Technical Data
EEDEN14-201
RWEYQ-T
TABLE OF CONTENTS
RWEYQ-T
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
4
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Capacity Table Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling/Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring Diagrams - Three Phase
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
10
11
Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Sound Pressure Spectrum
12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Service Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant Pipe Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
22
23
Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1
is mn eU t sr T oy - So Q d Y Vt E RuW RVO
Features
Reduced CO2 emmisions thanks to the use of geothermal energy as
a renewable energy source
No need for an external heating or cooling source when used in
geothermal mode
2-stage heat recovery: first stage between indoor units, second stage
between outdoor units thanks to the storage of energy in the water
circuit
Keep your system in top condition via our ACNSS service: 24/7
monitoring for maximum efficiency, extended lifetime, immediate
service support thanks to failure prediction and a clear understanding
of operability and usage
Customize your VRV for best seasonal efficiency & comfort with the
weather dependant Variable Refrigerant Temperature function
Inverter
Specifications
RWEYQ8T
RWEYQ10T
System
RWEYQ8T
RWEYQ10T
RWEYQ18T
RWEYQ8T
RWEYQ8T
RWEYQ16T
RWEYQ20T
RWEYQ24T
RWEYQ10T
RWEYQ28T
RWEYQ8T
RWEYQ10T
RWEYQ26T
RWEYQ8T
RWEYQ30T
RWEYQ10T
RWEYQ10T
RWEYQ8T
RWEYQ10T
HP
10
16
18
20
24
26
28
30
Cooling capacity
Nom.
kW
22.4 (1) /
22.4 (2)
28.0 (1) /
27.5 (2)
44.8 (1) /
44.8 (2)
50.4 (1) /
49.9 (2)
56.0 (1) /
55.0 (2)
67.2 (1) /
67.2 (2)
72.8 (1) /
72.3 (2)
78.4 (1) /
77.4 (2)
84.0 (1) /
82.5 (2)
Heating capacity
Nom.
kW
25.0 (3) /
25.0 (4)
31.5 (3) /
31.5 (4)
50.0 (3) /
50.0 (4)
56.5 (3) /
56.5 (4)
63.0 (3) /
63.0 (4)
75.0 (3) /
75.0 (4)
81.5 (3) /
81.5 (4)
88.0 (3) /
88.0 (4)
94.5 (3) /
94.5 (4)
Nom.
kW
4.42 (1) /
4.45 (2)
6.14 (1) /
6.35 (2)
10.6 (1) /
10.8 (2)
12.3 (1) /
12.7 (2)
13.3 (1) /
13.4 (2)
15.0 (1) /
15.3 (2)
16.7 (1) /
17.2 (2)
18.4 (1) /
19.1 (2)
Heating
Nom.
kW
4.21 (3) /
4.30 (4)
6.00 (3) /
6.20 (4)
10.2 (3) /
10.5 (4)
12.0 (3) /
12.4 (4)
12.6 (3) /
12.9 (4)
14.4 (3) /
14.8 (4)
16.2 (3) /
16.7 (4)
18.0 (3) /
18.6 (4)
EER
5.07 (1) /
5.03 (2)
4.56 (1) /
4.33 (2)
5.07 (1) /
5.03 (2)
4.77 (1) /
4.62 (2)
4.56 (1) /
4.33 (2)
5.07 (1) /
5.03 (2)
4.86 (1) /
4.74 (2)
4.69 (1) /
4.51 (2)
4.56 (1) /
4.33 (2)
COP
5.94 (3) /
5.81 (4)
5.25 (3) /
5.08 (4)
5.94 (3) /
5.81 (4)
5.53 (3) /
5.38 (4)
5.25 (3) /
5.08 (4)
5.94 (3) /
5.81 (4)
5.65 (3) /
5.51 (4)
5.43 (3) /
5.27 (4)
5.25 (3) /
5.08 (4)
Min.
100
125
200
225
250
300
325
350
375
Nom.
200
250
400
450
500
600
650
700
750
260
325
520
585
650
780
845
910
975
Capacity control
Method
36 (5)
Max.
Casing
Material
Dimensions
Unit
Weight
Packing
mm
1,000
Width
mm
780
Depth
mm
550
mm
1,131
Width
mm
890
Depth
mm
660
Unit
kg
137
Packed unit
kg
149
Carton
3.1
Material
Weight
Packing 2
kg
Material
Weight
Packing 3
kg
Material
Weight
Heat exchanger
Type
Compressor
Quantity
Fan
Height
Packed unit
Inverter controlled
kg
Wood
8.3
Plastic
0.2
Model
Inverter
Type
Hermetically sealed
scroll compressor
Type
Cool Nom m/
ing
.
min
External
static
pressure
Max.
Pa
Nom.
dBA
Sound pressure
level
Cooling
Nom.
dBA
Operation range
Cooling
Min.~Max.
CD
B
-~-
Heating
Min.~Max.
CW
B
-~-
Inlet water
temperature
Cool Min. CD
ing
~Ma B
x.
10~45
-~-
Heat Min. CW
ing
~Ma B
x.
-~-
50
51
53
54
55
56
Specifications
RWEYQ8T
Type
Charge
Refrigerant oil
kg
Type
RWEYQ24T
4.2
RWEYQ30T
Flare connection
mm
9.52
12.7
15.9
19.1
Braze connection
mm
19.10 (9)
22.2 (9)
28.6 (8)
Type
34.9 (8)
Braze connection
OD
mm
15.9 (10) /
19.10 (11)
19.1 (10) /
22.10 (11)
Outlet
Water
Inlet
Outlet
OU - Max. m
IU
After Max. m
bran
ch
120
90 (15)
90 (14)
Total piping
length
Syst Actu m
em al
300
Level
difference
OU - Outd m
IU
oor
unit
in
high
est
posit
ion
50
Indo m
or
unit
in
high
est
posit
ion
40
Max. m
15
Item
RWEYQ28T
Type
IU IU
RWEYQ26T
Drain
Piping length
PED
RWEYQ20T
2.7
Heat insulation
Safety devices
3.5
OD
Discharge
gas
RWEYQ18T
Type
OD
Gas
RWEYQ16T
Charged volume
Piping connections Liquid
RWEYQ10T
R-410A
01
02
Fusible plugs
03
Inverter overload
protector
04
PC board fuse
Category
Category II
RWEYQ8T
Name
Phase
Frequency
Voltage range
Current
RWEYQ10T
RWEYQ16T
RWEYQ18T
RWEYQ20T
Y1
RWEYQ24T
3N~
Hz
50
Voltage
380-415
Min.
-10
Max.
10
Nominal running
current (RLA) 50Hz
Cooling
7.2
RWEYQ26T
RWEYQ28T
RWEYQ30T
23.9
26.2
28.5
9.5
14.4
16.7
19.0
21.6
Specifications
RWEYQ8T
Wiring
connections 50Hz
kVa
RWEYQ10T
RWEYQ16T
RWEYQ18T
RWEYQ20T
RWEYQ24T
RWEYQ26T
RWEYQ28T
1,811
2,716
37.9
12.6
25.3
20
32
50
13.5
27.0
40.5
5G
Quantity
Remark
RWEYQ30T
3
2
F1,F2
Both indoor and outdoor unit
Notes
(1) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol)
(2) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol.
(3) Heating: Indoor temp. 20CDB; inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol).
(4) Heating: Indoor temp. 20CDB; inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol.
(5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% \<=
CR \<= 130%)
(6) Operation range extension in case of Glycol is used in combination with fieldsettings (see installation manual).
(7) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
(8) Sound values are measured in a semi-anechoic room.
(9) In case of heat recovery system
(10) In case of heat pump system
(11) This unit should not be installed outdoors, but indoors e.g. in a machine room.
(12) Hold ambient temperature at 0-40C and humidity at 80%RH or less. Heat rejection from the casing: 0.64kW/8HP
(13) Hold ambient temperature at 0-40C and humidity at 80%RH or less. Heat rejection from the casing: 0.71kW/10HP
(14) Refer to refrigerant pipe selection or installation manual
(15) RLA is based on following conditions: indoor temp. 27CDB, 19CWB; inlet water temp. 30C
(16) MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always max. running current.
(17) MCA must be used to select the correct field wiring size. The MCA can be regarded as the maximum running current.
(18) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
(19) TOCA means the total value of each OC set.
(20) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(21) Maximum allowable voltage range variation between phases is 2%.
(22) In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is
connected only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value.
(23) EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for
equipment with rated 75A
(24) EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input
current \> 16A and 75A per phase
(25) Ssc: Short-circuit power
(26) system impedance
(27) Multi combination (16-30HP) data is corresponding with the standard multi combination as mentioned on 3D084911
(28) For more details on standard accessories refer to Installation/operation manual
(29) In case of heat pump system, gas pipe is not used
Options
RWEYQ-T
VRV 4 Water Cooled Option list
VLQJOHXQLWV
5:(<47
5:(<47
Item
5:(<47
XQLWPXOWL
5:(<47
5:(<47
.5&$
%53$
.-%$
'7$$
.+540+
5:(<47
XQLWPXOWL
5:(<47
5:(<47
5:(<47
.+540+
.+540+
Refnet header
.+540+
Heat recovery
.+540+
.+540+
.+5407
.+5407
Heat pump
.+5407
.+5407
Refnet joint
.+5407
.+5407
Heat recovery
.+5407
.+5407
2XWGRRUXQLWPXOWLSLSLQJFRQQHFWLRQNLWIRUH/P (note 2)
2XWGRRUXQLWPXOWLSLSLQJFRQQHFWLRQNLWIRUH/R (note 2)
&RQJXUDWRUFDEOH
%+)43
%+)43
%+)43
%+)43
(.3&&$%
NOTES
1. In case of a heat recovery system, the COOL/HEAT selector can not be connected.
2. )RULQVWDOODWLRQVZLWKRXWVSHFLDOUHTXLUHPHQWVWRZDUGVUHUHJXODWLRQVWKHVWDQGDUGSLSLQJFRQQHFWLRQNLWVFDQEHXVHG
)RULQVWDOODWLRQVZLWKVSHFLDOUHTXLUHPHQWVWRZDUGVUHUHJXODWLRQVWKHLQVXODWLRQVFDQEHUHSODFHGE\XVLQJNLWV(.+%)4 (.+%)4
7KHNLWVFRQWDLQDOWHUQDWLYHLQVXODWLRQPDWHULDOZKLFKFRPSOLHVZLWK(1%6GDQGZLWK%6FODVV
7KHUHTXLUHGTXDQWLW\RI(.%+)4NLWVWRUHSODFHWKHLQVXODWLRQVLVVKRZQLQWKHWDEOHEHORZ
%+)43
%+)43
%+)43
%+)43
(.%+)4
1
2
2
(.%+)4
1
2
1
2
3D085180
Combination table
RWEYQ-T
RWEYQ8T
10HP
RWEYQ10T
RWEYQ16T
RWEYQ18T
RWEYQ20T
1
2
RWEYQ24T
RWEYQ26T
RWEYQ28T
RWEYQ30T
1
2
3
3D084911
Combination table
RWEYQ-T
VRV4 Watercooled - Indoor unit combination Restrictions
Indoor unit combination pattern
VRV* DX
indoor
VRV* DX indoor
AHU(3)
0(1)
4
0:
X:
AHU
Allowed
Not allowed
NOTES
1. O(1)
AHU connection only (combination with VRV DX indoor units is not allowed; max. 30HP = 3x 250 class EKEXV kits)
o X-control is possible (up to 3 x [EKEXV + EKEQF*box] are allowed to one outdoor unit (system)); no Variable Refrigerant Temperature control
possible
o Y-control is possible (up to 3 x [EKEXV + EKEQF*box] are allowed to one outdoor unit (system)); no Variable Refrigerant Temperature control
possible
2. AHU connection combined with VRV DX indoor units
o Z-control is possible (EKEQM* boxes are allowed limited connection ratio restrictions)
3. AHU (3) Following are considered as AHU
o EKEXV + EKEQ(M/F) + AHU coil
o Biddle aircurtains
o FXMQ_MF units
Information
- VKM is considered to be a regular VRV DX indoor unit
- VAM does not have limitation on connection as there is no refrigerant connection with the outdoor unit (only communication F1/F2)
3D085697
Capacity tables
5-1
,QRUGHUWRIXOOOPRUH\RXUUHTXLUHPHQWVRQTXLFNDFFHVVRIGDWDLQWKHIRUPDW\RXUHTXLUHZHKDYHGHYHORSHGDWRROWR
FRQVXOWFDSDFLW\WDEOHV
%HORZ\RXFDQQGWKHOLQNWRWKHFDSDFLW\WDEOHGDWDEDVHDQGDQRYHUYLHZRIDOOWKHWRROVZHKDYHWRKHOS\RXVHOHFWWKH
FRUUHFWSURGXFW
&
DSDFLW\WDEOHGDWDEDVHOHWV\RXQGEDFNDQGH[SRUWTXLFNO\WKHFDSDFLW\LQIRUPDWLRQ\RXDUHORRNLQJIRUEDVHGXSRQXQLW
PRGHOUHIULJHUDQWWHPSHUDWXUHDQGFRQQHFWLRQUDWLR
KWWSH[WUDQHWGDLNLQHXURSHFRPFDSWDE
(GDWDDSSJLYHVDFRPSOHWHRYHUYLHZRIWKH'DLNLQSURGXFWVDYDLODEOHLQ\RXUFRXQWU\ZLWKDOOHQJLQHHULQJGDWDDQG
FRPPHUFLDOLQIRLQ\RXURZQODQJXDJH'RZQORDGWKHDSSQRZ
KWWSVLWXQHVDSSOHFRPXVDSSGDLNLQHGDWDLG"PW
6HOHFWLRQVRIWZDUHDOORZV\RXWRGRORDGFDOFXODWLRQVHTXLSPHQWVHOHFWLRQVDQGHQHUJ\VLPXODWLRQVIRURXU959'DLNLQ
$OWKHUPDUHIULJHUDWLRQDQGDSSOLHGV\VWHPVSURGXFWV
KWWSH[WUDQHWGDLNLQHXURSHFRPHQVRIWZDUHGRZQORDGVGHIDXOWMVS
Capacity tables
5-2
RWEYQ-T
959:DWHUFRROHGZDWHUOWHURZLQJ
TXDQWLW\FKDUDFWHULVWLF
3D079903A
:DWHURZ>OPLQ@
4D085757
10
Capacity tables
5-2
RWEYQ-T
Water volume
Head loss
L/min
kPa
mH2O
50
9.3
1.0
60
12.9
1.3
80
26.5
1.3
96
30.9
2.7
120
47.2
4.8
150
72.2
7.4
NOTE
1. This value shows the amount of head loss per one unit
CA08A496D
11
Capacity tables
5-3
RWEYQ8T
Rate of change in cooling capacity
NOTES
/LTXLGSLSH
12.7
5. 5HDGFRROLQJKHDWLQJFDSDFLW\UDWHRIFKDQJHLQWKHDERYHJXUHVEDVHGRQWKHIROORZLQJHTXLYDOHQWOHQJWK
2YHUDOOHTXLYDOHQWOHQJWK HTXLYDOHQWOHQJWKWRPDLQSLSH[&RUUHFWLRQIDFWRU(TXLYDOHQWOHQJWKDIWHUEUDQFKLQJ
&KRRVHDFRUUHFWLRQIDFWRUIURPWKHIROORZLQJWDEOH
[ :KHQFRROLQJFDSDFLW\LVFDOFXODWHGJDVSLSHVL]H
:KHQKHDWLQJFDSDFLW\LVFDOFXODWHGOLTXLGSLSHVL]H
Rate of change
REMHFWSLSLQJ
&RROLQJJDVSLSH
+HDWLQJOLTXLGSLSH
([DPSOH5:(<47<
&RUUHFWLRQIDFWRU
6WDQGDUGVL]H
6L]HLQFUHDVH
(TXLYDOHQWOHQJWK
(TXLYDOHQW
length
,QGRRUXQLW
2XWVLGHXQLW
*DVSLSHVWDQGDUGVL]H
/LTXLGSLSHVL]HLQFUHDVH
%UDQFK
,QWKHDERYHFDVH
&RROLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
+HDWLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
7KHFRUUHFWLRQIDFWRULQ
FRROLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
KHDWLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
6. ([SODQDWLRQRIV\PEROV
Hp/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQLQIHULRUSRVLWLRQ
HM/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQVXSHULRUSRVLWLRQ
/(TXLYDOHQWSLSHOHQJWKP
&DSDFLW\FRUUHFWLRQIDFWRU
'LDPHWHURISLSHV
0RGHO
5:(<47
/LTXLGSLSH
9.5
3D062332A
12
Capacity tables
5-3
RWEYQ10,20T
Rate of change in cooling capacity
3D048283D
NOTES
/LTXLGSLSH
12.7
19.1
5. 5HDGFRROLQJKHDWLQJFDSDFLW\UDWHRIFKDQJHLQWKHDERYHJXUHVEDVHGRQWKHIROORZLQJHTXLYDOHQWOHQJWK
2YHUDOOHTXLYDOHQWOHQJWK HTXLYDOHQWOHQJWKWRPDLQSLSH[&RUUHFWLRQIDFWRU(TXLYDOHQWOHQJWKDIWHUEUDQFKLQJ
&KRRVHDFRUUHFWLRQIDFWRUIURPWKHIROORZLQJWDEOH
[ :KHQFRROLQJFDSDFLW\LVFDOFXODWHGJDVSLSHVL]H
:KHQKHDWLQJFDSDFLW\LVFDOFXODWHGOLTXLGSLSHVL]H
Rate of change
REMHFWSLSLQJ
&RROLQJJDVSLSH
+HDWLQJOLTXLGSLSH
([DPSOH5:(<47<
&RUUHFWLRQIDFWRU
6WDQGDUGVL]H
6L]HLQFUHDVH
(TXLYDOHQWOHQJWK
(TXLYDOHQW
length
,QGRRUXQLW
2XWVLGHXQLW
*DVSLSHVWDQGDUGVL]H
/LTXLGSLSHVL]HLQFUHDVH
%UDQFK
,QWKHDERYHFDVH
&RROLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
+HDWLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
7KHFRUUHFWLRQIDFWRULQ
FRROLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
KHDWLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
6. ([SODQDWLRQRIV\PEROV
Hp/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQLQIHULRUSRVLWLRQ
HM/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQVXSHULRUSRVLWLRQ
/(TXLYDOHQWSLSHOHQJWKP
&DSDFLW\FRUUHFWLRQIDFWRU
'LDPHWHURISLSHV
0RGHO
5:(<47
5:(<47
/LTXLGSLSH
9.5
15.9
13
Capacity tables
5-3
RWEYQ16,18,24,26,28,30T
Rate of change in cooling capacity
3D048284D
NOTES
/LTXLGSLSH
15.9
19.1
22.2
5. 5HDGFRROLQJKHDWLQJFDSDFLW\UDWHRIFKDQJHLQWKHDERYHJXUHVEDVHGRQWKHIROORZLQJHTXLYDOHQWOHQJWK
2YHUDOOHTXLYDOHQWOHQJWK HTXLYDOHQWOHQJWKWRPDLQSLSH[&RUUHFWLRQIDFWRU(TXLYDOHQWOHQJWKDIWHUEUDQFKLQJ
&KRRVHDFRUUHFWLRQIDFWRUIURPWKHIROORZLQJWDEOH
[ :KHQFRROLQJFDSDFLW\LVFDOFXODWHGJDVSLSHVL]H
:KHQKHDWLQJFDSDFLW\LVFDOFXODWHGOLTXLGSLSHVL]H
Rate of change
REMHFWSLSLQJ
&RROLQJJDVSLSH
+HDWLQJOLTXLGSLSH
([DPSOH5:(<47
&RUUHFWLRQIDFWRU
6WDQGDUGVL]H
6L]HLQFUHDVH
(TXLYDOHQW
length
(TXLYDOHQWOHQJWK
,QGRRUXQLW
2XWVLGHXQLW
*DVSLSHVWDQGDUGVL]H
/LTXLGSLSHVL]HLQFUHDVH
%UDQFK
,QWKHDERYHFDVH
&RROLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
+HDWLQJ2YHUDOOHTXLYDOHQWOHQJWK P[P P
7KHFRUUHFWLRQIDFWRULQ
FRROLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
KHDWLQJFDSDFLW\ZKHQ+S PLVWKXVDSSUR[LPDWHO\
6. ([SODQDWLRQRIV\PEROV
Hp/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQLQIHULRUSRVLWLRQ
HM/HYHOGLIIHUHQFHPEHWZHHQLQGRRUDQGRXWVLGHXQLWVZKHUHLQGRRUXQLWLQVXSHULRUSRVLWLRQ
/(TXLYDOHQWSLSHOHQJWKP
&DSDFLW\FRUUHFWLRQIDFWRU
'LDPHWHURISLSHV
0RGHO
RWEYQ16T
5:(<47
5:(<47
14
/LTXLGSLSH
12.7
15.9
19.1
Dimensional drawings
RWEYQ-T
Top View
8x 17
(Foundation Bolt Hole)
Bottom View
6
(After attaching
accessories pipe)
Front View
Manufacturers
label
Item
Part Name
Remark
Liquid Pipe
See note 2
See note 2
See note 2
Water Inlet
Water Outlet
Drain Outlet
Earth Terminal
M5
29
29
10
11
Grounding terminal
3D085178
NOTES
Heat Pump
9.5
19.1
RWEYQ8
Heat Recovery
9.5
19.1
15.9
Heat Pump
9.5
22.2
RWEYQ10
Heat Recovery
9.5
22.2
19.1
15
Centre of gravity
RWEYQ8T
RWEYQ10T
Center of foundation
bolt hole
Center of foundation
bolt hole
Front view
Center of foundation
bolt hole
Side view
4D048289F
16
Piping diagrams
RWEYQ8-10T
Filter
Solenoid valve
Check valve
Filter
Electronic
expansion
valve
Solenoid valve
Heat
exchanger
pipe
Check valve
Capillary
tube
Low
SENPL pressure
sensor
Filter
Oil
separator
Solenoid valve
Filter
Solenoid valve
Strainer
Check valve
Gauge port
DUHFRQQHFWLRQ
Filter
Four way
valve
Capillary
tube
Receiver
Fusible plug
Compressor
6WRSYDOYHZLWKVHUYLFHSRUWRQRQVLWHSLSLQJVLGHPPDUHFRQQHFWLRQ
Pressure
regulating valve
Capillary
tube
Gauge port
DUHFRQQHFWLRQ
Capillary
tube
Service port
Filter
Electronic
expansion
valve
Solenoid valve
Filter
Plate heat
exchanger
Water inlet
4D048290D
17
Wiring diagrams
9-1
RWEYQ8-10T
Power supply
(Note 4)
On
Off
Operation output
(Note 9)
Is connector color for printed circuit board.
Is connector color for component.
Is discrimination color for component lead wire.
Cool/heat selector
in-out
out-out out-multi
(Note 5)
Cool
Heat
Cool
Heat
Fan
Cool/heat selector (optional accessory)
outdoor (Q1)(Q2)
outdoor (F1)(F2)
indoor (F1)(F2)
Interlock
(Note 8)
Detail of mic
El.compo.box
A1P
A2P
A3P
A4P
BS1 ~5
C63, C66
DS1
E1HC
F1U
F1U, F2U
H1P ~8P
HAP
K1M
K1R
K3R
K5R
K6R
K7R
K8R
K9R
K10R
K11R
K12R
K13R
L1R
M1C
M1F, M2F
PS
Q1RP
R50, R59
R95
R1T
R2T
R3T
R4T
R5T
R6T
S1NPH
S1NPL
S1PH
T1A
T1R
V1CP
V1R
V2R
X1A, X3A
X1M
X1M
X2M
X3M
X4M
Y1E
Y3E
Y1S
Y2S
Y3S
Y4S
Y5S
Y6S
Y7S
Z1C
Z1F
S1S
S2S
Cool/heat selector
Selector switch (fan / cool-heat)
Selector switch (cool/heat)
NOTES
2P350961
18
10
Power supply
Main
Switch
Outside units
2 Wires cables
(Transmission line)
[Unit 1]
Switch
Fuse
Switch
Switch
Fuse
Fuse
[Unit 2]
:KHQWKHSRZHUVRXUFHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV!
Power supply
Main
Switch
Outside units
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
[Unit 1]
[Unit 3]
[Unit 2]
2 Wires cables
(Transmission line)
[Unit 3]
10
Switch
Fuse
Power supply
Power supply
Main
Switch
Main
Switch
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
2 Wires cables Fuse
(Power line)
BS Units
2 Wires cables
(Transmission line)
Switch
2 Wires cables Fuse
(Power line)
Indoor Units
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
2 Wires cables
(Power line)
Switch
Fuse
Fuse
2 Wires cables
2 Wires cables
(Power line)
(Power line)
Cooling only unit
Switch
2 Wires cables Fuse
(Power line)
BS Units
2 Wires cables
(Transmission line)
Switch
2 Wires cables Fuse
(Power line)
Indoor Units
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
Cooling only unit
3D048823E
NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.
Use copper conductors only.
As for details, see wiring diagram.
Install circuit breaker for safety.
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
Unit shall be grounded in compliance with the applicable local and national codes.
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
Be sure to install the switch and the fuse to the power line of each equipement.
Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
19
10
Power supply
Main
Switch
10
Outside units
Main
Switch
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
[Unit 2]
[Unit 3]
[Unit 1]
Switch
Switch
Fuse
Fuse
:KHQWKHSRZHUVRXUFHLVFRQQHFWHGLQVHULHVEHWZHHQWKHXQLWV!
Power supply
Outside units
2 Wires cables
(Transmission line)
[Unit 1]
Switch
[Unit 2]
2 Wires cables
(Transmission line)
[Unit 3]
Switch
Fuse
Fuse
Power supply
Power supply
Main
Switch
Main
Switch
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
Switch
Switch
Fuse
Fuse
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Transmission line)
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Transmission line)
Switch
Switch
Fuse
Fuse
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Transmission line)
Switch
Fuse
2 Wires cables
(Power line)
2 Wires cables
(Power line)
2 Wires cables
(Power line)
2 Wires cables
(Power line)
Indoor Units
2 Wires cables
(Power line)
2 Wires cables
(Power line)
2 Wires cables
(Power line)
2 Wires cables
(Power line)
Indoor Units
3D048824E
NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
20
All wiring, components and materials to be procured on the site must comply with the applicable local and national codes.
Use copper conductors only.
As for details, see wiring diagram.
Install circuit breaker for safety.
$OOHOGZLULQJDQGFRPSRQHQWVPXVWEHSURYLGHGE\OLFHQVHGHOHFWULFLDQ
Unit shall be grounded in compliance with the applicable local and national codes.
:LULQJVKRZQDUHJHQHUDOSRLQWVRIFRQQHFWLRQJXLGHVRQO\DQGDUHQRWLQWHQGHGIRURUWRLQFOXGHDOOGHWDLOVIRUDVSHFLFLQVWDOODWLRQ
Be sure to install the switch and the fuse to the power line of each equipement.
Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the equipment utilizing the multiple power sources.
,IWKHUHH[LVWVWKHSRVVLELOLW\RIUHYHUVHGSKDVHORVHSKDVHPRPHQWDU\EODFNRXWRUWKHSRZHUJRHVRQDQGRIIZKLOHWKHSURGXFWLVRSHUDWLQJDWWDFKDUHYHUVHGSKDVHSURWHFWLRQFLUFXLWORFDOO\
5XQQLQJWKHSURGXFWLQUHYHUVHGSKDVHPD\EUHDNWKHFRPSUHVVRUDQGRWKHUSDUWV
11
Sound data
3
Octave band sound pressure level dB (0dB = 0.0002 bar)
RWEYQ10T
Approximate
threshold hearing for
continuous noise
11
Approximate
threshold hearing for
continuous noise
4D048340D
4D062222A
NOTES
NOTES
21
12
Installation
12 - 1 Service Space
500 or more
12
For installation
in a row
Service space
(rear)
Service space
(rear)
Outside unit
Outside unit
500 or more
RWEYQ-T
390 or more
Outside unit
Water piping
installation space
Secure enough
space for removing
front plate
350 or less
20 or more
Space for
installation in
a row
20 or more
Space for
installation in
a row
350 or more
20 or more
Space for
installation in
a row
Service space
(front)
20 or more
Space for
installation in
a row
20 or more
Space for
installation in
a row
100 or more
Front view
250 or less
22
Service space
(front)
300 or more
Service space
(front)
900 or more
H: free
W: 179 mm
900 or more
3D048341F
12
Installation
RWEYQ-T
VRV4 Watercooled Field Piping Restrictions (1/3)
Maximum piping length
Reference drawing see page 2/3
Total
Piping
Length
Longest pipe
(A+[B,J])
Actual / (Equivalent)
$IWHUUVWEUDQFK
(B,J)
Actual
120/(140)m
40 m(1)
10/(13)m
50/(40)m
15m
2m
300m
50/(55)m(2)
120/(140)m
120/(140)m
40 m
40 m
10/13m
10/13m
40/(40)m
40/(40)m
40/(40)m
15m
15m
2m
2m
300m
300m
Standard
Only VRV DX indoor connected
Standard multi combination
Pair
Multi(3)
Mix(4)
AHU connection
$IWHUUVWEUDQFKIRU
outdoor multi (D)
2XWGRRUDERYHLQGRRU
Actual / (Equivalent)
Indoor to indoor
(H2)
Outdoor to outdoor
(H3)
12
LQGRRUDERYHRXWGRRU
NOTES
For standard multi combinations; see 3D084911
(1) Extension is possible if all below conditions are met (limitation can be extended up to 90m)
D7KHSLSLQJOHQJWKEHWZHHQDOOLQGRRUWRWKHQHDUHVWEUDQFKNLWLVP
E,WLVQHFHVVDU\WRLQFUHDVHWKHSLSHVL]HRIWKHJDVDQGOLTXLGSLSLQJLIWKHSLSHOHQJWKEHWZHHQWKHUVWDQGWKHQDOEUDQFKNLWLVRYHUP
If the increased pipe size is larger than the pipe size of the main pipe, then the pipe size of the main pipe has to be increased as well.
F:KHQWKHSLSLQJVL]HLVLQFUHDVHGEWKHSLSLQJOHQJWKKDVWREHFRXQWHGDVGRXEOH7KHWRWDOSLSLQJOHQJWKKDVWREHZLWKLQOLPLWDWLRQVVHHWDEOHDERYH
G7KHSLSLQJOHQJWKGLIIHUHQFHEHWZHHQWKHQHDUHVWLQGRRUIURPUVWEUDQFKWRWKHRXWGRRUXQLWDQGIDUWKHVWLQGRRUWRWKHRXWGRRUXQLWLVP
(2) The allowable minimum length is 5 m.
8VLQJVHYHUDO$+8(.(;9(.(4NLWV
0L[RI$+8DQG959';LQGRRU
3D085696
RWEYQ-T
VRV4 Watercooled Field Piping Restrictions (2/3)
VRV Watercooled
VRV indoor
AHU
AHU
VRV indoor
NOTES
AHU connection
Pair
P
5m
Multi (1)
P
5m
Mix (2)
P
5m
NOTES
3D085696
23
12
Installation
Total
Allowable capacity
capacity
12
50~130%
50~110%(2)
90~110%(2)
VRV DX indoor
AHU
50~130%
50~110%
-
0~110%
90~110%
NOTES
1. When using AHU connection: see EKEXV kit as an indoor unit for counting the total number of indoor units
2. Restrictions by air handling unit capacity
3. Pair AHU = system with 1 AHU connected to one watercooled unit // Multi AHU = system with several AHU connected to 1 watercooled unit system
I. FXMQ_MF model is considered as an AHU, following AHU limitations and respecting additional limitations:
0D[LPXP);04B0)FRQQHFWLRQUDWLR&5ZKHQFRPELQHGZLWK959';LQGRRUXQLWV&5
0D[LPXP);04B0)FRQQHFWLRQUDWLR&5ZKHQRQO\$+8LVXVHG&5
RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI);04B0)XQLW
II. Biddle aircurtain is considered as an AHU, following AHU limitations
RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI%LGGOHXQLW
Ill. [EKEXV + EKEQ] combined with AHU is considered as an AHU, following AHU limitations
RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI(.(;9(.(4XQLW
IV. VKM is considered to be a regular VRV DX indoor unit
RSHUDWLRQUDQJHLQIRUPDWLRQVHHVSHFLFDWLRQVRI9.0XQLW
V. VAM does not have limitations on connection as there is no refrigerant connection with the watercooled unit (only communication F1/F2; so counting in # indoor units)
3D085696
24
12
Installation
Example:
Downstream capacity for E=capacity index of unit 1
Downstream capacity for D=capacity index of unit 1+capacity index of
unit 2
a
D
B
C y
3
H
1,2
3
a,b,c
x,y
1
2
3
4
5
Choose from the following table in accordance with the outdoor unit total
capacity type, connected downstream.
Piping outer diameter size (mm)
Suction gas pipe
19.1
22.2
Liquid pipe
9.5
28.6
12.7
15.9
22.2
34.9
19.1
28.6
8+10
16
18+20+24
26+30
Choose from the following table in accordance with the indoor unit total
capacity type, connected downstream. Do not let the connection piping
exceed the refrigerant piping size chosen by the general system model name.
Piping outer diameter size (mm)
Suction gas pipe
Liquid pipe
15.9
19.1
9.5
22.2
12.7
28.6
15.9
34.9
19.1
41.3
Size up
Liquid size (mm)
9.5 12.7
12.7 15.9
15.9 19.1
19.1 22.2
The pipe thickness of the refrigerant piping shall comply with the
applicable legislation. The minimal pipe thickness for R410A piping
must be in accordance with the table below.
Pipe (mm)
6.4
9.5
12.7
15.9
19.1
22.2
28.6
34.9
41.3
Indoor unit
capacity index
<150
150x<200
200x<290
290x<420
420x<640
640x<920
920
Outdoor unit
Main pipes
Increase only liquid pipe size
First refrigerant branch kit
Indoor unit
HP Class
8
10
16
18+20
24
26+30
Outdoor unit
capacity type
(HP)
When the equivalent pipe length between outdoor and indoor units
is 80 m or more, the size of the main liquid pipe must be increased.
Depending on the length of the piping, the capacity may drop, but
even in such a case it is possible to increase the size of the main
pipe.
INFORMATION
12
Pipe size for direct connection to indoor unit must be the same as the
connection size of the indoor unit.
Indoor unit capacity index
15, 20, 25, 32, 40, 50
63, 80, 100, 125
200
250
In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the following
into account:
25
12
Installation
Refrigerant Refnets
For piping example, refer to "Selection of piping size" .
12
2 pipes
KHRQ22M29T9
KHRQ22M64T
KHRQ22M75T
3 pipes
KHRQ23M29T9
KHRQ23M64T
KHRQ23M75T
For Refnet joints other than the first branch (e.g. Refnet joint b),
select the proper branch kit model based on the total capacity index
of all indoor units connected after the refrigerant branch.
When using Refnet joints at the first branch counted from the
outdoor unit side, choose from the following table in accordance with
the capacity of the outdoor unit (e.g. Refnet joint a).
2 pipes
KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
KHRQ22M75T
Make sure to perform the piping installation within the range of the
maximum allowable pipe length, allowable level difference and allowable
length after branching as indicated below.
Definitions
Actual piping length: pipe length between outdoor1 and indoor units.
Equivalent piping length2: pipe length between outdoor(1) and indoor
units.
Total piping length: total piping length from the outdoor(1) to all indoor
units.
Difference in height between outdoor and indoor units: H1
Difference in height between indoor and indoor units: H2
Difference in height between outdoor and outdoor units: H3
3 pipes
KHRQ23M20T
KHRQ23M29T9
KHRQ23M64T
KHRQ23M75T
2 pipes
KHRQ22M29H
KHRQ22M29H
KHRQ22M64Ha
KHRQ22M75H
3 pipes
KHRQ23M29H
KHRQ23M29H
KHRQ23M64H(a)
KHRQ23M75H
If the pipe size above the Refnet header is 34.9 or more, KHRQ22M75H/
KHRQ23M75H is required.
INFORMATION
Maximum 8 branches can be connected to a header.
BHFQ22P1007
BHFQ22P1517
BHFQ23P907
BHFQ23P1357
NOTICE
Refrigerant branch kits can only be used with R410A.
1.
2.
If the system capacity is >10HP, re-read "the first outdoor branch as seen
from the indoor unit".
Assume equivalent piping length of Refnet joint=0.5 m, Refnet
header=1 m, BSVQ100/160=4 m and BSVQ250=6 m (for calculation
purposes of equivalent piping length, not for refrigerant charge
calculations).
4PEN347465-1A(2)
26
12
Installation
RWEYQ-T
B1
j
1
Unit
BS units Indoor units
( B1 - B4 ) ( 1 - 8 )
l B2
k
G
B3
o
4
B4
REFNET header
q
5
H1
Cooling only
( 7 8 )
Unit
7 H2
B2
f
g
B1
F
k
G
First outdoor h 1
branch
3 4
f
B2
Cooling only
( 5 6 )
B1
7 H2
H1
H3
e
B2
B3
B4
f
1
t
s
Cooling only
( 7 8 )
l
6
8 H2
7
H1
Unit 1
Unit
BS units Indoor units
( B1 - B6 ) ( 1 - 8 )
12
B5
l
B6
k
5
H2
H1
Heat recovery system
( 1 - 6 )
4
Cooling only
( 7 8 )
Example 1.3
REFNET header
Indoor units
( 1 - 8 )
Heat recovery system
( 1 - 4 , 7 8 )
f B3 h B4
B1
B2
e g
c
i
B5
j
B6
k
6
Heat recovery
system ( 1 - 6 )
7 H2
8
Cooling only
( 7 8 )
H1
H3
Example 2.2
BS units
( B1 - B6 )
Indoor units
( 1 - 8 )
Unit 1
Cooling only
( 5 6 )
H3
Example 2.1
j
B4
BS units
( B1 - B5 )
p
o
REFNET header
B5 n
B
B3
e
1
H2
d
B1
b
r
Unit 1
B4
Refnet header
p
B3
e
D
REFNET header
Example 1.2
d
C
B2
B4
Indoor units
BS units ( B1 - B5 ) ( 1 - 8 )
Indoor unit
Refnet joint
i
B3
f
1
H1
B5 n
e
B1
Example 1.1
Multi outdoor unit
system
m
A
Example 2.3
Refnet joint
Connection to BS unit
BS units
3-pipe
Indoor units
2-pipe
Outdoor
unit side
HP/LP gas
Indoor
unit side
Suction gas
Gas piping
Liquid
Liquid
piping
Refnet header
First outdoor branch
First outdoor branch
First outdoor branch
First outdoor branch
BS unit
u
Maximum allowable length
(2)
Equivalent length
Total piping length
120 m
140 m
300 m
Example 1.2
unit 4: a+b+i+j120 m
unit 5: a+b+k120 m
unit 8: a+m+n+p120 m
Example 1.1
unit 8: a+b+c+d+e+s120 m
Example 2.1
unit 8: a+b+c+d+e+s120 m
Example 1.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+o+p+q+r+s
300 m
Example 1.3
unit 8: a+o120 m
unit 4: a+h+i120 m
Example 2.1
a+b+c+d+e+f+g+h+i+j+k+l+m+n+o+p+q+r+s
300 m
Between outdoor branch and outdoor unit (only in case >10 HP)
10 m
Equivalent length
13 m
Example 3
r, s, t10 m; u5 m
4PEN347465-1A(3)
27
12
Installation
12
The pipe length from the first refrigerant branch kit to the indoor unit 40 m.
Example 1.1: unit 8: b+c+d+e+s40 m
Example 1.2: unit 5: b+k40 m, unit 8: m+n+p40 m
Example 1.3: unit 8: o40 m
However, extension is possible if all below conditions are met. In this case
limitation can be extended up to 90 m.
The piping between the outdoor units must be routed level or slightly
upward to avoid the risk of oil retention into the piping.
Pattern 1
2
b
c
B
d
C
e
D
f
E
p H1
7
H2
The piping length between all indoor to the nearest branch kit is
40 m.
3
1
c.
Example: h, i, j p40 m
b.
g
F
1 Outdoor units
2 Refnet joints (A~G)
3 Indoor unit (1~8)
a.
Pattern 2
When the piping size is increased (step b), the piping length has
to be counted as double (except for the main pipe and the pipes
that are not increased in pipe size).
For the gas piping (both discharge and suction gas pipings in case
of the heat recovery system) after the branch, install a trap of
200 mm or larger using the piping included in the piping kit for
connecting the outdoor unit. Otherwise, the refrigerant may stay in
the piping, causing damage to the outdoor unit.
The total piping length has to be within limitations (see table above).
Example: a+b*2+c*2+d*2+e*2+f*2+g*2+h+i+j+k+l+m+n+p300 m.
d.
1
1 200 mm
If the piping length between the outdoor unit connecting pipe kit or
between the outdoor units exceeds 2 m, create a rise of 200 mm or
more in the gas line within a length of 2 m from the kit.
If 2 m
2
1
1 To indoor unit
2 2 m
3 Piping between outdoor units
If 2 m
4
2
1
2
3
4
1.
To indoor unit
2 m
Rising height: 200 mm
2 m
4PEN347465-1A(4)
28
13
Operation range
RWEYQ-T
+($7380323(5$7,21
5DQJHIRUFRQWLQXRXV
operation
5DQJHIRUZDUPLQJXSRSHUDWLRQ
5DQJHIRURSHUDWLRQ
Heating
,QOHWZDWHUWHPSHUDWXUH&
5DQJHIRUFRQWLQXRXV
operation
,QOHWZDWHUWHPSHUDWXUH&
Cooling
13
5DQJHIRURSHUDWLRQ
,QGRRUWHPSHUDWXUH&:%
,QGRRUWHPSHUDWXUH&'%
NOTES
3D085182
29
13
Operation range
RWEYQ-T
+($75(&29(5<23(5$7,21
5DQJHIRUFRQWLQXRXV
operation
,QOHWZDWHUWHPSHUDWXUH&
5DQJHIRUSXOOGRZQRHSUDWLRQ
5DQJHIRURSHUDWLRQ
Heating range
13
Cooling range
2SHUDWLRQUDQJHH[WHQVLRQLQFDVH
RI*O\FROLVXVHGLQFRPELQDWLRQ
ZLWKHOGVHWWLQJV6HHLQVWDOODWLRQ
PDQXDO
+HDWLQJXQLW&'%
&RROLQJXQLW&:%
,QGRRUWHPSHUDWXUH
NOTES
30
3D085183
The present leaflet is drawn up by way of information only and does not
constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.
has compiled the content of this leaflet to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products
and services presented therein. Specifications are subject to change
without prior notice. Daikin Europe N.V. explicitly rejects any liability for
any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.
BARCODE
Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende