Busduct System

Schneider Busway

Common Application of Busduct


Transformer to Switchboard

Schneider Busway

Common Application of Busduct


Horizontal Plug-in Busduct
Large Scale Factory, e.g. HAECO

Schneider Busway

Common Application of Busduct


Vertical Plug-in Riser
Typical Comm., Ind., Res. in HK

Schneider Busway

Common Application of Busduct


Switchboard to Switchboard
Example: Main Sw Bd to A/C Plant

Schneider Busway

Basic Construction of Busduct


Sandwich type construction
Less space requirement
Improve heat dissipation
Reduce temperature rise
Higher current rating available
Various IP rating available

Schneider Busway

High Grade Copper Busbar


High conductivity copper
Silver plated over full length, enhance low
contact resistance and high conductivity
Thickness of copper bar = 6.3 mm
Rectangular design enhance heat dissipation

Schneider Busway

Temperature Rise
Sandwich construction and high conductivity
copper busbar temp.rise less than 55oC at
full load

Schneider Busway

Busbar Insulation
2 layers 0.2mm Mylar insulation
(IEC requires 1 layer)
Excellent dielectric properties
0.1mm Mylar can withstand 7000V
Class B insulation (130oC)

Schneider Busway

Integral Ground Bus


1.6mm Aluminum enclosure
as ground bus
50% continuous capacity
Lower ground impedance
Comply with international
requirement, UL, IEC, IEE
wiring regulation

Schneider Busway

EZ Joint Pak
Schneider Patten Design
Single bolt connection
Double head
Visible tighten torque
Belleville washer
Tighten torque = 105N-m (70
lb-ft)

Schneider Busway

EZ Joint Pak
Electroplated surface reduce
contact resistance
Each joint pak allows 3 mm
adjustment for thermal
expansion
Reduce installation time and
equipment
Improve reliability

Schneider Busway

Product Range
Feeder, Riser , Plug-in
Common Rating 200A-600A & 800A-5000A
Rated Voltage = 600V
IP rating:
Feeder : IP40, IP41, IP54, IP65, IP66
Plug-in / Riser : IP40, IP54

Schneider Busway

Common Fitting
Elbows
Standard 90o

Schneider Busway

Common Fitting
Elbows
Other shape available upon request e.g.
Double elbows, Offset, Elbow + flanged end

Schneider Busway

Common Fitting
Flanged End
For connection to Switchboard
For connection cable to busduct

Schneider Busway

Common Fitting
Expansion Joint
Allow 38mm expansion
Apply where busduct pass through structural
expansion joint

Schneider Busway

Vertical Hangers
Fixed hangers
Spring Hangers
Apply in new building
Eliminate the effect of
settlement

Schneider Busway

Plug-in Units
Fusible PIU (30A-1600A)
MCCB PIU (16-1600A)

Schneider Busway

Plug-in Units
High level of safety
Complete insulated conductor
Interlocks
Contact earth terminal first

Schneider Busway

System Design
Cable Vs busduct
Choice of breaking capacity, IP rating
Earthing system arrangement
Voltage drop consideration
Provision for expansion
Harmonic issue

Schneider Busway

Cable Vs Busduct
Busduct system have advantage in high ampere
range, say 600A or up
Comparison between cable & busduct
Cable

Busduct

Space requirement

High

Low

Heat Dissipation

Poor

Good

Temperature rise

Poor

Good

Voltage Drop

High

Fair

Electromagnetic Interference

High

Low

Labour Cost

Higher

Lower

Schneider Busway

Choice of Breaking Capacity


Breaking Capacity
Main distribution Vs Submain Distribution
1 sec and 3 sec requirement

Schneider Busway

Choice of IP Rating
Minimize water hazard
Horizontal Vs Vertical
Corridor Vs meter room

Schneider Busway

Earthing System Arrangement


IGB through out the whole run of busduct
No need for additional or external earthing
conductor
Each tap-off box bond to IGB

Schneider Busway

Voltage Drop Consideration


4% Voltage drop from source to final circuit
(IEE Wiring Regualtion)
Longer the busduct length, Higher the voltage
drop
Try to shorten length of busduct
Upgrade the busduct, e.g use 1200A busduct
for 1000A circuit

Schneider Busway

Provision of Expansion
Thermal expansion
Busbar thermal expansion absorbed by joint
pack
No need to install any expansion joint
Structural expansion
Busduct cannot absorb expansion
Shear force can damage busduct
Expansion fitting should be installed

Schneider Busway

Harmonic Issues
Generated by Non-linear load, e.g. UPS,
Inverters, High frequency lamps
Can overheat neutral conductor
Alter the operation of Tx, Capacity bank
Affect the normal operation of switchgear
nuisance tripping
200% neutral busduct cannot solve the
problem
Apply power control equipment, like harmonic
filter OR Upgrade the whole busduct
Schneider Busway

Installation Procedure
Video of Installation (about 8 minutes)

Schneider Busway

Water / Dust Precaution


Provide alternative path / heating point
Damage insulation
Latent hazard of short circuit
Measurement
Double packing (plastic bag+carton box)
Apply rain coat provided by manufacturer
after installation each day
Proper storage management

Schneider Busway

Water / Dust Precaution


Double packing (plastic bag+carton box)

Schneider Busway

Water / Dust Precaution


Double packing (plastic bag+carton box)

Schneider Busway

Water / Dust Precaution


Apply rain coat provided by manufacturer
after installation each day

Schneider Busway

Water / Dust Precaution


Proper storage management

Schneider Busway

Quality Project Management Services


Product Training
Site Measurement
Optimum busduct routing design
Detail shop drawing preparation
On site technical support
Training on installation procedure
Missing Link and Remedial Units
Joint inspection (not contractual service)

Schneider Busway

Missing Links / Remedial Units


Missing link reserve 1 pc of busduct for final measurement
Increase accuracy of busudct dimension
Save time for rectifying installation mistake
Streamline the installation

Missing Link

Schneider Busway

Missing Links / Remedial Units


A neighborhood factory enhance fast delivery of
missing links and remedial units (within 1 week
delivery to HK)

Schneider Busway

Contractor-Supplier Interaction
Project Start

Technical support
and routing deisgn

After sales services


and missing links

AutoCad Drawing

Installation support

We are not only a


busduct supplier

Project
Management
Support

BRASS and
manufacturing
instruction

Fabrication
Schneider Busway

Testing & Commissioning - Factory


Factory Test 7500V dc Hi-pot
Test
100% test before delivery
Insulation = 10M/ ft
(IEC require 1M/ ft )
Check weak point of insulation

Schneider Busway

Testing & Commissioning On Site


Mega test before any energization
NEMA:
M =100/ Length of Busduct in Ft (1000V)
HK Code of Practice
0.5 M at 500Vdc
Ductile test of entire length
Joint inspection by both contractor and supplier
Alignment, Installation procedure,etc

Schneider Busway

Maintenance Issues
Vertical spring hanger adjustment
Bowing Symptom
Thermal checking/ scanning

Schneider Busway

Vertical Spring Hanger Adjustment


Adjustment need after a period of usage, esp
new building
Make compensation for settlement and
concrete shinkage

Schneider Busway

Vertical Spring Hanger Adjustment


Adjust the length of spring to provide adequate
vertical support to busduct

Schneider Busway

Bowing Symptom

Schneider Busway

Bowing Symptom
Common causes
Misalignment
Improper installation, e.g. loosen bolts
Improper vertical support
Uneven pressure or expansion force the
busduct to bend at weak points
Bowing can make permanent deforming of
busduct

Schneider Busway

Thermal Checking / Scanning


Improper installation poor contact
Abnormal temperature rise (usually
happened in joints)
Collect temperature data and compare
Find out the abnormal heating point and
rectify

Schneider Busway

Trouble shooting
Common causes of burnt busduct
Water/dust ingress during installation stage
Water ingress after energize (for IP40
mainly)
Improper installation, e.g. misalignment,
lossen bolts
Some real examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Some Real Examples

Schneider Busway

Trouble Shooting
Recommend spare parts
1 pair of flanged ends for each busduct
rating used
A number of plug-in units
24-hours services hotline provided by
Schneider Busway
7298 9771(for HK Market)

Schneider Busway

End of Presentation!
Thank you!

Schneider Busway