Rc Cos +X c Sin )

7. Cable impedance and current carrying capacity


data has been considered from vendor data.
References:
1. Basis of Design - Electrical BOD-00-E-0001
2. IEC 60364-52 - Electrical Installation - Wiring
Systems
3. Vendor Catalogues.

Page 4 of 5

3-PHASE 415V FEEDER LOADS CABLE SELECTION TABLE - 1C @ 53C

LOAD RATING (kW)

Current (Amps)

415

0.4930

1.7

12258

16927

22187

26676

31138

36355

43369

49491

56353

63204

69448

3.5

6129

8463

11094

13338

15569

18177

21685

24746

28177

31602

34724

5.2

4086

5642

7396

8892

10379

12118

14456

16497

18784

21068

23149

7.0

3065

4232

5547

6669

7784

9089

10842

12373

14088

15801

17362

8.7

2452

3385

4437

5335

6228

7271

8674

9898

11271

12641

13890

10.4

2043

2821

3698

4446

5190

6059

7228

8249

9392

10534

11575

10

17.4

1226

1693

2219

2668

3114

3635

4337

4949

5635

6320

6945

15

26.1

817

1128

1479

1778

2076

2424

2891

3299

3757

4214

4630

20

34.8

613

846

1109

1334

1557

1818

2168

2475

2818

3160

3472

25

43.5

490

677

887

1067

1246

1454

1735

1980

2254

2528

2778

30

52.2

409

564

740

889

1038

1212

1446

1650

1878

2107

2315

40

69.6

306

423

555

667

778

909

1084

1237

1409

1580

1736

50

87.0

245

339

444

534

623

727

867

990

1127

1264

1389

60

104.3

282

370

445

519

606

723

825

939

1053

1157

70

121.7

317

381

445

519

620

707

805

903

992

75

130.4

296

356

415

485

578

660

751

843

926

80

139.1

333

389

454

542

619

704

790

868

100

173.9

364

434

495

564

632

694

125

217.4

347

396

451

506

556

150

260.9

376

421

463

175

304.3

361

397

200

347.8

225

391.3

250

434.8

50

70

95

120

150

185

240

300

400

500

630

0.3410

0.2460

0.1960

0.1590

0.1280

0.0981

0.0792

0.0630

0.0505

0.0407

Resistance @ 90C (Ohms/1000m)

0.092

0.088

0.086

0.083

0.083

0.082

0.081

0.08

0.079

0.078

0.078

Reactance @50Hz (Ohms/1000m)

230

285

330

380

430

480

560

640

710

810

910

Current Rating (A)

198

245

284

327

370

413

482

550

611

697

783

Current Post Temperature Derating for 53C

93

115

133

154

174

194

226

259

287

327

368

Project Installation Current Rating (A)

Symbols and abreviations used:

347

Cable Size (mm2)

Notes:
1. Overcurrent protection shall not exceed current
ratings for the cable.
2. Cables sized for installation on underground
trenches.
3. All cables are stranded copper XLPE insulated
with a maximum conductor operating temperature of
90C.
4. Maximum lengths are calculated for a maximum
voltage drop of 4%.
5. Derating factors for design ambient temperature
(53C) is 0.86 as per Table A.52-15 of IEC 60364-552.
6. Derating factor for installation is 0.47 as per Table
A.52-18 of IEC 60364-5-52.
7. Cable impedance and current carrying capacity
data has been considered from vendor data.
References:
1. Basis of Design - Electrical BOD-00-E-0001
2. IEC 60364-52 - Electrical Installation - Wiring
Systems
3. Vendor Catalogues.

MAXIMUM LENGTH OF CABLE RUN (m)

L = maximum permissible cable length (m)

Vd 3 = maximum allowable volt drop (volt)

I = maximum load current (Amp)


Rc = cable resistance at 90 deg C (Ohm/km)
Xc = cable reactance at 50Hz (Ohm/km)
= power angle of the maximum load current

8. The figures listed in the above table are the maximum permissible cable length at
the relevant load, and are calculated from :

L=

1000V d 3

3I ( Rc Cos +X c Sin )
Page 5 of 5