Honeywell Process Solutions

MasterLogic PLC
Software Change Notice
R220
July 2012

Release 220
Honeywell

Notices and Trademarks


Copyright 2012 by Honeywell International Srl.
Release 220 July, 2012

While this information is presented in good faith and believed to be accurate, Honeywell disclaims
the implied warranties of merchantability and fitness for a particular purpose and makes no
express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The
information and specifications in this document are subject to change without notice.
Honeywell, PlantScape, Experion, and TotalPlant are registered trademarks of Honeywell
International Inc.
Other brand or product names are trademarks of their respective owners.

Honeywell Process Solutions


1860 W. Rose Garden Lane
Phoenix, AZ 85027 USA
1-800 822-7673

ii

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

About This Document


This document contains information related to MasterLogic PLC software and firmware releases
only for ML-200R. It is recommended that user fully understands the notices covered in this
document before start working with the MLPLC.

Release Information
Document Name

Document
ID

Release
Number

Publication
Date

R220

July 2012

MasterLogic PLC Software Change Notice

Reference
Document

Model Number

ML200 CPU and SoftMaster Users Guide

R220
July 2012

Analog Input Module 2MLF-AV8A, AC8A


User's Guide

ML200-AI

Analog Output Module 2MLF DV4A/8A,


2MLF DC4A/8A User's Guide

ML200-AO

Digital Input/Output Modules ML 200


DI/DO Module User's Guide

ML200 - DI/DO

Fast Ethernet I/F Module 2MLL-FEnet


User's Guide

ML200 Fenet

2MLF-HO2A, 2MLF-HD2A High Speed


Counter Module User's Guide

2MLF-HO2A, 2MLFHD2A

MasterLogic PLC Instruction List

ML200-IL

Isolated Analog Input Module 2MLFAD4S User's Guide

ML200-IAI

Isolated Analog Output Module 2MLFDV4S, 2MLF-DC4S User's Guide

ML200-IAO

MasterLogic PLC Software Change Notice


Honeywell

iii

Support and Other Contacts

Document

iv

Model Number

Isolated Thermocouple Input Module


TC4S User's Guide

ML200-ITIM

Profibus-DP Pnet I/F Module 2MLLPMEA User's Guide

ML200-PMEA

Resistance Temperature Detector 2MLFRD4A User's Guide

ML200-RTD

Serial Communication I/F Module 2MLLC22A, 2MLL-CH2A, 2MLL-C42A User's


Guide

ML200-Snet

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

Support and Other Contacts

Support and Other Contacts


United States and Canada
Contact:
Phone:

Fascimile:
Mail:

Honeywell Solution Support Center


1-800-822-7673
Calls are answered by dispatcher between 6:00 am and 4:00 pm
Mountain Standard Time. Emergency calls outside normal working hours
are received by an answering service and returned within one hour.
1-973-455-5000
Honeywell TAC, MS L17
1860 W. Garden Lane
Phoenix, AZ, 85027 USA

Europe, Middle East, and Africa (EMEA)


Contact:
Phone:
Fascimile:
Mail:

Honeywell TAC-EMEA
+32-2-728-2345
+32-2-728-2696
TAC-BE02
Hermes Plaza
Hermeslaan, 1H
B-1831 Diegem, Belgium

Contact:
Phone:

Honeywell Global TAC Pacific


1300-364-822 (toll free within Australia)
+61-8-9362-9559 (outside Australia)
+61-8-9362-9564
Honeywell Limited Australia
5 Kitchener Way
Burswood 6100, Western Australia
GTAC@honeywell.com

Pacific

Fascimile:
Mail:

Email:

India
Contact:
Phone:
Fascimile:
Mail:

Email:

R220
July 2012

Honeywell Global TAC India


+91-20- 6603-9400
+91-20- 6603-9800
Honeywell Automation India Ltd
56 and 57, Hadapsar Industrial Estate
Hadapsar, Pune 411 013, India
Global-TAC-India@honeywell.com

MasterLogic PLC Software Change Notice


Honeywell

Support and Other Contacts

Korea
Contact:
Phone:
Fascimile:
Mail:

Email:

Honeywell Global TAC Korea


+82-80-782-2255 (toll free within Korea)
+82-2-792-9015
Honeywell Co., Ltd
4F, Sangam IT Tower
1590, DMC Sangam-dong, Mapo-gu
Seoul, 121-835, Korea
Global-TAC-Korea@honeywell.com

Peoples Republic of China


Contact:
Phone:

Mail:

Email:

Honeywell Global TAC China


+86- 21-2219-6888
800-820-0237
400-820-0386
Honeywell (China) Co., Ltd
33/F, Tower A, City Center, 100 Zunyi Rd.
Shanghai 200051, Peoples Republic of China
Global-TAC-China@honeywell.com

Singapore
Contact:
Phone:
Fascimile:
Mail:

Email:

Honeywell Global TAC South East Asia


+65-6580-3500
+65-6580-3501
+65-6445-3033
Honeywell Private Limited
Honeywell Building
17, Changi Business Park Central 1
Singapore 486073
GTAC-SEA@honeywell.com

Taiwan
Contact:
Phone:
Fascimile:
Mail:

Email:

vi

Honeywell Global TAC Taiwan


+886-7-536-2567
+886-7-536-2039
Honeywell Taiwan Ltd.
17F-1, No. 260, Jhongshan 2nd Road.
Cianjhen District
Kaohsiung, Taiwan, ROC
Global-TAC-Taiwan@honeywell.com

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

Support and Other Contacts

Japan
Contact:
Phone:
Fascimile:
Mail:

Email:

Honeywell Global TAC Japan


+81-3-6730-7160
+81-3-6730-7228
Honeywell Japan Inc.
New Pier Takeshiba, South Tower Building,
20th Floor, 1-16-1 Kaigan, Minato-ku,
Tokyo 105-0022, Japan
Global-TAC-JapanJA25@honeywell.com

Elsewhere
Call your nearest Honeywell office.

World Wide Web


Honeywell Solution Support Online:
http://www.honeywellprocess.com

Training Classes
Honeywell Automation College:
http://www.automationcollege.com

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

vii

Symbol Definitions

Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol

Definition
ATTENTION: Identifies information that requires special
consideration.

TIP: Identifies advice or hints for the user, often in terms of


performing a task.

CAUTION

Indicates a situation which, if not avoided, may result in equipment


or work (data) on the system being damaged or lost, or may result in
the inability to properly operate the process.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used
to alert against unsafe practices.
CAUTION symbol on the equipment refers the user to the product
manual for additional information. The symbol appears next to
required information in the manual.
WARNING: Indicates a potentially hazardous situation, which, if not
avoided, could result in serious injury or death.
WARNING symbol on the equipment refers the user to the product
manual for additional information. The symbol appears next to
required information in the manual.

viii

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

Contents
1.

BEFORE YOU BEGIN ...................................................................11


1.1

Review the latest information ..................................................................... 11


Checking for updates ...............................................................................................11

1.2

2.

Overview ....................................................................................................... 11

ABOUT THIS RELEASE ...............................................................13


2.1

Components of this release ........................................................................ 13

2.2

Hardware and software compatibility matrix............................................. 13

2.3

Hardware list ................................................................................................. 14

2.4

New features in this release ........................................................................ 18


Firmware 2.10 ..........................................................................................................18
SoftMaster 3.63 ........................................................................................................18
SoftMaster 3.64 ........................................................................................................19

3.

2.5

Problems resolved ....................................................................................... 20

2.6

Known issues with MLPLC.......................................................................... 21

SOFTMASTER INSTALLATION ...................................................23


3.1

4.

Installing SoftMaster .................................................................................... 23

PLC FIRMWARE UPGRADE ........................................................25


4.1

Overview ....................................................................................................... 25

4.2

Upgrading PLC firmware for ML200R Expansion driver module (redundant


and non-redundant) ..................................................................................... 25

4.3

Upgrading PLC firmware for ML200R Expansion Manager (Built inside


CPU module) ................................................................................................. 27

4.4

Upgrading PLC firmware for ML200R CPU offline .................................... 29

4.5

Upgrading PLC firmware for ML200R CPU online .................................... 31

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

ix

Contents

4.6

Upgrading OS for Communication Module using SoftMaster-NM...........33

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

1. Before you begin


1.1

Review the latest information


Checking for updates
Before installing any software, check the extranet site using the following link
http://acsnet.honeywell.com/sites/ML_Globalization/Shared%20Documents/Forms/AllIt
ems.aspx?RootFolder=%2fsites%2fML%5fGlobalization%2fShared%20Documents%2f
User%20Documents&FolderCTID=&View=%7b5432F171%2dB69C%2d4A59%2dA33
6%2dF5651317A9DA%7d, for documentations including the updates to this SCN.

1.2

Overview
ML200R is Honeywells next generation Programmable Logic Controllers which
supports CPU level redundancy.
It provides the following:

Real power

Performance and versatility with compact size

High speed scanning of I/O Channels and execution of program instructions

Open network through Ethernet

Profibus, remote I/O, engineer-friendly programming and diagnostic software tools.

Experion interface is qualified with ModBus and MLDP.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

11

1. Before you begin


1.2. Overview

12

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

2. About this release


2.1

Components of this release


The following table lists the components and their version numbers.
Component

2.2

Version Number

SoftMaster

3.64

CPU firmware

2.10

Expansion Manager

2.10

Expansion Driver

2.10

FENet OS

3.20

SNet OS

3.0

Hardware and software compatibility matrix


ATTENTION
For more information on compatibility versions, contact Honeywell TAC.

The following table provides the hardware and software compatibility matrix.
Model Number

R220
July 2012

Hardware Version

OS Version

SoftMaster

V3.64

SoftMaster-NM

V3.64

2MLR-CPUH/T
2MLR-CPUH/F

V5.0

V2.10

V5.1

V2.10

2MLR-DBSH
2MLR-DBSF
2MLR-DBST

V5.0

V2.10

2MLR-DBDH
2MLR-DBDF
2MLR-DBDT

V2.10

MasterLogic PLC Software Change Notice


Honeywell

13

2. About this release


2.3. Hardware list

Model Number

2.3

Hardware Version

OS Version

2MLF-AC8A

V6.3

V1.12

2MLF-AD4S

V5.0

V1.02

2MLF-AD8A

V5.1

V1.02

2MLF-AD16A

V5.0

V1.02

2MLF-AV8A

V6.3

V1.12

2MLF-DC4A

V6.0

V1.10

2MLF-DC4S

V5.1

V1.00

2MLF-DC8A

V5.1

V1.00

2MLF-DV4A

V6.2

V1.10

2MLF-DV8A

V5.1

V1.00

2MLF-HO2A
2MLF-HD2A

V6.0

V1.14

2MLF-RD4A

V6.0

V1.00

2MLF-TC4S

V6.1

V1.01

2MLL-C22A
2MLL-C42A
2MLL-CH2A

V5.1

V3.0

2MLL-EFMF
2MLL-EFMT

V5.0

V3.20

Hardware list
The following table provides the list of hardware.
Model Number

Specifications

2MLR-CPUH/F

Max. I/O:23,808Pts., Redundant CPU, FO


CPU

2MLR-CPUH/T
14

Max. I/O:23,808Pts., Redundant CPU, TP


MasterLogic PLC Software Change Notice
Honeywell

R220
July 2012

2. About this release


2.3. Hardware list

Model Number

Specifications

2MLR-AC12

Redundant Power 110V, 5.5A

2MLR-AC22

Redundant Power 220V, 5.5A

2MLR-AC13

Power

Redundant Power 110V, 8.5A

2MLR-AC23

Redundant Power 220V, 8.5A

2MLR-DC42

Redundant Power DC24V

2MLR-M02P

Main Base 2 slot

2MLR-M06P

Main Base 6 slot


Base

2MLR-E12P

Expansion Base 12 slot

2MLR-E12H

Expansion Redundancy Base 12 slot

2MLR-DBST

Expansion Driver, TP

2MLR-DBSF

Expansion
Driver

2MLR-DBSH

Expansion Driver, TP/FO

2MLR-DBDT
2MLR-DBDF

Expansion Redundancy Driver, TP


Expansion
Redundancy
Driver

2MLR-DBDH
2MLC-F201

Expansion Driver, FO

Expansion Redundancy Driver, FO


Expansion Redundancy Driver, TP/FO

Sync Cable

Multimode Fiber Optic Cable, LC


connector, 2.0m

2MLI-D21A

8Pts. DC24V Input (Sink/Source Type)

2MLI-D22A

16Pts. DC24V Input (Sink/Source Type)

2MLI-D22B

16Pts. DC24V Input (Source Type)


Digital Input

R220
July 2012

2MLI-D24A

32Pts. DC24V Input (Sink/Source Type)

2MLI-D24B

32Pts. DC24V Input (Source Type)

2MLI-D28A

64Pts. DC24V Input (Sink/Source Type)

MasterLogic PLC Software Change Notice


Honeywell

15

2. About this release


2.3. Hardware list

Model Number

Specifications

2MLI-D28B

64Pts. DC24V Input (Source Type)

2MLI-A12A

16Pts. AC110V Input

2MLI-A21A

8Pts. AC220V Input

2MLI-A21C

8Pts. AC220V Input

2MLQ-RY1A

8Pts. Relay Output, 2A , 1Pts./COM

2MLQ-RY2A

16Pts. Relay Output, 2A (5A/COM)

2MLQ-RY2B

16Pts. Relay Output, 2A , BuiVaristor

2MLQ-SS2A

16Pts. Triac Output, 1A

2MLQ-TR2A

16Pts. TR Output, 0.5A (Sink Type)


Digital Output

2MLQ-TR4A

32Pts. TR Output, 0.1A (Sink Type)

2MLQ-TR8A

64Pts. TR Output, 0.1A (Sink Type)

2MLQ-TR2B

16Pts. TR Output, 0.5A (Source Type)

2MLQ-TR4B

32Pts. TR Output, 0.1A (Source Type)

2MLQ-TR8B

62Pts. TR Output, 0.1A (Source Type)

2MLQ-TR1C

8Pts. TR Output, 2A (Sink Type)

2MLF-AV8A

Voltage Input, 8channels

2MLF-AC8A

Current Input, 8channels

2MLF-AD8A

16

Analog Input

Voltage/Current Input, 8channels

2MLF-AD4S

Voltage/Current Input, 4channels, Isolated

2MLF-AD16A

Voltage/Current Input, 16channels

2MLF-RD4A

RTD Input

RTD Input, 4channels

2MLF-TC4S

TC Input

Thermocouple Input, 4channels, Isolated

2MLF-DV4A

Analog Output

Voltage Output, 4channels

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

2. About this release


2.3. Hardware list

Model Number

Specifications

2MLF-DC4A

Current Output, 4channels

2MLF-DC8A

Current Output, 8channels

2MLF-DV8A

Voltage Output, 8channels

2MLF-DC4S

Current Output, 4channels, Isolated

2MLF-HO2A
2MLF-HD2A

High Speed
Counter

Pulse Input, 2channels, Open Collector


Pulse Input, 2channels, Line Drive
Fast Ethernet, 100/100Mbps, RJ-45
(Electric)

2MLL-EFMT
FEnet
2MLL-EFMF

Fast Ethernet, 100/100Mbps, SC Type


(Fiber Optic)

2MLL-C22A

Serial Communication, RS-232C


2channels

2MLL-C42A

Snet

Serial Communication, RS-422 2channels


Serial Communication, RS-232C/RS-422
(1ch each)

2MLL-CH2A
2MLL-PMEA

Pnet

Profibus, Master, 12Mbps, DP Standard

2MLL-DMEA

Dnet

DeviceNet Interface Card

2MLT-DMMA

DUMMY Module for empty I/O slots


DUMMY

2MLR-DMMA
USB-301A

USB Cable

DUMMY Module for empty Power Supply


slots - used for ML200R
Engineering cable for SoftMaster

SmartLink Board & Connection Cable for Digital I/Os (Only for 32/64 points Sink
Type)
Model Number
R32C-NS5A-40P

R220
July 2012

Specifications
Relay Board

SmartLink Relay Board, 40point

MasterLogic PLC Software Change Notice


Honeywell

17

2. About this release


2.4. New features in this release

Model Number

Specifications

TG7-1H40S

Terminal Board

Cable Assembly for Terminal Board, 40p40p, 1.5m

C40HF-15PB-1
C40HF-30PB-1

Cable between
SmartLink and
PLC I/Os

C40HF-15PB-1

Cable Assembly for Terminal Board, 40p40p, 3.0m


Cable Assembly for Relay Board, 40p-40p,
1.5m
Cable Assembly for Relay Board, 40p-40p,
3.0m

C40HF-30PB-1

2.4

SmartLink Terminal Board, 40point

New features in this release


The following are the new features/enhancements in this release.

Firmware 2.10

Support for dual I/O link redundancy (2MLR-DBDT/F/H and 2MLR-E12H)

Support for Profibus slave interface module (2MLL-PSEA)

Support for two new digital I/O cards.

2MLI-A21C

2MLQ-TR1C

SoftMaster 3.63

Inclusion of above mentioned firmware features.

Addition of the following instructions.

18

AB Expression: CPT

ARY instruction: ARY_CMP_EQ, ARY_CMP_NE

Support for downloading binary file to CPU without opening the source file.

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

2. About this release


2.4. New features in this release

Addition of the following flags for SOE event information.

_SOE_LOG_CNT

_SOE_LOG_ROTATE

_SOE_READ_LOG_CNT

_SOE_READ_LOG_ROTATE

Addition of the following flags to enable/disable HS/P2P link in ladder program.

_HS_ENABLE_STATE, _HS_REQ_NUM, _HS_REQ

_P2P_ENABLE_STATE, _P2P_REQ_NUM, _P2P_REQ

Addition of scan time information flag for fixed cycle task:


_CYCLE_TASK_SCAN_TIME

SoftMaster 3.64

Support for two new digital I/O cards.

2MLI-A21C

2MLQ-TR1C

In I/O Parameter window, Digital module list shows the module name instead of
module type.

Audo Detect function is added to check connected port number automatically for
RS-232C setting.

Refresh User Function/FB function is added to update all if UDF or UDFB is


modified.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

19

2. About this release


2.5. Problems resolved

2.5

Problems resolved
This section describes the notable problems resolved in this release.
PAR

20

Brief description of the problem

1-MN2NVY

Error 104 does not have any information on error message.

1-MN2O2P

Warning 43 does not have any information.

1-MN2O6J

SoftMaster tool shows a user incomprehensible dialog box on


selecting the Module Change Wizard.

1-MN2O9A

When SoftMaster is connected to ML200R through USB and if you


continuously perform power OFF/ON, remove/connect DBDT
modules, DBDT cables, DBDT reset and so on., then SoftMaster
does not responds at times.

1-MN2OAY

In the SoftMaster-NM window, when you right-click the FENet


module and selecting Properties in the tree view, the properties of
the module are not displayed.

1-MN3EO5

In SoftMaster 3.63, the updated MLPLC user guide is not displayed


from the Help menu.

1-MN3EQX

CPU status does not come to online automatically after power OFF
both the Master and Standby CPUs and power ON one after
another.

1-P2HHZ5

SoftMaster is crashing occasionally while performing online edit


operation continuously.

1-P2HHZZ

Unable to install SoftMaster on Windows 2K8 server systems.

1-QY2KSI

Masterlogic Address Configuration Error for P2P when we use the


data size in multiple of 16.

1-R9219U

There is no possiblity to do ON-LINE EDITING. During write an online change of Softmaster 3.61 program is terminated with
message (It is general information from Windows about problem in
application, which needs to close Softmaster and detail information
about dll).

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

2. About this release


2.6. Known issues with MLPLC

2.6

Known issues with MLPLC


This section describes the notable known issues with MLPLC.
PAR

Brief description of the


problem

Work-around/Preventive action

1-IDQPMD

Separate flags are needed for


ML200R types to differentiate
ML200R - CPUH/T & CPU H/F
types. This is required to appear
in MLDP Communication display.

This is only for display notification


and is not on function. At present,
common ML200R types are
displayed as 2MLR-CPUH/T.

1-IDQPMZ

E039 does not show proper LED


status.

Functionality is working properly.


Only LED status mismatch occurs.

Remove the power supply of both


CPU A and B and connect it
again. The PLC shows E039. But
the Master - RUN/STOP LED is
Green that shows PLC is running,
Standby - RUN/STOP LED is
RED that shows CPU is stopped.
The small sync window in
SoftMaster shows both PLC is
running.
1-IDQPOA

After changing and downloading


only IO parameters in SoftMaster,
if you select Start Monitor, a
warning message appears before
the monitoring starts.

Functionality is working properly.


This warning message can be
ignored.

1-IDQPPR

Any of the variable name that


contains 'load' (For example,
overload) in the SoftMaster may
result an unexpected behavior of
program execution.

Avoid using variable names which


contains the word load.

1-HXO8AD

Sometimes, Average Value


parameter for an AI module in I/O
parameter window shows Red
and this does not allow to
changing any of the module
parameters.

Delete the module from I/O


parameter, add manually and then
configure it.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

21

2. About this release


2.6. Known issues with MLPLC

PAR

Brief description of the


problem

Work-around/Preventive action

1-CWHPS4

In SoftMaster, Communication
Module Info under System
Monitoring for the CPU module,
the Port 1 Number and Port 2
Number information is reversed.

No workaround exists.

1-IZFAPN

In DISOE module, Force I/O


feature is not available.

No workaround exists.

1-J60Q9B

In SoftMaster, when we add


some function blocks in a ladder
diagram, the shortcut of the
function block is also added in the
Most Recently Used option in
the Function/FB pane. But this
shortcut is not appearing in
SoftMaster 3.61.

No workaround exists.

22

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

3. SoftMaster Installation
3.1

Installing SoftMaster
To install SoftMaster, perform the following steps.
Step

Action

Double-click setup.exe and execute the installation file. The Installation


Wizard appears.

Click Next. The Customer Information window appears.

Type your name and company name and then click Next.
You are prompted to specify the folder to install SoftMaster.

The default installation folder is displayed. If you want to change the folder,
click Browse and select a new folder.

ATTENTION
SoftMaster needs 30 MB of free disk space. In case of inadequate
free space, you are prompted to select a disk with enough capacity.
5

After selecting a folder, click Next.


The installation may take a few minutes.

R220
July 2012

Click Finish to complete the installation.

MasterLogic PLC Software Change Notice


Honeywell

23

3. SoftMaster Installation
3.1. Installing SoftMaster

24

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.1

Overview
PLC firmware must be upgraded in the following sequence.

Upgrading ML200R PLC firmware for Expansion Driver (2MLR-DBST, F, H)

Upgrading ML200R PLC firmware for Expansion Manager (Built inside CPU)

Upgrading PLC firmware for ML200R CPU (2MLR-CPUH/T,F)


ATTENTION

4.2

For more details on firmware upgrade and firmware files, contact


Honeywell TAC.

During PLC firmware upgradation, ensure to connect the USB cable to


Master CPU.

Upgrading PLC firmware for ML200R Expansion


driver module (redundant and non-redundant)
ATTENTION

The Expansion Manager/Driver module OS cannot be upgraded online.

The following procedure is given by considering the CPU A as Master


and CPU B as Standby.

To upgrade PLC firmware for Expansion Driver module (redundant and non-redundant),
perform the following steps.
Step

Action

Change both the CPUs to STOP mode, and ensure that the key switch is in
REMOTE mode.

Connect the USB cable to the master CPU.

Execute MasterLogic OS Downloader 1.1.exe.


The MasterLogic OS Downloader dialog box appears.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

25

4. PLC firmware upgrade


4.2. Upgrading PLC firmware for ML200R Expansion driver module (redundant and non-redundant)

Step
4

Action
Choose Connect > Serial Port/CPU Setup.
The Connection Setup dialog box appears.

Click USB in the Media drop-down list.

6
Click
7

Click

The OS Download dialog box appears.


8

In the OS Download window, perform the following:


a)

Under Download Mode, click USB.

b)

In the OS Type drop-down list, click ML200R-ExtDriver.

c)

Click Open and select OS as 2MLR_SLAVE_Vxxx.bin.

After the download is complete, the downloader tool changes to initial mode
and LED in the Expansion driver module blinks.
9

Power off and on (Reset CPU and IO base) to make upgrade firmware online.

ATTENTION
If there are more than two expansion bases in the system, all the
expansion bases (particular ring) are upgraded at once.
10

26

If dual I/O link redundant topology is used, then follow the below steps to
upgrade the expansion driver module for both ring network.
a)

Change CPU A to CPU B.

b)

Connect USB to CPU B and repeat the steps 2 through 9.

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.3. Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module)

4.3

Upgrading PLC firmware for ML200R Expansion


Manager (Built inside CPU module)
ATTENTION
The following procedure is given by considering the CPU A as Master and
CPU B as Standby.

To upgrade PLC firmware for Expansion Manager (redundant and non-redundant),


perform the following steps.
Step

Action

Change both the CPUs to STOP mode, and ensure that the key switch is in
REMOTE mode.

Connect the USB cable to the Master CPU.

Execute MasterLogic OS Downloader 1.1.exe.


The MasterLogic OS Downloader dialog box appears.

Choose Connect > Serial Port/CPU Setup.


The Connection Setup dialog box appears.

Click USB in the Media drop-down list.

6
Click
7

Click

The OS Download dialog box appears.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

27

4. PLC firmware upgrade


4.3. Upgrading PLC firmware for ML200R Expansion Manager (Built inside CPU module)

Step
8

Action
In the OS Download dialog box, perform the following:
a)

Under Download Mode, click USB.

b)

Click ML200R-ExtManager in the OS Type drop-down list.

c)

Click Open and select OS as 2MLR_CPUH_Master_Vxxx.bin.

After the download is complete, downloader tool changes to initial mode and
waits for CPU ACT LED to blink.
9

Power off and on (Reset CPU) to make upgrade firmware online.

ATTENTION
In case of expansion manager, OS of Master and Standby are
migrated at once. Ensure to check if OS is updated in the Standby
CPU and reset.
10

28

If dual I/O link redundant topology is used, then follow the below steps to
upgrade the expansion manager module for CPU B.
a)

Change CPU A to CPU B.

b)

Connect USB to CPU B and repeat the steps 2 through 9.

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.4. Upgrading PLC firmware for ML200R CPU offline

4.4

Upgrading PLC firmware for ML200R CPU offline


To upgrade PLC firmware for CPU during offline mode, perform the following steps.
Step

Action

Change both the CPUs to STOP mode, and ensure that the key switch is in
REMOTE mode.

Connect the USB cable to the Master CPU.

Execute MasterLogic OS Downloader 1.1.exe.


The MasterLogic OS Downloader dialog box appears.

Choose Connect > Serial Port/CPU Setup.


The Connection Setup dialog box appears.

Click USB in the Media drop-down list.

6
Click
7

Click

The OS Download dialog box appears.


8

In the OS Download window, perform the following:


a)

Under Download Mode, click USB.

b)

Click ML CPU Series in the OS Type drop-down list.

c)

Click ML200R Boot. The following actions occur by default.

d)

R220
July 2012

CPU Dot Matrix: OSwr

CPU LED: Blink in RUN/STOP WAR. ERR order

Standby CPU shows the same indication

Click Open and select OS as 2MLR_CPUH_Main_Vxx.bin.

MasterLogic PLC Software Change Notice


Honeywell

29

4. PLC firmware upgrade


4.4. Upgrading PLC firmware for ML200R CPU offline

Step

Action
After the download is complete in Master CPU,
The downloader tool change to initial mode
CPU LED blinks for few times
Master CPU changes to STOP mode.

Power off and on (Reset CPU) to make upgrade firmware online.


CPU OS upgradation for Master CPU is completed.

ATTENTION
Ensure the following status in Standby CPU.

CPU Dot Matrix: OSwr

CPU LED: Blink in RUN/STOP WAR. ERR order

10

Connect USB to Standby CPU and repeat the steps 4 through 7.

11

In the OS Download dialog box, click Open and select OS as


2MLR_CPUH_Main_Vxx.bin.
After the download is complete,
The downloader tool change to initial mode
CPU LED blinks for few times
Standby CPU changes to STOP mode.

12

Power off and on (Reset CPU) to make upgrade firmware online.


CPU OS upgradation for Standby CPU is completed.

30

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.5. Upgrading PLC firmware for ML200R CPU online

4.5

Upgrading PLC firmware for ML200R CPU online


ATTENTION

Only CPU firmware version can be upgraded online and not Expansion
Manager/Driver.

Ensure that the CPU OS version to be installed is compatible with the


existing Expansion driver/Expansion manager OS version.

To upgrade PLC firmware for CPU during operation (online), perform the following
steps.
ATTENTION
The following procedure is given by considering the CPU A as Master and
CPU B as Standby.
Execute the procedure carefully based on your current status of CPU or
ensure CPU A as Master and follow the procedure.
Step

Action

Remove the synchronization cable (OFC) between Master CPU (A) and
Standby CPU (B) and all I/O cables connected to Standby CPU (B) to isolate
the Standby CPU (B) from operation.

Change the mode from REMOTE to RUN using a key switch. Hence, the
isolated Standby CPU (B) becomes a Master CPU (B).

Change the isolated CPU to STOP mode, and ensure that the key switch is
set back to REMOTE mode

Execute MasterLogic OS Downloader 1.1.exe.


The MasterLogic OS Downloader dialog box appears.

Choose Connect > Serial Port/CPU Setup.


The Connection Setup dialog box appears.

Click USB in the Media drop-down list.

7
Click

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

31

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

Step

Action

Click

The OS Download dialog box appears.


9

In the OS Download window, perform the following:


a)

Under Download Mode, click USB.

b)

Click ML CPU Series in the OS Type drop-down list.

c)

Click ML200R Boot. The following actions occur by default.

d)

CPU Dot Matrix: OSwr

CPU LED: Blink in RUN/STOP WAR. ERR order

Click Open and select OS as 2MLR_CPUH_Main_Vxx.bin.

After the download is complete in the isolated CPU (B),


The downloader tool change to initial mode
CPU LED blinks for few times
CPU (B) changes to STOP mode.
Power off the CPU (B) and connect the synchronization cable and I/O

cable to CPU (B).


10

Power off and on (Reset CPU) to make upgrade firmware online.


CPU OS upgradation for this CPU (B) is completed.

32

11

Power on CPU (B) and change its mode to RUN (by Key switch or
SoftMaster). Both CPUs are in RUN mode even if the OS versions are
different.

12

Change Master CPU (A) to STOP mode. Then, this Master CPU (A) becomes
Standby CPU (A) and the Standby CPU (B) becomes Master CPU (B)

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

Step
13

Action
Repeat steps 1 through 10 for CPU (A) which is Standby CPU.
CPU OS upgradation for this CPU (A) is completed.

14

4.6

Power on CPU (A) and change its mode to RUN (by Key switch or
SoftMaster). Both CPUs are in RUN mode being CPU (B) as Master and
CPU (A) as Standby.

Upgrading OS for Communication Module using


SoftMaster-NM
To upgrade Communication module using SoftMaster-NM, perform the following steps.
Step

Action

Connect USB cable to Master CPU (for example, CPU A) and launch
SoftMaster-NM.

From SoftMaster-NM, choose Online > Upload/Download (File).


The Download/Upload(File) dialog box appears.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

33

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

Step

Action

Select the communication module and then click BBMBoot. The LED of
FENet module is changed to Download mode and PLC CPU will reset after
BBMBoot is selected.

From SoftMaster-NM, choose Online > Connect and then Online >
Upload/Download (File).
The Download/Upload(File) dialog box appears.
The mode is changed to OS Update Mode.

ATTENTION
FDEnet is displayed as communication module only after BBMBoot
execution. Ensure to select the proper Base and Slot number.
5

Select the OS and then click Download.


The Open dialog box appears.

34

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

Step

Action

Select the FEnet OS Firmware file and then click Open.


The OS download begins. It takes few minutes to complete.

After the download is complete the following message appears.

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

35

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

Step

Action

Power off the Master CPU A and then re-connect the synchronization cable
and I/O cables to CPU A and it changes back to Standby mode.

From SoftMaster, choose Online > Control Redundancy and then click
Change Master.
Repeat Step 1 to 8 with CPU B (Master).

36

Choose Online > System Diagnosis from SoftMaster-NM to verify if the OS


version is downloaded to the System.

MasterLogic PLC Software Change Notice


Honeywell

R220
July 2012

4. PLC firmware upgrade


4.6. Upgrading OS for Communication Module using SoftMaster-NM

R220
July 2012

MasterLogic PLC Software Change Notice


Honeywell

37

Honeywell Process Solutions