Required Material:

1) Data sheet
2) Hart Communicator
Step wise Procedure:
*Ask panel man to put the controller in manual mode for control loop
*Isolate the Control valve from the process.
WARNING
The Isolation of control valve from the process shall be done by field o
perator. Careful step shall be done to ensure no upset to the operation.
*Hook up HART Communicator and verify some parameters by refer to data sheet suc
h as Tag Number, OP and etc.
*Change from normal mode to setup mode
*Select auto find stop (wait some minute)
*If full open is more than 100% select open adjustment and put new number as per
calculation
*Make an auto calibration ( wait some minute)
*Verify the linearity by increasing and decreasing the travel (0%,25%,50%,75%,10
0%,75%,50%,25% and 0%of range)
*After completion of the job ask panel operator to put loops back in normal mode
*Fill the calibration form and file it for future reference.
Example calculation
A: Max travel from stem
70mm
B: Scale plate
50mm
New open adjustment should be (50/70) X 100 = 71.48%

How to Calibrate Control Valve? Which Instrument is Used?


For the calibration of a control valve a loop calibrator or a pressure calibrato
r can be used between 3-15psi.Check the valve position for 3psi which is to be 0
for a NC type valves.In such manner check the valve position for various ranges
(6psi,9psi,12psi & 15psi).the valve position should be 0 for 3psi and 50% for 9
psi and completely opened for15psi.
The same procedure is applicable for NO type valves.The valve is open for 3 psi
and completely closed for 15psi.Any errors occurred may be rectified by Zero spa
n adjustment.
In the case of HART , you can use a HART communicator ( Emersson 375 ,475..etc )
for calibrating a valve , apply 4 mA for 0% , 20 mA for 100% ,

alibration instrument required.


1.portable pneumatic calibrator
INPUT signal OUTPUT
Generate 0.2 kg/cm 0% of v/v travel
0.4 25%
0.6 50%
0.8 75%
1.0 100%
If you observe any deviation adjust accordingly.
BY using DRUG calibrater we can easily calibrate just we

need a air line having pressure of 6kg as input of CV.


by giving 4-20mA signal through DRUG.
for example
4mA CV in close position
8mA 25%
12mA 50%
16mA 75%
20mA 100%
To calibrate a valve first check the input signal range if
it is 0.2 to 1.0 Kg/cm2 or different.
Calculate the span ( Difference between higher limit to
lower limit=1.0-0.2=.8 ) Now divide it in four equal parts
that is 0.2 Kg/cm2 this is 25% of the span.
Now check the valve travel like 2 inches, 3 inches or any
other value Divide it in four equal parts 25% of the travel.
Apply 25% of the span value+ 0.2= 0.4 Kg/cm2 it is 25% of
travel and apply full span value and see you get the
complete travel if you find difference adjust the spring
accordingly.
before do the stroke checking we have make sure the bench
calibration after that we should check 0-100% stroke
irst you have to now your limits if its pneumatic work
from 20 to 100kpa if current i 4 to 20ma
supply pressure,
1.bench set
2.beam alignments
3.calibration