Professional Documents
Culture Documents
For Viscotherm
TECHNICAL
MANUAL
773
Publ. Nr.
Supersedes
TIB-773-GB-0107
TIB-773-GB-0305
CONTENTS
1. PREFACE....................................................................................................4
1.1
1.2
1.3
1.4
General.......................................................................................................................4
Sysmbols....................................................................................................................4
Copyright ...................................................................................................................4
To record import serial numbers ...............................................................................5
6. DIMENSIONS...........................................................................................24
6.1 Viscosity control station ..........................................................................................24
6.2 Airfilter-Regulator ...................................................................................................26
6.3 Alarm pressure switch .............................................................................................27
6.3.1
Alarm pressure switch ...................................................................................27
6.3.2
Alarm pressure switch ...................................................................................27
6.4 Analog viscosity indicator .......................................................................................28
6.4.1
Indicator with alarm contracts .......................................................................28
6.4.2
Indicator without alarm contacts ...................................................................28
6.5 Starter box................................................................................................................29
7. OPERATING INSTRUCTIONS...............................................................30
7.1
7.1.1
Adjustment of control parameters .................................................................30
7.1.2
Manual operation...........................................................................................31
7.2 Initial start-up ..........................................................................................................32
7.3 Tuning to process.....................................................................................................32
7.4 Routine start-up and shut down ...............................................................................33
8. MAINTENANCE......................................................................................33
8.1 General.....................................................................................................................33
8.2 Maintenance schedule..............................................................................................33
8.3 "A" Maintenance checks..........................................................................................34
8.4 "B" Maintenance checks..........................................................................................34
8.5 "C" Maintenance checks..........................................................................................35
8.6 Maintenance of viscosity control station .................................................................36
8.6.1
Daily servicing...............................................................................................36
8.6.2
Annual servicing............................................................................................36
8.7 Maintenance of airfilter regulator............................................................................39
8.7.1
Daily servicing...............................................................................................39
8.7.2
Annual servicing............................................................................................39
8.8 Maintenance of analog viscosity indicator ..............................................................40
8.9 Maintenance of pressure alarm switch ....................................................................40
8.10 Maintenance of starter box...................................................................................40
1. PREFACE
1.1 GENERAL
This manual contains instructions for installation, operation and maintenance of the control components
supplied with a VAF Viscotherm pneumatic fuel viscosity control system Series V12.
This manual supplements the IOM instructions for the Viscotherm Sensor/Pneumatic Transmitter
Assembly, as published in Technical Manual No. 766.
For IOM information of the control valve for steam or thermal oil, and the viscosity recorder (if this option is
supplied), refer to the separate manuals supplied with these system components.
To ensure safe and correct installation and operation of your Viscotherm system read this manual
completely before starting operations.
For any additional information contact:
VAF Instruments B.V.
Vierlinghstraat 24, NL-3316 EL Dordrecht
P.O. Box 40, NL-3300 AA Dordrecht
The Netherlands
Or your local authorized VAF dealer.
Their addresses can be found on www.vaf.nl
1.2 SYSMBOLS
The symbols below are used to call attention to specific types of information.
A warning to use caution! In some instances, personal injury or damage to the Viscotherm unit or
control system may result if these instructions are not followed properly.
An explanation or information of interest.
1.3 COPYRIGHT
This manual is copyrighted with all rights reserved.
While every precaution has been taken in the preparation of this manual, no responsibility for errors or
omissions is assumed. Neither is any liability assumed for damages resulting from the use of the information
contained herein.
Viscotherm is a registered trademark of VAF Instruments B.V.
Nameplate data
2. SYSTEM DESCRIPTION
2.1 SYSTEM ARRANGEMENT DIAGRAM
Figure 1
Auto/manual switch
By means of the AUTO/MANUAL transfer switch of the bypass panel, the controlling pressure for the
pneumatic relay can be switched between the flapper-nozzle and the output of the manual regulator. Thus a
choice can be made between automatic control of the output and manual control.
Description of proportional + reset action of controller
(refer to figure 3)
With a decrease in the measured actual viscosity (fuel becoming thinner) the following occurs:
1. The output of the differential pressure transmitter also decreases, causing the measuring diaphragm of the
controller to collapse.
2. The black pointer rotates counter clockwise.
3. The flapper moves toward the nozzle as a result of the downward motion of link assembly ABC, causing
the flapper to restrict the nozzle flow and increasing nozzle back pressure P1.
4. Air supply pressure feeding through the restrictor expands the nozzle diaphragm.
5. The inlet port of the pneumatic relay opens and the exhaust port closes.
6. The output pressure P2 increases (as indicated on the output gauge).
7. The feedback bellows expand, moving link JL to the right.
8. Proportional link FG, pivoting around F, causes link GD to move upward.
9. Lever assembly E also moves upward, turning the flapper away from the nozzle.
10. Determined by the setting of the reset valve, the pressure inside the reset bellows increases slowly,
moving link JL to the left. This results in a slow further increase of the output pressure (reset action). The
reset action will continue until the measured value is back at the setpoint and the bellows is in
equilibrium.
11. The increasing output pressure P2 (step 6) is sent to the control valve, resulting in less steam or thermal
liquid supplied to the heater (assuming the control valve is 'air-to-close'), to increase the viscosity of the
fuel oil (fuel becoming thicker).
10
11
3.4 AIRFILTER-REGULATOR
This pressure-reducing regulator (Figure 5) is a simple automatic device which controls the downstream
pressure by balancing the force set by a spring against the force produced by the desired output pressure
acting on a diaphragm.
When the spring force is greater than the output pressure force, the diaphragm assembly moves downward
and the inlet supply valve opens, permitting the controlled pressure to increase.
When the regulated pressure force is greater than the force set by the spring, the diaphragm assembly moves
upward, closing the pilot valve and uncovering the relief port.
The air then escapes to atmosphere through the relief opening in the bonnet until the spring and pressure
forces are balanced.
The required output pressure is set by turning the range adjust screw and is indicated on the pressure gauge.
A spring loaded drain valve is used for periodic draining of the liquid which collects in the bowl.
12
Figure 6
13
4.2 AIRFILTER-REGULATOR
Type
Maximum supply pressure
Regulated output pressure
Air output capacity
Connections
Materials
Housing
Valve plug
Range spring
Diaphragm
Filter element
Filter mesh width
Ambient temperature range
Accessories supplied
Weight
14
Weight:
15
(see figure 7)
Use 6x1 mm or tubing or piping for making pneumatic connections.
1. Make sure that the I-port on the back of the controller has been connected to the I-port of the auto-manual
station. The internal I-tube clamp should be tightened (figure 8).
2. Connect supply port (E) of the auto-manual station to a regulated 1.4 bar (20 psi) air supply tapped from
the OUT port of the airfilter-regulator.
3. Connect output port V of the auto-manual station to the air connection of the steam, or thermal oil,
control valve.
4. Connect NPTF process port M1 to the OUT port of the differential pressure transmitter. Also see
Technical Manual 766 supplied with the sensor/transmitter assembly).
The maximum air pressure applied to M1 should never exceed 100 kPa (1 bar; 15 psi).
16
Figure 7 Pneumatic connections of control station with low mounted auto-manual station (left) and side
mounted auto-manual station (right)
17
5.2 AIRFILTER-REGULATOR
1. Install the airfilter-regulator in an upright position, using the bracket provided. Required mounting parts:
two (2) bolts, nuts and washers, M6 or 1/4".
2. Leave sufficient clearance to remove the lower bowl for servicing.
3. Make pneumatic connections as shown in figure 9, using 6 x 1 mm or tubing.
a) Connect the IN port to a compressed air supply with a maximum air pressure of 20 bar (300 psi).
b) Connect the OUT port to the IN connection of the dP-transmitter and to the supply port E of the
viscosity control station.
The two remaining taps (stamped "G") are reduced pressure outlets. One is used by the pressure gauge, the
other one is plugged.
Regulate to 20 psi (1.4 bar)
NPT female IN
Supply air
from compressor
max. 20 bar
(300 psi)
Output pressure
gauge
NPT OUT
Connect to:
Supply port E of control station
IN connection of dPtransmitter
Figure 9 Airfilter-regulator
18
19
500 V
3A
250V
50 W=
2A=
20
21
22
23
6. DIMENSIONS
6.1 VISCOSITY CONTROL STATION
24
25
6.2 AIRFILTER-REGULATOR
Figure 17 Airfilter-regulator
26
Figure 19
28
Figure 20
29
7. OPERATING INSTRUCTIONS
7.1 VISCOSITY CONTROL STATION
7.1.1 Adjustment of control parameters
The desired, or setpoint, viscosity value is indicated by the red pointer (3, Fig. 21). To adjust this pointer,
turn the setpoint adjustment knob (1) until the red pointer is at the desired viscosity.
The proportional band can be adjusted by means of the graduated dial (2). The proportional band value is
indicated by the red arrow at the left hand side of the dial (partially covered by the setpoint pointer)
The dial has two areas with the same scale division, one area for direct and one for reverse control action.
1
2
30
Check the control action, which is determined by the position of the proportional band dial. It should be
- in reverse position when the control valve action is air to close,
- in direct position when the control valve action is air to open.
Unless ordered otherwise the control parameters are preset in the factory as follows:
proportional band 35 %, control action reverse, reset time 5 minutes.
Refer to section 8.3 in case one or more of these parameters must be altered.
7.1.2 Manual operation
To switch over from automatic to manual control, simply turn knob A of the auto-manual station (Fig. 22)
to
The output pressure to the control valve will now graduately be adjusted to match
from
the setting of knob B.
By turning knob B, the air output pressure to the control valve can be adjusted. This pressure is indicated by
gauge C.
To switch back to automatic operation, simply turn knob A back to the
output signal will graduately be adjusted to the actual controller setting.
A
Figure 22 Auto-manual station
31
32
8. MAINTENANCE
8.1 GENERAL
Under normal conditions the Viscotherm system requires a minimum of maintenance.
"Normal" conditions means:
a) A clean operating environment.
b) Viscotherm system components installed in accordance with the installation instructions given.
c) Operation of the viscosity control system in accordance with this manual and other related publications
issued by VAF Instruments B.V.
d) The air supply for pneumatic system components is free from oil, moisture and dirt.
e) Uninterrupted electric power supply at the normal specified values.
33
Daily
Weekly
Monthly
Annually
DP-transmitter
Alarm pressure
Further disassembly, inspection and repair of the Viscotherm system instruments will only be carried out if,
in the opinion of our service engineer, the maintenance work and running trials have indicated a failure.
34
35
36
e) Check that the output signal is still 0.6 bar; if not, slightly loosen the two screws M (figure 23) and
gradually move the plate supporting the nozzle/flapper assembly until the required output signal is
obtained.
f) Adjust the proportional band to 10% direct action, and thereafter to 10% reverse action. Check whether
the output signal of the controller remains at 0.6 bar (9 psi) with a maximum deviation of 0.03 bar (0.5
psi). If so, the controller is properly aligned; otherwise, proceed as follows:
g) Should the control signal deviate from 9 psi when adjusting the proportional band as indicated in step f
with a same difference, but of opposite sign (plus and minus) on direct and reverse action (p.E.: signal is
9 + 2 = 11 psi on reverse action and 9 - 2 = 7 psi on direct action), turn slowly and gradually screw H
(figure 23) to adjust the output signal at 9 psi. After this adjustment, repeat step f.
The reset screw is protected by a threaded plug. Take out this protection before adjusting.
h) Should the control signal deviate from 9 psi when adjusting the proportional band with unequal
difference of opposite sign on direct and reverse action (p.E.: signal is 9 + 3 = 12 psi on reverse action
and 9 - 1 = 8 psi on direct action), adjust the proportional band to 10% direct acting.If on this position
the deviation is higher than on reverse action, turn flapper nut (figure 24), clockwise until half of the
deviations algebraic addition is eliminated. Example: For the above mentioned, this would be (3 + (1)):2 = 1 psi. To eliminate this value, rotate the flapper nut until the output is 12 - 1 = 11 psi. Should the
deviation be lower on reverse than on direct action, turn the flapper nut counter-clockwise.
i)
After every operation on the flapper as described under step h, repeat steps e through h.
Flapper nut
Figure 24 Nozzle / flapper assembly
37
When reassembling the relay, check that positioning of mounting holes on diaphragms and gaskets is
correct. Notice the reference marks engraved on all components; these should coincide with the reference
marks on the base plate.
j) Re-install the relay in the control station and re-connect the air connection.
38
Figure 26 Airfilter-regulator
39
40
9. TROUBLE SHOOTING
9.1 GENERAL
Before using the trouble shooting tables in this section make sure that:
the bunker fuel has the correct standard viscosity;
all by-pass and block valves of the Viscotherm system are in correct positions (either open or closed, as
specified in this manual and in Technical Manual 766 supplied with the Viscotherm sensor/dPtransmitter;
the supply of steam or thermal liquid to the fuel heater is sufficient;
the spring-loaded valve in the return line from the engine to the mixing tank is working properly and is
set to the correct value;
all pneumatic pipings and process connections are not leaking or clogged.
all electric connections are in good order.
Some system problems, arising as errors in viscosity indication, are due to disturbances of the viscosity
sensor/dP-transmitter assembly. Refer to the trouble-shooting section of Technical Manual 766 supplied with
the Series V12 sensor/dP-transmitter.
CORRECTIVE ACTION
CORRECTIVE ACTION
41
CORRECTIVE ACTION
Repair leak.
CORRECTIVE ACTION
Replace gasket(s).
42
POSSIBLE CAUSE
CORRECTIVE ACTION
43
CORRECTIVE ACTION
CORRECTIVE ACTION
CORRECTIVE ACTION
44
The control valve for steam or thermal liquid must be correctly sized. It should be large enough to
maintain the process for most load conditions. If it operates near the full open position continually,
it is probably undersize and does not have sufficient control. If it operates near the closed position
continually, it is probably oversize. For valve sizing formulas and further trouble shooting
instructions refer to the technical manual supplied with the valve
45
Qty.
Description
26
46
47
Qty.
1*
2
3
4
6
7
8
9
10
11
12*
13
14*
15
16
17
--
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
19
Part Name
Recommended spare parts. Refer to table 6 for contents of spare parts kit.
48
Qty.
1
2
2
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
Part Name
* Recommended spare parts. Refer to table 6 for contents of spare parts kit.
+ The diaphragm of item 509 must be led through the hole in the intermediate plate, item 510.
49
Qty.
4
1
1
1
1
1
1
2
2
1
2
2
1
1
1
1
1
1
1
4
2
1
1
Part Name
Screw M4 x 35
Upper plate
Valve spring
Intermediate plate
Diaphragm assy
Loading spring
Spring guide
Screw M4 x 10
O-ring
Air connector
Mounting pillar
Fixing plate
Base plate
Pressure adjusting knob
O-ring
Gauge holding plate
Pressure gauge output signal
Switch knob
Name plate
Screw M4 x 10
O-ring
Distributor
Switch block
* Recommended spare parts. Refer to table 6 for contents of spare parts kit.
50
Qty
Part Name
21
22
23
4
kit
1
Figure 28
1
12 14
Figure 29
1 508 509 511 516 556
Figure 30
5 9
21
1x
1x 1x 1x
1x 1x 1x
51
1x
1x
1x
1x
1x
Figure 32 Airfilter-regulator
Table 7: Airfilter-regulator
Item No.
Fig. 32
Qty
Part Number
Part Name
0670-0005
1*
2
3
1
1
1
0673-0031
1419-0007
0653-0002
52
Qty
Part Number
Part Name
1
1
0653-0059
0653-0062
Viscosity indicator
Viscosity indicator with NO/NC alarm contacts
53
54
Qty
1
4
2
1
2
2
2
2
2
2
4
4
1
1
1
1
1
4
1
1
4
2
2
1
1
1
1
1
4
2
1
1
1
1
1
1
1
Part. Name
Part. No.
0610-0008
55
Check*
Date
Remarks
Authorized
Signature
Months
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
ABC
56
57
4. Defects not covered by the guarantee are those which occur partially or wholly as a result of:
A. non-observance of the operation and maintenance instructions or other than foreseeable normal usage;
B. normal wear and tear;
C. assembly/installation by third parties, including the principal;
D. the application of any government regulation regarding the nature or quality of the material used;
E. materials or goods used in consultation with the principal;
F. materials or goods provided by the principal to the contractor for processing;
G. materials, goods, working methods and constructions insofar as are applied at the express instruction
of the principal, and materials or goods supplied by or on behalf of the principal;
H. components obtained from third parties by the contractor insofar as that party has given no guarantee
to the contractor.
5. If the principal fails to fulfil any obligation properly or on time ensuing from the agreement concluded
between the principal and the contractor or any agreement connected to it, the contractor shall not be
bound by any of these agreements to any guarantee regardless of how it is referred to. If, without previous
written approval from the contractor, the principal commences disassembly, repair or other work on the
product or allows it to be commenced, then every agreement with regard to guarantee shall be void.
6. Claims regarding defects must be submitted in writing as quickly as possible and not later than 14 days
after the discovery of such. All claims against the contractor regarding faults shall be void if this term is
exceeded. Claims pertaining to the guarantee must be submitted within one year of the valid complaint on
penalty of invalidity.
7. If the contractor replaces components/products under the terms of his guarantee obligations, the replaced
components/products shall become the property of the contractor.
8. Unless otherwise agreed, a guarantee on repair or overhaul work carried out by the contractor or other
services shall only be given on the correctness of the manner in which the commissioned work is carried
out, this for a period of 6 months. This guarantee only covers the single obligation of the contractor to
carry out the work concerned once again in the event of unsound work. In this case, subarticle 3A shall
apply equally.
9. No guarantee shall be given regarded the inspection conducted, advice given and similar matters.
10. Alleged failure to comply with his guarantee commitments on the part of the contractor shall not absolve
the principal from his obligations ensuing from any agreement concluded with the contractor.
11. No guarantee shall be given on products which form a part of, or on work and services on, goods older
than 8 years.
58
Revision 0305:
1. Alarm pressure switch (Figure 12A, 13A and 18A) added
Revision 0107:
7.1.1 Corrected red pointer is 3, knob is 1, graduated dial is 2.
59
60