You are on page 1of 8

Product V&V Lab

ODVI, Schneider-Electric India


No. 88 (P), Sahasra Shree,
EPIP Indl. Area, Whitefield,
Bangalore-560 066

Test Report No : RI_201309318_001


Title: Flammability/Glow Wire Test
Requestor Name: Rachna Verma

GTCI Reference Number: GTCI-PVV-Lab-13-591

Project Name : Des.Acti9DB

Test Request No: : 201309318_001

X Design Functional Verification

Validation

Objective
Follow up

Expertise

Other

Test Mode: Test in laboratory

Nature Of Test: Design critical analysis

Test Objective:
To check the glow wire test on neutral link support and its model sample at 960C
Test

Date(s) of Testing

Starting Date:

10/12/2013

Finished Date

12/12/2013

Test(s) Performed:
1. Glow wire test
Standards and Methods
Product Standard :

IEC 63439-3

Internal Standard :
Other : IEC 60695-2-10, IEC 60695-2-10 and as per customer request
Items
Tested

Maturity

Mock Up

Prototype

Pilot Product

X Commercial Product

Item Designation:
Reference Batch - (Dimension: 75 X 75 X 1.5 )

02 Nos.

Neutral Link support-End samples

04 Nos.

Result

Test is in conformity to the specifications

Dept

Product V&V Lab

Written By:

Number of Pages

Date

13/12/2013

Reviewed By:

Ramesh Murugan

Abhinav Sinha

This Test Report relates only to the items tested.


This Test Report shall not be reproduced, except in full, without written approval of the laboratory

SE-VnV.Lab-RC-TRP
Issue / Rvision 01

Schneider Electric India ODVI Power

1/8

CONTENT
1.

PRODUCT DESCRIPTION .......................................................................................................................... 3

2.

LAB AMBIENT CONDITION ....................................................................................................................... 3

3.

TEST DESCRIPTION .................................................................................................................................. 3

4.

EQUIPMENT DETAILS ............................................................................................................................... 5

5.

UNCERTAINITY MEASUREMENT ............................................................................................................... 5

6.

RESULTS ................................................................................................................................................... 5

7.

APPENDIX ................................................................................................................................................. 8

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

2/8

1. PRODUCT DESCRIPTION
The samples used for testing are as shown in Table 1.1 below...
Sample No

Sample Description

Quantity

Other Details

201309318_001 01 to 02

Reference Batch - (Dimension: 75 X 75 X 1.5 )

02 Nos

Fresh samples

201309318_001 03 to 06

Neutral Link support-End samples

04 Nos.

(Akulon Material)

Table 1.1: Sample Description

2. LAB AMBIENT CONDITION


PV&V lab temperature 23.1C and Humidity 41% RH

3. TEST DESCRIPTION
3.1 The following observations are made on the samples before the Test:
Samples are checked visually and no damages observed on the samples
3.2 Detailed description of the Test:
The equipment is made as per the IEC 60695-2-10
The sample is mounted vertically on a stand.
The test temperature is set at 960 C .
The tip of the glow wire is brought in contact with the thinnest area of cross section of the
Specimen for a period of 30 seconds.
The penetration of the tip is limited to 7mm through the sample.
After 30 seconds the specimen is moved away and the time taken for the flame to get
extinguished and the height of the flame during the time of contact is noted down.
Also, it is observed if the wooden piece wrapped in tissue placed is burnt or not
Perform the test on the samples at different orientations

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

3/8

Test Setup Photos

Neutral link support

Model sampless Neutral link support

Acceptance Criteria
X Standard Compliance

Specific

Additional information:
1. There is no visible flame and no sustained glowing
2. Flames and glowing on the sample extinguish themselves within 30sec after the removal of the glow-wire.
3. There shall be no ignition of the tissue paper or scorching of the pinewood board

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

4/8

4.

EQUIPMENT DETAILS
SL. No

Equipment Name

Make

Sl. No

Calibration Valid Upto

Glow wire tester

SCR

607130

4 April 2014

Table 4.1: Measuring/Recording Equipment Details


External Testing Lab used for Testing: NA

5.

UNCERTAINITY MEASUREMENT
Thermometer used to measure the temperature has Uncertainty of : +/- 0.96Deg C

6. RESULTS
These results refer only to the items tested
Results and observations

Sample no

201309318_001-01

Time taken for the flame to


extinguish itself after the
removal of the glow-wire

201309318_001-02

No flame observed after the removal of


the glow-wire

Tissue paper ignited

No

No

Result

Conformity

Conformity

Table 6.1: Test Results

201309318_00105

201309318_001-06

Time taken for the


flame to extinguish
itself after the removal
of the glow-wire

201309318_00104
No flame
observed after
the removal of
the glow-wire

Tissue paper ignited

No

No

No

Result

Conformity

Conformity

Conformity

Sample no

Table 6.2: Test Results

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

5/8

Samples Photos-After Test

Reference Batch- 201309318_001 - 01

Reference Batch- 201309318_001 02

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

6/8

201309318_001 - 04

201309318_001 - 05

201309318_001 - 06

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

7/8

Detailed Conclusion:
1. Flames and glow on the sample extinguish themselves within 30sec after the removal of the glow-wire.
2. There was no ignition of the tissue paper or scorching of the pinewood board .

Since the tissue paper did not burn during and after glow wire penetration through the sample and no flame observed
on the sample after removal of the glow wire penetration, the test in conformity to the specifications for sample no
201309318_001-01, 02, 04,05 and 06

7. APPENDIX
Akulon Material white samples for Acti9 DBs
It was observed that if plastic material drops directly on tissue paper placed below the sample, it catches fire. If plastic
material drops creeps through the surface of sample and then fall on tissue paper, it does not catches fire.

Document No.
SE-VnV.Lab-RC-TRP

Schneider Electric India ODVI Power

Test Report No

RI_ 201309318_001

8/8