You are on page 1of 158

Lionel Ng, LPBS - Low Voltage Products

Welcome To ABB
Technical Sharing Session
ABB Group
September 24, 2013 | Slide 1

MV & LV Transformer Substations


Theory & Short Circuit Calculation
ABB Group
September 24, 2013 | Slide 2

Contents

General information on MV/LV transformer substations


Calculation of short-circuit currents
Choice of protection and control devices
Example of study of a MV/LV network

General Information
MV/LV Transformer Substations
The electrical substations can be divided into
public substations
belong to the electricity utility
supply private users in AC single-phase or three-phase current
(230V and 400V)
urban type in bricks
rural type installed externally directly on the MV pylon

private substations
belong to the user
civil users (schools, hospitals, etc.) and industrial users
are mostly located in the same rooms of the factory

General Information
MV/LV Transformer Substations
Typical structure of a substation
where the switching apparatus of
the utility is installed.
where the measuring units
are located
contains the transformer and
the MV and LV switching
apparatus

General Information
MV/LV Transformer Substations
Most common management methods

Substation with a single transformer

General Information
MV/LV Transformer Substations
Most common management methods

It is possible to use the


Emax with a wire interlock
(mechanical interlock)
between two CBs

Substation with two transformers


(one as a spare for the other)

General Information
MV/LV Transformer Substations
Most common management methods

two transformers which operate


in parallel on the same busbar

General Information
MV/LV Transformer Substations
Most common management methods

It is possible to use the


Emax with a wire interlock
(mechanical interlock)
between three CBs

two transformers which operate simultaneously on


two separate half-busbars

General Information
MV/LV Transformer Substations
MV/LV transformers
is the most important part of the transformer substation
single transformer for low powers (up to 630kVA - 800kVA)
several units in parallel for higher powers (1000kVA - 2500kVA)
type of cooling system
air
oil

most used
AN cooling with natural air circulation
ONAN cooling with natural oil and air circulation types

General Information
MV/LV Transformer Substations
MV/LV transformers

ONAN transformer containing more than 500 kg of oil (> 800kVA)

General Information
MV/LV Transformer Substations
MV/LV transformers
one single trafo or two trafos in parallel?

750M
VA

1600kVA
6%

800kVA
4%

400V

750M
VA

800kVA
4%
400V

37 kA

55kA

General Information
MV/LV Transformer Substations
Management philosophy for the protections
L1 trip
ensured service continuity

General Information
MV/LV Transformer Substations
Management philosophy for the protections
ILV1 and CLV trip
power supply is maintained to the half-busbar

trip

trip

General Information
MV/LV Transformer Substations
Management philosophy for the protections
IMV1 and ILV1 trip to isolate the trafo affected by the fault
ensured service continuity
a logic for the disconnection of non-priority loads should be
foreseen

General Information
MV/LV Transformer Substations
Management philosophy for the protections
IMV1 trip, ILV1 trip for pulling
service continuity of the whole plant
a logic for the disconnection of non-priority loads should be
foreseen

General Information
MV/LV Transformer Substations
LV protection devices
L function protection against
overload

General Information
MV/LV Transformer Substations
LV protection devices

S function protection against


delayed short-circuit

General Information
MV/LV Transformer Substations
LV protection devices

I function protection
against instantaneous
short-circuit

General Information
MV/LV Transformer Substations
LV protection devices

G function protection
against earth-fault

MV/LV Transformer Substations


Calculation of Short Circuit Currents
IEC 60909-0 (CEI 11-25)
Short-circuit:
Accidental or intentional conductive path between two or more
conductive parts forcing the electric potential differences between
these conductive parts to be equal or close to zero

Short-circuit current:
Overcurrent resulting from a short-circuit in an electric system

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Main components involved in a short-circuit calculation
Distribution networks
Generators
Transformers
Asynchronous motors
Cables

Each component of the network is replaced by its


relevant impedance

Zknet

ZcMV

ZTR

ZcLV

MV/LV Transformer Substations


Calculation of Short Circuit Currents
The equivalent network is solved according to standard
electrotechnical rules (circuits in series / in parallel)
Zkne

ZcM

ZT

ZcLV
Un

Ik

Un

3 Z knet Z cMV Z TR Z cLV

Ik

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Distribution network
it is necessary to know the network short-circuit power
from 250MVA to 500MVA Un 30kV
from 700MVA to 1500MVA Un > 30kV
according to IEC 60076-5

Z knet

Un2

Sknet

Un
3 Iknet

MV/LV Transformer Substations


Calculation of Short Circuit Currents

Generators
it is necessary to know
rated apparent power Sn
rated voltage Un
subtransient reactance xd
from 10% to 20% smooth rotor (isotropic machines)
from 15% to 30% salient pole rotor (anisotropic machines)

"
2
x
U
X "d d n
100 Sn

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Transformer
it is necessary to know

rated apparent power Sn


primary rated voltage voltage U1n
secondary rated voltage U2n
short-circuit voltage uk% from 4% to 8%
according to IEC 60076-5

Z TR

uk % U22n

100 Sn

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Asynchronous motors
In case of short-circuit it functions as a
generator with a xd from 20% to 25%
a current equal to 4-6 times the In can be
assumed as contribution to the short-circuit
the minimum criteria for taking into
consideration the phenomenon
(Ik shortcircuit without motor contribution)

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example
Sk = 500 MVA
UMV= 20 kV

ZcMV = 0.01

Sn = 400 kVA
U= 20/0.4 kV
uk% = 4 %
ZcLV = 0.06

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example
U

Z u20kV

U2
20 103

0.8
Sk
500 106

400
Z u400V Z u20kV
200002

3.2 104

Sk = 500
MVA
UMV= 20 kV

Zu = 0.32
m

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example
U
Zu = 0.32 m
2

400
Z cMV 400V Z cMV 20kV
200002

4 106

ZcMV = 0.01

ZcMV = 410-3 m

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example

U
Zu = 0.32 m

2
400 0.016
uk % UnLV
4
ZT

100 Sn
100 400 103
2

ZcMV = 410-3 m

Sn = 400 kVA
U= 20/0.4 kV
uk% = 4 %

ZT = 0.016

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example

U
Zu = 0.32 m

ZcMV = 410-3 m

ZT = 16 m

ZcLV = 0.61
m

ZcLV = 0.61 m

MV/LV Transformer Substations


Calculation of Short Circuit Currents
Example

Sk = 500
MVA
UMV= 20 kV

Zu = 0.32 m

ZcMV = 410-3 m

Ik

Ik

Un

3 Z u Z cMV Z T

Un

ZT = 16 m

14.1kA

3 Z u Z cMV Z T Z cLV

ZcLV = 0.61 m

13.6kA

Un = 400 V

MV & LV Transformer Substations


General Information about Circuit
Breakers
ABB Group
September 24, 2013 | Slide 34

MV/LV Transformer Substations


IEC Standard Definition of Circuit Breakers
Definitions

Circuit-breaker: a mechanical switching device capable of making,


carrying and breaking currents under normal circuit conditions and
also making, carrying for a specified time, and breaking currents
under specified abnormal circuit conditions such as those of
overload or short-circuit (IEC 60947-1 def. 2.2.11)

MV/LV Transformer Substations


IEC Standard Definition of Circuit Breakers
Definitions

Moulded case CB: a circuit-breaker having a supporting


housing of moulding insulating material forming an
integral part of the circuit-breaker (Isomax / Tmax /
Formula)

Air CB: a circuit-breaker in which the contacts open and


close in air at atmospheric pressure (Emax)

MV/LV Transformer Substations


IEC Standard Definition of Circuit Breakers
Definitions

Current-limiting circuit-breaker: a circuit-breaker with a


break-time short enough to prevent the short-circuit
current reaching its peak value (IEC 60947-2 def. 2.3)

MV/LV Transformer Substations


Current-Limiting Circuit Breakers
I

Prospective
peak value

Limited
peak
value

t
Specific let-through
energy (I2t)

Prospective shortcircuit current


Limited short-circuit
current

MV/LV Transformer Substations


Current-Limiting Circuit Breakers

Ip

Limited
peak
value
Specific let-through
energy

Icc

Prospecti
ve peak
value

Prospective shortcircuit current

I2t

Limited shortcircuit current

Icc

go

MV/LV Transformer Substations


Current-Limiting Circuit Breakers
Curva di limitazione

Ip
1E5kA

T2L160 In160 A
1E4kA

40 kA

1E3kA

Prospective
peak value

84 kA
100kA
16 kA
10kA

Limited peak
value

1kA

1E-2kA

0.1kA

1kA

Irms

10kA

40 kA

MV/LV Transformer Substations


Selection of Protective Devices
Generalities about the main electrical parameters
Rated operational voltage Ue: the value of voltage which
determines the application and to which all the other
parameters are referred to
Rated uninterrupted current Iu: the value of current which the
device is able to carry for an indefinite time. It defines the size
of the CB
Rated current In: the value of current which characterizes the
protection release installed. Is often related to the rated
current of the load protected

MV/LV Transformer Substations


Selection of Protective Devices
Generalities about the main electrical parameters
Rated ultimate short-circuit breaking capacity Icu: it is the
r.m.s. value of the symmetrical component of the short-circuit
current which the circuit-breaker is able to break (test cycle Ot-CO)
Rated service short-circuit breaking capacity Ics: it is the r.m.s.
value of the symmetrical component of the shortcircuit current
which the circuit-breaker is able to break (O-t-CO-t-CO)

T5N400 PR221DS-LS/I In 320

Icu

MV/LV Transformer Substations


Selection of Protective Devices
Ultimate Short-Circuit Breaking Capacity (Icu):
breaking capacity for which the prescribed conditions
according to a specified test sequence do not include
the capability of the CB to carry its rated current
continuously

- test sequence: O - 3 min - CO


- dielectric withstand at 2 x Ue
- verification of overload release at 2.5 x I1

MV/LV Transformer Substations


Selection of Protective Devices
Service Short-Circuit Breaking Capacity (ICS):
breaking capacity for which the prescribed conditions
according to a specified test sequence include the
capability of the CB to carry its rated current continuously
- test sequence: O - 3 min - CO - 3 min CO
(25%-50%-75%-100% of Icu)

- operational performance capability: (5% of Noperating cycle


for operational performance capability- table 8 60947-2)

- dielectric withstand at 2 x Ue
- verification of temperature rise at Iu (the temperature doesnt
exceed the limits of table 7 60947-2)

- verification of overload release at 1.45 x I1

MV/LV Transformer Substations


Selection of Protective Devices
Generalities about the main electrical parameters
Rated short-circuit making capacity Icm: it is the maximum
prospective peak current which the circuit-breaker must be
able to make
Icm=n x Icu

T5N400 PR221DS-LS/I In 320

Icu 36kA Icm 75.6 kA @415V

MV/LV Transformer Substations


Selection of Protective Devices
Generalities about the main electrical parameters
Rated short-time withstand current Icw: it is the r.m.s. value of
the alternate current component which the circuit-breaker is
able to withstand without damages for a determined time,
preferred values being 1s and 3 s
Defined for category B only

MV/LV Transformer Substations


Selection of Protective Devices

MV/LV Transformer Substations


Selection of Protective Devices
Generalities about the main electrical parameters
Dont forget

Ue Un
Icu or Ics Ik
Icm Ip

Ue, Icu, Ics, Icm?

MV/LV Transformer Substations


Selection of Protective Devices
Protection of feeders
against overload
Ib In or I1 Iz

against short-circuit
I2t k2S2

In
Iz S

Ib

MV/LV Transformer Substations


Selection of Protective Devices

MV/LV Transformer Substations


Selection of Protective Devices

MV/LV Transformer Substations


Selection of Protective Devices
Protection of generators
Ingen I1
I3 or I2 2.5-4 x Ingen

MV/LV Transformer Substations


Selection of Protective Devices
Protection of transformers
InT I1
Upstream CB

I3 or I2 Iinrush

MV/LV Transformer Substations


Example of an MV/LV Network
20kV

Steps
determining the short-circuit
currents
choosing the CB
setting of the MV overcurrent
protection
setting of the LV overcurrent
protection

400V

MV/LV Transformer Substations


Example of an MV/LV Network
20kV

400V

MV/LV Transformer Substations


Example of an MV/LV Network
20kV

400V

Low voltage selectivity


with ABB circuit breakers
Selectivity definitions and Standards
ABB Group
September 24, 2013 | Slide 57

Agenda
Low voltage selectivity with ABB circuit breakers

Definitions and Standards

Selectivity techniques
Back-up protection

Introduction
What is selectivity?
Selectivity (or discrimination)

A is the supply side circuit


breaker (or upstream)

is a type of coordination of two or


more protective devices in series.
Selectivity is done between
one circuit breaker on the supply side
and one circuit breaker, or more than
one, on the load side.

B and C are the load side circuit


breakers (or downstream)

Introduction
Protection system philosophy

Reduce the stress and prevent damage

Minimize the area and the duration of


power loss

DAMAGE REDUCTION

Better selectivity

FAULT

CONTINUITY OF SERVICE

Fast fault elimination

Main purposes of coordination


Selectivity purpose
Selective coordination among devices
is fundamental for economical and technical reasons
It is studied in order to:

rapidly identify the area involved in the problem;

bound the effects of a fault by excluding just the affected zone of the
network;

preserve the continuity of service and good power quality to the sound
parts of the network;

provide a quick and precise identification of the fault to the personnel in


charge of maintenance or to management system, in order to restore
the service as rapidly as possible;

achieve a valid compromise between reliability, simplicity and cost


effectiveness.

Standards definition
Selectivity
The definition of selectivity

IEC 60947-1 Standard: Low voltage equipment


Part 1: General rules for low voltage equipment

IEC 60947-1
def. 2.5.23

Trip selectivity (for overcurrent) is a coordination between the


operating characteristics of two or more overcurrent protection
devices, so that, when an overcurrent within established limits
occurs, the device destined to operate within those limits trips
whereas the others do not trip

Overcurrent selectivity
Example
In occurrence of a fault
(an overload or a short circuit)
if selectivity is provided
only the downstream circuit
breaker opens.

Overcurrent selectivity
Example
In occurrence of a fault
(an overload or a short circuit)
if selectivity is not provided
both the upstream and the
downstream circuit breakers
could open
All the system is out of service!

Standards definition
Partial and total selectivity
IEC 60947-2
def. 2.17.2 - 2.17.3

A and B connected in series:


partial selectivity and total selectivity.

Standards definition
Partial selectivity
Partial selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection up to a
given level of overcurrent, without making the other device trip.

Is is the ultimate
selectivity
value!

B opens only according to fault current


lower than a certain current value;
values equal or greater than Is
will give the trip of both A and B.
Is = ImA

Standards definition
Total selectivity
Total selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection without
making the other device trip.

Only B trips for every current value


lower or equal to the maximum
short-circuit current.
Is = Ik

Standards definition
Partial and total selectivity
Upstream circuit breaker A

T4N 250 PR221DS In = 250 (Icu = 36kA)


Downstream circuit breaker B
S 294 C100 (Icu = 15kA)

Selectivity analysis
Time-current curves

Overload zone
Thermal protection
L protection

Time-current selectivity

Short-circuit zone
Magnetic protection
S, D, I and EF protections

Current, time, energy, zone,


directional, zone directional selectivity

Selectivity analysis
Real currents
Real currents circulating through the circuit breakers

I>

I>

IA = IB
tA

I>

I>

I>

I>

I>

I>

I>

IA = (IB + Iloads) / 2

IA = IB + Iloads
tA
tB

I>

I>

tA

tB

tB

IA=IB

IB IA

IA

IB

Agenda
Low voltage selectivity with ABB circuit breakers

ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 71

Definitions and Standards

Selectivity techniques

Back-up protection

Introduction
Selectivity techniques

Current selectivity

Time selectivity

Energy selectivity

Zone (logical) selectivity

ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 72

Current selectivity
Base concept

Current selectivity: closer to the power supply


the fault point is, higher the fault current is
3kA

In order to guarantee selectivity,


the protections must be set to different
values of current thresholds
1kA

tA

The ultimate selectivity value


is equal to the instantaneous trip threshold
of the upstream protection device

Other methods are needed to have a total


selectivity

tA

A
Ultimate
selectivity
value

tB

ImB

ImA

Current selectivity
Example
Circuit breaker A will be set to a value which does not
trip for faults which occur on the load side of B.
(I3Amin >1kA)
Circuit breaker B will be set to trip for faults which
occur on its load side (I3Bmax < 1kA)
104s

Is

103s

Is = I3Amin

102s
10s

Here the selectivity is a total selectivity,


because it is guaranteed up to the maximum
value of the short-circuit current, 1kA.

1s
B
10-1s
10-2s

0.1kA

1kA

3kA

10kA

Current selectivity
Plus and minus
Plus
Easy to be realized
Economic
Instantaneous

CURRENT SELECTIVITY
Minus
Selectivity is often only partial
Current thresholds rise very quickly

Time selectivity
Base concept

Time selectivity is based on a trip delay of the upstream


circuit breaker, so to let to the downstream protection the
time suitable to trip

Setting strategy:
progressively increase the
trip delays getting closer to
the power supply source

On the supply side


the S function is required

Time selectivity
Example
A will be set with the current threshold I2
adjusted so as not to create trip overlapping
and with a trip time t2 adjusted so that
B always clears the fault before A

B will be set with an instantaneous trip


against short-circuit

I
k
104s

Is

The ultimate selectivity value is:

103s
102s
10s

1s

I2
t2

10-1s
10-2s
0.1kA

1kA

10kA

100kA

Is = IcwA

(if function I = OFF)

Is = I3minA

(if function I = ON)

Time selectivity
Example
Which is the problem of time selectivity?

In the case of fault occurring at the busbars,


circuit breaker A takes a delayed trip time t2

I
k

The network must withstand high values of


let-through energy!

104s
103s
102s
10s

If there are many hierarchical levels, the


progressive delays could be significant!

1s

t2

10-1s
10-2s
0.1kA

1kA

10kA

100kA

Time selectivity
Plus and minus
Plus
Economic solution
Easy to be realized

TIME SELECTIVITY
Minus
Quick rise of setting levels
High values of let-through energy

Energy selectivity
Base concept
Energy selectivity is based on the currentlimiting characteristics of some circuit breakers

104s

103s
A

102s
10s
1s
B
10-1s
10-2s

0.1kA

1kA

The ultimate current


selectivity values
is given by the
manufacturer
(Coordination tables)

10kA

Current-limiting circuit breaker


has an extremely fast trip time,
short enough to prevent the
current from reaching its peak

Energy selectivity
Example

104s
103s

Is = 20kA

Circuit breaker A conditions:

102s
B
10s

I3=OFF

1s

S as for time selectivity

10-1s

10-2s

0.1kA

1kA

10kA

Energy selectivity
Plus and minus
PLUS
High selectivity values
Reduced tripping times
Low stress and network disturbance

ENERGY SELECTIVITY
MINUS
Increasing of circuit breakers size

Zone selectivity
Base concept

Zone selectivity is an evolution of the time


selectivity, obtained by means of a electrical
interlock between devices
locking
signal

The circuit breaker which detects a fault


communicates this to the one on the supply side,
sending a locking signal

Only the downstream circuit breaker opens,


with no need to increase the intentional time
delay

Fault

Zone 3

A Does Not Open


B Does Not Open

Zone 2

Zone 1

Zone selectivity
Example

C Opens

Zone selectivity
Specifications

an external source of 24V

dedicated trip units

PR223EF for Tmax T4, T5 and T6

PR332/P for Tmax T7 and T8

PR122/P and PR123/P for Emax

PR332/P and PR333/P for X1

Is

up to 100kA for Tmax

Is

up to Icw for Emax

Zone 2

a shielded twisted pair cable

Zone 3

Zone 1

Zone selectivity needs:

It is possible to obtain zone selectivity between Tmax and Emax

Zone selectivity
Plus and minus
PLUS
Trip times reduced
Low thermal and dynamic stress
High number of hierarchical levels
Can be made between same size circuit breakers

ZONE SELECTIVITY
MINUS
Cost and complexity of the installation
Additional wiring and components

Agenda
Low voltage selectivity with ABB circuit breakers

ABB Group, BU Breakers and Switches


September 24, 2013 | Slide 87

Definitions and Standards

Selectivity techniques

Back-up protection

Back-up protection
What is back-up protection?
Back-up protection (or cascading)
is a type of coordination of two protective
devices in series which is done in electrical
installations where continuous operation is
not an essential requirement.

Back-up protection
excludes the use
of selectivity!!!

Back-up protection
Standards definition
The definition of back-up is given by the
IEC 60947-1 Standard: Low voltage equipment

Part 1: General rules for low voltage equipment

IEC 60947-1
def. 2.5.24

Back-up is a coordination of two overcurrent protective


devices in series, where the protective device on the supply
side, with or without the assistance of the other protective
device, trips first in order to prevents any excessive stress on
downstream devices.

Back-up protection
Base concept

Back-up is used by those who need


to contain the plant costs

The use of a current-limiting circuit


breaker on the supply side
permits the installation of lower performance
circuit breakers on the load side

Both the continuity of service and the selectivity are sacrificed

Back-up protection
Application example

T4L 250

Ik = 100 kA
Icu (T4L+T1N) = 100kA

T4L 250

T4L 250

T4L 250

Icu = 120kA

T1N 160

T1N 160

T1N 160

Icu = 36kA

Back-up protection tables

Back-up protection
Application example

T4L 250
A

Ik = 100kA

Icu (T4L+T1N) = 100kA

Ik = 100kA
T1N 160

T1N 160

T1N 160

General power supply


is always lost

Back-up protection
Plus and minus

Plus

Economic solution
Quick tripping times

BACK-UP PROTECTION
Minus

No selectivity
Low power quality

Example of Selectivity

~
T5H 630A

70kA

T3N 160A

36kA

Incoming = T5H 630A (70kA


rating) Outgoing = T3N 160A
(36kA rating)
Results: The co-ordination
resulted in a conditional shortcircuit of 65kA for the T3 mccb!

Iz

The discrimination is up to 20kA.

65kA

Example of Selectivity
Discrimination

Example of Selectivity
Back-Up

Example of Selectivity
Meaning of Selectivity Value
T5H

70kA

T5H 70kA
T3N 36kA
T3N

Fault level at Y is 20kA


Y is 20kA

36kA

Example of Selectivity
Meaning of Selectivity Value
T5H

T3N

70kA

T5H
20kA
T3N

36kA

Example of Selectivity
Meaning of Selectivity Value

5kA fault

T5H
ON

T3N
Trip

T5H

70kA

T3N

36kA

5kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON

T3N
Trip
Trip

T5H

70kA

T3N

36kA
10kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON
20kA fault Trip

T3N
Trip
Trip
Trip

T5H

70kA

T3N

36kA
20kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON
20kA fault Trip
36kA fault Trip

T3N
Trip
Trip
Trip
Trip

T5H

70kA

T3N

36kA
36kA

Example of Selectivity
Meaning of Selectivity Value

5kA fault
10kA fault
20kA fault
36kA fault
65kA fault

T5H
ON
ON
Trip
Trip
Trip

T3N
Trip
Trip
Trip
Trip
Trip

T5H

70kA

T3N

36kA
65kA

MV/LV Transformer Substations


Selection of Protective & Control Devices
Motor co-ordination
ABB offers co-ordination tables

MV/LV Transformer Substations


Selection of Protective & Control Devices
Co-ordination between CBs and switch-disconnectors
400V

T2S160

T1D160

DOC
Electrical Installation Calculation and
Dimensioning
ABB Group
September 24, 2013 | Slide 107

Contents
Introduction
Aim of the application
Target users
Products managed
How it works
Features

Support Tools
ABB Software Desktop
Assistance
How to obtain the software

DOC
Introduction

ABB Group
September 24, 2013 | Slide 109

Aim of the application

DOC is the software for Electrical Installations Calculation


and Dimensioning

Introduction
Aim of the application
Target users
Product managed

Draw single-line diagrams

How it works

Perform electrical calculation according to the


Standards

Choose the correct switching and protecting devices


(MV and lv devices)

Set the trip units and check for discrimination

Prepare a complete project documentation

Features

Support Tools
ASD
Assistance
How to obtain the
software

Target user

Introduction
Aim of the application
Target users
Product managed

DOC is complete and precise, but smart and flexible and


can be used from everyone interested in calculating
electrical installation or part of them

Consultants

Electrical Engineers

Panel builders

Installers

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Product managed

DOC allows and the selection of a wide range of ABB


Products

Introduction
Aim of the application
Target users
Product managed

Medium Voltage products

How it works

Low Voltage products

Motors

Transformers

Features

Support Tools
ASD
Assistance
How to obtain the
software

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Air Circuit- Breakers

New Emax

Emax

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Molded Case Circuit Breakers

Tmax

Isomax

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Miniature Circuit Breakers

System PRO M

System PRO M Compact

S800

Smissline

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

RCCBs

System PRO M

System PRO M Compact

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Fuses

OFAX

OFASB

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Switch Fuses

E930

OESA

OS

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Disconnectors

New Emax MS

Emax MS

Tmax D

Isomax D

OT

OETL

E200

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Contactors

AF

EN

ESB

E250

E259

E260

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Manual Motor Starter

MS116, MS325, MS450, MS495, MS496

MO325, MO450, MO495, MO496 , MO497

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Low Voltage Products

Thermal Overload

TAxxDU, ExxDU

UMC-22

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Medium Voltage Products

Circuit breaker

Secondary distribution SF6 and Vacuum up to 24kV 630A 16kA

Primary distribution SF6 and Vacuum up to 36kV 3150A 50kA

Product managed

Introduction

Medium Voltage Products

Circuit breaker

Aim of the application


Target users
Product managed

REF542Plus/DK

How it works

PR521/DK

PR521/P (50-51)

PR521/P (50-51-51N)

REF542Plus

REF610

REJ525

PR512/P (50-51)

PR512/P (50-51-50N-51N)

PR512/PD

Features

Support Tools
ASD
Assistance
How to obtain the
software

Product managed

Introduction

Medium Voltage Products

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Disconnectors

SHS2/A

SHS2/I

SHS2/IB

SHS2/IF

SHS2/N-I

Earth Disconnectors

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Medium Voltage Products

Switch Disconnectors

SHS2/T1

SHS2/T1M

SHS2/T2

SHS2/T2F

SHS2/T2M

SHS2/T2MF

SHS2/N-T1

SHS2/N-T1M

SHS2/N-T2

SHS2/N-T2F

SHS2/N-T2M

SHS2/N-T2MF

Product managed

Introduction

Medium Voltage Products

General Purpose Fuses

Aim of the application


Target users
Product managed

CEF 7.2kV 200A

How it works

CEF 12kV 125A

CEF 17.5kV 100A

Features

Support Tools
ASD
Assistance
How to obtain the
software

CEF 24kV 80A

Motor Fuses

CEM 7.2kV 315A

CEM 12kV 100A

Product managed

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Medium Voltage Products

Cables

Sized according to
the ABB
XLPE Cable Systems
Users Guide"

Product managed

Introduction

Other Products

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Motors

M2xxx

M3xxx

Transformers

Oil Distribution Transformers

RESIBLOC

How
DOC it works
How it Works

Features - Professional and Light Profiles

Introduction

DOC can be used with 2 different profiles

Depending on the user needs and skills it can be recommended to use


the Light Profile which hides the advanced and complex features

DOC Light is for ...

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

... first time, unskilled DOC users

... installers panel builders


who need a simple tool to draw
and verify small networks

DOC Professional is for ...

... skilled DOC users

... customers working on industrial


applications

... engineering companies


OEMs looking for a powerful
calculation and design tool

Features - Single line diagram drawing

Introduction

Different layout available:

Aim of the application


Target users
Product managed

How it works
Features

Blank Page

More flexible

Allows representing rings and meshes

Main project data available beside the objects

Support Tools
ASD
Assistance
How to obtain the
software

Column Page

Faster and easier drawing

Main project data available in the grid

Features - Single line diagram drawing

Introduction

Different ways to draw the symbols:

Aim of the application


Target users
Product managed

By Single Objects

More flexible

Allows representing rings and meshes

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

By Macros

Faster and easier drawing

Note: it is possible to use Single Objects


and Macros independently from the layout

Features - Single line diagram drawing

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

When using the Column layout, Objects are numbered by Page &
Column

All the object in the same feeder have the same number

I.e: Page =1, Column=3 leads to QF1.3+ WC1.3 +L1.3

Features - Single line diagram drawing

Introduction

It is possible to draw one scheme on more than one page

Use the Add Sheet and Change layout commands to prepare new empty
pages

Use the Cross References to connect two objects

Use the Previous/Next Sheet commands to turn the pages

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Features - Plant General Properties Window

This window is shown when starting a new project. Set all the options
carefully to spare time when drawing and calculating the electrical
installation

Main options:

Introduction
Aim of the application
Target users
Product managed

How it works

Features

Support Tools
ASD
Assistance
How to obtain the
software

Power supply definition


Voltage level
Default distribution system
Default number of phases
Method for SC calculations
Method for cable sizing
Options for addressing the device
selection

Features - Suggested Workflow

A toolbar on the right side of the working area suggests the preferred
way to develop a project with DOC

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools

ASD
Assistance
How to obtain the
software

MV diagram drawing
LV diagram drawing
Calculation and automatic project dimensioning
Protection and discrimination verification thru the curves
Auxiliaries scheme drawing
Switchboard configuration
Printouts

Features - MV Diagram Drawing

The Medium Voltage section of the project can be drawn by the Macros
of the typical units of the Unimix switchboard or by Objects for more
flexibility

To pass to the Low Voltage section it is necessary to use the


transformers (when a low voltage section is not needed, the drawing
can be completed with MV Loads or Motors)

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Features - Lv Diagram Drawing

The Low Voltage section of the project can be drawn by the Macros or
by Objects for more flexibility

The Macros available represents the most common Objects


combinations; not available combinations can be realized using the
Objects

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Power Supply

Support Tools
ASD
Assistance
How to obtain the
software

1 Macro = 1 Feeder = Many


single objects

I.e.: CB+Cable+Load

I.e.: Fuse+Cable+Load

Faster drawing

Switchboard Arrival

Sub-Switchboard

Interlock graphical representation

Pop-up window
Feeders

When drawing a feeder it is


possible to insert the main

Motor Coordination

data making the drawing phase faster

Features - Calculation and automatic dimensioning

Introduction
Aim of the application
Target users
Product managed

Load-Flow

DOC can calculate the current distribution, the voltage profile


and the voltage drop profile in load condition considering:

Section with different number of phases

Features

Unbalanced loads (automatic balance is optional)

Support Tools

Transformer Voltage Regulator

Cable dimensioning

Presence of meshes

More distribution systems

How it works

ASD
Assistance
How to obtain the
software

Features - Calculation and automatic dimensioning

Introduction

Cable dimensioning

Given the power required by the loads and the motors, DOC is
able to size the cables in an iterative process bringing to the
section optimization and the current profile calculation

DOC implements several calculation methods

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

IEC 60364

CEI 64-8 Italian standard

VDE 298 German standard

NFC 15-100 French standard

UNE 20460 Spanish standard

IEC 60092 (for naval installation)

Features - Calculation and automatic dimensioning

Introduction

Short Circuit

DOC can calculate the maximum and minimum short


circuit currents, with or without the motor contribution,
for symmetrical and non-symmetrical faults, for different
times

DOC implements several calculation methods

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

IEC 60909 LV\MV network, AC, 50-60Hz

IEC 60363 Naval

ABB SACE A Division of ABB S.p.A., MK-TO, 2009 June

NFC 15-100 French national standard

Symmetrical components method

Features - Calculation and automatic dimensioning

Introduction
Aim of the application
Target users
Product managed

Configuration Management

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

In DOC it is possible to
simulate different
scenarios for the electrical
installation defining the
open/closed position for
the switching and
protecting devices
The calculation are
performed in the worst
condition

Features - Calculation and automatic dimensioning

Introduction

Devices Selection

The calculation leads to an automatic proposal for all


the devices drawn in the scheme

When more than one product is technically suitable,


DOC proposes the basic one

It is possible to change the solution proposed by DOC


and to lock the user choice thanks to the padlocks
present in all the selection windows

Aim of the application


Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Features - Calculation and automatic dimensioning

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

DOC gives the possibility to perform the temperature riseassessment according to IEC 60890 in a early stage of the
installation design

Features - Curves

With DOC it is possible to manage

Introduction

Aim of the application


Target users
Product managed

Time-current diagrams for the devices present in the scheme

Set the thermomagnetic and electronic trip units

Realize discrimination studies involving MV and LV devices

Verify the cable protection

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Time-Current curve LLL

1E4s

1E3s

100s

10s

-TM1

1s

-QF2, HD4/UniMix-R 24.06.12 P230, REF542Plus/DK


0.1s
-QF5, E4S 4000 PR121-LI 4000A
1E-2s
1E-2kA

0.1kA

1kA

10kA

100kA

Features Switchboard configuration

With DOC it is now possible to configure switchboard:

By using a Wizar configuration: three steps guide procedure to create a


switchboard.

By using a toolbar on the left side of working area:

Insert and move column, Kit and device

Tracking busbar system and temperature rise assessment

Layer management (door, panel and plate layer, show hide busbars)

Modify switchboard dimension

Smart commands (switchboard table, labels, accessories)

Features - Project documentation

Different reports sections allows the creation of a unique file


documenting the project

Introduction
Aim of the application
Target users
Product managed

The report sections can be added/removed according to the needs

Calculation hypothesis

Features

Short circuit calculations

Support Tools

Cable Protections

MV / LV devices list and settings

How it works

ASD
Assistance
How to obtain the
software

Export in MS Excel is available

The report language can be different from the current language

Support
Tools
DOC
Support Tools

ABB Software Desktop

ABB Software Desktop (ASD)

Introduction
Aim of the application
Target users
Product managed

ASD is automatically installed with the first installed software

ASD functionalities:

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Allows to run the software


Manage the language
Registration
Software upgrade
Contact Software Support

ABB Software Desktop

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

ABB Group
September 24, 2013 | Slide 152

Registration

Visit www.bol.it.abb.com

Click on Profile Management

ABB Software Desktop

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

ABB Group
September 24, 2013 | Slide 153

Registration

Click on New User

ABB Software Desktop

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Starting on a New
Project
The Single Line Diagram

ABB Group
September 24, 2013 | Slide 154

Registration

Click on Subscribe

ABB Software Desktop

Registration

Introduction
Aim of the application
Target users
Product managed

After registering via internet ,


you will receive immediately
an e-mail with ID and PSW
to access the Upgrade
Service

Use them to check for


available Upgrades before
starting using the Software

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

ABB Software Desktop

Upgrade DOC via internet

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Use The Automatic Upgrade


Service allows you to
maintain the software
aligned to the latest
improvements delivered
from ABB SACE them to
check for available
Upgrades before starting
using the Software

Assistance

Introduction
Aim of the application
Target users
Product managed

How it works

How to contact us Software support


Ask the ABB SACE Software Assistance for any question you may
have regarding the software tools

Features

Support Tools
ASD
Assistance
How to obtain the
software

Email

Call Center

software.tools@it.abb.com

+39 035 395 570

On line

http://www.bol.it.abb.com

How to obtain the software

Introduction
Aim of the application
Target users
Product managed

How it works
Features

Support Tools
ASD
Assistance
How to obtain the
software

Refer to the ABB Local Sales Organization for a free copy of the
software

You might also like