Professional Documents
Culture Documents
Basement Fires
Fire in a basement is very different to that above ground for two fundamental reasons. Firstly, true basements
are enclosed, with no windows or means of ventilation, this condition allows for rapid heat build up with nowhere
for the heat to dissipate to, other than internal openings within the basement. Within a basement, the most
common internal vertical opening into which smoke will want to dissipate is the stairs, which are likely to be
required and possibly used for means of escape. This is obviously an undesirable situation, i.e. excessive heat
build up, with the only natural path for dispersal being the escape route. Secondly, fires below ground are likely
to require offensive fire-fighting, whereby the Fire Service need to enter the space and fight the fire internally. To
do so, fire-fighters will need to descend from the ground floor into the basement area, which may require them to
pass through the hot gas layer, this can put fire service personnel at considerable risk.
On the basis that increased heat build up is the primary concern with basement fires, it should be no surprise that
the critical fire safety requirement placed on a basement is ventilation, i.e. a means of allowing the smoke and
heat to pass from the basement area to external, thus reducing the risk associated with the conditions described
above. There are two common methods of reducing the smoke / heat build up within basements, namely natural
and mechanical ventilation, although it is noted there are variations thereof.
It is noted that requirements under current guidance can be difficult to achieve and in some cases, due to a lack
of design understanding, basement smoke vents have been removed / covered during refurbishment projects,
leading to non compliances.
This bulletin discusses the design requirements set out in the current guidance.
Basements Requiring Ventilation
The current Building Regulations in England and Wales require that a smoke control system to be provided for
any basement storey that has:
In order to achieve compliance with the Building Regulations, the following primary guidance is available:
Approved Document B (B3) Basement Car Park Smoke Ventilation
BS 7346-7: 2006 Code of practice on functional recommendations and calculation methods for smoke
and heat control systems for covered car parks
Approved Document B (B3) Basement Car Park Smoke Ventilation
This Approved Document covers the provision of natural and mechanical ventilation for basement car parks.
Natural Ventilation:
Naturally ventilated car parks require a minimum 1/40th (2.5%) of the net floor area of the basement car park in
openings linked directly to the atmosphere, with at least 50% of the opening being split between two opposing
walls, this allows a good flow across the vents and ensures that the system is not undermined by wind pressure
acting on one side of the building, as a positive pressure to one face, should assume a negative pressure to the
opposing.
Mechanical Ventilation:
The minimum rate for a mechanically ventilated car park is 10 air changes per hour under fire conditions. The
system should be independent of any other ventilating system (other than any system providing normal
ventilation to the car park). Other design considerations include:
The system should be designed to run in two parts, each part capable of extracting 50% of the rates set out in
above and designed so that each part may operate singly or simultaneously;
Each part of the system should have an independent power supply which would operate in the event of failure of
the main supply;
Extract point should be arranged so that 50% of the outlets are at high level and 50% at low level; and
The fans should be rated to run at 300C for a minimum of 60 minutes and the ductwork and fixings should be
constructed of materials having a melting point not less than 800C.
Unlike other basement occupancies, due to the well defined fire load in basement car parks a sprinkler system is
not required by the guidance when a powered extract system is used.
BS 7346-7: 2006 Code of practice on functional recommendations and calculation methods for smoke and heat
control systems for covered car parks
This British Standard gives guidance on providing smoke ventilation from enclosed car parks. It outlines the
design requirements for natural and mechanical systems, to ensure smoke clearance, aid fire-fighting and to give
protection to the means of escape. In addition to a conventional natural ventilation / mechanical ventilation, BS
7346-7 also covers performance-based mechanical ventilation in basement car parks using jet/impulse fans.
Where jet fans are employed the design utilises sets of fans to exert thrust on the air within a space to accelerate
air, creating flow in a desired pattern, effectively moving smoke and smoke within that space. In large basement
car parks, selective operation of the jet fans associated with the affected fire zone will direct the smoke to the
appropriate extract location by the most efficient route. The jet fans will induce air from other areas outside the
fire zone, moving the smoke within a predetermined path; the objective being to protect unaffected zones,
escape routes and fire-fighters access routes from smoke contamination.
The effectiveness of a jet fan system in basement car parks is often demonstrated by using computational fluid
dynamics (CFD) model. However, it must be borne in mind that CFD modelling should not be used as the only
tool for system design as it is possible that inaccurate information may be used within models, resulting in
substandard analyses.
Conclusion
Basement smoke ventilation is fundamental to ensuring that the specific conditions that occur in a basement
environment can be appropriately dealt with. The published guidelines for basement smoke ventilation designs
have been discussed along with the recommended methods of meeting the performance requirement of the
Building Regulations. The optimal solution for a specific building is not always clear and will require careful
consideration. In some instances, the guidance document requirements can not be easily applied to a design, if
this is the case a fire engineering solution that meets with the functional objectives of the Building Regulations
can be adopted and applied on a bespoke basis.
http://www.smoke-vent.co.uk/a_basic_introduction_to_smoke_control.html
http://magazine.sfpe.org/content/smoke-control-very-tall-buildings-past-presentand-future
http://magazine.sfpe.org/content/passive-smoke-control-design
http://k2s.cc/file/8af1a072dda4f/1936504243.pdf
http://avaxhm.com/ebooks/engeneering_technology/1936504243.html
http://k2s.cc/file/8af1a072dda4f