A NGEL LA ZA RO & A SSOCIA TES INTERNA TIONA L


(Consulting Engineer & Architects)
Date
: Jul-21-2014
Client : MAYNILAD
Subject : Analysis & Design of Basement Wall Nomenclature

SD - KIOSK-MYNLD
A.H. Sinconiegue
Jul-21-2014
Rhonda Divina A. Rapirap
Jul-21-2014
Angel Lazaro III. Ph.D
Jul-21-2014

PROPOSED FOOD KIOSK


SURCHARGE
t
RB

W3

PAE

W1
d5
d3

Psur
H

d4
h1
Psoil
d7
d2

W2
d1

d6

h
HEEL

TOE

Seismic Pressure Diag.

Surcharge Diag.

Soil Pressure Diag.

BASEMENT WALL SECTION

Fig. A - BASEMENT WALL NOMENCLATURE

Analysis and Design Refferences :


1.0 National Structural Code of The Philippines (NSCP) 2010, Volume 1 , 6th Edition for Building, Towers
and other Vertical Srtuctures
by :
Association of Structural Engineers in the Philippines. ( ASEP)
2.0 National Structural Code of the Philippines (NSCP) 1997, Volumn 2, 2ND Edition, Bridges
ASD(Allowable Stress Design)
by:
Association of Structural Engineers in the Philippines. ( ASEP)
3.0 AASHTO Bridge Design and Specification 2002-2010
by:

American Association of State Highway and Transportation Officials (AASHTO)

4.0 Design of Reinforced Concrete ACI 318-05 Code Edition, Seventh Edition
by:

Jack C. McCormac & James K. Nelson

Spreadsheet Condition
This spreadsheet is applicable only on non- slopping backfill and the use of this spreadsheet is only
for structure having the same configuration.
Wall Dimensions :
Total height of retaining wall, H
Height of the soil at the back of the wall, h1
Height of the soil at the exposed face of the wall, h2
Stem thickness, t
Total length of footing, L
Footing thickness, h
Surcharge Height, Sh =

Design Notes:
3300
3300
1200
250
1600
400
150

mm
mm
mm
mm
mm
mm
mm

- Neglect Soil Passive Pressure for Critical Design of Stem - NSCP 5.5.2
- Wall Inertia Effects not considered - NSCP 5.6.4
- Overall Stability with Earthquake Force (Seed & Whitman) - AASHTO 5.8.9.1
- Factor of Safety in Sliding and Overturning are Reduced to 75% of Original
Value at Earthquake Condition - AASHTO 5.8.9.1A
- Wall analyzed as Propped Beam.

A NGEL LA ZA RO & A SSOCIA TES INTERNA TIONA L


(Consulting Engineer & Architects)

REFERENCE

Date
: Jul-21-2014
Client
: MAYNILAD
Subject : Analysis & Design of Basement Wall Nomenclature
ANALYSIS AND DESIGN CALCULATION
A. WALL PARAMETERS
Total height of retaining wall, H
Height of the soil at the back of the wall, h1
Height of the soil at the exposed face of the wall, h2
Stem thickness, t
Total length of footing, L
Footing thickness, h
Surcharge Height, Sh =

Project ID
Cal'c by
Date
Checked by
Date
Aprroved by
Date

SD - KIOSK-MYNLD
A.H. Sinconiegue
Jul-21-2014
Rhonda Divina A. Rapirap
Jul-21-2014
Angel Lazaro III. Ph.D
Jul-21-2014
REMARKS

3300
3300
1200
250
1600
400
150

mm
mm
mm
mm
mm
mm
mm

B. CONCRETE PARAMETERS
Compressive strength @ 28 days, f'c
Modulus of Elasticity, Ec = 4700f'c
Unit weight (normal concrete), c

NSCP II-Sec. 8.7.1

28 Mpa
24870.06 Mpa
3
24 KN/m

C. STEEL PARAMETERS
MPa (Grade 40) for 12mm and smaller bars , fy
(to be used for temp. and shrinkage bars)

276 Mpa

MPa (Grade 60) for larger bars (>12mm) , fy


(to be used for main and shear bars)

414 Mpa

Modulus of Elasticity, Es
Main Horizontal bar size at exposed side, he
MainVertical bar size at exposed side, ve
Main Horizontal bar size at rear, hr
Main Vertical bar size at rear, vr
Main Reinforcement bar size at heel, h
Main Reinforcement bar size at toe, t
Temperature bar size, tb
Stirrup bar size, s

NSCP II-Sec.8.7.2

200000
10
10
10
12
12
12
10
12

Mpa
mm
mm
mm
mm
mm
mm
mm
mm

D. SOIL PARAMETERS
Unit Weight of Soil, s

NSCP II-Sec.5.5.5
NSCP II-Sec.5.5.5

E.

NSCP II-App. (H-9)


NSCP II-App. (H-8)

3
18 KN/m

Allowable Bearing Capacity on Site, qall


Surcharge, S
Factor of Saefty against Overturning, FSOT

150 kPa
2.7 kPa
2

Factor of Saefty against Sliding, FSSL


Angle of Internal friction of soil,
Backfill Slope angle,

1.5
30
0.00

Seismic Parameter
Importance Factor, I
Acceleration factor, A
Horizontal Acceleration Coefficient, 0.50*A = kh
Vertical Acceleration Coefficient, kv
Check Horizontal Acceleration, (1-kv)*TAN(-)
Arc tan(kh/(1-kv)) =

1
0.40
0.2
0.00
0.46
11.31

F. Miscellaneous Parameters

NSCP I-Sec.407.8.3.1
NSCP I-Sec.409.4.2.1
NSCP I-Sec.409.4.2.3
NSCP I-Sec.410.3.7.3
NSCP I-Sec.411.3.1.1

Consider 1.0 meter strip , b


Minimum Concrete Cover, Cc
Flexural strength reduction factor, f
Shear strength reduction factor, s
Compressive block depth reduction factor, 1
Normal weight concrete modification factor,
Coefficient of Friction, =

1000 mm
75 mm
0.9
0.75
0.85
1.0
0.5

G. Design Calculation
Calculation for coefficient of active pressure, ka = (1-sin)/(1+sin)
Consider 1.0 meter strip, b =
Calculation for active soil force, Psoil = 1/2*s*(h1-h)^2*ka

0.33
1000 mm
25.23 KN

Calculation surcharge force, Psur = (S/s)*(s)*(h1-T)Ka

7.569 KN

Calculation for negative unfactored moment @ base, Mnneg


Mnneg = Psoil*(h1-h)/7.5 + Psur*(h1-h)/8

12.499 KN.m

Calculation for negative factored moment @ base, Muneg = 1.6*Mn


Convert resultant force into a uniform load
For soil force, w1 = 2*Psoil/(h1-h)
For surcharge force, w2 = Psur/(h1-h)
Effective length, leff = (h1 - h)
Summation of moment about point B, Ra = Mn/leff + (w1*leff)/3 + (w2*leff)/3
Summation of moment about point A, RB = (w1*leff)/6 + (w2*leff)/2 - Mn/leff
Calculation for dist where max moment occur @ shear is zero, x
x2 =
7.884 2.61 x 3
0
by trial and error , x =

19.999 KN.m
17.4
2.61
2900
24.915
7.884

KN/m
KN/m
mm
KN
KN

1243.46 mm

Derived from shear diag.

Calculation for max positive unfactore moment, Mnpos


Mnpos = RB*x - w1*x^3/6*leff - w2*x^2/2

5.863 KN.m

Calculation for factore positve moment, Mupos = 1.6*Mnpos

9.382 KN.m

Check if assumed stem thickness is adequate to carry induced load by soil


Calculation for effective thickness, teff = t - cc - vr/2
2

NSCP I-Sec.410.6.1
NSCP I-Sec.410.6.1

Coefficient of Resistance, Rn = Mu/f*b*teff


Check for rho min , sqrt(fc')/4*fy
Rho min should not be less than with, 1.4/fy
Therefore adopt rho min, min =
Calculation for rho theoritical, = 0.85*fc'/fy ( 1 - sqrt( 1 - 2*Rn/0.85*fc'))
Use rho minimum for design

Derived from moment diag.

169.00 mm
0.78 MPa
0.0032
0.0034
0.0034
0.0019

Calculate for rho balnce, b = 0.85*fc'*1*600 / fy*(600 + fy)

N.A

Calculate for rho max, max = 0.75*b

N.A

Non-compliant

Not Aplicable

NSCP I-Sec.414.4.2

Therefor adopt design rho, des =

0.0034

Calculation for mechanical ratio, = des*fy/fc'

0.0500

Check for the req'd thickness of the stem, treq'd = sqrt(Muneg/(f*fc'*b**(1-0.59*))


Therefore, Assumed thickness is satisfactory
Vertical Reinforcement Design @ the rear face of the wall :
Calculate for minimum vertical steel area, Avmin = 0.0015*b*t

127.89 mm

NSCP I-Sec.411.4.1.1
NSCP I-Sec.411.2
NSCP I-Sec.411.6.6.1

NSCP I-Sec.412.4.2
NSCP I-Sec.412.4.2
NSCP I-Sec.412.4.1

Check for actual vertical steel area required, Aactual


Calculation for provide main steel area, Avr = PI()*(vr)2/4

2
113.10 mm

Calculation for total number bars, N = Aactual/Avr


Calculation for Spacing, Svr , b/N
Check vert spacing,
3*t
450
Therefore adopt actual spacing, Sactual
Therefore use :
6- 12mm vertical main bars spaced @
Check for Shear adequacy of wall:
Calculation for factored shear force, Vu =1.6( MAX( RA & RB))

6.0
160.00
750.00
450.00
160.00

NSCP I-Sec. 414.4.5


NSCP I-Sec. 414.4.5

NSCP I-Sec.410.6.1
NSCP I-Sec.410.6.1

pcs
mm
mm
mm
mm

Per meter strip

160mm O.C
39.863 KN

Nominal Shear provided by concrete, Vc = 0.17**SQRT(fc')*b*teff

152.025 KN

Calculation for factored shear provided by concrete, sVc

114.019 KN

Check Vu if < 0.5*sVc

57.009 KN

Stem thickness is adequate to carry shear stresses


Check for development length on bottom of wall footing:
Calculate for, ldc = 0.24*fy*vr/*SQRT(fc')
Calculate for, ldc = 0.043*fy*vr
Therefore adopt maximum value above, ldc
Check for minumum, ldcmm
Therefore adopt for actual development length, ldcact
Horizontal Reinforcement Design @ the rear face of the wall:
Calculate main steel area provided, Ahr = PI()*(hr)2/4

NSCP I-Sec. 414.4.3

375 mm
2
571.50 mm
2
mm
571.50

Calcualtion for the total vert. steel area required, Avreq'd = des*b*teff

NSCP I-Sec. 414.4.5


NSCP I-Sec. 414.4.5

Compliant

226
214
226
200

mm
mm
mm
mm

226 mm

Compliant

2
78.540 mm
2
1812.5 mm

Calculate for total hor. steel area req'd, Ahreq'd = 0.0025*(h1-h)*t


Calculation for total number of main bar, N = Ahreq'd / Ahr
Calculation for horizontal spacing, Shr = (h1-h)/N
Check hor. spacing :
3*t
450
Therefore adopt actual spacing, Sactual =
Therefore use :
24-10mm horizontal main bar
spaced @120mmO.C
Vertical Main Reinforcement Design @ the exposed face of the wall:
2
Coefficient of resistance, Rn = Mupos/f*b*teff
Check for rho min , sqrt(fc')/4*fy
Rho min should not be less than with, 1.4/fy
Therefore adopt rho min, min =
Calculation for rho theoritical, = 0.85*fc'/fy ( 1 - sqrt( 1 - 2*Rn/0.85*fc'))
Use rho minimum for design
Calculate for rho balnce, b = 0.85*fc'*1*600 / fy*(600 + fy)
Calculate for rho max, max = 0.75*b

24
120
750
450
120

pcs
mm
mm
mm
mm

0.365 MPa
0.0032
0.0034
0.0034
0.0009

Full Height of Wall

Non-compliant

N.A
N.A

Not Aplicable

NSCP I-Sec. 414.4.2

Therefor adopt design rho, des =


Vertical Reinforcement Design @ the exposed face of the wall :
Calculate for minimum vertical steel area, Avmin = 0.0015*b*t

0.0034
2
375 mm
2
571.50 mm

Calcualtion for the total vert. steel area required, Avreq'd = des*b*teff

571.50 mm
2
78.54 mm

Check for actual vertical steel area required, Aactual


2

Calculation for provide main steel area, Ave = PI()*(ve) /4

NSCP I-Sec. 414.4.5


NSCP I-Sec. 414.4.5

Calculation for total number bars, N = Aactual/Ave


Calculation for Spacing, Sve , b/N
Check vert. spacing, 3*t
450
Therefore adopt actual spacing, Sactual
Therefore use:
8 - 10mm vertical main bar spaced @
120mm O.C
Horizontal Reinforcement Design @ the exposed face of the wall:
2
Calculate main steel area provided, Ahe = PI()*(he) /4

NSCP I-Sec.414.4.3

Calculate for total hor. steel area req'd, Ahreq'd = 0.0025*(h1-h)*t

NSCP I-Sec. 414.4.5


NSCP I-Sec. 414.4.5

Calculation for total number of main bar, N = Ahreq'd / Ahe


Calculation for horizontal spacing, Shr = (h1-h)/N
Check hor. spacing :
3*t
450
Therefore adopt actual spacing, Sactual =
Therefore use:
24 - 10mm
horizontal main bar spaced @

8.0
120
750
450
120

78.540 mm
2
1812.5 mm
24
120
750
450
120

120mm O.C

pcs
mm
mm
mm
mm

pcs
mm
mm
mm
mm

Full Height of Wall

Fig.1

CHECK FOR STABILITY FOR NORMAL CONDITION


Pressure Diagram induced by Soil & Surcharge

RB

B
Note:

As per actual condition of the wall


the reaction induced by the slab at
the above level is considered.

W1

W3

d5
d3

Psur
d4
Psoil
d2

W2
d1

d6
A
h
HEEL

TOE

AASHTO 5.8.9.1A
NSCP II-Sec. 5.5.5
AASHTO 5.8.9.1A
NSCP II-Sec. 5.5.5

Weights and Forces: Consider 1.0 meter strip


Weight due to concrete wall, W1 = c*(h1-h)*b*t

17.400 KN

Weight due to concrete footing, W2 = c*L*b*h

15.360 KN

Weight to soil backfill, W3 = s*((L-t)/2)*(h1-h)*b

35.235 KN

Reaction induced by slab @ the upper level, RB


Force induced by the soil backfill, Psoil
Force induced by surcharge load, Psur

5.863 KN
25.230 KN
7.569 KN

Moment arm about toe:


Moment arm for soil induced force, d1 = h1/3
Moment arm for surcharge force, d2 = h1/2
Moment arm for force due to slab above level, d3 = h1
Moment arm for soil backfill, d4 = L - (L-t)/4)
Moment arm for wight concrete wall, d5 = L/2
Moment arm for weight of concrete footing, d6 = L/2
Check for factor of safety as per code provision:
Resisting Moment, RM = (RB*d3)+(W1*d5)+(W2*d6)+(W3*d4)
Overturning Moment, OM = (Psoil*d1) + (Psur*d2)
Summation for vertical forces, Ry = W1 + W2 + W3
Check for factor of safety against sliding, FSSL = *(RY/(Psoil+Psur-RB))
Therefore, Basement Retaining Wall is failed against sliding, Provide Shear Key
Check for factor of safety against overturning, FSOT= RM/OM
Therefore, Basement Retaining Wall is safe agaisnt overturning, section increase not needed
Check for allowable soil bearing pressure :
Distance of resultant from toe, X = (RM - OM)/Ry
Eccentricity of Resultant Force e = L/2 - X
Check if Trapezoidal or Triangular Pressure, L/6
When e < L/6 adopt Trapezoidal Pressure
Calculate Minimum Soil Pressure, qumin = (Ry/L)*(1 - 6*e/L)
Calculate for Maximum Soil Pressure, qumax = (Ry/L)*(1 + 6*e/L)
When qumax < qall, therefore section is satisfactory

1100.00
1650.00
3300.00
1262.50
800.00
800.00

mm
mm
mm
mm
mm
mm

90.042 KN.m
40.242 KN.m
67.995 KN
1.26
2.24

Non-Compliant
Compliant

732.40 mm
67.60 mm
266.67 mm
31.725 kPa
53.269 kPa

Compliant
Compliant

DESIGN OF REINFORCEMENT OF HEEL:


Effective depth of footing to be consider, heff = h - Cc - h/2
AASHTO 11.5.5

Factored Weight due to Soil at Rear Face, W3U = 1.35*(S*((L-t)/2))*(h1-h)*b

AASHTO 11.5.5

Factored Weight due to concrete at heel portion, WheelU = 1.25*(C*(L-t)/2*h*b)

319.00 mm
47.57 KN
8.10 KN

Calculate for Factored Shear at the face of top base, Vu = W3U + WheelU

55.67 KN

Caculate for Ultimate bending Moment, Mu = (W3U + WheelU)*((L-t)/4))

18.788 KN.m

Note : Although it is true that there is some upward soil pressure, the designer choose to neglect it because it is relatively small. This is the unlikely condition that would exist if there occurred a leteral force overload and no associated increased vertical loads causing uplift of the heel. The ultimate moment must be due to the factored load
(wt of soil including surcharge and weight of footing on the postion of heel.
NSCP I--Sec.411.4.1.1
NSCP I--Sec.411.2

NSCP I--Sec.410.6.1
NSCP I--Sec.410.6.1

Nominal Shear provided by concrete, Vc = 0.17**SQRT(fc')*b*heff

286.96 KN

Calculation for factored shear provided by concrete, sVc


The footing thickness h is adeqaute to carry such shear stresses

215.22 KN

Coefficeint of resistance, Rn = Mu / (f*b*heff2)


Check for rho min , sqrt(fc')/4*fy
Rho min should not be less than with, 1.4/fy
Therefore adopt rho min, min =
Calculate for theoritical rho, = (0.85*fc'/fy)*(1 - sqrt(1 - 2*Rn/(0.85*fc'))
Use rho minimum for design

0.205 Mpa
0.0032
0.0034
0.0034
0.0005

Calculate for rho balnce, b = 0.85*fc'*1*600 / fy*(600 + fy)

N.A

Calculate for rho max, max = 0.75*b

N.A
Not Aplicable

Therefore adopt design rho, des =

0.0034

Compliant

Non-compliant

Calculation for mechanical ratio, = des*fy/fc'

0.0500

Check for the req'd thickness of the ft., hreq'd = sqrt(Mu/(f*fc'*b**(1-0.59*))


The assumed base/footing thickness is satisfactory
Calculate for the total req'd steel area, As = des*b*heff

123.95 mm
1078.74 mm
2
113.10 mm

Calculation for main steel area provided, Apro = PI()*(h2)/4


Calculation for number of bars per strip, N = As/Apro

10 pcs

Calculation for req'd main bar spacing, Sreq'd = b/N


Therefore use:
10 - 12mm
main steel bar in heel

NSCP I- Sec. 407.13.2.1

spaced @100mm O.C

Temperature and Shrinkage bar:


TOP BARS
For grade 276 bars, steel ratio, temp

0.0020
2
1280.00 mm
2
78.540 mm

Calculation for temp and shrink bar provided, Apro = PI()*tb2/4


Calculation for number of bar per meter strip, N = Areq'd/Apro

17 pcs

Calculate for req'd spacing, Sreq'd = L/N


Check for Spacing,
5*h
450 mm
Therefore use:

17 - 10mm

Per meter strip

100 mm

Calculation for req'd steel area,Areq'd = temp*L*h

NSCP I- Sec 407.13.2.2


NSCP I- Sec 407.13.2.2

Compliant
2

90 mm
2000 mm
450 mm

temperature and shrinkage bar

space @90mm O.C

DESIGN OF REINFORCEMENT OF TOE:


Fig. 2

Trapeziodal Pressure Diagram


Note:

(L-t)/2

qumin
qumax

- The max. pressure at the


base footing create bending
moment at the stem of wall
and shear. The designer
choose to neglect the soil
on top of footing .

q1
q2
R1
R2

NSCP I--Sec.411.4.1.1
NSCP I--Sec.411.2

NSCP I--Sec.410.6.1
NSCP I--Sec.410.6.1

Calculation for dist. From toe to the face of stem, (L-t)/2


Calculation for valu of q1 = qumax - qumin
Calculation for value of q2 = (q1*(L-t)/2)/L
Calculation for value of R1 = (qumax - q2)*((L-t)/2)*b
Calculation for value of R2 = 1/2*(q2)*((L-t)/2)*b
Calculation for factored shear, Vu = 1.6*(R1+R2)
Calculation for factored moment, Mu = 1.6*(R1*(L-t)/4) + 1.6*(R2*(2/3)*((L-t)/2))

675.00
21.544
9.089
29.822
3.068
52.623
18.312

mm
kPa
kPa
KN
KN
KN
KN

Nominal Shear provided by concrete, Vc = 0.17**SQRT(fc')*b*heff

286.96 KN

Calculation for factored shear provided by concrete, sVc


The footing thickness h is adeqaute to carry such shear stresses

215.22

Coefficeint of resistance, Rn = Mu / (f*b*heff)


Check for rho min , sqrt(fc')/4*fy
Rho min should not be less than with, 1.4/fy
Therefore adopt rho min, min =
Calculate for theoritical rho, = (0.85*fc'/fy)*(1 - sqrt(1 - 2*Rn/(0.85*fc'))
Use rho minimum for design

0.200 Mpa
0.0032
0.0034
0.0034
0.0005

Calculate for rho balnce, b = 0.85*fc'*1*600 / fy*(600 + fy)

N.A

Calculate for rho max, max = 0.75*b

N.A

Compliant

Non-compliant

Not Aplicable
Therefore adopt design rho, des =

0.0034

Calculation for mechanical ratio, = des*fy/fc'

0.0500

Check for the req'd thickness of the ft., hreq'd = sqrt(Mu/(f*fc'*b**(1-0.59*))


The assumed base/footing thickness is satisfactory
Calculate for the total req'd steel area, As = des*b*heff

122.37 mm

Calculation for main steel area provided, Apro = PI()*(h )/4

Calculation for req'd main bar spacing, Sreq'd = b/N

100 mm

10 - 12mm

main steel bar @ toe

spaced @100mm O.C

BOT BARS

For grade 276 bars, steel ratio, temp

0.0020
2
1280.00 mm
2
78.540 mm

Calculation for req'd steel area,Areq'd = temp*L*h


Calculation for temp and shrink bar provided, Apro = PI()*tb2/4
Calculation for number of bar per meter strip, N = Areq'd/Apro
NSCP Sec 407.13.2.2
NSCP Sec 407.13.2.2

113.10 mm
10 pcs

Temperature and Shrinkage bar:


NSCP Sec. 407.13.2.1

1078.74 mm

Calculation for number of bars per strip, N = As/Apro

Therefore use:

17 pcs

Calculate for req'd spacing, Sreq'd = L/N


Check for Spacing,
5*h
450 mm
Therefore use:

17 - 10mm

Compliant
2

temperature and shinkage bar @ toe

90 mm
2000 mm
450 mm
spaced @90mm O.C

BASE SHEAR KEY NOMENCLATURE


Fig. 3 . Passive Earth Pressure

h
hT

Pp1

hS

Pp2
a

Total active pressure, F = Psoil + Psur


Vertical Resultant, Ry=
Required resistant for sliding, Fu =1.5*F
Friction Resistance , Fr = *Ry
Furnished Resisitance,R = Fu - Fr
Required height of Shear Key, hT = sqrt(2*R/(s*kp))

32.799
67.995
49.199
33.998
15.201
760.00

Height of shear key, hs = hT - h

360.00 mm

Calculation for Coefficient of Passive Pressure, kp = (1 + sin)/(1 - sin)

3.00
7.776 KN

Passive Rectangular Pressure at the face of shear key, Pp1 = s*h*hs*b*kp


Passive Triangular Pressure at the face of shear key, Pp2 = (1/2)*(s)*(hs^2)*b*kp
Maximum factored moment, Mu = 1.6*(Pp1*hs/2 + Pp2*(2hs/3))
Use rho min, min

NSCP I--Sec.411.4.1.1
NSCP I--Sec.411.2

KN
KN
KN
KN
KN
mm

3.4992 KN
3.5831808 KN.m
0.0034

Calculation for mechanical ration, = min*fy/fc'


Calculation for Coefficient of Resistance, Rn = fc'**(1 - 0.59*)
Calculate for shear key thickness, a = sqrt(Mu/f*Rn*b)
Factore shear force, Vu = 1.6*(R)
Nominal Shear provided by concrete, Vc = 0.17**SQRT(fc')*b*heff

0.0500
1.359
60.00
24.322
43.275

Calculation for factored shear provided by concrete, sVc


The shear key thickness is adequate to carry such shear stress

32.456 KN

Mpa
mm
KN
KN
Compliant

Therefore, for the reinforcement of shear key extent the vertical bars at the rear face to the shear key
Summary of Shear Key section :

Total Heigth, hsT = hs + Cc + vr/2

450.00 mm

Total Width, aT = a + Cc + vr/2

150.00 mm

H. Results & Reinforcement Arragement

6- 12mm space @

24-10mm
160mm O.C

160mm O.C

space @

EXPOSED FACE OF BASEMENT


WALL.

8 - 10mm
120mm O.C

spaced @

24 - 10mm
120mm O.C

spaced @

SOIL BACKFILL @ REAR


FACE OF THE WALL.

10 - 12mm
spaced @100mm O.C

10 - 12mm
spaced @100mm O.C

TOE

HEEL

17 - 10mm
space @90mm O.C
17 - 10mm
spaced @90mm O.C

REVISION NO.

DESCRIPTION OF REVISION

DATE

CHECKED

DATE

APPROVED

Fig.1

CHECK FOR STABILITY FOR SEISMIC CONDITION


Pressure Diagram induced by Seismic Force & Surcharge

RB

W3

PAE

W1
d5
d3

Psur
d4

d7
d2

W2
d6
A
h
HEEL

TOE

L
Weights and Forces:
Consider 1.0 meter strip
Weight due to concrete wall, W1 = c*(h1-h)*b*t

17.400 KN

Weight due to concrete footing, W2 = c*L*b*h

15.360 KN

Weight to soil backfill, W3 = s*((L-t)/2)*(h1-h)*b

35.235 KN

Reaction induced by slab @ the upper level, RB


Force induced by seismic, PAE = (0.375(kh)(ws)(h1)2)
Force induced by surcharge load, Psur
Moment arm about toe:
Moment arm for soil induced force, d7 = 2*h1/3
Moment arm for surcharge force, d2 = h1/2
Moment arm for force due to slab above level, d3 = h1
Moment arm for soil backfill, d4 = L - (L-t)/4)
Moment arm for wight concrete wall, d5 = L/2
Moment arm for weight of concrete footing, d6 L/2
Check for factor of safety as per code provision:
Resisting Moment, RM = (RB*d3)+(W1*d5)+(W2*d6)+(W3*d4)
Overturning Moment, OM = (PAE*d1) + (Psur*d2)
AASHTO 5.8.9.1A
NSCP II-Sec. 5.5.5
AASHTO 5.8.9.1A
NSCP II-Sec. 5.5.5

Summation for vertical forces, Ry = W1 + W2 + W3


Check for factor of safety against sliding, FSSL = *(RY/(Psoil+Psur))
Thefore, Basement Retaining Wall is safe against sliding, Shear Key is not Needed
Check for factor of safety against overturning, FSOT= RM/OM
Therefore, Basement Retaining Wall is safe agaisnt overturning, section increase not needed

5.863 KN
14.702 KN
7.569 KN

2200.00 mm
1650.00 mm
3300.00 mm
1262.50 mm
800.00 mm
800.00 mm
90.042 KN.m
44.832 KN.m
67.995 KN
2.07
2.01

Compliant
Compliant